3585PS1i1 Freefoam BBA Certificate
Freefoam-Bba-Certificate Freefoam-BBA-Certificate Freefoam-BBA-Certificate PDF cabp
2016-04-20
: Pdf Freefoam Bba Certificate Freefoam_BBA_Certificate FreeFoam DataSheets PDF
Open the PDF directly: View PDF .
Page Count: 12
Page 1 of 12
TECHNICAL APPROVALS FOR CONSTRUCTION
APPROVAL
INSPECTION
TESTING
CERTIFICATION
Freefoam Plastics Limited
Central Commercial Park
Centre Park Road
Cork
Ireland
Tel: 00 353 21 4966 311 Fax: 00 353 21 4965 273
e-mail: marketing@freefoam.com
website: www.freefoam.com
British Board of Agrément
tel: 01923 665300
Bucknalls Lane
fax: 01923 665301
Garston, Watford
e-mail: mail@bba.star.co.uk
Herts WD25 9BA
website: www.bbacerts.co.uk
©2012
The BBA is a UKAS accredited certification body — Number 113. The schedule of the current scope of accreditation for product certification is
available in pdf format via the UKAS link on the BBA website at www.bbacerts.co.uk
Readers are advised to check the validity and latest issue number of this Agrément Certificate by either referring to the BBA website or contacting the BBA direct.
FREEFOAM PLASTICS LIMITED ROOF TRIM SYSTEMS
FREEFOAM WHITE PVC-U ROOF TRIM SYSTEM
This Agrément Certificate Product Sheet(1) relates to the
Freefoam White PVC-U Roof Trim System, comprising
fascia, soffit and barge boards, soffit ventilator, and
accessories for external use at the roofline as a substitute
for timber or other conventional materials.
(1) Hereinafter known as ‘Certificate’.
CERTIFICATION INCLUDES:
• factors relating to compliance with Building
Regulations where applicable
• factors relating to additional non-regulatory
information where applicable
• independently verified technical specification
• assessment criteria and technical investigations
• design considerations
• installation guidance
• regular surveillance of production
• formal three-yearly review.
KEY FACTORS ASSESSED
Ventilation — the ventilated soffit board can contribute towards providing the necessary roof space ventilation
(see section 4).
Strength and stability — in terms of wind loading resistance the system can be used in all areas of the UK (see section 6).
Performance in relation to fire — when tested in accordance with BS 476-7 : 1997 the cellular boards achieved a
Class 1Y surface spread of flame rating and rigid hollow soffit boards achieved a surface spread of flame rating of
Class 2Y (see section 7).
Durability — the system will retain its decorative qualities for a period in excess of 20 years with only minor changes
in surface appearance (see section 9).
Agrément Certificate
99/3585
Product Sheet 1
The BBA has awarded this Certificate to the company named above for the system described herein. This system
has been assessed by the BBA as being fit for its intended use provided it is installed, used and maintained as set
out in this Certificate.
On behalf of the British Board of Agrément
Date of First issue: 9 August 2012 Sean Moriarty — Head of Approvals Greg Cooper
Originally certificated on 8 March 1999 Energy and Ventilation Chief Executive
Page 2 of 12
In the opinion of the BBA, the Freefoam White PVC-U Roof Trim System, if installed, used and maintained in
accordance with the provisions of this Certificate, will meet or contribute to meeting the relevant requirements of
the following Building Regulations (the presence of a UK map indicates that the subject is related to the Building
Regulations in the region or regions of the UK depicted):
The Building Regulations 2010 (England and Wales)
Requirement: C2(b) Resistance to moisture
Comment: The system will contribute to providing protection against the penetration of moisture to the inner surface of
the building on which it is installed. See section 3.1 of this Certificate.
Requirement: C2(c) Resistance to moisture
Comment: When used in accordance with this Certificate, the soffit ventilation products can contribute to enabling a
roof to meet this Requirement. See sections 4.1 to 4.10 of this Certificate.
Requirement: Regulation 7 Materials and workmanship
Comment: The components of the system are acceptable. See section 9.1 and the Installation part of this Certificate.
The Building (Scotland) Regulations 2004 (as amended)
Regulation: 8(1)(2) Fitness and durability of materials and workmanship
Comment: The system is acceptable. See sections 8.1, 8.2 and 9.1 and the Installation part of this Certificate.
