Ab P2101
User Manual: Pdf Ab-p2101
Open the PDF directly: View PDF .
Page Count: 73
Download | ![]() |
Open PDF In Browser | View PDF |
<12002388 001> Page 2 Test item Description ................................. : Personal Computer Trademark .................................. : ASUS Model and/or type reference.......... : 1. Prodigy-P4S 2. AB-P2101 Manufacturer .............................. : Same as client. Rating(s) .................................... : 100-240Vac, 47-63Hz, Max. 3A ................................................. : Particulars: test item vs. test requirements Equipment mobility ............................................ : Movable equipment Operating condition............................................ : Continuous operation Tested for IT power systems............................... : Yes IT testing, phase-phase voltage (V) ...................... : IT, 230V for Norway Class of equipment ............................................ : Class I Mass of equipment (kg) ...................................... : 7.4kg Protection against ingress of water ...................... : IPX0 Test case verdicts Test case does not apply to the test object ........... : N(.A.) Test item does meet the requirement ................... : P(ass) Test item does not meet the requirement .............. : F(ail) ....................................................................... : Testing Date of receipt of test item ................................ : May, 2002 Date(s) of performance of test ............................ : May, 2002 ....................................................................... : General remarks This test report shall not be reproduced except in full without the written approval of the testing laboratory. The test results presented in this report relate only to the item tested. "(see remark #)" refers to a remark appended to the report. "(see appended table)" refers to a table appended to the report. Throughout this report a point is used as the decimal separator. Factory: 1. ASUSTek Computer Inc. No. 5, Shing Yeh Street, Kwei Shan Hsiang, Taoyuan Hsien 333, Taiwan, R.O.C. 2. ASUSTeK Computer Inc. No. 150, Li-Te Rd., Peitou, Taipei, Taiwan, R.O.C. TRF No.: I950___D TRF originator: FIMKO <12002388 001> Page 3 Comments: Brief description of the test sample: The model Prodigy-P4S and AB-P2101 are personal computers for general office use. These two models are identical except for model name. The internal building-in switching power supply is CB approved and evaluated according to Standard IEC 60950:A1+A2+A3+A4. Details of the power supply see appended table 1.5.1. Unless otherwise specified, all tests were performed on model AB-P2101 to represent the other similar model. The test samples were pre-production sample without serial numbers. TRF No.: I950___D TRF originator: FIMKO <12002388 001> Page 4 Copy of marking plate: TRF No.: I950___D TRF originator: FIMKO <12002388 001> Page 5 IEC 950 Clause Requirement − Test 1 GENERAL P 1.5 Components P 1.5.1 Comply with IEC 950 or relevant component standard Components which were found to affect safety aspects comply with the requirements of this standard or within the safety aspects of the relevant IEC component standards. (see appended tables) P 1.5.2 Evaluation and testing of components Components which are certified to IEC and /or national standards are used correctly within their ratings. Components not covered by IEC standards are tested under the conditions present in the equipment. P The equipment is not plug-in Dimensions (mm) of mains plug for direct plug-in ........................................................ : type N Torque and pull test of mains plug for direct plug-in; torque (Nm); pull (N) N Result – Remark Verdict 1.5.3 Transformers Transformer used are suitable for their intended application and comply with the relevant requirements of the standard and particularly Annex C. P 1.5.4 High voltage components (component; No high voltage components manufacturer; flammability) ........................... : used. N 1.5.5 Interconnecting cables Interconnection cable for signal output to other devices and signal input from accessories are carrying only SELV voltages on an energy level below 240VA. P → Except for the insulation material, there are no further requirements to the interconnection cable. 1.5.6 Mains capacitors TRF No.: I950___D In approved SPS. N TRF originator: FIMKO <12002388 001> Page 6 IEC 950 Clause Requirement − Test 1.6 Power interface 1.6.1 Steady state input current Result – Remark Verdict P Highest load according to 1.2.2.1 for this equipment is the FDD, HDD, CD-RW, DVD-ROM and CD-ROM permanently access, the dummy loads of 2.5W in each USB connections and a dummy load of 5Vdc/10W to represent each slots on computer mainboard. The operator can connect additional options like a parallel printer or a serial device. The output power of max. 0.5W is considered to be negligible. P (see appended table) Current deviation during normal operating cycle <+10% P 1.6.2 Voltage limit of hand-held equipment This appliance is not a handheld equipment. N 1.6.3 Neutral conductor insulated from earth and body The neutral is not identified in the equipment. Basic insulation for rated voltage between earthed parts and primary phases. P 1.6.4 Components in equipment intended for IT power Phase to earth designed in system according to phase-to-phase working voltage. The Y2 type capacitor used between phase-to-earth. P 1.6.5 Mains supply tolerance (V) ............................ : +6%, -10% Documentation specifies a rating of AC 100-240V at 47-63Hz with +6%, -10% tolerance. Relevant tests were done with the range of 90-254V at 47-63Hz. P 1.7 Marking and instructions P 1.7.1 Rated voltage (V) ......................................... : 100-240VAC P N Symbol of nature of supply for d.c. ................ : Mains from AC source TRF originator: FIMKO TRF No.: I950___D <12002388 001> Page 7 IEC 950 Clause Requirement − Test Result – Remark Verdict Rated frequency (Hz) .................................... : 47-63Hz P Rated current (A) ......................................... : Max. 3A P Manufacturer ............................................... : Not shown P Trademark .................................................. : ASUS P Type/model ................................................. : 1. Prodigy-P4S P 2. AB-P2101 Symbol of Class II ........................................ : Class I equipment N Certification marks ....................................... : N, UL, CUL N 1.7.2 Safety instructions The users manual contains information for operation, installation, servicing, transport, storage and technical data. Marking for laser class 1 type CD-ROM (or CD-RW, DVD-ROM), with the following wording: CLASS 1 LASER PRODUCT APPAREIL A LASER DE CLASSE 1 LASERSCHUTZKLASSE1 PRODUKT P 1.7.3 Short duty cycles Equipment is designed for continuous operation. N 1.7.4 Marking for voltage setting/frequency setting ... : Full range design, no necessary adjustment. N 1.7.5 Marking at power outlets .............................. : No outlet. N 1.7.6 Marking at fuseholders .................................. : In approved SPS. N 1.7.7.1 Protective earthing terminals Appliance inlet used. N 1.7.7.2 Terminal for external primary power supply conductors The equipment with appliance inlet is intended to be used with the detachable type power supply cord. N 1.7.8.1 Identification and location of switches and The marking and indication of controls ...................................................... : the functional switch is located that indication of function clearly. P 1.7.8.2 Colours of controls and indicators .................. : No safety relevant controls or indicators. N 1.7.8.3 Symbols according to IEC 417 ....................... : The switch on front panel with symbol according to IEC P TRF No.: I950___D TRF originator: FIMKO <12002388 001> Page 8 IEC 950 Clause Requirement − Test Result – Remark Verdict 60417, No. 5009 (line half inside circle). 1.7.8.4 Figures used for marking ............................... : No indicator for different position. N 1.7.8.5 Location of markings and indications for Switch marking placed on switches and controls ................................... : the switch knob. P 1.7.9 Isolation of multiple power sources ................. : Only one supply from the mains. N 1.7.10 Instructions for installation to IT power system The instructions will be provided when national approval. N 1.7.11 Instructions when protection relies on building installation Connected to the mains by pluggable type A. N 1.7.12 Marking when leakage current exceeds 3,5 mA Leakage current does not exceed 3.5mA. N 1.7.13 Indication at thermostats and regulating devices No adjustable thermostats. N 1.7.14 Language of safety markings/instructions User’s manual provided in English. Version in other languages will be provided when national approval. P Language .................................................... : English 1.7.15 Durability and legibility The label was subjected to the permanence of marking test. The label was rubbed with cloth soaked with water for 15 sec. and then again for 15 sec. with the cloth soaked with petroleum spirit. P After this test there was no damage to the label. The marking on the label did not fade. There was no curling nor lifting of the label edge. 1.7.16 Removable parts No required markings placed on removable parts. P 1.7.17 Warning text for replaceable lithium batteries Lithium battery for real time clock is exchangeable. Warning sentence printed in manual. P 1.7.18 Language .................................................... : English Operator access with a tool ........................... : The inside of the personal computer is regarded to be P TRF No.: I950___D TRF originator: FIMKO <12002388 001> Page 9 IEC 950 Clause Requirement − Test Result – Remark Verdict operator access area. This area is accessible when enclosure of computer is be disassembled with a screwdriver. When the enclosure is disassembled, the earthed metal enclosure of SPS is accessible. However, the SPS enclosure can be opened with the same screw driver as the screw head is in same construction. Therefore, the SPS provided with electric shock hazard symbol (ISO 3864, No. 5036) on its rating label to discourage the user to access. 1.7.19 Equipment for restricted access locations ........ : No restricted access location. N 2 PROTECTION FROM HAZARDS P 2.1 Protection against electric shock and energy hazards P 2.1.1 Access to energized parts See below. P 2.1.2 Protection in operator access areas As the user’s manual specifies directions for the operator how to add additional memory cards or add-on cards inside the enclosure, the inside of this server is regarded to be operator access area. With the disassembled server enclosure, the accessible SPS is covered with an earthed metal enclosure. P The construction of this metal enclosure prevents the accessibility to any parts with only basic insulation to ELV or hazardous voltage with test pin or test finger. Test by inspection ........................................ : dto TRF No.: I950___D P TRF originator: FIMKO <12002388 001> Page 10 IEC 950 Clause 2.1.3.1 Requirement − Test Result – Remark Verdict Test with test finger ..................................... : dto P Test with test pin ........................................ : dto P Insulation of internal wiring in an ELV circuit accessible to operator No ELV wiring in operator accessible area. N N Working voltage (V); distance (mm) through insulation .................................................... : 2.1.3.2 Operator accessible insulation of internal wiring at hazardous voltage No hazardous voltage wiring in operator accessible area. N 2.1.4.1 Protection in service access areas No maintenance work in operation mode necessary. N 2.1.4.2 Protection in restricted access locations It is not intended to be used in restricted locations N 2.1.5 Energy hazard in operator access area The overall output of the SPS is below 240VA. P 2.1.6 Clearances behind conductive enclosures Refer to 4.2. P 2.1.7 Shafts of manual controls None at ELV or hazardous voltage N 2.1.8 Isolation of manual controls None at ELV or hazardous voltage N 2.1.9 Conductive casings of capacitors In approved SPS. N 2.1.10 Risk of electric shock from stored charge on capacitors connected to mains circuit In approved SPS. N Time-constant (s); measured voltage (V) ......... : — 2.2 Insulation P 2.2.1 Methods of insulation The insulation materials provided in the equipment with adequate thickness and adequate creepage distance over their surface and clearance distance through air. P 2.2.2 Properties of insulating materials Natural rubber, asbestos or hygroscopic materials are not used P 2.2.3 Humidity treatment Total time elapsed: 48 hrs P Humidity (%) ............................................... : 95% R.H. Temperature (°C) ......................................... : 25°C TRF No.: I950___D TRF originator: FIMKO <12002388 001> Page 11 IEC 950 Clause Requirement − Test Result – Remark 2.2.4 Requirements for insulation Please refer to 5.3, 2.9 and 5.1. P 2.2.5 Insulation parameters Both parameters were considered. P 2.2.6 Categories of insulation The adequate levels of safety insulation is provided and maintained to comply with the requirements of this standard. P 2.2.7.1 General rules for working voltages The rms and the peak voltages were measured on the approved building-in switching power supply. P 2.2.7.2 Clearances in primary circuits Considered P 2.2.7.3 Clearances in secondary circuits See clause 5.4.4. N 2.2.7.4 Creepage distances Considered P 2.2.7.5 Electric strength tests Considered P 2.2.8.1 Bridging capacitors ....................................... : No component bridged reinforced or double insulation. N 2.2.8.2 Bridging resistors No component bridged reinforced or double insulation. N 2.2.8.3 Accessible parts N 2.3 Safety extra-low voltage (SELV) circuits P 2.3.1 Voltage (V) of SELV circuits under normal 42.4V peak or 60VDC are operating conditions and after a single fault ..... : not exceeded in SELV circuit under normal operation or single fault condition 2.3.2 Between any SELV circuits Voltage (V) between any two conductors of SELV circuit(s) and for Class I equipment 42.4V peak or 60VDC are not exceeded between any conductor of SELV circuit and equipment protective earthing terminal under normal operating conditions ........................... : P 2.3.3 Single fault did not cause Voltage (V) of SELV in the event of a single failure of basic or supplementary insulation or of excessive voltage in a component ............................................... : accessible SELV circuits. Limits of 71V peak and 120V DC were not exceed and SELV limits not for TRF No.: I950___D Verdict TRF originator: FIMKO <12002388 001> Page 12 IEC 950 Clause Requirement − Test Result – Remark Verdict longer than 0.2 seconds Method used for separation ........................... : Method 1 P 2.3.4 Additional constructional requirements IEC 60083 and IEC 60320 connectors are not used in SELV. P 2.3.5 Connection of SELV circuits to other circuits See 2.3.2 and 2.3.3. N No direct connection between SELV and any primary circuits. 