340606 Rev.B Installation Directions
2014-11-11
: Pdf 63182-Installationsheet 63182-InstallationSheet 785007 Batch12 unilog
Open the PDF directly: View PDF .
Page Count: 4

WIRING GENERAL INSTRUCTIONS
1. NOTICE: For installation only by a qualified electrician in accordance with
the National Electrical Code, local codes and the instructions provided on
this document.
2. CAUTION: RISKS OF ELECTRICAL SHOCK. More than one disconnect
switch may be required to de-energize the connected equipment before
servicing. Disconnect all power supplies to this disconnect switch before
removing cover and exposing interior.
3. Suitable for use on circuits capable of delivering not more than (see chart
below for cat. no. and application) RMS symmetrical amperes, 600 VAC
maximum.
Man Mtr Motor
Cat No. Cntlr Disconnect
PS30SS (AX) 10,000 10,000
PS60SS(AX)
PS100SS(AX) 10,000 5,000
4. NOTICE: Separate over-current protection must be provided in accor-
dance with National Electrical Code, article 220 or Canadian Electrical
Code, section B, as appropriate.
5. This enclosure includes a provision for locking the switch handle in the
“OFF” position. This feature accepts up to a 5/16 inch (8 mm) diameter pad-
lock shackle. This lockout feature is designed to isolate power from the con-
nected equipment in order to comply with OSHA lockout/tagout regulation
29 CFR part 1910.147. This feature DOES NOT isolate power supplied to
this disconnect switch during internal servicing of this disconnect switch.
6. This disconnect switch must NOT be used as a
junction box for feed-thru connections.
7. The switch in this device was available with or
without a “pre-break” auxiliary contact. If the
device was purchased with an auxiliary contact,
the auxiliary contact’s rating is 600VAC, 10
amps. The pre-break feature allows the auxiliary
contact to open slightly prior to the main con-
tacts opening. This is useful for signaling computer controlled equipment that
power will be dis-connected. The auxiliary contact can be wired with one nor-
mally opened or one normally closed contact, (see diagram at right for wiring).
8. Consult Pass & Seymour/Legrand distributor for auxiliary contact availability.
INSTALLATION INSTRUCTIONS
1. Loosen (do not remove) four (4) enclosure cover screws and lift off cover.
2. Remove feet and screws from poly bag and mount the
feet to the device in the desired position using the
screws provided. Torque screws according to chart
below. (See figure 1 for mounting dimensions using
attached mounting feet).
FOOT MOUNTING SCREW TORQUE
30 AMP 18 in. lbs. (2.0 N•m)
60/100 AMP 10-12 in. lbs. (1.1-1.4 N•m)
NOTE: Device must always be mounted using mount-
ing feet extended. DO NOT drill mounting holes
through enclosure. Mounting feet will accept up to 3/8″
dia. screws (not provided). Device must be mounted
with end of ground plate reading “TOP” in upward direction.
DIMENSIONS: INCH [MM]
MOUNTING PATTERN TABLE
ABCDEFG
306.36 [162] 8.70 [221] 5.60 [142] 7.94 [202] 3.78 [96] 6.12 [155] N/A
AMP
60/100 7.75 [197] 11.0 [279] 6.87 [174] 10.12 [257] 4.75 [121] 8.00 [203] 2.38 [60]
AMP
3. Drill or punch appropriate hole size (see chart below) at the desired con-
duit entry location. Drill centers are provided at the top, bottom and inside
the back of the enclosure.
NOTE: Use only listed/certified conduit hubs rated for Type 4X and 12K
applications.
NOTE: Back feed is NOT permitted in Type 12K applications. Back feed
IS permitted in Type 4X applications.