Regulation: 9 Building standards — construction
Standard: 3.10 Precipitation
Comment: The system will contribute to satisfying this Standard, with reference to clause 3.10.1(1)(2), by giving
protection against the penetration of moisture to the inner surface of the building on which it is installed.
See section 3.1 of this Certificate.
Standard: 3.15 Condensation
Comment: The soffit ventilation products can contribute to enabling a roof to meet this Standard, with reference to
clauses 3.15.1(1), 3.15.3(1), 3.15.5(1) and 3.15.7(1). See sections 4.1 to 4.10 of this Certificate.
(1) Technical Handbook (Domestic).
(2) Technical Handbook (Non-Domestic).
The Building Regulations (Northern Ireland) 2000 (as amended)
Regulation: B2 Fitness of materials and workmanship
Comment: The system is acceptable. See section 9.1 and the Installation part of this Certificate.
Regulation: B3(2) Suitability of certain materials
Comment: The system is acceptable. See sections 8.1 and 8.2 of this Certificate.
Regulation: C4(b) Resistance to ground moisture and weather
Comment: The system will contribute to providing protection against the penetration of moisture to the inner surface of
the building on which it is installed. See section 3.1 of this Certificate.
Regulation: C5 Condensation
Comment: The soffit ventilators can contribute towards enabling a roof to meet the requirements of this Regulation.
See sections 4.1 to 4.10 of this Certificate.
Construction (Design and Management) Regulations 2007
Construction (Design and Management) Regulations (Northern Ireland) 2007
Information in this Certificate may assist the client, CDM co-ordinator, designer and contractors to address their
obligations under these Regulations.
See section: 10 General (10.7 to 10.10) of this Certificate.
Additional Information
NHBC Standards 2011
NHBC accepts the use of the Freefoam White PVC-U Roof Trim System, provided it is installed, used and maintained
in accordance with this Certificate, in relation to NHBC Standards, Chapter 7.2 Pitched roofs.
Technical Specification
1 Description
1.1 The Freefoam White PVC-U Roof Trim System is for external use on roofs as a substitute for timber or other
conventional materials.
Regulations
Page 3 of 12
1.2 The system comprises a range of cellular PVC-U (PVC-UE) boards, and are shown in Figure 1. Ancillary
components including a rigid soffit ventilator, rigid hollow soffits and other extruded trims, and injection moulded joints
and end caps are shown in Figure 2.
Figure 1 Fascia/barge boards
Page 4 of 12
Figure 2 Ancillary components
Page 5 of 12
1.3 Characteristics of the cellular boards are shown in Table 1 and compatibility to ancillary components in Table 2.
Table 1 Characteristics of boards
Standard
length
(m)
Width
(mm)
Nominal
thickness
(mm)
Minimum thickness
of outer skin
(mm)
Average
density
(kg·m·–3)
FW
Plain fascia
5 100, 125, 150 175, 200, 225, 250, 300, 400,
410(1) (F410P), 450, 605(1) (F605P)
10 0.4 0.48
FO
Ogee fascia
5 100, 150, 175, 200, 225, 250, 300, 390 10 0.4 0.48
FMS
Magnum square leg fascia
5 150, 175, 200, 225, 250, 300, 410(1) 18 0.4 0.48
GPB
Soffit board
5 100, 125, 150, 175, 200, 225, 250, 300,
350, 400 (GPB405), 450, 500, 600 (GPB605)
10 0.4 0.48
FMXS
Magnum Xtra square leg fascia
5 150, 175, 200, 225, 250, 405(1) 25 0.4 0.48
FMR
Magnum roundnose fascia
5 150, 175, 200, 225, 250, 405(1) 18 0.4 0.48
FMD
Magnum duo fascia
5 150, 175, 200, 225, 250, 405(1) 15 0.4 0.48
FMO
Magnum ogee fascia
5 150, 175, 200, 225, 250, 405(1) 18 0.4 0.48
FMXD
Magnum roundnose fascia
5 150, 175, 200, 225, 250, 300, 405(1) 23 0.4 0.48
FMF
Magnum flat fascia
5 100, 125, 150, 175, 200, 250, 300 16 0.4 0.48
FML
Square edged fascia
5 150, 175, 200, 225, 250, 405(1) 15 0.4 0.48
(1) Double ended board.
