Installation Instructions
ACX 57xx Series Controller
© 2010 Schneider Electric, all rights reserved.
Controller Installation (Models 5740 and 5720)
To install the controller, follow these steps:
1. Mount the controller to a panel using screws. (See the
“Physical Dimensions” sections of this document.)
NOTE: Read the “Wiring Rules” section of this document
before performing the next steps. Do not apply power
to the controller until all connections are secured.
2. Connect the Ethernet, Service Port, and RS- 485 connec-
tions based on your requirements. (See the “Ethernet,
Service Port and Comm Port Connections” section of this
document.)
3. Connect the Tamper, Universal Inputs, Card Reader/Key-
pad, and Form C Digital Output connections based on
your requirements. (See the corresponding sections of this
document.)
4. (Optional) Connect the Expansion Modules based on your
requirements. (See the xP Expansion Module Reference, 30-
3001-840 and/or the xPB Expansion Module Reference,
30-3001-883.)
5. Connect the power supply connector of the controller to a
UL Listed UL 294 or UL 603 power limited power supply.
Access the PC board and connect the battery. (See the “DC
Power and Battery Backup Connections” section.)
6. Apply power to the ACX 57xx Series controller.
7. Congure the controller using the controllers embedded
WebServer pages and CyberStation. For more information,
refer to the “Related Documentation” section at the end of
this document.
30-3001-998
Rev D.1
EXP PORT PWR
AC POWER
24 VAC
90 VA
50/60 HZ
RX
CPU
TX
+
-
SHLD
IN
RTN
RS- 485
ETHERNET
10/100
BASE T
1
2
3
4
5
6
7
8
10 IN 1
12 IN 2
14 RTN
16 IN 3
18 IN 4
20 RTN
22 IN 5
24 IN 6
26 RTN
9 I N 7
11 IN 8
15 IN 9
13 RTN
17 IN 10
21 IN 11
23 IN 12
19 RTN
25 RTN
360mA
N
L
-
+
DC POWER
12-28 VDC
50W
TAMPER
SERVICE PORT
UNIVERSAL INPUTS
27
29
31
33
35
37
39
41
43
45
47
49
3
4
28
30
32
34
36
38
40
42
44
46
48
50
1
2
PWR
GND
1-DATA
0-CLK
LED1
LED2
PWR
GND
1-DATA
0-CLK
LED1
LED2
24VDC
CLEAR
MEMORY
1
2
3
4
73
71
69
67
65
63
61
59
57
55
53
51
7
8
74
72
70
68
66
64
62
60
58
56
54
52
5
6
PWR
GND
1-DATA
0-CLK
LED1
LED2
PWR
GND
1-DATA
0-CLK
LED1
LED2
75
76
77
78
79
80
81
82
83
84
85
86
DIGITAL OUTPUTS
CONTACT RATING:
24VAC , 3A
30VDC , 3A
OFF AUTO ON
OFF AUTO ON
OFF AUTO ON
OFF AUTO ON
1
2
3
4
CARD
READERS
5VDC , 120mA
OR
12VDC , 180mA
POWER RATING
Tamper
Universal
Inputs
Card
Readers
Expansion Modules
Card
Readers
Form C
Digital
Outputs
9
50
Service
Port
Ethernet
RS 485
Power
Supply
Cover Tab
Cover Tab
NOTE: The illustration shows a
5740 Series Model. The 5720 Series
contains only 8 Universal Inputs, 4 Card
Readers, and 2 Form C Digital Outputs.
Caution: Use care when moving and
replacing the cover to avoid damaging
components. To remove the cover, press
the right side cover tab, lift up slightly
and carefully free the left side. Reverse
the order to replace the cover.
Wiring Rules
Grounding the Controller
To insure proper operation of the controller, the power supply must be
connected to a good earth ground.
Inspecting the Ground
Be sure to have your grounds inspected before you begin the installa-
tion process.
Check your grounds as follows:
Inspect the building power distribution panel for earth-ground termina-
tion. If the ground termination is any of the following, it is not adequate
and must be corrected:
• Does not exist
• Is connected to a corroded or galvinized pipe
• Is connected using a small gauge wire (less than 14 AWG).
Be sure your Andover Continuum cabinet is connected to the ground
with a copper conductor that terminates at the distribution panel. For
more information, see the “Related Documentation” section at the end
of this document.
These modules are intended for installation
within the UL Listed enclosure UL-ENCL for
UL 294 and UL 1076.
For reliable operation, follow these wiring guidelines:
• Never lay wires across the surface of a printed circuit board.
• Use shielded wire.
