CX_LightingControlRelayInstructions012611 Installation Directions

2014-05-16

: Pdf 687430-Installationsheet 687430-InstallationSheet 640181 Batch3 unilog

Open the PDF directly: View PDF PDF.
Page Count: 4

DownloadCX_LightingControlRelayInstructions012611  Installation Directions
Open PDF In BrowserView PDF
 
 

CXR Lighting Control Relays – For use with CX Series Panels
Installation Instructions
 
Hubbell Building Automation
9601 Dessau Road  Building One  Suite 100  Austin, TX 78754
Toll Free: 888-698-3242  Fax: 512-450-1215
www.hubbell-automation.com
CONTENTS
These instructions include information as follows:
Precautions
Description
Product Configurations
Installing Individual Relay Cards
Connecting Lighting Loads
Connecting Low Voltage Inputs
Operating the Panel
Troubleshooting
Relay Specifications

PRECAUTIONS

















READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
CAUTION - RISK OF ELECTRICAL SHOCK. To prevent electrical shock, turn off power at the circuit
breaker before installing or servicing unit. Never wire energized electrical components.
NOTICE: For installation by a licensed electrician in accordance with National and/or local Electrical Codes
and the following instructions.
CAUTION: USE COPPER CONDUCTOR ONLY.
Be sure to read and understand all instructions before installing or servicing unit
For Indoor use only. Do not use outdoors.
Do not mount near gas or electric heaters.
Disconnect switch or a circuit breaker must be provided and marked as the disconnecting device.
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
Confirm that device ratings are suitable for application prior to installation.
No user serviceable parts contained inside unit. Refer all service related questions to the factory. All servicing
shall be performed by qualified service personnel.
Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by
unauthorized personnel.
Use only approved materials and components (i.e. twist on connectors, electrical box, etc.) as appropriate for
installation.
NOTICE: Do not install if product appears to be damaged.
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the
equipment may be impaired.
Do not use this equipment for other than intended use.

SAVE THESE INSTRUCTIONS!

DESCRIPTION
CXR Relays are designed to be installed in CX Series Panels only. Individual relays of any type can be placed in
any position in the panel. Two pole relays fit in the same space as one pole relays. Relay types are as follows:
Relay
Model
CXR

Relay Type
2N
3L
TN
TC

20A, 1P, NO Elect Held, 120/277VAC
30A, 1P, Latching, 120/277/, 20A 347VAC
20A, 2P, NO Elect Held, 208/240/480VAC
20A, 2P, NC Elect Held, 208/240/480VAC

INSTALLING INDIVIDUAL RELAY CARDS
Install Relays in the CX Panel as follows:
1. Disconnect Low Voltage Control Input Plug located at the top of the Mother Board
2. Align the relay board in the desired relay position and insert the Relay Card Plug Connector (Male) into the
socket (Female) on the mother board. Be sure that all of the pines line up and that the connection is tight.
3. Insert and tighten the Relay Card Mounting Screw. Be sure that when tightened that the Relay Card Plug
Connector does not loosen due to the torque force.
All terminations within the panel enclosure require installation by a licensed electrician in accordance with National
and/or local Electrical Codes
Caution: ALWAYS remove supply power to the Panel Mother Board prior to making any connections between
relay boards and panel mother board. Failure to do so may result in personnel injury, damage to the panel, and
void its warranty

Figure 1 – CX Panel Interior
Low Voltage Control
Power Input Plug

Panel Mother Board

Relay Card Mounting
Screw
Relay Card Plug
Connector

 