Table 2 Ancillary component and board compatibility
FW FO FMS FMXS FMR FMD FMO FMXD FMF FML
FWJ ✓—✓✓
——————
FWX ✓—✓✓
——————
FWXI ✓—✓✓
——————
FOJ —✓————✓———
FOX —✓————✓———
FOXI —✓————✓———
FMRJJ ————✓✓
—✓——
FMRXX ————✓✓
—✓——
FMRXI ————✓✓
—✓——
FLJ —————————✓
FLX —————————✓
FLXI —————————✓
FFMJJ ————————✓—
FFMXX ————————✓—
1.4 The soffit ventilator provides a means of ventilating the roof void.
1.5 The PVC-UE boards comprise a closed cell cellular PVC-U core beneath an outer weathering impact modified
PVC-U skin. The extruded trims are composed of impact modified PVC-U and the injection mouldings of PVC-U.
1.6 The cellular boards are manufactured by co-extruding a high-impact PVC-U compound onto a foamable PVC-U
compound, cooling and forming to section. Cellular PVC-U is formed during the process by the evolution of gas from
sodium bicarbonate present in the foamable PVC-U compound.
1.7 The PVC-U trims are manufactured using conventional extrusion and injection moulding techniques.
Page 6 of 12
1.8 Continuous quality control is undertaken during manufacture. Checks include:
• appearance
• colour
• dimensions
• weight per metre
• impact strength
• heat reversion
• heat ageing.
1.9 The recommended fixings for use with various components of the system are listed in Table 3.
Table 3 System components and their recommended fixings(1)
Component Type of fixing
Fascia board White plastic headed (12 mm) 40 mm x 3 mm, 50 mm x 3 mm and
65 mm x 3 mm stainless steel annular ring shank nails
Soffit trim 30 mm stainless steel secret fix cladding pins
Other components White plastic headed (7 mm) 25 mm x 2 mm, 30 mm x 2 mm and
40 mm x 2 mm stainless steel annular ring shank nails
(1) Available from the manufacturer.
2 Delivery and site handling
2.1 The boards are delivered in packs sealed in polythene sleeves. Pack quantities vary dependent upon the type
of profile.
2.2 Care must be taken to avoid contact with solvents and materials containing organic components such as coal tar.
2.3 The packs should be unloaded by hand to avoid damage, stored flat in the polythene sleeves on a clean, level
surface in stacks not exceeding one metre in height and restrained from collapse. To avoid damage, it is recommended
that additional protection is provided when the planks are stored in the open.
Assessment and Technical Investigations
The following is a summary of the assessment and technical investigations carried out on the Freefoam White PVC-U
Roof Trim System.
Design Considerations
3 General
3.1 The Freefoam White PVC-U Roof Trim System is suitable for external use to provide a protective and
decorative trim to roofs where timber or other conventional materials would normally be used. The system will
provide adequate protection to the interior of the building from the penetration of moisture.
3.2 The system must be fixed only to structurally sound building substrates, at centres not exceeding 600 mm. Rafter
feet and gable ladders should be adequately supported to ensure rigidity. Replacement, rather than fixing over existing
fascia, is recommended. Timber roof structures, to which the system is fixed, must be designed and/or constructed
in accordance with the relevant Building Regulations and, as appropriate, in compliance with one of the following
technical specifications:
• BS EN 1995-1-1 : 2004
• The Building Regulations 2010 (England and Wales), Approved Document A1/2, Section 2A
• The Building Regulations (Northern Ireland) 2000, Part D Structure.
3.3 Cellular PVC-UE components have a similar coefficient of thermal expansion to that of conventional solid PVC-U.
A 5 mm gap should be provided at the end of each board, at the joint trim (ie 10 mm between boards), to allow for
movement. Care should be taken not to install the system in extremes of temperature. The recommended temperature for
installation is between 5°C and 25°C.
4 Ventilation
4.1 Freefoam soffit ventilators can contribute towards providing the necessary roof space ventilation. Guidance
on the provision of adequate ventilation is given in the 2004 edition of the Approved Document C2 Resistance
to moisture to the Building Regulations 2010 (England and Wales), and in BS 5250 : 2011, section 4.
