Powerwave Technologies 5JS0118 Nexus Dual Band Repeater User Manual 044 05207 Nexus FT RM WRM

Powerwave Technologies Inc Nexus Dual Band Repeater 044 05207 Nexus FT RM WRM

Final Users Manual

Download: Powerwave Technologies 5JS0118 Nexus Dual Band Repeater User Manual 044 05207 Nexus FT RM WRM
Mirror Download [FCC.gov]Powerwave Technologies 5JS0118 Nexus Dual Band Repeater User Manual 044 05207 Nexus FT RM WRM
Document ID1318150
Application ID7kjdSujL5QRQ10biRl6b8w==
Document DescriptionFinal Users Manual
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize78.29kB (978647 bits)
Date Submitted2010-07-27 00:00:00
Date Available2010-07-27 00:00:00
Creation Date2008-04-03 11:11:56
Producing SoftwareAcrobat Distiller 8.1.0 (Windows)
Document Lastmod2010-07-27 11:34:44
Document Title044-05207 Nexus FT RM WRM.book
Document CreatorPScript5.dll Version 5.2.2
Document Author: rwillett

RACK MOUNT REPEATER
RM
NEXUS FT
INSTALLATION AND SERVICE MANUAL
RACK MOUNT RADIO
044-05207 Rev A
April 2008
© 2008 Powerwave Technologies Incorporated. All rights reserved.
Powerwave Technologies and the Powerwave logo are registered trademarks.
Powerwave Technologies Inc. reserves the right to make changes to documentation and equipment, including but not limited to component substitution and circuitry changes. Changes that impact this document may be subsequently incorporated in a later revision
of this document.
This Powerwave product is designed to operate within the Normal Operating (typical operating) ranges or conditions specified in this
document. Operation of this equipment beyond the specified ranges in this document may cause (1) spurious emissions that violate
regulatory requirements; (2) the equipment to be automatically removed from service when maximum thresholds are exceeded; or
(3) the equipment to not perform in accordance with its specifications. It is the Operator's responsibility to ensure this equipment is
properly installed and operated within Powerwave operating specifications to obtain proper performance from the equipment and to
comply with regulatory requirements.
The rated output power of a Nexus FT is for multiple carriers. As long as the composite power does not exceed the rated power
(20W for North America), derating is not required for multiple carriers. For situations where regulatory requirements require reduced
interference to adjacent band users, the rating would have to be reduced by 3 dB. This power reduction is to be by means of input
power or gain reduction and not by an attenuator at the output of the device. Input power is rated at 115/230VAC, 50/60Hz, and
should be protected based on the power and fuse specifications in Chapter 5 of this manual. Power strips should, at a minimum,
conform to this requirement to prevent equipment damage and possible overload.
Federal Communications Commission (FCC)
This device complies with the technical standards governing mobile radio devices in accordance with FCC Rules. This device is
intended to facilitate the reception and transmission of mobile radio devices in the cellular, PCS or other mobile services, and its
operation by end users or others requires carrier consent under FCC rules. This equipment has been tested and found to comply
with the limits for a Class A digital device, pursuant to CRF47 part 15 of the FCC rules. This equipment is also certified to CRF47 part
22 (cellular), part 24 (PCS) and part 90 (iDEN800 and iDEN900) of the FCC Rules depending on the band of operation. Changes or
modifications not expressly approved by Powerwave Technologies, Inc. for compliance could void the user’s authority to operate this
equipment. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated
in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used
in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own
expense.
Industry Canadian Requirements
All Powerwave apparatus introduced in the Canadian market meet all requirements of the Canadian Interference-Causing Equipment Regulations. The -20dB bandwidth at 1900 MHz band is 80 MHz. The -20dB bandwidth at the 850 MHz is 34 MHz. The output
impedance of the unit referenced in this document is 50 Ohms. The -20dB bandwidth at IDEN 800MHz band is 26 MHz. The Manufacturer's rated output power of this equipment is for multi carrier operation. For situations when multiple carrier signals are present,
the power rating per carrier would have to be reduced. For example, the power rating per carrier should be reduced by 3dB if two
carriers are present. A special situation can exist where the power rating per carrier will need to be reduced further due to high crest
factor (peak power) waveforms. Consult your Powerwave representative for these situations. This power reduction is to be by
means of input power or gain reduction and not by an attenuator at the output of the device. The input signal is optical so input
impedance requirements are not applicable. The term “IC:” before the radio certification number only signifies that Industry of Canada technical specifications were met. Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
European Requirements
The Powerwave Nexus FT apparatus introduced in EU markets are certified to ESTI EN 300 609-4 (GSM900 and DCS1800) and
ESTI EN 301 908-11 (WCDMA).
