700021 700023 700024 700025 Installation Manual

2017-06-22

: Pdf 700021 700023 700024 700025 Installationmanual 700021_700023_700024_700025 InstallationManual product s

Open the PDF directly: View PDF PDF.
Page Count: 28

4
Name
Shape Quantity
1
1
1
Clip anchor
Mounting plate fixing
screw ST3.9 X 25
Remote control
Fixing screw for remote
controller holder ST2.9 x 10
Remote controller holder
Dry battery AAA.LR03
Seal
Drain joint
Mounting plate
5
5
2
1
Optional
Parts
2
1
1
User manual
Installation manual
Line sets sold separately.
Connecting pipe
assembly
Liquid
side
Gas side
6.35(1/4 “)
9.52(3/8”)
9.52(3/8”)
12.7( 1/2”)
16(5/8”)
Select Installation Location
(Page 9)
And Drill Wall Hole
(Page 10)
1
Attach Mounting Plate
(Page 10)
2
Prepare Refrigerant Piping
(Page 12)
4
3b
12cm
(4.75”)
2.3m (90.55”)
12cm
(4.75”)
15cm (5.9”)
Determine Wall Hole Position...
(Page 10)
3a
Mount Indoor Unit
(Page 16)
STEP 8
Wrap Piping and Cable
(Page 15)
123
Connect Drain Hose
(Page 13) Connect Signal Cable
(Page 14)
5 6
7
8
Wall Mounting Plate
Refrigerant
Piping
Signal
Cable
Drainage
Pipe
Louver
Functional Filter
(On Front of Main
Filter - Some Units)
Front Panel
Outdoor
Power Cable
(Some Units)
Remote Holder Remote Control
(Some Units)
12cm/4.75”
or more
2.3m/90.55” or more
12cm/4.75”
or more
15cm/5.9” or more
Wall
Indoor
Outdoor
mm7-5
(0.2-0.3”)
192mm/7.55”
232mm/9.15”
426mm/16.8”
128mm/5.05”
43mm/1.7”
297mm /11.7”
Left rear wall
hole 65mm/2.5”
Right rear wall
hole 65mm/2.5”
802mm/31.6”
43mm/1.7”
43mm/1.7”
Indoor unit outline
101mm/4”
179mm/7.05”
136mm/5.35”
37mm/1.45”
290mm/11.4”
49mm/1.95”
Right rear wall
hole 65mm/2.5”
722mm/28.45”
49mm/1.95”
348.4mm/13.7”
Indoor unit outline
144mm/5.65”
58mm/2.3”
319mm/12.55”
57mm/2.25”
40mm/1.55”
Right rear wall
hole 65mm/2.5”
Model C
965mm/38”
138mm/5.45”
34mm/1.35”/
517.4mm/20.37”
Indoor unit outline
Left rear wall hole
65mm/2.5”
219mm/8.6”
553mm/21.77”
300mm/11.8in
335mm/13.2”
Right rear wall
hole 65mm/2.5”
Model D
1080mm/42.5”
53.5mm /2.1”
47mm/1.85”
76mm/3”
53.5mm/2.1”
47mm/1.85”
148.7mm
/5.85”
151mm/5.95”
174.3mm/6.85”
Indoor unit outline
Left rear wall hole
65mm/2.5”
172mm/6.8”
362mm/14.25”
Right rear wall
hole 65mm/2.5”
Model E
1259mm/49.55”
52mm/2.05”
389mm/15.3”
332mm/13.05”
257mm/10.1”
643.6mm/25.3”
52mm/2.05” Indoor unit outline
Knock-out
Panel
CORRECT
Make sure there ar
kinks or dent in drain
hose to ensure proper
drainage.
NOT CORRECT
Kinks in the drain hose
will create water traps.
NOT CORRECT
Kinks in the drain hose
will create water traps.
NOT CORRECT
Do not place the end
of the drain hose in
water or in containers
that collect water
. This
will prevent proper
drainage.
North America
Appliance Amps (A) AWG
10 18
13 16
18 14
25 12
30 10
Other Regions
Rated Current of
Appliance (A)
Nominal Cross-Sectional
Area (mm²)/in
2
> 3 and 6 0.75/.03”
> 6 and 10 1/.28”
> 10 and 16 1.5/.06”
> 16 and 25 2.5/.10”
> 25 and 32 4/.16”
> 32 and 40 6/.24”
Terminal block
Wire cover
Screw
Cable clamp
The Wiring Diagram is located
on the inside of the indoor unit’s
wire cover.
Indoor Unit
Space
behind unit
Refrigerant
piping
Drain hose
Signal wire
Insulation
tape
Move to left or right
30-50mm
(1.2-1.95”)
30-50mm
(1.2-1.95”)
evoba
/24”
mc06
60cm/24”
on right
30cm/12”
on left
200cm/79”
in front
30cm/12”
from back
wall
Strong wind
Strong wind
Strong wind
Wind baffle
W
A
B
D