2.3.8 Construction of SELV circuits N 2.3.9 SELV circuits connected to other circuits N 2.4 Limited current circuits N 2.4.2 Frequency (Hz) ............................................ : — Measured current (mA) ................................. : N Measured voltage (V) ................................... : Measured capacitance (µF) ............................ : — Measured voltage (V) ................................... : Measured charge (µC) ................................... : — Measured voltage (V) ................................... : — Measured energy (mJ) .................................. : N 2.4.6 Limited current circuit supplied from or connected to other circuits ............................ : N 2.5 Provisions for earthing P 2.5.1 Class I equipment 2.4.3 2.4.4 2.4.5 N N Basic insulated conductive parts touchable in operator area earthed reliably. P N Warning label for service personnel 2.5.2 Protective earthing in Class II equipment Class I equipment N 2.5.3 Switches/fuses in earthing conductors No switches or fuses in earthing conductor. P 2.5.4 Assured earthing connection for Class I equipment in systems comprising Class I and Class II equipment This unit has its own earthing connection. Any other units connected via the interconnecting cable to other P TRF No.: I950___D TRF originator: FIMKO <12002388 001> Page 13 IEC 950 Clause Requirement − Test Result – Remark Verdict unit shall provide SELV only. The equipment does not comprise class I and class II 2.5.5 Green/yellow insulation Green/yellow wire from inlet to chassis in the approved SPS. P 2.5.6 Continuity of earth connections It is not possible to disconnect earth without disconnecting mains as an appliance inlet is used. P 2.5.7 Making and breaking of protective earthing connections Plug or inlet, earthing connected before and disconnected after hazardous voltage. No other operator removable parts. P 2.5.8 Disconnection protective earthing connections It is not necessary to disconnect earthing except for the removing of the earthed parts itself P 2.5.9 Protective earthing terminals for fixed supply conductors or for non-detachable power supply cords 2.5.10 Corrosion resistance All safety earthing connections in compliance with Annex J. P 2.5.11 Resistance (O) of protective earthing conductors ≤ 0,1 O ≤ 0.1Ω, see below. P N Test current (A) ........................................... : (see appended table) 2.6 Disconnection from primary power P 2.6.1 General requirements 2.6.2 Type of disconnect device ............................. : Appliance inlet 2.6.3 Disconnect device in permanently connected equipment Pluggable equipment type A. N 2.6.4 Parts of disconnect device which remain energized When plug or inlet is disconnected no remaining parts with hazardous voltage in the equipment P 2.6.5 Switches in flexible cords No isolation switch provided. N TRF No.: I950___D The appliance inlet is considered to be the disconnect device P P TRF originator: FIMKO <12002388 001> Page 14 IEC 950 Clause Requirement − Test Result – Remark 2.6.6 Disconnection of both poles simultaneously in single-phase equipment The plug or inlet disconnects both poles simultaneously. P 2.6.7 Disconnection of all phase conductors of supply in three-phase equipment Single phase N 2.6.8 Marking of switch acting as disconnect device N 2.6.9 Installation instructions if plug on power supply cord acts as disconnect device N Language .................................................... : Verdict 2.6.11 Interconnected equipment Certified plug or inlet, earthing connected before phases are connected P 2.6.12 Multiple power sources Only one supply connection provided. N 2.7 Overcurrent and earth fault protection in primary circuits 2.7.1 Basic requirements Equipment relies on 16A rated fuse or circuit breaker of the wall outlet installation protection of the building installation in regard to L to N short circuit. Overcurrent protection is provided by the built-in device fuse in SPS. P 2.7.2 Protection against faults not covered in 5.4 The protection devices are well dimensioned and mounted. P 2.7.3 Short-circuit backup protection Pluggable equipment type A, the building installation is considered as providing short circuit protection P 2.7.4 Number and location of protective devices ...... : Overcurrent protection by one built-in fuse in approved SPS. 2.7.5 Protection by several devices Only one fuse in approved SPS. N 2.7.6 Warning to service personnel With reversible type plug to the mains, hazardous voltage may be still presented in the equipment after the internal fuse opens. However, as it is considered that the plug to the mains will be disconnected during service P TRF No.: I950___D P P TRF originator: FIMKO <12002388 001> Page 15 IEC 950 Clause Requirement − Test Result – Remark Verdict work, no marking were requested. 2.8 Safety interlock N No operator accessible areas which presents hazards in the meaning of this standard. 2.8.2 Design N 2.8.3 Protection against inadvertent reactivation N 2.8.4 Reliability N 2.8.5 Overriding an interlock N 2.8.6.1 Contact gap (mm) ........................................ : N 2.8.6.2 Switch performing 50 cycles N 2.8.6.3 Electric strength test: test voltage (V) ............. : N 2.8.7 Protection against overstress N 2.9 Clearances, creepage distances and distances through insulation P Nominal voltage (V) ...................................... : AC 100-240V General P 2.9.2 Clearances See below P 2.9.2.1 Clearances in primary circuits All in approved SPS. P 2.9.2.2 Clearances in secondary circuits See clause 5.4.4. N 2.9.3 Creepage distances In approved SPS. P CTI tests ..................................................... : 2.9.4.1 Minimum distances through insulation In approved SPS. P 2.9.4.2 Thin sheet material In approved SPS. P 2.9.4.3 2.9.4.4 Number of layers (pcs) .................................. : P Electrical strength test: test voltage (V) .......... : P Printed boards Not applied for N Distance through insulation N Electric strength test at voltage for thin sheet insulating material N Number of layers (pcs) .................................. : N Wound components without interleaved TRF No.: I950___D No wound components N TRF originator: FIMKO <12002388 001> Page 16 IEC 950 Clause 2.9.5 Requirement − Test Result – Remark insulation without interleaved insulation. Number of layers (pcs) .................................. : N Two wires in contact inside component; angle between 45° and 90° N Routine testing for finished component N Distances on coated printed boards No coated printed wiring boards. 2.9.7 Enclosed and sealed parts N N Routine testing for electric strength 2.9.6 Verdict No hermetically sealed components. N Temperature T1 (°C) ..................................... : N Humidity % ................................................. : N Spacings filled by insulating compound In approved SPS. P Temperature T1 (°C) ..................................... : N Humidity % ................................................. : N 2.9.8 Component external terminations In approved SPS. P 2.9.9 Insulation with varying dimensions Insulation kept homogenous. N 2.10 Interconnection of equipment 2.10.1 General requirements 2.10.2 Type of interconnection circuits ..................... : Interconnection circuits of SELV through the connectors. No ELV interconnection circuits. 2.10.3 ELV circuits as interconnection circuits 2.11 Limited power source N Use of limited power source .......................... : Supplied from the mains. N TRF No.: I950___D P See below. N No ELV interconnection. P N TRF originator: FIMKO <12002388 001> Page 17 IEC 950 Clause Requirement − Test 3 WIRING, CONNECTIONS AND SUPPLY P 3.1 General P 3.1.1 Cross-sectional area of internal wiring/interconnecting cables All internal wires are UL recognized wiring that is PVC insulated, rated VW-1, min. 80°C, 300V. Internal wiring gauge is suitable for current intended to be carried. P Protection of internal wiring and interconnecting cables No internal wire for primary power distribution. N 3.1.2 Wireways Wires do not touch sharp edges and heatsinks which could damage the insulation and cause hazard. P 3.1.3 Fixing of internal wiring Internal wires with only basic isolation are routed so that they are not close to any live bare components. The wires are secured by solder pins and quick connect terminals so that a loosening of the terminal connection is unlikely. P 3.1.4 Fixing of uninsulated conductors Securely held on PCB. No hazard. P 3.1.5 Insulation of internal wiring The insulation of the individual conductors are suitable for the application and the working voltage. For the insulation material see 3.1.1. P 3.1.6 Wires coloured green/yellow only for protective earth connection See 2.5.5. P 3.1.7 Fixing of beads and similar ceramic insulators Not used. N 3.1.8 Required electrical contact pressure Electrical and earthing connections screwed two or more complete threads into metal. No screws of insulating material for electrical and earthing connections, or where P TRF No.: I950___D Result – Remark Verdict TRF originator: FIMKO <12002388 001> Page 18 IEC 950 Clause Requirement − Test Result – Remark Verdict supplementary or reinforced insulation could be impaired by a metal replacement. 3.1.9 Reliable electrical connections All current carrying and safety earthing connections are metal to metal P 3.1.10 End of stranded conductor No risk of stranded conductors coming loose. P 3.1.11 Use of spaced thread screws/thread-cutting screws No self tapping screws are used. P 3.2 Connection to primary power P 3.2.1 Type of connection ...................................... : Appliance inlet. P Only one mains supply Design of product with more than one supply connection .................................................. : connection. N Provision for permanent connection ................ : Not permanently connected. N Size (mm) of cables and conduits ................... : N 3.2.2 The appliance inlet complies with IEC 60320 and is located at the rear of the unit. P 3.2.3 Appliance inlet 3.2.4 Not provided. Type and cross-sectional area (mm²) of power supply cord ................................................. : N 3.2.5 Cord anchorage N Test: 25 times; 1 s; pull (N) .......................... : Longitudinal displacement ≤ 2 mm .................. : N No parts under this unit likely to damage the power supply cord. No sharp edges. P 3.2.6 Protection of power supply cord 3.2.7 Cord guard N D (mm) ....................................................... : Test: mass (g) ............................................. : Radius of curvature of the cord ≤ 1,5 D N Supply wiring space N 3.2.8 TRF No.: I950___D TRF originator: FIMKO <12002388 001> Page 19 IEC 950 Clause Requirement − Test 3.3 Wiring terminals for external power supply conductors Result – Remark Verdict N Unit with detachable power supply cord, connected on appliance inlet. 3.3.1 Terminals N 3.3.2 Special non-detachable cord N Type of connection ...................................... : — Pull test at 5 N N 3.3.3 Screws and nuts N 3.3.4 Fixing of conductors N 3.3.5 Connection of connectors N 3.3.6 Size of terminals N Nominal thread diameter (mm) ....................... : N 3.3.7 Protection against damage of conductors N 3.3.8 Terminal location N 3.3.9 Test with 8 mm stranded wire N 4 PHYSICAL REQUIREMENTS P 4.1 Stability and mechanical hazards P 4.1.1 Stability tests P Angle of 10° This appliance is of a stable mechanical construction and does not overbalance when tilted to an angle of 10° from its normal upright position. Test: force (N) ............................................. : Equipment is not a floorstanding unit. No hazardous moving part P N P 4.1.2 Protection against personal injury 4.1.3 No hazardous moving parts. Warning and means provided for stopping the moving part ................................................. : 4.1.4 Edges and corners Edges and corners of the enclosure are rounded P 4.1.5 Enclosure of a high pressure lamp No lamp with cold pressure of 0.2MPa or hot pressure N TRF No.: I950___D N TRF originator: FIMKO <12002388 001> Page 20 IEC 950 Clause Requirement − Test Result – Remark Verdict 0.4MPa. 4.2 Mechanical strength and stress relief P 4.2.1 General P 4.2.2 Internal enclosures 30 N ± 3 N; 5 s 30N force tested on internal enclosure (SPS). P 4.2.3 External enclosures 250 N ± 10 N; 5 s 250N applied to outer enclosure. P 4.2.4 Steel ball tests P Fall test 500g steel sphere ball fall, from 1.3m height onto enclosure near power supply circuit. P Swing test 500g steel sphere ball as pendulum onto enclosure near power supply circuit. No safety relevant damages. P 4.2.5 Drop test Not a hand-held equipment. N 4.2.6 Hazardous voltages are Heat test for enclosures of moulded or formed thermoplastic materials: 7 h; T (°C) ................ : contained in the approved SPS. As the SPS is complete enclosed by an earthed metal enclosure which meets the requirements of 2.1.2, the oven test is not considered to be necessary. N 4.2.7 Compliance criteria No safety relevant damages to impact the requirements of 2.1.2, 2.1.5, 2.5.1, 2.5.2, 2.9, 3.2.5, 4.1.2 and 6.2.2. P 4.2.8 Mechanical strength of cathode ray tubes Unit does not employ a cathode ray tube N 4.3 Construction details 4.3.1 Changing of setting for different power supply voltages Auto voltage select design. N 4.3.2 Adjustment of accessible control devices No control device. N 4.3.4 Prevention of dangerous concentration of dust, powder, liquid and gas Equipment in intended use not considered to be exposed to these. N TRF No.: I950___D P TRF originator: FIMKO <12002388 001> Page 21 IEC 950 Clause Requirement − Test 4.3.5 Fixing of knobs, grips, handles, levers N Test: force (N) ............................................. : N 4.3.6 Driving belts/couplings shall not ensure electrical Not used for insulation. insulation N 4.3.7 Retaining of sleeves Sleevings on wiring reliable kept in position by cable ties or by the use of heatshrunk sleeving. No sleeving used as supplementary insulation. N 4.3.9 Protection of loosening parts Electrical and mechanical connections can be expected to withstand usual mechanical stress. For the protection, solder pins, cable ties and heatshrunk tubing are used. P 4.3.11 Resistance to oil and grease Insulation not in contact with oil or grease N 4.3.12 Protection against harmful concentration of ionizing radiation, ultraviolet light, laser or flammable gases (for laser see IEC 825-1) No ionizing radiation or flammable liquids presents. P 4.3.13 Securing of screwed connections No connection likely to be exposed to mechanical stress are provided in unit. P 4.3.15 Openings in the top of enclosure No bare parts at hazardous voltage directly over the openings. P Result – Remark The LED power is far below LED class 1 limit. Dimensions (mm) ......................................... : (see appended table) 4.3.16 Openings in the sides of enclosure Verdict No bare parts at hazardous voltage within 5° projectary areas. Dimensions (mm) ......................................... : (see appended table) In operator and service area, mismate of connectors were prevented by incompatible form or location. P P 4.3.17 Interchangeable plugs and sockets 4.3.18 Torque test for direct plug-in equipment N Additional torque (Nm) .................................. : N 4.3.19 Protection against excessive pressure N 4.3.20 Protection of heating elements in Class I TRF No.: I950___D No heating elements. N TRF originator: FIMKO <12002388 001> Page 22 IEC 950 Clause Requirement − Test Result – Remark Verdict equipment 4.3.21 Protection of lithium batteries P Construction of protection circuit ................... : For RTC battery: P a) Prevent from force charging by D1 and R63. b) Reverse polarity installation is impossible. 