Powerwave Technlogies Inc., 1801 East St. Andrew Place, CA 92705 Santa Ana, USA.
Phone +1 714 466 1000 – Fax +1 714 466 5800 – Internet www.powerwave.com
Warnings, Cautions, and Notes
Warnings, Cautions, and Notes are found throughout this manual where applicable. The associated
icons in warnings and cautions are used to quickly identify a potential condition that could result in the
consequences described below if precautions are not taken. Notes clarify and provide additional
information to assist the user.
WARNING: The warning symbol means danger. You are in a situation that could cause
bodily injury or death. Before you work on any equipment, be aware of the hazards
involved with electrical and RF circuitry and be familiar with standard practices for
preventing accidents.
CAUTION: The caution symbol means the potential exists for equipment damage or loss
of data.
NOTE Notes contain helpful suggestions or references to material not covered in the document.
044-05207 Rev A
Revision Record
Nexus FT RMR
Revision Record
Revision Letter
Rev A
ii
Date of Change
Reason for Change
April 2008
Initial release
044-05207 Rev A
Preface
Safety
Any personnel involved in installation, operation, or service of units included in a Powerwave Distributed
Antenna System (DAS) must understand and follow the points below.
❑
Powerwave Nexus FT Rack Mount Radios (RMR) are designed to receive and amplify
signals from one or more base stations and retransmit the signals to one or more mobile
stations. They also act the other way round, that is to receive signals from one or more
mobile stations, then amplify and retransmit the signals to the base stations. Powerwave
Nexus FT RMR systems must be used exclusively for this purpose and nothing else.
❑
Units supplied with power from the mains must be connected to grounded outlets and
in conformity with the local prescriptions.
❑
Power supply units supplied from the mains contain dangerous voltage that can cause
electric shock. Disconnect the mains prior to any work in such a unit. Local regulations
are to be followed when servicing such units. Only authorized service personnel are
allowed to service units while the mains are connected.
❑
All RF transmitting units, including Nexus FT RMRs, will generate radio signals and
thereby give rise to electromagnetic fields that may be hazardous to the health of any
person who is extensively exposed close to an antenna.
Human Exposure to RF Radiation
Safe distances must be kept when working around antennas. The following paragraphs describe the cautions
to be aware of during the installation and maintenance of antenna systems and how to calculate safety
distances needed for RF radiation at different antenna power and frequencies.
Antennas
To be able to receive and transmit signals, a RMR is connected to a donor antenna directed towards the base
station and a service antenna directed towards the coverage area. A fiber optic cable from the base station
might, however, be substituted for the donor antenna.
Installation and Maintenance of Antenna Systems
Installation and maintenance of all antenna systems must be performed with respect to the radiation exposure
limits for public areas. The antenna radiation level is affected by RMR output power, antenna gain, and
transmission devices such as cables, connectors, splitters and feeders. Also, the system minimum coupling
loss, typically between 25dB and 35dB, is determined by a standard with the purpose to protect base stations
from noise and other performance dropping effects.
Radiation Exposure
The World Health Organization (WHO) and International Commission on Non-Ionising Radiation Protection
(ICNIRP) have determined recommendations for radiation exposure. ICNIRP recommends not to exceed the
following radiation power for public exposure:
Frequency Radiation power
800/900 MHz
1800/1900 MHz
2100 MHz
4.5W/m²
9.0W/m²
10.0W/m²
For antennas larger than 20cm the maximum radiation power can be calculated by using the following formula:
S= P/(4πr2)
044-05207 Rev A
S = Radiation power in W/m²
P = Output power in W
r = Distance between antenna and human in meters
iii
Electrostatic Discharge (ESD)
Nexus FT RMR
Electrostatic Discharge (ESD)
ESD can severly damage essential parts of the equipment if not handled carefully. Parts on
printed circuit board assemblies (PCBA) as well as other parts in the equipment are sensitive
to ESD. Never touch the PCBA or uninsulated conductor surfaces unless absolutely
necessary.