CONNECTING LIGHTING LOADS
With the power turned off, route the lighting system line and load leads through the high voltage area of the panel
shown in Figure 1. Connect line and load leads for each lighting load to the output terminals of the appropriate relay
as delineated in the project plans and/or Panel Load Schedule. Space is provided for the circuit identification number
to be written adjacent to the terminals on each relay card.
Caution: Prior to making any connections to the relay outputs, verify that none of the loads are shorted. Failure
to do so may result in personnel injury, damage to the panel, and void its warranty
Notice: If no Panel Load Schedule exists, use the Panel Load Schedule Form supplied in the clear plastic pocket
inside the Panel Door to record the lighting circuit relay assignments while connecting the relays
CONNECTING LOW VOLTAGE INPUT
Bring the low voltage wiring for the contact inputs in through the knockouts in the low voltage wiring area where
indicated in Figure 1. The CXR Relay Card includes one input. The input is software configurable through
programming to support momentary switches, maintained switches (latching), motion sensors, or photocells. The
input may be connected prior to programming. Inputs may be connected to any terminal location regardless of final
control programming. Connect contact closure input devices to the input terminals using 18 AWG wire.
Notice: Use the Panel Load Schedule Form supplied in the clear plastic pocket inside the Panel Door to record
the low voltage input types while making connections.
Low Voltage Control Diagrams shown in Figure 3 below are for use with Hubbell Building Automation Input
Devices ONLY. Diagrams may not apply to input devices from other manufacturers.

Figure 2 - Low Voltage Input Wiring Diagrams

OPERATING THE PANEL
Connect the User Interface control ribbon cable to the User Interface Ribbon Cable Connector on the Mother Board
where shown in Figure 3. The User Interface control ribbon cable is supplied connected to the User Interface
Module that is attached to the panel door. Connect the green ground jumper to the panel housing ground lug, labeled
“GND” with the hardware provided. The green ground jumper is supplied attached to the panel door. Provide
control power to the panel and restore power to the lighting circuits at the source circuit breakers. The panel will
take a few moments to initialize during which time the User Interface screen on the front of the panel door will
initiate and display the clock, date, and time zone un-programmed factory defaults. Inside the panel the Mother
board power status LED will show continuous “green”. The Relay board status LED will turn on “green” for
approximately 2 seconds and then go off. Push. But do not hold the Relay Manual Control button on each relay card
to operate each relay to test functionality. The Relay State Status LED will turn on “red” when the relay is energized
and be off when the relay is un-energized. The panel is now fully functional and ready to control the lighting loads.

Figure 3 - Panel Start-Up Controls

 
TROUBLESHOOTING
A blinking “green” Relay board status LED indicates that communication has not been properly established for this
card. Contact Hubbell Building Automation Technical Service at (888) 698-3242 for assistance and replacement as
required.
CXR RELAY SPECIFICATIONS






Relay Load Ratings:
o CXR2N – 120/277VAC, Electrically Held, NO, 20Amps, HID and Fluorescent Ballast 15Amps
Tungsten (120V only), 3/4HP at 120V and 277V,
o CXR3L – 120/277/347VAC, Latching, 30Amps, HID and Fluorescent Ballast at 120/277 VAC, and
20A mps Tungsten at 120VAC, 1HP at 120V, and 20Amps, HID and Fluorescent Ballast at 347V
o CXRTN – 208/240/480VAC, Electrically Held, NO, 20Amps, HID, Ballast, 2HP
o CXRTC – 208/240/480VAC, Electrically Held, NC, 20Amps, HID, Ballast, 2HP
Low Voltage Input – One located on relay board:
o Low Voltage Switches – 2 or 3 wire momentary or maintained style, with or without LED indication.
o Motion Sensor Input – Three wire 24 VDC,
o Photocell – Four wire 24VDC power, 0-10V DC control input.
Operating Environment:
o Indoor Use Only; 0 to 50°C; Relative Humidity: 0 – 90% non-condensing.

72 – 00447



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
Author                          : dkennedy
Create Date                     : 2011:01:30 11:33:04-06:00
Modify Date                     : 2011:01:30 11:33:04-06:00
XMP Toolkit                     : Adobe XMP Core 4.2.1-c041 52.342996, 2008/05/07-20:48:00
Creator Tool                    : PScript5.dll Version 5.2.2
Format                          : application/pdf
Title                           : Microsoft Word - CX_LightingControlRelayInstructions012611.doc
Creator                         : dkennedy
Producer                        : Acrobat Distiller 9.0.0 (Windows)
Document ID                     : uuid:cd561cac-d13d-4006-aa0c-ab732bb94242
Instance ID                     : uuid:4c9038b9-ffce-4cef-abf4-e909d9f1bc01
Page Count                      : 4
EXIF Metadata provided by EXIF.tools

Navigation menu