• Terminate the shield of the wires at one end of the run
only — preferably at the end where your ACX controller is
located.
When stripping wire, be careful not to drop small pieces of wire
inside the cabinet.
• Don’t run your wiring in the same conduit with
AC power.
• Don’t run your wiring in the same conduit with your
output wiring.
Caution: Earth ground ( ) must be connected to
avoid module damage.
Physical Dimensions
8.25"
209.6 mm
9.5"
241.3 mm
2.25"
57.2 mm
7.662"
194.615 mm
8.912"
226.365 mm
Power Supply and Battery Backup Connection
DC Power Supply Connections
50W
90
AC Power Supply Connections*
50
90
Warning
* This method is not evaluated by UL.
Power Supply and Battery Backup Connection (Continued)
During shipment the internal battery pack has been disconnected to prevent it from draining prior to installation.
To activate the battery:
1. Locate the plastic tabs on the side panel of the controller. (See illustration on the rst page of this document.)
2. Using your ngers, gently depress the right tab while lifting the cover. Remove the cover to access the main circuit board.
3. Connect the battery connector into the receptacle as shown in the illustration below.
Internal Battery Connection
Ethernet, Service Port and Comm Port Connections
ETHERNET
Ethernet Cable w/
RJ-45 Connector
Service Port RS-485 4-pin connector
RoamIO2
RS-485 Connector +
Shield
1 3
Innet eld bus can be congured on
the RS-485 port
Cabinet Tamper Input Connections
The cabinet tamper input connects to cabinet tamper switches located on the cabinet door and wall. When the cabinet
tamper input changes, the CabinetTamper system variable is updated and an access event is sent to CyberStation.
Cabinet
Tamper
Input
IN
12
RTN
Universal Input Connections
Each universal input connector contains six inputs as illustrated below. Each input can be operated as a supervised or general purpose Universal
Input. (Each input must be congured as a supervised input for UL 1076.) You can assign any input to any door or reader for any function, includ-
ing: Door Switch input, Request to Exit (REX), Alternate Door Access (ADA) REX Input, Bond Sensor input, and ADA Entry Request input.
Universal
Inputs
IN1
IN2
RTN
RTN
RTN
IN3
IN4
IN5
IN6
NOTE: DIP Switches (under the cover)
allow you to select whether or not you
want a pull-up resistor in the circuit.
Default is set to ON for general use.
5
6
Supervised Input Connection Wiring
RTN
Contact
Closure
External
Resistor
10 K
Normally Closed (NC) Series
INx
RTN
Contact
Closure
External
Resistors
10 K
Normally Closed (NC) Series Parallel
INx
RTN
Contact
Closure
External
Resistors
10 K
Normally Open (NO) Series Parallel
INx
Card Reader/Keypad Connections
Each card reader/keypad connector contains two inputs as illustrated below. Each reader input can be connected to a card reader, dedicated key-
pad, or a reader/keypad combination. A Keyboard Interface Module (KIM*) is required to connect separate reader and keypad devices on the same
reader input. Card reader voltage selection (+5 VDC or +12 VDC) and card reader type (CK34 or ABA/Wiegand*) are jumper selectable. The
jumpers are located near the card reader connectors (under the cover) on the main board.
* KIM and card reader types CK34 and ABA/Wiegand are not evaluated by UL.
Card Reader/
Keypad Inputs PWR
PWR
GND
GND
DATA1
DATA1
CLK0
CLK0
LED1
LED1
LED2
LED2
Card
Reader2
Card
Reader1
Card Reader Jumper Settings
Connecting a Single Card Reader
DATA / I
GND
CLK / 0
LED1
PWR (+5 VDC or +12 VDC
Set by Voltage Jumper)
DATA I
GND
DATA 0
LED1
PWR
Weigand
Reader
or
Reader with Keypad
LED2
LED2
Voltage 1 Voltage 3
Volyage 2 Voltage 4
Type 1
Type 3
Type 2
Type 4
Voltage 7 Voltage 5
Voltage 8 Voltage 6
Type 5
Type 7
Type 6
Type 8
Card Reader
Jumper Settings
Card Readers
5 - 8
Card Readers
1 - 4
Card Reader Voltage
(Single Pin) +5VDC
(Default)
+12VDC
Card Reader Type
(Double Pin) ABA or Wiegand
(Default)
Card Key (CK34)
WRONG!
Connecting Two Readers or a Keypad and a Reader
With the addition of the Keypad Interface Module (KIM*), the controller can interface to both a keypad and a reader simultaneously. This assumes
that they are both Wiegand devices of similar voltage range. The KIM module presents the ACX controller with one pair of signals.