30 AMP 60/100 AMP 60/100 AMP
HUB TRADE SIZE 3/4″1″1-1/4″
APPROXIMATE 1-1/18″1-3/8″1-3/4″
HOLE SIZE (28 MM) (34.99 MM) (44.4 MM)
NOTE: If 1-1/4″conduit hub is being used for 60A or 100A applications,
grounding plate must first be removed by unscrewing from inside
back of enclosure and the three break-out tabs removed from each
opening that corresponds with the conduit entry locations designated
for the installation (see figure 2).
Figure 2
4. Install conduit hub (not provided) with sealing ring between hub and enclo-
sure. Tighten conduit nut securely to ensure watertight seal and ground
connection.
5. Mount disconnect switch as intended on equipment, wall or other location
after pre-drilling for screws per selected pattern table dimensions.
6. Installing conduit directly above the switch is not recommended in applica-
tions where condensation can occur in the conduit. When using top feed
entrance, drip loops must always be formed as illustrated in figures 3 and 4.
Figure 3 Figure 4
WIRING INSTRUCTIONS
Wire size may vary with application. Select conductors in accordance with
ampacity table 310-16 of the National Electrical Code or Table 2 of the
Canadian Electrical Code.
1. CAUTION: Use copper conductors only.
2. Terminals will accept wire sizes listed in Table 1 below.
3. Cleanly cut and strip 1/2″(13mm) of insulation from end of cable. DO NOT
TIN CONDUCTORS.
4. Connected equipment electrical rating must not exceed the rating of the
device.
5. Select the correct wiring diagram from wiring diagram chart and wire switch
as illustrated, making sure to provide condensation drip loop as shown in
figures 3 and 4. Insert stripped cables fully into terminal openings, tighten
terminal screws per Table 1 below.
6. With switch handle in “OFF” position, replace enclosure cover being sure
O-ring is seated properly in groove provided around cover. Tighten enclo-
sure cover screws according to TABLE 1.
READ AND SAVE THESE INSTRUCTIONS!
DISCONNECT SWITCH
30, 60, 100 AMP.
OUTDOOR/INDOOR (TYPE 4X WATERTIGHT,
CORROSION RESISTANT) INDOOR
(TYPE 12K DUST TIGHT)
Table 1
SWITCH GROUND NEUTRAL AUXILIARY (IF SUPPLIED) COVER
AMPS TERMINAL TERMINAL SCREW TERMINAL TERMINAL SCREW TERMINAL TERMINAL SCREW TERMINAL TERMINAL SCREW SCREW
CAPACITY TORQUE CAPACITY TORQUE CAPACITY TORQUE CAPACITY TORQUE TORQUE
30 #8-14 AWG 15-20 in. lbs. #6-14 AWG 10-12 in. lbs. #6-14 AWG 10-12 in. lbs. #12 AWG 4-5 in. lbs. 18 in. lbs.
(1.7-2.3 N•m) (1.2-1.4 N•m) (1.2-1.4 N•m) (0.5-0.6 N•m) (2.0 N•m)
60 #2-10 AWG 25-27 in. lbs. #4-10 AWG 10-12 in. lbs. #4-10 AWG 10-12 in. lbs. #12 AWG 5-7 in. lbs. 12-15 in. lbs.
(2.8-3.0 N•m) (1.2-1.4 N•m) (1.2-1.4 N•m) (0.6-0.8 N•m) (1.4-1.7 N•m)
100 #2-10 AWG 25-27 in. lbs. #0-10 AWG 22-26 in. lbs. #0-10 AWG 22-26 in. lbs. #12 AWG 5-7 in. lbs. 12-15 in. lbs.
(2.8-3.0 N•m) (2.8-3.0 N•m) (2.8-3.0 N•m) (0.6-0.8 N•m) (1.4-1.7 N•m)
Figure 1
*= top mounted auxiliary contact

WIRING DIAGRAMS
NOTE: “G” designates grounding wire (bare, green or green with yellow
stripe and green/yellow grounding buss).
“N” designates the blue neutral (grounded) terminal.
“W” designates the white neutral (grounded) wire.
