USER’S MANUAL Solar Pump Inverter 2.2kw LS

User Manual: Pdf Solar pump inverter 2.2kw LS manual

Open the PDF directly: View PDF PDF.
Page Count: 22

DownloadUSER’S MANUAL Solar Pump Inverter 2.2kw LS
Open PDF In BrowserView PDF
User Manual

2.2KW LS (Low PV Input Range)
Solar Inverter for Water Pump

Version: 1.1

Table Of Contents
ABOUT THIS MANUAL ...................................................................................................................................... 1
Purpose ............................................................................................................................................................ 1
Scope ............................................................................................................................................................... 1
SAFETY INSTRUCTIONS................................................................................................................................... 1
Inspection ......................................................................................................................................................... 1
Installation ........................................................................................................................................................ 1
Operation ......................................................................................................................................................... 2
Maintenance .................................................................................................................................................... 2
INTRODUCTION ................................................................................................................................................. 3
Features ........................................................................................................................................................... 3
Basic System Architecture ............................................................................................................................... 3
Product Overview ............................................................................................................................................. 4
INSTALLATION ................................................................................................................................................... 5
Unpacking and Inspection................................................................................................................................ 5
Preparation ...................................................................................................................................................... 5
Mounting the Unit ............................................................................................................................................. 5
PV Connection ................................................................................................................................................. 6
AC Input Connection ........................................................................................................................................ 7
AC Output (Motor) Connection ........................................................................................................................ 8
Final Assembly ................................................................................................................................................. 9
Remote Communication Connection ............................................................................................................. 10
Control Signal Connection (Optional) ............................................................................................................ 10
COMMISSIONING ............................................................................................................................................. 11
OPERATION ...................................................................................................................................................... 12
Power ON/OFF .............................................................................................................................................. 12
Operation and Display Panel ......................................................................................................................... 12
Parameter Setting .......................................................................................................................................... 13
Fault and Warning Code ................................................................................................................................. 18
Fault Reference Code .................................................................................................................................... 18
Warning Reference Codes ............................................................................................................................. 19
SPECIFICATIONS ............................................................................................................................................. 20

ABOUT THIS MANUAL
Purpose
This manual describes the assembly, installation, operation and troubleshooting of this unit. Please read
this manual carefully before installations and operations. Keep this manual for future reference.

Scope
This manual provides safety and installation guidelines as well as information on tools and wiring.

SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions. Read and
keep this manual for future reference.

Inspection

If missing components or damaged inverter is found after receiving, please do NOT install or operate it.
Otherwise, it may cause human injury or equipment damage.

Installation

1. Before installation, please make sure if the voltage range of PV panel and AC input voltage range meet the
requirement.
2. Check if all wires are firmly connected without short circuit. Otherwise, it will cause equipment damage.
3. Do NOT install this inverter under direct sunlight because high temperature may cause equipment damage.
4. Please install the inverter away from inflammable and explosive objectives. Please ensure no liquid can
enter the inverter.
5. Please install the inverter on metal non-combustible surface.

1. CAUTION!! Only qualified personnel can install and operate this inverter.
2. To reduce risk of electric shock, disconnect power source before making wire connection. Otherwise, it may
cause electrical shock.
3. To reduce risk of electric shock, NEVER touch any terminals on electric circuits.

1

Operation

1. Only after wire connection is complete and put cover back to the inverter, it’s ok to do commissioning.
Otherwise, it will cause electric shock
2. If sunlight is sufficient but little water is pumped, maybe the wires on motor connection are reversely
connected. Please reverse any two wires of them.
3. When testing water pump, be sure to install water pump at appropriate water level. Never allow water
pump in dry running. Otherwise, the inverter will activate protection.

Maintenance

1. Only qualified personnel can maintain, repair, inspect the inverter and replace any components.
2. It may still contain energy after disconnecting power source for 10 minutes. Only service the unit after the
bus voltage is within safe range.

