Philips Lighting North America LRM1743 OccuSwitch Wireless Occupancy Sensor User Manual

Philips Lighting North America Corporation OccuSwitch Wireless Occupancy Sensor

User Manual

OCCUSWITCH WIRELESS
LRM1743
Wireless Occupancy Sensor
Job Information Device Type #:
Job Name:
Cat. No.:
Notes:
Ordering Information
Philips Part No. Description
LRM174300 OccuSwitch Wireless occupancy sensor
Description
Philips LRM1743 Ceiling mount Occupancy Sensor is part of the Oc-
cuSwitch Wireless family of products that provide automatic lighting
control for energy management and user comfort. The wireless feature
adapts well to retrofit installation where pulling wires across existing
ceilings is too expensive.
The OccuSwitch Wireless occupancy sensor can be installed with the
other Day Light Regulation products to create a complete wireless light-
ing control system for a single space. Up to 16 devices (Switches, Dim-
mers, Occupancy Sensors & Multi-Sensors) can be linked to automati-
cally control the lighting.
LR1743 Ceiling mount wireless occupancy sensor
Applications
Classrooms • Conference rooms • Offices • Restrooms (fan & lights)
Multimedia rooms • Lounges • Break Rooms • Storage areas, etc . . . .
Philips OccuSwitch Wireless Control
System is a simple, easy, and effort-
less way to create a more sustainable
work environment
Features
Easy-to-install retrofit
Wireless controls means no sensor wiring needed, eliminating
the task of opening the ceiling to install sensor.
Sensor easily links to wall switch or dimmer.
Up to 16 devices can be linked t o make a single network.
Meets Federal Energy Mandate. Title 24, ASHRAE 90.1 (2010)
& 189.1, IECC.
Advance Occupancy sensing
Proven Passive Infrared (PIR) sensing technology coupled with
high-tech logic delivers advanced occupancy detection.
Micro controller based logic reduces false triggers to optimize
energy savings and maintain lamp life.
Self adaptive time delay - Manual knob sets minimum time
delay only, if longer time delay is needed the sensor self
adapts to improve performance.
Robust wireless communication with ZigBee Pro 2.4 protocol
at 2.4 GHz.
Sleek Low Profile Design
Styles low-profile design blends easily blends into any office or
other professional setting. 3.3 Inch (84mm) diameter X 0.98
inch (25mm) thin.
10 year no-maintenance operation with a heavy duty long life
3.6 volt Lithium-thionyl chloride battery.
Philips Lighting Systems & Controls - GBU Controls
10275 West Higgins Road, Rosemont IL 60018
© 2011 Philips Lighting Electronics North America
Subject to change without notice. All rights reserved.
A Division of Philips Electronics North America Corporation
OCCUSWITCH WIRELESS
LRM1743
Wireless Occupancy Sensor
Technical Specification
Detection Technology: Passive Infrared (PIR)
Intelligent Delay Timer: The switch-off delay minimum can be manu-
ally set between 1 and 30 minutes. Initial setting is automatically ad-
justed to the occupancy pattern, but never less then the manual set-
ting.
Mounting Height: Can be installed for up to 12ft ceiling height
Wireless Network Protocol:
ZigBee Pro 2.4GHz Universal license free band
Wireless Range:
Switch to Sensor: 50ft (17m) - In office buildings.
Switch to Switch (same plane): 18ft (6m)
Switch to Switch (line of sight): 50ft (17m)
Colors: Ceiling Off-White
Battery: Standard AA size 3.6V DC Lithium-thionyl chloride (Included)
10 year plus lifetime rating under normal operation.
Operating Conditions: For Indoor use only.
Temperature 41°F to 104°F (5°C to 40°C)
Humidity 20% to 85%, (Non-condensing)
Regulatory Compliance:
UL, CSA, FCC, RoHS, California Title 24
Physical Dimensions:
Diameter x Depth: 3.3 x 0.98 inches (83 x 25mm)
Weight: 18 oz. (0.5 kg)
Wireless Compatibility: -Multiple devices can be connected
Switches (LRA1721)
Dimmers (LRD1730)
Occupancy Sensors (LRM1743)
Multi Sensors (LRM1769)
Product Warranty
The Philips OccuSwitch™ Wireless products, when properly installed and under normal conditions of use (without overload, abuse or alteration), is warranted to
you, the original user, for a period of two (2) years from the date of original purchase, to be free from defects in materials and workmanship. For further informa-
tion, please contact Philips Lighting Electronics N.A Customer Care at 1-800-372-3331 or www.philips.com/advance.
Rotating Shield
Detection Area
Will vary based on ceiling height. For a typical ceiling height of 8 ft
(2.4m):
Major motion 17.7 x 23.6ft (5.40m x 7.20m)
Minor motion 11.8 x 17.7ft (3.60m x 5.40m)
Larger areas will require multiple sensors. Up to 16 devices can be
linked for one space. The retractable sensor shield can be rotated
to partially mask the sensor’s field of view and prevent unwanted
movement detection.
Tel: Support: 1-800-372-3331
Email: tech.support.rosemont@philips.com
Website: www.usa.lighting.philips.com
Published and printed in the USA 4/11