Nexus 1450 Power Meter Modbus Manual V.1.02 E171707
User Manual: Pdf Nexus-1450-Meter-Modbus-Manual E171707
Open the PDF directly: View PDF
.
Page Count: 472
| Download | |
| Open PDF In Browser | View PDF |
V.1.02
March 20, 2018
This page intentionally left blank.
Nexus® 1450 High Performance Meter Modbus Protocol User Manual V.1.02
Published by:
Electro Industries/GaugeTech (EIG)
1800 Shames Drive
Westbury, NY 11590
Copyright Notice
All rights reserved. No part of this publication may be reproduced or transmitted in
any form or by any means, electronic or mechanical, including photocopying, recording, or information storage or retrieval systems or any future forms of duplication, for
any purpose other than the purchaser's use, without the expressed written permission
of Electro Industries/GaugeTech.
© 2018 Electro Industries/GaugeTech
Nexus® is a registered trademark of Electro Industries/GaugeTech. The distinctive
shape, style and overall appearance of the Nexus® 1450 meter is a trademark of
Electro Industries/GaugeTech. Communicator EXTTM is a trademark of Electro Industries/GaugeTech.
Windows® is a registered trademark of Microsoft Corporation in the United States
and/or other countries.
Modbus® is a registered trademark of Schneider Electric, licensed to the Modbus
Organization, Inc.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
i
This page intentionally left blank.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
ii
Customer Service and Support
Customer support is available 9:00 am to 4:30 pm, Eastern Standard Time, Monday
through Friday. Please have the model, serial number and a detailed problem description available. If the problem concerns a particular reading, please have all meter
readings available. When returning any merchandise to EIG, a return materials
authorization number is required. For customer or technical assistance, repair or
calibration, phone 516-334-0870 or fax 516-338-4741.
About Electro Industries/GaugeTech (EIG)
Founded in 1975 by engineer and inventor Dr. Samuel Kagan, Electro Industries/
GaugeTech changed the face of power monitoring forever with its first breakthrough
innovation: an affordable, easy-to-use AC power meter.
More than forty years since its founding, Electro Industries/GaugeTech, the leader in
power monitoring and control, continues to revolutionize the industry with the highest
quality, cutting edge power monitoring and control technology on the market today.
An ISO 9001:2015 certified company, EIG sets the industry standard for advanced
power quality and reporting, revenue metering and substation data acquisition and
control. EIG products can be found on site at mainly all of today's leading manufacturers, industrial giants and utilities.
EIG products are primarily designed, manufactured, tested and calibrated at our facility in Westbury, New York.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
iii
This page intentionally left blank.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
iv
Table of Contents
Table of Contents
Copyright Notice i
Customer Service and Support iii
About Electro Industries/GaugeTech (EIG) iii
1: Modbus Protocol Overview 1-1
1.1: Introduction 1-1
1.2: Communication Packets (Modbus RTU) 1-1
1.3: Slave Address and Broadcast Request 1-1
1.4: Function Codes 1-2
1.4.1: Function Code 03H - Read Holding Registers 1-2
1.4.2: Function Code 04H - Read Input Registers 1-3
1.4.3: Function Code 06H - Preset Single Register 1-4
1.4.4: Function Code 10H - Preset Multiple Registers 1-5
1.5: CRC (Error Checksum) Algorithm 1-6
1.6: Dead Time 1-7
1.7: Exception Response (Error Codes) 1-7
1.8: Modbus Extensions 1-8
1.8.1: Function Code 23H - Read Holding Registers Multiple
Times 1-9
2: Modbus Register Map 2-1
2.1: Introduction 2-1
2.2: Modbus Map Holding Registers MM-1
2.3: Modbus Map Input Registers MM-102
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
TOC-1
Table of Contents
3: Communication Data Formats 3-1
3.1: Introduction 3-1
3.2: Type F1 - Null Terminated ASCII String 3-1
3.3: Type F2 - Fixed Length ASCII String 3-2
3.4: Type F3 - Time Stamp 3-2
3.5: Type F4 - Day of Week 3-3
3.6: Type F6 - High Speed Inputs, Delta and Current State 3-3
3.7: Type F7- Secondary Voltage, Current, VA, VAR, Watts, Hz or
Flicker 3-4
3.8: Type F8 - Power Factor 3-5
3.9: Type F9 - Angle 3-6
3.10: Type F10 - Percentage 3-7
3.11: Type F11 - Energy Counter (Packed BCD / Secondary) 3-8
3.12: Type F12 - Energy Counter (Binary / Secondary) 3-9
3.13: Type F13 - Phase Sequence 3-9
3.14: Type F14 - Block/Rolling Window Average Status 3-9
3.15: Type F15 - Limit States 3-11
3.16: Type F16 - Low Speed (Internal) Input States 3-12
3.17: Type F17 - Digital Input States in Digital Input Option Board 3-13
3.18: Type F18 - Digital Input Option Board Input Accumulation /
Cumulative Demand 3-14
3.19: Type F33 - Temperature 3-15
3.20: Type F34 - Limit and Relay Logic States 3-16
3.21: Type F35 - Relay Delays 3-17
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
TOC-2
Table of Contents
3.22: Type F36 - Desired Relay States 3-17
3.23: Type F37 - Relays Pending Update 3-18
3.24: Type F38 Shadowed Relay States 3-19
3.25: Type F39 - Confirmed Polled Relay States 3-20
3.26: Type F40 - Valid Flags for Confirmed Relay States 3-21
3.27: Type F41 - Locked Relays, Relays 1-16 3-22
3.28: Type F42 - Locked Relay States 3-23
3.29: Type F43 - Miscellaneous Flags 3-24
3.30: Type F44 - Digital Input Option Module Data States 3-25
3.31: Type F45 - Analog Input Modules’ Data States 3-26
3.32: Type F46 - High Byte of Modbus Register (Signed) 3-27
3.33: Type F47 - High Byte of Modbus Register (Unsigned) 3-27
3.34: Type F49 - Low Byte of Modbus Register (Unsigned) 3-27
3.35: Type F51 - Two-Byte (Unsigned) 3-27
3.36: Type F52 - Four-Byte (Signed) 3-27
3.37: Type F53 - Four-Byte (Unsigned) 3-27
3.38: Type F55 - Eight-Byte (Unsigned) 3-28
3.39: Type F56 - Flicker Countdown 3-28
3.40: Type F57 - Accumulation in the Interval 3-29
3.41: Type F58 - 12-bit RTU Sanity Register 3-29
3.42: Type F62 - Scaled Pulse Accumulation, Aggregation or Average 3-29
3.43: Type F64 - Scaled Energy 3-31
3.44: Type F65 - Scaled Energy Setting 3-32
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
TOC-3
Table of Contents
3.45: Type F67 - K-Factor 3-33
3.46: Type F68 - Secondary 1 Cycle RMS Voltage and Current 3-34
3.47: Type F69 - Angle 3-34
3.48: Type F70 - Harmonic Over Threshold Flag 3-35
3.49: Type F71 - Out of Range Status 3-36
3.50: Type F72 - Time Stamp (Packed BCD) 3-36
3.51: Type F73 - Magnitude 3-36
3.52: Type F74 - Number 4 Bytes - Unsigned Integer 3-37
3.53: F75 - Flagging 3-37
3.54: Type F76 - Valid Status 3-37
3.55: Type F77 - Voltage Flag 3-38
3.56: Type F78 - Current Flag 3-39
3.57: Type F79 - General Readings (RMS, Ratio…) 3-39
3.58: Type F82 - Point Update Flag 3-40
3.59: Type F83 - Phase Sequence 3-40
3.60: Type F90 - 16.7 usec Counter (Used for duration timestamping.) 3-40
3.61: Type F97 - Hookup Configuration 3-40
3.62: Type F99 - Frequency Type 3-41
3.63: Type F100 - Waveform Sample Rate 3-42
3.64: Type F101 - High Resolution RTC Timestamp 3-42
3.65: Type F102 - Calibration Gain 3-43
3.66: Type F103 - Alternate Format Power Factor 3-43
3.67: Type F105 - RTC Status 3-44
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
TOC-4
Table of Contents
3.68: Type F106 - Line Synch Mode 3-44
3.69: Type F107 - Daylight Savings Time Mode 3-45
3.70: Type F108 - Threshold Enable Channel 3-47
3.71: Type F112 - 16 Bits, General Purpose (Used for status information, including statuses of EN 50160 and TOU.) 3-47
3.72: Type F113 - 32 Bits, General Purpose (Used for status information, including status of EN 50160.) 3-48
3.73: Type F115 - 4 Byte Counter 3-48
3.74: Type F117 - Energy Counter 3-48
3.75: Type F118 - Power Factor 3-49
3.76: Type F119 - Byte Array 3-49
3.77: Type F120 - IEEE 32 bit Single Precision Floating Point 3-49
3.78: Type F122 - Timestamp (packed S-Format) 3-50
3.79: Type F123 - Time-of-Use (TOU) Calendar Entry 3-50
3.80: Type F124 - Time-of-Use (TOU) Rate Change 3-54
3.81: Type F125 - Time-of-Use (TOU) Monitored Data Set Options 3-54
3.82: Type F126 - Time-of-Use (TOU) Monitor Time Timestamp 3-55
4: Modbus Register Map Notes 4-1
5: Information for Downloading Logs 5-1
5.1: Downloading Logs - Overview 5-1
5.1.1 Log Download Using Non-increment Index Method 5-3
5.1.1.1: Steps for Downloading a Log 5-5
5.1.1.2: Downloading Time Stamps with Examples 5-6
5.1.1.3: Downloading Records with Examples 5-9
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
TOC-5
Table of Contents
5.1.2: Log Download Using Auto-Increment Index Method 5-12
5.1.2.1: Download using Auto Increment Window Sequence 5-13
5.1.2.2: Download Using Auto Increment Window Sequence and
Function Code 35 5-14
6: Meter Programmable Settings Block 6-1
6.1: Communication Settings Block (45057-45074) 6-1
6.2: Limit Settings Block (45077-45204) 6-2
6.3 Historical Log Settings Block (45205-45464) 6-4
6.4: High Speed Inputs Settings Block (45501-45723) 6-5
6.5: External Digital Output Module Settings Block (45729-45808) 6-5
6.7: External KYZ Output Module Settings Block (45893-45907) 6-7
6.8: CT & PT Ratio Settings Block (45909-45924) 6-8
6.9: Hookup and Time Settings Block (45925-45944) 6-8
6.10: Average Settings Block (45949-45952) 6-11
6.11: Exception Profile Block (45953-45968) 6-11
6.12: Device Label Settings Block (45969-45992) 6-11
6.13: Network Card Settings Blocks (30153-30208, 51197-51198 - Ports 5 and 6;
30209-30720 - Port 5; 45993-46016, 50785-51154, 52297-52300 - Port 6) 6-12
6.14: Block Window Average External Synchronization Block (46017) 6-16
6.15: Display Configuration Block (46018) 6-17
6.16: Energy Direction Block (46019) 6-17
6.17: Reserved for Future Use (46020) 6-17
6.18: Full Scale Block (46021-46036) 6-17
6.19: External Module Software Interface Block (46053-46196) 6-17
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
TOC-6
Table of Contents
6.20: External Module Port Assignment Block (46197-46206) 6-18
6.21: Manual Control Relay Block (46207-46208) 6-18
6.22: Internal Input Pulse Accumulation Scale Factor Block
(46209-46325) 6-19
6.23: I2t and V2t Threshold Block (46326-46329) 6-19
6.24: Internal KYZ Settings Block (46330-46372) 6-20
6.25: Internal Input Pulse Accumulation Unit Label Block
(46373-46420) 6-22
6.26: ElectroLogic Block (46421-46804) 6-23
6.27: Limit Profile Label Block (46805-47060) 6-23
6.28: External Analog Output Module Channel Update Block
(47061-47062) 6-23
6.29: Miscellaneous DNP Settings Block (47063-47104) 6-24
6.30: Custom DNP Definition Block for Analog Input (Object 30)
(47105-47360) 6-27
6.31: Custom DNP Definition Block for Binary Counter (Object 20)
(47361-47424) 6-28
6.32: Custom DNP Definition Block for Binary Input (Object 1)
(47425-47456) 6-30
6.33: Custom DNP Definition Block for Binary Output (Object 10)
(47457-47458) 6-31
6.34: Custom DNP Definition Block for Global Values (47459-47463) 6-32
6.35: External Digital Output Module Labels Block (49793-50176) 6-32
6.36: Reserved for Future Use (50273-50784) 6-32
6.37: Reserved for Future Use (50785-50860) 6-32
6.38: Reserved for Future Use (51201-51712) 6-32
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
TOC-7
Table of Contents
6.39: Energy Scale Settings (51713-51746) 6-33
6.40: Master RTU Block (51862-52245) 6-35
6.41: Accumulators/Aggregators Average Full Scale (52249-52296) 6-35
6.25: Update Settings Block (52977-53248) 6-36
6.43: Reserved for Future Use (53249-53348) 6-37
6.44: Reserved for Future Use (55296-57344) 6-37
6.45: Waveform and PQ Settings 6-37
7: Register Block Titles 7-1
7.1: Device Identification Block (00001-00080) 7-1
7.2: Real Time Block (00081-00089) 7-1
7.3: 1 Cycle Block (00090-00118) 7-3
7.4: High Speed Block (00119-00175) 7-4
7.5: One Second Block (00176-00235) 7-4
7.6: Thermal Average Block (00236-00295) 7-4
7.7: Maximum Block (00296-00396) 7-5
7.8: Minimum Block (00397-00497) 7-5
7.9: Maximum Time Stamp Block (00498-00737) 7-5
7.10: Minimum Time Stamp Block (00738-00977) 7-5
7.11: Energy Block (Secondary) (00978-01021) 7-6
7.12: Harmonic Magnitude Block (01022-01789) 7-6
7.13: Harmonic Phase Block (01790-02557) 7-6
7.14: THD/K-Factor Block (02558-02566) 7-6
7.15: Harmonic Time Stamp Block (02567-02590) 7-6
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
TOC-8
Table of Contents
7.16: Phase Angle Block (02591-02604) 7-6
7.17: Block Window Average Block (02605-02683) 7-7
7.18: Rolling Window/Predictive Rolling Window Block
(02684-02768) 7-7
7.19: Limit Block (02769-02773) 7-7
7.20: Reserved for Future Use (02774-02841) 7-7
7.21: Internal Input Pulse Accumulation Block (05745-05796) 7-8
7.22: Pulse Accumulation Block Window Average / Maximum Block
(05797-05945) 7-8
7.23: Temperature (05946) 7-8
7.24: Analog Input Block (05947-05978) 7-8
7.25: Limit Combination Block (05979-05980) 7-8
7.26: Relay Logic Block (05981-06014) 7-8
7.27: Reset Time Block (06015-06038) 7-9
7.28: Reserved for Future Use (06040-06076) 7-9
7.29: KYZ Output Accumulation Block (06097-06110) 7-9
7.30: Input Option Board Data Status Block (06111-06112) 7-9
7.31: Flicker Status Block (06114-06126) 7-9
7.32: Instantaneous Flicker Block (06127-06136) 7-9
7.33: Short Term Flicker Block (06137-06186) 7-10
7.34: Long Term Flicker Block (06187-06236) 7-10
7.35: Additional Energy Block (06237-06392) 7-10
7.36: Energy and Pulses in the Interval Block (06393-006488) 7-11
7.37: Flicker Countdown Block (06489-006490) 7-11
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
TOC-9
Table of Contents
7.38: Cumulative Demand Block (06491-006502) 7-12
7.39: Uncompensated and Q Block (06665-06907) 7-12
7.40: Scaled Energy Block (06908-07829) 7-12
7.41: Reserved for Future Use (07830-07859) 7-13
7.42: Negative Maximum Pulse Aggregation Average Block
(07864-07895) 7-13
7.43: Reserved for Future Use (07896-07910) 7-13
7.44: New Demand Block (Either Block Window Average or
Sliding Window Average (07928-08039) 7-13
7.45: Scratchpad Block (08193 - 08320) 7-13
7.46: Master Device Data Block (08449-08704) 7-13
7.47: EN 50160/IEC 61000-4-30 Power Quality Test (08705-11054) 7-14
7.48: Frozen Energy Blocks (11265-11650) 7-14
7.49: Previous Block Window Average Block (11651-11742) 7-14
7.50: Previous Rolling Window Average Block (11743-11834) 7-14
7.51: Previous Scaled Energy Block (11835-11894) 7-14
7.52: One Second Three Phase Mean RMS Block (11895-11900) 7-14
7.53: Block Window Max/Min and 10 Minute Mean THD Block
(11901-12138) 7-14
7.54: Coincident Power Factor (12141-12156) 7-14
7.55: Customized Modbus Block (12289-14336) 7-15
7.56: Nexus Master Polling Data Block (14337-14604) 7-15
7.57: Additional and Vpe Block (14849-14942) 7-15
7.58: Block Window, Max/Min Block, P-E 7-15
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
TOC-10
Table of Contents
7.59: Enhanced Factory Settings Block (16385-24576) 7-15
7.60: Enhanced Programmable Settings Block (24577-32768) 7-15
7.61: TOU Status Section Block (34817-34826) 7-15
7.62: TOU Profile Section Block (34833-36608) 7-16
7.63: Reserved for Future Use (36737-36800) 7-16
7.64: Historical Log 1 Snapshot Header (36865-36883) 7-16
7.65: Historical Log 2 Snapshot Header (36929-36947) 7-17
7.66: System Event Log Header (37505-37526) 7-17
7.67: External Device Information Block Header (37761-37778) 7-19
7.68: External Device Programming Block Header (37825-37842) 7-20
7.69: Device History Block Header (37889-37906) 7-21
7.70: Direct Memory Access Header (37953-37970) 7-21
7.71: Window Index Block (38145-38162) 7-21
7.72: Window Mode Block (38209-38226) 7-23
7.73: Window Block (38273-39424) 7-25
7.74: Auto Increment Window Block (39423-39488) 7-27
7.75: Alarm Block (40961-41105) 7-29
7.76: TOU Action Log Header (41217-41240) 7-32
7.77: TOU Month/Season Log Header (41281-41304) 7-32
7.78: Port Control Block (41729-42496) 7-32
7.79: Reserved for Future Use (44545-44578) 7-35
7.80: Programmable Settings Block 1 (45057-57344) 7-35
7.81: Action Block - Resetting Meter Registers (57345-57517) 7-36
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
TOC-11
Table of Contents
7.82: Device Identification Block 2 (65088-65280) 7-39
7.83: Password Block (65316-65344) 7-40
8:Alternative Method for Downloading Logs 8-1
8.1: Overview 8-1
8.2: Historical Log 1 Format 8-1
8.3: Historical Log 2 Format 8-3
8.4: System Event Log Format 8-5
9: Additional Procedures 9-1
9.1: Overview 9-1
9.2: Port Locking - Overview 9-1
9.2.1: Sequence for Port Locking 9-1
9.2.2: Transmission 9-2
9.2.3: Reception 9-2
9.2.4: Port Unlocking Sequence 9-2
9.3: Updating Programmable Settings 9-3
9.4: Time of Use Information 9-11
Glossary GL-1
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
TOC-12
1: Modbus Protocol Overview
1: Modbus Protocol Overview
1.1: Introduction
The Nexus® 1450 meter can communicate with other devices using the RTU
transmission mode of the AEG Modicon Modbus protocol.
• RS485 communication supports multiple Nexus® meters connected on a network.
It is a two-wire connection operating up to 115200 baud.
• See the Nexus® 1450 Meter Installation and Operation Manual for wiring details.
1.2: Communication Packets (Modbus RTU)
Communication takes place between a Modbus master and one or more Nexus® slave
devices. The master device initiates all communication by transmitting an information
packet, called the "request," to a specific slave device. The slave replies with its own
packet, called the "response." A packet is a serial string of 8-bit bytes consisting of
the following:
Slave Address
1 byte
Function Code
1 byte
Data
N bytes: high-ordered byte first, low-order
byte second
CRC (RTU Error Checksum)
2 bytes
Dead Time
3.5 bytes transmission time
A single packet can transmit a maximum of 125 registers.
1.3: Slave Address and Broadcast Request
Each slave device on a communication bus has its own unique address. Only the slave
addressed by a master will respond. The response packet returned to the master will
have the same value in the slave address field as the request packet. Addresses are
programmable and range from 1 to 247.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
1-1
1: Modbus Protocol Overview
A slave address of 0 is a broadcast command that allows the master to send the same
packet to all devices at once. All slaves will obey the packet's instructions, but none
will respond. The broadcast request feature is available only with function codes 6 and
10, preset single registers, and preset multiple registers, respectively. See Tables 1.3
and 1.4.
1.4: Function Codes
A packet's function code tells the addressed slave what action to perform. The
Nexus® 1450 meter supports the following Modbus function codes:
Table 1.1: Function Codes
Hex
Dec
Description
03H
3
Read Holding
Registers
04H
4
Read Input
Registers
06H
6
Preset Single
Register
10H
16
Preset Multiple
Registers
1.4.1: Function Code 03H - Read Holding Registers
This function allows a master station to read one or more parameter values (data
registers) from a Nexus® meter slave. The data registers are 16-bit (two byte) values
transmitted in "Big Endian" format: high-ordered byte first, low-ordered byte second.
The master device sends a packet defining a start register for the slave and the
number of registers to read. The slave responds with a packet containing the
requested parameter values within the range specified in the request.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
1-2
1: Modbus Protocol Overview
In the following example, a master device requests a Nexus® meter slave at address
01H to transmit two values beginning at register 00001. The slave replies with values
3031H and 3037H from registers 00001 and 00002.
Table 1.2: Function Code 03H Example
Master Packet
Slave Packet
Slave Address
01H
Slave Address
01H
Function Code
03H
Function Code
03H
Data Starting Address - Hi
00H
Byte Count
04H
Data Starting Address - Lo
00H
Data 1-Hi
30H
Number of Registers - Hi
00H
Data 1-Lo
31H
Number of Registers - Lo
02H
Data 2-Hi
30H
CRC-Lo
C4H
Data 2-Lo
37H
CRC-Hi
0BH
CRC-Lo
F1H
CRC-Hi
2AH
1.4.2: Function Code 04H - Read Input Registers
This function allows a master station to read one or more parameter values (data
registers) from a Nexus® meter slave. The data registers are 16-bit (two byte) values
transmitted in "Big Indian" format: high-ordered byte first, low-ordered byte second.
The master device sends a packet defining a start register for the slave and the
number of registers to read. The slave responds with a packet containing the
requested parameter values within the range specified in the request.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
1-3
1: Modbus Protocol Overview
In the following example, a master device requests a Nexus® meter slave at address
01H to transmit two values beginning at register 00001. The slave replies with values
3031H and 3037H from registers 00001 and 00002.
Table 1.3: Function Code 04H Example
Master Packet
Slave Packet
Slave Address
01H
Slave Address
01H
Function Code
04H
Function Code
04H
Data Starting Address - Hi
00H
Byte Count
04H
Data Starting Address - Lo
00H
Data 1-Hi
30H
Number of Registers - Hi
00H
Data 1-Lo
31H
Number of Registers - Lo
02H
Data 2-Hi
30H
CRC-Lo
C4H
Data 2-Lo
37H
CRC-Hi
0BH
CRC-Lo
F1H
CRC-Hi
2AH
1.4.3: Function Code 06H - Preset Single Register
This function allows a master station to modify a single register in a Nexus® meter
slave. The data registers are 16-bit (two byte) values transmitted high-ordered byte
first, low-ordered byte second.
In the following example, a master device stores the value 0001H at register 57346 in
a Nexus® meter slave at address 01H.
Table 1.4: Function Code 6H Example
Master Packet
Slave Packet
Slave Address
01H
Slave Address
01H
Function Code
06H
Function Code
06H
Data Starting Address- Hi
E0H
Data Starting Address - Hi
E0H
Data starting Address-Lo
01H
Data Starting Address-Lo
01H
Data-Hi
00H
Data-Hi
00H
Data-Lo
01H
Data-Lo
01H
CRC-Lo
2EH
CRC-Lo
2EH
CRC-Hi
0AH
CRC-Hi
0AH
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
1-4
1: Modbus Protocol Overview
1.4.4: Function Code 10H - Preset Multiple Registers
This function allows a master station to modify a group of consecutive registers in a
Nexus® meter slave. Registers are 16-bit (two byte) values transmitted high-ordered
byte first, low-ordered byte second.
In the following example, a master device stores the value 0001H at register 57345,
0001H at register 57346, and 0001H at register 57347 in a Nexus® meter slave at
address 01H.
Table 1.5: Function Code 10H Example
Master Packet
Slave Packet
Slave Address
01H
Slave Address
01H
Function Code
10H
Function Code
10H
Data Starting Address- Hi
E0H
Data Starting Address Hi
E0H
Data starting Address-Lo
01H
Data Starting AddressLo
01H
Number of Setpoints-Hi
00H
Number of Setpoints-Hi
00H
Number of Setpoints-Lo
03H
Number of SetpointsLo
03H
Byte Count
06H
CRC-Lo
E6H
Data #1-Hi
00H
CRC-Hi
08H
Data #1-Lo
01H
Data #2-Lo
00H
Data #2-Hi
01H
Data #3-Lo
00H
Data #3-Hi
01H
CRC-Lo
4DH
CRC-Hi
46H
NOTE: The Modbus map address range in hexadecimal is 0000H - FFFFH; and in
decimal is 00001 - 65536. The addresses given in the Nexus® 1450 Meter Modbus
Register Map in Chapter 2 are in decimal. For some SCADA software, to read holding
registers (see Section 1.4.1: Function Code 03H - Read Holding Registers on page 12), the address format should be: 4(XXXXX), with the XXXXX being the decimal
address.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
1-5
1: Modbus Protocol Overview
1.5: CRC (Error Checksum) Algorithm
The Cyclic Redundancy Check (CRC) field is an error checksum calculation that
enables a slave device to determine if a request packet has been corrupted during
transmission.
Every request packet transmitted from master to slave includes a special 16-bit value
derived from a CRC-16 algorithm performed on the packet's contents. When a
Nexus® meter slave receives a packet, it performs a CRC-16 calculation and
compares the value with the one included in the request packet. If the two values do
not match, the slave will ignore the packet.
Following is the pseudocode for calculating the 16-bit CRC:
Initialize a 16-bit register to FFFFH.
Initialize the generator polynomial to A001H.
FOR n=1 to # of bytes in packet
XOR nth data byte with the 16-bit register
FOR bits_shifted = 1 to 8
SHIFT 1 bit to the right
IF (bit shifted out EQUAL 1)
XOR generator polynomial with the 16-bit register
and store result in the 16-bit register
END IF
END FOR
END FOR
The resulting 16-bit register contains the CRC-16 checksum.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
1-6
1: Modbus Protocol Overview
1.6: Dead Time
A Nexus® meter slave considers a transmission from a master complete when it has
received no data for a period of 3.5 byte transmission times - approximately 7 ms at
4800 baud and 300 microseconds at 115200 baud. If the master transmits, with any
gaps between bytes that are longer than this time period, the slaves will perceive it as
dead time. At the conclusion of the dead time, all unaddressed slaves begin listening
for a new packet from the master.
1.7: Exception Response (Error Codes)
A Nexus® meter slave will send its master an exception response packet if it has
encountered an invalid command or other problem while carrying out the master's
instructions. The function code of the response will have the most significant bit set.
The data field of the exception Response contains an error code specific to the type of
problem.
Table 1.5 lists the different error codes supported by the Nexus® 1450 meter.
Table 1.5: Exception Response (Error Codes)
Error Code
Name
Description
01
Illegal Function
The slave does not support the function code of
the transmitted request packet.
02
Illegal Data Address
The slave does not recognize the address in the
data field of the transmitted request packet.
03
Illegal Data Value
The value referenced in the transmitted request
packet is not supported by the register on the
Nexus® meter slave.
06
Busy, Rejected Packet
The slave is busy performing a long operation
and cannot receive the request packet.
0Ah
Gateway Paths Not
Available
Used for Modbus TCP when the 2nd RS485 port
is configured as a Ethernet Gateway.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
1-7
1: Modbus Protocol Overview
In the following example, a master Device requests a Nexus® meter slave at address
01H to transmit the value at register 00256. The slave replies with an error, indicating
that it is busy.
Table 1.6: Exception Response Example
Master Packet
Slave Packet
Address
01H
Address
01H
Function Code
03H
Function
Code
83H
Data Starting Address- Hi
01H
Error Code
06H
Data starting Address-Lo
00H
CRC-Lo
C1H
Number of Registers-Hi
00H
CRC-Hi
32H
Number of Registers-Lo
01H
CRC-Lo
85H
CRC-Hi
F6H
1.8: Modbus Extensions
Modbus read requests have a maximum size when using standard Modbus function.
EIG developed Enhanced (Non-Standard) Modbus read requests to allow larger than
standard responses. This requires fewer requests and, is therefore, more efficient.
Also, total download time is reduced.
This function is also more efficient with log retrieval. It allows the network card(s) to
communicate with the main unit using DNP protocol, utilizing a Modbus connection.
As part of the non-standard extensions to the Modbus protocol, the Nexus® 1450
meter supports the following additional Modbus function codes:
Modbus Extensions
Function Code
Hex
Dec
23H
35
Description
Read Holding Registers Multiple Times
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
1-8
1: Modbus Protocol Overview
1.8.1: Function Code 23H - Read Holding Registers Multiple
Times
This function allows a master station to read the binary contents of holding registers
(4X references) in the slave multiple times. Broadcast is not supported.
The master device sends a packet defining the starting register, quantity of registers
to be read, and the repeat count. Registers are addressed starting at zero, i.e., registers 1-16 are addressed as 0-15.
Here is an example of a request to read registers 40108-40110 twice from slave
device 17:
Function Code
Example
(Hex)
Field Name
Slave Address
11
Function Code
23
Data Starting Address-Hi
00
Data Starting Address-Lo
6B
Number of Registers-Hi
00
Number of Registers-Lo
03
Repeat Count
02
Error Check (LRC or CRC)
The register data in the response message is packed as two bytes per register, with
the binary contents right justified within each byte. For each register, the first byte
contains the high order bits and the second contains the low order bits.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
1-9
1: Modbus Protocol Overview
Data is scanned at the following maximum rates, depending on the repeat count:
Repeat Count
RTU Framing
ASCII Framing
1
509 Registers
253 Registers
2
254 Registers
126 Registers
3
169 Registers
84 Registers
4
127 Registers
63 Registers
5
101 Registers
50 Registers
6
84 Registers
42 Registers
7
72 Registers
36 Registers
The response is returned when the data is completely assembled. Here is an example
of a response to the data given earlier:
Function Code 23H/43H Example (Response)
Example
(Hex)
Field Name
Slave Address
11
Function Code
23
Byte Count Hi
00
Byte Count Lo
0C
Data Hi (Register 40108, First Read)
02
Data Lo (Register 40108, First Read)
2B
Data Hi (Register 40109, First Read)
00
Data Lo (Register 40109, First Read)
00
Data Hi (Register 40110, First Read)
00
Data Lo (Register 40110, First Read)
64
Data Hi (Register 40108, Second Read)
02
Data Lo (Register 40108, Second Read)
2B
Data Hi (Register 40109, Second Read)
00
Data Lo (Register 40109, Second Read)
00
Data Hi (Register 40110, Second Read)
00
Data Lo (Register 40110, Second Read)
64
Error Check (LRC or CRC)
--
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
1-10
1: Modbus Protocol Overview
The contents of register 40108 are shown as the two-byte values of 02 2B hexadecimal or 555 decimal. The contents of registers 40109 - 40110 is 00 00 and 00 64
hexadecimal or 0 and 100 decimal.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
1-11
1: Modbus Protocol Overview
This page intentionally left blank.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
1-12
2: Modbus Register Map
2: Modbus Register Map
2.1: Introduction
The Nexus® 1450 meter’s Modbus register map begins on the following page. First
the Holding Registers section is shown, then the Input Registers section is shown.
• One second readings use the One Second block, registers 00176-00235, described
in Section 7.5: One Second Block (00176-00235) on page 7-4.
• Resetting maximums, minimums, energy readings and/or logs use the Action block,
registers 57345-57393, described in Section Section 7.7: Maximum Block (0029600396) on page 7-5 and Section 7.8: Minimum Block (00397-00497) on page 7-5.
• Time may be set in the Nexus® meter using the Real Time block, registers 0008100089, described in Section 7.2: Real Time Block (00081-00089) on page 7-1.
The remainder of this manual elaborates on aspects of the Modbus register map.
• Chapter 3 gives a detailed description of communication formats referred to in the
register map's "Type" column. See the Table of Contents for a list of the register
map's "Types" and the pages on which they are explained.
• Chapter 4 gives an explanation of the register map's "Notes" column.
• Chapter 5 gives explanation on, and instructions for downloading logs.
• Chapter 6 gives instructions on Large Data Access (LDA) and downloading logs.
• Chapter 7 gives an explanation of the Programmable Settings blocks.
• Chapter 8 gives descriptions of all the Nexus® 1450 meter Modbus register map's
register Block titles and the registers included in each block.
• Chapter 9 gives instructions on an alternative method of downloading logs.
• Chapter 10 gives instructions on additional procedures: port control, updating programmable settings, TOU modifications, and calibration.
• The Glossary gives an explanation of terminology.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
2-1
2: Modbus Register Map
• Note that depending on the meter’s security settings, some readings may be
unavailable until the user provides the proper authentication information (username and password).
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
2-2
2: Modbus Map - Holding Registers
2.2: Modbus Map Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
0000H-0007H
0008H-000FH
0010H-0017H
0018H-001FH
0020H-0027H
0028H-002FH
0030H-0037H
0038H-003FH
0040H-0047H
Identification Block
00001-00008
00009-00016
00017-00024
00025-00032
00033-00040
00041-00048
00049-00056
00057-00064
00065-00072
0
1
1
1
1
1
1
1
1
0
0
1
2
3
4
5
6
7
0048H-0049H
00073-00074
2
0
004AH-004BH
004CH-004FH
00075-00076
00077-00080
Real Time Block
00081-00084
00085-00088
00089
One Cycle Block
00090-0093
00094-0095
00096-0097
00098-0099
00100-0101
00102-0103
00104-0105
00106-0107
00108-0109
00110-0111
00112-0113
00114-0115
00116-0117
00118
High Speed
00119-00122
00123-00124
00125-00126
00127-00128
00129-00130
00131-00132
00133-00134
00135-00136
00137-00138
00139-00140
00141-00142
00143-00144
00145-00146
00147-00148
00149-00150
00151-00152
00153-00154
00155-00156
00157-00158
00159-00160
00161-00162
00163-00164
00165-00166
00167-00168
00169-00170
3
0
6
7
8
0
0
0
9
10
10
10
11
12
12
12
13
15
14
14
14
16
0
0
1
2
0
0
1
2
0
0
0
1
2
0
17
18
18
18
19
20
20
20
21
22
22
22
23
23
23
24
25
25
25
26
27
27
27
28
29
0
0
1
2
0
0
1
2
0
0
1
2
0
1
2
0
0
1
2
0
0
1
2
0
0
0050H-0053H
0054H-0057H
0058H
0059H-005CH
005DH-005EH
005FH-0060H
0061H-0062H
0063H-0064H
0065H-0066H
0067H-0068H
0069H-006AH
006BH-006CH
006DH-006EH
006FH-0070H
0071H-0072H
0073H-0074H
0075H
0076H-0079H
007AH-007BH
007CH-007DH
007EH-007FH
0080H-0081H
0082H-0083H
0084H-0085H
0086H-0087H
0088H-0089H
008AH-008BH
008CH-008DH
008EH-008FH
0090H-0091H
0092H-0093H
0094H-0095H
0096H-0097H
0098H-0099H
009AH-009BH
009CH-009DH
009EH-009FH
00A0H-00A1H
00A2H-00A3H
00A4H-00A5H
00A6H-00A7H
00A8H-00A9H
DNP
Obj
Description
Range
Device Name
Firmware Variation String 1
Firmware Variation String 2
Firmware Variation String 3
Firmware Variation String 4
Firmware Variation String 5
Firmware Variation String 6
Firmware Variation String 7
Firmware Variation String 8
Nexus Comm Boot Version Number (Major). See also register
0xFD00-0xFD01 for Minor
9.9.9.9 / 0.0.0.0
Nexus Comm Run-Time Version Number (Major). See also register
0xFD07-0xFD08 for Minor
9.9.9.9 / 0.0.0.0
Removed
50
50
50
50
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Units
Type
R/W
F1
F1
F1
F1
F1
F1
F1
F1
F1
R
R
R
R
R
R
R
R
R
0.0.0.1 version
F2
R
0.0.0.1 version
F2
R
On Time
Current Time
Current Day of the Week
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
Sunday - Saturday
10 msec
10 msec
F3
F3
F4
R
R/W
R
One cycle Block Time Stamp
One cycle Phase A-N Voltage
One cycle Phase B-N Voltage
One cycle Phase C-N Voltage
One cycle Vaux Voltage
One cycle Phase A Current
One cycle Phase B Current
One cycle Phase C Current
One cycle Measured Neutral Current (Iaux)
One cycle Calculated Neutral Current (Ires)
One cycle Phase A-B Voltage
One cycle Phase B-C Voltage
One cycle Phase A-C Voltage
One cycle High Speed Input Delta and Current State
12/31/9999 23:59:59.99
10 msec
F3
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F6
R
R
R
R
R
R
R
R
R
R
R
R
R
R
High Speed Block Time Stamp
High Speed Phase A-N Voltage
High Speed Phase B-N Voltage
High Speed Phase C-N Voltage
High Speed Vaux Voltage
High Speed Phase A Current
High Speed Phase B Current
High Speed Phase C Current
High Speed Measured Neutral Current
High Speed Phase A-B Voltage
High Speed Phase B-C Voltage
High Speed Phase A-C Voltage
High Speed Phase A VA
High Speed Phase B VA
High Speed Phase C VA
High Speed Three Phase VA
High Speed Phase A VAR
High Speed Phase B VAR
High SpeedPhase C VAR
High Speed Three Phase VAR
High Speed Phase A Watts
High Speed Phase B Watts
High Speed Phase C Watts
High Speed Three Phase Watts
High Speed Frequency
12/31/9999 23:59:59.99
+32767 V / 0 V
+32767 V / 0 V
+32767 V / 0 V
+ 32767 V / 0 V
+32767 V / 0 V
+32767 V / 0 V
+32767 V / 0 V
+32767 V / 0 V
+32767 V / 0 V
+32767 V / 0 V
+32767 V / 0 V
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VAR / -32768 VAR
+32767 VAR / -32768 VAR
+32767 VAR / -32768 VAR
+32767 VAR / -32768 VAR
+32767 W / -32768 W
+32767 W / -32768 W
+32767 W / -32768 W
+32767 W / -32768 W
+32767 Hz / 0 Hz
10 msec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 VA sec
1/ 65536 VA sec
1/ 65536 VA sec
1/ 65536 VA sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 Hz
F3
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
1
1, 2
1, 2
1
4
4
4
4
6
6
6
4
4
4
9
9
9
9
9
9
9
9
9
9
9
9
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-1
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
00AAH
00ABH
00ACH
00ADH
00171
00172
00173
00174
30
30
30
31
0
1
2
0
30
30
30
30
00AEH
00175
One Second Block
00176-00179
00180-00181
00182-00183
00184-00185
00186-00187
00188-00189
00190-00191
00192-00193
00194-00195
00196-00197
00198-00199
00200-00201
00202-00203
00204-00205
00206-00207
00208-00209
00210-00211
00212-00213
00214-00215
00216-00217
00218-00219
00220-00221
00222-00223
00224-00225
00226-00227
00228-00229
00230
00231
00232
00233
00234
00235
Block
00236-00239
00240-00241
00242-00243
00244-00245
00246-00247
00248-00249
00250-00251
00252-00253
00254-00255
00256-00257
00258-00259
00260-00261
00262-00263
00264-00265
00266-00267
00268-00269
00270-00271
00272-00273
00274-00275
00276-00277
00AFH-00B2H
00B3H-00B4H
00B5H-00B6H
00B7H-00B8H
00B9H-00BAH
00BBH-00BCH
00BDH-00BEH
00BFH-00C0H
00C1H-00C2H
00C3H-00C4H
00C5H-00C6H
00C7H-00C8H
00C9H-00CAH
00CBH-00CCH
00CDH-00CEH
00CFH-00D0H
00D1H-00D2H
00D3H-00D4H
00D5H-00D6H
00D7H-00D8H
00D9H-00DAH
00DBH-00DCH
00DDH-00DEH
00DFH-00E0H
00E1H-00E2H
00E3H-00E4H
00E5H
00E6H
00E7H
00E8H
00E9H
00EAH
00EBH-00EEH
00EFH-00F0H
00F1H-00F2H
00F3H-00F4H
00F5H-00F6H
00F7H-00F8H
00F9H-00FAH
00FBH-00FCH
00FDH-00FEH
00FFH-0100H
0101H-0102H
0103H-0104H
0105H-0106H
0107H-0108H
0109H-010AH
010BH-010CH
010DH-010EH
010FH-0110H
0111H-0112H
0113H-0114H
Description
High Speed Phase A Power Factor
High Speed Phase B Power Factor
High Speed Phase C Power Factor
High Speed Three Phase Power Factor
Range
Units
Type
R/W
3.999 / 0.000
3.999 / 0.000
3.999 / 0.000
3.999 / 0.000
0.001 PF
0.001 PF
0.001 PF
0.001 PF
F8
F8
F8
F8
R
R
R
R
32
0
30
High Speed Phase A-N Voltage to Auxiliary Voltage Phase Angle
+ 180 / - 180
0.01 degree
F9
R
33
34
34
34
35
36
36
36
37
38
39
39
39
40
40
40
41
42
42
42
43
44
44
44
45
46
47
47
47
48
49
49
0
0
1
2
0
0
1
2
0
0
0
1
2
0
1
2
0
0
1
2
0
0
1
2
0
0
0
1
2
0
0
1
50
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
One second Block Time Stamp
One second Phase A-N Voltage
One second Phase B-N Voltage
One second Phase C-N Voltage
One second Vaux Voltage
One second Phase A Current
One second Phase B Current
One second Phase C Current
One second Measured Neutral Current
One second Calculated Neutral Current
One second Phase A-B Voltage
One second Phase B-C Voltage
One second Phase C-A Voltage
One second Phase A VA
One second Phase B VA
One second Phase C VA
One second VA
One second Phase A VAR
One second Phase B VAR
One second Phase C VAR
One second Three VAR
One second Phase A Watts
One second Phase B Watts
One second Phase C Watts
One second Watts
One second Frequency
One second Phase A Power Factor
One second Phase B Power Factor
One second Phase C Power Factor
One second Three Phase Power Factor
One second Voltage Imbalance
One second Current Imbalance
12/31/9999 23:59:59.99
+ 32767 V / 0 V
+ 32767 V / 0 V
+ 32767 V / 0 V
+ 32767 V / 0 V
+32767 A / 0 A
+32767 A / 0 A
+32767 A / 0 A
+32767 A / 0 A
+32767 A / 0 A
+ 32767 V / 0 V
+ 32767 V / 0 V
+ 32767 V / 0 V
+ 32767 V / 0 V
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VAR / -32768 VAR
+32767 VAR / -32768 VAR
+32767 VAR / -32768 VAR
+32767 VAR / -32768 VAR
+32767 W / -32768 W
+32767 W / -32768 W
+32767 W / -32768 W
+32767 W / -32768 W
+ 32767 Hz / 0 Hz
3.999 / 0
3.999 / 0
3.999 / 0
3.999 / 0
+327.67% / -327.68%
+327.67% / -327.68%
10 msec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 VA sec
1/ 65536 VA sec
1/ 65536 VA sec
1/ 65536 VA sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 Hz
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.01%
0.01%
F3
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F8
F8
F8
F8
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
50
51
51
51
52
53
53
53
54
55
56
56
56
57
57
57
58
59
59
59
0
0
1
2
0
0
1
2
0
0
0
1
2
0
1
2
0
0
1
2
50
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Thermal Average Block Time Stamp
Thermal Average Phase A-N Voltage
Thermal Average Phase B-N Voltage
Thermal Average Phase C-N Voltage
Thermal Average Aux Voltage
Thermal Average Phase A Current
Thermal Average Phase B Current
Thermal Average Phase C Current
Thermal Average Measured Neutral Current
Thermal Average Calculated Neutral Current
Thermal Average Phase A-B Voltage
Thermal Average Phase B-C Voltage
Thermal Average Phase C-A Voltage
Thermal Average Phase A VA
Thermal Average Phase B VA
Thermal Average Phase C VA
Thermal Average VA
Thermal Average Phase A VAR
Thermal Average Phase B VAR
Thermal Average Phase C VAR
12/31/9999 23:59:59.99
+ 32767 V / 0 V
+ 32767 V / 0 V
+ 32767 V / 0 V
+ 32767 V / 0 V
+ 32767 A / 0 A
+ 32767 A / 0 A
+ 32767 A / 0 A
+ 32767 A / 0 A
+ 32767 A / 0 A
+ 32767 V / 0 V
+ 32767 V / 0 V
+ 32767 V / 0 V
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VAR / -32768 VAR
+32767 VAR / -32768 VAR
+32767 VAR / -32768 VAR
10 msec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 VA sec
1/ 65536 VA sec
1/ 65536 VA sec
1/ 65536 VA sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
F3
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
1
4
4
4
4
6
6
6
6
4
4
4
9
9
9
9
9
9
9
9
9
9
9
9
1
4
4
4
4
6
6
6
6
4
4
4
9
9
9
9
9
9
9
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-2
2: Modbus Map - Holding Registers
Addr. (hex)
0115H-0116H
0117H-0118H
0119H-011AH
011BH-011CH
011DH-011EH
011FH-0120H
0121H
0122H
0123H
0124H
0125H
0126H
0127H-012AH
012BH-012CH
012DH-012EH
012FH-0130H
0133H-0134H
0135H-0136H
0137H-0138H
0139H-013AH
013BH-013CH
013DH-013EH
013FH-0140H
0141H-0142H
0143H-0144H
0145H-0146H
0147H-0148H
0149H-014AH
014BH-014CH
014DH-014EH
014FH-0150H
0151H-0152H
0153H-0154H
0155H-0156H
0157H-0158H
0159H-015AH
015BH-015CH
015DH-015EH
015FH-0160H
0161H-0162H
0163H-0164H
0165H-0166H
0167H-0168H
0169H-016AH
016BH-016CH
016DH
016EH
016FH
0170H
0171H
0172H
0173H
0174H
0175H
0176H
0177H
0178H
0179H
Address(4X)
00278-00279
00280-00281
00282-00283
00284-00285
00286-00287
00288-00289
00290
00291
00292
00293
00294
00295
Maximum Block
00296-00299
00300-00301
00302-00303
00304-00305
00308-00309
00310-00311
00312-00313
00314-00315
00316-00317
00318-00319
00320-00321
00322-00323
00324-00325
00326-00327
00328-00329
00330-00331
00332-00333
00334-00335
00336-00337
00338-00339
00340-00341
00342-00343
00344-00345
00346-00347
00348-00349
00350-00351
00352-00353
00354-00355
00356-00357
00358-00359
00360-00361
00362-00363
00364-00365
00366
00367
00368
00369
00370
00371
00372
00373
00374
00375
00376
00377
00378
Line
Pt
DNP
Obj
Range
Units
Type
R/W
60
61
61
61
62
63
64
64
64
65
66
66
0
0
1
2
0
0
0
1
2
0
0
1
30
30
30
30
30
30
30
30
30
30
30
30
Thermal Average VAR
Thermal Average Phase A Watts
Thermal Average Phase B Watts
Thermal Average Phase C Watts
Thermal Average Watts
Thermal Average Frequency
Thermal Average Phase A Power Factor
Thermal Average Phase B Power Factor
Thermal Average Phase C Power Factor
Thermal Average Power Factor
Thermal Average Voltage Imbalance
Thermal Average Current Imbalance
+32767 VAR / -32768 VAR
+32767 W / -32768 W
+32767 W / -32768 W
+32767 W / -32768 W
+32767 W / -32768 W
+ 32767 Hz / 0 Hz
3.999 / 0
3.999 / 0
3.999 / 0
3.999 / 0
+327.67% / -327.68%
+327.67% / -327.68%
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 Hz
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.01%
0.01%
F7
F7
F7
F7
F7
F7
F8
F8
F8
F8
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
9
9
9
9
9
67
68
68
68
70
70
70
71
72
73
73
73
74
74
74
75
76
76
76
77
78
78
78
79
80
80
80
81
82
82
82
83
84
85
85
85
86
87
87
87
88
89
89
89
90
91
0
0
1
2
0
1
2
0
0
0
1
2
0
1
2
0
0
1
2
0
0
1
2
0
0
1
2
0
0
1
2
0
0
0
1
2
0
0
1
2
0
0
1
2
0
0
50
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Maximum Block Time Stamp
Maximum Thermal Average Phase A-N Voltage
Maximum Thermal Average Phase B-N Voltage
Maximum Thermal Average Phase C-N Voltage
Maximum Thermal Average Phase A Current
Maximum Thermal Average Phase B Current
Maximum Thermal Average Phase C Current
Maximum Thermal Average Measured Neutral Current
Maximum Thermal Average Calculated Neutral Current
Maximum Thermal Average Phase A-B Voltage
Maximum Thermal Average Phase B-C Voltage
Maximum Thermal Average Phase C-A Voltage
Maximum Thermal Average Phase A VA
Maximum Thermal Average Phase B VA
Maximum Thermal Average Phase C VA
Maximum Thermal Average VA
Maximum Thermal Average Phase A Positive VAR
Maximum Thermal Average Phase B Positive VAR
Maximum Thermal Average Phase C Positive VAR
Maximum Thermal Average Positive VAR
Maximum Thermal Average Phase A Negative VAR
Maximum Thermal Average Phase B Negative VAR
Maximum Thermal Average Phase C Negative VAR
Maximum Thermal Average Negative VAR
Maximum Thermal Average Phase A Watts Positive
Maximum Thermal Average Phase B Watts Positive
Maximum Thermal Average Phase C Watts Positive
Maximum Thermal Average Positive Watts
Maximum Thermal Average Phase A Watts Negative
Maximum Thermal Average Phase B Watts Negative
Maximum Thermal Average Phase C Watts Negative
Maximum Thermal Average Negative Watts
Maximum Thermal Average Frequency
Maximum Thermal Average Phase A Power Factor Quadrant 1
Maximum Thermal Average Phase B Power Factor Quadrant 1
Maximum Thermal Average Phase C Power Factor Quadrant 1
Maximum Thermal Average Power Factor Quadrant 1
Maximum Thermal Average Phase A Power Factor Quadrant 2
Maximum Thermal Average Phase B Power Factor Quadrant 2
Maximum Thermal Average Phase C Power Factor Quadrant 2
Maximum Thermal Average Power Factor Quadrant 2
Maximum Thermal Average Phase A Power Factor Quadrant 3
Maximum Thermal Average Phase B Power Factor Quadrant 3
Maximum Thermal Average Phase C Power Factor Quadrant 3
Maximum Thermal Average Power Factor Quadrant 3
Maximum Thermal Average Phase A Power Factor Quadrant 4
12/31/9999 23:59:59.99
+ 32767 V / 0 V
+ 32767 V / 0 V
+ 32767 V / 0 V
+ 32767 A / 0 A
+ 32767 A / 0 A
+ 32767 A / 0 A
+ 32767 A / 0 A
+ 32767 A / 0 A
+ 32767 V / 0 V
+ 32767 V / 0 V
+ 32767 V / 0 V
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VAR / 0 VAR
+32767 VAR / 0 VAR
+32767 VAR / 0 VAR
+32767 VAR / 0 VAR
0 VAR / -32768 VAR
0 VAR / -32768 VAR
0 VAR / -32768 VAR
0 VAR / -32768 VAR
+32767 W / 0 W
+32767 W / 0 W
+32767 W / 0 W
+32767 W / 0 W
0 W / -32768 W
0 W / -32768 W
0 W / -32768 W
0 W / -32768 W
+ 32767 Hz / 0 Hz
0.999 / 0
0.999 / 0
0.999 / 0
0.999 / 0
3.999 / 3.000
3.999 / 3.000
3.999 / 3.000
3.999 / 3.000
2.999 / 2.000
2.999 / 2.000
2.999 / 2.000
2.999 / 2.000
1.999 / 1.000
10 msec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 VA sec
1/ 65536 VA sec
1/ 65536 VA sec
1/ 65536 VA sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 Hz
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
F3
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F8
F8
F8
F8
F8
F8
F8
F8
F8
F8
F8
F8
F8
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
1
4
4
4
6
6
6
Description
Notes
6
4
4
4
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-3
2: Modbus Map - Holding Registers
Addr. (hex)
017AH
017BH
017CH
017DH
017EH
017FH
0180H
0181H
0182H
0183H
0184H
0185H
0186H
0187H
0188H-0189H
018AH-018BH
018CH-018FH
0190H-0191H
0192H-0193H
0194H-0195H
0196H-0197H
0198H-0199H
019AH-019BH
019CH-019DH
019EH-019FH
01A0H-01A1H
01A2H-01A3H
01A4H-01A5H
01A6H-01A7H
01A8H-01A9H
01AAH-01ABH
01ACH-01ADH
01AEH-01AFH
01B0H-01B1H
01B2H-01B3H
01B4H-01B5H
01B6H-01B7H
01B8H-01B9H
01BAH-01BBH
01BCH-01BDH
01BEH-01BFH
01C0H-01C1H
01C2H-01C3H
01C4H-01C5H
01C6H-01C7H
01C8H-01C9H
01CAH-01CBH
01CCH-01CDH
01CEH-01CFH
01D0H-01D1H
01D2H
01D3H
01D4H
01D5H
01D6H
01D7H
01D8H
01D9H
Address(4X)
00379
00380
00381
00382
00383
00384
00385
00386
00387
00388
00389
00390
00391
00392
00393-00394
00395-00396
Minimum Block
00397-00400
00401-00402
00403-00404
00405-00406
00407-00408
00409-00410
00411-00412
00413-00414
00415-00416
00417-00418
00419-00420
00421-00422
00423-00424
00425-00426
00427-00428
00429-00430
00431-00432
00433-00434
00435-00436
00437-00438
00439-00440
00441-00442
00443-00444
00445-00446
00447-00448
00449-00450
00451-00452
00453-00454
00455-00456
00457-00458
00459-00460
00461-00462
00463-00464
00465-00466
00467
00468
00469
00470
00471
00472
00473
00474
Line
Pt
DNP
Obj
91
91
92
93
93
94
94
94
95
95
95
96
96
96
97
97
1
2
0
0
1
0
1
2
0
1
2
0
1
2
0
1
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
98
99
99
99
100
101
101
101
102
103
104
104
104
105
105
105
106
107
107
107
108
109
109
109
110
111
111
111
112
113
113
113
114
115
116
116
116
117
118
118
118
119
0
0
1
2
0
0
1
2
0
0
0
1
2
0
1
2
0
0
1
2
0
0
1
2
0
0
1
2
0
0
1
2
0
0
0
1
2
0
0
1
2
0
50
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
Range
Units
Type
R/W
Maximum Thermal Average Phase B Power Factor Quadrant 4
Maximum Thermal Average Phase C Power Factor Quadrant 4
Maximum Thermal Average Power Factor Quadrant 4
Maximum Thermal Average Voltage Imbalance
Maximum Thermal Average Current Imbalance
Maximum THD Phase A-N / A-B Voltage
Maximum THD Phase B-N / B-C Voltage
Maximum THD Phase C-N / C-A Voltage
Maximum THD Phase A Current
Maximum THD Phase B Current
Maximum THD Phase C Current
Maximum K-Factor Phase A Current
Maximum K-Factor Phase B Current
Maximum K-Factor Phase C Current
Coincident Thermal Average VAR for Maximum Positive Watt
Coincident Thermal Average VAR for Maximum Negative Watt
1.999 / 1.000
1.999 / 1.000
1.999 / 1.000
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
327.67 / -327.68
327.67 / -327.68
327.67 / -327.68
+32767 VAR / -32768 VAR
+32767 VAR / -32768 VAR
0.001 PF
0.001 PF
0.001 PF
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01
0.01
0.01
1/ 65536 W sec
1/ 65536 W sec
F8
F8
F8
F10
F10
F10
F10
F10
F10
F10
F10
F67
F67
F67
F7
F7
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Minimum Block Time Stamp
Minimum Thermal Average Phase A-N Voltage
Minimum Thermal Average Phase B-N Voltage
Minimum Thermal Average Phase C-N Voltage
Minimum Thermal Average Vaux Voltage
Minimum Thermal Average Phase A Current
Minimum Thermal Average Phase B Current
Minimum Thermal Average Phase C Current
Minimum Thermal Average Measured Neutral Current
Minimum Thermal Average Calculated Neutral Current
Minimum Thermal Average Phase A-B Voltage
Minimum Thermal Average Phase B-C Voltage
Minimum Thermal Average Phase C-A Voltage
Minimum Thermal Average Phase A VA
Minimum Thermal Average Phase B VA
Minimum Thermal Average Phase C VA
Minimum Thermal Average VA
Minimum Thermal Average Phase A Positive VAR
Minimum Thermal Average Phase B Positive VAR
Minimum Thermal Average Phase C Positive VAR
Minimum Thermal Average Positive VAR
Minimum Thermal Average Phase A Negative VAR
Minimum Thermal Average Phase B Negative VAR
Minimum Thermal Average Phase C Negative VAR
Minimum Thermal Average Negative VAR
Minimum Thermal Average Phase A Positive Watts
Minimum Thermal Average Phase B Positive Watts
Minimum Thermal Average Phase C Positive Watts
Minimum Thermal Average Positive Watts
Minimum Thermal Average Phase A Negative Watts
Minimum Thermal Average Phase B Negative Watts
Minimum Thermal Average Phase C Negative Watts
Minimum Thermal Average Negative Watts
Minimum Thermal Average Frequency
Minimum Thermal Average Phase A Power Factor Quadrant 1
Minimum Thermal Average Phase B Power Factor Quadrant 1
Minimum Thermal Average Phase C Power Factor Quadrant 1
Minimum Thermal Average Power Factor Quadrant 1
Minimum Thermal Average Phase A Power Factor Quadrant 2
Minimum Thermal Average Phase B Power Factor Quadrant 2
Minimum Thermal Average Phase C Power Factor Quadrant 2
Minimum Thermal Average Power Factor Quadrant 2
12/31/9999 23:59:59.99
+ 32767 V / 0 V
+ 32767 V / 0 V
+ 32767 V / 0 V
+ 32767 V / 0 V
+ 32767 A / 0 A
+ 32767 A / 0 A
+ 32767 A / 0 A
+ 32767 A / 0 A
+ 32767 A / 0 A
+ 32767 V / 0 V
+ 32767 V / 0 V
+ 32767 V / 0 V
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VAR / 0 VAR
+32767 VAR / 0 VAR
+32767 VAR / 0 VAR
+32767 VAR / 0 VAR
0 VAR / -32768 VAR
0 VAR / -32768 VAR
0 VAR / -32768 VAR
0 VAR / -32768 VAR
+32767 W / 0 W
+32767 W / 0 W
+32767 W / 0 W
+32767 W / 0 W
0 W / -32768 W
0 W / -32768 W
0 W / -32768 W
0 W / -32768 W
+ 32767 Hz / 0 Hz
0.999 / 0
0.999 / 0
0.999 / 0
0.999 / 0
3.999 / 3.000
3.999 / 3.000
3.999 / 3.000
3.999 / 3.000
10 msec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 V sec
1/ 65536 VA sec
1/ 65536 VA sec
1/ 65536 VA sec
1/ 65536 VA sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 Hz
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
F3
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F8
F8
F8
F8
F8
F8
F8
F8
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
9
9
1
4
4
4
4
6
6
6
6
4
4
4
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-4
2: Modbus Map - Holding Registers
Address(4X)
Line
Pt
DNP
Obj
120
120
120
121
122
122
122
123
124
124
125
125
125
126
126
126
127
127
127
128
128
0
1
2
0
0
1
2
0
0
1
0
1
2
0
1
2
0
1
2
0
1
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
01F1H-01F4H
01F5H-01F8H
01F9H-01FCH
01FDH-0200H
0201H-0204H
0205H-0208H
0209H-020CH
00475
00476
00477
00478
00479
00480
00481
00482
00483
00484
00485
00486
00487
00488
00489
00490
00491
00492
00493
00494-00495
00496-00497
Stamp Block
00498-00501
00502-00505
00506-00509
00510-00513
00514-00517
00518-00521
00522-00525
129
129
129
129
129
129
129
0
1
2
3
4
5
6
020DH-0210H
00526-00529
129
0211H-0214H
0215H-0218H
0219H-021CH
021DH-0220H
0221H-0224H
0225H-0228H
0229H-022CH
022DH-0230H
00530-00533
00534-00537
00538-00541
00542-00545
00546-00549
00550-00553
00554-00557
00558-00561
129
129
129
129
129
129
129
129
0231H-0234H
00562-00565
Addr. (hex)
01DAH
01DBH
01DCH
01DDH
01DEH
01DFH
01E0H
01E1H
01E2H
01E3H
01E4H
01E5H
01E6H
01E7H
01E8H
01E9H
01EAH
01EBH
01ECH
01EDH-01EEH
01EFH-01F0H
Description
Range
Units
Type
R/W
Notes
Minimum Thermal Average Phase A Power Factor Quadrant 3
Minimum Thermal Average Phase B Power Factor Quadrant 3
Minimum Thermal Average Phase C Power Factor Quadrant 3
Minimum Thermal Average Power Factor Quadrant 3
Minimum Thermal Average Phase A Power Factor Quadrant 4
Minimum Thermal Average Phase B Power Factor Quadrant 4
Minimum Thermal Average Phase C Power Factor Quadrant 4
Minimum Thermal Average Power Factor Quadrant 4
Minimum Thermal Average Voltage Imbalance
Minimum Thermal Average Current Imbalance
Minimum THD Phase A-N Voltage / Phase A-B Voltage
Minimum THD Phase B-N Voltage / Phase B-C Voltage
Minimum THD Phase C-N Voltage / Phase C-A Voltage
Minimum THD Phase A Current
Minimum THD Phase B Current
Minimum THD Phase C Current
Minimum K-Factor Phase A Current
Minimum K-Factor Phase B Current
Minimum K-Factor Phase C Current
Coincident Thermal Average VAR for Minimum Positive Watt
Coincident Thermal Average VAR for Minimum Negative Watt
2.999 / 2.000
2.999 / 2.000
2.999 / 2.000
2.999 / 2.000
1.999 / 1.000
1.999 / 1.000
1.999 / 1.000
1.999 / 1.000
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
327.67 / -327.68
327.67 / -327.68
327.67 / -327.68
+32767 VAR / -32768 VAR
+32767 VAR / -32768 VAR
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01
0.01
0.01
1/ 65536 W sec
1/ 65536 W sec
F8
F8
F8
F8
F8
F8
F8
F8
F10
F10
F10
F10
F10
F10
F10
F10
F67
F67
F67
F7
F7
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
9
9
50
50
50
50
50
50
50
Maximum Thermal Average Phase A-N Voltage Time Stamp
Maximum Thermal Average Phase B-N Voltage Time Stamp
Maximum Thermal Average Phase C-N Voltage Time Stamp
Maximum Thermal Average Auxiliary Voltage Time Stamp
Maximum Thermal Average Phase A Current Time Stamp
Maximum Thermal Average Phase B Current Time Stamp
Maximum Thermal Average Phase C Current Time Stamp
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
F3
F3
F3
F3
F3
F3
F3
R
R
R
R
R
R
R
1
1
1
1
1
1
1
7
50
Maximum Thermal Average Measured Neutral Current Time Stamp 12/31/9999 23:59:59.99
10 msec
F3
R
1
8
9
10
11
12
13
14
15
50
50
50
50
50
50
50
50
Maximum Thermal Average Calculated Neutral Current Time Stamp
Maximum Thermal Average Phase A-B Voltage Time Stamp
Maximum Thermal Average Phase B-C Voltage Time Stamp
Maximum Thermal Average Phase C-A Voltage Time Stamp
Maximum Thermal Average Phase A VA Time Stamp
Maximum Thermal Average Phase B VA Time Stamp
Maximum Thermal Average Phase C VA Time Stamp
Maximum Thermal Average VA Time Stamp
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
F3
F3
F3
F3
F3
F3
F3
F3
R
R
R
R
R
R
R
R
1
1
1
1
1
1
1
1
129
16
50
Maximum Thermal Average Phase A Positive VAR Time Stamp
12/31/9999 23:59:59.99
10 msec
F3
R
1
0235H-0238H
00566-00569
129
17
50
Maximum Thermal Average Phase B Positive VAR Time Stamp
12/31/9999 23:59:59.99
10 msec
F3
R
1
0239H-023CH
023DH-0240H
00570-00573
00574-00577
129
129
18
19
50
50
Maximum Thermal Average Phase C Positive VAR Time Stamp
Maximum Thermal Average Positive VAR Time Stamp
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
10 msec
10 msec
F3
F3
R
R
1
1
0241H-0244H
00578-00581
129
20
50
Maximum Thermal Average Phase A Negative VAR Time Stamp
12/31/9999 23:59:59.99
10 msec
F3
R
1
0245H-0248H
00582-00585
129
21
50
Maximum Thermal Average Phase B Negative VAR Time Stamp
12/31/9999 23:59:59.99
10 msec
F3
R
1
0249H-024CH
024DH-0250H
00586-00589
00590-00593
129
129
22
23
50
50
Maximum Thermal Average Phase C Negative VAR Time Stamp
Maximum Thermal Average Negative VAR Time Stamp
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
10 msec
10 msec
F3
F3
R
R
1
1
0251H-0254H
00594-00597
129
24
50
Maximum Thermal Average Phase A Watts Positive Time Stamp
12/31/9999 23:59:59.99
10 msec
F3
R
1
0255H-0258H
00598-00601
129
25
50
Maximum Thermal Average Phase B Watts Positive Time Stamp
12/31/9999 23:59:59.99
10 msec
F3
R
1
0259H-025CH
025DH-0260H
00602-00605
00606-00609
129
129
26
27
50
50
Maximum Thermal Average Phase C Watts Positive Time Stamp
Maximum Thermal Average Positive Watts Time Stamp
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
10 msec
10 msec
F3
F3
R
R
1
1
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-5
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
0261H-0264H
00610-00613
129
28
50
0265H-0268H
00614-00617
129
29
50
0269H-026CH
026DH-0270H
0271H-0274H
00618-00621
00622-00625
00626-00629
129
129
129
30
31
32
50
50
50
0275H-0278H
0279H-027CH
00630-00633
00634-00637
129
129
33
34
50
50
027DH-0280H
0281H-0284H
00638-00641
00642-00645
129
129
35
36
50
50
0285H-0288H
00646-00649
129
37
50
0289H-028CH
00650-00653
129
38
50
028DH-0290H
00654-00657
129
39
50
0291H-0294H
00658-00661
129
40
50
Description
Range
Units
Type
R/W
Maximum Thermal Average Phase A Watts Negative Time Stamp
12/31/9999 23:59:59.99
10 msec
F3
R
1
Maximum Thermal Average Phase B Watts Negative Time Stamp
12/31/9999 23:59:59.99
10 msec
F3
R
1
Maximum Thermal Average Phase C Watts Negative Time Stamp
Maximum Thermal Average Negative Watts Time Stamp
Maximum Thermal Average Frequency Time Stamp
Maximum Thermal Average Phase A Power Factor Quadrant 1 Time
Stamp
Maximum Thermal Average Phase B Power Factor Quadrant 1
Maximum Thermal Average Phase C Power Factor Quadrant 1 Time
Stamp
Maximum Thermal Average Power Factor Quadrant 1
Maximum Thermal Average Phase A Power Factor Quadrant 2 Time
Stamp
Maximum Thermal Average Phase B Power Factor Quadrant 2 Time
Stamp
Maximum Thermal Average Phase C Power Factor Quadrant 2 Time
Stamp
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
10 msec
10 msec
10 msec
F3
F3
F3
R
R
R
1
1
1
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
10 msec
10 msec
F3
F3
R
R
1
1
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
10 msec
10 msec
F3
F3
R
R
1
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
R
R
R
R
R
R
R
R
R
R
R
R
1
1
1
1
1
1
1
1
1
1
1
1
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
F3
F3
F3
F3
F3
F3
F3
R
R
R
R
R
R
R
1
1
1
1
1
1
1
Maximum Thermal Average Power Factor Quadrant 2 Time Stamp
Maximum Thermal Average Phase A Power Factor Quadrant 3 Time
Stamp
Maximum Thermal Average Phase B Power Factor Quadrant 3 Time
Stamp
Maximum Thermal Average Phase C Power Factor Quadrant 3 Time
Stamp
Notes
0295H-0298H
00662-00665
129
41
50
0299H-029CH
00666-00669
129
42
50
029DH-02A0H
00670-00673
129
43
50
02A1H-02A4H
00674-00677
129
44
50
02A5H-02A8H
00678-00681
129
45
50
02A9H-02ACH
00682-00685
129
46
50
02ADH-02B0H
00686-00689
129
47
50
02B1H-02B4H
02B5H-02B8H
02B9H-02BCH
02BDH-02C0H
02C1H-02C4H
02C5H-02C8H
02C9H-02CCH
02CDH-02D0H
02D1H-02D4H
02D5H-02D8H
02D9H-02DCH
02DDH-02E0H
00690-00693
00694-00697
00698-00701
00702-00705
00706-00709
00710-00713
00714-00717
00718-00721
00722-00725
00726-00729
00730-00733
00734-00737
129
129
129
129
129
129
129
129
129
129
129
129
48
49
50
51
52
53
54
55
56
57
58
59
50
50
50
50
50
50
50
50
50
50
50
50
02E1H-02E4H
02E5H-02E8H
02E9H-02ECH
02EDH-02F0H
02F1H-02F4H
02F5H-02F8H
02F9H-02FCH
00738-00741
00742-00745
00746-00749
00750-00753
00754-00757
00758-00761
00762-00765
130
130
130
130
130
130
130
0
1
2
3
4
5
6
50
50
50
50
50
50
50
Maximum Thermal Average Power Factor Quadrant 4 Time Stamp 12/31/9999 23:59:59.99
Maximum Thermal Average Voltage Imbalance Time Stamp
12/31/9999 23:59:59.99
Maximum Thermal Average Current Imbalance Time Stamp
12/31/9999 23:59:59.99
Maximum THD Phase A-N / A-B Voltage Time Stamp
12/31/9999 23:59:59.99
Maximum THD Phase B-N / B-C Voltage Time Stamp
12/31/9999 23:59:59.99
Maximum THD Phase C-N / C-A Voltage Time Stamp
12/31/9999 23:59:59.99
Maximum THD Phase A Current Time Stamp
12/31/9999 23:59:59.99
Maximum THD Phase B Current Time Stamp
12/31/9999 23:59:59.99
Maximum THD Phase C Current Time Stamp
12/31/9999 23:59:59.99
Maximum K-Factor Phase A Current Time Stamp
12/31/9999 23:59:59.99
Maximum K-Factor Phase B Current Time Stamp
12/31/9999 23:59:59.99
Maximum K-Factor Phase C Current Time Stamp
12/31/9999 23:59:59.99
Minimum Time Stamp Block
Minimum Thermal Average Phase A-N Voltage Time Stamp
12/31/9999 23:59:59.99
Minimum Thermal Average Phase B-N Voltage Time Stamp
12/31/9999 23:59:59.99
Minimum Thermal Average Phase C-N Voltage Time Stamp
12/31/9999 23:59:59.99
Minimum Thermal Average Auxiliary Voltage Time Stamp
12/31/9999 23:59:59.99
Minimum Thermal Average Phase A Current Time Stamp
12/31/9999 23:59:59.99
Minimum Thermal Average Phase B Current Time Stamp
12/31/9999 23:59:59.99
Minimum Thermal Average Phase C Current Time Stamp
12/31/9999 23:59:59.99
02FDH-0300H
00766-00769
130
7
50
Minimum Thermal Average Measured Neutral Current Time Stamp 12/31/9999 23:59:59.99
10 msec
F3
R
1
0301H-0304H
0305H-0308H
00770-00773
00774-00777
130
130
8
9
50
50
Minimum Thermal Average Calculated Neutral Current Time Stamp 12/31/9999 23:59:59.99
Minimum Thermal Average Phase A-B Voltage Time Stamp
12/31/9999 23:59:59.99
10 msec
10 msec
F3
F3
R
R
1
1
Maximum Thermal Average Power Factor Quadrant 3 Time Stamp
Maximum Thermal Average Phase A Power Factor Quadrant 4 Time
Stamp
Maximum Thermal Average Phase B Power Factor Quadrant 4 Time
Stamp
Maximum Thermal Average Phase C Power Factor Quadrant 4 Time
Stamp
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-6
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
0309H-030CH
030DH-0310H
0311H-0314H
0315H-0318H
0319H-031CH
031DH-0320H
00778-00781
00782-00785
00786-00789
00790-00793
00794-00797
00798-00801
130
130
130
130
130
130
10
11
12
13
14
15
50
50
50
50
50
50
0321H-0324H
0325H-0328H
0329H-032CH
032DH-0330H
00802-00805
00806-00809
00810-00813
00814-00817
130
130
130
130
16
17
18
19
0331H-0334H
00818-00821
130
Description
Range
Units
Type
R/W
Notes
Minimum Thermal Average Phase B-C Voltage Time Stamp
Minimum Thermal Average Phase C-A Voltage Time Stamp
Minimum Thermal Average Phase A VA Time Stamp
Minimum Thermal Average Phase B VA Time Stamp
Minimum Thermal Average Phase C VA Time Stamp
Minimum Thermal Average VA Time Stamp
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
F3
F3
F3
F3
F3
F3
R
R
R
R
R
R
1
1
1
1
1
1
50
50
50
50
Minimum Thermal Average Phase A Positive VAR Time Stamp
Minimum Thermal Average Phase B Positive VAR Time Stamp
Minimum Thermal Average Phase C Positive VAR Time Stamp
Minimum Thermal Average Positive VAR Time Stamp
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
10 msec
10 msec
10 msec
10 msec
F3
F3
F3
F3
R
R
R
R
1
1
1
1
20
50
Minimum Thermal Average Phase A Negative VAR Time Stamp
12/31/9999 23:59:59.99
10 msec
F3
R
1
0335H-0338H
00822-00825
130
21
50
Minimum Thermal Average Phase B Negative VAR Time Stamp
12/31/9999 23:59:59.99
10 msec
F3
R
1
0339H-033CH
033DH-0340H
00826-00829
00830-00833
130
130
22
23
50
50
Minimum Thermal Average Phase C Negative VAR Time Stamp
Minimum Thermal Average Negative VAR Time Stamp
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
10 msec
10 msec
F3
F3
R
R
1
1
0341H-0344H
00834-00837
130
24
50
Minimum Thermal Average Phase A Positive Watts Time Stamp
12/31/9999 23:59:59.99
10 msec
F3
R
1
0345H-0348H
00838-00841
130
25
50
Minimum Thermal Average Phase B Positive Watts Time Stamp
12/31/9999 23:59:59.99
10 msec
F3
R
1
0349H-034CH
034DH-0350H
00842-00845
00846-00849
130
130
26
27
50
50
Minimum Thermal Average Phase C Positive Watts Time Stamp
Minimum Thermal Average Positive Watts Time Stamp
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
10 msec
10 msec
F3
F3
R
R
1
1
0351H-0354H
00850-00853
130
28
50
Minimum Thermal Average Phase A Negative Watts Time Stamp
12/31/9999 23:59:59.99
10 msec
F3
R
1
0355H-0358H
00854-00857
130
29
50
Minimum Thermal Average Phase B Negative Watts Time Stamp
12/31/9999 23:59:59.99
10 msec
F3
R
1
0359H-035CH
035DH-0360H
0361H-0364H
00858-00861
00862-00865
00866-00869
130
130
130
30
31
32
50
50
50
Minimum Thermal Average Phase C Negative Watts Time Stamp
Minimum Thermal Average Negative Watts Time Stamp
Minimum Thermal Average Frequency Time Stamp
Minimum Thermal Average Phase A Power Factor Quadrant 1 Time
Stamp
Minimum Thermal Average Phase B Power Factor Quadrant 1 Time
Stamp
Minimum Thermal Average Phase C Power Factor Quadrant 1 Time
Stamp
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
10 msec
10 msec
10 msec
F3
F3
F3
R
R
R
1
1
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
0365H-0368H
00870-00873
130
33
50
0369H-036CH
00874-00877
130
34
50
036DH-0370H
00878-00881
130
35
50
0371H-0374H
00882-00885
130
36
50
0375H-0378H
00886-00889
130
37
50
0379H-037CH
00890-00893
130
38
50
037DH-0380H
00894-00897
130
39
50
0381H-0384H
00898-00901
130
40
50
0385H-0388H
00902-00905
130
41
50
0389H-038CH
00906-00909
130
42
50
038DH-0390H
00910-00913
130
43
50
0391H-0394H
00914-00917
130
44
50
0395H-0398H
00918-00921
130
45
50
0399H-039CH
00922-00925
130
46
50
Minimum Thermal Average Power Factor Quadrant 1 Time Stamp
Minimum Thermal Average Phase A Power Factor Quadrant 2 Time
Stamp
Minimum Thermal Average Phase B Power Factor Quadrant 2 Time
Stamp
Minimum Thermal Average Phase C Power Factor Quadrant 2 Time
Stamp
Minimum Thermal Average Power Factor Quadrant 2 Time Stamp
Minimum Thermal Average Phase A Power Factor Quadrant 3 Time
Stamp
Minimum Thermal Average Phase B Power Factor Quadrant 3 Time
Stamp
Minimum Thermal Average Phase C Power Factor Quadrant 3 Time
Stamp
12/31/9999 23:59:59.99
10 msec
F3
R
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
12/31/9999 23:59:59.99
10 msec
F3
R
1
Minimum Thermal Average Power Factor Quadrant 3 Time Stamp 12/31/9999 23:59:59.99
Minimum Thermal Average Phase A Power Factor Quadrant 4 Time
Stamp
12/31/9999 23:59:59.99
Minimum Thermal Average Phase B Power Factor Quadrant 4 Time
Stamp
12/31/9999 23:59:59.99
10 msec
F3
R
1
10 msec
F3
R
1
10 msec
F3
R
1
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-7
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
039DH-03A0H
00926-00929
130
47
50
03A1H-03A4H
03A5H-03A8H
03A9H-03ACH
00930-00933
00934-00937
00938-00941
130
130
130
48
49
50
50
50
50
03ADH-03B0H
00942-00945
130
51
50
03B1H-01B4H
00946-00949
130
52
50
03B5H-03B8H
03B9H-03BCH
03BDH-03C0H
03C1H-03C4H
03C5H-03C8H
03C9H-03CCH
03CDH-03D0H
00950-00953
00954-00957
00958-00961
00962-00965
00966-00969
00970-00973
00974-00977
130
130
130
130
130
130
130
53
54
55
56
57
58
59
50
50
50
50
50
50
50
03D1H-03D4H
00978-00981
131
0
50
03D5H-03D8H
00982-00985
132
0
20
03D9H-03DCH
00986-00989
132
1
20
03DDH-03E0H
00990-00993
132
2
20
03E1H-03E4H
00994-00997
132
3
20
03E5H-03E8H
00998-01001
132
4
20
03E9H-03ECH
01002-01005
133
0
20
03EDH-03F0H
01006-01009
133
1
20
03F1H-03F4H
01010-01013
133
2
20
03F5H-03F8H
01014-01017
133
3
20
03F9H-03FCH
01018-01021
133
4
20
03FDH
03FEH
03FFH
0400H
0401H
0402H
0403H
0404H
0405H
0406H
0407H
0408H
0409H
040AH
040BH
040CH
040DH
040EH
01022
01023
01024
01025
01026
01027
01028
01029
01030
01031
01032
01033
01034
01035
01036
01037
01038
01039
134
134
134
134
134
134
134
134
135
135
135
135
135
135
135
135
136
136
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
0
1
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
Range
Minimum Thermal Average Phase C Power Factor Quadrant 4 Time
Stamp
12/31/9999 23:59:59.99
Minimum Thermal Average Power Factor Quadrant 4 Time Stamp 12/31/9999 23:59:59.99
Minimum Thermal Average Voltage Imbalance Time Stamp
12/31/9999 23:59:59.99
Minimum Thermal Average Current Imbalance Time Stamp
12/31/9999 23:59:59.99
Minimum THD Phase A-N Voltage / Phase A-B Voltage Time
Stamp
12/31/9999 23:59:59.99
Minimum THD Phase B-N Voltage / Phase B-C Voltage Time
Stamp
12/31/9999 23:59:59.99
Minimum THD Phase C-N Voltage / Phase C-A Voltage Time
Stamp
12/31/9999 23:59:59.99
Minimum THD Phase A Current Time Stamp
12/31/9999 23:59:59.99
Minimum THD Phase B Current Time Stamp
12/31/9999 23:59:59.99
Minimum THD Phase C Current Time Stamp
12/31/9999 23:59:59.99
Minimum K-Factor Phase A Current Time Stamp
12/31/9999 23:59:59.99
Minimum K-Factor Phase B Current Time Stamp
12/31/9999 23:59:59.99
Minimum K-Factor Phase C Current Time Stamp
12/31/9999 23:59:59.99
Energy Block (Secondary)
Energy Block Time Stamp
12/31/9999 23:59:59.99
+9,999,999,999,999,999 VAh /
VAhour (BCD)
0 VAh
+9,999,999,999,999,999 VARh
Positive VARhour (BCD)
/ 0 VARh
0 VARh / Negative VARhour (BCD)
9,999,999,999,999,999 VARh
+9,999,999,999,999,999 Wh / 0
Positive Watthour (BCD)
Wh
0 Wh / -9,999,999,999,999,999
Negative Watthour (BCD)
Wh
+9,999,999,999,999,999 VAh /
VAhour (Binary)
0 VAh
+9,999,999,999,999,999 VARh
Positive VARhour (Binary)
/ 0 VARh
0 VARh / Negative VARhour (Binary)
9,999,999,999,999,999 VARh
+9,999,999,999,999,999 Wh / 0
Positive Watthour (Binary)
Wh
0 Wh / -9,999,999,999,999,999
Negative Watthour (Binary)
Wh
Harmonic Magnitude Block (IEC 61000-4-30 1.6 sec Update)
th
+327.67% / -327.68%
Phase A-N / Phase A-B Voltage 0 Harmonic Magnitude
st
+327.67% / -327.68%
Phase A-N / Phase A-B Voltage 1 Harmonic Magnitude
nd
+327.67% / -327.68%
Phase A-N / Phase A-B Voltage 2 Harmonic Magnitude
rd
+327.67% / -327.68%
Phase A-N / Phase A-B Voltage 3 Harmonic Magnitude
th
+327.67% / -327.68%
Phase A-N / Phase A-B Voltage 4 Harmonic Magnitude
th
+327.67% / -327.68%
Phase A-N / Phase A-B Voltage 5 Harmonic Magnitude
th
+327.67% / -327.68%
Phase A-N / Phase A-B Voltage 6 Harmonic Magnitude
th
+327.67% / -327.68%
Phase A-N / Phase A-B Voltage 7 Harmonic Magnitude
th
+327.67% / -327.68%
Phase A-N / Phase A-B Voltage 8 Harmonic Magnitude
th
+327.67% / -327.68%
Phase A-N / Phase A-B Voltage 9 Harmonic Magnitude
th
+327.67% / -327.68%
Phase A-N / Phase A-B Voltage 10 Harmonic Magnitude
th
+327.67% / -327.68%
Phase A-N / Phase A-B Voltage 11 Harmonic Magnitude
th
+327.67% / -327.68%
Phase A-N / Phase A-B Voltage 12 Harmonic Magnitude
th
+327.67% / -327.68%
Phase A-N / Phase A-B Voltage 13 Harmonic Magnitude
th
+327.67% / -327.68%
Phase A-N / Phase A-B Voltage 14 Harmonic Magnitude
th
+327.67% / -327.68%
Phase A-N / Phase A-B Voltage 15 Harmonic Magnitude
th
+327.67% / -327.68%
Phase A-N / Phase A-B Voltage 16 Harmonic Magnitude
th
+327.67% / -327.68%
Phase A-N / Phase A-B Voltage 17 Harmonic Magnitude
Units
Type
R/W
10 msec
F3
R
1
10 msec
10 msec
10 msec
F3
F3
F3
R
R
R
1
1
1
10 msec
F3
R
1
10 msec
F3
R
1
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
F3
F3
F3
F3
F3
F3
F3
R
R
R
R
R
R
R
1
1
1
1
1
1
1
10 msec
F3
R
1
1 VAH
F11
R
1 VARH
F11
R
1 VARH
F11
R
1 WH
F11
R
1 WH
F11
R
1 VAH
F12
R
1 VARH
F12
R
1 VARH
F12
R
1 WH
F12
R
1 WH
F12
R
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-8
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
040FH
0410H
0411H
0412H
0413H
0414H
0415H
0416H
0417H
0418H
0419H
041AH
041BH
041CH
041DH
041EH
041FH
0420H
0421H
0422H
0423H
0424H
0425H
0426H
0427H
0428H
0429H
042AH
042BH
042CH
042DH
042EH
042FH
0430H
0431H
0432H
0433H
0434H
0435H
0436H
0437H
0438H
0439H
043AH
043BH
043CH
043DH
043EH
043FH
0440H
0441H
0442H
0443H
0444H
0445H
0446H
01040
01041
01042
01043
01044
01045
01046
01047
01048
01049
01050
01051
01052
01053
01054
01055
01056
01057
01058
01059
01060
01061
01062
01063
01064
01065
01066
01067
01068
01069
01070
01071
01072
01073
01074
01075
01076
01077
01078
01079
01080
01081
01082
01083
01084
01085
01086
01087
01088
01089
01090
01091
01092
01093
01094
01095
136
136
136
136
136
136
136
136
136
136
136
136
136
136
137
137
137
137
137
137
137
137
137
137
137
137
137
137
137
137
137
137
137
137
137
137
137
137
137
137
137
137
137
137
137
137
138
138
138
138
138
138
138
138
138
138
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
0
1
2
3
4
5
6
7
8
9
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
Phase A-N / Phase A-B Voltage 18th Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 19 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 20 Harmonic Magnitude
st
Phase A-N / Phase A-B Voltage 21 Harmonic Magnitude
nd
Phase A-N / Phase A-B Voltage 22 Harmonic Magnitude
rd
Phase A-N / Phase A-B Voltage 23 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 24 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 25 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 26 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 27 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 28 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 29 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 30 Harmonic Magnitude
st
Phase A-N / Phase A-B Voltage 31 Harmonic Magnitude
nd
Phase A-N / Phase A-B Voltage 32 Harmonic Magnitude
rd
Phase A-N / Phase A-B Voltage 33 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 34 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 35 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 36 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 37 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 38 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 39 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 40 Harmonic Magnitude
st
Phase A-N / Phase A-B Voltage 41 Harmonic Magnitude
nd
Phase A-N / Phase A-B Voltage 42 Harmonic Magnitude
rd
Phase A-N / Phase A-B Voltage 43 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 44 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 45 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 46 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 47 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 48 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 49 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 50 Harmonic Magnitude
st
Phase A-N / Phase A-B Voltage 51 Harmonic Magnitude
nd
Phase A-N / Phase A-B Voltage 52 Harmonic Magnitude
rd
Phase A-N / Phase A-B Voltage 53 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 54 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 55 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 56 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 57 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 58 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 59 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 60 Harmonic Magnitude
st
Phase A-N / Phase A-B Voltage 61 Harmonic Magnitude
nd
Phase A-N / Phase A-B Voltage 62 Harmonic Magnitude
rd
Phase A-N / Phase A-B Voltage 63 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 64 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 65 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 66 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 67 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 68 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 69 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 70 Harmonic Magnitude
st
Phase A-N / Phase A-B Voltage 71 Harmonic Magnitude
nd
Phase A-N / Phase A-B Voltage 72 Harmonic Magnitude
rd
Phase A-N / Phase A-B Voltage 73 Harmonic Magnitude
Range
Units
Type
R/W
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-9
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
0447H
0448H
0449H
044AH
044BH
044CH
044DH
044EH
044FH
0450H
0451H
0452H
0453H
0454H
0455H
0456H
0457H
0458H
0459H
045AH
045BH
045CH
045DH
045EH
045FH
0460H
0461H
0462H
0463H
0464H
0465H
0466H
0467H
0468H
0469H
046AH
046BH
046CH
046DH
046EH
046FH
0470H
0471H
0472H
0473H
0474H
0475H
0476H
0477H
0478H
0479H
047AH
047BH
047CH
047DH
047EH
01096
01097
01098
01099
01100
01101
01102
01103
01104
01105
01106
01107
01108
01109
01110
01111
01112
01113
01114
01115
01116
01117
01118
01119
01120
01121
01122
01123
01124
01125
01126
01127
01128
01129
01130
01131
01132
01133
01134
01135
01136
01137
01138
01139
01140
01141
01142
01143
01144
01145
01146
01147
01148
01149
01150
01151
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
139
139
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
0
1
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
Phase A-N / Phase A-B Voltage 74th Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 75 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 76 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 77 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 78 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 79 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 80 Harmonic Magnitude
st
Phase A-N / Phase A-B Voltage 81 Harmonic Magnitude
nd
Phase A-N / Phase A-B Voltage 82 Harmonic Magnitude
rd
Phase A-N / Phase A-B Voltage 83 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 84 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 85 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 86 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 87 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 88 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 89 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 90 Harmonic Magnitude
st
Phase A-N / Phase A-B Voltage 91 Harmonic Magnitude
nd
Phase A-N / Phase A-B Voltage 92 Harmonic Magnitude
rd
Phase A-N / Phase A-B Voltage 93 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 94 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 95 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 96 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 97 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 98 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 99 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 100 Harmonic Magnitude
st
Phase A-N / Phase A-B Voltage 101 Harmonic Magnitude
nd
Phase A-N / Phase A-B Voltage 102 Harmonic Magnitude
rd
Phase A-N / Phase A-B Voltage 103 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 104 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 105 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 106 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 107 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 108 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 109 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 110 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 111 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 112 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 113 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 114 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 115 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 116 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 117 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 118 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 119 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 120 Harmonic Magnitude
st
Phase A-N / Phase A-B Voltage 121 Harmonic Magnitude
nd
Phase A-N / Phase A-B Voltage 122 Harmonic Magnitude
rd
Phase A-N / Phase A-B Voltage 123 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 124 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 125 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 126 Harmonic Magnitude
th
Phase A-N / Phase A-B Voltage 127 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 0 Harmonic Magnitude
st
Phase B-N / Phase B-C Voltage 1 Harmonic Magnitude
Range
Units
Type
R/W
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-10
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
047FH
0480H
0481H
0482H
0483H
0484H
0485H
0486H
0487H
0488H
0489H
048AH
048BH
048CH
048DH
048EH
048FH
0490H
0491H
0492H
0493H
0494H
0495H
0496H
0497H
0498H
0499H
049AH
049BH
049CH
049DH
049EH
049FH
04A0H
04A1H
04A2H
04A3H
04A4H
04A5H
04A6H
04A7H
04A8H
04A9H
04AAH
04ABH
04ACH
04ADH
04AEH
04AFH
04B0H
04B1H
04B2H
04B3H
04B4H
04B5H
04B6H
01152
01153
01154
01155
01156
01157
01158
01159
01160
01161
01162
01163
01164
01165
01166
01167
01168
01169
01170
01171
01172
01173
01174
01175
01176
01177
01178
01179
01180
01181
01182
01183
01184
01185
01186
01187
01188
01189
01190
01191
01192
01193
01194
01195
01196
01197
01198
01199
01200
01201
01202
01203
01204
01205
01206
01207
139
139
139
139
139
139
140
140
140
140
140
140
140
140
141
141
141
141
141
141
141
141
141
141
141
141
141
141
141
141
142
142
142
142
142
142
142
142
142
142
142
142
142
142
142
142
142
142
142
142
142
142
142
142
142
142
2
3
4
5
6
7
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
nd
Phase B-N / Phase B-C Voltage 2 Harmonic Magnitude
rd
Phase B-N / Phase B-C Voltage 3 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 4 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 5 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 6 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 7 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 8 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 9 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 10 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 11 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 12 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 13 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 14 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 15 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 16 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 17 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 18 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 19 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 20 Harmonic Magnitude
st
Phase B-N / Phase B-C Voltage 21 Harmonic Magnitude
nd
Phase B-N / Phase B-C Voltage 22 Harmonic Magnitude
rd
Phase B-N / Phase B-C Voltage 23 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 24 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 25 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 26 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 27 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 28 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 29 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 30 Harmonic Magnitude
st
Phase B-N / Phase B-C Voltage 31 Harmonic Magnitude
nd
Phase B-N / Phase B-C Voltage 32 Harmonic Magnitude
rd
Phase B-N / Phase B-C Voltage 33 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 34 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 35 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 36 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 37 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 38 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 39 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 40 Harmonic Magnitude
st
Phase B-N / Phase B-C Voltage 41 Harmonic Magnitude
nd
Phase B-N / Phase B-C Voltage 42 Harmonic Magnitude
rd
Phase B-N / Phase B-C Voltage 43 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 44 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 45 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 46 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 47 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 48 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 49 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 50 Harmonic Magnitude
st
Phase B-N / Phase B-C Voltage 51 Harmonic Magnitude
nd
Phase B-N / Phase B-C Voltage 52 Harmonic Magnitude
rd
Phase B-N / Phase B-C Voltage 53 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 54 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 55 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 56 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 57 Harmonic Magnitude
Range
Units
Type
R/W
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-11
2: Modbus Map - Holding Registers
Addr. (hex)
04B7H
04B8H
04B9H
04BAH
04BBH
04BCH
04BDH
04BEH
04BFH
04C0H
04C1H
04C2H
04C3H
04C4H
04C5H
04C6H
04C7H
04C8H
04C9H
04CAH
04CBH
04CCH
04CDH
04CEH
04CFH
04D0H
04D1H
04D2H
04D3H
04D4H
04D5H
04D6H
04D7H
04D8H
04D9H
04DAH
04DBH
04DCH
04DDH
04DEH
04DFH
04E0H
04E1H
04E2H
04E3H
04E4H
04E5H
04E6H
04E7H
04E8H
04E9H
04EAH
04EBH
04ECH
04EDH
04EEH
Address(4X)
01208
01209
01210
01211
01212
01213
01214
01215
01216
01217
01218
01219
01220
01221
01222
01223
01224
01225
01226
01227
01228
01229
01230
01231
01232
01233
01234
01235
01236
01237
01238
01239
01240
01241
01242
01243
01244
01245
01246
01247
01248
01249
01250
01251
01252
01253
01254
01255
01256
01257
01258
01259
01260
01261
01262
01263
Line
142
142
142
142
142
142
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
Pt
26
27
28
29
30
31
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
DNP
Obj
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
th
Phase B-N / Phase B-C Voltage 58 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 59 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 60 Harmonic Magnitude
st
Phase B-N / Phase B-C Voltage 61 Harmonic Magnitude
nd
Phase B-N / Phase B-C Voltage 62 Harmonic Magnitude
rd
Phase B-N / Phase B-C Voltage 63 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 64 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 65 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 66 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 67 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 68 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 69 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 70 Harmonic Magnitude
st
Phase B-N / Phase B-C Voltage 71 Harmonic Magnitude
nd
Phase B-N / Phase B-C Voltage 72 Harmonic Magnitude
rd
Phase B-N / Phase B-C Voltage 73 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 74 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 75 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 76 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 77 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 78 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 79 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 80 Harmonic Magnitude
st
Phase B-N / Phase B-C Voltage 81 Harmonic Magnitude
nd
Phase B-N / Phase B-C Voltage 82 Harmonic Magnitude
rd
Phase B-N / Phase B-C Voltage 83 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 84 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 85 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 86 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 87 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 88 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 89 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 90 Harmonic Magnitude
st
Phase B-N / Phase B-C Voltage 91 Harmonic Magnitude
nd
Phase B-N / Phase B-C Voltage 92 Harmonic Magnitude
rd
Phase B-N / Phase B-C Voltage 93 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 94 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 95 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 96 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 97 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 98 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 99 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 100 Harmonic Magnitude
st
Phase B-N / Phase B-C Voltage 101 Harmonic Magnitude
nd
Phase B-N / Phase B-C Voltage 102 Harmonic Magnitude
rd
Phase B-N / Phase B-C Voltage 103 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 104 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 105 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 106 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 107 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 108 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 109 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 110 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 111 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 112 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 113 Harmonic Magnitude
Range
Units
Type
R/W
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-12
2: Modbus Map - Holding Registers
Addr. (hex)
04EFH
04F0H
04F1H
04F2H
04F3H
04F4H
04F5H
04F6H
04F7H
04F8H
04F9H
04FAH
04FBH
04FCH
04FDH
04FEH
04FFH
0500H
0501H
0502H
0503H
0504H
0505H
0506H
0507H
0508H
0509H
050AH
050BH
050CH
050DH
050EH
050FH
0510H
0511H
0512H
0513H
0514H
0515H
0516H
0517H
0518H
0519H
051AH
051BH
051CH
051DH
051EH
051FH
0520H
0521H
0522H
0523H
0524H
0525H
0526H
Address(4X)
01264
01265
01266
01267
01268
01269
01270
01271
01272
01273
01274
01275
01276
01277
01278
01279
01280
01281
01282
01283
01284
01285
01286
01287
01288
01289
01290
01291
01292
01293
01294
01295
01296
01297
01298
01299
01300
01301
01302
01303
01304
01305
01306
01307
01308
01309
01310
01311
01312
01313
01314
01315
01316
01317
01318
01319
Line
143
143
143
143
143
143
143
143
143
143
143
143
143
143
144
144
144
144
144
144
144
144
145
145
145
145
145
145
145
145
146
146
146
146
146
146
146
146
146
146
146
146
146
146
146
146
147
147
147
147
147
147
147
147
147
147
Pt
50
51
52
53
54
55
56
57
58
59
60
61
62
63
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
DNP
Obj
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
th
Phase B-N / Phase B-C Voltage 114 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 115 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 116 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 117 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 118 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 119 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 120 Harmonic Magnitude
st
Phase B-N / Phase B-C Voltage 121 Harmonic Magnitude
nd
Phase B-N / Phase B-C Voltage 122 Harmonic Magnitude
rd
Phase B-N / Phase B-C Voltage 123 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 124 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 125 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 126 Harmonic Magnitude
th
Phase B-N / Phase B-C Voltage 127 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 0 Harmonic Magnitude
st
Phase C-N / Phase C-A Voltage 1 Harmonic Magnitude
nd
Phase C-N / Phase C-A Voltage 2 Harmonic Magnitude
rd
Phase C-N / Phase C-A Voltage 3 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 4 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 5 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 6 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 7 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 8 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 9 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 10 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 11 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 12 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 13 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 14 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 15 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 16 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 17 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 18 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 19 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 20 Harmonic Magnitude
st
Phase C-N / Phase C-A Voltage 21 Harmonic Magnitude
nd
Phase C-N / Phase C-A Voltage 22 Harmonic Magnitude
rd
Phase C-N / Phase C-A Voltage 23 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 24 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 25 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 26 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 27 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 28 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 29 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 30 Harmonic Magnitude
st
Phase C-N / Phase C-A Voltage 31 Harmonic Magnitude
nd
Phase C-N / Phase C-A Voltage 32 Harmonic Magnitude
rd
Phase C-N / Phase C-A Voltage 33 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 34 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 35 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 36 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 37 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 38 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 39 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 40 Harmonic Magnitude
st
Phase C-N / Phase C-A Voltage 41 Harmonic Magnitude
Range
Units
Type
R/W
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-13
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
0527H
0528H
0529H
052AH
052BH
052CH
052DH
052EH
052FH
0530H
0531H
0532H
0533H
0534H
0535H
0536H
0537H
0538H
0539H
053AH
053BH
053CH
053DH
053EH
053FH
0540H
0541H
0542H
0543H
0544H
0545H
0546H
0547H
0548H
0549H
054AH
054BH
054CH
054DH
054EH
054FH
0550H
0551H
0552H
0553H
0554H
0555H
0556H
0557H
0558H
0559H
055AH
055BH
055CH
055DH
055EH
01320
01321
01322
01323
01324
01325
01326
01327
01328
01329
01330
01331
01332
01333
01334
01335
01336
01337
01338
01339
01340
01341
01342
01343
01344
01345
01346
01347
01348
01349
01350
01351
01352
01353
01354
01355
01356
01357
01358
01359
01360
01361
01362
01363
01364
01365
01366
01367
01368
01369
01370
01371
01372
01373
01374
01375
147
147
147
147
147
147
147
147
147
147
147
147
147
147
147
147
147
147
147
147
147
147
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
nd
Phase C-N / Phase C-A Voltage 42 Harmonic Magnitude
rd
Phase C-N / Phase C-A Voltage 43 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 44 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 45 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 46 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 47 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 48 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 49 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 50 Harmonic Magnitude
st
Phase C-N / Phase C-A Voltage 51 Harmonic Magnitude
nd
Phase C-N / Phase C-A Voltage 52 Harmonic Magnitude
rd
Phase C-N / Phase C-A Voltage 53 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 54 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 55 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 56 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 57 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 58 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 59 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 60 Harmonic Magnitude
st
Phase C-N / Phase C-A Voltage 61 Harmonic Magnitude
nd
Phase C-N / Phase C-A Voltage 62 Harmonic Magnitude
rd
Phase C-N / Phase C-A Voltage 63 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 64 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 65 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 66 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 67 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 68 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 69 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 70 Harmonic Magnitude
st
Phase C-N / Phase C-A Voltage 71 Harmonic Magnitude
nd
Phase C-N / Phase C-A Voltage 72 Harmonic Magnitude
rd
Phase C-N / Phase C-A Voltage 73 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 74 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 75 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 76 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 77 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 78 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 79 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 80 Harmonic Magnitude
st
Phase C-N / Phase C-A Voltage 81 Harmonic Magnitude
nd
Phase C-N / Phase C-A Voltage 82 Harmonic Magnitude
rd
Phase C-N / Phase C-A Voltage 83 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 84 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 85 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 86 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 87 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 88 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 89 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 90 Harmonic Magnitude
st
Phase C-N / Phase C-A Voltage 91 Harmonic Magnitude
nd
Phase C-N / Phase C-A Voltage 92 Harmonic Magnitude
rd
Phase C-N / Phase C-A Voltage 93 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 94 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 95 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 96 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 97 Harmonic Magnitude
Range
Units
Type
R/W
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-14
2: Modbus Map - Holding Registers
Addr. (hex)
055FH
0560H
0561H
0562H
0563H
0564H
0565H
0566H
0567H
0568H
0569H
056AH
056BH
056CH
056DH
056EH
056FH
0570H
0571H
0572H
0573H
0574H
0575H
0576H
0577H
0578H
0579H
057AH
057BH
057CH
057DH
057EH
057FH
0580H
0581H
0582H
0583H
0584H
0585H
0586H
0587H
0588H
0589H
058AH
058BH
058CH
058DH
058EH
058FH
0590H
0591H
0592H
0593H
0594H
0595H
0596H
Address(4X)
01376
01377
01378
01379
01380
01381
01382
01383
01384
01385
01386
01387
01388
01389
01390
01391
01392
01393
01394
01395
01396
01397
01398
01399
01400
01401
01402
01403
01404
01405
01406
01407
01408
01409
01410
01411
01412
01413
01414
01415
01416
01417
01418
01419
01420
01421
01422
01423
01424
01425
01426
01427
01428
01429
01430
01431
Line
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
148
149
149
149
149
149
149
149
149
150
150
150
150
150
150
150
150
151
151
151
151
151
151
151
151
151
151
Pt
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
8
9
DNP
Obj
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
th
Phase C-N / Phase C-A Voltage 98 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 99 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 100 Harmonic Magnitude
st
Phase C-N / Phase C-A Voltage 101 Harmonic Magnitude
nd
Phase C-N / Phase C-A Voltage 102 Harmonic Magnitude
rd
Phase C-N / Phase C-A Voltage 103 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 104 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 105 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 106 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 107 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 108 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 109 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 110 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 111 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 112 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 113 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 114 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 115 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 116 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 117 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 118 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 119 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 120 Harmonic Magnitude
st
Phase C-N / Phase C-A Voltage 121 Harmonic Magnitude
nd
Phase C-N / Phase C-A Voltage 122 Harmonic Magnitude
rd
Phase C-N / Phase C-A Voltage 123 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 124 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 125 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 126 Harmonic Magnitude
th
Phase C-N / Phase C-A Voltage 127 Harmonic Magnitude
th
Phase A Current 0 Harmonic Magnitude
st
Phase A Current 1 Harmonic Magnitude
nd
Phase A Current 2 Harmonic Magnitude
rd
Phase A Current 3 Harmonic Magnitude
th
Phase A Current 4 Harmonic Magnitude
th
Phase A Current 5 Harmonic Magnitude
th
Phase A Current 6 Harmonic Magnitude
th
Phase A Current 7 Harmonic Magnitude
th
Phase A Current 8 Harmonic Magnitude
th
Phase A Current 9 Harmonic Magnitude
th
Phase A Current 10 Harmonic Magnitude
th
Phase A Current 11 Harmonic Magnitude
th
Phase A Current 12 Harmonic Magnitude
th
Phase A Current 13 Harmonic Magnitude
th
Phase A Current 14 Harmonic Magnitude
th
Phase A Current 15 Harmonic Magnitude
th
Phase A Current 16 Harmonic Magnitude
th
Phase A Current 17 Harmonic Magnitude
th
Phase A Current 18 Harmonic Magnitude
th
Phase A Current 19 Harmonic Magnitude
th
Phase A Current 20 Harmonic Magnitude
st
Phase A Current 21 Harmonic Magnitude
nd
Phase A Current 22 Harmonic Magnitude
rd
Phase A Current 23 Harmonic Magnitude
th
Phase A Current 24 Harmonic Magnitude
th
Phase A Current 25 Harmonic Magnitude
Range
Units
Type
R/W
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-15
2: Modbus Map - Holding Registers
Addr. (hex)
0597H
0598H
0599H
059AH
059BH
059CH
059DH
059EH
059FH
05A0H
05A1H
05A2H
05A3H
05A4H
05A5H
05A6H
05A7H
05A8H
05A9H
05AAH
05ABH
05ACH
05ADH
05AEH
05AFH
05B0H
05B1H
05B2H
05B3H
05B4H
05B5H
05B6H
05B7H
05B8H
05B9H
05BAH
05BBH
05BCH
05BDH
05BEH
05BFH
05C0H
05C1H
05C2H
05C3H
05C4H
05C5H
05C6H
05C7H
05C8H
05C9H
05CAH
05CBH
05CCH
05CDH
05CEH
Address(4X)
01432
01433
01434
01435
01436
01437
01438
01439
01440
01441
01442
01443
01444
01445
01446
01447
01448
01449
01450
01451
01452
01453
01454
01455
01456
01457
01458
01459
01460
01461
01462
01463
01464
01465
01466
01467
01468
01469
01470
01471
01472
01473
01474
01475
01476
01477
01478
01479
01480
01481
01482
01483
01484
01485
01486
01487
Line
151
151
151
151
151
151
152
152
152
152
152
152
152
152
152
152
152
152
152
152
152
152
152
152
152
152
152
152
152
152
152
152
152
152
152
152
152
152
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
Pt
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
DNP
Obj
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
th
Phase A Current 26 Harmonic Magnitude
th
Phase A Current 27 Harmonic Magnitude
th
Phase A Current 28 Harmonic Magnitude
th
Phase A Current 29 Harmonic Magnitude
th
Phase A Current 30 Harmonic Magnitude
st
Phase A Current 31 Harmonic Magnitude
nd
Phase A Current 32 Harmonic Magnitude
rd
Phase A Current 33 Harmonic Magnitude
th
Phase A Current 34 Harmonic Magnitude
th
Phase A Current 35 Harmonic Magnitude
th
Phase A Current 36 Harmonic Magnitude
th
Phase A Current 37 Harmonic Magnitude
th
Phase A Current 38 Harmonic Magnitude
th
Phase A Current 39 Harmonic Magnitude
th
Phase A Current 40 Harmonic Magnitude
st
Phase A Current 41 Harmonic Magnitude
nd
Phase A Current 42 Harmonic Magnitude
rd
Phase A Current43 Harmonic Magnitude
th
Phase A Current 44 Harmonic Magnitude
th
Phase A Current 45 Harmonic Magnitude
th
Phase A Current 46 Harmonic Magnitude
th
Phase A Current 47 Harmonic Magnitude
th
Phase A Current 48 Harmonic Magnitude
th
Phase A Current 49 Harmonic Magnitude
th
Phase A Current 50 Harmonic Magnitude
st
Phase A Current 51 Harmonic Magnitude
nd
Phase A Current 52 Harmonic Magnitude
rd
Phase A Current 53 Harmonic Magnitude
th
Phase A Current 54 Harmonic Magnitude
th
Phase A Current 55 Harmonic Magnitude
th
Phase A Current 56 Harmonic Magnitude
th
Phase A Current 57 Harmonic Magnitude
th
Phase A Current 58 Harmonic Magnitude
th
Phase A Current 59 Harmonic Magnitude
th
Phase A Current 60 Harmonic Magnitude
st
Phase A Current 61 Harmonic Magnitude
nd
Phase A Current 62 Harmonic Magnitude
rd
Phase A Current 63 Harmonic Magnitude
th
Phase A Current 64 Harmonic Magnitude
th
Phase A Current 65 Harmonic Magnitude
th
Phase A Current 66 Harmonic Magnitude
th
Phase A Current 67 Harmonic Magnitude
th
Phase A Current 68 Harmonic Magnitude
th
Phase A Current 69 Harmonic Magnitude
th
Phase A Current 70 Harmonic Magnitude
st
Phase A Current 71 Harmonic Magnitude
nd
Phase A Current 72 Harmonic Magnitude
rd
Phase A Current 73 Harmonic Magnitude
th
Phase A Current 74 Harmonic Magnitude
th
Phase A Current 75 Harmonic Magnitude
th
Phase A Current 76 Harmonic Magnitude
th
Phase A Current 77 Harmonic Magnitude
th
Phase A Current 78 Harmonic Magnitude
th
Phase A Current 79 Harmonic Magnitude
th
Phase A Current 80 Harmonic Magnitude
st
Phase A Current 81 Harmonic Magnitude
Range
Units
Type
R/W
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-16
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
05CFH
05D0H
05D1H
05D2H
05D3H
05D4H
05D5H
05D6H
05D7H
05D8H
05D9H
05DAH
05DBH
05DCH
05DDH
05DEH
05DFH
05E0H
05E1H
05E2H
05E3H
05E4H
05E5H
05E6H
05E7H
05E8H
05E9H
05EAH
05EBH
05ECH
05EDH
05EEH
05EFH
05F0H
05F1H
05F2H
05F3H
05F4H
05F5H
05F6H
05F7H
05F8H
05F9H
05FAH
05FBH
05FCH
05FDH
05FEH
05FFH
0600H
0601H
0602H
0603H
0604H
0605H
0606H
01488
01489
01490
01491
01492
01493
01494
01495
01496
01497
01498
01499
01500
01501
01502
01503
01504
01505
01506
01507
01508
01509
01510
01511
01512
01513
01514
01515
01516
01517
01518
01519
01520
01521
01522
01523
01524
01525
01526
01527
01528
01529
01530
01531
01532
01533
01534
01535
01536
01537
01538
01539
01540
01541
01542
01543
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
153
154
154
154
154
154
154
154
154
155
155
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
0
1
2
3
4
5
6
7
0
1
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
Phase A Current 82nd Harmonic Magnitude
rd
Phase A Current 83 Harmonic Magnitude
th
Phase A Current 84 Harmonic Magnitude
th
Phase A Current 85 Harmonic Magnitude
th
Phase A Current 86 Harmonic Magnitude
th
Phase A Current 87 Harmonic Magnitude
th
Phase A Current 88 Harmonic Magnitude
th
Phase A Current 89 Harmonic Magnitude
th
Phase A Current 90 Harmonic Magnitude
st
Phase A Current 91 Harmonic Magnitude
nd
Phase A Current 92 Harmonic Magnitude
rd
Phase A Current 93 Harmonic Magnitude
th
Phase A Current 94 Harmonic Magnitude
th
Phase A Current 95 Harmonic Magnitude
th
Phase A Current 96 Harmonic Magnitude
th
Phase A Current 97 Harmonic Magnitude
th
Phase A Current 98 Harmonic Magnitude
th
Phase A Current 99 Harmonic Magnitude
th
Phase A Current 100 Harmonic Magnitude
st
Phase A Current 101 Harmonic Magnitude
nd
Phase A Current 102 Harmonic Magnitude
rd
Phase A Current 103 Harmonic Magnitude
th
Phase A Current 104 Harmonic Magnitude
th
Phase A Current 105 Harmonic Magnitude
th
Phase A Current 106 Harmonic Magnitude
th
Phase A Current 107 Harmonic Magnitude
th
Phase A Current 108 Harmonic Magnitude
th
Phase A Current 109 Harmonic Magnitude
th
Phase A Current 110 Harmonic Magnitude
th
Phase A Current 111 Harmonic Magnitude
th
Phase A Current 112 Harmonic Magnitude
th
Phase A Current 113 Harmonic Magnitude
th
Phase A Current 114 Harmonic Magnitude
th
Phase A Current 115 Harmonic Magnitude
th
Phase A Current 116 Harmonic Magnitude
th
Phase A Current 117 Harmonic Magnitude
th
Phase A Current 118 Harmonic Magnitude
th
Phase A Current 119 Harmonic Magnitude
th
Phase A Current 120 Harmonic Magnitude
st
Phase A Current 121 Harmonic Magnitude
nd
Phase A Current 122 Harmonic Magnitude
rd
Phase A Current 123 Harmonic Magnitude
th
Phase A Current 124 Harmonic Magnitude
th
Phase A Current 125 Harmonic Magnitude
th
Phase A Current 126 Harmonic Magnitude
th
Phase A Current 127 Harmonic Magnitude
th
Phase B Current 0 Harmonic Magnitude
st
Phase B Current 1 Harmonic Magnitude
nd
Phase B Current 2 Harmonic Magnitude
rd
Phase B Current 3 Harmonic Magnitude
th
Phase B Current 4 Harmonic Magnitude
th
Phase B Current 5 Harmonic Magnitude
th
Phase B Current 6 Harmonic Magnitude
th
Phase B Current 7 Harmonic Magnitude
th
Phase B Current 8 Harmonic Magnitude
th
Phase B Current 9 Harmonic Magnitude
Range
Units
Type
R/W
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-17
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
0607H
0608H
0609H
060AH
060BH
060CH
060DH
060EH
060FH
0610H
0611H
0612H
0613H
0614H
0615H
0616H
0617H
0618H
0619H
061AH
061BH
061CH
061DH
061EH
061FH
0620H
0621H
0622H
0623H
0624H
0625H
0626H
0627H
0628H
0629H
062AH
062BH
062CH
062DH
062EH
062FH
0630H
0631H
0632H
0633H
0634H
0635H
0636H
0637H
0638H
0639H
063AH
063BH
063CH
063DH
063EH
01544
01545
01546
01547
01548
01549
01550
01551
01552
01553
01554
01555
01556
01557
01558
01559
01560
01561
01562
01563
01564
01565
01566
01567
01568
01569
01570
01571
01572
01573
01574
01575
01576
01577
01578
01579
01580
01581
01582
01583
01584
01585
01586
01587
01588
01589
01590
01591
01592
01593
01594
01595
01596
01597
01598
01599
155
155
155
155
155
155
156
156
156
156
156
156
156
156
156
156
156
156
156
156
156
156
157
157
157
157
157
157
157
157
157
157
157
157
157
157
157
157
157
157
157
157
157
157
157
157
157
157
157
157
157
157
157
157
158
158
2
3
4
5
6
7
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
0
1
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
Phase B Current 10th Harmonic Magnitude
th
Phase B Current 11 Harmonic Magnitude
th
Phase B Current 12 Harmonic Magnitude
th
Phase B Current 13 Harmonic Magnitude
th
Phase B Current 14 Harmonic Magnitude
th
Phase B Current 15 Harmonic Magnitude
th
Phase B Current 16 Harmonic Magnitude
th
Phase B Current 17 Harmonic Magnitude
th
Phase B Current 18 Harmonic Magnitude
th
Phase B Current 19 Harmonic Magnitude
th
Phase B Current 20 Harmonic Magnitude
st
Phase B Current 21 Harmonic Magnitude
nd
Phase B Current 22 Harmonic Magnitude
rd
Phase B Current 23 Harmonic Magnitude
th
Phase B Current 24 Harmonic Magnitude
th
Phase B Current 25 Harmonic Magnitude
th
Phase B Current 26 Harmonic Magnitude
th
Phase B Current 27 Harmonic Magnitude
th
Phase B Current 28 Harmonic Magnitude
th
Phase B Current 29 Harmonic Magnitude
th
Phase B Current 30 Harmonic Magnitude
st
Phase B Current 31 Harmonic Magnitude
nd
Phase B Current 32 Harmonic Magnitude
rd
Phase B Current 33 Harmonic Magnitude
th
Phase B Current 34 Harmonic Magnitude
th
Phase B Current 35 Harmonic Magnitude
th
Phase B Current 36 Harmonic Magnitude
th
Phase B Current 37 Harmonic Magnitude
th
Phase B Current 38 Harmonic Magnitude
th
Phase B Current 39 Harmonic Magnitude
th
Phase B Current 40 Harmonic Magnitude
st
Phase B Current 41 Harmonic Magnitude
nd
Phase B Current 42 Harmonic Magnitude
rd
Phase B Current43 Harmonic Magnitude
th
Phase B Current 44 Harmonic Magnitude
th
Phase B Current 45 Harmonic Magnitude
th
Phase B Current 46 Harmonic Magnitude
th
Phase B Current 47 Harmonic Magnitude
th
Phase B Current 48 Harmonic Magnitude
th
Phase B Current 49 Harmonic Magnitude
th
Phase B Current 50 Harmonic Magnitude
st
Phase B Current 51 Harmonic Magnitude
nd
Phase B Current 52 Harmonic Magnitude
rd
Phase B Current 53 Harmonic Magnitude
th
Phase B Current 54 Harmonic Magnitude
th
Phase B Current 55 Harmonic Magnitude
th
Phase B Current 56 Harmonic Magnitude
th
Phase B Current 57 Harmonic Magnitude
th
Phase B Current 58 Harmonic Magnitude
th
Phase B Current 59 Harmonic Magnitude
th
Phase B Current 60 Harmonic Magnitude
st
Phase B Current 61 Harmonic Magnitude
nd
Phase B Current 62 Harmonic Magnitude
rd
Phase B Current 63 Harmonic Magnitude
th
Phase B Current 64 Harmonic Magnitude
th
Phase B Current 65 Harmonic Magnitude
Range
Units
Type
R/W
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-18
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
063FH
0640H
0641H
0642H
0643H
0644H
0645H
0646H
0647H
0648H
0649H
064AH
064BH
064CH
064DH
064EH
064FH
0650H
0651H
0652H
0653H
0654H
0655H
0656H
0657H
0658H
0659H
065AH
065BH
065CH
065DH
065EH
065FH
0660H
0661H
0662H
0663H
0664H
0665H
0666H
0667H
0668H
0669H
066AH
066BH
066CH
066DH
066EH
066FH
0670H
0671H
0672H
0673H
0674H
0675H
0676H
01600
01601
01602
01603
01604
01605
01606
01607
01608
01609
01610
01611
01612
01613
01614
01615
01616
01617
01618
01619
01620
01621
01622
01623
01624
01625
01626
01627
01628
01629
01630
01631
01632
01633
01634
01635
01636
01637
01638
01639
01640
01641
01642
01643
01644
01645
01646
01647
01648
01649
01650
01651
01652
01653
01654
01655
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
158