2

INTRODUCTION
Interest in renewable energy has increased over the past few years due to solar power becoming more cost
effective and eco-friendly. This is a solar inverter which allows power to be switched from the DC power
obtained from solar panels to the AC power needed to control the pump.

With the renewable solar inverter,

pumps can adapt to solar power sources rather than traditional electrical supplies or generators.
This solar inverter is built-in with MPPT solar charger to maximize solar power. Besides, it is easy to install with
low maintenance cost. It becomes an eco-friendly solution for the rural areas where grid power is expensive
and unreliable.
Besides, this inverter also accepts single-phase AC input. It allows the inverter to automatically switch between
PV power and AC utility to guarantee water pump operation during night time.

Features


Built-in MPPT solar charger



Supports single-phase asynchronous motor or three-phase asynchronous motor



Built-in full protection and self-diagnosis



Soft start function prevents water hammer effect and extends system lifecycle



Comprehensive LCD and LEDs display real-time system status



Remote monitoring through RS-485



Supports single-phase AC input. When PV energy is not sufficient, the inverter will automatically switch
to AC input.



Optional remote panel is available.

Basic System Architecture
This solar inverter is specially designed to power water pump. The following illustration shows basic application
for this inverter. It also includes PV modules and remote float switches to have a complete running system.

3

Product Overview

1. PV input
2. Single-phase AC input
3. AC output
4. RS-485 communication port
5. RS-232 communication port
6. Signal control slot
7. Display screen (Refer to Operation and Display Panel for the details)
8. LED indicators (Refer to Operation and Display Panel for the details)
9. Operation buttons (Refer to Operation and Display Panel for the details)

4

INSTALLATION
Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should
have received the following items inside of package:
 The unit x 1
 User manual x 1
 RJ45 cable x 1
 RS-232 cable x 1

Preparation
Before connecting all wirings, please take off bottom cover by removing two screws as shown below.

Mounting the Unit
Consider the following points before selecting where to install:
 Do not mount the inverter on flammable construction
materials.
 Mount on a solid metal surface.
 Avoid direct sunlight. Be sure the environment is shady and
cool.
 Be sure to install the inverter into a box with waterproof and
dustproof.
 Install this inverter at eye level in order to allow the LCD
display to be read at all times.
 The recommended installation position is to be adhered to
the wall vertically.
 Be sure to keep other objects and surfaces as shown in the
diagram to guarantee sufficient heat dissipation and to
have enough space for removing wires.
SUITABLE FOR MOUNTING ON CONCRETE OR
OTHER NON-COMBUSTIBLE SURFACE ONLY.

5

1.

Drill four holes in the marked locations with four

2.

Install the unit by screwing four screws. It’s
recommended to use M5 screws.

screws.

PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter
and PV modules. The recommended spec of DC breaker is C16A/2P/750VDC/20KA for 2.2KW LS.
NOTE: It’s required to install PV combiner box when using several PV modules in parallel and series.

CAUTION: Important
Before making PV connection, be sure to do the following actions to prevent human injury or machine damage.
1. It’s required to turn off circuit breaker.
2. Make sure connect positive pole (+) of PV input connector in inverter to positive pole (+) of PV modules and
negative pole (-) of PV input connector in inverter to negative pole (-) of PV modules.

PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
1. Open circuit Voltage (Voc) of PV modules not exceeds max. DC voltage (450VDC).
2. Accumulated voltage of connected PV panels should be close to 330V for inverter with 220V output voltage.
To calculate PV module numbers in series (N) and in parallel (M), please follow below formula:
 For three-phase output:
 Imp>Po/(Kvo x 0.9 x M)
 For single-phase output, please use 2 times of PV power rating.
 Imp>2 x Po/(Kvo x 0.9 x M)

Po represents the rated output power.
Kvo is equal to 330V/345V/360V for 220V/230V/240V output voltage respectively.

 Maximum PV module numbers in series (N) > 330 / Vmp
We strongly recommend the total PV Vmp is around 330Vdc to get the optimum MPPT output.