Guidance for Northern Ireland towards the provision of roof space ventilation is given in ‘deemed to satisfy’ Technical
Booklet C : 1994 and BS 5250 : 2011.
Page 7 of 12
4.2 When providing roof space ventilation it is essential that the airway must not become blocked by the loft
insulation. This may be achieved by the use of a suitable BBA-approved insulation retainer producing an air passage
with an effective area (geometric free area) at least equal to that of the soffit ventilator used.
4.3 The soffit ventilator trim (without mesh) has a vented area of 25 298 mm2 per m run (equivalent to a continuous
slot of about 25.3 mm wide at eaves level) and is suitable for the applications given in sections 4.4 to 4.6.
4.4 For roofs with a pitch of 15° or more, where both the ceiling and insulation are horizontal, soffit ventilation
products with a minimum effective area of 10 000 mm2 per m run, if used in accordance with section 4.2, can
provide adequate ventilation to insulated loft spaces as set out in BS 5250 : 2011, Annex H. The soffit ventilation
product should run along the eaves of the longest opposite sides of a rectangular roof to provide adequate cross-
ventilation. The ventilators are suitable for use with traditional (semi-permeable) and high performance (impermeable)
sarking felts. Consideration should be given to the use of high-level ventilation openings to increase the ventilation
rate for roofs as recommended in BS 5250 : 2011, Annex H. The use of high-level ventilation openings is strongly
recommended in roofs with a pitch greater than 35° or roof spans in excess of 10 m.
4.5 For roofs where the ceiling follows the pitch of the roof, soffit ventilation products with a minimum effective area of
25 000 mm2 per m run, if used in conjunction with suitable high-level ventilation, can provide adequately for roof voids
as set out in BS 5250 : 2011, Annex H. It is essential that a minimum unrestricted air space of 50 mm is maintained
between the underside of the roof deck and the top of the insulation. Consideration should be given to the probability
of the sarking felt bowing between rafters and it should be ensured that this does not reduce the gap between felt
and insulation to less than 50 mm. Where there is an obstruction to the ventilation, eg rooflights or a change in
pitch of roof, adequate ventilation, in accordance with the requirements of BS 5250 : 2011, Annex H, should be
provided above and below the obstruction using suitable ventilators. The required ventilation at high level and around
obstructions may be achieved by using a suitable BBA-approved ventilator.
4.6 For roofs with a pitch of less than 15°, soffit ventilation products with a minimum effective area of 25 000 mm2
per m run, if used in accordance with section 4.2, can provide adequate ventilation to insulated roof voids as set
out in BS 5250 : 2011, Annex H. When providing roof space ventilation for flat roofs, it is essential that a minimum
unrestricted air space of 50 mm is maintained between the underside of the roof deck and the top of the insulation.
Ventilation should be provided along two opposite sides of the deck: where possible these should be the two longest
sides in order to achieve maximum cross-ventilation. The recommendations contained in BS 5250 : 2011, Annex H,
should be followed when planning the provision of ventilation to flat roofs, especially where spans exceed five m, or
for concrete deck roofs. Where a flat roof has a span of greater than 10 m, or is not of a simple rectangular plan,
more ventilation will be required, totalling at least 0.6% of the total area of the roof. It should be noted that cold flat
roof construction is generally unacceptable in Scotland and not the preferred option elsewhere in the UK(1).
(1) See BRE Report (BR 262 : 2002) Thermal insulation: avoiding risks.
4.7 Where soffit ventilation products are used in lean-to or mono-pitched roofs, high-level ventilation, in accordance
with BS 5250 : 2011, Annex H, must be provided.
4.8 Where a pitched roof abuts a wall, additional high-level ventilation must be arranged to provide an open area at
least equal to a 5 mm slot running the full length of the abutment.
4.9 Soffit ventilation product sections meet NHBC requirements for protection against the ingress of birds, rodents or
large insects.
4.10 The dimensions of the slots in soffit ventilation products are such that the risk of blockage is limited. However,
blockage by insects and debris will impair their performance as vents and they should be examined occasionally and
cleared if necessary.
5 Practicability of installation
The system is designed to be installed by a competent general builder, or a contractor, experienced with this type
of system.