If you must handle the PCBAs or uninsulated conductor surfaces, use ESD protective
equipment or first touch the chassis with your hand. Never let your clothes touch PCBAs or
uninsulated conductor surfaces and always store PCBAs in ESD-safe bags.
iv
044-05207 Rev A
Chapter 1
Product Description
Introduction
This manual contains information and procedures for installation, operation, and maintenance of the Rack
Mount Radio module as part of the Nexus FT Rack Mount Repeater. In this manual, the Nexus FT Rack Mount
Radio is referred to as the RMR. The manual is organized into chapters as follows:
❑
Chapter 1- Product Description
❑
Chapter 2- Controls and Indicators
❑
Chapter 3- Installation
❑
Chapter 4- Maintenance
❑
Chapter 5- Specifications
Scope of Manual
This manual is intended for use by service technicians familiar with similar types of equipment. It contains
service information required for the equipment described and is current as of the printing date. Changes which
occur after the printing date may be incorporated by a complete manual revision or alternatively as additions.
Overview
The RMR is a repeater designed to be part of a Distributed Antenna System (DAS). The components are
mounted on a 19” rack and are intended for use in an in-door, temperature controlled environment.
As part of a DAS, the RMR extends coverage into uncovered areas in wireless mobile systems such as base
station fringe areas, tunnels, convention centers, airports, and buildings. It receives, amplifies, and transmits
signals to/from a Base Transceiver Station (BTS) and to/from Mobile Stations (MS) with both directions being
served simultaneously.
The RMR unit is a dual wide band, bi-directional, RF amplifier with two separate donor ports and a common
(duplexed) service port per band. It connects to an Optical to RF Distribution Unit (ORD) where RF signals are
combined or split and converted to an optical signal in the Uplink direction. In the Downlink direction, optical
signals are converted to RF and split to RF outputs. Two separate full duplex fibers handle signal transport
between the BTS Master Unit and the ORD. The DL signal and the UL signal combine onto one optical fiber
through a Wavelength Division Multiplexer (WDM). Wide band 4-way combiners handle RF splitting and
combining.
A Wireless Portal module distributes the DL/UL signals to/from the DAS.
The RMR is microprocessor controlled with alarm and operational status LEDs visible on the front. Cooling is
provided through forced air fans. Operational parameters, such as gain and power levels are set using a PC
running Powerwave OM-Online software which communicates with the RMRs either locally or remotely via
modem. Remote operation can be accomplished via PSTN or a GSM net. The Operation and Maintenance
System (OMS) provides for Network Operations Center (NOC) configuration and alarm monitoring.
The RMR is a fiber fed system designed to provide a high output power level and comes equipped with a Multi
Carrier Power Amp (MCPA) in the downlink path. The MCPA is located in the RMR cabinet along with a power
supply.
044-05207 Rev A
1-1
Rack Mount Radio module (RMR)
Nexus FT RMR
Cabinet Design
The RMR modules are intended to be mounted in a 19 inch cabinet at least 600mm deep, similar to the one
shown Figure 1-1.
Typical RMR position
Figure 1-1 Powerwave RMR rack- fully equipped
Rack Mount Radio module (RMR)
Figure 1-2 RMR
RMRs can handle multiple carriers over a wide band. Each band requires one RMR for the uplink and downlink.
The rack can be equipped with up to four RMRs.
1-2
044-05207 Rev A
Chapter 2
Controls, Indicators and Connectors
Introduction
This chapter contains descriptions of the controls, indicators and connectors for the RMR.
Indicators
Red
Amber
Figure 2-1 External Indicators
The LEDs, shown in Figure 2-1, provide easy identification of a fault in the system. The amber operation LED
lights up approximately 15 seconds after the main power is switched on. When the LED is steady, the RMR is
ready for operation. The red alarm LED indicates a system error alarm when flashing and a critical alarm
when steady.
044-05207 Rev A
2-1
Nexus FT RMR
2-2
044-05207 Rev A
Chapter 3
Installation
Introduction
This chapter contains unpacking, inspection, and installation instructions for installing and powering up the
RMR.
Site Survey
Powerwave recommends that a site survey be performed prior to equipment ordering or installation.
Performing a detailed site survey reduces or eliminates installation and turn-up delays. Pay particular
attention to power plant capacity, cooling needs, floor space, and RF/DC cabling/breaker requirements.