4.3.22 Ageing of barrier/screen secured with adhesive N Day 1: temperature (°C); time (weeks) ............ : N Day 8/22/57: a) temperature (°C) for 1 h b) temperature (°C) for 4 h c) temperature (°C) over 8 h .......................... : N Day 9/23/58: a) relative humidity (%) for 72 h b) temperature (°C) for 1 h c) temperature (°C) for 4 h d) temperature (°C) over 8 h .......................... : N 4.4 Resistance to fire P 4.4.1 Methods of achieving resistance to fire Use of materials with the required flammability classes. P 4.4.2 Minimizing the risk of ignition Electrical parts are not likely to ignite nearby materials. Parts not protected against overheating under fault conditions. P Temperatures see 5.1. Printed board: manufacturer; type; flammability : See 1.5.1 appended table See below. P P 4.4.3 Flammability of materials and components 4.4.3.2 Material and component: manufacturer; type; Internal components except flammability ................................................ : small parts are V-2 or better. P 4.4.3.3 Exemptions ................................................. : Considered. P 4.4.3.4 Wiring harnesses: manufacturer; flammability .. : Insulating material consists of PVC. P 4.4.3.5 No cord anchorage. Cord anchorage bushings: manufacturer; flammability ................................................ : N 4.4.3.6 Air filter assemblies: manufacturer; flammability : No air filter assemblies N TRF No.: I950___D TRF originator: FIMKO <12002388 001> Page 23 IEC 950 Clause Requirement − Test 4.4.4 Protective metal enclosure Enclosures and decorative parts: manufacturer; type; flammability ........................................ : with decorative front plastic panel and cover. The front panel and cover assumed as decorative part with the flammability class HB was acceptable. 4.4.5 Conditions for fire enclosures 4.4.5.1 With having the following Components requiring fire enclosure: manufacturer; flammability ............................ : components: Result – Remark See 4.4.5.1 n components with windings n wiring n semiconductor devices, transistors, diodes, integrated circuits n resistors, capacitors, inductors Verdict P P P the fire enclosure is required. 4.4.5.2 Components not requiring fire enclosure .......... : See 4.4.5.1 4.4.6 Fire enclosure construction Protection against emission of flame, molten metal, flaming or glowing particles or drops by the fire enclosure without bottom openings. (see appended table) P 4.4.7 Doors or covers in fire enclosures No door or cover within fire enclosure. N 4.4.8 Flammable liquids No flammable liquids in this unit. N 5 THERMAL AND ELECTRICAL REQUIREMENTS P 5.1 Heating P Heating tests 5.2 Earth leakage current 5.2.1 General TRF No.: I950___D (see appended table) N P P The leakage current was P measured from primary to TRF originator: FIMKO <12002388 001> Page 24 IEC 950 Clause Requirement − Test Result – Remark Verdict chassis. 5.2.2 5.2.3 5.2.4 5.2.5 (see attached tables) P Test voltage (V) ........................................... : (see attached tables) P Measured current (mA) ................................. : (see attached table) Max. allowed current (mA) ............................ : 3.5mA Leakage current Single-phase equipment See 5.2.2 P Test voltage (V) ........................................... : Measured current (mA) ................................. : Max. allowed current (mA) ............................ : 3.5mA Three-phase equipment Single phase equipment N Test voltage (V) ........................................... : Measured current (mA) ................................. : Max. allowed current (mA) ............................ : Equipment with earth leakage current exceeding 3,5 mA Leakage current does not exceed 3.5mA N Test voltage (V) ........................................... : Measured current (mA) ................................. : Max. allowed current (mA) ............................ : Cross-sectional area (mm²) of internal protective earthing conductor ....................................... : Warning label N 5.3 Electric strength P 5.3.1 General All tests voltages were applied for 1 minute in the chamber after the humidity test of 2.2.3 and in warm conditions after the heating test of 5.1. P No isolation breakdown was observed (results see appended tables). 5.3.2 Test procedure TRF No.: I950___D (see appended table) P TRF originator: FIMKO <12002388 001> Page 25 IEC 950 Clause Requirement − Test 5.4 Abnormal operating and fault conditions 5.4.2 Motors Non-approved components used. Results see annex B and table 5.4. P 5.4.3 Transformers The protection of the SPS and transformer are approved with the approval of the SPS. P 5.4.4 Compliance of operational insulation Result – Remark Verdict P P Power supply is approved component, the over-current protection of the power supply ensures that there occur no hazard if there is short circuit in the SELV circuit. Method used ............................................... : Method c) considered. Due to • all components are mounted on PCB of flammability class V-1 • wiring is insulated by PVC • no risk of electrical shock N No test had been performed. 5.4.5 Electromechanical components in secondary circuits No electromechanical components. N 5.4.6 Other components and circuits Faults in primary and secondary components and operational insulation were already considered during the approval of the SPS. N No other abnormal tests necessary. 5.4.7 Test in any expected condition and foreseeable misuse Ventilation blocked and DC fan locked test: Results see appended table. P No hazard by operating buttons and controls not in accordance with the instructions. 5.4.8 Unattended use of equipment having thermostats, temperature limiters etc. None of them are used. N 5.4.9 Compliance No fire propagated beyond the equipment. No molten metal was emitted. Electric P TRF No.: I950___D TRF originator: FIMKO <12002388 001> Page 26 IEC 950 Clause Requirement − Test Result – Remark Verdict strength test primary→SELV and primary→PE were passed. None of them outside the approved SPS. 5.4.10 Ball-pressure test of thermoplastic parts; impression shall not exceed 2 mm 6 CONNECTION TO TELECOMMUNICATION NETWORKS P N Equipment is not intended be connected TNV. 6.1 General N 6.2 TNV circuits N 6.2.1.1 Limits of the TNV circuits N 6.2.1.1 a) TNV-1 circuits N 6.2.1.1 b) TNV-2 and TNV-3 circuits N 6.2.1.2 Separation from other circuits and from accessible parts N Voltage (V) in SELV circuits, TNV-1 circuits and accessible conductive parts in event of single insulation fault or component failure ............... : N Operating voltages generated externally N Voltage (V) in SELV circuit, TNV-1 circuit or accessible conductive part ............................. : N Separation from hazardous voltages ............... : N Insulation between TNV circuit and circuit at hazardous voltage N Method used ............................................... : N Connection of TNV circuits to other circuits N Insulation (mm) between TNV circuit supplied conductively from secondary circuit and hazardous voltage circuit ............................... : N Protection against contact with bare conductive parts of TNV-2 and TNV-3 circuits N Test with test finger N Test with test probe N Battery compartments N Marking next to door/on door N 6.2.1.3 6.2.1.4 6.2.1.5 6.2.2.1 6.2.2.2 TRF No.: I950___D TRF originator: FIMKO <12002388 001> Page 27 IEC 950 Clause Requirement − Test 6.3 Protection of telecommunication network service personnel, and users of other equipment connected to the telecommunication network, from hazards in the equipment N 6.3.1 Protection from hazardous voltages N 6.3.2 Use of protective earthing N Language of installation instructions ............... : N Result – Remark 6.3.3.1 Insulation between TNV circuit and parts or circuitry that may be earthed 6.3.3.2 Exclusions ................................................... : N 6.3.4.1 Limitation of leakage current (mA) to telecommunication network ........................... : N 6.3.4.2 Summation of leakage currents from telecommunication network ........................... : N 6.4 Protection of equipment users from voltages on the telecommunication networks N 6.4.1 Separation requirements N 6.4.2 Test procedure N 6.4.2.1 Impulse test: separation between TNV-1 circuits/TNV-3 circuits and: N 6.4.2.1 a) unearthed conductive parts/non-conductive parts of the equipment expected to be held or touched during normal use; test at 2,5 kV N 6.4.2.1 b) parts and circuitry that can be touched by the test finger except contacts of connectors that cannot be touched by test probe; test at 1,5 kV N 6.4.2.1 c) circuitry which is provided for connection of other equipment; test at 1,5 kV N 6.4.2.2 Electric strength test: separation between TNV-1 circuits/TNV-3 circuits and: N 6.4.2.2 a) unearthed conductive parts/non-conductive parts of the equipment expected to be held or touched during normal use; test at 1,5 kV N 6.4.2.2 b) parts and circuitry that can be touched by the test finger except contacts of connectors that cannot be touched by test probe; test at 1,0 kV N 6.4.2.2 c) circuitry which is provided for connection of other equipment; test at 1,0 kV N 6.4.2.3 Compliance criteria N TRF No.: I950___D (see appended table 5.3) Verdict N TRF originator: FIMKO <12002388 001> Page 28 IEC 950 Clause Requirement − Test 6.5 Protection of telecommunication wiring system from overheating N Maximum continuous output current (A) ......... : N A ANNEX A, TESTS FOR RESISTANCE TO HEAT AND FIRE N A.1 Flammability test for fire enclosures of moveable equipment having a total mass exceeding 18 kg, and of stationary equipment N A.2 Flammability test for fire enclosures of moveable equipment having a total mass not exceeding 18 kg, and for materials located within fire enclosures N A.3 High current arcing ignition test N A.3.6 Number of arcs ............................................ : N A.4 Hot wire ignition test N A.4.6 Ignition time (s) ........................................... : N A.5 Hot flaming oil test N A.6 Flammability test for classifying materials V-0, V-1 or V-2 N A.7 Flammability test for classifying foamed materials HF-1, HF-2 or HBF N A.8 Flammability test for classifying materials HB N A.9 Flammability test for classifying materials 5V N A Tested material N Preconditioning: 7 days (168 h); temperature (°C) ............................................................ : — Mounting of samples during test .................... : — Wall thickness ............................................. : — Sample 1 burning time .................................. : N Sample 2 burning time .................................. : N Sample 3 burning time .................................. : N Material: compliance with the requirements N Manufacturer of tested material ..................... : — Type of tested material ................................. : — Additional information ................................... : — TRF No.: I950___D Result – Remark Verdict TRF originator: FIMKO <12002388 001> Page 29 IEC 950 Clause Requirement − Test B ANNEX B, MOTOR TESTS UNDER ABNORMAL CONDITIONS P B.1 General requirements P Position ...................................................... : 1. CPU Fan — Result – Remark Verdict 2. System Fan Manufacturer ............................................... : Delta Electronics Inc. — Type .......................................................... : 1. AFC0612BC — 2. EFC0412BD Rated voltage (V) or current (A) ..................... : 1. 12V/0.3A — 2. 