6 Strength and stability
6.1 When installed in accordance with this Certificate, the system will withstand, without damage or permanent
deflection, the wind loads likely to be encountered in the United Kingdom. In exposed locations, care should be taken
to ensure that all profiles are adequately fixed.
6.2 The system has adequate resistance to hard and soft body impacts likely to occur in practice.
6.3 PVC-U gutters, as specified in BS EN 12200-1 : 2000, may be screw-fixed directly to the Magnum boards.
Gutter bracket spacings must not exceed one metre; reduced spacings are recommended in the Scottish Highlands
where snow loading should be considered. Other lightweight gutters may also be screw-fixed to the Magnum board
provided the maximum bracket loading, covered in BS EN 12200-1 : 2000, is not exceeded. For other boards, all
gutters should be fixed through the fascia to rafter ends of other sound timber.
6.4 Magnum boards will support all eaves tiles in common usage in the UK (up to 10 kg load per one metre length of
fascia) provided that the boards are installed as per the requirements of this Certificate.
Page 8 of 12
6.5 Apart from the exception detailed in section 6.4, the fascia boards are not loadbearing and must not be used
to support fixtures such as roof tiles, gutters, other components of the roof structure or television aerials. Telephone and
power cables may be run along the boards but the main brackets for these services should be fixed through the fascia
to structurally sound timber.
7 Performance in relation to fire
7.1 When tested in accordance with BS 476-7 : 1997, the cellular boards achieved a Class 1Y surface spread of
flame rating, and rigid hollow soffit boards achieved a Class 2Y surface spread of flame rating.
7.2 On exposure to fire, PVC-U tends to char and may fall away. The spread of flame along its surface is limited. It is
unlikely that the roof trim system will significantly affect the overall fire performance of any roof in which it is installed.
7.3 Where it is normal practice to carry the eaves box over between dwellings, it is important that the box is fire-
stopped at compartment walls.
8 Maintenance
8.1 The system can be cleaned by washing with water and mild detergent. Abrasive or solvent-based cleaners
should not be used. Materials can be cut and drilled, using normal woodworking tools, if repairs are required.
8.2 As with all PVC products, paint can adversely affect the impact strength of the PVC-U sections, and the application
of dark colours could lead to a risk of thermal distortion. Painting, therefore is, not recommended.
9 Durability
9.1 Results of accelerated weathering tests indicate that the system is as durable as conventional solid PVC-U
and that profiles will retain adequate impact resistance for a period in excess of 20 years.
9.2 The system will retain its decorative qualities for a period in excess of 20 years with only minor changes in surface
appearance.
9.3 Where the timber substrate is preservative treated with copper/chrome/arsenic(1) or copper/chrome/boron, care
must be taken to ensure that sufficient time is allowed for complete fixation of the preservative (approximately seven days)
to avoid corrosion of screws and nails used to fix the components.
(1) CCA products should not be used in domestic applications according to European Union Restrictions.
Installation
10 General
10.1 Installation of the Freefoam White PVC-U Roof Trim System must be carried out in accordance with the
manufacturer’s instructions and the requirements of this Certificate (see Figures 3 and 4).
Page 9 of 12
Figure 3 Typical fascia and soffit installation details
Page 10 of 12
Figure 4 Typical soffit box detail
typical soffit box detail
FW square fascia
FW square fascia
FWX square
fascia corner
F105 ‘F’ trim
F105 ‘F’ trim
FZ106 flexible
‘H’ joint trim(1)
GPB general
purpose board
GPB general
purpose board
GPB general
purpose board
(1) FZ106 is outside the
scope of this Certificate
FMS Magnum
square fascia
FMS Magnum
square fascia
FMS Magnum
square fascia
FMS Magnum
square fascia
FMS Magnum
square fascia
FMS Magnum
square fascia
FWX square
fascia corner
FWX square
fascia corner
FWX square
fascia corner
FZ106 flexible
’H’ joint trim(1)
GPB general
purpose board
10.2 Fascia, soffit and barge boards should be fixed to structurally sound timber at centres not exceeding 600 mm,
using the nails and pins specified by the manufacturer. Rotten timber must be replaced by new treated timber.