Cabinet dimensions and weights are listed in Chapter 5.
Unpacking and Inspection
This equipment has been operated, tested, and calibrated at the factory. Carefully open container to remove
equipment. Retain all packing material that can be reassembled in the event unit must be returned to the
factory. Perform the following steps:
❑ Visually inspect equipment for damage that may have occurred during shipment. If possible, in the
presence of the delivery person.
❑ Check for evidence of water damage, bent or warped chassis, loose screws or nuts, or extraneous
packing material in connectors.
If equipment is damaged, file a claim with the carrier once the extent of any damage is assessed.
If equipment must be returned to factory, please contact factory for a Return Material Authorization (RMA),
see Chapter 4.
RMR Rack Location
The RMR is designed for use in an indoor, temperature controlled environment mounted on a 19 inch rack as
supplied by the customer. A preferable site for the RMR is a location free of obstructions, easily accessible
and allows for proper air-flow and ventilation.
Connections
This section describes general examples of how to connect the input and output ports on the RMR.
Main Power and Grounding
Local regulations need to be followed for the main power connection. RMRs are approved in accordance with
EN and UL/cUL regulations. This is, however, only valid if a classified power cord is used. For the Nexus FTto
meet these regulations you must select one of the following classified and approved cord types:
❑ EN – H 05 W5 - F HMR
❑ UL – AWM Style 2587
❑ CSA– AWM 1 A/B 11 A/B
WARNING: For RMRs supplied from the main power source, the main outlet must be
grounded.
044-05207 Rev A
3-1
Connections
Nexus FT RMR
RF Connections
RF cable connections should be verified both internally and externally before powering up the equipment.
This section illustrates the general internal connections of the RMR. Verify these connections with the as-built
drawings and documents for your specific system configuration. Table 3-1 and Figure 3-2 show the steps to
connect the RMR to the Optical and RF Distribution(ORD) module.
Table 3-1 RMR Cable Connection Procedure
Step
Action
Connect an RF cable between RMR Donor 1 IN terminal and A1 terminal on ORD RFM 1. Then
connect an RF cable between A terminal of RFM 1 to bottom terminal of FMR 1.
Connect an RF cable between RMR Donor 2 IN terminal and B1 terminal on ORD RFM 1. Then
connect an RF cable between B terminal of ORD RFM 1 to top terminal of ORD FMR 2.
Connect an RF cable between RMR Donor 1 OUT terminal and A1 terminal on ORD RFM 2. Then
connect an RF cable between A terminal of ORD RFM 2 to top terminal of ORD FMR 1.
Connect an RF cable between RMR Donor 2OUT terminal and B1 terminal on ORD RFM 2. Then
connect an RF cable between B terminal of RFM 2 to bottom terminal of FMR 2.
Figure 3-1 RMR to ORD cable connections
3-2
044-05207 Rev A
Nexus FT RMR
Commissioning
Commissioning
Before proceeding, carefully read the Safety section and check all connections made during the installation.
A RMR can be configured locally with OM-Online by connecting a standard serial cable from the COM port on
the PC to the P31 PC port (RS-232) located on the front of the RMR Details on using OM-Online are
described in the OM-Online User ManualConnecting a PC for Local Access
044-05207 Rev A
3-3
Commissioning
Nexus FT RMR
Initial Startup
To complete the inital start-up of the RMR, follow the steps listed in Table 3-3.
Table 3-2 Initial Statup Procedure
Step
Action
Turn main power on
Check the LEDs on the RMR. Refer to Figure 2-1 in Chapter 2 for correct power up indications.
NOTE When optimizing RMRs, offset the UL gain 20dB less than the DL gain as a starting point.
Always monitor the UL pass bands for noise levels and/or IMDs when optimizing and
commissioning.
3-4
044-05207 Rev A
Nexus FT RMR
044-05207 Rev A
Commissioning
3-5
Commissioning
Nexus FT RMR
This page intentionally left blank
3-6
044-05207 Rev A
Chapter 4
Maintenance
Introduction
This chapter contains periodic maintenance and performance test procedures for the RMR.
Periodic Maintenance
Periodic maintenance requirements are listed in Table 4-1, as well as the intervals at which the tasks should
be performed.
