Advance 71A8453001D 400W High Pressure Ballast Spec Sheet

2014-07-05

: Pdf 656946-Attachment 656946-Attachment 781087 Batch5 unilog

Open the PDF directly: View PDF PDF.
Page Count: 1

High Pressure
Sodium
Lamp Ballast
Catalog Number 71A8453
For 400W S51/M169
60 Hz CWA
Status: Active
DIMENSIONS AND DATA
1.30"
6.50"
5.75"
B
MAX.
A
0.7"
0.30" WIDE
2 SLOTS
4 1/4 X 4 3/4 CORE - 2 COIL UNIT
3.90"
4.75"
4.40"
4.40"4.25"
4 HOLES
CLEARED
FOR #10
THRU-BOLTS
Capacitor: 7C550P24
Capacitance: 55
Dia/Oval Dim: 1.75
Height: 5.15
Temp Rating: 105°C
Ballast to Lamp Distance
(BTL) = 2 feet
Temp Rating: 105°C
Ignitor: LI501-H4
Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representitive of relative performance.
Actual performance can vary depending on operating conditions. Specifications are subject to change without notice.
PHILIPS LIGHTING ELECTRONICS N.A.
10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018
Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance
Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886
INPUT VOLTS 120 208 240 277 480
CIRCUIT TYPE
POWER FACTOR (min)
REGULATION
Line Volts
Lamp Watts
LINE CURRENT (Amps)
Operating................................................... 3.86 2.20 1.93 1.73 0.96
Open Circuit............................................... 1.80 1.00 0.90 0.84 0.44
Starting...................................................... 3.45 2.00 1.74 1.54 0.90
UL TEMPERATURE RATINGS
Insulation Class
Coil Temperature Code C C D D C
MIN. AMBIENT STARTING TEMP.
NOM. OPEN CIRCUIT VOLTAGE
INPUT VOLTAGE AT LAMP DROPOUT........................... 86 150 171 193 335
INPUT WATTS
RECOMMENDED FUSE (Amps)..................................... 10 6 5 5 3
CORE and COIL
Dimension (A)
Dimension (B)
Weight (lbs.)
Lead Lengths
CAPACITOR REQUIREMENT
Microfarads
Volts (min.)
Fault Current Withstand (amps)
60 Hz TEST PROCEDURES (Refer to Philips Lighting
Electronics N.A. TEST Procedure for HID Ballasts - Form
High Potential Test (Volts)
1 minute
2 seconds
Open Circuit Voltage Test (Volts)
Short-Circuit Current Test (Amps)
Secondary Current
Input Current.............................................. 2.68 1.54 1.35 1.18 0.67
4.03 2.30 2.01 1.77 1.00
CWA
98%
±10%
±10%
H(180°C)
1029
-40°F or -40°C
195
465
2.65
4.35
16
12"
55.0
240
2000
2500
176-214
6.10-7.40
Wiring Diagram:
Fig. M
LAMP
CAP
LAMP
COM COM
LINE V
LINE V
LINE V
IGNITOR
X1X3
X2
LINE V
CAP CAP
Typical Ordering Information
(please call Philips Lighting Electronics N.A. for suffix availability)
Order Suffix Description
Revised: 09/23/08