10.3 Magnum fascia boards may be used directly to support PVC-U and other lightweight gutters (see section 6.3).
Other components of the system are not loadbearing (see section 6.5).
10.4 Magnum boards may be used to support eaves tiles (see section 6.4). In certain geographical/topographical
locations the eaves tiles will need to be restrained in order to resist wind uplift. Guidance on this fixing should be
sought from the manufacturer of the eaves tiles.
10.5 Sarking felt should be checked to ensure that it is in good condition and extends onto the verge rafter and over
a felt support into the gutter at the eaves. Damaged or worn felt should be replaced or, if occurring at the eaves, made
watertight using an eaves protector.
10.6 Soffit ventilation products should be selected and installed so that the roof ventilation conforms to the relevant
Building Regulations.
10.7 Normal precautions should be taken when working at roof level. The use of protective goggles when cutting and
nailing is recommended.
10.8 The components of the system are easy to work using normal woodworking tools for cutting, drilling and shaping.
Handsaws should have a fine-toothed blade. Hand-held and bench-mounted power tools with a carbide-tipped blade
should be run at speeds similar to, or higher than, those normally used for timber.
10.9 When using power tools to cut or shape the product, it is advisable to use a coarse particle dust mask and eye
protection.
10.10 No special training is required to install the roof trim system correctly, provided the manufacturer’s instructions
and the procedures outlined in section 10 of this Certificate are followed.
11 Procedure
11.1 Selected boards and accessories are assembled and cut to size.
11.2 Rafter feet are cut to a line.
11.3 Noggings, soffit bearers, battens, eaves fillets, brackets and other additional timber supports are fixed to a
sound substrate.
11.4 Protective films should be removed just prior to fixing, ie peeled off as nailing progresses along the board.
11.5 The summary for the installation details of fascia, soffit and barge boards (see sections 11.6 to 11.17) should
be read with reference to the appropriate diagrams in Figures 3 and 4.
Fascia boards
11.6 Fascia boards are fixed to rafter feet at centres not exceeding 600 mm, using two specified ring-shanked nails.
Magnum boards may be fixed directly to rafter feet using 65 mm long nails. For other boards, it is normal practice to fix(1)
to the rafter feet through a 25 mm thick, marine plywood backing board or equivalent previously fixed to the rafter timbers.
(1) Using nails at least 40 mm long.
Page 11 of 12
11.7 Butt joints between fascia boards should be made at the rafter with a 10 mm wide expansion gap between
and with both boards fixed to the rafter foot. A joiner trim is fixed to one board only with a specified 25 mm or 30 mm
long nail or a suitable low-modulus silicone sealant
11.8 At corners, both boards are fixed to sound timber, allowing a 5 mm expansion gap at the end of each board.
A corner trim is fixed to the end of one board as described in section 11.7.
11.9 Internal corner joints are covered by internal corner trims. These are fixed to the end of one board with a low-
modulus neutral-cure silicone as described for the adhesive external corner joint in section 11.8.
11.10 For the Magnum boards, gutter brackets may be fixed directly into the board using, for each bracket, at least
two 25 mm long by 4.8 mm diameter parallel thread form screws recommended by the manufacturer, ensuring that
the screws penetrate the rear face of the board and that the bracket spacings do not exceed 1 metre. For the 9 mm
board, gutter brackets are screwed through the fascia board into the timber support.
Soffit boards
11.11 Soffits are made from cellular soffit boards or rigid hollow soffits. The latter may be used lengthways or in short
lengths at right angles to the wall. To give a tongue-and-groove effect, the indented face should be exposed.
11.12 The soffit should fit into or onto the fascia and into a trim or onto a nogging on the wall.
11.13 The boards are fixed to rafter feet, soffit bearers, or other timber support at centres along their length, not
exceeding 600 mm, and across their width, not exceeding 150 mm, using the specified 30 mm nails.
11.14 Where required, soffit boards may be joined along their length or width using a joint trim.
11.15 To comply with building regulations a ventilator trim is incorporated into the soffit, as necessary.
Barge boards
11.16 Barge boards are installed by fixing fascia boards to a gable ladder, rafter face or noggings using the
procedures given for fascia boards in section 11.6.
11.17 Barge boards meeting at a ridge should be mitred to the appropriate angle.
11.18 Box ends are constructed from fascia board and trims to suit the roof pitch and overhang requirement. Any
timber framework required in the construction of the box end must be preservative treated.
