Installation Instructions 30-3001-502 Rev C CX9702 SiteController Mounting Screw N 2 1. Disable DHCP; set the IP address of your PC to 169.254.1.2 2. Connect Crossover cable from Ethernet port to the PC 3. Run Web Browser. Go to url: http://169.254.1.1/main 4. Logon using default Andover Controls username, password 5. Enter parameters on web screen L 3 TO RESET IP ADDRESS to DEFAULT 169.254.1.1 Remove Cover Press and hold IP button until the CPU light illuminates steady on The controller is now reset to its factory default condition Reconfigure as indicated above FUSE F2 250 VAC 1.5 A CAUTION (L) MORE THAN ONE DISCONNECT SWITCH MAY BE REQUIRED TO DE-ENERGIZE THIS EQUIPMENT BEFORE SERVICING. 4 + 12V OR 24VDC 5 24VDC 12VDC @ 100mA - IN1 7 IN2 8 RET 9 IN3 10 IN4 INTERNAL ON INPUT REFERENCE RESISTOR NC LOCK C C NO NO RET RET + PS - 16 IN8 Optional: Required for lock voltage feedback and internal MOV protection. NCSeries NCSerPar 10K OHM RESISTOR KIM Board Required to parallel Keypads with Readers D A T A / 1 C L K / 0 L E D 2 22 23 L E D 1 P W R G N D 18 19 20 21 RS-485 STATUS RS-485 CHANNEL 2 RET 43 LOCK2 AC PWR SERVICE PORT TD FUSE F7 125 VAC 3.5 A LOCK 2 POWER SOURCE RS-232 STATUS OFF AUTO ON INTERNAL EXTERNAL P W R G N D D A T A / 1 C L K / 0 L E D 1 L E D 2 24 25 26 27 28 29 30 31 32 RD + ONLINE SHLD RD ETHERNET 10/100 MB OUT3 RTS OUT 3 DCD OUTPUT OVERRIDE OUT 4 45 NO 44 SYSTEM STATUS CPU DTR CTS DCD RTS GND RD DSR TXD 12VDC 5VDC OUTPUTS NC 46 C LOCK1 CABLE TYPE: 22-24 AWG, twisted pair, shielded 100-120 ohm Impedance <12.5pF between conductors NOSerPar 10K OHM RESISTORS 10K OHM RESISTORS READERS/KEYPADS @180 mA @120 mA FUSE F6 125 VAC 3.5 A LOCK 1 POWER SOURCE EXTERNAL RS-485 RECOMMENDED SUPERVISED INPUT TYPES CHANNEL 1 OUTPUT CONTACTS INTERNAL 17 RET CLASS 2 READER POWER 12VDC 24VDC @1 A @300 mA LOCK 2 PWR LOCK NC 42 C 41 NO 40 RET 39 NC 38 C 37 Outputs (2 Door Locks, 2 General) NO 36 NC 35 OUT4 1 2 3 4 5 6 7 8 14 RET 15 IN7 Battery Connector 12VDC 24VDC Jumper Installed DISCONNECT AC POWER BEFORE CHANGING ANY CLASS 2 POWER SELECTION JUMPER S U P E R V I S E D Mounting Screw 24VAC/ 30VDC @3 A 10K OFF LOCK 1 PWR 12 IN5 13 IN6 + INTERNAL EXTERNAL 5.12V 11 RET Inputs (4 Universal, 4 Supervised) Jumper Installed NC IN1 IN2 IN3 IN4 OFF ON LOCK POWER SOURCE EXTERNAL RESET IP BUTTON UNDER COVER U N I V E R S A L - 47 Each Lock INPUTS 6 48 CLASS 2 INTERNAL LOCK POWER TYPICAL LOCK OUTPUT CONNECTIONS LOCK POWER SOURCE CLEAR MEMORY 0-5VDC 12VDC CX (N) CLASS 2 REX / AUX POWER REX/AUX Power Connector BATTERY For help entering parameters on web screen, invoke Help page from the web screen. USE COPPER CONDUCTORS ONLY AC Power Supply Connector FUSE F1 125 VAC 5 A CONFIGURATION / SETUP AC POWER 115-230 VAC 115 VA 50/60 HZ 1 C 34 NO 33 RS-232 OFF AUTO ON ACTIVITY Mounting Screw LINK Mounting Screw Reader Inputs Ethernet Port RS-232 RJ485 Connector Connector Service Port Controller Installation To install the controller, follow these steps: 1. Mount the controller in an enclosure or to a panel using screws. (See the “Physical Dimensions and Mounting” section of this document.) NOTE: Read the “Wiring Rules” section of this document before performing the next steps. Do not apply power to the controller until all connections are secured. 2. Connect the AC power supply connector of the controller to a standard 115V three-prong power cord. 3. Locate the REX/AUX power connector and jumpers. Configure the jumper to indicate either 12 or 24 VDC. (See the “Power Connections” section of this document for jumper settings.) 4. Locate the battery connector block and connect the battery to the corresponding terminals. (See the “Power Connections” section of this document.) 