12675 2 Taco 005 Sf2 Ifc Product Overview User Manual

User Manual: Pump 12675 2 Taco 005-Sf2-Ifc Product Overview

Open the PDF directly: View PDF PDF.
Page Count: 2

The redesigned 005-IFC features a larger removable Integral Flow Check,designed to improve pump
performance, simplify piping and reduce installation costs. The spring loaded IFC
®
replaces a separate
in-line flow check to ensure protection against reverse flow and gravity flow. IFC is now available on all
00
®
circulators including Priority Zoning and Variable Speed control models.
Model 005-IFC® Cartridge Circulator
©Taco Catalog # 100-8.7
Supersedes: 03/08/07
Effective Date: 10/17/08
Printed in USA
Use at 40%, Centered (In place of “Do it Once. Do it right” on Catalog Sheets) NOTE: Remove Hydronic Components & Systems
Water Circulation
Pumps & Circulators
Standard
Submittal Data Information
Model 005-IFC
®
Cartridge Circulator
Submittal Data # 101-083
Supersedes: 03/08/07
Effective: 10/17/08
Application
Hydronic Heating/Cooling Hydro-Air Fan Coils
Radiant Domestic Water Recirculation (Bronze / Stainless Steel)
Indirect Water Heaters
The 005-IFC is designed to simplify piping, reduce installation costs and improve system perfor-
mance when zoning with 00® circulators. By locating the IFC inside the pump, a separate in-line
flow check is eliminated. The low pressure drop of the IFC increases flow performance vs. in-line
flow checks. Both the IFC and the cartridge are easily accessed for removal and service.
FLOW-GPM
012345678910 11 12 13 14 15 16 17 18
TOTAL HEAD-FEET
0
2
4
6
8
10
12
14
16
FLOW-M3/H
0.0 0.2 0.4 0.60.8 1.0 1.2 1.4 1.6 1.82.0 2.2 2.4 2.62.8 3.03.2 3.4 3.6 3.84.0
TOTAL HEAD-METERS
0.0
0.6
1.2
1.8
2.4
3.0
3.6
4.2
4.8
003B-IFC
005-IFC
006-IFC
006B-IFC
007-IFC
008-IFC
008B-IFC
INTEGRAL FLOWCHECK (IFC®) MODELS
Performance Field - 60Hz
AB
E
F
D
C
Mounting Positions
Standard Optional
OK if over 20 psi
Flange Orientation
Features
Integral Flow Check (
IFC
®
)
Simplifies piping
Prevents reverse flow and gravity flow
Eliminates separate in-line flow check
Reduces installed cost
Improves system performance
Easy to service
Unique replaceable cartridge-field serviceable
Unmatched reliability-maintenance free
Quiet, efficient operation
Self lubricating, No mechanical seal
Wide range of applications
Cast Iron, Bronze or Stainless Steel construction
Flanged connections
Materials of Construction
Casing (Volute): Cast Iron, Bronze or
304 Stainless Steel
Integral Flow Check
(
IFC
®
)
:
Body, Plunger....Acetal
O-ring Seals......EPDM
Spring.................Stainless Steel
Stator Housing: Steel
Cartridge: Stainless Steel
Impeller: Non-Metallic
Shaft: Ceramic
Bearings: Carbon
O-Ring & Gaskets: EPDM
Model Nomenclature
F Cast Iron, Flanged
BF Bronze, Flanged
SF 304 Stainless Steel, Flanged
IFC Integral Flow Check
Variations:
Z Zoning Circulator
VR Variable Speed Outdoor Reset
VS Variable Speed Set Point
VV Variable Speed Variable Voltage
J – Bronze Cartridge with Cast Iron Casing
Performance Data
Flow Range: 0 - 13.5 GPM
Head Range: 0 - 7.5 Feet
Minimum Fluid Temperature: 40˚F (4˚C)
Maximum Fluid Temperature: 230°F (110˚C)
Maximum Working Pressure: 125 psi
Connection Sizes: 3/4”, 1”, 1-1/4”, 1-1/2” Flanged
FOR INDOOR USE ONLY
Use at 40%, Centered (In place of “Do it Once. Do it right” on Catalog Sheets) NOTE: Remove Hydronic Components & Systems
Taco Inc., 1160 Cranston Street, Cranston, RI 02920 / (401) 942-8000 / Fax (401) 942-2360
Taco (Canada) Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8 / (905) 564-9422 / Fax (905) 564-9436
www.taco-hvac.com
A B C D E F Ship Wt.
Model Casing in. mm in. mm in. mm in. mm in. mm in. mm lbs. Kg
005-F2-2 IFC Cast Iron 5-5/8 143 4-1/8 105 3-3/16 81 2-15/16 75 5 127 6-3/8 162 8 3.6
005-F2-3 IFC
Cast Iron 5-3/8 137 4-1/8 105 3-3/16 81 2-15/16 75 5 127 6-3/8 162 8 3.6
005-BF2-1 IFC
Bronze 5-5/8 143 4-1/8 105 3-3/16 81 2-15/16 75 5 127 6-3/8 162 8 3.6
005-SF2-IFC
S. Steel 5-5/8 143 4-1/8 105 3-3/16 81 2-15/16 75 5 127 6-3/8 162 8 3.6
Pump Dimensions & Weights
Model Volts Hz Ph Amps RPM HP
Cast Iron 115 60 1 .52 3250 1/35
Bronze / SS 115 60 1 .54 3250 1/35
Motor Permanent Split Capacitor
Type Impedance Protected
Motor
Options
220/50/1, 220/60/1, 230/60/1, 100/110/50/60/1
Electrical Data
Optional
005-F2-3 IFC