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
th
Phase B Current 66 Harmonic Magnitude
th
Phase B Current 67 Harmonic Magnitude
th
Phase B Current 68 Harmonic Magnitude
th
Phase B Current 69 Harmonic Magnitude
th
Phase B Current 70 Harmonic Magnitude
st
Phase B Current 71 Harmonic Magnitude
nd
Phase B Current 72 Harmonic Magnitude
rd
Phase B Current 73 Harmonic Magnitude
th
Phase B Current 74 Harmonic Magnitude
th
Phase B Current 75 Harmonic Magnitude
th
Phase B Current 76 Harmonic Magnitude
th
Phase B Current 77 Harmonic Magnitude
th
Phase B Current 78 Harmonic Magnitude
th
Phase B Current 79 Harmonic Magnitude
th
Phase B Current 80 Harmonic Magnitude
st
Phase B Current 81 Harmonic Magnitude
nd
Phase B Current 82 Harmonic Magnitude
rd
Phase B Current 83 Harmonic Magnitude
th
Phase B Current 84 Harmonic Magnitude
th
Phase B Current 85 Harmonic Magnitude
th
Phase B Current 86 Harmonic Magnitude
th
Phase B Current 87 Harmonic Magnitude
th
Phase B Current 88 Harmonic Magnitude
th
Phase B Current 89 Harmonic Magnitude
th
Phase B Current 90 Harmonic Magnitude
st
Phase B Current 91 Harmonic Magnitude
nd
Phase B Current 92 Harmonic Magnitude
rd
Phase B Current 93 Harmonic Magnitude
th
Phase B Current 94 Harmonic Magnitude
th
Phase B Current 95 Harmonic Magnitude
th
Phase B Current 96 Harmonic Magnitude
th
Phase B Current 97 Harmonic Magnitude
th
Phase B Current 98 Harmonic Magnitude
th
Phase B Current 99 Harmonic Magnitude
th
Phase B Current 100 Harmonic Magnitude
st
Phase B Current 101 Harmonic Magnitude
nd
Phase B Current 102 Harmonic Magnitude
rd
Phase B Current 103 Harmonic Magnitude
th
Phase B Current 104 Harmonic Magnitude
th
Phase B Current 105 Harmonic Magnitude
th
Phase B Current 106 Harmonic Magnitude
th
Phase B Current 107 Harmonic Magnitude
th
Phase B Current 108 Harmonic Magnitude
th
Phase B Current 109 Harmonic Magnitude
th
Phase B Current 110 Harmonic Magnitude
th
Phase B Current 111 Harmonic Magnitude
th
Phase B Current 112 Harmonic Magnitude
th
Phase B Current 113 Harmonic Magnitude
th
Phase B Current 114 Harmonic Magnitude
th
Phase B Current 115 Harmonic Magnitude
th
Phase B Current 116 Harmonic Magnitude
th
Phase B Current 117 Harmonic Magnitude
th
Phase B Current 118 Harmonic Magnitude
th
Phase B Current 119 Harmonic Magnitude
th
Phase B Current 120 Harmonic Magnitude
st
Phase B Current 121 Harmonic Magnitude
Range
Units
Type
R/W
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-19
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
0677H
0678H
0679H
067AH
067BH
067CH
067DH
067EH
067FH
0680H
0681H
0682H
0683H
0684H
0685H
0686H
0687H
0688H
0689H
068AH
068BH
068CH
068DH
068EH
068FH
0690H
0691H
0692H
0693H
0694H
0695H
0696H
0697H
0698H
0699H
069AH
069BH
069CH
069DH
069EH
069FH
06A0H
06A1H
06A2H
06A3H
06A4H
06A5H
06A6H
06A7H
06A8H
06A9H
06AAH
06ABH
06ACH
06ADH
06AEH
01656
01657
01658
01659
01660
01661
01662
01663
01664
01665
01666
01667
01668
01669
01670
01671
01672
01673
01674
01675
01676
01677
01678
01679
01680
01681
01682
01683
01684
01685
01686
01687
01688
01689
01690
01691
01692
01693
01694
01695
01696
01697
01698
01699
01700
01701
01702
01703
01704
01705
01706
01707
01708
01709
01710
01711
158
158
158
158
158
158
159
159
159
159
159
159
159
159
160
160
160
160
160
160
160
160
161
161
161
161
161
161
161
161
161
161
161
161
161
161
161
161
162
162
162
162
162
162
162
162
162
162
162
162
162
162
162
162
162
162
58
59
60
61
62
63
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
Phase B Current 122nd Harmonic Magnitude
rd
Phase B Current 123 Harmonic Magnitude
th
Phase B Current 124 Harmonic Magnitude
th
Phase B Current 125 Harmonic Magnitude
th
Phase B Current 126 Harmonic Magnitude
th
Phase B Current 127 Harmonic Magnitude
th
Phase C Current 0 Harmonic Magnitude
st
Phase C Current 1 Harmonic Magnitude
nd
Phase C Current 2 Harmonic Magnitude
rd
Phase C Current 3 Harmonic Magnitude
th
Phase C Current 4 Harmonic Magnitude
th
Phase C Current 5 Harmonic Magnitude
th
Phase C Current 6 Harmonic Magnitude
th
Phase C Current 7 Harmonic Magnitude
th
Phase C Current 8 Harmonic Magnitude
th
Phase C Current 9 Harmonic Magnitude
th
Phase C Current 10 Harmonic Magnitude
th
Phase C Current 11 Harmonic Magnitude
th
Phase C Current 12 Harmonic Magnitude
th
Phase C Current 13 Harmonic Magnitude
th
Phase C Current 14 Harmonic Magnitude
th
Phase C Current 15 Harmonic Magnitude
th
Phase C Current 16 Harmonic Magnitude
th
Phase C Current 17 Harmonic Magnitude
th
Phase C Current 18 Harmonic Magnitude
th
Phase C Current 19 Harmonic Magnitude
th
Phase C Current 20 Harmonic Magnitude
st
Phase C Current 21 Harmonic Magnitude
nd
Phase C Current 22 Harmonic Magnitude
rd
Phase C Current 23 Harmonic Magnitude
th
Phase C Current 24 Harmonic Magnitude
th
Phase C Current 25 Harmonic Magnitude
th
Phase C Current 26 Harmonic Magnitude
th
Phase C Current 27 Harmonic Magnitude
th
Phase C Current 28 Harmonic Magnitude
th
Phase C Current 29 Harmonic Magnitude
th
Phase C Current 30 Harmonic Magnitude
st
Phase C Current 31 Harmonic Magnitude
nd
Phase C Current 32 Harmonic Magnitude
rd
Phase C Current 33 Harmonic Magnitude
th
Phase C Current 34 Harmonic Magnitude
th
Phase C Current 35 Harmonic Magnitude
th
Phase C Current 36 Harmonic Magnitude
th
Phase C Current 37 Harmonic Magnitude
th
Phase C Current 38 Harmonic Magnitude
th
Phase C Current 39 Harmonic Magnitude
th
Phase C Current 40 Harmonic Magnitude
st
Phase C Current 41 Harmonic Magnitude
nd
Phase C Current 42 Harmonic Magnitude
rd
Phase C Current43 Harmonic Magnitude
th
Phase C Current 44 Harmonic Magnitude
th
Phase C Current 45 Harmonic Magnitude
th
Phase C Current 46 Harmonic Magnitude
th
Phase C Current 47 Harmonic Magnitude
th
Phase C Current 48 Harmonic Magnitude
th
Phase C Current 49 Harmonic Magnitude
Range
Units
Type
R/W
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-20
2: Modbus Map - Holding Registers
Addr. (hex)
06AFH
06B0H
06B1H
06B2H
06B3H
06B4H
06B5H
06B6H
06B7H
06B8H
06B9H
06BAH
06BBH
06BCH
06BDH
06BEH
06BFH
06C0H
06C1H
06C2H
06C3H
06C4H
06C5H
06C6H
06C7H
06C8H
06C9H
06CAH
06CBH
06CCH
06CDH
06CEH
06CFH
06D0H
06D1H
06D2H
06D3H
06D4H
06D5H
06D6H
06D7H
06D8H
06D9H
06DAH
06DBH
06DCH
06DDH
06DEH
06DFH
06E0H
06E1H
06E2H
06E3H
06E4H
06E5H
06E6H
Address(4X)
01712
01713
01714
01715
01716
01717
01718
01719
01720
01721
01722
01723
01724
01725
01726
01727
01728
01729
01730
01731
01732
01733
01734
01735
01736
01737
01738
01739
01740
01741
01742
01743
01744
01745
01746
01747
01748
01749
01750
01751
01752
01753
01754
01755
01756
01757
01758
01759
01760
01761
01762
01763
01764
01765
01766
01767
Line
162
162
162
162
162
162
162
162
162
162
162
162
162
162
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
Pt
18
19
20
21
22
23
24
25
26
27
28
29
30
31
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
DNP
Obj
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
th
Phase C Current 50 Harmonic Magnitude
st
Phase C Current 51 Harmonic Magnitude
nd
Phase C Current 52 Harmonic Magnitude
rd
Phase C Current 53 Harmonic Magnitude
th
Phase C Current 54 Harmonic Magnitude
th
Phase C Current 55 Harmonic Magnitude
th
Phase C Current 56 Harmonic Magnitude
th
Phase C Current 57 Harmonic Magnitude
th
Phase C Current 58 Harmonic Magnitude
th
Phase C Current 59 Harmonic Magnitude
th
Phase C Current 60 Harmonic Magnitude
st
Phase C Current 61 Harmonic Magnitude
nd
Phase C Current 62 Harmonic Magnitude
rd
Phase C Current 63 Harmonic Magnitude
th
Phase C Current 64 Harmonic Magnitude
th
Phase C Current 65 Harmonic Magnitude
th
Phase C Current 66 Harmonic Magnitude
th
Phase C Current 67 Harmonic Magnitude
th
Phase C Current 68 Harmonic Magnitude
th
Phase C Current 69 Harmonic Magnitude
th
Phase C Current 70 Harmonic Magnitude
st
Phase C Current 71 Harmonic Magnitude
nd
Phase C Current 72 Harmonic Magnitude
rd
Phase C Current 73 Harmonic Magnitude
th
Phase C Current 74 Harmonic Magnitude
th
Phase C Current 75 Harmonic Magnitude
th
Phase C Current 76 Harmonic Magnitude
th
Phase C Current 77 Harmonic Magnitude
th
Phase C Current 78 Harmonic Magnitude
th
Phase C Current 79 Harmonic Magnitude
th
Phase C Current 80 Harmonic Magnitude
st
Phase C Current 81 Harmonic Magnitude
nd
Phase C Current 82 Harmonic Magnitude
rd
Phase C Current 83 Harmonic Magnitude
th
Phase C Current 84 Harmonic Magnitude
th
Phase C Current 85 Harmonic Magnitude
th
Phase C Current 86 Harmonic Magnitude
th
Phase C Current 87 Harmonic Magnitude
th
Phase C Current 88 Harmonic Magnitude
th
Phase C Current 89 Harmonic Magnitude
th
Phase C Current 90 Harmonic Magnitude
st
Phase C Current 91 Harmonic Magnitude
nd
Phase C Current 92 Harmonic Magnitude
rd
Phase C Current 93 Harmonic Magnitude
th
Phase C Current 94 Harmonic Magnitude
th
Phase C Current 95 Harmonic Magnitude
th
Phase C Current 96 Harmonic Magnitude
th
Phase C Current 97 Harmonic Magnitude
th
Phase C Current 98 Harmonic Magnitude
th
Phase C Current 99 Harmonic Magnitude
th
Phase C Current 100 Harmonic Magnitude
st
Phase C Current 101 Harmonic Magnitude
nd
Phase C Current 102 Harmonic Magnitude
rd
Phase C Current 103 Harmonic Magnitude
th
Phase C Current 104 Harmonic Magnitude
th
Phase C Current 105 Harmonic Magnitude
Range
Units
Type
R/W
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-21
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
06E7H
06E8H
06E9H
06EAH
06EBH
06ECH
06EDH
06EEH
06EFH
06F0H
06F1H
06F2H
06F3H
06F4H
06F5H
06F6H
06F7H
06F8H
06F9H
06FAH
06FBH
06FCH
01768
01769
01770
01771
01772
01773
01774
01775
01776
01777
01778
01779
01780
01781
01782
01783
01784
01785
01786
01787
01788
01789
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
163
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Phase C Current 106th Harmonic Magnitude
th
Phase C Current 107 Harmonic Magnitude
th
Phase C Current 108 Harmonic Magnitude
th
Phase C Current 109 Harmonic Magnitude
th
Phase C Current 110 Harmonic Magnitude
th
Phase C Current 111 Harmonic Magnitude
th
Phase C Current 112 Harmonic Magnitude
th
Phase C Current 113 Harmonic Magnitude
th
Phase C Current 114 Harmonic Magnitude
th
Phase C Current 115 Harmonic Magnitude
th
Phase C Current 116 Harmonic Magnitude
th
Phase C Current 117 Harmonic Magnitude
th
Phase C Current 118 Harmonic Magnitude
th
Phase C Current 119 Harmonic Magnitude
th
Phase C Current 120 Harmonic Magnitude
st
Phase C Current 121 Harmonic Magnitude
nd
Phase C Current 122 Harmonic Magnitude
rd
Phase C Current 123 Harmonic Magnitude
th
Phase C Current 124 Harmonic Magnitude
th
Phase C Current 125 Harmonic Magnitude
th
Phase C Current 126 Harmonic Magnitude
th
Phase C Current 127 Harmonic Magnitude
06FDH
06FEH
06FFH
0700H
0701H
0702H
0703H
0704H
0705H
0706H
0707H
0708H
0709H
070AH
070BH
070CH
070DH
070EH
070FH
0710H
0711H
0712H
0713H
0714H
0715H
0716H
0717H
0718H
0719H
071AH
071BH
071CH
071DH
01790
01791
01792
01793
01794
01795
01796
01797
01798
01799
01800
01801
01802
01803
01804
01805
01806
01807
01808
01809
01810
01811
01812
01813
01814
01815
01816
01817
01818
01819
01820
01821
01822
164
164
164
164
164
164
164
164
165
165
165
165
165
165
165
165
166
166
166
166
166
166
166
166
166
166
166
166
166
166
166
166
167
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Phase A-N / Phase A-B Voltage 0 Harmonic Phase
st
Phase A-N / Phase A-B Voltage 1 Harmonic Phase
nd
Phase A-N / Phase A-B Voltage 2 Harmonic Phase
rd
Phase A-N / Phase A-B Voltage 3 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 4 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 5 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 6 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 7 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 8 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 9 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 10 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 11 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 12 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 13 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 14 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 15 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 16 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 17 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 18 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 19 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 20 Harmonic Phase
st
Phase A-N / Phase A-B Voltage 21 Harmonic Phase
Phase A-N / Phase A-B Voltage 22nd Harmonic Phase
rd
Phase A-N / Phase A-B Voltage 23 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 24 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 25 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 26 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 27 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 28 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 29 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 30 Harmonic Phase
st
Phase A-N / Phase A-B Voltage 31 Harmonic Phase
nd
Phase A-N / Phase A-B Voltage 32 Harmonic Phase
Description
th
Range
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
Harmonic Phase Block
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
Units
Type
R/W
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-22
2: Modbus Map - Holding Registers
Addr. (hex)
071EH
071FH
0720H
0721H
0722H
0723H
0724H
0725H
0726H
0727H
0728H
0729H
072AH
072BH
072CH
072DH
072EH
072FH
0730H
0731H
0732H
0733H
0734H
0735H
0736H
0737H
0738H
0739H
073AH
073BH
073CH
073DH
073EH
073FH
0740H
0741H
0742H
0743H
0744H
0745H
0746H
0747H
0748H
0749H
074AH
074BH
074CH
074DH
074EH
074FH
0750H
0751H
0752H
0753H
0754H
0755H
Address(4X)
01823
01824
01825
01826
01827
01828
01829
01830
01831
01832
01833
01834
01835
01836
01837
01838
01839
01840
01841
01842
01843
01844
01845
01846
01847
01848
01849
01850
01851
01852
01853
01854
01855
01856
01857
01858
01859
01860
01861
01862
01863
01864
01865
01866
01867
01868
01869
01870
01871
01872
01873
01874
01875
01876
01877
01878
Line
167
167
167
167
167
167
167
167
167
167
167
167
167
167
167
167
167
167
167
167
167
167
167
167
167
167
167
167
167
167
167
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
Pt
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
DNP
Obj
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
rd
Phase A-N / Phase A-B Voltage 33 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 34 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 35 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 36 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 37 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 38 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 39 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 40 Harmonic Phase
st
Phase A-N / Phase A-B Voltage 41 Harmonic Phase
nd
Phase A-N / Phase A-B Voltage 42 Harmonic Phase
rd
Phase A-N / Phase A-B Voltage 43 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 44 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 45 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 46 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 47 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 48 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 49 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 50 Harmonic Phase
st
Phase A-N / Phase A-B Voltage 51 Harmonic Phase
nd
Phase A-N / Phase A-B Voltage 52 Harmonic Phase
rd
Phase A-N / Phase A-B Voltage 53 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 54 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 55 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 56 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 57 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 58 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 59 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 60 Harmonic Phase
st
Phase A-N / Phase A-B Voltage 61 Harmonic Phase
nd
Phase A-N / Phase A-B Voltage 62 Harmonic Phase
rd
Phase A-N / Phase A-B Voltage 63 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 64 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 65 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 66 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 67 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 68 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 69 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 70 Harmonic Phase
st
Phase A-N / Phase A-B Voltage 71 Harmonic Phase
nd
Phase A-N / Phase A-B Voltage 72 Harmonic Phase
rd
Phase A-N / Phase A-B Voltage 73 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 74 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 75 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 76 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 77 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 78 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 79 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 80 Harmonic Phase
st
Phase A-N / Phase A-B Voltage 81 Harmonic Phase
nd
Phase A-N / Phase A-B Voltage 82 Harmonic Phase
rd
Phase A-N / Phase A-B Voltage 83 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 84 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 85 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 86 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 87 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 88 Harmonic Phase
Range
Units
Type
R/W
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-23
2: Modbus Map - Holding Registers
Addr. (hex)
0756H
0757H
0758H
0759H
075AH
075BH
075CH
075DH
075EH
075FH
0760H
0761H
0762H
0763H
0764H
0765H
0766H
0767H
0768H
0769H
076AH
076BH
076CH
076DH
076EH
076FH
0770H
0771H
0772H
0773H
0774H
0775H
0776H
0777H
0778H
0779H
077AH
077BH
077CH
077DH
077EH
077FH
0780H
0781H
0782H
0783H
0784H
0785H
0786H
0787H
0788H
0789H
078AH
078BH
078CH
078DH
Address(4X)
01879
01880
01881
01882
01883
01884
01885
01886
01887
01888
01889
01890
01891
01892
01893
01894
01895
01896
01897
01898
01899
01900
01901
01902
01903
01904
01905
01906
01907
01908
01909
01910
01911
01912
01913
01914
01915
01916
01917
01918
01919
01920
01921
01922
01923
01924
01925
01926
01927
01928
01929
01930
01931
01932
01933
01934
Line
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
168
169
169
169
169
169
169
169
169
170
170
170
170
170
170
170
170
171
Pt
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
0
DNP
Obj
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
th
Phase A-N / Phase A-B Voltage 89 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 90 Harmonic Phase
st
Phase A-N / Phase A-B Voltage 91 Harmonic Phase
nd
Phase A-N / Phase A-B Voltage 92 Harmonic Phase
rd
Phase A-N / Phase A-B Voltage 93 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 94 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 95 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 96 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 97 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 98 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 99 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 100 Harmonic Phase
st
Phase A-N / Phase A-B Voltage 101 Harmonic Phase
nd
Phase A-N / Phase A-B Voltage 102 Harmonic Phase
rd
Phase A-N / Phase A-B Voltage 103 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 104 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 105 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 106 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 107 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 108 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 109 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 110 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 111 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 112 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 113 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 114 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 115 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 116 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 117 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 118 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 119 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 120 Harmonic Phase
st
Phase A-N / Phase A-B Voltage 121 Harmonic Phase
nd
Phase A-N / Phase A-B Voltage 122 Harmonic Phase
rd
Phase A-N / Phase A-B Voltage 123 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 124 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 125 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 126 Harmonic Phase
th
Phase A-N / Phase A-B Voltage 127 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 0 Harmonic Phase
st
Phase B-N / Phase B-C Voltage 1 Harmonic Phase
nd
Phase B-N / Phase B-C Voltage 2 Harmonic Phase
rd
Phase B-N / Phase B-C Voltage 3 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 4 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 5 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 6 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 7 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 8 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 9 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 10 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 11 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 12 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 13 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 14 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 15 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 16 Harmonic Phase
Range
Units
Type
R/W
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-24
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
078EH
078FH
0790H
0791H
0792H
0793H
0794H
0795H
0796H
0797H
0798H
0799H
079AH
079BH
079CH
079DH
079EH
079FH
07A0H
07A1H
07A2H
07A3H
07A4H
07A5H
07A6H
07A7H
07A8H
07A9H
07AAH
07ABH
07ACH
07ADH
07AEH
07AFH
07B0H
07B1H
07B2H
07B3H
07B4H
07B5H
07B6H
07B7H
07B8H
07B9H
07BAH
07BBH
07BCH
07BDH
07BEH
07BFH
07C0H
07C1H
07C2H
07C3H
07C4H
07C5H
01935
01936
01937
01938
01939
01940
01941
01942
01943
01944
01945
01946
01947
01948
01949
01950
01951
01952
01953
01954
01955
01956
01957
01958
01959
01960
01961
01962
01963
01964
01965
01966
01967
01968
01969
01970
01971
01972
01973
01974
01975
01976
01977
01978
01979
01980
01981
01982
01983
01984
01985
01986
01987
01988
01989
01990
171
171
171
171
171
171
171
171
171
171
171
171
171
171
171
172
172
172
172
172
172
172
172
172
172
172
172
172
172
172
172
172
172
172
172
172
172
172
172
172
172
172
172
172
172
172
172
173
173
173
173
173
173
173
173
173
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
0
1
2
3
4
5
6
7
8
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
th
Phase B-N / Phase B-C Voltage 17 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 18 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 19 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 20 Harmonic Phase
st
Phase B-N / Phase B-C Voltage 21 Harmonic Phase
nd
Phase B-N / Phase B-C Voltage 22 Harmonic Phase
rd
Phase B-N / Phase B-C Voltage 23 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 24 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 25 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 26 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 27 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 28 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 29 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 30 Harmonic Phase
st
Phase B-N / Phase B-C Voltage 31 Harmonic Phase
nd
Phase B-N / Phase B-C Voltage 32 Harmonic Phase
rd
Phase B-N / Phase B-C Voltage 33 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 34 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 35 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 36 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 37 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 38 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 39 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 40 Harmonic Phase
st
Phase B-N / Phase B-C Voltage 41 Harmonic Phase
nd
Phase B-N / Phase B-C Voltage 42 Harmonic Phase
rd
Phase B-N / Phase B-C Voltage 43 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 44 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 45 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 46 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 47 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 48 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 49 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 50 Harmonic Phase
st
Phase B-N / Phase B-C Voltage 51 Harmonic Phase
nd
Phase B-N / Phase B-C Voltage 52 Harmonic Phase
rd
Phase B-N / Phase B-C Voltage 53 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 54 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 55 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 56 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 57 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 58 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 59 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 60 Harmonic Phase
st
Phase B-N / Phase B-C Voltage 61 Harmonic Phase
nd
Phase B-N / Phase B-C Voltage 62 Harmonic Phase
rd
Phase B-N / Phase B-C Voltage 63 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 64 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 65 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 66 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 67 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 68 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 69 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 70 Harmonic Phase
st
Phase B-N / Phase B-C Voltage 71 Harmonic Phase
nd
Phase B-N / Phase B-C Voltage 72 Harmonic Phase
Range
Units
Type
R/W
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-25
2: Modbus Map - Holding Registers
Addr. (hex)
07C6H
07C7H
07C8H
07C9H
07CAH
07CBH
07CCH
07CDH
07CEH
07CFH
07D0H
07D1H
07D2H
07D3H
07D4H
07D5H
07D6H
07D7H
07D8H
07D9H
07DAH
07DBH
07DCH
07DDH
07DEH
07DFH
07E0H
07E1H
07E2H
07E3H
07E4H
07E5H
07E6H
07E7H
07E8H
07E9H
07EAH
07EBH
07ECH
07EDH
07EEH
07EFH
07F0H
07F1H
07F2H
07F3H
07F4H
07F5H
07F6H
07F7H
07F8H
07F9H
07FAH
07FBH
07FCH
07FDH
Address(4X)
01991
01992
01993
01994
01995
01996
01997
01998
01999
02000
02001
02002
02003
02004
02005
02006
02007
02008
02009
02010
02011
02012
02013
02014
02015
02016
02017
02018
02019
02020
02021
02022
02023
02024
02025
02026
02027
02028
02029
02030
02031
02032
02033
02034
02035
02036
02037
02038
02039
02040
02041
02042
02043
02044
02045
02046
Line
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
173
174
Pt
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
0
DNP
Obj
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
rd
Phase B-N / Phase B-C Voltage 73 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 74 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 75 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 76 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 77 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 78 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 79 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 80 Harmonic Phase
st
Phase B-N / Phase B-C Voltage 81 Harmonic Phase
nd
Phase B-N / Phase B-C Voltage 82 Harmonic Phase
rd
Phase B-N / Phase B-C Voltage 83 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 84 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 85 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 86 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 87 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 88 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 89 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 90 Harmonic Phase
st
Phase B-N / Phase B-C Voltage 91 Harmonic Phase
nd
Phase B-N / Phase B-C Voltage 92 Harmonic Phase
rd
Phase B-N / Phase B-C Voltage 93 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 94 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 95 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 96 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 97 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 98 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 99 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 100 Harmonic Phase
st
Phase B-N / Phase B-C Voltage 101 Harmonic Phase
nd
Phase B-N / Phase B-C Voltage 102 Harmonic Phase
rd
Phase B-N / Phase B-C Voltage 103 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 104 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 105 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 106 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 107 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 108 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 109 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 110 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 111 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 112 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 113 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 114 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 115 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 116 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 117 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 118 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 119 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 120 Harmonic Phase
st
Phase B-N / Phase B-C Voltage 121 Harmonic Phase
nd
Phase B-N / Phase B-C Voltage 122 Harmonic Phase
rd
Phase B-N / Phase B-C Voltage 123 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 124 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 125 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 126 Harmonic Phase
th
Phase B-N / Phase B-C Voltage 127 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 0 Harmonic Phase
Range
Units
Type
R/W
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-26
2: Modbus Map - Holding Registers
Addr. (hex)
07FEH
07FFH
0800H
0801H
0802H
0803H
0804H
0805H
0806H
0807H
0808H
0809H
080AH
080BH
080CH
080DH
080EH
080FH
0810H
0811H
0812H
0813H
0814H
0815H
0816H
0817H
0818H
0819H
081AH
081BH
081CH
081DH
081EH
081FH
0820H
0821H
0822H
0823H
0824H
0825H
0826H
0827H
0828H
0829H
082AH
082BH
082CH
082DH
082EH
082FH
0830H
0831H
0832H
0833H
0834H
0835H
Address(4X)
02047
02048
02049
02050
02051
02052
02053
02054
02055
02056
02057
02058
02059
02060
02061
02062
02063
02064
02065
02066
02067
02068
02069
02070
02071
02072
02073
02074
02075
02076
02077
02078
02079
02080
02081
02082
02083
02084
02085
02086
02087
02088
02089
02090
02091
02092
02093
02094
02095
02096
02097
02098
02099
02100
02101
02102
Line
174
174
174
174
174
174
174
175
175
175
175
175
175
175
175
176
176
176
176
176
176
176
176
176
176
176
176
176
176
176
176
177
177
177
177
177
177
177
177
177
177
177
177
177
177
177
177
177
177
177
177
177
177
177
177
177
Pt
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
DNP
Obj
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
st
Phase C-N / Phase C-A Voltage 1 Harmonic Phase
nd
Phase C-N / Phase C-A Voltage 2 Harmonic Phase
rd
Phase C-N / Phase C-A Voltage 3 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 4 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 5 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 6 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 7 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 8 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 9 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 10 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 11 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 12 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 13 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 14 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 15 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 16 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 17 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 18 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 19 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 20 Harmonic Phase
st
Phase C-N / Phase C-A Voltage 21 Harmonic Phase
nd
Phase C-N / Phase C-A Voltage 22 Harmonic Phase
rd
Phase C-N / Phase C-A Voltage 23 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 24 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 25 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 26 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 27 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 28 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 29 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 30 Harmonic Phase
st
Phase C-N / Phase C-A Voltage 31 Harmonic Phase
nd
Phase C-N / Phase C-A Voltage 32 Harmonic Phase
rd
Phase C-N / Phase C-A Voltage 33 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 34 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 35 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 36 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 37 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 38 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 39 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 40 Harmonic Phase
st
Phase C-N / Phase C-A Voltage 41 Harmonic Phase
nd
Phase C-N / Phase C-A Voltage 42 Harmonic Phase
rd
Phase C-N / Phase C-A Voltage 43 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 44 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 45 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 46 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 47 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 48 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 49 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 50 Harmonic Phase
st
Phase C-N / Phase C-A Voltage 51 Harmonic Phase
nd
Phase C-N / Phase C-A Voltage 52 Harmonic Phase
rd
Phase C-N / Phase C-A Voltage 53 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 54 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 55 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 56 Harmonic Phase
Range
Units
Type
R/W
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-27
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
0836H
0837H
0838H
0839H
083AH
083BH
083CH
083DH
083EH
083FH
0840H
0841H
0842H
0843H
0844H
0845H
0846H
0847H
0848H
0849H
084AH
084BH
084CH
084DH
084EH
084FH
0850H
0851H
0852H
0853H
0854H
0855H
0856H
0857H
0858H
0859H
085AH
085BH
085CH
085DH
085EH
085FH
0860H
0861H
0862H
0863H
0864H
0865H
0866H
0867H
0868H
0869H
086AH
086BH
086CH
086DH
02103
02104
02105
02106
02107
02108
02109
02110
02111
02112
02113
02114
02115
02116
02117
02118
02119
02120
02121
02122
02123
02124
02125
02126
02127
02128
02129
02130
02131
02132
02133
02134
02135
02136
02137
02138
02139
02140
02141
02142
02143
02144
02145
02146
02147
02148
02149
02150
02151
02152
02153
02154
02155
02156
02157
02158
177
177
177
177
177
177
177
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
25
26
27
28
29
30
31
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
Phase C-N / Phase C-A Voltage 57th Harmonic Phase
th
Phase C-N / Phase C-A Voltage 58 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 59 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 60 Harmonic Phase
st
Phase C-N / Phase C-A Voltage 61 Harmonic Phase
nd
Phase C-N / Phase C-A Voltage 62 Harmonic Phase
rd
Phase C-N / Phase C-A Voltage 63 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 64 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 65 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 66 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 67 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 68 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 69 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 70 Harmonic Phase
st
Phase C-N / Phase C-A Voltage 71 Harmonic Phase
nd
Phase C-N / Phase C-A Voltage 72 Harmonic Phase
rd
Phase C-N / Phase C-A Voltage 73 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 74 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 75 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 76 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 77 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 78 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 79 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 80 Harmonic Phase
st
Phase C-N / Phase C-A Voltage 81 Harmonic Phase
nd
Phase C-N / Phase C-A Voltage 82 Harmonic Phase
rd
Phase C-N / Phase C-A Voltage 83 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 84 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 85 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 86 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 87 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 88 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 89 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 90 Harmonic Phase
st
Phase C-N / Phase C-A Voltage 91 Harmonic Phase
nd
Phase C-N / Phase C-A Voltage 92 Harmonic Phase
rd
Phase C-N / Phase C-A Voltage 93 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 94 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 95 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 96 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 97 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 98 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 99 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 100 Harmonic Phase
st
Phase C-N / Phase C-A Voltage 101 Harmonic Phase
nd
Phase C-N / Phase C-A Voltage 102 Harmonic Phase
rd
Phase C-N / Phase C-A Voltage 103 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 104 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 105 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 106 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 107 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 108 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 109 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 110 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 111 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 112 Harmonic Phase
Range
Units
Type
R/W
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-28
2: Modbus Map - Holding Registers
Addr. (hex)
086EH
086FH
0870H
0871H
0872H
0873H
0874H
0875H
0876H
0877H
0878H
0879H
087AH
087BH
087CH
087DH
087EH
087FH
0880H
0881H
0882H
0883H
0884H
0885H
0886H
0887H
0888H
0889H
088AH
088BH
088CH
088DH
088EH
088FH
0890H
0891H
0892H
0893H
0894H
0895H
0896H
0897H
0898H
0899H
089AH
089BH
089CH
089DH
089EH
089FH
08A0H
08A1H
08A2H
08A3H
08A4H
08A5H
Address(4X)
02159
02160
02161
02162
02163
02164
02165
02166
02167
02168
02169
02170
02171
02172
02173
02174
02175
02176
02177
02178
02179
02180
02181
02182
02183
02184
02185
02186
02187
02188
02189
02190
02191
02192
02193
02194
02195
02196
02197
02198
02199
02200
02201
02202
02203
02204
02205
02206
02207
02208
02209
02210
02211
02212
02213
02214
Line
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
179
179
179
179
179
179
179
179
180
180
180
180
180
180
180
180
181
181
181
181
181
181
181
181
181
181
181
181
181
181
181
181
182
182
182
182
182
182
182
182
182
Pt
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
DNP
Obj
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
th
Phase C-N / Phase C-A Voltage 113 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 114 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 115 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 116 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 117 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 118 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 119 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 120 Harmonic Phase
st
Phase C-N / Phase C-A Voltage 121 Harmonic Phase
nd
Phase C-N / Phase C-A Voltage 122 Harmonic Phase
rd
Phase C-N / Phase C-A Voltage 123 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 124 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 125 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 126 Harmonic Phase
th
Phase C-N / Phase C-A Voltage 127 Harmonic Phase
th
Phase A Current 0 Harmonic Phase
st
Phase A Current 1 Harmonic Phase
nd
Phase A Current 2 Harmonic Phase
rd
Phase A Current 3 Harmonic Phase
th
Phase A Current 4 Harmonic Phase
th
Phase A Current 5 Harmonic Phase
th
Phase A Current 6 Harmonic Phase
th
Phase A Current 7 Harmonic Phase
th
Phase A Current 8 Harmonic Phase
th
Phase A Current 9 Harmonic Phase
th
Phase A Current 10 Harmonic Phase
th
Phase A Current 11 Harmonic Phase
th
Phase A Current 12 Harmonic Phase
th
Phase A Current 13 Harmonic Phase
th
Phase A Current 14 Harmonic Phase
th
Phase A Current 15 Harmonic Phase
th
Phase A Current 16 Harmonic Phase
th
Phase A Current 17 Harmonic Phase
th
Phase A Current 18 Harmonic Phase
th
Phase A Current 19 Harmonic Phase
th
Phase A Current 20 Harmonic Phase
st
Phase A Current 21 Harmonic Phase
nd
Phase A Current 22 Harmonic Phase
rd
Phase A Current 23 Harmonic Phase
th
Phase A Current 24 Harmonic Phase
th
Phase A Current 25 Harmonic Phase
th
Phase A Current 26 Harmonic Phase
th
Phase A Current 27 Harmonic Phase
th
Phase A Current 28 Harmonic Phase
th
Phase A Current 29 Harmonic Phase
th
Phase A Current 30 Harmonic Phase
st
Phase A Current 31 Harmonic Phase
nd
Phase A Current 32 Harmonic Phase
Phase A Current 33rd Harmonic Phase
th
Phase A Current 34 Harmonic Phase
th
Phase A Current 35 Harmonic Phase
th
Phase A Current 36 Harmonic Phase
th
Phase A Current 37 Harmonic Phase
th
Phase A Current 38 Harmonic Phase
th
Phase A Current 39 Harmonic Phase
Phase A Current 40th Harmonic Phase
Range
Units
Type
R/W
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-29
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
08A6H
08A7H
08A8H
08A9H
08AAH
08ABH
08ACH
08ADH
08AEH
08AFH
08B0H
08B1H
08B2H
08B3H
08B4H
08B5H
08B6H
08B7H
08B8H
08B9H
08BAH
08BBH
08BCH
08BDH
08BEH
08BFH
08C0H
08C1H
08C2H
08C3H
08C4H
08C5H
08C6H
08C7H
08C8H
08C9H
08CAH
08CBH
08CCH
08CDH
08CEH
08CFH
08D0H
08D1H
08D2H
08D3H
08D4H
08D5H
08D6H
08D7H
08D8H
08D9H
08DAH
08DBH
08DCH
08DDH
02215
02216
02217
02218
02219
02220
02221
02222
02223
02224
02225
02226
02227
02228
02229
02230
02231
02232
02233
02234
02235
02236
02237
02238
02239
02240
02241
02242
02243
02244
02245
02246
02247
02248
02249
02250
02251
02252
02253
02254
02255
02256
02257
02258
02259
02260
02261
02262
02263
02264
02265
02266
02267
02268
02269
02270
182
182
182
182
182
182
182
182
182
182
182
182
182
182
182
182
182
182
182
182
182
182
182
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
Phase A Current 41st Harmonic Phase
nd
Phase A Current 42 Harmonic Phase
rd
Phase A Current43 Harmonic Phase
th
Phase A Current 44 Harmonic Phase
th
Phase A Current 45 Harmonic Phase
th
Phase A Current 46 Harmonic Phase
th
Phase A Current 47 Harmonic Phase
th
Phase A Current 48 Harmonic Phase
th
Phase A Current 49 Harmonic Phase
th
Phase A Current 50 Harmonic Phase
st
Phase A Current 51 Harmonic Phase
nd
Phase A Current 52 Harmonic Phase
rd
Phase A Current 53 Harmonic Phase
th
Phase A Current 54 Harmonic Phase
th
Phase A Current 55 Harmonic Phase
th
Phase A Current 56 Harmonic Phase
th
Phase A Current 57 Harmonic Phase
th
Phase A Current 58 Harmonic Phase
th
Phase A Current 59 Harmonic Phase
th
Phase A Current 60 Harmonic Phase
st
Phase A Current 61 Harmonic Phase
nd
Phase A Current 62 Harmonic Phase
rd
Phase A Current 63 Harmonic Phase
th
Phase A Current 64 Harmonic Phase
th
Phase A Current 65 Harmonic Phase
th
Phase A Current 66 Harmonic Phase
th
Phase A Current 67 Harmonic Phase
th
Phase A Current 68 Harmonic Phase
th
Phase A Current 69 Harmonic Phase
th
Phase A Current 70 Harmonic Phase
st
Phase A Current 71 Harmonic Phase
nd
Phase A Current 72 Harmonic Phase
rd
Phase A Current 73 Harmonic Phase
th
Phase A Current 74 Harmonic Phase
th
Phase A Current 75 Harmonic Phase
th
Phase A Current 76 Harmonic Phase
th
Phase A Current 77 Harmonic Phase
th
Phase A Current 78 Harmonic Phase
th
Phase A Current 79 Harmonic Phase
th
Phase A Current 80 Harmonic Phase
st
Phase A Current 81 Harmonic Phase
nd
Phase A Current 82 Harmonic Phase
rd
Phase A Current 83 Harmonic Phase
th
Phase A Current 84 Harmonic Phase
th
Phase A Current 85 Harmonic Phase
th
Phase A Current 86 Harmonic Phase
th
Phase A Current 87 Harmonic Phase
th
Phase A Current 88 Harmonic Phase
th
Phase A Current 89 Harmonic Phase
th
Phase A Current 90 Harmonic Phase
st
Phase A Current 91 Harmonic Phase
nd
Phase A Current 92 Harmonic Phase
rd
Phase A Current 93 Harmonic Phase
th
Phase A Current 94 Harmonic Phase
th
Phase A Current 95 Harmonic Phase
th
Phase A Current 96 Harmonic Phase
Range
Units
Type
R/W
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-30
2: Modbus Map - Holding Registers
Addr. (hex)
08DEH
08DFH
08E0H
08E1H
08E2H
08E3H
08E4H
08E5H
08E6H
08E7H
08E8H
08E9H
08EAH
08EBH
08ECH
08EDH
08EEH
08EFH
08F0H
08F1H
08F2H
08F3H
08F4H
08F5H
08F6H
08F7H
08F8H
08F9H
08FAH
08FBH
08FCH
08FDH
08FEH
08FFH
0900H
0901H
0902H
0903H
0904H
0905H
0906H
0907H
0908H
0909H
090AH
090BH
090CH
090DH
090EH
090FH
0910H
0911H
0912H
0913H
0914H
0915H
Address(4X)
02271
02272
02273
02274
02275
02276
02277
02278
02279
02280
02281
02282
02283
02284
02285
02286
02287
02288
02289
02290
02291
02292
02293
02294
02295
02296
02297
02298
02299
02300
02301
02302
02303
02304
02305
02306
02307
02308
02309
02310
02311
02312
02313
02314
02315
02316
02317
02318
02319
02320
02321
02322
02323
02324
02325
02326
Line
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
183
184
184
184
184
184
184
184
184
185
185
185
185
185
185
185
185
186
186
186
186
186
186
186
186
186
Pt
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
8
DNP
Obj
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
th
Phase A Current 97 Harmonic Phase
th
Phase A Current 98 Harmonic Phase
th
Phase A Current 99 Harmonic Phase
th
Phase A Current 100 Harmonic Phase
st
Phase A Current 101 Harmonic Phase
nd
Phase A Current 102 Harmonic Phase
rd
Phase A Current 103 Harmonic Phase
th
Phase A Current 104 Harmonic Phase
th
Phase A Current 105 Harmonic Phase
th
Phase A Current 106 Harmonic Phase
th
Phase A Current 107 Harmonic Phase
th
Phase A Current 108 Harmonic Phase
th
Phase A Current 109 Harmonic Phase
th
Phase A Current 110 Harmonic Phase
th
Phase A Current 111 Harmonic Phase
th
Phase A Current 112 Harmonic Phase
th
Phase A Current 113 Harmonic Phase
th
Phase A Current 114 Harmonic Phase
th
Phase A Current 115 Harmonic Phase
th
Phase A Current 116 Harmonic Phase
th
Phase A Current 117 Harmonic Phase
th
Phase A Current 118 Harmonic Phase
th
Phase A Current 119 Harmonic Phase
th
Phase A Current 120 Harmonic Phase
st
Phase A Current 121 Harmonic Phase
nd
Phase A Current 122 Harmonic Phase
rd
Phase A Current 123 Harmonic Phase
th
Phase A Current 124 Harmonic Phase
th
Phase A Current 125 Harmonic Phase
th
Phase A Current 126 Harmonic Phase
th
Phase A Current 127 Harmonic Phase
th
Phase B Current 0 Harmonic Phase
st
Phase B Current 1 Harmonic Phase
nd
Phase B Current 2 Harmonic Phase
rd
Phase B Current 3 Harmonic Phase
th
Phase B Current 4 Harmonic Phase
th
Phase B Current 5 Harmonic Phase
th
Phase B Current 6 Harmonic Phase
th
Phase B Current 7 Harmonic Phase
th
Phase B Current 8 Harmonic Phase
th
Phase B Current 9 Harmonic Phase
th
Phase B Current 10 Harmonic Phase
th
Phase B Current 11 Harmonic Phase
th
Phase B Current 12 Harmonic Phase
th
Phase B Current 13 Harmonic Phase
th
Phase B Current 14 Harmonic Phase
th
Phase B Current 15 Harmonic Phase
th
Phase B Current 16 Harmonic Phase
th
Phase B Current 17 Harmonic Phase
th
Phase B Current 18 Harmonic Phase
th
Phase B Current 19 Harmonic Phase
th
Phase B Current 20 Harmonic Phase
st
Phase B Current 21 Harmonic Phase
nd
Phase B Current 22 Harmonic Phase
rd
Phase B Current 23 Harmonic Phase
th
Phase B Current 24 Harmonic Phase
Range
Units
Type
R/W
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-31
2: Modbus Map - Holding Registers
Addr. (hex)
0916H
0917H
0918H
0919H
091AH
091BH
091CH
091DH
091EH
091FH
0920H
0921H
0922H
0923H
0924H
0925H
0926H
0927H
0928H
0929H
092AH
092BH
092CH
092DH
092EH
092FH
0930H
0931H
0932H
0933H
0934H
0935H
0936H
0937H
0938H
0939H
093AH
093BH
093CH
093DH
093EH
093FH
0940H
0941H
0942H
0943H
0944H
0945H
0946H
0947H
0948H
0949H
094AH
094BH
094CH
094DH
Address(4X)
02327
02328
02329
02330
02331
02332
02333
02334
02335
02336
02337
02338
02339
02340
02341
02342
02343
02344
02345
02346
02347
02348
02349
02350
02351
02352
02353
02354
02355
02356
02357
02358
02359
02360
02361
02362
02363
02364
02365
02366
02367
02368
02369
02370
02371
02372
02373
02374
02375
02376
02377
02378
02379
02380
02381
02382
Line
186
186
186
186
186
186
186
187
187
187
187
187
187
187
187
187
187
187
187
187
187
187
187
187
187
187
187
187
187
187
187
187
187
187
187
187
187
187
187
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
Pt
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
DNP
Obj
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
th
Phase B Current 25 Harmonic Phase
th
Phase B Current 26 Harmonic Phase
th
Phase B Current 27 Harmonic Phase
th
Phase B Current 28 Harmonic Phase
th
Phase B Current 29 Harmonic Phase
th
Phase B Current 30 Harmonic Phase
st
Phase B Current 31 Harmonic Phase
nd
Phase B Current 32 Harmonic Phase
rd
Phase B Current 33 Harmonic Phase
th
Phase B Current 34 Harmonic Phase
th
Phase B Current 35 Harmonic Phase
th
Phase B Current 36 Harmonic Phase
th
Phase B Current 37 Harmonic Phase
th
Phase B Current 38 Harmonic Phase
th
Phase B Current 39 Harmonic Phase
th
Phase B Current 40 Harmonic Phase
st
Phase B Current 41 Harmonic Phase
nd
Phase B Current 42 Harmonic Phase
rd
Phase B Current43 Harmonic Phase
th
Phase B Current 44 Harmonic Phase
th
Phase B Current 45 Harmonic Phase
th
Phase B Current 46 Harmonic Phase
th
Phase B Current 47 Harmonic Phase
th
Phase B Current 48 Harmonic Phase
th
Phase B Current 49 Harmonic Phase
th
Phase B Current 50 Harmonic Phase
st
Phase B Current 51 Harmonic Phase
nd
Phase B Current 52 Harmonic Phase
rd
Phase B Current 53 Harmonic Phase
th
Phase B Current 54 Harmonic Phase
th
Phase B Current 55 Harmonic Phase
th
Phase B Current 56 Harmonic Phase
th
Phase B Current 57 Harmonic Phase
th
Phase B Current 58 Harmonic Phase
th
Phase B Current 59 Harmonic Phase
th
Phase B Current 60 Harmonic Phase
st
Phase B Current 61 Harmonic Phase
nd
Phase B Current 62 Harmonic Phase
rd
Phase B Current 63 Harmonic Phase
th
Phase B Current 64 Harmonic Phase
th
Phase B Current 65 Harmonic Phase
th
Phase B Current 66 Harmonic Phase
th
Phase B Current 67 Harmonic Phase
th
Phase B Current 68 Harmonic Phase
th
Phase B Current 69 Harmonic Phase
th
Phase B Current 70 Harmonic Phase
st
Phase B Current 71 Harmonic Phase
nd
Phase B Current 72 Harmonic Phase
rd
Phase B Current 73 Harmonic Phase
th
Phase B Current 74 Harmonic Phase
th
Phase B Current 75 Harmonic Phase
th
Phase B Current 76 Harmonic Phase
th
Phase B Current 77 Harmonic Phase
th
Phase B Current 78 Harmonic Phase
th
Phase B Current 79 Harmonic Phase
th
Phase B Current 80 Harmonic Phase
Range
Units
Type
R/W
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-32
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
094EH
094FH
0950H
0951H
0952H
0953H
0954H
0955H
0956H
0957H
0958H
0959H
095AH
095BH
095CH
095DH
095EH
095FH
0960H
0961H
0962H
0963H
0964H
0965H
0966H
0967H
0968H
0969H
096AH
096BH
096CH
096DH
096EH
096FH
0970H
0971H
0972H
0973H
0974H
0975H
0976H
0977H
0978H
0979H
097AH
097BH
097CH
097DH
097EH
097FH
0980H
0981H
0982H
0983H
0984H
0985H
02383
02384
02385
02386
02387
02388
02389
02390
02391
02392
02393
02394
02395
02396
02397
02398
02399
02400
02401
02402
02403
02404
02405
02406
02407
02408
02409
02410
02411
02412
02413
02414
02415
02416
02417
02418
02419
02420
02421
02422
02423
02424
02425
02426
02427
02428
02429
02430
02431
02432
02433
02434
02435
02436
02437
02438
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
188
189
189
189
189
189
189
189
189
190
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
0
1
2
3
4
5
6
7
0
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
st
Phase B Current 81 Harmonic Phase
nd
Phase B Current 82 Harmonic Phase
rd
Phase B Current 83 Harmonic Phase
th
Phase B Current 84 Harmonic Phase
th
Phase B Current 85 Harmonic Phase
th
Phase B Current 86 Harmonic Phase
th
Phase B Current 87 Harmonic Phase
th
Phase B Current 88 Harmonic Phase
th
Phase B Current 89 Harmonic Phase
th
Phase B Current 90 Harmonic Phase
st
Phase B Current 91 Harmonic Phase
nd
Phase B Current 92 Harmonic Phase
rd
Phase B Current 93 Harmonic Phase
th
Phase B Current 94 Harmonic Phase
th
Phase B Current 95 Harmonic Phase
th
Phase B Current 96 Harmonic Phase
th
Phase B Current 97 Harmonic Phase
th
Phase B Current 98 Harmonic Phase
th
Phase B Current 99 Harmonic Phase
th
Phase B Current 100 Harmonic Phase
st
Phase B Current 101 Harmonic Phase
nd
Phase B Current 102 Harmonic Phase
rd
Phase B Current 103 Harmonic Phase
th
Phase B Current 104 Harmonic Phase
th
Phase B Current 105 Harmonic Phase
th
Phase B Current 106 Harmonic Phase
th
Phase B Current 107 Harmonic Phase
th
Phase B Current 108 Harmonic Phase
th
Phase B Current 109 Harmonic Phase
th
Phase B Current 110 Harmonic Phase
th
Phase B Current 111 Harmonic Phase
th
Phase B Current 112 Harmonic Phase
th
Phase B Current 113 Harmonic Phase
th
Phase B Current 114 Harmonic Phase
th
Phase B Current 115 Harmonic Phase
th
Phase B Current 116 Harmonic Phase
th
Phase B Current 117 Harmonic Phase
th
Phase B Current 118 Harmonic Phase
th
Phase B Current 119 Harmonic Phase
th
Phase B Current 120 Harmonic Phase
st
Phase B Current 121 Harmonic Phase
nd
Phase B Current 122 Harmonic Phase
rd
Phase B Current 123 Harmonic Phase
th
Phase B Current 124 Harmonic Phase
th
Phase B Current 125 Harmonic Phase
th
Phase B Current 126 Harmonic Phase
th
Phase B Current 127 Harmonic Phase
th
Phase C Current 0 Harmonic Phase
Phase C Current 1st Harmonic Phase
nd
Phase C Current 2 Harmonic Phase
rd
Phase C Current 3 Harmonic Phase
th
Phase C Current 4 Harmonic Phase
th
Phase C Current 5 Harmonic Phase
th
Phase C Current 6 Harmonic Phase
th
Phase C Current 7 Harmonic Phase
Phase C Current 8th Harmonic Phase
Range
Units
Type
R/W
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-33
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
0986H
0987H
0988H
0989H
098AH
098BH
098CH
098DH
098EH
098FH
0990H
0991H
0992H
0993H
0994H
0995H
0996H
0997H
0998H
0999H
099AH
099BH
099CH
099DH
099EH
099FH
09A0H
09A1H
09A2H
09A3H
09A4H
09A5H
09A6H
09A7H
09A8H
09A9H
09AAH
09ABH
09ACH
09ADH
09AEH
09AFH
09B0H
09B1H
09B2H
09B3H
09B4H
09B5H
09B6H
09B7H
09B8H
09B9H
09BAH
09BBH
09BCH
09BDH
02439
02440
02441
02442
02443
02444
02445
02446
02447
02448
02449
02450
02451
02452
02453
02454
02455
02456
02457
02458
02459
02460
02461
02462
02463
02464
02465
02466
02467
02468
02469
02470
02471
02472
02473
02474
02475
02476
02477
02478
02479
02480
02481
02482
02483
02484
02485
02486
02487
02488
02489
02490
02491
02492
02493
02494
190
190
190
190
190
190
190
191
191
191
191
191
191
191
191
191
191
191
191
191
191
191
191
192
192
192
192
192
192
192
192
192
192
192
192
192
192
192
192
192
192
192
192
192
192
192
192
192
192
192
192
192
192
192
192
193
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
0
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
th
Phase C Current 9 Harmonic Phase
th
Phase C Current 10 Harmonic Phase
th
Phase C Current 11 Harmonic Phase
th
Phase C Current 12 Harmonic Phase
th
Phase C Current 13 Harmonic Phase
th
Phase C Current 14 Harmonic Phase
th
Phase C Current 15 Harmonic Phase
th
Phase C Current 16 Harmonic Phase
th
Phase C Current 17 Harmonic Phase
th
Phase C Current 18 Harmonic Phase
th
Phase C Current 19 Harmonic Phase
th
Phase C Current 20 Harmonic Phase
st
Phase C Current 21 Harmonic Phase
nd
Phase C Current 22 Harmonic Phase
rd
Phase C Current 23 Harmonic Phase
th
Phase C Current 24 Harmonic Phase
th
Phase C Current 25 Harmonic Phase
th
Phase C Current 26 Harmonic Phase
th
Phase C Current 27 Harmonic Phase
th
Phase C Current 28 Harmonic Phase
th
Phase C Current 29 Harmonic Phase
th
Phase C Current 30 Harmonic Phase
st
Phase C Current 31 Harmonic Phase
nd
Phase C Current 32 Harmonic Phase
rd
Phase C Current 33 Harmonic Phase
th
Phase C Current 34 Harmonic Phase
th
Phase C Current 35 Harmonic Phase
th
Phase C Current 36 Harmonic Phase
th
Phase C Current 37 Harmonic Phase
th
Phase C Current 38 Harmonic Phase
th
Phase C Current 39 Harmonic Phase
th
Phase C Current 40 Harmonic Phase
st
Phase C Current 41 Harmonic Phase
nd
Phase C Current 42 Harmonic Phase
rd
Phase C Current43 Harmonic Phase
th
Phase C Current 44 Harmonic Phase
th
Phase C Current 45 Harmonic Phase
th
Phase C Current 46 Harmonic Phase
th
Phase C Current 47 Harmonic Phase
th
Phase C Current 48 Harmonic Phase
th
Phase C Current 49 Harmonic Phase
th
Phase C Current 50 Harmonic Phase
st
Phase C Current 51 Harmonic Phase
nd
Phase C Current 52 Harmonic Phase
rd
Phase C Current 53 Harmonic Phase
th
Phase C Current 54 Harmonic Phase
th
Phase C Current 55 Harmonic Phase
th
Phase C Current 56 Harmonic Phase
Phase C Current 57th Harmonic Phase
th
Phase C Current 58 Harmonic Phase
th
Phase C Current 59 Harmonic Phase
th
Phase C Current 60 Harmonic Phase
st
Phase C Current 61 Harmonic Phase
nd
Phase C Current 62 Harmonic Phase
rd
Phase C Current 63 Harmonic Phase
Phase C Current 64th Harmonic Phase
Range
Units
Type
R/W
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-34
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
09BEH
09BFH
09C0H
09C1H
09C2H
09C3H
09C4H
09C5H
09C6H
09C7H
09C8H
09C9H
09CAH
09CBH
09CCH
09CDH
09CEH
09CFH
09D0H
09D1H
09D2H
09D3H
09D4H
09D5H
09D6H
09D7H
09D8H
09D9H
09DAH
09DBH
09DCH
09DDH
09DEH
09DFH
09E0H
09E1H
09E2H
09E3H
09E4H
09E5H
09E6H
09E7H
09E8H
09E9H
09EAH
09EBH
09ECH
09EDH
09EEH
09EFH
09F0H
09F1H
09F2H
09F3H
09F4H
09F5H
02495
02496
02497
02498
02499
02500
02501
02502
02503
02504
02505
02506
02507
02508
02509
02510
02511
02512
02513
02514
02515
02516
02517
02518
02519
02520
02521
02522
02523
02524
02525
02526
02527
02528
02529
02530
02531
02532
02533
02534
02535
02536
02537
02538
02539
02540
02541
02542
02543
02544
02545
02546
02547
02548
02549
02550
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
193
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Description
th
Phase C Current 65 Harmonic Phase
th
Phase C Current 66 Harmonic Phase
th
Phase C Current 67 Harmonic Phase
th
Phase C Current 68 Harmonic Phase
th
Phase C Current 69 Harmonic Phase
th
Phase C Current 70 Harmonic Phase
st
Phase C Current 71 Harmonic Phase
nd
Phase C Current 72 Harmonic Phase
rd
Phase C Current 73 Harmonic Phase
th
Phase C Current 74 Harmonic Phase
th
Phase C Current 75 Harmonic Phase
th
Phase C Current 76 Harmonic Phase
th
Phase C Current 77 Harmonic Phase
th
Phase C Current 78 Harmonic Phase
th
Phase C Current 79 Harmonic Phase
th
Phase C Current 80 Harmonic Phase
st
Phase C Current 81 Harmonic Phase
nd
Phase C Current 82 Harmonic Phase
rd
Phase C Current 83 Harmonic Phase
th
Phase C Current 84 Harmonic Phase
th
Phase C Current 85 Harmonic Phase
th
Phase C Current 86 Harmonic Phase
th
Phase C Current 87 Harmonic Phase
th
Phase C Current 88 Harmonic Phase
th
Phase C Current 89 Harmonic Phase
th
Phase C Current 90 Harmonic Phase
st
Phase C Current 91 Harmonic Phase
nd
Phase C Current 92 Harmonic Phase
rd
Phase C Current 93 Harmonic Phase
th
Phase C Current 94 Harmonic Phase
th
Phase C Current 95 Harmonic Phase
th
Phase C Current 96 Harmonic Phase
th
Phase C Current 97 Harmonic Phase
th
Phase C Current 98 Harmonic Phase
th
Phase C Current 99 Harmonic Phase
th
Phase C Current 100 Harmonic Phase
st
Phase C Current 101 Harmonic Phase
nd
Phase C Current 102 Harmonic Phase
rd
Phase C Current 103 Harmonic Phase
th
Phase C Current 104 Harmonic Phase
th
Phase C Current 105 Harmonic Phase
th
Phase C Current 106 Harmonic Phase
th
Phase C Current 107 Harmonic Phase
th
Phase C Current 108 Harmonic Phase
th
Phase C Current 109 Harmonic Phase
th
Phase C Current 110 Harmonic Phase
th
Phase C Current 111 Harmonic Phase
th
Phase C Current 112 Harmonic Phase
th
Phase C Current 113 Harmonic Phase
th
Phase C Current 114 Harmonic Phase
th
Phase C Current 115 Harmonic Phase
th
Phase C Current 116 Harmonic Phase
th
Phase C Current 117 Harmonic Phase
th
Phase C Current 118 Harmonic Phase
th
Phase C Current 119 Harmonic Phase
th
Phase C Current 120 Harmonic Phase
Range
Units
Type
R/W
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
F9
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-35
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
09F6H
09F7H
09F8H
09F9H
09FAH
09FBH
09FCH
02551
02552
02553
02554
02555
02556
02557
193
193
193
193
193
193
193
57
58
59
60
61
62
63
30
30
30
30
30
30
30
09FDH
09FEH
09FFH
0A00H
0A01H
0A02H
0A03H
0A04H
0A05H
02558
02559
02560
02561
02562
02563
02564
02565
02566
194
195
196
197
198
199
200
201
202
0
0
0
0
0
0
0
0
0
30
30
30
30
30
30
30
30
30
0A06H-0A09H
0A0AH-0A0DH
0A0EH-0A11H
0A12H-0A15H
0A16H-0A19H
0A1AH-0A1DH
02567-02570
02571-02574
02575-02578
02579-02582
02583-02586
02587-02590
203
204
205
206
207
208
0
0
0
0
0
0
50
50
50
50
50
50
0A1EH-0A21H
0A22H
0A23H
0A24H
0A25H
0A26H
0A27H
0A28H
0A29H
0A2AH
0A2BH
02591-02594
02595
02596
02597
02598
02599
02600
02601
02602
02603
02604
209
210
210
210
211
211
211
212
212
212
213
0
0
1
2
0
1
2
0
1
2
0
50
30
30
30
30
30
30
30
30
30
30
0A2CH-0A2FH
0A30H
0A31H-0A32H
0A33H-0A34H
0A35H-0A36H
0A37H-0A38H
0A39H-0A3AH
0A32BH-0A3CH
02605-02608
02609
02610-02611
02612-02613
02614-02615
02616-02617
02618-02619
02620-02621
214
215
216
216
216
217
217
217
0
0
0
1
2
0
1
2
0A3DH-0A3EH
0A3FH-0A40H
0A41H-0A42H
0A43H-0A44H
0A45H-0A46H
02622-02623
02624-02625
02626-02627
02628-02629
02630-02631
217
217
218
218
218
0A47H-0A48H
0A49H-0A4AH
02632-02633
02634-02635
218
218
Description
Range
Units
Type
R/W
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
F9
F9
F9
F9
F9
F9
F9
R
R
R
R
R
R
R
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01
0.01
0.01
F10
F10
F10
F10
F10
F10
F67
F67
F67
R
R
R
R
R
R
R
R
R
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
F3
F3
F3
F3
F3
F3
R
R
R
R
R
R
1
1
1
1
1
1
10 msec
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
F3
F9
F9
F9
F9
F9
F9
F9
F9
F9
F13
R
R
R
R
R
R
R
R
R
R
R
1
10 msec
R
R
R
R
R
R
R
R
1
1/ 65536 VA sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 VA sec
1/ 65536 VAR sec
1/ 65536 VAR sec
F3
F14
F7
F7
F7
F7
F7
F7
9
9
9
9
9
9
+32767 W /0 W
0 W / -32768 W
+32767 VA / 0 VA
+32767 VAR / 0 VAR
0 VAR / -32768 VAR
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 VA sec
1/ 65536 VAR sec
1/ 65536 VAR sec
F7
F7
F7
F7
F7
R
R
R
R
R
9
9
9
9
9
+32767 W /0 W
0 W / -32768 W
1/ 65536 W sec
1/ 65536 W sec
F7
F7
R
R
9
9
+32767 VAR / -32768 VAR
1/ 65536 VAR sec
F7
R
9
+32767 VAR / -32768 VAR
1/ 65536 VAR sec
F7
R
9
st
50
30
30
30
30
30
30
30
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
+180 degree / -180 degree
THD/K-Factor Block
Phase A-N / Phase A-B Voltage THD
+327.67% / -327.68%
Phase B-N / Phase B-C Voltage THD
+327.67% / -327.68%
Phase C-N / Phase C-A Voltage THD
+327.67% / -327.68%
Phase A Current THD
+327.67% / -327.68%
Phase B Current THD
+327.67% / -327.68%
Phase C Current THD
+327.67% / -327.68%
Phase A Current K-Factor
327.67 / -327.68
Phase B Current K-Factor
327.67 / -327.68
Phase C Current K-Factor
327.67 / -327.68
Harmonic Time Stamp Block
Phase A-N / Phase A-B Voltage Harmonic Time Stamp
12/31/9999 23:59:59.99
Phase B-N / Phase B-C Voltage Harmonic Time Stamp
12/31/9999 23:59:59.99
Phase C-N / Phase C-A Voltage Harmonic Time Stamp
12/31/9999 23:59:59.99
Phase A Current Harmonic Time Stamp
12/31/9999 23:59:59.99
Phase B Current Harmonic Time Stamp
12/31/9999 23:59:59.99
Phase C Current Harmonic Time Stamp
12/31/9999 23:59:59.99
Phase Angle Block
Phase Angle Block Time Stamp
12/31/9999 23:59:59.99
Phase Angle Phase A-N Voltage
+180 degree / -180 degree
Phase Angle Phase B-N Voltage
+180 degree / -180 degree
Phase Angle Phase C-N Voltage
+180 degree / -180 degree
Phase Angle Phase A Current
+180 degree / -180 degree
Phase Angle Phase B Current
+180 degree / -180 degree
Phase Angle Phase C Current
+180 degree / -180 degree
Phase Angle Phase A-B Voltage
+180 degree / -180 degree
Phase Angle Phase B-C Voltage
+180 degree / -180 degree
Phase Angle Phase C-A Voltage
+180 degree / -180 degree
Voltage Phase Sequence
Block Window Average Block
Block Window Average Block Time Stamp
12/31/9999 23:59:59.99
Block Window Average Status
Block Window Average VA
+32767 VA / 0 VA
Block Window Average VAR
+32767 VAR / -32768 VAR
Block Window Average Watt
+32767 W / -32768 W
Maximum Block Window Average VA
+32767 VA / 0 VA
Maximum Block Window Average Positive VAR
+32767 VAR / 0 VAR
Maximum Block Window Average Negative VAR
0 VAR / -32768 VAR
3
4
0
1
2
30
30
30
30
30
Maximum Block Window Average Positive Watt
Maximum Block Window Average Negative Watt
Minimum Block Window Average VA
Minimum Block Window Average Positive VAR
Minimum Block Window Average Negative VAR
3
4
30
30
Minimum Block Window Average Positive Watt
Minimum Block Window Average Negative Watt
Coincident Block Window Average VAR for Maximum Positive
Watt
Coincident Block Window Average VAR for Maximum Negative
Watt
0A4BH-0A4CH
02636-02637
219
0
30
0A4DH-0A4EH
02638-02639
219
1
30
Phase C Current 121 Harmonic Phase
nd
Phase C Current 122 Harmonic Phase
rd
Phase C Current 123 Harmonic Phase
th
Phase C Current 124 Harmonic Phase
th
Phase C Current 125 Harmonic Phase
th
Phase C Current 126 Harmonic Phase
th
Phase C Current 127 Harmonic Phase
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-36
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
0A4FH-0A50H
02640-02641
219
2
30
0A51H-0A52H
0A53H-0A56H
0A57H-0A5AH
0A5BH-0A5EH
0A5FH-0A62H
0A63H-0A66H
0A67H-0A6AH
0A6BH-0A6EH
0A6FH-0A72H
0A73H-0A76H
0A77H-0A7AH
02642-02643
02644-02647
02648-02651
02652-02655
02656-02659
02660-02663
02664-02667
02668-02671
02672-02675
02676-02679
02680-02683
219
220
220
220
220
220
221
221
221
221
221
3
0
1
2
3
4
0
1
2
3
4
30
50
50
50
50
50
50
50
50
50
50
0A7BH-0A7EH
0A7FH
0A80H-0A81H
0A82H-0A83H
0A84H-0A85H
0A86H-0A87H
0A88H-0A89H
0A8AH-0A8BH
0A8CH-0A8DH
0A8EH-0A8FH
0A910H-0A91H
0A92H-0A93H
0A94H-0A95H
0A96H-0A97H
0A98H-0A99H
0A9AH-0A9BH
0A9CH-0A9DH
0A9EH-0A9FH
02684-02687
02688
02689-02690
02691-02692
02693-02694
02695-02696
02697-02698
02699-02700
02701-02702
02703-02704
02705-02706
02707-02708
02709-02710
02711-02712
02713-02714
02715-02716
02717-02718
02719-02720
222
223
224
224
224
225
225
225
226
226
226
226
226
227
227
227
227
227
0
0
0
1
2
0
1
2
0
1
2
3
4
0
1
2
3
4
50
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
0AA0H-0AA1H
02721-02722
228
0
30
0AA2H-0AA3H
02723-02724
228
1
30
0AA4H-0AA5H
02725-02726
228
2
30
0AA6H-0AA7H
0AA8H-0AABH
0AACH-0AAFH
0AB0H-0AB3H
0AB4H-0AB7H
0AB8H-0ABBH
0ABCH-0ABFH
0AC0H-0AC3H
0AC4H-0AC7H
0AC8H-0ACBH
0ACCH-0ACFH
02727-02728
02729-02732
02733-02736
02737-02740
02741-02744
02745-02748
02749-02752
02753-02756
02757-02760
02761-02764
02765-02768
228
229
229
229
229
229
230
230
230
230
230
3
0
1
2
3
4
0
1
2
3
4
30
50
50
50
50
50
50
50
50
50
50
0AD0H
0AD1H
0AD2H
0AD3H
0AD4H
0AD5H
0AD6H-0AD7H
02769
231 0-15
1
02770
231 16-31
1
02771
232 0-15
1
02772
232 16-31
1
02773
233
0-7
1
Digital Input Block
02774
234 0-7
1
02775-02776
235 0
20
Description
Range
Coincident Block Window Average VAR for Minimum Positive
Watt
+32767 VAR / -32768 VAR
Coincident Block Window Average VAR for Minimum Negative
=G1990+32767 VAR / -32768
Watt
VAR
Maximum Block Window Average VA Time Stamp
12/31/9999 23:59:59.99
Maximum Block Window Average Positive VAR Time Stamp
12/31/9999 23:59:59.99
Maximum Block Window Average Negative VAR Time Stamp
12/31/9999 23:59:59.99
Maximum Block Window Average Positive Watt Time Stamp
12/31/9999 23:59:59.99
Maximum Block Window Average Negative Watt Time Stamp
12/31/9999 23:59:59.99
Minimum Block Window Average VA Time Stamp
12/31/9999 23:59:59.99
Minimum Block Window Average Positive VAR Time Stamp
12/31/9999 23:59:59.99
Minimum Block Window Average Negative VAR Time Stamp
12/31/9999 23:59:59.99
Minimum Block Window Average Positive Watt Time Stamp
12/31/9999 23:59:59.99
Minimum Block Window Average Negative Watt Time Stamp
12/31/9999 23:59:59.99
Rolling Window Block
Rolling Window Average Block Time Stamp
12/31/9999 23:59:59.99
Rolling Window Average Status
Reserved
+32767 VA / 0 VA
Reserved
+32767 VAR / -32768 VAR
Reserved
+32767 W / -32768 W
Rolling Window Average VA
+32767 VA / 0 VA
Rolling Window Average VAR
+32767 VAR / -32768 VAR
Rolling Window Average W
+32767 W / -32768 W
Maximum Rolling Window Average VA
+32767 VA / 0 VA
Maximum Rolling Window Average Positive VAR
+32767 VAR / 0 VAR
Maximum Rolling Window Average Negative VAR
0 VAR / -32768 VAR
Maximum Rolling Window Average Positive Watt
+32767 W /0 W
Maximum Rolling Window Average Negative Watt
0 W / -32768 W
Minimum Rolling Window Average VA
+32767 VA / 0 VA
Minimum Rolling Window Average Positive VAR
+32767 VAR / 0 VAR
Minimum Rolling Window Average Negative VAR
0 VAR / -32768 VAR
Minimum Rolling Window Average Positive Watt
+32767 W /0 W
Minimum Rolling Window Average Negative Watt
0 W / -32768 W
Coincident Rolling Window Average VAR for Maximum Positive
Watt
+32767 VAR / -32768 VAR
Coincident Rolling Window Average VAR for Maximum Negative
Watt
+32767 VAR / -32768 VAR
Coincident Rolling Window Average VAR for Minimum Positive
Watt
+32767 VAR / -32768 VAR
Coincident Rolling Window Average VAR for Minimum Negative
Watt
+32767 VAR / -32768 VAR
Maximum Rolling Window Average VA Time Stamp
12/31/9999 23:59:59.99
Maximum Rolling Window Average Positive VAR Time Stamp
12/31/9999 23:59:59.99
Maximum Rolling Window Average Negative VAR Time Stamp
12/31/9999 23:59:59.99
Maximum Rolling Window Average Positive Watt Time Stamp
12/31/9999 23:59:59.99
Maximum Rolling Window Average Negative Watt Time Stamp
12/31/9999 23:59:59.99
Minimum Rolling Window Average VA Time Stamp
12/31/9999 23:59:59.99
Minimum Rolling Window Average Positive VAR Time Stamp
12/31/9999 23:59:59.99
Minimum Rolling Window Average Negative VAR Time Stamp
12/31/9999 23:59:59.99
Minimum Rolling Window Average Positive Watt Time Stamp
12/31/9999 23:59:59.99
Minimum Rolling Window Average Negative Watt Time Stamp
12/31/9999 23:59:59.99
Limit Block
Limit States, Value 1 Comparisons, 1-16
Limit States, Value 1 Comparisons, 17-32
Limit States, Value 2 Comparisons, 1-16
Limit States, Value 2 Comparisons, 17-32
Low Speed (Internal) Inputs
Digital Input States, Module 1
Digital Input Accumulation 1, Module 1
4,294,967,295 / 0
Units
Type
R/W
Notes
1/ 65536 VAR sec
F7
R
9
1/ 65536 VAR sec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
F7
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
R
R
R
R
R
R
R
R
R
R
R
9
1
1
1
1
1
1
1
1
1
1
10 msec
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
1
1/ 65536 VA sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 VA sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 VA sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 VA sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 W sec
F3
F14
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
1/ 65536 VAR sec
F7
R
9
1/ 65536 VAR sec
F7
R
9
1/ 65536 VAR sec
F7
R
9
1/ 65536 VAR sec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
F7
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
R
R
R
R
R
R
R
R
R
R
R
9
1
1
1
1
1
1
1
1
1
1
F15
F15
F15
F15
F16
R
R
R
R
R
F17
F18
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-37
2: Modbus Map - Holding Registers
Addr. (hex)
0AD8H-0AD9H
0ADBH-0ADCH
0ADDH-0ADEH
0ADEH-0ADFH
0AE0H-0AE1H
0AE2H-0AE3H
0AE4H-0AE5H
0AE6H
0AE7H-0AE8H
0AE9H-0AEAH
0AEBH-0AECH
0AEDH-0AEEH
0AEFH-0AF0H
0AF1H-0AF2H
0AF3H-0AF4H
0AF5H-0AF6H
0AF7H
0AF8H-0AF9H
0AFAH-0AFBH
0AFCH-0AFDH
0AFEH-0AFFH
0B00H-0B01H
0B02H-0B03H
0B04H-0B05H
0B06H-0B07H
0B08H
0B09H-0B0AH
0B0BH-0B0CH
0B0DH-0B0EH
0B0FH-0B10H
0B11H-0B12H
0B13H-0B14H
0B15H-0B16H
0B17H-0B18H
0B43H-0BFFH
0C00H-0C01H
0C02H-0C03H
0C04H-0C05H
0C06H-0C07H
0C08H-0C09H
0C0AH-0C0BH
0C0CH-0C0DH
0C0EH-0C0FH
0C10H-0C11H
0C12H-0C13H
0C14H-0C15H
0C16H-0C17H
0C18h-0C19H
0C1AH
0C1BH
0C1CH
0C1DH
0C1EH-0C1FH
0C20H-0C21H
0C22H-0C23H
0C24H-0C25H
0C26H
0C27H
0C28H
Address(4X)
02777-02778
02779-02780
02781-02782
02783-02784
02785-02786
02787-02788
02789-02790
02791
02792-02793
02794-02795
02796-02797
02798-02799
02800-02801
02802-02803
02804-02805
02806-02807
02808
02809-02810
02811-02812
02813-02814
02815-02816
02817-02818
02819-02820
02821-02822
02823-02824
02825
02826-02827
02828-02829
02830-02831
02832-02833
02834-02835
02836-02837
02838-02839
02840-02841
02884-03072
03073-03074
03075-03076
03077-03078
03079-03080
03081-03082
03083-03084
03085-03086
03087-03088
03089-03090
03091-03092
03093-03094
03095-03096
03097-03098
03099
03100
03101
03102
03103-03104
03105-03106
03107-03108
03109-03110
03111
03112
03113
Line
235
235
235
235
235
235
235
236
237
237
237
237
237
237
237
237
238
239
239
239
239
239
239
239
239
240
241
241
241
241
241
241
241
241
Pt
1
2
3
4
5
6
7
0-7
0
1
2
3
4
5
6
7
0-7
0
1
2
3
4
5
6
7
0-7
0
1
2
3
4
5
6
7
DNP
Obj
20
20
20
20
20
20
20
1
20
20
20
20
20
20
20
20
1
20
20
20
20
20
20
20
20
1
20
20
20
20
20
20
20
20
Description
Digital Input Accumulation 2, Module 1
Digital Input Accumulation 3, Module 1
Digital Input Accumulation 4, Module 1
Digital Input Accumulation 5, Module 1
Digital Input Accumulation 6, Module 1
Digital Input Accumulation 7, Module 1
Digital Input Accumulation 8, Module 1
Digital Input States, Module 2
Digital Input Accumulation 1, Module 2
Digital Input Accumulation 2, Module 2
Digital Input Accumulation 3, Module 2
Digital Input Accumulation 4, Module 2
Digital Input Accumulation 5, Module 2
Digital Input Accumulation 6, Module 2
Digital Input Accumulation 7, Module 2
Digital Input Accumulation 8, Module 2
Digital Input States, Module 3
Digital Input Accumulation 1, Module 3
Digital Input Accumulation 2, Module 3
Digital Input Accumulation 3, Module 3
Digital Input Accumulation 4, Module 3
Digital Input Accumulation 5, Module 3
Digital Input Accumulation 6, Module 3
Digital Input Accumulation 7, Module 3
Digital Input Accumulation 8, Module 3
Digital Input States, Module 4
Digital Input Accumulation 1, Module 4
Digital Input Accumulation 2, Module 4
Digital Input Accumulation 3, Module 4
Digital Input Accumulation 4, Module 4
Digital Input Accumulation 5, Module 4
Digital Input Accumulation 6, Module 4
Digital Input Accumulation 7, Module 4
Digital Input Accumulation 8, Module 4
reserved
One cycle Phase A VA
One cycle Phase B VA
One cycle Phase C VA
One cycle Three Phase VA
One cycle Phase A VAR
One cycle Phase B VAR
One cycle Phase C VAR
One cycle Three Phase VAR
One cycle Phase A Watts
One cycled Phase B Watts
One cycle Phase C Watts
One cycle Three Phase Watts
One cycle Frequency
One cycle Phase A Power Factor
One cycle Phase B Power Factor
One cycle Phase C Power Factor
One cycle Three Phase Power Factor
One cycle Phase A Fundamental VAR
One cycle Phase B Fundamental VAR
One cycle Phase C Fundamental VAR
One cycle Three Phase Fundamental VAR
One cycle Phase A Fundamental Power Factor
One cycle Phase B Fundamental Power Factor
One cycle Phase C Fundamental Power Factor
Range
Units
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VAR / -32768 VAR
+32767 VAR / -32768 VAR
+32767 VAR / -32768 VAR
+32767 VAR / -32768 VAR
+32767 W / -32768 W
+32767 W / -32768 W
+32767 W / -32768 W
+32767 W / -32768 W
+32767 Hz / 0 Hz
3.999 / 0.000
3.999 / 0.000
3.999 / 0.000
3.999 / 0.000
+32767 VAR / -32768 VAR
+32767 VAR / -32768 VAR
+32767 VAR / -32768 VAR
+32767 VAR / -32768 VAR
3.999 / 0.000
3.999 / 0.000
3.999 / 0.000
1/ 65536 VA sec
1/ 65536 VA sec
1/ 65536 VA sec
1/ 65536 VA sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 Hz
0.001 PF
0.001 PF
0.001 PF
0.001 PF
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 VAR sec
0.001 PF
0.001 PF
0.001 PF
Type
R/W
F18
F18
F18
F18
F18
F18
F18
F17
F18
F18
F18
F18
F18
F18
F18
F18
F17
F18
F18
F18
F18
F18
F18
F18
F18
F17
F18
F18
F18
F18
F18
F18
F18
F18
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F8
F8
F8
F8
F7
F7
F7
F7
F8
F8
F8
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-38
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
Description
0C29H
03114
One cycle Three Phase Fundamental Power Factor
0C2AH-166FH
03115-05744
reserved
Range
3.999 / 0.000
Reserved Block
Units
Type
0.001 PF
F8
R/W
Notes
R
R
1670H-1673H
05745-05748
399
0
50
Internal Input Pulse Accumulation Block
Internal Input Pulse Accumulation Block Time Stamp
12/31/9999 23:59:59.99
10 msec
F3
R
1674H-1677H
05749-05752
400
0
20
Pulse Accumulation Internal Input 1
1 Unit
F62
R
+/- 9,223,372,036,854,776,808
1678H-167BH
05753-05756
400
1
20
Pulse Accumulation Internal Input 2
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
167CH-167FH
05757-05760
400
2
20
Pulse Accumulation Internal Input 3
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
1680H-1683H
05761-05764
400
3
20
Pulse Accumulation Internal Input 4
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
1684H-1687H
05765-05768
400
4
20
Pulse Accumulation Internal Input 5
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
1688H-168BH
05769-05772
400
5
20
Pulse Accumulation Internal Input 6
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
168CH-168FH
05773-05776
400
6
20
Pulse Accumulation Internal Input 7
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
1690H-1693H
05777-05780
400
7
20
Pulse Accumulation Internal Input 8
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
R
1694H-1697H
05781-05784
401
0
20
Pulse Accumulation Aggregation 1
+/- 9,223,372,036,854,776,808
1 Unit
F62
1698H-169BH
05785-05788
401
1
20
Pulse Accumulation Aggregation 2
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
169CH-169FH
05789-05792
401
2
20
Pulse Accumulation Aggregation 3
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
16A0H-16A3H
05793-05796
401
3
20
Pulse Accumulation Aggregation 4
1 Unit
F62
R
16A4H-16A7H
05797-05800
402
0
50
16A8H
05801
403
0
30
+/- 9,223,372,036,854,776,808
Pulse Accumulation Block Window Average / Maximum Block
Pulse Accumulation Block Window Average / Maximum Block
Time Stamp
12/31/9999 23:59:59.99
Pulse Accumulation Block Window Average / Maximum Block
Status
16A9H-16ACH
05802-05805
404
0
20
Block Window Average Internal Input 1
+/- 9,223,372,036,854,776,808
16ADH-16B0H
05806-05809
404
1
20
Block Window Average Internal Input 2
+/- 9,223,372,036,854,776,808
16B1H-16B4H
16B5H-16B8H
05810-05813
05814-05817
404
404
2
3
20
20
Block Window Average Internal Input 3
Block Window Average Internal Input 4
+/- 9,223,372,036,854,776,808
+/- 9,223,372,036,854,776,808
10 msec
F3
R
F14
R
1 Unit
F62
R
1 Unit
F62
R
1 Unit
1 Unit
F62
F62
R
R
16B9H-16BCH
05818-05821
404
4
20
Block Window Average Internal Input 5
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
16BDH-16C0H
16C1H-16C4H
05822-05825
05826-05829
404
404
5
6
20
20
Block Window Average Internal Input 6
Block Window Average Internal Input 7
+/- 9,223,372,036,854,776,808
+/- 9,223,372,036,854,776,808
1 Unit
1 Unit
F62
F62
R
R
16C5H-16C8H
05830-05833
404
7
20
Block Window Average Internal Input 8
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
16C9H-16CCH
05834-05837
405
0
20
Block Window Average Aggregation 1
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
16CDH-16D0H
05838-05841
405
1
20
Block Window Average Aggregation 2
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
16D1H-16D4H
05842-05845
405
2
20
Block Window Average Aggregation 3
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
16D5H-16D8H
05846-05849
405
3
20
Block Window Average Aggregation 4
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
16D9H-16DCH
16DDH-16E0H
05850-05853
05854-05857
406
406
0
1
20
20
Maximum Block Window Average Internal Input 1
Maximum Block Window Average Internal Input 2
+/- 9,223,372,036,854,776,808
+/- 9,223,372,036,854,776,808
1 Unit
1 Unit
F62
F62
R
R
16E1H-16E4H
16E5H-16E8H
05858-05861
05862-05865
406
406
2
3
20
20
Maximum Block Window Average Internal Input 3
Maximum Block Window Average Internal Input 4
+/- 9,223,372,036,854,776,808
+/- 9,223,372,036,854,776,808
1 Unit
1 Unit
F62
F62
R
R
1
1
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-39
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
Description
Range
Units
Type
R/W
16E9H-16ECH
05866-05869
406
4
20
Maximum Block Window Average Internal Input 5
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
16EDH-16F0H
05870-05873
406
5
20
Maximum Block Window Average Internal Input 6
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
16F1H-16F4H
05874-05877
406
6
20
Maximum Block Window Average Internal Input 7
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
16F5H-16F8H
05878-05881
406
7
20
Maximum Block Window Average Internal Input 8
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
16F9H-16FCH
05882-05885
407
0
20
Maximum Block Window Average Aggregation 1
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
16FDH-1700H
05886-05889
407
1
20
Maximum Block Window Average Aggregation 2
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
1701H-1704H
05890-05893
407
2
20
Maximum Block Window Average Aggregation 3
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
1705H-1708H
1709H-170CH
170DH-1710H
1711H-1714H
1715H-1718H
1719H-171CH
171DH-1720H
1721H-1724H
1725H-1728H
1729H-172CH
172DH-1730H
1731H-1734H
1735H-1738H
05894-05897
05898-05901
05902-05905
05906-05909
05910-05913
05914-05917
05918-05921
05922-05925
05926-05929
05930-05933
05934-05937
05938-05941
05942-05945
407
408
408
408
408
408
408
408
408
409
409
409
409
3
0
1
2
3
4
5
6
7
0
1
2
3
20
50
50
50
50
50
50
50
50
50
50
50
50
1 Unit
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
F62
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
R
R
R
R
R
R
R
R
R
R
R
R
R
1739H
05946
410
0
30
0.1 degree C
F33
173AH
173BH
173CH
173DH
173EH
173FH
1740H
1741H
1742H
1743H
1744H
1745H
1746H
1747H
1748H
1749H
174AH
174BH
174CH
174DH
174EH
174FH
1750H
1751H
1752H
1753H
1754H
1755H
1756H
1757H
05947
05948
05949
05950
05951
05952
05953
05954
05955
05956
05957
05958
05959
05960
05961
05962
05963
05964
05965
05966
05967
05968
05969
05970
05971
05972
05973
05974
05975
05976
411
411
411
411
411
411
411
411
412
412
412
412
412
412
412
412
413
413
413
413
413
413
413
413
414
414
414
414
414
414
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
0
1
2
3
4
5
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
Maximum Block Window Average Aggregation 4
+/- 9,223,372,036,854,776,808
Maximum Block Window Average Internal Input 1 Time Stamp
12/31/9999 23:59:59.99
Maximum Block Window Average Internal Input 2 Time Stamp
12/31/9999 23:59:59.99
Maximum Block Window Average Internal Input 3 Time Stamp
12/31/9999 23:59:59.99
Maximum Block Window Average Internal Input 4 Time Stamp
12/31/9999 23:59:59.99
Maximum Block Window Average Internal Input 5 Time Stamp
12/31/9999 23:59:59.99
Maximum Block Window Average Internal Input 6 Time Stamp
12/31/9999 23:59:59.99
Maximum Block Window Average Internal Input 7 Time Stamp
12/31/9999 23:59:59.99
Maximum Block Window Average Internal Input 8 Time Stamp
12/31/9999 23:59:59.99
Maximum Block Window Average Aggregation 1 Time Stamp
12/31/9999 23:59:59.99
Maximum Block Window Average Aggregation 2 Time Stamp
12/31/9999 23:59:59.99
Maximum Block Window Average Aggregation 3 Time Stamp
12/31/9999 23:59:59.99
Maximum Block Window Average Aggregation 4 Time Stamp
12/31/9999 23:59:59.99
Temperature
Nexus Internal Temperature
+3276.7 C / -3276.8 C
Analog Input Block
Analog Input 1, Module 1
+327.67% / -327.68%
Analog Input 2, Module 1
+327.67% / -327.68%
Analog Input 3, Module 1
+327.67% / -327.68%
Analog Input 4, Module 1
+327.67% / -327.68%
Analog Input 5, Module 1
+327.67% / -327.68%
Analog Input 6, Module 1
+327.67% / -327.68%
Analog Input 7, Module 1
+327.67% / -327.68%
Analog Input 8, Module 1
+327.67% / -327.68%
Analog Input 1, Module 2
+327.67% / -327.68%
Analog Input 2, Module 2
+327.67% / -327.68%
Analog Input 3, Module 2
+327.67% / -327.68%
Analog Input 4, Module 2
+327.67% / -327.68%
Analog Input 5, Module 2
+327.67% / -327.68%
Analog Input 6, Module 2
+327.67% / -327.68%
Analog Input 7, Module 2
+327.67% / -327.68%
Analog Input 8, Module 2
+327.67% / -327.68%
Analog Input 1, Module 3
+327.67% / -327.68%
Analog Input 2, Module 3
+327.67% / -327.68%
Analog Input 3, Module 3
+327.67% / -327.68%
Analog Input 4, Module 3
+327.67% / -327.68%
Analog Input 5, Module 3
+327.67% / -327.68%
Analog Input 6, Module 3
+327.67% / -327.68%
Analog Input 7, Module 3
+327.67% / -327.68%
Analog Input 8, Module 3
+327.67% / -327.68%
Analog Input 1, Module 4
+327.67% / -327.68%
Analog Input 2, Module 4
+327.67% / -327.68%
Analog Input 3, Module 4
+327.67% / -327.68%
Analog Input 4, Module 4
+327.67% / -327.68%
Analog Input 5, Module 4
+327.67% / -327.68%
Analog Input 6, Module 4
+327.67% / -327.68%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
Notes
1
1
1
1
1
1
1
1
1
1
1
1
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-40
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
1758H
1759H
05977
05978
414
414
6
7
30
30
Analog Input 7, Module 4
Analog Input 8, Module 4
175AH
175BH
05979
05980
415
415
0-15
16-31
1
1
Limit States, Combinations, 1-16
Limit States, Combinations, 17-32
Description
175CH-175FH
1760H
1761H
1762H
1763H
1764H
1765H
1766H
1767H
1768H
1769H
176AH
05981-05984
05985
05986
05987
05988
05989
05990
05991
05992
05993
05994
05995
416
417
418
419
420
421
422
423
424
425
426
427
0
0-15
0-15
0-15
0-15
0-15
0-15
0-15
0-15
0-15
0-15
0-15
50
1
1
1
1
1
1
1
1
1
1
1
Relay Logic Block Time Stamp
Relay Logic States, Input 1, Relays 1-16
Relay Logic States, Input 2, Relays 1-16
Relay Logic States, Input 3, Relays 1-16
Relay Logic States, Input 4, Relays 1-16
Relay Logic States, Input 5, Relays 1-16
Relay Logic States, Input 6, Relays 1-16
Relay Logic States, Input 7, Relays 1-16
Relay Logic States, Input 8, Relays 1-16
Relay Logic States, Gate A, Relays 1-16
Relay Logic States, Gate B, Relays 1-16
Relay Logic States, Gate C, Relays 1-16
176BH
176CH
176DH
176EH
176FH
1770H
1771H
1772H
1773H
1774H
1775H
1776H
1777H
1778H
1779H
177AH
177BH
177CH
177DH
05996
05997
05998
05999
06000
06001
06002
06003
06004
06005
06006
06007
06008
06009
06010
06011
06012
06013
06014
428
429
430
431
432
432
432
432
432
432
432
432
433
434
435
436
437
438
439
0-15
0-15
0-15
0-15
0-1
2-3
4-5
6-7
8-9
10-11
12-13
14-15
0-15
0-15
0-15
0-15
0-15
0-15
0-15
1
1
1
1
30
30
30
30
30
30
30
30
1
1
1
10
1
1
1
Relay Logic States, Gate D, Relays 1-16
Relay Logic States, Gate E, Relays 1-16
Relay Logic States, Gate F, Relays 1-16
Relay Logic States, Gate G, Relays 1-16
Delay Timer, Relay 1 / Relay 2
Delay Timer, Relay 3 / Relay 4
Delay Timer, Relay 5 / Relay 6
Delay Timer, Relay 7 / Relay 8
Delay Timer, Relay 9 / Relay 10
Delay Timer, Relay 11 / Relay 12
Delay Timer, Relay 13 / Relay 14
Delay Timer, Relay 15 / Relay 16
Desired Relay States, Relays 1-16
Relays Pending Updates, Relays 1-16
Shadowed Relay States, Relays 1-16
Confirmed Polled Relay States, Relays 1-16
Valid Flags for Confirmed Relay States, Relays 1-16
Locked Relays, Relays 1-16
Locked Relay States, Relays 1-16
177EH-1781H
1782H-1785H
1786H-1789H
178AH-178DH
178EH-1791H
1792H-1795H
06015-06018
06019-06022
06023-06026
06027-06030
06031-06034
06035-06038
440
440
440
440
440
440
0
1
2
3
4
5
50
50
50
50
50
50
Reset Time Block Time Stamp
Reset Maximum Time Stamp
Reset Minimum Time Stamp
Reset Energy Time Stamp
Reserved
Reset Pulse Accumulations/Aggregations Time Stamps
Range
Units
Type
R/W
+327.67% / -327.68%
+327.67% / -327.68%
Limit Combination Block
0.01%
0.01%
F10
F10
R
R
F34
F34
R
R
F3
F34
F34
F34
F34
F34
F34
F34
F34
F34
F34
F34
R
R
R
R
R
R
R
R
R
R
R
R
F34
F34
F34
F34
F35
F35
F35
F35
F35
F35
F35
F35
F36
F37
F38
F39
F40
F41
F42
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
F3
F3
F3
F3
F3
F3
R
R
R
R
R
R
Relay Logic Block
12/31/9999 23:59:59.99
Reset Time Block
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
Miscellaneous Flags
10 msec
10 msec
10 msec
10 msec
10 msec
10 msec
Notes
1
1
1
1
1
1
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-41
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
Description
Range
Units
Current Time Stamp Status:
MSB first, Bit[15-12] = Current Weekday, 0=Sunday,
6= Saturday
Bit[11]
= Not defined
Bit[10]
= Debugging 1 = Line Synch
Frequency Valid)
Bit[09]
= IRIG-B Year Valid
Bit[08]
= Debugging, 1= IRIG-B Time
Continue Forwarding)
Bit[07]
= Active IRIG-B
Bit[06]
= Active DST
Bit[05]
= Active Line Synch
Bit[04]
= Active Cold Load
Bit[03]
= DST Spring Date, it means current
date/time is before DST period
starting moment of current calender year
Bit[02] = DST Fall Date, it means current date/time
is after DST period ending moment of
current calender year
Bit[01] = Active SNTP
Bit[00] = 1 = Battery low flag)
R/W
Notes
F51
1796H
06039
441
0-15
1
1797H-179AH
179BH-179EH
179FH-17A2H
17A3H
17A4H-17A7H
06040-06043
06044-06047
06048-06051
06052
06053-06056
442
443
443
444
0
0
1
0
50
50
50
30
Test Mode Block Time Stamp
Test Mode Start Time
Test Mode Current Test Start Time
Test Mode Block Average Status / Rolling Average Status
Reserved
17A8H-17AFH
06057-06060
446
0
20
Test Mode Total VAh (Q1234)
17B0H-17B7H
06061-06064
446
1
20
Test Mode Received VARh (Q34)
17B8H-17BFH
06065-06068
446
2
20
Test Mode Delivered VARh (Q12)
99999999999999.9999999/99999999999999.9999999 VAh 1/ 4294967296 Wh sec
99999999999999.9999999/99999999999999.9999999
VARh
1/ 4294967296 Wh sec
99999999999999.9999999/99999999999999.9999999
VARh
1/ 4294967296 Wh sec
17C0H-17C7H
06069-06072
446
3
20
Test Mode Received Wh (Q14)
99999999999999.9999999/99999999999999.9999999 Wh
17C8H-17CFH
06073-06076
446
4
20
17D0H-17D3H
17D4H-17D5H
17D6H-17D7H
17D8H-17D9H
17DAH-17DBH
17DCH-17DDH
06097-06100
06101-06102
06103-06104
06105-06106
06107-06108
06109-06110
447
448
448
448
448
448
0
0
1
2
3
4
20
20
20
20
20
17DEH
06111
449
0-3
1
Test Mode
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
99999999999999.9999999/99999999999999.9999999 Wh
KYZ Output Accumulation Block
KYZ Output Accumulation Block Time Stamp
12/31/9999 23:59:59.99
KYZ Output Accumulation #1, Test Pulse 1 LED
4,294,967,295 / 0
KYZ Output Accumulation #2, Test Pulse 2 LED
4,294,967,295 / 0
KYZ Output Accumulation #3, Pulse Output 1 LED / Relay 1
4,294,967,295 / 0
KYZ Output Accumulation #4, Pulse Output 2 LED / Relay 2
4,294,967,295 / 0
Reserved
4,294,967,295 / 0
Input Option Board Data Statusr Block
MSB first, Bit[15] = 1st DIO module status valid
Bit[14] = 2nd DIO module status valid
Bit[13] = 3rd DIO module status valid
Bit[12] = 4th DIO module status valid
Test Mode Delivered Wh (Q23)
Type
10 msec
10 msec
10 msec
F3
F3
F3
F14
F117
R
F117
R
F117
R
1/ 4294967296 Wh sec
F117
R
1/ 4294967296 Wh sec
F117
R
F3
F18
F18
F18
F18
F18
R
R
R
R
R
F44
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-42
2: Modbus Map - Holding Registers
Addr. (hex)
17DFH
Address(4X)
06112
Line
Pt
DNP
Obj
450
0-15
1
450
16-31
1
Description
Range
Units
MSB first, Bit[15] = 1st AIN module AI chn 01 valid
Bit[14] = 1st AIN module AI chn 02 valid
Bit[13] = 1st AIN module AI chn 03 valid
Bit[12] = 1st AIN module AI chn 04 valid
Bit[11] = 1st AIN module AI chn 05 valid
Bit[10] = 1st AIN module AI chn 06 valid
Bit[09] = 1st AIN module AI chn 07 valid
Bit[08] = 1st AIN module AI chn 08 valid
Bit[07] = 2nd AIN module AI chn 09 valid
Bit[06] = 2nd AIN module AI chn 10 valid
Bit[05] = 2nd AIN module AI chn 11 valid
Bit[04] = 2nd AIN module AI chn 12 valid
Bit[03] = 2nd AIN module AI chn 13 valid
Bit[02] = 2nd AIN module AI chn 14 valid
Bit[01] = 2nd AIN module AI chn 15 valid
Bit[00] = 2nd AIN module AI chn 16 valid
MSB first, Bit[15] = 3rd AIN module AI chn 01 valid
Bit[14] = 3rd AIN module AI chn 02 valid
Bit[13] = 3rd AIN module AI chn 03 valid
Bit[12] = 3rd AIN module AI chn 04 valid
Bit[11] = 3rd AIN module AI chn 05 valid
Bit[10] = 3rd AIN module AI chn 06 valid
Bit[09] = 3rd AIN module AI chn 07 valid
Bit[08] = 3rd AIN module AI chn 08 valid
Bit[07] = 4th AIN module AI chn 09 valid
Bit[06] = 4th AIN module AI chn 10 valid
Bit[05] = 4th AIN module AI chn 11 valid
Bit[04] = 4th AIN module AI chn 12 valid
Bit[03] = 4th AIN module AI chn 13 valid
Bit[02] = 4th AIN module AI chn 14 valid
Bit[01] = 4th AIN module AI chn 15 valid
Bit[00] = 4th AIN module AI chn 16 valid
17E0H
06113
17E1H-17E4H
17EDH
06114-06117
06126
451
453
0
0
50
30
17EEH-17F1H
17F2H-17F3H
17F4H-17F5H
17F6H-17F7H
06127-06130
06131-06132
06133-06134
06135-06136
454
455
455
455
0
0
1
2
50
30
30
30
Flicker Status Block
Flicker Status Block Time Stamp
12/31/9999 23:59:59.99
Flicker Status: value = 0000 means not available or stopped
Instantaneous Flicker Block
Instantaneous Flicker Block Time
12/31/9999 23:59:59.99
+32767 / 0
Instantaneous Flicker VAN
+32767 / 0
Instantaneous Flicker VBN
+32767 / 0
Instantaneous Flicker VCN
17F8H-17FBH
06137-06140
456
0
50
Short Term Flicker Block Time
12/31/9999 23:59:59.99
17FCH-17FDH
17FEH-17FFH
1800H-1801H
1802H-1803H
1804H-1805H
1806H-1807H
1808H-1809H
180AH-180BH
180CH-180DH
06141-06142
06143-06144
06145-06146
06147-06148
06149-06150
06151-06152
06153-06154
06155-06156
06157-06158
457
457
457
458
458
458
459
459
459
0
1
2
0
1
2
0
1
2
30
30
30
30
30
30
30
30
30
+32767 / 0
+32767 / 0
+32767 / 0
+32767 / 0
+32767 / 0
+32767 / 0
+32767 / 0
+32767 / 0
+32767 / 0
180EH-1811H
1812H-1815H
1816H-1819H
181AH-181DH
181EH-1821H
1822H-1825H
06159-06162
06163-06166
06167-06170
06171-06174
06175-06178
06179-06182
460
461
461
461
462
462
0
0
1
2
0
1
50
50
50
50
50
50
Short Term Flicker VAN
Short Term Flicker VBN
Short Term Flicker VCN
Maximum Short Term Flicker VAN
Maximum Short Term Flicker VBN
Maximum Short Term Flicker VCN
Minimum Short Term Flicker VAN
Minimum Short Term Flicker VBN
Minimum Short Term Flicker VCN
Short Term Flicker Interval End Time Stamp
Maximum Short Term Flicker VAN Time Stamp
Maximum Short Term Flicker VBN Time Stamp
Maximum Short Term Flicker VCN Time Stamp
Minimum Short Term Flicker VAN Time Stamp
Minimum Short Term Flicker VBN Time Stamp
Type
R/W
F45
R
F45
R
Notes
F3
R
1/ 65536
1/ 65536
1/ 65536
F3
F7
F7
F7
R
R
R
Short Term Flicker Block
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
F3
1/ 65536
1/ 65536
1/ 65536
1/ 65536
1/ 65536
1/ 65536
1/ 65536
1/ 65536
1/ 65536
F7
F7
F7
F7
F7
F7
F7
F7
F7
R
R
R
R
R
R
R
R
R
F3
F3
F3
F3
F3
F3
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-43
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
1826H-1829H
06183-06186
462
2
50
Description
Range
Units
12/31/9999 23:59:59.99
Minimum Short Term Flicker VCN Time Stamp
Type
R/W
F3
182AH-182DH
182EH-182FH
1830H-1831H
1832H-1833H
1834H-1835H
1836H-1837H
1838H-1839H
183AH-183BH
06187-06190
06191-06192
06193-06194
06195-06196
06197-06198
06199-06200
06201-06202
06203-06204
463
464
464
464
465
465
465
466
0
0
1
2
0
1
2
0
50
30
30
30
30
30
30
30
Long Term Flicker Block Time
Long Term Flicker VAN
Long Term Flicker VBN
Long Term Flicker VCN
Maximum Long Term Flicker VAN
Maximum Long Term Flicker VBN
Maximum Long Term Flicker VCN
Minimum Long Term Flicker VAN
Long Term Flicker Block
12/31/9999 23:59:59.99
+32767 / 0
+32767 / 0
+32767 / 0
+32767 / 0
+32767 / 0
+32767 / 0
+32767 / 0
183CH-183DH
06205-06206
466
1
30
Minimum Long Term Flicker VBN
+32767 / 0
1/ 65536
F7
R
183EH-183FH
06207-06208
466
2
30
Minimum Long Term Flicker VCN
+32767 / 0
1/ 65536
F7
R
1840H-1843H
1844H-1847H
06209-06212
06213-06216
467
468
0
0
50
50
Long Term Flicker Interval End Time Stamp
Maximum Long Term Flicker VAN Time Stamp
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
F3
F3
1848H-184BH
184CH-184FH
1850H-1853H
1854H-1857H
1858H-185BH
06217-06220
06221-06224
06225-06228
06229-06232
06233-06236
468
468
469
469
469
1
2
0
1
2
50
50
50
50
50
Maximum Long Term Flicker VBN Time Stamp
Maximum Long Term Flicker VCN Time Stamp
Minimum Long Term Flicker VAN Time Stamp
Minimum Long Term Flicker VBN Time Stamp
Minimum Long Term Flicker VCN Time Stamp
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
F3
F3
F3
F3
F3
185CH-185FH
1890H-18ABH
06237-06240
06289-06316
470
0
50
Additional Energy Block Time
Reserved
Additional Energy Block
12/31/9999 23:59:59.99
F3
18ACH-18AFH
06317-06320
475
0
20
Quadrant 1 Watthour, Secondary
18B0H-18B3H
06321-06324
475
1
20
Quadrant 4 Watthour, Secondary
18B4H-18B7H
06325-06328
475
2
20
Quadrant 2 Watthour, Secondary
18B8H-18BBH
06329-06332
475
3
20
Quadrant 3 Watthour, Secondary
18BCH-18BFH
06333-06336
476
0
20
Quadrant 1 VAhour, Secondary
18C0H-18C3H
06337-06340
476
1
20
Quadrant 1 VARhour, Secondary
18C4H-18C7H
06341-06344
476
2
20
Quadrant 4 VAhour, Secondary
18C8H-18CBH
06345-06348
476
3
20
Quadrant 4 VARhour, Secondary
18CCH-18CFH
06349-06352
476
4
20
Quadrant 2 VAhour, Secondary
18D0H-18D3H
06353-06356
476
5
20
Quadrant 2 VARhour, Secondary
Notes
1/ 65536
1/ 65536
1/ 65536
1/ 65536
1/ 65536
1/ 65536
1/ 65536
F3
F7
F7
F7
F7
F7
F7
F7
R
R
R
R
R
R
R
R
+9,999,999,999,999,999 WH / 0
WH
+9,999,999,999,999,999 WH / 0
WH
+9,999,999,999,999,999 WH / 0
WH
+9,999,999,999,999,999 WH / 0
WH
+9,999,999,999,999,999 VAh /
0 VAh
+9,999,999,999,999,999 VARh
/ 0 VARh
+9,999,999,999,999,999 VAh /
0 VAh
+9,999,999,999,999,999 VARh
/ 0 VARh
+9,999,999,999,999,999 VAh /
0 VAh
+9,999,999,999,999,999 VARh
/ 0 VARh
+9,999,999,999,999,999 VAh /
0 VAh
+9,999,999,999,999,999 VARh
/ 0 VARh
1 WH
F12
R
1 WH
F12
R
1 WH
F12
R
1 WH
F12
R
1 VAH
F12
R
1 VARH
F12
R
1 VAH
F12
R
1 VARH
F12
R
1 VAH
F12
R
1 VARH
F12
R
1 VAH
F12
R
1 VARH
F12
R
R
R
R
R
R
R
R
R
R
R
18D4H-18D7H
06357-06360
476
6
20
Quadrant 3 VAhour, Secondary
18D8H-18DBH
06361-06364
476
7
20
Quadrant 3 VARhour, Secondary
18DCH-18F7H
06365-06392
18F8H-18FBH
18FCH
18FDH
18FEH
18FFH
1900H
06393-06396
06397
06398
06399
06400
06401
479
480
480
480
480
480
0
0
1
2
3
4
50
30
30
30
30
30
Energy and Pulses in the Interval
Energy and Pulses in the Interval Block Time Stamp
12/31/9999 23:59:59.99
Total VAhour (Quadrants 1+2+3+4) in the Interval, Secondary
65,535 / 0
Positive VARhour (Quadrants 1+2) in the Interval, Secondary
65,535 / 0
Negative VARhour (Quadrants 3+4) in the Interval, Secondary
65,535 / 0
Positive Watthour (Quadrants 1+4) in the Interval, Secondary
65,535 / 0
Negative Watthour (Quadrants 2+3) in the Interval, Secondary
65,535 / 0
1 VAH
1 VARH
1 VARH
1 WH
1 WH
F3
F57
F57
F57
F57
F57
1901H-1920H
1921H-1922H
1923H-1924H
1925H-1926H
1927H-1928H
06402-06433
06434-06435
06436-06437
06438-06439
06440-06441
483
483
483
483
0
1
2
3
30
30
30
30
Reserved
Pulse Accumulation, Internal Input 1 in the Interval, Scaled
Pulse Accumulation, Internal Input 2 in the Interval, Scaled
Pulse Accumulation, Internal Input 3 in the Interval, Scaled
Pulse Accumulation, Internal Input 4 in the Interval, Scaled
1 Unit
1 Unit
1 Unit
1 Unit
F18
F18
F18
F18
Reserved
R
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-44
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
1929H-192AH
192BH-192CH
192DH-192EH
192FH-1930H
1931H-1932H
1933H-1934H
1935H-1936H
1937H-1938H
1939H
193AH
193BH
193CH
193DH
193EH
193FH
1940H
1941H
1942H
1943H
1944H
06442-06443
06444-06445
06446-06447
06448-06449
06450-06451
06452-06453
06454-06455
06456-06457
06458
06459
06460
06461
06462
06463
06464
06465
06466
06467
06468
06469
483
483
483
483
484
484
484
484
485
485
485
485
486
486
486
486
486
486
486
486
4
5
6
7
0
1
2
3
0
1
2
3
0
1
2
3
4
5
6
7
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
1945H-1952H
1953H
1954H
1955H
1956H
06470-06483
06484
06485
06486
06487
489
489
489
489
0
1
2
3
30
30
30
30
1957H
06488
489
4
30
1958H
1959H
06489
06490
490
490
0
1
30
30
195AH-195DH
195EH-195FH
1960H-1961H
06491-06494
06495-06496
06497-06498
491
492
492
0
0
1
50
30
30
ct_gain_switch (0000 for low range, 1111 for high range, others for
auto range)
65,535 / 0
Flicker Countdown Block
Short Term Flicker Countdown
65,535 / 0
Long Term Flicker Countdown
65,535 / 0
Cumulative Demand Block
Cumulative Demand Block Time Stamp
12/31/9999 23:59:59.99
Positive Watt (Quadrants 1+4) Cumulative Demand
4,294,967,295 / 0
Negative Watt (Quadrants 2+3) Cumulative Demand
4,294,967,295 / 0
1962H-1963H
06499-06500
493
0
30
Positive Watt (Quadrants 1+4) Continuous Cumulative Demand
Description
Range
Units
Type
R/W
Pulse Accumulation, Internal Input 5 in the Interval, Scaled
Pulse Accumulation, Internal Input 6 in the Interval, Scaled
Pulse Accumulation, Internal Input 7 in the Interval, Scaled
Pulse Accumulation, Internal Input 8 in the Interval, Scaled
Pulse Aggregation 1 in the Interval, Scaled
Pulse Aggregation 2 in the Interval, Scaled
Pulse Aggregation 3 in the Interval, Scaled
Pulse Aggregation 4 in the Interval, Scaled
Quadrant 1 Watthour in the Interval, Secondary
Quadrant 4 Watthour in the Interval, Secondary
Quadrant 2 Watthour in the Interval, Secondary
Quadrant 3 Watthour in the Interval, Secondary
Quadrant 1 VAhour in the Interval, Secondary
Quadrant 1 VARhour in the Interval, Secondary
Quadrant 4 VAhour in the Interval, Secondary
Quadrant 4 VARhour in the Interval, Secondary
Quadrant 2 VAhour in the Interval, Secondary
Quadrant 2 VARhour in the Interval, Secondary
Quadrant 3 VAhour in the Interval, Secondary
Quadrant 3 VARhour in the Interval, Secondary
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
4,294,967,295 / 0
65,535 / 0
65,535 / 0
65,535 / 0
65,535 / 0
65,535 / 0
65,535 / 0
65,535 / 0
65,535 / 0
65,535 / 0
65,535 / 0
65,535 / 0
65,535 / 0
1 Unit
1 Unit
1 Unit
1 Unit
1 Unit
1 Unit
1 Unit
1 Unit
1 WH
1 WH
1 WH
1 WH
1 VAH
1 VARH
1 VAH
1 VARH
1 VAH
1 VARH
1 VAH
1 VARH
F18
F18
F18
F18
F18
F18
F18
F18
F57
F57
F57
F57
F57
F57
F57
F57
F57
F57
F57
F57
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Reserved
KYZ Pulse Output in the Interval, Relay 1 - Pulse 1
KYZ Pulse Output in the Interval, Relay 2 - Pulse 2
KYZ Pulse Output in the Interval, Relay 3
KYZ Pulse Output in the Interval, Relay 4
65,535 / 0
65,535 / 0
65,535 / 0
65,535 / 0
1 pulse
1 pulse
1 pulse
1 pulse
F57
F57
F57
F57
R
R
R
R
R
R/W
1 second
1 second
4,294,967,295 / 0
F56
F56
R
R
F3
F18
F18
R
R
R
F18
R
F18
R
1964H-1965H
06501-06502
493
1
30
1A08H-1A09H
1A0AH-1A0BH
1A0CH-1A0DH
1A0EH-1A0FH
1A10H-1A11H
06665-06666
06667-06678
06669-06670
06671-06672
06673-06674
500
500
500
501
502
0
1
2
0
0
30
30
30
30
30
Uncompensated One second Phase A VA
Uncompensated One second Phase B VA
Uncompensated One second Phase C VA
Uncompensated One second VA
Uncompensated One second Phase A VAR
Negative Watt (Quadrants 2+3) Continuous Cumulative Demand
4,294,967,295 / 0
Uncompensated and Q Block
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VA / 0 VA
+32767 VAR / - 32768 VAR
1/65536 VA sec
1/65536 VA sec
1/65536 VA sec
1/65536 VA sec
1/65536 VAR sec
F7
F7
F7
F7
F7
1A12H-1A13H
1A14H-1A15H
1A16H-1A17H
1A18H-1A19H
1A1AH-1A1BH
1A1CH-1A1DH
1A1EH-1A1FH
06675-06676
06677-06678
06679-06680
06681-06682
06683-06684
06685-06686
06687-06688
502
502
503
504
504
504
505
1
2
0
0
1
2
0
30
30
30
30
30
30
30
Uncompensated One second Phase B VAR
Uncompensated One second Phase C VAR
Uncompensated One second VAR
Uncompensated One second Phase A W
Uncompensated One second Phase B W
Uncompensated One second Phase C W
Uncompensated One second W
1/65536 VAR sec
1/65536 VAR sec
1/65536 VAR sec
1/65536 W sec
1/65536 W sec
1/65536 W sec
1/65536 W sec
F7
F7
F7
F7
F7
F7
F7
1A20H-1A23H
06689-06692
506
0
20
Uncompensated VAh, secondary BCD
1 VAh
F11
1A24H-1A27H
06693-06706
506
1
20
Uncompensated + VARh, secondary BCD
1 VARh
F11
1A28H-1A2BH
06697-06700
506
2
20
Uncompensated - VARh, secondary BCD
1 VARh
F11
1A2CH-1A2FH
06701-06704
506
3
20
Uncompensated + Wh, seconary BCD
1 Wh
F11
+32767 VAR / - 32768 VAR
+32767 VAR / - 32768 VAR
+32767 VAR / - 32768 VAR
+32767 W / - 32768 W
+32767 W / - 32768 W
+32767 W / - 32768 W
+32767 W / - 32768 W
9,999,999,999,999,999 VAh / 0
VAh
9,999,999,999,999,999 VARh /
0 VARh
9,999,999,999,999,999 VARh /
0 VARh
9,999,999,999,999,999 Wh / 0
Wh
Notes
Debug and
production
only
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-45
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
Description
1A30H-1A33H
1A34H-1A37H
1A38H-1A3BH
1A3CH-1A3FH
1A40H-1A43H
1A44H-1A47H
1A48H-1A6FH
1A70H
1A71H
1A72H
1A73H
1A74H
06705-06708
06709-06712
06713-06716
06717-06720
06721-06724
06725-06728
06729-06768
06769
06770
06771
06772
06773
506
507
507
507
507
507
4
0
1
2
3
4
20
20
20
20
20
20
510
510
510
510
510
0
1
2
3
4
30
30
30
30
30
1A81H-1A82H
1A83H-1A84H
1A85H-1A86H
1A87H-1A88H
1A89H-1A8AH
1A8BH-1A8CH
1A8DH-1A8EH
1A8FH-1A90H
1A91H-1A92H
1A93H-1A96H
1A97H-1A9AH
1A9BH-1A9EH
1A9FH-1AA2H
06784-06785
06786-06787
06788-06789
06790-06791
06792-06793
06794-06795
06796-06797
06798-06799
06800-06801
06802-06805
06806-06809
06810-06813
06814-06817
512
512
512
513
514
515
515
516
516
517
517
518
518
0
1
2
0
0
0
1
0
1
0
1
0
1
30
30
30
30
30
30
30
30
30
50
50
50
50
Uncompensated - Wh, seconary BCD
Uncompensated VAh, secondary, binary
Uncompensated +VARh, secondary, binary
Uncompensated -VARh, secondary, binary
Uncompensated +Wh, secondary, binary
Uncompensated -Wh, secondary, binary
Reserved
Uncompensated VAh in the Interval, secondary
Uncompensated +VARh in the Interval, secondary
Uncompensated -VARh in the Interval, secondary
Uncompensated +Wh in the Interval, secondary
Uncompensated -Wh in the Interval, secondary
Reserved
One second Phase A Q
One second Phase B Q
One second Phase C Q
One second Q
Thermal Average Q
Maximum Thermal Average + Q
Maximum Thermal Average - Q
Minimum Thermal Average + Q
Minimum Thermal Average - Q
Maximum Thermal Average + Q Time Stamps
Maximum Thermal Average - Q Time Stamps
Minimum Thermal Average + Q Time Stamps
Minimum Thermal Average - Q Time Stamps
1AA3H-1AA6H
06818-06821
519
0-1
20
+ Qh, secondary BCD
1AA7H-1AAAH
06822-06825
519
0-1
20
- Qh, secondary BCD
1AABH-1AAEH
06826-06829
520
0
20
+ Qh, secondary binary
1AAFH-1AB2H
1AB3H-1AC0H
1AC1H
1AC2H
1AC3H-1AC6H
1AD7H-1AC8H
1AC9H-1ACAH
1ACBH-1ACCH
1ACDH-1ACEH
1ACFH-1AD0H
1AD1H-1AD4H
1AD5H-1AD8H
1AD9H-1ADCH
1ADDH-1AE0H
1AE1H-1AE2H
1AE3H-1AE4H
1AE5H-1AE6H
1AE7H-1AE8H
1AE9H-1AEAH
1AEBH-1AEEH
1AEFH-1AF2H
1AF3H-1AF6H
1AF7H-1AFAH
06830-06833
06834-06849
06850
06851
06852-06855
06856-06857
06858-06859
06860-06861
06862-06863
06864-06865
06866-06869
06870-06873
06874-06877
06878-06881
06882-06883
06884-06885
06886-06887
06888-06889
06890-06891
06892-06895
06896-06899
06900-06903
06904-06907
520
1
20
523
523
0
1
30
30
525
526
526
527
527
528
528
529
529
530
531
531
532
532
533
533
534
534
0
0
1
0
1
0
1
0
1
0
0
1
0
1
0
1
0
1
30
30
30
30
30
50
50
50
50
30
30
30
30
30
50
50
50
50
- Qh, secondary binary
Reserved
+ Qh in the Interval, secondary
- Qh in the Interval, secondary
Reserved
Block Window Average Q
Maximum Block Window Average + Q
Maximum Block Window Average - Q
Minimum Block Window Average + Q
Minimum Block Window Average - Q
Maximum Block Window Average + Q Time Stamps
Maximum Block Window Average - Q Time Stamps
Minimum Block Window Average + Q Time Stamps
Minimum Block Window Average - Q Time Stamps
Rolling Window Average Q
Maximum Rolling Window Average + Q
Maximum Rolling Window Average - Q
Minimum Rolling Window Average + Q
Minimum Rolling Window Average - Q
Maximum Rolling Window Average + Q Time Stamps
Maximum Rolling Window Average - Q Time Stamps
Minimum Rolling Window Average + Q Time Stamps
Minimum Rolling Window Average - Q Time Stamps
1AFBH-1AFEH
06908-06911
535
0
50
Scaled Energy Block Timestamp
Range
Units
Type
9,999,999,999,999,999 Wh / 0
Wh
9,999,999,999,999,999 / 0
9,999,999,999,999,999 / 0
9,999,999,999,999,999 / 0
9,999,999,999,999,999 / 0
9,999,999,999,999,999 / 0
9,999,999,999,999,999 / 0
65,535 / 0
65,535 / 0
65,535 / 0
65,535 / 0
65,535 / 0
1 Wh
1 VAh
1 VARh
1 VARh
1 Wh
1 Wh
1
1
1
1
1
1
F11
F12
F12
F12
F12
F12
F12
F47
F47
F47
F47
F47
+32767 Q / -32768 Q
+32767 Q / -32768 Q
+32767 Q / -32768 Q
+32767 Q / -32768 Q
+32767 Q / -32768 Q
+32767 Q / -32768 Q
+32767 Q / -32768 Q
+32767 Q / -32768 Q
+32767 Q / -32768 Q
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
9,999,999,999,999,999 Qh / 0
Qh
9,999,999,999,999,999 Qh / 0
Qh
9,999,999,999,999,999 Qh / 0
Qh
9,999,999,999,999,999 Qh / 0
Qh
1/65536 Q sec
1/65536 Q sec
1/65536 Q sec
1/65536 Q sec
1/65536 Q sec
1/65536 Q sec
1/65536 Q sec
1/65536 Q sec
1/65536 Q sec
F7
F7
F7
F7
F7
F7
F7
F7
F7
F3
F3
F3
F3
1 Qh
F11
1 Qh
F11
1 Qh
F12
1 Qh
F12
65,535 / 0
65,535 / 0
1
1
F47
F47
1/65536 Q sec
1/65536 Q sec
1/65536 Q sec
1/65536 Q sec
1/65536 Q sec
F7
F7
F7
F7
F7
F3
F3
F3
F3
F7
F7
F7
F7
F7
F3
F3
F3
F3
+32767 Q / -32768 Q
+32767 Q / -32768 Q
+32767 Q / -32768 Q
+32767 Q / -32768 Q
+32767 Q / -32768 Q
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
+32767 Q / -32768 Q
+32767 Q / -32768 Q
+32767 Q / -32768 Q
+32767 Q / -32768 Q
+32767 Q / -32768 Q
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
Scaled Energy Block
12/31/9999 23:59:59.99
1/65536 Q sec
1/65536 Q sec
1/65536 Q sec
1/65536 Q sec
1/65536 Q sec
R/W
Notes
F3
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-46
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
Description
1AFFH-1B00H
06912-06913
536
0
20
Total VAh (Quadrant 1+2+3+4) Scaled Primary
1B01H-1B02H
06914-06915
536
1
20
Positive VARh (Quadrant 1+2) Scaled Priamry
1B03H-1B04H
06916-06917
536
2
20
Negative VARh (Quadrant 3+4) Scaled Primary
1B05H-1B06H
06918-06919
537
0
20
Positive Wh (Quadrant 1+4) Scaled Primary
1B07H-1B08H
06920-06921
537
1
20
Quadrant 1 VAh Scaled Primary
1B09H-1B0AH
06922-06923
537
2
20
Quadrant 1 VARh Scaled Primary
1B0BH-1B0CH
06924-06925
537
3
20
Quadrant 4 VAh Scaled Primary
1B0DH-1B0EH
06926-06927
537
4
20
Quadrant 4 VARh Scaled Primary
1B0FH-1B10H
06928-06929
537
5
20
Negative Wh (Quadrant 2+3) Scaled Primary
1B11H-1B12H
1B13H-1B14H
06930-06931
06932-06933
537
537
6
7
20
20
Quadrant 2 VAh Scaled Primary
Quadrant 2 VARh Scaled Primary
1B15H-1B16H
06934-06935
537
8
20
Quadrant 3 VAh Scaled Primary
1B17H-1B18H
06936-06937
537
9
20
Quadrant 3 VARh Scaled Primary
1B19H-1B1AH
06938-06939
538
0
20
I2t Phase A Scaled Priamry
1B1BH-1B1CH
06940-06941
538
1
20
I2t Phase B Scaled Primary
1B1DH-1B1EH
06942-06943
538
2
20
I2t Phase C Scaled Primary
1B1FH-1B20H
06944-06945
538
3
20
V2t Phase A Scaled Primary
1B21H-1B22H
06946-06947
538
4
20
V2t Phase B Scaled Primary
1B23H-1B24H
06948-06949
538
5
20
V2t Phase C Scaled Primary
1B25H-1B26H
06950-06951
539
0
20
Quadrant 1 Wh Scaled Primary
1B27H-1B28H
06952-06953
539
1
20
Quadrant 4 Wh Scaled Primary
1B29H-1B2AH
06954-06955
539
2
20
Quadrant 2 Wh Scaled Primary
1B2BH-1B2CH
06956-06957
539
3
20
Quadrant 3 Wh Scaled Primary
1B2DH-1B2EH
06958-06959
450
0
20
Uncompensated Total VAh, Scaled Primary
1B2FH-1B30H
06960-06961
540
1
20
Uncompensated + VARh Scaled Primary
1B31H-1B32H
06962-06963
540
2
20
Uncompensated - VARh Scaled Primary
1B33H-1B34H
06964-06965
540
3
20
Uncompensated + Wh Scaled Primary
1B35H-1B36H
06966-06967
540
4
20
Uncompensated - Wh Scaled Primary
1B37H-1B38H
06968-06969
541
0
20
+ Qh Scaled Primary
1B39H-1B3AH
06970-06971
541
1
20
- Qh Scaled Primary
1B3BH-1B3CH
1B3DH-1B3EH
1B3FH-1B40H
06972-06973
06974-06975
06976-06977
542
542
542
0
1
2
20
20
20
Test Mode Block Window Average VA
Test Mode Block Window Average +VAR
Test Mode Block Window Average -VAR
Range
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
variable (9999 through
999999999 / 0)
Test Mode Demand
+32767.9999 VA / 0 VA
+32767.9999 VAR / 0 VAR
0 VAR / -32767.9999 VAR
Units
Type
6
-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
variable 106 - 10-7
F64
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
variable 10 - 10
-7
1/ 65536 VA sec
1/ 65536 VAR sec
1/ 65536 VAR sec
R/W
Notes
F64
F7
F7
F7
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-47
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
1B41H-1B42H
1B43H-1B44H
06978-06979
06980-06981
542
542
3
4
20
20
1B4FH-1B50H
06992-06993
543
0
20
1B51H-1B52H
06994-06995
543
1
20
1B53H-1B54H
06996-06997
543
2
20
1B55H-1B56H
06998-06999
543
3
20
1B57H-1B58H
07000-07001
543
4
20
1B59H-1B5AH
07002-07003
543
5
20
1B5BH-1B5CH
07004-07005
543
6
20
1B5DH-1B5EH
07006-07007
543
7
20
1B5FH-1B60H
1B61H-1B62H
07008-07009
07010-07011
544
0
20
544
1
20
1B63H-1B64H
07012-07013
544
2
20
1B65H-1B66H
07014-07015
544
3
20
1E41H-1E42H
07746-07747
583
0
30
1E43H-1E44H
07748-07749
583
1
30
1E45H-1E46H
07750-07751
583
2
30
1E47H-1E48H
07752-07753
584
0
30
1E49H-1E4AH
07754-07755
584
1
30
1E4BH-1E4CH
07756-07757
584
2
30
1E4DH-1E4EH
07758-07759
584
3
30
1E4FH-1E50H
07760-07761
584
4
30
1E51H-1E52H
1E53H-1E54H
1E55H-1E56H
07762-07763
07764-07765
07766-07767
584
584
584
5
6
7
30
30
30
1E57H-1E58H
1E59H-1E5AH
07768-07769
07770-07771
584
584
8
9
30
30
1E5BH-1E5CH
07772-07773
585
0
30
1E5DH-1E5EH
07774-07775
585
1
30
1E5FH-1E60H
07776-07777
585
2
30
1E61H-1E62H
07778-07779
585
3
30
1E63H-1E64H
07780-07781
585
4
30
1E65H-1E66H
07782-07783
585
5
30
Description
Range
Test Mode Block Window Average +W
Test Mode Block Window Average -W
+32767.9999 W / 0 W
0 W / -32767.9999 W
Scaled Energy Block – Cont.