THIS MANUAL MOTOR CONTROLLER CARRIES A MAXIMUM HORSE
POWER RATING ACCORDING TO THE CHARTS BELOW.
INSTRUCCIONES GENERALES PARA CONEXIÓN
1. NOTAR: Para instalación solo por un electricista de acuerdo con el
National Electrical Code, códigos locales y las instrucciones provistas en
este documento.
2. CUIDADO: RIESGO DE SACUDIDA ELÉCTRICA. Más de un chucho de
desconectar puede que sea necesario para cortar la corriente del equipo
conectado antes de dar servicio. Desconecte todas las tomas de corri-
ente antes de quitar la tapa y exponer el interior.
3. Adecuado para uso con un circuito capaz de proveer no más de (vea la
carta abajo para el número y la aplicación de catálogo) RMS Amperes
simétricas, máximo 600 VAC.
Número de Regulador Desconexión
Catálogo Manual del motor del motor
PS30SS (AX) 10,000 10,000
PS60SS(AX)
PS100SS(AX) 10,000 5,000
4. NOTAR: Protección separada para sobre-corriente debería de ser provista
de acuerdo con el National Electrical Code, artículo 220, o Canadian
Electrical Code, sección B, como sea apropiado.
5. Esta caja incluye una provisión para trancar la palanca del chucho en la
posición “APAGADO.” Esta característica permite un grillete para canda-
dos de hasta 5/16 pulgadas (8 mm). Esta característica de trancar esta
diseñada para aislar corriente del equipo conectado de modo que este de
acuerdo con la parte 1910.147 de la reglamentación de tranque/bloqueo
29 de OSHA. Esta característica NO aísla corriente llevada a este cucho
de desconectar durante la provisión de servicio interno al chucho de
desconectar.
6. Este chucho de desconectar NO debe ser
utilizado como una caja de conexión para
conexiones de alimentación.
7. El chucho en este aparato se dispone con o
sin un contacto auxiliar de “pre-interrumpir.” Si
el aparato se compro con el contacto auxiliar,
la especificación del contacto auxiliar es 600 VAC, 10 Amps. La característi-
ca de pre-interrumpir le permite al contacto auxiliar abrirse un poco antes
de la apertura de los contactos centrales. Esto es útil para señalarle a
equipo controlado por computadoras que se cortara la corriente. Este con-
tacto auxiliar puede ser alambrado con un contacto normalmente abierto o
un contacto normalmente cerrado, (vea diagrama a la derecha para alam-
brado).
8. Consulte Pass & Seymour/Legrand para disponibilidad de contactos
auxiliares.
INSTRUCCIONES DE INSTALACIÓN
1. Afloje (no quite) cuatro (4) tornillos de la tapa de la caja y levante la tapa.
2. Saque tornillos y pata de bolsa de plástico y monte las patas al aparato
en la posición deseada utilizando los tornillos provistos. Apriete tornillos
de acuerdo al cuadro siguiente. (Vea la figura 1 para dimensiones de mon-
tar utilizando patas montadas.)
TORSIÓN DE TORNILLOS DE MONTURA DE PATA
30 AMP 18 pulg. lbs. (2.0 N•m)
60/100 AMP 10-12 pulg. lbs. (1.1-1.4 N•m)
NOTAR: El aparato debería de estar montado siem-
pre con las patas extendidas. NO taladre huecos de
montura en la caja. Patas de montura aceptaran
hasta tornillos de 3/8″diag. (no provistos). El apara-
to debería de ser montado con el plato de tierra
indicando “TOP” hacia arriba.
Figura 1
DIMENSIONES: PULGADAS [MM]
TABLA DE PATRÓN DE MONTURA
ABCDEFG
30 6.36 [162] 8.70 [221] 5.60 [142] 7.94 [202] 3.78 [96] 6.12 [155] N/A
AMP
60/100 7.75 [197] 11.0 [279] 6.87 [174] 10.12 [257] 4.75 [121] 8.00 [203] 2.38 [60]
AMP
3. Taladre o abra un hueco de tamaño apropiado (vea tabla siguiente) en el
lugar deseado de entrada de conductor. Centros de taladrar están provis-
tos en la tapa, fondo y dentro de la parte de atrás de la caja.