DATA 0
GND
DATA 1
LED
PWR
Wiegand Reader
or
Reader with Keypad
or Keypad only
DATA / I
GND
CLK / 0
LED
PWR
(Set by
Voltage
Jumper)
GND
LED
PWR
DATA / I
CLK / 0
P1
DATA / I
DATA / 0
DATA / I
DATA / 0
P2
P3
Keypad Interface Module*
DATA 0
DATA 1
Wiegand Reader
or
Reader with Keypad
or Keypad only
ACX 57xx
* This KIM configuration is not evaluated by UL.
Card Reader/Keypad Connections (Continued)
Card Reader/Keypad Connections (Continued)
Connecting a CardKey Reader*
You can connect a CardKey reader directly to the ACX 57xx controller, however, the CardKey reader requires a +12 VDC supply for the red and
green lamps. NOTE: In the illustration below, the PWR input from the controller is set to +5 VDC using the Card Reader Voltage jumper, and the
Card Reader Type jumper is set to CK34.
* This conguration is not evaluated by UL.
ACX 57xx
+5 VDC
Form C Digital Output Connections
The ACX 57xx Series controller includes either two (ACX 5720 model) or four (ACX 5740 model) Form C single-pole double-throw relay out-
puts. Form C relays contain both a normally open (NO) and a normally closed (NC) output. These output contacts operate as a standard relay, as
described in the “Relay Operation” text box. The illustration below is a simplied schematic of each output channel.
OUTx NC
OUTx COM
OUTx NO
Relay Operation:
When the output is set to ON:
NO contacts close
NC contacts open
Form C Digital Output Connections (Continued)
Wiring Door Outputs (NO Circuit)
The illustration below represents a typical door output installation when the circuit is normally open (NO). The gure shows a normally
de-energized lock (when secured) in a fail secure mode. Always be sure to use “panic” hardware that allows emergency exit from the secured area.
Note the location of the metal oxide varistor (MOV) and the Door Strike electric locking mechanism.
C
12 or 24 VDC
MOV
(TAC #01-2020-095)
UL Listed Door Strike
Power Supply
(UL Listed power limited power supply)
Wiring Door Outputs (NC Circuit)
The illustration below represents a typical door output installation when the circuit is normally closed (NC). The gure shows a normally
de-energized lock (when secured) in a fail safe mode. If a power loss occurs, the lock opens. Note the location of the metal oxide varistor (MOV)
and the electromagnetic door lock.
C
12 or 24 VDC
MOV
(TAC #01-2020-095)
UL Listed Electromagnetic
Door Lock
Power Supply
(UL Listed power limited power supply)
Dimensions
8.25” W x 9.5” L x 2.25” H (209.6 x 241.3 x 57.2 mm)
Weight
1.73 lbs. (0.78 kg)
Enclosure Type
UL open class, ammability rating of UL94-5V, IP 10
Mounting
Andover Continuum UL Listed model UL-ENCL is available for UL
294 and UL 1076.
Operating Environment
Temperature: 32o to 122o F (0o to 50o C)
Humidity: 10 to 90% RH, non-condensing
Input Power
12–28VDC @ 50W
24VAC @ 90VA, 50/60 Hz.
Universal Input Voltage Range
0-5 V
Internal Battery
NiMH, 3.6 VDC, 800 mAh
Real Time Clock
Battery-backed by an internal battery.
Ethernet LAN Interface
10/100 Ethernet: Ethernet cable with RJ-45 connector.
Serial Comm. Interface
One programmable port, software congurable as a wireless adapter,
RoamIO2 or third-party system. Innet can be congured on the
RS-485 port.
Service Port
RS-485, 3-Pin connector
Innet Bus Length
4,000 ft (1,220m) standard for Innet using approved shielded, twisted
pair, low capacitance cable. InLink module allows extensions to
longer distances.
Input Connections
ACX 57xx Series inputs types include: cabinet tamper, universal
inputs, and card reader/keypad.
Cabinet tamper: 2-pin connector for cabinet tamper switches located
on the cabinet door and wall.
Universal inputs: 6 (572x models) or 12 (574x models) universal
inputs that can be operated as a supervised or general purpose UI.
Alarm Inputs: 6 (572x models) or 12 (574x models) supervised
inputs. Single or double resistor supervision, series or parallel.
Input Protection: Transient voltage suppressor (TVS) on each input .
Card Reader/Keypad: 4 (572x models) or 8 (574x models) inputs.
Each input can be connected to a card reader, dedicated keypad, or
reader/keypad combination.