variable (9999 through
Pulse Accumulation Inputs 1, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 2, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 3, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 4, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 5, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 6, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 7, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 8, Scaled
999999999 / 0)
variable (9999 through
Pulse Aggregations 1, Scaled
999999999 / 0)
variable (9999 through
Pulse Aggregations 2, Scaled
999999999 / 0)
variable (9999 through
Pulse Aggregations 3, Scaled
999999999 / 0)
variable (9999 through
Pulse Aggregations 4, Scaled
999999999 / 0)
variable (9999 through
Total VAh (Quadrant 1+2+3+4) in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
Positive VARh (Quadrant 1+2) in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
Negative VARh (Quadrant 3+4) in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
Positive Wh (Quadrant 1+4) in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
Quadrant 1 VAh in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
Quadrant 1 VARh in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
Quadrant 4 VAh in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
Quadrant 4 VARh in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
Negative Wh (Quadrant 2+3) in the Interval, Scaled Primary
999999999 / 0)
Quadrant 2 VAh in the Interval, Scaled Primary
999999999 / 0)
Quadrant 2 VARh in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
Quadrant 3 VAh in the Interval, Scaled Primary
999999999 / 0)
Quadrant 3 VARh in the Interval, Sclaed Primary
999999999 / 0)
variable (9999 through
I2t Phase A in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
I2t Phase B in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
I2t Phase C in the Interval, Sclaed Primary
999999999 / 0)
variable (9999 through
V2t Phase A in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
V2t Phase B in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
V2t Phase C in the Interval, Scaled Primary
999999999 / 0)
Units
Type
R/W
1/ 65536 W sec
1/ 65536 W sec
F7
F7
R
R
variable 106 - 10-7
F64
variable 106 - 10-7
F64
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
variable 106 - 10-7
variable 106 - 10-7
F64
F64
F64
variable 106 - 10-7
variable 106 - 10-7
F64
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
variable 10 - 10
-7
Notes
F64
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-48
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
1E67H-1E68H
07784-07785
586
0
30
1E69H-1E6AH
07786-07787
586
1
30
1E6BH-1E6CH
07788-07789
586
2
30
1E6DH-1E6EH
07790-07791
586
3
30
1E6FH-1E70H
1E71H-1E72H
07792-07793
07794-07795
587
587
0
1
30
30
1E73H-1E74H
07796-07797
587
2
30
1E75H-1E76H
07798-07799
587
3
30
1E77H-1E78H
07800-07801
587
4
30
1E79H-1E7AH
07802-07803
588
0
30
1E7BH-1E7CH
07804-07805
588
1
30
1E7DH-1E7EH
07806-07807
589
0
30
1E7FH-1E80H
07808-07809
589
1
30
1E81H-1E82H
07810-07811
589
2
30
1E83H-1E84H
07812-07813
589
3
30
1E85H-1E86H
07814-07815
589
4
30
1E87H-1E88H
07816-07817
589
5
30
1E89H-1E8AH
07818-07819
589
6
30
1E8BH-1E8CH
07820-07821
589
7
30
1E8DH-1E8EH
07822-07823
590
0
30
1E8FH-1E90H
07824-07825
590
1
30
1E91H-1E92H
07826-07827
590
2
30
1E93H-1E94H
07828-07829
590
3
30
1E95H-1E98H
1E99H
1E9AH
1E9BH
1E9CH
1E9DH
1E9EH
1E9FH-1EA2H
1EA3H-1EA6H
1EA7H-1EAAH
1EABH-1EAEH
1EAFH-1EB2H
07830-07833
07834
07835
07836
07837
07838
07839
07840-07843
07844-07847
07848-07851
07852-07855
07856-07859
591
592
592
593
593
594
594
595
595
596
596
597
0
0
1
0
1
0
1
0
1
0
1
0
50
30
30
30
30
30
30
50
50
50
50
50
1EB3H-1EB6H
07860-07863
Description
Range
variable (9999 through
Quadrant 1 Wh in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
Quadrant 4 Wh in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
Quadrant 2 Wh in the Interval, Sclaed Primary
999999999 / 0)
variable (9999 through
Quadrant 3 Wh in the Interval, Scaled Primary
999999999 / 0)
Uncompensated Total VAh (Q 1+2+3+4) in the Interval, Scaled
variable (9999 through
Primary
999999999 / 0)
Uncompensated + VARh in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
Uncompensated - VARh in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
Uncompensated + Wh in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
Uncompensated - Wh in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
+ Qh in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
- Qh in the Interval, Scaled Primary
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 1 in the Interval, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 2 in the Interval, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 3 in the Interval, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 4 in the Interval, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 5 in the Interval, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 6 in the Interval, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 7 in the Interval, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 8 in the Interval, Scaled
999999999 / 0)
variable (9999 through
Pulse Aggregations 1 in the Interval, Scaled
999999999 / 0)
variable (9999 through
Pulse Aggregations 2 in the Interval, Scaled
999999999 / 0)
variable (9999 through
Pulse Aggregations 3 in the Interval, Scaled
999999999 / 0)
variable (9999 through
Pulse Aggregations 4 in the Interval, Scaled
999999999 / 0)
Total Average Power Factor Block
Total Average Power Factor Block Timestamp
12/31/9999 23:59:59.99
Total Average Power Factor Q14
1.000 / 0
Total Average Power Factor Q23
1.000 / 0
Maximum Total Average Power Factor Q14
1.000 / 0
Maximum Total Average Power Factor Q23
1.000 / 0
Minimum Total Average Power Factor Q14
1.000 / 0
Minimum Total Average Power Factor Q23
1.000 / 0
Maximum Total Average Power Factor Q14 Timestamp
12/31/9999 23:59:59.99
Maximum Total Average Power Factor Q23 Timestamp
12/31/9999 23:59:59.99
Minimum Total Average Power Factor Q14 Timestamp
12/31/9999 23:59:59.99
Minimum Total Average Power Factor Q23 Timestamp
12/31/9999 23:59:59.99
Total Average Power Factor Reset Timestamp
12/31/9999 23:59:59.99
Reserved
Units
Type
variable 106 - 10-7
F64
variable 106 - 10-7
F64
6
-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
variable 10 - 10
variable 106 - 10-7
F64
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 10 - 10
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
F3
F8
F8
F8
F8
F8
F8
F3
F3
F3
F3
F3
R/W
Notes
R
R
R
R
R
R
R
R
R
R
R
R
R
Negative Maximum Pulse Aggregation Average Block
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-49
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
1EB7H-1EBAH
07864-07867
599
0
30
Negative Maximum Block Window Average Aggregation 1
30
Negative Maximum Block Window Average Aggregation 2-4
0 /- 9,223,372,036,854,776,808 1 Unit
Negative Maximum Block Window Average Aggregation 1 Time
Stamp
12/31/9999 23:59:59.99
10 msec
Negative Maximum Block Window Average Aggregation 2-4 Time
Stamp
12/31/9999 23:59:59.99
10 msec
New Demand Block(Either Block window average or Sliding Window Average)
VAQ1234
+32767 VA / 0 VA
1/ 65536 VA sec
WQ14
+32767 W / 0 W
1/ 65536 W sec
WQ23
+32767 W / 0 W
1/ 65536 W sec
VARQ12
+32767 VAR / 0 VAR
1/ 65536 VAR sec
VARQ34
+32767 VAR / 0 VAR
1/ 65536 VAR sec
pQ
+32767 Q / 0 Q
1/ 65536 Q sec
nQ
+32767 Q / 0 Q
1/ 65536 Q sec
WQ1
+32767 W / 0 W
1/ 65536 W sec
WQ2
+32767 W / 0 W
1/ 65536 W sec
WQ3
+32767 W / 0 W
1/ 65536 W sec
WQ4
+32767 W / 0 W
1/ 65536 W sec
VARQ1
+32767 VAR / 0 VAR
1/ 65536 VAR sec
VARQ2
+32767 VAR / 0 VAR
1/ 65536 VAR sec
VARQ3
+32767 VAR / 0 VAR
1/ 65536 VAR sec
VARQ4
+32767 VAR / 0 VAR
1/ 65536 VAR sec
VAQ1
+32767 VA / 0 VA
1/ 65536 VA sec
VAQ2
+32767 VA / 0 VA
1/ 65536 VA sec
VAQ3
+32767 VA / 0 VA
1/ 65536 VA sec
VAQ4
+32767 VA / 0 VA
1/ 65536 VA sec
I2T Phase A
+32767 I2T / 0 I2T
1/ 65536 I2T sec
I2T Phase B
+32767 I2T / 0 I2T
1/ 65536 I2T sec
I2T Phase C
+32767 I2T / 0 I2T
1/ 65536 I2T sec
V2T Phase A
+32767 V2T / 0 V2T
1/ 65536 V2T sec
V2T Phase B
+32767 V2T / 0 V2T
1/ 65536 V2T sec
V2T Phase C
+32767 V2T / 0 V2T
1/ 65536 V2T sec
Uncompensated VA
+32767 VA / 0 VA
1/ 65536 VA sec
Uncompensated +VAR
+32767 VAR / 0 VAR
1/ 65536 VAR sec
Uncompensated -VAR
+32767 VAR / 0 VAR
1/ 65536 VAR sec
Uncompensated +W
+32767 W / 0 W
1/ 65536 W sec
Uncompensated -W
+32767 W / 0 W
1/ 65536 W sec
1EBBH-1EC6H
07868-07879
599
1-3
1EC7H-1ECAH
07880-07883
600
0
1ECBH-1ED6H
07884-07895
600
1-3
1EF7H-1EF8H
1EF9H-1EFAH
1EFBH-1EFCH
1EFDH-1EFEH
1EFFH-1F00H
1F01H-1F02H
1F03H-1F04H
1F05H-1F06H
1F07H-1F08H
1F09H-1F0AH
1F0BH-1F0CH
1F0DH-1F0EH
1F0FH-1F10H
1F11H-1F12H
1F13H-1F14H
1F15H-1F16H
1F17H-1F18H
1F19H-1F1AH
1F1BH-1F1CH
1F1DH-1F1EH
1F1FH-1F20H
1F21H-1F22H
1F23H-1F24H
1F25H-1F26H
1F27H-1F28H
1F29H-1F2AH
1F2BH-1F2CH
1F2DH-1F2EH
1F2FH-1F30H
1F31H-1F32H
07928-07929
07930-07931
07932-07933
07934-07935
07936-07937
07938-07939
07940-07941
07942-07943
07944-07945
07946-07947
07948-07949
07950-07951
07952-07953
07954-07955
07956-07957
07958-07959
07960-07961
07962-07963
07964-07965
07966-07967
07968-07969
07970-07971
07972-07973
07974-07975
07976-07977
07978-07979
07980-07981
07982-07983
07984-07985
07986-07987
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
1227
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
Description
Range
Units
0 /- 9,223,372,036,854,776,808 1 Unit
Type
R/W
F62
R
F62
R
F3
R
F3
R
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
1F33H-1F36H
07988-07991
1228
0
Internal Input 1
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
1F37H-1F3AH
07992-07995
1228
1
Internal Input 2
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
1F3BH-1F3EH
07996-07999
1228
2
Internal Input 3
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
1F3FH-1F42H
08000-08003
1228
3
Internal Input 4
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
1F43H-1F46H
08004-08007
1228
4
Internal Input 5
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
R
1F47H-1F4AH
08008-08011
1228
5
Internal Input 6
+/- 9,223,372,036,854,776,808
1 Unit
F62
1F4BH-1F4EH
08012-08015
1228
6
Internal Input 7
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
1F4FH-1F52H
08016-08019
1228
7
Internal Input 8
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
1F53H-1F56H
08020-08023
1229
0
Aggregation 1
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
1F57H-1F5AH
1F5BH-1F5EH
08024-08027
08028-08031
1229
1229
1
2
Aggregation 2
Aggregation 3
+/- 9,223,372,036,854,776,808
+/- 9,223,372,036,854,776,808
1 Unit
1 Unit
F62
F62
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-50
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
1F5FH-1F62H
1F63H
1F64H
1F65H
1F66H
1F67H-1F9DH
08032-08035
8036
8037
8038
8039
08040-08088
1229
1230
1230
1230
1231
3
0
1
2
0
DNP
Obj
Description
Aggregation 4
PF
+PF
-PF
Uncomp PF
Reserved
Range
Units
Type
R/W
+/- 9,223,372,036,854,776,808
-1.0 / 1.0
0 / 1.0
0 / 1.0
-1.0 / 1.0
1 Unit
0.001 PF
0.001 PF
0.001 PF
0.001 PF
F62
F103
F103
F103
F103
R
R
R
R
R
F3
F7
F7
F7
F9
F9
F9
F7
F7
F7
F7
R
R
R
R
R
R
R
R
R
R
R
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
F3
R
F12
R
F12
R
Notes
,
Master Device Data Block
2100H-21FFH
08449-08704
2200H-2203H
2204H-2205H
2206H-2207H
2208H-2209H
220AH
220BH
220CH
220DH-220EH
2215H-2216H
2217H-2218H
2219H-221AH
08705-08708
08709-08710
08711-08712
08713-08714
08715
08716
08717
08718-08719
08726-08727
08728-08729
08730-08731
603
604
604
604
605
605
605
606
608
608
608
0
0
1
2
0
1
2
0
0
1
2
23D6H
23D7H
23D8H
23D9H
23DAH
23DBH
23DCH
23DDH
23DEH
23DFH
23E0H
23E1H
23E2H
23E3H
23E4H
23E5H
23E6H
23E7H
23E8H-23EBH
23ECH-23EFH
23F0H-23F3H
23F4H-23F7H
23F8H-23FBH
23FCH-23FFH
2400H-2403H
2404H-2407H
2408H-240BH
240CH-240FH
2410FH-2413H
2414H-2417H
09175
09176
09177
09178
09179
09180
09181
09182
09183
09184
09185
09186
09187
09188
09189
09190
09191
09192
09193-09196
09197-09200
09201-09204
09205-09208
09209-09212
09213-09216
09217-09220
09221-09224
09225-09228
09229-09232
09233-09236
09237-09240
656
657
658
659
660
661
662
662
662
663
663
663
664
664
664
665
665
665
666
666
666
666
666
666
667
667
667
667
667
667
0
0
0
0
0
0
0
1
2
0
1
2
0
1
2
0
1
2
0
1
2
3
4
5
0
1
2
3
4
5
2C00H-2C03H
11265-11268
900
0
2C04H-2C07H
11269-11272
901
0
2C08H-2C0BH
11273-11276
901
1
Power Quality Test (EN-50160/IEC61000-4-30) Dynamic Readings Block
Dynamic Readings Block Time Stamp
12/31/9999 23:59:59.99
10 msec
Sym Comp Voltage Magnitude 3 Sec - zero sequence
+32767 / -32768
1/65536 V
Sym Comp Voltage Magnitude 3 Sec - positive sequence
+32767 / -32768
1/65536 V
Sym Comp Voltage Magnitude 3 Sec - negative sequence
+32767 / -32768
1/65536 V
Sym Comp Voltage Phase 3 Sec - zero sequence
+327.67 / -327.68
0.01 degree
Sym Comp Voltage Phase 3 Sec - positive sequence
+327.67 / -327.68
0.01 degree
Sym Comp Voltage Phase 3 Sec - negative sequence
+327.67 / -327.68
0.01 degree
10 sec Ave Freq
+32767Hz / 0Hz
1/65536Hz
Sym Comp Voltage Magnitude 10 Min - zero sequence
+32767 / -32768
1/65536 V
Sym Comp Voltage Magnitude 10 Min - positive sequence
+32767 / -32768
1/65536 V
Sym Comp Voltage Magnitude 10 Min - negative sequence
+32767 / -32768
1/65536 V
Total Demand Distortion (TDD)
TDD Phase A-N / Phase A-B Voltage
+327.67% / -327.68%
0.01%
TDD Phase B-N / Phase B-C Voltage
+327.67% / -327.68%
0.01%
TDD Phase C-N / Phase C-A Voltage
+327.67% / -327.68%
0.01%
TDD Phaes A Current
+327.67% / -327.68%
0.01%
TDD Phaes B Current
+327.67% / -327.68%
0.01%
TDD Phase C Current
+327.67% / -327.68%
0.01%
Maximum TDD Phase A-N / Phase A-B Voltage
+327.67% / -327.68%
0.01%
Maximum TDD Phase B-N / Phase B-C Voltage
+327.67% / -327.68%
0.01%
Maximum TDD Phase C-N / Phase C-A Voltage
+327.67% / -327.68%
0.01%
Maximum TDD Phaes A Current
+327.67% / -327.68%
0.01%
Maximum TDD Phaes B Current
+327.67% / -327.68%
0.01%
Maximum TDD Phaes C Current
+327.67% / -327.68%
0.01%
Minimum TDD Phase A-N / Phase A-B Voltage
+327.67% / -327.68%
0.01%
Minimum TDD Phase B-N / Phase A-B Voltage
+327.67% / -327.68%
0.01%
Minimum TDD Phase C-N / Phase A-B Voltage
+327.67% / -327.68%
0.01%
Minimum TDD Phase A Current
+327.67% / -327.68%
0.01%
Minimum TDD Phase B Current
+327.67% / -327.68%
0.01%
Minimum TDD Phase C Current
+327.67% / -327.68%
0.01%
Maximum TDD Phase A-N / Phase A-B Voltage Timestamp
12/31/9999 23:59:59.99
10 msec
Maximum TDD Phase B-N / Phase B-C Voltage Timestamp
12/31/9999 23:59:59.100
11 msec
Maximum TDD Phase C-N / Phase C-A Voltage Timestamp
12/31/9999 23:59:59.101
12 msec
Maximum TDD Phase A Current Timestamp
12/31/9999 23:59:59.102
13 msec
Maximum TDD Phase B Current Timestamp
12/31/9999 23:59:59.103
14 msec
Maximum TDD Phase C Current Timestamp
12/31/9999 23:59:59.104
15 msec
Minimum TDD Phase A-N / Phase A-B Voltage Timestamp
12/31/9999 23:59:59.105
16 msec
Minimum TDD Phase B-N / Phase B-C Voltage Timestamp
12/31/9999 23:59:59.106
17 msec
Minimum TDD Phase C-N / Phase C-A Voltage Timestamp
12/31/9999 23:59:59.107
18 msec
Minimum TDD Phase A Current Timestamp
12/31/9999 23:59:59.108
19 msec
Minimum TDD Phase A Current Timestamp
12/31/9999 23:59:59.109
20 msec
Minimum TDD Phase A Current Timestamp
12/31/9999 23:59:59.110
21 msec
Frozen Energy Block
Frozen Energy Block Time Stamp
12/31/9999 23:59:59.99
10 msec
Frozen Energy - Secondary Energy Readings
+9,999,999,999,999,999 VAh /
VA hour (Quadrant 1+2+3+4), Secondary
0 VAh
1 VAH
+9,999,999,999,999,999 VARh
VAR hour (Quadrant 1+2), Secondary
/ 0 VARh
1 VARH
1
1
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-51
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
Description
2C0CH-2C0FH
11277-11280
901
2
VAR hour (Quadrant 2+3), Secondary
2C10H-2C13H
11281-11284
901
3
Watt hour (Quadrant 1+4) , Secondary
2C14H-2C17H
11285-11288
901
4
Watt hour (Quadrant 2+3), Secondary
2C18H-2C1BH
11289-11292
901
5
VA hour (Quadrant 1), Secondary
2C1CH-2C1FH
11293-11296
901
6
VAR hour (Quadrant 1), Secondary
2C20H-2C23H
11297-11300
901
7
VA hour (Quadrant 4), Secondary
2C2CH-2C27H
11301-11304
901
8
VAR hour (Quadrant 4), Secondary
2C28H-2C2BH
11305-11308
901
9
VA hour (Quadrant 2), Secondary
2C2CH-2C2FH
11309-11312
901
10
VAR hour (Quadrant 2), Secondary
2C30H-2C33H
11313-11316
901
11
VA hour (Quadrant 3), Secondary
2C34H-2C37H
11317-11320
901
12
VAR hour (Quadrant 3), Secondary
2C38H-2C3BH
11321-11324
901
13
2
+9,999,999,999,999,999 I t / 0
2
+9,999,999,999,999,999 I t / 0
11325-11328
901
14
I t Phase B, Secondary
11329-11332
901
15
I t Phase C, Secondary
901
16
+9,999,999,999,999,999 I t / 0
2
2C40H-2C43H
11333-11336
2
I t Phase A, Secondary
2C3CH-2C3FH
2C44H-2C47H
Range
0 VARh / 9,999,999,999,999,999 VARh
+9,999,999,999,999,999 Wh / 0
Wh
0 Wh / -9,999,999,999,999,999
Wh
+9,999,999,999,999,999 VAh /
0 VAh
+9,999,999,999,999,999 VARh
/ 0 VARh
+9,999,999,999,999,999 VAh /
0 VAh
+9,999,999,999,999,999 VARh
/ 0 VARh
+9,999,999,999,999,999 VAh /
0 VAh
+9,999,999,999,999,999 VARh
/ 0 VARh
+9,999,999,999,999,999 VAh /
0 VAh
+9,999,999,999,999,999 VARh
/ 0 VARh
2
V t Phase A, Secondary
Units
Type
R/W
1 VARH
F12
R
1 WH
F12
R
1 WH
F12
R
1 VAH
F12
R
1 VARH
F12
R
1 VAH
F12
R
1 VARH
F12
R
1 VAH
F12
R
1 VARH
F12
R
1 VAH
F12
R
1 VARH
F12
R
2
F12
R
2
2
1It
2
1It
F12
R
2
1It
F12
R
2
2
F12
R
2
2
R
+9,999,999,999,999,999 V t / 0 1 V t
2
2C48H-2C4BH
11337-11340
901
17
V t Phase B, Secondary
+9,999,999,999,999,999 V t / 0 1 V t
F12
2C4CH-2C4FH
11341-11344
901
18
2
V t Phase C, Secondary
1 V 2t
F12
R
2C50H-2C53H
11345-11348
901
19
Watt hour (Quadrant 1), Secondary
1 WH
F12
R
2C54H-2C57H
11349-11352
901
20
Watt hour (Quadrant 4), Secondary
1 WH
F12
R
2C58H-2C5BH
11353-11356
901
21
Watt hour (Quadrant 2), Secondary
1 WH
F12
R
2C5CH-2C5FH
11357-11360
901
22
Watt hour (Quadrant 3), Secondary
+9,999,999,999,999,999 V2t / 0
+9,999,999,999,999,999 WH / 0
WH
+9,999,999,999,999,999 WH / 0
WH
+9,999,999,999,999,999 WH / 0
WH
+9,999,999,999,999,999 WH / 0
WH
R
11361-11364
11365-11368
11369-11372
11373-11376
11377-11380
11381-11384
901
901
901
901
901
901
23
24
25
26
27
28
VA hour (Quadrant 1+2+3+4), Uncompensated, Secondary
VAR hour (Quadrant 1+2), Uncompensated, Secondary
VAR hour (Quadrant 3+4), Uncompensated , Secondary
Watt hour (Quadrant 1+4), Uncompensated, Secondary
Watt hour (Quadrant 2+3), Uncompensated , Secondary
Q hour, positive, Secondary
1 WH
1
1
1
1
1
1 Qh
F12
2C60H-2C63H
2C64H-2C67H
2C68H-2C6BH
2C6CH-2C6FH
2C70H-2C73H
2C74H-2C77H
F12
F12
F12
F12
F12
F12
2C78H-2C7BH
11385-11388
901
29
Q hour, negative, Secondary
1 Qh
F12
2C7CH-2CF3H
11389-11566
9,999,999,999,999,999 / 0
9,999,999,999,999,999 / 0
9,999,999,999,999,999 / 0
9,999,999,999,999,999 / 0
9,999,999,999,999,999 / 0
Qh
9,999,999,999,999,999 Qh / 0
Qh
Reserved Block
Reserved
Notes
R
Frozen Energy - Internal Input Pulse Accumulation Readings
2CF4H-2CF7H
11509-11512
903
0
Pulse Accumulation Internal Input 1
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
2CF8H-2CFBH
11513-11516
903
1
Pulse Accumulation Internal Input 2
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
2CFCH-2CFFH
11517-11520
903
2
Pulse Accumulation Internal Input 3
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
2D00H-2D03H
11521-11524
903
3
Pulse Accumulation Internal Input 4
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-52
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
2D04H-2D07H
11525-11528
903
4
DNP
Obj
Description
Pulse Accumulation Internal Input 5
Range
Units
Type
R/W
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
2D08H-2D0BH
11529-11532
903
5
Pulse Accumulation Internal Input 6
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
2D0CH-2D0FH
11533-11536
903
6
Pulse Accumulation Internal Input 7
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
2D10H-2D13H
11537-11540
903
7
Pulse Accumulation Internal Input 8
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
2D14H-2D17H
11541-11544
903
8
Pulse Accumulation Aggregation 1
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
2D18H-2D1BH
11545-11548
903
9
Pulse Accumulation Aggregation 2
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
2D1CH-2D1FH
11549-11552
903
10
Pulse Accumulation Aggregation 3
+/- 9,223,372,036,854,776,808
1 Unit
F62
R
2D20H-2D23H
11553-11556
903
11
Pulse Accumulation Aggregation 4
1 Unit
F62
R
2D24H-2D25H
2D26H-2D27H
2D28H-2D29H
2D2AH-2D2BH
2D2CH-2D2DH
11557-11558
11559-11560
11561-11562
11563-11564
11565-11566
904
904
904
904
904
0
1
2
3
4
F18
F18
F18
F18
F18
R
R
R
R
R
2D2EH-2D2FH
11567-11568
905
0
2D30H-2D31H
11569-11570
905
1
2D32H-2D33H
11571-11572
905
2
+/- 9,223,372,036,854,776,808
Frozen Energy - KYZ Output Accumulation Readings
KYZ Output Accumulation, Relay 1 - Pulse 1
4,294,967,295 / 0
KYZ Output Accumulation, Relay 2 - Pulse 2
4,294,967,295 / 0
KYZ Output Accumulation, Relay 3
4,294,967,295 / 0
KYZ Output Accumulation, Relay 4
4,294,967,295 / 0
Reserved
4,294,967,295 / 0
Frozen Energy - Scaled Energy Readings
variable (9999 through
VA hour (Quadrant 1+2+3+4), Scaled Primary
999999999 / 0)
variable (9999 through
VAR hour (Quadrant 1+2), Scaled Primary
999999999 / 0)
variable (9999 through
VAR hour (Quadrant 2+3), Scaled Primary
999999999 / 0)
variable (9999 through
Watt hour (Quadrant 1+4) , Scaled Primary
999999999 / 0)
variable (9999 through
VA hour (Quadrant 1), Scaled Primary
999999999 / 0)
variable (9999 through
VAR hour (Quadrant 1), Scaled Primary
999999999 / 0)
variable (9999 through
VA hour (Quadrant 4), Scaled Primary
999999999 / 0)
VAR hour (Quadrant 4), Scaled Primary
999999999 / 0)
variable (9999 through
Watt hour (Quadrant 2+3), Scaled Primary
999999999 / 0)
variable (9999 through
VA hour (Quadrant 2), Scaled Primary
999999999 / 0)
variable (9999 through
VAR hour (Quadrant 2), Scaled Primary
999999999 / 0)
VA hour (Quadrant 3), Scaled Primary
999999999 / 0)
variable (9999 through
VAR hour (Quadrant 3), Scaled Primary
999999999 / 0)
variable (9999 through
I2t Phase A, Scaled Primary
999999999 / 0)
variable (9999 through
I2t Phase B, Scaled Primary
999999999 / 0)
variable (9999 through
I2t Phase C, Scaled Primary
999999999 / 0)
variable (9999 through
V2t Phase A, Scaled Primary
999999999 / 0)
variable (9999 through
V2t Phase B, Scaled Primary
999999999 / 0)
variable (9999 through
V2t Phase C, Scaled Primary
999999999 / 0)
variable (9999 through
Watt hour (Quadrant 1), Scaled Primary
999999999 / 0)
variable (9999 through
Watt hour (Quadrant 4), Scaled Primary
999999999 / 0)
2D34H-2D35H
11573-11574
905
3
2D36H-2D37H
11575-11576
905
4
2D38H-2D39H
11577-11578
905
5
2D3AH-2D3BH
2D3CH-2D3DH
11579-11580
11581-11582
905
905
6
7
2D3EH-2D3FH
11583-11584
905
8
2D40H-2D41H
11585-11586
905
9
2D42H-2D43H
2D44H-2D45H
11587-11588
11589-11590
905
905
10
11
2D46H-2D47H
11591-11592
905
12
2D48H-2D49H
11593-11594
905
13
2D4AH-2D4BH
11595-11596
905
14
2D4CH-2D4DH
11597-11598
905
15
2D4EH-2D4FH
11599-11600
905
16
2D50H-2D51H
11601-11602
905
17
2D52H-2D53H
11603-11604
905
18
2D54H-2D55H
11605-11606
905
19
2D56H-2D57H
11607-11608
905
20
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
6
-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
variable 106 - 10-7
F64
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
variable 10 - 10
variable 106 - 10-7
F64
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
6
-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
variable 10 - 10
-7
Notes
F64
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-53
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
2D58H-2D59H
11609-11610
905
21
2D5AH-2D5BH
11611-11612
905
22
2D5CH-2D5DH
11613-11614
905
23
2D5EH-2D5FH
11615-11616
905
24
2D60H-2D61H
11617-11618
905
25
2D62H-2D63H
11619-11620
905
26
2D64H-2D65H
11621-11622
905
27
2D66H-2D67H
11623-11624
905
28
2D68H-2D69H
11625-11626
905
29
2D6AH-2D6BH
11627-11628
906
0
2D6CH-2D6DH
11629-11630
906
1
2D6EH-2D6FH
11631-11632
906
2
2D70H-2D71H
11633-11634
906
3
2D72H-2D73H
11635-11636
906
4
2D74H-2D75H
11637-11638
906
5
2D76H-2D77H
11639-11640
906
6
2D78H-2D79H
11641-11642
906
7
2D7AH-2D7BH
11643-11644
906
8
2D7CH-2D7DH
11645-11646
906
9
2D7EH-2D7FH
11647-11648
906
10
DNP
Obj
2D80H-2D81H
11649-11650
906
11
2D82H-2D83H
2D84H-2D85H
2D86H-2D87H
2D88H-2D89H
2D8AH-2D8BH
2D8CH-2D8DH
2D8EH-2D8FH
2D90H-2D91H
2D92H-2D93H
2D94H-2D95H
11651-11652
11653-11654
11655-11656
11657-11658
11659-11660
11661-11662
11663-11664
11665-11666
11667-11668
11669-11670
907
907
907
907
907
908
908
908
908
908
0
1
2
3
4
0
1
2
3
4
30
30
30
30
30
30
30
30
30
30
2D96H-2D97H
11671-11672
909
0
30
2D98H-2D99H
11673-11674
909
1
30
2D9AH-2D9BH
11675-11676
909
2
30
2D9CH-2D9DH
11677-11678
909
3
30
Description
Range
variable (9999 through
Watt hour (Quadrant 2), Scaled Primary
999999999 / 0)
variable (9999 through
Watt hour (Quadrant 3), Scaled Primary
999999999 / 0)
variable (9999 through
VA hour (Quadrant 1+2+3+4), Uncompensated, Scaled Primary
999999999 / 0)
variable (9999 through
VAR hour (Quadrant 1+2), Uncompensated, Scaled Primary
999999999 / 0)
variable (9999 through
VAR hour (Quadrant 3+4), Uncompensated , Scaled Primary
999999999 / 0)
variable (9999 through
Watt hour (Quadrant 1+4), Uncompensated, Scaled Primary
999999999 / 0)
variable (9999 through
Watt hour (Quadrant 2+3), Uncompensated , Scaled Primary
999999999 / 0)
variable (9999 through
Q hour, positive, Scaled Primary
999999999 / 0)
variable (9999 through
Q hour, negative, Scaled Scaled Primary
999999999 / 0)
Frozen Energy - Scaled Internal Input Pulse Accumulation Readings
variable (9999 through
Pulse Accumulation Inputs 1, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 2, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 3, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 4, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 5, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 6, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 7, Scaled
999999999 / 0)
variable (9999 through
Pulse Accumulation Inputs 8, Scaled
999999999 / 0)
variable (9999 through
Pulse Aggregations 1, Scaled
999999999 / 0)
variable (9999 through
Pulse Aggregations 2, Scaled
999999999 / 0)
variable (9999 through
Pulse Aggregations 3, Scaled
999999999 / 0)
variable (9999 through
Pulse Aggregations 4, Scaled
999999999 / 0)
Previous Block Window Average Block
Previous Maximum Block Window Average VA
+32767 VA / 0 VA
Previous Maximum Block Window Average Positive VAR
+32767 VAR / 0 VAR
Previous Maximum Block Window Average Negative VAR
0 VAR / -32768 VAR
Previous Maximum Block Window Average Positive Watt
+32767 W /0 W
Previous Maximum Block Window Average Negative Watt
0 W / -32768 W
Previous Minimum Block Window Average VA
+32767 VA / 0 VA
Previous Minimum Block Window Average Positive VAR
+32767 VAR / 0 VAR
Previous Minimum Block Window Average Negative VAR
0 VAR / -32768 VAR
Previous Minimum Block Window Average Positive Watt
+32767 W /0 W
Previous Minimum Block Window Average Negative Watt
0 W / -32768 W
Coin. Block Window Average VAR for Previous Maximum Positive
Watt
+32767 VAR / -32768 VAR
Coin. Block Window Average VAR for Previous Maximum
Negative Watt
+32767 VAR / -32768 VAR
Coin. Block Window Average VAR for Previous Minimum Positive
Watt
+32767 VAR / -32768 VAR
Coin. Block Window Average VAR for Previous Minimum
Negative Watt
+32767 VAR / -32768 VAR
Units
Type
variable 106 - 10-7
F64
variable 106 - 10-7
F64
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
6
-7
variable 10 - 10
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
variable 10 - 10
-7
R/W
Notes
F64
1/ 65536 VA sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 VA sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 W sec
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
R
R
R
R
R
R
R
R
R
R
9
9
9
9
9
9
9
9
9
9
1/ 65536 VAR sec
F7
R
9
1/ 65536 VAR sec
F7
R
9
1/ 65536 VAR sec
F7
R
9
1/ 65536 VAR sec
F7
R
9
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-54
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
2D9EH-2DA1H
11679-11682
910
0
50
2DA2H-2DA5H
11683-11686
910
1
50
2DA6H-2DA9H
11687-11690
910
2
50
2DAAH-2DADH
11691-11694
910
3
50
2DAEH-2DB1H
2DB2H-2DB5H
11695-11698
11699-11702
910
911
4
0
50
50
2DB6H-2DB9H
11703-11706
911
1
50
2DBAH-2DBDH
11707-11710
911
2
50
2DBEH-2DC1H
11711-11714
911
3
50
2DC2H-2DC5H
2DC6H-2DC7H
2DC8H-2DC9H
2DCAH-2DCBH
2DCCH-2DCDH
2DCEH-2DD1H
2DD2H-2DD5H
2DD6H-2DD9H
2DDAH-2DDDH
11715-11718
11719-11720
11721-11722
11723-11724
11725-11726
11727-11730
11731-11734
11735-11738
11739-11742
911
912
912
913
913
914
914
915
915
4
0
1
0
1
0
1
0
1
50
30
30
30
30
50
50
50
50
2DDEH-2DDFH
2DE0H-2DE1H
2DE2H-2DE3H
2DE4H-2DE5H
2DE6H-2DE7H
2DE8H-2DE9H
2DEAH-2DEBH
2DECH-2DEDH
2DEEH-2DEFH
2DF0H-2DF1H
11743-11744
11745-11746
11747-11748
11749-11750
11751-11752
11753-11754
11755-11756
11757-11758
11759-11760
11761-11762
916
916
916
916
916
917
917
917
917
917
0
1
2
3
4
0
1
2
3
4
30
30
30
30
30
30
30
30
30
30
2DF2H-2DF3H
11763-11764
918
0
30
2DF4H-2DF5H
11765-11766
918
1
30
2DF6H-2DF7H
11767-11768
918
2
30
2DF8H-2DF9H
2DFAH-2DFDH
11769-11770
11771-11774
918
919
3
0
30
2DFEH-2E01H
2E02H-2E05H
11775-11778
11779-11782
919
919
1
2
2E06H-2E09H
11783-11786
919
3
2E0AH-2E0DH
2E0EH-2E11H
11787-11790
11791-11794
919
920
4
0
2E12H-2E15H
11795-11798
920
1
2E16H-2E19H
11799-11802
920
2
2E1AH-2E1DH
11803-11806
920
3
2E1EH-2E21H
11807-11810
920
4
Description
Range
Previous Maximum Block Window Average VA Time Stamp
12/31/9999 23:59:59.99
Previous Maximum Block Window Average Positive VAR Time
Stamp
12/31/9999 23:59:59.99
Previous Maximum Block Window Average Negative VAR Time
Stamp
12/31/9999 23:59:59.99
Previous Maximum Block Window Average Positive Watt Time
Stamp
12/31/9999 23:59:59.99
Previous Maximum Block Window Average Negative Watt Time
Stamp
12/31/9999 23:59:59.99
Previous Minimum Block Window Average VA Time Stamp
12/31/9999 23:59:59.99
Previous Minimum Block Window Average Positive VAR Time
Stamp
12/31/9999 23:59:59.99
Previous Minimum Block Window Average Negative VAR Time
Stamp
12/31/9999 23:59:59.99
Previous Minimum Block Window Average Positive Watt Time
Stamp
12/31/9999 23:59:59.99
Previous Minimum Block Window Average Negative Watt Time
Stamp
12/31/9999 23:59:59.99
Previous Maximum Block Window Average + Q
+32767 Q / -32768 Q
Previous Maximum Block Window Average - Q
+32767 Q / -32768 Q
Previous Minimum Block Window Average + Q
+32767 Q / -32768 Q
Previous Minimum Block Window Average - Q
+32767 Q / -32768 Q
Previous Maximum Block Window + Q Time Stamps
12/31/9999 23:59:59.99
Previous Maximum Block Window - Q Time Stamps
12/31/9999 23:59:59.99
Previous Minimum Block Window + Q Time Stamps
12/31/9999 23:59:59.99
Previous Minimum Block Window - Q Time Stamps
12/31/9999 23:59:59.99
Previous Rolling Window Block
Previous Maximum Rolling Window Average VA
+32767 VA / 0 VA
Previous Maximum Rolling Window Average Positive VAR
+32767 VAR / 0 VAR
Previous Maximum Rolling Window Average Negative VAR
0 VAR / -32768 VAR
Previous Maximum Rolling Window Average Positive Watt
+32767 W /0 W
Previous Maximum Rolling Window Average Negative Watt
0 W / -32768 W
Previous Minimum Rolling Window Average VA
+32767 VA / 0 VA
Previous Minimum Rolling Window Average Positive VAR
+32767 VAR / 0 VAR
Previous Minimum Rolling Window Average Negative VAR
0 VAR / -32768 VAR
Previous Minimum Rolling Window Average Positive Watt
+32767 W /0 W
Previous Minimum Rolling Window Average Negative Watt
0 W / -32768 W
Coin. Rolling Window Average VAR for Previous Maximum
Positive Watt
+32767 VAR / -32768 VAR
Coin. Rolling Window Average VAR for Previous Maximum
Negative Watt
+32767 VAR / -32768 VAR
Coin. Rolling Window Average VAR for Previous Minimum
Positive Watt
+32767 VAR / -32768 VAR
Coin. Rolling Window Average VAR for Previous Minimum
Negative Watt
+32767 VAR / -32768 VAR
Previous Maximum Rolling Window Average VA Time Stamp
12/31/9999 23:59:59.99
Previous Maximum Rolling Window Average Positive VAR Time
Stamp
12/31/9999 23:59:59.99
Stamp
12/31/9999 23:59:59.99
Previous Maximum Rolling Window Average Positive Watt Time
Stamp
12/31/9999 23:59:59.99
Previous Maximum Rolling Window Average Negative Watt Time
Stamp
12/31/9999 23:59:59.99
Previous Minimum Rolling Window Average VA Time Stamp
12/31/9999 23:59:59.99
Previous Minimum Rolling Window Average Positive VAR Time
Stamp
12/31/9999 23:59:59.99
Previous Minimum Rolling Window Average Negative VAR Time
Stamp
12/31/9999 23:59:59.99
Previous Minimum Rolling Window Average Positive Watt Time
Stamp
12/31/9999 23:59:59.99
Previous Minimum Rolling Window Average Negative Watt Time
Stamp
12/31/9999 23:59:59.99
Units
Type
R/W
Notes
10 msec
F3
R
1
10 msec
F3
R
1
10 msec
F3
R
1
10 msec
F3
R
1
10 msec
10 msec
F3
F3
R
R
1
1
10 msec
F3
R
1
10 msec
F3
R
1
10 msec
F3
R
1
10 msec
1/65536 Q sec
1/65536 Q sec
1/65536 Q sec
1/65536 Q sec
F3
F7
F7
F7
F7
F3
F3
F3
F3
R
1
1/ 65536 VA sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 VA sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 W sec
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
R
R
R
R
R
R
R
R
R
R
9
9
9
9
9
9
9
9
9
9
1/ 65536 VAR sec
F7
R
9
1/ 65536 VAR sec
F7
R
9
1/ 65536 VAR sec
F7
R
9
1/ 65536 VAR sec
10 msec
F7
F3
R
R
9
1
10 msec
10 msec
F3
F3
R
R
1
1
10 msec
F3
R
1
10 msec
10 msec
F3
F3
R
R
1
1
10 msec
F3
R
1
10 msec
F3
R
1
10 msec
F3
R
1
10 msec
F3
R
1
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-55
2: Modbus Map - Holding Registers
DNP
Obj
Addr. (hex)
Address(4X)
Line
Pt
Range
Units
Type
2E22H-2E25H
2E26H-2E29H
11811-11814
11815-11818
921
922
0-1
0-1
Previous Maximum Rolling Window Average +/- Q
Previous Minimum Rolling Window Average +/- Q
+32767 Q / -32768 Q
+32767 Q / -32768 Q
1/65536 Q sec
1/65536 Q sec
F7
F7
2E2AH-2E31H
11819-11826
923
0-1
Previous Maximum Rolling Window Average +/- Q Time Stamps
12/31/9999 23:59:59.99
F3
2E32H-2E39H
11827-11834
924
0-1
F3
2E3AH-2E3BH
11835-11836
925
0
20
2E3CH-2E3DH
11837-11838
925
1
20
2E3EH-2E3FH
2E40H-2E41H
2E42H-2E43H
11839-11840
11841-11842
11843-11844
925
926
926
2
0
1
20
20
20
2E44H-2E45H
11845-11846
926
2
20
2E46H-2E47H
11847-11848
926
3
20
Previous Minimum Rolling Window Average +/- Q Time Stamps
12/31/9999 23:59:59.99
Previous Scaled Energy Block
variable (9999 through
Previous Total VAh (Quadrant 1+2+3+4) Scaled Primary
999999999 / 0)
variable (9999 through
Previous Positive VARh (Quadrant 1+2) Scaled Priamry
999999999 / 0)
variable (9999 through
Prevoius Negative VARh (Quadrant 3+4) Scaled Primary
999999999 / 0)
Previous Positive Wh (Quadrant 1+4) Scaled Primary
999999999 / 0)
Previous Quadrant 1 VAh Scaled Primary
999999999 / 0)
variable (9999 through
Previous Quadrant 1 VARh Scaled Primary
999999999 / 0)
variable (9999 through
Previous Quadrant 4 VAh Scaled Primary
999999999 / 0)
variable (9999 through
Previous Quadrant 4 VARh Scaled Primary
999999999 / 0)
variable (9999 through
Previous Negative Wh (Quadrant 2+3) Scaled Primary
999999999 / 0)
variable (9999 through
Previous Quadrant 2 VAh Scaled Primary
999999999 / 0)
variable (9999 through
Previous Quadrant 2 VARh Scaled Primary
999999999 / 0)
variable (9999 through
Previous Quadrant 3 VAh Scaled Primary
999999999 / 0)
variable (9999 through
Previous Quadrant 3 VARh Scaled Primary
999999999 / 0)
variable (9999 through
Prevoius I2t Phase A Scaled Priamry
999999999 / 0)
variable (9999 through
Previous I2t Phase B Scaled Primary
999999999 / 0)
variable (9999 through
Previous I2t Phase C Scaled Primary
999999999 / 0)
variable (9999 through
Previous V2t Phase A Scaled Primary
999999999 / 0)
variable (9999 through
Previous V2t Phase B Scaled Primary
999999999 / 0)
variable (9999 through
Previous V2t Phase C Scaled Primary
999999999 / 0)
variable (9999 through
Previous Quadrant 1 Wh Scaled Primary
999999999 / 0)
variable (9999 through
Previous Quadrant 4 Wh Scaled Primary
999999999 / 0)
variable (9999 through
Previous Quadrant 2 Wh Scaled Primary
999999999 / 0)
variable (9999 through
Prevoius Quadrant 3 Wh Scaled Primary
999999999 / 0)
variable (9999 through
Prevoius Uncompensated Total VAh, Scaled Primary
999999999 / 0)
variable (9999 through
Previous Uncompensated + VARh Scaled Primary
999999999 / 0)
variable (9999 through
Previous Uncompensated - VARh Scaled Primary
999999999 / 0)
variable (9999 through
Previous Uncompensated + Wh Scaled Primary
999999999 / 0)
variable (9999 through
Previous Uncompensated - Wh Scaled Primary
999999999 / 0)
variable (9999 through
Previous + Qh Scaled Primary
999999999 / 0)
2E48H-2E49H
11849-11850
926
4
20
2E4AH-2E4BH
11851-11852
926
5
20
2E4CH-2E4DH
11853-11854
926
6
20
2E4EH-2E4FH
11855-11856
926
7
20
2E50H-2E51H
11857-11858
926
8
20
2E52H-2E53H
11859-11860
926
9
20
2E54H-2E55H
11861-11862
927
0
20
2E56H-2E57H
11863-11864
927
1
20
2E58H-2E59H
11865-11866
927
2
20
2E5AH-2E5BH
11867-11868
927
3
20
2E5CH-2E5DH
11869-11870
927
4
20
2E5EH-2E5FH
11871-11872
927
5
20
2E60H-2E61H
11873-11874
928
0
20
2E62H-2E63H
11875-11876
928
1
20
2E64H-2E65H
11877-11878
928
2
20
2E66H-2E67H
11879-11880
928
3
20
2E68H-2E69H
11881-11882
929
0
20
2E6AH-2E6BH
11883-11884
929
1
20
2E6CH-2E6DH
11885-11886
929
2
2E6EH-2E6FH
11887-11888
929
3
2E70H-2E71H
11889-11890
929
4
2E72H-2E73H
11891-11892
930
0
20
20
Description
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
variable 106 - 10-7
variable 106 - 10-7
F64
F64
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
6
-7
F64
variable 106 - 10-7
F64
variable 106 - 10-7
F64
variable 10 - 10
R/W
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-56
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
2E74H-2E75H
11893-11894
930
1
2E76H-2E77H
2E78H-2E79H
2E7AH-2E7BH
11895-11896
11897-11898
11899-11900
931
932
933
0
0
0
30
30
30
2E7CH-2E7FH
2E80H-2E83H
2E84H-2E87H
11901-11904
11905-11908
11909-11912
934
934
934
0
1
2
50
50
50
2E88H-2E8BH
11913-11916
934
3
50
2E8CH-2E8FH
11917-11920
934
4
50
2E90H-2E93H
2E94H-2E97H
2E98H-2E9BH
2E9CH-2E9FH
2EA0H-2EA3H
11921-11924
11925-11928
11929-11932
11933-11936
11937-11940
934
934
934
934
934
5
6
7
8
9
50
50
50
50
50
2EA4H-2EA7H
11941-11944
934
10
50
2EA8H-2EABH
11945-11948
934
11
50
2EACH-2EAFH
2EB0H-2EB3H
2EB4H-2EB7H
2EB8H-2EBBH
2EBCH-2EBFH
11949-11952
11953-11956
11957-11960
11961-11964
11965-11968
934
934
934
934
934
12
13
14
15
16
50
50
50
50
50
2EC0H-2EC3H
11969-11972
934
17
50
2EC4H-2EC7H
11973-11976
934
18
50
2EC8H-2ECBH
2ECCH-2ECFH
2ED0H-2ED3H
2ED4H-2ED7H
2ED8H-2EDBH
11977-11980
11981-11984
11985-11988
11989-11992
11993-11996
934
934
934
934
934
19
20
21
22
23
50
50
50
50
50
2EDCH-2EDFH
11997-12000
934
24
50
2EE0H-2EE3H
12001-12004
934
25
50
2EE4H-2EE7H
2EE8H-2EEBH
2EECH-2EEFH
2EF0H-2EF3H
2EF4H-2EF7H
2EF8H-2EFBH
2EFCH
2EFDH
2EFEH
2EFFH
2F00H
2F01H
2F02H-2F03H
2F04H-2F05H
2F06H-2F07H
12005-12008
12009-12012
12013-12016
12017-12020
12021-12024
12025-12028
12029
12030
12031
12032
12033
12034
12035-12036
12037-12038
12039-12040
934
934
934
934
934
934
935
935
935
936
936
936
937
938
939
26
27
28
29
30
31
0
1
2
0
1
2
0
0
0
50
50
50
50
50
50
30
30
30
30
30
30
30
30
30
Description
Range
variable (9999 through
Previous - Qh Scaled Primary
999999999 / 0)
One Second Three Phase Mean RMS Block
One Second Three Phase Mean RMS Vpn
+ 32767 V / 0 V
One Second Three Phase Mean RMS Amp
+ 32767 A / 0 A
One Second Three Phase Mean RMS Vpp
+ 32767 V / 0 V
Block Window Max/Min and 10 Minute Mean THD Block
Block Window Max/Min and 10 Minute Mean THD Block
Timestamp
12/31/9999 23:59:59.99
Block Window Max./Min Interval 1 Timestamp
12/31/9999 23:59:59.99
Block Window Max/Min Interval 2 Timestamp
12/31/9999 23:59:59.99
Block Window Max Interval 1 Three Phase Mean RMS Vpn
Timestamp
12/31/9999 23:59:59.99
Block Window Max Interval 1 Three Phase Mean RMS Amp
Timestamp
12/31/9999 23:59:59.99
Block Window Max Interval 1 Three Phase Mean RMS Vpp
Timestamp
12/31/9999 23:59:59.99
Block Window Max Interval 1 VAR Q1+2 Timestamp
12/31/9999 23:59:59.99
Block Window Max Interval 1 VAR Q3+4 Timestamp
12/31/9999 23:59:59.99
Block Window Max Interval 1 W Q1+4 Timestamp
12/31/9999 23:59:59.99
Block Window Max Interval 1 W Q2+3 Timestamp
12/31/9999 23:59:59.99
Block Window Max Interval 2 Three Phase Mean RMS Vpn
Timestamp
12/31/9999 23:59:59.99
Block Window Max Interval 2 Three Phase Mean RMS Amp
Timestamp
12/31/9999 23:59:59.99
Block Window Max Interval 2 Three Phase Mean RMS Vpp
Timestamp
12/31/9999 23:59:59.99
Block Window Max Interval 2 VAR Q1+2 Timestamp
12/31/9999 23:59:59.99
Block Window Max Interval 2 VAR Q3+4 Timestamp
12/31/9999 23:59:59.99
Block Window Max Interval 2 W Q1+4 Timestamp
12/31/9999 23:59:59.99
Block Window Max Interval 2 W Q2+3 Timestamp
12/31/9999 23:59:59.99
Block Window Min Interval 1 Three Phase Mean RMS Vpn
Timestamp
12/31/9999 23:59:59.99
Block Window Min Interval 1 Three Phase Mean RMS Amp
Timestamp
12/31/9999 23:59:59.99
Block Window Min Interval 1 Three Phase Mean RMS Vpp
Timestamp
12/31/9999 23:59:59.99
Block Window Min Interval 1 VAR Q1+2 Timestamp
12/31/9999 23:59:59.99
Block Window Min Interval 1 VAR Q3+4 Timestamp
12/31/9999 23:59:59.99
Block Window Min Interval 1 W Q1+4 Timestamp
12/31/9999 23:59:59.99
Block Window Min Interval 1 W Q2+3 Timestamp
12/31/9999 23:59:59.99
Block Window Min Interval 2 Three Phase Mean RMS Vpn
Timestamp
12/31/9999 23:59:59.99
Block Window Min Interval 2 Three Phase Mean RMS Amp
Timestamp
12/31/9999 23:59:59.99
Block Window Min Interval 2 Three Phase Mean RMS Vpp
Timestamp
12/31/9999 23:59:59.99
Block Window Min Interval 2 VAR Q1+2 Timestamp
12/31/9999 23:59:59.99
Block Window Min Interval 2 VAR Q3+4 Timestamp
12/31/9999 23:59:59.99
Block Window Min Interval 2 W Q1+4 Timestamp
12/31/9999 23:59:59.99
Block Window Min Interval 2 W Q2+3 Timestamp
12/31/9999 23:59:59.99
10 Minute Mean THD Timestamp
12/31/9999 23:59:59.99
10 Minute Mean THD Van/Vab
+327.67% / -327.68%
10 Minute Mean THD Vbn/Vbc
+327.67% / -327.68%
10 Minute Mean THD Vcn/Vca
+327.67% / -327.68%
10 Minute Mean THD Ia
+327.67% / -327.68%
10 Minute Mean THD Ib
+327.67% / -327.68%
10 Minute Mean THD Ic
+327.67% / -327.68%
Block Window Max Interval 1 Mean Vpn
+ 32767 V / 0 V
Block Window Max Interval 1 Mean Amp
+ 32767 A / 0 A
Block Window Max Interval 1 Mean Vpp
+ 32767 V / 0 V
Units
Type
variable 106 - 10-7
F64
1/ 65536 V sec
1/ 65536 A sec
1/ 65536 V sec
F7
F7
F7
R/W
Notes
R
R
R
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
F3
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
1/ 65536 V sec
1/ 65536 A sec
1/ 65536 V sec
F3
F3
F3
F3
F3
F3
F10
F10
F10
F10
F10
F10
F7
F7
F7
R
R
R
R
R
R
R
R
R
5
6
5
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-57
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
2F08H-2F09H
2F0AH-2F0BH
2F0CH-2F0DH
2F0EH-2F0FH
2F10H-2F11H
2F12H-2F13H
2F14H-2F15H
2F16H-2F17H
2F18H-2F19H
2F1AH-2F1BH
2F1CH-2F1DH
2F1EH-2F1FH
2F20H-2F21H
2F22H-2F23H
2F24H-2F25H
2F26H-2F27H
2F28H-2F29H
2F2AH-2F2BH
2F2CH-2F2DH
2F2EH-2F2FH
2F30H-2F31H
2F32H-2F33H
2F34H-2F35H
2F36H-2F37H
2F38H-2F39H
2F3AH-2F3DH
2F3EH-2F41H
2F42H-2F45H
2F46H-2F49H
2F4AH-2F4DH
2F4EH-2F51H
2F52H-2F55H
2F56H-2F59H
2F5AH-2F5BH
2F5CH-2F5DH
2F5EH-2F5FH
2F60H-2F61H
2F62H-2F63H
2F64H-2F65H
2F66H-2F67H
2F68H-2F69H
12041-12042
12043-12044
12045-12046
12047-12048
12049-12050
12051-12052
12053-12054
12055-12056
12057-12058
12059-12060
12061-12062
12063-12064
12065-12066
12067-12068
12069-12070
12071-12072
12073-12074
12075-12076
12077-12078
12079-12080
12081-12082
12083-12084
12085-12086
12087-12088
12089-12090
12091-12094
12095-12098
12099-12102
12103-12106
12107-12110
12111-12114
12115-12118
12119-12122
12123-12124
12125-12126
12127-12128
12129-12130
12131-12132
12133-12134
12135-12136
12137-12138
940
940
940
940
941
942
943
944
944
944
944
945
946
947
948
948
948
948
949
950
951
952
952
952
952
953
953
953
953
953
953
953
953
954
954
954
954
954
954
954
954
0
1
2
3
0
0
0
0
1
2
3
0
0
0
0
1
2
3
0
0
0
0
1
2
3
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
50
50
50
50
50
50
50
50
30
30
30
30
30
30
30
30
2F6CH
2F6DH
2F6EH
2F6FH
2F74H
2F75H
2F76H
2F77H
12141
12142
12143
12144
12149
12150
12151
12152
1232
1232
1232
1232
1234
1234
1234
1234
0
1
2
3
0
1
2
3
4000H-4007H
4008H-400BH
400CH-400FH
4010H-4017H
4018H-403FH
4040H-5FFFH
16385-16392
16393-16396
16397-16400
16401-16408
16408-16448
16449-24576
Description
Range
Block Window Max Interval 1 VAR Q1+2
+32767 VAR / 0 VAR
Block Window Max Interval 1 VAR Q3+4
0 VAR / -32768 VAR
Block Window Max Interval 1 W Q1+4
+32767 W /0 W
Block Window Max Interval 1 W Q2+3
0 W / -32768 W
Block Window Max Interval 2 Mean Vpn
+ 32767 V / 0 V
Block Window Max Interval 2 Mean Amp
+ 32767 A / 0 A
Block Window Max Interval 2 Mean Vpp
+ 32767 V / 0 V
Block Window Max Interval 2 VAR Q1+2
+32767 VAR / 0 VAR
Block Window Max Interval 2 VAR Q3+4
0 VAR / -32768 VAR
Block Window Max Interval 2 W Q1+4
+32767 W /0 W
Block Window Max Interval 2 W Q2+3
0 W / -32768 W
Block Window Min Interval 1 Mean Vpn
+ 32767 V / 0 V
Block Window Min Interval 1 Mean Amp
+ 32767 A / 0 A
Block Window Min Interval 1 Mean Vpp
+ 32767 V / 0 V
Block Window Min Interval 1 VAR Q1+2
+32767 VAR / 0 VAR
Block Window Min Interval 1 VAR Q3+4
0 VAR / -32768 VAR
Block Window Min Interval 1 W Q1+4
+32767 W /0 W
Block Window Min Interval 1 W Q2+3
0 W / -32768 W
Block Window Min Interval 2 Mean Vpn
+ 32767 V / 0 V
Block Window Min Interval 2 Mean Amp
+ 32767 A / 0 A
Block Window Min Interval 2 Mean Vpp
+ 32767 V / 0 V
Block Window Min Interval 2 VAR Q1+2
+32767 VAR / 0 VAR
Block Window Min Interval 2 VAR Q3+4
0 VAR / -32768 VAR
Block Window Min Interval 2 W Q1+4
+32767 W /0 W
Block Window Min Interval 2 W Q2+3
0 W / -32768 W
Block Window Max Interval 1 Overall VAR Timestamp
12/31/9999 23:59:59.99
Block Window Max Interval 1 Overall W Timestamp
12/31/9999 23:59:59.99
Block Window Max Interval 2 Overall VAR Timestamp
12/31/9999 23:59:59.99
Block Window Max Interval 2 Overall W Timestamp
12/31/9999 23:59:59.99
Block Window Min Interval 1 Overall VAR Timestamp
12/31/9999 23:59:59.99
Block Window Min Interval 1 Overall W Timestamp
12/31/9999 23:59:59.99
Block Window Min Interval 2 Overall VAR Timestamp
12/31/9999 23:59:59.99
Block Window Min Interval 2 Overall W Timestamp
12/31/9999 23:59:59.99
Block Window Max Interval 1 Overall VAR
+32767 VAR / -32768 VAR
Block Window Max Interval 1 Overall W
+32767 W / -32768 W
Block Window Max Interval 2 Overall VAR
+32767 VAR / -32768 VAR
Block Window Max Interval 2 Overall W
+32767 W / -32768 W
Block Window Min Interval 1 Overall VAR
+32767 VAR / -32768 VAR
Block Window Min Interval 1 Overall W
+32767 W / -32768 W
Block Window Min Interval 2 Overall VAR
+32767 VAR / -32768 VAR
Block Window Min Interval 2 Overall W
+32767 W / -32768 W
Coincident Power Factor
Coincident Block Window Average PF for Maximum +W
3.999 / 0.000
Coincident Block Window Average PF for Maximum -W
3.999 / 0.000
Coincident Block Window Average PF for Minimum +W
3.999 / 0.000
Coincident Block Window Average PF for Minimum -W
3.999 / 0.000
Previous Coinc. Block Window Average PF for Maximum +W
3.999 / 0.000
Previous Coinc. Block Window Average PF for Maximum -W
3.999 / 0.000
Previous Coinc. Block Window Average PF for Minimum +W
3.999 / 0.000
Previous Coinc. Block Window Average PF for Minimum -W
3.999 / 0.000
Enhanced Factory Settings Block
Hardware Options (16 bytes)
Serial Numbers (8 bytes, binary numbers)
Reserved
OEM Model String
Reserved
Undefined
Enhanced Programmable Settings Block 2 (Range: 6000H-7FFFH)
Nexus 15xx Master RTU (Function Code 0x03 Only) Group Labels
Units
Type
R/W
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 V sec
1/ 65536 A sec
1/ 65536 V sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 V sec
1/ 65536 A sec
1/ 65536 V sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 V sec
1/ 65536 A sec
1/ 65536 V sec
1/ 65536 VAR sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 W sec
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
9
9
9
9
5
6
5
9
9
9
9
5
6
5
9
9
9
9
5
6
5
9
9
9
9
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 VAR sec
1/ 65536 W sec
1/ 65536 VAR sec
1/ 65536 W sec
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F3
F3
F3
F3
F3
F3
F3
F3
F7
F7
F7
F7
F7
F7
F7
F7
Notes
R
R
R
R
R
R
R
R
9
9
9
9
9
9
9
9
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
0.001 PF
F8
F8
F8
F8
F8
F8
F8
F8
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-58
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
6000H-61FFH
24577-25088
6200H-63FFH
25089-25600
6400H-64FFH
25601-25856
6500H-65FFH
25857-26112
6600H-67FFH
6800H-689FH
68A0H-68A1H
68A2H-68A3H
68A4H-68A5H
68A6H-68A7H
68A8H-68A9H
68AAH-68ABH
68ACH-68ADH
68AEH-68AFH
68B0H-68B1H
68B2H-68B3H
68B4H-68B5H
68B6H-68B7H
68B8H-68B9H
68BAH-68BBH
68BCH-68BDH
68BEH-68BFH
68C0H-68C1H
68C2H-68C3H
68C4H-68C5H
68C6H-68C7H
68C8H-68C9H
68CAH-68CBH
68CCH-68CDH
68CEH-68CFH
68D0H-68D1H
68D2H-68D3H
68D4H-68D5H
68D6H-68D7H
68D8H-68D9H
68DAH-68DBH
68DCH-68DDH
68DEH-68DFH
68E0H-6FFFH
26111-26624
26625-26784
26785-26786
26787-26788
26789-26790
26791-26792
26793-26794
26795-26796
26797-26798
26799-26800
26801-26802
26803-26804
26805-26806
26807-26808
26809-26810
26811-26812
26813-26814
26815-26816
26817-26818
26819-26820
26821-26822
26823-26824
26825-26826
26827-26828
26829-26830
26831-26832
26833-26834
26835-26836
26837-26838
26839-26840
26841-26842
26843-26844
26845-26846
26847-26848
26849-28672
7000H-707FH
28673-28800
Line
Pt
DNP
Obj
Description
Range
Units
Type
R/W
Notes
Group Label[0]
Group Label[1]
...
Group Label[127]
Item Label[0]
Item Label[1]
...
Item Label[127]
Item Descriptor[0]
Item Descriptor[1]
...
Item Descriptor[127]
Item Limit[0] Setpoint 1
Item Limit[0] Setpoint 2
Item Limit[1] Setpoint 1
Item Limit[1] Setpoint 2
...
Item Limit[31] Setpoint 1
Item Limit[31] Setpoint 2
Undefined
Reserved
1st Digital Input Option board (Slot 3) chn 01 rollover settings
1st Digital Input Option board (Slot 3) chn 02 rollover settings
1st Digital Input Option board (Slot 3) chn 03 rollover settings
1st Digital Input Option board (Slot 3) chn 04 rollover settings
1st Digital Input Option board (Slot 3) chn 05 rollover settings
1st Digital Input Option board (Slot 3) chn 06 rollover settings
1st Digital Input Option board (Slot 3) chn 07 rollover settings
1st Digital Input Option board (Slot 3) chn 08 rollover settings
1st Digital Input Option board (Slot 3) chn 09 rollover settings
1st Digital Input Option board (Slot 3) chn 10 rollover settings
1st Digital Input Option board (Slot 3) chn 11 rollover settings
1st Digital Input Option board (Slot 3) chn 12 rollover settings
1st Digital Input Option board (Slot 3) chn 13 rollover settings
1st Digital Input Option board (Slot 3) chn 14 rollover settings
1st Digital Input Option board (Slot 3) chn 15 rollover settings
1st Digital Input Option board (Slot 3) chn 16 rollover settings
2nd Digital Input Option board (Slot 4) chn 01 rollover settings
2nd Digital Input Option board (Slot 4) chn 02 rollover settings
2nd Digital Input Option board (Slot 4) chn 03 rollover settings
2nd Digital Input Option board (Slot 4) chn 04 rollover settings
2nd Digital Input Option board (Slot 4) chn 05 rollover settings
2nd Digital Input Option board (Slot 4) chn 06 rollover settings
2nd Digital Input Option board (Slot 4) chn 07 rollover settings
2nd Digital Input Option board (Slot 4) chn 08 rollover settings
2nd Digital Input Option board (Slot 4) chn 09 rollover settings
2nd Digital Input Option board (Slot 4) chn 10 rollover settings
2nd Digital Input Option board (Slot 4) chn 11 rollover settings
2nd Digital Input Option board (Slot 4) chn 12 rollover settings
2nd Digital Input Option board (Slot 4) chn 13 rollover settings
2nd Digital Input Option board (Slot 4) chn 14 rollover settings
2nd Digital Input Option board (Slot 4) chn 15 rollover settings
2nd Digital Input Option board (Slot 4) chn 16 rollover settings
Reserved
Nexus 15xx Interval Log Settings Block
Interval Log 3 Item[0]: Line, Pointer
Interval Log 3 Item[1]: Line, Pointer
...
Interval Log 3 Item[63]: Line, Pointer
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-59
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
7080H-70FFH
28801-28928
7100H-717FH
28929-29056
7180H-71FFH
29057-29184
7200H-727FH
29185-29312
7280H-72FFH
29313-29440
7300HH
7301HH
7302HH
7303HH
7304HH
7305HH
7306HH
7307HH
7308HH
7309HH
730AHH
730BHH
730CH-748BH
29441
29442
29443
29444
29445
29446
29447
29448
29449
29450
29451
29452
29453-29836
748CH-750BH
29837-29964
750CH-754BH
29965-30028
754CH
30029
754DH
754EH
754FH
7550H
7551H
30030
30031
30032
30033
30034
7552H
30035
7553H
30036
7554H-756BH
3003730060
756CH-756FH
30061-30064
Line
Pt
DNP
Obj
Description
Range
Units
Type
R/W
Notes
Interval Log 4 Item[0]: Line, Pointer
Interval Log 4 Item[1]: Line, Pointer
...
Interval Log 4 Item[63]: Line, Pointer
Interval Log 5 Item[0]: Line, Pointer
Interval Log 5 Item[1]: Line, Pointer
...
Interval Log 5 Item[63]: Line, Pointer
Interval Log 6 Item[0]: Line, Pointer
Interval Log 6 Item[1]: Line, Pointer
...
Interval Log 6 Item[63]: Line, Pointer
Interval Log 7 Item[0]: Line, Pointer
Interval Log 7 Item[1]: Line, Pointer
...
Interval Log 7 Item[63]: Line, Pointer
Interval Log 8 Item[0]: Line, Pointer
Interval Log 8 Item[1]: Line, Pointer
...
Interval Log 8 Item[63]: Line, Pointer
Interval Log 3 Interval
Interval Log 4 Interval
Interval Log 3 Record Size
Interval Log 4 Record Size
Interval Log 5 Interval
Interval Log 6 Interval
Interval Log 5 Record Size
Interval Log 6 Record Size
Interval Log 7 Interval
Interval Log 8 Interval
Interval Log 7 Record Size
Interval Log 8 Record Size
Reserved
Event Triggered Log Item[0]: Line, Pointer
Event Triggered Log Item[1]: Line, Pointer
...
Event Triggered Log Item[63]: Line, Pointer
Reserved
MSB
Byte[1]: Event Triggered Log Internal Input ID
Byte[0]: Reserved
MSB
Byte[1]: Reserved
Byte[0]: Event Triggered Log Enabled
Event Triggered Log Recording Speed
Event Triggered Log Recoding Duration
Event Triggered Log Record Size
Event Triggered Log Multiple Sequence
MSB first
Byte[1]: undefined
Byte[0]: bit 7 - 2 - reserved
bit 1 - 0 - disable TLC when all current are zero
= 00 = NO
= 01 = YES
= 10 = YES
= 11 = NO
Reserved
Waveform Voltage Envolope Wave Shape Threshold
Reserved
Waveform Current Change of Rate Threshold
Reserved
Waveform Capture Rules
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-60
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
7570H-7571H
30065-30066
7572H-7573H
30067-30068
7574H
30069
7575H
30070
7576H
30071
7577H
30072
7578H
7579H
757AH
30073
30074
30075
757BH
30076
757CH
757DH
757EH
757FH
7580H
7581H
7582H
7583H
7584H
7585H
7586H
7587H
7588H
7589H
758AH
758BH
758CH
758DH-758EH
30077
30078
30079
30080
30081
30082
30083
30084
30085
30086
30087
30088
30089
30090
30091
30092
30093
30094-30095
Line
Pt
DNP
Obj
Description
Range
Units
Type
R/W
Notes
Waveform Capture Window Amount
0 = 1 capture
1 = 2 capture
...
65535 = 65536 capture
>65535 = 1 capture
Reserved
Waveform samples/cycles @60Hz
0 = 16
1 = 32
2 = 64
3 = 128
4 = 256
5 = 512
6 = 1024
>6= 1024
MSB
Byte[1]: Waveform Pre Trigger (>=1 <=179)
Byte[0]: Waveform Post Trigger (>=1 <=179
Waveform Digital Input Triggers (MSB)
Byte[1]: Undefined
Byte[0]: Bit [7] = Input 8
Bit [6] = Input 7
Bit [5] = Input 6
Bit [4] = Input 5
Bit [3] = Input 4
Bit [2] = Input 3
Bit [1] = Input 2
Bit [0 ]= Input 1
Reserved
Voltage A Threshold % of full scale
Voltage B Threshold % of full scale
Voltage C Threshold % of full scale
Mode/Enable(MSB)
Bit[15]-Bit[11]: Reserved
Bit[10]: Transien Enable - Channel Vc
Bit[9]: Transien Enable - Channel Vb
Bit[8]: Transien Enable - Channel Va
Bit[7]-Bit[2]: Reserved
Bit[1]: Transient Mode: 0=PH-N, 1=PH-PH
Bit[0]: Transient Mode: 0=Disabled, 1=Enabled
Waveform Transient
+6553.5% / -6553.5%
+6553.5% / -6553.5%
+6553.5% / -6553.5%
0.1%
0.1%
0.1%
Waveform Transient Settings
Number Maximum of Channel
Channel 1 Number
Channel 2 Number
Channel 3 Number
Channel 4 Number
Channel 5 Number
Channel 6 Number
Channel 7 Number
Channel 8 Number
Channel 9 Number
Channel 10 Number
Channel 11 Number
Channel 12 Number
Channel 13 Number
Channel 14 Number
Channel 15 Number
Channel 16 Number
Power Quality Enable
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-61
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
758FH
30096
7590H-7591H
30097-30098
7592H-7593H
7594H-7595H
7596H-7597H
7598H-7599H
759AH-759BH
759CH-759DH
759EH-759FH
75A0H-75A1H
75A2H-75A3H
75A4H-75A5H
75A6H-75A7H
75A8H-75A9H
75AAH-75ABH
75ACH-75ADH
75AEH-75AFH
75B0H-75B1H
75B2H-75B3H
75B4H-75FFH
30099-30100
30101-30102
30103-30104
30105-30106
30107-30108
30109-30110
30111-30112
30113-30114
30115-30116
30117-30118
30119-30120
30121-30122
30123-30124
30125-13126
30127-30128
30129-30130
30131-30132
30133-30208
7600H-7601H
7602H-7603H
7604H-7605H
30209-30210
30211-30212
30213-30214
7606H
30215
7607H
30216
7608H-760FH
7610H-7611H
7612H-7613H
7614H-7615H
7616H
7617H
30217-30224
30225-30226
30227-30228
30229-30230
30231
30232
7618H-7621H
30233-30242
7622H
30243
7623H-7663H
30244-30308
7664H-7683H
7684H-76A3H
76A4H-76C3H
76C4H-76E3H
76E4H-76F3H
76F4H-7703H
30309-30340
30341-30372
30373-30404
30405-30436
30437-30452
30453-30468
Line
Pt
DNP
Obj
Description
Range
Transient Waveform Trigger (MSB)
Bit[15]-Bit[6]: Reserved
Bit[5]: Transient Waveform Trigger Enable - Channel Vca
Bit[4]: Transient Waveform Trigger Enable - Channel Vbc
Bit[3]: Transient Waveform Trigger Enable - Channel Vab
Bit[2]: Transient Waveform Trigger Enable - Channel Vcn
Bit[1]: Transient Waveform Trigger Enable - Channel Vbn
Bit[0]: Transient Waveform Trigger Enable - Channel Van
0=Enable, 1=Disable
Log Configuration Settings
Log Mode
0 = Maximum Number of 1Mbyte files allowed
>0 Not defined
System Events Log Size
4,294,967,295 / 0
Interval Log 1 Log Size
4,294,967,295 / 0
Interval Log 2 Log Size
4,294,967,295 / 0
Interval Log 3 Log Size
4,294,967,295 / 0
Interval Log 4 Log Size
4,294,967,295 / 0
Interval Log 5 Log Size
4,294,967,295 / 0
Interval Log 6 Log Size
4,294,967,295 / 0
Interval Log 7 Log Size
4,294,967,295 / 0
Interval Log 8 Log Size
4,294,967,295 / 0
Event Triggered Log Size
4,294,967,295 / 0
Sequence of Event (Limits) Log Size
4,294,967,295 / 0
Digital Input Log Size
4,294,967,295 / 0
Digital Output Log Size
4,294,967,295 / 0
Flicker Log Size
4,294,967,295 / 0
Waveform Log Size
4,294,967,295 / 0
Power Quality Log Size
4,294,967,295 / 0
Transients Log Size
4,294,967,295 / 0
Reserved
Network Card #2 Settings (Part 1 of 2)
IP Address
Subnet Mask
Default Gateway
MSB
Byte[1]: Port 2 Baud Rate
Byte[0]: Gateway Delay
MSB
Byte[1]: Mode
Byte[0]: Mode 2
Computer Name
DNS Server 1 IP Address
DNS Server 2 IP Address
Server / Service Enable Bits
Email Port Number
FTP Port Number
Network Card #2 Settings (Part 2 of 2)
Reserved
Email Mode (MSB)
Bit[15]: 0=authenicantion on; 1=authentication off
Bit[14]~Bit[0] = Not defined
Reserved
Email Client Settings
Email Server IP Address/name
Administrator Email Address
Email Replay Address
Email Subject Text
Email username
Email Password
FTP Client Settings
Units
Type
R/W
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
F53
F53
F53
F53
F53
F53
F53
F53
F53
F53
F53
F53
F53
F53
F53
F53
F53
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-62
2: Modbus Map - Holding Registers
Line
Pt
DNP
Obj
Description
Addr. (hex)
Address(4X)
7704H-7713H
7714H-7723H
7724H-7763H
7764H-7783H
30469-30484
30485-30500
30501-30567
30565-30596
Username
Password
Startup Path/Directory
Server IP Address/Name
7784H-7785H
7786H
30597-30598
30599
IP Address
Update Interval(1=100msec to 65000=6500 seconds)
Range
Units
Type
R/W
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
R
R
R
R
R
Notes
GE Protocol (EGD)
7787H
7788H-7789H
778AH-778BH
30600
30601-30602
30603-30604
778CH-778DH
778EH
778FH
7790H-7791H
7792H-7793H
7794H-7795H
7796H-7797H
7798H-7799H
779AH-779BH
779CH-779DH
779EH-779FH
77A0H-77A3H
77A4H-77A7H
77A8H-77ABH
77ACH-77AFH
77B0H-77B1H
77B2H
77B3H
77B4H-77B7H
30605-30606
30607
30608
30609-30610
30611-30612
30613-30614
30615-30616
30617-30618
30619-30620
30621-30622
30623-30624
30625-30628
30629-30632
30633-30636
30637-30640
30641-30642
30643
30644
30645-30648
77B8H
30649
77B9H
77BAH
77BBH
77BCH-77DBH
77DCH-77FBH
77FCH-77FFH
30651
30652
30652
30653-30684
30685-30716
30617-30720
7800H
7801H
7802H
7803H
7804H
30721
30722
30723
30724
30725
MSB
Byte[1]: Connection Type (0=broadsact, 1=multicast, 2=unicast)
Byte[0]: Options (Bit[0]: 1=Use IP as Producer ID, 0=Use User
Defined)
User Producer ID
Reserved
DNP LAN/WAN
MSB
Byte[3]: Mode(0=disabled, 1=standard settings, 2=user settings, 3>=
disabled)
Byte[2]: Bitmap (Bit[7]: TCP Enable, Bit[6]=UDP enable, Bit[5]:
Validate Ports, Bit[4]: UDP Defined Port)
Byte[1]: UDP Address
Byte[0]: Validate IP
TCP Listen Port
UDP Listen Port
Valid IP Address #1
Valid IP Address #2
Valid IP Address #3
Valid IP Address #4
Valid IP Subnet Mask #1
Valid IP Subnet Mask #2
Valid IP Subnet Mask #3
Valid IP Subnet Mask #4
Valid TCP Start Ports
Valid TCP End Ports
Valid UDP Start Ports
Valid UDP End Ports
Valid Multicast Group Address
Valid UDP Respond Port
Device Address
Reserved
SNTP Settings
Synch Source
MSB first,
Byte[1] - Synch Source: 0 = IRIG-B(default); 1 = SNTP; 2 = Line
synch; 3 = PTP (IEEE 1588); 255 = No synch; others = undefined.