5. Connect the Ethernet and Communication Port connections based on your requirements. (See the “Ethernet and Comm Port Connections” section of this document.) 6. Connect the Universal Inputs, Card Reader/Keypad, and Form C Digital Output connections based on your requirements. (See the corresponding sections of this document.) 7. Apply power to the CX9702 controller. 8. Configure the controller using the controller’s embedded WebServer pages and CyberStation online help topics. © 2010 Schneider Electric., all rights reserved. Physical Dimensions and Mounting 10.34” (263 mm) 2.08” (53 mm) .30” 9.75” (8 mm) (247.7mm) 2 N 3 L 1. Disable DHCP, set the IP address of your PC to 169.254.1.2 2. Connect Crossover cable from Ethernet port to a PC 3. Run Web Browser. Go to url: http://169.254.1.1 4. Logon using default Andover Controls username, password 5. Enter parameters on web screen CAUTION (L) MORE THAN ONE DISCONNECT SWITCH MAY BE REQUIRED TO DE-ENERGIZE THIS EQUIPMENT BEFORE SERVICING. 5 24VDC @ 100mA 0-5VDC 8.00” (203.2 mm) IN1 7 IN2 8 RET 9 IN3 10 IN4 11 RET 12 IN5 IN6 13 14 RET 15 IN7 16 IN8 17 IN1 IN2 IN3 IN4 LOCK POWER SOURCE INTERNAL INTERNAL EXTERNAL EXTERNAL NC NC LOCK 5.12V C C NO NO RET RET ON INPUT REFERENCE RESISTOR LOCK FUSE F6 125 VAC 3.5 A LOCK 1 POWER SOURCE S U P E R V I S E D NC 46 EXTERNAL C NCSeries NCSerPar 10K OHM RESISTOR 10K OHM RESISTORS KIM Board Required to parallel Keypads with Readers RS-485 STATUS RS-485 CHANNEL 2 CPU AC PWR SERVICE PORT RET 43 SYSTEM STATUS CABLE TYPE: 22-24 AWG, twisted pair, shielded 100-120 ohm Impedance <12.5pF between conductors NOSerPar 10K OHM RESISTORS RS-232 STATUS TD LOCK2 NC 42 FUSE F7 125 VAC 3.5 A LOCK 2 POWER SOURCE INTERNAL OFF AUTO ON EXTERNAL 30 31 32 G N D D A T A / 1 C L K / 0 L E D 1 L E D 2 P W R G N D D A T A / 1 C L K / 0 L E D 1 L E D 2 18 19 20 21 22 23 24 25 26 27 28 29 + SHLD RD ONLINE RD RTS OUT 3 DCD OUTPUT OVERRIDE ETHERNET 10/100 MB OUT 4 45 NO 44 RS-485 RECOMMENDED SUPERVISED INPUT TYPES CHANNEL 1 OUTPUTS INTERNAL P W R 5VDC OUTPUT CONTACTS 24VAC/ 30VDC @3 A - PS DCD CTS DCD RTS GND RD DSR TXD 12VDC LOCK 2 PWR 24VDC LOCK1 READERS/KEYPADS @180 mA @120 mA 24VDC 12VDC @1 A @300 mA 12VDC DISCONNECT AC POWER BEFORE CHANGING ANY CLASS 2 POWER SELECTION JUMPER RET CLASS 2 READER POWER + LOCK 1 PWR 10K OFF OFF ON Each Lock LOCK POWER SOURCE RESET IP BUTTON UNDER COVER U N I V E R S A L CLASS 2 INTERNAL LOCK POWER TYPICAL LOCK OUTPUT CONNECTIONS CLEAR MEMORY INPUTS 6 + SiteController 12VDC 12V OR 24VDC - - 47 CX (N) CLASS 2 REX / AUX POWER + 48 OUT3 C 41 NO 40 RET 39 NC 38 C 37 NO 36 NC 35 OUT4 C 34 1 2 3 4 5 6 7 8 4 12VDC TO RESET IP ADDRESS to DEFAULT 169.254.1.1 Remove Cover Press and hold IP button while momentarily pressing Clear Memory button Release IP button when CPU light blinks 3 times Reconfigure as indicated above FUSE F2 1.5 A 250 VAC (225 mm) BATTERY For Help entering parameters into the web screen, click the Help button USE COPPER CONDUCTORS ONLY 8.87” FUSE F1 5A 250 VAC CONFIGURATION / SETUP AC POWER 115/230 VA C 115 VA 50/60 HZ 1 NO 33 RS-232 OFF AUTO ON ACTIVITY .44” (11 mm) 4x .187” (4.75 mm) LINK Note: This open class product must be installed in a NEMA Type 1 enclosure. Wiring Rules These modules are intended for installation within the enclosure of another product with a minimum NEMA 1 rating or IP10 equivalent. For reliable input operation, follow these input wiring guidelines: • Never lay wires across the surface of a printed circuit board. • Wires should never be within 1” or 25 mm of any component on a printed circuit board. • Use shielded input wire. • Terminate