12V/0.24A B.2 Test conditions N B.3 Maximum temperatures N B.4 Running overload test N B.5 Locked-rotor overload test N Test duration (days) ..................................... : — Electric strength test: test voltage (V) ............. : — B.6 Running overload test for DC motor in secondary circuits N B.7 Locked-rotor overload test for DC motor in secondary circuits P B.7.2 Test time (h) ............................................... : N B.7.3 Test time (h) ............................................... : 7 hours P Results see table 5.4. B.8 Test for motors with capacitors N B.9 Test for three-phase motors N B.10 Test for series motors N Test voltage (V) ........................................... : — ANNEX C, TRANSFORMERS N Position ...................................................... : — Manufacturer ............................................... : — Type .......................................................... : — Rated values ............................................... : — Temperatures N C TRF No.: I950___D TRF originator: FIMKO <12002388 001> Page 30 IEC 950 Clause Requirement − Test Result – Remark Verdict Thermal cut-out N Overload test N Conventional transformer N Insulation N Precautions ................................................. : N Retaining of end turns of all windings N Earthing test at 25 A N C.3 Electric strength test N H ANNEX H, IONIZING RADIATION N Ionizing radiation N Measured radiation ....................................... : — Measured high-voltage (kV) ........................... : — Measured focus voltage (kV) ......................... : — CRT markings .............................................. : — Certified by ................................................. : — Standard used ............................................. : — ANNEX U, INSULATED WINDING WIRES FOR USE AS MULTIPLE PLAYER INSULATION N See separate test report N C.1 C.2 U TRF No.: I950___D TRF originator: FIMKO <12002388 001> Page 31 IEC 950 Clause Requirement − Test 1.5.1 TABLE: list of critical components Result – Remark Verdict P object/part No. manufacturer type/model / trademark technical data standard mark(s) of conformity1) Enclosure -- -- Metal, thickness = 0.7mm -- -- Front Panel/ Base -- -- HB or better UL94 UL PCB -- -- V-1 min, 105°C UL 94 UL Power supply AsusTek Computer Inc. ATTP-165AAP I/P : 100-240V, 47-63Hz, 3A, Class I IEC 60950 CB by TUV Product Service (Ref. Certif. NO. DE 3-51401) 5V/0.75A 12V/1.1A IEC 60950 TUV, UL Fujitsu Ltd. MAJ3xxxMy 5V/1.0A (x=0-9 12V/1.2A y=a-z or blank) IEC 60950 TUV, UL Seagate Technology Inc. ST336704LC 12V/1.1A IEC 60950 TUV, UL Seagate Technology Inc. ST318451LC 5V/ varies 12V /varies IEC 60950 TUV, UL Seagate Technology Inc. 9N2* 5V/0.95A 12V/0.55A IEC 60950 VDE, UL Seagate Technology Inc. 9P4* 5V/0.80A 12V/0.83A IEC 60950 VDE, UL Samsung Electronics Co., Ltd. SN-124 5V, 1.5A Laser Class 1 IEC 60950 IEC TUV, UL 60825-1 O/P : +5V/8A, +3.3V/8A, +12V/9A, -12V/0.3A +5Vsb/1.5A HDD ( Optional ) IBM Japan Ltd. CD- ROM (Optional) TRF No.: I950___D DDYX-Tnnnnn (X=S, P, or A n=0-9) TRF originator: FIMKO <12002388 001> Page 32 IEC 950 Clause Requirement − Test Result – Remark Verdict Teac Corporation CD-2XXXX (X is alphanumeric characters or blank) 5V, 1.5A Laser Class 1 IEC 60950 IEC 60825-1 TUV, UL Lite-On LTN5V, 1A XX5XXXXX Laser Class 1 (X=A-Z, 0-9 or blank) IEC 60950 IEC 60825-1 TUV, UL Asustek Computer Inc. CD-SXX/A 5V/ 1.2A (X=A-Z or 0-9) 12V/1.5A Laser Class 1 IEC 60950 IEC 60825-1 TUV, UL Asustek Computer Inc. CD-SXXXX 5V/ 1.2A (X=A-Z or 0-9) 12V/1.5A Laser Class 1 IEC 60950 IEC 60825-1 TUV, UL Asustek Computer Inc. CD-SXXX/A 5V/ 1.2A (X=A-Z or 0-9) 12V/1.5A Laser Class 1 IEC 60950 IEC 60825-1 TUV, UL FDD ( Optional ) Sony corp. MPF720-xxx MFD720-xxx IEC 60 950 TUV, UL CD- RW Driver (Optional) Asustek Computer Inc. CRW-XXXXX 5V, 1.5A (X=A-Z or 0-9) Laser Class 1 IEC 60950 IEC 60825-1 TUV, UL DVD- ROM (Optional) Asustek Computer Inc. DVD-EXXXX 5V/ 0.9A (X=A-Z or 0-9) 12V/1.5A Laser Class 1 IEC 60950 IEC 60825-1 TUV, UL System DC FAN Delta EFC0412BD 12V, 0.24A 10.10 CFM -- UL CPU DC FAN Delta Electronics Inc. AFC0612BC 12V, 0.3A, 27.72 -CFM UL RTC Battery Sony CR2032 3V, 220mAh, Lithium type -- UL Matsushita battery Industrial CR2032 3V, 210mAh, Lithium type -- UL Matsushita electric Industry CR2032 3V, 220mAh, Lithium type -- UL Toshiba Battery Co., Ltd CR2032 3V, 220mAh, Lithium type -- UL TRF No.: I950___D 5V, 730mA TRF originator: FIMKO <12002388 001> Page 33 IEC 950 Clause Requirement − Test Hitachi Maxell Result – Remark CR2032 3V, 210mAh, Lithium type Verdict -- UL 1 ) an asterisk indicates a mark which assures the agreed level of surveillance 1.6 TABLE: electrical data P fuse # Irated (A) U (V) P (W) I (A) Ifuse (A) Fuse -- 90V/50Hz 114 1.29 1.29 Unit at max. normal load Fuse -- 90V/60Hz 114 1.28 1.28 dto Fuse 3 100V/50Hz 114 1.16 1.16 dto Fuse 3 100V/60Hz 114 1.15 1.15 dto Fuse 3 240V/50Hz 112 0.53 0.53 dto Fuse 3 240V/60Hz 112 0.55 0.55 dto Fuse -- 254V/50Hz 112 0.52 0.52 dto Fuse -- 254V/60Hz 113 0.53 0.53 dto 2.5.11 condition/status TABLE: ground continue test Location P Resistant measured (Ω) Comments Inlet ground pin to metal enclosure 0.029 25A Test Current, 1 min Inlet ground pin to metal enclosure 0.030 30A Test Current, 2 min 2.9.2 and 2.9.3 TABLE: clearance and creepage distance measurements clearance cl and creepage distance dcr at/of: TRF No.: I950___D Up (V) U r.m.s. (V) required cl (mm) N cl (mm) required dcr (mm) dcr (mm) TRF originator: FIMKO <12002388 001> Page 34 IEC 950 Clause Requirement − Test 2.9.4.1 TABLE: distance through insulation measurements Result – Remark distance through insulation di at/of: U r.m.s. (V) 4.3.15/16 & 4.4.6 Verdict N test voltage (V) required di (mm) Table: enclosure openings Location di (mm) P Size (mm) Comments Top Ø 1.75mm Round, cover an area 285mm x 20mm. Side Ø 4.95mm Round, cover an area 87.3mm x 50mm. 5.1 TABLE: temperature rise measurements P test voltage (V) .......................................... a) 100-10% b) 240+6% t1 (°C) ...................................................... t2 (°C) ...................................................... temperature rise dT of part/at: Test Voltage dT (K) required dT (K) a) b) -- T1 coil 29.5 29.3 55 T1 core 27.4 27.3 55 T2 coil 18.5 18.3 55 T2 core 14.3 14.0 55 PFC1 coil 30.5 24.2 70 PFC1 core 25.6 18.6 70 L1 coil 26.8 26.5 70 LF2 coil 31.5 28.2 70 LF coil 30.2 28.1 70 TRF No.: I950___D TRF originator: FIMKO <12002388 001> Page 35 IEC 950 Clause Requirement − Test Result – Remark Verdict C11 body 21.3 19.9 50 Heatsink of CPU 16.8 16.3 -- RTC battery body 26.5 26.2 -- HDD body 8.0 8.8 -- FDD body 11.4 11.4 -- CD-ROM body 9.2 9.5 -- Enclosure inside near heatsink (top) 9.5 9.3 -- 13.2 12.7 -- Enclosure outside near heatsink (top) 8.0 7.9 35 Enclosure outside near SPS (top) 9.5 9.2 35 23.6ºC 23.7ºC -- Enclosure inside near SPS (top) Ambient temperature rise dT of winding: R1 (Ω) R2 (Ω) dT (K) required dT (K) Insulation class Comments: The temperatures were measured by thermal couple method under worst case normal load as described in 1.6.1 at voltages described in 1.6.5. With a specified ambient temperature of 35°C, the max. temperature rise is calculated as follows: Winding components or components: - class A → dTmax = 75K - 10K - (35-25)K = 55K Electrolyte capacitor or components with: - max. absolute temp. of 85°C → dTmax = (85-35) K = 50K - max. absolute temp. of 105°C → dTmax = (105-35) K = 70K Touchable enclosure (Metal) surface with: - max. temp. rise 45K→ dTmax = 45K-(35-25) K = 35K 5.2 TABLE: leakage current measurement P Condition current L→PE (mA) System on 0.46 0.44 System off 0.46 0.46 TRF No.: I950___D current N→PE (mA) comments TRF originator: FIMKO <12002388 001> Page 36 IEC 950 Clause Requirement − Test Input voltage Input frequency Overall capacity 5.3 : : : Result – Remark Verdict 254V 63Hz In approved SPS TABLE: electric strength measurements P test voltage applied between: test voltage (V) breakdown Primary to Secondary DC 4242 No Primary to Ground DC 2677 No 5.4 TABLE: fault condition tests P ambient temperature (°C) .............................. : 25°C model/type of power supply .......................... : ATP-165AAP manufacturer of power supply ....................... : Asustek rated markings of power supply ..................... : See table 1.5.1 No. component No. 1 Ventilation openings blocked 240 3.3 hr -- -- Max. temp. are recorded for SPS: T1 coil = 94.4ºC, T1 core = 91.0ºC, T2 coil = 82.4ºC, T2 core = 74.4ºC, L1 coil = 89.3ºC, LF2 coil = 93.3ºC, LF coil = 88.2ºC, ambient = 21.7ºC, no hazards 2 DC Fan locked 240 1.7 hr -- -- Max. temp. are recorded for SPS: T1 coil = 59ºC, T1 core = 57ºC, T2 coil = 57ºC, T2 core = 54ºC, L1 coil = 65ºC, LF2 coil = 51ºC, LF coil = 54ºC, ambient = 23.8ºC, no hazards (for CPU) TRF No.: I950___D fault test voltage (V) test time fuse No. fuse current (A) result TRF originator: FIMKO <12002388 001> Page 37 IEC 950 Clause 3 Requirement − Test DC Fan Result – Remark -- DC Fan 240 2.3 hr -- locked 240 2.2 hr -- -- Max. temp. are recorded for SPS: T1 coil = 64.2ºC, T1 core = 61.5ºC, T2 coil = 50.6ºC, T2 core = 44.8ºC, L1 coil = 60.1ºC, LF2 coil = 66.5ºC, LF coil = 63.3ºC, ambient = 23.6ºC, no hazards locked 240 2 hr -- -- Max. temp. are recorded for SPS: T1 coil = 58.7ºC, T1 core = 55.9ºC, T2 coil = 43.2ºC, T2 core = 37.9ºC, L1 coil = 57.4ºC, LF2 coil = 53.3ºC, LF coil = 58.9ºC, ambient = 23.7ºC, no hazards (for SPS, inside) 5 DC Fan Max. temp. are recorded for SPS: T1 coil = 56.0ºC, T1 core = 53.5ºC, T2 coil = 45.3ºC, T2 core = 41.3ºC, L1 coil = 53.4ºC, LF2 coil = 54.7ºC, LF coil = 54.8ºC, ambient = 23.8ºC, no hazards locked (for system) 4 Verdict (for SPS, outside) Lock rotor test 6 DC Fan, model EFC0412BD locked 12VDC 7 hr -- -- The max. temp. of coil=60.5°C at ambient = 22.7°C, no hazards 7 DC Fan, model AFC0612BC locked 12VDC 7 hr -- -- The max. temp. of coil=52.2°C at ambient = 22.6°C, no hazards 5.4.10 TABLE: ball pressure test of thermoplastics N required impression diameter (mm) ................. : ≤ 2 mm part TRF No.: I950___D test temperature (°C) impression diameter (mm) TRF originator: FIMKO <12002388 001> Page 38 National Deviation Clause Requirement − Test Result – Remark APPENDIX EN 60950:1992+A1:1993:+A2:1993 + A3:1995 + A4:1997 + A11:1997 TEST REPORT Verdict P (IEC Publication 60950 2nd edition, 1991+Amd.1,1992+Amd.2, 1993 + Amd.3, 1995 + Amd.4, 1996) CENELEC common modification, Special National condition, Nation deviation and other information according to CB Bulletin No. 101A, December 2001 EXPLANATION FOR ABBREVIATIONS C=CENELEC common modification, S=Special National condition, D=National deviation, F=Other information, AT=Austria, GB=Great Britain, CH=Switzerland, DE=Germany, DK=Denmark, FI=Finland, FR=France, NO=Norway, SE=Sweden. P=Pass, F=Fail, N=Not applicable. place in the column to the right. 1.2.4.1 S (DK). Certain types of Class I appliances (see subclause 3.2.1) may be provided with a plug not establishing earthing continuity when inserted into Danish socket-outlets. No power cord provided. N 1.5.1 D (SE). Add the following: No such switch. N Considered, see report IEC 60950. P NOTE: Switches containing mercury such as thermostats, relay and level controllers are not allowed. 1.6.4 S (NO). Note 2: In Norway, due to the IT power system used, capacitors are required to be rated for the applicable phase-to-phase voltage (230V) 1.7.2 S (NO). Note 4: In Norway, if separation between the Required texts will be printed mains and a communication system/network, other on label and affix to unit than public telecommunication networks, relies upon when national approved. connection to safety earth, the equipment shall have a marking stating that is must be connected to an earthed mains socket-outlet. N NOTE: For requirements to be connected to a public telecommunication network, see 6.2.1.4. 1.7.2 S (SE). If the separation between the mains and a SELV terminal relies upon connection to the safety earth, the apparatus shall have a marking stating that it must be connected to an earthed mains socket-outlet when a SELV circuit is connected to network passing both unearthed and earthed electrical environment. The marking text shall be in Swedish and as follows: “Apparaten skall anslutas till jordat uttag när den ansluts till ett nätverk”. Required texts will be printed on label and affix to unit when national approved. N CENELEC common modification, Special National condition, Nation deviation and other information according to CB Bulletin No. 101A, December 2001 Page 39 <12002388 001> National Deviation Clause Requirement − Test Result – Remark 1.7.2 D (DK). Supply cords of Class I appliances, which are delivered without a plug, must be provided with a visible tag with the following text: “Vigtigt. Lederen med grøn/gul isolation mä Kun tilsluttes en klemme No power cord provided. N Verdict mærket eller ”. If essential for the safety of the appliance, the tag must in addition be provided with a diagram, which shows the connection of the other conductors, or be provided with the following text: “For tilslutning af de øvrige ledere, se medfølgende installationsvejledning”. 1.7.2 C Delete note 4. Deleted N 1.7.5 S (DK). Socket-outlets for providing power to other equipment shall be in accordance with the Heavy Current Regulations, Section 107-2-D1, Standard Sheet DK 1-3a, DK 1-5a or DK 1-7a when used on Class I equipment. No socket outlet. N 1.7.5 D (DK). Class II appliances shall not be fitted with socket-outlets for providing power to other appliances. Class I equipment. N 1.7.14 D (DE). Directions for use with rules to prevent certain Not a technical labor hazards for (among others) maintenance of the equipment. technical labor equipment, also for imported technical labor equipment shall be written in German language. NOTE: Of this requirement, rules for use even only by service personnel are not exempted. 1.7.17 D (CH). (Ordinance on environmentally hazardous substances SR 814.013) Annex 4.10 of SR 814.013 applies for batteries. To be evaluated when national approval. P 2.3.3 C Delete Method 4 and the line in note 1 relating to this method Deleted. N 2.3.6 C Delete the note. Deleted. N 2.3.5 S (NO). In Norway, marking and insulation requirements according to subclause 1.7.2, Note 4, and 6.2.1.4, Note 2, apply. No marking required. N 2.3.6 S (FR). Method 3 is not acceptable. Method 3 is not used. P 2.3.7 C Replace the text of this sub-clause by: Void. Replaced. N 2.3.9 S (NO). Marking and insulation requirements according No marking required. to this annex, subclauses 1.7.02 and 6.2.01.4 b) apply. 2.5.2 S (DK, NO) Add after the first paragraph: “The above exception is not acceptable in pluggable equipment type A “ Added, no exception applied. N 2.5.2 C Delete the note. Deleted. N N N CENELEC common modification, Special National condition, Nation deviation and other information according to CB Bulletin No. 101A, December 2001 <12002388 001> Page 40 National Deviation Clause Requirement − Test Result – Remark 2.7.1 C Replace the text of this sub-clause by: Basic requirements Replaced. P Verdict To protect against excess current, short-circuits and earth faults in primary circuits, protective devices shall be included ether as integral parts of the equipment or as a part of the building installation, subject to all of the following a), b), c) and d): (a) Except as detailed in (b) and (c), protective devices necessary to comply with the requirements of Sub-clause 5.4 shall be included as integral parts of the equipment. (b) For components in series with the mains input to the equipment such as the supply cord, appliance coupler, RFI filter and switch, short circuit and earth fault protection may be provided with protective devices in the installation. (c) It is permitted for equipment with rated current exceeding 16A, which is pluggable equipment type B or permanently connected equipment, to rely on dedicated overcurrent and short circuit protection in the building installation, provided that the means of protection, e.g. fuses or circuit breaker, is fully specified in the installation instruction (d) If reliance is placed on protection in the building installation, the installation instructions shall comply with Sub-clause 1.7.11 except that for pluggable equipment Type A the building installation shall be regarded as providing protection in accordance with the rating of the wall socket outlet and 1.7.11 does not apply. 