Byte[0] - Mode: 0 = Unicast; 1 = Broadcast (not implemented)
Port Default to 123 if equal to 0x000 or 0xFFFF
Synch Rate in minute: >=1(default) and <= 1440 (24Hours)
Timeout in seconds: >=10(default) and <= 60
Server 1 Name or IP Address is ASCII character
Server 2 Name or IP Address is ASCII character
Reserved
IEC 61000-4-30: Block Settings
Voltage Boundary Hysteresis
Phase A-N Voltage Sag Setpoint
0% / +65535%
Phase B-N Voltage Sag Setpoint
0% / +65535%
Phase C-N Voltage Sag Setpoint
0% / +65535%
Phase A-B Voltage Sag Setpoint
0% / +65535%
Phase B-C Voltage Sag Setpoint
0% / +65535%
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-63
2: Modbus Map - Holding Registers
Line
Pt
DNP
Obj
Description
Addr. (hex)
Address(4X)
7805H
7806H
7807H
7808H
7809H
780AH
780BH
780CH
780DH
780EH
780FH
7810H
7811H
7812H
7813H
7814H
7815H
7816H
7817H
30726
30727
30728
30729
30730
30731
30732
30733
30734
30735
30736
30737
30738
30739
30740
30741
30742
30743
30744
Phase C-A Voltage Sag Setpoint
Phase X-N Voltage Sag Setpoint
Phase N-E Voltage Sag Setpoint
Phase A-E Voltage Sag Setpoint
Phase B-E Voltage Sag Setpoint
Phase C-E Voltage Sag Setpoint
Phase X-E Voltage Sag Setpoint
Phase A-N Voltage Swell Setpoint
Phase B-N Voltage Swell Setpoint
Phase C-N Voltage Swell Setpoint
Phase A-B Voltage Swell Setpoint
Phase B-C Voltage Swell Setpoint
Phase C-A Voltage Swell Setpoint
Phase X-N Voltage Swell Setpoint
Phase N-E Voltage Swell Setpoint
Phase A-E Voltage Swell Setpoint
Phase B-E Voltage Swell Setpoint
Phase C-E Voltage Swell Setpoint
Phase X-E Voltage Swell Setpoint
7818H
7819H
781AH
781BH
781CH
781DH
781EH
781FH
30745
30746
30747
30748
30749
30750
30751
30752
Phase A Current Sag Setpoint
Phase B Current Sag Setpoint
Phase C Current Sag Setpoint
Phase X Current Sag Setpoint
Phase A Current Swell Setpoint
Phase B Current Swell Setpoint
Phase C Current Swell Setpoint
Phase X Current Swell Setpoint
7820H
7821H
7822H
7823H
7824H
7825H
7826H
7827H
7828H
7829H
7829H
782BH
30753
30754
30755
30756
30757
30758
30759
30760
30761
30762
30763
30764
Phase A-N Voltage Setpoint
Phase B-N Voltage Setpoint
Phase C-N Voltage Setpoint
Phase A-B Voltage Setpoint
Phase B-C Voltage Setpoint
Phase C-A Voltage Setpoint
Phase X-N Voltage Setpoint
Phase N-E Voltage Setpoint
Phase A-E Voltage Setpoint
Phase B-E Voltage Setpoint
Phase C-E Voltage Setpoint
Phase X-E Voltage Setpoint
782CH
782DH
782EH
782FH
7830H
7831H
7832H
7833H
7834H
7835H
7836H
7837H
30765
30766
30767
30768
30769
30770
30771
30772
30773
30774
30775
30776
Phase A-N Voltage Setpoint
Phase B-N Voltage Setpoint
Phase C-N Voltage Setpoint
Phase A-B Voltage Setpoint
Phase B-C Voltage Setpoint
Phase C-A Voltage Setpoint
Phase X-N Voltage Setpoint
Phase N-E Voltage Setpoint
Phase A-E Voltage Setpoint
Phase B-E Voltage Setpoint
Phase C-E Voltage Setpoint
Phase X-E Voltage Setpoint
7838H
7839H
783AH
783BH
30777
30778
30779
30780
Phase A-N Voltage
Phase B-N Voltage
Phase C-N Voltage
Phase A-B Voltage
Range
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
Current Boundary Hysteresis
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
Voltage Boundary Interruptions
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
Voltage Boundary Interruptions Hysteresis
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
Voltage Nominal
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
Units
Type
R/W
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-64
2: Modbus Map - Holding Registers
Line
Pt
DNP
Obj
Description
Addr. (hex)
Address(4X)
783CH
783DH
783EH-783FH
30781
30782
30783-30784
7840H
7841H
7842H
7843H
7844H
7845H
7846H
7847H
7848H
7849H
784AH
784BH
784CH
784DH
784EH
784FH
7850H
7851H
7852H
7853H
7854H
7855H
7856H
7857H
7858H
7859H
785AH
785BH
785CH
785DH
785EH
785FH
7860H
7861H
7862H
7863H
7864H
7865H
7866H
7867H
7868H
7869H
786AH
786BH
786CH
786DH
786EH
786FH
7870H
7871H
7872H
7873H
30785
30786
30787
30788
30789
30790
30791
30792
30793
30794
30795
30796
30797
30798
30799
30800
30801
30802
30803
30804
30805
30806
30807
30808
30809
30810
30811
30812
30813
30814
30815
30816
30817
30818
30819
30820
30821
30822
30823
30824
30825
30826
30827
30828
30829
30830
30831
30832
30833
30834
30835
30836
Order #0
Order #1
Order #2
Order #3
Order #4
Order #5
Order #6
Order #7
Order #8
Order #9
Order #10
Order #11
Order #12
Order #13
Order #14
Order #15
Order #16
Order #17
Order #18
Order #19
Order #20
Order #21
Order #22
Order #23
Order #24
Order #25
Order #26
Order #27
Order #28
Order #29
Order #30
Order #31
Order #32
Order #33
Order #34
Order #35
Order #36
Order #37
Order #38
Order #39
Order #40
Order #41
Order #42
Order #43
Order #44
Order #45
Order #46
Order #47
Order #48
Order #49
Order #50
Order #51
7874H
7875H
30837
30838
Order #0
Order #1
Phase B-C Voltage
Phase C-A Voltage
Reserved
Range
0% / +65535%
0% / +65535%
0% / +65535%
Harmonic Subgroup Magnitude Threshould
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
Interharmonic Subgroup Magnitude Threshould
0% / +65535%
0% / +65535%
Units
Type
R/W
0.01%
0.01%
0.01%
F10
F10
F10
R
R
R
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
0.01%
0.01%
F10
F10
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-65
2: Modbus Map - Holding Registers
Line
Pt
DNP
Obj
Description
Addr. (hex)
Address(4X)
7876H
7877H
7878H
7879H
787AH
787BH
787CH
787DH
787EH
787FH
7880H
7881H
7882H
7883H
7884H
7885H
7886H
7887H
7888H
7889H
788AH
788BH
788CH
788DH
788EH
788FH
7890H
7891H
7892H
7893H
7894H
7895H
7896H
7897H
7898H
7899H
789AH
789BH
789CH
789DH
789EH
789FH
78A0H
78A1H
78A2H
78A3H
78A4H
78A5H
78A6H
78A7H
30839
30840
30841
30842
30843
30844
30845
30846
30847
30848
30849
30850
30851
30852
30853
30854
30855
30856
30857
30858
30859
30860
30861
30862
30863
30864
30865
30866
30867
30868
30869
30870
30871
30872
30873
30874
30875
30876
30877
30878
30879
30880
30881
30882
30883
30884
30885
30886
30887
30888
Order #2
Order #3
Order #4
Order #5
Order #6
Order #7
Order #8
Order #9
Order #10
Order #11
Order #12
Order #13
Order #14
Order #15
Order #16
Order #17
Order #18
Order #19
Order #20
Order #21
Order #22
Order #23
Order #24
Order #25
Order #26
Order #27
Order #28
Order #29
Order #30
Order #31
Order #32
Order #33
Order #34
Order #35
Order #36
Order #37
Order #38
Order #39
Order #40
Order #41
Order #42
Order #43
Order #44
Order #45
Order #46
Order #47
Order #48
Order #49
Order #50
Order #51
78A8H
78A9H
78AAH
78ABH
78ACH
78ADH
78AEH
78AFH
30889
30890
30891
30892
30893
30894
30895
30896
Order #0
Order #1
Order #2
Order #3
Order #4
Order #5
Order #6
Order #7
Range
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
Harmonic Group Magnitude Threshold (Factory Use Only)
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
Units
Type
R/W
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-66
2: Modbus Map - Holding Registers
Line
Pt
DNP
Obj
Description
Addr. (hex)
Address(4X)
78B0H
78B1H
78B2H
78B3H
78B4H
78B5H
78B6H
78B7H
78B8H
78B9H
78BAH
78BBH
78BCH
78BDH
78BEH
78BFH
78C0H
78C1H
78C2H
78C3H
78C4H
78C5H
78C6H
78C7H
78C8H
78C9H
78CAH
78CBH
78CCH
78CDH
78CEH
78CFH
78D0H
78D1H
78D2H
78D3H
78D4H
78D5H
78D6H
78D7H
78D8H
78D9H
78DAH
78DBH
30897
30898
30899
30900
30901
30902
30903
30904
30905
30906
30907
30908
30909
30910
30911
30912
30913
30914
30915
30916
30917
30918
30919
30920
30921
30922
30923
30924
30925
30926
30927
30928
30929
30930
30931
30932
30933
30934
30935
30936
30937
30938
30939
30940
Order #8
Order #9
Order #10
Order #11
Order #12
Order #13
Order #14
Order #15
Order #16
Order #17
Order #18
Order #19
Order #20
Order #21
Order #22
Order #23
Order #24
Order #25
Order #26
Order #27
Order #28
Order #29
Order #30
Order #31
Order #32
Order #33
Order #34
Order #35
Order #36
Order #37
Order #38
Order #39
Order #40
Order #41
Order #42
Order #43
Order #44
Order #45
Order #46
Order #47
Order #48
Order #49
Order #50
Order #51
78DCH
78DDH
78DEH
78DFH
78E0H
78E1H
78E2H
78E3H
78E4H
78E5H
78E6H
78E7H
78E8H
78E9H
30941
30942
30943
30944
30945
30946
30947
30948
30949
30950
30951
30952
30953
30954
Order #0
Order #1
Order #2
Order #3
Order #4
Order #5
Order #6
Order #7
Order #8
Order #9
Order #10
Order #11
Order #12
Order #13
Range
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
Interharmonic Group Magnitude Threshold (Factory Use Only)
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
Units
Type
R/W
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-67
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
78EAH
78EBH
78ECH
78EDH
78EEH
78EFH
78F0H
78F1H
78F2H
78F3H
78F4H
78F5H
78F6H
78F7H
78F8H
78F9H
78FAH
78FBH
78FCH
78FDH
78FEH
78FFH
7900H
7901H
7902H
7903H
7904H
7905H
7906H
7907H
7908H
30955
30956
30957
30958
30959
30960
30961
30962
30963
30964
30965
30966
30967
30968
30969
30970
30971
30972
30973
30974
30975
30976
30977
30978
30979
30980
30981
30982
30983
30984
30985
Line
Pt
DNP
Obj
Description
Order #14
Order #15
Order #16
Order #17
Order #18
Order #19
Order #20
Order #21
Order #22
Order #23
Order #24
Order #25
Order #26
Order #27
Order #28
Order #29
Order #30
Order #31
Order #32
Order #33
Order #34
Order #35
Order #36
Order #37
Order #38
Order #39
Order #40
Order #41
Order #42
Order #43
Order #44
Range
Units
Type
R/W
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
7909H
30986
Order #45
0% / +65535%
0.01%
F10
R
790AH
790BH
790CH
790DH
790EH
790FH
30987
30988
30989
30990
30991
30992
Order #46
Order #47
Order #48
Order #49
Order #50
Order #51
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0% / +65535%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F10
F10
F10
F10
F10
F10
R
R
R
R
R
R
7910H
7911H
7912H
7913H-791FH
30993
30994
30995
30996-31008
F108
F10
F51
F51
R
R
7920H
7921H
7922H
7923H
31009
31010
31011
31012
7924H
31013
Threshold Enable Channel #
Mains Signalling Threshold
0% / +65535%
Mains Signalling Interharmonics Bin Start Number
Mains Signalling Interharmonics Bin Start Number
Overvoltage (Phase to Earth) Threshold
Phase N-E Voltage Setpoint
0.00 / +655.35
Phase A-E Voltage Setpoint
0.00 / +655.35
Phase B-E Voltage Setpoint
0.00 / +655.35
Phase C-E Voltage Setpoint
0.00 / +655.35
MSB
Byte[1]: Allowed Long Interruption in a Year.
Range from 0 to 100. Values>100 are equal to 100.
Byte[0]: Rapid Voltage Change Data Source
0 = 10/12 Cycles Update RMS
1 = 1 Cycles Update RMS
2~255 = 10/12 Cycles Update RMS
0.01%
Volts
Volts
Volts
Volts
Notes
R
R
R
R
F112
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-68
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
7925H
31014
7926H
31015
7927H
31016
7928H
7929H
31017
31018
792AH
792BH-7FFF
31019
31021-32768
8800H
34817
8801H
8802H-8805H
8806H
8807H
34818
34819-34822
34823
34824
Line
Pt
DNP
Obj
Description
Range
MSB
Byte[1]: Supply Voltage Unbalance Upper Limit.
0 = Less than or equal to 2%
1 = Less than or equal to 3%
2~255 = Less than or equal to 2%
Byte[0]: Voltage Dip Concern Threshold Phase A
see detail on modbus register below
MSB
Byte[1]: Voltage Dip Concern Threshold Phase B
Byte[0]: Voltage Dip Concern Threshold Phase C
0 = Greater than or equal to 10%
1 = Greater than or equal to 15%
2 = Greater than or equal to 20%
3 = Greater than or equal to 30%
4 = Greater than or equal to 40%
5 = Greater than or equal to 50%
6 = Greater than or equal to 60%
7 = Greater than or equal to 70%
8 = Greater than or equal to 85%
9~255 = Greater than or equal to 85%
MSB
Byte[1]: First Day of Week
0 = Sunday
1 = Monday
2~255 = Sunday
Byte[0]: Not Defined
Sliding Reference Usr Sag/Swell Enable for Voltage
Sliding Reference Usr Sag/Swell Enable for Current
Interval Maximum/Minimum/Average
MSB
Byte[1]: Interval
Not Defined
TOU Status Section
TOU Status
bits: -aaa ttts ssdd mmmm
aaa=active schedule(0-7), ttt=current tier(1-4), sss=current season(14), dd=current daytype(0-3), mmmm=current month(1-12)
TOU profile update count since meter startup
Last TOU profile update time since meter startup
reserved
Detailed TOU status, when bit is set in the bit mask
0x8000=TOU is ready and running
0x4000=TOU is initializing
0x2000=TOU is in self-read mode
0x1000=TOU is in manual read mode
0x0800=Season block is customized as Weekly self-read
0x0400=Season block is customized as Daily self-read
0x0200=TOU profile update and re-initialization of TOU
0x0008=Error, block window average not triggered on time internal
in meter profile
0x0004=Meter profile has errors
0x0002=TOU profile validation found errors
0x0001=TOU profile has errors
Units
Type
R/W
F112
R
F112
R
F112
R
F77
F78
R
R
F112
R
R
F112
R
F51
F3
F51
F51
R
R
R
R
Notes
continue block
for 32bytes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-69
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
8808H
34825
8809H
34826
880AH-880FH
34827-34832
8810H-8817H
34833-34840
8818H
8819H
881AH-881BH
881CH-881FH
8820H-8823H
8824H-882BH
882CH
34841
34842
34843-34844
34845-34848
34849-34852
34853-34860
34861
882DH
882EH-8835H
34862
34863-34870
8836H-883DH
34871-34878
883EH-884FH
8850H-8A11H
34879-34896
34897-35346
8A12H-8A43H
35347-35396
8A44H-8A4BH
35397-35404
8A4CH-8A52H
35405-35411
8A53H-8A62H
35412-35427
8A63H
35428
Line
Pt
DNP
Obj
Type
R/W
TOU Profile validation errors, when bit is set in the bit mask
0x0800=no schedule specified
0x0400=bad schedule in annual profile
0x0200=day type too big
0x0100=number used exceeded
0x0080=unsupported calendar format
0x0040=repeat is zero
0x0020=unsupported built-in day
0x0010=bad day of week
0x0008=week too big
0x0004=bad day in every month
0x0002=bad day of month
0x0001=month too big
TOU profile update status code
0=No error/Update Idle
0xFFFF=Meter is checking the TOU profile, set by meter after meter
received all data
1=TOU update profile length error
2=TOU update profile header error
3=TOU update profile invalid device type
4=TOU update profile checksum error
5=TOU update profile validation failed
reserved
TOU Profile Section
TOU profile header
Description
Range
Units
F51
R
F51
R
F51
R
F2
R/W
TOU profile version
reserved
TOU profile length
TOU profile modified date/time
reserved
TOU target device ID string
TOU demand type
0=Sliding Window, 1=Block Window
TOU demand interval, seconds
Scaled energy format IDs, byte array 0 to 15, for TOU energy
accumulators in data sets 1 to 16. Value 0=no scaled energy format
used. Valid scaled energy formats are 1-52
Data Set Coincident Demand Type IDs, byte array 0 to 15, for
coincident demand in data set 1 to 16. Value of 0=no type is
assigned, and thus meter will not apply PTCT multiplying factors.
Valid settings are from 1-30
reserved
Calendar entries
3 registers (6 bytes) each, 150 entries total
Tier Change List
50 entries total
Schedule Indexs
array 0-49
Day type assignments
7 entries, 1st= Sun type…7th=Sat type
value 0-3
Annual Profile
4x4 table of seasons vs. day types. Data specifies the schedule to use
for all days of that type in a given season. First 4 registers are
Season 0, next 4 are Season 1, etc. Registers 1 to 4 within a season
block are for Holiday, Day Type 1, Day Type 2 and Day Type 3.
Assigning 16 to unused cells is recommended.
F51
F51
F53
F3
F51
F2
F51
R/W
R/W
R/W
R/W
R/W
R/W
R/W
F51
F47/F49
R/W
R/W
F47/F49
R/W
F51
F123
R/W
R/W
F124
R/W
F119
R/W
F51
R/W
F51
R/W
Accumulator #1 Register Identifier
(Data's Modbus register address)
F51
R/W
Notes
continue block
for 1768 byte
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-70
2: Modbus Map - Holding Registers
DNP
Obj
Type
R/W
Peak Demand Register #1 Identifier
(Data's Modbus register address)
Coincident Demand Register #1 Identifier
(Data's Modbus register address)
Monitored Data Set #1 Options
Label for Data Set #1
Label for Accumulator of set #1
Label for Peak Demand of set #1
Label for Coincident Demand of set #1
Label for Cumulative Demand of set #1
Definition of Monitored Data Sets #2 - #16
reserved
Label for day types 1, 2, 3
Label for total tier
Labels for tiers 1 - 4
Labels for holidays 1 - 31
Labels for months 1 - 12
Labels for seasons 1 - 4
Month Self Read Time of Day
high byte is hour (0-23), low byte is minute (5, 15, 30, 60); must be
aligned with the demand interval
Season Self Read Time of Day
high byte is hour (0-23), low byte is minute (5, 15, 30, 60); must be
aligned with the demand interval
Number of months
If number of months = 0, all month data will be month 1; similarly if
number of seasons = 0, all season data will be season 1.
F51
R/W
R51
R/W
F125
F2
F2
F2
F2
F2
F51
F2
F2
F2
F2
F2
F2
F112
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
F112
R/W
F51
R/W
36583
Number of seasons
If number of months = 0, all month data will be month 1; similarly if
number of seasons = 0, all season data will be season 1.
F51
R/W
8EE7H
8EE8H
36584
36585
F51
F51
R/W
R/W
8EE9H-8EEFH
8EF0H-8EF6H
8EF7H
36586-36592
36593-36599
36600
F51
F51
F51
R/W
R/W
R/W
8EF8H-8F7FH
36601-36736
F51
R
9000H-9001H
9002H
9003H
9004H
9005H-9008H
9009H-900CH
900DH-9010H
9011H
9012H
36865-36866
36867
36868
36869
36870-36873
36874-36877
36878-36881
36882
36883
9040H-9041H
9042H
9043H
9044H
9045H-9048H
9049H-904CH
904DH-9050H
9051H
9052H
36929-36930
36931
36932
36933
36934-36937
36938-36941
36942-36945
36946
36947
Number of day types
TOU Option bits
0x0001= for customized weekly and daily self-read setup (breaks the
linke between season and month data)
reserved
TOU profile footer
TOU profile checksum
CRC16, MSB first
reserved
Historical Log 1 Snapshot Header
Historical Log 1 Snapshot Memory Size
4,294,967,295 bytes / 0 bytes
Historical Log 1 Snapshot Record Size
65535 bytes / 0 bytes
Historical Log 1 Snapshot First Index
record 65535 / record 0
Historical Log 1 Snapshot Last Index
record 65535 / record 0
Historical Log 1 Snapshot First Time Stamp
12/31/9999 23:59:59.99
Historical Log 1 Snapshot Last Time Stamp
12/31/9999 23:59:59.99
Historical Log 1 Snapshot Valid Bitmap
Historical Log 1 Max Records
65535 records / 0 records
Historical Log 1 Reset Status
Historical Log 2 Snapshot Header
Historical Log 2 Snapshot Memory Size
4,294,967,295 bytes / 0 bytes
Historical Log 2 Snapshot Record Size
65535 bytes / 0 bytes
Historical Log 2 Snapshot First Index
record 65535 / record 0
Historical Log 2 Snapshot Last Index
record 65535 / record 0
Historical Log 2 Snapshot First Time Stamp
12/31/9999 23:59:59.99
Historical Log 2 Snapshot Last Time Stamp
12/31/9999 23:59:59.99
Historical Log 2 Snapshot Valid Bitmap
Historical Log 2 Max Records
65535 records / 0 records
Historical Log 2 Reset Status
Addr. (hex)
Address(4X)
8A64H
35429
8A65H
35430
8A66H
8A67H-8A6EH
8A6FH-8A76H
8A77H-8A7EH
8A7FH-8A86H
8A87H-8A8EH
8A8FH-8D22H
8D23H-8D2AH
8D2BH-8D42H
8D43H-8D4AH
8D4BH-8D6AH
8D6BH-8E62H
8E63H-8EC2H
8EC3H-8EE2H
8EE3H
35431
35432-35439
35440-35447
35448-35455
35456-35463
35464-35471
35472-36131
36132-36139
36140-36163
36164-36171
36172-36203
36204-36451
36452-36547
36548-36579
36580
8EE4H
36581
8EE5H
36582
8EE6H
Line
Pt
Description
Range
Units
1 byte
1 byte
1 record
1 record
10 msec
10 msec
1 record
1 byte
1 byte
1 record
1 record
10 msec
10 msec
1 record
Notes
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-71
2: Modbus Map - Holding Registers
Line
Pt
DNP
Obj
Description
Range
Addr. (hex)
Address(4X)
9280H-9281H
9282H
9283H
9284H
9285H-9288H
9289H-928CH
928DH-9290H
9291H
9292H
37505-37506
37507
37508
37509
37510-37513
37514-37517
37518-37521
37522
37523
System Event Log Memory Size
System Event Log Record Size
System Event Log First Index
System Event Log Last Index
System Event Log First Time Stamp
System Event Log Last Time Stamp
System Event Log Valid Bitmap
System Event Log Max Records
System Event Log Reset Status
9500H
9501H
950AH
38145
38146
38155
Window Index for Historical Log 1
Window Index for Historical Log 2
Window Index for System Event Log
9540H
9541H
954AH
38209
38210
38219
Window Mode for Historical Log 1
Window Mode for Historical Log 2
Window Mode for System Event Log
9580H-95BFH
95C0H-95FFH
9800H-983FH
38273-38336
38337-38400
38913-38976
Historical Log 1 Window
Historical Log 2 Window
System Event Log Window
99FEH
99FFH
9A00H-9A3FH
39423
39424
39425-39488
Auto Increment Configuration
Auto Increment Window Index
Auto Increment Log Window
A300H
A301H-A303H
A304H
A305H
A306H
A307H
A308H
A309H
A30AH
A30BH
A30CH
A30DH
A30EH
A30FH
A310H
A311H
A312H
A313H
A314H
A315H
A316H
A317H
A318H
A400H-A5FFH
41729
41730-41732
41733
41734
41735
41736
41737
41738
41739
41740
41741
41742
41743
41744
41745
41746
41747
41748
41749
41750
41751
41752
41753
41985-42496
Port Control Command
Port Control Lock States
Port Control Pointer RecIn Comm 4
Port Control Pointer RecOut Comm 4
Port Control Pointer TrmIn Comm 4
Port Control Pointer TrmOut Comm 4
Port Control Pointer RecIn Comm 3
Port Control Pointer RecOut Comm 3
Port Control Pointer TrmIn Comm 3
Port Control Pointer TrmOut Comm 3
Port Control Pointer RecIn Comm 2
Port Control Pointer RecOut Comm 2
Port Control Pointer TrmIn Comm 2
Port Control Pointer TrmOut Comm 2
Port Control Pointer RecIn Comm 1 (232/485)
Port Control Pointer RecOut Comm 1 (232/485)
Port Control Pointer TrmIn Comm 1 (232/485)
Port Control Pointer TrmOut Comm 1 (232/485)
Port Control Pointer RecIn Comm Reserved (DIAG)
Port Control Pointer RecOut Comm Reserved (DIAG)
Port Control Pointer TrmIn Comm Reserved (DIAG)
Port Control Pointer TrmOut Comm Reserved (DIAG)
Port and Buffer Selection
Communication Buffer
ADC0H-ADFFH
44481-44544
Reserved
System Event Log Header
4,294,967,295 bytes / 0 bytes
65535 bytes / 0 bytes
record 65535 / record 0
record 65535 / record 0
12/31/9999 23:59:59.99
12/31/9999 23:59:59.99
65535 records / 0 records
Window Index Block
record 65535 / record 0
record 65535 / record 0
record 65535 / record 0
Window Mode Block
Units
1 byte
1 byte
1 record
1 record
10 msec
10 msec
1 record
1 record
1 record
1 record
Type
R/W
Notes
R
R
R
R
R
R
R
R
R
R/W
R/W
R/W
R/W
R/W
R/W
Ch.5
Ch.5
Ch.5
R
R
R
Ch.5
Ch.5
Ch.5
R/W
R/W
R
Ch.5
Ch.5
Ch.5
W
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Ch.5
Window Block
Auto Increment Window Block
Port Control Block
byte 511 / byte 0
byte 511 / byte 0
byte 511 / byte 0
byte 511 / byte 0
byte 511 / byte 0
byte 511 / byte 0
byte 511 / byte 0
byte 511 / byte 0
byte 511 / byte 0
byte 511 / byte 0
byte 511 / byte 0
byte 511 / byte 0
byte 511 / byte 0
byte 511 / byte 0
byte 511 / byte 0
byte 511 / byte 0
byte 511 / byte 0
byte 511 / byte 0
byte 511 / byte 0
byte 511 / byte 0
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
R
Test Mode: Preset Enrgy Update
AE00H
AE01H-AE20H
44545
44546-44577
Preset Energy File Block Index
Preset Energy File Block
W
W
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-72
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
AE21H
44578
B000H
B001H
B002H
B003H
B004H
B005H
B006H
B007H
B008H
B009H
B00AH
B00BH
B00CH
B00DH
B00EH
B00FH
B010H
B011H
B012H
B013H
45057
45058
45059
45060
45061
45062
45063
45064
45065
45066
45067
45068
45069
45070
45071
45072
45073
45074
45075
45076
B014H
B015H
B016H
B017H
B018H
B019H
B01AH
B01BH
B01CH
B01DH
B01EH
B01FH
B020H
B021H
B022H
B023H
B024H
B025H
B026H
B027H
B028H
B029H
B02AH
B02BH
B02CH
B02DH
B02EH
45077
45078
45079
45080
45081
45082
45083
45084
45085
45086
45087
45088
45089
45090
45091
45092
45093
45094
45095
45096
45097
45098
45099
45100
45101
45102
45103
Line
Pt
DNP
Obj
Description
Range
R: Preset Energy File Update Status:
0x0000 - Update file not allowed
0x0001 - Update file start
0x0002 - Update file progress
0x0003 - Update file sucess
0x0004 - Update file fail(bad format)
0x0005 - Update file fail(bad crc)
0x0006 - Update file fail(timeout)
0xFFFF - Update file allow
W: Preset Energy File checksum
Programmable Settings Block 1 (Range: B000H - CFFFH)
Communication Settings Block
Address, Port 4 (I/O)
Protocol & Baud Rate, Port 4 (I/O)
Parity & Stop Bits, Port 4 (I/O)
Data Bits & Response Delay, Port 4(I/O)
Address, Port 3
Protocol & Baud Rate, Port 3
Parity & Stop Bits, Port 3
Data Bits & Response Delay, Port 3
Address, Port 2
Protocol & Baud Rate, Port 2
Parity & Stop Bits, Port 2
Data Bits & Response Delay, Port 2
Address, Port 1 (232/485)
Protocol & Baud Rate, Port 1 (232/485)
Parity & Stop Bits, Port 1 (232/485)
Data Bits & Response Delay, Port 1 (232/485)
Port 4 (I/O) Mode / Port 3 Mode
Port 2 Mode / Port 1 Mode
Reserved
Reserved
Limit Settings Block
Line Number, Limit 1
Point Number and SAB, Limit 1
Value 1, Limit 1
Value 2, Limit 1
Line Number, Limit 2
Point Number and SAB, Limit 2
Value 1, Limit 2
Value 2, Limit 2
Line Number, Limit 3
Point Number and SAB, Limit 3
Value 1, Limit 3
Value 2, Limit 3
Line Number, Limit 4
Point Number and SAB, Limit 4
Value 1, Limit 4
Value 2, Limit 4
Line Number, Limit 5
Point Number and SAB, Limit 5
Value 1, Limit 5
Value 2, Limit 5
Line Number, Limit 6
Point Number and SAB, Limit 6
Value 1, Limit 6
Value 2, Limit 6
Line Number, Limit 7
Point Number and SAB, Limit 7
Value 1, Limit 7
Units
Type
R/W
Notes
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-73
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
B02FH
B030H
B031H
B032H
B033H
B034H
B035H
B036H
B037H
B038H
B039H
B03AH
B03BH
B03CH
B03DH
B03EH
B03FH
B040H
B041H
B042H
B043H
B044H
B045H
B046H
B047H
B048H
B049H
B04AH
B04BH
B04CH
B04DH
B04EH
B04FH
B050H
B051H
B052H
B053H
B054H
B055H
B056H
B057H
B058H
B059H
B05AH
B05BH
B05CH
B05DH
B05EH
B05FH
B060H
B061H
B062H
B063H
B064H
B065H
B066H
B067H
B068H
B069H
45104
45105
45106
45107
45108
45109
45110
45111
45112
45113
45114
45115
45116
45117
45118
45119
45120
45121
45122
45123
45124
45125
45126
45127
45128
45129
45130
45131
45132
45133
45134
45135
45136
45137
45138
45139
45140
45141
45142
45143
45144
45145
45146
45147
45148
45149
45150
45151
45152
45153
45154
45155
45156
45157
45158
45159
45160
45161
45162
Line
Pt
DNP
Obj
Description
Range
Value 2, Limit 7
Line Number, Limit 8
Point Number and SAB, Limit 8
Value 1, Limit 8
Value 2, Limit 8
Line Number, Limit 9
Point Number and SAB, Limit 9
Value 1, Limit 9
Value 2, Limit 9
Line Number, Limit 10
Point Number and SAB, Limit 10
Value 1, Limit 10
Value 2, Limit 10
Line Number, Limit 11
Point Number and SAB, Limit 11
Value 1, Limit 11
Value 2, Limit 11
Line Number, Limit 12
Point Number and SAB, Limit 12
Value 1, Limit 12
Value 2, Limit 12
Line Number, Limit 13
Point Number and SAB, Limit 13
Value 1, Limit 13
Value 2, Limit 13
Line Number, Limit 14
Point Number and SAB, Limit 14
Value 1, Limit 14
Value 2, Limit 14
Line Number, Limit 15
Point Number and SAB, Limit 15
Value 1, Limit 15
Value 2, Limit 15
Line Number, Limit 16
Point Number and SAB, Limit 16
Value 1, Limit 16
Value 2, Limit 16
Line Number, Limit 17
Point Number and SAB, Limit 17
Value 1, Limit 17
Value 2, Limit 17
Line Number, Limit 18
Point Number and SAB, Limit 18
Value 1, Limit 18
Value 2, Limit 18
Line Number, Limit 19
Point Number and SAB, Limit 19
Value 1, Limit 19
Value 2, Limit 19
Line Number, Limit 20
Point Number and SAB, Limit 20
Value 1, Limit 20
Value 2, Limit 20
Line Number, Limit 21
Point Number and SAB, Limit 21
Value 1, Limit 21
Value 2, Limit 21
Line Number, Limit 22
Point Number and SAB, Limit 22
Units
Type
R/W
Notes
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-74
2: Modbus Map - Holding Registers
Line
Pt
DNP
Obj
Description
Addr. (hex)
Address(4X)
B06AH
B06BH
B06CH
B06DH
B06EH
B06FH
B070H
B071H
B072H
B073H
B074H
B075H
B076H
B077H
B078H
B079H
B07AH
B07BH
B07CH
B07DH
B07EH
B07FH
B080H
B081H
B082H
B083H
B084H
B085H
B086H
B087H
B088H
B089H
B08AH
B08BH
B08CH
B08DH
B08EH
B08FH
B090H
B091H
B092H
B093H
45163
45164
45165
45166
45167
45168
45169
45170
45171
45172
45173
45174
45175
45176
45177
45178
45179
45180
45181
45182
45183
45184
45185
45186
45187
45188
45189
45190
45191
45192
45193
45194
45195
45196
45197
45198
45199
45200
45201
45202
45203
45204
Value 1, Limit 22
Value 2, Limit 22
Line Number, Limit 23
Point Number and SAB, Limit 23
Value 1, Limit 23
Value 2, Limit 23
Line Number, Limit 24
Point Number and SAB, Limit 24
Value 1, Limit 24
Value 2, Limit 24
Line Number, Limit 25
Point Number and SAB, Limit 25
Value 1, Limit 25
Value 2, Limit 25
Line Number, Limit 26
Point Number and SAB, Limit 26
Value 1, Limit 26
Value 2, Limit 26
Line Number, Limit 27
Point Number and SAB, Limit 27
Value 1, Limit 27
Value 2, Limit 27
Line Number, Limit 28
Point Number and SAB, Limit 28
Value 1, Limit 28
Value 2, Limit 28
Line Number, Limit 29
Point Number and SAB, Limit 29
Value 1, Limit 29
Value 2, Limit 29
Line Number, Limit 30
Point Number and SAB, Limit 30
Value 1, Limit 30
Value 2, Limit 30
Line Number, Limit 31
Point Number and SAB, Limit 31
Value 1, Limit 31
Value 2, Limit 31
Line Number, Limit 32
Point Number and SAB, Limit 32
Value 1, Limit 32
Value 2, Limit 32
B094H
B095H
B096H
B097H
B098H
B099H
B09AH
B09BH
B09CH
B09DH
B09EH
B09FH
B0A0H
B0A1H
B0A2H
B0A3H
45205
45206
45207
45208
45209
45210
45211
45212
45213
45214
45215
45216
45217
45218
45219
45220
Line Number, Historical Log 1, Parameter 1
Point Number, Historical Log 1, Parameter 1
Line Number, Historical Log 1, Parameter 2
Point Number, Historical Log 1, Parameter 2
Line Number, Historical Log 1, Parameter 3
Point Number, Historical Log 1, Parameter 3
Line Number, Historical Log 1, Parameter 4
Point Number, Historical Log 1, Parameter 4
Line Number, Historical Log 1, Parameter 5
Point Number, Historical Log 1, Parameter 5
Line Number, Historical Log 1, Parameter 6
Point Number, Historical Log 1, Parameter 6
Line Number, Historical Log 1, Parameter 7
Point Number, Historical Log 1, Parameter 7
Line Number, Historical Log 1, Parameter 8
Point Number, Historical Log 1, Parameter 8
Range
Units
Type
R/W
Notes
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Historical Log Settings Block
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-75
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
B0A4H
B0A5H
B0A6H
B0A7H
B0A8H
B0A9H
B0AAH
B0ABH
B0ACH
B0ADH
B0AEH
B0AFH
B0B0H
B0B1H
B0B2H
B0B3H
B0B4H
B0B5H
B0B6H
B0B7H
B0B8H
B0B9H
B0BAH
B0BBH
B0BCH
B0BDH
B0BEH
B0BFH
B0C0H
B0C1H
B0C2H
B0C3H
B0C4H
B0C5H
B0C6H
B0C7H
B0C8H
B0C9H
B0CAH
B0CBH
B0CCH
B0CDH
B0CEH
B0CFH
B0D0H
B0D1H
B0D2H
B0D3H
B0D4H
B0D5H
B0D6H
B0D7H
B0D8H
B0D9H
B0DAH
B0DBH
B0DCH
B0DDH
B0DEH
45221
45222
45223
45224
45225
45226
45227
45228
45229
45230
45231
45232
45233
45234
45235
45236
45237
45238
45239
45240
45241
45242
45243
45244
45245
45246
45247
45248
45249
45250
45251
45252
45253
45254
45255
45256
45257
45258
45259
45260
45261
45262
45263
45264
45265
45266
45267
45268
45269
45270
45271
45272
45273
45274
45275
45276
45277
45278
45279
Line
Pt
DNP
Obj
Description
Line Number, Historical Log 1, Parameter 9
Point Number, Historical Log 1, Parameter 9
Line Number, Historical Log 1, Parameter 10
Point Number, Historical Log 1, Parameter 10
Line Number, Historical Log 1, Parameter 11
Point Number, Historical Log 1, Parameter 11
Line Number, Historical Log 1, Parameter 12
Point Number, Historical Log 1, Parameter 12
Line Number, Historical Log 1, Parameter 13
Point Number, Historical Log 1, Parameter 13
Line Number, Historical Log 1, Parameter 14
Point Number, Historical Log 1, Parameter 14
Line Number, Historical Log 1, Parameter 15
Point Number, Historical Log 1, Parameter 15
Line Number, Historical Log 1, Parameter 16
Point Number, Historical Log 1, Parameter 16
Line Number, Historical Log 1, Parameter 17
Point Number, Historical Log 1, Parameter 17
Line Number, Historical Log 1, Parameter 18
Point Number, Historical Log 1, Parameter 18
Line Number, Historical Log 1, Parameter 19
Point Number, Historical Log 1, Parameter 19
Line Number, Historical Log 1, Parameter 20
Point Number, Historical Log 1, Parameter 20
Line Number, Historical Log 1, Parameter 21
Point Number, Historical Log 1, Parameter 21
Line Number, Historical Log 1, Parameter 22
Point Number, Historical Log 1, Parameter 22
Line Number, Historical Log 1, Parameter 23
Point Number, Historical Log 1, Parameter 23
Line Number, Historical Log 1, Parameter 24
Point Number, Historical Log 1, Parameter 24
Line Number, Historical Log 1, Parameter 25
Point Number, Historical Log 1, Parameter 25
Line Number, Historical Log 1, Parameter 26
Point Number, Historical Log 1, Parameter 26
Line Number, Historical Log 1, Parameter 27
Point Number, Historical Log 1, Parameter 27
Line Number, Historical Log 1, Parameter 28
Point Number, Historical Log 1, Parameter 28
Line Number, Historical Log 1, Parameter 29
Point Number, Historical Log 1, Parameter 29
Line Number, Historical Log 1, Parameter 30
Point Number, Historical Log 1, Parameter 30
Line Number, Historical Log 1, Parameter 31
Point Number, Historical Log 1, Parameter 31
Line Number, Historical Log 1, Parameter 32
Point Number, Historical Log 1, Parameter 32
Line Number, Historical Log 1, Parameter 33
Point Number, Historical Log 1, Parameter 33
Line Number, Historical Log 1, Parameter 34
Point Number, Historical Log 1, Parameter 34
Line Number, Historical Log 1, Parameter 35
Point Number, Historical Log 1, Parameter 35
Line Number, Historical Log 1, Parameter 36
Point Number, Historical Log 1, Parameter 36
Line Number, Historical Log 1, Parameter 37
Point Number, Historical Log 1, Parameter 37
Line Number, Historical Log 1, Parameter 38
Range
Units
Type
R/W
Notes
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-76
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
B0DFH
B0E0H
B0E1H
B0E2H
B0E3H
B0E4H
B0E5H
B0E6H
B0E7H
B0E8H
B0E9H
B0EAH
B0EBH
B0ECH
B0EDH
B0EEH
B0EFH
B0F0H
B0F1H
B0F2H
B0F3H
B0F4H
B0F5H
B0F6H
B0F7H
B0F8H
B0F9H
B0FAH
B0FBH
B0FCH
B0FDH
B0FEH
B0FFH
B100H
B101H
B102H
B103H
B104H
B105H
B106H
B107H
B108H
B109H
B10AH
B10BH
B10CH
B10DH
B10EH
B10FH
B110H
B111H
B112H
B113H
B114H
B115H
B116H
B117H
B118H
B119H
45280
45281
45282
45283
45284
45285
45286
45287
45288
45289
45290
45291
45292
45293
45294
45295
45296
45297
45298
45299
45300
45301
45302
45303
45304
45305
45306
45307
45308
45309
45310
45311
45312
45313
45314
45315
45316
45317
45318
45319
45320
45321
45322
45323
45324
45325
45326
45327
45328
45329
45330
45331
45332
45333
45334
45335
45336
45337
45338
Line
Pt
DNP
Obj
Description
Point Number, Historical Log 1, Parameter 38
Line Number, Historical Log 1, Parameter 39
Point Number, Historical Log 1, Parameter 39
Line Number, Historical Log 1, Parameter 40
Point Number, Historical Log 1, Parameter 40
Line Number, Historical Log 1, Parameter 41
Point Number, Historical Log 1, Parameter 41
Line Number, Historical Log 1, Parameter 42
Point Number, Historical Log 1, Parameter 42
Line Number, Historical Log 1, Parameter 43
Point Number, Historical Log 1, Parameter 43
Line Number, Historical Log 1, Parameter 44
Point Number, Historical Log 1, Parameter 44
Line Number, Historical Log 1, Parameter 45
Point Number, Historical Log 1, Parameter 45
Line Number, Historical Log 1, Parameter 46
Point Number, Historical Log 1, Parameter 46
Line Number, Historical Log 1, Parameter 47
Point Number, Historical Log 1, Parameter 47
Line Number, Historical Log 1, Parameter 48
Point Number, Historical Log 1, Parameter 48
Line Number, Historical Log 1, Parameter 49
Point Number, Historical Log 1, Parameter 49
Line Number, Historical Log 1, Parameter 50
Point Number, Historical Log 1, Parameter 50
Line Number, Historical Log 1, Parameter 51
Point Number, Historical Log 1, Parameter 51
Line Number, Historical Log 1, Parameter 52
Point Number, Historical Log 1, Parameter 52
Line Number, Historical Log 1, Parameter 53
Point Number, Historical Log 1, Parameter 53
Line Number, Historical Log 1, Parameter 54
Point Number, Historical Log 1, Parameter 54
Line Number, Historical Log 1, Parameter 55
Point Number, Historical Log 1, Parameter 55
Line Number, Historical Log 1, Parameter 56
Point Number, Historical Log 1, Parameter 56
Line Number, Historical Log 1, Parameter 57
Point Number, Historical Log 1, Parameter 57
Line Number, Historical Log 1, Parameter 58
Point Number, Historical Log 1, Parameter 58
Line Number, Historical Log 1, Parameter 59
Point Number, Historical Log 1, Parameter 59
Line Number, Historical Log 1, Parameter 60
Point Number, Historical Log 1, Parameter 60
Line Number, Historical Log 1, Parameter 61
Point Number, Historical Log 1, Parameter 61
Line Number, Historical Log 1, Parameter 62
Point Number, Historical Log 1, Parameter 62
Line Number, Historical Log 1, Parameter 63
Point Number, Historical Log 1, Parameter 63
Line Number, Historical Log 1, Parameter 64
Point Number, Historical Log 1, Parameter 64
Line Number, Historical Log 2, Parameter 1
Point Number, Historical Log 2, Parameter 1
Line Number, Historical Log 2, Parameter 2
Point Number, Historical Log 2, Parameter 2
Line Number, Historical Log 2, Parameter 3
Point Number, Historical Log 2, Parameter 3
Range
Units
Type
R/W
Notes
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-77
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
B11AH
B11BH
B11CH
B11DH
B11EH
B11FH
B120H
B121H
B122H
B123H
B124H
B125H
B126H
B127H
B128H
B129H
B12AH
B12BH
B12CH
B12DH
B12EH
B12FH
B130H
B131H
B132H
B133H
B134H
B135H
B136H
B137H
B138H
B139H
B13AH
B13BH
B13CH
B13DH
B13EH
B13FH
B140H
B141H
B142H
B143H
B144H
B145H
B146H
B147H
B148H
B149H
B14AH
B14BH
B14CH
B14DH
B14EH
B14FH
B150H
B151H
B152H
B153H
B154H
45339
45340
45341
45342
45343
45344
45345
45346
45347
45348
45349
45350
45351
45352
45353
45354
45355
45356
45357
45358
45359
45360
45361
45362
45363
45364
45365
45366
45367
45368
45369
45370
45371
45372
45373
45374
45375
45376
45377
45378
45379
45380
45381
45382
45383
45384
45385
45386
45387
45388
45389
45390
45391
45392
45393
45394
45395
45396
45397
Line
Pt
DNP
Obj
Description
Range
Line Number, Historical Log 2, Parameter 4
Point Number, Historical Log 2, Parameter 4
Line Number, Historical Log 2, Parameter 5
Point Number, Historical Log 2, Parameter 5
Line Number, Historical Log 2, Parameter 6
Point Number, Historical Log 2, Parameter 6
Line Number, Historical Log 2, Parameter 7
Point Number, Historical Log 2, Parameter 7
Line Number, Historical Log 2, Parameter 8
Point Number, Historical Log 2, Parameter 8
Line Number, Historical Log 2, Parameter 9
Point Number, Historical Log 2, Parameter 9
Line Number, Historical Log 2, Parameter 10
Point Number, Historical Log 2, Parameter 10
Line Number, Historical Log 2, Parameter 11
Point Number, Historical Log 2, Parameter 11
Line Number, Historical Log 2, Parameter 12
Point Number, Historical Log 2, Parameter 12
Line Number, Historical Log 2, Parameter 13
Point Number, Historical Log 2, Parameter 13
Line Number, Historical Log 2, Parameter 14
Point Number, Historical Log 2, Parameter 14
Line Number, Historical Log 2, Parameter 15
Point Number, Historical Log 2, Parameter 15
Line Number, Historical Log 2, Parameter 16
Point Number, Historical Log 2, Parameter 16
Line Number, Historical Log 2, Parameter 17
Point Number, Historical Log 2, Parameter 17
Line Number, Historical Log 2, Parameter 18
Point Number, Historical Log 2, Parameter 18
Line Number, Historical Log 2, Parameter 19
Point Number, Historical Log 2, Parameter 19
Line Number, Historical Log 2, Parameter 20
Point Number, Historical Log 2, Parameter 20
Line Number, Historical Log 2, Parameter 21
Point Number, Historical Log 2, Parameter 21
Line Number, Historical Log 2, Parameter 22
Point Number, Historical Log 2, Parameter 22
Line Number, Historical Log 2, Parameter 23
Point Number, Historical Log 2, Parameter 23
Line Number, Historical Log 2, Parameter 24
Point Number, Historical Log 2, Parameter 24
Line Number, Historical Log 2, Parameter 25
Point Number, Historical Log 2, Parameter 25
Line Number, Historical Log 2, Parameter 26
Point Number, Historical Log 2, Parameter 26
Line Number, Historical Log 2, Parameter 27
Point Number, Historical Log 2, Parameter 27
Line Number, Historical Log 2, Parameter 28
Point Number, Historical Log 2, Parameter 28
Line Number, Historical Log 2, Parameter 29
Point Number, Historical Log 2, Parameter 29
Line Number, Historical Log 2, Parameter 30
Point Number, Historical Log 2, Parameter 30
Line Number, Historical Log 2, Parameter 31
Point Number, Historical Log 2, Parameter 31
Line Number, Historical Log 2, Parameter 32
Point Number, Historical Log 2, Parameter 32
Line Number, Historical Log 2, Parameter 33
Units
Type
R/W
Notes
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-78
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
B155H
B156H
B157H
B158H
B159H
B15AH
B15BH
B15CH
B15DH
B15EH
B15FH
B160H
B161H
B162H
B163H
B164H
B165H
B166H
B167H
B168H
B169H
B16AH
B16BH
B16CH
B16DH
B16EH
B16FH
B170H
B171H
B172H
B173H
B174H
B175H
B176H
B177H
B178H
B179H
B17AH
B17BH
B17CH
B17DH
B17EH
B17FH
B180H
B181H
B182H
B183H
B184H
B185H
B186H
B187H
B188H
B189H
B18AH
B18BH
B18CH
B18DH
B18EH
B18FH
45398
45399
45400
45401
45402
45403
45404
45405
45406
45407
45408
45409
45410
45411
45412
45413
45414
45415
45416
45417
45418
45419
45420
45421
45422
45423
45424
45425
45426
45427
45428
45429
45430
45431
45432
45433
45434
45435
45436
45437
45438
45439
45440
45441
45442
45443
45444
45445
45446
45447
45448
45449
45450
45451
45452
45453
45454
45455
45456
Line
Pt
DNP
Obj
Description
Range
Point Number, Historical Log 2, Parameter 33
Line Number, Historical Log 2, Parameter 34
Point Number, Historical Log 2, Parameter 34
Line Number, Historical Log 2, Parameter 35
Point Number, Historical Log 2, Parameter 35
Line Number, Historical Log 2, Parameter 36
Point Number, Historical Log 2, Parameter 36
Line Number, Historical Log 2, Parameter 37
Point Number, Historical Log 2, Parameter 37
Line Number, Historical Log 2, Parameter 38
Point Number, Historical Log 2, Parameter 38
Line Number, Historical Log 2, Parameter 39
Point Number, Historical Log 2, Parameter 39
Line Number, Historical Log 2, Parameter 40
Point Number, Historical Log 2, Parameter 40
Line Number, Historical Log 2, Parameter 41
Point Number, Historical Log 2, Parameter 41
Line Number, Historical Log 2, Parameter 42
Point Number, Historical Log 2, Parameter 42
Line Number, Historical Log 2, Parameter 43
Point Number, Historical Log 2, Parameter 43
Line Number, Historical Log 2, Parameter 44
Point Number, Historical Log 2, Parameter 44
Line Number, Historical Log 2, Parameter 45
Point Number, Historical Log 2, Parameter 45
Line Number, Historical Log 2, Parameter 46
Point Number, Historical Log 2, Parameter 46
Line Number, Historical Log 2, Parameter 47
Point Number, Historical Log 2, Parameter 47
Line Number, Historical Log 2, Parameter 48
Point Number, Historical Log 2, Parameter 48
Line Number, Historical Log 2, Parameter 49
Point Number, Historical Log 2, Parameter 49
Line Number, Historical Log 2, Parameter 50
Point Number, Historical Log 2, Parameter 50
Line Number, Historical Log 2, Parameter 51
Point Number, Historical Log 2, Parameter 51
Line Number, Historical Log 2, Parameter 52
Point Number, Historical Log 2, Parameter 52
Line Number, Historical Log 2, Parameter 53
Point Number, Historical Log 2, Parameter 53
Line Number, Historical Log 2, Parameter 54
Point Number, Historical Log 2, Parameter 54
Line Number, Historical Log 2, Parameter 55
Point Number, Historical Log 2, Parameter 55
Line Number, Historical Log 2, Parameter 56
Point Number, Historical Log 2, Parameter 56
Line Number, Historical Log 2, Parameter 57
Point Number, Historical Log 2, Parameter 57
Line Number, Historical Log 2, Parameter 58
Point Number, Historical Log 2, Parameter 58
Line Number, Historical Log 2, Parameter 59
Point Number, Historical Log 2, Parameter 59
Line Number, Historical Log 2, Parameter 60
Point Number, Historical Log 2, Parameter 60
Line Number, Historical Log 2, Parameter 61
Point Number, Historical Log 2, Parameter 61
Line Number, Historical Log 2, Parameter 62
Point Number, Historical Log 2, Parameter 62
Units
Type
R/W
Notes
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-79
2: Modbus Map - Holding Registers
Line
Pt
DNP
Obj
Description
Addr. (hex)
Address(4X)
B190H
B191H
B192H
B193H
B194H
B195H
B196H
B197H
45457
45458
45459
45460
45461
45462
45463
45464
Line Number, Historical Log 2, Parameter 63
Point Number, Historical Log 2, Parameter 63
Line Number, Historical Log 2, Parameter 64
Point Number, Historical Log 2, Parameter 64
Snapshot Interval, Historical Log 1
Snapshot Interval, Historical Log 2
Record Size, Historical Log 1
Record Size, Historical Log 2
B198H
B199H
B19AH
B19BH
B19CH
B19DH
B19EH
B19FH
B1A0H
B1A1H
B1A2H
B1A3H
B1A4H
B1A5H
B1A6H
B1A7H
B1A8H
B1A9H
B1AAH
B1ABH
B1ACH
B1ADH
B1AEH
B1AFH
B1B0H
B1B1H
B1B2H
B1B3H
B1B4H
B1B5H
B1B6H
B1B7H
B1B8H
B1B9H
B1BAH
B1BBH
45465
45466
45467
45468
45469
45470
45471
45472
45473
45474
45475
45476
45477
45478
45479
45480
45481
45482
45483
45484
45485
45486
45487
45488
45489
45490
45491
45492
45493
45494
45495
45496
45497
45498
45499
45500
Phase A-N Voltage Below Setpoint
Phase B-N Voltage Below Setpoint
Phase C-N Voltage Below Setpoint
Phase A-B Voltage Below Setpoint
Phase B-C Voltage Below Setpoint
Phase C-A Voltage Below Setpoint
Phase X-N Voltage Below Setpoint
Phase N-E Voltage Below Setpoint
Phase A-E Voltage Below Setpoint
Phase B-E Voltage Below Setpoint
Phase C-E Voltage Below Setpoint
Phase X-E Voltage Below Setpoint
Phase A-N Voltage Below Setpoint
Phase B-N Voltage Above Setpoint
Phase C-N Voltage Above Setpoint
Phase A-B Voltage Above Setpoint
Phase B-C Voltage Above Setpoint
Phase C-A Voltage Above Setpoint
Phase X-N Voltage Above Setpoint
Phase N-E Voltage Above Setpoint
Phase A-E Voltage Above Setpoint
Phase B-E Voltage Above Setpoint
Phase C-E Voltage Above Setpoint
Phase X-E Voltage Above Setpoint
Phase A Current Below Setpoint
Phase B Current Below Setpoint
Phase C Current Below Setpoint
Phase X Current Below Setpoint
Phase A Current Above Setpoint
Phase B Current Above Setpoint
Phase C Current Above Setpoint
Phase X Current Above Setpoint
Voltage RMS Sag/Swell
Voltage Wave shape
Current RMS Sag/Swell
Current RMS Chng ROR
B1BCH-B1C3H
B1C4H-B1CBH
B1CCH-B1D3H
B1D4H-B1D5H
B1D6H
B1D7H
B1D8H-B1DFH
B1E0H-B1E7H
B1E8H-B1EFH
B1F0H-B1F1H
B1F2H
B1F3H
B1F4H-B1FBH
45501-45508
45509-45516
45517-45524
45525-45526
45527
45528
45529-45536
45537-45544
45545-45552
45553-45554
45555
45556
45557-45564
Range
3600/0
3600/0
Waveform/CBEMA Settings Block
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
+327.67% / -327.68%
Units
1 second
1 second
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
Type
R/W
Notes
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
High Speed Input Settings Block
Input 1 Name
Input 1 Open Label
Input 1 Close Label
Input 1 Value
Input 1 Mode
Reserved
Input 2 Name
Input 2 Open Label
Input 2 Close Label
Input 2 Value
Input 2 Mode
Reserved
Input 3 Name
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-80
2: Modbus Map - Holding Registers
Line
Pt
DNP
Obj
Description
Range
Addr. (hex)
Address(4X)
B1FCH-B203H
B204H-B20BH
B20CH-B20DH
B20EH
B20FH
B210H-B217H
B218H-B21FH
B220H-B227H
B228H-B229H
B22AH
B22BH
B22CH-B233H
B234H-B23BH
B23CH-B243H
B244H-B245H
B246H
B247H
B248H-B24FH
B250H-B257H
B258H-B25FH
B260H-B261H
B262H
B263H
B264H-B26BH
B26CH-B273H
B274H-B27BH
B27CH-B27DH
B27EH
B27FH
B280H-B287H
B288H-B28FH
B290H-B297H
B298H-B299H
B29AH
B29BH
B29CH-B29FH
45565-45572
45573-45580
45581-45582
45583
45584
45585-45592
45593-45600
45601-45608
45609-45610
45611
45612
45613-45620
45621-45628
45629-45636
45637-45638
45639
45640
45641-45648
45649-45656
45657-45664
45665-45666
45667
45668
45669-45676
45677-45684
45685-45692
45693-45694
45695
45696
45697-45704
45705-45712
45713-45720
45721-45722
45723
45724
45725-45728
Input 3 Open Label
Input 3 Close Label
Input 3 Value
Input 3 Mode
Reserved
Input 4 Name
Input 4 Open Label
Input 4 Close Label
Input 4 Value
Input 4 Mode
Reserved
Input 5 Name
Input 5 Open Label
Input 5 Close Label
Input 5 Value
Input 5 Mode
Reserved
Input 6 Name
Input 6 Open Label
Input 6 Close Label
Input 6 Value
Input 6 Mode
Reserved
Input 7 Name
Input 7 Open Label
Input 7 Close Label
Input 7 Value
Input 7 Mode
Reserved
Input 8 Name
Input 8 Open Label
Input 8 Close Label
Input 8 Value
Input 8 Mode
Reserved
Reserved
B2A0H
B2A1H-B2A3H
B2A4H
B2A5H
B2A6H
B2A7H
B2A8H
B2A9H
B2AAH
B2ABH
B2ACH
B2ADH
B2AEH
B2AFH
B2B0H
B2B1H
B2B2H
B2B3H
B2B4H
B2B5H-B2B7H
B2B8H
B2B9H
45729
45730-45732
45733
45734
45735
45736
45737
45738
45739
45740
45741
45742
45743
45744
45745
45746
45747
45748
45749
45750-45752
45753
45754
External Digital Output Module Settings Block
Address, External Digital Output Module 1
Reserved
Line Number, Relay 1, External Digital Output Module 1
Point Number, Relay 1, External Digtial Output Module 1
Line Number, Relay 2, External Digital Output Module 1
Point Number, Relay 2, External Digtial Output Module 1
Line Number, Relay 3, External Digital Output Module 1
Point Number, Relay 3, External Digtial Output Module 1
Line Number, Relay 4, External Digital Output Module 1
Point Number, Relay 4, External Digtial Output Module 1
Line Number, Relay 5, External Digital Output Module 1
Point Number, Relay 5, External Digtial Output Module 1
Line Number, Relay 6, External Digital Output Module 1
Point Number, Relay 6, External Digtial Output Module 1
Line Number, Relay 7, External Digital Output Module 1
Point Number, Relay 7, External Digtial Output Module 1
Line Number, Relay 8, External Digital Output Module 1
Point Number, Relay 8, External Digtial Output Module 1
Address, External Digital Output Module 2
Reserved
Line Number, Relay 1, External Digital Output Module 2
Point Number, Relay 1, External Digtial Output Module 2
Units
Type
R/W
Notes
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-81
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
B2BAH
B2BBH
B2BCH
B2BDH
B2BEH
B2BFH
B2C0H
B2C1H
B2C2H
B2C3H
B2C4H
B2C5H
B2C6H
B2C7H
B2C8H
B2C9H-B2CBH
B2CCH
B2CDH
B2CEH
B2CFH
B2D0H
B2D1H
B2D2H
B2D3H
B2D4H
B2D5H
B2D6H
B2D7H
B2D8H
B2D9H
B2DAH
B2DBH
B2DCH
B2DDH-B2DFH
B2E0H
B2E1H
B2E2H
B2E3H
B2E4H
B2E5H
B2E6H
B2E7H
B2E8H
B2E9H
B2EAH
B2EBH
B2ECH
B2EDH
B2EEH
B2EFH
B2F0H-B2F3H
45755
45756
45757
45758
45759
45760
45761
45762
45763
45764
45765
45766
45767
45768
45769
45770-45772
45773
45774
45775
45776
45777
45778
45779
45780
45781
45782
45783
45784
45785
45786
45787
45788
45789
45790-45792
45793
45794
45795
45796
45797
45798
45799
45800
45801
45802
45803
45804
45805
45806
45807
45808
45809-45812
B2F4H
B2F5H-B2F7H
B2F8H
B2F9H
B2FAH
B2FBH
B2FCH
B2FDH
45813
45814-45816
45817
45818
45819
45820
45821
45822
Line
Pt
DNP
Obj
Description
Range
Line Number, Relay 2, External Digital Output Module 2
Point Number, Relay 2, External Digtial Output Module 2
Line Number, Relay 3, External Digital Output Module 2
Point Number, Relay 3, External Digtial Output Module 2
Line Number, Relay 4, External Digital Output Module 2
Point Number, Relay 4, External Digtial Output Module 2
Line Number, Relay 5, External Digital Output Module 2
Point Number, Relay 5, External Digtial Output Module 2
Line Number, Relay 6, External Digital Output Module 2
Point Number, Relay 6, External Digtial Output Module 2
Line Number, Relay 7, External Digital Output Module 2
Point Number, Relay 7, External Digtial Output Module 2
Line Number, Relay 8, External Digital Output Module 2
Point Number, Relay 8, External Digtial Output Module 2
Address, External Digital Output Module 3
Reserved
Line Number, Relay 1, External Digital Output Module 3
Point Number, Relay 1, External Digtial Output Module 3
Line Number, Relay 2, External Digital Output Module 3
Point Number, Relay 2, External Digtial Output Module 3
Line Number, Relay 3, External Digital Output Module 3
Point Number, Relay 3, External Digtial Output Module 3
Line Number, Relay 4, External Digital Output Module 3
Point Number, Relay 4, External Digtial Output Module 3
Line Number, Relay 5, External Digital Output Module 3
Point Number, Relay 5, External Digtial Output Module 3
Line Number, Relay 6, External Digital Output Module 3
Point Number, Relay 6, External Digtial Output Module 3
Line Number, Relay 7, External Digital Output Module 3
Point Number, Relay 7, External Digtial Output Module 3
Line Number, Relay 8, External Digital Output Module 3
Point Number, Relay 8, External Digtial Output Module 3
Address, External Digital Output Module 4
Reserved
Line Number, Relay 1, External Digital Output Module 4
Point Number, Relay 1, External Digtial Output Module 4
Line Number, Relay 2, External Digital Output Module 4
Point Number, Relay 2, External Digtial Output Module 4
Line Number, Relay 3, External Digital Output Module 4
Point Number, Relay 3, External Digtial Output Module 4
Line Number, Relay 4, External Digital Output Module 4
Point Number, Relay 4, External Digtial Output Module 4
Line Number, Relay 5, External Digital Output Module 4
Point Number, Relay 5, External Digtial Output Module 4
Line Number, Relay 6, External Digital Output Module 4
Point Number, Relay 6, External Digtial Output Module 4
Line Number, Relay 7, External Digital Output Module 4
Point Number, Relay 7, External Digtial Output Module 4
Line Number, Relay 8, External Digital Output Module 4
Point Number, Relay 8, External Digtial Output Module 4
Reserved
External Analog Output Module Settings Block
Address, External Analog Output Module 1
Reserved
Line Number, Relay 1, External Analog Output Module 1
Point Number, Relay 1, External Digtial Output Module 1
Line Number, Relay 2, External Analog Output Module 1
Point Number, Relay 2, External Digtial Output Module 1
Line Number, Relay 3, External Analog Output Module 1
Point Number, Relay 3, External Digtial Output Module 1
Units
Type
R/W
Notes
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-82
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
B2FEH
B2FFH
B300H
B301H
B302H
B303H
B304H
B305H
B306H
B307H
B308H
B309H-B30BH
B30CH
B32DH
B30EH
B30FH
B310H
B311H
B312H
B313H
B314H
B315H
B316H
B317H
B318H
B319H
B31AH
B31BH
B31CH
B31DH-B31FH
B320H
B321H
B322H
B323H
B324H
B325H
B326H
B327H
B328H
B329H
B32AH
B32BH
B32CH
B32DH
B32EH
B32FH
B330H
B331H-B333H
B334H
B335H
B336H
B337H
B338H
B339H
B33AH
B33BH
B33CH
B33DH
B33EH
45823
45824
45825
45826
45827
45828
45829
45830
45831
45832
45833
45834-45836
45837
45870
45839
45840
45841
45842
45843
45844
45845
45846
45847
45848
45849
45850
45851
45852
45853
45854-45856
45857
45858
45859
45860
45861
45862
45863
45864
45865
45866
45867
45868
45869
45870
45871
45872
45873
45874-45876
45877
45878
45879
45880
45881
45882
45883
45884
45885
45886
45887
Line
Pt
DNP
Obj
Description
Line Number, Relay 4, External Analog Output Module 1
Point Number, Relay 4, External Digtial Output Module 1
Line Number, Relay 5, External Analog Output Module 1
Point Number, Relay 5, External Digtial Output Module 1
Line Number, Relay 6, External Analog Output Module 1
Point Number, Relay 6, External Digtial Output Module 1
Line Number, Relay 7, External Analog Output Module 1
Point Number, Relay 7, External Digtial Output Module 1
Line Number, Relay 8, External Analog Output Module 1
Point Number, Relay 8, External Digtial Output Module 1
Address, External Analog Output Module 2
Reserved
Line Number, Relay 1, External Analog Output Module 2
Point Number, Relay 1, External Digtial Output Module 2
Line Number, Relay 2, External Analog Output Module 2
Point Number, Relay 2, External Digtial Output Module 2
Line Number, Relay 3, External Analog Output Module 2
Point Number, Relay 3, External Digtial Output Module 2
Line Number, Relay 4, External Analog Output Module 2
Point Number, Relay 4, External Digtial Output Module 2
Line Number, Relay 5, External Analog Output Module 2
Point Number, Relay 5, External Digtial Output Module 2
Line Number, Relay 6, External Analog Output Module 2
Point Number, Relay 6, External Digtial Output Module 2
Line Number, Relay 7, External Analog Output Module 2
Point Number, Relay 7, External Digtial Output Module 2
Line Number, Relay 8, External Analog Output Module 2
Point Number, Relay 8, External Digtial Output Module 2
Address, External Analog Output Module 3
Reserved
Line Number, Relay 1, External Analog Output Module 3
Point Number, Relay 1, External Digtial Output Module 3
Line Number, Relay 2, External Analog Output Module 3
Point Number, Relay 2, External Digtial Output Module 3
Line Number, Relay 3, External Analog Output Module 3
Point Number, Relay 3, External Digtial Output Module 3
Line Number, Relay 4, External Analog Output Module 3
Point Number, Relay 4, External Digtial Output Module 3
Line Number, Relay 5, External Analog Output Module 3
Point Number, Relay 5, External Digtial Output Module 3
Line Number, Relay 6, External Analog Output Module 3
Point Number, Relay 6, External Digtial Output Module 3
Line Number, Relay 7, External Analog Output Module 3
Point Number, Relay 7, External Digtial Output Module 3
Line Number, Relay 8, External Analog Output Module 3
Point Number, Relay 8, External Digtial Output Module 3
Address, External Analog Output Module 4
Reserved
Line Number, Relay 1, External Analog Output Module 4
Point Number, Relay 1, External Digtial Output Module 4
Line Number, Relay 2, External Analog Output Module 4
Point Number, Relay 2, External Digtial Output Module 4
Line Number, Relay 3, External Analog Output Module 4
Point Number, Relay 3, External Digtial Output Module 4
Line Number, Relay 4, External Analog Output Module 4
Point Number, Relay 4, External Digtial Output Module 4
Line Number, Relay 5, External Analog Output Module 4
Point Number, Relay 5, External Digtial Output Module 4
Line Number, Relay 6, External Analog Output Module 4
Range
Units
Type
R/W
Notes
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-83
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
B33FH
B340H
B341H
B342H
B343H
45888
45889
45890
45891
45892
B344H
Line
Pt
DNP
Obj
Description
Range
Units
Type
R/W
R
R
R
R
R
45893
Point Number, Relay 6, External Digtial Output Module 4
Line Number, Relay 7, External Analog Output Module 4
Point Number, Relay 7, External Digtial Output Module 4
Line Number, Relay 8, External Analog Output Module 4
Point Number, Relay 8, External Digtial Output Module 4
External KYZ Output Module Settings Block
Address, External KYZ Output Module 1
B345H
45894
Energy Assignement, Relay 1-2, External KYZ Output Module 1
R
B346H
B347H
B348H
45895
45896
45897
Energy Assignement, Relay 3-4, External KYZ Output Module 1
Reserved
Address, External KYZ Output Module 2
R
B349H
45898
Energy Assignement, Relay 1-2, External KYZ Output Module 2
R
B34AH
B34BH
B34CH
45899
45900
45901
Energy Assignement, Relay 3-4, External KYZ Output Module 2
Reserved
Address, External KYZ Output Module 3
R
B34DH
45902
Energy Assignement, Relay 1-2, External KYZ Output Module 3
R
B34EH
B34FH
B350H
45903
45904
45905
Energy Assignement, Relay 3-4, External KYZ Output Module 3
Reserved
Address, External KYZ Output Module 4
R
B351H
45906
Energy Assignement, Relay 1-2, External KYZ Output Module 4
R
B352H
B353H
45907
45908
R
B354H-B355H
B356H-B357H
B358H-B359H
B35AH-B35BH
B35CH-B35DH
B35EH-B35FH
B360H-B361H
B362H-B363H
45909-45910
45911-45912
45913-45914
45915-45916
45917-45918
45919-45920
45921-45922
45923-45924
B364H
B365H
45925
45926
B366H
45927
B367H
B368H-B36BH
B36CH-B36FH
B370H-B371H
B372H-B373H
B374H-B375H
B376H-B377H
B378H-B37BH
45928
45930-45932
45934-45936
45937-45938
45939-45940
45941-45942
45943-45944
45945-45948
B37CH
B37DH
B37EH
45949
45950
45951
Energy Assignement, Relay 3-4, External KYZ Output Module 4
Reserved
CT & PT Ratio Settings Block
Phase Current CT Ratio Numerator
+999,999.99 / +0.01
Phase Current CT Ratio Denominator
+999,999.99 / +0.01
Measured Neutral Current CT Ratio Numerator
+999,999.99 / +0.01
Measured Neutral Current CT Ratio Denominator
+999,999.99 / +0.01
Phase Voltage PT Ratio Numerator
+999,999.99 / +0.01
Phase Voltage PT Ratio Denominator
+999,999.99 / +0.01
Auxiliary Voltage PT Ratio Numerator
+999,999.99 / +0.01
Auxiliary Voltage PT Ratio Denominator
+999,999.99 / +0.01
Hookup and Time Settings Block
Hookup
Frequency & Time Zone Hour Selection
MSB First,
Byte[1]: Time Zone Half Hour
Byte[0]: Daylight Savings Time Enable
0 = DST Enabled
1 = Auto DST
2 = User defined
3 = Auto DST/US EPA 2005
Transformer Loss Compensation (TLC) & Internal KYZ Form
Daylight Savings Time Start
Daylight Savings Time End
% Loss of Watts due to Iron (TLC)
% Loss of Watts due to Copper (TLC)
% Loss of VAR due to Iron (TLC)
% Loss of VAR due to Copper (TLC)
Reserved
Average Settings Block
Thermal and Block Averaging Time Interval
65535 / 0
Rolling Averaging Sub-Interval
65535 / 0
Reserved
Notes
R
R
R
R
1/100 A pri
1/100 A sec
1/100 A pri
1/100 A sec
1/100 V pri
1/100 V sec
1/100 V pri
1/100 V sec
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
1 second
1 second
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-84
2: Modbus Map - Holding Registers
Line
Pt
DNP
Obj
Description
Addr. (hex)
Address(4X)
B37FH
45952
B380H-B38FH
45953-45968
Reserved
B390H-B397H
B398H-B39FH
B3A0H-B3A7H
45969-45976
45977-45984
45985-45992
Meter Designation
Auxiliary Voltage Label (1250 only)
Measured Neutral Current Label
B3A8H-B3A9H
B3AAH-B3ABH
B3ACH-B3ADH
B3AEH
B3AFH
B3B0H-B3B7H
B3B8H-B3B9H
B3BAH-B3BBH
45993-45994
45995-45996
45997-45998
45999
46000
46001-46008
46009-46010
46011-46012
B3BCH-B3BDH
46013-46014
B3BEH
B3BFH
46015
46016
B3C0H
46017
B3C1H
46018
B3C2H
46019
Rolling Sub-Intervals / Time of Use Log Enable
Range
Units
1~255/not used
Exception Profile Block
Type
R/W
Notes
R
Device Label Settings Block
B3C3H
46020
B3C4H-B3C5H
B3C6H-B3C7H
B3C8H-B3C9H
B3CAH-B3CBH
B3CCH-B3CDH
B3CEH-B3CFH
B3D0H-B3D1H
B3D2H-B3D3H
B3D4H-B3D5H
B3D6H-B3D7H
B3D8H-B3D9H
B3DAH-B3E3H
46021-46022
46023-46024
46025-46026
46027-46028
46029-46030
46031-46032
46033-46034
46035-46036
46037-46038
46039-46040
46041-46042
46043-46052
B3E4H
B3E5H
B3E6H
46053
46054
46055
Network Settings Block
IP Address
Subnet Mask
Default Gateway
Port 2 Baud Rate / Gateway Delay
Mode/ Mode 2
Computer Name
DNS Server 1 IP Address
DNS Server 2 IP Address
Server / Service Enable Bits.
MSB first,
Bit[31-30] = Reserved
Bit[29] = GE-EGD Data Port Enabled
Bit[28] = WEB Server Enabled
Bit[27] = SMTP Client Enabled
Bit[26] = FTP Server Enabled
Bit[25] = FTP Client Enabled
Bit[24-21] = Reserved
Bit[20] = SNTP Enabled
Bit[19] = IEC 61850 Server Enabled
Bit[18] = IEC 61850 Goose Enabled
Bit[17-0] = Unused
Email Port Number
FTP Port Number
Block Window Average External Synchronization Block
BWA Synch Enable / BWA Synch Mask
Display Configuration Block
Display Configuration
Energy Direction Block
Received Energy Direction/Power Factor labeling
Test Mode Configuration Block
Test Mode Exit Delay Time
MSB First:
MSB: 0 - 60 = 0 - 60 minutes
61 - 255 = undefined
LSB: undefined
Full Scale Block
Full Scale Phase Current
65535 / 0
Full Scale Measured Neutral Current
65535 / 0
Full Scale Phase-to-Neutral Voltage
65535 / 0
Full Scale Auxiliary Voltage
65535 / 0
Full Scale Phase-To-Phase Voltage
65535 / 0
Full Scale Phase Power
65535 / 0
Full Scale Total Power
65535 / 0
Full Scale Frequency
65535 / 0
Full Scale Phase-To-Earth Voltage
Full Scale XE Voltage
Full Scale NE Voltage
Reserved
External Module Software Interface Block
External Module 1 & 2 Type
External Module 3 & 4 Type
External Module 5 & 6 Type
R
R
R
R
R
R
R
R
R
R
R
R
R
1 / 65536
1 / 65536
1 / 65536
1 / 65536
1 / 65536
1 / 65536
1 / 65536
1 / 65536
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-85
2: Modbus Map - Holding Registers
Line
Pt
DNP
Obj
Description
Range
Units
Type
R/W
Addr. (hex)
Address(4X)
B3E7H
B3E8H
B3E9H
B3EAH
B3EBH
B3ECH
B3EDH
B3EEH
B3EFH
B3F0H
B3F1H
B3F2H
B3F3H
B3F4H-B3FBH
B3FCH-B403H
B404H-B40BH
B40CH-B413H
B414H-B41BH
B41CH-B423H
B424H-B24BH
B24CH-B433H
B434H-B43BH
B43CH-B443H
B444H-B44BH
B44CH-B453H
B454H-B45BH
B45CH-B463H
B464H-B46BH
B46CH-B473H
46056
46057
46058
46059
46060
46061
46062
46063
46064
46065
46066
46067
46068
46069-46076
46077-46084
46085-46092
46093-46100
46101-46108
46109-46116
46117-46124
46125-46132
46133-46140
46141-46148
46149-46156
46157-46164
46165-46172
46173-46180
46181-46188
46189-46196
B474H-B475H
B476H
B477H
B478H-B479H
B47AH
B47BH
B47CH
B47DH
46197
46199
46200
46201
46203
46204
46205
46206
Reserved
Digital Output Module 1 & 2 Port Assignment
Digital Output Module 3 & 4 Port Assignment
Reserved
Analog Output Module 1 & 2 Port Assignment
Analog Output Module 3 & 4 Port Assignment
KYZ Output Module 1 & 2 Port Assignment
KYZ Output Module 3 & 4 Port Assignment
B47EH
B47FH
46207
46208
Manual Control Relay Settings
Reserved
R
R
B480H-B481H
B482H-B483H
B484H-B485H
B486H-B487H
B488H-B489H
B48AH-B48BH
B48CH-B48DH
B48EH-B48FH
46209-46210
46211-46212
46213-46214
46215-46216
46217-46218
46219-46220
46221-46222
46223-46224
Internal Input Pulse Accumulation Scale Factor Block
Internal Input 1 Pulse Accumulation Scale Factor
4294967295 / 0
Internal Input 2 Pulse Accumulation Scale Factor
4294967295 / 0
Internal Input 3 Pulse Accumulation Scale Factor
4294967295 / 0
Internal Input 4 Pulse Accumulation Scale Factor
4294967295 / 0
Internal Input 5 Pulse Accumulation Scale Factor
4294967295 / 0
Internal Input 6 Pulse Accumulation Scale Factor
4294967295 / 0
Internal Input 7 Pulse Accumulation Scale Factor
4294967295 / 0
Internal Input 8 Pulse Accumulation Scale Factor
4294967295 / 0
R
R
R
R
R
R
R
R
B490H
46225
Internal Input 1 & 2 Pulse Accumulation Aggregator Assignment
R
B491H
46226
Internal Input 3 & 4 Pulse Accumulation Aggregator Assignment
R
B492H
46227
Internal Input 5 & 6 Pulse Accumulation Aggregator Assignment
R
B493H
B494H-B49BH
B49CH-B4A3H
46228
46229-46236
46237-46244
Internal Input 7 & 8 Pulse Accumulation Aggregator Assignment
Internal Input 1 Pulse Accumulation Label
Internal Input 2 Pulse Accumulation Label
External Module 7 & 8 Type
External Module 9 & 10 Type
External Module 11 & 12 Type
External Module 13 & 14 Type
External Module 15 & 16 Type
External Module 1 & 2 Slot
External Module 3 & 4 Slot
External Module 5 & 6 Slot
External Module 7 & 8 Slot
External Module 9 & 10 Slot
External Module 11 & 12 Slot
External Module 13 & 14 Slot
External Module 15 & 16 Slot
External Module 1 Label
External Module 2 Label
External Module 3 Label
External Module 4 Label
External Module 5 Label
External Module 6 Label
External Module 7 Label
External Module 8 Label
External Module 9 Label
External Module 10 Label
External Module 11 Label
External Module 12 Label
External Module 13 Label
External Module 14 Label
External Module 15 Label
External Module 16 Label
Notes
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
External Module Port Assignment Block
R
R
R
R
R
R
R
R
Manual Control Relay Block
F2
F2
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-86
2: Modbus Map - Holding Registers
Line
Pt
DNP
Obj
Description
Addr. (hex)
Address(4X)
B4A4H-B4ABH
B4ACH-B4B3H
B4B4H-B4BBH
B4BCH-B4C3H
B4C4H-B4CBH
B4CCH-B4D3H
B4D4H-B4DBH
B4DCH-B4E3H
B4E4H-B4EBH
B4ECH-B4F3H
B4F4H
46245-46252
46253-46260
46261-46268
46269-46276
46277-46284
46285-46292
46293-46300
46301-46308
46309-46316
46317-46324
46325
Internal Input 3 Pulse Accumulation Label
Internal Input 4 Pulse Accumulation Label
Internal Input 5 Pulse Accumulation Label
Internal Input 6 Pulse Accumulation Label
Internal Input 7 Pulse Accumulation Label
Internal Input 8 Pulse Accumulation Label
Internal Input Pulse Aggregation 1 Label
Internal Input Pulse Aggregation 2 Label
Internal Input Pulse Aggregation 3 Label
Internal Input Pulse Aggregation 4 Label
Nexus Watthour Selection / Aggregation Assignment
B4F5H-B4F6H
B4F7H-B4F8H
46326-46327
46328-46329
I2t Threshold
2
V t Threshold
B4F9H
B4FAH
B4FBH
B4FCH
B4FDH
B4FEH-B4FFH
B500H-B501H
B502H-B503H
B504H-B505H
B506H-B507H
B508H
B509H
B50AH
B50BH
B50CH
B50DH
B50EH
B50FH
B510H
B511H
B512H-B523H
46330
46331
46332
46333
46334
46335-46336
46337-46338
46339-46340
46341-46342
46343-46344
46345
46346
46347
46348
46349
46350
46351
46352
46353
46354
46355-46372
B524H-B527H
B528H-B52BH
B52CH-B52FH
B530H-B533H
B534H-B537H
B538H-B53BH
B53CH-B53FH
B540H-B543H
B544H-B547H
B548H-B54BH
B54CH-B54FH
B550H-B553H
46373-46376
46377-46380
46381-46384
46385-46388
46389-46392
46393-46396
46397-46400
46401-46404
46405-46408
46409-46412
46413-46416
46417-46420
B554H-B555H
B556H-B557H
B558H-B559H
B55AH-B55BH
B55CH-B55DH
B55EH-B55FH
B560H-B561H
B562H-B563H
B564H
46421-46422
46423-46424
46425-46426
46427-46428
46429-46430
46431-46432
46433-46434
46435-46436
46437
Range
Units
Type
R/W
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
R
R
R
R
R
R
R
R
R
R
R
Notes
I2t and V2t Threshold Block
R
R
Internal KYZ Settings Block
Internal KYZ Pulse Width (Relay 1-Pulse 1/ Relay 2-Pulse 2)
Internal KYZ Pulse Width (Relay 3/ Relay 4)
Reserved / Internal KYZ Channel Select (Relay 1-Pulse 1)
Internal KYZ Channel Select (Relay 2-Pulse 2/ Relay 3)
Internal KHZ Channel Select (Relay 4/ Reserved)
Internal KYZ Watthour Per Pulse (Relay 1-Pulse 1)
Internal KYZ Watthour Per Pulse (Relay 2-Pulse 2)
Internal KYZ Watthour Per Pulse (Relay 3)
Internal KYZ Watthour Per Pulse (Relay 4)
Reserved
Internal KYZ enable/ End of Interval Pulse enable
End of Interval Pulse (Relay, Width)
Cold Load Delay / Cumulative Demand Settings
Short Term Flicker Interval / Long Term Flicker Interval
Flicker Voltage Adaptor Level
Flicker Base Frequency/Min power off
Block Average Cont.
Accum Mode/Reserved
Block Window Max/Min Interval 1
Block Window Max/Min Interval 2
Reserved
Internal Input Pulse Accumulation Unit Label Block
Internal Input 1 Pulse Accumulation Unit Label
Internal Input 2 Pulse Accumulation Unit Label
Internal Input 3 Pulse Accumulation Unit Label
Internal Input 4 Pulse Accumulation Unit Label
Internal Input 5 Pulse Accumulation Unit Label
Internal Input 6 Pulse Accumulation Unit Label
Internal Input 7 Pulse Accumulation Unit Label
Internal Input 8 Pulse Accumulation Unit Label
Internal Input Pulse Aggregation 1 Unit Label
Internal Input Pulse Aggregation 2 Unit Label
Internal Input Pulse Aggregation 3 Unit Label
Internal Input Pulse Aggregation 4 Unit Label
ElectroLogic Block
Relay 1 Combination Tree Input Line 1, Point 1
Relay 1 Combination Tree Input Line 2, Point 2
Relay 1 Combination Tree Input Line 3, Point 3
Relay 1 Combination Tree Input Line 4, Point 4
Relay 1 Combination Tree Input Line 5, Point 5
Relay 1 Combination Tree Input Line 6, Point 6
Relay 1 Combination Tree Input Line 7, Point 7
Relay 1 Combination Tree Input Line 8, Point 8
Relay 1 Combination Logic (Combination A/ Combination B)
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-87
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
B565H
B566H
B567H
B568H
B569H-B56BH
B56CH-B56DH
B56EH-B56FH
B570H-B571H
B572H-B573H
B574H-B575H
B576H-B577H
B578H-B579H
B57AH-B57BH
B57CH
B57DH
B57EH
B57FH
B580H
B581H-B583H
B584H-B585H
B586H-B587H
B588H-B589H
B58AH-B58BH
B58CH-B58DH
B58EH-B58FH
B590H-B591H
B592H-B593H
B594H
B595H
B596H
B597H
B598H
B599H-B59BH
B59CH-B59DH
B59EH-B59FH
B5A0H-B5A1H
B5A2H-B5A3H
B5A4H-B5A5H
B5A6H-B5A7H
B5A8H-B5A9H
B5AAH-B5ABH
B5ACH
B5ADH
B5AEH
B5AFH
B5B0H
B5B1H-B5B3H
B5B4H-B5B5H
B5B6H-B5B7H
B5B8H-B5B9H
B5BAH-B5BBH
B5BCH-B5BDH
B5BEH-B5BFH
B5C0H-B5C1H
B5C2H-B5C3H
B5C4H
B5C5H
B5C6H
B5C7H
46438
46439
46440
46441
46442-46444
46445-46446
46447-46448
46449-46450
46451-46452
46453-46454
46455-46456
46457-46458
46459-46460
46461
46462
46463
46464
46465
46466-46468
46469-46470
46471-46472
46473-46474
46475-46476
46477-46478
46479-46480
46481-46482
46483-46484
46485
46486
46487
46488
46489
46490-46492
46493-46494
46495-46496
46497-46498
46499-46500
46501-46502
46503-46504
46505-46506
46507-46508
46509
46510
46511
46512
46513
46514-46516
46517-46518
46519-46520
46521-46522
46523-46524
46525-46526
46527-46528
46529-46530
46531-46532
46533
46534
46535
46536
Line
Pt
DNP
Obj
Description
Range
Relay 1 Combination Logic (Combination C/ Combination D)
Relay 1 Combination Logic (Combination E/ Combination F)
Relay 1 Combination Logic (Combination G/ Reserved)
Relay 1 Set Delay/ Reset Delay
Reserved
Relay 2 Combination Tree Input Line 1, Point 1
Relay 2 Combination Tree Input Line 2, Point 2
Relay 2 Combination Tree Input Line 3, Point 3
Relay 2 Combination Tree Input Line 4, Point 4
Relay 2 Combination Tree Input Line 5, Point 5
Relay 2 Combination Tree Input Line 6, Point 6
Relay 2 Combination Tree Input Line 7, Point 7
Relay 2 Combination Tree Input Line 8, Point 8
Relay 2 Combination Logic (Combination A/ Combination B)
Relay 2 Combination Logic (Combination C/ Combination D)
Relay 2 Combination Logic (Combination E/ Combination F)
Relay 2 Combination Logic (Combination G/ Reserved)
Relay 2 Set Delay/ Reset Delay
Reserved
Relay 3 Combination Tree Input Line 1, Point 1
Relay 3 Combination Tree Input Line 2, Point 2
Relay 3 Combination Tree Input Line 3, Point 3
Relay 3 Combination Tree Input Line 4, Point 4
Relay 3 Combination Tree Input Line 5, Point 5
Relay 3 Combination Tree Input Line 6, Point 6
Relay 3 Combination Tree Input Line 7, Point 7
Relay 3 Combination Tree Input Line 8, Point 8
Relay 3 Combination Logic (Combination A/ Combination B)
Relay 3 Combination Logic (Combination C/ Combination D)
Relay 3 Combination Logic (Combination E/ Combination F)
Relay 3 Combination Logic (Combination G/ Reserved)
Relay 3 Set Delay/ Reset Delay
Reserved
Relay 4 Combination Tree Input Line 1, Point 1
Relay 4 Combination Tree Input Line 2, Point 2
Relay 4 Combination Tree Input Line 3, Point 3
Relay 4 Combination Tree Input Line 4, Point 4
Relay 4 Combination Tree Input Line 5, Point 5
Relay 4 Combination Tree Input Line 6, Point 6
Relay 4 Combination Tree Input Line 7, Point 7
Relay 4 Combination Tree Input Line 8, Point 8
Relay 4 Combination Logic (Combination A/ Combination B)
Relay 4 Combination Logic (Combination C/ Combination D)
Relay 4 Combination Logic (Combination E/ Combination F)
Relay 4 Combination Logic (Combination G/ Reserved)
Relay 4 Set Delay/ Reset Delay
Reserved
Relay 5 Combination Tree Input Line 1, Point 1
Relay 5 Combination Tree Input Line 2, Point 2
Relay 5 Combination Tree Input Line 3, Point 3
Relay 5 Combination Tree Input Line 4, Point 4
Relay 5 Combination Tree Input Line 5, Point 5
Relay 5 Combination Tree Input Line 6, Point 6
Relay 5 Combination Tree Input Line 7, Point 7
Relay 5 Combination Tree Input Line 8, Point 8
Relay 5 Combination Logic (Combination A/ Combination B)
Relay 5 Combination Logic (Combination C/ Combination D)
Relay 5 Combination Logic (Combination E/ Combination F)
Relay 5 Combination Logic (Combination G/ Reserved)
Units
Type
R/W
Notes
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-88
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
B5C8H
B5C9H-B5CBH
B5CCH-B5CDH
B5CEH-B5CFH
B5D0H-B5D1H
B5D2H-B5D3H
B5D4H-B5D5H
B5D6H-B5D7H
B5D8H-B5D9H
B5DAH-B5DBH
B5DCH
B5DDH
B5DEH
B5DFH
B5E0H
B5E1H-B5E3H
B5E4H-B5E5H
B5E6H-B5E7H
B5E8H-B5E9H
B5EAH-B5EBH
B5ECH-B5EDH
B5EEH-B5EFH
B5F0H-B5F1H
B5F2H-B5F3H
B5F4H
B5F5H
B5F6H
B5F7H
B5F8H
B5F9H-B5FBH
B5FCH-B5FDH
B5FEH-B5FFH
B600H-B601H
B602H-B603H
B604H-B605H
B606H-B607H
B608H-B609H
B60AH-B60BH
B60CH
B60DH
B60EH
B60FH
B610H
B611H-B613H
B614H-B615H
B616H-B617H
B618H-B619H
B61AH-B61BH
B61CH-B61DH
B61EH-B61FH
B620H-B621H
B622H-B623H
B624H
B625H
B626H
B627H
B628H
B629H-B62BH
B62CH-B62DH
46537
46538-46540
46541-46542
46543-46544
46545-46546
46547-46548
46549-46550
46551-46552
46553-46554
46555-46556
46557
46558
46559
46560
46561
46562-46564
46565-46566
46567-46568
46569-46570
46571-46572
46573-46574
46575-46576
46577-46578
46579-46580
46581
46582
46583
46584
46585
46586-46588
46589-46590
46591-46592
46593-46594
46595-46596
46597-46598
46599-46600
46601-46602
46603-46604
46605
46606
46607
46608
46609
46610-46612
46613-46614
46615-46616
46617-46618
46619-46620
46621-46622
46623-46624
46625-46626
46627-46628
46629
46630
46631
46632
46633
46634-46636
46637-46638
Line
Pt
DNP
Obj
Description
Range
Relay 5 Set Delay/ Reset Delay
Reserved
Relay 6 Combination Tree Input Line 1, Point 1
Relay 6 Combination Tree Input Line 2, Point 2
Relay 6 Combination Tree Input Line 3, Point 3
Relay 6 Combination Tree Input Line 4, Point 4
Relay 6 Combination Tree Input Line 5, Point 5
Relay 6 Combination Tree Input Line 6, Point 6
Relay 6 Combination Tree Input Line 7, Point 7
Relay 6 Combination Tree Input Line 8, Point 8
Relay 6 Combination Logic (Combination A/ Combination B)
Relay 6 Combination Logic (Combination C/ Combination D)
Relay 6 Combination Logic (Combination E/ Combination F)
Relay 6 Combination Logic (Combination G/ Reserved)
Relay 6 Set Delay/ Reset Delay
Reserved
Relay 7 Combination Tree Input Line 1, Point 1
Relay 7 Combination Tree Input Line 2, Point 2
Relay 7 Combination Tree Input Line 3, Point 3
Relay 7 Combination Tree Input Line 4, Point 4
Relay 7 Combination Tree Input Line 5, Point 5
Relay 7 Combination Tree Input Line 6, Point 6
Relay 7 Combination Tree Input Line 7, Point 7
Relay 7 Combination Tree Input Line 8, Point 8
Relay 7 Combination Logic (Combination A/ Combination B)
Relay 7 Combination Logic (Combination C/ Combination D)
Relay 7 Combination Logic (Combination E/ Combination F)
Relay 7 Combination Logic (Combination G/ Reserved)
Relay 7 Set Delay/ Reset Delay
Reserved
Relay 8 Combination Tree Input Line 1, Point 1
Relay 8 Combination Tree Input Line 2, Point 2
Relay 8 Combination Tree Input Line 3, Point 3
Relay 8 Combination Tree Input Line 4, Point 4
Relay 8 Combination Tree Input Line 5, Point 5
Relay 8 Combination Tree Input Line 6, Point 6
Relay 8 Combination Tree Input Line 7, Point 7
Relay 8 Combination Tree Input Line 8, Point 8
Relay 8 Combination Logic (Combination A/ Combination B)
Relay 8 Combination Logic (Combination C/ Combination D)
Relay 8 Combination Logic (Combination E/ Combination F)
Relay 8 Combination Logic (Combination G/ Reserved)
Relay 8 Set Delay/ Reset Delay
Reserved
Relay 9 Combination Tree Input Line 1, Point 1
Relay 9 Combination Tree Input Line 2, Point 2
Relay 9 Combination Tree Input Line 3, Point 3
Relay 9 Combination Tree Input Line 4, Point 4
Relay 9 Combination Tree Input Line 5, Point 5
Relay 9 Combination Tree Input Line 6, Point 6
Relay 9 Combination Tree Input Line 7, Point 7
Relay 9 Combination Tree Input Line 8, Point 8
Relay 9 Combination Logic (Combination A/ Combination B)
Relay 9 Combination Logic (Combination C/ Combination D)
Relay 9 Combination Logic (Combination E/ Combination F)
Relay 9 Combination Logic (Combination G/ Reserved)
Relay 9 Set Delay/ Reset Delay
Reserved
Relay 10 Combination Tree Input Line 1, Point 1
Units
Type
R/W
Notes
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-89
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
B62EH-B62FH
B630H-B631H
B632H-B633H
B634H-B635H
B636H-B637H
B638H-B639H
B63AH-B63BH
B63CH
B63DH
B63EH
B63FH
B640H
B641H-B643H
B644H-B645H
B646H-B647H
B648H-B649H
B64AH-B64BH
B64CH-B64DH
B64EH-B64FH
B650H-B651H
B652H-B653H
B654H
B655H
B656H
B657H
B658H
B659H-B65BH
B65CH-B65DH
B65EH-B65FH
B660H-B661H
B662H-B663H
B664H-B665H
B666H-B667H
B668H-B669H
B66AH-B66BH
B66CH
B66DH
B66EH
B66FH
B670H
B671H-B673H
B674H-B675H
B676H-B677H
B678H-B679H
B67AH-B67BH
B67CH-B67DH
B67EH-B67FH
B680H-B681H
B682H-B683H
B684H
B685H
B686H
B687H
B688H
B689H-B68BH
B68CH-B68DH
B68EH-B68FH
B690H-B691H
B692H-B693H
46637-4663846639-46640
46641-46642
46643-46644
46645-46646
46647-46648
46649-46650
46651-46652
46653
46654
46655
46656
46657
46658-46660
46661-46662
46663-46664
46665-46666
46667-46668
46669-46670
46671-46672
46673-46674
46675-46676
46677
46678
46679
46680
46681
46682-46684
46685-46686
46687-46688
46689-46690
46691-46692
46693-46694
46695-46696
46697-46698
46699-46700
46701
46702
46703
46704
46705
46706-46708
46709-46710
46711-46712
46713-46714
46715-46716
46717-46718
46719-46720
46721-46722
46723-46724
46725
46726
46727
46728
46729
46730-46732
46733-46734
46735-46736
46737-46738
46739-46740
Line
Pt
DNP
Obj
Description
Range
Relay 10 Combination Tree Input Line 2, Point 2
Relay 10 Combination Tree Input Line 3, Point 3
Relay 10 Combination Tree Input Line 4, Point 4
Relay 10 Combination Tree Input Line 5, Point 5
Relay 10 Combination Tree Input Line 6, Point 6
Relay 10 Combination Tree Input Line 7, Point 7
Relay 10 Combination Tree Input Line 8, Point 8
Relay 10 Combination Logic (Combination A/ Combination B)
Relay 10 Combination Logic (Combination C/ Combination D)
Relay 10 Combination Logic (Combination E/ Combination F)
Relay 10 Combination Logic (Combination G/ Reserved)
Relay 10 Set Delay/ Reset Delay
Reserved
Relay 11 Combination Tree Input Line 1, Point 1
Relay 11 Combination Tree Input Line 2, Point 2
Relay 11 Combination Tree Input Line 3, Point 3
Relay 11 Combination Tree Input Line 4, Point 4
Relay 11 Combination Tree Input Line 5, Point 5
Relay 11 Combination Tree Input Line 6, Point 6
Relay 11 Combination Tree Input Line 7, Point 7
Relay 11 Combination Tree Input Line 8, Point 8
Relay 11 Combination Logic (Combination A/ Combination B)
Relay 11 Combination Logic (Combination C/ Combination D)
Relay 11 Combination Logic (Combination E/ Combination F)
Relay 11 Combination Logic (Combination G/ Reserved)
Relay 11 Set Delay/ Reset Delay
Reserved
Relay 12 Combination Tree Input Line 1, Point 1
Relay 12 Combination Tree Input Line 2, Point 2
Relay 12 Combination Tree Input Line 3, Point 3
Relay 12 Combination Tree Input Line 4, Point 4
Relay 12 Combination Tree Input Line 5, Point 5
Relay 12 Combination Tree Input Line 6, Point 6
Relay 12 Combination Tree Input Line 7, Point 7
Relay 12 Combination Tree Input Line 8, Point 8
Relay 12 Combination Logic (Combination A/ Combination B)
Relay 12 Combination Logic (Combination C/ Combination D)
Relay 12 Combination Logic (Combination E/ Combination F)
Relay 12 Combination Logic (Combination G/ Reserved)
Relay 12 Set Delay/ Reset Delay
Reserved
Relay 13 Combination Tree Input Line 1, Point 1
Relay 13 Combination Tree Input Line 2, Point 2
Relay 13 Combination Tree Input Line 3, Point 3
Relay 13 Combination Tree Input Line 4, Point 4
Relay 13 Combination Tree Input Line 5, Point 5
Relay 13 Combination Tree Input Line 6, Point 6
Relay 13 Combination Tree Input Line 7, Point 7
Relay 13 Combination Tree Input Line 8, Point 8
Relay 13 Combination Logic (Combination A/ Combination B)
Relay 13 Combination Logic (Combination C/ Combination D)
Relay 13 Combination Logic (Combination E/ Combination F)
Relay 13 Combination Logic (Combination G/ Reserved)
Relay 13 Set Delay/ Reset Delay
Reserved
Relay 14 Combination Tree Input Line 1, Point 1
Relay 14 Combination Tree Input Line 2, Point 2
Relay 14 Combination Tree Input Line 3, Point 3
Relay 14 Combination Tree Input Line 4, Point 4
Units
Type
R/W
Notes
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-90
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
B694H-B695H
B696H-B697H
B698H-B699H
B69AH-B69BH
B69CH
B69DH
B69EH
B69FH
B6A0H
B6A1H-B6A3H
B6A4H-B6A5H
B6A6H-B6A7H
B6A8H-B6A9H
B6AAH-B6ABH
B6ACH-B6ADH
B6AEH-B6AFH
B6B0H-B6B1H
B6B2H-B6B3H
B6B4H
B6B5H
B6B6H
B6B7H
B6B8H
B6B9H-B6BBH
B6BCH-B6BDH
B6BEG-B6BFH
B6C0H-B6C1H
B6C2H-B6C3H
B6C4H-B6C5H
B6C6H-B6C7H
B6C8H-B6C9H
B6CAH-B6CBH
B6CCH
B6CDH
B6CEH
B6CFH
B6D0H
B6D1H-B6D3H
46741-46742
46743-46744
46745-46746
46747-46748
46749
46750
46751
46752
46753
46754-46756
46757-46758
46759-46760
46761-46762
46763-46764
46765-46766
46767-46768
46769-46770
46771-46772
46773
46774
46775
46776
46777
46778-46780
46781-46782
46783-46784
46785-46786
46787-46788
46789-46790
46791-46792
46793-46794
46795-46796
46797
46798
46799
46800
46801
46802-46804
B6D4H-B6DBH
B6DCH-B6E3H
B6E4H-B6EBH
B6ECH-B6F3H
B6F4H-B6FBH
B6FCH-B703H
B704H-B70BH
B70CH-B713H
B714H-B71BH
B71CH-B723H
B724H-B72BH
B72CH-B733H
B734H-B73BH
B73CH-B743H
B744H-B74BH
B74CH-B753H
B754H-B75BH
B75CH-B763H
B764H-B76BH
B76CH-B773H
B774H-B77BH
46805-46812
46813-46820
46821-46828
46829-46836
46837-46844
46845-46852
46853-46860
46861-46868
46869-46876
46877-46884
46885-46892
46893-46900
46901-46908
46909-46916
46917-46924
46925-46932
46933-46940
46941-46948
46949-46956
46957-46964
46965-46972
Line
Pt
DNP
Obj
Description
Range
Relay 14 Combination Tree Input Line 5, Point 5
Relay 14 Combination Tree Input Line 6, Point 6
Relay 14 Combination Tree Input Line 7, Point 7
Relay 14 Combination Tree Input Line 8, Point 8
Relay 14 Combination Logic (Combination A/ Combination B)
Relay 14 Combination Logic (Combination C/ Combination D)
Relay 14 Combination Logic (Combination E/ Combination F)
Relay 14 Combination Logic (Combination G/ Reserved)
Relay 14 Set Delay/ Reset Delay
Reserved
Relay 15 Combination Tree Input Line 1, Point 1
Relay 15 Combination Tree Input Line 2, Point 2
Relay 15 Combination Tree Input Line 3, Point 3
Relay 15 Combination Tree Input Line 4, Point 4
Relay 15 Combination Tree Input Line 5, Point 5
Relay 15 Combination Tree Input Line 6, Point 6
Relay 15 Combination Tree Input Line 7, Point 7
Relay 15 Combination Tree Input Line 8, Point 8
Relay 15 Combination Logic (Combination A/ Combination B)
Relay 15 Combination Logic (Combination C/ Combination D)
Relay 15 Combination Logic (Combination E/ Combination F)
Relay 15 Combination Logic (Combination G/ Reserved)
Relay 15 Set Delay/ Reset Delay
Reserved
Relay 16 Combination Tree Input Line 1, Point 1
Relay 16 Combination Tree Input Line 2, Point 2
Relay 16 Combination Tree Input Line 3, Point 3
Relay 16 Combination Tree Input Line 4, Point 4
Relay 16 Combination Tree Input Line 5, Point 5
Relay 16 Combination Tree Input Line 6, Point 6
Relay 16 Combination Tree Input Line 7, Point 7
Relay 16 Combination Tree Input Line 8, Point 8
Relay 16 Combination Logic (Combination A/ Combination B)
Relay 16 Combination Logic (Combination C/ Combination D)
Relay 16 Combination Logic (Combination E/ Combination F)
Relay 16 Combination Logic (Combination G/ Reserved)
Relay 16 Set Delay/ Reset Delay
Reserved
Limit Profile Label Block
Limit 1 Label
Limit 2 Label
Limit 3 Label
Limit 4 Label
Limit 5 Label
Limit 6 Label
Limit 7 Label
Limit 8 Label
Limit 9 Label
Limit 10 Label
Limit 11 Label
Limit 12 Label
Limit 13 Label
Limit 14 Label
Limit 15 Label
Limit 16 Label
Limit 17 Label
Limit 18 Label
Limit 19 Label
Limit 20 Label
Limit 21 Label
Units
Type
R/W
Notes
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-91
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
B77CH-B783H
B784H-B78BH
B78CH-B793H
B794H-B79BH
B79CH-B7A3H
B7A4H-B7ABH
B7ACH-B7B3H
B7B4H-B7BBH
B7BCH-B7C3H
B7C4H-B7CBH
B7CCH-B7D3H
46973-46980
46981-46988
46989-46996
46997-47004
47005-47012
47213-47020
47021-47028
47029-47036
47037-47044
47045-47052
47053-47060
B7D4H
B7D5H
47061
47062
Line
Pt
DNP
Obj
Description
Range
Units
Limit 22 Label
Limit 23 Label
Limit 24 Label
Limit 25 Label
Limit 26 Label
Limit 27 Label
Limit 28 Label
Limit 29 Label
Limit 30 Label
Limit 31 Label
Limit 32 Label
Type
R/W
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
R
R
R
R
R
R
R
R
R
R
R
Notes
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
ch.7
External Analog Output Module Channel Update Block
B7D6H
47063
B7D7H
47064
B7D8H
47065
B7D9H
47066
B7DAH-B7DDH
47067-47070
B7DEH
47071
B7DFH
47072
B7E0H
47073
B7E1H-B7FFH
47074-47104
Module 1/ Module 2
Module 3/ Module 4
R
R
DNP Block
Miscellaneous DNP Settings Block
MSB: Scale for Analog Output of Average Pulse Accumulation
LSB: Compressed DNP Mapping
MSB: Energy in the interval
LSB:
DNP Time synchronization
DNP Time Synchronization Time Interval
Bit[15-14]: DNP Configuration
00: DNP Level 1
01: DNP Level 2
10: Reserved
11: DNP Level 1
Bit 13: Class 0 Counter Object
0: Object 20
1: Object 21
Bit 12: DNP Freeze Schedule
0: Disable
1: Enable
Bit 11: DNP Unsolicited Response Mode
0: Off
1: On
Bit 10: DNP Disable Unsolicited Response On Startup
0: No
1: Yes
Bit 9: DNP Enable Unsolicited Response for Class 1
0: No
1: Yes
Bit 8: DNP Enable Unsolicited Response for Class 1
0: No
1: Yes
Bit 7: DNP Enable Unsolicited Response for Class 3
0: No
1: Yes
Bits[0-6]: Reserved
DNP Freeze Date & Time
12/31/9999 23:59:59.99
DNP Freeze Interval
MSB: Hour
LSB:
Minute
DNP Unsolicited Response: Destination Address
MSB first: from 1 to 65519
R
R
R
R
10 msec
F3
R
R
DNP Unsolicited Response:
High Byte: Confirmation Timoeut - from 1 sec to 60 sec
Low Byte: Number of Retry - from 1 to 16, but 16 retry forever
Reserved
Custom DNP Definition Block for Analog Input (Object 30)
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-92
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
B800H
47105
B801H
47106
B802H
47107
B803H
47108
B804H-B8FFH
47109-47360
B900H
47361
B901H
47362
B902H-B903H
47363-47364
B904H
47365
B905H-B907H
B908H-B93FH
47366-47368
47369-47424
B940H
47425
B941H
47426
B942H-B943H
B944H-B95FH
47427-47428
47429-47456
B960H
B961H
47457
47458
B962H
47459
B963H
47460
B964H
47461
B965H
47462
B966H
47463
B967H
47464
B968H-B969H
B96AH-B96BH
B96CH-B96DH
B96EH-B96FH\
47465
47466
47467
47468
Line
Pt
DNP
Obj
Description
Range
Point 0: Line Number
Line
Number from an analog input readings, such as 34 (One second
Phase-Neutron Voltage Update)
Point 0:
MSB: Point Number
Point
Number from an analog input readings, such as 0 (Phase A-N
Voltage from One secod phase-neutron voltage)
LSB: Reserved
Point 0: Deadband
-328% / +328%
Point 0:
MSB: Class Assignment (8 bit bitmap)
LSB: Reserved
Point 1 - Point 63
Custom DNP Definition Block for Binary Counter (Object 20)
Point 0: Line Number
Line
Number from an accumulation readings, such as 537 (Energy
Scaled)
Point 0:
MSB: Point Number
Point
Number from an accumulation readings, such as 0 (Positive Wh
(Quadrant 1+4) from Energy Scaled)
LSB: Scaling
Point 0: Delta values for Event to occur
Point 0:
MSB: Class Assignment (8 bit bitmap)
LSB: Reserved
Point 0, reserved
Point 1 - Point 8
Custom DNP Definition Block for Binary Input (Object 1)
Point 0-7: Line Number
Line
Number from a binary input readings, such as 233 (Low Speed
(Internal) Inputs)
Point 0-7:
MSB: Point Number
Point
Number from a binary input readings, such as 0 (Input 1 from Low
Speed (Internal) Inputs)
LSB: Class Assignment (8 bit bitmap)
Point 0-7: Reserved
Point 8-15 - Point 57-64
Custom DNP Definition Block for Binary Output (Object 10)
Relay: Enable/Disable
Reset: Enable/Disable
Custom DNP Definition Block for Global Values
Choice Of Variation 0:
MSB: For Binary Input (Object 1)
LSB: For Binary Input Change (Object 2)
Choice Of Variation 0:
MSB: For Binary Counter (Object 20)
Choice Of Variation 0:
MSB: For Counter Change Event (Object 22)
LSB: For Frozen Counter Event (Object 23)
Choice Of Variation 0:
MSB: For Analog Input (Object 30)
LSB: For Frozen Analog Input (Object 31)
Choice Of Variation 0:
MSB: For Analog Change Event (Object 32)
LSB: For Frozen Analog Event (Object 33)
MSB: Custom 16-bit Scaling Enable
LSB: Reserved
Scale for Ia, b, c, n
+32767 A / 0 A
Scale for Iaux
+32767 A / 0 A
Scale for Van, bn, cn
+32767 V / 0 V
Scale for Vaux
+32767 V / 0 V
Units
Type
R/W
Notes
R
R
0.01%
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
1/ 65536 A sec
1/ 65536 A sec
1/ 65536 V sec
1/ 65536 V sec
F7
F7
F7
F7
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-93
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
B970H-B971H
B972H-B973H
B974H-B975H
B976H-B977H
B978H-B979H
B97AH-BDFFH
BE00H-C27FH
47469
47470
47471
47472
47473
47474-48640
48641-49792
C280H-C287H
C288H-C28FH
C290H-C297H
C298H-C29FH
C2A0H-C2A7H
C2A8H-C2AFH
C2B0H-C2B7H
C2B8H-C2BFH
C2C0H-C2C7H
C2C8H-C2CFH
C2D0H-C2D7H
C2D8H-C2DFH
C2E0H-C2E7H
C2E8H-C2EFH
C2F0H-C2F7H
C2F8H-C2FFH
C300H-C307H
C308H-C30FH
C310H-C317H
C318H-C31FH
C320H-C327H
C328H-C32FH
C330H-C337H
C338H-C33FH
C340H-C347H
C348H-C34FH
C350H-C357H
C358H-C35FH
C360H-C367H
C368H-C36FH
C370H-C377H
C378H-C37FH
C380H-C387H
C388H-C38FH
C390H-C397H
C398H-C39FH
C3A0H-C3A7H
C3Q8H-C3AFH
C3B0H-C3B7H
C3B8H-C3BFH
C3C0H-C3C7H
C3C8H-C3CFH
C3D0H-C3D7H
C3D8H-C3DFH
C3E0H-C3E7H
C3E8H-C3EFH
C3F0H-C3F7H
C3F8H-C3FFH
49793-49800
49801-49808
49809-49816
49817-49824
49825-49832
49833-49840
49841-49848
49849-49856
49857-49864
49865-49872
49873-49880
49881-49888
49889-49896
49897-49904
49905-49912
49913-49920
49921-49928
49929-49936
49937-49944
49945-49952
49953-49960
49961-49968
49969-49976
49977-49984
49985-49992
49993-50000
50001-50008
50009-50016
50017-50024
50025-50032
50033-50040
50041-50048
50049-50056
50057-50064
50065-50072
50073-50080
50081-50088
50089-50096
50097-50104
50105-50112
50113-50120
50121-50128
50129-50136
50137-50144
50145-50152
50153-50160
50161-50168
50169-50176
C400H-C45FH
50177-50272
Line
Pt
DNP
Obj
Description
Scale for Vab, bc, ca
Scale for Power a, b, c
Scale for Total Power
Scale for Frequency (High End)
Scale for Frequency (Low End)
Reserved
Reserved
Range
Units
Type
R/W
+32767 V / 0 V
+32767 W / -32768 W
+32767 W / -32768 W
+32767 Hz / -32768 Hz
+32767 Hz / -32768 Hz
1/ 65536 V sec
1/ 65536 W sec
1/ 65536 W sec
1/ 65536 Hz
1/ 65536 Hz
F7
F7
F7
F7
F7
R
R
R
R
R
External Digital Output Module Labels Block
Module 1 Relay Label 1
Module 1 Relay Label 2
Module 1 Relay Label 3
Module 1 Relay Label 4
Module 2 Relay Label 1
Module 2 Relay Label 2
Module 2 Relay Label 3
Module 2 Relay Label 4
Module 3 Relay Label 1
Module 3 Relay Label 2
Module 3 Relay Label 3
Module 3 Relay Label 4
Module 4 Relay Label 1
Module 4 Relay Label 2
Module 4 Relay Label 3
Module 4 Relay Label 4
Module 1 Relay Common Shorted to Normally Closed Label 1
Module 1 Relay Common Shorted to Normally Closed Label 2
Module 1 Relay Common Shorted to Normally Closed Label 3
Module 1 Relay Common Shorted to Normally Closed Label 4
Module 2 Relay Common Shorted to Normally Closed Label 1
Module 2 Relay Common Shorted to Normally Closed Label 2
Module 2 Relay Common Shorted to Normally Closed Label 3
Module 2 Relay Common Shorted to Normally Closed Label 4
Module 3 Relay Common Shorted to Normally Closed Label 1
Module 3 Relay Common Shorted to Normally Closed Label 2
Module 3 Relay Common Shorted to Normally Closed Label 3
Module 3 Relay Common Shorted to Normally Closed Label 4
Module 4 Relay Common Shorted to Normally Closed Label 1
Module 4 Relay Common Shorted to Normally Closed Label 2
Module 4 Relay Common Shorted to Normally Closed Label 3
Module 4 Relay Common Shorted to Normally Closed Label 4
Module 1 Relay Common Shorted to Normally Opened Label 1
Module 1 Relay Common Shorted to Normally Opened Label 2
Module 1 Relay Common Shorted to Normally Opened Label 3
Module 1 Relay Common Shorted to Normally Opened Label 4
Module 2 Relay Common Shorted to Normally Opened Label 1
Module 2 Relay Common Shorted to Normally Opened Label 2
Module 2 Relay Common Shorted to Normally Opened Label 3
Module 2 Relay Common Shorted to Normally Opened Label 4
Module 3 Relay Common Shorted to Normally Opened Label 1
Module 3 Relay Common Shorted to Normally Opened Label 2
Module 3 Relay Common Shorted to Normally Opened Label 3
Module 3 Relay Common Shorted to Normally Opened Label 4
Module 4 Relay Common Shorted to Normally Opened Label 1
Module 4 Relay Common Shorted to Normally Opened Label 2
Module 4 Relay Common Shorted to Normally Opened Label 3
Module 4 Relay Common Shorted to Normally Opened Label 4
Reserved Block
Reserved
Customizable Modbus Map Settings Block
Notes
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-94
2: Modbus Map - Holding Registers
Line
Pt
DNP
Obj
Description
Range
Addr. (hex)
Address(4X)
C460H-C461H
C462H-C65FH
50273-50274
50275-50784
Line 1, Point 1
Line 2, Point 2 - Line 256, Point 256
C660H
C661H
C662H-C663H
C664H-C665H
C666H-C667H
C668H-C669H
C66AH
C66BH
C66CH-C6ABH
50785
50786
50787-50788
50789-50790
50791-50792
50793-50794
50795
50796
50797-50860
Enable/ Disable
TFTP Port
Client IP
Server IP
Default Gateway
Subnet Mask
Email Mode
FTP Download
Download Filename (128 Bytes)
C6ACH-C6CBH
50861-50892
Email Server IP Addres / Name (64 bytes)
C6CCH-C6EBH
C6ECH-C70BH
C70CH-C72BH
C72CH-C73BH
C73CH-C74BH
C74CH-C7CBH
C7CCH-C7D3H
50893-50924
50925-50956
50957-50988
50989-51004
51005-51020
51021-51148
51149-51156
Nxs Comm Email Processing Service IP Address / Name (64 bytes)
Return / Reply Address (64 bytes)
Email Subject Text (64 Bytes)
Email Username (32 Bytes)
Email Password (32 Bytes)
Reserved
Reserved
DNP LAN/WAN
MSB: Mode
LSB: Bitmap Set
MSB: UDP Addressing
LSB: Validate Source IPs
TCP Listen Port
UDP Listen Port
Valid IP Address 1
Valid IP Address 2
Valid IP Address 3
Valid IP Address 4
Valid IP Subnet Mask 1
Valid IP Subnet Mask 2
Valid IP Subnet Mask 3
Valid IP Subnet Mask 4
TCP Starting Valid Client Ports
TCP Ending Valid Client Ports
UDP Starting Valid Client Ports
UDP Ending Valid Client Ports
Reserved
UDP Respond Port
Device Address
Reserved
Customizable Modbus Map Format Block
Custom Modbus Point 1 Style / Format
Custom Modbus Point 1 Unit / Special
Custom Modbus Points 2-256 Style / Format and Unit / Special
Energy Scale Settings
Q1234 VAh/ Q12 VARh
Q34 VARh/ Q14 Wh
Q1 VAh/ Q1 VARh
Q4 VAh/ Q4 VARh
Q23 Wh/ Q2 VAh
Q2 VARh/ Q3 VAh
Q3 VARh/ I2t Phase A
I2t Phase B/ I2t Phase C
2
2
V t Phase A/ V t Phase B
Units
Type
R/W
Notes
R
R
Network Settings 10/100 Card
Auto TFTP Download Settings
Email Client settings
C7D4H
51157
C7D5H
51158
C7D6H
C7D7H
C7D8H-C7D9H
C7DAH-C7DBH
C7DCH-C7DDH
C7DEH-C7DFH
C7E0H-C7E1H
C7E2H-C7E3H
C7E4H-C7E5H
C7E6H-C7E7H
C7E8H-C7EBH
C7ECH-C7EFH
C7F0H-C7F3H
C7F4H-C7F7H
C7F8H-C7F9H
C7FAH
C7FBH
C7FCH-C7FFH
51159
51160
51161-51162
51163-51164
51165-61166
51167-51168
51169-51170
51171-51172
51173-51174
51175-51176
51177-51180
51181-51184
51185-51188
51189-51192
51193-51194
51195
51196-51200
C800H
C801H
C802H-C9FFH
51201
51202
51203-51712
CA00H
CA01H
CA02H
CA03H
CA04H
CA05H
CA06H
CA07H
CA08H
51713
51714
51715
51716
51717
51718
51719
51720
51721
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
F65
F65
F65
F65
F65
F65
F65
F65
F65
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-95
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
CA09H
CA0AH
CA0BH
CA0CH
51722
51723
51724
51725
CA0DH
CA0EH
CA0FH-CA13H
CA14H
CA15H
CA16H
CA17H
CA18H
CA19H
CA1AH
51726
51727
51728-51732
51733
51734
51735
51736
51737
51738
51739
CA1BH
51740
CA1CH-CA1DH
CA1EH-CA1FH
CA20H-CA21H
CA22H-CA94H
51741-51742
51743-51744
51745-51746
51747-51861
CA95H
CA96H
CA97H
CA98H-CC14H
51862
51863
51864
51865-52245
CA95H
CA96H
CA97H
CA98H-CC14H
CC15H-CEEFH
51862
51863
51864
51865-52245
52246-52976
CEF0H-CF6FH
CF70H-CFEFH
CFF0H
CFF1H
CFF2H
CFF3H
CFF4H-CFF5H
CFF6H
CFF7H
CFF8H
CFF9H
CFFAH
CFFBH-CFFEH
CFFFH
52977-53104
53105-53232
53233
53234
53235
53236
53237-53238
53239
53240
53241
53242
53243
53244-53247
53248
D000H
D001H
D002H
D003H
D004H
D005H
D006H
D007H
D008H
D009H
D00AH
D00BH
53249
53250
53251
53252
53253
53254
53255
53256
53257
53258
53259
53260
Line
Pt
DNP
Obj
Description
Range
Units
2
Type
V t Phase C/ Q1 Wh
Q4 Wh/ Q2 Wh
Q3 Wh/ Q1234 VAh, Uncompensated
Q12 VARh, Uncompensated/ Q34 VARh, Uncompensated
F65
F65
F65
F65
Q14 Wh, Uncompensated/ Q23 Wh, Uncompensated
+Qh/ -Qh
Reserved
Pulse Accumulation, Input 1/ Pulse Accumulation Input 2
Pulse Accumulation, Input 3/ Pulse Accumulation Input 4
Pulse Accumulation, Input 5/ Pulse Accumulation Input 6
Pulse Accumulation, Input 7/ Pulse Accumulation Input 8
Pulse Aggregation 1/ Pulse Aggregation 2
Pulse Aggregation 3/ Pulse Aggregation 4
SYNCH connection (Yes/No 1-255/0) / FVF change per day (1-50)
MSB: KYZ Operation Status Enable
LSB: KYZ Operation Satus Selection: KYZ1=0; KYZ2=1; KYZ3=2;
KYZ4=3
TDD Reference Voltage
TDD Reference Current
EN50160 Nominal Voltage
Reserved
Nexus 15xx Master RTU Block (Modbus RTU only Func Code 0x03 Only)
Polling Order 1/ Device address
Starting Modbus address
Number of Register
Repeat 127 times
Accumulator/Aggregators Limit
Polling Order 1/ Device address
Starting Modbus address
Number of Register
Repeat 127 times
Reserved
Update Settings Block
User Memo Field (256 bytes)
Name of User Who Last Updated the Profile (256 bytes)
Device Profile Version (Year)
Device Profile Version (Month/ Day)
Device Profile Version (Build)
Pro Software ID
Electro Industries Device Type (Base Unit)
Electro Industries Device Type (Option 1/ Option 2)
Electro Industries Device Type (Option 3/ Option 4)
Update Programming Software Version Number (Major)
Update Programming Software Version Number (Minor)
Update Programming Software Version Number (Revision)
Update Time
Programmable Settings Block Checksum
12-Bit RTU Block
Sanity Rregister
Phase A Current
+5 A / 0 A
5 / 2048 A sec
Phase B Current
+5 A / 0 A
5 / 2048 A sec
Phase C Current
+5 A / 0 A
5 / 2048 A sec
Phase A-N Voltage
+150 V / 0 V
150 / 2048 V sec
Phase B-N Voltage
+150 V / 0 V
150 / 2048 V sec
Phase C-N Voltage
+150 V / 0 V
150 / 2048 V sec
Total Watt
+1500 W / -1500 W
1500 / 2048 W sec
Total VAR
+1500 VAR / -1500 VAR
1500 / 2048 VAR sec
Phase A Watt
+1500 W / -1500 W
1500 / 2048 W sec
Phase B Watt
+1500 W / -1500 W
1500 / 2048 W sec
Phase C Watt
+1500 W / -1500 W
1500 / 2048 W sec
F65
F65
R/W
Notes
F65
F65
F65
F65
F65
F65
F47
F49
F7
F7
R
R
F58
F59
F59
F59
F59
F59
F59
F59
F59
F59
F59
F59
R
R
R
R
R
R
R
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-96
2: Modbus Map - Holding Registers
DNP
Obj
Addr. (hex)
Address(4X)
Range
Units
Type
R/W
D00CH
D00DH
D00EH
D00FH-D010H
D011H
D012H-D013H
D014H-D015H
53261
53262
53263
53264-53265
53266
53267-53268
53269-53270
Phase A VAR
Phase B VAR
Phase C VAR
Reserved
Computed Neutral Current
Positive Watthour
Negative Watthour
+1500 VAR / -1500 VAR
+1500 VAR / -1500 VAR
+1500 VAR / -1500 VAR
1500 / 2048 VAR sec
1500 / 2048 VAR sec
1500 / 2048 VAR sec
F59
F59
F59
R
R
R
+5 A / 0 A
+99,999,999 kWh / 0 kWh
0 kWh / +99,999,999 kWh
5 / 2048 A sec
1 kWh pri
1 kWh pri
F59
F60
F60
R
R
R
D016H-D017H
53271-53272
Positive VARhour
+99,999,999 kVARh / 0 kVARh 1 kVARh pri
F60
R
D018H-D019H
D01AH
D01BH-D062H
D063H
53273-53274
53275
53276-53347
53348
Negative VARhour
Frequency
Reserved
Energy Reset
0 kVARh / +99,999,999 kVARh 1 kVARh pri
45 Hz / 75 Hz
30 / 4096 Hz
F60
F61
R
R
D800H-DFFFH
55296-57344
NVRAM readings (Diagnostic Purpose only)
E000H
E001H
E002H
E003H
E004H-E022H
E023H
E024H
E025H
E029H
E02BH
E02DH
E02EH
E02FH
E030H
E032H
E033H
E034H
E035H
E036H
E037H
E038H
E039H
E03AH
E03BH
E03CH
E03DH
E03EH
E04AH
E04BH
E04CH
E04DH
E04EH
E04FH
E050H
E053H
E0A4H
E0AAH
E0ABH
E0ACH
57345
57346
57347
57348
57349-57379
57380
57381
57382
57386
57388
57390
57391
57392
57393
57395
57396
57397
57398
57399
57400
57401
57402
57403
57404
57405
57406
57407
57419
57420
57421
57422
57423
57424
57425
57428
57509
57515
57516
57517
F2A0H-F2DFH
F2E0H-F2E7H
F2E8H
62113-62176
62177-62184
62185
Line
Pt
Description
Notes
W
NVRAM Window
Action Block
Log Reset
Maximum Reset
Minimum Reset
Energy Reset
Reserved
Internal KYZ Enable
Flicker Action
Enumeration
Undefined
Reset Time Of Use Current Month
Reset Internal Input Accumulations and Aggregations
Refresh External IO Header Information
Refresh External IO Programming Information
Relay Locking Relay Selection
Relay Locking Action Selection
Reset Test Mode Data
Reset KYZ Output Accumulations
Reset Cumulative Demand
Reset Historical Log 1
Reset Historical Log 2
Reset Sequence of Events Log (limit alarm log)
Reset Digital Input Log
Reset Relay Output Log
Reset EN50160 10min Trending Log
Reset Waveform Log
Reset PQ Log
Reset System Event Log
Reset Total Average Power Factor
Reset Historical Log 3
Reset Historical Log 4
Reset Historical Log 5
Reset Historical Log 6
Reset Historical Log 7
Reset Historical Log 8
Reset Event Triggered Log
Reset Core Trending log
Reset Time of Use Current Season/week/day
Time of Use Manual Read Season/week/day Block Data
Time of Use Manual Read Month Block Data
(all TOU data, and resets under command E001, E002, E003, E02B
Passoword extended
Ciphertext
Seed
System Security Status
W
W
W
W
Ch.5
R/W
R/W
R/W
R/W
R/W
W
W
R/W
R/W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
R/W
R
R
Security
Security
Security
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-97
2: Modbus Map - Holding Registers
Line
Pt
DNP
Obj
Description
Range
Units
Type
Addr. (hex)
Address(4X)
F2E9H
F2EAH
F2EBH-F2EFH
F2F0H
F2F1H
F2F2H
F2F3H
F2F4H
62186
62187
62188-62192
62193
62194
62195
62196
62197
F900H-F903H
F904H-F905H
F906H-F907H
F908H-F909H
F90AH-F90BH
F90CH-F90DH
F90EH-F90FH
F910H-F911H
F912H-F913H
F914H-F915H
F916H-F917H
F918H-F919H
F91AH-F91BH
F91CH-F91DH
F91EH-F91FH
F920H-F921H
F922H-F923H
F924H-F925H
F926H-F927H
F928H-F929H
F92AH-F92BH
F92CH-F92DH
F92EH-F92FH
F930H-F931H
F932H-F933H
F934H-F935H
F936H-F937H
F938H-F939H
F93AH-F93BH
F93CH-F93DH
F93EH-F93FH
F940H-F941H
F942H-F943H
F944H-F945H
F946H-F947H
F948H-F949H
F94AH-F94BH
63745-63748
63749-63750
63751-63752
63753-63754
63755-63756
63757-63758
63759-63760
63761-63762
63763-63764
63765-63766
63767-63768
63769-63770
63771-63772
63773-63774
63775-63776
63777-63778
63779-63780
63781-63782
63783-63784
63785-63786
63787-63788
63789-63790
63791-63792
63793-63794
63795-63796
63797-63798
63799-63800
63801-63802
63803-63804
63805-63806
63807-63808
63809-63810
63811-63812
63813-63814
63815-63816
63817-63818
63819-63820
FE13H-FE16H
FE17H-FE20H
65044-65047
65048-65057
Security Access Status
Session Role Index
Session Privilege
Remaing Block Timeout Left
User Index
Session Inactivity Timeout Left
Remaing Seed Timeout Left
Inactivity Timeout
3second RMS Result Frame 150cycles for 50Hz sytem, 180cycles for 60HZ sytem
3 sec Update RTC Timestamp
12/31/9999 23:59:59.99
10 msec
3 sec RMS Phase A-N Voltage
-32767.999/+32767.999
Volts
3 sec RMS Phase B-N Voltage
-32767.999/+32767.999
Volts
3 sec RMS Phase C-N Voltage
-32767.999/+32767.999
Volts
3 sec RMS Phase A-B Voltage
-32767.999/+32767.999
Volts
3 sec RMS Phase B-C Voltage
-32767.999/+32767.999
Volts
3 sec RMS Phase C-A Voltage
-32767.999/+32767.999
Volts
3 sec RMS Phase X-N Voltage
-32767.999/+32767.999
Amps
3 sec RMS Vres Voltage
-32767.999/+32767.999
Volts
3 sec RMS Ires Current
-32767.999/+32767.999
Amps
1 sec ADC count V1
-32767.999/+32767.999
Volts
2 sec ADC count V2
-32767.999/+32767.999
Volts
3 sec ADC count V3
-32767.999/+32767.999
Volts
4 sec ADC count V4
-32767.999/+32767.999
Volts
3 sec RMS Phase N-E Voltage
-32767.999/+32767.999
Volts
3 sec RMS Phase A Current
-32767.999/+32767.999
Amps
3 sec RMS Phase B Current
-32767.999/+32767.999
Amps
3 sec RMS Phase C Current
-32767.999/+32767.999
Amps
3 sec RMS Phase X Current
-32767.999/+32767.999
Amps
3 sec MEAN Phase A-N Voltage
-32767.999/+32767.999
Volts
3 sec MEAN Phase B-N Voltage
-32767.999/+32767.999
Volts
3 sec MEAN Phase C-N Voltage
-32767.999/+32767.999
Volts
3 sec MEAN Phase A-B Voltage
-32767.999/+32767.999
Volts
3 sec MEAN Phase B-C Voltage
-32767.999/+32767.999
Volts
3 sec MEAN Phase C-A Voltage
-32767.999/+32767.999
Volts
3 sec MEAN Phase X-N Voltage
-32767.999/+32767.999
Volts
3 sec MEAN Vres Voltage
-32767.999/+32767.999
Volts
3 sec MEAN Ires Current
-32767.999/+32767.999
Amps
1 sec ADC count I1
-32767.999/+32767.999
Volts
2 sec ADC count I2
-32767.999/+32767.999
Volts
3 sec ADC count I3
-32767.999/+32767.999
Volts
4 sec ADC count I4
-32767.999/+32767.999
Volts
3 sec MEAN Phase N-E Voltage
-32767.999/+32767.999
Volts
3 sec MEAN Phase A Current
-32767.999/+32767.999
Amps
3 sec MEAN Phase B Current
-32767.999/+32767.999
Amps
3 sec MEAN Phase C Current
-32767.999/+32767.999
Amps
3 sec MEAN Phase X Current
-32767.999/+32767.999
Amps
Compact Flash Block
Reserved
Serial Number: ASCII, right justified, with no null string terminator
FE21H-FE24H
65058-65061
FAT Type: ASCII, right justified, with no null string terminator
F2
FE25H-FE38H
FE39H-FE3EH
65062-65081
65082-65087
F2
FE3FH
FE40H-FE47H
FE48H-FE4FH
FE50H-FE57H
FE58H-FE5FH
65088
65089-65096
65097-65104
65105-65112
65113-65120
Model Number: ASCII, left justified, with no null string terminator
Reserved
Device Identification Block 2
Reserved
Device FPGA hardware ID
Device FPGA firmware ID
System preboot version
System preboot build time
F3
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
F7
R/W
Notes
R
R/W
R
R
R/W
R
R
R
Security
Security
Security
Security
Security
Security
Security
Security
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
F55
F2
F112
F1
F1
F1
F1
R
R
R
R
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-98
2: Modbus Map - Holding Registers
Line
Pt
DNP
Obj
Description
Range
Units
Type
R/W
F1
F1
F1
F1
R
R
R
R
Addr. (hex)
Address(4X)
FE60H-FE67H
FE68H-FE6FH
FE70H-FE77H
FE78H-FE7FH
FE80H-FEFFH
65121-65128
65129-65136
65137-65144
65145-65152
65153-65280
System uboot version
System uboot build time, 1/2
System uboot build time, 2/2
Device module ucc_dsp version
Reserved
FF23H-FF27H
FF28H
FF29H
FF2AH
FF2BH-FF2CH
FF2DH
FF2EH
FF2FH
65316-65320
65321
65322
65323
65324-65325
65326
65327
65328
Level 2 User Password
Level 2 Password State
Sealing Switch State
Sealing Switch Timeout Status
Reserved
Level 2 Password Lock
Password Sequence/Status
Password Command
FF40H
65345
NVRAM Configuration
R
FF41H
65346
Current Time Stamp Status:
MSB first, Bit[15-12] = Current Weekday, 0=Sunday,
6= Saturday
Bit[11]
= Not defined
Bit[10]
= Debugging 1 = Line Synch
Frequency Valid)
Bit[09]
= IRIG-B Year Valid
Bit[08]
= Debugging, 1= IRIG-B Time
Continue Forwarding)
Bit[07]
= Active IRIG-B
Bit[06]
= Active DST
Bit[05]
= Active Line Synch
Bit[04]
= Active Cold Load
Bit[03]
= DST Spring Date, it means current
date/time is before DST period
starting moment of current calender year
Bit[02] = DST Fall Date, it means current date/time
is after DST period ending moment of
current calender year
Bit[01] = Active SNTP
Bit[00] = 1 = Battery low flag)
R
FF42H
FF43H
FF44H
FF45H
65347
65348
65349
65350
Reserved
Reserved
Sealing Switch Installed
Vswitch state
FF50H-FF57H
65361-65368
Reserved
FF60H-FF63H
65377
Reserved
Password Block
Fixed Length String
Enumeration
Enumeration
Enumeration
Enumeration
Enumeration
Enumeration
Enumeration
Dynamic Configuration Block
Enumeration
W
R
R
R/W
R
R/W
R
R/W
Notes
Ch.8.106
Ch.8.106
Ch.8.106
Ch.8.106
Ch.8.106
Ch.8.106
R
R
R
R
Hardware Options Block
R
Reserved Status Block
R
Tiny Encryption Input Block
FF68H-FF6FH
65385-65392
Tiny Encryption Input Registers
R/W
Flash Control Block
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-99
2: Modbus Map - Holding Registers
Addr. (hex)
Address(4X)
Line
Pt
DNP
Obj
Description
Range
FF80H
65409
Nexus Comm Operation Indicator:
MSB fisrt,
Bit[00] = 1: Comm Run error (checksum/not found/read).(N/A to
RUN).