Table 4-1 Recommended Periodic Maintenance
Task
Interval
Action
Inspection of cables
and connectors
12 months
Inspect power, RF and Fiber cables for signs of damage or wear
(frayed insulation, cracks, punctures, etc.) Check connections to be
sure they are tight
Optional
Perform cable sweeps
Clean equipment
Clean as required depending on operating environment
Troubleshooting
The sections that follow contain a list of problems that could occur and a few suggested actions that might
correct each problem. If the suggested corrective action does not eliminate the problem, please contact your
Powerwave field representative or help line for further instruction.
Clearing Alarm Faults
Table 4-2 lists the alarms that can be generated in the RMR. Critical, Error and Warning alarms are sent
automatically from a RMR to OM-Online, stored and then viewed in the Alarm window.
Table 4-2 Alarm Troubleshooting
ID
Alarm Text
Power
Power
044-05207 Rev A
Alarm Unit
PSM
FON
Alarm
Description
Critical
PSM does not work properly. A sum signal from the PSM
indicates that at least one voltage output has dropped. If no mains
breakdown relay is used, then the alarm will also be sent at mains
breakdown
Ceasing
PSM. Ceasing is sent if the PSM works at start-up, and there is a
corresponding critical PSM alarm logged in the Events log. The
RMR will restart when the power is back and this alarm will be
sent
Ceasing
PSU2 in the cover works properly again. Ceasing is sent if the
PSU2 works at start-up, and there is a corresponding critical
PSU2 alarm logged in the Events Log. The RMR will restart when
the power is back and this alarm will be sent
Error
The FON 10 Volt charger voltage is below limit. Suggested
remedy: Replace the FON
4-1
Troubleshooting
Nexus FT RMR
Table 4-2 Alarm Troubleshooting (Continued)
ID
Alarm Text
RMR restart
Mains
breakdown
Alarm Unit
CU
External
Alarm
Description
Ceasing
The cause of the alarm has ceased
None
Power on start, or user ordered reboot. Logged to indicate a
normal power up, or a restart ordered by the operator
Warning
Software error restart, 1st – 7th time. Restart 1st to 7th time during
a 14 day period. The counter is reset every 14th day, counted
from power up
Error
Software error restart 8th – 10th time. Restart 8th to 10th time
during the 14 day period. At the 11th time, the SW bank will be
blocked and not used anymore until a user ordered reset is
performed, or power is switched off/on
Critical
The mains power is gone. Used with an external relay indicating
mains breakdown. The external relay should be connected to
External Alarm 1 and the RMR configured to indicate this alarm. If
no relay is used, a mains breakdown will be reported as a PSM
fault
Ceasing
The mains power is back. Sent if there is a corresponding critical
mains breakdown alarm logged in the Events Log. The RMR will
restart when the power is back
Alarm reset
CU
None
Alarm reset by the user. All alarms are reset. The cause of the
alarm will be re-evaluated and reported, if still active
Local bus
error
WBA #,
MCPA#
Error
Error when communicating on the bus. The CU has no contact
with the WBA, or MCPA PCBA, which is taken out of service
Main bkd w
backup
External
Error
Used to indicate that the mains is no longer available. RMR is
powered by external battery backup unit. Suggested remedy:
Check the mains power
Ceasing
The cause of the alarm has ceased
Err in ADconverter
Warning
The analog-to-digital converter on the CU PCBA does not give
reliable values
New unit
detected
None
Compared to the last power on, the CU has recognized at least
one additional hardware unit
Inst. unit lost
Error
Compared to the last power on, the CU lacks at least one
hardware unit
10
EEPROM
error
Error
EEP read or write fail. Data cannot be written or read from the
EEPROM on the CU PCBA. User parameters are stored in the
EEPROM
11
Log memory
fault
Error
Log memory fault. Indicates that the log memory on the CU PCBA
is faulty. The RMR will not work. Not available in all CU software
versions
12
High temp
Warning
The CU PCBA temperature is higher than 90°C
Ceasing
The CU PCBA temperature has fallen below 90°C
CU
CU
13
REFO error
Error
Significant REFO drift or error detected by CU
14
Ext REFO
error
Warning
Suggested remedy: Check the reference source and the cables
4-2
044-05207 Rev A
Nexus FT RMR
Troubleshooting
Table 4-2 Alarm Troubleshooting (Continued)
ID
15
Alarm Text
CU battery
fault
Alarm Unit
CU
Alarm
Description
Warning
CU RAM battery fault. The battery for the RAM on the CU PCBA
has a voltage outside the normal 2.7 to 3.5 Volt. An alarm may be
initiated at start-up if the RMR has been stored out of power for a
long time. Suggested remedy: Ensure jumper P3 on the CU PCBA
is mounted to charge the battery
Ceasing
The cause of the alarm has ceased
16
SW load error
CU
Error
Software load error. An error has occurred during a software load
process. The flash memory does not contain a proper software.