NOTAR: Use solo cubos de conductor listados/certificados y de regu-
lación para aplicaciones de Tipo 4X y 12K.
NOTAR: Retroalimentación NO es permitido en aplicaciones de Tipo 12K.
Retroalimentación SI es permitido en aplicaciones de 4X.
30 AMP 60/100 AMP 60/100 AMP
TAMAÑO DE CUBO 3/4″1″1-1/4″
TAMAÑO DE HUECO 1-1/18″1-3/8″1-3/4″
(28 MM) (34.99 MM) (44.4 MM)
NOTAR: Si un cubo conductor de 1-1/4″se esta utilizando para aplicaciones
de 60A ó 100A, se debería de quitar el plato de tierra anteriormente,
destornillando de adentro de la parte de atrás de la caja, y quitando
las tres aletas que les corresponden a cada entrada de conductor
designadas para la instalación. (Vea figura 2).
Figura 2
4. Instale cubo conductor (no incluido) con un aro sellador entre el cubo y la
caja. Apriete el cubo del tornillo conductor bien para asegurar estancamien-
to y conexión a tierra.
5. Monte chucho de desconectar como desee al equipo, pared o algún otro
sitio después de pre-taladrar para tornillos las dimensiones de la tabla para
el patrón pre-seleccionado.
6. Instalación de el conductor directamente encima del chucho no es
recomendado en aplicaciones donde condensación puede ocurrir en el
conductor. En utilización de la entrada de arriba de alimentación, bucles de
escurrir siempre deberían ser formados como indicado en las figuras 3 y 4.
Figura 3 Figura 4
LEA Y GUARDE ESTAS INSTRUCCIONES!
INSTRUCCIONES EN ESPAÑOL
100 Amp 600 VAC
5 HP 120 VAC
10 HP 208 VAC
15 HP 240 VAC
15 HP 277 VAC
30 HP 480 VAC
25 HP 3ø 240 VAC
50 HP 3ø 480 VAC
50 HP 3ø 600 VAC
20 HP 3øY 120/208 VAC
50 HP 3øY 277/480 VAC
50 HP 3øY 347/600 VAC
60 Amp 600 VAC
3 HP 120 VAC
10 HP 208 VAC
10 HP 240 VAC
15 HP 277 VAC
20 HP 480 VAC
20 HP 3ø 240 VAC
40 HP 3ø 480 VAC
50 HP 3ø 600 VAC
20 HP 3øY 120/208 VAC
40 HP 3øY 277/480 VAC
50 HP 3øY 347/600 VAC
30 Amp 600 VAC
1 HP 120 VAC
2 HP 208 VAC
3HP 240 VAC
3HP 277 VAC
5HP 480 VAC
5 HP 3ø 240 VAC
10 HP 3ø 480 VAC
10 HP 3ø 600 VAC
5 HP 3øY 120/208 VAC
10 HP 3øY 277/480 VAC
10 HP 3øY 347/600 VAC
CHUCHO DE DESCONECTAR
30, 60, 100 AMP.
EXTERIOR/INTERIOR (TIPO 4X ESTANCO,
RESISTENTE AL ÓXIDO) INTERIOR
(TIPO 12K SELLADO CONTRA EL POLVO)
*= contacto auxiliar de montaje superior

INSTRUCCIONES DE ALAMBRADO
Tamaño de alambre puede variar dependiendo de la aplicación. Elija conduc-
tores con aislamiento con el vector 310-16 del ampacity del Código Eléctrico
Nacional o el vector 2 del Código Eléctrico Canadiense.