Bit[01] = 1: Programmable Setting error (checksum/not found/read).
Bit[02] = 1: CF not found/discovered
Bit[03] = 1: Force in boot using default comm. setting.(N/A to
RUN).
Bit[04] = 1: Meter in BOOT, 0: Meter in RUNTIME
Bit[05] = 1: FPGA firmware error (checksum/loading/not
found/read).
Bit[06] = 1: DSP2 firmware error (checksum/not found/read).
Bit[07] = 1: Generic memory test failed.(N/A to RUN).
Bit[08] = 1: COMM internal memory test failed. (N/A to RUN).
Bit[09] = 1: File system failed. (N/A to RUN).
Bit[10] = 1: Logging stopped due to invalid log folder/files.
Bit[11] = 1: Running/Pause folder error.(N/A to BOOT)
Bit[12] = 1: Scan board failure.(N/A to RUN)
Bit[13] = 1: V-switch invalid settings. (N/A to RUN)
Bit[14] = 1: IEC 61850 server not running. (N/A to BOOT)
Bit[15] = 1: Additional error status are available.(N/A to BOOT)
FF82H
65411
Connected port information
Enumeration
DSP Operation Indicator:
MSB fisrt,
Bit[00] = 1: Comm Run error (checksum/not found/read).(N/A to
RUN).
Bit[01] = 1: Programmable Setting error (checksum/not found/read).
Bit[02] = 1: Not defined
Bit[03] = 1: Not defined
Bit[04] = 1: Not defined
Bit[05] = 1: Data transfer queue overflow
Bit[06] = 1: Not defined
Bit[07] = 1: Missed watchdog kick, real time break
Bit[08] = 1: FRAM initialization failed.
Bit[09] = 1: Error detected, LSB is not zero.
Bit[10] = 1: Not defined
Bit[11] = 1: Not defined
Bit[12] = 1: Not defined
Bit[13] = 1: Not defined
Bit[14] = 1: Not defined
Bit[15] = 1: Not defined
FF85H
FF88H
FF89H
FF8AH
FF8BH
FF8CH
FFB0H-FFBFH
FFC0H-FFDEH
FFDFH
65414
65417
65418
65419
65420
65421
65457-65472
65473-65503
65504
Reserved
Reserved
Reserved
Reserved
Reserved
Meter Reserved
Reserved
app restart after profile update, write 0x0001
FFE0H
FFE1H
FFE2H-FFE5H
FFE6H
65505
65506
65507-65510
65511
Update status
Update error code
file data time
file checksum
FFFAH
FFFBH
65531
65532
Units
Type
R/W
F112
R
Notes
R
R/W
Ch.5
W
Update Information Block
Meter Restart
Complete Meter Restart Command - write 0x0001
Reserved
W
Meter Serial Number
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-100
2: Modbus Map - Holding Registers
Addr. (hex)
FFFCH-FFFFH
Address(4X)
Line
Pt
DNP
Obj
65533-65536
Description
Meter Serial Number
Range
9,999,999,999,999,999 / 0
Units
1
Type
F11
R/W
R
Notes
16-digit
Packed BCD
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-101
2: Modbus Map - Input Registers
2.3: Modbus Map Input Registers
Addr. (hex)
85F0H-85F3H
85F4H-85F5H
85F6H-85F7H
85F8H-85F9H
85FAH-85FBH
85FCH-85FDH
85FEH-85FFH
8600H
8601H
8602H
8603H
8604H
8605H
8606H-8607H
8608H-8609H
860AH-860BH
860CH-860DH
860EH-860FH
8610H-8611H
8612H
8613H
8614H
8615H
8616H
8617H
8618H-8619H
861AH-861BH
861CH-861DH
861EH-861FH
8620H-8621H
8622H-8623H
8624H-8625H
8626H-8627H
Address(3X)
Line
Pt
34289-34292
34293-34294
34295-34296
34297-34298
34299-34300
34301-34302
34303-34304
34305
34306
34307
34308
34309
34310
34311-34312
34313-34314
34315-34316
34317-34318
34319-34320
34321-34322
34323
34324
34325
34326
34327
34328
34329-34330
34331-34332
34333-34334
34335-34336
34337-34338
34339-34340
34341-34342
34343-34344
DNP
Obj
Description
Range
Symmetrical Component @3sec, 10min, 2hour
P-N channels are available in WYE type hookups
P-P channels are available in Delta type hookups
3 sec Update RTC Timestamp
12/31/9999
3 sec Symm Comp Mag (Voltage PN) - Zero Sequence -32768/+32767.999
3 sec Symm Comp Mag (Voltage PN) - Pos Sequence -32768/+32767.999
3 sec Symm Comp Mag (Voltage PN) - Neg Sequence -32768/+32767.999
10 min Symm Comp Mag (Voltage PN) - Zero
-32768/+32767.999
10 min Symm Comp Mag (Voltage PN) - Pos Sequence -32768/+32767.999
10 min Symm Comp Mag (Voltage PN) - Neg
-32768/+32767.999
3 sec Symm Comp Phase (Voltage PN) - Zero Sequence +180 degree / -180
3 sec Symm Comp Phase (Voltage PN) - Pos Sequence +180 degree / -180
3 sec Symm Comp Phase (Voltage PN) - Neg Sequence +180 degree / -180
10 min Symm Comp Phase (Voltage PN) - Zero
+180 degree / -180
10 min Symm Comp Phase (Voltage PN) - Pos
+180 degree / -180
10 min Symm Comp Phase (Voltage PN) - Neg
+180 degree / -180
3 sec Symm Comp Mag (Current PN) - Zero Sequence -32768/+32767.999
3 sec Symm Comp Mag (Current PN) - Pos Sequence -32768/+32767.999
3 sec Symm Comp Mag (Current PN) - Neg Sequence -32768/+32767.999
10 min Symm Comp Mag (Current PN) - Zero
-32768/+32767.999
10 min Symm Comp Mag (Current PN) - Pos Sequence -32768/+32767.999
10 min Symm Comp Mag (Current PN) - Neg Sequence -32768/+32767.999
3 sec Symm Comp Phase (Current PN) - Zero Sequence +180 degree / -180
3 sec Symm Comp Phase (Current PN) - Pos Sequence +180 degree / -180
3 sec Symm Comp Phase (Current PN) - Neg Sequence +180 degree / -180
10 min Symm Comp Phase (Current PN) - Zero
+180 degree / -180
10 min Symm Comp Phase (Current PN) - Pos
+180 degree / -180
10 min Symm Comp Phase (Current PN) - Neg
+180 degree / -180
3 sec Symm Comp Ratio (Current PN) - Zero Sequence 0/65535.9999
3 sec Symm Comp Ratio (Current PN) - Neg Sequence 0/65535.9999
3 sec Symm Comp Ratio (Current PP) - Neg Sequence 0/65535.9999
10 min Symm Comp Ratio (Current PN) - Zero
0/65535.9999
10 min Symm Comp Ratio (Current PN) - Neg
0/65535.9999
10 min Symm Comp Ratio (Current PP) - Neg
0/65535.9999
2 hour Symm Comp Ratio (Current PN) - Zero
0/65535.9999
2 hour Symm Comp Ratio (Current PN) - Neg
0/65535.9999
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Units
10 msec
Volts
Volts
Volts
Volts
Volts
Volts
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
Amp
Amp
Amp
Amp
Amp
Amp
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
0.01 degree
1/65536
1/65536
1/65536
1/65536
1/65536
1/65536
1/65536
1/65536
Type R/W
F3
F73
F73
F73
F73
F73
F73
F9
F9
F9
F9
F9
F9
F73
F73
F73
F73
F73
F73
F9
F9
F9
F9
F9
F9
F79
F79
F79
F79
F79
F79
F79
F79
Notes
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
MM-102
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
8628H-8629H
862AH
862BH
862CH
862DH
862EH-862FH
8630H-8631H
8632H-8633H
8634H-8635H
8636H-8637H
8638H-8639H
863AH-863BH
863CH-863DH
863EH-863FH
8640H-86EBH
86ECH-86EFH
86F0H-86FFH
34345-34346
34347
34348
34349
34350
34351-34352
34353-34354
34355-34356
34357-34358
34359-34360
34361-34362
34363-34364
34365-34366
34367-34368
34369-34540
34541-34544
34545-34560
8B40H-8B43H
8B44H-8B45H
8B46H-8B47H
8B48H-8B49H
8B4AH-8B4BH
8B4CH-8B4DH
8B4EH-8B4FH
8B50H-8B51H
8B52H-8B53H
8B54H-8B55H
8B56H-8B57H
8B58H-8B59H
8B5AH-8B5BH
8B5CH-8B5DH
8B5EH-8B5FH
8B60H-8B61H
8B62H-8B63H
8B64H-8B65H
35649-35652
35653-35654
35655-35656
35657-35658
35659-35660
35661-35662
35663-35664
35665-35666
35667-35668
35669-35670
35671-35672
35673-35674
35675-35676
35677-35678
35679-35680
35681-35682
35683-35684
35685-35686
Line
Pt
DNP
Obj
Description
Range
2 hour Symm Comp Ratio (Current PP) - Neg Sequence 0/65535.9999
3 sec Uunbalance Counter
0/+65535
10 min Uunbalance Counter
0/+65536
2 hour Uunbalance Counter
0/+65537
Reserved
3 sec Symm Comp Ratio (Voltage PN) - Zero Sequence 0/65535.9999
3 sec Symm Comp Ratio (Voltage PN) - Neg Sequence 0/65535.9999
3 sec Symm Comp Ratio (Voltage PP) - Neg Sequence 0/65535.9999
10 min Symm Comp Ratio (Voltage PN) - Zero
0/65535.9999
10 min Symm Comp Ratio (Voltage PN) - Neg
0/65535.9999
10 min Symm Comp Ratio (Voltage PP) - Neg
0/65535.9999
2 hour Symm Comp Ratio (Voltage PN) - Zero
0/65535.9999
2 hour Symm Comp Ratio (Voltage PN) - Neg
0/65535.9999
2 hour Symm Comp Ratio (Voltage PP) - Neg Sequence 0/65535.9999
Reserved
Reserved
Reserved
Interval Maximum/Minimum/Average block
10 min Interval Maximum/Minimum Timestamp
12/31/9999
10 min Interval Maximum RMS Phase A-N Voltage
0/+65535.65535
10 min Interval Maximum RMS Phase B-N Voltage
0/+65535.65535
10 min Interval Maximum RMS Phase C-N Voltage
0/+65535.65535
10 min Interval Maximum RMS Phase A-B Voltage
0/+65535.65535
10 min Interval Maximum RMS Phase B-C Voltage
0/+65535.65535
10 min Interval Maximum RMS Phase C-A Voltage
0/+65535.65535
10 min Interval Maximum RMS Phase X-N Voltage
0/+65535.65535
10 min Interval Maximum RMS Phase A-E Voltage
0/+65535.65535
10 min Interval Maximum RMS Phase B-E Voltage
0/+65535.65535
10 min Interval Maximum RMS Phase C-E Voltage
0/+65535.65535
10 min Interval Maximum RMS Phase X-E Voltage
0/+65535.65535
10 min Interval Maximum RMS Phase N-E Voltage
0/+65535.65535
10 min Interval Minimum RMS Phase A-N Voltage
0/+65535.65535
10 min Interval Minimum RMS Phase B-N Voltage
0/+65535.65535
10 min Interval Minimum RMS Phase C-N Voltage
0/+65535.65535
10 min Interval Minimum RMS Phase A-B Voltage
0/+65535.65535
10 min Interval Minimum RMS Phase B-C Voltage
0/+65535.65535
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Units
Type R/W
1/65536
1
1
1
F79
F51
F51
F51
R
R
R
R
1/65536
1/65536
1/65536
1/65536
1/65536
1/65536
1/65536
1/65536
1/65536
F79
F79
F79
F79
F79
F79
F79
F79
F79
R
R
R
R
R
R
R
R
R
10 msec
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
F3
F79
F79
F79
F79
F79
F79
F79
F79
F79
F79
F79
F79
F79
F79
F79
F79
F79
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Notes
MM-103
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
8B66H-8B67H
8B68H-8B69H
8B6AH-8B6BH
8B6CH-8B6DH
8B6EH-8B6FH
8B70H-8B71H
8B72H-8B73H
8B74H-8B75H
8B76H-8B77H
8B78H-8B79H
8B7AH-8B7BH
8B7CH-8B7DH
8B7EH-8B7FH
8B80H-8B81H
8B82H-8B83H
8B84H-8B85H
8B86H-8B87H
8B88H-8B89H
8B8AH-8B8BH
35687-35688
35689-35690
35691-35692
35693-35694
35695-35696
35697-35698
35699-35700
35701-35702
35703-35704
35705-35706
35707-35708
35709-35710
35711-35712
35713-35714
35715-35716
35717-35718
35719-35720
35721-35722
35723-35724
D027H
53288
10380
0
D028H
53289
10380
1
D029H-D02BH
D02CH-D02EH
D02FH
D030H
D031H-D033H
D034H-D036H
53290-53292
53293-53295
53296
53297
53298-53300
53301-53303
10381
103801
10382
10382
10383
10383
0
1
0
1
0
1
DNP
Obj
Description
10 min Interval Minimum RMS Phase C-A Voltage
10 min Interval Minimum RMS Phase X-N Voltage
10 min Interval Minimum RMS Phase A-E Voltage
10 min Interval Minimum RMS Phase B-E Voltage
10 min Interval Minimum RMS Phase C-E Voltage
10 min Interval Minimum RMS Phase X-E Voltage
10 min Interval Minimum RMS Phase N-E Voltage
10 min Interval Average RMS Phase A-N Voltage
10 min Interval Average RMS Phase B-N Voltage
10 min Interval Average RMS Phase C-N Voltage
10 min Interval Average RMS Phase A-B Voltage
10 min Interval Average RMS Phase B-C Voltage
10 min Interval Average RMS Phase C-A Voltage
10 min Interval Average RMS Phase X-N Voltage
10 min Interval Average RMS Phase A-E Voltage
10 min Interval Average RMS Phase B-E Voltage
10 min Interval Average RMS Phase C-E Voltage
10 min Interval Average RMS Phase X-E Voltage
10 min Interval Average RMS Phase N-E Voltage
TOU Data
Current Month ID
1=Jan, 12=Dec
Prior Month ID
1=Jan, 12=Dec
Last month self-read time
Next month self-read time
Current Season ID
Prior Season ID
Last season self-read time
Next season self-read time
Current Month
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
0/+65535.65535
0/+65535.65535
0/+65535.65535
0/+65535.65535
0/+65535.65535
0/+65535.65535
0/+65535.65535
0/+65535.65535
0/+65535.65535
0/+65535.65535
0/+65535.65535
0/+65535.65535
0/+65535.65535
0/+65535.65535
0/+65535.65535
0/+65535.65535
0/+65535.65535
0/+65535.65535
0/+65535.65535
Units
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Type R/W
F79
F79
F79
F79
F79
F79
F79
F79
F79
F79
F79
F79
F79
F79
F79
F79
F79
F79
F79
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
F51
R
F51
R
F122
F122
F51
F51
F122
F122
R
R
R
R
R
R
Notes
MM-104
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
base=10384,
group
count=96,
groups=15
DNP
Obj
Description
Tier 0 is for total
Current Month Tier 0:
Current Month Tier 1:
Current Month Tier 2:
Current Month Tier 3:
Current Month Tier 4:
Current Month Tier 0:
Current Month Tier 1:
Current Month Tier 2:
Current Month Tier 3:
Current Month Tier 4:
Current Month Tier 0:
Current Month Tier 1:
Current Month Tier 2:
Current Month Tier 3:
Current Month Tier 4:
D037-D038
D039-D03A
D03B-D03C
D03D-D03F
53304-53305
53306-53307
53308-53309
53310-53312
10384
10385
10386
10387
0
0
0
0
D041
D041-D042
D043-D044
D045-D046
D047-D048
D049-D04B
53313
53314-53315
53316-53317
53318-53319
53320-53321
53322-53324
10388
10389
10390
10391
10392
10393
0
0
0
0
0
0
D04D
D04D-D04E
D04F-D050
D051-D052
D053-D054
D055-D057
53325
53326-53327
53328-53329
53330-53331
53332-53333
53334-53336
10394
10395
10396
10397
10398
10399
0
0
0
0
0
0
Electro Industries/GaugeTech
Units
Type R/W
Notes
Whole month data
Whole month data
Whole month data
Whole month data
Whole month data
Initial season data
Initial season data
Initial season data
Initial season data
Initial season data
Final season data
Final season data
Final season data
Final season data
Final season data
Current Month, Whole Month, Tier 0
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
The Leader In Power Monitoring and Smart Grid Solutions
Range
Doc# E171707
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
MM-105
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D059
D059-D05A
D05B-D05C
D05D-D05E
D05F-D060
D061-D063
53337
53338-53339
53340-53341
53342-53343
53344-53345
53346-53348
10400
10401
10402
10403
10404
10405
0
0
0
0
0
0
D065
D065-D066
D067-D068
D069-D06A
D06B-D06C
D06D-D06F
53349
53350-53351
53352-53353
53354-53355
53356-53357
53358-53360
10406
10407
10408
10409
10410
10411
0
0
0
0
0
0
D071
D071-D072
D073-D074
D075-D076
D077-D078
D079-D07B
53361
53362-53363
53364-53365
53366-53367
53368-53369
53370-53372
10412
10413
10414
10415
10416
10417
0
0
0
0
0
0
D07D
D07D-D07E
D07F-D080
D081-D082
D083-D084
D085-D087
53373
53374-53375
53376-53377
53378-53379
53380-53381
53382-53384
10418
10419
10420
10421
10422
10423
0
0
0
0
0
0
D089
D089-D08A
D08B-D08C
D08D-D08E
D08F-D090
D091-D093
53385
53386-53387
53388-53389
53390-53391
53392-53393
53394-53396
10424
10425
10426
10427
10428
10429
0
0
0
0
0
0
D095
53397
10430
0
DNP
Obj
Description
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
R
Notes
MM-106
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D095-D096
D097-D098
D099-D09A
D09B-D09C
D09D-D09F
53398-53399
53400-53401
53402-53403
53404-53405
53406-53408
10431
10432
10433
10434
10435
0
0
0
0
0
D0A1
D0A1-D0A2
D0A3-D0A4
D0A5-D0A6
D0A7-D0A8
D0A9-D0AB
53409
53410-53411
53412-53413
53414-53415
53416-53417
53418-53420
10436
10437
10438
10439
10440
10441
0
0
0
0
0
0
D0AD
D0AD-D0AE
D0AF-D0B0
D0B1-D0B2
D0B3-D0B4
D0B5-D0B7
53421
53422-53423
53424-53425
53426-53427
53428-53429
53430-53432
10442
10443
10444
10445
10446
10447
0
0
0
0
0
0
D0B9
D0B9-D0BA
D0BB-D0BC
D0BD-D0BE
D0BF-D0C0
D0C1-D0C3
53433
53434-53435
53436-53437
53438-53439
53440-53441
53442-53444
10448
10449
10450
10451
10452
10453
0
0
0
0
0
0
D0C5
D0C5-D0C6
D0C7-D0C8
D0C9-D0CA
D0CB-D0CC
D0CD-D0CF
53445
53446-53447
53448-53449
53450-53451
53452-53453
53454-53456
10454
10455
10456
10457
10458
10459
0
0
0
0
0
0
D0D1
D0D1-D0D2
53457
53458-53459
10460
10461
0
0
DNP
Obj
Description
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
F52
F64
F120
F120
F122
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
Notes
MM-107
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D0D3-D0D4
D0D5-D0D6
D0D7-D0D8
D0D9-D0DB
53460-53461
53462-53463
53464-53465
53466-53468
10462
10463
10464
10465
0
0
0
0
D0DD
D0DD-D0DE
D0DF-D0E0
D0E1-D0E2
D0E3-D0E4
D0E5-D0E7
53469
53470-53471
53472-53473
53474-53475
53476-53477
53478-53480
10466
10467
10468
10469
10470
10471
0
0
0
0
0
0
D0E9
D0E9-D0EA
D0EB-D0EC
D0ED-D0EE
D0EF-D0F0
D0F1-D0F3
53481
53482-53483
53484-53485
53486-53487
53488-53489
53490-53492
10472
10473
10474
10475
10476
10477
0
0
0
0
0
0
D0F5
D0F5-D0F6
53493
53494-53495
10478
10479
0
0
D0F7-D0F8
D0F9-D0FA
D0FB-D0FC
D0FD-D0FF
53496-53497
53498-53499
53500-53501
53502-53504
10480
10481
10482
10483
0
0
0
0
D101
D101-D102
D103-D104
D105-D106
D107-D108
D109-D10B
53505
53506-53507
53508-53509
53510-53511
53512-53513
53514-53516
10484
10485
10486
10487
10488
10489
0
0
0
0
0
0
D10D
D10D-D10E
53517
53518-53519
10490
10491
0
0
DNP
Obj
Description
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Current Month, Whole Month, Tier 1
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
Notes
MM-108
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D10F-D110
D111-D112
D113-D114
D115-D117
53520-53521
53522-53523
53524-53525
53526-53528
10492
10493
10494
10495
0
0
0
0
D119
D119-D11A
D11B-D11C
D11D-D11E
D11F-D120
D121-D123
53529
53530-53531
53532-53533
53534-53535
53536-53537
53538-53540
10496
10497
10498
10499
10500
10501
0
0
0
0
0
0
D125
D125-D126
D127-D128
D129-D12A
D12B-D12C
D12D-D12F
53541
53542-53543
53544-53545
53546-53547
53548-53549
53550-53552
10502
10503
10504
10505
10506
10507
0
0
0
0
0
0
D131
D131-D132
D133-D134
D135-D136
D137-D138
D139-D13B
53553
53554-53555
53556-53557
53558-53559
53560-53561
53562-53564
10508
10509
10510
10511
10512
10513
0
0
0
0
0
0
D13D
D13D-D13E
D13F-D140
D141-D142
D143-D144
D145-D147
53565
53566-53567
53568-53569
53570-53571
53572-53573
53574-53576
10514
10515
10516
10517
10518
10519
0
0
0
0
0
0
D149
D149-D14A
D14B-D14C
53577
53578-53579
53580-53581
10520
10521
10522
0
0
0
DNP
Obj
Description
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
R
R
R
Notes
MM-109
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D14D-D14E
D14F-D150
D151-D153
53582-53583
53584-53585
53586-53588
10523
10524
10525
0
0
0
D155
D155-D156
D157-D158
D159-D15A
D15B-D15C
D15D-D15F
53589
53590-53591
53592-53593
53594-53595
53596-53597
53598-53600
10526
10527
10528
10529
10530
10531
0
0
0
0
0
0
D161
D161-D162
D163-D164
D165-D166
D167-D168
D169-D16B
53601
53602-53603
53604-53605
53606-53607
53608-53609
53610-53612
10532
10533
10534
10535
10536
10537
0
0
0
0
0
0
D16D
D16D-D16E
D16F-D170
D171-D172
D173-D174
D175-D177
53613
53614-53615
53616-53617
53618-53619
53620-53621
53622-53624
10538
10539
10540
10541
10542
10543
0
0
0
0
0
0
D179
D179-D17A
D17B-D17C
D17D-D17E
D17F-D180
D181-D183
53625
53626-53627
53628-53629
53630-53631
53632-53633
53634-53636
10544
10545
10546
10547
10548
10549
0
0
0
0
0
0
D185
D185-D186
D187-D188
D189-D18A
53637
53638-53639
53640-53641
53642-53643
10550
10551
10552
10553
0
0
0
0
DNP
Obj
Description
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
R
R
R
R
MM-110
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D18B-D18C
D18D-D18F
53644-53645
53646-53648
10554
10555
0
0
D191
D191-D192
D193-D194
D195-D196
D197-D198
D199-D19B
53649
53650-53651
53652-53653
53654-53655
53656-53657
53658-53660
10556
10557
10558
10559
10560
10561
0
0
0
0
0
0
D19D
D19D-D19E
D19F-D1A0
D1A1-D1A2
D1A3-D1A4
D1A5-D1A7
53661
53662-53663
53664-53665
53666-53667
53668-53669
53670-53672
10562
10563
10564
10565
10566
10567
0
0
0
0
0
0
D1A9
D1A9-D1AA
D1AB-D1AC
D1AD-D1AE
D1AF-D1B0
D1B1-D1B3
53673
53674-53675
53676-53677
53678-53679
53680-53681
53682-53684
10568
10569
10570
10571
10572
10573
0
0
0
0
0
0
D1B5
D1B5-D1B6
53685
53686-53687
10574
10575
0
0
D1B7-D1B8
D1B9-D1BA
D1BB-D1BC
D1BD-D1BF
53688-53689
53690-53691
53692-53693
53694-53696
10576
10577
10578
10579
0
0
0
0
D1C1
D1C1-D1C2
D1C3-D1C4
53697
53698-53699
53700-53701
10580
10581
10582
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Current Month, Whole Month, Tier 2
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
R
R
R
MM-111
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D1C5-D1C6
D1C7-D1C8
D1C9-D1CB
53702-53703
53704-53705
53706-53708
10583
10584
10585
0
0
0
D1CD
D1CD-D1CE
D1CF-D1D0
D1D1-D1D2
D1D3-D1D4
D1D5-D1D7
53709
53710-53711
53712-53713
53714-53715
53716-53717
53718-53720
10586
10587
10588
10589
10590
10591
0
0
0
0
0
0
D1D9
D1D9-D1DA
D1DB-D1DC
D1DD-D1DE
D1DF-D1E0
D1E1-D1E3
53721
53722-53723
53724-53725
53726-53727
53728-53729
53730-53732
10592
10593
10594
10595
10596
10597
0
0
0
0
0
0
D1E5
D1E5-D1E6
D1E7-D1E8
D1E9-D1EA
D1EB-D1EC
D1ED-D1EF
53733
53734-53735
53736-53737
53738-53739
53740-53741
53742-53744
10598
10599
10600
10601
10602
10603
0
0
0
0
0
0
D1F1
D1F1-D1F2
D1F3-D1F4
D1F5-D1F6
D1F7-D1F8
D1F9-D1FB
53745
53746-53747
53748-53749
53750-53751
53752-53753
53754-53756
10604
10605
10606
10607
10608
10609
0
0
0
0
0
0
D1FD
D1FD-D1FE
D1FF-D200
D201-D202
53757
53758-53759
53760-53761
53762-53763
10610
10611
10612
10613
0
0
0
0
DNP
Obj
Description
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
R
R
R
R
MM-112
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D203-D204
D205-D207
53764-53765
53766-53768
10614
10615
0
0
D209
D209-D20A
D20B-D20C
D20D-D20E
D20F-D210
D211-D213
53769
53770-53771
53772-53773
53774-53775
53776-53777
53778-53780
10616
10617
10618
10619
10620
10621
0
0
0
0
0
0
D215
D215-D216
D217-D218
D219-D21A
D21B-D21C
D21D-D21F
53781
53782-53783
53784-53785
53786-53787
53788-53789
53790-53792
10622
10623
10624
10625
10626
10627
0
0
0
0
0
0
D221
D221-D222
D223-D224
D225-D226
D227-D228
D229-D22B
53793
53794-53795
53796-53797
53798-53799
53800-53801
53802-53804
10628
10629
10630
10631
10632
10633
0
0
0
0
0
0
D22D
D22D-D22E
D22F-D230
D231-D232
D233-D234
D235-D237
53805
53806-53807
53808-53809
53810-53811
53812-53813
53814-53816
10634
10635
10636
10637
10638
10639
0
0
0
0
0
0
D239
D239-D23A
D23B-D23C
D23D-D23E
D23F-D240
53817
53818-53819
53820-53821
53822-53823
53824-53825
10640
10641
10642
10643
10644
0
0
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-113
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D241-D243
53826-53828
10645
0
D245
D245-D246
D247-D248
D249-D24A
D24B-D24C
D24D-D24F
53829
53830-53831
53832-53833
53834-53835
53836-53837
53838-53840
10646
10647
10648
10649
10650
10651
0
0
0
0
0
0
D251
D251-D252
D253-D254
D255-D256
D257-D258
D259-D25B
53841
53842-53843
53844-53845
53846-53847
53848-53849
53850-53852
10652
10653
10654
10655
10656
10657
0
0
0
0
0
0
D25D
D25D-D25E
D25F-D260
D261-D262
D263-D264
D265-D267
53853
53854-53855
53856-53857
53858-53859
53860-53861
53862-53864
10658
10659
10660
10661
10662
10663
0
0
0
0
0
0
D269
D269-D26A
D26B-D26C
D26D-D26E
D26F-D270
D271-D273
53865
53866-53867
53868-53869
53870-53871
53872-53873
53874-53876
10664
10665
10666
10667
10668
10669
0
0
0
0
0
0
D275
D275-D276
53877
53878-53879
10670
10671
D277-D278
D279-D27A
53880-53881
53882-53883
10672
10673
DNP
Obj
Description
Range
Units
Type R/W
F122 R
0
0
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
0
0
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
F64 R
F120 R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
Notes
MM-114
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D27B-D27C
D27D-D27F
53884-53885
53886-53888
10674
10675
0
0
D281
D281-D282
D283-D284
D285-D286
D287-D288
D289-D28B
D28D
D28D-D28E
D28F-D290
D291-D292
D293-D294
D295-D297
53889
53890-53891
53892-53893
53894-53895
53896-53897
53898-53900
53901
53902-53903
53904-53905
53906-53907
53908-53909
53910-53912
10676
10677
10678
10679
10680
10681
10682
10683
10684
10685
10686
10687
0
0
0
0
0
0
0
0
0
0
0
0
D299
D299-D29A
D29B-D29C
D29D-D29E
D29F-D2A0
D2A1-D2A3
53913
53914-53915
53916-53917
53918-53919
53920-53921
53922-53924
10688
10689
10690
10691
10692
10693
0
0
0
0
0
0
D2A5
D2A5-D2A6
D2A7-D2A8
D2A9-D2AA
D2AB-D2AC
D2AD-D2AF
53925
53926-53927
53928-53929
53930-53931
53932-53933
53934-53936
10694
10695
10696
10697
10698
10699
0
0
0
0
0
0
D2B1
D2B1-D2B2
D2B3-D2B4
D2B5-D2B6
D2B7-D2B8
53937
53938-53939
53940-53941
53942-53943
53944-53945
10700
10701
10702
10703
10704
0
0
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
14
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-115
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D2B9-D2BB
53946-53948
10705
0
D2BD
D2BD-D2BE
D2BF-D2C0
D2C1-D2C2
D2C3-D2C4
D2C5-D2C7
53949
53950-53951
53952-53953
53954-53955
53956-53957
53958-53960
10706
10707
10708
10709
10710
10711
0
0
0
0
0
0
D2C9
D2C9-D2CA
D2CB-D2CC
D2CD-D2CE
D2CF-D2D0
D2D1-D2D3
53961
53962-53963
53964-53965
53966-53967
53968-53969
53970-53972
10712
10713
10714
10715
10716
10717
0
0
0
0
0
0
D2D5
D2D5-D2D6
D2D7-D2D8
D2D9-D2DA
D2DB-D2DC
D2DD-D2DF
53973
53974-53975
53976-53977
53978-53979
53980-53981
53982-53984
10718
10719
10720
10721
10722
10723
0
0
0
0
0
0
D2E1
D2E1-D2E2
D2E3-D2E4
D2E5-D2E6
D2E7-D2E8
D2E9-D2EB
53985
53986-53987
53988-53989
53990-53991
53992-53993
53994-53996
10724
10725
10726
10727
10728
10729
0
0
0
0
0
0
D2ED
D2ED-D2EE
D2EF-D2F0
D2F1-D2F2
D2F3-D2F4
53997
53998-53999
54000-54001
54002-54003
54004-54005
10730
10731
10732
10733
10734
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-116
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D2F5-D2F7
54006-54008
10735
0
D2F9
D2F9-D2FA
D2FB-D2FC
D2FD-D2FE
D2FF-D300
D301-D303
54009
54010-54011
54012-54013
54014-54015
54016-54017
54018-54020
10736
10737
10738
10739
10740
10741
0
0
0
0
0
0
D305
D305-D306
D307-D308
D309-D30A
D30B-D30C
D30D-D30F
54021
54022-54023
54024-54025
54026-54027
54028-54029
54030-54032
10742
10743
10744
10745
10746
10747
0
0
0
0
0
0
D311
D311-D312
D313-D314
D315-D316
D317-D318
D319-D31B
54033
54034-54035
54036-54037
54038-54039
54040-54041
54042-54044
10748
10749
10750
10751
10752
10753
0
0
0
0
0
0
D31D
D31D-D31E
D31F-D320
D321-D322
D323-D324
D325-D327
54045
54046-54047
54048-54049
54050-54051
54052-54053
54054-54056
10754
10755
10756
10757
10758
10759
0
0
0
0
0
0
D329
D329-D32A
D32B-D32C
D32D-D32E
D32F-D330
54057
54058-54059
54060-54061
54062-54063
54064-54065
10760
10761
10762
10763
10764
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-117
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D331-D333
54066-54068
10765
0
D335
D335-D336
54069
54070-54071
10766
10767
0
0
D337-D338
D339-D33A
D33B-D33C
D33D-D33F
54072-54073
54074-54075
54076-54077
54078-54080
10768
10769
10770
10771
0
0
0
0
D341
D341-D342
D343-D344
D345-D346
D347-D348
D349-D34B
54081
54082-54083
54084-54085
54086-54087
54088-54089
54090-54092
10772
10773
10774
10775
10776
10777
0
0
0
0
0
0
D34D
D34D-D34E
D34F-D350
D351-D352
D353-D354
D355-D357
54093
54094-54095
54096-54097
54098-54099
54100-54101
54102-54104
10778
10779
10780
10781
10782
10783
0
0
0
0
0
0
D359
D359-D35A
D35B-D35C
D35D-D35E
D35F-D360
D361-D363
54105
54106-54107
54108-54109
54110-54111
54112-54113
54114-54116
10784
10785
10786
10787
10788
10789
0
0
0
0
0
0
D365
D365-D366
D367-D368
D369-D36A
54117
54118-54119
54120-54121
54122-54123
10790
10791
10792
10793
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Current Month, Whole Month, Tier 4
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
R
R
R
R
MM-118
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D36B-D36C
D36D-D36F
54124-54125
54126-54128
10794
10795
0
0
D371
D371-D372
D373-D374
D375-D376
D377-D378
D379-D37B
54129
54130-54131
54132-54133
54134-54135
54136-54137
54138-54140
10796
10797
10798
10799
10800
10801
0
0
0
0
0
0
D37D
D37D-D37E
D37F-D380
D381-D382
D383-D384
D385-D387
54141
54142-54143
54144-54145
54146-54147
54148-54149
54150-54152
10802
10803
10804
10805
10806
10807
0
0
0
0
0
0
D389
D389-D38A
D38B-D38C
D38D-D38E
D38F-D390
D391-D393
54153
54154-54155
54156-54157
54158-54159
54160-54161
54162-54164
10808
10809
10810
10811
10812
10813
0
0
0
0
0
0
D395
D395-D396
D397-D398
D399-D39A
D39B-D39C
D39D-D39F
54165
54166-54167
54168-54169
54170-54171
54172-54173
54174-54176
10814
10815
10816
10817
10818
10819
0
0
0
0
0
0
D3A1
D3A1-D3A2
D3A3-D3A4
D3A5-D3A6
D3A7-D3A8
54177
54178-54179
54180-54181
54182-54183
54184-54185
10820
10821
10822
10823
10824
0
0
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-119
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D3A9-D3AB
54186-54188
10825
0
D3AD
D3AD-D3AE
D3AF-D3B0
D3B1-D3B2
D3B3-D3B4
D3B5-D3B7
54189
54190-54191
54192-54193
54194-54195
54196-54197
54198-54200
10826
10827
10828
10829
10830
10831
0
0
0
0
0
0
D3B9
D3B9-D3BA
D3BB-D3BC
D3BD-D3BE
D3BF-D3C0
D3C1-D3C3
54201
54202-54203
54204-54205
54206-54207
54208-54209
54210-54212
10832
10833
10834
10835
10836
10837
0
0
0
0
0
0
D3C5
D3C5-D3C6
D3C7-D3C8
D3C9-D3CA
D3CB-D3CC
D3CD-D3CF
54213
54214-54215
54216-54217
54218-54219
54220-54221
54222-54224
10838
10839
10840
10841
10842
10843
0
0
0
0
0
0
D3D1
D3D1-D3D2
D3D3-D3D4
D3D5-D3D6
D3D7-D3D8
D3D9-D3DB
54225
54226-54227
54228-54229
54230-54231
54232-54233
54234-54236
10844
10845
10846
10847
10848
10849
0
0
0
0
0
0
D3DD
D3DD-D3DE
D3DF-D3E0
D3E1-D3E2
D3E3-D3E4
54237
54238-54239
54240-54241
54242-54243
54244-54245
10850
10851
10852
10853
10854
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-120
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D3E5-D3E7
54246-54248
10855
0
D3E9
D3E9-D3EA
D3EB-D3EC
D3ED-D3EE
D3EF-D3F0
D3F1-D3F3
54249
54250-54251
54252-54253
54254-54255
54256-54257
54258-54260
10856
10857
10858
10859
10860
10861
0
0
0
0
0
0
D3F5
D3F5-D3F6
54261
54262-54263
10862
10863
0
0
D3F7-D3F8
D3F9-D3FA
D3FB-D3FC
D3FD-D3FF
54264-54265
54266-54267
54268-54269
54270-54272
10864
10865
10866
10867
0
0
0
0
D401
D401-D402
D403-D404
D405-D406
D407-D408
D409-D40B
54273
54274-54275
54276-54277
54278-54279
54280-54281
54282-54284
10868
10869
10870
10871
10872
10873
0
0
0
0
0
0
D40D
D40D-D40E
D40F-D410
D411-D412
D413-D414
D415-D417
54285
54286-54287
54288-54289
54290-54291
54292-54293
54294-54296
10874
10875
10876
10877
10878
10879
0
0
0
0
0
0
D419
D419-D41A
D41B-D41C
D41D-D41E
D41F-D420
54297
54298-54299
54300-54301
54302-54303
54304-54305
10880
10881
10882
10883
10884
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Current Month, Initial Season, Tier 0
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-121
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D421-D423
54306-54308
10885
0
D425
D425-D426
D427-D428
D429-D42A
D42B-D42C
D42D-D42F
54309
54310-54311
54312-54313
54314-54315
54316-54317
54318-54320
10886
10887
10888
10889
10890
10891
0
0
0
0
0
0
D431
D431-D432
D433-D434
D435-D436
D437-D438
D439-D43B
54321
54322-54323
54324-54325
54326-54327
54328-54329
54330-54332
10892
10893
10894
10895
10896
10897
0
0
0
0
0
0
D43D
D43D-D43E
D43F-D440
D441-D442
D443-D444
D445-D447
54333
54334-54335
54336-54337
54338-54339
54340-54341
54342-54344
10898
10899
10900
10901
10902
10903
0
0
0
0
0
0
D449
D449-D44A
D44B-D44C
D44D-D44E
D44F-D450
D451-D453
54345
54346-54347
54348-54349
54350-54351
54352-54353
54354-54356
10904
10905
10906
10907
10908
10909
0
0
0
0
0
0
D455
D455-D456
D457-D458
D459-D45A
D45B-D45C
54357
54358-54359
54360-54361
54362-54363
54364-54365
10910
10911
10912
10913
10914
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-122
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D45D-D45F
54366-54368
10915
0
D461
D461-D462
D463-D464
D465-D466
D467-D468
D469-D46B
54369
54370-54371
54372-54373
54374-54375
54376-54377
54378-54380
10916
10917
10918
10919
10920
10921
0
0
0
0
0
0
D46D
D46D-D46E
D46F-D470
D471-D472
D473-D474
D475-D477
54381
54382-54383
54384-54385
54386-54387
54388-54389
54390-54392
10922
10923
10924
10925
10926
10927
0
0
0
0
0
0
D479
D479-D47A
D47B-D47C
D47D-D47E
D47F-D480
D481-D483
54393
54394-54395
54396-54397
54398-54399
54400-54401
54402-54404
10928
10929
10930
10931
10932
10933
0
0
0
0
0
0
D485
D485-D486
D487-D488
D489-D48A
D48B-D48C
D48D-D48F
54405
54406-54407
54408-54409
54410-54411
54412-54413
54414-54416
10934
10935
10936
10937
10938
10939
0
0
0
0
0
0
D491
D491-D492
D493-D494
D495-D496
D497-D498
54417
54418-54419
54420-54421
54422-54423
54424-54425
10940
10941
10942
10943
10944
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-123
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D499-D49B
54426-54428
10945
0
D49D
D49D-D49E
D49F-D4A0
D4A1-D4A2
D4A3-D4A4
D4A5-D4A7
54429
54430-54431
54432-54433
54434-54435
54436-54437
54438-54440
10946
10947
10948
10949
10950
10951
0
0
0
0
0
0
D4A9
D4A9-D4AA
D4AB-D4AC
D4AD-D4AE
D4AF-D4B0
D4B1-D4B3
54441
54442-54443
54444-54445
54446-54447
54448-54449
54450-54452
10952
10953
10954
10955
10956
10957
0
0
0
0
0
0
D4B5
D4B5-D4B6
54453
54454-54455
10958
10959
0
0
D4B7-D4B8
D4B9-D4BA
D4BB-D4BC
D4BD-D4BF
54456-54457
54458-54459
54460-54461
54462-54464
10960
10961
10962
10963
0
0
0
0
D4C1
D4C1-D4C2
D4C3-D4C4
D4C5-D4C6
D4C7-D4C8
D4C9-D4CB
54465
54466-54467
54468-54469
54470-54471
54472-54473
54474-54476
10964
10965
10966
10967
10968
10969
0
0
0
0
0
0
D4CD
D4CD-D4CE
D4CF-D4D0
D4D1-D4D2
D4D3-D4D4
54477
54478-54479
54480-54481
54482-54483
54484-54485
10970
10971
10972
10973
10974
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Current Month, Initial Season, Tier 1
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-124
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D4D5-D4D7
54486-54488
10975
0
D4D9
D4D9-D4DA
D4DB-D4DC
D4DD-D4DE
D4DF-D4E0
D4E1-D4E3
54489
54490-54491
54492-54493
54494-54495
54496-54497
54498-54500
10976
10977
10978
10979
10980
10981
0
0
0
0
0
0
D4E5
D4E5-D4E6
D4E7-D4E8
D4E9-D4EA
D4EB-D4EC
D4ED-D4EF
54501
54502-54503
54504-54505
54506-54507
54508-54509
54510-54512
10982
10983
10984
10985
10986
10987
0
0
0
0
0
0
D4F1
D4F1-D4F2
D4F3-D4F4
D4F5-D4F6
D4F7-D4F8
D4F9-D4FB
54513
54514-54515
54516-54517
54518-54519
54520-54521
54522-54524
10988
10989
10990
10991
10992
10993
0
0
0
0
0
0
D4FD
D4FD-D4FE
D4FF-D500
D501-D502
D503-D504
D505-D507
54525
54526-54527
54528-54529
54530-54531
54532-54533
54534-54536
10994
10995
10996
10997
10998
10999
0
0
0
0
0
0
D509
D509-D50A
D50B-D50C
D50D-D50E
D50F-D510
54537
54538-54539
54540-54541
54542-54543
54544-54545
11000
11001
11002
11003
11004
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-125
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D511-D513
54546-54548
11005
0
D515
D515-D516
D517-D518
D519-D51A
D51B-D51C
D51D-D51F
54549
54550-54551
54552-54553
54554-54555
54556-54557
54558-54560
11006
11007
11008
11009
11010
11011
0
0
0
0
0
0
D521
D521-D522
D523-D524
D525-D526
D527-D528
D529-D52B
54561
54562-54563
54564-54565
54566-54567
54568-54569
54570-54572
11012
11013
11014
11015
11016
11017
0
0
0
0
0
0
D52D
D52D-D52E
D52F-D530
D531-D532
D533-D534
D535-D537
54573
54574-54575
54576-54577
54578-54579
54580-54581
54582-54584
11018
11019
11020
11021
11022
11023
0
0
0
0
0
0
D539
D539-D53A
D53B-D53C
D53D-D53E
D53F-D540
D541-D543
54585
54586-54587
54588-54589
54590-54591
54592-54593
54594-54596
11024
11025
11026
11027
11028
11029
0
0
0
0
0
0
D545
D545-D546
D547-D548
D549-D54A
D54B-D54C
54597
54598-54599
54600-54601
54602-54603
54604-54605
11030
11031
11032
11033
11034
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
25
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
MM-126
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D54D-D54F
54606-54608
11035
0
D551
D551-D552
D553-D554
D555-D556
D557-D558
D559-D55B
54609
54610-54611
54612-54613
54614-54615
54616-54617
54618-54620
11036
11037
11038
11039
11040
11041
0
0
0
0
0
0
D55D
D55D-D55E
D55F-D560
D561-D562
D563-D564
D565-D567
54621
54622-54623
54624-54625
54626-54627
54628-54629
54630-54632
11042
11043
11044
11045
11046
11047
0
0
0
0
0
0
D569
D569-D56A
D56B-D56C
D56D-D56E
D56F-D570
D571-D573
54633
54634-54635
54636-54637
54638-54639
54640-54641
54642-54644
11048
11049
11050
11051
11052
11053
0
0
0
0
0
0
D575
D575-D576
54645
54646-54647
11054
11055
0
0
D577-D578
D579-D57A
D57B-D57C
D57D-D57F
54648-54649
54650-54651
54652-54653
54654-54656
11056
11057
11058
11059
0
0
0
0
D581
D581-D582
D583-D584
D585-D586
54657
54658-54659
54660-54661
54662-54663
11060
11061
11062
11063
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Current Month, Initial Season, Tier 2
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
R
R
R
R
MM-127
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D587-D588
D589-D58B
54664-54665
54666-54668
11064
11065
0
0
D58D
D58D-D58E
D58F-D590
D591-D592
D593-D594
D595-D597
54669
54670-54671
54672-54673
54674-54675
54676-54677
54678-54680
11066
11067
11068
11069
11070
11071
0
0
0
0
0
0
D599
D599-D59A
D59B-D59C
D59D-D59E
D59F-D5A0
D5A1-D5A3
54681
54682-54683
54684-54685
54686-54687
54688-54689
54690-54692
11072
11073
11074
11075
11076
11077
0
0
0
0
0
0
D5A5
D5A5-D5A6
D5A7-D5A8
D5A9-D5AA
D5AB-D5AC
D5AD-D5AF
54693
54694-54695
54696-54697
54698-54699
54700-54701
54702-54704
11078
11079
11080
11081
11082
11083
0
0
0
0
0
0
D5B1
D5B1-D5B2
D5B3-D5B4
D5B5-D5B6
D5B7-D5B8
D5B9-D5BB
54705
54706-54707
54708-54709
54710-54711
54712-54713
54714-54716
11084
11085
11086
11087
11088
11089
0
0
0
0
0
0
D5BD
D5BD-D5BE
D5BF-D5C0
D5C1-D5C2
D5C3-D5C4
54717
54718-54719
54720-54721
54722-54723
54724-54725
11090
11091
11092
11093
11094
0
0
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-128
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D5C5-D5C7
54726-54728
11095
0
D5C9
D5C9-D5CA
D5CB-D5CC
D5CD-D5CE
D5CF-D5D0
D5D1-D5D3
54729
54730-54731
54732-54733
54734-54735
54736-54737
54738-54740
11096
11097
11098
11099
11100
11101
0
0
0
0
0
0
D5D5
D5D5-D5D6
D5D7-D5D8
D5D9-D5DA
D5DB-D5DC
D5DD-D5DF
54741
54742-54743
54744-54745
54746-54747
54748-54749
54750-54752
11102
11103
11104
11105
11106
11107
0
0
0
0
0
0
D5E1
D5E1-D5E2
D5E3-D5E4
D5E5-D5E6
D5E7-D5E8
D5E9-D5EB
54753
54754-54755
54756-54757
54758-54759
54760-54761
54762-54764
11108
11109
11110
11111
11112
11113
0
0
0
0
0
0
D5ED
D5ED-D5EE
D5EF-D5F0
D5F1-D5F2
D5F3-D5F4
D5F5-D5F7
54765
54766-54767
54768-54769
54770-54771
54772-54773
54774-54776
11114
11115
11116
11117
11118
11119
0
0
0
0
0
0
D5F9
D5F9-D5FA
D5FB-D5FC
D5FD-D5FE
D5FF-D600
54777
54778-54779
54780-54781
54782-54783
54784-54785
11120
11121
11122
11123
11124
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-129
2: Modbus Map - Input Registers
DNP
Obj
Addr. (hex)
Address(3X)
Line
Pt
Description
D601-D603
54786-54788
11125
0
D605
D605-D606
D607-D608
D609-D60A
D60B-D60C
D60D-D60F
54789
54790-54791
54792-54793
54794-54795
54796-54797
54798-54800
11126
11127
11128
11129
11130
11131
0
0
0
0
0
0
D611
D611-D612
D613-D614
D615-D616
D617-D618
D619-D61B
54801
54802-54803
54804-54805
54806-54807
54808-54809
54810-54812
11132
11133
11134
11135
11136
11137
0
0
0
0
0
0
D61D
D61D-D61E
D61F-D620
D621-D622
D623-D624
D625-D627
54813
54814-54815
54816-54817
54818-54819
54820-54821
54822-54824
11138
11139
11140
11141
11142
11143
0
0
0
0
0
0
D629
D629-D62A
D62B-D62C
D62D-D62E
D62F-D630
D631-D633
54825
54826-54827
54828-54829
54830-54831
54832-54833
54834-54836
11144
11145
11146
11147
11148
11149
0
0
0
0
0
0
D635
D635-D636
54837
54838-54839
11150
11151
0
0
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
D637-D638
D639-D63A
54840-54841
54842-54843
11152
11153
0
0
Current Month, Initial Season, Tier 3
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64 R
F120 R
MM-130
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D63B-D63C
D63D-D63F
54844-54845
54846-54848
11154
11155
0
0
D641
D641-D642
D643-D644
D645-D646
D647-D648
D649-D64B
54849
54850-54851
54852-54853
54854-54855
54856-54857
54858-54860
11156
11157
11158
11159
11160
11161
0
0
0
0
0
0
D64D
D64D-D64E
D64F-D650
D651-D652
D653-D654
D655-D657
54861
54862-54863
54864-54865
54866-54867
54868-54869
54870-54872
11162
11163
11164
11165
11166
11167
0
0
0
0
0
0
D659
D659-D65A
D65B-D65C
D65D-D65E
D65F-D660
D661-D663
54873
54874-54875
54876-54877
54878-54879
54880-54881
54882-54884
11168
11169
11170
11171
11172
11173
0
0
0
0
0
0
D665
D665-D666
D667-D668
D669-D66A
D66B-D66C
D66D-D66F
54885
54886-54887
54888-54889
54890-54891
54892-54893
54894-54896
11174
11175
11176
11177
11178
11179
0
0
0
0
0
0
D671
D671-D672
D673-D674
D675-D676
D677-D678
54897
54898-54899
54900-54901
54902-54903
54904-54905
11180
11181
11182
11183
11184
0
0
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-131
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D679-D67B
54906-54908
11185
0
D67D
D67D-D67E
D67F-D680
D681-D682
D683-D684
D685-D687
54909
54910-54911
54912-54913
54914-54915
54916-54917
54918-54920
11186
11187
11188
11189
11190
11191
0
0
0
0
0
0
D689
D689-D68A
D68B-D68C
D68D-D68E
D68F-D690
D691-D693
54921
54922-54923
54924-54925
54926-54927
54928-54929
54930-54932
11192
11193
11194
11195
11196
11197
0
0
0
0
0
0
D695
D695-D696
D697-D698
D699-D69A
D69B-D69C
D69D-D69F
54933
54934-54935
54936-54937
54938-54939
54940-54941
54942-54944
11198
11199
11200
11201
11202
11203
0
0
0
0
0
0
D6A1
D6A1-D6A2
D6A3-D6A4
D6A5-D6A6
D6A7-D6A8
D6A9-D6AB
54945
54946-54947
54948-54949
54950-54951
54952-54953
54954-54956
11204
11205
11206
11207
11208
11209
0
0
0
0
0
0
D6AD
D6AD-D6AE
D6AF-D6B0
D6B1-D6B2
D6B3-D6B4
54957
54958-54959
54960-54961
54962-54963
54964-54965
11210
11211
11212
11213
11214
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-132
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D6B5-D6B7
54966-54968
11215
0
D6B9
D6B9-D6BA
D6BB-D6BC
D6BD-D6BE
D6BF-D6C0
D6C1-D6C3
54969
54970-54971
54972-54973
54974-54975
54976-54977
54978-54980
11216
11217
11218
11219
11220
11221
0
0
0
0
0
0
D6C5
D6C5-D6C6
D6C7-D6C8
D6C9-D6CA
D6CB-D6CC
D6CD-D6CF
54981
54982-54983
54984-54985
54986-54987
54988-54989
54990-54992
11222
11223
11224
11225
11226
11227
0
0
0
0
0
0
D6D1
D6D1-D6D2
D6D3-D6D4
D6D5-D6D6
D6D7-D6D8
D6D9-D6DB
54993
54994-54995
54996-54997
54998-54999
55000-55001
55002-55004
11228
11229
11230
11231
11232
11233
0
0
0
0
0
0
D6DD
D6DD-D6DE
D6DF-D6E0
D6E1-D6E2
D6E3-D6E4
D6E5-D6E7
55005
55006-55007
55008-55009
55010-55011
55012-55013
55014-55016
11234
11235
11236
11237
11238
11239
0
0
0
0
0
0
D6E9
D6E9-D6EA
D6EB-D6EC
D6ED-D6EE
D6EF-D6F0
55017
55018-55019
55020-55021
55022-55023
55024-55025
11240
11241
11242
11243
11244
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-133
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D6F1-D6F3
55026-55028
11245
0
D6F5
D6F5-D6F6
55029
55030-55031
11246
11247
0
0
D6F7-D6F8
D6F9-D6FA
D6FB-D6FC
D6FD-D6FF
55032-55033
55034-55035
55036-55037
55038-55040
11248
11249
11250
11251
0
0
0
0
D701
D701-D702
D703-D704
D705-D706
D707-D708
D709-D70B
55041
55042-55043
55044-55045
55046-55047
55048-55049
55050-55052
11252
11253
11254
11255
11256
11257
0
0
0
0
0
0
D70D
D70D-D70E
D70F-D710
D711-D712
D713-D714
D715-D717
55053
55054-55055
55056-55057
55058-55059
55060-55061
55062-55064
11258
11259
11260
11261
11262
11263
0
0
0
0
0
0
D719
D719-D71A
D71B-D71C
D71D-D71E
D71F-D720
D721-D723
55065
55066-55067
55068-55069
55070-55071
55072-55073
55074-55076
11264
11265
11266
11267
11268
11269
0
0
0
0
0
0
D725
D725-D726
D727-D728
D729-D72A
55077
55078-55079
55080-55081
55082-55083
11270
11271
11272
11273
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Current Month, Initial Season, Tier 4
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
R
R
R
R
MM-134
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D72B-D72C
D72D-D72F
55084-55085
55086-55088
11274
11275
0
0
D731
D731-D732
D733-D734
D735-D736
D737-D738
D739-D73B
55089
55090-55091
55092-55093
55094-55095
55096-55097
55098-55100
11276
11277
11278
11279
11280
11281
0
0
0
0
0
0
D73D
D73D-D73E
D73F-D740
D741-D742
D743-D744
D745-D747
55101
55102-55103
55104-55105
55106-55107
55108-55109
55110-55112
11282
11283
11284
11285
11286
11287
0
0
0
0
0
0
D749
D749-D74A
D74B-D74C
D74D-D74E
D74F-D750
D751-D753
55113
55114-55115
55116-55117
55118-55119
55120-55121
55122-55124
11288
11289
11290
11291
11292
11293
0
0
0
0
0
0
D755
D755-D756
D757-D758
D759-D75A
D75B-D75C
D75D-D75F
55125
55126-55127
55128-55129
55130-55131
55132-55133
55134-55136
11294
11295
11296
11297
11298
11299
0
0
0
0
0
0
D761
D761-D762
D763-D764
D765-D766
D767-D768
55137
55138-55139
55140-55141
55142-55143
55144-55145
11300
11301
11302
11303
11304
0
0
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-135
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D769-D76B
55146-55148
11305
0
D76D
D76D-D76E
D76F-D770
D771-D772
D773-D774
D775-D777
55149
55150-55151
55152-55153
55154-55155
55156-55157
55158-55160
11306
11307
11308
11309
11310
11311
0
0
0
0
0
0
D779
D779-D77A
D77B-D77C
D77D-D77E
D77F-D780
D781-D783
55161
55162-55163
55164-55165
55166-55167
55168-55169
55170-55172
11312
11313
11314
11315
11316
11317
0
0
0
0
0
0
D785
D785-D786
D787-D788
D789-D78A
D78B-D78C
D78D-D78F
55173
55174-55175
55176-55177
55178-55179
55180-55181
55182-55184
11318
11319
11320
11321
11322
11323
0
0
0
0
0
0
D791
D791-D792
D793-D794
D795-D796
D797-D798
D799-D79B
55185
55186-55187
55188-55189
55190-55191
55192-55193
55194-55196
11324
11325
11326
11327
11328
11329
0
0
0
0
0
0
D79D
D79D-D79E
D79F-D7A0
D7A1-D7A2
D7A3-D7A4
55197
55198-55199
55200-55201
55202-55203
55204-55205
11330
11331
11332
11333
11334
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-136
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D7A5-D7A7
55206-55208
11335
0
D7A9
D7A9-D7AA
D7AB-D7AC
D7AD-D7AE
D7AF-D7B0
D7B1-D7B3
55209
55210-55211
55212-55213
55214-55215
55216-55217
55218-55220
11336
11337
11338
11339
11340
11341
0
0
0
0
0
0
D7B5
D7B5-D7B6
55221
55222-55223
11342
11343
0
0
D7B7-D7B8
D7B9-D7BA
D7BB-D7BC
D7BD-D7BF
55224-55225
55226-55227
55228-55229
55230-55232
11344
11345
11346
11347
0
0
0
0
D7C1
D7C1-D7C2
D7C3-D7C4
D7C5-D7C6
D7C7-D7C8
D7C9-D7CB
55233
55234-55235
55236-55237
55238-55239
55240-55241
55242-55244
11348
11349
11350
11351
11352
11353
0
0
0
0
0
0
D7CD
D7CD-D7CE
D7CF-D7D0
D7D1-D7D2
D7D3-D7D4
D7D5-D7D7
55245
55246-55247
55248-55249
55250-55251
55252-55253
55254-55256
11354
11355
11356
11357
11358
11359
0
0
0
0
0
0
D7D9
D7D9-D7DA
D7DB-D7DC
D7DD-D7DE
D7DF-D7E0
55257
55258-55259
55260-55261
55262-55263
55264-55265
11360
11361
11362
11363
11364
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Current Month, Final Season, Tier 0
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-137
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D7E1-D7E3
55266-55268
11365
0
D7E5
D7E5-D7E6
D7E7-D7E8
D7E9-D7EA
D7EB-D7EC
D7ED-D7EF
55269
55270-55271
55272-55273
55274-55275
55276-55277
55278-55280
11366
11367
11368
11369
11370
11371
0
0
0
0
0
0
D7F1
D7F1-D7F2
D7F3-D7F4
D7F5-D7F6
D7F7-D7F8
D7F9-D7FB
55281
55282-55283
55284-55285
55286-55287
55288-55289
55290-55292
11372
11373
11374
11375
11376
11377
0
0
0
0
0
0
D7FD
D7FD-D7FE
D7FF-D800
D801-D802
D803-D804
D805-D807
55293
55294-55295
55296-55297
55298-55299
55300-55301
55302-55304
11378
11379
11380
11381
11382
11383
0
0
0
0
0
0
D809
D809-D80A
D80B-D80C
D80D-D80E
D80F-D810
D811-D813
55305
55306-55307
55308-55309
55310-55311
55312-55313
55314-55316
11384
11385
11386
11387
11388
11389
0
0
0
0
0
0
D815
D815-D816
D817-D818
D819-D81A
D81B-D81C
55317
55318-55319
55320-55321
55322-55323
55324-55325
11390
11391
11392
11393
11394
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-138
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D81D-D81F
55326-55328
11395
0
D821
D821-D822
D823-D824
D825-D826
D827-D828
D829-D82B
55329
55330-55331
55332-55333
55334-55335
55336-55337
55338-55340
11396
11397
11398
11399
11400
11401
0
0
0
0
0
0
D82D
D82D-D82E
D82F-D830
D831-D832
D833-D834
D835-D837
55341
55342-55343
55344-55345
55346-55347
55348-55349
55350-55352
11402
11403
11404
11405
11406
11407
0
0
0
0
0
0
D839
D839-D83A
D83B-D83C
D83D-D83E
D83F-D840
D841-D843
55353
55354-55355
55356-55357
55358-55359
55360-55361
55362-55364
11408
11409
11410
11411
11412
11413
0
0
0
0
0
0
D845
D845-D846
D847-D848
D849-D84A
D84B-D84C
D84D-D84F
55365
55366-55367
55368-55369
55370-55371
55372-55373
55374-55376
11414
11415
11416
11417
11418
11419
0
0
0
0
0
0
D851
D851-D852
D853-D854
D855-D856
D857-D858
55377
55378-55379
55380-55381
55382-55383
55384-55385
11420
11421
11422
11423
11424
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-139
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D859-D85B
55386-55388
11425
0
D85D
D85D-D85E
D85F-D860
D861-D862
D863-D864
D865-D867
55389
55390-55391
55392-55393
55394-55395
55396-55397
55398-55400
11426
11427
11428
11429
11430
11431
0
0
0
0
0
0
D869
D869-D86A
D86B-D86C
D86D-D86E
D86F-D870
D871-D873
55401
55402-55403
55404-55405
55406-55407
55408-55409
55410-55412
11432
11433
11434
11435
11436
11437
0
0
0
0
0
0
D875
D875-D876
55413
55414-55415
11438
11439
0
0
D877-D878
D879-D87A
D87B-D87C
D87D-D87F
55416-55417
55418-55419
55420-55421
55422-55424
11440
11441
11442
11443
0
0
0
0
D881
D881-D882
D883-D884
D885-D886
D887-D888
D889-D88B
55425
55426-55427
55428-55429
55430-55431
55432-55433
55434-55436
11444
11445
11446
11447
11448
11449
0
0
0
0
0
0
D88D
D88D-D88E
D88F-D890
D891-D892
D893-D894
55437
55438-55439
55440-55441
55442-55443
55444-55445
11450
11451
11452
11453
11454
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Current Month, Final Season, Tier 1
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-140
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D895-D897
55446-55448
11455
0
D899
D899-D89A
D89B-D89C
D89D-D89E
D89F-D8A0
D8A1-D8A3
55449
55450-55451
55452-55453
55454-55455
55456-55457
55458-55460
11456
11457
11458
11459
11460
11461
0
0
0
0
0
0
D8A5
D8A5-D8A6
D8A7-D8A8
D8A9-D8AA
D8AB-D8AC
D8AD-D8AF
55461
55462-55463
55464-55465
55466-55467
55468-55469
55470-55472
11462
11463
11464
11465
11466
11467
0
0
0
0
0
0
D8B1
D8B1-D8B2
D8B3-D8B4
D8B5-D8B6
D8B7-D8B8
D8B9-D8BB
55473
55474-55475
55476-55477
55478-55479
55480-55481
55482-55484
11468
11469
11470
11471
11472
11473
0
0
0
0
0
0
D8BD
D8BD-D8BE
D8BF-D8C0
D8C1-D8C2
D8C3-D8C4
D8C5-D8C7
55485
55486-55487
55488-55489
55490-55491
55492-55493
55494-55496
11474
11475
11476
11477
11478
11479
0
0
0
0
0
0
D8C9
D8C9-D8CA
D8CB-D8CC
D8CD-D8CE
D8CF-D8D0
55497
55498-55499
55500-55501
55502-55503
55504-55505
11480
11481
11482
11483
11484
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-141
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D8D1-D8D3
55506-55508
11485
0
D8D5
D8D5-D8D6
D8D7-D8D8
D8D9-D8DA
D8DB-D8DC
D8DD-D8DF
55509
55510-55511
55512-55513
55514-55515
55516-55517
55518-55520
11486
11487
11488
11489
11490
11491
0
0
0
0
0
0
D8E1
D8E1-D8E2
D8E3-D8E4
D8E5-D8E6
D8E7-D8E8
D8E9-D8EB
55521
55522-55523
55524-55525
55526-55527
55528-55529
55530-55532
11492
11493
11494
11495
11496
11497
0
0
0
0
0
0
D8ED
D8ED-D8EE
D8EF-D8F0
D8F1-D8F2
D8F3-D8F4
D8F5-D8F7
55533
55534-55535
55536-55537
55538-55539
55540-55541
55542-55544
11498
11499
11500
11501
11502
11503
0
0
0
0
0
0
D8F9
D8F9-D8FA
D8FB-D8FC
D8FD-D8FE
D8FF-D900
D901-D903
55545
55546-55547
55548-55549
55550-55551
55552-55553
55554-55556
11504
11505
11506
11507
11508
11509
0
0
0
0
0
0
D905
D905-D906
D907-D908
D909-D90A
D90B-D90C
55557
55558-55559
55560-55561
55562-55563
55564-55565
11510
11511
11512
11513
11514
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-142
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D90D-D90F
55566-55568
11515
0
D911
D911-D912
D913-D914
D915-D916
D917-D918
D919-D91B
55569
55570-55571
55572-55573
55574-55575
55576-55577
55578-55580
11516
11517
11518
11519
11520
11521
0
0
0
0
0
0
D91D
D91D-D91E
D91F-D920
D921-D922
D923-D924
D925-D927
55581
55582-55583
55584-55585
55586-55587
55588-55589
55590-55592
11522
11523
11524
11525
11526
11527
0
0
0
0
0
0
D929
D929-D92A
D92B-D92C
D92D-D92E
D92F-D930
D931-D933
55593
55594-55595
55596-55597
55598-55599
55600-55601
55602-55604
11528
11529
11530
11531
11532
11533
0
0
0
0
0
0
D935
D935-D936
55605
55606-55607
11534
11535
0
0
D937-D938
D939-D93A
D93B-D93C
D93D-D93F
55608-55609
55610-55611
55612-55613
55614-55616
11536
11537
11538
11539
0
0
0
0
D941
D941-D942
D943-D944
D945-D946
55617
55618-55619
55620-55621
55622-55623
11540
11541
11542
11543
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Current Month, Final Season, Tier 2
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
R
R
R
R
MM-143
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D947-D948
D949-D94B
55624-55625
55626-55628
11544
11545
0
0
D94D
D94D-D94E
D94F-D950
D951-D952
D953-D954
D955-D957
55629
55630-55631
55632-55633
55634-55635
55636-55637
55638-55640
11546
11547
11548
11549
11550
11551
0
0
0
0
0
0
D959
D959-D95A
D95B-D95C
D95D-D95E
D95F-D960
D961-D963
55641
55642-55643
55644-55645
55646-55647
55648-55649
55650-55652
11552
11553
11554
11555
11556
11557
0
0
0
0
0
0
D965
D965-D966
D967-D968
D969-D96A
D96B-D96C
D96D-D96F
55653
55654-55655
55656-55657
55658-55659
55660-55661
55662-55664
11558
11559
11560
11561
11562
11563
0
0
0
0
0
0
D971
D971-D972
D973-D974
D975-D976
D977-D978
D979-D97B
55665
55666-55667
55668-55669
55670-55671
55672-55673
55674-55676
11564
11565
11566
11567
11568
11569
0
0
0
0
0
0
D97D
D97D-D97E
D97F-D980
D981-D982
D983-D984
55677
55678-55679
55680-55681
55682-55683
55684-55685
11570
11571
11572
11573
11574
0
0
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-144
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D985-D987
55686-55688
11575
0
D989
D989-D98A
D98B-D98C
D98D-D98E
D98F-D990
D991-D993
55689
55690-55691
55692-55693
55694-55695
55696-55697
55698-55700
11576
11577
11578
11579
11580
11581
0
0
0
0
0
0
D995
D995-D996
D997-D998
D999-D99A
D99B-D99C
D99D-D99F
55701
55702-55703
55704-55705
55706-55707
55708-55709
55710-55712
11582
11583
11584
11585
11586
11587
0
0
0
0
0
0
D9A1
D9A1-D9A2
D9A3-D9A4
D9A5-D9A6
D9A7-D9A8
D9A9-D9AB
55713
55714-55715
55716-55717
55718-55719
55720-55721
55722-55724
11588
11589
11590
11591
11592
11593
0
0
0
0
0
0
D9AD
D9AD-D9AE
D9AF-D9B0
D9B1-D9B2
D9B3-D9B4
D9B5-D9B7
55725
55726-55727
55728-55729
55730-55731
55732-55733
55734-55736
11594
11595
11596
11597
11598
11599
0
0
0
0
0
0
D9B9
D9B9-D9BA
D9BB-D9BC
D9BD-D9BE
D9BF-D9C0
55737
55738-55739
55740-55741
55742-55743
55744-55745
11600
11601
11602
11603
11604
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-145
2: Modbus Map - Input Registers
DNP
Obj
Addr. (hex)
Address(3X)
Line
Pt
Description
D9C1-D9C3
55746-55748
11605
0
D9C5
D9C5-D9C6
D9C7-D9C8
D9C9-D9CA
D9CB-D9CC
D9CD-D9CF
55749
55750-55751
55752-55753
55754-55755
55756-55757
55758-55760
11606
11607
11608
11609
11610
11611
0
0
0
0
0
0
D9D1
D9D1-D9D2
D9D3-D9D4
D9D5-D9D6
D9D7-D9D8
D9D9-D9DB
55761
55762-55763
55764-55765
55766-55767
55768-55769
55770-55772
11612
11613
11614
11615
11616
11617
0
0
0
0
0
0
D9DD
D9DD-D9DE
D9DF-D9E0
D9E1-D9E2
D9E3-D9E4
D9E5-D9E7
55773
55774-55775
55776-55777
55778-55779
55780-55781
55782-55784
11618
11619
11620
11621
11622
11623
0
0
0
0
0
0
D9E9
D9E9-D9EA
D9EB-D9EC
D9ED-D9EE
D9EF-D9F0
D9F1-D9F3
55785
55786-55787
55788-55789
55790-55791
55792-55793
55794-55796
11624
11625
11626
11627
11628
11629
0
0
0
0
0
0
D9F5
D9F5-D9F6
55797
55798-55799
11630
11631
0
0
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
D9F7-D9F8
D9F9-D9FA
55800-55801
55802-55803
11632
11633
0
0
Current Month, Final Season, Tier 3
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64 R
F120 R
MM-146
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
D9FB-D9FC
D9FD-D9FF
55804-55805
55806-55808
11634
11635
0
0
DA01
DA01-DA02
DA03-DA04
DA05-DA06
DA07-DA08
DA09-DA0B
55809
55810-55811
55812-55813
55814-55815
55816-55817
55818-55820
11636
11637
11638
11639
11640
11641
0
0
0
0
0
0
DA0D
DA0D-DA0E
DA0F-DA10
DA11-DA12
DA13-DA14
DA15-DA17
55821
55822-55823
55824-55825
55826-55827
55828-55829
55830-55832
11642
11643
11644
11645
11646
11647
0
0
0
0
0
0
DA19
DA19-DA1A
DA1B-DA1C
DA1D-DA1E
DA1F-DA20
DA21-DA23
55833
55834-55835
55836-55837
55838-55839
55840-55841
55842-55844
11648
11649
11650
11651
11652
11653
0
0
0
0
0
0
DA25
DA25-DA26
DA27-DA28
DA29-DA2A
DA2B-DA2C
DA2D-DA2F
55845
55846-55847
55848-55849
55850-55851
55852-55853
55854-55856
11654
11655
11656
11657
11658
11659
0
0
0
0
0
0
DA31
DA31-DA32
DA33-DA34
DA35-DA36
DA37-DA38
55857
55858-55859
55860-55861
55862-55863
55864-55865
11660
11661
11662
11663
11664
0
0
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-147
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DA39-DA3B
55866-55868
11665
0
DA3D
DA3D-DA3E
DA3F-DA40
DA41-DA42
DA43-DA44
DA45-DA47
55869
55870-55871
55872-55873
55874-55875
55876-55877
55878-55880
11666
11667
11668
11669
11670
11671
0
0
0
0
0
0
DA49
DA49-DA4A
DA4B-DA4C
DA4D-DA4E
DA4F-DA50
DA51-DA53
55881
55882-55883
55884-55885
55886-55887
55888-55889
55890-55892
11672
11673
11674
11675
11676
11677
0
0
0
0
0
0
DA55
DA55-DA56
DA57-DA58
DA59-DA5A
DA5B-DA5C
DA5D-DA5F
55893
55894-55895
55896-55897
55898-55899
55900-55901
55902-55904
11678
11679
11680
11681
11682
11683
0
0
0
0
0
0
DA61
DA61-DA62
DA63-DA64
DA65-DA66
DA67-DA68
DA69-DA6B
55905
55906-55907
55908-55909
55910-55911
55912-55913
55914-55916
11684
11685
11686
11687
11688
11689
0
0
0
0
0
0
DA6D
DA6D-DA6E
DA6F-DA70
DA71-DA72
DA73-DA74
55917
55918-55919
55920-55921
55922-55923
55924-55925
11690
11691
11692
11693
11694
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-148
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DA75-DA77
55926-55928
11695
0
DA79
DA79-DA7A
DA7B-DA7C
DA7D-DA7E
DA7F-DA80
DA81-DA83
55929
55930-55931
55932-55933
55934-55935
55936-55937
55938-55940
11696
11697
11698
11699
11700
11701
0
0
0
0
0
0
DA85
DA85-DA86
DA87-DA88
DA89-DA8A
DA8B-DA8C
DA8D-DA8F
55941
55942-55943
55944-55945
55946-55947
55948-55949
55950-55952
11702
11703
11704
11705
11706
11707
0
0
0
0
0
0
DA91
DA91-DA92
DA93-DA94
DA95-DA96
DA97-DA98
DA99-DA9B
55953
55954-55955
55956-55957
55958-55959
55960-55961
55962-55964
11708
11709
11710
11711
11712
11713
0
0
0
0
0
0
DA9D
DA9D-DA9E
DA9F-DAA0
DAA1-DAA2
DAA3-DAA4
DAA5-DAA7
55965
55966-55967
55968-55969
55970-55971
55972-55973
55974-55976
11714
11715
11716
11717
11718
11719
0
0
0
0
0
0
DAA9
DAA9-DAAA
DAAB-DAAC
DAAD-DAAE
DAAF-DAB0
55977
55978-55979
55980-55981
55982-55983
55984-55985
11720
11721
11722
11723
11724
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-149
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DAB1-DAB3
55986-55988
11725
0
DAB5
DAB5-DAB6
55989
55990-55991
11726
11727
0
0
DAB7-DAB8
DAB9-DABA
DABB-DABC
DABD-DABF
55992-55993
55994-55995
55996-55997
55998-56000
11728
11729
11730
11731
0
0
0
0
DAC1
DAC1-DAC2
DAC3-DAC4
DAC5-DAC6
DAC7-DAC8
DAC9-DACB
56001
56002-56003
56004-56005
56006-56007
56008-56009
56010-56012
11732
11733
11734
11735
11736
11737
0
0
0
0
0
0
DACD
DACD-DACE
DACF-DAD0
DAD1-DAD2
DAD3-DAD4
DAD5-DAD7
56013
56014-56015
56016-56017
56018-56019
56020-56021
56022-56024
11738
11739
11740
11741
11742
11743
0
0
0
0
0
0
DAD9
DAD9-DADA
DADB-DADC
DADD-DADE
DADF-DAE0
DAE1-DAE3
56025
56026-56027
56028-56029
56030-56031
56032-56033
56034-56036
11744
11745
11746
11747
11748
11749
0
0
0
0
0
0
DAE5
DAE5-DAE6
DAE7-DAE8
DAE9-DAEA
56037
56038-56039
56040-56041
56042-56043
11750
11751
11752
11753
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Current Month, Final Season, Tier 4
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
R
R
R
R
MM-150
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DAEB-DAEC
DAED-DAEF
56044-56045
56046-56048
11754
11755
0
0
DAF1
DAF1-DAF2
DAF3-DAF4
DAF5-DAF6
DAF7-DAF8
DAF9-DAFB
56049
56050-56051
56052-56053
56054-56055
56056-56057
56058-56060
11756
11757
11758
11759
11760
11761
0
0
0
0
0
0
DAFD
DAFD-DAFE
DAFF-DB00
DB01-DB02
DB03-DB04
DB05-DB07
56061
56062-56063
56064-56065
56066-56067
56068-56069
56070-56072
11762
11763
11764
11765
11766
11767
0
0
0
0
0
0
DB09
DB09-DB0A
DB0B-DB0C
DB0D-DB0E
DB0F-DB10
DB11-DB13
56073
56074-56075
56076-56077
56078-56079
56080-56081
56082-56084
11768
11769
11770
11771
11772
11773
0
0
0
0
0
0
DB15
DB15-DB16
DB17-DB18
DB19-DB1A
DB1B-DB1C
DB1D-DB1F
56085
56086-56087
56088-56089
56090-56091
56092-56093
56094-56096
11774
11775
11776
11777
11778
11779
0
0
0
0
0
0
DB21
DB21-DB22
DB23-DB24
DB25-DB26
DB27-DB28
56097
56098-56099
56100-56101
56102-56103
56104-56105
11780
11781
11782
11783
11784
0
0
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-151
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DB29-DB2B
56106-56108
11785
0
DB2D
DB2D-DB2E
DB2F-DB30
DB31-DB32
DB33-DB34
DB35-DB37
56109
56110-56111
56112-56113
56114-56115
56116-56117
56118-56120
11786
11787
11788
11789
11790
11791
0
0
0
0
0
0
DB39
DB39-DB3A
DB3B-DB3C
DB3D-DB3E
DB3F-DB40
DB41-DB43
56121
56122-56123
56124-56125
56126-56127
56128-56129
56130-56132
11792
11793
11794
11795
11796
11797
0
0
0
0
0
0
DB45
DB45-DB46
DB47-DB48
DB49-DB4A
DB4B-DB4C
DB4D-DB4F
56133
56134-56135
56136-56137
56138-56139
56140-56141
56142-56144
11798
11799
11800
11801
11802
11803
0
0
0
0
0
0
DB51
DB51-DB52
DB53-DB54
DB55-DB56
DB57-DB58
DB59-DB5B
56145
56146-56147
56148-56149
56150-56151
56152-56153
56154-56156
11804
11805
11806
11807
11808
11809
0
0
0
0
0
0
DB5D
DB5D-DB5E
DB5F-DB60
DB61-DB62
DB63-DB64
56157
56158-56159
56160-56161
56162-56163
56164-56165
11810
11811
11812
11813
11814
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-152
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DB65-DB67
56166-56168
11815
0
DB69
DB69-DB6A
DB6B-DB6C
DB6D-DB6E
DB6F-DB70
DB71-DB73
56169
56170-56171
56172-56173
56174-56175
56176-56177
56178-56180
11816
11817
11818
11819
11820
11821
0
0
0
0
0
0
DB75
DB75-DB76
56181
56182-56183
11822
11823
0
0
base=11824,
group
count=96,
groups=15
DNP
Obj
Description
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Tier 0 is for total
Prior Month Tier 0:
Prior Month Tier 1:
Prior Month Tier 2:
Prior Month Tier 3:
Prior Month Tier 4:
Prior Month Tier 0:
Prior Month Tier 1:
Prior Month Tier 2:
Prior Month Tier 3:
Prior Month Tier 4:
Prior Month Tier 0:
Prior Month Tier 1:
Prior Month Tier 2:
Prior Month Tier 3:
Prior Month Tier 4:
DB77-DB78
DB79-DB7A
DB7B-DB7C
DB7D-DB7F
56184-56185
56186-56187
56188-56189
56190-56192
11824
11825
11826
11827
56184
56186
56188
56190
DB81
56193
11828
56193
Electro Industries/GaugeTech
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
R
Whole month data
Whole month data
Whole month data
Whole month data
Whole month data
Initial season data
Initial season data
Initial season data
Initial season data
Initial season data
Final season data
Final season data
Final season data
Final season data
Final season data
Prior Month, Whole Month, Tier 0
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
The Leader In Power Monitoring and Smart Grid Solutions
Range
Doc# E171707
MM-153
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DB81-DB82
DB83-DB84
DB85-DB86
DB87-DB88
DB89-DB8B
56194-56195
56196-56197
56198-56199
56200-56201
56202-56204
11829
11830
11831
11832
11833
56194
56196
56198
56200
56202
DB8D
DB8D-DB8E
DB8F-DB90
DB91-DB92
DB93-DB94
DB95-DB97
56205
56206-56207
56208-56209
56210-56211
56212-56213
56214-56216
11834
11835
11836
11837
11838
11839
56205
56206
56208
56210
56212
56214
DB99
DB99-DB9A
DB9B-DB9C
DB9D-DB9E
DB9F-DBA0
DBA1-DBA3
56217
56218-56219
56220-56221
56222-56223
56224-56225
56226-56228
11840
11841
11842
11843
11844
11845
56217
56218
56220
56222
56224
56226
DBA5
DBA5-DBA6
DBA7-DBA8
DBA9-DBAA
DBAB-DBAC
DBAD-DBAF
56229
56230-56231
56232-56233
56234-56235
56236-56237
56238-56240
11846
11847
11848
11849
11850
11851
56229
56230
56232
56234
56236
56238
DBB1
DBB1-DBB2
DBB3-DBB4
DBB5-DBB6
DBB7-DBB8
DBB9-DBBB
56241
56242-56243
56244-56245
56246-56247
56248-56249
56250-56252
11852
11853
11854
11855
11856
11857
56241
56242
56244
56246
56248
56250
DBBD
DBBD-DBBE
56253
56254-56255
11858
11859
56253
56254
DNP
Obj
Description
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
F52
F64
F120
F120
F122
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
Notes
MM-154
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DBBF-DBC0
DBC1-DBC2
DBC3-DBC4
DBC5-DBC7
56256-56257
56258-56259
56260-56261
56262-56264
11860
11861
11862
11863
56256
56258
56260
56262
DBC9
DBC9-DBCA
DBCB-DBCC
DBCD-DBCE
DBCF-DBD0
DBD1-DBD3
56265
56266-56267
56268-56269
56270-56271
56272-56273
56274-56276
11864
11865
11866
11867
11868
11869
56265
56266
56268
56270
56272
56274
DBD5
DBD5-DBD6
DBD7-DBD8
DBD9-DBDA
DBDB-DBDC
DBDD-DBDF
56277
56278-56279
56280-56281
56282-56283
56284-56285
56286-56288
11870
11871
11872
11873
11874
11875
56277
56278
56280
56282
56284
56286
DBE1
DBE1-DBE2
DBE3-DBE4
DBE5-DBE6
DBE7-DBE8
DBE9-DBEB
56289
56290-56291
56292-56293
56294-56295
56296-56297
56298-56300
11876
11877
11878
11879
11880
11881
56289
56290
56292
56294
56296
56298
DBED
DBED-DBEE
DBEF-DBF0
DBF1-DBF2
DBF3-DBF4
DBF5-DBF7
56301
56302-56303
56304-56305
56306-56307
56308-56309
56310-56312
11882
11883
11884
11885
11886
11887
56301
56302
56304
56306
56308
56310
DBF9
DBF9-DBFA
DBFB-DBFC
56313
56314-56315
56316-56317
11888
11889
11890
56313
56314
56316
DNP
Obj
Description
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
R
R
R
Notes
MM-155
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DBFD-DBFE
DBFF-DC00
DC01-DC03
56318-56319
56320-56321
56322-56324
11891
11892
11893
56318
56320
56322
DC05
DC05-DC06
DC07-DC08
DC09-DC0A
DC0B-DC0C
DC0D-DC0F
56325
56326-56327
56328-56329
56330-56331
56332-56333
56334-56336
11894
11895
11896
11897
11898
11899
56325
56326
56328
56330
56332
56334
DC11
DC11-DC12
DC13-DC14
DC15-DC16
DC17-DC18
DC19-DC1B
56337
56338-56339
56340-56341
56342-56343
56344-56345
56346-56348
11900
11901
11902
11903
11904
11905
56337
56338
56340
56342
56344
56346
DC1D
DC1D-DC1E
DC1F-DC20
DC21-DC22
DC23-DC24
DC25-DC27
56349
56350-56351
56352-56353
56354-56355
56356-56357
56358-56360
11906
11907
11908
11909
11910
11911
56349
56350
56352
56354
56356
56358
DC29
DC29-DC2A
DC2B-DC2C
DC2D-DC2E
DC2F-DC30
DC31-DC33
56361
56362-56363
56364-56365
56366-56367
56368-56369
56370-56372
11912
11913
11914
11915
11916
11917
56361
56362
56364
56366
56368
56370
DC35
DC35-DC36
56373
56374-56375
11918
11919
56373
56374
DC37-DC38
56376-56377
11920
0
DNP
Obj
Description
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Prior Month, Whole Month, Tier 1
Accumulator for Monitored Data Set 1
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
R
MM-156
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DC39-DC3A
DC3B-DC3C
DC3D-DC3F
56378-56379
56380-56381
56382-56384
11921
11922
11923
0
0
0
DC41
DC41-DC42
DC43-DC44
DC45-DC46
DC47-DC48
DC49-DC4B
56385
56386-56387
56388-56389
56390-56391
56392-56393
56394-56396
11924
11925
11926
11927
11928
11929
0
0
0
0
0
0
DC4D
DC4D-DC4E
DC4F-DC50
DC51-DC52
DC53-DC54
DC55-DC57
56397
56398-56399
56400-56401
56402-56403
56404-56405
56406-56408
11930
11931
11932
11933
11934
11935
0
0
0
0
0
0
DC59
DC59-DC5A
DC5B-DC5C
DC5D-DC5E
DC5F-DC60
DC61-DC63
56409
56410-56411
56412-56413
56414-56415
56416-56417
56418-56420
11936
11937
11938
11939
11940
11941
0
0
0
0
0
0
DC65
DC65-DC66
DC67-DC68
DC69-DC6A
DC6B-DC6C
DC6D-DC6F
56421
56422-56423
56424-56425
56426-56427
56428-56429
56430-56432
11942
11943
11944
11945
11946
11947
0
0
0
0
0
0
DC71
DC71-DC72
DC73-DC74
DC75-DC76
56433
56434-56435
56436-56437
56438-56439
11948
11949
11950
11951
0
0
0
0
DNP
Obj
Description
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
R
R
R
R
MM-157
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DC77-DC78
DC79-DC7B
56440-56441
56442-56444
11952
11953
0
0
DC7D
DC7D-DC7E
DC7F-DC80
DC81-DC82
DC83-DC84
DC85-DC87
56445
56446-56447
56448-56449
56450-56451
56452-56453
56454-56456
11954
11955
11956
11957
11958
11959
0
0
0
0
0
0
DC89
DC89-DC8A
DC8B-DC8C
DC8D-DC8E
DC8F-DC90
DC91-DC93
56457
56458-56459
56460-56461
56462-56463
56464-56465
56466-56468
11960
11961
11962
11963
11964
11965
0
0
0
0
0
0
DC95
DC95-DC96
DC97-DC98
DC99-DC9A
DC9B-DC9C
DC9D-DC9F
56469
56470-56471
56472-56473
56474-56475
56476-56477
56478-56480
11966
11967
11968
11969
11970
11971
0
0
0
0
0
0
DCA1
DCA1-DCA2
DCA3-DCA4
DCA5-DCA6
DCA7-DCA8
DCA9-DCAB
56481
56482-56483
56484-56485
56486-56487
56488-56489
56490-56492
11972
11973
11974
11975
11976
11977
0
0
0
0
0
0
DCAD
DCAD-DCAE
DCAF-DCB0
DCB1-DCB2
DCB3-DCB4
56493
56494-56495
56496-56497
56498-56499
56500-56501
11978
11979
11980
11981
11982
0
0
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-158
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DCB5-DCB7
56502-56504
11983
0
DCB9
DCB9-DCBA
DCBB-DCBC
DCBD-DCBE
DCBF-DCC0
DCC1-DCC3
56505
56506-56507
56508-56509
56510-56511
56512-56513
56514-56516
11984
11985
11986
11987
11988
11989
0
0
0
0
0
0
DCC5
DCC5-DCC6
DCC7-DCC8
DCC9-DCCA
DCCB-DCCC
DCCD-DCCF
56517
56518-56519
56520-56521
56522-56523
56524-56525
56526-56528
11990
11991
11992
11993
11994
11995
0
0
0
0
0
0
DCD1
DCD1-DCD2
DCD3-DCD4
DCD5-DCD6
DCD7-DCD8
DCD9-DCDB
56529
56530-56531
56532-56533
56534-56535
56536-56537
56538-56540
11996
11997
11998
11999
12000
12001
0
0
0
0
0
0
DCDD
DCDD-DCDE
DCDF-DCE0
DCE1-DCE2
DCE3-DCE4
DCE5-DCE7
56541
56542-56543
56544-56545
56546-56547
56548-56549
56550-56552
12002
12003
12004
12005
12006
12007
0
0
0
0
0
0
DCE9
DCE9-DCEA
DCEB-DCEC
DCED-DCEE
DCEF-DCF0
56553
56554-56555
56556-56557
56558-56559
56560-56561
12008
12009
12010
12011
12012
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-159
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DCF1-DCF3
56562-56564
12013
0
DCF5
DCF5-DCF6
56565
56566-56567
12014
12015
0
0
DCF7-DCF8
DCF9-DCFA
DCFB-DCFC
DCFD-DCFF
56568-56569
56570-56571
56572-56573
56574-56576
12016
12017
12018
12019
0
0
0
0
DD01
DD01-DD02
DD03-DD04
DD05-DD06
DD07-DD08
DD09-DD0B
56577
56578-56579
56580-56581
56582-56583
56584-56585
56586-56588
12020
12021
12022
12023
12024
12025
0
0
0
0
0
0
DD0D
DD0D-DD0E
DD0F-DD10
DD11-DD12
DD13-DD14
DD15-DD17
56589
56590-56591
56592-56593
56594-56595
56596-56597
56598-56600
12026
12027
12028
12029
12030
12031
0
0
0
0
0
0
DD19
DD19-DD1A
DD1B-DD1C
DD1D-DD1E
DD1F-DD20
DD21-DD23
56601
56602-56603
56604-56605
56606-56607
56608-56609
56610-56612
12032
12033
12034
12035
12036
12037
0
0
0
0
0
0
DD25
DD25-DD26
DD27-DD28
DD29-DD2A
56613
56614-56615
56616-56617
56618-56619
12038
12039
12040
12041
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Prior Month, Whole Month, Tier 2
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
R
R
R
R
MM-160
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DD2B-DD2C
DD2D-DD2F
56620-56621
56622-56624
12042
12043
0
0
DD31
DD31-DD32
DD33-DD34
DD35-DD36
DD37-DD38
DD39-DD3B
56625
56626-56627
56628-56629
56630-56631
56632-56633
56634-56636
12044
12045
12046
12047
12048
12049
0
0
0
0
0
0
DD3D
DD3D-DD3E
DD3F-DD40
DD41-DD42
DD43-DD44
DD45-DD47
56637
56638-56639
56640-56641
56642-56643
56644-56645
56646-56648
12050
12051
12052
12053
12054
12055
0
0
0
0
0
0
DD49
DD49-DD4A
DD4B-DD4C
DD4D-DD4E
DD4F-DD50
DD51-DD53
56649
56650-56651
56652-56653
56654-56655
56656-56657
56658-56660
12056
12057
12058
12059
12060
12061
0
0
0
0
0
0
DD55
DD55-DD56
DD57-DD58
DD59-DD5A
DD5B-DD5C
DD5D-DD5F
56661
56662-56663
56664-56665
56666-56667
56668-56669
56670-56672
12062
12063
12064
12065
12066
12067
0
0
0
0
0
0
DD61
DD61-DD62
DD63-DD64
DD65-DD66
DD67-DD68
56673
56674-56675
56676-56677
56678-56679
56680-56681
12068
12069
12070
12071
12072
0
0
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-161
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DD69-DD6B
56682-56684
12073
0
DD6D
DD6D-DD6E
DD6F-DD70
DD71-DD72
DD73-DD74
DD75-DD77
56685
56686-56687
56688-56689
56690-56691
56692-56693
56694-56696
12074
12075
12076
12077
12078
12079
0
0
0
0
0
0
DD79
DD79-DD7A
DD7B-DD7C
DD7D-DD7E
DD7F-DD80
DD81-DD83
56697
56698-56699
56700-56701
56702-56703
56704-56705
56706-56708
12080
12081
12082
12083
12084
12085
0
0
0
0
0
0
DD85
DD85-DD86
DD87-DD88
DD89-DD8A
DD8B-DD8C
DD8D-DD8F
56709
56710-56711
56712-56713
56714-56715
56716-56717
56718-56720
12086
12087
12088
12089
12090
12091
0
0
0
0
0
0
DD91
DD91-DD92
DD93-DD94
DD95-DD96
DD97-DD98
DD99-DD9B
56721
56722-56723
56724-56725
56726-56727
56728-56729
56730-56732
12092
12093
12094
12095
12096
12097
0
0
0
0
0
0
DD9D
DD9D-DD9E
DD9F-DDA0
DDA1-DDA2
DDA3-DDA4
56733
56734-56735
56736-56737
56738-56739
56740-56741
12098
12099
12100
12101
12102
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-162
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DDA5-DDA7
56742-56744
12103
0
DDA9
DDA9-DDAA
DDAB-DDAC
DDAD-DDAE
DDAF-DDB0
DDB1-DDB3
56745
56746-56747
56748-56749
56750-56751
56752-56753
56754-56756
12104
12105
12106
12107
12108
12109
0
0
0
0
0
0
DDB5
DDB5-DDB6
56757
56758-56759
12110
12111
0
0
DDB7-DDB8
DDB9-DDBA
DDBB-DDBC
DDBD-DDBF
56760-56761
56762-56763
56764-56765
56766-56768
12112
12113
12114
12115
0
0
0
0
DDC1
DDC1-DDC2
DDC3-DDC4
DDC5-DDC6
DDC7-DDC8
DDC9-DDCB
56769
56770-56771
56772-56773
56774-56775
56776-56777
56778-56780
12116
12117
12118
12119
12120
12121
0
0
0
0
0
0
DDCD
DDCD-DDCE
DDCF-DDD0
DDD1-DDD2
DDD3-DDD4
DDD5-DDD7
56781
56782-56783
56784-56785
56786-56787
56788-56789
56790-56792
12122
12123
12124
12125
12126
12127
0
0
0
0
0
0
DDD9
DDD9-DDDA
DDDB-DDDC
DDDD-DDDE
56793
56794-56795
56796-56797
56798-56799
12128
12129
12130
12131
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Prior Month, Whole Month, Tier 3
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
R
R
R
R
MM-163
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DDDF-DDE0
DDE1-DDE3
56800-56801
56802-56804
12132
12133
0
0
DDE5
DDE5-DDE6
DDE7-DDE8
DDE9-DDEA
DDEB-DDEC
DDED-DDEF
56805
56806-56807
56808-56809
56810-56811
56812-56813
56814-56816
12134
12135
12136
12137
12138
12139
0
0
0
0
0
0
DDF1
DDF1-DDF2
DDF3-DDF4
DDF5-DDF6
DDF7-DDF8
DDF9-DDFB
56817
56818-56819
56820-56821
56822-56823
56824-56825
56826-56828
12140
12141
12142
12143
12144
12145
0
0
0
0
0
0
DDFD
DDFD-DDFE
DDFF-DE00
DE01-DE02
DE03-DE04
DE05-DE07
56829
56830-56831
56832-56833
56834-56835
56836-56837
56838-56840
12146
12147
12148
12149
12150
12151
0
0
0
0
0
0
DE09
DE09-DE0A
DE0B-DE0C
DE0D-DE0E
DE0F-DE10
DE11-DE13
56841
56842-56843
56844-56845
56846-56847
56848-56849
56850-56852
12152
12153
12154
12155
12156
12157
0
0
0
0
0
0
DE15
DE15-DE16
DE17-DE18
DE19-DE1A
DE1B-DE1C
56853
56854-56855
56856-56857
56858-56859
56860-56861
12158
12159
12160
12161
12162
0
0
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-164
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DE1D-DE1F
56862-56864
12163
0
DE21
DE21-DE22
DE23-DE24
DE25-DE26
DE27-DE28
DE29-DE2B
56865
56866-56867
56868-56869
56870-56871
56872-56873
56874-56876
12164
12165
12166
12167
12168
12169
0
0
0
0
0
0
DE2D
DE2D-DE2E
DE2F-DE30
DE31-DE32
DE33-DE34
DE35-DE37
56877
56878-56879
56880-56881
56882-56883
56884-56885
56886-56888
12170
12171
12172
12173
12174
12175
0
0
0
0
0
0
DE39
DE39-DE3A
DE3B-DE3C
DE3D-DE3E
DE3F-DE40
DE41-DE43
56889
56890-56891
56892-56893
56894-56895
56896-56897
56898-56900
12176
12177
12178
12179
12180
12181
0
0
0
0
0
0
DE45
DE45-DE46
DE47-DE48
DE49-DE4A
DE4B-DE4C
DE4D-DE4F
56901
56902-56903
56904-56905
56906-56907
56908-56909
56910-56912
12182
12183
12184
12185
12186
12187
0
0
0
0
0
0
DE51
DE51-DE52
DE53-DE54
DE55-DE56
DE57-DE58
56913
56914-56915
56916-56917
56918-56919
56920-56921
12188
12189
12190
12191
12192
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-165
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DE59-DE5B
56922-56924
12193
0
DE5D
DE5D-DE5E
DE5F-DE60
DE61-DE62
DE63-DE64
DE65-DE67
56925
56926-56927
56928-56929
56930-56931
56932-56933
56934-56936
12194
12195
12196
12197
12198
12199
0
0
0
0
0
0
DE69
DE69-DE6A
DE6B-DE6C
DE6D-DE6E
DE6F-DE70
DE71-DE73
56937
56938-56939
56940-56941
56942-56943
56944-56945
56946-56948
12200
12201
12202
12203
12204
12205
0
0
0
0
0
0
DE75
DE75-DE76
56949
56950-56951
12206
12207
0
0
DE77-DE78
DE79-DE7A
DE7B-DE7C
DE7D-DE7F
56952-56953
56954-56955
56956-56957
56958-56960
12208
12209
12210
12211
0
0
0
0
DE81
DE81-DE82
DE83-DE84
DE85-DE86
DE87-DE88
DE89-DE8B
56961