6

Below are popular solar panel specifications in the market:
A. 75-A: 75W, Vmp=17.46V, Imp=4.3A, Voc=21.96V
B. 75-B: 75W, Vmp=13.3V, Imp=5.64A, Voc=16.94V
C. 140-A: 140W, Vmp=17.9V, Imp=7.82A, Voc=22.0V
D. 250-A: 250W, Vmp=30.64, Imp=8.16A, Voc=37.38V

Output type

PV Panel 75-A

PV Panel 75-B

PV Panel 140-A

PV Panel 250-A

Three-phase
output

19 pieces in Series
x 2 Strings
(2850W PV Panels)

25 pieces in Series
x 2 Strings
(3750W PV Panels)

19 pieces in Series
(2660W PV Panels)

11 pieces in Series
(2750W PV Panels)

Single-phase
output

19 pieces in Series
x 4 Strings
(5700W PV Panels)

25 pieces in Series
x 3 Strings
(5625W PV Panels)

19 pieces in Series
x 2 Strings
(5320W PV Panels)

11 pieces in Series
x 2 Strings
(5500W PV Panels)

Please follow below steps to implement PV module connection:
1. Remove insulation sleeve 10 mm for positive and negative conductors.
2. Check correct polarity of connection cable from PV modules and PV input
connectors. Then, connect positive pole (+) of connection cable to positive
pole (+) of PV input connector. Connect negative pole (-) of connection
cable to negative pole (-) of PV input connector.

3. Make sure the wires are securely connected.

AC Input Connection
CAUTION: Before connecting to AC power source, please install a separate AC circuit breaker between

inverter and AC utility. It’s recommended to use 25A/2P/230V/4500A circuit breaker.

CAUTION: Important
Before making AC input connection, be sure to do the following actions to prevent human injury or machine
damage.
1. It’s required to turn off circuit breaker.
2. Make sure to connect single-phase AC input to the L & N input connectors in inverter.
Recommended terminal types:

7

Suggested cable requirement:
Model

Typical

Wire size

Amperage

Terminal
Dimensions
d (mm)

2.2KW LS

Torque Value

22A

11 AWG

4.5

D (mm)
9.5

1.3 ~ 1.4 Nm

Please follow below steps to implement AC input connection:
1. Before making AC input connection, be sure to disconnect all circuit breakers or disconnectors first.
2. Remove insulation sleeve 10mm for two conductors. And shorten phase L and neutral conductor N 3 mm.
3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws.
L→LINE (brown or black)
N→Neutral (blue)

4. Make sure the wires are securely connected.

AC Output (Motor) Connection
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC output
connection. To reduce risk of injury, please use the proper recommended terminal and cable size as below.
Recommended terminal types:

Suggested cable requirement:
Model

Typical

Wire size

Amperage

Terminal
Dimensions
d (mm)

2.2KW LS

15A

Torque Value

13 AWG

4.5

D (mm)
9.5

1.3 ~ 1.4 Nm

Please follow below steps to implement AC output connection:
1. Remove insulation sleeve 10mm for two conductors if applying single-phase output or three conductors if
applying three-phase output. And shorten these conductor 3 mm.
2. Please follow below steps to complete output wire connection.

8

Single-phase motor connection
If applying for single-phase output application, please connect AC output U and W terminals to single-phase
motor as shown below:

Three-phase motor connection
NOTE: If sunlight or AC input is normal, but little water is pumped, maybe the output wires on motor
connection are reversely connected. Please reverse any two wires of them.
International standards for motor lead wire
US
Black (BLK)
Red (RED)
Yellow (YEL)
Ground (GND)
International
Gray (GRY)
Black (BLK)
Brown (BRN)
Ground (GND)

3. Make sure the wires are securely connected.
4. Make sure the control setting is matching the real wiring application.

Final Assembly
After connecting all wirings, please put bottom cover back by screwing two screws as shown below.