1. CUIDADO: Use solo conductores de cobre.
2. Bornes aceptaran tamaños de alambres como aparecen en la Tabla 1 que sigue.
3. Corte y pele 1/2” (13 mm) de aislamiento de la punta del cable. NO
ESTAÑE LOS CONDUCTORES.
4. Potencia nominal del equipo conectado no debería de exceder la potencia
nominal del aparato.
5. Elija el diagrama de alambrado y chucho de alambrado correcto del cuadro
de diagramas de alambrado como indicado, asegurándose de incluir bucle
de condensación como indicado en las figuras 3 y 4. Introduzca los cables
pelados en las aperturas de las bornes, apriete los tornillos de bornea
segun la Tabla 1 que sigue.
6. Con la palanca del chucho en la posición “OFF”, reemplace la tapa de la
caja asegurándose que el cello-O esta bien ajustado en su acanaladura
alrededor de la tapa. Apriete los tornillos de la tapa de la caja segun la Tabla 1.
DIAGRAMAS DE ALAMBRADO
NOTA: “G” indica el conductor de puesta a tierra
(desnudo, verde o verde y amarillo).
“N” indica la barra neutra azul (puesta a tierra).
“W” indica el conductor neutro blanco (puesto a tierra).
ESTE CONTROLADOR DE MOTOR MANUAL LLEVA UNA POTENCIA
MÁXIMA DE CABALLOS DE FUERZA SEGÚN LOS CUADROS SIGUIENTES.
Tabla 1
CHUCHO TIERRA NEUTRAL AUXILIAR (SI INCLUIDO) TAPA
AMPS CAPACIDAD TORSIÓN DE CAPACIDAD TORSIÓN DE CAPACIDAD TORSIÓN DE CAPACIDAD TORSIÓN DE TORSIÓN DE
DE BORNEA TORNILLO DE BORNEA TORNILLO DE BORNEA TORNILLO DE BORNEA TORNILLO TORNILLO
30 #8-14 AWG 15-20 pul.lbs. #6-14 AWG 10-12 pul.lbs. #6-14 AWG 10-12 pul.lbs. #12 AWG 4-5 pul.lbs. 18 pul.lbs.
(1.7-2.3 N•m) (1.2-1.4 N•m) (1.2-1.4 N•m) (0.5-0.6 N•m) (2.0 N•m)
60 #2-10 AWG 25-27pul.lbs. #4-10 AWG 10-12 pul.lbs. #4-10 AWG 10-12 pul.lbs. #12 AWG 5-7 pul.lbs. 12-15 pul.lbs.
(2.8-3.0 N•m) (1.2-1.4 N•m) (1.2-1.4 N•m) (0.6-0.8 N•m) (1.4-1.7 N•m)
100 #2-10 AWG 25-27pul.lbs. #0-10 AWG 22-26 pul.lbs. #0-10 AWG 22-26 pul.lbs. #12 AWG 5-7 pul.lbs. 12-15 pul.lbs.
(2.8-3.0 N•m) (2.8-3.0 N•m) (2.8-3.0 N•m) (0.6-0.8 N•m) (1.4-1.7 N•m)
100 Amp 600 VAC
5 HP 120 VAC
10 HP 208 VAC
15 HP 240 VAC
15 HP 277 VAC
30 HP 480 VAC
25 HP 3ø 240 VAC
50 HP 3ø 480 VAC
50 HP 3ø 600 VAC
20 HP 3øY 120/208 VAC
50 HP 3øY 277/480 VAC
50 HP 3øY 347/600 VAC
60 Amp 600 VAC
3 HP 120 VAC
10 HP 208 VAC
10 HP 240 VAC
15 HP 277 VAC
20 HP 480 VAC
20 HP 3ø 240 VAC
40 HP 3ø 480 VAC
50 HP 3ø 600 VAC
20 HP 3øY 120/208 VAC
40 HP 3øY 277/480 VAC
50 HP 3øY 347/600 VAC
30 Amp 600 VAC
1 HP 120 VAC
2 HP 208 VAC
3HP 240 VAC
3HP 277 VAC
5HP 480 VAC
5 HP 3ø 240 VAC
10 HP 3ø 480 VAC
10 HP 3ø 600 VAC
5 HP 3øY 120/208 VAC
10 HP 3øY 277/480 VAC
10 HP 3øY 347/600 VAC
INSTRUCTIONS GENERALES DE CABLAGE:
1. ATTENTION: Ne peut être installé que par un électricien qualifié, en
accord avec le Code National Electrique, les codes locaux et les instruc-
tions fournies dans ce document.