56962-56963
56964-56965
56966-56967
56968-56969
56970-56972
12212
12213
12214
12215
12216
12217
0
0
0
0
0
0
DE8D
DE8D-DE8E
DE8F-DE90
DE91-DE92
56973
56974-56975
56976-56977
56978-56979
12218
12219
12220
12221
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Prior Month, Whole Month, Tier 4
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
R
R
R
R
MM-166
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DE93-DE94
DE95-DE97
56980-56981
56982-56984
12222
12223
0
0
DE99
DE99-DE9A
DE9B-DE9C
DE9D-DE9E
DE9F-DEA0
DEA1-DEA3
56985
56986-56987
56988-56989
56990-56991
56992-56993
56994-56996
12224
12225
12226
12227
12228
12229
0
0
0
0
0
0
DEA5
DEA5-DEA6
DEA7-DEA8
DEA9-DEAA
DEAB-DEAC
DEAD-DEAF
56997
56998-56999
57000-57001
57002-57003
57004-57005
57006-57008
12230
12231
12232
12233
12234
12235
0
0
0
0
0
0
DEB1
DEB1-DEB2
DEB3-DEB4
DEB5-DEB6
DEB7-DEB8
DEB9-DEBB
57009
57010-57011
57012-57013
57014-57015
57016-57017
57018-57020
12236
12237
12238
12239
12240
12241
0
0
0
0
0
0
DEBD
DEBD-DEBE
DEBF-DEC0
DEC1-DEC2
DEC3-DEC4
DEC5-DEC7
57021
57022-57023
57024-57025
57026-57027
57028-57029
57030-57032
12242
12243
12244
12245
12246
12247
0
0
0
0
0
0
DEC9
DEC9-DECA
DECB-DECC
DECD-DECE
DECF-DED0
57033
57034-57035
57036-57037
57038-57039
57040-57041
12248
12249
12250
12251
12252
0
0
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-167
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DED1-DED3
57042-57044
12253
0
DED5
DED5-DED6
DED7-DED8
DED9-DEDA
DEDB-DEDC
DEDD-DEDF
57045
57046-57047
57048-57049
57050-57051
57052-57053
57054-57056
12254
12255
12256
12257
12258
12259
0
0
0
0
0
0
DEE1
DEE1-DEE2
DEE3-DEE4
DEE5-DEE6
DEE7-DEE8
DEE9-DEEB
57057
57058-57059
57060-57061
57062-57063
57064-57065
57066-57068
12260
12261
12262
12263
12264
12265
0
0
0
0
0
0
DEED
DEED-DEEE
DEEF-DEF0
DEF1-DEF2
DEF3-DEF4
DEF5-DEF7
57069
57070-57071
57072-57073
57074-57075
57076-57077
57078-57080
12266
12267
12268
12269
12270
12271
0
0
0
0
0
0
DEF9
DEF9-DEFA
DEFB-DEFC
DEFD-DEFE
DEFF-DF00
DF01-DF03
57081
57082-57083
57084-57085
57086-57087
57088-57089
57090-57092
12272
12273
12274
12275
12276
12277
0
0
0
0
0
0
DF05
DF05-DF06
DF07-DF08
DF09-DF0A
DF0B-DF0C
57093
57094-57095
57096-57097
57098-57099
57100-57101
12278
12279
12280
12281
12282
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-168
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DF0D-DF0F
57102-57104
12283
0
DF11
DF11-DF12
DF13-DF14
DF15-DF16
DF17-DF18
DF19-DF1B
57105
57106-57107
57108-57109
57110-57111
57112-57113
57114-57116
12284
12285
12286
12287
12288
12289
0
0
0
0
0
0
DF1D
DF1D-DF1E
DF1F-DF20
DF21-DF22
DF23-DF24
DF25-DF27
57117
57118-57119
57120-57121
57122-57123
57124-57125
57126-57128
12290
12291
12292
12293
12294
12295
0
0
0
0
0
0
DF29
DF29-DF2A
DF2B-DF2C
DF2D-DF2E
DF2F-DF30
DF31-DF33
57129
57130-57131
57132-57133
57134-57135
57136-57137
57138-57140
12296
12297
12298
12299
12300
12301
0
0
0
0
0
0
DF35
DF35-DF36
57141
57142-57143
12302
12303
0
0
DF37-DF38
DF39-DF3A
DF3B-DF3C
DF3D-DF3F
57144-57145
57146-57147
57148-57149
57150-57152
12304
12305
12306
12307
57144
57146
57148
57150
DF41
DF41-DF42
DF43-DF44
DF45-DF46
DF47-DF48
57153
57154-57155
57156-57157
57158-57159
57160-57161
12308
12309
12310
12311
12312
57153
57154
57156
57158
57160
DNP
Obj
Description
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Prior Month, Initial Season, Tier 0
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-169
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DF49-DF4B
57162-57164
12313
57162
DF4D
DF4D-DF4E
DF4F-DF50
DF51-DF52
DF53-DF54
DF55-DF57
57165
57166-57167
57168-57169
57170-57171
57172-57173
57174-57176
12314
12315
12316
12317
12318
12319
57165
57166
57168
57170
57172
57174
DF59
DF59-DF5A
DF5B-DF5C
DF5D-DF5E
DF5F-DF60
DF61-DF63
57177
57178-57179
57180-57181
57182-57183
57184-57185
57186-57188
12320
12321
12322
12323
12324
12325
57177
57178
57180
57182
57184
57186
DF65
DF65-DF66
DF67-DF68
DF69-DF6A
DF6B-DF6C
DF6D-DF6F
57189
57190-57191
57192-57193
57194-57195
57196-57197
57198-57200
12326
12327
12328
12329
12330
12331
57189
57190
57192
57194
57196
57198
DF71
DF71-DF72
DF73-DF74
DF75-DF76
DF77-DF78
DF79-DF7B
57201
57202-57203
57204-57205
57206-57207
57208-57209
57210-57212
12332
12333
12334
12335
12336
12337
57201
57202
57204
57206
57208
57210
DF7D
DF7D-DF7E
DF7F-DF80
DF81-DF82
DF83-DF84
57213
57214-57215
57216-57217
57218-57219
57220-57221
12338
12339
12340
12341
12342
57213
57214
57216
57218
57220
DNP
Obj
Description
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-170
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DF85-DF87
57222-57224
12343
57222
DF89
DF89-DF8A
DF8B-DF8C
DF8D-DF8E
DF8F-DF90
DF91-DF93
57225
57226-57227
57228-57229
57230-57231
57232-57233
57234-57236
12344
12345
12346
12347
12348
12349
57225
57226
57228
57230
57232
57234
DF95
DF95-DF96
DF97-DF98
DF99-DF9A
DF9B-DF9C
DF9D-DF9F
57237
57238-57239
57240-57241
57242-57243
57244-57245
57246-57248
12350
12351
12352
12353
12354
12355
57237
57238
57240
57242
57244
57246
DFA1
DFA1-DFA2
DFA3-DFA4
DFA5-DFA6
DFA7-DFA8
DFA9-DFAB
57249
57250-57251
57252-57253
57254-57255
57256-57257
57258-57260
12356
12357
12358
12359
12360
12361
57249
57250
57252
57254
57256
57258
DFAD
DFAD-DFAE
DFAF-DFB0
DFB1-DFB2
DFB3-DFB4
DFB5-DFB7
57261
57262-57263
57264-57265
57266-57267
57268-57269
57270-57272
12362
12363
12364
12365
12366
12367
57261
57262
57264
57266
57268
57270
DFB9
DFB9-DFBA
DFBB-DFBC
DFBD-DFBE
DFBF-DFC0
57273
57274-57275
57276-57277
57278-57279
57280-57281
12368
12369
12370
12371
12372
57273
57274
57276
57278
57280
DNP
Obj
Description
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-171
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DFC1-DFC3
57282-57284
12373
57282
DFC5
DFC5-DFC6
DFC7-DFC8
DFC9-DFCA
DFCB-DFCC
DFCD-DFCF
57285
57286-57287
57288-57289
57290-57291
57292-57293
57294-57296
12374
12375
12376
12377
12378
12379
57285
57286
57288
57290
57292
57294
DFD1
DFD1-DFD2
DFD3-DFD4
DFD5-DFD6
DFD7-DFD8
DFD9-DFDB
57297
57298-57299
57300-57301
57302-57303
57304-57305
57306-57308
12380
12381
12382
12383
12384
12385
57297
57298
57300
57302
57304
57306
DFDD
DFDD-DFDE
DFDF-DFE0
DFE1-DFE2
DFE3-DFE4
DFE5-DFE7
57309
57310-57311
57312-57313
57314-57315
57316-57317
57318-57320
12386
12387
12388
12389
12390
12391
57309
57310
57312
57314
57316
57318
DFE9
DFE9-DFEA
DFEB-DFEC
DFED-DFEE
DFEF-DFF0
DFF1-DFF3
57321
57322-57323
57324-57325
57326-57327
57328-57329
57330-57332
12392
12393
12394
12395
12396
12397
57321
57322
57324
57326
57328
57330
DFF5
DFF5-DFF6
57333
57334-57335
12398
12399
57333
57334
DFF7-DFF8
DFF9-DFFA
DFFB-DFFC
57336-57337
57338-57339
57340-57341
12400
12401
12402
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Prior Month, Initial Season, Tier 1
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64 R
F120 R
F120 R
MM-172
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
DFFD-DFFF
57342-57344
12403
0
E001
E001-E002
E003-E004
E005-E006
E007-E008
E009-E00B
57345
57346-57347
57348-57349
57350-57351
57352-57353
57354-57356
12404
12405
12406
12407
12408
12409
0
0
0
0
0
0
E00D
E00D-E00E
E00F-E010
E011-E012
E013-E014
E015-E017
57357
57358-57359
57360-57361
57362-57363
57364-57365
57366-57368
12410
12411
12412
12413
12414
12415
0
0
0
0
0
0
E019
E019-E01A
E01B-E01C
E01D-E01E
E01F-E020
E021-E023
57369
57370-57371
57372-57373
57374-57375
57376-57377
57378-57380
12416
12417
12418
12419
12420
12421
0
0
0
0
0
0
E025
E025-E026
E027-E028
E029-E02A
E02B-E02C
E02D-E02F
57381
57382-57383
57384-57385
57386-57387
57388-57389
57390-57392
12422
12423
12424
12425
12426
12427
0
0
0
0
0
0
E031
E031-E032
E033-E034
E035-E036
E037-E038
57393
57394-57395
57396-57397
57398-57399
57400-57401
12428
12429
12430
12431
12432
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-173
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E039-E03B
57402-57404
12433
0
E03D
E03D-E03E
E03F-E040
E041-E042
E043-E044
E045-E047
57405
57406-57407
57408-57409
57410-57411
57412-57413
57414-57416
12434
12435
12436
12437
12438
12439
0
0
0
0
0
0
E049
E049-E04A
E04B-E04C
E04D-E04E
E04F-E050
E051-E053
57417
57418-57419
57420-57421
57422-57423
57424-57425
57426-57428
12440
12441
12442
12443
12444
12445
0
0
0
0
0
0
E055
E055-E056
E057-E058
E059-E05A
E05B-E05C
E05D-E05F
57429
57430-57431
57432-57433
57434-57435
57436-57437
57438-57440
12446
12447
12448
12449
12450
12451
0
0
0
0
0
0
E061
E061-E062
E063-E064
E065-E066
E067-E068
E069-E06B
57441
57442-57443
57444-57445
57446-57447
57448-57449
57450-57452
12452
12453
12454
12455
12456
12457
0
0
0
0
0
0
E06D
E06D-E06E
E06F-E070
E071-E072
E073-E074
57453
57454-57455
57456-57457
57458-57459
57460-57461
12458
12459
12460
12461
12462
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-174
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E075-E077
57462-57464
12463
0
E079
E079-E07A
E07B-E07C
E07D-E07E
E07F-E080
E081-E083
57465
57466-57467
57468-57469
57470-57471
57472-57473
57474-57476
12464
12465
12466
12467
12468
12469
0
0
0
0
0
0
E085
E085-E086
E087-E088
E089-E08A
E08B-E08C
E08D-E08F
57477
57478-57479
57480-57481
57482-57483
57484-57485
57486-57488
12470
12471
12472
12473
12474
12475
0
0
0
0
0
0
E091
E091-E092
E093-E094
E095-E096
E097-E098
E099-E09B
57489
57490-57491
57492-57493
57494-57495
57496-57497
57498-57500
12476
12477
12478
12479
12480
12481
0
0
0
0
0
0
E09D
E09D-E09E
E09F-E0A0
E0A1-E0A2
E0A3-E0A4
E0A5-E0A7
57501
57502-57503
57504-57505
57506-57507
57508-57509
57510-57512
12482
12483
12484
12485
12486
12487
0
0
0
0
0
0
E0A9
E0A9-E0AA
E0AB-E0AC
E0AD-E0AE
E0AF-E0B0
57513
57514-57515
57516-57517
57518-57519
57520-57521
12488
12489
12490
12491
12492
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-175
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E0B1-E0B3
57522-57524
12493
0
E0B5
E0B5-E0B6
57525
57526-57527
12494
12495
0
0
E0B7-E0B8
E0B9-E0BA
E0BB-E0BC
E0BD-E0BF
57528-57529
57530-57531
57532-57533
57534-57536
12496
12497
12498
12499
0
0
0
0
E0C1
E0C1-E0C2
E0C3-E0C4
E0C5-E0C6
E0C7-E0C8
E0C9-E0CB
57537
57538-57539
57540-57541
57542-57543
57544-57545
57546-57548
12500
12501
12502
12503
12504
12505
0
0
0
0
0
0
E0CD
E0CD-E0CE
E0CF-E0D0
E0D1-E0D2
E0D3-E0D4
E0D5-E0D7
57549
57550-57551
57552-57553
57554-57555
57556-57557
57558-57560
12506
12507
12508
12509
12510
12511
0
0
0
0
0
0
E0D9
E0D9-E0DA
E0DB-E0DC
E0DD-E0DE
E0DF-E0E0
E0E1-E0E3
57561
57562-57563
57564-57565
57566-57567
57568-57569
57570-57572
12512
12513
12514
12515
12516
12517
0
0
0
0
0
0
E0E5
E0E5-E0E6
E0E7-E0E8
E0E9-E0EA
57573
57574-57575
57576-57577
57578-57579
12518
12519
12520
12521
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Prior Month, Initial Season, Tier 2
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
R
R
R
R
MM-176
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E0EB-E0EC
E0ED-E0EF
57580-57581
57582-57584
12522
12523
0
0
E0F1
E0F1-E0F2
E0F3-E0F4
E0F5-E0F6
E0F7-E0F8
E0F9-E0FB
57585
57586-57587
57588-57589
57590-57591
57592-57593
57594-57596
12524
12525
12526
12527
12528
12529
0
0
0
0
0
0
E0FD
E0FD-E0FE
E0FF-E100
E101-E102
E103-E104
E105-E107
57597
57598-57599
57600-57601
57602-57603
57604-57605
57606-57608
12530
12531
12532
12533
12534
12535
0
0
0
0
0
0
E109
E109-E10A
E10B-E10C
E10D-E10E
E10F-E110
E111-E113
57609
57610-57611
57612-57613
57614-57615
57616-57617
57618-57620
12536
12537
12538
12539
12540
12541
0
0
0
0
0
0
E115
E115-E116
E117-E118
E119-E11A
E11B-E11C
E11D-E11F
57621
57622-57623
57624-57625
57626-57627
57628-57629
57630-57632
12542
12543
12544
12545
12546
12547
0
0
0
0
0
0
E121
E121-E122
E123-E124
E125-E126
E127-E128
57633
57634-57635
57636-57637
57638-57639
57640-57641
12548
12549
12550
12551
12552
0
0
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-177
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E129-E12B
57642-57644
12553
0
E12D
E12D-E12E
E12F-E130
E131-E132
E133-E134
E135-E137
57645
57646-57647
57648-57649
57650-57651
57652-57653
57654-57656
12554
12555
12556
12557
12558
12559
0
0
0
0
0
0
E139
E139-E13A
E13B-E13C
E13D-E13E
E13F-E140
E141-E143
57657
57658-57659
57660-57661
57662-57663
57664-57665
57666-57668
12560
12561
12562
12563
12564
12565
0
0
0
0
0
0
E145
E145-E146
E147-E148
E149-E14A
E14B-E14C
E14D-E14F
57669
57670-57671
57672-57673
57674-57675
57676-57677
57678-57680
12566
12567
12568
12569
12570
12571
0
0
0
0
0
0
E151
E151-E152
E153-E154
E155-E156
E157-E158
E159-E15B
57681
57682-57683
57684-57685
57686-57687
57688-57689
57690-57692
12572
12573
12574
12575
12576
12577
0
0
0
0
0
0
E15D
E15D-E15E
E15F-E160
E161-E162
E163-E164
57693
57694-57695
57696-57697
57698-57699
57700-57701
12578
12579
12580
12581
12582
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-178
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E165-E167
57702-57704
12583
0
E169
E169-E16A
E16B-E16C
E16D-E16E
E16F-E170
E171-E173
57705
57706-57707
57708-57709
57710-57711
57712-57713
57714-57716
12584
12585
12586
12587
12588
12589
0
0
0
0
0
0
E175
E175-E176
57717
57718-57719
12590
12591
0
0
E177-E178
E179-E17A
E17B-E17C
E17D-E17F
57720-57721
57722-57723
57724-57725
57726-57728
12592
12593
12594
12595
0
0
0
0
E181
E181-E182
E183-E184
E185-E186
E187-E188
E189-E18B
57729
57730-57731
57732-57733
57734-57735
57736-57737
57738-57740
12596
12597
12598
12599
12600
12601
0
0
0
0
0
0
E18D
E18D-E18E
E18F-E190
E191-E192
E193-E194
E195-E197
57741
57742-57743
57744-57745
57746-57747
57748-57749
57750-57752
12602
12603
12604
12605
12606
12607
0
0
0
0
0
0
E199
E199-E19A
E19B-E19C
E19D-E19E
57753
57754-57755
57756-57757
57758-57759
12608
12609
12610
12611
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Prior Month, Initial Season, Tier 3
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
R
R
R
R
MM-179
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E19F-E1A0
E1A1-E1A3
57760-57761
57762-57764
12612
12613
0
0
E1A5
E1A5-E1A6
E1A7-E1A8
E1A9-E1AA
E1AB-E1AC
E1AD-E1AF
57765
57766-57767
57768-57769
57770-57771
57772-57773
57774-57776
12614
12615
12616
12617
12618
12619
0
0
0
0
0
0
E1B1
E1B1-E1B2
E1B3-E1B4
E1B5-E1B6
E1B7-E1B8
E1B9-E1BB
57777
57778-57779
57780-57781
57782-57783
57784-57785
57786-57788
12620
12621
12622
12623
12624
12625
0
0
0
0
0
0
E1BD
E1BD-E1BE
E1BF-E1C0
E1C1-E1C2
E1C3-E1C4
E1C5-E1C7
57789
57790-57791
57792-57793
57794-57795
57796-57797
57798-57800
12626
12627
12628
12629
12630
12631
0
0
0
0
0
0
E1C9
E1C9-E1CA
E1CB-E1CC
E1CD-E1CE
E1CF-E1D0
E1D1-E1D3
57801
57802-57803
57804-57805
57806-57807
57808-57809
57810-57812
12632
12633
12634
12635
12636
12637
0
0
0
0
0
0
E1D5
E1D5-E1D6
E1D7-E1D8
E1D9-E1DA
E1DB-E1DC
57813
57814-57815
57816-57817
57818-57819
57820-57821
12638
12639
12640
12641
12642
0
0
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-180
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E1DD-E1DF
57822-57824
12643
0
E1E1
E1E1-E1E2
E1E3-E1E4
E1E5-E1E6
E1E7-E1E8
E1E9-E1EB
57825
57826-57827
57828-57829
57830-57831
57832-57833
57834-57836
12644
12645
12646
12647
12648
12649
0
0
0
0
0
0
E1ED
E1ED-E1EE
E1EF-E1F0
E1F1-E1F2
E1F3-E1F4
E1F5-E1F7
57837
57838-57839
57840-57841
57842-57843
57844-57845
57846-57848
12650
12651
12652
12653
12654
12655
0
0
0
0
0
0
E1F9
E1F9-E1FA
E1FB-E1FC
E1FD-E1FE
E1FF-E200
E201-E203
57849
57850-57851
57852-57853
57854-57855
57856-57857
57858-57860
12656
12657
12658
12659
12660
12661
0
0
0
0
0
0
E205
E205-E206
E207-E208
E209-E20A
E20B-E20C
E20D-E20F
57861
57862-57863
57864-57865
57866-57867
57868-57869
57870-57872
12662
12663
12664
12665
12666
12667
0
0
0
0
0
0
E211
E211-E212
E213-E214
E215-E216
E217-E218
57873
57874-57875
57876-57877
57878-57879
57880-57881
12668
12669
12670
12671
12672
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-181
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E219-E21B
57882-57884
12673
0
E21D
E21D-E21E
E21F-E220
E221-E222
E223-E224
E225-E227
57885
57886-57887
57888-57889
57890-57891
57892-57893
57894-57896
12674
12675
12676
12677
12678
12679
0
0
0
0
0
0
E229
E229-E22A
E22B-E22C
E22D-E22E
E22F-E230
E231-E233
57897
57898-57899
57900-57901
57902-57903
57904-57905
57906-57908
12680
12681
12682
12683
12684
12685
0
0
0
0
0
0
E235
E235-E236
57909
57910-57911
12686
12687
0
0
E237-E238
E239-E23A
E23B-E23C
E23D-E23F
57912-57913
57914-57915
57916-57917
57918-57920
12688
12689
12690
12691
0
0
0
0
E241
E241-E242
E243-E244
E245-E246
E247-E248
E249-E24B
57921
57922-57923
57924-57925
57926-57927
57928-57929
57930-57932
12692
12693
12694
12695
12696
12697
0
0
0
0
0
0
E24D
E24D-E24E
E24F-E250
E251-E252
57933
57934-57935
57936-57937
57938-57939
12698
12699
12700
12701
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Prior Month, Initial Season, Tier 4
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
R
R
R
R
MM-182
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E253-E254
E255-E257
57940-57941
57942-57944
12702
12703
0
0
E259
E259-E25A
E25B-E25C
E25D-E25E
E25F-E260
E261-E263
57945
57946-57947
57948-57949
57950-57951
57952-57953
57954-57956
12704
12705
12706
12707
12708
12709
0
0
0
0
0
0
E265
E265-E266
E267-E268
E269-E26A
E26B-E26C
E26D-E26F
57957
57958-57959
57960-57961
57962-57963
57964-57965
57966-57968
12710
12711
12712
12713
12714
12715
0
0
0
0
0
0
E271
E271-E272
E273-E274
E275-E276
E277-E278
E279-E27B
57969
57970-57971
57972-57973
57974-57975
57976-57977
57978-57980
12716
12717
12718
12719
12720
12721
0
0
0
0
0
0
E27D
E27D-E27E
E27F-E280
E281-E282
E283-E284
E285-E287
57981
57982-57983
57984-57985
57986-57987
57988-57989
57990-57992
12722
12723
12724
12725
12726
12727
0
0
0
0
0
0
E289
E289-E28A
E28B-E28C
E28D-E28E
E28F-E290
57993
57994-57995
57996-57997
57998-57999
58000-58001
12728
12729
12730
12731
12732
0
0
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-183
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E291-E293
58002-58004
12733
0
E295
E295-E296
E297-E298
E299-E29A
E29B-E29C
E29D-E29F
58005
58006-58007
58008-58009
58010-58011
58012-58013
58014-58016
12734
12735
12736
12737
12738
12739
0
0
0
0
0
0
E2A1
E2A1-E2A2
E2A3-E2A4
E2A5-E2A6
E2A7-E2A8
E2A9-E2AB
58017
58018-58019
58020-58021
58022-58023
58024-58025
58026-58028
12740
12741
12742
12743
12744
12745
0
0
0
0
0
0
E2AD
E2AD-E2AE
E2AF-E2B0
E2B1-E2B2
E2B3-E2B4
E2B5-E2B7
58029
58030-58031
58032-58033
58034-58035
58036-58037
58038-58040
12746
12747
12748
12749
12750
12751
0
0
0
0
0
0
E2B9
E2B9-E2BA
E2BB-E2BC
E2BD-E2BE
E2BF-E2C0
E2C1-E2C3
58041
58042-58043
58044-58045
58046-58047
58048-58049
58050-58052
12752
12753
12754
12755
12756
12757
0
0
0
0
0
0
E2C5
E2C5-E2C6
E2C7-E2C8
E2C9-E2CA
E2CB-E2CC
58053
58054-58055
58056-58057
58058-58059
58060-58061
12758
12759
12760
12761
12762
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-184
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E2CD-E2CF
58062-58064
12763
0
E2D1
E2D1-E2D2
E2D3-E2D4
E2D5-E2D6
E2D7-E2D8
E2D9-E2DB
58065
58066-58067
58068-58069
58070-58071
58072-58073
58074-58076
12764
12765
12766
12767
12768
12769
0
0
0
0
0
0
E2DD
E2DD-E2DE
E2DF-E2E0
E2E1-E2E2
E2E3-E2E4
E2E5-E2E7
58077
58078-58079
58080-58081
58082-58083
58084-58085
58086-58088
12770
12771
12772
12773
12774
12775
0
0
0
0
0
0
E2E9
E2E9-E2EA
E2EB-E2EC
E2ED-E2EE
E2EF-E2F0
E2F1-E2F3
58089
58090-58091
58092-58093
58094-58095
58096-58097
58098-58100
12776
12777
12778
12779
12780
12781
0
0
0
0
0
0
E2F5
E2F5-E2F6
58101
58102-58103
12782
12783
0
0
E2F7-E2F8
E2F9-E2FA
E2FB-E2FC
E2FD-E2FF
58104-58105
58106-58107
58108-58109
58110-58112
12784
12785
12786
12787
0
0
0
0
E301
E301-E302
E303-E304
E305-E306
E307-E308
58113
58114-58115
58116-58117
58118-58119
58120-58121
12788
12789
12790
12791
12792
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Prior Month, Final Season, Tier 0
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-185
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E309-E30B
58122-58124
12793
0
E30D
E30D-E30E
E30F-E310
E311-E312
E313-E314
E315-E317
58125
58126-58127
58128-58129
58130-58131
58132-58133
58134-58136
12794
12795
12796
12797
12798
12799
0
0
0
0
0
0
E319
E319-E31A
E31B-E31C
E31D-E31E
E31F-E320
E321-E323
58137
58138-58139
58140-58141
58142-58143
58144-58145
58146-58148
12800
12801
12802
12803
12804
12805
0
0
0
0
0
0
E325
E325-E326
E327-E328
E329-E32A
E32B-E32C
E32D-E32F
58149
58150-58151
58152-58153
58154-58155
58156-58157
58158-58160
12806
12807
12808
12809
12810
12811
0
0
0
0
0
0
E331
E331-E332
E333-E334
E335-E336
E337-E338
E339-E33B
58161
58162-58163
58164-58165
58166-58167
58168-58169
58170-58172
12812
12813
12814
12815
12816
12817
0
0
0
0
0
0
E33D
E33D-E33E
E33F-E340
E341-E342
E343-E344
58173
58174-58175
58176-58177
58178-58179
58180-58181
12818
12819
12820
12821
12822
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-186
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E345-E347
58182-58184
12823
0
E349
E349-E34A
E34B-E34C
E34D-E34E
E34F-E350
E351-E353
58185
58186-58187
58188-58189
58190-58191
58192-58193
58194-58196
12824
12825
12826
12827
12828
12829
0
0
0
0
0
0
E355
E355-E356
E357-E358
E359-E35A
E35B-E35C
E35D-E35F
58197
58198-58199
58200-58201
58202-58203
58204-58205
58206-58208
12830
12831
12832
12833
12834
12835
0
0
0
0
0
0
E361
E361-E362
E363-E364
E365-E366
E367-E368
E369-E36B
58209
58210-58211
58212-58213
58214-58215
58216-58217
58218-58220
12836
12837
12838
12839
12840
12841
0
0
0
0
0
0
E36D
E36D-E36E
E36F-E370
E371-E372
E373-E374
E375-E377
58221
58222-58223
58224-58225
58226-58227
58228-58229
58230-58232
12842
12843
12844
12845
12846
12847
0
0
0
0
0
0
E379
E379-E37A
E37B-E37C
E37D-E37E
E37F-E380
58233
58234-58235
58236-58237
58238-58239
58240-58241
12848
12849
12850
12851
12852
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-187
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E381-E383
58242-58244
12853
0
E385
E385-E386
E387-E388
E389-E38A
E38B-E38C
E38D-E38F
58245
58246-58247
58248-58249
58250-58251
58252-58253
58254-58256
12854
12855
12856
12857
12858
12859
0
0
0
0
0
0
E391
E391-E392
E393-E394
E395-E396
E397-E398
E399-E39B
58257
58258-58259
58260-58261
58262-58263
58264-58265
58266-58268
12860
12861
12862
12863
12864
12865
0
0
0
0
0
0
E39D
E39D-E39E
E39F-E3A0
E3A1-E3A2
E3A3-E3A4
E3A5-E3A7
58269
58270-58271
58272-58273
58274-58275
58276-58277
58278-58280
12866
12867
12868
12869
12870
12871
0
0
0
0
0
0
E3A9
E3A9-E3AA
E3AB-E3AC
E3AD-E3AE
E3AF-E3B0
E3B1-E3B3
58281
58282-58283
58284-58285
58286-58287
58288-58289
58290-58292
12872
12873
12874
12875
12876
12877
0
0
0
0
0
0
E3B5
E3B5-E3B6
58293
58294-58295
12878
12879
0
0
E3B7-E3B8
E3B9-E3BA
E3BB-E3BC
58296-58297
58298-58299
58300-58301
12880
12881
12882
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Prior Month, Final Season, Tier 1
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64 R
F120 R
F120 R
MM-188
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E3BD-E3BF
58302-58304
12883
0
E3C1
E3C1-E3C2
E3C3-E3C4
E3C5-E3C6
E3C7-E3C8
E3C9-E3CB
58305
58306-58307
58308-58309
58310-58311
58312-58313
58314-58316
12884
12885
12886
12887
12888
12889
0
0
0
0
0
0
E3CD
E3CD-E3CE
E3CF-E3D0
E3D1-E3D2
E3D3-E3D4
E3D5-E3D7
58317
58318-58319
58320-58321
58322-58323
58324-58325
58326-58328
12890
12891
12892
12893
12894
12895
0
0
0
0
0
0
E3D9
E3D9-E3DA
E3DB-E3DC
E3DD-E3DE
E3DF-E3E0
E3E1-E3E3
58329
58330-58331
58332-58333
58334-58335
58336-58337
58338-58340
12896
12897
12898
12899
12900
12901
0
0
0
0
0
0
E3E5
E3E5-E3E6
E3E7-E3E8
E3E9-E3EA
E3EB-E3EC
E3ED-E3EF
58341
58342-58343
58344-58345
58346-58347
58348-58349
58350-58352
12902
12903
12904
12905
12906
12907
0
0
0
0
0
0
E3F1
E3F1-E3F2
E3F3-E3F4
E3F5-E3F6
E3F7-E3F8
58353
58354-58355
58356-58357
58358-58359
58360-58361
12908
12909
12910
12911
12912
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-189
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E3F9-E3FB
58362-58364
12913
0
E3FD
E3FD-E3FE
E3FF-E400
E401-E402
E403-E404
E405-E407
58365
58366-58367
58368-58369
58370-58371
58372-58373
58374-58376
12914
12915
12916
12917
12918
12919
0
0
0
0
0
0
E409
E409-E40A
E40B-E40C
E40D-E40E
E40F-E410
E411-E413
58377
58378-58379
58380-58381
58382-58383
58384-58385
58386-58388
12920
12921
12922
12923
12924
12925
0
0
0
0
0
0
E415
E415-E416
E417-E418
E419-E41A
E41B-E41C
E41D-E41F
58389
58390-58391
58392-58393
58394-58395
58396-58397
58398-58400
12926
12927
12928
12929
12930
12931
0
0
0
0
0
0
E421
E421-E422
E423-E424
E425-E426
E427-E428
E429-E42B
58401
58402-58403
58404-58405
58406-58407
58408-58409
58410-58412
12932
12933
12934
12935
12936
12937
0
0
0
0
0
0
E42D
E42D-E42E
E42F-E430
E431-E432
E433-E434
58413
58414-58415
58416-58417
58418-58419
58420-58421
12938
12939
12940
12941
12942
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-190
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E435-E437
58422-58424
12943
0
E439
E439-E43A
E43B-E43C
E43D-E43E
E43F-E440
E441-E443
58425
58426-58427
58428-58429
58430-58431
58432-58433
58434-58436
12944
12945
12946
12947
12948
12949
0
0
0
0
0
0
E445
E445-E446
E447-E448
E449-E44A
E44B-E44C
E44D-E44F
58437
58438-58439
58440-58441
58442-58443
58444-58445
58446-58448
12950
12951
12952
12953
12954
12955
0
0
0
0
0
0
E451
E451-E452
E453-E454
E455-E456
E457-E458
E459-E45B
58449
58450-58451
58452-58453
58454-58455
58456-58457
58458-58460
12956
12957
12958
12959
12960
12961
0
0
0
0
0
0
E45D
E45D-E45E
E45F-E460
E461-E462
E463-E464
E465-E467
58461
58462-58463
58464-58465
58466-58467
58468-58469
58470-58472
12962
12963
12964
12965
12966
12967
0
0
0
0
0
0
E469
E469-E46A
E46B-E46C
E46D-E46E
E46F-E470
58473
58474-58475
58476-58477
58478-58479
58480-58481
12968
12969
12970
12971
12972
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-191
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E471-E473
58482-58484
12973
0
E475
E475-E476
58485
58486-58487
12974
12975
0
0
E477-E478
E479-E47A
E47B-E47C
E47D-E47F
58488-58489
58490-58491
58492-58493
58494-58496
12976
12977
12978
12979
0
0
0
0
E481
E481-E482
E483-E484
E485-E486
E487-E488
E489-E48B
58497
58498-58499
58500-58501
58502-58503
58504-58505
58506-58508
12980
12981
12982
12983
12984
12985
0
0
0
0
0
0
E48D
E48D-E48E
E48F-E490
E491-E492
E493-E494
E495-E497
58509
58510-58511
58512-58513
58514-58515
58516-58517
58518-58520
12986
12987
12988
12989
12990
12991
0
0
0
0
0
0
E499
E499-E49A
E49B-E49C
E49D-E49E
E49F-E4A0
E4A1-E4A3
58521
58522-58523
58524-58525
58526-58527
58528-58529
58530-58532
12992
12993
12994
12995
12996
12997
0
0
0
0
0
0
E4A5
E4A5-E4A6
E4A7-E4A8
E4A9-E4AA
58533
58534-58535
58536-58537
58538-58539
12998
12999
13000
13001
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Prior Month, Final Season, Tier 2
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
R
R
R
R
MM-192
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E4AB-E4AC
E4AD-E4AF
58540-58541
58542-58544
13002
13003
0
0
E4B1
E4B1-E4B2
E4B3-E4B4
E4B5-E4B6
E4B7-E4B8
E4B9-E4BB
58545
58546-58547
58548-58549
58550-58551
58552-58553
58554-58556
13004
13005
13006
13007
13008
13009
0
0
0
0
0
0
E4BD
E4BD-E4BE
E4BF-E4C0
E4C1-E4C2
E4C3-E4C4
E4C5-E4C7
58557
58558-58559
58560-58561
58562-58563
58564-58565
58566-58568
13010
13011
13012
13013
13014
13015
0
0
0
0
0
0
E4C9
E4C9-E4CA
E4CB-E4CC
E4CD-E4CE
E4CF-E4D0
E4D1-E4D3
58569
58570-58571
58572-58573
58574-58575
58576-58577
58578-58580
13016
13017
13018
13019
13020
13021
0
0
0
0
0
0
E4D5
E4D5-E4D6
E4D7-E4D8
E4D9-E4DA
E4DB-E4DC
E4DD-E4DF
58581
58582-58583
58584-58585
58586-58587
58588-58589
58590-58592
13022
13023
13024
13025
13026
13027
0
0
0
0
0
0
E4E1
E4E1-E4E2
E4E3-E4E4
E4E5-E4E6
E4E7-E4E8
58593
58594-58595
58596-58597
58598-58599
58600-58601
13028
13029
13030
13031
13032
0
0
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-193
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E4E9-E4EB
58602-58604
13033
0
E4ED
E4ED-E4EE
E4EF-E4F0
E4F1-E4F2
E4F3-E4F4
E4F5-E4F7
58605
58606-58607
58608-58609
58610-58611
58612-58613
58614-58616
13034
13035
13036
13037
13038
13039
0
0
0
0
0
0
E4F9
E4F9-E4FA
E4FB-E4FC
E4FD-E4FE
E4FF-E500
E501-E503
58617
58618-58619
58620-58621
58622-58623
58624-58625
58626-58628
13040
13041
13042
13043
13044
13045
0
0
0
0
0
0
E505
E505-E506
E507-E508
E509-E50A
E50B-E50C
E50D-E50F
58629
58630-58631
58632-58633
58634-58635
58636-58637
58638-58640
13046
13047
13048
13049
13050
13051
0
0
0
0
0
0
E511
E511-E512
E513-E514
E515-E516
E517-E518
E519-E51B
58641
58642-58643
58644-58645
58646-58647
58648-58649
58650-58652
13052
13053
13054
13055
13056
13057
0
0
0
0
0
0
E51D
E51D-E51E
E51F-E520
E521-E522
E523-E524
58653
58654-58655
58656-58657
58658-58659
58660-58661
13058
13059
13060
13061
13062
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-194
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E525-E527
58662-58664
13063
0
E529
E529-E52A
E52B-E52C
E52D-E52E
E52F-E530
E531-E533
58665
58666-58667
58668-58669
58670-58671
58672-58673
58674-58676
13064
13065
13066
13067
13068
13069
0
0
0
0
0
0
E535
E535-E536
58677
58678-58679
13070
13071
0
0
E537-E538
E539-E53A
E53B-E53C
E53D-E53F
58680-58681
58682-58683
58684-58685
58686-58688
13072
13073
13074
13075
0
0
0
0
E541
E541-E542
E543-E544
E545-E546
E547-E548
E549-E54B
58689
58690-58691
58692-58693
58694-58695
58696-58697
58698-58700
13076
13077
13078
13079
13080
13081
0
0
0
0
0
0
E54D
E54D-E54E
E54F-E550
E551-E552
E553-E554
E555-E557
58701
58702-58703
58704-58705
58706-58707
58708-58709
58710-58712
13082
13083
13084
13085
13086
13087
0
0
0
0
0
0
E559
E559-E55A
E55B-E55C
E55D-E55E
58713
58714-58715
58716-58717
58718-58719
13088
13089
13090
13091
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Prior Month, Final Season, Tier 3
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
R
R
R
R
MM-195
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E55F-E560
E561-E563
58720-58721
58722-58724
13092
13093
0
0
E565
E565-E566
E567-E568
E569-E56A
E56B-E56C
E56D-E56F
58725
58726-58727
58728-58729
58730-58731
58732-58733
58734-58736
13094
13095
13096
13097
13098
13099
0
0
0
0
0
0
E571
E571-E572
E573-E574
E575-E576
E577-E578
E579-E57B
58737
58738-58739
58740-58741
58742-58743
58744-58745
58746-58748
13100
13101
13102
13103
13104
13105
0
0
0
0
0
0
E57D
E57D-E57E
E57F-E580
E581-E582
E583-E584
E585-E587
58749
58750-58751
58752-58753
58754-58755
58756-58757
58758-58760
13106
13107
13108
13109
13110
13111
0
0
0
0
0
0
E589
E589-E58A
E58B-E58C
E58D-E58E
E58F-E590
E591-E593
58761
58762-58763
58764-58765
58766-58767
58768-58769
58770-58772
13112
13113
13114
13115
13116
13117
0
0
0
0
0
0
E595
E595-E596
E597-E598
E599-E59A
E59B-E59C
58773
58774-58775
58776-58777
58778-58779
58780-58781
13118
13119
13120
13121
13122
0
0
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-196
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E59D-E59F
58782-58784
13123
0
E5A1
E5A1-E5A2
E5A3-E5A4
E5A5-E5A6
E5A7-E5A8
E5A9-E5AB
58785
58786-58787
58788-58789
58790-58791
58792-58793
58794-58796
13124
13125
13126
13127
13128
13129
0
0
0
0
0
0
E5AD
E5AD-E5AE
E5AF-E5B0
E5B1-E5B2
E5B3-E5B4
E5B5-E5B7
58797
58798-58799
58800-58801
58802-58803
58804-58805
58806-58808
13130
13131
13132
13133
13134
13135
0
0
0
0
0
0
E5B9
E5B9-E5BA
E5BB-E5BC
E5BD-E5BE
E5BF-E5C0
E5C1-E5C3
58809
58810-58811
58812-58813
58814-58815
58816-58817
58818-58820
13136
13137
13138
13139
13140
13141
0
0
0
0
0
0
E5C5
E5C5-E5C6
E5C7-E5C8
E5C9-E5CA
E5CB-E5CC
E5CD-E5CF
58821
58822-58823
58824-58825
58826-58827
58828-58829
58830-58832
13142
13143
13144
13145
13146
13147
0
0
0
0
0
0
E5D1
E5D1-E5D2
E5D3-E5D4
E5D5-E5D6
E5D7-E5D8
58833
58834-58835
58836-58837
58838-58839
58840-58841
13148
13149
13150
13151
13152
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-197
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E5D9-E5DB
58842-58844
13153
0
E5DD
E5DD-E5DE
E5DF-E5E0
E5E1-E5E2
E5E3-E5E4
E5E5-E5E7
58845
58846-58847
58848-58849
58850-58851
58852-58853
58854-58856
13154
13155
13156
13157
13158
13159
0
0
0
0
0
0
E5E9
E5E9-E5EA
E5EB-E5EC
E5ED-E5EE
E5EF-E5F0
E5F1-E5F3
58857
58858-58859
58860-58861
58862-58863
58864-58865
58866-58868
13160
13161
13162
13163
13164
13165
0
0
0
0
0
0
E5F5
E5F5-E5F6
58869
58870-58871
13166
13167
0
0
E5F7-E5F8
E5F9-E5FA
E5FB-E5FC
E5FD-E5FF
58872-58873
58874-58875
58876-58877
58878-58880
13168
13169
13170
13171
0
0
0
0
E601
E601-E602
E603-E604
E605-E606
E607-E608
E609-E60B
58881
58882-58883
58884-58885
58886-58887
58888-58889
58890-58892
13172
13173
13174
13175
13176
13177
0
0
0
0
0
0
E60D
E60D-E60E
E60F-E610
E611-E612
58893
58894-58895
58896-58897
58898-58899
13178
13179
13180
13181
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Prior Month, Final Season, Tier 4
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
R
R
R
R
MM-198
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E613-E614
E615-E617
58900-58901
58902-58904
13182
13183
0
0
E619
E619-E61A
E61B-E61C
E61D-E61E
E61F-E620
E621-E623
58905
58906-58907
58908-58909
58910-58911
58912-58913
58914-58916
13184
13185
13186
13187
13188
13189
0
0
0
0
0
0
E625
E625-E626
E627-E628
E629-E62A
E62B-E62C
E62D-E62F
58917
58918-58919
58920-58921
58922-58923
58924-58925
58926-58928
13190
13191
13192
13193
13194
13195
0
0
0
0
0
0
E631
E631-E632
E633-E634
E635-E636
E637-E638
E639-E63B
58929
58930-58931
58932-58933
58934-58935
58936-58937
58938-58940
13196
13197
13198
13199
13200
13201
0
0
0
0
0
0
E63D
E63D-E63E
E63F-E640
E641-E642
E643-E644
E645-E647
58941
58942-58943
58944-58945
58946-58947
58948-58949
58950-58952
13202
13203
13204
13205
13206
13207
0
0
0
0
0
0
E649
E649-E64A
E64B-E64C
E64D-E64E
E64F-E650
58953
58954-58955
58956-58957
58958-58959
58960-58961
13208
13209
13210
13211
13212
0
0
0
0
0
DNP
Obj
Description
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F120 R
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-199
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
E651-E653
58962-58964
13213
0
E655
E655-E656
E657-E658
E659-E65A
E65B-E65C
E65D-E65F
58965
58966-58967
58968-58969
58970-58971
58972-58973
58974-58976
13214
13215
13216
13217
13218
13219
0
0
0
0
0
0
E661
E661-E662
E663-E664
E665-E666
E667-E668
E669-E66B
58977
58978-58979
58980-58981
58982-58983
58984-58985
58986-58988
13220
13221
13222
13223
13224
13225
0
0
0
0
0
0
E66D
E66D-E66E
E66F-E670
E671-E672
E673-E674
E675-E677
58989
58990-58991
58992-58993
58994-58995
58996-58997
58998-59000
13226
13227
13228
13229
13230
13231
0
0
0
0
0
0
E679
E679-E67A
E67B-E67C
E67D-E67E
E67F-E680
E681-E683
59001
59002-59003
59004-59005
59006-59007
59008-59009
59010-59012
13232
13233
13234
13235
13236
13237
0
0
0
0
0
0
E685
E685-E686
E687-E688
E689-E68A
E68B-E68C
59013
59014-59015
59016-59017
59018-59019
59020-59021
13238
13239
13240
13241
13242
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-200
2: Modbus Map - Input Registers
DNP
Obj
Addr. (hex)
Address(3X)
Line
Pt
E68D-E68F
59022-59024
13243
0
E691
E691-E692
E693-E694
E695-E696
E697-E698
E699-E69B
59025
59026-59027
59028-59029
59030-59031
59032-59033
59034-59036
13244
13245
13246
13247
13248
13249
0
0
0
0
0
0
E69D
E69D-E69E
E69F-E6A0
E6A1-E6A2
E6A3-E6A4
E6A5-E6A7
59037
59038-59039
59040-59041
59042-59043
59044-59045
59046-59048
13250
13251
13252
13253
13254
13255
0
0
0
0
0
0
E6A9
E6A9-E6AA
E6AB-E6AC
E6AD-E6AE
E6AF-E6B0
E6B1-E6B3
59049
59050-59051
59052-59053
59054-59055
59056-59057
59058-59060
13256
13257
13258
13259
13260
13261
0
0
0
0
0
0
E6B5
E6B5-E6B6
59061
59062-59063
13262
13263
0
0
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
59288-59289
59290-59291
59292-59293
base=13264,
group
count=6*16=
96,
groups=5
13264
13265
13266
0
0
0
Current Season
Current Season Tier 0 (total)
Current Season Tier 1
Current Season Tier 2
Current Season Tier 3
Current Season Tier 4
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
E797-E798
E799-E79A
E79B-E79C
Description
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64 R
F120 R
F120 R
MM-201
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
E79D-E79F
E7A1
E7A1-E7A2
E7A3-E7A4
E7A5-E7A6
E7A7-E7A8
59294-59296
59297
59298-59299
59300-59301
59302-59303
59304-59305
13267
13268
13269
13270
13271
13272
E7A9-E7AB
E7AD
E7AD-E7AE
E7AF-E7B0
E7B1-E7B2
E7B3-E7B4
59306-59308
59309
59310-59311
59312-59313
59314-59315
59316-59317
13273
13274
13275
13276
13277
13278
E7B5-E7B7
E7B9
E7B9-E7BA
E7BB-E7BC
E7BD-E7BE
E7BF-E7C0
59318-59320
59321
59322-59323
59324-59325
59326-59327
59328-59329
13279
13280
13281
13282
13283
13284
E7C1-E7C3
E7C5
E7C5-E7C6
E7C7-E7C8
E7C9-E7CA
E7CB-E7CC
59330-59332
59333
59334-59335
59336-59337
59338-59339
59340-59341
13285
13286
13287
13288
13289
13290
E7CD-E7CF
E7D1
E7D1-E7D2
E7D3-E7D4
E7D5-E7D6
E7D7-E7D8
59342-59344
59345
59346-59347
59348-59349
59350-59351
59352-59353
13291
13292
13293
13294
13295
13296
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-202
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
E7D9-E7DB
E7DD
E7DD-E7DE
E7DF-E7E0
E7E1-E7E2
E7E3-E7E4
59354-59356
59357
59358-59359
59360-59361
59362-59363
59364-59365
13297
13298
13299
13300
13301
13302
E7E5-E7E7
E7E9
E7E9-E7EA
E7EB-E7EC
E7ED-E7EE
E7EF-E7F0
59366-59368
59369
59370-59371
59372-59373
59374-59375
59376-59377
13303
13304
13305
13306
13307
13308
E7F1-E7F3
E7F5
E7F5-E7F6
E7F7-E7F8
E7F9-E7FA
E7FB-E7FC
59378-59380
59381
59382-59383
59384-59385
59386-59387
59388-59389
13309
13310
13311
13312
13313
13314
E7FD-E7FF
E801
E801-E802
E803-E804
E805-E806
E807-E808
59390-59392
59393
59394-59395
59396-59397
59398-59399
59400-59401
13315
13316
13317
13318
13319
13320
E809-E80B
E80D
E80D-E80E
E80F-E810
E811-E812
E813-E814
59402-59404
59405
59406-59407
59408-59409
59410-59411
59412-59413
13321
13322
13323
13324
13325
13326
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-203
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
E815-E817
E819
E819-E81A
E81B-E81C
E81D-E81E
E81F-E820
59414-59416
59417
59418-59419
59420-59421
59422-59423
59424-59425
13327
13328
13329
13330
13331
13332
E821-E823
E825
E825-E826
E827-E828
E829-E82A
E82B-E82C
59426-59428
59429
59430-59431
59432-59433
59434-59435
59436-59437
13333
13334
13335
13336
13337
13338
E82D-E82F
E831
E831-E832
E833-E834
E835-E836
E837-E838
59438-59440
59441
59442-59443
59444-59445
59446-59447
59448-59449
13339
13340
13341
13342
13343
13344
E839-E83B
E83D
E83D-E83E
E83F-E840
E841-E842
E843-E844
59450-59452
59453
59454-59455
59456-59457
59458-59459
59460-59461
13345
13346
13347
13348
13349
13350
E845-E847
E849
E849-E84A
E84B-E84C
E84D-E84E
E84F-E850
59462-59464
59465
59466-59467
59468-59469
59470-59471
59472-59473
13351
13352
13353
13354
13355
13356
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-204
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
E851-E853
E855
E855-E856
59474-59476
59477
59478-59479
13357
13358
13359
E857-E858
E859-E85A
E85B-E85C
59480-59481
59482-59483
59484-59485
13360
13361
13362
E85D-E85F
E861
E861-E862
E863-E864
E865-E866
E867-E868
59486-59488
59489
59490-59491
59492-59493
59494-59495
59496-59497
13363
13364
13365
13366
13367
13368
E869-E86B
E86D
E86D-E86E
E86F-E870
E871-E872
E873-E874
59498-59500
59501
59502-59503
59504-59505
59506-59507
59508-59509
13369
13370
13371
13372
13373
13374
E875-E877
E879
E879-E87A
E87B-E87C
E87D-E87E
E87F-E880
59510-59512
59513
59514-59515
59516-59517
59518-59519
59520-59521
13375
13376
13377
13378
13379
13380
E881-E883
E885
E885-E886
E887-E888
E889-E88A
E88B-E88C
59522-59524
59525
59526-59527
59528-59529
59530-59531
59532-59533
13381
13382
13383
13384
13385
13386
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Current Season Tier 1
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-205
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
E88D-E88F
E891
E891-E892
E893-E894
E895-E896
E897-E898
59534-59536
59537
59538-59539
59540-59541
59542-59543
59544-59545
13387
13388
13389
13390
13391
13392
E899-E89B
E89D
E89D-E89E
E89F-E8A0
E8A1-E8A2
E8A3-E8A4
59546-59548
59549
59550-59551
59552-59553
59554-59555
59556-59557
13393
13394
13395
13396
13397
13398
E8A5-E8A7
E8A9
E8A9-E8AA
E8AB-E8AC
E8AD-E8AE
E8AF-E8B0
59558-59560
59561
59562-59563
59564-59565
59566-59567
59568-59569
13399
13400
13401
13402
13403
13404
E8B1-E8B3
E8B5
E8B5-E8B6
E8B7-E8B8
E8B9-E8BA
E8BB-E8BC
59570-59572
59573
59574-59575
59576-59577
59578-59579
59580-59581
13405
13406
13407
13408
13409
13410
E8BD-E8BF
E8C1
E8C1-E8C2
E8C3-E8C4
E8C5-E8C6
E8C7-E8C8
59582-59584
59585
59586-59587
59588-59589
59590-59591
59592-59593
13411
13412
13413
13414
13415
13416
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-206
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
0
E8C9-E8CB
E8CD
E8CD-E8CE
E8CF-E8D0
E8D1-E8D2
E8D3-E8D4
59594-59596
59597
59598-59599
59600-59601
59602-59603
59604-59605
13417
13418
13419
13420
13421
13422
E8D5-E8D7
E8D9
E8D9-E8DA
E8DB-E8DC
E8DD-E8DE
E8DF-E8E0
59606-59608
59609
59610-59611
59612-59613
59614-59615
59616-59617
13423
13424
13425
13426
13427
13428
E8E1-E8E3
E8E5
E8E5-E8E6
E8E7-E8E8
E8E9-E8EA
E8EB-E8EC
59618-59620
59621
59622-59623
59624-59625
59626-59627
59628-59629
13429
13430
13431
13432
13433
13434
E8ED-E8EF
E8F1
E8F1-E8F2
E8F3-E8F4
E8F5-E8F6
E8F7-E8F8
59630-59632
59633
59634-59635
59636-59637
59638-59639
59640-59641
13435
13436
13437
13438
13439
13440
E8F9-E8FB
E8FD
E8FD-E8FE
E8FF-E900
E901-E902
E903-E904
59642-59644
59645
59646-59647
59648-59649
59650-59651
59652-59653
13441
13442
13443
13444
13445
13446
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-207
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
E905-E907
E909
E909-E90A
E90B-E90C
E90D-E90E
E90F-E910
59654-59656
59657
59658-59659
59660-59661
59662-59663
59664-59665
13447
13448
13449
13450
13451
13452
E911-E913
E915
E915-E916
59666-59668
59669
59670-59671
13453
13454
13455
E917-E918
E919-E91A
E91B-E91C
59672-59673
59674-59675
59676-59677
13456
13457
13458
E91D-E91F
E921
E921-E922
E923-E924
E925-E926
E927-E928
59678-59680
59681
59682-59683
59684-59685
59686-59687
59688-59689
13459
13460
13461
13462
13463
13464
E929-E92B
E92D
E92D-E92E
E92F-E930
E931-E932
E933-E934
59690-59692
59693
59694-59695
59696-59697
59698-59699
59700-59701
13465
13466
13467
13468
13469
13470
E935-E937
E939
E939-E93A
E93B-E93C
E93D-E93E
E93F-E940
59702-59704
59705
59706-59707
59708-59709
59710-59711
59712-59713
13471
13472
13473
13474
13475
13476
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Current Season Tier 2
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-208
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
E941-E943
E945
E945-E946
E947-E948
E949-E94A
E94B-E94C
59714-59716
59717
59718-59719
59720-59721
59722-59723
59724-59725
13477
13478
13479
13480
13481
13482
E94D-E94F
E951
E951-E952
E953-E954
E955-E956
E957-E958
59726-59728
59729
59730-59731
59732-59733
59734-59735
59736-59737
13483
13484
13485
13486
13487
13488
E959-E95B
E95D
E95D-E95E
E95F-E960
E961-E962
E963-E964
59738-59740
59741
59742-59743
59744-59745
59746-59747
59748-59749
13489
13490
13491
13492
13493
13494
E965-E967
E969
E969-E96A
E96B-E96C
E96D-E96E
E96F-E970
59750-59752
59753
59754-59755
59756-59757
59758-59759
59760-59761
13495
13496
13497
13498
13499
13500
E971-E973
E975
E975-E976
E977-E978
E979-E97A
E97B-E97C
59762-59764
59765
59766-59767
59768-59769
59770-59771
59772-59773
13501
13502
13503
13504
13505
13506
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-209
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
0
E97D-E97F
E981
E981-E982
E983-E984
E985-E986
E987-E988
59774-59776
59777
59778-59779
59780-59781
59782-59783
59784-59785
13507
13508
13509
13510
13511
13512
E989-E98B
E98D
E98D-E98E
E98F-E990
E991-E992
E993-E994
59786-59788
59789
59790-59791
59792-59793
59794-59795
59796-59797
13513
13514
13515
13516
13517
13518
E995-E997
E999
E999-E99A
E99B-E99C
E99D-E99E
E99F-E9A0
59798-59800
59801
59802-59803
59804-59805
59806-59807
59808-59809
13519
13520
13521
13522
13523
13524
E9A1-E9A3
E9A5
E9A5-E9A6
E9A7-E9A8
E9A9-E9AA
E9AB-E9AC
59810-59812
59813
59814-59815
59816-59817
59818-59819
59820-59821
13525
13526
13527
13528
13529
13530
E9AD-E9AF
E9B1
E9B1-E9B2
E9B3-E9B4
E9B5-E9B6
E9B7-E9B8
59822-59824
59825
59826-59827
59828-59829
59830-59831
59832-59833
13531
13532
13533
13534
13535
13536
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-210
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
E9B9-E9BB
E9BD
E9BD-E9BE
E9BF-E9C0
E9C1-E9C2
E9C3-E9C4
59834-59836
59837
59838-59839
59840-59841
59842-59843
59844-59845
13537
13538
13539
13540
13541
13542
E9C5-E9C7
E9C9
E9C9-E9CA
E9CB-E9CC
E9CD-E9CE
E9CF-E9D0
59846-59848
59849
59850-59851
59852-59853
59854-59855
59856-59857
13543
13544
13545
13546
13547
13548
E9D1-E9D3
E9D5
E9D5-E9D6
59858-59860
59861
59862-59863
13549
13550
13551
E9D7-E9D8
E9D9-E9DA
E9DB-E9DC
59864-59865
59866-59867
59868-59869
13552
13553
13554
E9DD-E9DF
E9E1
E9E1-E9E2
E9E3-E9E4
E9E5-E9E6
E9E7-E9E8
59870-59872
59873
59874-59875
59876-59877
59878-59879
59880-59881
13555
13556
13557
13558
13559
13560
E9E9-E9EB
E9ED
E9ED-E9EE
E9EF-E9F0
E9F1-E9F2
E9F3-E9F4
59882-59884
59885
59886-59887
59888-59889
59890-59891
59892-59893
13561
13562
13563
13564
13565
13566
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Current Season Tier 3
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-211
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
E9F5-E9F7
E9F9
E9F9-E9FA
E9FB-E9FC
E9FD-E9FE
E9FF-EA00
59894-59896
59897
59898-59899
59900-59901
59902-59903
59904-59905
13567
13568
13569
13570
13571
13572
EA01-EA03
EA05
EA05-EA06
EA07-EA08
EA09-EA0A
EA0B-EA0C
59906-59908
59909
59910-59911
59912-59913
59914-59915
59916-59917
13573
13574
13575
13576
13577
13578
EA0D-EA0F
EA11
EA11-EA12
EA13-EA14
EA15-EA16
EA17-EA18
59918-59920
59921
59922-59923
59924-59925
59926-59927
59928-59929
13579
13580
13581
13582
13583
13584
EA19-EA1B
EA1D
EA1D-EA1E
EA1F-EA20
EA21-EA22
EA23-EA24
59930-59932
59933
59934-59935
59936-59937
59938-59939
59940-59941
13585
13586
13587
13588
13589
13590
EA25-EA27
EA29
EA29-EA2A
EA2B-EA2C
EA2D-EA2E
EA2F-EA30
59942-59944
59945
59946-59947
59948-59949
59950-59951
59952-59953
13591
13592
13593
13594
13595
13596
Pt
DNP
Obj
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Description
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-212
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
EA31-EA33
EA35
EA35-EA36
EA37-EA38
EA39-EA3A
EA3B-EA3C
59954-59956
59957
59958-59959
59960-59961
59962-59963
59964-59965
13597
13598
13599
13600
13601
13602
EA3D-EA3F
EA41
EA41-EA42
EA43-EA44
EA45-EA46
EA47-EA48
59966-59968
59969
59970-59971
59972-59973
59974-59975
59976-59977
13603
13604
13605
13606
13607
13608
EA49-EA4B
EA4D
EA4D-EA4E
EA4F-EA50
EA51-EA52
EA53-EA54
59978-59980
59981
59982-59983
59984-59985
59986-59987
59988-59989
13609
13610
13611
13612
13613
13614
EA55-EA57
EA59
EA59-EA5A
EA5B-EA5C
EA5D-EA5E
EA5F-EA60
59990-59992
59993
59994-59995
59996-59997
59998-59999
60000-60001
13615
13616
13617
13618
13619
13620
EA61-EA63
EA65
EA65-EA66
EA67-EA68
EA69-EA6A
EA6B-EA6C
60002-60004
60005
60006-60007
60008-60009
60010-60011
60012-60013
13621
13622
13623
13624
13625
13626
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-213
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
EA6D-EA6F
EA71
EA71-EA72
EA73-EA74
EA75-EA76
EA77-EA78
60014-60016
60017
60018-60019
60020-60021
60022-60023
60024-60025
13627
13628
13629
13630
13631
13632
EA79-EA7B
EA7D
EA7D-EA7E
EA7F-EA80
EA81-EA82
EA83-EA84
60026-60028
60029
60030-60031
60032-60033
60034-60035
60036-60037
13633
13634
13635
13636
13637
13638
EA85-EA87
EA89
EA89-EA8A
EA8B-EA8C
EA8D-EA8E
EA8F-EA90
60038-60040
60041
60042-60043
60044-60045
60046-60047
60048-60049
13639
13640
13641
13642
13643
13644
EA91-EA93
EA95
EA95-EA96
60050-60052
60053
60054-60055
13645
13646
13647
EA97-EA98
EA99-EA9A
EA9B-EA9C
60056-60057
60058-60059
60060-60061
13648
13649
13650
EA9D-EA9F
EAA1
EAA1-EAA2
EAA3-EAA4
EAA5-EAA6
EAA7-EAA8
60062-60064
60065
60066-60067
60068-60069
60070-60071
60072-60073
13651
13652
13653
13654
13655
13656
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Current Season Tier 4
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-214
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
EAA9-EAAB
EAAD
EAAD-EAAE
EAAF-EAB0
EAB1-EAB2
EAB3-EAB4
60074-60076
60077
60078-60079
60080-60081
60082-60083
60084-60085
13657
13658
13659
13660
13661
13662
EAB5-EAB7
EAB9
EAB9-EABA
EABB-EABC
EABD-EABE
EABF-EAC0
60086-60088
60089
60090-60091
60092-60093
60094-60095
60096-60097
13663
13664
13665
13666
13667
13668
EAC1-EAC3
EAC5
EAC5-EAC6
EAC7-EAC8
EAC9-EACA
EACB-EACC
60098-60100
60101
60102-60103
60104-60105
60106-60107
60108-60109
13669
13670
13671
13672
13673
13674
EACD-EACF
EAD1
EAD1-EAD2
EAD3-EAD4
EAD5-EAD6
EAD7-EAD8
60110-60112
60113
60114-60115
60116-60117
60118-60119
60120-60121
13675
13676
13677
13678
13679
13680
EAD9-EADB
EADD
EADD-EADE
EADF-EAE0
EAE1-EAE2
EAE3-EAE4
60122-60124
60125
60126-60127
60128-60129
60130-60131
60132-60133
13681
13682
13683
13684
13685
13686
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-215
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
EAE5-EAE7
EAE9
EAE9-EAEA
EAEB-EAEC
EAED-EAEE
EAEF-EAF0
60134-60136
60137
60138-60139
60140-60141
60142-60143
60144-60145
13687
13688
13689
13690
13691
13692
EAF1-EAF3
EAF5
EAF5-EAF6
EAF7-EAF8
EAF9-EAFA
EAFB-EAFC
60146-60148
60149
60150-60151
60152-60153
60154-60155
60156-60157
13693
13694
13695
13696
13697
13698
EAFD-EAFF
EB01
EB01-EB02
EB03-EB04
EB05-EB06
EB07-EB08
60158-60160
60161
60162-60163
60164-60165
60166-60167
60168-60169
13699
13700
13701
13702
13703
13704
EB09-EB0B
EB0D
EB0D-EB0E
EB0F-EB10
EB11-EB12
EB13-EB14
60170-60172
60173
60174-60175
60176-60177
60178-60179
60180-60181
13705
13706
13707
13708
13709
13710
EB15-EB17
EB19
EB19-EB1A
EB1B-EB1C
EB1D-EB1E
EB1F-EB20
60182-60184
60185
60186-60187
60188-60189
60190-60191
60192-60193
13711
13712
13713
13714
13715
13716
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-216
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
0
EB21-EB23
EB25
EB25-EB26
EB27-EB28
EB29-EB2A
EB2B-EB2C
60194-60196
60197
60198-60199
60200-60201
60202-60203
60204-60205
13717
13718
13719
13720
13721
13722
EB2D-EB2F
EB31
EB31-EB32
EB33-EB34
EB35-EB36
EB37-EB38
60206-60208
60209
60210-60211
60212-60213
60214-60215
60216-60217
13723
13724
13725
13726
13727
13728
EB39-EB3B
EB3D
EB3D-EB3E
EB3F-EB40
EB41-EB42
EB43-EB44
60218-60220
60221
60222-60223
60224-60225
60226-60227
60228-60229
13729
13730
13731
13732
13733
13734
EB45-EB47
EB49
EB49-EB4A
EB4B-EB4C
EB4D-EB4E
EB4F-EB50
60230-60232
60233
60234-60235
60236-60237
60238-60239
60240-60241
13735
13736
13737
13738
13739
13740
EB51-EB53
EB55
EB55-EB56
60242-60244
60245
60246-60247
13741
13742
13743
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Prior Season
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
MM-217
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
EB57-EB58
EB59-EB5A
EB5B-EB5C
60248-60249
60250-60251
60252-60253
base=13744
group
count=6*16=
96,
groups=5
13744
13745
13746
EB5D-EB5F
EB61
EB61-EB62
EB63-EB64
EB65-EB66
EB67-EB68
60254-60256
60257
60258-60259
60260-60261
60262-60263
60264-60265
13747
13748
13749
13750
13751
13752
EB69-EB6B
EB6D
EB6D-EB6E
EB6F-EB70
EB71-EB72
EB73-EB74
60266-60268
60269
60270-60271
60272-60273
60274-60275
60276-60277
13753
13754
13755
13756
13757
13758
EB75-EB77
EB79
EB79-EB7A
EB7B-EB7C
EB7D-EB7E
EB7F-EB80
60278-60280
60281
60282-60283
60284-60285
60286-60287
60288-60289
13759
13760
13761
13762
13763
13764
EB81-EB83
EB85
EB85-EB86
EB87-EB88
EB89-EB8A
EB8B-EB8C
60290-60292
60293
60294-60295
60296-60297
60298-60299
60300-60301
13765
13766
13767
13768
13769
13770
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Prior Season Tier 0 (total)
Prior Season Tier 1
Prior Season Tier 2
Prior Season Tier 3
Prior Season Tier 4
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
Notes
MM-218
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
0
EB8D-EB8F
EB91
EB91-EB92
EB93-EB94
EB95-EB96
EB97-EB98
60302-60304
60305
60306-60307
60308-60309
60310-60311
60312-60313
13771
13772
13773
13774
13775
13776
EB99-EB9B
EB9D
EB9D-EB9E
EB9F-EBA0
EBA1-EBA2
EBA3-EBA4
60314-60316
60317
60318-60319
60320-60321
60322-60323
60324-60325
13777
13778
13779
13780
13781
13782
EBA5-EBA7
EBA9
EBA9-EBAA
EBAB-EBAC
EBAD-EBAE
EBAF-EBB0
60326-60328
60329
60330-60331
60332-60333
60334-60335
60336-60337
13783
13784
13785
13786
13787
13788
EBB1-EBB3
EBB5
EBB5-EBB6
EBB7-EBB8
EBB9-EBBA
EBBB-EBBC
60338-60340
60341
60342-60343
60344-60345
60346-60347
60348-60349
13789
13790
13791
13792
13793
13794
EBBD-EBBF
EBC1
EBC1-EBC2
EBC3-EBC4
EBC5-EBC6
EBC7-EBC8
60350-60352
60353
60354-60355
60356-60357
60358-60359
60360-60361
13795
13796
13797
13798
13799
13800
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-219
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
0
EBC9-EBCB
EBCD
EBCD-EBCE
EBCF-EBD0
EBD1-EBD2
EBD3-EBD4
60362-60364
60365
60366-60367
60368-60369
60370-60371
60372-60373
13801
13802
13803
13804
13805
13806
EBD5-EBD7
EBD9
EBD9-EBDA
EBDB-EBDC
EBDD-EBDE
EBDF-EBE0
60374-60376
60377
60378-60379
60380-60381
60382-60383
60384-60385
13807
13808
13809
13810
13811
13812
EBE1-EBE3
EBE5
EBE5-EBE6
EBE7-EBE8
EBE9-EBEA
EBEB-EBEC
60386-60388
60389
60390-60391
60392-60393
60394-60395
60396-60397
13813
13814
13815
13816
13817
13818
EBED-EBEF
EBF1
EBF1-EBF2
EBF3-EBF4
EBF5-EBF6
EBF7-EBF8
60398-60400
60401
60402-60403
60404-60405
60406-60407
60408-60409
13819
13820
13821
13822
13823
13824
EBF9-EBFB
EBFD
EBFD-EBFE
EBFF-EC00
EC01-EC02
EC03-EC04
60410-60412
60413
60414-60415
60416-60417
60418-60419
60420-60421
13825
13826
13827
13828
13829
13830
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-220
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
EC05-EC07
EC09
EC09-EC0A
EC0B-EC0C
EC0D-EC0E
EC0F-EC10
60422-60424
60425
60426-60427
60428-60429
60430-60431
60432-60433
13831
13832
13833
13834
13835
13836
EC11-EC13
EC15
EC15-EC16
60434-60436
60437
60438-60439
13837
13838
13839
EC17-EC18
EC19-EC1A
EC1B-EC1C
60440-60441
60442-60443
60444-60445
13840
13841
13842
EC1D-EC1F
EC21
EC21-EC22
EC23-EC24
EC25-EC26
EC27-EC28
60446-60448
60449
60450-60451
60452-60453
60454-60455
60456-60457
13843
13844
13845
13846
13847
13848
EC29-EC2B
EC2D
EC2D-EC2E
EC2F-EC30
EC31-EC32
EC33-EC34
60458-60460
60461
60462-60463
60464-60465
60466-60467
60468-60469
13849
13850
13851
13852
13853
13854
EC35-EC37
EC39
EC39-EC3A
EC3B-EC3C
EC3D-EC3E
EC3F-EC40
60470-60472
60473
60474-60475
60476-60477
60478-60479
60480-60481
13855
13856
13857
13858
13859
13860
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Prior Season Tier 1
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-221
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
EC41-EC43
EC45
EC45-EC46
EC47-EC48
EC49-EC4A
EC4B-EC4C
60482-60484
60485
60486-60487
60488-60489
60490-60491
60492-60493
13861
13862
13863
13864
13865
13866
EC4D-EC4F
EC51
EC51-EC52
EC53-EC54
EC55-EC56
EC57-EC58
60494-60496
60497
60498-60499
60500-60501
60502-60503
60504-60505
13867
13868
13869
13870
13871
13872
EC59-EC5B
EC5D
EC5D-EC5E
EC5F-EC60
EC61-EC62
EC63-EC64
60506-60508
60509
60510-60511
60512-60513
60514-60515
60516-60517
13873
13874
13875
13876
13877
13878
EC65-EC67
EC69
EC69-EC6A
EC6B-EC6C
EC6D-EC6E
EC6F-EC70
60518-60520
60521
60522-60523
60524-60525
60526-60527
60528-60529
13879
13880
13881
13882
13883
13884
EC71-EC73
EC75
EC75-EC76
EC77-EC78
EC79-EC7A
EC7B-EC7C
60530-60532
60533
60534-60535
60536-60537
60538-60539
60540-60541
13885
13886
13887
13888
13889
13890
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-222
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
EC7D-EC7F
EC81
EC81-EC82
EC83-EC84
EC85-EC86
EC87-EC88
60542-60544
60545
60546-60547
60548-60549
60550-60551
60552-60553
13891
13892
13893
13894
13895
13896
EC89-EC8B
EC8D
EC8D-EC8E
EC8F-EC90
EC91-EC92
EC93-EC94
60554-60556
60557
60558-60559
60560-60561
60562-60563
60564-60565
13897
13898
13899
13900
13901
13902
EC95-EC97
EC99
EC99-EC9A
EC9B-EC9C
EC9D-EC9E
EC9F-ECA0
60566-60568
60569
60570-60571
60572-60573
60574-60575
60576-60577
13903
13904
13905
13906
13907
13908
ECA1-ECA3
ECA5
ECA5-ECA6
ECA7-ECA8
ECA9-ECAA
ECAB-ECAC
60578-60580
60581
60582-60583
60584-60585
60586-60587
60588-60589
13909
13910
13911
13912
13913
13914
ECAD-ECAF
ECB1
ECB1-ECB2
ECB3-ECB4
ECB5-ECB6
ECB7-ECB8
60590-60592
60593
60594-60595
60596-60597
60598-60599
60600-60601
13915
13916
13917
13918
13919
13920
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-223
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
ECB9-ECBB
ECBD
ECBD-ECBE
ECBF-ECC0
ECC1-ECC2
ECC3-ECC4
60602-60604
60605
60606-60607
60608-60609
60610-60611
60612-60613
13921
13922
13923
13924
13925
13926
ECC5-ECC7
ECC9
ECC9-ECCA
ECCB-ECCC
ECCD-ECCE
ECCF-ECD0
60614-60616
60617
60618-60619
60620-60621
60622-60623
60624-60625
13927
13928
13929
13930
13931
13932
ECD1-ECD3
ECD5
ECD5-ECD6
60626-60628
60629
60630-60631
13933
13934
13935
ECD7-ECD8
ECD9-ECDA
ECDB-ECDC
60632-60633
60634-60635
60636-60637
13936
13937
13938
ECDD-ECDF
ECE1
ECE1-ECE2
ECE3-ECE4
ECE5-ECE6
ECE7-ECE8
60638-60640
60641
60642-60643
60644-60645
60646-60647
60648-60649
13939
13940
13941
13942
13943
13944
ECE9-ECEB
ECED
ECED-ECEE
ECEF-ECF0
ECF1-ECF2
ECF3-ECF4
60650-60652
60653
60654-60655
60656-60657
60658-60659
60660-60661
13945
13946
13947
13948
13949
13950
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Prior Season Tier 2
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-224
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
ECF5-ECF7
ECF9
ECF9-ECFA
ECFB-ECFC
ECFD-ECFE
ECFF-ED00
60662-60664
60665
60666-60667
60668-60669
60670-60671
60672-60673
13951
13952
13953
13954
13955
13956
ED01-ED03
ED05
ED05-ED06
ED07-ED08
ED09-ED0A
ED0B-ED0C
60674-60676
60677
60678-60679
60680-60681
60682-60683
60684-60685
13957
13958
13959
13960
13961
13962
ED0D-ED0F
ED11
ED11-ED12
ED13-ED14
ED15-ED16
ED17-ED18
60686-60688
60689
60690-60691
60692-60693
60694-60695
60696-60697
13963
13964
13965
13966
13967
13968
ED19-ED1B
ED1D
ED1D-ED1E
ED1F-ED20
ED21-ED22
ED23-ED24
60698-60700
60701
60702-60703
60704-60705
60706-60707
60708-60709
13969
13970
13971
13972
13973
13974
ED25-ED27
ED29
ED29-ED2A
ED2B-ED2C
ED2D-ED2E
ED2F-ED30
60710-60712
60713
60714-60715
60716-60717
60718-60719
60720-60721
13975
13976
13977
13978
13979
13980
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-225
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
ED31-ED33
ED35
ED35-ED36
ED37-ED38
ED39-ED3A
ED3B-ED3C
60722-60724
60725
60726-60727
60728-60729
60730-60731
60732-60733
13981
13982
13983
13984
13985
13986
ED3D-ED3F
ED41
ED41-ED42
ED43-ED44
ED45-ED46
ED47-ED48
60734-60736
60737
60738-60739
60740-60741
60742-60743
60744-60745
13987
13988
13989
13990
13991
13992
ED49-ED4B
ED4D
ED4D-ED4E
ED4F-ED50
ED51-ED52
ED53-ED54
60746-60748
60749
60750-60751
60752-60753
60754-60755
60756-60757
13993
13994
13995
13996
13997
13998
ED55-ED57
ED59
ED59-ED5A
ED5B-ED5C
ED5D-ED5E
ED5F-ED60
60758-60760
60761
60762-60763
60764-60765
60766-60767
60768-60769
13999
14000
14001
14002
14003
14004
ED61-ED63
ED65
ED65-ED66
ED67-ED68
ED69-ED6A
ED6B-ED6C
60770-60772
60773
60774-60775
60776-60777
60778-60779
60780-60781
14005
14006
14007
14008
14009
14010
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-226
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
0
ED6D-ED6F
ED71
ED71-ED72
ED73-ED74
ED75-ED76
ED77-ED78
60782-60784
60785
60786-60787
60788-60789
60790-60791
60792-60793
14011
14012
14013
14014
14015
14016
ED79-ED7B
ED7D
ED7D-ED7E
ED7F-ED80
ED81-ED82
ED83-ED84
60794-60796
60797
60798-60799
60800-60801
60802-60803
60804-60805
14017
14018
14019
14020
14021
14022
ED85-ED87
ED89
ED89-ED8A
ED8B-ED8C
ED8D-ED8E
ED8F-ED90
60806-60808
60809
60810-60811
60812-60813
60814-60815
60816-60817
14023
14024
14025
14026
14027
14028
ED91-ED93
ED95
ED95-ED96
60818-60820
60821
60822-60823
14029
14030
14031
ED97-ED98
ED99-ED9A
ED9B-ED9C
60824-60825
60826-60827
60828-60829
14032
14033
14034
ED9D-ED9F
EDA1
EDA1-EDA2
EDA3-EDA4
EDA5-EDA6
EDA7-EDA8
60830-60832
60833
60834-60835
60836-60837
60838-60839
60840-60841
14035
14036
14037
14038
14039
14040
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Prior Season Tier 3
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64
F120
F120
F122
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-227
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
EDA9-EDAB
EDAD
EDAD-EDAE
EDAF-EDB0
EDB1-EDB2
EDB3-EDB4
60842-60844
60845
60846-60847
60848-60849
60850-60851
60852-60853
14041
14042
14043
14044
14045
14046
EDB5-EDB7
EDB9
EDB9-EDBA
EDBB-EDBC
EDBD-EDBE
EDBF-EDC0
60854-60856
60857
60858-60859
60860-60861
60862-60863
60864-60865
14047
14048
14049
14050
14051
14052
EDC1-EDC3
EDC5
EDC5-EDC6
EDC7-EDC8
EDC9-EDCA
EDCB-EDCC
60866-60868
60869
60870-60871
60872-60873
60874-60875
60876-60877
14053
14054
14055
14056
14057
14058
EDCD-EDCF
EDD1
EDD1-EDD2
EDD3-EDD4
EDD5-EDD6
EDD7-EDD8
60878-60880
60881
60882-60883
60884-60885
60886-60887
60888-60889
14059
14060
14061
14062
14063
14064
EDD9-EDDB
EDDD
EDDD-EDDE
EDDF-EDE0
EDE1-EDE2
EDE3-EDE4
60890-60892
60893
60894-60895
60896-60897
60898-60899
60900-60901
14065
14066
14067
14068
14069
14070
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-228
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
0
EDE5-EDE7
EDE9
EDE9-EDEA
EDEB-EDEC
EDED-EDEE
EDEF-EDF0
60902-60904
60905
60906-60907
60908-60909
60910-60911
60912-60913
14071
14072
14073
14074
14075
14076
EDF1-EDF3
EDF5
EDF5-EDF6
EDF7-EDF8
EDF9-EDFA
EDFB-EDFC
60914-60916
60917
60918-60919
60920-60921
60922-60923
60924-60925
14077
14078
14079
14080
14081
14082
EDFD-EDFF
EE01
EE01-EE02
EE03-EE04
EE05-EE06
EE07-EE08
60926-60928
60929
60930-60931
60932-60933
60934-60935
60936-60937
14083
14084
14085
14086
14087
14088
EE09-EE0B
EE0D
EE0D-EE0E
EE0F-EE10
EE11-EE12
EE13-EE14
60938-60940
60941
60942-60943
60944-60945
60946-60947
60948-60949
14089
14090
14091
14092
14093
14094
EE15-EE17
EE19
EE19-EE1A
EE1B-EE1C
EE1D-EE1E
EE1F-EE20
60950-60952
60953
60954-60955
60956-60957
60958-60959
60960-60961
14095
14096
14097
14098
14099
14100
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-229
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
EE21-EE23
EE25
EE25-EE26
EE27-EE28
EE29-EE2A
EE2B-EE2C
60962-60964
60965
60966-60967
60968-60969
60970-60971
60972-60973
14101
14102
14103
14104
14105
14106
EE2D-EE2F
EE31
EE31-EE32
EE33-EE34
EE35-EE36
EE37-EE38
60974-60976
60977
60978-60979
60980-60981
60982-60983
60984-60985
14107
14108
14109
14110
14111
14112
EE39-EE3B
EE3D
EE3D-EE3E
EE3F-EE40
EE41-EE42
EE43-EE44
60986-60988
60989
60990-60991
60992-60993
60994-60995
60996-60997
14113
14114
14115
14116
14117
14118
EE45-EE47
EE49
EE49-EE4A
EE4B-EE4C
EE4D-EE4E
EE4F-EE50
60998-61000
61001
61002-61003
61004-61005
61006-61007
61008-61009
14119
14120
14121
14122
14123
14124
EE51-EE53
EE55
EE55-EE56
61010-61012
61013
61014-61015
14125
14126
14127
0
0
EE57-EE58
EE59-EE5A
EE5B-EE5C
61016-61017
61018-61019
61020-61021
14128
14129
14130
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
Prior Season Tier 4
Accumulator for Monitored Data Set 1
Peak Demand for Monitored Data Set 1
Coincident Demand for Monitored Data Set 1
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
R
R
F64 R
F120 R
F120 R
MM-230
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
EE5D-EE5F
EE61
EE61-EE62
EE63-EE64
EE65-EE66
EE67-EE68
61022-61024
61025
61026-61027
61028-61029
61030-61031
61032-61033
14131
14132
14133
14134
14135
14136
EE69-EE6B
EE6D
EE6D-EE6E
EE6F-EE70
EE71-EE72
EE73-EE74
61034-61036
61037
61038-61039
61040-61041
61042-61043
61044-61045
14137
14138
14139
14140
14141
14142
EE75-EE77
EE79
EE79-EE7A
EE7B-EE7C
EE7D-EE7E
EE7F-EE80
61046-61048
61049
61050-61051
61052-61053
61054-61055
61056-61057
14143
14144
14145
14146
14147
14148
EE81-EE83
EE85
EE85-EE86
EE87-EE88
EE89-EE8A
EE8B-EE8C
61058-61060
61061
61062-61063
61064-61065
61066-61067
61068-61069
14149
14150
14151
14152
14153
14154
EE8D-EE8F
EE91
EE91-EE92
EE93-EE94
EE95-EE96
EE97-EE98
61070-61072
61073
61074-61075
61076-61077
61078-61079
61080-61081
14155
14156
14157
14158
14159
14160
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 1 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 1
Accumulator for Monitored Data Set 2
Peak Demand for Monitored Data Set 2
Coincident Demand for Monitored Data Set 2
Timestamp for Monitored Data Set 2 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 2
Accumulator for Monitored Data Set 3
Peak Demand for Monitored Data Set 3
Coincident Demand for Monitored Data Set 3
Timestamp for Monitored Data Set 3 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 3
Accumulator for Monitored Data Set 4
Peak Demand for Monitored Data Set 4
Coincident Demand for Monitored Data Set 4
Timestamp for Monitored Data Set 4 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 4
Accumulator for Monitored Data Set 5
Peak Demand for Monitored Data Set 5
Coincident Demand for Monitored Data Set 5
Timestamp for Monitored Data Set 5 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 5
Accumulator for Monitored Data Set 6
Peak Demand for Monitored Data Set 6
Coincident Demand for Monitored Data Set 6
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-231
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
EE99-EE9B
EE9D
EE9D-EE9E
EE9F-EEA0
EEA1-EEA2
EEA3-EEA4
61082-61084
61085
61086-61087
61088-61089
61090-61091
61092-61093
14161
14162
14163
14164
14165
14166
EEA5-EEA7
EEA9
EEA9-EEAA
EEAB-EEAC
EEAD-EEAE
EEAF-EEB0
61094-61096
61097
61098-61099
61100-61101
61102-61103
61104-61105
14167
14168
14169
14170
14171
14172
EEB1-EEB3
EEB5
EEB5-EEB6
EEB7-EEB8
EEB9-EEBA
EEBB-EEBC
61106-61108
61109
61110-61111
61112-61113
61114-61115
61116-61117
14173
14174
14175
14176
14177
14178
EEBD-EEBF
EEC1
EEC1-EEC2
EEC3-EEC4
EEC5-EEC6
EEC7-EEC8
61118-61120
61121
61122-61123
61124-61125
61126-61127
61128-61129
14179
14180
14181
14182
14183
14184
EEC9-EECB
EECD
EECD-EECE
EECF-EED0
EED1-EED2
EED3-EED4
61130-61132
61133
61134-61135
61136-61137
61138-61139
61140-61141
14185
14186
14187
14188
14189
14190
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 6 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 6
Accumulator for Monitored Data Set 7
Peak Demand for Monitored Data Set 7
Coincident Demand for Monitored Data Set 7
Timestamp for Monitored Data Set 7 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 7
Accumulator for Monitored Data Set 8
Peak Demand for Monitored Data Set 8
Coincident Demand for Monitored Data Set 8
Timestamp for Monitored Data Set 8 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 8
Accumulator for Monitored Data Set 9
Peak Demand for Monitored Data Set 9
Coincident Demand for Monitored Data Set 9
Timestamp for Monitored Data Set 9 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 9
Accumulator for Monitored Data Set 10
Peak Demand for Monitored Data Set 10
Coincident Demand for Monitored Data Set 10
Timestamp for Monitored Data Set 10 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 10
Accumulator for Monitored Data Set 11
Peak Demand for Monitored Data Set 11
Coincident Demand for Monitored Data Set 11
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-232
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
EED5-EED7
EED9
EED9-EEDA
EEDB-EEDC
EEDD-EEDE
EEDF-EEE0
61142-61144
61145
61146-61147
61148-61149
61150-61151
61152-61153
14191
14192
14193
14194
14195
14196
EEE1-EEE3
EEE5
EEE5-EEE6
EEE7-EEE8
EEE9-EEEA
EEEB-EEEC
61154-61156
61157
61158-61159
61160-61161
61162-61163
61164-61165
14197
14198
14199
14200
14201
14202
EEED-EEEF
EEF1
EEF1-EEF2
EEF3-EEF4
EEF5-EEF6
EEF7-EEF8
61166-61168
61169
61170-61171
61172-61173
61174-61175
61176-61177
14203
14204
14205
14206
14207
14208
EEF9-EEFB
EEFD
EEFD-EEFE
EEFF-EF00
EF01-EF02
EF03-EF04
61178-61180
61181
61182-61183
61184-61185
61186-61187
61188-61189
14209
14210
14211
14212
14213
14214
EF05-EF07
EF09
EF09-EF0A
EF0B-EF0C
EF0D-EF0E
EF0F-EF10
61190-61192
61193
61194-61195
61196-61197
61198-61199
61200-61201
14215
14216
14217
14218
14219
14220
Pt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DNP
Obj
Description
Timestamp for Monitored Data Set 11 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 11
Accumulator for Monitored Data Set 12
Peak Demand for Monitored Data Set 12
Coincident Demand for Monitored Data Set 12
Timestamp for Monitored Data Set 12 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 12
Accumulator for Monitored Data Set 13
Peak Demand for Monitored Data Set 13
Coincident Demand for Monitored Data Set 13
Timestamp for Monitored Data Set 13 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 13
Accumulator for Monitored Data Set 14
Peak Demand for Monitored Data Set 14
Coincident Demand for Monitored Data Set 14
Timestamp for Monitored Data Set 14 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 14
Accumulator for Monitored Data Set 15
Peak Demand for Monitored Data Set 15
Coincident Demand for Monitored Data Set 15
Timestamp for Monitored Data Set 15 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 15
Accumulator for Monitored Data Set 16
Peak Demand for Monitored Data Set 16
Coincident Demand for Monitored Data Set 16
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
Notes
F122 R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
F122
R
R
R
R
R
R
F51
F52
F64
F120
F120
R
R
R
R
R
MM-233
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
Line
Pt
EF11-EF13
EF15
EF15-EF16
61202-61204
61205
61206-61207
14221
14222
14223
0
0
EF17H
EF18H
EF19H
EF1AH
61208
61209
61210
61211
14248
14249
14249
14249
0
1
2
3
EF1BH-EF34H
61212-61237
EF35H-EF4EH
61238-61263
EF4FH-EF56H
61264-61271
EF57H-EF5EH
61272-61279
EF5FH-EF66H
61280-61287
EF67H-EF6EH
61288-61295
EF6FH
61296
EF70H
EF71H-EF73H
EF74H-EF76H
EF77H-EF79H
EF7AH-EF7CH
61297
61298-61300
61301-61302
61303-61305
61306-61308
0
DNP
Obj
Description
Range
Timestamp for Monitored Data Set 16 Peak &
Coincident Demand
Reserved
Cumulative Demand for Monitored Data Set 16
One cycle: Extra Readings
One cycle Total Power Factor
3.999 / 0.000
One cycle Phase C Power Factor
3.999 / 0.000
One cycle Phase B Power Factor
3.999 / 0.000
One cycle Phase A Power Factor
3.999 / 0.000
TOU: Extra Readings
TOU Previous Month Scaled Energy Formats, 1-52, 2
formats per register
TOU Previous Season Scaled Energy Formats, 1-52, 2
formats per register
TOU Previous Month Scaled Energy IDs, 1-16, 1 ID for
each data set, 2 IDs per register. 0=no scaled energy
format assigned, valid settings are 1-52
TOU Previous Season Scaled Energy IDs, 1-16, 1 ID
for each data set, 2 IDs per register. 0=no scaled
energy format assigned, valid settings are 1-52.
TOU Previous Month coincident demand type IDs, 116, 1 ID for each data set, 2 IDs per register. For PF
type data, ID=0, not assigned. For VAR type data,
valid settings are 2,3,6,8,11,13,25,26.
TOU Previous Season coincident demand type IDs, 116, 1 ID for each data set, 2 IDs per register. For PF
type data, ID=0, not assigned. For VAR type data,
valid settings are 2,3,6,8,11,13,25,26.
TOU Previous Month Status Bits
(Format is same as in holding register 0x8807)
TOU Previous Season Status Bits
(Format is same as in holding register 0x8807)
Last month start time
Current month start time
Last season/week/day start time
Current season/week/day start time
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Units
Type R/W
Notes
F122 R
0.001 PF
0.001 PF
0.001 PF
0.001 PF
F51
F52
R
R
F8
F8
F8
F8
R
R
R
R
F65
R
F65
R
F47/F
49
R
F47/F
49
R
F47/F
49
R
F47/F
49
R
F51
R
F51
F122
F122
F122
F122
R
R
R
R
R
MM-234
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
F000H-F007H
F001H-F00FH
F010H-F017H
F018H-F01FH
F020H-F027H
F028H-F02FH
F030H-F03FH
F040H-F047H
F041H-F04FH
F050H-F057H
F058H-F05FH
F060H-F067H
F068H-F06FH
F070H-F07FH
F080H-F087H
F088H-F08FH
F090H-F097H
F098H-F09FH
F0A0H-F0A7H
F0A8H-F0AFH
F0B0H-F0BFH
F0C0H-F1FFH
F200H-F20FH
F210H-F21FH
F220H-F227H
F228H-F22FH
F230H-F237H
F238H-F23FH
F240H-F247H
F248H-F24FH
F250H-F257H
F258H-F25FH
F260H-F267H
F268H-F26FH
61441-61448
61449-61456
61457-61464
61465-61472
61473-61480
61481-61488
61489-61504
61505-61512
61513-61520
61521-61528
61529-61536
61537-61544
61545-61552
61553-61568
61569-61576
61577-61584
61585-61592
61593-61600
61601-61608
61609-61616
61617-61632
61639-61952
61953-61968
61969-61984
61985-61992
61993-62000
62001-62008
62009-62016
62017-62024
62025-62032
62033-62040
62041-62048
62049-62056
62057-62064
Line
Pt
DNP
Obj
Description
Device Hardware Information Block
name of board#1
serial number of board#1
board number of board#1
rev of board#1
test status of board#1
test date of board#1
reserved
name of board#2
serial number of board#2
board number of board#2
rev of board#2
test status of board#2
test date of board#2
reserved
name of board#3
serial number of board#3
board number of board#3
rev of board#3
test status of board#3
test date of board#3
reserved
compact flash card model
compact flash card serial number
compact flash card firmware id
compacf flash card file partition type
cpu type
cpu clock frequency
cpu rev
cpu rev id
cpu platform
cpu memory size
fpga hardware id or trace id
fpga firmware id
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Range
Units
Type R/W
F1
F1
F1
F1
F1
F1
R
R
R
R
R
R
F1
F1
F1
F1
F1
F1
R
R
R
R
R
R
F1
F1
F1
F1
F1
F1
R
R
R
R
R
R
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
R
R
R
R
R
R
R
R
R
R
Notes
MM-235
2: Modbus Map - Input Registers
Addr. (hex)
Address(3X)
F270H-F277H
F278H-F27FH
F280H-F287H
F288H-F28FH
F290H-F2AFH
F2B0H-F2CFH
F2D0H-F2EFH
F2F0H-F2FFH
F300H-F30FH
F310H-F317H
F318H-F31FH
F320H-F32DH
F32EH-F32FH
F330H-F33DH
F33EH-F33FH
F340H-F34DH
F34EH-F34FH
F350H-F35DH
F35EH-F35FH
F360H-F36DH
F36EH-F36FH
F370H-F37DH
F37EH-F37FH
F380H-F388FH
F389H-F38FH
F390H-F398H
F399H-F39FH
62065-62072
62073-62080
62081-62088
62089-62096
62097-62128
62129-62160
62161-62192
62193-62208
62209-62224
62225-62232
62233-62240
62241-62254
62255-62256
62257-62270
62271-62272
62273-62286
62287-62288
62289-62302
62303-62304
62305-62318
62319-62320
62321-62334
62335-62336
62337-62345
62346-62352
62353-62361
62362-62368
Line
Pt
DNP
Obj
Description
Range
Units
Type R/W
dsp runtime version
dsp runtime buildtime
preboot version
preboot build tune
uboot id user1 copy
uboot id user2 copy
uboot id factory copy
linux kernel name
linux kernel version
kernel module ucc_dsp version
F1
F1
F1
F1
F1
R
R
R
R
R
R
R
R
R
R
modbus map version, disk copy
F1
R
modbus map version, ram copy
F1
R
apps archive version
F1
R
apps archive buildtime
F1
R
web archive version
F1
R
web archive buildtime
F1
R
MAC address for port5, ethernet0
F1
R
MAC address for port6, ethernet1
F1
R
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E171707
Notes
MM-236
3: Communication Data Formats
3: Communication Data Formats
3.1: Introduction
This chapter expands upon information listed in the Nexus® 1450 meter's Modbus
register map, shown in Chapter 2. Section Headings (F1, F2, etc.) refer to the value in
the register map's "Type" column.
