DL DPL SPEC
2019-02-20
: Pdf Dl Dpl Spec DL_DPL_SPEC spec products dual-lite
Open the PDF directly: View PDF .
Page Count: 2
DPL
Photoluminescent Exit Signs
Application
The DPL Series of photoluminescent exit signage offers exit compliance
with UL listed legible viewing distances of 50’, 75’ and 100’. The signs
absorb and store ambient light from, fluorescent, mercury vapor, metal
halide, and LED light sources, and are designed to provide emergency
illumination for a minimum of 90 minutes in the event of power loss.
The signs require a continuous minimum of 5 foot-candles to maintain
the charge. The DPL photoluminescent exit signs do not require AC or
electrical power. All signs have a 25 year lifecycle.
Construction
The DPL Series is available in four differing construction models.
AF - Aluminum Frame with rigid PVC, photoluminescent background
P - injection molded ABS plastic polymer, photoluminescent letters
PM - high-density polyethylene (HDPE) with aluminum face and back,
photoluminescent letters
A - Acrylic, photoluminescent letters
All signs ship with a ceiling mount bracket and 2 self-adhesive backed
arrows for directional indication. See page 2 for additional construction
details.
Illumination
The DPL Series is manufactured with phosphorescent (glow-in-
the-dark) pigments, which are based on Strontium Oxide Aluminate
Chemistry. Sign will remain visible and legible to the rated distance
indicated, for a minimum of 90 minutes after all light has been
extinguished.
Installation
All signs can be wall mounted, and include a ceiling mount bracket,
which can be installed to facilitate ceiling or end mounting. Wall
anchors or screws(supplied by others) can be used to mount the sign
directly to the wall surface, or ceiling mounted by use of the supplied
bracket.
Compliances
UL924 Listed
NFPA 101, NFPA 70
OSHA
Warranty
5 Year Full
FEATURES
ORDERING GUIDE
Catalog Number
Comments Type
AF- 50’ Viewing Distance with
Aluminum Frame
P-100’ Viewing Distance ABS
Thermoplastic
PM- 50/75’ Viewing Distance
Poly-Metal
A - 75’ Viewing Distance Acrylic
DPL
Model Construction Viewing Distance Face Color
AF Aluminum Frame 50 50' SSingle RRed
PABS Thermoplastic 75 75' DDouble GGreen
PM Poly Metal 100 100'
AAcrylic
Note: Please refer to RDC guide to select from stocked models.
DPL
Photoluminescent Exit Signs
Web: www.dual-lite.com • Tech Support: (866)-313-3909
701 Millennium Blvd. • Greenville, SC 29607 U.S.A.
Copyright © Dual-Lite, a division of Hubbell Lighting, Inc., All Rights Reserved
Specifications subject to change without notice. • Printed in U.S.A. 0604085 DPL 10/18
Type AF Construction includes a photoluminescent background, letters in red or green with 7/8” stroke and 7” height, and are rated at 50’ viewing distance.
Sign substrate made of photoluminescent self-extinguishing PVC. High and low level mounting, for indoor use only. Includes aluminum mounting bracket in
matte finish.
Type P Constructed of injection molded ABS thermoplastic with red or green background. Letters are 1” stroke and 8” height, and are rated at 100’ viewing
distance. Type P exits are suitable for wet location and indoor or outdoor use. Includes color-matched powder coated bracket.
Type PM Constructed of high-density polyethylene (HDPE) with aluminum face and back, photoluminescent letters. 50’ viewing distance sign letters are 1”
stroke and 7” high with brushed aluminum, red or green background. Indoor use only. Includes polished aluminum mounting bracket.
75’ viewing distance sign letters are 1’ stroke and 7 ½” high with red or green backgrounds. Suitable for wet location and indoor or outdoor use. Includes
polished aluminum mounting bracket.
Type A Constructed of high gloss acrylic in fire engine red and vivid green with chrome bracket. 75’ viewing distance sign letters are 7/8” stroke and 7 ½”
high. Indoor use only. Includes chrome plated mounting bracket. Suitable for wet location and indoor or outdoor use
Type AF Type P
SPECIFICATIONS
DIMENSIONS
Type PM
Type A
Standard Features Include:
- Maintenance free exit compliance
- No electricity required
- Quick Installation
- Made in USA
- High or low mounting
Application Note: Install photoluminescent exit signs only in locations
where an external illumination source is present, is deemed reliable, and
is supplied by a circuit not controlled by automatic timers or sensors, and
where controls are accessible only to authorized personnel. A minimum
of 5 foot-candle(54lux) external illumination of unfiltered metal halide,
fluorescent, mercury vapor or LED charging light sources required on
sign face at all times of building occupancy.