2. DANGER: RISQUES DE CHOC ELECTRIQUE. Il est possible qu’il faille
plus d’un interrupteur de courant pour désactiver l’équipement branché
avant d’effectuer des réparations. Débrancher toutes les sources
d’alimentation en courant de l’interrupteur avant de retirer le couvercle
et d’exposer l’intérieur.
3. A utiliser dans un circuit qui ne peut pas fournir plus de (voir le
diagramme cí-dessous pour le numéro de catalogue at l’application)
ampères symmétriques, moyenne quadratique, 600 Volts AC maximum.
Numéro de Contrôleur Débranchement
Catalogue Manual de moteur de motor
PS30SS (AX) 10,000 10,000
PS60SS(AX)
PS100SS(AX) 10,000 5,000
4. ATTENTION: Fournir une protection de surcharge séparée, en accord
avec le Code National Electrique, article 220 ou le Code Electrique
Canadien, section B, selon le cas.
5. Ce boîtier offre la possibilité de vérouiller la poignée de l’interrupteur en
position “ARRET”. Ce dispositif accepte un cadenas avec une chaîne
jusqu’à 5/16 de pouce (8 mm) de diamètre. Ce dispositif de vérouillage
est conçu pour isoler l’équipement branché du courant, afin de se
soumettre à la règle 29 CFR section 1910.147 d’OSHA verrouillage/
étiquetage. Ce dispositif N’ISOLE PAS le courant fourni à l’interrupteur
lors de réparations exécutées à l’intérieur de l’interrupteur de courant.
6. Cet interrupteur de courant NE DOIT PAS être utilisé comme boîte de
dérivation pour des connexions qui le traversent.
7. L’interrupteur dans cet appareil était offert avec
ou sans contact auxiliaire “pré-coupure.” Si
l’appareil a été acheté avec un contact auxiliaire,
la capacité nominale du contact auxiliaire est de
600 Volts AC, 10 ampères. Ce dispositif de “pré-
coupure” permet au contact auxiliaire de s’ouvrir
légèrement avant l’ouverture des contacts
principaux. Ceci s’avère utile pour indiquer à un
équipement contrôlé par ordinateur que l’alimentation en courant va être
coupée. Le contact auxiliaire peut être câblé avec un contact normalement
ouvert ou normalement fermé (voir diagramme à droite pour le câblage).
8. Consulter un distributeur Pass & Seymour/Legrand au sujet de la
disponibilité du contact auxiliaire.
INSTRUCTIONS D’INSTALLATION
1. Desserrer (ne pas enlever) les quatre vis du couvercle et retirer le couver-
cle en le soulevant.
2. Retirer les pieds et les vis du sachet plastique et monter les pieds sur
l’appareil dans la position désirée en utilisant les vis fournies. Serrer les
vis selon le tableau ci-dessous (Voir figure 1 pour les dimensions de mon-
tage si vous utilisez les pieds de montage fournis).
COUPLE DE SERRAGE DES VIS DE PIEDS
30 AMPERES 18 pouce.livres. (2.0 N•m)
60/100 AMPERES 10-12 pouce.livres. (1.1-1.4 N•m)
REMARQUE: L’appareil doit toujours être monté en
utilisant les pieds de montage étendus.