Card Reader/Keypad
Card Reader Type: Wiegand, ABA, or CardKey (jumper selectable)
Max Number of bits/Card: Up to 260 bits/card for FIPS (UL evaluated
for up to 37 bits - Wiegand only)
Card Reader Power: +5 VDC @ 120 mA or +12 VDC @ 180 mA
max power (jumper selectable)
Wiring Distance: (500 ft. (152.4 m) max. using 18 AWG)
(Card Reader to ACX) (200 ft. (60.96 m) max using 22 AWG)
Door Output Connections
ACX 57xx Series output types include: 2 (572x models) or 4 (574x mod-
els) Form C relays with a manual Override switch.
Door Outputs: Up to 4 Form C relays
Output Rating: 24 VAC/30 VDC @ 3 Amp
Reader LED Output: (2) each, open collector; up to 100 mA
Output Protection: 5000 V isolation 270 V MOVs on each output.
Overrides: 3-position manual override switch on each output for
manual control of relay. LED override status indicator.
Power and Communications Connections
Power: 3-position connector on left side of module for connection to a
power supply.
xP Power: 6-pin connector, 24 VDC 360 mA
Ethernet: RJ-45 connector for 10/100 Ethernet.
Service port: 4-pin connector for ROAM I/O2 or Wireless Adapter
RS-485: 3-pin connector for Innet eld bus.
Status Indicator LEDs
System: CPU
RS-485: TX, RX
Ethernet: ACT/LINK, 10/100 Mbps
xP Pwr: Expansion module 24 VDC power
Push Button Switches
Clear Memory: RESET/Clear Memory
Reset IP Address: (On PC board) Resets Network address settings in
ash memory and restores all non-volatile settings to
factory defaults.
DIP Switches
Universal Inputs, 10 KOhm pull-up disable/enable
Specications
Conguring the ACX 57xx Series Controller
(NOTE: Check with your system administrator for assistance.)
1. Disable the DHCP Services on your PC.
2. Disconnect your computer from the network and set your IP
address to 169.254.1.2 and your subnet mask to 255.255.0.0.
3. Using a CAT5 cable (straight-through or crossover), connect
the PC Ethernet port to the ACX 57xx Ethernet port.
4. Run your web browser, then go to URL: http://169.254.1.1 to
display the Andover Continuum Embedded WebServer page in the
ACX 57xx Series controller.
5. Select Controller Conguration from the WebServer page.
6. Log on using the default Andover Continuum user name and
password.
7. Enter relevant conguration parameters on the WebServer
Conguration web pages.
8. After entering the parameters, click the Commit Changes/Restart
Controller button on the WebServer page. (Restore the PC, and
connect the controller to the network when it reboots.)
For more information, please see the online help in the NetController II
embedded web pages and the “Related Documentation” section at the
end of this document.
Federal Communications Commission
FCC Rules and Regulations CFR 47, Part 15, Class A
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference.
(2) This device must accept any interference received, including interference that may cause undesired operation.
Caution: The user that changes or makes modications not expressly approved by Schneider Electric for compliance could void the user’s author-
ity to operate the equipment.
Industry Canada
ICES-003
This is a Class A digital device that meets all requirements of the Canadian Interference Causing Equipment Regulations.
CE - Compliance to European Union (EU)
89/336/EEC - EMC Directive
This equipment complies with the rules of the Ofcial Journal of the European Union specied in the EMC directive
89/336/EEC governing the Self Declaration of the CE Marking for the European Union.
C-Tick (Australian Communications Authority (ACA))
AS/NZS 3548
This equipment carries the C-Tick label and complies with EMC and radio communications regulations of the Australian Communications Author-
ity (ACA), governing the Australian and New Zealand (AS/NZS) communities.
WEEE - Directive of the European Union (EU)
This equipment and its packaging carry the waste of electrical and electronic equipment (WEEE) label, in compliance with European Union (EU)
Directive 2002/96/EC, governing the disposal and recycling of electrical and electronic equipment in the European community.
UL 916 Listed product for the United States and Canada, Open Energy Management Equipment
Regulatory Notices
Document Document Number
ACX 57xx Series Operation and Technical Reference Guide 30-3001-999
Network Security Conguration Guide 30-3001-996
Andover Continuum CyberStation Access Control Essentials
Guide
30-3001-405
Andover Continuum CyberStation online help
Related Documentation
CUS
58B2
The following related documentation provides more information on Andover Continuum products.
These documents are neither required nor evaluated by Underwriters Laboratories (UL) for UL Listings.