the shield of the input wires at one end of the run only — preferably at the end where your I/O module is located. • When stripping wire, be careful not to drop small pieces of wire inside the cabinet. • Don’t run your input wiring in the same conduit with AC power. • Don’t run your input wiring in the same conduit with your output wiring. Grounding the Controller To insure proper operation of the controller, it must be connected to a good Earth ground. The connection must be made as close to the module as possible. Inspecting the Ground Be sure to have your grounds inspected before you begin the installation process. Check your grounds as follows: Inspect the building power distribution panel for Earth-ground termination. If the ground termination is any of the following, it is not adequate and must be corrected: • Does not exist • Is connected to a corroded or galvanized pipe • Is connected using a small gauge wire (less than 14 AWG). Be sure your Andover Continuum cabinet is connected to the ground with a copper conductor that terminates at the distribution panel. Power Connections Battery Back-Up Connection AC Power Supply Connections 115-230 VAC ~ 115 VA 50/60 HZ Battery N 115 Volts AC Power L Note: Schneider Electric Battery part number: 01-2100-423 (12V/7.0 AHr lead-acid battery) Back-up duration expandable by use of greater amp-hour batteries. REX/AUX Power Connection Jumper selectable 12V or 24V DC @ 100mA Jumper Settings 24VDC 12VDC Ethernet and Comm Port Connections Ethernet Cable w/ RJ-45 Connector Service Port RS-485 4-pin connector Ethernet For use with the RoamIO2 1 RS-485 Connector + Shield 3 1 RS-232 Connector DTR CTS DCD RTS Ground RD DSR TXD 8 Universal Input Connections Each universal input connector contains four inputs as illustrated below. Each input can be operated as a supervised or general purpose Universal Input. You can assign any input to any door or reader for any function, including: Door Switch input, Request to Exit (REX), Alternate Door Access (ADA) REX Input, Bond Sensor input, and ADA Entry Request input. Universal Inputs NOTE: DIP Switches allow you to select whether or not you want a pull-up resistor in the circuit. Default is set to “ON” for general use. To utilize one of these inputs as a supervised input, the DIP switch must be set to the “ON” Position. IN1 IN2 RTN IN3 IN4 RTN Supervised Input Connections Four supervised inputs can be used for closure contacts such as relays or switches. They provide connection of conventional normally open or normally closed contacts to the CX9702 SiteController. One or more 10K Ohm resistors must be placed across the input as shown below. Supervised IN5 Inputs IN6 RTN IN7 IN8 RTN Supervised Input Connection Wiring Normally Closed (NC) Series Parallel Normally Closed (NC) Series External Resistor 10 KΩ External Resistors 10 KΩ AUX or DOOR or REX AUX or DOOR or REX Contact Closure Contact Closure RTN RTN Normally Open (NO) Series Parallel External Resistors 10 KΩ AUX or DOOR or REX Contact Closure RTN Card Reader/Keypad Connections Each card reader/keypad connector contains an input as illustrated below. Each reader input can be connected to a card reader, dedicated keypad, or a reader/keypad combination. A Keyboard Interface Module (KIM) is required to connect separate reader and keypad devices on the same reader input. Card reader voltage (+5 VDC or +12 VDC) is jumper selectable. The jumpers are located to the left of the card reader connectors on the main board. Card Reader Voltage Jumper Settings (Single Pin) Card Reader/ Keypad Inputs +5VDC (Default) Card Reader2 Card Reader1 PWR GND DATA1 CLK0 LED1 LED2 PWR GND DATA1 