3.2: Type F1 - Null Terminated ASCII String
Length: Depends on the reading.
Each register contains two bytes. Each byte stands for an ASCII character. The printable portion of the string is terminated with a Null character (ASCII 00H). Any characters after the terminating Null character are ignored.
Example:
Registers 00001 - 00008, the Device Name, might contain the following data:
Address
00001
00002
00003
00004
00005
00006
00007
00008
Value
3031H
3731H
204EH
6578H
7573H
2031H
3435H
3000H
Bytes
30H
31H
37H
31H
20H
43H
65H
78H
75H
73H
20H
31H
34H
35H
30H
00H
ASCII
‘0’
‘1’
‘7’
‘1’
‘’
‘N’
‘e’
‘x’
‘u’
‘s’
‘’
‘1’
‘4’
‘5’
‘0’
Null
Register
"01”
"71”
"N”
String
"ex”
"us”
"1”
"45”
"0"
"0171 Nexus 1450"
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-1
3: Communication Data Formats
3.3: Type F2 - Fixed Length ASCII String
Length: Depends on the reading.
Each register contains two bytes. Each byte stands for an ASCII character. All bytes
are significant. There is no terminating character.
Example:
Registers 00073 - 00074, the Nexus® Comm Boot version number, which might
contain the following data:
Address
00073
00074
Value
3030H
3134H
Bytes
30H
30H
31H
31H
ASCII
‘0’
‘0’
‘1’
‘1’
Register
“00”
String
“14”
“0014”
3.4: Type F3 - Time Stamp
Length: 4 Registers (8 bytes)
Order: Least significant byte first
Range: 2/31/9999 23:59:59.99
Unit: 10 ms
Each register contains two bytes. Each byte contains a binary number representing up
to two digits in a part of date and time. The units for each byte are century, year,
month, date, hour, minute, second and 10 millisecond. Hour is in 24-hour form,
00H = 0 = 12 AM, 01H = 1 = 1 AM, …, 0BH = 11 = 11 AM, 0CH = 12 = 12 PM, 0DH
= 13 = 1 PM, …, 17H = 23 = 11 PM.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-2
3: Communication Data Formats
Example:
Registers 00081 - 00084, On Time, might contain the following data:
Address
00081
00082
00083
00084
Value
140EH
0619H
0913H
3056H
Bytes
Decimal
Unit
14H
0EH
06H
19H
09H
13H
30H
56H
20
14
6
25
9
19
48
86
Century
Year
Month
Date
Hour
Minute
Second
10 Millisecond
Date
June 25, 2014 9:19:48:86 AM
3.5: Type F4 - Day of Week
Length: 1 Register (2 bytes)
This register contains a 16-bit number, associated with the days of the week as
follows:
Value
Day of the Week
Value
Day of the Week
0001H
Sunday
0005H
Thursday
0002H
Monday
0006H
Friday
0003H
Tuesday
0007H
Saturday
0004H
Wednesday
3.6: Type F6 - High Speed Inputs, Delta and Current State
Length: 1 Register (2 bytes)
This register has two bytes. Each byte has eight bits. The bits in each byte are associated with the meter’s 8 high speed inputs - the least significant bit with input 1,
through to the most significant bit with input 8.
The most significant byte contains Delta information about the high speed inputs; the
least significant byte contains the current state of the high speed inputs. For Delta
bits, a bit value of 1 means one or more were noticed on this input during the last
cycle; a bit value of 0 means no changes were noticed on this input during the last
cycle. For current state bits, a bit value of 1 means the input is open; a bit value of 0
means the input is closed.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-3
3: Communication Data Formats
Example:
Address
00118
Value
0461H
Bytes
04H
0
0
0
0
61H
0
1
0
0
0
1
High Speed Input Delta
Meaning
Interpretation
1
0
0
0
0
1
High Speed Input Current State
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
_
_
_
_
_
Change
_
_
Clsd
Opn
Opn
Clsd
Clsd
Clsd
Clsd
Opn
Inputs 7, 6, and ,and 1 are now open and Input 3 changed state at least once during the last cycle.
3.7: Type F7- Secondary Voltage, Current, VA, VAR, Watts, Hz or
Flicker
Length: 2 Registers (4 bytes)
Range: +32767 / -32768
Unit: 1/65536 V, A, VA, VAR, W or Hz
The registers together contain a four-byte signed (2's compliment) integer. Positive
values have the most significant bit clear, and have the same magnitude as an
unsigned integer. Negative values have the most significant bit set. The magnitude of
a negative value is found by complementing (inverting) all of the bits and adding 1.
Examples:
Registers 00153 - 00154, Tenth second Phase A VAR might contain the following data:
Address
00153
00154
Value
0001H
4000H
4-byte signed integer (Hex)
00014000H
Most significant bit
0
4-byte integer (Decimal)
+81920
1/65536 VAR Secondary
+1.25 VAR secondary
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-4
3: Communication Data Formats
Registers 00153 - 00154, Tenth second Phase A VAR, might contain the following
data:
Address
00153
00154
Value
FFFEH
C000H
4-byte signed integer (Hex)
FFFEC000H
Most significant bit
1
Compliment
00013FFFH
Increment
00014000H
4-byte integer (Decimal)
-81920
1/65536 VAR Secondary
-1.25 VAR secondary
3.8: Type F8 - Power Factor
Length: 1 Register (2 bytes)
Range: 3.999 / 0.000
Unit: 0.001 PF
This register contains a 16 bit unsigned number. This number varies from 0000H 0F9FH, or 0 to 3999 in decimal. This representation allows for expressing power
factor from 0 to 1 in the four quadrants, as shown in the following table (which is
oriented clockwise, starting from 90 degrees):
Quadrant
Value
Hex
PF
Dec
Value
Hex
Value
PF
Dec
Hex
PF
Dec
1
0000H
0
0.0000
01F4H
500
0.500
03E7H
999
0.999
4
03E8H
1000
1.000
05DCH
1500
0.500
07CFH
1999
0.001
3
07D0H
2000
0.0000
09c4h
2500
0.500
0bb7h
2999
0.999
2
0bb8h
3000
1.000
0dach
3500
0.500
0f9fh
3999
0.001
Application of sign and lead/lag labels (is 9CFH -0.500 Lead or +0.500 Lag) depends
on the programmable setting called Power Factor Labeling, located in register 46019,
described in Section 6.16. Energy direction Block.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-5
3: Communication Data Formats
Examples:
Register 00171, Tenth second Phase A Power Factor, might contain the following data:
Address
00171
Value
0C10H
Decimal
3088
PF
Q2, 0.912
Register 00171, Tenth second Phase A Power Factor, might contain the following data:
Address
00171
Value
0390H
Decimal
912
PF
Q1, 0.912
3.9: Type F9 - Angle
Length: 1 Register (2 byte)
Range: +180 / -180
Unit: 0.01 degree
This register contains a 16-bit signed (2's complement) number. Positive values have
the most significant bit clear, and have the same magnitude as an unsigned integer.
Negative values have the most significant bit set. The magnitude of a negative value
is found by complimenting (inverting) all of the bits and adding 1.
Examples:
Register 00175, Tenth second Phase A-N Voltage to Auxiliary Voltage Phase Angle,
might contain the following data:
Address
00175
Value
08BBH
Most significant bit
0
Decimal
+2235
Angle
+22.35 Degrees
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-6
3: Communication Data Formats
Register 00175, Tenth second Phase A-N Voltage to Auxiliary Voltage Phase Angle,
might contain the following data.
Address
00175
Value
F745H
Most significant bit
1
Compliment
08BAH
Increment
08BBH
Decimal
-2235
Angle
-22.35 Degrees
3.10: Type F10 - Percentage
Length: 1 Register (2 bytes)
Range: +327.67% / - 327.68%
Unit: 0.01%
This register contains a 16-bit signed (2's compliment) number. Positive values have
the most significant bit clear, and have the same magnitude as an unsigned integer.
Negative values have the most significant bit set. The magnitude of a negative value
is found by complimenting (inverting) all of the bits and adding 1.
Examples:
Register 00234, One second Voltage Imbalance, might contain the following data:
Address
00234
Value
08BBH
Most significant bit
0
Decimal
+2235
Percent
+22.35%
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-7
3: Communication Data Formats
Register 00234, One second Voltage Imbalance, might contain the following data:
Address
00234
Value
F745H
Most significant bit
1
Compliment
08BAH
Increment
08BBH
Decimal
-2235
Percent
-22.35%
3.11: Type F11 - Energy Counter (Packed BCD / Secondary)
Length: 4 Registers (8 bytes)
Range: 9,999,999,999,999,999 / 0 VAh, VARh or Wh secondary
Unit: 1 VAh, VARh or Wh secondary
These registers contain 8 bytes of Packed BCD. Each register contains 2 bytes. Each
byte contains 2 nibbles. Each nibble represents a decimal digit from 0-9. All together,
there are 16 nibbles, and therefore a 16-digit decimal number can be represented.
Example:
Registers 00982 - 00985, VAhour, might contain the following data:
Address
00982
00983
00984
00985
Value
000H
0001H
0534H
1284H
Bytes
00H
Nibbles
00H
00H
01H
05H
34H
12H
84H
0H
0H
0H
0H
0H
0H
0H
1H
0H
5H
3H
4H
1H
2H
8H
4H
Digit
0
0
0
0
0
0
0
1
0
5
3
4
1
2
8
4
Unit
P
T
VAh
G
M
k
105,341,284 VAh secondary
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-8
3: Communication Data Formats
3.12: Type F12 - Energy Counter (Binary / Secondary)
Length: 4 Registers (8 bytes)
Range: 9,999,999,999,999,999 / 0 VAh, VARh or Wh secondary
Unit: 1 VAh, VARh or Wh secondary
These registers contain an 8-byte unsigned integer.
Example:
Registers 01002-01005, VAhour, might contain the following data:
Address
01002
01003
01004
01005
Value
0000H
0000H
0647H
6164H
8-byte unsigned integer (Hex)
0000000006476164H
Decimal
105341284
VAh
105,341,284 VAh secondary
3.13: Type F13 - Phase Sequence
Length: 1 Register (2 bytes)
This register contains a 16-bit unsigned integer, most-significant byte first, associated
with the Phase Sequence as follows:
Value (Hex)
Phase
Sequence
0000H
A-B-C
0001H
C-B-A
3.14: Type F14 - Block/Rolling Window Average Status
Length: 1 Register (2 bytes)
This register contains a 16-bit unsigned integer, associated with the Average Status
as follows:
Value (Hex)
Average Status
0000H
Not yet available
0001H
Available
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-9
3: Communication Data Formats
This is the Status Register for Block Window Average (02605-02683) and Rolling
Window Average (02684-02768).
If a value is not yet computed by the Nexus® device, the Status value will be zero.
• When the value is zero, Communicator EXTTM software displays asterisks for values.
• In Modbus, a value will be returned based on the type of reading.
• Negative Maximums and Positive Minimums return: 7FFFFFFFH or
2,147,483,647.
• Positive Maximums and Negative Minimums return: 80000000H or +/2,147,483,647.
• No Timestamp will be assigned to the reading.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-10
3: Communication Data Formats
3.15: Type F15 - Limit States
Length: 1 Register (2 bytes)
This register has two bytes. Each byte has eight bits. The bits in these bytes are associated with the 16 Limits, the most significant bit of the most significant byte with
Limit 1 (or 17), through to the least significant bit of the least significant byte with
Limit 16 (or 32).
A bit value of 1 means that the particular limit has been passed, while a bit value of 0
means that the particular limit has not been passed.
Example:
Register 02769, Limit States, Value 1 Comparison, 1-16, might contain the following
data:
Address
02769
Value
0461H
Bytes
04H
61H
Bits
0
0
0
0
0
1
0
0
0
1
1
0
0
0
0
1
Points
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Limit
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Passed
No
No
No
No
No
Yes
No
No
No
Yes
Yes
No
No
No
No
Yes
Interpretation
Limits 6, 10, 11, and 16 are currently passed; all others are not passed.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-11
3: Communication Data Formats
3.16: Type F16 - Low Speed (Internal) Input States
Length: 1 Register (2 bytes)
This register has two bytes. Each byte has eight bits. The bits in the most significant
byte are associated with the eight Status Inputs, the most significant bit with input 8,
through to the least significant bit with Input 1. The least significant byte is undefined.
A bit value of 1 means the input is open; a bit value of 0 means the input is closed.
Example:
Register 02773, Low Speed (Internal) Inputs, might contain the following data:
Address
(Hex)
02773
Value
5100H
Bytes
51H
Bits
0
1
0
1
0
00H
0
0
1
0
0
0
0
0
0
0
0
3
2
1
Undefined
Input
8
7
6
5
4
3
2
1
Meaning
Clsd
Opn
Clsd
Opn
Clsd
Clsd
Clsd
Opn
Interpretation
8
7
6
5
4
Inputs 7, 5 and 1 are open; all other inputs are closed.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-12
3: Communication Data Formats
3.17: Type F17 - Digital Input States in Digital Input Option Board
Length: 1 Register (2 bytes)
This register has two bytes. Each byte has eight bits. The bits in the most significant
byte are associated with the eight Digital Inputs in a Digital Input Option board, the
most significant bit with input 8, through to the least significant bit with Input 1. The
least significant byte is undefined.
A bit value of 1 means the input is open; a bit value of 0 means the input is closed.
Example:
Register 0AD5H, Digital Input States, Digital Input Option board in Slot 3, might
contain the following data:
Address
(Hex)
0AD5H
Value
5100H
Bytes
51H
00H
Bits
0
0
0
0
0
0
0
0
0
1
0
1
0
0
0
1
Point
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Digital Input States
Undefined
Input
8
7
6
5
4
3
2
1
Meaning
Clsd
Opn
Clsd
Opn
Clsd
Clsd
Clsd
Opn
Interpretation
Inputs 7, 5 and 1 are open; all other inputs are closed.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-13
3: Communication Data Formats
3.18: Type F18 - Digital Input Option Board Input Accumulation /
Cumulative Demand
Length: 2 Registers (4 bytes)
Range: 4,294,967,295/0
Unit: Accumulated Transitions, Accumulated Primary Watts
These registers contain a 4 byte unsigned integer.
Example:
Registers 0AD6H-0AD7H, Input Accumulation 1, Digital Input Option Board in slot 3,
might contain the following data:
Addr (Hex)
0AD6H
0AD7H
Value
0647H
6164H
4 byte unsigned integer
06476164H
Decimal
105341284
Accumulated Transitions
105,341,284 Accumulated Transitions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-14
3: Communication Data Formats
3.19: Type F33 - Temperature
Length: 1 Register (2 bytes)
Range: +3276.7 C / - 3276.8 C
Unit: 0.1 degree C
This register contains a 16-bit signed (2's compliment) number. Positive values have
the most significant bit clear and have the same magnitude as an unsigned integer.
Negative values have the most significant bit set. The magnitude of a negative value
is found by complimenting (inverting) all of the bits and adding 1.
Examples:
Register 05946, meter's Internal Temperature, might contain the following data:
Address
05946
Value
08BBH
Most significant bit
0
Decimal
+223
Celsius
+22.3 degree C
Register 05946, meter's Internal Temperature, might contain the following data:
Address
05946
Value
F745H
Most significant bit
1
Compliment
08BAH
Increment
08BBH
Decimal
-223
Celsius
-22.3 degree C
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-15
3: Communication Data Formats
3.20: Type F34 - Limit and Relay Logic States
Length 1 Register (2 bytes)
This register has two bytes. Each byte has eight bits. The bits in these bytes are associated with the 16 Limits or Relays, the most significant bit of the most significant
byte with Limit 1 (or 17, or Relay 1), through to the least significant bit of the least
significant byte with Limit 16 (or 32, or Relay 16).
A bit value of 1 means TRUE, while a bit value of 0 means FALSE. TRUE and FALSE
result from the AND, OR XOR, Hysteresis and NOT of two input values of 1 or 0.
Example:
Register 175AH, Limit States, Combinations, 1-16, might contain the following data:
Addr (Hex)
175AH
Value
0461H
Bytes
04H
61H
Bits
0
0
0
0
0
1
0
0
0
1
1
0
0
0
0
1
Point
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Limit
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Logic (T/F)
F
F
F
F
F
T
F
F
F
T
T
F
F
F
F
T
Interpretation
Limit Combinations 6, 10, 11 and 16 are currently TRUE, all others are FALSE.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-16
3: Communication Data Formats
3.21: Type F35 - Relay Delays
Length: 1/2 Register (1 byte) (2 per Register)
This register has two bytes. Each byte contains an unsigned integer which is a countdown delay. A relay logic tree must be stable for the duration of the delay before triggering a relay. Delays are preloaded when the Gate G value changes. They are decremented every pass thereafter, until they reach zero.
Example:
Register 06000, Delay Timer, Relay 1 / Relay 2, might contain the following data:
Address
04H
00H
Value
0400H
Bytes
06000
Interpretation
Relay 1 has 4 seconds of delay remaining, Relay 2 has no delay remaining.
3.22: Type F36 - Desired Relay States
Length: 1 Register (1 bytes)
This register has two bytes. Each byte has eight bits. The bits in these bytes are associated with the 16 Relays, the most significant bit of the most significant byte with
Relay 1, through the least significant bit of the least significant byte with Relay 16.
A bit value of 1 means the relay should be energized (connected to Normal Open); a
bit value of 0 means the relay should be de-energized (connected to Normal Close).
These are states pending transmission to the relays.
Example:
Register 06008, Desired Relay States, Relays 1-16, might contain the following data:
Address
06008
Value
0461H
Bytes
04H
61H
Bits
0
0
0
0
0
1
0
0
0
1
1
0
0
0
0
1
Limit
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
State (NO/NC)
NC
NC
NC
NC
NC
NO
NC
NC
NC
NO
NO
NC
NC
NC
NC
NO
Interpretation
Relays 6, 10, 11 and 16 should be energized; all others de-energized.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-17
3: Communication Data Formats
3.23: Type F37 - Relays Pending Update
Length: 1 Register (2 bytes)
This register has two bytes. Each byte has eight bits. The bits in these bytes are associated with the 16 Relays, the most significant byte with Relay 1 through to the least
significant bit of the least significant byte with Relay 16.
A bit value of 1 means the physical relay needs to be updated, a bit value of 0 means
the physical relay does not need to be updated.
Example:
Register 06009, Relays Pending Updates 1-16, might contain the following data:
Address
06009
Value
0461H
Bytes
04H
61H
Bits
0
0
0
0
0
1
0
0
0
1
1
0
0
0
0
1
Point
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Relay
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Update?
No
Yes
Yes
Interpretation
Relays 6, 10, 11 and 16 need to be updated, all others are in their correct states.
Yes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
Yes
3-18
3: Communication Data Formats
3.24: Type F38 Shadowed Relay States
Length: 1 Register (2 bytes)
This register has two bytes. Each byte has eight bits. The bits in these bytes are associated with the 16 Relays, the most significant byte with Relay 1 through to the least
significant bit of the least significant byte with Relay 16.
A bit value of 1 means the relay is supposed to be energized (connected to Normal
Open), a bit value of 0 means the relay is supposed to be de-energized (connected to
Normal Close). These states have not necessarily been confirmed by polling the relay
device.
Example:
Register 06010, Shadowed Relay States 1-16, might contain the following data:
Address
060010
Value
0461H
Bytes
04H
61H
Bits
0
0
0
0
0
1
0
0
0
1
0
0
0
0
0
0
Point
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Relay
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
State (NO/NC)
NC
NC
NC
NC
NC
NO
NC
NC
NC
NO
NC
NC
NC
NC
NC
NC
Interpretation
Relays 6 and 10 are supposed to be energized, all others de-energized,
not necessarily confirmed.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-19
3: Communication Data Formats
3.25: Type F39 - Confirmed Polled Relay States
Length: 1 Register (2 bytes)
This register has two bytes. Each byte has eight bits. The bits in these bytes are associated with the 16 Relays, the most significant byte with Relay 1 through to the least
significant bit of the least significant byte with Relay 16.
A bit value of 1 means the relay was energized (connected to Normal Open) when last
polled, a bit value of 0 means the relay was de-energized (connected to Normal
Close) when last polled. These states may not be current on the relays, since operations may have occurred since the last poll.
Example:
Register 06011, Confirmed Polled Relay States 1-16, might contain the following
data:
Address
060011
Value
0461H
Bytes
04H
61H
Bits
0
0
0
0
0
1
0
0
0
1
1
0
0
0
0
1
Point
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Relay
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
State (NO/NC)
NC
NC
NC
NC
NC
NO
NC
NC
NC
NO
NO
NC
NC
NC
NC
NO
Interpretation
Relays 6 ,10, 11, and 16 were energized when last polled, all others
were de-energized.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-20
3: Communication Data Formats
3.26: Type F40 - Valid Flags for Confirmed Relay States
Length: 1 Register (2 bytes)
This register has two bytes. Each byte has eight bits. The bits in these bytes are associated with the 16 Relays, the most significant byte with Relay 1 through to the least
significant bit of the least significant byte with Relay 16.
A bit value of 1 means the confirmed states in Confirmed Polled Relay States register
(06011) are valid, a bit value of 0 means the confirmed states have not yet been
polled.
Example:
Register 06012, Valid Flags for Confirmed Relay States, might contain the following
data:
Address
060012
Value
FFF0H
Bytes
FFH
F0H
Bits
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
Point
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Relay
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Valid?
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
Interpretation
Confirmed states for Relays 13-16 have not yet been polled and are not yet valid.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-21
3: Communication Data Formats
3.27: Type F41 - Locked Relays, Relays 1-16
Length: 1 Register (2 bytes)
This register has two bytes. Each byte has eight bits. The bits in these bytes are associated with the 16 Relays, the most significant byte with Relay 1 through to the least
significant bit of the least significant byte with Relay 16.
A bit value of 1 means the relay has been locked, overriding the Relay Logic Tree for
this relay. A bit value of 0 means the relay is operating normally according to the
Relay Logic Tree.
Example:
Register 06013, Locked Relays, Relays 1-16, might contain the following data:
Address
060013
Value
0461H
Bytes
04H
61H
Bits
0
0
0
0
0
1
0
0
0
1
1
0
0
0
0
1
Point
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Relay
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Lock
Lock
Locked?
Interpretation
Lock
Lock
Relays 6, 10, 11, and 16 are locked; all other relays are under control
of the RelayLogic tree.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-22
3: Communication Data Formats
3.28: Type F42 - Locked Relay States
Length: 1 Register (2 bytes)
This register has two bytes. Each byte has eight bits. The bits in these bytes are associated with the 16 Relays, the most significant byte with Relay 1 through to the least
significant bit of the least significant byte with Relay 16.
These bits are valid only if the relays have been selected for locking, as reported in
the Locked Relays register, 060013.
A bit value of 1 means the relay is locked energized (connected to Normal Open). A
bit value of 0 means the relay is locked de-energized (connected to Normal Close).
Example:
Register 060014, Locked Relay States, Relays 1-16, might contain the following data:
Address
060014
Value
0461H
Bytes
04H
61H
Bits
0
0
0
0
0
1
0
0
0
1
1
0
0
0
0
1
Point
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Relay
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
NO/NC
NC
NC
NC
NC
NC
NO
NC
NC
NC
NO
NO
NC
NC
NC
NC
NO
Interpretation
Relays 6, 10, 11, and 16 are energized; all other relays are de-energized, if they are locked.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-23
3: Communication Data Formats
3.29: Type F43 - Miscellaneous Flags
Length: 1 Register (2 bytes)
This register has two bytes. Each byte has eight bits. The bits in these bytes are associated with various miscellaneous functions, as follows:
MSB first, Bit[15] = Battery Status (if it is lower than 2.55 V)
Bit[14] = user current threshold
Bit[13] = Internal failure
Bit[12] = Profile change
Bit[11] = Test Mode
Bit[10] = Time change
Bit[09] = IRIG-B year available
Bit[08] = Not Defined, reserved for debugging (with FW B.0053, 1= IRIG-B
Time continue Forwarding)
Bit[07] = Active IRIG-B
Bit[06] = Active DST
Bit[05] = Active Line Synch
Bit[04] = Active Cold Load
Bit[03] = DST Spring Date (the current date/time is before DST start time for the
current calendar year)
Bit[02] = DST Fall Date (the current date/time is after DST start time for the current
calendar year)
Bit[01] = Active SNTP
Bit[00] = Not defined, reserved for debugging (with FW B.0053, 1 = Battery low flag)
Example:
Register 1796H, Miscellaneous Flags, might contain the following data:
Address
1796H
Value
8000H
Bytes
80H
00H
Bits
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Point
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Interpretation
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Battery is low.
Doc#
E171707
3-24
3: Communication Data Formats
3.30: Type F44 - Digital Input Option Module Data States
Length: 1 Register (2 bytes)
This register has two bytes. Each byte has eight bits. The bits in these bytes are associated with the status of the data received from Digital Input Option Module, as follows:
Bit
Point
Meaning
15 (MSB)
0
Status of Data from Digital Input Option Board in slot 3 (Modbus
Register 0AD5H, 0AE6H)??
14
1
Status of Data from Digital Input Option Board in slot 4 (Modbus
Register 0A57H, 0B08H)??
13-0 (LSB)
Undefined
Digital Input Option Board Data Status -A bit value of 0 means that the data from this
Digital Input option board is not yet valid; either the board is not present or has not
yet been polled. A bit value of 1 means that the data from this Digital Input option
board has been polled at least once and is valid.
Example:
Register 17DEH, Digital Input Option Module Data States, might contain the following
data:??
Addr (Hex)
17DEH
Value
8000H
Bytes
80H
0
0
-
-
00H
Bits
1
0
0
Point
0
1
Digital Input
Option Module
1
2
Status
OK
-
Interpretation
Data from Digital Input Option Module 1 (Register 0AD5H) is valid, data from
Digital Input Option Module 2 is not valid.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
0
0
Doc#
0
0
E171707
0
0
0
0
0
0
0
3-25
3: Communication Data Formats
3.31: Type F45 - Analog Input Modules’ Data States
Length: 2 Registers (4 bytes)
This register has four bytes. Each byte has eight bits. The bits in these bytes are
associated with the status of the data received from the Analog Input Modules, as
follows:
Reg
Bit
Point
Meaning
0
15 (MSB)
0
Status of Analog Input 1, Module 1 (Modbus Register 173AH)
0
14-8
1-7
Status of Analog Inputs 2-8, Module 1 (Modbus Registers 173BH174IH)
0
7-0
8-15
Status of Analog Inputs 1-8, Module 2 (Modbus Registers 1742H1749H)
1
15-8
16-23
Status of Analog Inputs 1-8, Module 3 (Modbus Registers 174AH1751H)
1
7-0
24-31
Status of Analog Inputs 1-8, Module 4 (Modbus Registers 1752H1759H)
Analog Input Module Data Status - A bit value of 0 means that the data from this Analog Input Module is not yet valid; either the module is not present or has not yet been
polled. A bit value of 1 means that the data from this Analog Input Module has been
polled at least once and is valid.
Example:
Register 06112, Analog Input Modules’ Data States, might contain the following data:
Addr (Hex)
06112
Value
8000H
Bytes
80H
00H
Bits
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Point
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Analog Input
Module
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
Input
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Status
OK
OK
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Interpretation
Data from Inputs 1-2 of Analog Input Module 1 is valid (Registers 173AH-173BH),
data from Inputs 3-8 of Analog Input Module 1 is not valid; data from Inputs 1-8 of
Analog Input Module 2 is not valid.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-26
3: Communication Data Formats
3.32: Type F46 - High Byte of Modbus Register (Signed)
Length: 1 byte
High Byte of Modbus Register, Signed
Range: +127 / -128
Unit: 1
3.33: Type F47 - High Byte of Modbus Register (Unsigned)
Length: 1 byte
High Byte of Modbus Register, Unsigned
Range: 255 / 0
Unit: 1
3.34: Type F49 - Low Byte of Modbus Register (Unsigned)
Length: 1 byte
Low Byte of Modbus Register, Unsigned
Range: 255 / 0
Unit: 1
3.35: Type F51 - Two-Byte (Unsigned)
Length: 2 bytes
Two-Byte, Unsigned
Range: 65,535 / 0
Unit: 1
3.36: Type F52 - Four-Byte (Signed)
Length: 4 bytes
Four-Byte, Signed
Range: +2,147,483,647 / -2,147,483,648
Unit: 1
3.37: Type F53 - Four-Byte (Unsigned)
Length: 4 bytes
Four-Byte, Unsigned
Range: 4,294,967,295 / 0
Unit: 1
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-27
3: Communication Data Formats
3.38: Type F55 - Eight-Byte (Unsigned)
Length: 8 bytes
Eight-Byte, Unsigned
Range: 18,446,744,073,709,551,615 / 0
Unit: 1
3.39: Type F56 - Flicker Countdown
Length: 1 Register (2 bytes)
Range: 65,535 / 0 seconds
Unit: 1 second
This register contains an unsigned integer which is a countdown in seconds until the
end of a Flicker interval, Short Term or Long Term.
Example:
Register 06489, Short Term Flicker Countdown, might contain the following data:
Address
06489
Value
0400H
Decimal
1024
Interpretation
1024 seconds remain until the next
Short Term Flicker is computed.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-28
3: Communication Data Formats
3.40: Type F57 - Accumulation in the Interval
Length: 1 Register (2 bytes)
Range: 465,535 / 0
Unit: VAh, VARh, Wh secondary or pulses
These registers contain a 2-byte unsigned integer.
Example:
Register 06397, Total VA hour (Quadrants 1+2+3+4) in the Interval, Secondary,
might contain the following data:
Address
06937
Value
0647H
Decimal
1607
VAh Secondary
1607 VAh Secondary
3.41: Type F58 - 12-bit RTU Sanity Register
Length: 1 Register
This register indicates the status of the meter. A normally functioning meter reports a
value of 0x00000 or 0. Any non-zero value indicates that the unit is operating improperly.
3.42: Type F62 - Scaled Pulse Accumulation, Aggregation or Average
Length: 4 Registers (8 bytes)
Range: +9,223,372,036,854,776,807 / -9,223,372,036,854,776,808
Unit: 1 Unit
This register contains an 8-byte signed (2's complement) number. Positive values
have the most significant bit clear and have the same magnitude as an unsigned integer. Negative values have the most significant bit set. The magnitude of a negative
value is found by complementing (inverting) all of the bits and adding 1.
Type F62 does not use the multiplier from the Energy Scale Settings from the Nexus®
meter's Device Profile. It uses the multiplier from the Nexus® meter's Internal Input
Pulse Accumulations Setup screen (Device Profile > Revenue & Energy Settings >
Pulse Accumulations).
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-29
3: Communication Data Formats
Examples:
Registers 05834 - 05837, Block Window Average Aggregation 1, might contain the
following data:
Address
05834
05835
05836
05837
Value (Hex)
0000H
0000H
0001H
2345H
8 byte Signed Integer (Hex)
000000000001245H
Most Significant Bit
0
Decimal
+74565
Accumulated Transitions
+74,565 Units
Registers 05834-05837, Block Window Average Aggregation 1, might contain the
following data:
Address
05834
05835
05836
05837
Value (Hex)
FFFFH
FFFFH
FFFEH
DCBBH
8 byte Signed Integer (Hex)
FFFFFFFFFFFEDCBBH
Most Significant Bit
1
Complement
0000000000012345H
Increment
0000000000012345H
Decimal
-74565
Accumulated Transitions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
-74,565 Units
Doc#
E171707
3-30
3: Communication Data Formats
3.43: Type F64 - Scaled Energy
Length: 2 Registers (4 bytes)
Range: 99 / 0 through 999,999,999 / 0 (variable, 2-9 digits)
Unit: 10-7 through 106 units (variable)
This register contains an 4-byte signed integer. The range and resolution of a given
reading is controlled by programmable Energy Scale Settings, which govern both the
range of the reading (from 2 to 9 digits) and the units of the reading (from 7 decimal
places of Wh (10-7) to no decimal places of MWh (106). Refer to Type F65 for a
description of the Scaled Energy Programmable Setting (Device Profile > Revenue &
Energy Settings > Energy Scaling).
Example:
Registers 06912-06913, Total VAh (Quadrant 1+2+3+4) Scaled Primary, might
contain the following data:
Address
06912
06913
Value
075BH
CD15H
4-byte Hex
075HCD15H
Decimal
123,456,789
• If the Programmable Settings indicated 5 decimal places of WH, then the interpreted value would be 1,234.56789 Wh.
• If the Programmable Settings indicated 0 decimal places of MWh, then the interpreted value would be 123,456,789 MWh.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-31
3: Communication Data Formats
3.44: Type F65 - Scaled Energy Setting
Length: 1/2 a Register (1 byte)
Each register contains 2 bytes. Each byte contains settings for a base quantity. The
format of a byte is as follows:
Bit
7
Meaning
6
5
4
Digits
3
2
Unit
1
0
Decimal Places
• Digits is a 3-bit field, which is offset by 2 to represent from 2 to 9 displayable digits.
• Unit is a 2-bit field, where the values from 0 to 2 represent units of Wh (100), k
(103) and M (106). The value 3 is undefined and is treated the same as 2, signifying M (106).
• Decimal Places is a 3-bit field, where the bits represent from 0 to 7 decimal places.
Example:
For the following, the Q1234 VAh has a current value internally of 123,456,789.0123
VAh.
Register CA00H
Digits
Unit
D.P
.
Hex
Binary
20xxH
001 00 000
3
VAh, 100
0
8BxxH
100 01 011
6
kVAh, 103
3
88xxH
100 01 000
6
kVAh, 103
93xxH
100 10 011
6
72xxH
011 10 010
C2xxH
110 00 010
Pattern
Reading in Register
1AFFH-1B00H
Display
Hex
Decimal
000003
789
789VAh
xxx.xxx kVAh
0006F855H
456789
456.789 kVAh
0
Xxxxxx kVAh
0001E240H
123456
123,456 kVAh
MVAh, 106
3
xxx.xxx MVAh
0001E240H
123456
123,456 MVAh
5
MVAh, 106
2
xxx.xx MVAh
00003039H
12345
123.45 MVAh
8
VAh, 100
2
xxxxxx.xx VAh
02B90135H
45678901
456,789.01 VAh
xxxVAh
The Scaled Energy Programmable Setting can be accessed by clicking: Device Profile
> Revenue & Energy Settings > Energy Scaling.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-32
3: Communication Data Formats
3.45: Type F67 - K-Factor
Length: 1 Register (2 bytes)
Range: +327.67 / - 327.68
Unit: 0.01
This register contains a 16-bit signed (2's complement) number. Positive values have
the most significant bit clear and have the same magnitude as an unsigned integer.
Negative values have the most significant bit set. The magnitude of a negative value
is found by complementing (inverting) all of the bits and adding 1.
Examples:
Register 00390, Maximum K-Factor Phase A Current, might contain the following
data:
Address
00390
Value (Hex)
08BBH
Most significant bit
0
Decimal
+2235
K-Factor
+22.35
Register 0185H, Maximum K-Factor Phase A Current, might contain the following
data:
Address
00390
Value (Hex)
F745H
Most significant bit
1
Complement
08BAH
Increment
08BBH
Decimal
-2235
K-Factor
-22.35
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-33
3: Communication Data Formats
3.46: Type F68 - Secondary 1 Cycle RMS Voltage and Current
Length: 2 Registers (4 bytes)
Range: 4,294,967,295 V, A / 0 V, A
Unit: 1/65536 V, A
These registers form a 4-byte unsigned integer in which the first register contains the
LSB word.
Example:
Address
0x005D
0x005E
Value
0xE6D7
0x0077
4-byte unsigned integer(Hex)
0x0077E6D7
4-byte unsigned integer (Decimal)
1/65536 V secondary
7,857,879
119.902
3.47: Type F69 - Angle
Length: 1 Register (2 Bytes) - signed integer
Order: Most significant byte first
Range: -327.68 / +327.67
Unit:
0.01 degree
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-34
3: Communication Data Formats
3.48: Type F70 - Harmonic Over Threshold Flag
Length: 4 Register (8 Bytes)
Order: Least significant word first (inside word, most significant bit first)
Range: N/A
Unit:
N/A
A bit value of 1 means harmonic over threshold event.
Word
Harmonic Order
Word 0
Word 1
Word 2
Word 3
Bit 0 = Order 0
Bit 0 = Order 16
Bit 0 = Order 32
Bit 1 = Order 1
Bit 1 = Order 17
Bit 1 = Order 33
Bit 2 = Order 2
Bit 2 = Order 18
Bit 2 = Order 34
Bit 3 = Order 3
Bit 3 = Order 19
Bit 3 = Order 35
Bit 0 = Order 48
Bit 4 = Order 4
Bit 4 = Order 20
Bit 4 = Order 36
Bit 1 = Order 49
Bit 5 = Order 5
Bit 5 = Order 21
Bit 5 = Order 37
Bit 2 = Order 50
Bit 6 = Order 6
Bit 6 = Order 22
Bit 6 = Order 38
Bit 3 = Order 51
Bit 7 = Order 7
Bit 7 = Order 23
Bit 7 = Order 39
Bit 4-15 = N/A
Bit 8 = Order 8
Bit 8 = Order 24
Bit 8 = Order 40
Bit 9 = Order 9
Bit 9 = Order 25
Bit 9 = Order 41
Bit 10 = Order 10
Bit 10 = Order 26
Bit 10 = Order 42
Bit 11 = Order 11
Bit 11 = Order 27
Bit 11 = Order 43
Bit 12 = Order 12
Bit 12 = Order 28
Bit 12 = Order 44
Bit 13 = Order 13
Bit 13 = Order 29
Bit 13 = Order 45
Bit 14 = Order 14
Bit 14 = Order 30
Bit 14 = Order 46
Bit 15 = Order 15
Bit 15 = Order 31
Bit 15 = Order 47
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-35
3: Communication Data Formats
3.49: Type F71 - Out of Range Status
Length: 1 Register (2 Byte)
Order: Most significant byte first
Range: N/A
Unit: N/A
Value
Description
0
Normal
1
Out
3.50: Type F72 - Time Stamp (Packed BCD)
Length: 4 Register (8 Byte)
Order: Least significant byte first
Range: 12/31/9999 23:59:59.99
Unit: 10 ms
Each register contains 2 bytes. Each byte contains 2 nibbles. Each nibble represents a
decimal digit from 0-9.
Byte
Nibble
0
15
1
14
13
Year
2
12
11
3
10
9
Month
4
8
Day
7
5
6
Hour
5
6
4 3
Minute
7
2
Seconds
1
0
Centiseconds
3.51: Type F73 - Magnitude
Length: 2 Register (4 Byte)
Order: Least significant word first
Range: -32768/+32767.9999
Unit: 1/65536 Volts/Degree/Hz
Word
0
1
Fraction
Integer
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-36
3: Communication Data Formats
3.52: Type F74 - Number 4 Bytes - Unsigned Integer
Length: 2 Register (4 Byte) - unsigned integer
Order: Least significant word first
Range: 0/+4294967295
Unit: 1
3.53: F75 - Flagging
Length: 1 Register (2 Byte)
Order: Most significant byte first
Range: N/A
Unit: N/A
Value
Description
0
Normal
1
Flagging
3.54: Type F76 - Valid Status
Length: 1 Register (2 Byte)
Order: Most significant byte first
Range: N/A
Unit: N/A
Value
Description
0x55AA
Valid
Others
Invalid
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-37
3: Communication Data Formats
3.55: Type F77 - Voltage Flag
Length: 1 Register (2 Byte)
Order: Most significant byte first
Range: N/A
Unit: N/A
• A bit value of 1 means one of the following situations occurred; a bit value of 0
means one of the following situations did not occur:
• Waveform Voltage RMS Sag event
• Waveform Voltage RMS Swell event
• Voltage Waveshape Pre-Trigger event
• Transient Positive Side Over-Range Pre-Trigger event
• Transient Negative Side Over-Range Pre-Trigger event
• Interruption event
• Waveform Voltage RMS Sag State Transition
• Waveform Voltage RMS Swell State Transition
• Interruption transition
• Waveform Voltage RMS Sag Valid
• Waveform Voltage RMS Swell Valid
• Voltage Waveshape Pre-Trigger Valid
• Transient Map waveform mask (transient trigger set will lead waveform/PQ trigger set)
• Sliding reference Usr sag/swell enable for voltage
Byte
Byte 1
Bits
15
Channels
14
13
N/A
12
Byte 0
11
10
9
8
7
6
5
4
3
2
1
0
Vne
Vce
Vbe
Vae
Vne
Vxn
Vca
Vbc
Vab
Vcn
Vbn
Van
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-38
3: Communication Data Formats
3.56: Type F78 - Current Flag
Length: 1 Register (2 Byte)
Order: Most significant byte first
Range: N/A
Unit: N/A
• A bit value of 1 means one of the following situations occurred; a bit value of 0
means one of the following situations did not occur:
• Waveform Current RMS Sag event
• Waveform Current RMS Swell event
• Waveform Current RMS Sag State Transition
• Waveform Current RMS Swell State Transition
• Current RMS Change of Rate Over-Range Valid
• Sliding reference Usr sag/swell enabled for current
Byte
Byte 1
Bits
15
14
13
12
Byte 0
11
10
Channels
9
8
7
6
5
N/A
4
3
2
1
0
Ix
Ic
Ib
Ia
3.57: Type F79 - General Readings (RMS, Ratio…)
Length: 2 Register (4 Byte)
Order: Least significant word first
Range: 0/+65535.9999
Unit: 1/65536 Volts/Amps
Word
0
1
Fraction
Integer
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-39
3: Communication Data Formats
3.58: Type F82 - Point Update Flag
Length: 1 Register (2 Byte)
Order: Most significant byte first
Range: N/A
Unit: N/A
A bit value of 1 means that an event occurred.
Byte
Byte 1
Bits
15
14
13
12
Byte 0
11
Reference
Channels
10
9
8
7
6
N/A
5
4
3
2
1
0
5th
4th
3rd
2nd
1st
3.59: Type F83 - Phase Sequence
Length: 1 Register (2 Byte)
Order: Most significant byte first
Range: N/A
Unit: N/A
Value
Description
0xABC0
ABC sequence
0xCBA1
ACB sequence
3.60: Type F90 - 16.7 usec Counter (Used for duration timestamping.)
Length: 2 Register (4 Byte) - unsigned integer
Order: Least significant word first
Range: + 4294967295/0
Unit: 16.7 usec
3.61: Type F97 - Hookup Configuration
Length: 1 Register (2 Byte)
Order: Most significant byte first
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-40
3: Communication Data Formats
Range: N/A
Unit: N/A
Value
Description
0
4-Wire Wye
1
3-Wire Delta 3 CT
2
3-Wire Delta 2 CT
3
4-Wire Wye 2.5 Element
4
4-Wire Delta Ground
3.62: Type F99 - Frequency Type
Length: 1 Register (2 Byte)
Order: Most significant byte first
Range: N/A
Unit: N/A
Value
Description
0
50 Hz
1
60 Hz
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-41
3: Communication Data Formats
3.63: Type F100 - Waveform Sample Rate
Length: 1 Register (2 Byte)
Order: Most significant byte first
Range: N/A
Unit: N/A
Value
Description
0
Full sample rate
2
1/2 of full sample rate
4
1/4 of full sample rate
…
…
64
1/64 of full sample rate
3.64: Type F101 - High Resolution RTC Timestamp
Length: 1 Register (2 Byte)
Order: Most significant byte first
Range: N/A
Unit: N/A
Bits
Description
0~14
1 count = 100us = 0.1ms, range up to 9999 = 0.9999second
15
1 means IRIG_B synchronized, 0 means IRIG_B lost
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-42
3: Communication Data Formats
3.65: Type F102 - Calibration Gain
Length: 2 Register (4 Byte)
Order: Least significant word first
Range: +16.999999996/0
Unit: N/A
The calibration gain number is a 32 bit number where 4 most significant bits are
unsigned integer and the others 28 bits are fractional of this number.
Example:
0x10539783 = 1.020408164
0x10000000 = 1.000000000
0x0FD7720F = 0.990099009
3.66: Type F103 - Alternate Format Power Factor
Length: 1 Register (2 Byte)
Order: Most significant byte first
Range: -1.0 / 1.0
Unit:
1/1000
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-43
3: Communication Data Formats
3.67: Type F105 - RTC Status
Length: 1 Register (2 Byte)
Order: Most significant byte first
Range: N/A
Unit: N/A
Bits
Description
0~1
Not defined
2
DST fall date
3
DST spring date
4
Active cold load
5
Active line sync
6
Active DST
7
Active GPS
8~15
Not defined
3.68: Type F106 - Line Synch Mode
Length: 1 Register (2 Byte)
Order: Most significant byte first
Range: N/A
Unit: N/A
Bits
0
Description
0=disable
1=enable
1
0=50Hz
1=60Hz
2~15
Not defined
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-44
3: Communication Data Formats
3.69: Type F107 - Daylight Savings Time Mode
Length: 1 Register (2 Byte)
Order: Most significant byte first
Range: N/A
Unit: N/A
Value
Description
0
Disable
1
Use onboard chip
2
User programmable:
16 bytes, Most significant byte first.
Settings #1
Byte 15-14: Reserved
Byte 13: Month
Byte 12: Date
Byte 11: Hour
Byte 10: Minute
Byte 9: Seconds
Byte 8: Reserved
Settings #2
Byte 7-6: Reserved
Byte 5: Month
Byte 4: Date
Byte 3: Hour
Byte 2: Minute
Byte 1: Seconds
Byte 0: Reserved
3
Use new standard (US, 2005)
4
Use Shark Format:
8 bytes, Most significant byte first.
Settings #1
Byte 7: Month
Byte 6: Week
Byte 5: Day
Byte 4: Hour
Settings #2
Byte 3: Month
Byte 2: Week
Byte 1: Day
Byte 0: Hour
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-45
3: Communication Data Formats
Value
5
Description
Use new user programmable:
10 bytes, Most significant byte first.
Settings #1
Byte 9: Month
Byte 8: Week
Byte 7: Day
Byte 6: Hour
Settings #2
Byte 5: Month
Byte 4: Week
Byte 3: Day
Byte 2: Hour
Settings #3
Byte 5: Shift hour for settings #1
Byte 4: Shift hour for settings #2
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-46
3: Communication Data Formats
3.70: Type F108 - Threshold Enable Channel
Length: 1 Register (2 Byte)
Order: Most significant byte first
Range: N/A
Unit: N/A
Value
Description
0
Enable Threshold for Phase A-N voltage channel
1
Enable Threshold for Phase B-N voltage channel
2
Enable Threshold for Phase C-N voltage channel
3
Enable Threshold for Phase A-B voltage channel
4
Enable Threshold for Phase B-C voltage channel
5
Enable Threshold for Phase C-A voltage channel
6
Enable Threshold for Phase X-N voltage channel
7~12
Not defined
13
Enable Threshold for Phase N-E voltage channel
14
Enable Threshold for Phase A current channel
15
Enable Threshold for Phase B current channel
16
Enable Threshold for Phase C current channel
17
Enable Threshold for Phase X current channel
18~255
Not defined
256
Cover all voltages
257
Cover all currents
258
Cover all voltages and currents
259~65535
Not defined
3.71: Type F112 - 16 Bits, General Purpose (Used for status information, including statuses of EN 50160 and TOU.)
Length: 2 Bytes
Order: N/A
Range: N/A
Unit: N/A
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-47
3: Communication Data Formats
3.72: Type F113 - 32 Bits, General Purpose (Used for status information, including status of EN 50160.)
Length: 4 Bytes
Order: N/A
Range: N/A
Unit: N/A
3.73: Type F115 - 4 Byte Counter
Length: 2 Register (4 Byte)
Order: Least significant word first
Range: +4294967295/0
Unit: 1
Word
0
1
LSW
MSW
Value = MSW * 65536 + LSW
3.74: Type F117 - Energy Counter
Length: 4 Register (8 Byte)
Order: Most significant byte first
Range: -65535.9999/+65535.9999
Unit: 1/4294967296 VAh, VARh, Wh, Qh, I2T, V2T secondary
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-48
3: Communication Data Formats
3.75: Type F118 - Power Factor
Length: 2 Register (4 Byte)
Order: Most significant byte first
Range: 0/+3.9999999
Unit: 1/16777216 PF
This register express power factor from 0 to 1 in the four quadrants, as follows:
Quadrant
Value
PF
Value
PF
Value
PF
4
0
0
0.5
0.5
0.9999999
0.9999999
1
1
1
1.5
0.5
1.9999999
0.0000001
2
2
0
2.5
0.5
2.9999999
0.9999999
3
3
1
3.5
0.5
3.9999999
0.0000001
3.76: Type F119 - Byte Array
Length: n bytes
Order: Array starts at high byte of starting Modbus register. Each Modbus register has
two bytes.
Range: 255 / 0, unsigned
Unit: 1
3.77: Type F120 - IEEE 32 bit Single Precision Floating Point
Length: 4 bytes
Order: Most significant byte first, bit 31 is in MSB.
Range: N/A
Unit: N/A
Bits, Sign: 1[31], Exponent: 8[30-23], Fraction: 23[22-0]
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-49
3: Communication Data Formats
3.78: Type F122 - Timestamp (packed S-Format)
Length: 6 bytes
Order: see table
Range: N/A
Unit: N/A
Stores a date from 2000 to 2099. Timestamp has a Minimum resolution of 1 second.
The high bits of each timestamp byte are used as flags to record meter state information at the time of the timestamp. These bits should be masked out, unless needed.
Byte
0
1
2
3
4
5
Value
Year
Month
Day
Hour
Minute
Second
Range
0-99 (+2000)
1-12
1-31
0-23
0-59
0-59
Mask
0x7F
0x0F
0x1F
0x1F
0x3F
0x3F
3.79: Type F123 - Time-of-Use (TOU) Calendar Entry
Length: 6 bytes
Order: see table
Range: N/A
Unit: N/A
Dates are specified using one of 5 possible formats per the type bits in each calendar
entry:
• type 0 = Fixed; exact date of the form month/day/year
• type 1 = Recurring; dates of the form month/day, applied every year.
Example: Independence Day is July 4th
• type 2 = Floating; dates of the form "nth occurrence in month M of D day of the
week," applied every year.
Example: Thanksgiving is 4th Thursday in November
• type 3 = Built-in; dates that cannot use the other formats, e.g. Easter and Good
Friday
• type 4 = Repeating; dates every N days from a reference date. Reference date is in
month/day/year format.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-50
3: Communication Data Formats
Example: Every 60 days beginning on Jan 1, 2013. Y=13, M=1, D=1, N=60; dates
are Jan 1, Mar 2, May 1, June 30, etc.
• types 5-7 are not used
Year, month, week, day and qualifier fields depend on the format. Not all fields are
used in each format.
• year = actual year minus 2000, range 2001 - 2063. 0 indicates every year.
• month = 0 to 12. 0 indicates every month. Set to 0 for built-in dates.
• week = specifies nth occurrence of a day of the week for floating format. Set to 0
for all other formats. See following TOU Calendar Note 4.
• day = 1-31 for fixed, recurring, and repeating, 1-7 (Sun - Sat) for floating, or 1-2
(1-Easter, 2-Good Friday) for built-in.
• Qualifier is an enumeration: 1-this day, 2-next day, 3-next also, 4 weekday, 5- Sat
to Fri (if the holiday falls on a Saturday, make Friday the holiday), 6-Sun to Mon (if
the holiday falls on a Sunday, make Monday the holiday).
• Action field does not depend on the type. Actions are specified by setting individual
bits and multiple bits may be set. See TOU Calendar Note 11, on the next page.
1st Register
47
46
Fixed
Type 0
Recurring
Type 1
Floating
Type 2
Built-in
Type 3
Repeating
Type 4
45
44
43
42
41
40
39
--
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
38
37
action11
Doc#
E171707
36
35
34
33
32
qualifier 1-6
3-51
3: Communication Data Formats
2nd Register
31
30
Fixed
29
28
27
26
25
year2 0-63
Recurring
24
23
22
21
20
19
18
17
month 1-12
day of month6 1-31
month3 0-12
day of month6, 7, 12 0-31
month3,13 0-12
day of week8, 13 1-7
--
name9 1-2
ref month5 1-12
ref day5 1-31
--
--
Floating
Built-in
Repeating
16
ref year2, 5 0-63
3rd Register
15
Fixed
Recurring
14
13
11
10
9
8
7
6
5
4
3
2
1
0
---
Floating
week4,13 0-5
Built-in
--
Repeating
12
--
repeats days 1-255
TOU Calendar Notes:
1 Unused fields (--) should be set to 0
2 Actual year = specified year + 2000
3 Month = 0 specifies every month
4 Week = 0 (every week), 1 - 4 (1st - 4th week), or 5 (last week)
5 Reference is the fixed date on which the first repeat period begins
6 Day of month is 1 through number of days in that month
7 If month = 0, day of month can be 1 through 28, only
8 Day of week is 1 (Sunday) through 7 (Saturday)
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-52
3: Communication Data Formats
9 Name is 1 (Easter) or 2 (Good Friday)
10 Qualifier enumeration:
• this day - use only the exact date specified
• next day - use the day following the date specified
• next day - use both the date specified and the next day
• weekday - combination of Sat to Fri and Sun to Mon
• Sat to Fri - if the date specified falls on Sat, use the day before (Fri), instead
• Sun to Mon - if the date specified falls on Sun, use the day after (Mon), instead
11 Action is bit-mapped (SMHHHHH) and supports multiple actions:
• S - season self read; change to next season
• M - month self read; change to next month
• HHHHH - make this day a holiday HHHHH (up to 31 holidays possible, numbered
1-31)
12 When customizing the season block for daily use, entry should be set to:
Action=Season; Type=Recurring; Qualifier=this day; Month=0; DOM=0
13 When customizing the season block for weekly use, entry should be set to:
Action=Season; Type=Floating; Qualifier=this day; Month=0; Week=0;
DOW=1- 7
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-53
3: Communication Data Formats
3.80: Type F124 - Time-of-Use (TOU) Rate Change
Length: 2 bytes
Order: see table
Range: N/A
Unit: N/A
Bits
hhhhhmmm mmm--ttt
Description
Each entry specifies the time of a tier change and which rate to adopt at that time.
- unused bit, always 0
hhhhh = hour, 0 to 23
mmmmmm = minute; must be aligned with demand intervals (or sub-intervals)
ttt - new rate number, 1 to 4.
Note: all unused entries must be at the end of the list and should be set to all
zeros.
3.81: Type F125 - Time-of-Use (TOU) Monitored Data Set Options
Length: 2 bytes
Order: see table
Range: N/A
Unit: N/A
Bits
Description
00000000 hgfedcba
a =1 to enable accumulator register monitoring
b = accumulator register sign (0-positive, 1-negative)
c = 1 to enable peak demand monitoring
de = demand register type (00-positive power, 10-negative power, 01-positive PF,
11-negative PF)
f = 1 to enable cumulative demand
g* = 1 to enable coincident demand association
h= coincident demand entity (1-VAR, 0-PF)
all unused bits are zeroes
* meaningful only if accumulator register is +/- Whr & d=1
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-54
3: Communication Data Formats
3.82: Type F126 - Time-of-Use (TOU) Monitor Time Timestamp
Length: 16 bytes
Order: see table
Range: N/A
Unit: N/A
Byte
0,1
2,3
4,5
6,7
8,9
10,11
12,13
14,15
Value
Year
Month
Day
DOW
Hour
Minute
Second
Flag Bits
Range
1-65535
1-12
1-31
1-7
0-23
0-59
0-59
-------- -----cba
Detail
0=Year2000,
1=Year 2001,
2= Year 2002,
etc.
1 =Jan.,
2 = Feb.,
3=March,
etc.
Day of
the
month
Day of
the
week:
1=Sun,
7=Sat
Hour of
the day:
0=12am,
23 =11pm
Number
of
minutes
Number
of
seconds
c=long
b=short
a=DST
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-55
3: Communication Data Formats
This page is intentionally left blank.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
3-56
4: Modbus Register Map Notes
4: Modbus Register Map Notes
The information in this chapter refers to the Modbus Register Map's "Notes" column.
Chapter 2 contains the Modbus Map.
1. Time information can be supplied from many different sources, an internal Real
Time Clock, or an external GPS Clock. The internal Real Time Clock has a backup
battery, which is used to maintain the passage of time when the Nexus® unit is
without operational power. It is similar to those used in PCs and it reports time
accurate to the second. The external GPS clock is supported through an IRIG-B
connection, allowing synchronization and accuracy to the hundredth of a second
(10 milliseconds). The internal RTC clock can be synchronized by an external SNTP
source or through a communication link consisting of Modbus or DNP3.
2. These registers, when read, always report the time as reported by the Nexus®
unit, either from the internal Real Time Clock or the external GPS Clock. Values
written here for the purpose of updating the internal Real Time Clock are not read
back.
3. These values are calculated by the Nexus® 1450 meter's DSP Processor, as part of
the Waveform Capture function.
4. To convert Phase voltages in secondary volts into primary volts, multiply by the
Phase voltage PT Ratio, composed of the Phase Voltage PT Ratio Numerator and
Denominator (Registers 45917 - 45918 and 45919 - 45920).
5. Auxiliary voltage is in secondary volts. To convert this value into primary volts,
multiply by the Auxiliary Voltage PT Ratio, composed of the Auxiliary Voltage PT
Ratio Numerator and Denominator (Registers 45921 - 45922 and 45923 - 45924).
6. Phase and Calculated Neutral Currents are in secondary amps. To convert this
value into primary amps, multiply by the Phase Current CT Ratio, composed of the
Phase Current CT Ratio Numerator and Denominator (Registers 45909 - 45910 and
45911 - 45912).
7. Not used.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
4-1
4: Modbus Register Map Notes
8. Measured Neutral is the true RMS measurement of current passing through the
meter. Calculated Neutral is the RMS produced by adding the three Phase Current
samples together and treating the result as a sample of the neutral line.
9. VA, VAR and Watts are in secondary. To convert this value into primary VA, VAR or
Watts, multiply by the Phase Voltage PT Ratio, composed of the Phase Voltage PT
Ratio Numerator and Denominator (Registers 45917 - 45918 and 45919 - 45919)
and by the Phase Current CT Ratio, composed of the Phase Current CT Ratio
Numerator and Denominator (Registers 45909- 45910 and 45911 - 45912).
10. Not used.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
4-2
5: Information for Downloading Logs
5: Information for Downloading Logs
5.1: Downloading Logs - Overview
• There are three methods for downloading logs from the Nexus®1450 meter: nonincrement index, auto-increment index and file system access.
• Each of the Nexus® meter's ports act independently, allowing multiple Modbus
masters access to all the retrievable data in a Nexus® meter slave.
• Log Memory Allocation (Quotas): Logs are made up of files that are each 1 MB in
size. The user is able to assign how many files each log will get; however, the
System Events log, and historical logs 1 and 2 have a maximum size of 1 and 8 MB,
respectively, in order to maintain backwards compatibility. A log with no file
assigned to it is disabled and will not run.
• Memory Gap Engine: To avoid the oldest record being overwritten during the download log process when the log is in pause mode, 5% of the memory allocated for
the log will be empty (unused) during the normal operation. When the download
process starts in a paused log, that reserved memory is used to save new records.
If the process is fast enough, the download process can finish without dropping any
records. On the other hand, if the download process is slow, the gap can be
completely filled and then new records will be dropped (not saved).
• Log Reset: This register (located at 57345), when written to, causes all logs to be
cleared. This action should be performed only under the following circumstances:
• When the programmable settings are modified such that data already in the logs
is invalidated; for example, any modifications involving the record size or organization of the contents of a snapshot, will require the logs to be cleared of any
previous data. When settings changes like this are made, the Communicator
EXTTM software displays a message telling you that the logs will be reset and
asking if you want to download them first.
• When the Run-Time code is upgraded, resulting in one of the following: a redefinition of the layout or meaning of the programmable settings or in altered
behavior or capabilities of the logs. In this case, the software will prompt you to
reset the logs by clicking on a button on the screen.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
5-1
5: Information for Downloading Logs
• Note that logs can also be reset via the Reset screen on the display, or the Reset
Device Parameters screen from Communicator EXTTM software. If Password
Protection has been enabled, a second level password is required for performing
the reset.
• Downloading any log involves the Log Snapshot header: Header blocks for the
different logs begin at register 36865. This block of registers holds the following
information about the log:
• Memory Size: 4-byte unsigned integers representing the amount of memory, in
bytes, allocated to the log.
• Record Size: an unsigned integer representing the size, in bytes, of a record in
the log.
• First Index: an unsigned integer representing the index of the first
(oldest) record in the log.
• Last Index: an unsigned integer representing the index of the last (newest)
record in the log. The value FFFFH indicates that the log is empty.
• First Time Stamp: These registers hold the time stamp from the first (oldest)
record in:
Byte
Range
Description
0
0 - 255
century
1
0 - 99
year
2
1 - 12
month
3
1 - 31
day
4
0 - 23
hour
5
0 - 59
minute
6
0 - 59
second
7
0 - 99
centisecond
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
5-2
5: Information for Downloading Logs
• Last Time Stamp: These registers hold the time stamp from the last (newest)
record in the Log. The byte order and description are the same as for the first
time stamp.
• Valid Bitmap: These registers hold the bit flags indicating whether the Nexus®
slave recognizes the lines in the Historical Log Settings block (the block beginning at register 45205). The first bit represents the validity of the last data
pointer in the historical log settings. A value of 1 means the data pointer is
acceptable and can be stored. A value of 0 means that the data pointer is invalid
or unrecognized and cannot be stored.
• Max Records: an unsigned integer representing the total number of records the
log is capable of holding. In order to maintain a one-for-one relationship in parallel logs (Sequence of Events State and Sequence of Events Snapshot logs, for
example), the maximum number of records that a log can store is defined by the
log that holds the fewest records. Logs capable of holding more records are
restricted.
• Reset Status: When the value of this register is “1,” the log is currently being
reset, i.e., the log files are being cleared.
5.1.1 Log Download Using Non-increment Index Method
NOTES:
• This method is offered for backward compatibility and can be applied only to the
System Events log and historical logs 1 and 2.
• In the following sections, the designation "first 128 bytes of the log" is a physical
description based on the absolute address of the memory allocated to the log. The
first (oldest) record in the log may not be located at the beginning of the log.
A Modbus master uses a log window consisting of 64 registers to retrieve logs from a
Nexus® 1450 meter slave. A log is divided into numbered sections called “indexes,”
which are transferred through the log window in sequence.
• Window index tells the Modbus master which 128-byte section of the log the
window is using to retrieve the log. The block of window index registers for the
different logs begin at 38145.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
5-3
5: Information for Downloading Logs
• When the Modbus master writes a new value to the window index, a new section
of the log will fill the window. For example, when the Index is 0000H, the first
128 bytes of the log are available in the window; when the Index is 0001H, the
second 128 bytes of the log are available in the window, and so on.
• When a value other than FFFFH is written to the window index, the index is
updated and the log is paused. A 30-second timer is initiated on the log write
action. If the timer expires (a new index is not written within 30 seconds), the
log will continue logging.
• Should multiple ports access the same log simultaneously, the log will
pause while any 30-second timer is running. The log will continue logging
only when all ports time out.
• When read, the window index returns the number of the index currently in use
by the window. When written to, the window index sets a new index for the
window to retrieve the log.
• Window mode defines the two available modes the window may use to retrieve a
log: Download mode and Time Stamp mode. The window mode block begins at
register 38209.
• Download Mode: In Download mode, the log window accesses consecutive, 128byte blocks of the log. For example, when the Window Index is 0000H, the first
128 bytes of the log are available in the Window; when the Index is 0001H, the
second 128 bytes of the log are available in the Window.
• Time Stamp Mode: In Time Stamp mode, the log window accesses the time
stamp of the records, in blocks of 16 time stamps at a time. When the window
index is 0000H, the time stamp of the first 16 records (records 0-15) in the log
are available in the window; when the window index is 0001H, the time stamp of
the second 16 records (records 16-31) in the log are available in the window,
and so on.
• Log Window: The log window is a 64-register, 128-byte view of a log. The window
index defines which part of a log is currently available in the window. Log windows
begin at register 38273.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
5-4
5: Information for Downloading Logs
5.1.1.1: Steps for Downloading a Log
The following steps outline the process for downloading a log. Details and examples
for downloading time stamps and records follow in Sections 5.1.1.2 and 5.1.1.3.
1. Read the Nexus® meter's Programmable Settings block (registers 45057-53248).
This information will be used to interpret the data retrieved from the log.
2. Pause the log by writing an initial, non-FFFFH value to the log window index
register.
3. Read and store the log header information.
4. Determine the starting window index and window offset. Within the meter’s physical memory, the log is divided into blocks of 128 bytes sequentially numbered.
Window index gives the number of a block, and window offset gives the position
inside that block.
5. Determine the largest window index and window offset.
6. Determine the ending window index and window offset.
7. Set the window mode to download mode.
8. Set the log window index to the starting window index.
9. Read the window from starting offset to the end of the window.
10. Increment the window index.
11. Read the window from beginning to end.
12. Repeat steps 10 and 11 until the largest or ending window index is reached.
• If the largest window index is reached, go to step 13.
• If the ending window index is reached, go to step 15.
13. Read window from beginning, up to (but not including) the largest offset.
14. Set window index to 0. Go to step 12.
15. Read window from the beginning, up to (but not including) the ending offset.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
5-5
5: Information for Downloading Logs
5.1.1.2: Downloading Time Stamps with Examples
The following steps detail the process for downloading time stamps from a log, using
values from Historical Log 1 as an example.
1. Read the Nexus® meter's programmable settings block (registers 45057-53248).
2. Pause the log by writing an initial, non-FFFFH value to the Historical Log 1 window
index register.
Example: Write 0000H to the window index for Historical Log 1, register 38145.
3. Read and store the Historical Log 1 header information.
Example: Historical Log 1 Snapshot header
Address
Description
Example Value
36865-36866
Historical Log 1 Snapshot Memory Size
1851392
36867
Historical Log 1 Snapshot Record Size
64
36868
Historical Log 1 Snapshot First Index
501
36869
Historical Log 1 Snapshot Last Index
500
36870-36873
Historical Log 1 Snapshot First Time Stamp
7/10/14
12:32:00.000
36874-36877
Historical Log 1 Snapshot Last Time Stamp
7/30/14
14:40:00.000
35878-36881
Historical Log 1 Snapshot Valid Bitmap
FFFC 0000
36882
Historical Log 1 Snapshot Max Records
28928
4. Determine the starting window index and starting window offset using these
formulas:
Starting Window Index = Int([8 x First Index]/128).
Starting Window Offset = (8 x First Index) % 128.
Example:
Starting Window Index: Int (8 x 501/128) = Int (31.3125) = 31.
Starting Window Offset: (8 x 501) % 128 = 40.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
5-6
5: Information for Downloading Logs
5. Determine the largest window index and the largest window offset using these
formulas:
Largest Window Index = Int ([8 x Max Records]/128).
Largest Window Offset = (8 x Max Records) % 128.
Example:
Largest Window Index = Int([8 x 28928]/128) = Int(1808) = 1808
Largest Window Offset = (8 x 28928) % 128 = 0
6. Determine the ending window Index and the ending window offset using these
formulas:
Ending Window Index = Int([8 x {Last Index + 1}]/128)
Ending Window Offset = (8 x [Last Index +1]) % 128
Example:
Ending Window Index = Int([8 x {500 + 1}]/128 = Int(31.3125) = 31
Ending Window Offset = (8 x [500 + 1]) % 128 = 40
7. Set the window mode to download mode by writing the Timestamp Mode code
(0001H) to the Log Window Mode register.
Example:
Write the value 0001H to the window mode for Historical Log 1, register 38209.
8. Set the window index to the starting window index.
Example:
Write the value 31 (001FH) to the Interval 1 log window index, register 38145.
9. Read window from starting offset to end of window:
Starting offset = First Register of Window + (starting Window offset/2).
Example:
38273 + (40/2) = 38293
Read from 38293 - 38336.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
5-7
5: Information for Downloading Logs
10. Increment the window index.
Example:
Write the value 32 (0020H) to the Historical Log 1 window index, register 38145.
11. Read the Window from beginning to end.
Example:
Read the Historical Log 1 window from register 38273 to 38336.
12. Repeat steps 10 and 11 until the largest or ending window index is reached.
• If the Largest Window Index is reached, go to step 13.
• If the Ending Window Index is reached, go to step 15.
Example:
If Window Index = 1808, go to step 13. If Window Index = 31, go to step 15.
13. Read Window from beginning, up to (but not including) the largest offset:
Largest Offset = First Register of Window + (largest Window offset/2).
Example:
(Index = 1808).
38273 + (0/2) = 38273.
Read from 38273 up to 38273; therefore, read nothing.
14. Set Window Index to 0. Go to step 12.
Example:
Write the value 0 (0000H) to the window index Historical Log 1, register 38145.
15. Read Window from the beginning, up to (but not including) the ending offset:
Ending Offset = First Register of Window + (Ending Window Offset/2).
Example: (Index = 31).
38273 +40/2 = 38293.
Read from 38273 up to (but not including) 38293; therefore, read 38273 - 38292.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
5-8
5: Information for Downloading Logs
5.1.1.3: Downloading Records with Examples
The following steps detail the process for downloading records from a log, using
values from an Historical Log 1 as an example.
1. Read the Nexus® meter's programmable settings block (registers 45057-53248).
2. Pause the log by writing an initial, non-FFFFH value to the log window index register.
Example: Write 0000H to the window index for Historical Log 1, register 38145.
3. Read and store the log header information.
Example: Historical Log 1 Log Snapshot Header
Description
Address
Example Value
36865-36866
Historical Log 1 Snapshot
Memory Size
1851392
36867
Historical Log 1 Snapshot
Record Size
64
36868
Historical Log 1 Snapshot
First Index
501
36869
Historical Log 1 Snapshot
Last Index
500
36870-36873
Historical Log 1 Snapshot
First Timestamp
7/10/99
12:32:00.000
36874-36877
Historical Log 1 Snapshot
Last Timestamp
7/30/99
14:40:00.000
36878-36881
Historical Log 1 Snapshot
Valid Bitmap
FFFC 0000
36882
Historical Log 1 Snapshot
Max Records
28928
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
5-9
5: Information for Downloading Logs
4. Determine the starting window index and starting window offset using these
formulas:
Starting Window Index = Int([Record Size x First Index]/128).
Starting Window Offset = (Record Size x First Index) % 128.
Example:
Starting Window Index: Int(64 x 501/128) = Int (250.5) = 250.
Starting Window offset: (64 x 501) % 128 = 64.
5. Determine the largest window index and the largest window offset using these
formulas:
Largest Window Index = Int([Record Size x Max Records]/128).
Largest Window Offset = (Record Size x Max Records) % 128.
Example:
Largest Window Index = Int([64 x 28928]/128) = Int(14464) = 14464.
Largest Window Offset = (64 x 28928) % 128 = 0.
6. Determine the ending window index and the ending window offset using these
formulas:
Ending Window Index = Int([Record Size x {Last Index + 1}]/128).
Ending Window Offset = (Record Size x [Last Index +1]) % 128.
Example:
Ending Window Index = Int([64 x {500 + 1}]/128 = Int(250.5) = 250.
Ending Window Offset = (64 x [500 + 1]) % 128 = 64.
7. Set the window mode to download mode by writing the Download Mode code
(0000H) to the log window mode register.
Example:
Write the value 0000H to the window mode for Historical Log 1, register 38209.
8. Set the window index to the starting window index.
Example:
Write the value 250 (00FAH) to the Historical Log 1 window index, register 38145.
9. Read window from starting offset to end of window:
Starting offset = First Register of Window + (starting Window offset/2).
Example:
38273 + (64/2) = 38305.
Read from 38305 - 38356.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
5-10
5: Information for Downloading Logs
10. Increment the window index.
Example:
Write the value 251 (00FBH) to the Historical Log 1 window index, register 38145.
11. Read the window from beginning to end.
Example:
Read the Historical Log 1 window from register 38273 to 38336.
12. Repeat steps 10 and 11 until the largest or ending window index is reached.
• If the largest window Index is reached, go to step 13.
• If the ending window Index is reached, go to step 15.
Example:
If Window Index = 14464, go to step 13.
If Window Index = 250, go to step 15.
13. Read window from beginning, up to (but not including) the largest offset.
Largest Offset = First Register of Window + (Largest Window Offset/2).
Example: (Index = 14464).
38273 + (0/2) = 38273.
Read from 38273 up to 38273; therefore, read nothing.
14. Set Window Index to 0. Go to step 12.
Example:
Write the value 0 (0000H) to the window index Historical Log 1, register 38145.
15. Read window from the beginning, up to (but not including) the ending offset.
Ending offset = First Register of Window + (ending Window offset/2).
Example: (Index = 250).
38273 + 64/2 = 38305.
Read from 38272 up to (but not including) 38304; therefore, read 38273 - 38304.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
5-11
5: Information for Downloading Logs
5.1.2: Log Download Using Auto-Increment Index Method
Note that this method is offered for backward compatibility and can only be applied to
the System Events log and Historical logs 1 and 2.
• Auto Incrementing Interface
• Auto Increment Configuration (register 39423, 0x099FE):
• When read, this register returns the configuration in use (shown on the next
page) by the auto increment log window to access logs on this port.
• When written, this register sets the configuration used by the auto increment log
window to access logs on this port. Each port accesses a separate, independent
configuration through this register, allowing all four ports to access logs with
different configurations.
• The least significant byte indicates which log is being accessed, as shown below:
0x000
Historical Log 1
0x001
Historical Log 2
0x00A
System Event Log
0x00E-0x0FF
Undefined
• The most significant byte defines the following modes, Paused Download mode
(0x000), and Running Download mode (0x001).
• In Paused Download mode (0x000), the log being accessed is paused new records are not added to the log while it is paused.
• In Running Download mode (0x001), the log being accessed is not
paused - new records may be added to the log. When downloading in this
mode, it is possible that records may be overwritten before, or even
during, access to that record.
• Auto Increment Window Index (0x099FF)
• When read, this register returns the index used by the auto increment log
window to access logs on this port.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
5-12
5: Information for Downloading Logs
• When written, this register sets the index used by the auto increment log window
to access logs on this port. Each port accesses a separate, independent index
through this register, allowing all four ports to access different areas of logs at
the same time.
• When read, the index is incremented before being returned in the Modbus
response. If the Auto Increment mode is Paused Download mode (0x001xx in
register 0x099FE), the appropriate log is paused, preventing the addition of new
records while the log is being accessed. A 30-second timer is initiated on these
reads. Should the timer run out (the index is not incremented/read in 30
seconds), the appropriate log will be allowed to continue logging.
• Should multiple ports access the same log simultaneously, the log will be paused
while the 30-second timer is running; the log will be allowed to continue
logging only when all ports time out.
• Auto Increment Log Window (0x09A3F)
• These registers are a 128-byte window into a log, as specified in the auto increment configuration (register 0x099FE). Depending on the auto increment
window index, a different 128-byte area of a log can be accessed.
5.1.2.1: Download using Auto Increment Window Sequence
1. Software should select the appropriate download mode and log through the auto
increment configuration register (0x000xx or 0x001xx to register 0x099FE).
2. Software should read the appropriate header information.
3. Software should initialize the window index by writing a value 1 less than the
desired starting index to the auto increment window index register.
Example: To start at window 0, write:
0x0FFFF to register 0x099FF.
4. Software should store the log header information.
5. Software should read the auto increment window index and auto increment log
window (registers 0x099FF-0x09A3F).
6. Software should verify the expected value for the auto increment window index.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
5-13
5: Information for Downloading Logs
7. Software should store the first 128 bytes of the log from the auto increment log
window.
8. Repeat steps 5-7 until the desired amount of the log has been read and stored. The
number of reads of the window can be determined by dividing the total memory in
the log by the window size.
5.1.2.2: Download Using Auto Increment Window Sequence and
Function Code 35
1. Software should select the appropriate download mode and log through the auto
increment configuration register (0x000xx or 0x001xx to register 0x099FE).
2. Software should read the appropriate header information.
3. Software should initialize the window index by writing a value 1 less then the
desired starting index to the auto increment window index register.
Example: To start at window 0, write:
0x0FFFF to register 0x099FF.
4. Software should store the log header information.
5. Software should read the auto increment window index and auto increment log
window (registers 0x099FF-0x09A3F) n times using the non-standard Modbus
Function Code 67 Read Holding Registers Multiple Times.
6. Software should verify the expected values for the auto increment window index.
7. Software should store each of the 128 byte segments of the log from the auto
increment log window.
8. Repeat steps 5-7 until the desired amount of the log has been read and stored.
The number of reads of the window can be determined by dividing the total
memory in the log by the window size, and again by dividing by the number of
repeats being used with Function Code 67.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
5-14
6: Meter Programmable Settings Block
6: Meter Programmable Settings Block
Chapter 2 contains the Nexus® 1450 meter's Modbus Register Map. This chapter
gives a detailed description of each of the Programmable Settings blocks.
6.1: Communication Settings Block (45057-45074)
• Device Address - 2 bytes, unsigned integer, ranging from 0000H to FFFFH
• Protocol - 1 byte, unsigned integer
• Baud Rate - 1 byte, unsigned integer
• Parity - 1 byte, unsigned integer
• Stop Bits - 1 byte, unsigned integer
• Data Bits - 1 byte, unsigned integer
• Response Delay - 1 byte, unsigned integer.
• Port Mode - 1 byte, unsigned integer; The value 1 means Master; value 0 means
Slave. Port 1 is always a Slave.
Communication Settings Block Specifications
Value
Protocol
Baud Rate
Parity
Stop Bits
Data Bits
Response
Delay (ms)
0
Modbus ASCII
4800
None
5
0.00
1
Modbus RTU
9600
Even
6
0.25
2
DNP 3.0
19200
Odd
7
0.50
3
38400
Mark
8
0.75
4
57600
Space
5
115200
1.00
1.25
6
1.50
7
1 stop
1.75
8
1.5 stop
2.00
9-14
2.25-3.50
15
2 stop
16-255
3.75
4.00-63.75
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-1
6: Meter Programmable Settings Block
6.2: Limit Settings Block (45077-45204)
• Limit Comparisons - Internal Representations
• A Nexus® meter has 32 Limits Objects.
• Each Limit Object performs two independent comparisons with a selected
computed value and combines them into a combined output. Information needed to
perform these actions: channel identification, comparison values, comparison
directions and combination type.
• Channel identification is performed by referencing the internal data table of the
meter, by specifying the Line Number and Point Number for a particular value. For
example: to monitor 1 second VAN values, use Line 34, Point 0; 1 second VBN, use
Line 34, Point 1; 1 second IA, use Line 36, Point 0; Thermal Average VAN, use Line
51, Point 0. To leave a Limit unassigned, use Line 65535, any point.
• Comparison values are entered using percentages relative to the programmed full
scales of the system. For VAN, the phase-to-neutral Voltage Full Scale would be
referenced. If it is programmed to 120.0 V secondary with a phase voltage PT of
120:1, then a comparison of 13.2 kV primary would be a limit of 108 V secondary
or 90.00% of the Full Scale. A 90.00% comparison for IA with a phase Current Full
Scale of 5.0 A secondary and a phase current CT of 2000:5 would be a comparison
of 4.5 A secondary or 1800 A primary. Negative percentages would be used where
appropriate (Watts, VAR, etc.). Special cases like PF and KF would depend on fixed
internal Full Scales. Human interfaces could represent this in terms of quadrature
and angle, instead of the internal percentage representation.
• Each comparison has a direction associated with it - Above or Below. A 90.00%
comparison could be for above 90.00% or below 90.00%.
• Finally, each limit object is able to produce a third output which is a combination of
the two comparisons. This combination could be an AND, OR, NAND, NOR, XOR or
Hysteresis. So, a user can produce a band of between 40.00% and 80.00% by
combining above 40.00% AND below 80.00%; over 110.00%/under 90.00%
alarms by combining above 110.00% OR below 90.00%, on after over 110.00%,
off after below 90.00% by combining above 110.00% and below 90.00% with
Hysteresis.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-2
6: Meter Programmable Settings Block
• The structure for a combination is:
2 byte
Line Number
1 byte
Point Number
1 byte
Direction and Combination (SAB)
2 byte
Comparison 1 Percentage (Value 1)
2 byte
Comparison 2 Percentage (Value 2)
Total of 8 bytes per Limit Object, total of 256 bytes for 32 Limit Objects.
• The structure for the Direction and Combination byte is:
Bits 7-5
Unused, set to 0
Bit 4
Negate combination (AND -> NAND, etc.)
Bits 3-2
00 = AND combination
01 = OR combination
10 = XOR combination
11 = Hysteresis combination
Bit 1
0 = Comparison 2 is below
1 = Comparison 2 is above
Bit 0
0 = Comparison 1 is below
1 = Comparison 1 is above
• Hysteresis combination uses comparison 1 to set the combination, and comparison
2 to clear the combination. If both inputs are asserted, comparison 1 has priority.
The usual arrangement would be to program comparison 1 to above a large value
and comparison 2 to below a small value. When the monitored value goes above
comparison 1, the combination will be set to a 1, until the monitored value goes
below comparison 2, when the combination will be cleared to a 0.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-3
6: Meter Programmable Settings Block
• Poll-able information would consist of:
32 bits
Comparison 1 states for 32 limits
32 bits
Comparison 2 states for 32 limits
32 bits
Combination states for 32 limits
Total of 96 bits (12 bytes)
6.3 Historical Log Settings Block (45205-45464)
• Historical Log 1 Data Pointers (45205 - 45332), Historical Log 2 Data Pointers
(45333 - 45460).
• These registers indicate which information to include in a record in the Historical
Log. Each Data Pointer has the following 4 (four) byte structure:
Data Pointer 4-Byte Structure
Size
Format
Description
2 byte
Unsigned integer
Line number
1 byte
Unsigned character
Point number
1 byte
unsigned character
Reserved
• A Line Number is an index into the Communication Table. Example: Line Number
11 is for the 12th line in the Communication Table, 0.1 second Phase-to-Neutral
Voltages. Data Pointers with Line Numbers greater than the number of lines in
the table are ignored.
• A Point Number is an index into a Line in the Communication Table. Example:
Point Number 1 is for the second entry in a Line. Line Number 11, Point Number
1 is the 2nd in the 12th line, 0.1 second VBN. Data Pointers with Point Numbers
greater than the number of points for the line are ignored.
• Snapshot Interval for Historical Log 1 (45361), for Historical Log 2 (45462).
• One register, 2 byte unsigned integers ranged from 0 to 3600.
• The unit is 1 second.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-4
6: Meter Programmable Settings Block
• Historical Log 1 Record Size (45463), Historical Log 2 Record Size (45464).
• This register is an enumeration for the size of a record in the Historical Log. The
valid values are:
0x00004 = 16 byte records
0x00000 = 32 byte records
0x00001 = 64 byte records
0x00002 = 128 byte records
0x00003 = 256 byte records
6.4: High Speed Inputs Settings Block (45501-45723)
• Input Name - 8 registers, 16 bytes, 16 characters for the name.
• Input Open Label - 8 registers, 16 bytes, 16 characters for label, Not Shorted, State
1.
• Input Closed Label - 8 registers, 16 bytes, 16 characters for label, Shorted, State 0.
• Input Value - 2 registers, currently not used.
• Input Mode - Bit 0 will define the normal condition of the input.
High Speed Input Settings
Bit 0
Normal Condition
Binary State
0
Open
State 1 (not shorted)
1
Closed
State 0 (shorted)
6.5: External Digital Output Module Settings Block (45729-45808)
• Up to 4 External Digital Output Modules can be addressed in this block.
• Address is 2 bytes, unsigned integers.
• A value of 0x0FFFF for an address indicates that this device is unused.
• Line Number is 2 bytes, unsigned integers.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-5
6: Meter Programmable Settings Block
• Point Number is 1 byte, unsigned integers.
• Line Number and Point Number will point which limit is going to be used for the
relay of the External Digital Output Module. See 6.5: External Digital Output Module Settings Block (45729-45808), on page 6-5.
• Up to 4 External Analog Output Modules can be addressed in this block.
• Address is 2 bytes, unsigned integers.
• A value of 0x0FFFF for an address indicates that this device is unused.
• Line Number is 2 bytes, unsigned integers.
• Point Number is 1 byte, unsigned integers.
• Line Number and Point Number will point which limit is going to be used for each
output of the External Analog Output Module.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-6
6: Meter Programmable Settings Block
6.7: External KYZ Output Module Settings Block (45893-45907)
• Up to 4 External KYZ Output Modules can be addressed in this block.
• Address - 2 bytes, unsigned integers.
• A value of 0x0FFFF for an address indicates that this device is unused.
• The energy assignments are as follows:
KYZ Output Relay Byte Energy Assignments
Value
Energy Assignment
0
Disabled
1
Q (1+4)Wh
2
Q1 VAh
3
Q1 VARh
4
Q4 VAh
5
Q4 VARh
6
Q (2+3)Wh
7
Q2 VAh
8
Q2 VARh
9
Q3 VAh
10
Q3 VARh
11-18
Internal Inputs Accumulations 1-8
19-22
Internal Input Aggregator 1-4
23-30
External Digital Input Module 1 in Accumulator 1-8
31-38
External Digital Input Module 2 in Accumulator 1-8
39-46
External Digital Input Module 3 in Accumulator 1-8
47-54
External Digital Input Module 4 in Accumulator 1-8
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-7
6: Meter Programmable Settings Block
6.8: CT & PT Ratio Settings Block (45909-45924)
• Address is 2 registers, 4 bytes, unsigned integers.
• Primary numbers and secondary numbers are in these blocks for the proper ratios.
6.9: Hookup and Time Settings Block (45925-45944)
• Hookup is 1 register, 2 bytes.
• High byte is Configuration Bits; Voltage selection.
• When bit 0 is cleared, 150V.
• When bit 0 is set, 300V.
• Low byte is Wye/Delta selection.
Wye/Delta Byte Energy Assignments
Value
•
Assignment
0
Wye
1
Delta, 3 CTs
2
Delta, 2 CTs
3
2.5 Element
4
4 Wire Delta
Frequency is currently not used.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-8
6: Meter Programmable Settings Block
• Time Zone is 1 register, 2 bytes, signed integer. The zone descriptor value varies
from -13 to +13. The zone descriptor value 0 represents Greenwich Mean Time.
Time Zone Descriptor
Value
Zone Descriptor
0
ZD0
50
ZD + 0.5
100
ZD + 1
150
ZD + 1.5
-100
ZD - 1
-150
ZD - 1.5
• Daylight Savings Time Enable is 1 byte, unsigned integer.
Daylight Savings Time Enable
Value
Zone Descriptor
0
Disabled
1
Use Clock chip
2
Use programming block
• Transformer Loss Compensation (TLC) Enable is1 byte, unsigned integer.
Transformer Loss Compensation (TLC) Enable
Value
Bits 0 & 1
Bit 2
0
Disabled
Add
1
Iron only
Subtract
2
Copper only
3 Both
• Internal KYZ Form is 1 byte bit map. Refer to the Internal KYZ Settings Block
(46330) for more detail.
• A bit value of 0 = Form C = Pulse of the relay.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-9
6: Meter Programmable Settings Block
• A bit value of 1 = Form A = Transition of the relay.
Internal KYZ Form Relay Assignments
Bit Number
7
6
5
4
3
2
Relay Assignments
1
2
3
4
LED
1
0
• Daylight Savings Time Start/End.
• Address - 4 registers, 8 bytes. Each byte has unsigned integer values (example
below).
Daylight Savings Time Start/End Byte Assignments
Register
45929
45930
45931
45932
Byte
High
Low
High
Low
High
Low
High
Low
Assignments
Reserved
Reserved
Month
Day
Hour
Minute
Second
Reserved
• % Loss of Watt or VAR
• Address - 2 registers, 4 bytes, 2 bytes for integers and 2 bytes for fractions.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-10
6: Meter Programmable Settings Block
6.10: Average Settings Block (45949-45952)
• Thermal and Block Averaging Time Interval is 1 register, 2 bytes unsigned integer.
The unit is in 1 second.
• Rolling Average Sub-Interval is 1 register, 2 bytes unsigned integer.
• Number of Sliding Windows is 1 byte, unsigned integer.
• Time of Use Log Enable is as follows:.
Value
0
1 - 255
Time of Use Enable
Description
disabled
enabled
6.11: Exception Profile Block (45953-45968)
This block is not yet defined.
6.12: Device Label Settings Block (45969-45992)
• Meter Designation is 8 registers, 16 bytes Hex ASCII.
• Auxiliary Voltage Label is 8 registers, 16 bytes Hex ASCII.
• Measured Neutral Current Label is 8 registers, 16 bytes Hex ASCII.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-11
6: Meter Programmable Settings Block
6.13: Network Card Settings Blocks (30153-30208, 51197-51198 Ports 5 and 6; 30209-30720 - Port 5; 45993-46016, 50785-51154,
52297-52300 - Port 6)
The Modbus registers for the ports 5 and 6 settings are distributed in different parts of
the Programmable Settings block and the Enhanced Programmable Settings block.
Since the settings themselves have the same characteristics irrespective of the card,
they are all explained in this section.
• IEC 61850 GOOSE Message Configuration is MSB first; Bits 31-16 reserved; Bits
15-00: when set, enables 16th - 1st position of the memory for received GOOSE
message for Boolean data type input to trigger waveform capture.
• Port Use is MSB first; Byte 7-4: reserved; Byte 3: GE EGD (Data Producer); Byte 2:
Modbus TCP Client; Byte 1: Alarm/Email; Byte 0: SNTP.
• IP Address is 2 registers, 4 bytes. Each byte has unsigned integer value.
• Subnet Mask is 2 registers, 4 bytes. Each byte has unsigned integer value.
• Default Gateway is 2 registers, 4 bytes. Each byte has unsigned integer value.
• Port 2 Baud Rate is 1 byte, unsigned integer.
Port 2 Baud Rate Values
Value
Baud Rate
0
4800
1
9600
2
19200
3
38400
4
57600
5
115200
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-12
6: Meter Programmable Settings Block
• Gateway Delay - 1 byte, unsigned integers.
Gateway Delay in Milliseconds
Value
Delay in ms
0
0
1
15
2-255
30-3825
• Mode 1 is Network Mode 1. 1 register, only High Byte is used.
• Bit 7 is IP Address Resolution.
• A bit value of 1 means use DHCP server.
• A bit value of 0 means use IP address of NEXUS/EEPROM.
• Bits 0-6 are Reserved.
• Computer Name is 8 registers, 16 bytes Hex ASCII.
• Server IP Address is 2 registers, 4 bytes. Each byte has unsigned integer values.
• Mode 2 is Network Mode 2; 1 byte.
• Bit 7 is IP Address Resolution
• A bit value of 0 means use IP address of NEXUS/EEPROM.
• Bits 0-6 are Reserved
• Computer Name
• DNS Server 1 IP Address is 2 registers, 4 bytes. Each byte has unsigned integer
values.
• DNS Server 2 IP Address is 2 registers, 4 bytes. Each byte has unsigned integer
values.
• Server / Service Enable Bits - 32 Bits - Reserved for future use.
• The next 4 bytes are undefined.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-13
6: Meter Programmable Settings Block
• Email Client Settings
15 14 13
12
11 10
Email Mode
9 8 7 6
5
4
3
2
1
0
Bit 15: Require Authorization
1=No, 0=Yes
• MSB first, send email on:
• Bits 31-10: undefined
• Bit 9: Transient capture
• Bits 8-6: reserved
• Bit 5: not used
• Bit 4: Relay output change
• Bit 3: PQ (CBEMA) event
• Bit 2: Waveform capture
• Bit 1: Digital input status change
• Bit 0: Limit status change
• DNP LAN/WAN
DNP LAN/WAN Bitmap
7
6
5
4
3
2
1
0
• Mode is a 1 byte unsigned integer.
• Bitmap Set is an 8-bit bitmap.
• Bit 7 is TCP Enable.
• A value of 0 means DNP over TCP listening point disabled.
• A value of 1 means DNP over TCP listening point enabled.
• Bit 6 is UDP Enable.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-14
6: Meter Programmable Settings Block
• A value of 0 means DNP over UDP end point disabled.
• A value of 1 means DNP over UDP end point enabled.
• Bit 5 is Validate Client Point.
• A value of 0 means no validation and any port is accepted.
• A value of 1 means validate connections against the first 1-4 entries.
• Bit 4 is UDP Response Behavior.
• A value of 0 means respond to Client port.
• A value of 1 means respond to programmed UDP respond port.
• Bit 3 to Bit 0 are reserved.
• UDP Addressing is an 1 byte unsigned integer.
• Validate Connection Count is an 1 byte unsigned integer.
• TCP Listen Port is a two byte unsigned integer - TCP listening port.
• UDP Listen Port is a two byte unsigned integer - UDP listening port.
• Multicast Group Address is reserved for future use.
• UDP Respond Port is a 2 byte unsigned integer.
• A value of 0 means respond to the Client port.
• A value of 1 means respond to the programmed UDP response port.
• SNTP: Sync source, MSB first;
• Byte 1: Sync source (0=IRIG-B, 1=SNTP, 2=Line sync, 3=PTP (IEEE 1588),
255=No sync.
• Byte 0: Mode (0=Unicast, 1=Broadcast - not implemented currently)
• Port defaults to 123 if equal to 0x000 or 0xFFFF
• Sync Rate in minutes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-15
6: Meter Programmable Settings Block
• Timeout in seconds
• Server 1 Name or IP address in ASCII
• Server 2 Name or IP address in ASCII
• Port Numbers
• Web server listen port number (valid numbers greater than 0 and less than
65536).
• GE EGD data port number (valid numbers greater than 0 and less than 65536).
6.14: Block Window Average External Synchronization Block (46017)
• BWA Synch Enable is 1 byte.
• Instead of using the time interval, the Nexus® meter can calculate the Thermal
and Block average when the pulse is detected on one of the High Speed Inputs.
Block Window Average Synchronization Assignments
Value
Assignments
0
Disabled
1-255
Enabled
• BWA Synch Mask is 1 byte. Only one input can be selected at a time. That means
only one of the 8 bits can be set at a time.
Block Window Average Synchronization Mask Input Assignments
Bit
0
1
2
3
4
5
6
7
Input Number
1
2
3
4
5
6
7
8
• Proper Value for each Assigned Input:
Proper Value for Block Window Average Synchronization Mask Assigned Inputs
Assigned Input
1
2
3
4
5
6
7
8
Proper Value
1
2
4
8
16
32
64
128
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-16
6: Meter Programmable Settings Block
6.15: Display Configuration Block (46018)
• Display Configuration Block is 1 register, 2 bytes.
• Bit 15: Only applies to the voltage reading.
• A bit value of 1 = Primary voltage displayed.
• A bit value of 0 = Secondary voltage displayed.
• Bit 0-14 is Reserved.
6.16: Energy Direction Block (46019)
• Received Energy Direction is 1 register, High byte only.
Energy Direction Block Values
Value
•
Description
0
(Q1+4)W = Received and (Q2+3)W = Delivered
1
(Q1+4)W = Delivered and (Q2+3)W = Received
Power Factor Labeling - 1 register, Low Byte only.
Power Factor Label Values
Value
Description
0
Method 1 = Q1+ lag, Q2- lag, Q3- lead, Q4+ lead
1
Method 2 =Q1+ lag, Q2- lead, Q3+ lag, Q4- lead
2-255
Method 3 =Q1+ lag, Q2- lag, Q3- lead, Q4+ lead
6.17: Reserved for Future Use (46020)
6.18: Full Scale Block (46021-46036)
• Full Scale Block is 2 registers, 4 bytes - 2 bytes integers and 2 bytes fraction
values.
6.19: External Module Software Interface Block (46053-46196)
• External Module Types is a 1 byte value, unsigned integer.
• External Module Slots is a 1 byte value, unsigned integer.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-17
6: Meter Programmable Settings Block
• External Module Label is 8 registers, 16 bytes; Hex ASCII.
External Module Types and Slots
Value
Type
Slot
0
Not assigned
1
1
KYZ
2
3
Analog Output 4-20 mA, 4 channel
4
4
Analog Output 4-20 mA, 8 channel
6
Analog Output 0-1 mA, 4 channel
6
Analog Output 0-1 mA, 8 channel
7
Digital Output
6.20: External Module Port Assignment Block (46197-46206)
• Port Assignment bytes are enumerated as in the following table:
External Module Port Assignments
Value
Assignment
0x000
Port 4
0x001
Port 3
0x002
Port 2
0x003
Port 1 (232/485)
0x004
Diagnostic Port (not
currently in use)
6.21: Manual Control Relay Block (46207-46208)
• Manual Control Relay Settings are 1 register, 2 bytes.
• Up to four Relay Output Modules can be attached to a Nexus® meter. A total of 16
relays can be controlled. The table below indicates which bit controls which relay.
Relay Control
Modules
Module 1
Module 2
Module 3
Module 4
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Relays
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-18
6: Meter Programmable Settings Block
• A bit value of 1 means Manual Relay Control Only.
• A bit value of 0 means ElectroLogicTM and Manual relay control.
6.22: Internal Input Pulse Accumulation Scale Factor Block
(46209-46325)
• Scale Factors Block is 2 registers, 4 bytes unsigned integers.
• Aggregator Assignments is 1 byte unsigned integers.
• Pulse Accumulation Labels is 8 registers, 16 bytes; Hex ASCII.
Internal Input Pulse Accumulator Assignments
Value
Energy
Assigned Aggregator
0
Q1 and Q4 Whr
None
1
Q2 and Q3 Whr
Add to Aggregator 1
Add to Aggregator 2
Add to Aggregator 3
Add to Aggregator 4
Subtract from Aggregator 1
Subtract from Aggregator 2
Subtract from Aggregator 3
Subtract from Aggregator 4
• Nexus® Meter Watt hour Selection is a 1 byte unsigned integer.
• Aggregation Assignment is a 1 byte unsigned integer.
6.23: I2t and V2t Threshold Block (46326-46329)
• I squared T is 2 registers, 4 bytes. 2-byte integers, 2-byte fractions; Secondary
Current Value.
• V squared T is 2 registers, 4 bytes. 2-byte integers, 2-byte fractions; Secondary
Volt Value.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-19
6: Meter Programmable Settings Block
6.24: Internal KYZ Settings Block (46330-46372)
• Internal KYZ Enable is 1 byte.
• A bit value of 1 = KYZ is enabled.
• A bit value of 0 = KYZ is disabled.
Internal KYZ Enable Assignment
Bit
Assignment
Bit 7
Test Pulse 1 LED
Bit 6
Test Pulse 2 LED
Bit 5
Pulse Output 1 LED/Relay 1
Bit 4
Pulse Output 2 LED/Relay 2
• Internal KYZ Pulse Width is a 1 byte, unsigned integer.
Internal KYZ Pulse Width
Value
0
1
2
3
4
5-127
Pulse width in ms
Disable
5
10
15
20
25-635
• Internal KYZ Channel Assignment is a 1 byte, unsigned integer.
Internal KYZ Channel Assignment
Value
Channel Assignment
0
+Qh Total,
1
-Qh Total,
2
Quad 1 Watthour,
3
Quad 2 Watthour,
4
Quad 3 Watthour,
5
Quad 4 Watthour,
6
Quad 1 VARhour,
7
Quad 2 VARhour,
8
Quad 3 VARhour,
9
Quad 4 VARhour,
10
Quad 1 VAhour,
11
Quad 2 VAhour,
12
Quad 3 VAhour,
13
Quad 4 VAhour,
14
N/A,
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-20
6: Meter Programmable Settings Block
15
N/A,
16
N/A,
17
N/A,
18
N/A,
19
N/A,
20
Uncompensated VAhour Quad1+4, Total,
21
Uncompensated Wattagehour Quad1+4, Total,
22
Uncompensated Wattagehour Quad2+3, Total,
23
Uncompensated VARhour Quad1+2, Total,
24
Uncompensated VARhour Quad3+4, Total,
25
N/A,
26
N/A,
27
N/A,
28
N/A,
29
N/A,
30
N/A,
31
N/A,
32
Quad (1+2+3+4) VAhour,
33
Quad (1 + 4) Watthour,
34
Quad (2 + 3) Watthour,
35
Quad (1 + 2) VARhour,
36
Quad (3 + 4) VARhour,
37
N/A,
38
N/A,
39
N/A,
40
Quad (1+2+3+4) Watthour,
41
Quad (1+2+3+4) VARhour,
42
N/A,
43
N/A,
44
N/A,
45
N/A,
46
N/A,
47
N/A
• Internal KYZ Watt Hour per pulse is 2 registers, 4 bytes, 2 byte integer, 2 byte
fraction.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-21
6: Meter Programmable Settings Block
• End of Interval Pulse - the meter can generate a pulse upon completion of a block
window interva1. This pulse is generated on one of the relays and the pulse width is
selectable.
End of Interval Pulse
Byte
Value
Enable
Width
(milliseconds)
Relay
0
Disable Pulse
Test Pulse 1 LED
5 ms
1
Enable Pulse
Test Pulse 2 LED
10 ms
2
Pulse Output 1 LED/Relay 1
15 ms
3
Pulse Output 2 LED/Relay 2
20 ms
4-126
(25-635)ms
6.25: Internal Input Pulse Accumulation Unit Label Block
(46373-46420)
• Internal Input Pulse Accumulation Unit Label is 4 registers, 8 bytes. These labels
are used to describe the units a pulse represents. Units are usually one word and
are 8 characters or less.
• Examples of Units: Gallons, BTUs, Liters, Wh, kWh, VAh, etc.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-22
6: Meter Programmable Settings Block
6.26: ElectroLogic Block (46421-46804)
• The relay logic settings are as follows:
Bits 2-4
Combo Logic
000
AND
001
OR
010
XOR
011
Hysteresis
100
NAND
101
NOR
110
NXOR
111
NHysteresis
6.27: Limit Profile Label Block (46805-47060)
• Limit Profile Label block is 8 registers, 16 bytes; 16 characters.
6.28: External Analog Output Module Channel Update Block
(47061-47062)
• This block is added to improve the update speed of what is sent to the External
Analog Output Modules from the meter. It may be that not all channels of the
External Analog Output Module are in use. The value indicates the number of External Analog Output Module channels that are refreshed per Modbus message. In the
older versions of External Analog Output Modules, only one channel update was
possible at a time.
External Analog Output Module Update Speed
Value
Update
0
1 channel at a time
1
2 channels at a time
2
4 channels at a time
3
4 channels at a time
4-255
8 channels at a time
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-23
6: Meter Programmable Settings Block
6.29: Miscellaneous DNP Settings Block (47063-47104)
• Scale for Analog Output of Average Pulse Accumulation is 1 byte unsigned integer.
• Pulse accumulation values are 8-byte. But the Analog Output Module can accept 4byte quantity. Therefore, only 4 bytes out of 8 bytes will be sent to the Analog Output Module. This register decides which 4 bytes will be sent out.
Values
Bytes to be Sent Out
0
Bytes 7,6,5,4
1
Bytes 6,5,4,3
2
Bytes 5,4,3,2
3
Bytes 4,3,2,1
4
Bytes 3,2,1,0
• Energy in the Interval is a 1 byte unsigned Integer. This is the Interval Time for
Energy in the Interval. The unit is in minutes; the range is from 60 to 0.
• DNP Time Synchronization Enable is 1 byte. The register address is 47064 (Lower
Byte).
• A value of 1 means that DNP Time Synchronization is enabled.
• A value of 0 means that DNP Time Synchronization is disabled.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-24
6: Meter Programmable Settings Block
• DNP Time Synchronization Time Interval is 1 register, 2 bytes. The register address
47065.
Value
Time (1 minute interval)
0
No time synchronization
1
1 minute
2
2 minutes
...
...
60
1 hour
61
1 hour, 1 minute
...
...
1439
23 hours, 59 minutes
1440
1 day
1441-65535
1 day (default)
• Bitmap
• Bit 13: Choice of Class 0 poll between Object 20 and Object 21.
Register
40766 (Bit 13)
Value
Description
1
Object 21
0
Object 20
• Bit 12: Enable DNP Freeze Schedule.
Register
40766 (Bit 12)
Value
Description
1
Enabled
0
Disabled
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-25
6: Meter Programmable Settings Block
• DNP Freeze Date & Time is 4 registers, 8 bytes.
Register
Byte
Name
Range
47067 - High
7
Century
0-99
47067 - Low
6
Year
0-99
47068 - High
5
Month
1-12
47068 - Low
4
Day
1-31
47069 - High
3
Hour
0-23
47069 - Low
2
Minute
0-59
476070 - High
1
Second
0-50
476070 - Low
0
Centisecond
0 (always 0)
• DNP Freeze Interval is 1 register, 2 bytes.
Register
Byte
Name
Range
47071-High
1
Hour
0-48
47071-Low
0
Minute
0-59
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-26
6: Meter Programmable Settings Block
6.30: Custom DNP Definition Block for Analog Input (Object 30)
(47105-47360)
• Line number is a 2-byte unsigned integer.
• Point number is a 1-byte unsigned integer.
• Line number and Point number will indicate the Analog Input value to be used for
one of the points in Object 30.
• Reserved: 1 byte is reserved for future use.
• DeadBand is a 2-byte signed number (Percentage).
• Range is -328%/+327.8% • Unit is 0.01%
• If the Current Analog Value is different from the Previous value by more than the
Deadband percentage, the meter will generate an Analog Change Event value if
it is assigned to any Class.
• Class assignments (Currently only bits 5,4 and 3 are used) are 8-bit bitmap.
• When bit 5 is set, the Analog Change Event value will not be generated.
• When bit 5 is clear, bit 4 and bit 3 will assign the Analog Change Event
value to a Class.
Class Assignments for Analog Change Event
Bit 5
Bit 4
Bit 3
Class
Assignment
0
0
0
No class
0
0
1
Class 1
0
1
0
Class 2
0
1
1
Class 3
1
X
X
No class
1
X
X
No class
1
X
X
No class
1
X
X
No class
• Reserved: 1 byte is reserved for future use.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-27
6: Meter Programmable Settings Block
6.31: Custom DNP Definition Block for Binary Counter (Object 20)
(47361-47424)
• Line number is a 2-byte unsigned integer.
• Point number is a 1-byte unsigned integer.
• Line number and Point number will indicate the Binary Counter value to be used
for one of the point in Object 20.
• Scaling is a 1-byte unsigned integer.
• Range is 0-15.
• The meter has an 8-byte Binary Counter Value, while DNP can only give a 4-byte
value. By using this scaling, the user can get the proper range of data. The scaling value represents the power of 10.
• Delta Values is 4-byte unsigned integer
• If the Current Binary Counter value is different from the Previous value more
than Delta values, the Counter Change Event value will be generated if it is
assigned to a Class.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-28
6: Meter Programmable Settings Block
• Class assignments (Currently bits 5,4,3,2,1 and 0 are used) is 8-bit bitmap.
• When bit 5 is set, the Counter Change Event value will not be generated.
• When bit 5 is clear, bit 4 and bit 3 will assign the Counter Change Event
value to a Class.
Class Assignments for Counter Change Event
Bit 5
Bit 4
Class
Assignment
Bit 3
0
0
0
No class
0
0
1
Class 1
0
1
0
Class 2
0
1
1
Class 3
1
X
X
No class
1
X
X
No class
1
X
X
No class
1
X
X
No class
• When bit 2 is set, the Frozen Counter Event value will not be generated.
• When bit 2 is clear, bit 1 and bit 0 will assign the Frozen Counter Event
value to a Class.
Class Assignments for Frozen Counter Event
Bit 2
•
Bit 2
Class
Assignment
Bit 0
0
0
0
No class
0
0
1
Class 1
0
1
0
Class 2
0
1
1
Class 3
1
X
X
No class
1
X
X
No class
1
X
X
No class
1
X
X
No class
Reserved: 7 bytes are reserved for future use.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-29
6: Meter Programmable Settings Block
6.32: Custom DNP Definition Block for Binary Input (Object 1)
(47425-47456)
• Line number is a 2-byte unsigned integer
• Point number is a 1-byte unsigned integer
• Line number and Point number indicate the Binary Input value used for 8 points
in Object 1.
• Class Assignments is 8-bit bitmap (1 byte).
• Bits 7, 6 and 5 will assign the Binary Input Change value to a Class.
• Bits 4 to bit 0 are not used.