9

Remote Communication Connection
WARNING: Please do NOT mis-connect the wires between RJ45 and RS485/RS-232 converter.
First, please use one RS485 to RS 232 converter as media converter between inverter and computer. Please
follow below chart for wiring connection between RS485 on the inverter and media converter. It’s necessary to
connect to the utility as power source for the media converter. Then, use supplied RS-232 cable to connect to
converter and computer. After wiring is complete, the media converter will light on and any data transmission
occurs, the indicators for RXD and TXD will flash.

Control Signal Connection (Optional)
There are 7 ports in control signal connection. 2-port on the right side is to power supply for remote panel.
5-port on the left side is to detect water level to prevent water pump from dry running and water tank from
overflow/underflow.

Power Supply for Remote Panel
If using remote panel, please connect these two ports to supply power for remote panel. Please follow user
manual of remote panel for the detailed wire connection.
Remote float switch Detection
Control Signal Port:

Internal circuit:

10

Signal Port Status
Signal
Water
level status
Normal Level
Low Level
High Level

Remote Float Switch (1)
S1

S2

Remote Float Switch
(2)
S3

Open
Close
Open

Open
Open
Close

Close
Open
n/a

Remote float switch (1):
It’s to prevent water tank overflow or underflow by sensing a remote float switch in water tank. When water
level is normal, it will keep DI1 & COM2 and DI2 & COM2 in open status. When water level is high in water tank,
it will receive high-level signal (open status on DI1 & COM2 and closed status on DI2 & COM2) from float
switch and stop the inverter. When water tank is in low level, it will receive low-level signal (closed status on
DI1 & COM2 and open status on DI2) from float switch and start up the inverter. This action is only available
when the auto turn-on function is enabled. If the water level is normal, DI1 and COM2 are normally in open
status.
Remote float switch (2):
It’s to prevent the water pump dry running by connecting to remote float switch. The length of connecting wire
should not longer than 50m. If the water level is normal in the well, COM1 and DI3 (S3) is kept in normal close
status. If the water level is low in the well, COM1 and DI3 (S3) will be open status. If open status is detected
for COM1 and DI3 (S3), the inverter will automatically shut down in two seconds and show alarm. If closed
status is detected for COM1 and DI3 (S3) again, the inverter will automatically turn on in two seconds and clear
the alarm. And this automatic turn-on action only be effective when program P4.01 is set up as “1”. If this port
is not connected to water level probe, be sure to connect COM1 and DI3 together. It’s default setting from
factory.

COMMISSIONING
Step 1: Check the following requirements before commissioning:
 Ensure all wires are firmly and correctly connected
 Use a megger to check insulation of motor and wires
 Check if the open circuit DC voltage of PV module meets requirement

Step 2: Switch on DC breaker or AC breaker and provide power to the inverter. Then, LCD screen will show 0.00.
Please set up the parameters of the inverter such as rated power, rated frequency, rated current and rated
voltage. For the detailed setting, please check “Parameter setting” section in Operation chapter.
Step 3: Press “RUN” button to activate the inverter. If the output frequency or water yield is low, it may be
wrong for output wire connection. Please exchange any two wires connected to the motor. Please be sure the
output frequency and water yield are normal. It means the wire connection is correct and complete.

11

OPERATION
Power ON/OFF

Once the unit has been properly installed, simply press “RUN” button (located on the button area) to turn
on the unit.

Operation and Display Panel
The operation and display panel, shown in below chart, is on the top case of the inverter. It includes four
indicators, six function buttons and a display screen, indicating the operating status and input/output
power information.
LED indicators

Display screen

Function buttons

LED Indicator
LED Indicator

Messages

Hz

Green

Solid On

Output frequency value is displayed on the LCD screen.

A

Green

Solid On

Output current value is displayed on the LCD screen.

V

Green

Solid On

Output voltage value is displayed on the LCD screen.

A and V

Green

Solid on

Output power value is displayed on the LCD screen.