Suggested remedy: Check the CU software using the OM-Online
SW Manager. Do NOT restart the RMR
17
Log cleared
CU
None
Log memory has been cleared. The check sum in the Events Log
memory is faulty. The log is cleared. Can be caused of a bad RAM
battery backup or low voltage to the RAM
18
RTC restarted
CU
None
The time is changed by the operator (logged to keep track of
changes made to the RTC)
Warning
Time reset to 1994-01-01. The RTC was unable to keep track of
the time and did a reset. Suggested remedy: Ensure jumper P3 on
the CU PCBA is mounted to charge the battery
Error
RTC does not operate. The CU has detected an error in the RTC
operation which makes the time unreliable. Suggested remedy:
Replace the CU PCBA
Config
The door has been open 30 seconds without disabling the alarm
Ceasing
The door has been closed 30 seconds, or the alarm is disabled
Config
External alarm input EA1 active more than 1 second
Ceasing
External alarm input EA1 no longer active
Config
External alarm input EA2 active more than 1 second
Ceasing
External alarm input EA2 no longer active
Config
External alarm input EA3 active more than 1 second
Ceasing
External alarm input EA3 no longer active
Config
External alarm input EA4 active more than 1 second
Ceasing
External alarm input EA4 no longer active
19
RTC error
20
Door open
alarm
21
22
23
24
External
alarm 1
External
alarm 2
External
alarm 3
External
alarm 4
External
External
External
External
External
30
No modem
found
Remote ctrl
None
No modem found, that is no answer is returned on a poll string to
the modem
33
No
connection
Remote ctrl
None
No connection at callback. The RMR has tried to call as many
times as stated in the alarm call settings. No connection was
established.
044-05207 Rev A
4-3
Troubleshooting
Nexus FT RMR
Table 4-2 Alarm Troubleshooting (Continued)
ID
Alarm Text
Alarm Unit
Alarm
Description
Warning
No connection at alarm call. The RMR has tried to call as many
times as stated in the alarm call settings. No connection was
established. This alarm does not generate a new attempt to report
alarm by alarm call.
None
Invalid RMR password
34
Login failed
35
Remote
connection
Remote ctrl
None
Modem connection to OM-Online opened. Not logged on CU2.
Login Registry gives the same function and more information
about CU2
36
Modem init
failed
Remote ctrl
None
Initiation string to modem not OK. The initiation string sent to the
modem is not OK. The string may contain commands not
recognized by the modem. An alarm might be sent anyway.
Suggested remedy: Check the modem using the OM-Online or
OMS modem debugger
37
Remote
timeout
Remote ctrl
Warning
The time limit of 20 minutes is exceeded without extending the
timer. The modem connection is terminated by the RMR
38
PIN code
failed
Remote ctrl
Warning
The PIN code sent to MS is incorrect. To unlock the MS/SIM card,
the PUK code will probably be needed
Ceasing
The cause of the alarm has ceased
Warning
When using a PC-card together with the MS, the alarm indicates
contact with the PC-card, but MS is not present or turned off.
Note: A Nokia MS does not power-up after power failure.
