Position Technology POSIPIN User Manual CR R885 A manual
Position Technology Inc CR R885 A manual
Contents
- 1. CR R885 A manual
- 2. CR R885 S manual
CR R885 A manual
PIN and Proximity Reader
For Access Control Systems
(CR-R885-A)
Installation and Operating Instructions
Version 1.0
PosiPin 1
TABLE OF CONTENTS
Installation ............................................................................2
Technical Specifications .......................................................3
Feedback ..............................................................................5
Programming ........................................................................5
Card/Code Options ...............................................................6
Keypad Communication Format ...........................................6
Transfer Limit for 4-bits Buffered Format .............................7
Display on Card Read ..........................................................7
Keypad Lockout ....................................................................8
26-bit Wiegand Card Family Code Setting ...........................8
Reader’s Interface ................................................................9
Check-in Supervision ...........................................................9
Buzzer Setting ....................................................................10
Face Light Intensity ............................................................10
Face Light Operation ..........................................................10
Face Light Colour ...............................................................10
Changing the Installer Code ...............................................11
Panic Alarm ........................................................................11
Resetting to Default ............................................................11
Card Presentation Test ......................................................12
Warranty .............................................................................12
2 Installation and Operating Instructions
INSTALLATION
For PosiPin to function correctly with the access control system,
some programming may be required in the controller or control
panel of the host system. For further instructions, refer to the
appropriate manual. Only explanations directly concerning
PosiPin’s programming will be included in this manual.
Selecting an Installation Site:
• Avoid wiring the PosiPin cables in the same conduit as AC power
cables, lock power or signal wiring.
• Reader wiring must remain a minimum of 30cm (12in) away from
other wiring, such as wiring for AC power, computer data,
telephones, electric locks, etc.
• Avoid sites within 1.1m (3.5ft) of computer monitors or CRTs.
• Avoid sites near sources of broad spectrum EMI noise, such as
motors, pumps, generators, DC to AC converters, AC switching
relays, power supplies, and light dimmers.
• Avoid sites near potential sources of RF signals, such as cellular
phones, two-way radios, etc.
Mounting and Wiring
After selecting a site for the PosiPin, use the mounting plate as a
guide to drill two holes to secure the mounting plate and a hole for
the cable 0.95cm to 2.54cm (0.375in to 1in) wide. Place a grommet
around the edge of the hole for the cable. Prepare PosiPin’s cable
by cutting the cable jacket back 3.175cm (1.25in) and stripping the
wires back 0.635cm (0.25in). Splice PosiPin’s wires with a
recommended cable wire. Route the cable to the controller and
connect as shown in Figure 1: Connection drawing on page 4.
PosiPin 3
Mounting on Metal Surfaces
Although the read range may slightly decrease, PosiPin can be
mounted on metal. However, do not box in or surround the card
reader with any kind of metal. If the reader must be installed in a
metal enclosure, ensure that the face of the card reader is not
covered and that at least 1.6" (4cm) remain between the card
reader and the metal on all sides of the card reader.
TECHNICAL SPECIFICATIONS
Input Voltage: Typical: 13.8Vdc, min.: 11.0Vdc, max: 14.5Vdc
Input Current: Typical: 65mA @ 12.5Vdc, with card: 105mA
Consumption: Typical: 812mW @ 12.5Vdc, with card 1.31mW
Frequency: Exciter Field: 125KHz Pulse Modulated, receive low:
12.500KHz, Receive high: 15.625KHz
Operating Temp: -35°C (-31°F) to +65°C (+149°F)
Output formats: Reader: 26- and 37-bit Wiegand
Keypad: 8-, 26- and 37-bit Wiegand, 4-bit with or
without parity, and 4 bits buffered with or without parity
Cable Distance: 152.4m (500ft.)
Suggested Cables: 22AWG, 0.8mm, Multi-conductor, Alpha 5196, 5198
18AWG, 1.2mm, Multi-conductor, Alpha 5386, 5388
Belden 9553, 18AWG, 6-conductor, stranded w/
overall shield
Indicators: Beeper, red LED, green LED, red or green Face Light
Weight: 280g (9.8 oz.)
Material: Black, UV resistant, ABS plastic
Dimensions: 99.5mm (5.75in.) x 118.5mm (2in.) x 19.5mm (1in.)
4 Installation and Operating Instructions
Figure 1: Connection drawing
PosiPin 5
FEEDBACK
Visual Feedback: When information is entered on the reader’s
keypad, the red and/or green LEDs will flash, remain constant or
extinguish depending on the operation.