2.7.2 C Replace the text of this sub-clause by: Void. Replaced. N 2.8.4 C Delete the note. Deleted. N 2.9.1 S (NO). Note 3: In Norway, due to the IT power systems used, the mains supply voltage is considered to be equal to the phase-to-phase voltage. Mains voltage as reference voltage. P 2.9.4.2 C Amend the last line on page 117a as follows – Amended. N Solvent-based enamel coating on winding wire is not considered to be insulation in thin sheet material. Add a new sentence below the text on page 117a as follows – Requirements for wound components are given in 2.9.4.4. CENELEC common modification, Special National condition, Nation deviation and other information according to CB Bulletin No. 101A, December 2001 <12002388 001> Page 41 National Deviation Clause Requirement − Test 2.9.4.4 C Modify the title as follows – Result – Remark Verdict N 2.9.4.4 Wound components Replace the first paragraph and the two dashed paragraphs as follows – Unless one of the following situations applies, interleaved BASIC, SUPPLEMENTARY or REINFORCED INSULATION complying with 2.9.4.1 or 2.9.4.2 shall be provided between the windings. - the insulation on the winding wire complies with 2.9.4.1; or - the winding wire complies with annex U; or - the insulation between the windings is provided for separation between ZNV circuits and other parts in compliance with 6.4.1. Note – Examples of insulation of winding wire complying with annex U are polyamide and FEP. 2.11 C Delete notes 1, 2 and 3. 3.2.1 S (DK). Supply cords of single phase appliances No power cord provided. having a rated current not exceeding 10A shall be provided with a plug according to the Heavy Current Regulations Section 107-2-D1. Deleted. N N Class I equipment provided with socket-outlets with earth contacts or which are intended to be used in locations where protection against indirect contact is required according to the wiring rules shall be provided with a plug in accordance with standard sheet DK 2-1a or DK 2-5a. If poly-phase equipment and single-phase equipment having a rated current exceeding 10A is provided with a supply cord with a plug, this plug shall be in accordance with the Heavy Current Regulations Section 107-1-D1 or EN 60309-2. 3.2.1 S (CH). Supply cords of equipment having a rated current not exceeding 10A shall be provided with a plug complying with SEV 1011 or IEC 60884-1 and one of the following dimension sheets No power cord provided. N SEV 6532-2,1991 Plug type 15 3P+N+PE 250/400V, 10A SEV 6533-2,1991 Plug type 11 L+N 250V, 10A SEV 6534-2,1991 Plug type 12 L+N+PE 250V, 10A EN 60 309 applies for plugs for currents exceeding 10A CENELEC common modification, Special National condition, Nation deviation and other information according to CB Bulletin No. 101A, December 2001 <12002388 001> Page 42 National Deviation Clause Requirement − Test 3.2.1 S (GB). Apparatus which is fitted with a flexible cable No power cord provided. or cord and is designed to be connected to a mains socket conforming to BS1363 by means of that flexible cable or cord and plug, shall be fitted with a “standard plug” in accordance with Statutory Instrument 1768:1994 - The Plugs and Sockets etc. (Safety) Regulations 1994, unless exempted by those regulations. Result – Remark Verdict N Note: “standard plug” is defined in SI 1768:1994 and essentially means an approved plug conforming to BS 1363 or an approved conversion plug. 3.2.2 C Delete the note and in table 10, delete the values in parentheses. Deleted. N 3.2.4 S (GB). A power supply cord with conductor of 1.25mm² is allowed for equipment with rated current over 10A and up to and including 13A. No power cord provided. N 3.2.4 C Replace Replaced. N In table 13, replace the fourth and the fifth lines by: Replaced. N "60245 IEC 53" by "H05 RR-F", "60227 IEC 52" by "H03 VV-F or H03 VVH2-F" and "60227 IEC 53" by "H05 VV-F or H05 VVH2-F". In table 11, replace the first four lines by the following: Up to and including 6 0.75 1) Over 6 up to and including 10 1.0 (0.75)2) Over 10 up to and including 16 1.5 (1.0)3) In the conditions applicable to table 11, delete the words "in some countries" in condition 1). In the Note delete the second sentence. 3.3.5 C Over 10 up to and including 16 1.5 to 2.5 1.5 to by 4 3.3.5 S (GB). The range of conductor sizes of flexible cords No power cord provided. to be accepted by terminals for equipment with a rated current of over 10A and up to and including 13A is: 1.25mm² to 1.5mm² nominal cross-sectional area. N 4.3.18 S (GB). This test should be performed using an appropriate socket-outlet with an earthing contact. No direct plug-in equipment. N 4.4.4 C Delete note 2. Deleted. N 5.4.9 S (NO). Note: In Norway, the electric strength test includes testing of basic insulation in Class I pluggable equipment type B and permanently connected equipment. Considered. P 6.1 S (CH).Protective means in the equipment shall not prevent transient surge protection in the telecommunication network from operating properly (d.c. spark-over voltage of the surge suppressor installed in the telecommunication network: approx. 245V). No TNV. N CENELEC common modification, Special National condition, Nation deviation and other information according to CB Bulletin No. 101A, December 2001 <12002388 001> Page 43 National Deviation Clause Requirement − Test Result – Remark 6.2.1.2 C Add at the end of the sub-clause: This sub-clause only applies to TNV circuits normally operating in excess of the limits of SELV circuits. No TNV. N (SE). Supplementary insulation for a primary circuit is required between any TNV circuit and any circuit that has a connection to a protective earthing terminal. No TNV. N (NO). In Norway, supplementary insulation for a No TNV. primary circuits is required between any TNV circuit and any circuit that has a connection to a protective earthing terminal. N 6.2.1.3C 6.2.1.2 S Verdict In Sweden, this requirement does not apply to permanently connected equipment or pluggable equipment Type B. 6.2.1.2 S This requirement does not apply to permanently connected equipment or to pluggable equipment type B, installed in areas where equipotential bonding has been applied, e.g. a telecommunication Central Office. 6.2.1.4 C Delete the notes. Deleted. N 6.2.1.4 S (NO). Note 2: In Norway, method b) is not permitted. Insulation between parts conductively connected to the supply mains and parts connected to a public telecommunication network shall comply with the requirements for double or reinforced insulation. No TNV. N 6.2.1.4b) S (FI). Method b) is permitted only for permanently connected equipment or for pluggable equipment Type B. No TNV. N 6.2.1.5 S (NO). Note 2: In Norway, requirements according to 6.2.1.4, Note 2, apply No TNV. N 6.3.3. S (NO). In Norway, 6.3.3 is applicable for pluggable equipment type A and B and for permanently connected equipment. No TNV. N 6.3.3.1 S (SE). In Sweden, requirements according to this annex ZB, subclause 6.2.1.2 apply. No TNV. N 6.3.3.1 S (NO). In Norway, requirements according to subclause 6.2.1.2, national difference, 6.2.1.4, Note 2, and 6.3.3.2, Note 1, applied. No TNV. N 6.3.3.2 S (NO). Note 1: In Norway, exclusions are applicable No TNV. for permanently connected equipment and pluggable equipment Type B only. N 6.4.1 C Delete note 2. Deleted. N 6.4.2.1 C Delete note 2. Deleted. N 6.4.2.1 D (AT). Equipment shall comply with Uc = 2.0kV in cases b) and c). No TNV. N CENELEC common modification, Special National condition, Nation deviation and other information according to CB Bulletin No. 101A, December 2001 Page 44 <12002388 001> National Deviation Clause Requirement − Test Result – Remark Annex H. D (DE) No CRT. N Replaced. N Verdict a) A license is required by those who operate an Xray emission source. b) A license in accordance with clause 1 is not required by those who operate an X-ray emission source on which the electron acceleration voltage does not exceed 20 kV, if 1) the local dose rate at a distance of 0.1m from the surface does not exceed 1µSv/h and 2) it is adequately indicated on the X-ray emission source that i) X-rays are generated and ii) the electron acceleration voltage must not exceed the maximum value stipulated by the manufacturer or importer. c) A license in accordance with clause 1 is also not required by persons who operate an X-ray emission source on which the electron acceleration voltage exceeds 20 kV, if 1) the X-ray emission source has been granted a type approval and 2) it is adequately indicated on the X-ray emission source that i) X-ray are generated, ii) the device stipulated by the manufacturer or importer guarantees that the maximum permissible local does rate in accordance with the type approval is not exceeded and iii) the electron acceleration voltage must not exceed the maximum value stipulated by the manufacturer or importer. d) Furthermore, a license in accordance with clause 1 is also not required by persons who operate X-ray emission sources on which the electron acceleration voltage does not exceed 30 kV, if 1) the X-rays are generated only by intrinsically safety CRTs complying with Enclosure III, No.6, 2) the values stipulated in accordance with Enclosure III, bi, 6.2 are limited by technical measures and specified in the device and 3) it is adequately indicated on the X-ray emission source that the X-rays generated are adequately screened by the intrinsically safe CRT. Annex P C Replace the text of this annex by: See annex ZA. CENELEC common modification, Special National condition, Nation deviation and other information according to CB Bulletin No. 101A, December 2001 <12002388 001> Page 45 National Deviation Clause Requirement − Test Annex Q C Add for IEC 60529: Result – Remark Added. Verdict N Note: Endorsed by EN 60529:1991 (not modified) Add for IEC 60707 Note: Endorsed by HD441:1983 (not modified) Add for IEC 61058-1: Note: Endorsed by EN 61058:1992 (not modified). CENELEC common modification, Special National condition, Nation deviation and other information according to CB Bulletin No. 101A, December 2001 Page 46 <12002388 001> National Deviation Clause Requirement − Test Result – Remark APPENDIX EMKO-TSE(74-SEC)207/94 TO Verdict P EN 60950:1992+A1:1993+A2:1993+A3:1995+A4:1997+A11:1997 TEST REPORT (IEC Publication 60950 2nd edition, 1991 + Amd.1, 1992 + Amd.2, 1993 + Amd.3, 1995 + Amd.4, 1996) Nordic Explanations, and other information not covered by Appendix EN 60950:1992, + A1:1993 + A2:1993 + A3:1995 + A4:1997+A11:1997. EXPLANATION FOR ABBREVIATIONS NF=Nordic Explanations and other information. DK=Denmark, FI=Finland, NO=Norway, SE=Sweden. P=Pass, F=Fail, N=Not applicable. Placed in the column to the right. 1.2.02.01 (DK,FI,NO,SE). The heating test of separate power supplies of personal computers is carried out NF No separate power supply of personal computer. N 1.5.01 NF (DK,FI,NO,SE). The following capacitors are In approved SPS. P No transient protection components connected to safety earthed parts. P No outlet. N Included in the voltage range. P according to their rated output values marked on the power supplies. accepted across the mains: 1) X1 capacitor which complies with Publication IEC 60 384-14. 2) X2 capacitor which complies with Publication IEC 60 384-14 and which has been subjected to a pulse test according to § 12.11.2, except the value of the voltage is reduced to 2.5 kV. 3) X2 capacitor which complies with Publication IEC 60 384-14 in case the endurance test of § 12.11.2 has been modified so that the resistor of 220Ω through which the voltage of 1000 V rms is applied to the capacitor under test, is short circuited. 4) Capacitor which complies with Publication 195 S6, § 14.2. HD 1.5.02 NF (DK,FI,NO,SE). Transient protection components shall be installed in such a way that insulation for protection against electric shock will not be bridge. This means that transient protection components must not be connected to safety earthed parts in pluggable equipment or to other accessible parts. -3.2.3 (DK,FI,NO,SE). Interconnection couplers in accordance with EN 60 320-2-2 are accepted. Outlets of non-standard types are not accepted. 1.7.01 NF -1st dash (DK). When supplied in Denmark the appliances shall be set to 230 V . -5th dash (DK). The equipment may instead be Refer to CB report page 4. provided with a marking indicating name, trade-mark or identify of the responsible vendor. NORDIC Deviation EMKO-TSE(74-SEC)207/94 P Page 47 <12002388 001> National Deviation Clause Requirement − Test 2.1.04 NF (DK,FI,NO,SE). For monitors, warning label is not required for repairing area, neither the partial shielding against contact although the voltage is> 42.4 V peak or > 60 V d.c. Result – Remark No monitor. Verdict N 2.5.11 NF (DK,FI,NO,SE). Due to installation fuses of 16A, the Earthing test conducted at earth resistance shall always be controlled at 25 A. 25A, see IEC 60950 report. P 2.6.06 NF (DK,FI,NO,SE). The plug is regarded to be a Appliance inlet is considered as disconnect device. N 2.6.11 NF (DK,FI,NO). The warning label on an appliance with Only one supply from the mains. N disconnect device and therefore a single pole mains switch is acceptable (TC 74-WG 8's recommendation). two or several supply connections shall be in the official language of the country in question. (DK,FI,NO). UPS-appliances can be fitted with a Equipment is not a UPS. signal lamp instead of a warning label, under the condition that the function and location of the signal lamp is correct. Audible signal is not acceptable as warning. N 2.7.03 NF (DK,FI,NO,SE). A single-pole protective device is Only one fuse on live phase. P 2.9.01 NF (DK,FI,NO,SE). Pollution Degree 3 is considered Equipment is not a shredding machine N 4.2.07 NF (DK,FI,NO,SE). If there are visible cracks on the Metal enclosure. N 4.4.04 NF (DK,FI). Fire enclosure is required if the available Supplied from the mains. N dto. N acceptable. applicable for the following equipment which is within the scope of this standard: Document Shredder Machines. apparatus after the mechanical strength test, the apparatus is not rejected, if it still complies with the other requirements of subclause 4.2.7. power exceeds the values of a limited power source. The limited power source shall incorporate an isolating transformer and shall comply with the following: * The open-circuit voltage shall not exceed 42.4 V peak or d.c. and shall not generate voltages above the value and * The current which may be drawn for more than two minutes at any load, including short-circuit, shall not exceed 0.2 A. (NO). A fire enclosure is not required in spots of the equipment where the available power does not exceeded 50 VA and the available voltage 42.4 V (peak) or 60 V d.c. NORDIC Deviation EMKO-TSE(74-SEC)207/94 Page 48 <12002388 001> National Deviation Clause Requirement − Test 5.4.06 NF (DK,FI,NO,SE). Faults need not to be carried out in circuits which are supplied by an isolating transformer and which comply with the following: * The open-circuit voltage shall not exceed 42.4 V peak or d.c. and shall not generate voltages above the value and * The current which may be drawn for more than two minutes at any load, including short-circuit, shall not exceed 0.2 A. NORDIC Deviation EMKO-TSE(74-SEC)207/94 Result – Remark Supplied from the mains. Verdict N <12002388 001> Page 49 National Deviation Clause Requirement − Test Result – Remark APPENDIX China National Differences according to CB Bulletin, No. 101A, December 2001 Verdict P REPORT (IEC Publication 60950 2nd edition, 1991 + Amd.1, 1992 + Amd.2, 1993 + Amd.3, 1995 + Amd.4, 1996) EXPLANATION FOR ABBREVIATIONS P=Pass, F=Fail, N=Not applicable. Placed in the column to the right. 