Class Assignments for Binary Input Change
Bit 7
Bit 6
Bit 5
Class
Assignment
0
0
0
No class
0
0
1
Class 1
0
1
0
Class 2
0
1
1
Class 3
1
X
X
No class
1
X
X
No class
1
X
X
No class
1
X
X
No class
• Reserved: 4 bytes are reserved for future use.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-30
6: Meter Programmable Settings Block
6.33: Custom DNP Definition Block for Binary Output (Object 10)
(47457-47458)
• Enable / Disable Relays (1-16) (2 bytes):
• 0: Relay disabled
• 1: Relay enabled
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Relays
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
• Enable / Disable Resets (17-24) (1 byte):
• 0: Reset disabled
• 1: Reset enabled
Bits
Resets
15
Log Reset
14
Maximum Reset
13
Minimum Reset
12
Energy Reset
11
Reset TOU Current Season and Current Month
10
Reserved
9
Reset KYZ Output Accumulations
8
Restart
7-0
Reserved
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-31
6: Meter Programmable Settings Block
6.34: Custom DNP Definition Block for Global Values (47459-47463)
• When the master requests data from the object, it can specify the variation in the
request so the master can get the data formatted for its use. When the master asks
for Variation 0, the slave meter can respond with any variation(s). This programmable setting holds the variations available for a Variation 0 request.
Address
Object
Number
Object
Variations Available
for a Variation 0
Request
47459-High
Binary Input
1
1,2
47459-Low
Binary Input Change
2
1,2
47460-High
Binary Counter
20
1,2,5,6
47460-Low
Frozen Counter
21
1,2,5,6,9,10
47461-High
Counter Change Event
22
1,2,5,6
47461-Low
Frozen Counter Event
23
1,2,5,6
47462-High
Analog Input
30
1,2,3,4
47463-High
Analog Change Event
32
1,2,3,4
6.35: External Digital Output Module Labels Block (49793-50176)
• The External Digital Output Module Labels block is 8 registers, 16 bytes.
• Each relay, normally open, and normally closed can be named with 16 characters
• There are 4 of each label, for up to 4 modules.
6.36: Reserved for Future Use (50273-50784)
6.37: Reserved for Future Use (50785-50860)
6.38: Reserved for Future Use (51201-51712)
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-32
6: Meter Programmable Settings Block
6.39: Energy Scale Settings (51713-51746)
• This block contains the registers shown in the table, below.
Q1234 VAh
Q12 VARh
Q23 Wh
Q2 VAh (NA)
V2T Phase A
V2T Phase B
(NA)
Q34 VARh U
(NA)
Q4 VAh TM
(NA)
Pulse Acc 2
(NA)
Pulse Agg 2
(NA)
Q12 VARh U
(NA)
Q1 VARh TM
(NA)
Pulse Acc 1
Pulse Agg 1
Energy Scale Settings
Q14 Wh
Q1 Vah (NA) Q1 VARh (NA)Q4 VAh
Q4 VARh (NA)
(NA)
Q2 VARh (NA) Q3 VAh (NA) Q3 VARh
I2T Phase A I2T Phase B I2T Phase C
(NA)
(NA)
(NA)
Q1 Wh
Q4 Wh (NA) Q2 Wh (NA) Q3 Wh (NA)Q1234 VAh U
V2T Phase C
(NA)
(NA)
Q14 Wh U (NA)Q23 Wh U
+Qh
-Qh
Q14 Wh TM Q1 VAh TM
(NA)
(NA)
(NA)
Q4 VARh TM Q23 Wh TM Q2 VAh TM Q2 VARh TM Q3 VAh TM Q3 VARh TM
(NA)
(NA)
(NA)
(NA)
(NA)
(NA)
Pulse Acc 3
Pulse Acc 4 Pulse Acc 5 Pulse Acc 6 Pulse Acc 7 Pulse Acc 8
(NA)
(NA)
(NA)
(NA)
(NA)
(NA)
Pulse Agg 3
Pulse Agg 4 Sync
FVF
Op stat ot Op stat ot sel
(NA)
(NA)
en
Q34 VARh
• Each register contains 2 bytes. Each byte contains settings for a base quantity. The
format of a byte is as follows:
Bit
7
Meaning
6
5
Digits
4
3
Unit
2
1
0
Decimal Places
• Digits is a 3 bit field, which is offset by 2 to represent from 2 to 9 displayable digits.
• Unit is a 2-bit field, where the values from 0 to 2 represent units of Wh (100), k
(103) and M (106).
• The value 3 is undefined and is treated the same as 2, signifying M (106).
• Decimal Places is a 3-bit field, which represent from 0 to 7 decimal places.
• Examples: For the following, the Q1234 VAh has a current value of
123,456,789.0123 VAh.
Register CA00H
Hex
Binary
Digits
Unit
D.P.
Pattern
Reading
Hex
Decimal
Display
20xxH
001 00 000
3
VAh, 100
0
xxx VAh
00000315H
789
789 VAh
8BxxH
100 01 011
6
kVAh, 103
3
xxx.xxx
kVAh
0006F855H
456789
456.789
kVAh
88xxH
100 01 000
6
kVAh, 103
0
xxxxxx
kVAh
0001E240H
123456
123456
kVAh
93xxH
100 10 011
6
MVAh, 108
3
xxx.xxx
MVAh
0001E240H
123456
123.456
MVAh
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-33
6: Meter Programmable Settings Block
72xxH
011 10 010
5
MVAh, 108
2
xxx.xx
MVAh
00003039H
12345
123.45
MVAh
C2xxH
110 00 010
8
VAh, 100
2
xxxxxxxx
VAh
02B90135H
45678901
456,789.01
VAh
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-34
6: Meter Programmable Settings Block
6.40: Reserved for Future Use (51862-52245)
6.41: Accumulators/Aggregators Average Full Scale (52249-52296)
• 4 registers, 8 bytes integer number
• Range: 999999999999999/0
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-35
6: Meter Programmable Settings Block
6.42: Update Settings Block (52977-53248)
This block consists of the following registers:
• User Memo Field (256 bytes)- 128 registers, 256 bytes. User can write any notes
up to 255 characters in this memo field.
• Name of User Who Last Updated the Profile (256 bytes) - These registers are used
internally with the software. No interactions are required by the user.
• Device Profile Version (Year, Month/Day, Build) - These registers have the updated
date for Device Profile. These registers are used internally with the software. No
interactions are required by the user.
• Program Software ID - These registers have software ID. These registers are used
internally with the software. No interactions are required by the user.
• Electro Industries Device Type (Base Unit, Option 1/Option 2, Option 3/Option 4) These registers have information on what type of EIG meters that the software is
communicating to. These registers are used internally with the software. No interactions are required by the user.
• Update Programming Software Version Number (Major, Minor, Revision) - These
registers have software version number. These registers are used internally with
the software. No interactions are required by the user.
• Update Time - This register contains the time the profile was updated. No interactions are required by the user.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-36
6: Meter Programmable Settings Block
6.43: Reserved for Future Use (53249-53348)
6.44: Reserved for Future Use (55296-57344)
6.45: Waveform and PQ Settings
• RMS Set Points:
• The Set Points control at what RMS voltage or current above or below the Full
Scale value a waveform capture or PQ event occurs. The values are given in
percentage of Full Scale, where each count is equal to 0.01%. For example:
Voltage P-N Full Scale
120 V
Set Point Value
11070
Set Point Percentage
110.70%
RMS Set Point
132.84 V
• Each Set Point value is a 2 byte signed integer. The Below Set Point is used to
configure sag detection, and the Above Set Point is used to configure swell
detection. Below is the table of Set Points:
Set Point
Modbus
Address
Volts AN Below
0xB198
Volts BN Below
0xB199
Volts CN Below
0xB19A
Volts AB Below
0xB19B
Volts BC Below
0xB19C
Volts CA Below
0xB19D
Volts XN Below
0xB19E
Volts AN Above
0xB1A4
Volts BN Above
0xB1A5
Volts CN Above
0xB1A6
Volts AB Above
0xB1A7
Volts BC Above
0xB1A8
Volts CA Above
0xB1A9
Volts XN Above
0xB1AA
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-37
6: Meter Programmable Settings Block
Modbus
Address
Set Point
IA Below
0xB1B0
IB Below
0xB1B1
IC Below
0xB1B2
IN Below
0xB1B3
IA Above
0xB1B4
IB Above
0xB1B5
IC Above
0xB1B6
IN Above
0xB1B7
NOTE: Registers 0x7928 - 0x7929 must be set to zero for the Set Points to work.
• RMS Waveform Sag and Swell Limit Enables:
• Enables or disables waveform capture on the specified channel for sags and
swells. A value of 1 enables capture for sags and swells; a value of 0 disables
capture. Both sags and swells must be enabled together.
• Voltage Enables (register 0xB1B8):
Bit #
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
XE
CE
BE
AE
NE
XN
CA
BC
AB
CN
BN
AN
6
5
4
• Current Enables (register 0xB1BA):
Bit #
15
14
13
12
11
10
9
8
7
3
2
1
0
N
C
B
A
• Waveform Capture Count (register 0x7570-0x7571):
• Controls the number of records captured when a waveform event occurs. Since
the maximum size of a single waveform record is 180 cycles (approximately 3
seconds at a nominal 60 Hz), to perform a larger capture you need to capture
multiple records. The value is + 1, so a value of 0 results in 1 record, a value of
10 results in 11 records, and so on. The maximum number of captures is 65525.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-38
6: Meter Programmable Settings Block
• Waveform Capture Sample Rate (register 0x7574):
• Controls the number of samples per nominal 60 Hz cycle stored in the waveform
capture. Decreasing this can decrease the size of the record, allowing more
captures. Additionally, the maximum number of Cycles per Capture is affected
by the sample rate, as shown below:
Samples per 1/
60th of a second
Value
Maximum Cycles
per capture
0
16
180
1
32
180
2
64
180
3
128
180
4
256
120
5
512
60
6
1024
40
• Compression Factor (0x758C) must be set to match.
• Pre-Trigger Cycles (register 0x7575 - High Byte):
• The number of cycles to be included in the waveform capture from prior to the
triggering cycle. Must be between 1 and 179, and the sum of pre- and post-triggers must be <= the Max Cycles controlled by Sample Rate.
• Post-Trigger Cycles (register 0x7575 - Low Byte):
• The number of cycles to be included in the waveform capture after the triggering
cycle. Must be between 1 and the Max Cycles - Pre-Trigger.
• Internal Input Trigger Enables (register 0x7576):
• Enables or disables waveform and PQ capture on internal input triggers. A value
of 1 enables triggers on that input, a value of 0 disables triggers on that input.
Waveform Trigger Enable
1
2
3
4
5
6
7
Power Quality Trigger Enable
8
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
1
Doc#
2
3
4
E171707
5
6
7
8
6-39
6: Meter Programmable Settings Block
• Transient Set Points (register 0x7578 - 0x757A):
• The Transient Set Points control at what voltage magnitude a Transient capture
will be triggered. Note that Transients are triggered by the sample value, not the
cycle RMS. As such, the minimum allowed value for WYE hookup is 250%, and
for DELTA hookup is 144.2%. The values are given in percentage of Full Scale,
where each count is equal to 0.1%. For example:
Voltage P-N Full Scale
120v
Set Point Value
3100
Set Point Percentage
310.0%
Voltage Set Point
372v
• Each Set Point value is a 2 byte signed integer. Set Points are applied to both
Positive and Negative Triggers. Below is the table of Set Points:
Set Point
Modbus
Address
Volts A
0x7578
Volts B
0x7579
Volts C
0x757A
• Waveform Channel Selection Count (register 0x757C):
• The number of channels to be included in a waveform capture. This doesn't have
to be the same number of trigger channels.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-40
6: Meter Programmable Settings Block
• Waveform Channel Selection List (register 0x757D - 0x758B):
• The list of channels to be included in a waveform capture. Up to 15 channels may
be selected, though the first channel must always be Channel 80 (High Speed
Inputs). The list of channels do not have to be the same as the trigger channels.
Each channel is a 2 byte ID, shown below:
Channel
ID
Channel Name
High Speed Inputs
80
Volts AN
0
Volts BN
1
Volts CN
2
Volts AB
3
Volts BC
4
Volts CA
5
Volts XN
6
Volts NE
36
IA
37
IB
38
IC
39
IN
40
Volts Residual
7
I Residual
8
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-41
6: Meter Programmable Settings Block
• Waveform Compression Factor (register 0x758C):
• The Waveform Compression Factor must be set to match the Waveform Sample
Rate.
Compression
Factor Value
Samples per 1/
60th of a second
0
16
1
32
2
64
3
128
4
256
5
512
6
1024
• PQ Trigger Enables (register 0x758D - 0x758E):
• Enables or disables PQ Event triggering on individual channels. A value of 1
enables triggering, a value of 0 disables triggering.
• Voltage PQ Enables (register 0x758D):
15
Bit #
14
13
12
7
6
5
4
3
2
1
0
NE
XN
CA
BC
AB
CN
BN
AN
• Current PQ Enables (register 0x758D):
Bit #
15
14
13
12
11
10
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
9
Doc#
8
7
6
E171707
5
4
3
2
1
0
N
C
B
A
6-42
6: Meter Programmable Settings Block
• Return Hysteresis Set Points (register 0x7800 - 0x781F):
• The Return Hysteresis Set Point configures when a sag or swell event is considered to have returned to normal. For PQ Events, this triggers the return to normal event, signifying the end of a PQ Event.
• Hysteresis values are given as a percentage adjustment to the Set Point, where
each count is equal to 0.01% of Full Scale, offset towards nominal from the Set
Point. This Hysteresis value will always be closer to the full scale value then the
Set Point. Negative values are not allowed.
• For example, with swells:
Swell Set Point
110.0%
Swell Hysteresis
2.0%
Return Point
108.0%
• For example, with sags:
Sag Set Point
90.0%
Sag Hysteresis
2.0%
Return Point
92.0%
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-43
6: Meter Programmable Settings Block
• Each Set Point value is a 2 byte signed integer. A value of 0% disables Hysteresis.
Modbus
Address
Set Point
Volts AN Below
0x7800
Volts BN Below
0x7801
Volts CN Below
0x7802
Volts AB Below
0x7803
Volts BC Below
0x7804
Volts CA Below
0x7805
Volts XN Below
0x7806
Volts AN Above
0x780C
Volts BN Above
0x780D
Volts CN Above
0x780E
Volts AB Above
0x780F
Volts BC Above
0x7810
Volts CA Above
0x7811
Volts XN Above
0x7812
IA Below
0x7818
IB Below
0x7819
IC Below
0x781A
IN Below
0x781B
IA Above
0x781C
IB Above
0x781D
IC Above
0x781E
IN Above
0x781F
• USR Enables (register 0x7928 - 0x7929):
• Both registers must be set to zero for Waveform Set Points to operate.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
6-44
7: Register Block Titles
7: Register Block Titles
This chapter expands upon information listed in the Nexus® 1450 meter’s Modbus
Register Map (Chapter 2). “Register Block Titles” refers to a Register or Group of
Registers in the Register map that serve a particular purpose or function.
7.1: Device Identification Block (00001-00080)
Description: Registers included in this block: Device Name, Firmware Variation Strings
0-7, Comm Firmware Boot version number, Comm Firmware Runtime version number.
Note that the DSP Firmware information is located as follows:
• Run-Time Version Number is located in Modbus Holding registers FD03H-FD04H.
• ID is located in Modbus Holding registers FD05H-FD06H.
• Type is located in Modbus Holding register FD02H.
• State is located in Modbus Holding register FD40H. DSP is in Healthy state if the
value is 0.
• Variation String is located in Modbus Holding registers starting at EF80H, for 64
registers. It is a string type data with ASCII characters, 128 characters long. It
contains factory set firmware information for identification and informational
purposes.
All of the Device Identification and DSP Firmware data is in ASCII format. See Section
3.2: Type F1 - Null Terminated ASCII String on page 3-1 for information.
7.2: Real Time Block (00081-00089)
• Description: Registers included in this block: On Time, Current Time, Current Day
of the Week (see Section 3.3: Type F2 - Fixed Length ASCII String on page 3-2 and
Section 3.4: Type F3 - Time Stamp on page 3-2).
• On Time (00081-00084):
• These Registers keep the Time of the meter when it is turned on. The
format of the Registers follows the table below. Byte 0 indicates the high
byte of the Register 00081 and the byte 7 indicates the low byte of Register 00084. These Registers are Read Only.
Byte
0
Range
0-255
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description
Century
Doc#
E171707
7-1
7: Register Block Titles
Byte
Range
Description
1
0-99
Year
2
1-12
3
1-31
Day
4
0-23
Hour
5
0-59
Minute
6
0-59
Second
7
0-99
Centisecond
Month
• Current Time (00085-00088):
• These Registers keep the Current Time of the meter. These values are
kept by an internal battery even when the meter is off. The format of the
Registers follows the table on the previous page.
• Current Day of the Week (00089):
• This Register keeps the Current Day of the Week. The format follows the
table below.
Value
Day of
Week
0001H
Sunday
0002H
Monday
0003H
Tuesday
0004H
Wednesday
0005H
Thursday
0006H
Friday
0007H
Saturday
• Example of resetting the time on a meter:
• To set time as Wednesday, May 20, 2015, 3:45:00:00 P.M.: Century is 20
(14H); Year is 15 (0FH); Month is 05 (05H); Day is 20 (14H); Hour is 15
(0FH); Minute is 45 (2DH); Second is 00 (00H); Centisecond is 00 (00H);
Day of the Week is 0004H.
• The following data is sent to the Nexus® meter address 1. Registers
00085 through 00089 are written sequentially in one request. Register
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-2
7: Register Block Titles
00089, Current Day of the Week, must be included in the request. (Refer
to Chapter 1 for Function Code 1.)
0110005400050A140F05140F2D00000004B44A
01 - Meter Address
10 - Function Code
0054 - Starting Address
0005 - Number of Registers
0A - Number of Bytes
140F05140F2D00000004 - Actual data for Time and Date
B44A - Two-byte CRC Checksum
7.3: 1 Cycle Block (00090-00118)
• Description: 1 Cycle Registers included in this block: Block Time Stamp, Phase A-N,
B-N, C-N, Aux Voltage, Phase A, B, C Current, Measured Neutral Current, Calculated Neutral Current, Phase A-B, B-C, C-A Voltage, High Speed Input Delta and
Current State (see Section 3.3: Type F2 - Fixed Length ASCII String on page 3-2,
Section 3.5: Type F4 - Day of Week on page 3-3, Section 3.6: Type F6 - High Speed
Inputs, Delta and Current State on page 3-3).
• Type F68 Secondary 1 Cycle RMS Voltage and Current
• Length: 2 Register (4 bytes)
• Range: 4,294,967,295 V,A / 0 V,A
• Unit: 1/65536 V, A
• These registers together are a four-byte unsigned integer where the first register
contains the LSB word.
• Example:
Address: 0x005D – 0x005E
Value: 0xE6D7 – 0x0077
4-byte unsigned integer (Hex): 0x0077E6D7
4-byte integer (decimal):7,857,879
1/65536 V secondary: 119.902 V
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-3
7: Register Block Titles
7.4: High Speed Block (00119-00175)
• Description: High Speed Registers are updated with a user programmable rate of
between 2 cycles and 20 cycles; included in this block are: High Speed Block Time
Stamp, High Speed Phase A-N, B-N, C-N, High Speed Aux Voltage, High Speed
Phase A, B, C Current, High Speed Measured Neutral Current, High Speed Phase AB, B-C, C-A Voltage, High Speed Phase A, B, C VA, Three Phase VA, High Speed
Phase A, B, C VAR, Three Phase VAR, High Speed Phase A, B, C Watts, Three Phase
Watts, High Speed Frequency, High Speed Phase A, B, C Power Factor, Three Phase
Power Factor, High Speed Phase A-N Voltage to Aux Voltage Phase Angle (see Section 3.3: Type F2 - Fixed Length ASCII String on page 3-2, Section 3.7: Type F7Secondary Voltage, Current, VA, VAR, Watts, Hz or Flicker on page 3-4, Section
3.8: Type F8 - Power Factor on page 3-5, Section 3.9: Type F9 - Angle on page 36).
7.5: One Second Block (00176-00235)
• Description: One Second Registers included in this block: Block Time Stamp, Phase
A-N, B-N, C-N, Aux Voltage, Phase A, B, C Current, Measured Neutral Current, Calculated Neutral Current, Phase A-B, B-C, C-A Voltage, Phase A, B, C VA, VA, Phase
A, B, C VAR, Three Phase VAR, Phase A, B, C Watts, Three Phase Watts, Frequency,
Phase A, B, C Power Factor, Three Phase Power Factor, Voltage Imbalance, Current
Imbalance (see Section 3.3: Type F2 - Fixed Length ASCII String on page 3-2, Section 3.7: Type F7- Secondary Voltage, Current, VA, VAR, Watts, Hz or Flicker on
page 3-4, Section 3.8: Type F8 - Power Factor on page 3-5, Section 3.10: Type F10
- Percentage on page 3-7).
7.6: Thermal Average Block (00236-00295)
• Description: Thermal Average Registers included in this block: Block Time Stamp,
Phase A-N, B-N, C-N, Aux Voltage, Phase A, B, C Current, Measured Neutral Current, Calculated Neutral Current, Phase A-B, B-C, C-A Voltage, Phase A, B, C VA,
VA, Phase A, B, C VAR, VAR, Phase A, B, C Watts, Watts, Freq, Phase A, B, C PF, PF,
Voltage, Current Imbalance (see Section 3.3: Type F2 - Fixed Length ASCII String
on page 3-2, Section 3.7: Type F7- Secondary Voltage, Current, VA, VAR, Watts, Hz
or Flicker on page 3-4, Section 3.8: Type F8 - Power Factor on page 3-5, Section
3.10: Type F10 - Percentage on page 3-7).
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-4
7: Register Block Titles
7.7: Maximum Block (00296-00396)
• Description: Maximum (Thermal Average) Registers included in this block: Block
Time Stamp, Phase A-N, B-N, C-N, Aux Voltage, Phase A, B, C Current, Measured
Neutral Current, Calculated Neutral Current, Phase A-B, B-C, C-A Voltage, Phase A,
B, C VA, VA, Phase A, B, C Positive VAR, Positive VAR, Phase A, B, C Negative VAR,
Negative VAR, Phase A, B, C Positive Watts, Positive Watts, Phase A, B, C Negative
Watts, Negative Watts, Freq, Phase A, B, C PF Quadrants 1, 2, 3, 4, PF Quadrants
1, 2, 3, 4, Voltage Imbalance, Current Imbalance, THD Phase A-N /A-B, B-N /B-C,
C-N/C-A Voltage, THD Phase A, B, C Current, K-Factor Phase A, B, C Current, Coincident Thermal Average VAR for Max Pos Watt, Max Neg Watt (see Section 3.3:
Type F2 - Fixed Length ASCII String on page 3-2, Section 3.7: Type F7- Secondary
Voltage, Current, VA, VAR, Watts, Hz or Flicker on page 3-4, Section 3.8: Type F8 Power Factor on page 3-5, Section 3.10: Type F10 - Percentage on page 3-7).
7.8: Minimum Block (00397-00497)
• Description: Minimum (Thermal Average) Registers included in this block: All of the
Registers for Maximum Block but for Minimum Block (see Section 3.3: Type F2 Fixed Length ASCII String on page 3-2, Section 3.7: Type F7- Secondary Voltage,
Current, VA, VAR, Watts, Hz or Flicker on page 3-4, Section 3.8: Type F8 - Power
Factor on page 3-5, Section 3.10: Type F10 - Percentage on page 3-7).
7.9: Maximum Time Stamp Block (00498-00737)
• Description: Maximum (Thermal Average) Time Stamp Registers included in this
block: Phase A-N, B-N, C-N, Aux Voltage, Phase A, B, C Current, Measured Neutral
Current, Calculated Neutral Current, Phase A-B, B-C, C-A Voltage, Phase A, B, C
VA, VA, Phase A, B, C Positive VAR, Positive VAR, Phase A, B, C Negative VAR, Negative VAR, Phase A, B, C Positive Watts, Positive Watts, Phase A, B, C Negative
Watts, Negative Watts, Freq, Phase A, B, C PF Quadrants 1, 2, 3, 4, PF Quadrants
1, 2, 3, 4, Voltage Imbalance, Current Imbalance, THD Phase A-N/A-B, B-N/B-C, CN/C-A Voltage, THD Phase A, B, C Current, K-Factor Phase A, B, C Current (see
Section 3.3: Type F2 - Fixed Length ASCII String on page 3-2).
7.10: Minimum Time Stamp Block (00738-00977)
• Description: Minimum (Thermal Average) Time Stamp Registers included in this
block: All of the Registers for Maximum Time Stamp Block but for Minimum Block
(see Section 3.3: Type F2 - Fixed Length ASCII String on page 3-2).
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-5
7: Register Block Titles
7.11: Energy Block (Secondary) (00978-01021)
• Description: Energy Registers included in this block: Time Stamp, VAhour, Positive,
Negative VARhour, Positive, Negative Watthour (see Section 3.3: Type F2 - Fixed
Length ASCII String on page 3-2, Section 3.11: Type F11 - Energy Counter (Packed
BCD / Secondary) on page 3-8, Section 3.12: Type F12 - Energy Counter (Binary /
Secondary) on page 3-9).
7.12: Harmonic Magnitude Block (01022-01789)
• Description: Harmonic Magnitude Registers included in this block: Phase A-N/A-B,
B-N/B-C, C-N/C-A Voltage for 0th through 127th Harmonic Magnitude, Phase A, B,
C Current for 0th through 127th Harmonic Magnitude (see Section 3.10: Type F10 Percentage on page 3-7).
7.13: Harmonic Phase Block (01790-02557)
• Description: Harmonic Phase Registers included in this block: Phase A-N/A-B, B-N/
B-C, C-N/C-A Voltage for 0th through 127th Harmonic Phase, Phase A, B, C Current
for 0th through 127th Harmonic Phase (see Section 3.9: Type F9 - Angle on
page 3-6).
7.14: THD/K-Factor Block (02558-02566)
• Description: THD/K-Factor Registers included in this block: Phase A-N/A-B, B-N/BC, C-N/C-A Voltage THD, Phase A, B, C Current THD, Phase A, B, C Current K-Factor
(see Section 3.10: Type F10 - Percentage on page 3-7).
7.15: Harmonic Time Stamp Block (02567-02590)
• Description: Harmonic Time Stamp Registers included in this block: Phase A-N/A-B,
B-N/B-C, C-N/C-A Voltage, Phase A, B, C Current (see Section 3.4: Type F3 - Time
Stamp on page 3-2).
7.16: Phase Angle Block (02591-02604)
• Description: Phase Angle Registers included in this block: Time Stamp, Phase A-N,
B-N, C-N Voltage, Phase A, B, C Current, Phase A-B, B-C, C-A Voltage, Volt Phase
Seq. (see Section 3.3: Type F2 - Fixed Length ASCII String on page 3-2, Section
3.9: Type F9 - Angle on page 3-6, Section 3.13: Type F13 - Phase Sequence on
page 3-9).
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-6
7: Register Block Titles
7.17: Block Window Average Block (02605-02683)
• Description: Block Window Average Registers included in this block: Time Stamp,
Status, VA, VAR, Watt, Maximum VA, Positive VAR, Negative VAR, Positive Watt,
Negative Watt, Minimum VA, Positive VAR, Negative VAR, Positive Watt, Negative
Watt, Coincident VAR for Max Positive Watt, Neg Watt, Coincident VAR for Min Positive Watt, Neg Watt, VA Time Stamp, Time Stamp for Pos VAR, Neg VAR, Pos Watt,
Neg Watt, Minimum VA Time Stamp, Time Stamp for Minimum Pos VAR, Neg VAR,
Pos Watt, Neg Watt (see Section 3.3: Type F2 - Fixed Length ASCII String on
page 3-2, Section 3.7: Type F7- Secondary Voltage, Current, VA, VAR, Watts, Hz or
Flicker on page 3-4, Section 3.14: Type F14 - Block/Rolling Window Average Status
on page 3-9).
7.18: Rolling Window/Predictive Rolling Window Block
(02684-02768)
• Description: Rolling Window/Predictive Rolling Average Registers included in this
block: Time Stamp, Status, Predictive VA, VAR, Watt, VA, VAR, Watt, Maximum VA,
Positive VAR, Negative VAR, Positive Watt, Negative Watt, Min VA, Positive VAR,
Negative VAR, Positive Watt, Negative Watt, Coincident VAR for Max Positive Watt,
Neg Watt, Coincident VAR for Min Positive Watt, Neg Watt, VA Time Stamp, Time
Stamp for Pos VAR, Neg VAR, Pos Watt, Neg Watt, Min VA Time Stamp, Time Stamp
for Min Pos VAR, Neg VAR, Pos Watt, Neg Watt (see Section 3.3: Type F2 - Fixed
Length ASCII String on page 3-2, Section 3.7: Type F7- Secondary Voltage, Current, VA, VAR, Watts, Hz or Flicker on page 3-4, Section 3.14: Type F14 - Block/
Rolling Window Average Status on page 3-9).
7.19: Limit Block (02769-02773)
• Description: Limit Registers included in this block: Limit States, Value 1 Comparisons, 1-16, 17-32, Limits States, Value 2 Comparisons, 1-16, 17-32, Low Speed
Inputs (see Section 3.15: Type F15 - Limit States on page 3-11, Section 3.16: Type
F16 - Low Speed (Internal) Input States on page 3-12).
7.20: Reserved for Future Use (02774-02841)
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-7
7: Register Block Titles
7.21: Internal Input Pulse Accumulation Block (05745-05796)
• Description: Internal Input Pulse Accumulation Registers included in this block:
Time Stamp, Scaled Pulse Accumulations Internal Inputs 1-8, Scaled Pulse Accumulations 1-4 (see Section 3.3: Type F2 - Fixed Length ASCII String on page 3-2,
Section 3.40: Type F57 - Accumulation in the Interval on page 3-29).
7.22: Pulse Accumulation Block Window Average / Maximum Block
(05797-05945)
• Description: Pulse Accumulation Block Window Average / Maximum Registers
included in this block: Time Stamp, Status, Average Internal Inputs 1-8, Average
Aggregation 1-4, Maximum Average Internal Inputs 1-8, Maximum Average Aggregation 1-4, Maximum Internal Input Time Stamp 1-8, Maximum Average Aggregation Time Stamp 1-4 (see Section 3.3: Type F2 - Fixed Length ASCII String on
page 3-2, Section 3.14: Type F14 - Block/Rolling Window Average Status on
page 3-9, Section 3.40: Type F57 - Accumulation in the Interval on page 3-29).
7.23: Temperature (05946)
• Description: Nexus® meter’s Internal Temperature Register is in this block (see
Section 3.33: Type F47 - High Byte of Modbus Register (Unsigned) on page 3-27).
7.24: Analog Input Block (05947-05978)
• Description: This block contains registers for the optional Analog Inputs.
7.25: Limit Combination Block (05979-05980)
• Description: Limit Combination Registers included in this block: Limit States,
Combinations 1-16,17-32 (see Section Section 3.15: Type F15 - Limit States on
page 3-11).
7.26: Relay Logic Block (05981-06014)
• Description: Relay Logic Registers included in this block: Time Stamp, States,
Inputs 1-8, Relays 1-16, States, Gates A-G, Relays 1-16, Delay Timer, Relay 1/2 15/16, Relays 1-16 for Desired Relay States, Shadowed Relay States, Confirmed
Relay States, Valid Flags for Confirmed Relay States, Locked Relays, Locked Relay
States (see Section 3.20: Type F34 - Limit and Relay Logic States on page 3-16).
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-8
7: Register Block Titles
7.27: Reset Time Block (06015-06038)
• Description: Reset Time Registers included in this block: Time Stamp, Max Time
Stamp, Min Time Stamp, Energy Time Stamp, Current Season / Month TOU Time
Stamp (see Section 3.3: Type F2 - Fixed Length ASCII String on page 3-2).
7.28: Reserved for Future Use (06040-06076)
7.29: KYZ Output Accumulation Block (06097-06110)
• Description: KYZ Output Accumulation Registers included in this block: KYZ Output
Accumulation Block Time Stamp, KYZ Output Accumulation Relay 1/Pulse 1 LED,
KYZ Output Accumulation Relay 2/Pulse 2 LED, KYZ Output Accumulation Relay 3,
KYZ Output Accumulation Relay 4 (see Section 3.3: Type F2 - Fixed Length ASCII
String on page 3-2, Section 3.18: Type F18 - Digital Input Option Board Input
Accumulation / Cumulative Demand on page 3-14).
7.30: Input Option Board Data Status Block (06111-06112)
• Description: These registers contain statuses for the first and second optional Input
boards.
7.31: Flicker Status Block (06114-06126)
• Description: Flicker Status Registers included in this block: Flicker Status Block
Time Stamp, Flicker Start Time, Flicker End Time, Flicker Status (see Section 3.3:
Type F2 - Fixed Length ASCII String on page 3-2, Section 3.14: Type F14 - Block/
Rolling Window Average Status on page 3-9).
7.32: Instantaneous Flicker Block (06127-06136)
• Description: Instantaneous Flicker Registers included in this block: Instantaneous
Flicker Block Time, Instantaneous Flicker VAN, VBN, VCN (see Section 3.3: Type F2
- Fixed Length ASCII String on page 3-2, Section 3.7: Type F7- Secondary Voltage,
Current, VA, VAR, Watts, Hz or Flicker on page 3-4).
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-9
7: Register Block Titles
7.33: Short Term Flicker Block (06137-06186)
• Description: Short Term Flicker Registers included in this block: Short Term Flicker
Block Time, Short Term Flicker VAN, VBN, VCN, Maximum Short Term Flicker VAN,
VBN, VCN, Minimum Short Term Flicker VAN, VBN, VCN, Short Term Interval End
Time Stamp, Max Short Term Flicker VAN, VBN, VCN Time Stamps, Min Short Term
Flicker VAN, VBN, VCN Time Stamps (see Section 3.3: Type F2 - Fixed Length ASCII
String on page 3-2, Section 3.7: Type F7- Secondary Voltage, Current, VA, VAR,
Watts, Hz or Flicker on page 3-4).
7.34: Long Term Flicker Block (06187-06236)
• Description: Long Term Flicker Registers included in this block: Long Term Flicker
Block Time, Long Term Flicker VAN, VBN, VCN, Maximum Long Term Flicker VAN,
VBN, VCN, Minimum Long Term Flicker VAN, VBN, VCN, Long Term Interval End
Time Stamp, Maximum Long Term Flicker VAN, VBN, VCN Time Stamps, Minimum
Long Term Flicker VAN, VBN, VCN Time Stamps (see Section 3.3: Type F2 - Fixed
Length ASCII String on page 3-2, Section 3.7: Type F7- Secondary Voltage, Current, VA, VAR, Watts, Hz or Flicker on page 3-4).
7.35: Additional Energy Block (06237-06392)
• Description: Additional Energy Registers included in this block: Additional Energy
Block Time, Quadrants 1, 4, 2, 3 Watthour Secondary, Quadrant 1 VAhour, VARhour
Secondary, Quadrant 4 VAhour, VARhour Secondary, Quadrant 2 VAhour, VARhour
Secondary, Quadrant 3 VAhour, VARhour Secondary, Quadrants 1, 4, 2, 3 Watthour
Primary, Total VAhour Primary (Quadrants 1+2+3+4), Positive VARhour (Quadrants
1+2) Primary, Negative VARhour (Quadrants 3+4) Primary, Negative VARhour Primary, Quadrant 1, 4, 2, 3 Watthour Secondary, Quadrant 1 VAhour, VARhour
Secondary, Quadrant 4 VAhour, VARhour Secondary, Quadrant 2 VAhour, VARhour
Secondary, Quadrant 3 VAhour, VARhour Secondary, Quadrants 1, 4, 2, 3 Watthour
Primary, Total VAhour (Quadrants 1+2+3+4) Primary, Positive VARhour (Quadrants
1+2) Primary, Negative VARhour (Quadrants 3+4) Primary (see Section 3.3: Type
F2 - Fixed Length ASCII String on page 3-2, Section 3.11: Type F11 - Energy
Counter (Packed BCD / Secondary) on page 3-8, Section 3.12: Type F12 - Energy
Counter (Binary / Secondary) on page 3-9).
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-10
7: Register Block Titles
7.36: Energy and Pulses in the Interval Block (06393-006488)
• Description: Energy and Pulses in the Interval Registers included in this block:
Energy and Pulses in the Interval Block Time Stamp, Total VAhour (Quadrants
1+2+3+4) in the Interval Secondary, Positive VARhour (Quadrants 1+2) in the
Interval Secondary, Negative VARhour (Quadrants 3+4) in the Interval Secondary,
Positive Watthour (Quadrants 1+4) in the Interval Secondary, Negative Watthour
(Quadrants 2+3) in the Interval Secondary, Positive Watthour (Quadrants 1+4) in
the Interval Secondary, Negative Watthour (Quadrants 2+3) in the Interval
Secondary, Positive Watthour (Quadrants 1+4) in the Interval Primary, Quadrant 1
VAhour, VARhour in the Interval Primary, Quadrant 4 VAhour, VARhour in the Interval Primary, Negative Watthour (Quadrants 2+3) in the Interval Primary, Quadrant
2 VAhour, VARhour in the Interval Primary, Quadrant 3 VAhour, VARhour in the
Interval Primary, I2t Phase A, B, C in the Interval Primary, V2t Phases A, B, C in the
Interval Primary, Pulse Accumulation Internal Inputs 1-8 in the Interval Scaled,
Pulse Accumulation 1-4 in the Interval Scaled, Quadrants 1, 4, 2, 3 Watthour in the
Interval Secondary, Quadrant 1 VAhour, VARhour in the Interval Secondary, Quadrant 4 VAhour, VARhour in the Interval Secondary, Quadrant 2 VAhour, VARhour in
the Interval Secondary, Quadrant 3 VAhour, VARhour in the Interval Secondary,
Quadrants 1, 4, 2, 3 Watthour in the Interval Primary, Total VAhour (Quadrants
1+2+3+4) in the Interval Primary, Positive VARhour (Quadrants 1+2) in the Interval Primary, Negative VARhour (Quadrants 3+4) in the Interval Primary, KYZ Pulse
Output in the Interval Relays 1-4, Pulse 1 and 2 LEDs (see Section 3.3: Type F2 Fixed Length ASCII String on page 3-2, Section 3.18: Type F18 - Digital Input
Option Board Input Accumulation / Cumulative Demand on page 3-14, Section
3.37: Type F53 - Four-Byte (Unsigned) on page 3-27).
7.37: Flicker Countdown Block (06489-006490)
• Description: Flicker Countdown Registers included in this block: Short Term Flicker
Countdown, Long Term Flicker Countdown (see Section 3.36: Type F52 - Four-Byte
(Signed) on page 3-27).
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-11
7: Register Block Titles
7.38: Cumulative Demand Block (06491-006502)
• Description: Cumulative Demand Registers included in this block: Cumulative
Demand Block Time Stamp, Positive Watt (Quadrants 1+4) Cumulative Demand,
Negative Watt (Quadrants 2+3) Cumulative Demand, Positive Watt (Quadrants
1+4) Continuous Cumulative Demand, Negative Watt(Quadrants 2+3) Continuous
Cumulative Demand (see Section 3.3: Type F2 - Fixed Length ASCII String on
page 3-2, Section 3.18: Type F18 - Digital Input Option Board Input Accumulation /
Cumulative Demand on page 3-14).
7.39: Uncompensated and Q Block (06665-06907)
• Description: Uncompensated register readings are the readings to which Transformer Loss Compensation is not applied. Q Hour readings are 60 degree-shifted
hour readings from Watt hour readings. VAR hour readings are 90 degree-shifted
hour readings from Watt hour readings.
7.40: Scaled Energy Block (06908-07829)
• Description: Energy readings in Nexus® meters have Watt-hour, VAR-hour and VAhour as base units. In the real world, kilo, mega and giga-units are used more frequently. Therefore, Nexus® meters have scaled energy readings. This scale can be
modified using Communicator EXTTM software.
Length
2 Registers (4 bytes)
Range
99 / 0 through 999,999,999 / 0 (variable, 2-9 digits)
Unit
107 through 106 units (variable)
• This register contains a 4-byte MSB signed integer. The range and resolution of a
given reading is controlled by programmable Scaled Energy Settings, which govern
both the range of the reading (from 2 to 9 digits) and the units of the reading (from
7 decimal places of Wh (10-7) to no decimal places of MWh (106) (see Section
3.59: Type F83 - Phase Sequence on page 3-40 and Section 3.60: Type F90 - 16.7
usec Counter (Used for duration timestamp- ing.) on page 3-40).
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-12
7: Register Block Titles
7.41: Reserved for Future Use (07830-07859)
7.42: Negative Maximum Pulse Aggregation Average Block
(07864-07895)
• Description: Negative Maximum Average Aggregation 1-4 and Negative Maximum
Average Aggregation Time Stamp 1-4 registers are included in this block. Maximum
Average Aggregation 1-4 registers in Pulse Accumulation Block Window Average/
Maximum Block (05797-05945) will hold only positive values.
7.43: Reserved for Future Use (07896-07910)
7.44: New Demand Block (Either Block Window Average or
Sliding Window Average (07928-08039)
• Description: This block keeps Average Demand values including, watts, VAR, VA,
I2T, V2T, Uncompensated Energy, internal inputs and aggregators, and power
factor readings.
7.45: Scratchpad Block (08193 - 08320)
• Description: Scratchpad Registers 08193 - 08320 included in this block. The 128
registers in the Scratchpad Block are for temporary storage of information. At the
user’s discretion, data may be written to the registers and then read back.
• Example: Using one port, write energy readings from other devices. Those
energy readings can be read through another port.
7.46: Master Device Data Block (08449-08704)
• Description: These registers are used as a Scratch Pad between the Software and
the Network Card or Modem Card. These registers are not for polling by the users.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-13
7: Register Block Titles
7.47: EN 50160/IEC 61000-4-30 Power Quality Test (08705-11054)
• Description: These registers keep the EN 50160/IEC 61000-4-30 Power Quality
Report data, including Symmetrical Components, Harmonics and total harmonic
distortion (THD), short term and long term Flicker readings, total demand distortion (TDD), rapid voltage changes, supply voltage unbalance, Mains signaling values, dips and interruptions data, overvoltage, and supply voltage variation.
7.48: Frozen Energy Blocks (11265-11650)
• Description: These registers keep the Frozen blocks readings, including the time
stamp, Whr, VAhr, VARhr, I2T, V2T, Qhr, internal input pulse accumulations, KYZ
output accumulation readings, scaled energy readings, and scaled internal input
pulse accumulation readings.
7.49: Previous Block Window Average Block (11651-11742)
• Description: These registers keep the readings for the previous Block Demand
averaging, including VA, VAR, watts, and Q.
7.50: Previous Rolling Window Average Block (11743-11834)
• Description: These registers contain the readings for the previous Rolling Demand
averaging, including VA, VAR, watts, and Q.
7.51: Previous Scaled Energy Block (11835-11894)
• Description: These registers contain the previous readings for the scaled Energy
channels, including Whr, VAhr, VARhr, I2T, V2T, Qhr.
7.52: One Second Three Phase Mean RMS Block (11895-11900)
• Description: these registers keep the One Second Three Phase Mean RMS readings,
including Vpn, amp, and Vpp.
7.53: Block Window Max/Min and 10 Minute Mean THD Block
(11901-12138)
• Description: these registers keep the One Second Three Phase Mean RMS readings,
including Vpn, amp, and Vpp, THD, and Max and Min interval readings.
7.54: Coincident Power Factor (12141-12156)
• Description: these registers keep the coincident power factor readings.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-14
7: Register Block Titles
7.55: Customized Modbus Block (12289-14336)
• Description: All the readings in the Customizable Modbus Map Settings Block
(50273) can be read in this block. The format of the readings follows each individually assigned reading.
7.56: Nexus Master Polling Data Block (14337-14604)
• Description: The database polling information is kept in these registers.
7.57: Additional and Vpe Block (14849-14942)
• Description: This block contains registers that keep the high-speed readings, 1
second readings, Thermal average readings, and Vaux frequency.
7.58: Block Window, Max/Min Block, P-E
• Description: These registers keep Max and Min interval data for Phase to Earth
readings.
7.59: Enhanced Factory Settings Block (16385-24576)
• Description: These registers keep information on the meter’s hardware options,
serial numbers, and OEM information. Some of these registers are reserved for
future use.
7.60: Enhanced Programmable Settings Block (24577-32768)
• Description: These registers keep information on the meter’s Master RTU functionality, Digital Input option board rollover settings, Interval Log settings, Waveform
capture rules, Waveform transient readings, Waveform transient settings, Log configuration settings, Network card settings, Email client settings, FTP client settings,
GE EGD protocol settings, DNP LAN/WAN settings, SNTP settings, IEC 61000-4-30
settings (Hysteresis settings, Interruptions settings, nominal voltage, harmonic
magnitude thresholds, mains signaling thresholds, overvoltage thresholds, supply
voltage variation settings, and max/min interval settings). Some of these registers
are reserved for future use.
7.61: TOU Status Section Block (34817-34826)
• Description: These registers keep TOU profile status information, including number
of updates and current status of TOU function.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-15
7: Register Block Titles
7.62: TOU Profile Section Block (34833-36608)
• Description: These registers keep TOU profile settings, including TOU profile
version, length, date/time modified, TOU Demand type and interval, and details of
the profile settings.
7.63: Reserved for Future Use (36737-36800)
7.64: Historical Log 1 Snapshot Header (36865-36883)
• Description: Historical Log 1 Snapshot Registers included in this block:
• Memory Size: 4-byte unsigned integers representing the amount of memory, in
bytes, allocated to the log.
• Record Size: 2-byte integers representing the size, in bytes, of a record in the
log.
• First Index: 2-byte unsigned integers representing the index of the first (oldest)
record in the log.
• Last Index: 2-byte unsigned integers representing the index of the last (newest)
record in the log. The value 0x0FFFF indicates that the log is empty.
• First Time Stamp: these registers (8 bytes) hold the time stamp from the first
(oldest) record in the log.
Time Stamp Bytes
Byte
Range
Description
0
0-255
Century
1
0-99
Year
2
1-12
Month
3
1-31
Day
4
0-23
Hour
5
0-59
Minute
6
0-59
Second
7
0-99
Centisecond
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-16
7: Register Block Titles
• Last Time Stamp: these registers hold the Time Stamp from the last (newest)
record in the log. The byte order and description are the same as for the First
Time Stamp.
• Valid Bitmap: these registers hold the bit flags indicating whether the meter
recognizes the lines in the Historical Log Settings Block (the block at Register
45205). The first bit represents the validity of the Data Pointer in the Historical
Log Settings.
• A value of 1 means the Data Pointer is acceptable and can be stored. A
value of 0 means that the Data Pointer is invalid or unrecognized and not
able to be stored.
• Max Records: 2-byte unsigned integer representing the total number of records
the log is capable of holding. In order to maintain a one-for-one relationship in
parallel logs, the maximum number of records that a log can store is defined by
the log that holds the fewest records. Logs capable of holding more records are
restricted.
• Reset Status
7.65: Historical Log 2 Snapshot Header (36929-36947)
• Description: Historical Log 2 Snapshot Registers included in this block: The same as
for Log 1.
7.66: System Event Log Header (37505-37526)
• Memory Size: 4-byte unsigned integers representing the amount of memory, in
bytes, allocated to the log.
• Record Size: 2-byte unsigned integers representing the size, in bytes, of a record in
the log.
• First Index: 2-byte unsigned integers representing the Index of the First (Oldest)
record in the log.
• Last Index: 2-byte unsigned integers representing the Index of the Last (Newest)
record in the log.
• The value 0x0FFFF indicates that the log is empty.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-17
7: Register Block Titles
• First Time Stamp: These registers (8 bytes) hold the Time Stamp from the First
(Oldest) record in the log.
Time Stamp Bytes
Byte
Range
Description
0
0-255
Century
1
0-99
Year
2
1-12
Month
3
1-31
Day
4
0-23
Hour
5
0-59
Minute
6
0-59
Second
7
0-99
Centisecond
• Last Time Stamp: These registers hold the Time Stamp from the Last (Newest)
Record in the log. The byte order and description are the same as for the First
Time Stamp.
• Valid Bitmap: Undefined.
• Max Records: A 2-byte unsigned integer represents the total number of records
the log is capable of holding. In order to maintain a one-for-one relationship in
parallel logs, the maximum number of records that a log can hold is defined by
the log that holds the fewest records. Logs capable of holding more records are
restricted.
• Records in Log
• Reset Status
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-18
7: Register Block Titles
7.67: External Device Information Block Header (37761-37778)
• Description: External Device Information Registers included in this block:
• Memory Size: 4-byte unsigned integer representing the amount of memory, in
bytes, allocated to External Device Information Blocks. This memory is allocated
from RAM, not NVRAM.
• Record Size: unsigned integer representing the size, in bytes, of an External
Device Info Block.
• First Index: An unsigned integer representing the Index of the First External
Device Info Block.
• Last Index: An unsigned integer representing the Index of the Last External
Device Info Block.
• First Time Stamp: Since External Device Info Blocks are not recorded sequentially, these registers have no meaning.
• Last Time Stamp: Since External Device Info Blocks are not recorded sequentially, these registers have no meaning.
• Valid Bitmap: These registers hold the bit flags to indicate the validity of individual External Device Info Blocks. The first bit (high order bit in Register 37774)
represents the validity of the First External Device Info Block. The last bit (lowest order bit in Register 37777) represents the validity of the Last External
Device Info Block.
• A value of 1 means that the External Device was found and the meter
successfully received all of the Info Block for the External Device. A value
of 0 means that the External Device was not found, or errors have
occurred while trying to retrieve the Info Block or that no device is programmed for this slot.
• Max Records: This register holds an unsigned integer representing the total number of records the log can hold.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-19
7: Register Block Titles
7.68: External Device Programming Block Header (37825-37842)
• Description: External Device Programming Registers included in this block:
• Memory Size: These registers are a 4-byte unsigned integer representing the
amount of memory, in bytes, allocated to External Device Programming Blocks.
This memory is allocated from RAM, not NVRAM.
• Record Size: This register is an unsigned integer representing the size, in bytes,
of an External Device Programming Block.
• First Index: An unsigned integer representing the Index of the First External
Device Programming Block.
• Last Index: An unsigned integer representing the Index of the Last External
Device Programming Block.
• First Time Stamp: Since External Device Programming Blocks are not recorded
sequentially, these registers have no meaning.
• Last Time Stamp: Since External Device Programming Blocks are not recorded
sequentially, these registers have no meaning.
• Valid Bitmap: These registers hold the bit flags to indicate the validity of individual External Device Programming Blocks. The first bit (high order bit in Register
37838) represents the validity of the First External Device Programming Block.
The last bit (lowest order bit in Register 37841) represents the validity of the
Last External Device Programming Block.
• A value of 1 means that the External Device was found and the meter
successfully received all of the Programming Block for the External
Device. A value of 0 means that the External Device was not found, or
errors have occurred while trying to retrieve the Programming Block or
that no device is programmed for this slot.
• Max Records: This Register holds an unsigned integer representing the total
number of records the log is capable of holding.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-20
7: Register Block Titles
7.69: Device History Block Header (37889-37906)
• Description: This Register holds an unsigned integer representing the total number
of records the log is capable of holding.
7.70: Direct Memory Access Header (37953-37970)
• Description: Direct Memory Access currently not used.
7.71: Window Index Block (38145-38162)
• Description: Window Index Registers included in this block:
• Historical Log 1 (38145):
•When read, this register returns the Window Index for Historical Log 1 to
access Historical Log 1 on this port. When written, this register sets the
Index used by the Historical Log 1 Window to access Historical Log 1 on
this port. Each port accesses a separate, independent index through this
register, allowing all four ports to access different areas of Historical Log 1
at the same time.
• When a value other than 0x0FFFF is written to this register, the index is
updated.
• If the Window Mode for this log indicates a Paused Mode (0x00000 or
0x00001 in Register 38209), Historical Log 1 is paused, preventing the
addition of new records while the log is being accessed. A 30-second
timer is initiated on these writes. Should the timer run out (a new index is
not written within 30 seconds), Historical Log 1 will be allowed to continue logging.
• When a value of 0x0FFFF is written to this register, it signifies that the
port is finished accessing Historical Log 1, the 30-second timer is
canceled and Historical Log 1 will be allowed to continue logging.
• Should multiple ports access the same log simultaneously, the log will be
paused while either 30-second timer is running. The log will be allowed to
continue logging only when both ports time-out or write 0x0FFFF to their
Index Register.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-21
7: Register Block Titles
• Historical Log 2 (38146): When read, this register returns the Window Index for
Historical Log 2 to access Historical Log 2 on this port. Functionality follows the
Historical Log 1 Window Index (38145).
• System Log (38155): when read, this register returns the window index for the
System log, to access the System log on this port. Functionality follows the Historical log1 window index (38145).
• Device History Block (38160) - Currently not used.
• Direct Memory Access (38161) - Currently not used.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-22
7: Register Block Titles
7.72: Window Mode Block (38209-38226)
• Description: Window Mode Registers included in this block:
• Historical Log 1 (38209): When read, this register returns the Mode used by the
Historical Log 1 Window to access Historical Log 1 on this port. When written,
this register sets the Mode used by the Historical Log 1 Window to access Historical Log 1 on this port. Each port accesses a separate, independent Mode
through this Register, allowing all four ports to access Historical Log 1 in different modes.
• Currently, the Mode Register defines the following Modes: Paused Download
Mode (0x00000), Paused Time Stamp Mode (0x00001), Running Download
Mode (0x00002) and Running Time Stamp Mode (0x00003).
• In Download Modes (0x00000 and 0x00002), the Historical Log 1 Window
accesses consecutive 128-byte blocks of the Historical Log 1. When the
Index = 0x00000, the first 128 bytes of the log are readable in the window; when the Index = 0x00001, the second 128 bytes of the log are
readable in the window, and so on. The designation “first 128 bytes of the
log” is a physical description based on the absolute addresses of the
memory allocated to the log. The first (oldest) record in the log may not
be located at the beginning of the log.
• In Time Stamp Modes (0x00001 and 0x00003), the Historical Log 1 Window accesses the Time Stamps of the records in the Historical Log 1 in
blocks of 16 Time Stamps at a time. When the Index = 0x00000, the
Time Stamps of the first 16 records (records 0-15) in the log are readable
in the window; when the Index = 0x00001, the Time Stamps of the second 16 records (records 16-31) in the log are readable in the window, and
so on. The designation “first 16 records of the log” is a physical description based on the absolute addresses of the memory allocated to the log.
The first (oldest) record in the log may not be located at the beginning of
the log.
• In Paused Modes (0x00000 and 0x00001), the log being accessed is
paused and new records are not added to the log while it is paused.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-23
7: Register Block Titles
• In Running Modes (0x00002 and 0x00003), the log being accessed is not
paused and new records may be added to the log. When downloading in
these modes, it is possible the records may be overwritten before or
during the downloading of records.
• Historical Log 2 (38210): When read, this register returns the Mode in use by the
Historical Log 2 Window to access Historical Log 2 on this port. Functionality follows the Historical Log 1 Window Mode (38209).
• Limit Trigger Log (38211): When read, this register returns the Mode in use by
the Limit Trigger Log Window to access Limit Trigger Log on this port. Functionality follows the Historical Log 1 Window Mode (38209).
• Limit Snapshot Log (38212): When read, this register returns the Mode in use by
the Limit Snapshot Log Window to access Limit Snapshot Log on this port. Functionality follows the Historical Log 1 Window Mode (38209).
• Digital Input Log (38213): When read, this register returns the Mode in use by
the Digital Input Log Window to access Digital Input Log on this port. Functionality follows the Historical Log 1 Window Mode (38209).
• Digital Input Snapshot Log (38214): When read, this register returns the Mode in
use by the Digital Input Snapshot Log Window to access Digital Input Snapshot
Log on this port.Functionality follows the Historical Log 1 Window Mode (38209).
• Digital Output Log (38215): When read, this register returns the Mode in use by
the Digital Output Log Window to access Digital Output Log on this port. Functionality follows the Historical Log 1 Window Mode (38209).
• Digital Output Snapshot Log (38216): When read, this register returns the Mode
used by the Digital Output Snapshot Log Window to access Digital Output Snapshot Log on this port. Functionality follows Historical Log 1 Window Mode
(38209).
• Flicker Log (38217): When read, this register returns the Mode in use by the
Flicker Log Window to access Flicker Log on this port. Functionality follows the
Historical Log 1 Window Mode (38209).
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-24
7: Register Block Titles
• Waveform Trigger Log (38218): When read, this register returns the Mode in use
by the Waveform Trigger Log Window to access Waveform Trigger Log on this
port. Functionality follows Historical Log 1 Window Mode (38209).
• Register 38219 is currently not used.
• Waveform Samples Log (38220): When read, this register returns the Mode in
use by the Waveform Samples Log Window to access Waveform Samples Log on
this port. Functionality follows Historical Log 1 Window Mode (38209).
• PQ Log (38221): When read, this register returns the Mode in use by the PQ Log
Window to access PQ Log on this port. Functionality follows the Historical Log 1
Window Mode (38209).
• Register 38209 is currently not used.
• External Device Info Block (38223) - Currently not used.
• External Device Programming Block (38224) - Currently not used.
• Device History Block (38225) - Currently not used.
• Direct Memory Access (38226) - Currently not used.
7.73: Window Block (38273-39424)
• Description: Window Registers included in this block:
• Historical Log 1 (38273-38336): These registers are a 128-byte window into the
Historical Log 1. The particular 128-bytes that are accessed are dependent on
the Historical Log 1 window index.
• Historical Log 2 (38337-38400): These registers are a 128-byte window into the
Historical Log 2. The particular 128-bytes that are accessed are dependent on
the Historical Log 2 window index.
• Limit Trigger Log (38401-38464): These registers are a 128-byte window into
the Limit Trigger Log. The particular 128-bytes that are accessed are dependent
on the Limit Trigger Log window index.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-25
7: Register Block Titles
• Limit Snapshot Log (38465-38528): These registers are a 128-byte window into
the Limit Snapshot Log. The particular 128-bytes that are accessed are dependent on the Limit Snapshot Log window index.
• Digital Input Log (38529-38592): These registers are a 128-byte window into
the Digital Input Log. The particular 128-bytes that are accessed are dependent
on the Digital Input Log window index.
• Digital Input Snapshot Log (38593-38656): These registers are a 128-byte window into the Digital Input Snapshot Log. The particular 128-bytes that are
accessed are dependent on the Digital Input Snapshot Log window index.
• Digital Output Log (38657-38720): These registers are a 128-byte window into
the Digital Output Log. The particular 128-bytes that are accessed are dependent on the Digital Output Log window index.
• Digital Output Snapshot Log (38721-38784): These registers are a 128-byte
window into the Digital Output Snapshot Log. The particular 128-bytes that are
accessed are dependent on the Digital Output Snapshot Log window index.
• Flicker Log (38785-38848): These registers are a 128-byte window into the
Flicker Log. The particular 128-bytes that are accessed are dependent on the
Flicker Log window index.
• Waveform Trigger Log (38849-38912): These registers are a 128-byte window
into the Waveform Trigger Log. The particular 128-bytes that are accessed are
dependent on the Waveform Trigger Log window index.
• System Event Log Window (38913-38976):These registers are a 128-byte window into the System Events Log. The particular 128-bytes that are accessed are
dependent on the System Events Log window index.
• Waveform Samples Log (38977-39040): These registers are a 128-byte window
into the Waveform Samples Log. The particular 128-bytes that are accessed are
dependent on the Waveform Samples Log window index.
• PQ Log (39041-39104): These registers are a 128-byte window into the PQ Log.
The particular 128-bytes that are accessed are dependent on the PQ Log window
index.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-26
7: Register Block Titles
• External Device Info Block Window (39169-39232): These registers are a 128byte window into the External Device Info Blocks. The particular 128-bytes that
are accessed are dependent on the External Device Info Blocks window index.
(See Chapter 5.)
• External Device Info Block Window (39233-39296): These registers are a 128byte window into the External Device Programming Blocks. The particular 128bytes that are accessed are dependent on the External Device Programming
Blocks window index. (See Chapter 5.)
• Device History Block (39297-39360) - Currently not used.
• Direct Memory Access (39361-39424) - Currently not used.
7.74: Auto Increment Window Block (39423-39488)
• Auto Increment Configuration is 1 Register, 2 bytes. When read, this register
returns the configuration in use by the Auto Increment Log Window, to access logs
on this port. When written, this register sets the configuration used by the Auto
Increment Log Window, to access logs on this port. Each port accesses a separate,
independent configuration through this register allowing all four ports to access
logs with different configurations.
• The least significant byte indicates which log is being accessed. The appropriate
values are:
0x000 Historical Log 1
0x001 Historical Log 2
0x002 Sequence of Events State Log
0x003 Sequence of Events Snapshot Log
0x004 Digital Input State Log
0x005 Digital Input Snapshot Log
0x006 Digital Output State Log
0x007 Digital Output Snapshot Log
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-27
7: Register Block Titles
0x008 Flicker Log
0x009 Waveform Trigger Log
0x00A System Event Log
0x00B Waveform Sample Log
0x00C PQ Log
0x00D-0x0FF Undefined
• The most significant byte defines the following modes: Paused Download Mode
(0x000) and Running Download Mode (0x001).
• In Paused Download mode (0x000), the log being accessed is paused new records are not added to the log while it is paused.
• In Running Download mode (0x001), the log being accessed is not
paused - new records may be added to the log. When downloading in this
mode, it is possible that records may be overwritten before, or even
during, access to that record.
• Auto Increment Window Index is 1 register, 2 bytes. When read, this register
returns the index used by the Auto Increment Log Window, to access logs on this
port. When written, this register sets the index used by the Auto Increment Log
Window, to access logs on this port. Each port accesses a separate, independent
index through this register, allowing all four ports to access different areas of logs
at the same time.
• When read, the index is incremented before being returned in the Modbus
response. If the Auto Increment Mode is Paused Download mode (0x001xx in
register 39423, 0x099FE), the appropriate log is paused, preventing the addition
of new records while the log is being accessed. A 30-second timer is initiated on
these reads. Should the timer run out (the index is not incremented/read in 30
seconds), the appropriate log will be allowed to continue logging.
• When a value of 0x0FFFF is written to this register, this signifies that the port is
finished accessing the appropriate log, and the 30-second timer is canceled and
the appropriate log will be allowed to continue logging.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-28
7: Register Block Titles
• Should multiple ports access the same log simultaneously, the log will be paused
while either 30-second timer is running; the log will be allowed to continue logging only when both ports time-out or write 0x0FFFF to their index register.
• Auto Increment Log Window is 64 registers, 128 bytes. These registers are a
128-byte window into a log, as specified in the Auto Increment Configuration
(register 39423, 0x099FE). Depending on the Auto Increment Window Index, a
different 128-byte area of a log can be accessed. See Section 5.1.2: Log Download Using Auto-Increment Index Method on page 5-12, for the usage of these
registers.
7.75: Alarm Block (40961-41105)
• Description: Window Registers included in this block:
• Last Alarm (40961-40976): These Registers keep the latest Limit Trigger Log,
which records information about the limits. The log records which limits are currently exceeded and which limits have just changed. The 16 Registers contain 32
bytes. The record format is the same as the Limit Trigger Log Format.
• The first eight bytes are the Time Stamp. The format of the Time Stamp
is:
Time Stamp Bytes
Byte
Format
Range
Description
0
Binary
0-99
Century
1
Binary
0-99
Year
2
Binary
1-12
Month
3
Binary
1-31
Day
4
Binary
0-23
Hour
5
Binary
0-59
Minute
6
Binary
0-59
Second
7
Binary
0-99 +MSB
Centisecond
• An additional piece of information is contained in the centisecond byte.
The most significant bit indicates whether Limit Trigger monitoring was
continuous between the last record and this record. If the bit is 1, then
this is the first record recorded after a power-down, reset or download
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-29
7: Register Block Titles
and all unfinished durations prior to this record are lost. If the bit is 0,
then recording was continuous between the last record and this one.
• The next four bytes are a bitmap for the Current State of the Value 1
Comparisons of the Limits.
- The first bit (the most significant bit of the first byte) is the Current
State of the 1st Limit’s Value 1 Comparison. The last bit (the least
significant bit of the fourth byte) is the Current State of the 32nd Limit’s
Value 1 Comparison.
- A bit value of 1 means that the Comparison is exceeded (less than or
equal to Value 1 for a below limit; greater than Value 1 for an above
limit), a bit value of 0 means the Comparison is not exceeded (greater
than Value 1 for a below limit; less than or equal to Value 1 for an
above limit).
• The next four bytes are the same bitmap as above, but for the Current
State of the Value 2 Comparisons of the Limits.
• The next four bytes are a bitmap for the Delta of the Value 1 Comparisons of the Limits. The order of the bits is the same as above. A bit value
of 1 means that the State of the Value 1 Comparison changed since the
last alarm occurred; a bit value of 0 means that the State of the Value 1
Comparison did not change since the last alarm.
• The next four bytes are the same bitmap as above, but for the Delta of
the Value 2 Comparisons of the Limits.
• The next four bytes are a bitmap for the Current State of the Combinations of the Limits.
- The first bit (the most significant bit of the first byte) is the Current
State of the 1st Limit’s Combination of the Value 1 Comparison and the
Value 2 Comparison. The last bit (the least significant bit of the fourth
byte) is the Current State of the 32nd Limit’s Combination of the Value
1 Comparison and the Value 2 Comparison.
- A bit value of 1 means that the Combination is true; a bit value of 0
means that the Combination is false.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-30
7: Register Block Titles
• The last four bytes are the same bitmap as above, but for the Delta of the
Combination of the Limits.
• Last Alarm Snapshot (40977-41104): the registers store the latest Limit Snapshot Log. The record formats are also explained in Section 6: Meter Programmable Settings Block on page 6-1.
• Record Format: A record contains 32, 64, 128 or 256 bytes, depending
on how many channels have limits assigned to them. The first eight bytes
in each Record are the Time Stamp. The format of the Time Stamp is
shown on page 8-34.
• The remaining bytes are the values monitored by Limits (45077-45204).
If the first Data Pointer is requesting VBN, a 4-byte value, then the next 4
bytes in the Record is VBN. This continues, Data Pointer for Data Pointer,
until all Data Pointers have been satisfied, or the number of bytes is equal
to the Historical Log 1 Record Size.
• Limit Data Pointers (45077-45204): These registers indicate which values are
being monitored by Limits. Each Data Pointer has the following 8-byte structure:
Size
Format
Description
2-byte
Unsigned Integer
Line Number
1-byte
Unsigned Char
Point Number
1-byte
Unsigned Char
Limit Mode
2-byte
Unsigned Integer
Comparison 1 Value
2-byte
Unsigned Integer
Comparison 2 Value
• A Line Number is an index into the Communication Table. For example:
Line Number 11 is for the 12th Line in the Communication Table, 0.1 Second Phase-to-Neutral Voltages. Data Pointers with Line Numbers greater
than the number of lines in the table are ignored.
• A Point Number is an index into a Line in the Communication Table. For
example: Point Number 1 is for the second entry in a Line. Line Number
11, Point Number 1 is the 2nd in the 12th line, 0.1 Second VBN. Data
Pointers with Point Numbers greater than the number of points for the
line are ignored.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-31
7: Register Block Titles
• Latched Exception Flag (41105): This register tells you how many Limit Triggers
have occurred since the last time the registers were checked. This register is
Read Only.
• For example: Two Limit Exceptions occurred. Read the register from Port
1; you will notice 2 Limit Exceptions returned. Later, two more Limit
Exceptions occurred. Read the register again. From Port 1, you will notice
2 Limit Exceptions returned. From Port 2, you will notice 4 Limit Exceptions returned. Limit Exceptions are incremented so that you have a
history of Limit Exceptions in the Ports.
7.76: TOU Action Log Header (41217-41240)
• Description: TOU Action Log Header Registers included in this block: see registers
36865-36883.
7.77: TOU Month/Season Log Header (41281-41304)
• Description: TOU Month/Season Log Header Registers included in this block: see
registers 36865-36883.
7.78: Port Control Block (41729-42496)
• Description: Port Control Registers included in this block (see Chapter 5):
• Port Control Command (41729): When written, this register receives commands
meant to control the ports. Valid commands are:
0x00100 = Lock Port 4 (I/O) for my use
0x00101 = Lock Port 3 for my use
0x00102 = Lock Port 2 for my use
0x00103 = Lock Port 1 (232/485) for my use
0x00104 = Lock the Diagnostic Port for my use (currently not use)
0x00200 = Unlock Port 4
0x00201 = Unlock Port 3
0x00202 = Unlock Port 2
0x00203 = Unlock Port 1
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-32
7: Register Block Titles
0x00204 = Unlock the Diagnostic Port (currently not used)
• You cannot lock your own port.
• You cannot lock a port that is already locked.
• A port can only be unlocked by the port that locked it originally.
• Lock States (41730-41732): These registers contain 6 bytes. The first five bytes
contain codes indicating whether a port is locked by another port or not.
Port Control Lock States
Register
41731
High Byte
Port 4 (I/O)
Low Byte
Port 3
41732
Port 2
Port 1 (232/485)
41733
Diagnostic Port
Unused
• Initially, these bytes read as 0x0FF. When a port requests that another
port be locked to its use (0x00100 - 0x00104 to Register 41731), these
bytes will read with one of the following codes, indicating which port is
the locked owner of which port:
0x000 = Locked by Port 4 (I/O)
0x001 = Locked by Port 3
0x002 = Locked by Port 2
0x003 = Locked by Port 1 (232/485)
0x004 = Locked by the Diagnostic Port (currently not used)
0x0FF = Unlocked
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-33
7: Register Block Titles
• Pointers (41733-41752): These registers, when read, return the values of the
pointers controlling the Communication Buffers in the Nexus® device. They are
unsigned integers and represent the indexes of the series of bytes that are the
Receive and Transmit Circular Buffers. Since the buffers are 512 bytes long,
valid values should range from 0x00000 to 0x001FF.
• The order of the registers is:
Port Control Pointers
Port
ReceiveIn
ReceiveOut
41734
TransmitIn
41735
TransmitOut
Port 4 (I/O)
41733
Port 3
41737
Port 2
41741
41742
41743
41744
Port 1 (232/485)
41745
41746
41747
41748
Diagnostic Port
41749
41738
41739
41750
41751
41736
41740
41752
- ReceiveIn indexes the location where the next received character will be
placed in the Receive Buffer by the interrupt routine.
- ReceiveOut indexes the location where the next character should be
removed from the Receive Buffer by the parsing routine.
- TransmitIn indexes the location where the next character to be transmitted should be placed by the communication generation routine.
- TransmitOut indexes the location of the next character to be transmitted
by the interrupt routine.
- The Receive Buffer is empty if RecIn = (RecOut+1) Mod 512. The
Receive Buffer is full if RecIn = RecOut.
- The Transmit Buffer is empty if TrmIn = TrmOut. The Transmit Buffer is
full if TrmOut = TrmIn+1) Mod 512.
• When a port is locked, its pointers may be modified by the locking port.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-34
7: Register Block Titles
• When a TransmitIn Register is written, that causes the interrupt routines
to transmit characters in the Transmit Buffer from TransmitIn to TransmitOut.
• Receive and Transmit Buffers (41985-44544): These registers, when read, return
the contents of the appropriate Receive and Transmit Buffers. Each buffer is 256
Registers (512 bytes) long. The order of the buffers is:
Receive and Transmit Buffers
Port
Receive
Transmit
Port 4 (I/O)
41985-42240
43265-43520
Port 3
42241-42496
43521-43776
Port 2
42497-42752
43777-44032
Port 1 (232/485)
42753-43008
44033-44288
Diagnostic Port
43009-43264
44289-44544
7.79: Reserved for Future Use (44545-44578)
7.80: Programmable Settings Block 1 (45057-57344)
See Chapter 6 for details.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-35
7: Register Block Titles
7.81: Action Block - Resetting Meter Registers (57345-57517)
• Most of the registers in the Action Block are used to perform an action or reset a
meter register. Unless otherwise stated, the action is performed when a value, any
value, is written to that register.
• For example: In order to Reset Maximum Value in Meter Address 1, any value,
such as ‘1’ (0x00001) should be written to Register 57346 (0x0E001). The
appropriate Modbus RTU command for this example would be: 01 06 E001 0001
2E0A (See Chapter 1 for Modbus protocol overview.)
• Description: Action Registers included in this block:
• Log Reset (57345): This register, when written with any value, causes all logs to
be cleared. This action should be performed only under the following two
circumstances:
1. When the Programmable Settings are modified, such that data already in the
logs is invalidated. For example, any modifications involving the record size or
organization of the contents of a snapshot would require the logs to be cleared
of any previous data.
2. When the Run-Time Code is upgraded, resulting in one of the following:
- Redefinition of the layout or meaning of the Programmable Settings.
- Altered behavior or capabilities of the logs.
NOTE: Log Reset should be performed automatically by the software in either
case and should not be an action directly available to the user. (See Chapter 5.)
• Maximum Reset (57346): This register, when written with any value, causes all
Maximum Values to be cleared.
• Minimum Reset (57347): This register, when written with any value, causes all
Minimum Values to be cleared.
• Energy Reset (57348): This register, when written with any value, causes all
Energy Values to be cleared.
• Registers 57380-57382: Internal KYZ Enable, Internal KYZ Minimum Pulse
Width, Internal KYZ Pulses/Whr sec are obsolete. These registers are no longer
used.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-36
7: Register Block Titles
• Reset Time of Use Current Season and Current Month (57386): When written,
Time of Use Current Season and Current Month will reset.
• Manual Waveform Capture (57387): When written, the unit captures a waveform.
• Reset Internal Input Accumulations and Aggregations (57388): When written,
Internal Input Accumulations and Aggregations will reset.
• Override Data not yet Valid Block (57389): This register is for diagnostics of
communication between two microprocessors in the meter.
• Refresh External I/O Header Information (57390): This register, when written,
causes all External Devices to be polled for their Information Blocks.
• Refresh External I/O Programming Information (57391): This register, when
written, causes all External Devices to be polled for their Programming Blocks.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-37
7: Register Block Titles
• Relay Locking Relay Selection (57392): This register and register 57393 will
manually change the External Digital Output Modules’ Relays. Using register
57392, the user can select relays to be locked by register 57393.
- A bit value of 1 means that the relay will be affected by the value on the Action
Selection Register (57393).
- A bit value of 0 means that the relay will not be affected by the value on the
Action Selection Register (57393).
Relay Locking Relay Selection Register (57392)
Byte
High Byte
Module
Module 1
Low Byte
Module 2
Module 3
Module 4
Relay
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
• Relay Locking Action Selection (57393): This register will lock or unlock the
relays of the External Digital Output Modules in Relay Selection Register 57392.
Relays in the Selection Register (57392) with a bit value of 1 can be locked or
unlocked by this Register. The Register is a 2-byte unsigned integer.
Relay Locking Action Selection Values
Value
Description
0
Lock common to N.C. (normally closed)
1
Lock common to N.O. (normally open)
2
Unlock
3-65535
Not used
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-38
7: Register Block Titles
7.82: Device Identification Block 2 (65088-65280)
• Description: Device Identification Registers included in this block:
• Firmware Variation Strings (65089-65280):
• Eight Registers each and Null Terminated ASCII Strings (Terminating Null
(ASCII 00H) at the end of the string) (see Section 3.2: Type F1 - Null Terminated ASCII String on page 3-1.).
Operational Communication Settings
Value
Protocol
Baud
Rate
Parity
Stop Bits
Data Bits
Response
Delay (ms)
0
Modbus ASCII
4800
None
5
0.00
1
Modbus RTU
9600
Even
6
0.25
2
DNP 3.0
19200
Odd
7
0.50
3
38400
Mark
8
0.75
4
57600
Space
5
115200
1.00
1.25
6
1.50
7
1
1.75
8
1.5
2.00
9-14
2.25-3.50
15
2
3.75
16-255
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
4.00-63.75
Doc#
E171707
7-39
7: Register Block Titles
7.83: Password Block (65316-65344)
NOTE: The information in this section refers to the log in and log out functionality for
the meter’s Legacy security feature.
• Description: this register contains and enumeration that tells the device what action
to take. The enumeration is as follows:
0x00000 - Set Level 1 Password
0x00001 - Set Level 2 Password
0x00002 - Enable Password Protection
0x00003 - Disable Password Protection
0x00004 - Enable Sealing Switch Protection
0x00005 - Disable Sealing Switch Protection
0x00006 - Set Network User 1 User Name and Password
0x00007 - Set Network User 2 User Name and Password
0x00008 - Set Network User 3 User Name and Password
0x00009 - Set Network User 4 User Name and Password
0x0000A - Set Network User 5 User Name and Password
0x0000B - Set Network User 6 User Name and Password
0x0000C - Set Network User 7 User Name and Password
0x0000D - Set Network User 8 User Name and Password
0x0000E - Set Network User 1 Privileges
0x0000F - Set Network User 2 Privileges
0x00010 - Set Network User 3 Privileges
0x00011 - Set Network User 4 Privileges
0x00012 - Set Network User 5 Privileges
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-40
7: Register Block Titles
0x00013 - Set Network User 6 Privileges
0x00014 - Set Network User 7 Privileges
0x00015 - Set Network User 8 Privileges
0x00016 - Read Network User 1 user Name and Privileges
0x00017 - Read Network User 2 user Name and Privileges
0x00018 - Read Network User 3 user Name and Privileges
0x00019 - Read Network User 4 user Name and Privileges All successful commands set access back to Level 0, revoking the 2-minute timer of any active password.
• New Password A (65332-65336)
• New Password B (65340-65344)
• For setting Level 1 & Level 2 passwords: these registers are written to in
order to set the Level 1 or Level 2 Password. The same password should
be written to both sets of registers; a new password will be accepted only
if the values written to both sets of registers agree.
• After filling in both sets of registers, the Password Command register
should be written with the command indicating which password is being
updated.
• Passwords must be 10 bytes long - consistent padding with extra characters must be performed.If a password is shorter than 10 bytes should be
padded with SPACE (0x020) characters at the end.
• Acceptable Passwords should consist of the ASCII characters ‘ ‘ (0x020),
‘0’-‘9’ (0x030-0x039), ‘A’-‘Z’ (0x041-0x05A). Attempts to set a password
with illegal characters will fail.
• For setting network user name, password and privileges:
- For setting network user name and password, software should send
user name to New Password A field, and password to New Password B
field. Software should always set none-zero length to user name and
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-41
7: Register Block Titles
password fields. If username or password is shorter than 10 bytes, then
software should pad it with NULL (0x0) characters at the end.
• For setting network user privileges, software should send it to New Password A field, with undefined bit fields set to 0s.
• For reading network user name and privileges, the user must gain Level 2
password access to the meter and then issue the read network username
& privileges command. The meter will place the user name in New Password A field and user privileges in New Password B field for software to
read. The user cannot read the network password: the byte values in New
Password A and New Password B fields are encoded. If the user does not
have sufficient access rights or if the password command sequence
entered is not correct, the user will read 0's for New Password A and New
Password B fields.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
7-42
8: Alternative Method for Downloading Logs
8:Alternative Method for Downloading Logs
8.1: Overview
The preferred and recommended method for downloading logs from the Nexus® 1450
meter is using web API. For backward compatibility, the System Events Log and historical logs 1 and 2 can be downloaded using the serial method (see Chapter 5). This
chapter contains information on these logs.
8.2: Historical Log 1 Format
• Profile information is in the Programmable Settings Block (see Chapter 7 for
details).
• Historical Log 1 will fill to its total allocated memory. The number of records possible in the log is the total memory allocated divided by the record size (size of an
Historical Log snapshot) and the 8 bytes record header. For example:
Record size = 64
File allocated = 1MB = 1048576
Number of records = 1048576 /(64+72)=14563
• Historical Log 1 Record Size: (45463):
• This Register is an enumeration for the size of a record in the Historical
log. The valid values are:
0x00000 = 32 byte records
0x00001 = 64 byte records
0x00002 = 128 byte records
0x00003 = 256 byte records
0x00004 = 16 byte records
• Historical Log 1 Data Pointers: (45205-45332):
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-1
8: Alternative Method for Downloading Logs
• These Registers indicate which information to include in a record in the Historical
log. Each Data Pointer has the following four byte structure:
Size
Format
Description
2 byte
unsigned integer
Line Number
1 byte
unsigned character
Point number
1 byte
unsigned character
Reserved
• A Line Number is an index into the Communication Table. For example, Line
Number 11 is for the 12th line in the Communication Table, 0.1 second Phaseto-Neutral Voltages. Data Pointers with Line Numbers greater than the number
of lines in the table are ignored.
• A Point Number is an index into the Communication Table. For example, Point
Number 1 is for the second entry in a Line. Line Number 11, Point Number 1 is
the second in the twelfth line, 0.1 second VBN. Data Pointers with Point Numbers
greater than the number of points for the line are ignored.
• Record Format: A record contains as many bytes as specified by the Historical Log
1 Record Size Field in the Programmable Settings Block (45463). The first eight
bytes in each record is the Time Stamp. The format of the Time Stamp is:
Byte
Format
Range
Description
0
binary
0 - 99
century
1
binary
0 - 99
year
2
binary
1 - 12
month
3
binary
1 - 31
day
4
binary
0 - 23
hour
5
binary
0 - 59
minute
6
binary
0 - 59
second
7
binary
0 - 100
centisecond
• If the Historical record was recorded after powering up or the log was reset, the
record does not contain information covering a full interval and the most significant bit of the second's byte will be set.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-2
8: Alternative Method for Downloading Logs
• If the Historical record was recorded after time was adjusted, the record might
contain more or less than a full interval's worth of data.
• If time is advanced within the current interval, or advanced or rolled back
to outside the current interval, the record contains less than a full interval's worth of data and the most significant bit of the minute byte will be
set.
• If time is rolled back within the same interval, the record contains more
than a full interval's worth of data and the bit before the most significant
bit (bit 6) of the minute byte will be set.
• The remaining bytes are the values requested by the Historical Log 1 Data Pointers
(45205-45332). If the first Data Pointer is requesting VBN a 4 byte value, then the
next 4 bytes in the Record are VBN. This continues, Data Pointer for Data Pointer,
until all Data Pointers have been satisfied, or the number of bytes is equal to the
Historical Log 1 Record Size.
8.3: Historical Log 2 Format
• Profile information is in the Programmable Settings Block (see Chapter 7 for
details).
• Historical Log 2 will fill to its total allocated memory. The number of records possible in the log is the total memory allocated divided by the record size (size of an
Historical Log snapshot) and the eight bytes record header.
• Historical Log 2 Record Size: (45464):
• This Register is an enumeration for the size of a record in the Historical
log. The valid values are:
0x00000 = 32 byte records
0x00001 = 64 byte records
0x00002 = 128 byte records
0x00003 = 256 byte records
0x00004 = 16 byte records
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-3
8: Alternative Method for Downloading Logs
• Historical Log 1 Data Pointers: (45333-45332):
• These Registers indicate which information to include in a record in the Historical
log. Each Data Pointer has the following four byte structure:
Size
Format
Description
2 byte
unsigned integer
Line Number
1 byte
unsigned character
Point number
1 byte
unsigned character
Reserved
• A Line Number is an index into the Communication Table. For example, Line
Number 11 is for the 12th line in the Communication Table, 0.1 second Phaseto-Neutral Voltages. Data Pointers with Line Numbers greater than the number
of lines in the table are ignored.
• A Point Number is an index into the Communication Table. For example, Point
Number 1 is for the second entry in a Line. Line Number 11, Point Number 1 is
the second in the twelfth line, 0.1 second VBN. Data Pointers with Point Numbers
greater than the number of points for the line are ignored.
• Record Format: A record contains as many bytes as specified by the Historical Log
1 Record Size Field in the Programmable Settings Block (45463). The first eight
bytes in each record is the Time Stamp. The format of the Time Stamp is:
Byte
Format
Range
Description
0
binary
0 - 99
century
1
binary
0 - 99
year
2
binary
1 - 12
month
3
binary
1 - 31
day
4
binary
0 - 23
hour
5
binary
0 - 59
minute
6
binary
0 - 59
second
7
binary
0 - 100
centisecond
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-4
8: Alternative Method for Downloading Logs
• If the Historical record was recorded after powering up or the log was reset, the
record does not contain information covering a full interval and the most significant bit of the second's byte will be set.
• If the Historical record was recorded after time was adjusted, the record might
contain more or less than a full interval's worth of data.
• If time is advanced within the current interval, or advanced or rolled back
to outside the current interval, the record contains less than a full interval's worth of data and the most significant bit of the minute byte will be
set.
• If time is rolled back within the same interval, the record contains more
than a full interval's worth of data and the bit before the most significant
bit (bit 6) of the minute byte will be set.
• If the Historical Log 2 Time of Use Enable byte (45952) is disabled, the remaining
bytes are the values requested by the Historical Log 2 Data Pointers (4533345460). If the first Data Pointer is requesting VBN a 4 byte value, then the next 4
bytes in the Record are VBN. This continues, Data Pointer for Data Pointer, until all
Data Pointers have been satisfied, or the number of bytes is equal to the Historical
Log 2 Record Size.
8.4: System Event Log Format
• The System Event Log stores events which affect the operation of the meter, including power events, time changes, log retrieval, and firmware changes. The full list is
given on the next page.
• Record Format: The System Event record is 16 bytes.
[Timestamp] 8 bytes, Nexus Time stamp
[Record Type] 1 byte
[Record Details] 7 bytes
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-5
8: Alternative Method for Downloading Logs
• Event Table:
Byte
14
Byte
15
Current Major Version
Rec
Sequ
ence
Undefined
Firmware
ID
Current Minor Version
Rec
Sequ
ence
Undefined
Event
Type ID
System
Event Type
Record
Sequence
Bytes 0
to 7
0x000
Run Time
Status
(Power)
First
Time
Stamp
Event
Type ID
Details
Undefined
0x001
Password
First
Time
Stamp
Event
Type ID
Action
Port ID
0x002
Change Programmable
Settings
First
Time
Stamp
Event
Type ID
Undefined
0x003
Change
Firmware
First
Time
Stamp
Event
Type ID
Firmware
ID
Second
Time
Stamp
Event
Type ID
Byte 8
Byte 9
Byte 10
Byte 11
Byte 12
Byte
13
Undefined
0x004
Change
Time
First
Time
Stamp
Event
Type ID
Part
changed
Port ID
Undefined
0x005
Test Mode
First
Time
Stamp
Event
Type ID
Action
Port ID
Undefined
0x006
Log
Retrieval
First
Time
Stamp
Event
Type ID
Action
Log ID
Port ID
Rec
Sequence
Protocol
IP
Byte
1
IP
Byte 2
Second
Time
Stamp
Event
Type ID
Action
Log ID
Port ID
Rec
Sequence
IP
Byte
3
IP
Byte
4
Undefined
0x007
Feature
Reset
First
Time
Stamp
Event
Type ID
Item ID
Port ID
Undefined
0x008
System Initialization
problem
First
Time
Stamp
Event
Type ID
Problem
Type
Prob
Detail
Undefined
0x009
Change
meter serial
number
First
Time
Stamp
Event
Type ID
Rec
Sequence
Port ID
Old Serial Number MSB Part
Second
Time
Stamp
Event
Type ID
Rec
Sequence
Old Serial Number LSB Part
Undefined
0x00A
Bio-Block
First
Time
Stamp
Event
Type ID
Rec
Sequence
Block ID
Update
Order
Port ID
Reason =
1
Not Used
0x00A
Bio-Block
(Ethernet
Board 1)
First
Time
Stamp
Event
Type ID
Rec
Sequence
Block ID
=2
Update
Order
Port ID
Reason =
2
MAC
Byte
1
MAC
Byte 2
Second
Time
Stamp
Event
Type ID
Rec
Sequence
Block ID
=2
Update
Order
MAC B3
MAC
Byte
4
MAC
Byte
5
MAC
Byte 6
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-6
8: Alternative Method for Downloading Logs
Event
Type ID
System
Event Type
Record
Sequence
Bytes 0
to 7
0x00A
Bio-Block
(Front Panel
Board)
First
Time
Stamp
Second
0x00A
Bio-Block
(Digital
Board)
Byte 8
Byte 11
Byte
14
Reason
>= 2
Contrast
Byte
15
Byte 10
Event
Type ID
Rec
Sequence
Block ID
=3
Time
Stamp
Event
Type ID
Rec
Sequence
LCD Turnoff Timeout
X Left Coordinate
X Right Coordinate
Third
Time
Stamp
Event
Type ID
Rec
Sequence
Y Top Coordinate
Y Bottom Coordinate
Undefined
First
Time
Stamp
Event
Type ID
Rec
Sequence
Block ID
=8
Upd
Order
Port ID
Cal
Status
Second
Time
Stamp
Event
Type ID
Rec
Sequence
F Tst
Status
Fin Tst
Error
Undefined
Update
Order
0x00B
VSwitch
First
Time
Stamp
Event
Type ID
V-Switch
Value
Port ID
Undefined
0x00C
Security
First
Time
Stamp
Event
Type ID
Action
Port ID
User Acc
Idx
0x00D
Clock Compensation
First
Time
Stamp
Event
Type ID
Enabled/
Disabled
Port ID
Undefined
Byte 12
Byte
13
Byte 9
Port ID
Reason =
2
Volume
Cal
Error
Undefined
• Run Time Status - Power Record:
• The first byte of the sub-fields indicates whether power was lost or
regained at the recorded time:
0x000
Run Time was stopped (power loss, boot mode, etc.). The timestamp
record is that recorded before the meter be turned off.
0x001
Run Time has started.
0x002
Run Time is active (all readings have initialized, polling, logging limits,
etc. are enabled)
0x0030x0FF
Undefined
• The remaining 6 bytes of the sub-fields are undefined.
• Password Record:
• The Password System Event record is stored when the administrative
password is used or changed. See Security Record for changes in the individual user accounts.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-7
8: Alternative Method for Downloading Logs
• The first byte of the sub-fields indicates what action occurred at the
recorded time:
0x000
Password Protection was Enabled.
0x001
Password Protection was Disabled.
0x002
The Level 1 Password was changed.
0x003
The Level 2 Password was changed.
0x004
Level 1 access was granted.
0x005
Level 2 access was granted.
0x006
An invalid password was supplied.
0x007-0x0FF
Undefined
• The second byte of the sub-fields indicates what port was used for the
action:
0x000
internal use
0x001
PORT 1 - IR/OPTICAL PORT
0x002
LCD touch screen
0x003
ETHERNET 1
0x004
ETHERNET 2
0x005
PORT 3- RS485 - master or slave
0x006
reserved, N/A
0x007
USB only, N/A for UART
0x008
PORT 4 - RS485, master or slave
0x009
PORT 2 - UART, USB serial
0x00A-0x0FF
Undefined
• The remaining 5 bytes of the sub-fields are undefined.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-8
8: Alternative Method for Downloading Logs
• Change Programmable Settings:
• The 7 bytes of the sub-fields are undefined.
• The first byte of the sub-fields indicates which copy was successfully
created and saved. If all bits are zero, no copy was successfully created/
saved:
Bit 0 (Less significant bit) = 1 (First copy OK)
Bit 1 (Less significant bit) = 1 (Second copy OK)
Bit 2 (Less significant bit) = 1 (Third copy OK)
Bits 3-7 = Not defined
• The 6 bytes of the sub-fields are undefined.
• Change Firmware:
• This event type can generate up two consecutive records.
• The first byte of the sub-fields indicates which firmware has been
changed:
0x000
Comm Run Time
0x001
Undefined
0x002
Comm Boot
0x003
FPGA
0x004
DSP2 Run Time
0x005-0x0FF
Undefined
• The next 4 bytes of the sub-fields indicates the current major/minor
version number of the changed firmware. They major/minor version is
left leading with space/zeros. (For FPGA the minor firmware version will
be just into the second and third byte.)
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-9
8: Alternative Method for Downloading Logs
• The sixth byte of the sub-fields indicates the record sequence.
0x000
no extra record (for firmware that does not have minor
version number)
0x001
the first record of the sequence, it contains the major
version number
0x002
the second record of the sequence, it contains the minor
version number
• The seventh byte of the sub-fields is undefined
• Change Time:
• This record is used to indicate manual changes of the time of the meter,
as performed via communication commands. Automatic functions, such
as IRIG-B or Daylight Savings, are not indicated by this record.
• The first byte of the sub-fields indicates which part of the time change
this record shows:
0x000
Old Time - The time stamp is the old time
of the meter.
0x001
New Time - The time stamp is the new
time of the meter.
0x002
Old Time - Auto correction, time stamp
before correction was made. Internally
used, so next byte should be 0.
0x003
New Time - Auto correction, corrected
time stamp.
0x004-0x0FF
Undefined
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-10
8: Alternative Method for Downloading Logs
• The second byte of the sub-fields indicates what port was used to change
the time:
0x000
internal use
0x001
PORT 1 - IR/OPTICAL PORT
0x002
LCD touch screen
0x003
ETHERNET 1
0x004
ETHERNET 2
0x005
PORT 3- RS485 - master or slave
0x006
reserved, N/A
0x007
USB only, N/A for UART
0x008
PORT 4 - RS485, master or slave
0x009
PORT 2 - UART, USB serial
0x00A-0x0FF
Undefined
• The remaining 5 bytes of the sub-fields are undefined.
• Log Download:
• When logs are retrieved, the action is recorded in the system event log.
When retrieving logs over Ethernet, two records are generated to record
the IP address of the software doing the retrieval. When retrieving logs
otherwise, only one record is recorded.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-11
8: Alternative Method for Downloading Logs
• FIRST RECORD:
- The first byte indicates the log download action:
0x000
Download Started, Log records while downloading
0x001
Download Started, Log Paused while downloading
0x002
Download Ended.
0x003
Download Ended, dropped records. (Log download
using file system access)
- The second byte of the sub-fields indicates which log was being
downloaded:
0x000
Interval 1 Log
0x001
Interval 2 Log
0x002
Limit Log
0x003
n/a
0x004
Digital Input Log
0x005
n/a
0x006
Digital Output Log
0x007
n/a
0x008
Flicker Log
0x009
Waveform Log
0x00A
System Event Log
0x00B
Transient Log
0x00C
PQ Log
0x00D
Reset Log - NOT SUPPORTED
0x00E
Interval Log 3 Log
0x00F
Interval Log 4 Log
0x010
Interval Log 5 Log
0x011
Interval Log 6 Log
0x012
Interval Log 7 Log
0x013
Interval Log 8 Log
0x014
Event triggered Log
0x015-0x0FF
Undefined
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-12
8: Alternative Method for Downloading Logs
- The third byte of the sub-fields indicates what port was used to download the log:
0x000
internal use
0x001
PORT 1 - IR/OPTICAL PORT
0x002
LCD touch screen
0x003
ETHERNET 1
0x004
ETHERNET 2
0x005
PORT 3- RS485 - master or slave
0x006
reserved, N/A
0x007
USB only, N/A for UART
0x008
PORT 4 - RS485, master or slave
0x009
PORT 2 - UART, USB serial
0x00A-0x0FF
Undefined
- The fourth byte of the sub-fields indicates the sequence number:
(Ethernet only).
0x000
first record
0x001
second record
- The fifth byte of the sub-fields indicates the protocol: (Ethernet only).
0x000
MODBUS TCP
0x001
FTP
- The remaining 2 bytes of the sub-fields are the first two bytes of the
client IP address.
• SECOND RECORD:
- The first fourth bytes of the sub-fields are defined as into the first
record.
- The fifth and sixth bytes of the sub-fields are the last bytes of the client
IP address.
- The remaining 1 byte of the sub-fields is undefined.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-13
8: Alternative Method for Downloading Logs
• Feature Reset:
• A Feature Reset System Event record occurs when a log or accumulator is
reset by an external request.
• The first byte indicates what feature was being reset:
0x000
All Logs Reset
0x001
Maximum Reset
0x002
Minimum Reset
0x003
Energy Reset
0x004
Time of Use Current Month
0x005
Internal Input Accumulations and
Aggregations
0x006
KYZ Output Accumulations
0x007
Cumulative Demand
0x008
Interval 1 Log Reset
0x009
Interval 2 Log Reset
0x00A
Limit Log Reset
0x00B
Digital Input Log Reset
0x00C
Digital Output Log Reset
0x00D
Flicker Log Reset
0x00E
Waveform Log Reset
0x00F
PQ Log Reset
0x010
System Event Log Reset
0x011
Total Average Power Factor Reset
0x012
Time of Use Active registers
0x013
Test Mode - NOT SUPPORTED
0x014
Interval 3 Log Reset
0x015
Interval 4 Log Reset
0x016
Interval 5 Log Reset
0x017
Interval 6 Log Reset
0x018
Interval 7 Log Reset
0x019
Interval 8 Log Reset
0x01A
Event triggered Log Reset
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-14
8: Alternative Method for Downloading Logs
0x01B
Transient Log Reset
0x01C
EN50160 data reset
0x01D
EN50160 report reset
0x01E
EN50160 log reset
0x01F
EN50160 data preset
• The second byte of the sub-fields indicates what port was used to request
the reset.
0x000
internal use
0x001
PORT 1 - IR/OPTICAL PORT
0x002
LCD touch screen
0x003
ETHERNET 1
0x004
ETHERNET 2
0x005
PORT 3- RS485 - master or slave
0x006
reserved, N/A
0x007
USB only, N/A for UART
0x008
PORT 4 - RS485, master or slave
0x009
PORT 2 - UART, USB serial
0x00A-0x0FF
Undefined
• The remaining 5 bytes of the sub-fields are undefined.
• System Initialization Problem:
• The System Initialization System Event records when the meter detected
a problem during boot up.
• The first byte indicates the problem type:
0x000
Log Initialization
0x001-0x0FF
Undefined
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-15
8: Alternative Method for Downloading Logs
• The second byte of the sub-fields indicates the reason of the problem.
Bit (0x01)
The log folder into the compact flash has a bad layout: files are out of order, files are missed, file have
wrong size, directories exist into that folder
Bit 2 (0x02)
The memory allocated is bigger than the memory
available
Bit 3 (0x04)
The log folder and the system event log file was
created
Bit 4 (0x08)
Some log files are missed then they are created
(This bit should not be set, excepted for special
runtime version that allows creating log files)
Bit 5 (0x10)
The log files are out of order (This bit should not be
set, excepted for special runtime version that
allows creating log files)
Bit 6 (0x20)
There were extra log files in the end of the log
folder and they were deleted (This bit should not be
set, excepted for special runtime version that
allows creating log files)
Bit 7 (0x40)
There were extra files into the log folder (This bit
should not be set, excepted for special runtime version that allows creating log files)
• The remaining 5 bytes of the sub-fields are undefined.
• Change Meter Serial Number:
• This event generates two consecutive records.
• FIRST RECORD:
- The first byte of the sub-fields indicates the sequence number.
0x000
first record
0x001
second record
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-16
8: Alternative Method for Downloading Logs
- The second byte of the sub-fields indicates what port was used to
change the serial number:
0x000
internal use
0x001
PORT 1 - IR/OPTICAL PORT
0x002
LCD touch screen
0x003
ETHERNET 1
0x004
ETHERNET 2
0x005
PORT 3- RS485 - master or slave
0x006
reserved, N/A
0x007
USB only, N/A for UART
0x008
PORT 4 - RS485, master or slave
0x009
PORT 2 - UART, USB serial
0x00A-0x0FF
Undefined
- The remaining 5 bytes of the sub-fields are used to save the 5 most
significant bytes of the old meter serial number.
• SECOND RECORD:
- The first byte of the sub-fields indicates the sequence number.
0x001
second record
- The second, third and fourth bytes of the sub-fields are used to save the
3 less significant bytes of the old meter’s serial number.
- The remaining 3 bytes of the sub-fields are undefined.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-17
8: Alternative Method for Downloading Logs
• V-switch:
• A V-Switch system event record indicates the changing of the V-switch of
the meter.
• The first byte indicates the value of the v-switch to be updated to.
• The second byte of the sub-fields indicates what port was used for the
action:
0x000
internal use
0x001
PORT 1 - IR/OPTICAL PORT
0x002
LCD touch screen
0x003
ETHERNET 1
0x004
ETHERNET 2
0x005
PORT 3- RS485 - master or slave
0x006
reserved, N/A
0x007
USB only, N/A for UART
0x008
PORT 4 - RS485, master or slave
0x009
PORT 2 - UART, USB serial
0x00A-0x0FF
Undefined
• The remaining 5 bytes of the sub-fields are undefined.
• Security:
• A Security System Event record occurs when a security change occurs,
such as changing a username or password used to log on to the meter.
See Password Record for changes in the administrative password.
• The first byte of the sub-fields indicates what action occurred at the
recorded time:
0x000
Sealing switch enabled
0x001
Sealing switch disabled
0x002
Network username/password
changed
0x003
Network privileges changed
0x004-0x0FF
Undefined
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-18
8: Alternative Method for Downloading Logs
• The second byte of the sub-fields indicates what port was used for the
action:
0x000
internal use
0x001
PORT 1 - IR/OPTICAL PORT
0x002
LCD touch screen
0x003
ETHERNET 1
0x004
ETHERNET 2
0x005
PORT 3- RS485 - master or slave
0x006
reserved, N/A
0x007
USB only, N/A for UART
0x008
PORT 4 - RS485, master or slave
0x009
PORT 2 - UART, USB serial
0x00A-0x0FF
Undefined
• The third byte of the sub-fields is only valid for actions 0x002-0x003 and
indicates the user account number:
0x000
n/a
0x001
user account 1
0x002
user account 2
0x003
user account 3
0x004
user account 4
0x005
user account 5
0x006
user account 6
0x007
user account 7
0x008
user account 8
• The remaining 4 bytes of the sub-fields are undefined.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-19
8: Alternative Method for Downloading Logs
• Clock Compensation:
• The first byte indicate if the clock compensation was enabled or disabled:
0x000
Disabled
0x001
Enabled
• The second byte of the sub-fields indicates what port was used for the
action:
0x000
internal use
0x001
PORT 1 - IR/OPTICAL PORT
0x002
LCD touch screen
0x003
ETHERNET 1
0x004
ETHERNET 2
0x005
PORT 3- RS485 - master or slave
0x006
reserved, N/A
0x007
USB only, N/A for UART
0x008
PORT 4 - RS485, master or slave
0x009
PORT 2 - UART, USB serial
0x00A-0x0FF
Undefined
• The remaining 5 bytes of the sub-fields are undefined.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
8-20
9: Additional Procedures
9: Additional Procedures
9.1: Overview
This chapter contains additional procedures related to the Modbus map.
9.2: Port Locking - Overview
At times it may be necessary for a Modbus master connected to one port of a Nexus®
meter to communicate directly to a slave device connected to a different port of the
same meter. For example, software on a computer connected to one port of a Nexus®
meter might need to change settings on an external device connected to another port
of the meter. To accommodate this need, the following steps allow a Master to control
the transmit and receive buffers of another port.
To prevent contention, only one master at a time may control a given port. This is
referred to as "Locking a Port". If Port 1 is controlling Port 4, no other ports may
control Port 4 until Port 1 is finished.
9.2.1: Sequence for Port Locking
To lock a port, follow the steps below:
1. Determine the port to which the Modbus master is currently attached (read register
65411).
2. Determine that the desired port is currently unlocked: (read registers 41730 41732).
3. Write to lock the desired port: write 0100H - 0104H to register 41729.
4. Verify that the port is successfully locked (read registers 41730 - 41732).
5. Read the current states of the pointers: registers 41733 - 41752.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
9-1
9: Additional Procedures
9.2.2: Transmission
1. Decide which transmit buffer to use, from 4 to 7, and write it to register 41753.
2. Find the current position of the TrmIn pointer: registers 41735, 41739, 41743,
41747, 41751.
3. Add bytes to the transmit buffer starting at the position indexed by the TrmIn
pointer, up to the position before that indexed by the TrmOut pointer.
4. Write the new value for the TrmIn pointer (the position after the last byte added) to
the TrmIn pointer.
9.2.3: Reception
1. Decide which receive buffer to use, from 0 to 3, and write it to register 41753.
2. Find the current position of the RecOut pointer: registers 41734, 41738, 41742,
41746, 41750.
3. Read bytes starting at the position after that indexed by the RecOut pointer, up to
the position before the position indexed by the RecIn pointer.
4. Write the new value for the RecOut pointer (the position of the last byte read) to
the RecOut pointer.
9.2.4: Port Unlocking Sequence
To unlock a port, follow the steps below:
1. Empty the receive buffer (RecOut written so it is the position before RecIn).
2. Write to unlock the desired port: write 0200H - 0204H to register 41729.
3. Verify that the port is successfully unlocked: registers 41730 - 41732.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
9-2
9: Additional Procedures
9.3: Updating Programmable Settings
Note that this procedure is included for completeness, but is not recommended for
regular customer use. The Communicator EXTTM software creates the programmable
settings file automatically when it is used to update programmable settings. That is
the recommended procedure.
1. Build the binary programmable settings block to update to the meter. All 32k of
programmable settings must be updated.
a. The programmable settings are broken into two blocks, Block 1 and Block 2,
each 16384 bytes in size.
b. Compute the CRC16 on the first 16382 bytes of Block 1. We do not include the
last two bytes, as this is where the checksum is stored.
c. Continue computing the checksum (using the previously computed checksum as
the seed), on all 16384 bytes of Block 2.
d. Place the computed checksum into the last two bytes of Block 1.
2. If Level 2 Password Protection is enabled, send the Level 2 password to allow
updating of the programmable settings. If Sealing switch is enabled, press the
Sealing switch.
3. If any changes were made to the programmable settings which affect the logs, the
logs should be cleared:
a. Lock the logs to prevent them from being updated until the meter is reset. Write
0xABCD to register 0xE052.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
9-3
9: Additional Procedures
b. Write 0xFFFF to the register listed below to reset that log.
All Logs
0xE000
Historical 1
0xE035
Historical 2
0xE036
Sequence of Events
0xE037
Digital Input
0xE038
Digital Output
0xE039
Flicker
0xE03A
Waveform
0xE03B
PQ
0xE03C
Historical 3
0xE04A
Historical 4
0xE04B
Historical 5
0xE04C
Historical 6
0xE04D
Historical 7
0xE04E
Historical 8
0xE04F
Event Triggered
0xE050
Transient
0xE051
TOU Action Log
0xE0A5
TOU Month and Season Log
0xE0A7
4. Write the programmable settings data:
NOTE: All 32k of data must be written for the programmable settings to be
updated.
a. Write Block 1 for 16384 bytes starting at register 0xB000.
b. Write Block 2 for 16384 bytes starting at register 0x6000.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
9-4
9: Additional Procedures
5. Wait for the meter to finish storing the programmable settings.
a. Read the Programmable Settings Update Status registers: 7 registers starting at
0xFFE0.
offset
0x00
0
1
Match (MSB)
2
Mode (LSB)
0x08
3
4
Error Code
Time Stamp
5
6
7
Time Stamp
Checksum
• Match: Indicates if the RAM and stored programmable settings match. 0
indicates a match, 1 indicates no match.
• Mode: Indicates if the meter is in the process of updating the programmable settings. 0 indicates the process is idle, otherwise an update is in
progress.
• Error Code:
0 No Error
1 Internal Global Flag not set
2 Buffer not ready
3 Bad Checksum
4 Internal Checks Failed
5 Could not write file header
6 Data Write Error
• Time Stamp: Nexus 8 byte time stamp
• Checksum: Checksum of the stored programmable settings.
b. If the Status mode indicates that the update is idle, check that Match indicates
that the RAM and file copies match, and that Error Code indicates No Error.
• If so, programmable settings have successfully been updated, and you
may continue.
• If not, check the Status Error Code:
- If an error is indicated, exit the update.
- If no error is indicated, continue waiting.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
9-5
9: Additional Procedures
6. If logs were reset at the beginning of the process, wait for all logs to finish resetting before continuing:
a. Query the log status register for each of the logs.
Historical 1
0x9012
Historical 2
0x9052
Historical 3
0x9E17
Historical 4
0x9E57
Historical 5
0x9E97
Historical 6
0x9ED7
Historical 7
0x9F17
Historical 8
0x9F57
Event Triggered
0x9F97
Sequence of Events (aka,
Limits, Alarms)
0x9097
Digital Inputs
0x9117
Digital Outputs
0x9197
Flicker
0x9217
Waveform
0x9242
PQ
0x9317
System Events
0x9295
Transient
0x92C2
TOU Action Log
0xA117
TOU Month and Season Log
0xA157
b.Wait until all status registers read 0.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
9-6
9: Additional Procedures
7. Send the command to reset the meter. Programmable settings do not take effect
until the meter has been reset. The Reset command is protected by the Level 2
password and the Sealing switch, if those are enabled. The meter will not process
the Reset command if it's in the middle of processing a programmable settings
update.
a. Send 0x0001 to register 0xFFFA.
b. Wait at least 30 seconds for the device to restart.
NOTE: See the Programming flowchart beginning on the next page.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E171707
9-7
9: Additional Procedures
6WDUW
&OHDULQJ/RJ V
1R
Source Exif Data:
File Type : PDF
File Type Extension : pdf
MIME Type : application/pdf
PDF Version : 1.6
Linearized : Yes
Author : Electro Industries
Create Date : 2018:03:26 12:40:03Z
Modify Date : 2018:03:26 17:06:50-04:00
Has XFA : No
Language : en
XMP Toolkit : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Format : application/pdf
Creator : Electro Industries
Title : Nexus 1450 Power Meter Modbus Manual V.1.02
Creator Tool : FrameMaker 12.0.4
Metadata Date : 2018:03:26 17:06:50-04:00
Producer : Acrobat Distiller 10.1.16 (Windows)
Document ID : uuid:b1d3be82-0661-4634-9b19-1f168fb0baff
Instance ID : uuid:1c51e97f-06eb-4142-8d8c-c0c7a46876b8
Page Mode : UseOutlines
Page Count : 472
EXIF Metadata provided by EXIF.tools