Confirmation Beep: When an operation is successfully entered,
the reader emits a rapid series of beep tones (“beep-beep-beep-
beep-beep”).
Rejection Beep: When the system reverts to a previous status or
an operation is incorrectly entered, the reader emits one long beep
tone (“beeeeeeeeeep”).
PROGRAMMING
Ensure that corresponding programming is completed in the
control panel or controller connected to the PosiPin. To program:
1. Press and hold the [CLEAR] key for 4 seconds.
The reader emits a confirmation beep and the green LED illuminates.
2. Enter the [INSTALLER CODE]. Press the [ENTER] key.
(default:000000) Reader emits a confirmation beep and the green LED
flashes.
3. Enter the 3-digit [SECTION]. Press the [ENTER] key.
Reader emits a confirmation beep and the green LED stops flashing.
4. Enter the required [DATA]. Press the [ENTER] key.
The reader emits a confirmation beep and the green LED flashes.
5. To program another section, repeat steps 3 and 4. To exit
programming mode, press and hold the [CLEAR] key for 4 sec.
The reader emits a rejection beep and the green LED extinguishes.
6 Installation and Operating Instructions
CARD/CODE OPTIONS
Section [001]
[001][001]
[001] - Default: [3]
[3][3]
[3]
PosiPin can function as a reader, a keypad or as both combined.
KEYPAD COMMUNICATION FORMAT
Section [002]
[002][002]
[002] - Default: [1]
[1][1]
[1]
PosiPin must use the same keypad communication format as the
controller.
Enter Description
[0] Keypad and reader disabled.
For programming only.
[1] Reader only enabled. A user must present a valid
card to the reader for Access Granted.
[2] Keypad only enabled. A user must enter a valid
code on the keypad for Access Granted.
[3] Keypad and reader enabled. A user must present
a valid card and enter a valid code for Access
Granted.
Enter Description
[0] 8-bit Wiegand
[1] 26-bit Wiegand (also see section [006])
[2] 37-bit Wiegand
[3] 4 bits without parity
[4] 4 bits with parity
[5] 4 bits buffered without parity
(also see section [003])
[6] 4 bits buffered with parity (also see section [003])
PosiPin 7
TRANSFER LIMIT FOR 4-BITS BUFFERED FORMAT
Section [003]
[003][003]
[003] - Default: [00]
[00][00]
[00]
This feature sets the number of digits retained in memory before
the data is sent to the controller. For example, if section [003] is set
at 05, PosiPin will transmit once 5 digits are entered on the keypad.
This feature only applies when the format programmed in
Section [002] is set for Option [5]: 4 bits buffered without
parity or Option [6]: 4 bits buffered with parity.
DISPLAY ON CARD READ
Section [004]
[004][004]
[004] - Default: [3]
[3][3]
[3]
PosiPin’s response to a card being presented to the reader can be
adjusted according to the installation’s requirements.
Enter Description
[01] to [11] If section [002] is Option [5]: 4 bits buffered
without parity
[01] to [10] If section [002] is Option [6]: 4 bits buffered with
parity.
Enter Description
[0] Display on Card Read disabled
[1] Red Status LED flashes
[2] Green Status LED flashes
[3] Red and green Status LEDs flash
[4] Face Light flashes
[5] Face Light and red Status LED flash
[6] Face Light and green Status LED flash
[7] Face Light and both Status LEDs flash
8 Installation and Operating Instructions
KEYPAD LOCKOUT
Section [005]
[005][005]
[005] - Default: [0]
[0][0]
[0]
The PosiPin keypad comes with a feature that will lock the keypad
for 60 seconds when an installer code is entered incorrectly 3
consecutive times.
26-BIT WIEGAND CARD FAMILY CODE SETTING
Section [006]
[006][006]
[006] - Default: [000]
[000][000]
[000]
When the keypad is enabled, the card’s family code must be
programmed in order for the keypad to recognize the user’s PIN.
When a user enters a PIN on the keypad, PosiPin will automatically
add the family code programmed in section [006] to the beginning
of the PIN before transmitting the data to the controller. Therefore,
also ensure that all cards to be used with the PosiPin contain the
same family code.
This feature only applies when the communication format
programmed in Section [002] is set for Option [1]: 26-bit
Wiegand.