1.4.5, 1.6.5 The minimum supply tolerance is –10%, +6%; GB4943 sub-clause 1.4.5 and 1.6.5: The minimum supply tolerance is –10%, +10% according to Chinese situation. General IEC standard for plug is IEC 60083. The Chinese National standard for Plugs is GB1002-1996, which is not equivalent with IEC60083. N No power supply cord provided. China National Differences according to CB Bulletin, No. 101A, December 2001 N <12002388 001> Page 50 National Deviation Clause Requirement − Test Result – Remark APPENDIX Japanese National Differences according to CB Bulletin No. 101A, December 2001 Verdict P REPORT (IEC Publication 60950 : 1991 + A1 + A2 + A3 + A4) EXPLANATION FOR ABBREVIATIONS P=Pass, F=Fail, N=Not applicable. Placed in the column to the right. 2.9.2.1 Delete entire column headed by [Nominal mains supply voltage ≤150V (Transient rating 1500V)] in Table 3. Clearance distance from column 2 taken (≤300V) P Delete >150V from column headed by “Nominal mains supply voltage >150V, ≤300V (Transient rating 2500V)” in Table 3. 2.9.2.2 Delete entire column headed by “Nominal mains supply voltage ≤150V (Maximum transient in secondary circuit 800V see condition 6)” in Table 5 Clearance distance from column 2 taken (≤300V) P 2.9.4.4 Replacement: The following shall replace the entire existing paragraphs: Different Japanese standard text considered. N Title: Wounded components BASIC, SUPPLEMENTARY, DOUBLE or REINFORCED INSULATION is permitted in a wounded component using one of the following a), b), or c) constructions or the wounded component must use interleaved insulation which complies with 2.9.4.1 or 2.9.4.2: a) the winding wire is insulated with insulation complying with 2.9.4.1 other than solution based type enamel coatings. b) the winding wire is insulated with extruded multi-layers or wrapped layers of tape (each layer can be tested for electric strength) which complies with 2.9.4.1 and complies with annex U. c) the winding wire is insulated with extruded multi-layers or wrapped layers of tape (test can be only performed on finished winding wire) and complies with annex U. Japanese national Differences according to CB Bulletin No. 101A, December 2001 <12002388 001> Page 51 National Deviation Clause Requirement − Test Result – Remark Verdict Note 1 – see also 6.4.1. As to c), the number of constructional layers applied to the conductor to determine the grade of insulation of the winding wire shall not be less than as follows: - if BASIC INSULATION is required, a minimum of two layers or one extruded layer - if SUPPLEMENTARY INSULATION is required, a minimum of two layers or two extruded layers - if REINFORCED INSULATION is required, a minimum of three layers or three extruded layers As to b) and c), in case the CREEPAGE DISTANCES between wrapped layers of tape are less than Table 6 under Pollution degree 1, the distance between layers must be reliably cement together with insulation compound complying with 2.9.7 and with the test voltage in annex U.2 (Type tests) increased to 1.6 times. Note 2 – In case one layer of material is wrapped 50% or more, it is considered as two layers Where two insulated wires or one bare wire and one insulated wire are contacted inside the component and cross each other at an angle between 45° and 90°, physical separation shall be provided, for example in the form of insulating sleeving or sheet material, or by applying two times of the specified insulating layer(s), to relieve mechanical stress at the crossover point. The finished component shall pass ROUTINE TESTING for electric strength using the value of test voltage in 5.3. Compliance is checked by visual inspection and measurement, and as specified in annex U. However, the tests are not repeated if the material data sheets confirm compliance with annex U. 5.1 Addition: Add the following to 5) as specified in “Conditions applicable to table 16, parts 1 and 2” For other than those complied with IEC standards, refer to added condition 8) below. With regards to 1), insulating materials complying with Japanese requirement (Refer to Japanese difference for current IEC 60335-1 (3rd Edition) in CB Bulletin 94B), can be taken of data for that material to determine the appropriate maximum temperature rise. Japanese national Differences according to CB Bulletin No. 101A, December 2001 P Page 52 <12002388 001> National Deviation Clause Requirement − Test Result – Remark Annex U Replacement: Replaced Verdict N ANNEX U (normative) Insulated winding wires for use without interleaved insulation (see 2.9.4.4) This annex specifies winding wire whose insulation may be used to provide BASIC, SUPPLEMENTARY or REINFORCED INSULATION in wound components without interleaved insulation. This annex applies to round winding wire whose diameter is between 0.2mm and 1.00mm. With regard to other size, refer to IEC 60851. U.1 Wire construction N If the wire is insulated with two or more spirally wrapped layers of tape, the overlap of layers shall be adequate to ensure continued overlap during manufacture of the wound component. In order to maintain the overlap of layers, wire insulation layer of wrapped layers of tape must be adequately secured. U.2 Type tests N Unless it specifies, the wire shall pass the following six TYPE TESTS U.2.1 to U.2.4, carried out at a temperature between 15°C and 35°C and a relative humidity between 45% and 75%. Refer to the IEC 60851 first edition. U.2.1 Electric strength Test 13 of IEC 60851-5 (1988), 4.3.1 (test for twisted wire pairs), with a test voltage 2 times of appropriate voltage in Table 18 of this standard or 6kVr.m.s. whichever is the greater. Japanese national Differences according to CB Bulletin No. 101A, December 2001 N Page 53 <12002388 001> National Deviation Clause Requirement − Test U.2.2 Result – Remark Verdict N Adherence and flexibility Test 8 of IEC 60851-3, with a test voltage not less than the appropriate voltage in Table 18 of this standard or 3kVr.m.s. whichever is the greater. Table U.2.2.2 – Mandrel Nominal diameter of conductor (mm) 0.20 – 0.34 0.35 – 0.49 0.50 – 0.74 0.75 – 1.00 Mandrel diameter (mm±0.2mm) 4.0 6.0 8.0 10.0 The tension of winding wire while wire is wrapped around the mandrel, should be calculated so that it is equivalent to 118MPa±10% (118N/mm²±10%) from winding wire radial. U.2.3 N Heat shock Test 9 of IEC 60851-6, 3.1 and IEC 60851-3, 5.1.1.1, with a test voltage not less than the appropriate voltage in Table 18 of this standard or 3kVr.m.s. whichever is the greater. The temperature of oven is specified in the following Table U.2.3. Table U.2.2 shows and explains required mandrel diameter and tension. Test must be performed at room ambient after taking out from oven. Table U.2.3 – Oven Temperature Class Oven Temp. A (105) 200 E (120) 215 B (130) 225 F (155) 240 H (180) 260 (°C±2°C) U.2.4 Retention of electric strength after bending N Test 13 of IEC 60851-5 (1988), 4.6.1 c, with a test voltage not less than the appropriate voltage in Table 18 of this standard or 3kVr.m.s. whichever is the greater. Table U.2.2 shows and explains required mandrel diameter and tension. U.3 Routine test Winding wire is subjected to electric strength test during the production in accordance with U.3.1 and U.3.2 by wire manufacturer. Japanese national Differences according to CB Bulletin No. 101A, December 2001 N Page 54 <12002388 001> National Deviation Clause Requirement − Test U.3.1 Result – Remark Full-length test Verdict N Winding wire is subjected to electric strength test during the production for full wire length, with a test voltage not less than the appropriate voltage in Table 18 of this standard or 3kVr.m.s. or 4.2kV peak minimum. U.3.2 Audit test Test must be carried out according to IEC 60851-5 (1988) for twisted wire pairs. Electric strength test, with a test voltage 2 times of appropriate voltage in Table 18 of this standard or 6kVr.m.s. or 8.4kV peak minimum. Japanese national Differences according to CB Bulletin No. 101A, December 2001 N Page 55 <12002388 001> National Deviation Clause Requirement − Test Result – Remark APPENDIX Korean National Differences according to CB Bulletin, No. 101A, December 2001 Verdict P REPORT (IEC Publication 60950 2nd edition, 1991 + Amd.1, 1992 + Amd.2, 1993 + Amd.3, 1995 + Amd.4, 1996) EXPLANATION FOR ABBREVIATIONS P=Pass, F=Fail, N=Not applicable. Placed in the column to the right. General LIMITATIONS - Voltage ratings As national supply voltage is subject to be increased to 220V, an appliance rated 220V is to be allowed to obtain type approval in Korea. Either an appliance rated 110V or 220/110V is not allowed. When an appliance is supplied in Korea, it shall be set to and marked with 220V. Rated 100-240Vac and auto voltage select design. P Frequencies of 47-63Hz. P Instruction manual will be in Korean. N But free voltage appliance by SMPS (Switching Mode Power Supply) is allowed and it shall be marked with “100-220V”. General LIMITATIONS – Frequency Only appliances having supply frequency of 60Hz or a frequency range including 60Hz are accepted. When an appliance is supplied in Korea, it shall be set to and marked with 60Hz. General LIMITATIONS - Instruction Instruction manuals and appliance markings related to safety, including nameplate shall be in Korean or graphical symbols in IEC Publication 60417. 1.5.101 Addition: Plugs for the connection of the apparatus to the supply mains shall comply with the Korean requirements (KSC 8305). No power cord provided. N 7 Addition: The CISPR requirements have to be evaluated when submitted for national approval. N Radio frequency interference The apparatus shall comply with the relevant CISPR requirements. Korean National Differences according to CB Bulletin, No. 101A, December 2001 Page 56 <12002388 001> National Deviation Clause Requirement − Test Result – Remark APPENDIX Israel National Differences according to CB Bulletin, No. 101A, December 2001 Verdict P REPORT (IEC Publication 60950 2nd edition, 1991 + Amd.1, 1992 + Amd.2, 1993 + Amd.3, 1995 + Amd.4, 1996) EXPLANATION FOR ABBREVIATIONS P=Pass, F=Fail, N=Not applicable. Placed in the column to the right. 1.2.12.1 TN Power Distribution: Considered. P Shall be evaluated in national mark approval. N Shall be evaluated in national mark approval. N The mains system in Israel is TN-S or TN-C or TN-C-S. 1.7 Marking and Instructions: The package of the equipment shall be marked in Hebrew, and shall include: (a) The name of the manufacturer (b) The country of production (c) The year of production (d) The name and the address of the importer (e) The marking shall be on a rectangular label (of at least 50mm X 24mm) (f) The letters height should be at least 2mm (g) The color of the label shall be in contrast to the color of the package. 1.7.14 Language: All instructions and warnings concerning safety should be in the Hebrew language 2.101 EMC: Shall be provided and evaluated in national mark The equipment shall comply with SI 961 part 6 approval. (CISPR 22 + 24) N 3.2.2 Permanently connected equipment: N Additional note below table 10: In Israel the diameter of the conduit shall comply with the Electricity Law. Israel National Differences according to CB Bulletin, No. 101A, December 2001 <12002388 001> Page 57 National Deviation Clause Requirement − Test Result – Remark APPENDIX Australian National Differences according to CB Bulletin No. 101A, December 2001 (AS/NZS 3260-1993) Verdict P REPORT (IEC Publication 60950 2nd edition, 1991 + Amd.1, 1992 + Amd.2, 1993 + Amd.3, 1995 + Amd.4, 1996) EXPLANATION FOR ABBREVIATIONS P=Pass, F=Fail, N=Not applicable. Placed in the column to the right. 1.2.12.2 Add: “TT power systems are not permitted in Australia or New Zealand.” Added. N 1.2.12.3 Add: “IT power systems are not permitted in Australia or New Zealand.” Note: Australia and New Zealand principally use multiple-earthed neutral (MEN) systems but allow TN-C for installations using metal-sheathed cables. Added. N 1.5.1 Add to paragraph 1: “or the other relevant Australian or New Zealand Standard.” Added. P 1.5.2 Add to the first and third dashed items after the words “IEC component standard”: “or the other relevant Australian or New Zealand Standard.” Added. P 1.7.14 Add to paragraph 1: “In Australia and New Zealand all safety instructions shall be in English.” User manual is in English. P 2 Add after clause 2: “For the limit of direct current from a.c. appliances, refer to AS/NZS Appendix 3.” See Appendix 3. N 3.2.2 Substitute for table 10: “For sizes of cables and conduits in Australia, refer to AS 3000.” No power cord provided. N 3.2.4 Substitute for table 11: “For sizes of conductors in No power cord provided. power supply cords use following Table 11: Table 11 Sizes of conductors in power supply cords Rated current (A) Cross-section area (mm2) 0.5* > 0.2 ≤ 3 0.75 > 3 ≤ 7.5 1 > 7.5 ≤ 10 1.5 > 10 ≤ 16 2.5 > 16 ≤ 25 4 > 25 ≤ 32 6 > 32 ≤ 40 10 > 40 ≤ 63 * This nominal cross-section area is only allowed for class II appliances if the length of the power supply cord, measured between the point where the cord, or cord guard, enters the appliance, and the entry to the plug, does not exceed 2m (0.5mm2 three-core supply flexible cords are not permitted; see Note 2 to table 2.17 of AS/NZS 3191). N 4.4.1 For the Australian alternative resistance to fire test, refer to Appendix 2.” Not applied for Appendix 2. Australian National Differences according to CB Bulletin No. 101A, December 2001 N <12002388 001> Page 58 National Deviation Clause Requirement − Test Result – Remark 6.4.2 Replace the first paragraph by: “In Australia, compliance with 6.4.1 is checked by both the test of 6.4.2.1 and 6.4.2.2”. Delete the fourth paragraph ‘The choice of tests....manufacturer’. No TNV. N 6.4.2.1 Replace Clause 6.4.2.1 by: No TNV. Impulse test The electrical separation is subjected to ten impulses of alternating polarity, using the impulse test generator of Annex N. The interval between successive impulses is 60s and the initial voltage Uu is: - in case (a) of 6.4.1, 7kV for hand-held telephones and for handsets; and 2.5kV for other equipment; and - in case (b) and (c) 1.5kV. Notes: 1 The 7 kV impulse is to simulate measured lighting surges in typical Australian rural and semi-rural network lines. 