Suggested remedy: Ensure the cellular phone is connected
Ceasing
The cause of the alarm has ceased
Error
The backup battery on the RCU or the FON PCBA does not work
properly. Suggested remedy: Check cables or replace battery
Ceasing
The cause of the alarm has ceased
Warning
Low antenna isolation. The antenna isolation is lower than the
gain set. Gain is reduced by 10dB – 13dB below the oscillation
point. Suggested remedy: Decrease gain or increase antenna
isolation
Error
Low antenna isolation at lowest gain. The gain has been reduced
as much as possible but the oscillation still remains. The amplifier
is turned off. Suggested remedy: Decrease gain or increase
antenna isolation
Ceasing
Normal operation again, that is no oscillation can be detected
13dB above the gain set
Error
If a battery backup unit alarm is connected to external alarm 2,
then the operator can configure the RMR to display this alarm
when the battery backup unit indicates alarm
Ceasing
The cause of the alarm has ceased
Configur
able
If a fiber unit alarm is connected to external alarm 3, then the
operator can configure the RMR to display this alarm when the
fiber optical unit indicates alarm
Ceasing
The cause of the alarm has ceased
39
40
42
48
50
4-4
No phone
detected
Battery fault
Antenna
isolation
Battery
backup fault
Fiberoptical
error
Remote ctrl
RCU, FON
charger
WBA #,
Channel #,
UL/DL
External
FOT fiber
optics
044-05207 Rev A
Nexus FT RMR
Troubleshooting
Table 4-2 Alarm Troubleshooting (Continued)
ID
Alarm Text
Alarm Unit
Alarm
Description
70
Bad table
alarm
CU
Error
Requested table contains incorrect information (SW error)
71
Table not
found
CU
Error
Requested table not found in the database (SW or calibration
error)
72
Table
database
error
CU
Error
Table database not found (calibration error)
80
Antenna
SWR alarm
Donor
antenna
service
antenna
Error
Too low antenna return loss, caused either by cables, connectors,
or antenna problems.
90
91
92
FON power
alarm
FON
TxStable
alarm
FON RxLevel
alarm
FON RF
FON RF
FON
Suggested remedy: Check antenna and cables
Ceasing
The cause of the alarm has ceased
Error
A DC voltage on a FON PCBA is out of range. Suggested remedy:
Replace the FON PCBA.
Ceasing
The cause of the alarm has ceased
Error
Laser transmitter control loop voltage out of range. Suggested
remedy: Replace the FON PCBA
Ceasing
The cause of the alarm has ceased
Warning
Received optical level is below any of the two limits (one for
Warning and one for Error). Suggested remedy: Check optical
cables
Error
Received optical level is below any of the two limits (one for
Warning and one for Error). Suggested remedy: Check optical
cables
Ceasing
The cause of the alarm has ceased
93
FON SPI
alarm
FON F2F
Error
The SPI bus connection to the RF modem does not work properly.
Suggested remedy: Replace the FON PCBA
245
Not In
Allowed Area
CU
None
RMR is moved from the operating area and the RF HW is
switched on or off
Remarks:
The Main power breakdown alarm requires an optional relay described in the Main Power Breakdown Relay
section of Chapter 3.
044-05207 Rev A
4-5
Field Replaceable Units
Nexus FT RMR
Field Replaceable Units
The fan assembly is the only field replaceable component. If any other components fail please contact
Powerwave for service.
Fan replacement
NetWay Manager (NWM)
NWM is a Powerwave software package for network management. NWM can be used to access repeaters for
alarm reception, radio parameter configuration, software downloading and the scheduling of activities.
Return For Service Procedures
When returning products to Powerwave, the following procedures will ensure optimum response.
Obtaining an RMA
A Return Material Authorization (RMA) number must be obtained prior to returning equipment to the factory
for service. Pease contact our Repair Department at +1-714-466-1000 to obtain this number, or FAX your
request to +1-714-466-5800. Failure to obtain this RMA number may result in delays in receiving repair
service.
Repackaging for Shipment
To ensure safe shipment of the unit, it is recommended that the original package designed for shipping the
unit be reused. If it is not available, contact Powerwave’s Customer Service Department at 1-800-797-9283,
+1-714-466-100 or by e-mail at support@pwav.com for packing material.
4-6
044-05207 Rev A
Chapter 5
Specifications
Introduction
This chapter provides specifications for the RMR.
Table 5-1: RMR Specifications
Electrical
Frequency band UL
824 to 849 MHz (Cellular)
806 to 824 MHz (800 iDEN)
896 to 902 MHz (900 iDEN)
1850 to 1910 MHz (PCS)
1710 to 1755 MHz (AWS 2100)
Frequency band DL
869 to 894 MHz (Cellular)
851 to 869 MHz (800 iDEN)
935 to 941 MHz (900 iDEN)
1930 to 1990 MHz (PCS)
2110 to 2155 MHz (AWS 2100)
Max absolute delay
<300 ns
Gain adjustment range (in 1 dB steps)
30 dB
Gain
Uplink
Downlink
Variation
*These are typical values and may vary due
to cable length.