UL 294 (Access Control System Unit Subassemblies for the United States) and UL 1076 (Proprietary
Burglar Alarm System Unit Subassemblies for the United States) and C22.2 No. 205-M1893 (Signal
Equipment for Canada)
Note: Refer to the UL Listed Access Control Propietary Burglar Alarm System installation manual (the UL 294 Access Control and UL 1076 Propri-
etary Burglar Alarm Systems Reference, 30-3001-504) for specific wiring, operation, and compatibility information.
Schneider Electric
One High Street
North Andover, MA 01845
(978) 975-9600
Fax: (978) 975-9782
http://www.schneider-electric.com
Page 1 of 12 - Ftp://ftp.zenex.pl/katalogi/schneider/5_systemy_automatyki_i_bezpieczenstwa_w_budynkach/5_1_andover_continuum/pdf/instrukcje_materialy_techniczne/acx_57xx_series_controller_installation_instructions.en Acx 57xx Series Controller Installation Instructions.en
Page 2 of 12 - Ftp://ftp.zenex.pl/katalogi/schneider/5_systemy_automatyki_i_bezpieczenstwa_w_budynkach/5_1_andover_continuum/pdf/instrukcje_materialy_techniczne/acx_57xx_series_controller_installation_instructions.en Acx 57xx Series Controller Installation Instructions.en
Page 3 of 12 - Ftp://ftp.zenex.pl/katalogi/schneider/5_systemy_automatyki_i_bezpieczenstwa_w_budynkach/5_1_andover_continuum/pdf/instrukcje_materialy_techniczne/acx_57xx_series_controller_installation_instructions.en Acx 57xx Series Controller Installation Instructions.en
Page 4 of 12 - Ftp://ftp.zenex.pl/katalogi/schneider/5_systemy_automatyki_i_bezpieczenstwa_w_budynkach/5_1_andover_continuum/pdf/instrukcje_materialy_techniczne/acx_57xx_series_controller_installation_instructions.en Acx 57xx Series Controller Installation Instructions.en
Page 5 of 12 - Ftp://ftp.zenex.pl/katalogi/schneider/5_systemy_automatyki_i_bezpieczenstwa_w_budynkach/5_1_andover_continuum/pdf/instrukcje_materialy_techniczne/acx_57xx_series_controller_installation_instructions.en Acx 57xx Series Controller Installation Instructions.en
Page 6 of 12 - Ftp://ftp.zenex.pl/katalogi/schneider/5_systemy_automatyki_i_bezpieczenstwa_w_budynkach/5_1_andover_continuum/pdf/instrukcje_materialy_techniczne/acx_57xx_series_controller_installation_instructions.en Acx 57xx Series Controller Installation Instructions.en
Page 7 of 12 - Ftp://ftp.zenex.pl/katalogi/schneider/5_systemy_automatyki_i_bezpieczenstwa_w_budynkach/5_1_andover_continuum/pdf/instrukcje_materialy_techniczne/acx_57xx_series_controller_installation_instructions.en Acx 57xx Series Controller Installation Instructions.en
Page 8 of 12 - Ftp://ftp.zenex.pl/katalogi/schneider/5_systemy_automatyki_i_bezpieczenstwa_w_budynkach/5_1_andover_continuum/pdf/instrukcje_materialy_techniczne/acx_57xx_series_controller_installation_instructions.en Acx 57xx Series Controller Installation Instructions.en
Page 9 of 12 - Ftp://ftp.zenex.pl/katalogi/schneider/5_systemy_automatyki_i_bezpieczenstwa_w_budynkach/5_1_andover_continuum/pdf/instrukcje_materialy_techniczne/acx_57xx_series_controller_installation_instructions.en Acx 57xx Series Controller Installation Instructions.en
Page 10 of 12 - Ftp://ftp.zenex.pl/katalogi/schneider/5_systemy_automatyki_i_bezpieczenstwa_w_budynkach/5_1_andover_continuum/pdf/instrukcje_materialy_techniczne/acx_57xx_series_controller_installation_instructions.en Acx 57xx Series Controller Installation Instructions.en
Page 11 of 12 - Ftp://ftp.zenex.pl/katalogi/schneider/5_systemy_automatyki_i_bezpieczenstwa_w_budynkach/5_1_andover_continuum/pdf/instrukcje_materialy_techniczne/acx_57xx_series_controller_installation_instructions.en Acx 57xx Series Controller Installation Instructions.en
Page 12 of 12 - Ftp://ftp.zenex.pl/katalogi/schneider/5_systemy_automatyki_i_bezpieczenstwa_w_budynkach/5_1_andover_continuum/pdf/instrukcje_materialy_techniczne/acx_57xx_series_controller_installation_instructions.en Acx 57xx Series Controller Installation Instructions.en

Navigation menu