Green

Solid on

The inverter is running.

Green

OFF

STOP/RUN

The inverter stops.

NOTE: After the inverter is powered on, LED display will show following information in turns: current
output frequency, current output voltage, current output current, current PV voltage and current
output power. After the inverter is powered off, LED display will still show output frequency until it’s
0.
12

Function Buttons
Function Button
ESC/PROG
ENTER
RUN
STOP/RST

Description
To enter or exit setting mode.
To confirm the selection/value in setting mode.
To turn on the unit, press this button for at least 1 second.


To turn off the unit, press this button for at least 1 second.



To reset fault message, press this button for at least 1 second.

To increase the setting value.
To decrease the setting value.
and ENTER

Press these two buttons at the same time to move cursor location.

Parameter Setting
The entire display setting program structure is demonstrated as below chart.

13

Parameter setting procedure for water pump
Operation steps

Screen Display

1. Press “ESC/PROG” button for 500ms. Then, it will display “P0” in
display screen.

2. Press “ENTER” button for 500ms, display screen will show as in the
right chart.

3. Press “ENTER” button again to start to set up rated power of the water
pump. Press “ENTER” and “DOWN” buttons to switch cursor location.
Press “UP” or “DOWN” button to change value for rated power. Until it
shows correct rated power, please press “ENTER” button to confirm the
setting.

4. Press “UP” button for 500ms to switch to P0.01 program.

5. Press “ENTER” button to be able to set up rated frequency. Press
“ENTER” and “DOWN” buttons to switch cursor location. Them, press
“UP” or “DOWN” button to change value for nominal frequency. Until it
shows correct nominal frequency, please press “ENTER” button to
confirm the setting.

6. Press “UP” button for 500ms to switch to P0.02 program.

14

7. Press “ENTER” button to be able to set up nominal voltage of the water
pump. Press “ENTER” and “DOWN” buttons at the same time to switch
cursor. Then, press “UP” or “DOWN” button to change value for
nominal voltage. Until it shows correct nominal voltage, please press
“ENTER” button to confirm the setting.

8. Press “UP” button for 500ms to switch to P0.03 program.

9. Press “ENTER” button to be able to set up nominal current of the water
pump. Press “ENTER” and “DOWN” buttons to switch cursor location.
Then, press “UP” or “DOWN” button to change value for nominal
current. Until it shows correct nominal current, please press “ENTER”
button to confirm the setting.

10. Then, all parameters of water pump are set up completely. Press
“ESC/PROG” button to return to P0 level. Please press “ESC/PROG”
button again for 1 second to return to main interface.

11. Set up output setting to match the real wiring. P5.00 for setting
single-phase output or three-phase output.
12. Turn on the inverter by pressing “RUN” button. Then, RUN/STOP LED
will light up and display screen will show inverter information in turns.

CAUTION: Before turning on the inverter, be sure to the wiring connection is matching the P5.00 setting.
Otherwise, it will cause damage on the motor.
NOTE: If it’s requested to have the inverter is automatically turned on every morning, please set up program
P4.01 as “1” in standby mode.

15

Parameter Setting Table
〇: This parameter can be modified no matter the inverter is in operation or off status.

◎: This parameter can be modified only when inverter is turned off and it shows 0.00 Hz in display screen.
Program #
P0.00
P0.01

Description
Nominal power
Nominal
frequency

Setting Range
Unit
P0 Parameter settings for the motor

Default Value

Note

10-2200

W

2200

◎

50/60

Hz

50

◎

P0.02

Nominal voltage

187-264

V

220

◎

P0.03

Nominal current

0.1-60

A

14

◎

Hz

50

◎

Hz

10

◎

P0.04

P0.05

Upper limit for
frequency
Low

Setting value in
P0.05 – setting value
in P0.01

limit

for

frequency

6 – setting value in
P0.04

P1 Over-current device on the motor and torque increasing
P1.00

P1.01
P1.02
P1.03

A multiple of

Maximum

10-200

current limit
Kp

for
for

110

nominal current
〇

max.