CLK0 LED1 LED2 +12VDC NOTE: Disconnect AC power before changing any Class 2 Selection Jumper. Connecting a Single Card Reader PWR (+5 VDC or +12 VDC Set by Voltage Jumper) GND PWR Weigand Reader or Reader with Keypad GND DATA / I DATA I DATA 0 LED1 LED2 CLK / 0 LED1 LED2 Card Reader/Keypad Connections (Continued) Connecting Two Readers or a Keypad and a Reader With the addition of the Keypad Interface Module (KIM), the controller can interface to both a keypad and a reader simultaneously. This assumes that they are both Wiegand devices of similar voltage range. The KIM module presents the CX9702 SiteController with one pair of signals. CX9702 SiteController PWR (Set by Voltage Jumper) GND PWR Wiegand Reader or Reader with Keypad or Keypad only GND LED DATA 1 DATA 0 LED Keypad Interface Module P3 DATA / I DATA / 0 P1 DATA / I DATA / I CLK / 0 CLK / 0 P2 DATA / I DATA / 0 DATA 1 Wiegand Reader or Reader with Keypad or Keypad only DATA 0 LED GND PWR Door Lock Power Connections The two door lock output connections on the CX9702 SiteController can be supplied power internally from the controller or externally from a separate power supply. Power sourcing is jumper selectable. Jumpers are located to the left of each lock output connection. CLASS 2 INTERNAL LOCK POWER TYPICAL LOCK OUTPUT CONNECTIONS LOCK POWER SOURCE LOCK POWER SOURCE INTERNAL INTERNAL EXTERNAL EXTERNAL NC LOCK NC C C NO NO RET RET + Each Lock LOCK 1 PWR 24VDC 12VDC @1 A @300 mA 12VDC PS - LOCK 2 PWR 24VDC LOCK Note: If used, the voltage of internally supplied power is indicated by a jumper selection, as shown above. Door Lock/Form C Digital Output Connections The CX9702 SiteController includes four Form C single-pole double-throw relay outputs, two of which are commonly used for door lock outputs. Form C relays contain both a normally open (NO) and a normally closed (NC) output. These output contacts operate as a standard relay, as described in the “Relay Operation” text box. The illustration below is a simplified schematic of each output channel. OUTx NC OUTx COM OUTx NO Relay Operation: When the output is set to ON: • NO contacts close • NC contacts open Door Lock/Form C Digital Output Connections (Continued) Wiring Door Outputs (NO Circuit) The illustration below represents a typical door output installation when the circuit is normally open (NO). The figure shows a normally de-energized lock (when secured) in a fail secure mode. Always be sure to use “panic” hardware that allows emergency exit from the secured area. Note the location of the metal oxide varistor (MOV) and the Door Strike electric locking mechanism. Power Supply (UL listed power supply) 12 or 24 VDC MOV (Schneider Electric #01-2020-095) C Door Strik e (UL 1076 listed) Wiring Door Outputs (NC Circuit) The illustration below represents a typical door output installation when the circuit is normally closed (NC). The figure shows a normally de-energized lock (when secured) in a fail safe mode. If a power loss occurs, the lock opens. Note the location of the metal oxide varistor (MOV) and the electromagnetic door lock. MOV (Schneider Electric #01-2020-095) C Electromagnetic Door Lock (UL 1076 listed) 12 or 24 VDC Configuring the SiteController (NOTE: Check with your system administrator for assistance.) 1. Disable the DHCP Services on your PC. 6. Log on using the default Andover Continuum user name and password. 2. Disconnect your computer from the network and set your IP address to 169.254.1.2 and your subnet mask to 255.255.0.0. 7. Enter relevant configuration parameters on the WebServer Configuration web pages. 