Technical Investigations
12 Tests
Results of tests conducted on the Freefoam White PVC-U Roof Trim System were assessed to determine:
• weight per linear metre
• density
• ash content
• impact strength
• dimensional stability
• resistance to impact after UV ageing
• resistance to impact at low temperature
• accelerated weathering
• natural weathering
• nail pull-through
• water absorption
• heat reversion
• resistance to acetone
• Vicat softening temperature
• flexural strength and modulus of elasticity
• resistance to heat ageing
• resistance to tile and gutter loading.
13 Investigations
13.1 Following the determination of nail pull-through values, calculations were undertaken to establish the resistance of
the product to wind suction.
13.2 The dimensions of cellular boards and trims were checked.
13.3 An assessment was made of the acceptability of the soffit ventilator in meeting ventilation requirements.
13.4 An assessment was made of existing test data relating to:
• surface spread of flame
• colour stability.
Page 12 of 12
13.5 The manufacturing process, including the methods adopted for quality control, were examined and details were
obtained of the quality and composition of the materials used.
13.6 The practicability of installation was assessed.
Bibliography
BS 476-7 : 1997 Fire tests on building materials and structures — Method of test to determine the classification of the
surface spread of flame of products
BS 5250 : 2011 Code of practice for control of condensation in buildings
BS EN 1995-1-1 : 2004 Eurocode 5 : Design of timber structures — General — Common rules and rules for buildings
BS EN 12200-1 : 2000 Plastics rainwater piping systems for above ground external use unplasticized poly(vinyl
chloride) (PVC-U) — Specifications for pipes, fittings and the system
Conditions of Certification
14 Conditions
14.1 This Certificate:
• relates only to the product/system that is named and described on the front page
• is issued only to the company, firm, organisation or person named on the front page — no other company, firm,
organisation or person may hold or claim that this Certificate has been issued to them
• is valid only within the UK
• has to be read, considered and used as a whole document — it may be misleading and will be incomplete to be
selective
• is copyright of the BBA
• is subject to English Law.
14.2 Publications, documents, specifications, legislation, regulations, standards and the like referenced in this Certificate
are those that were current and/or deemed relevant by the BBA at the date of issue or reissue of this Certificate.
14.3 This Certificate will remain valid for an unlimited period provided that the product/system and its manufacture
and/or fabrication, including all related and relevant parts and processes thereof:
• are maintained at or above the levels which have been assessed and found to be satisfactory by the BBA
• continue to be checked as and when deemed appropriate by the BBA under arrangements that it will determine
• are reviewed by the BBA as and when it considers appropriate.
14.4 The BBA has used due skill, care and diligence in preparing this Certificate, but no warranty is provided.
14.5 In issuing this Certificate, the BBA is not responsible and is excluded from any liability to any company, firm,
organisation or person, for any matters arising directly or indirectly from:
• the presence or absence of any patent, intellectual property or similar rights subsisting in the product/system or any
other product/system
• the right of the Certificate holder to manufacture, supply, install, maintain or market the product/system
• actual installations of the product/system, including their nature, design, methods, performance, workmanship and
maintenance
• any works and constructions in which the product/system is installed, including their nature, design, methods,
performance, workmanship and maintenance
• any loss or damage, including personal injury, howsoever caused by the product/system, including its manufacture,
supply, installation, use, maintenance and removal
• any claims by the manufacturer relating to CE marking.
14.6 Any information relating to the manufacture, supply, installation, use, maintenance and removal of this product/
system which is contained or referred to in this Certificate is the minimum required to be met when the product/system
is manufactured, supplied, installed, used, maintained and removed. It does not purport in any way to restate the
requirements of the Health and Safety at Work etc. Act 1974, or of any other statutory, common law or other duty
which may exist at the date of issue or reissue of this Certificate; nor is conformity with such information to be taken as
satisfying the requirements of the 1974 Act or of any statutory, common law or other duty of care.
British Board of Agrément tel: 01923 665300
Bucknalls Lane
fax: 01923 665301
Garston, Watford
e-mail: mail@bba.star.co.uk
Herts WD25 9BA
website: www.bbacerts.co.uk
©2012