current control
Ki

%

max.

current control
60S overload
protection

50-6000

None

1000

〇

5-1000

None

100

〇

110-250

%

150

◎

110-250

%

250

◎

0-10

%

0

Overload
P1.04

protection on
motor
Voltage

P1.05

for

torque
increasing

Percentage of
nominal voltage

P2 DC battery voltage setting
P2.00

Over DC voltage
protection
Under

P2.01

P2.01 - 450
DC

voltage
protection

P2.02

PV

reference

voltage

Setting value in

90 – Setting value in
P2.00

V

450

◎

V

90

◎

V

330

〇

Setting value in
P2.01 – setting value
in P2.00

16

Program #

Description

Setting Range

Unit

Default Value

Note

P3 Protection setting for the inverter of the water pump
P3.00
P3.01
P3.02
P3.03
P3.04
P3.05
P3.06

Sleep mode while PV
energy is weak
Sleep

mode

for

dry

running
Allow

dry

pumping

duration
Over temperature fault
on inverter
Over

10-3600

S

120

〇

10-7200

S

1200

〇

1-3600

S

5

〇

°C

85

◎

°C

75

〇

1-3600

S

20

◎

1-3600

S

20

◎

setting value in
P3.04 ~ 100

temperature 10 ~ setting value in

warning on inverter
Acceleration

P3.03

time

for

time

for

motor
Deceleration
motor

P4 Inverter operation mode setting
0:Disable.
P4.00

P4.01

MPPT function
enable/disable

Auto turn-on

Control PV voltage
in setting value of

None

1

◎

None

0

◎

None

0000

◎

None

1

〇

None

0

◎

P2.02
1:Enable
0:Disable
1:Enable
P5 Output setting

Three-phase or
P5.00

single-phase output
setting

P5.01
P5.02

Remote monitored device
ID setting
Restore to default setting

0000: Single-phase
output
1111: Three-phase
output
1 ~ 247
0:No
1:Yes

17

Fault and Warning Code
All fault and warning codes can be reset by pressing “RST” button except for A07 and A11. When faults or
warning occur, press “RST” button and the inverter will enter standby mode. Please press “RUN” button to turn
on the inverter for operation again.
After A02 or A03 warning occurs, the inverter will auto restart operation after a period of sleep mode. If
pressing “RST” button during sleep mode, please be sure to press “RUN” button again for operation.

Fault Reference Code
Fault code
E01
E02
E03

Fault type
Time out for BUS soft start
Soft start relay fault
Over voltage in output

E04

Over current in output

E05
E06

Output voltage RMS High
High PV voltage

E07

Current unbalance

E09

Over Temperature

E10

Over current.

E11

Instantaneous Bus voltage over

E12
E13
E14
E15

Current detect fault
Output voltage detect fault
NTC0 no connect
NTC1 no connect

E16
E17
E18

Output setting is wrong.
AC input relay fault.
Bus voltage over 450 VDC

Possible Cause
The resistor of soft start is broken.
The soft start relay is broken.
1. Inverter control is abnormal.
2. Detection is interfered.
1. Output short circuited.
2. The motor is suddenly locked.
3. The motor is abnormal.
Inverter control is abnormal.
1. PV input voltage is too high.
2. There is something wrong with voltage
detection circuit.
1. Output phase loss
2. Output wire is short to the earth.
3. The motor is abnormal.
1. IGBT temperature is too high
2. The wire of IGBT temperature detection is not
connected.
1. Output short circuited.
2. The motor is suddenly locked.
3. Inverter connects to single phase motor but LCD
output setting is three-phase output.
1. Pump intrusion.
2. PV voltage is too high.
Current detection circuit is abnormal.
Voltage detection circuit is abnormal.
Heatsink detected wire is not connected.
Environment temperature detected wire is not
connected.
P5.00 parameter setting is wrong.
AC input relay is broken.
1. PV voltage is too high.
2. AC input voltage is too high.