Enter Description
[0] Keypad Lockout disabled
[1] Keypad Lockout enabled
Enter Description
[0] to [255] Cards’ Family Code
PosiPin 9
READER’S INTERFACE
Section [007]
[007][007]
[007] - Default: [0]
[0][0]
[0]
The reader component of the PosiPin must be programmed to use
the same reader communication format as the controller.
CHECK-IN SUPERVISION
Section [008]
[008][008]
[008] - Default: [0]
[0][0]
[0]
This feature only applies when the communication format
programmed in Section [002] is set for Option [1]: 26-bit
Wiegand or Option [2]: 37-bit Wiegand.
When no actions are performed on the PosiPin for a period of time,
it will communicate its status to the controller every 30 seconds by
sending a code to confirm its presence (26-bit Wiegand =
255:65535; 37-bit Wiegand = 65535:65535). If the PosiPin does
not communicate its status every 30 seconds, the controller can be
programmed to generate an alarm.
Enter Description
[0] 26-bit Wiegand
[1] 37-bit Wiegand
Enter Description
[0] Check-in Supervision disabled
[1] Check-in Supervision enabled
10 Installation and Operating Instructions
BUZZER SETTING
Section [101]
[101][101]
[101] - Default: [3]
[3][3]
[3]
The number of beep tones emitted as a response to a card being
presented to the reader can be adjusted from 0 (disabled) to 7 (7
rapid beep tones).
FACE LIGHT INTENSITY
Section [102]
[102][102]
[102] - Default: [4]
[4][4]
[4]
The Face Light’s illumination can be adjusted according to the
installation’s requirements from 0 (extinguished) to 8 (brightest).
FACE LIGHT OPERATION
Section [103]
[103][103]
[103] - Default: [1
[1[1
[1]
The Face Light can be set to remain illuminated continually or can
follow the Status LEDs’ state.
Enter Description
[0] to [7] Number of beep tones per response
Enter Description
[0] to [8] Face Light’s intensity level
Enter Description
[0] Face Light constant
[1] Face Light follows Status LEDs
PosiPin 11
FACE LIGHT COLOUR
Section [104]
[104][104]
[104] - Default: [0]
[0][0]
[0]
The Face Light’s colour can be red or green as desired.
This feature only applies when Face Light Operation
programmed in Section [103] is set for Option [0]: Face Light
constant.
CHANGING THE INSTALLER CODE
Section [200]
[200][200]
[200] - Default: 000000
The Installer Code is used to enter PosiPin’s programming mode.
The Installer Code is six digits long where each digit can be any
value from 0 to 9.
PANIC ALARM
A panic code can be generated and transmitted to the controller by
pressing and holding the [CLEAR] and [ENTER] keys for 2 seconds
(26-bit Wiegand = 255:65534; 37-bit Wiegand = 65535:65534).
This feature only applies when the communication format
programmed in Section [002] is set for Option [1]: 26-bit
Wiegand or Option [2]: 37-bit Wiegand.
Enter3 Description
[0] Red Face Light
[1] Green Face Light
12 Installation and Operating Instructions
RESETTING TO DEFAULT
To reset PosiPin to factory defaults, disconnect its power supply.
Press and hold the [1] and [2] keys simultaneously while re-
connecting its power supply.
CARD PRESENTATION TEST
Present the card to the reader as shown in the figure below. Place
the card parallel to the PosiPin reader and move it toward the
reader until the card code displays on the controller screen. At this
point, the card is read, decoded, data transmitted to the controller
and the controller has responded accordingly. To read the card
again, remove and re-insert the card into the reader's field.
WARRANTY
The Seller warrants its products to be free from defects in
materials and workmanship under normal use for a period of one
year. Except as specifically stated herein, all express or implied
warranties whatsoever, statutory or otherwise, including without
limitation, any implied warranty of merchantability and fitness for
a particular purpose, are expressly excluded. Because Seller
does not install or connect the products and because the
products may be used in conjunction with products not
manufactured by Seller, Seller cannot guarantee the
performance of the security system. Seller obligation and liability
under this warranty is expressly limited to repairing or replacing,
at Seller's option, any product not meeting the specifications. In
no event shall the Seller be liable to the buyer or any other
person for any loss or damages whether direct or indirect,
consequential or incidental, including without limitation any
damages for lost profits stolen goods or claims by any other
party caused by defective goods or otherwise arising from the
improper, incorrect or otherwise faulty installation or use of the
merchandise sold.
Printed in Canada 04/2001
PPINEI-00