2 The value of 2.5kV has been chosen primarily to ensure adequacy of the insulation concerned, but not necessarily to simulate likely overvoltages. N 6.4.2.2 Replace Clause 6.4.2.2 by: No TNV. Electric strength test The electrical separation is subjected for 60s to a substantially sinusoidal voltage having a frequency of 50Hz or 60Hz, or to a d.c. voltage equal to the peak value of the prescribed a.c. voltage. The a.c. test voltage is: - in case (a) of 6.4.1 3kV - in case (b) and (c) 1.5kV. The voltage is gradually raised from zero to the prescribed voltage and then held at that value for 60s. NOTE: 1. Where there are capacitors across the insulation under test, it is recommended that d.c. test voltages are used. 2. The 3 kV and 1.5kV values have been determined considering the low frequency induced voltages from the power supply distribution system. N Annex A Add. after Annex title: Alternative resistance to fire test-determination if ignitability and combustion propagation Not applied for this Appendix. N Appendix 2 Add. Appendix ALTERNATE RESISTANCE TO FIRE TEST DETERMINATION OF IGNITABILITY AND COMBUSTION PROPAGATION Not applied for this Appendix. N X2.0 GENERAL This test is an alternative to the testes in Annex A to allow approval of equipment which has inadequate documentation to verify having been tested to Annex A. Australian National Differences according to CB Bulletin No. 101A, December 2001 Verdict N <12002388 001> Page 59 National Deviation Clause Requirement − Test X2.1 SOLID INSULATION MATERIALS AND NONMETALLIC ENCLOSURES N X2.1.1 GENERAL REQUIREMENTS Parts of non metallic material shall be resistant to ignition and spread of fire. This requirement does not apply to decorative trims, knobs wiring insulation and other parts not likely to be ignited or to propagate flames from inside the equipment. Compliance is checked by the tests of Clauses X2.1.2, X2.1.3 and X2.1.4 as applicable and if necessary by the test of X2.2 N X2.1.2 NON-METALLIC MATERIAL Relevant parts of non-metallic material are subjected to the glow-wire test of AS/NZS 3350.1, the test being made at a temperature of 550°C. The 550°C glow-wire test need not be carried out on parts which are made of material classified as FH 3-40 mm/min or better according to IEC 60707. The sample of material submitted to the test of IEC 60707 shall be thicker than the relevant part. Insulating material of winding bobbins and formers are subject to the glow-wire test of AS/NZS 3350.1, the test being made a temperature of 650°C. Base material of printed circuit boards with any coating or encapsulation to the needle-flame test of AS/NZS 3350.1, however, flames shall have extinguished with 15s of removal of the test flame. The flame shall be applied to an edge of the board having the lowest heat sink effect, with the board orientated in its normal position of use and at a point, if possible, not less than 10mm from a corner. The needle-flame test is not carried out on base material which is made of material classified as FV-0 according to IEC 60707. The sample of material submitted to the test of IEC 60707 shall be no thicker than that of the relevant printed circuit board. Notes: 1. The test is not carried out on printed circuit boards contained in a metal enclosure that prevents flames or burning droplets from escaping. 2. If the printed circuit board is tested with components mounted and a component ignites during the test, this would not constitute a failure of the printed circuit board material unless it is ignited by the component. N Result – Remark Australian National Differences according to CB Bulletin No. 101A, December 2001 Verdict <12002388 001> Page 60 National Deviation Clause Requirement − Test X2.1.3 ATTENDED EQUIPMENT For equipment which is operated while attended, parts of insulating material supporting, in contact with or in close proximity to current carrying connections, other than those in SELV circuits are subject to the glow-wire test AS/NZS 3350.1, the test being made at a temperature of 650°C. However parts of insulating material supporting, in contact with or in close proximity to screw connections which carry a current exceeding 0.5A during normal operation and which are likely to be made or remade during installation, user maintenance or when replacing a supply cord assembled with the appliance by Type X attachment, are subject to the glow-wire test AS/NZS 3350.1, the test being made at a temperature of 750°C. Notes: 1. The test is not carried out on parts supporting welded connections. 2. ‘In close proximity’ is considered to be a distance not exceeding 3mm. Result – Remark Australian National Differences according to CB Bulletin No. 101A, December 2001 Verdict N <12002388 001> Page 61 National Deviation Clause Requirement − Test X2.1.4 UNATTENDED EQUIPMENT For equipment which is operated while unattended, parts of insulating material supporting, in contact with or in close proximity to current carrying connections, other than those in SELV circuits are subject to the glow-wire test AS/NZS 3350.1, the test being made at a temperature of 750°C. However parts of insulating material supporting, in contact with or in close proximity to screw connections which carry a current exceeding 0.5A during normal operation and which are likely to be made or remade during installation, user maintenance or when replacing a supply cord assembled with the appliance by Type X attachment, are subject to the glow-wire test AS/NZS 3350.1, the test being made at a temperature of 850°C. Notes: 1. The test is not carried out on parts supporting welded connections. 2. ‘In close proximity’ is considered to be a distance not exceeding 3mm. During the application of glow-wire, the height and duration of flames are measured. In addition, for parts which withstand the glow-wire test but which flame during the application of the glow-wire, the surrounding parts are subject to the needle-flame test of AS/NZS 3350.1 for the measured duration of the flame after or 30s, whichever is the least if a) They are positioned within a distance equal to the height of the flame; and b) they are likely to be impinged upon by the flame However, surrounding parts shielded by a separate barrier which meets the needle-flame test are not tested. The needle-flame test is not carried out on parts which are made of material classified as FV-0 or FV1 according to IEC 60707. The sample of material submitted to the test of IEC 60707 shall be no thicker than the relevant part. Note: Parts likely to be impinged upon by the flame are considered to be those within the envelope of a vertical cycling having a radius of 10mm and a height equal to the height of flame, positioned above the point of the material supporting, in contact with or in close proximity to connections. Result – Remark Australian National Differences according to CB Bulletin No. 101A, December 2001 Verdict N <12002388 001> Page 62 National Deviation Clause Requirement − Test X2.2 ADDITIONAL TEST REQUIREMENTS If parts, other than enclosures, do not withstand the test of clauses X2.1.3 or X2.1.4, by failure to extinguish within 30s after removal of the glow wire tip, the needle-flame test of AS/NZS 3350.1 is made on all parts of non-metallic material which are within a distance of 50mm or which are likely to be impinged upon by flame during the test of clauses X2.1.3 or X2.1.4. Parts shielded by a separate barrier which meets the flame-needle test are not tested. Notes: 1. If the enclosure does not withstand the glowwire test the appliance is considered to have failed to meet the requirement of Appendix 2 without the need for consequential testing. 2. If other parts do not withstand the glow-wire test due to ignition of the tissue paper and if this indicates that burning or glowing particles can fall onto an external surface underneath the appliance, the appliance is considered to have failed to meet the requirement of Appendix 2 without the need for consequential testing. 3. Parts likely to be impinged upon by the flame are considered to be those within the envelope of a vertical cylinder having a radius of 10mm and a height equal to the height of the flame, positioned above the point of the material supporting, in contact with or in close proximity to connections. The needle-flame test need not be carried out on parts which are made of classified as FV-0 or FV-1 according to IEC 60707. The sample of material submitted to the test of IEC 60707 shall be no thicker than the relevant part. N Appendix 3 Add Appendix: No DC component under D.C. COMPONENTS FROM A.C. EQUIPMENT normal operation condition. Equipment shall be designed so that in normal use the value of any direct current in the equipment neutral will not contribute unduly to the failure of the installation earth electrode by corrosion. Any device such as isolating transformer intended to prevent direct current in the supply shall be an integral part of the equipment. Compliance is checked by inspection and by operating the equipment (a) at the rated voltage under the conditions specified in Clause 5.1; (b) on a supply free from any d.c. component; and (c) in the maximum d.c. producing mode, if any, but not exceeding normal load; and measuring the d.c. component in the supply neutral caused by the equipment as described below. P Result – Remark Australian National Differences according to CB Bulletin No. 101A, December 2001 Verdict <12002388 001> Page 63 National Deviation Clause Requirement − Test Result – Remark If it is evident from the design of the equipment that there will be no d.c. component, e.g. equipment provided with a full-wave mains power supply or a mains isolating transformer, this test is not conducted. The permissible direct current in the equipment neutral shall not exceed (i) for equipment considered as operating continuously ............................... 5 mA; or (ii) for other than continuously operated equipment where t is the assessed daily average operating time, in hours ......(5*24)/t mA For equipment which is not continuously operated but includes a component or a device which is continuously energized, e.g. stand-by control or remote switching device, the summation of the product of the direct current from the control device over 24h and the direct current from the equipment for its assessed daily average operating time in hours shall not exceed 120mAh per day. The maximum value of direct current permitted in the neutral is 1.44A which could be applicable to equipment with an assessed average daily operating time of 5 min. or less. Notes: 1. When determining the assessed daily average operating time the approvals authority may accept evidence supplied by the manufacturer. 2. The d.c. peak value due to transient starting effects is ignored. The measuring system used to measure any direct current produced shall have a sufficiently high normal (series) mode rejection ratio, by the use of a low pass filter if necessary, to ensure that an overall uncertainty of less than 10% can be achieved. Australian National Differences according to CB Bulletin No. 101A, December 2001 Verdict Page 64 <12002388 001> National Deviation Clause Requirement − Test Result – Remark APPENDIX Canadian National Differences according to CB Bulletin No. 101A, December 2001 Verdict P (IEC Publication 60950 2nd edition, 1991 + Amd.1, 1992 + Amd.2, 1993 + Amd.3, 1995 + Amd.4, 1996) EXPLANATION FOR ABBREVIATIONS P=Pass, F=Fail, N=Not applicable. Placed in the column to the right. Special National Conditions 1.1.1 All equipment installations are required to be in accordance with the Canadian Electrical Code (CEC). Part 1, CAN/CSA C22.1, and with National Electrical Code (NEC), ANSI/NFPA 70, and, unless marked or otherwise identified, the Standard for the Protection of Electronic Computer/Data-Processing Equipment, ANSI/NFPA 75. Considered. P 1.7.1 Equipment for use on supply systems with a neutral and more than one phase conductor (e.g. 120/240 V, 3-wire) require a special marking format for electrical ratings. Single phase. N A voltage rating that exceeds an attachment plug cap rating is only permitted if it does not exceed the extreme operating conditions in Table 2 of CAN/CSA C22.2 No. 235, and if it is part of a range that extended into the Table 2 “Normal Operating Conditions.” Likewise, a voltage rating shall not be lower than specified “Normal Operating Condition,” unless it is part of a range that extends into the “Normal Operating Conditions.” 2.5.9 Terminals for permanent wiring are required to be suitable for U.S./Canadian wire gauge sizes and be rated 125 percent of the equipment rating. N 2.5.11 When subject to impedance testing, protective earthing and bonding are required to be tested to the additional test conditions that originate in CAN/CSA C22.2 No. 0.4. Considered, see IEC 60950 report. P 2.6.2 Motor control devices are required for cordconnected equipment with a motor if the motor (a) has a nominal voltage rating greater than 120V, (b) in rated more than 12 A, or (c) is rated more than 1/3 hp (locked rotor current over 43 A). Not motor control device. N 2.6.8 Vertically-mounted disconnect switches and circuit breakers are required to have the “on” position indicated by the handle in the up position. No vertically mounted disconnect switch or circuit breaker. N 2.6.11 For computer room applications, equipment with battery systems capable of supplying 750 VA for five minutes are required to have a battery disconnect means that may be connected to the computer room remote power off circuit. No battery system. N Canadian National Differences according to CB Bulletin No. 101A, December 2001 <12002388 001> Page 65 National Deviation Clause Requirement − Test Result – Remark Verdict 2.7.1 Suitable NEC/CEC branch circuit protection is required for all standard supply outlets and mediumbase or smaller lampholders if the supply branch circuit protection is not suitable. No power outlet. N No fuse in neutral or earth conductors. N Power distribution transformers distributing power at 100 volts or more, and rated 10KVA or more, required transformer overcurrent protection. Panelboards provided as part of information technology equipment are required to have suitable overcurrent protection. 2.7.6 Fuses provided in the earthed circuit conductor (neutral) are only permitted for equipment rated 125V, 15A. 2.11 Where a fuse is used to provide Class 2, Limited Power Source, or TNV current limiting, it shall not be operator-accessible unless it is not interchangeable. N 3.1.12 For lengths exceeding 2 m, external interconnecting flexible cord and cable assemblies are required to be suitable cable type (e.g. DP, CL2) described in the NEC. N For lengths 3.05 m or less, external interconnecting flexible cord and cable assemblies which are not types specified in the CEC/NEC are required to have special construction features and identification markings. 