18

Warning Reference Codes
Warning code
A01

Warning type
PV input voltage is too low.

A02
A03
A04

Weak sunlight
Dry running
Motor over-temperature
protection.

A05

Output overload protection

A06
A07
A08
A09

EEPROM error
IGBT over temperature warning
Over temperature warning
Over temperature

A10

Wrong parameter setting in the
motor.
Water tank is full.
Water tank is dry.
Well is dry.
Password verification is not
complete.
AC input voltage loss
Startup on single-phase output
fails.

A11
A12
A13
A14
A15
A16

A17

Inverter overload protection.

19

Possible Cause
1. PV input voltage is too low.
2. Sunlight is too weak.
Sunlight is too weak
Water level in the well is low.
1. The motor is suddenly locked.
2. The pump head is too high.
3. Wrong current setting on the motor.
1. The motor is suddenly locked.
2. Wrong current setting on the motor.
3. Inverter connects to three-phase motor but
LCD output setting is single phase output.
There is something wrong with EEPROM circuit.
Over temperature on IGBT.
Over temperature warning
1. Environment temperature is beyond the upper
limit.
2. The wire of environment temperature
detection is not connected.
Wrong parameter setting in the motor.
Water tank is full.
No water or water in low level in the water tower.
No water or water in low level in the well.
No password is set up.
AC input voltage is abnormal.
PV power is lower than specification.
1. If this warning occurs, if AC power input is
available, the inverter will switch to AC power
input for 30 minutes. After 30 minutes, the
inverter will switch back to PV input. If there is
no AC power input available, the inverter will
be in standby mode for 30 minutes and then
re-start up. If the sun is strong and this
warning code keeps alarm, please increase
your PV module no.
2. Increase PV power.
Output power is beyond the nominal output power
of the inverter.

SPECIFICATIONS
MODEL

2.2KW LS

Rated Output Power

2200 W

Power grid or AC generator input
220/230/240V(1PH)

Nominal voltage

(-15%~+10%)

Frequency range

47-63Hz

PV INPUT (DC)
Nominal DC Voltage / Maximum

320 VDC / 450 VDC

DC Voltage
Start-up Voltage

120VDC

MPPT Voltage Range

120 VDC ~ 420VDC

Number of MPP Trackers

1

AC OUTPUT
Nominal Voltage

220/230/240V VAC

Efficiency
Nominal Output Current
Motor Type

> 97%
14 A

10 A

Single-phase motor

Three-phase asynchronous motor

Frequency Precision

± 0.2%

PROTECTION
Phase lost, dry pumping, motor locked, weak sunlight, over-voltage,
Full Protection

under-voltage, over-current, surge, over-temperature and short circuit
protection

PHYSICAL
Dimension, D X W X H (mm)

110 x 230 x 342

Net Weight (kgs)

5

Type of Mechanical Protection

IP20

INTERACE
Communication Port

RS-232/RS-485

ENVIRONMENT
Humidity
Operating Temperature

< 95% RH (No condensing)
-20°C~45°C at 100% full load,

20

46°C~60°C power derating



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Encryption                      : Standard V4.4 (128-bit)
User Access                     : Print, Extract, Print high-res
Author                          : e2017256
Create Date                     : 2017:11:01 17:59:59+08:00
Modify Date                     : 2017:11:02 10:02:33+08:00
Language                        : zh-TW
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Format                          : application/pdf
Creator                         : e2017256
Title                           : USER’S MANUAL
Creator Tool                    : Microsoft® Word 2013
Metadata Date                   : 2017:11:02 10:02:33+08:00
Producer                        : Microsoft® Word 2013
Document ID                     : uuid:d6caed3c-f940-4e0d-a03e-514735f50c57
Instance ID                     : uuid:86af36f7-ebc9-4707-a2bb-f2be0a1974ad
Page Count                      : 22
EXIF Metadata provided by EXIF.tools

Navigation menu