NE PAS percer de trous de montage dans
le boîtier. Les pieds de montage acceptent
des vis jusqu’à 3/8 de pouce de diamètre
(non fournies). L’appareil doit être monté
avec le mot “HAUT” sur les extrêmités de
la plaque terre dirigé vers le haut.
Figura 1
DIMENSIONS: POUCES [MM]
TABLE DE GABARITS DE MONTAGE
ABCDEFG
30 6,36 [162] 8,70 [221] 5,60 [142] 7,94 [202] 3,78 [96] 6,12 [155] S.O.
AMPERES
60/100 7,75 [197] 11,00 [279] 6,87 [174] 10,12 [257] 4,75 [121] 8,00 [203] 2,38 [60]
AMPERES
LIRE ET SAUVEGARDER CES INSTRUCTIONS
INSTRUCTIONS EN FRANÇAIS
INTERRUPTEUR DE COURANT
30, 60, 100 AMPERES
EXTERIEUR/INTERIEUR (TYPE 4X ETANCHE,
RESISTANT A LA CORROSION) INTERIEUR
(TYPE 12K ETANCHE A LA POUSSIERE)
*= contact auxiliaire monté sur le dessus

3. Percer ou poinçonner un trou de taille convenable (voir table ci-dessous) à
l’endroit désiré pour l’entrée de la conduite.
Des centres de pré-perçage sont fournis en haut, en bas et à l’intérieur du
dos du boîtier.
REMARQUE: N’utiliser que des centres de conduites classés/certifiés pour
les applications de type 4X et 12K.
REMARQUE: L’alimentation par l’arriére N’EST PAS permise pour les
applications de type 12K. L’alimentation par l’arrière EST permise pour les
applications de type 4X.
30 AMPERES 60/100 AMPERES 60/100 AMPERES
TAILLE COMMERCIALE
DE CENTRE 3/4 pouce 1 pouce 1-1/4 pouce
TAILLE APPROXIMATIVE 1-1/18 pouce 1-3/8 pouce 1-3/4 pouce
DU TROU (28 MM) (34,99 MM) (44,4 MM)
REMARQUE: Si vous utilisez un centre de conduite de 1-1/4 pouce pour les
applications 60 A ou 100 A, la plaque de terre doit être retirée en premier en
dévissant le dos du boôtier depuis l’intérieur et les trois pattes cassables
retirées de chaque ouverture qui correspond á une entrée de conduite
désignée pour l’installation.(voir figure 2)
Figure 2
4. Installer le centre de la conduite (non fournie) avec l’anneau joint entre
le centre et le boîtier. Bien serrer l’écrou de la conduite pour assurer
l’étanchéité à l’eau et la connexion à la terre.
5. Monter l’interrupteur de courant comme désiré sur l’équipement, le mur
ou tout autre endroit après avoir pré-percé pour les vis en accord avec les
dimensions sélectionnées dans la table de gabarit.
6. Il n’est pas recommandé d’installer la conduite directement au dessus de
l’interrupteur pour les applications où il y a un risque de condensation
dans la conduite. Si vous utilisez une entrée d’alimentation par le haut,
toujours formez des boucles d’égouttement comme illustré dans les
figures 3 et 4.
Figure 3 Figure 4
INSTRUCTIONS DE CABLAGE
La taille des fils peut varier selon l’application. Choisissez les conducteurs
dans l'acordance avec le tableau 310-16 d'ampacity du code électrique
national ou le tableau 2 du code électrique canadien.
1. ATTENTION: N’utiliser que des conducteurs en cuivre.
2. Les bornes admettent les tailles de fils listées dans la Table 1 ci-dessous.
3. Couper proprement et dénuder 1/2 pouce (13 mm) d’isolant de
l’extrêmité du câble. NE PAS ETAMER LES CONDUCTEURS.
4. La capacité nominale électrique de l’équipement ne doit pas excéder la
capacité nominale de l’interrupteur.