3. Using a CAT5 cable (straight-through or crossover), connect the PC Ethernet port to the SiteController Ethernet port. 8. After entering the parameters, click the Commit Changes/Restart Controller button on the WebServer page. (Restore the PC, and connect the SiteController to the network when it reboots.) 4. Run your web browser, then go to URL: http://169.254.1.1 to display the Andover Continuum Embedded WebServer page in the SiteController. For more information, please see the online help topics in the controller’s embedded web pages or refer to SiteController cover. 5. Select Controller Configuration from the WebServer page. Specifications Dimensions Open Class: 8.9”H x 10.3”W x 2.1”D (225H x 262W x 53D) mm Small Enclosure: 14”H x 15”W x 3.25”D (356H x 381W x 82D) mm Medium Enclosure: 16”H x 22”W x 3.25”D (406H x 559W x 82D) mm Weight Open Class: 2.0 lbs (.96 kg) Small Enclosure: 11.0 lbs (6.09 kg) Medium Enclosure: 16.0 lbs (8.35 kg) Card Reader Type Supports Wiegand swipe and proximity readers, and keypads that support the Wiegand 8-bit burst format. Also supports ABA mag stripe readers. Maximum Number of Bits per Card: 256 Card Reader Power 5 V @ 120mA, 12V @ 180 mA, fused, jumper-selectable per controller Distance, Card Reader to Controller 500 ft. max. using 18-ga. wire; 200 ft. max. using 22-ga. wire Enclosure Type Open class; small or medium-size locked NEMA 1 enclosure with tamper switch available Door Switch Inputs 2, single or double resistor supervision. Useable as general-purpose digital inputs Operating Environment Temperature: 32o to 120o F (0o to 49o C) Humidity: 10 to 95% RH, non-condensing Request-to-Exit Inputs 2, single or double resistor supervision. Useable as general-purpose digital inputs Power 115/230VAC, 50/60 Hz, 115VA consumption Request-to-Exit Power 12V @ 100mA, 24V @100mA, fused, jumper-selectable Peripheral Power 30W, 5V/12V/24V (included in consumption total), for readers and locks Universal Inputs 4; each may be configured as a Voltage, Thermistor, Digital, Counter or Supervised input Overload Protection Fused with 1.5A 3AG fuse, 1500 volt transformer isolation. MOV protected. Voltage Range: 0-5V Resolution: 5 mV Accuracy: +/- 15 mV (+/- 0.3% FSR) Real Time Clock Battery-backed by UPS Battery Backup Operation Full Operation for 1 hour (typical), can be programmed to switch to CPU operation only (5 hours), or memory and clock backup only (7 days) using Schneider Electric battery P/N: 01-2100-423. Expandable by use of greater amp-hour batteries. Thermistor Type: 10K Ohm, Type III Thermistor Range: -30o to 230o F (-34o to 110o C) Resolution: 40o to 100o F (4o to 38o C) range; 0.20o F(0.11o C) typical Accuracy: 40o to 100o F (4o to 38o C) range; +/- 1.0 o F (+/- 0.55o C) Batteries Qty 1, 12V/7.0 AHr lead-acid battery (included with enclosure bundles) Digital & Counter Input Type: Contact Closure Frequency: 4 Hz (max.) Pulse Width: 125 ms (min.) (Digital pulse widths are based on Scan Time.) Battery Charging Circuit Included in power supply, 3 days deep discharge recovery time, fused Supervised Input Type: Single or Double Resistor Supervision, Parallel or Series Circuit Card Reader Inputs: 2 Specifications (continued) Door Strike Relay Outputs 2 Form C relays, no override switches. Usable as general-purpose digital outputs Door Strike Power 12V @ 1A, 24V @ 300 mA per output, fused, jumper-selectable per controller. Power can be interrupted by removing a jumper Output Indication LED’s Digital Relay Outputs 2 Form C relays, with local override switches Relay Contact Rating 3A@24VAC; 3A@30VDC Ethernet LAN Interface 10/100 Ethernet twisted pair, RJ-45 Ethernet Distance 327 feet (100m) standard between 2 nodes using 10/100 base-T unshielded twisted pair cable. Standard Ethernet repeaters allow for longer distances Serial Comm. Interface Port 1: RS-485 Infinet, maximum of 4 nodes. Includes service port. Port 2: RS-232: Modem, printer, Plain English™ software interface (modem or printer provided by others). (No terminal interface) Serial Comm. Speed 300 to 19.2K baud selectable Infinet Bus (optional) 4,000 feet (1,220m) standard for Infinet using approved shielded, twisted pair, low capacitance cable. Infilink module allows extension to longer distances. 