Air inlet
Air outlet
Air inlet
Outdoor Unit Dimensions (mm/in)
W x H x D
Mounting Dimensions
Distance A (mm/in) Distance B (mm/in)
681x434x285 (26.8”x17”x11.2”) 460 (18.10”) 292 (11.49”)
700x550x270 (27.5”x21.6”x10.62”) 450 (17.7”) 260 (10.24”)
780x540x250 (30.7”x21.25”x9.85”) 549 (21.6”) 276 (10.85”)
845x700x320 (33.25”x27.5”x12.6”) 560 (22”) 335 (13.2”)
810x558x310 (31.9”x22”x12.2”) 549 (21.6”) 325 (12.8”)
900x860x315 (35.4”x33.85”x12.4”) 590 (23.2”) 333 (13.1”)
945x810x395 (37.2”x31.9”x15.55”) 640 (25.2”) 405 (15.95”)
946x810x420 (37.21”x31.9”x16.53”) 673 (26.5”) 403 (15.87”)
946x810x410 (37.21”x31.9”x16.14”) 673 (26.5”) 403 (15.87”)
845x702x363 (33.25”x27.63”x14.29”) 540 (21.26”) 350 (13.8”)
700x550x275 (27.5”x21.6”x10.82”) 450 (17.7”) 260 (10.24”)
770x555x300 (30.3”x21.85”x11.81”) 487 (19.2”) 298 (11.73”)
800x554x333 (31.5”x21.8”x13.1”) 514 (20.24”) 340 (13.39”)
North America
Appliance Amps (A) AWG
10 18
13 16
18 14
25 12
30 10
Other Regions
Rated Current of
Appliance (A)
Nominal Cross-
Sectional Area (mm²)/in2
> 3 and 6 0.75/.03”
> 6 and 10 1/.04”
> 10 and 16 1.5/.06”
> 16 and 25 2.5.10”
> 25 and 32 4/.16”
> 32 and 40 6/.24”
Cover
Outdoor Unit Wiring Diagram
is located on the inside of the
wire cover on the outdoor unit.
Model Capacity (BTU/h) Max. Length (m) Max. Drop Height (m)
R410A Inverter Split Air
Conditioner
< 15,000 25 (82’) 10 (33’)
15,000 and < 24,000 30 (98.5’) 20 (66’)
24,000 and < 36,000 50 (164’
)2
5 (82’)
36,000 and 60,000 65 (213’)30 (98.5’)
≥10cm/4”Radius
Outer Diameter of
Pipe (mm)
A (mm)
Min. Max.
Ø 6.35 (Ø 0.25”) 0.7 (0.0275”) 1.3 (0.05”)
Ø 9.52 (Ø 0.375”) 1.0 (0.04”) 1.6 (0.063”)
Ø 12.7 (Ø 0.5”) 1.0 (0.04”) 1.8 (0.07”)
Ø 16 (Ø 0.63”) 2.0 (0.078”) 2.2 (0.086”)
TORQUE REQUIREMENTS
Outer Diameter of Pipe (mm) Tightening Torque (N•cm) Add. Tightening Torque (N•m)
Ø 6.35 (Ø 0.25”) 1,500 (11lb •ft) 1,600 (11.8lb •ft)
Ø 9.52 (Ø 0.375”) 2,500 (18.4lb •ft) 2,600 (19.18lb •ft)
Ø 12.7 0.5”) 3,500 (25.8lb•ft) 3,600 (26.55lb•ft)
Ø 16 0.63”) 4,500 (33.19lb•ft) 4,700 (34.67lb•ft)
Valve
cover
ADDITIONAL REFRIGERANT PER PIPE LENGTH
Connective Pipe
Length (m) Air Purging
Method Additional Refrigerant
< Standard pipe length
Vacuum Pump N/A
> Standard pipe
length Vacuum
Pump
Liquid Side: Ø 6.35 (ø 0.25”)
R22:
(Pipe length – standard length) x 30g/m
(Pipe length – standard length) x 0.32oZ/ft
Inverter R410A:
Fixed-frequency R410A:
Inverter R410A:
Fixed-frequency R410A:
(Pipe length – standard length) x 15g/m
(Pipe length – standard length) x 0.16oZ/ft
(Pipe length – standard length) x 20g/m
(Pipe length – standard length) x 0.21oZ/ft
(Pipe length – standard length) x 40g/m
(Pipe length – standard length) x 0.42oZ/ft
Liquid Side: Ø 9.52 (ø 0.375”)
R22:
(Pipe length – standard length) x 60g/m
(Pipe length – standard length) x 0.64oZ/ft
(Pipe length – standard length) x 30g/m
(Pipe length – standard length) x 0.32oZ/ft
List of Checks to Perform PASS/FAIL
No electrical leakage
Unit is properly grounded
All electrical terminals
properly covered
Indoor and outdoor units
are solidly installed
All pipe connection
points do not leak
Outdoor
(2):
Indoor
(2):
Water drains properly
from drain hose
All piping is properly
insulated
Unit performs COOL
function properly
Unit performs HEAT
function properly
Indoor unit louvers
rotate properly
Indoor unit responds to
remote controller
Manual control button