Data Sheet S85001 0333 Fire Alarm Bells

2014-09-05

: Pdf 659938-Attachment 659938-Attachment 793016 Batch7 unilog

Open the PDF directly: View PDF PDF.
Page Count: 2

Page 1 of 2 DATA SHEET S85001-0333
Not to be used for installation purposes. Issue 6
Edwards Signaling Catalog u Strobes, Horns, Bells, Chimes
09-16-13
Standard Features
Vibrating and single stroke
6 inch (150mm), 8 inch (200mm), 10 inch (250mm) sizes
Red or gray finish
Rugged compact mechanism
Heavy duty cast housing
Low power drain
Wide voltage selection
Indoor or weatherproof
Overview
Edwards Fire Alarm Bells are specially designed for fire alarm ap-
plications. The gongs are made of selected alloy steel to give the
loud, resonant tones necessary in fire alarm systems.
Three gong sizes are available to overcome different ambient noise
level.
The Fire Alarm Bells are of the underdome type with heavy duty
mechanisms. Each bell is supplied with a mounting plate that fits
any standard single-gang opening (see Installation Data). For
weather-proof application Edwards offers an optional surface
weatherproof back box. Refer to the Specification chart for ap-
plicability and cata-log number of the weatherproof back box for
the respective bell.
Finish — Standard gong and housing furnished gray with red
label. Optional red finish available. Add Suffix “R” to Catalog
Number.
FM — 438 and 439 Series Bells shown below are FM approved.
MEA
Fire Alarm Bells
Page 2 of 2 DATA SHEET S85001-0333
Not to be used for installation purposes. Issue 6
09-16-13
Contact us...
Phone: 1-800-336-4206
Web: www.edwardssignaling.com
Edwards Signaling is
an EDWARDS brand.
3 Farm Glen Boulevard
Farmington, CT 06032
In Canada, contact Chubb Edwards...
Email: inquiries@chubbedwards.com
Web: www.chubbedwards.com
© 2013 UTC Fire & Security Americas
Corporation, Inc. All rights reserved.
Specifications subject to change
without notice. Edwards is part of UTC
Climate, Controls & Security, a unit of
United Technologies Corporation.
Installation
WARNING: These devices will not op-
erate without electrical power. As fires
frequently cause power interruptions, we
suggest you discuss further safeguards
with your local fire protection specialist.
Edwards recommends that these Fire
Alarm Bells always be installed in accord-
ance with the latest recognized editions
of national and local codes.
Cat. Nos. 438D and 439D 6” and 10” Bells
Specifications & Ordering Information
Cat. No. DB @
10 ft Description Volts Amps Weatherproof
Box
323D-10AW-(R) 79 10" (250mm)
Single Stroke, Diode 20-24 Vdc 0.33 N/A
438D-6N5(R) 76 6" (150mm)
Vibrating, Diode 120 Vac 0.034 449
438D-10N5(R) 88 10" (250mm)
Vibrating, Diode 120 Vac 0.034 449
439D-6AW(R) 83 6" (150mm)
Vibrating, Diode 20-24 Vdc 0.085 449
439D-10AW(R) 86 10" (250mm)
Vibrating, Diode 20-24 Vdc 0.085 449
438D-8N5 86 8" (200mm)
Vibrating, Diode 120 Vac 0.034 449
439D-8AW(R) 84 8" (200mm)
Vibrating, Diode 20-24 Vdc 0.085 449
Mounting Accessories
449 Weatherpoof surface mount box, grey. C/w gasket.