4 Infinet nodes maximum SNMP Standard: Node system information. Optional: alarm information via SNMP Trap. Supports MIB level I and II. CX system information, alarms via SNMP TRAPs or direct polling, plus MIB II data Power 3-position barrier strip Ethernet RJ-45 connector for Ethernet 10/100 base-T Infinet, Inputs, Outputs Removable terminal strips User Terminal, Modem RJ-45 connector Microprocessor Motorola Coldfire, 32-bit, 66 MHz Memory SDRAM: 32MB; FLASH: 4MB Storage 290,000 Card Records, with 2,000 Events Software Compatibility CyberStation 1.53 or greater Agency Listings UL/CUL 916, FCC CFR 47 Part 15, EN55022, AS/NZS 3548, VCCI Class A, CE, Enclosure: UL 916 and CSA, C22.2. No. 205-M198 Regulatory Notices Federal Communications Commission FCC Rules and Regulations CFR 47, Part 15, Class A This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause undesired operation. Complies with FCC Part 68 Rules (when optional modem is installed). FCC Registration Number: AU7NMOIBMT5656R REN Number: 0.1B Caution: The user that changes or makes modifications not expressly approved by Schneider Electric for compliance could void the user’s authority to operate the equipment. Industry Canada ICES-003 This is a Class A digital device that meets all requirements of the Canadian Interference Causing Equipment Regulations. CE - Compliance to European Union (EU) 89/336/EEC - EMC Directive This equipment complies with the rules of the Official Journal of the European Union specified in the EMC directive 89/336/EEC governing the Self Declaration of the CE Marking for the European Union. C-Tick (Australian Communications Authority (ACA)) AS/NZS 3548 This equipment carries the C-Tick label and complies with EMC and radio communications regulations of the Australian Communications Authority (ACA), governing the Australian and New Zealand (AS/NZS) communities. WEEE - Directive of the European Union (EU) This equipment and its packaging carry the waste of electrical and electronic equipment (WEEE) label, in compliance with European Union (EU) Directive 2002/96/EC, governing the disposal and recycling of electrical and electronic equipment in the European community. US C 58B2 UL 916 Listed product for the United States and Canada, Open Energy Management Equipment Related Documentation Document Andover Continuum CyberStation Online Help Document Number N/A Schneider Electric One High Street North Andover, MA 01845 (978) 975-9600 Fax: (978) 975-9782 http://www.schneider-electric.com/buildings
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : No XMP Toolkit : 3.1-702 Producer : Acrobat Distiller 7.0.5 (Windows) Create Date : 2010:11:15 15:57:02-05:00 Creator Tool : PScript5.dll Version 5.2 Modify Date : 2010:11:23 15:29:50-05:00 Metadata Date : 2010:11:23 15:29:50-05:00 Format : application/pdf Creator : . Title : CX9702 SiteController Installation Instructions Document ID : uuid:195fd1cd-5cac-469a-9b73-6b412be7308c Instance ID : uuid:9efc6874-4ad7-420c-84ee-157932ab48f3 Page Count : 12 Page Layout : SinglePage Warning : [Minor] Ignored duplicate Info dictionaryEXIF Metadata provided by EXIF.tools