35 to 60 dB typical - Excluding fiber link
45 to 70 dB typical - Excluding fiber link
± 1.5 dB versus temperature including fiber link
± 2.0 dB versus DL frequency including fiber link
± 0.5 dB versus DL output power including fiber link
± 0.5 dB versus input voltage including fiber link
± 2.0 dB versus UL frequency including fiber link
Instantaneous bandwidth
25 MHz (Cellular)
18 MHz (800 iDEN)
6 MHz (900 iDEN)
60 MHz (PCS)
45 MHz (AWS)
Uplink AGC limit
0 dBm at donor output port
Downlink AGC limit
43 dBm at antenna port
Return Loss
11 dB (Service Port), 14 dB (Donor Port)
Downlink, Spurious and Emissions level
-13 dBm/1 MHz (FCC)
Downlink power
+43 dBm RMS (20 Watts) (for FCC)
Noise figure excluding fiber optic link
4 dB
Fiber-Optic Link Budget
10 dBo
Receiver input port return loss
14 dB
Power supply voltage
115/230 VAC
044-05207 Rev A
5-1
Introduction
Nexus FT RMR
Table 5-1: RMR Specifications (Continued)
Maximum Current Draw (Single Band)
6.5 A @ 115 VAC
3 A @ 230 VAC
Maximum Current Draw (Dual Band)
6 A @ 115 VAC
3 A @ 230 VAC
Recommended Fuse size
10 A for AC voltage
20 A for AC voltage
Power consumption
420 W typical, 600 W max
Impedance
Input
Output
50 Ω
Mechanical
Dimensions (W x H x D in inches)
484 x 153 x 580 mm (19 x 6 x 228.4 in)
Weight
<45 kg (100 lbs)
Service Antenna port connector
Female N-Type
Donor port connector
SMA
Environmental
Operating Temperature Range
-25 °C to +55 °C (-13°F to +131°F)
Altitude
-142 m to 4000 m (-466 ft. to 13100 ft.
Casing class
NEMA4/IP65
Fiber Optic Node (FON)
Bandwidth @ 3dB
800 – 2200 MHz
Power Consumption, total
<5 W
Wavelength
TX: DFB 1310 or 1550 nm
RX: 1250 – 1600 nm
Transmit
Max continuous RF input
RF attenuation settable by SW in 1dB steps
+36dBm
0-20dB
Receive
Max optic power input
RF attenuation settable by SW in 1dB steps
Alarm threshold level, settable warning
Alarm threshold level, settable error
+5dBm
4-24dB
0-40dBm
0-40dBm
5-2
044-05207 Rev A
Nexus FT RMR
044-05207 Rev A
Introduction
5-3
Introduction
Nexus FT RMR
This page intentionally left blank
5-4
044-05207 Rev A
Powerwave Installation and Service Manual
Worldwide Corporate Headquarters
1801 East St. Andrew Place
Santa Ana, CA 92705 USA
Tel: 714-466-1000
Fax: 714-466-5800
www.powerwave.com
Main European Office
Knarramasgatan 7 8tr
164 40 Kista, Sweden
Sweden
Tel: +46 8 540 822 00
Fax: +46 8 540 824 91
Main Asia-Pacific Office
23 F Tai Yau Building
181 Johnston Road
Wanchai, Hong Kong
Tel: +852 2512 6123
Fax: +852 2575 4860
©Copyright 2008, Powerwave Technologies, Inc. All Rights reserved. Powerwave, Powerwave Technologies, The Power in Wireless and the Powerwave logo are registered trademarks of Powerwave Technologies, Inc.

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Author                          : rwillett
Create Date                     : 2008:04:03 11:11:56-05:00
Modify Date                     : 2010:07:27 11:34:44-07:00
Has XFA                         : No
XMP Toolkit                     : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04
Producer                        : Acrobat Distiller 8.1.0 (Windows)
Creator Tool                    : PScript5.dll Version 5.2.2
Metadata Date                   : 2010:07:27 11:34:44-07:00
Document ID                     : uuid:c87c5e95-17d4-4e8e-8ef4-492d8fb6ec6d
Instance ID                     : uuid:ca0be96c-7e26-4a1b-a344-ceeb826e0f77
Format                          : application/pdf
Title                           : 044-05207 Nexus FT RM WRM.book
Creator                         : rwillett
Page Count                      : 27
EXIF Metadata provided by EXIF.tools
FCC ID Filing: E675JS0118

Navigation menu