5. Sélectionner le diagramme de câblage convenable dans le tableau de
diagrammes de câblage et câbler l’interrupteur en suivant l’illustration, en
s’assurant de former des boucles d’égouttement comme indiqué dans les
figures 3 et 4. Insérer les câbles dénudés complètement dans les ouver-
tures des bornes, serrer les vis des bornes selon la table 1 ci-dessous.
6. Avec la poignée de l’interrupteur en position “ARRET”, remettre en place
le couvercle du boîtier en s’assurant que le joint torique est bien en place
dans la gorge fournie autour du couvercle. Serrer les vis du couvercle de
boîtier selon la TABLE 1.
DIAGRAMMES DE CABLAGE
REMARQUE: “G” désigne le conducteur de MALT
(nu, vert ou vert avec bande jaune).
“N” désigne la barre de neutre bleue (mise à la terre).
“W” désigne le conducteur neutre blanc (mis à la terre).
CE CONTROLEUR DE MOTEUR MANUEL SUPPORTE UNE PUISSANCE
MAXIMALE , INDIQUEE DANS LES TABLES CI-DESSOUS.
Table 1
INTERRUPTEUR TERRE NEUTRE AUXILIAIRE (SI FOURNI) COUVERCLE
AMPERES CAPACITE SERRAGE VIS CAPACITE SERRAGE VIS CAPACITE SERRAGE VIS CAPACITE SERRAGE VIS SERRAGE VIS
BORNE BORNE BORNE BORNE BORNE BORNE BORNE BORNE
30 #8-14 AWG 15-20 po.livres #6-14 AWG 10-12 po.livres #6-14 AWG 10-12 po.livres #12 AWG 4-5 po.livres 18 po.livres
(1,7-2,3 N-m) (1,2-1,4 N-m) (1,2-1,4 N-m) (0,5-0,6 N-m) (2,0 N-m)
60 #2-10 AWG 25-27 po.livres #4-10 AWG 10-12 po.livres #4-10 AWG 10-12 po.livres #12 AWG 5-7 po.livres 12-15 po.livres
(2,8-3,0 N-m) (1,2-1,4 N-m) (1,2-1,4 N-m) (0,6-0,8 N-m) (1,4-1,7 N-m)
100 #2-10 AWG 25-27 po.livres #0-10 AWG 22-26 po.livres #0-10 AWG 22-26 po.livres #12 AWG 5-7 po.livres 12-15 po.livres
(2,8-3,0 N-m) (2,8-3,0 N-m) (2,8-3,0 N-m) (0,6-0,8 N-m) (1,4-1,7 N-m)
Pass & Seymour/Legrand P.O. Box 4822 Syracuse, NY 13221
Printed in U.S.A. REVISED: 10/1/03 P/N 340606 Rev. B
100 Amp 600 VAC
5 HP 120 VAC
10 HP 208 VAC
15 HP 240 VAC
15 HP 277 VAC
30 HP 480 VAC
25 HP 3ø 240 VAC
50 HP 3ø 480 VAC
50 HP 3ø 600 VAC
20 HP 3øY 120/208 VAC
50 HP 3øY 277/480 VAC
50 HP 3øY 347/600 VAC
60 Amp 600 VAC
3 HP 120 VAC
10 HP 208 VAC
10 HP 240 VAC
15 HP 277 VAC
20 HP 480 VAC
20 HP 3ø 240 VAC
40 HP 3ø 480 VAC
50 HP 3ø 600 VAC
20 HP 3øY 120/208 VAC
40 HP 3øY 277/480 VAC
50 HP 3øY 347/600 VAC
30 Amp 600 VAC
1 HP 120 VAC
2 HP 208 VAC
3 HP 240 VAC
3 HP 277 VAC
5 HP 480 VAC
5 HP 3ø 240 VAC
10 HP 3ø 480 VAC
10 HP 3ø 600 VAC
5 HP 3øY 120/208 VAC
10 HP 3øY 277/480 VAC
10 HP 3øY 347/600 VAC