3.2 Wiring methods (terminals, leads, etc.) used for the No power cord provided. connection of the equipment to the mains shall be in accordance with the CEC/NEC. N 3.2.1 Power supply cords are required to have attachment No power cord provided. plugs rated not less than 125 percent of the rated current of the equipment. N 3.2.2 Permanent connection of equipment to the mains by a power supply cord is not permitted. except for certain equipment,such as ATMs. No power cord provided. N 3.2.4 Power supply cords are required to be not longer than 4.5 m in length. No power cord provided. N Flexible power supply cords are required to be compatible with article 400 of the NEC 3.2.8 Permanently connected equipment is required to have a suitable wiring compartment and wiring bending space. No power cord provided. N 3.3 Wiring terminals and associated spacings for field wiring connections shall comply with CAN/CSA No. 0. No power cord provided. N 3.3.3 Wiring binding screws are not permitted to attach conductors larger than 10 AWG (5.3mm²). No wire binding screws used N Canadian National Differences according to CB Bulletin No. 101A, December 2001 <12002388 001> Page 66 National Deviation Clause Requirement − Test Result – Remark 4.3.12 Equipment with lasers is required to meet Code of Federal Regulations 21 CFR 1040 and Canadian Radiation Emitting Devices Act, REDR C1370, as applicable. Approved CD-ROM used. 4.4.1 For computer room application, automated No automated information information storage systems with combustible media storage system. greater than 27 cubic feet are required to have a provision for connection of either automatic sprinklers or a gaseous agent extinguishing system with an extended discharge. N 4.4.4 For computer room applications, enclosures with combustible material measuring greater than 0.9 m² or a single dimension greater than 1.8 m, are required to have flame spread rating of 50 or less. For other applications, enclosures with the same dimensions require a flame spread rating of 200 or less. N 4.4.8 The maximum quantity of flammable liquid stored in No liquid. equipment is required to meet NFPA 30. N Annex H Equipment that produces ionizing radiation is required to comply with Code of Federal Regulations, 21 CRF 1020 and/or Canadian Radiation Emitting Devices Act, REDR C1370, as applicable. N Enclosure is far smaller than 0.9m² or 1.8m in a single dimension. Verdict P Other Differences 1.5.1 Components of equipment must be suitable for the Components are UL or CSA application, and must comply with the requirements approved, see component list of the equipment standard and the Canadian or U.S. 1.5.1. components standards, as far as they may apply. The acceptance will be based on the following: A) A component certified by a Canadian or U.S. NCB to a Canadian or U.S. component standard will be checked for correct application and use in accordance with its specified rating. Where necessary, it will also be subjected to the applicable tests of the equipment standard. B) A component which has a CB Test Certificate for compliance with a relevant IEC component standard will be checked for correct application and use in accordance with its specified ratings. Where necessary, it will also be subjected to the applicable tests of the equipment standard, and to the applicable tests of the Canadian and U.S. component standard, under the conditions occurring in the equipment. Canadian National Differences according to CB Bulletin No. 101A, December 2001 P <12002388 001> Page 67 National Deviation Clause Requirement − Test Result – Remark Verdict C) A component which has no approval as in A) or B) above or which is used not in accordance its specified ratings, will be subjected to the applicable tests of the equipment standard, and to the applicable tests of the Canadian or U.S. component standard, under the conditions occurring in the equipment. D) Some components may require annual re-testing which may be carried out by the manufacturer, CSA or another laboratory. 3.4 Equipment connected to a centralized d.c. power system is required to meet special earthing wiring and marking requirements. N 4.1.6 Wall and ceiling mounted equipment is required to comply with special loading tests. N 4.1.7 Equipment with handles is required to comply with special loading tests. N 4.2.9 Enclosures around C.R.T´s having a diagonal dimension of 160 mm or more are required to reduce the risk of injury due to the implosion of the CRT. No CRT. N 6.2.1.1 Under normal operating conditions, the maximum acceptable TNN-2 and TNV-3 circuit levels for other than ringing signals are: (Uac/42.4 + Udc/60) < = 1. No TNV. N 6.2.2.2 Access restrictions to TNV-2 and TNV-3 circuits in battery compartment also apply to TNV-1 circuits. No TNV. N 6.3.4.3 Equipment intended to receive telecommunication ringing signals is required to comply with special leakage current measurement tests. No TNV. N 6.4.1 Enamel coating on winding wire not considered electrical separation unless subject to special investigation. No TNV. N 6.4.3 Equipment connected to a telecommunications network and supplied with an earphone intended to be held against the ear is required to comply with special acoustic pressure tests. No TNV. N 6.5 Where a fuse is used to provide current limiting, it shall not be operator-accessible unless it is not interchangeable. No TNV. N 6.6 Equipment intended for connection to telecommunication network outside plant cable is required to be protected against overvoltage from power line crosses. No TNV. N M.2 Continuous ringing signals up to 16 mA only are permitted if subject to special installation and performance restrictions. No TNV. N Canadian National Differences according to CB Bulletin No. 101A, December 2001 <12002388 001> Page 68 National Deviation Clause Requirement − Test Result – Remark APPENDIX US National Differences according to CB Bulletin No. 101A, December 2001 Verdict P for IEC 60950 (1991) 2nd Edition, Amendment No.1 (1992), Amendment No. 2 (1993), Amendment No. 3 (1995) and Amendment No. 4 (1996) EXPLANATION FOR ABBREVIATIONS P=Pass, F=Fail, N=Not applicable. Placed in the column to the right. The following national differences are based on national regulatory requirements. 1.1.1 All equipment installations are required to be in Considered. accordance with the National Electrical Code (NEC), ANSI/NFPA 70, and unless marked or otherwise identified, the Standard for the Protection Electronic Computer/Data-Processing Equipment, ANSI/NFPA 75. 1.7.1 Equipment for use on supply systems with a neutral and more than one phase conductor (e.g. 120/240V, 3-wire) require a special marking format for electrical rating. Single phase. P N A voltage rating that exceeds an attachment plug cap rating is only permitted if it does not exceed the extreme operating conditions in Table 2 of CAN/CSA C22.2 No. 235, and if it is part of a range that extends into the Table 2 “Normal Operating Conditions”. Likewise, a voltage rating shall not be lower than the specified “Normal Operating Conditions”, unless it is part of a range that extends into the “Normal Operating Conditions”. 2.5.9 Terminals for permanent wiring are required to be suitable for U.S./Canadian wire gauge sizes and be rated 125 percent of the equipment rating. N 2.5.11 The capacity of the connection between the earthing terminal and parts required to be earthed is required to comply with CAN/CSA C22.2 No. 0.4. Considered, see IEC 60950 report. P 2.6.2 Motor control devices are required for cordconnected equipment with a motor if the motor (a) has a nominal voltage rating greater than 120V, (b) is rated more than 12A, or (c) is rated more than 1/3 hp (locked rotor current over 43A). No motor control device. N 2.6.8 Vertically mounted disconnect switches and circuit breakers are required to have the “on” position indicated by the handle in the “up” position. No vertically mounted disconnect switch or circuit breaker. N 2.6.11 For computer room applications, equipment with battery systems capable of supplying 750VA for five minutes are required to have a battery disconnect means that may be connected to the computer room remote power-off circuit. No battery system. N US National Differences according to CB Bulletin No. 101A, December 2001 <12002388 001> Page 69 National Deviation Clause Requirement − Test 2.7.1 Suitable NEC/CEC branch circuit protection is required for all standard supply outlets and mediumbase or smaller lampholders if the supply branch circuit protection is not suitable. Result – Remark Verdict N Power distribution transformers distributing power at 100 volts or more, and rated 10kVA or more, require transformer overcurrent protection. Panelboards provided as part of information technology equipment are required to have suitable overcurrent protection. 2.7.6 Fuses provided in the earthed circuit conductor (neutral) are only permitted for equipment rated 125V, 15A. No fuse in earthing conductor. N 2.11 Where a fuse is used to provide current limiting, it shall not be operator-accessible unless it is not interchangeable. No fuse used for limited power. N 3.1.12 For lengths exceeding 3.05m, external interconnecting flexible cord and cable assemblies are required to be a suitable cable type (e.g. DP, CL2) described in the NEC. No power cord provided. N 3.2 Wiring methods (terminals, leads, etc.) used for the No power cord provided. connection of the equipment to the mains shall be in accordance with the NEC N 3.2.1 Power supply cords are required to have attachment No power cord provided. plugs rated not less than 125 percent of the rated current of the equipment. N 3.2.2 Permanent connection of equipment to the mains by No power cord provided. a power supply cord is not permitted. N 3.2.4 Power supply cords are required to be no longer than 4.5m in length. No power cord provided. N For length 3.05m or less, external interconnecting flexible cord and cable assemblies which are not types specified in the NEC are required to have special construction features and identical markings. Flexible power supply cords are required to be compatible with Article 400 of the NEC. 3.2.8 Permanently connected equipment is required to have a suitable wiring compartment and wiring bending space. No power cord provided. N 3.3 Wiring terminals and associated spacings for field wiring connections shall comply with CSA C22.2 No. 0. No power cord provided. N 3.3.3 Wire binding screws are not permitted to attach supply conductors larger than 10 AWG (5.3mm²). No wire binding screws. N US National Differences according to CB Bulletin No. 101A, December 2001 <12002388 001> Page 70 National Deviation Clause Requirement − Test Result – Remark 4.3.12 Equipment with lasers is required to meet Code of Federal Regulations 21CFR 1040 and Canadian Radiation Emitting Devices Act, REDR C1370. Approved CD-ROM used. 4.4.1 For computer room applications, automated No automated information information storage systems with combustible media storage system. greater than 27 cubic feet are required to have a provision for connection of either automatic sprinklers or a gaseous agent extinguishing system with an extended discharge. N 4.4.4 For computer room applications, enclosures with combustible material measuring greater than 0.93mm² or having a single dimension greater than 1.8m are required to have a flame spread rating of 50 or less. For other applications, enclosures with the same dimensions require a flame spread rating of 200 or less. N 4.4.8 The maximum quantity of flammable liquid stored in No liquid. equipment is required to meet NFPA 30. Verdict Enclosure is far smaller than 0.9m² or 1.8m in a single dimension. P N The following national differences are based on requirements other than national regulatory requirements. 1.5.1 Some components and materials associated with the Components are UL risk of fire, electric shock, or personal injury are approved, see component list required to have component or material ratings in 1.5.1. accordance with the applicable national (U.S. and Canadian) component or material requirements. These components include: P attachment plugs, cathode ray tubes, circuit breakers, communication circuit accessories, cord sets and power supply cords, enclosures (outdoor), flexible cords and cables, fuses, fuseholders, ground-fault current interrupters, industrial control equipment, insulating tape, lampholders, limit controls, printed wiring, protectors for communication circuits, receptacles, solid state controls, supplementary protectors, surge suppressors, switches, thermal cutoffs, thermostats, tubing, wire connectors, and wire and cables. 3.4 Equipment connected to a centralized d.c. power system is required to meet special earthing, wiring and marking requirements. No connection to centralized d.c. power system. N 4.1.6 Wall and ceiling mounted equipment is required to comply with special loading tests. No wall or ceiling mounted equipment. N 4.1.7 Equipment with handles is required to comply with special loading tests. No handles. N 4.2.9 Enclosures around CRT’s with a face area of 160mm or more are required to reduce the risk of injury due to the implosion of the CRT. No CRT. N US National Differences according to CB Bulletin No. 101A, December 2001 <12002388 001> Page 71 National Deviation Clause Requirement − Test Result – Remark 6.2.1.1 The maximum acceptable TNV circuit levels for other than ringing signals are: No TNV. N Verdict normal condition(Uac/42.4 + Udc/42.4 ≤1 for Udc ≤21.2 (Uac/32.8 + Udc/60) ≤ 1 for Udc >21.2 abnormal conditions(Uac/70.7 + Udc/120) ≤1 6.2.2.2 Access restrictions to TNV-2 and TNV-3 circuits in battery compartments also apply to TNV-1 circuits. No TNV. N 6.3.4.3 Equipment intended to receive telecommunication ringing signals is required to comply with special leakage current measurement test. No TNV. N 6.4.1 Enamel coating on winding wire are not considered electrical separation unless subjected to special investigation. No TNV. N 6.4.3 Equipment connected to a telecommunication network and supplied with an earphone intended to be held against the ear is required to comply with special acoustic pressure tests. No TNV. N 6.5 Equipment intended to provide power over the No TNV. telecommunication wiring system is required to limit output current to values which will not damage the telecommunication wiring system. N 6.6 Equipment intended for connection to telecommunication network outside plant cable is required to be protected against overvoltage. No TNV. N M.2 Continuous ringing signals up to 16mA only are permitted if subjected to special installation and performance restriction. No TNV. N US National Differences according to CB Bulletin No. 101A, December 2001
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.3 Linearized : Yes Creator : HP 9100C Digital Sender Create Date : 2002:06:18 14:38:19 Author : Producer : Title : Subject : CB-All Modify Date : 2002:06:18 15:28:21+08:00 Page Count : 73EXIF Metadata provided by EXIF.tools