IP-Series

TM

Intelligent
Panel Series
with float-less
technology!
• SIMPLEX
• DUPLEX
IP-SeriesTM control panels
incorporate programmable
pump features through a
simple, easy-to-use touch pad
on the inner door. Now pump
programming and system
monitoring is easier than ever!

Features:
• NEMA 4X weatherproof enclosure
for indoor/outdoor mounting
• Float-less level sensor is compact
and eliminates multiple wide-angle
floats for controlling pumps
• Redundant “ALARM” float included
for added security
• Easy-to-use touch pad for programming
pump on/off levels and alarm level
• Separate control and alarm fuses
• Digital display board for system
monitoring
• Alarm beacon and horn provide audio/
visual warning of alarm condition
• Auxiliary contacts
• Panel is field convertible for either demand dose or timed dose applications
• Inner panel door provides increased safety
• Instruction label on inside cover for
viewing and programming digital display

IP-SeriesTM
Simplex and
Duplex
Controls

Smart touch pad and sta
Innovative FLOAT-LESS Technology
The compact level sensor
detects the liquid level
in the tank and sends a
signal to the IP panel which
displays this level in inches
or centimeters for easier
monitoring of the system.
Pump activation and alarm
levels can be adjusted
using the panel touch
pad - eliminating the
need to go into the tank
for manual adjustment.

Panel Features:
Enclosure NEMA 4X weatherproof
for indoor or outdoor mounting.
Red Alarm Beacon.
Exterior Alarm Test/Normal/Silence
Switch allows horn and light to
be tested and horn to be silenced.
Alarm automatically resets when alarm
condition is cleared.
Alarm Horn provides audio
warning of alarm condition
(83 to 85 decibel rating).
Circuit Breakers provide pump
disconnect and branch circuit
protection.

Float-less Level
Sensor Features:

Power Relays control pump
by switching electrical lines.
Definite purpose contactors
used when pump full load
amps are above 15.

• Compact design for
confined space
applications

Incoming Control/
Alarm Power and Pump
Terminal Block Control
Power Indicator with fuse
indicator light illuminates
if control power is present in
panel. Alarm activates
if fuse is blown.

• One sensor takes the
place of up to 4 floats!

Alarm Power
Indicator with Fuse
indicator light illuminates
if alarm power
is present in panel.

• 10' vent tube

24 ⁄8”
3

• Operates on low voltage

• Easy to install and adjust
set points
• Level sensor operating
range is 4" to 99"
(8 to 252 cm).
• Cord length from vent
is 20'
• Stainless steel clamps
for mounting
• A redundant “Alarm”
float is included for
extra security.

LISTED

Note: Float tree not included

atus indicators make pump programming easy!
Inner-door Touch Pad Features

DUPLEX PANEL SHOWN

A Level Status Indicators illuminate
when set points are activated.
B HOA (Hand-Off-Automatic) buttons
control pump mode.

A

A
C

C Pump Run Indicators illuminate
when pumps are called to run.
D Lead/Lag Selector toggles pump
operation (alternate 1-2, 2-1).
E 6 Digit LED Display shows system
information including: level in
inches or centimeters, mode,
pump’s elapsed time (hh:mm), events
(cycles), alarm counter,
timed dose override counter
(timed dose only), and ON/OFF
times (timed dose only).
F NEXT Push Button toggles display.
G Up and SET Push Buttons set pump
ON/OFF times and activation levels.

D

E

A

A

C
B

B
F

G
G

IP panels come with easyto-read wiring diagram and
instruction label located
on the inside cover for
viewing and programming
the digital display.

MODEL

A

B

C

IPS-24L

6"

10"

10"

IPS-24H

6"

10"

12"

IPD-24L

6"

10"

10"

IPD-24H

6"

14"

16"

IPS-34-131

6"

12"

14"

IPS-34-141

6"

12"

14"

IPS-34-171

6"

12"

14"

IPS-34-191

6"

12"

14"

IPS-34-511

6"

12"

14"

IPS-54-121

6"

12"

14"

IPS-54-151

6"

12"

14"

IPS-54-161

6"

12"

14"

IPD-34-131

6"

14"

16"

IPD-34-141

6"

14"

16"

IPD-34-171

6"

14"

16"

IPD-34-191

6"

14"

16"

IPD-34-511

6"

14"

16"

IPD-54-121

6"

14"

16"

IPD-54-151

6"

14"

16"

IPD-54-161

6"

14"

16"

IP-SeriesTM Specifications
IPS-Series SIMPLEX
MODEL

Volts

Phase

Enclosure

Amps

Lbs

IPS-24L

120/208/240

1

NEMA 4X

0 – 14.9

16

IPS-24H

120/208/240

1

NEMA 4X

15 – 20

16

*IPS-24HC

120/208/240

1

NEMA 4X

15 – 20

18

208/240/480

3

NEMA 4X

1.6 – 2.5

16

Single Phase

Three Phase
IPS-34-131
IPS-34-141

208/240/480

3

NEMA 4X

2.5 – 4.0

16

IPS-34-171

208/240/480

3

NEMA 4X

4.0 – 6.3

16

IPS-34-191

208/240/480

3

NEMA 4X

6.0 – 10.0

16

IPS-34-511

208/240/480

3

NEMA 4X

9.0 – 14.0

16

IPS-54-121

575

3

NEMA 4X

1.6 – 2.5

16

IPS-54-151

575

3

NEMA 4X

2.5 – 4.0

16

IPS-54-161

575

3

NEMA 4X

4.0 – 6.3

16

All IP-SeriesTM panels are shipped
complete with the float-less level
sensor, redundant alarm float
and auxiliary contacts – standard.
For optional panel features or
custom panels consult factory
800-543-2550.

*Includes capacitor and relay for pump
models LSG202M-C and LSGX202M-C

IPD-Series DUPLEX
MODEL

Volts

Phase

Enclosure

Amps

Lbs

IPD-24L

120/208/240

1

NEMA 4X

0 – 14.9

23

IPD-24H

120/208/240

1

NEMA 4X

15 – 20

23

*IPD-24HC

120/208/240

1

NEMA 4X

15 – 20

26

IPD-34-131

208/240/480

3

NEMA 4X

1.6 – 2.5

25

IPD-34-141

208/240/480

3

NEMA 4X

2.5 – 4.0

25

IPD-34-171

208/240/480

3

NEMA 4X

4.0 – 6.3

25

IPD-34-191

208/240/480

3

NEMA 4X

6.0 – 10.0

25

IPD-34-511

208/240/480

3

NEMA 4X

9.0 – 14.0

25

IPD-54-121

575

3

NEMA 4X

1.6 – 2.5

25

IPD-54-151

575

3

NEMA 4X

2.5 – 4.0

25

IPD-54-161

575

3

NEMA 4X

4.0 – 6.3

25

Single Phase

Three Phase

*Includes capacitor and relay for use with models LSG202M-C and LSGX202M-C

www.
libertypumps
.com

Liberty Pumps • 7000 Apple Tree Avenue • Bergen, New York 14416
Phone 800-543-2550 Fax (585) 494-1839
Specifications are subject to change without notice. Copyright © Liberty Pumps, Inc. 2014 All rights reserved. LLIT6679-R02/14



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.3-c011 66.145661, 2012/02/06-14:56:27
Create Date                     : 2014:07:25 05:49:36-04:00
Metadata Date                   : 2014:07:25 05:49:43-04:00
Modify Date                     : 2014:07:25 05:49:43-04:00
Creator Tool                    : Adobe InDesign CS6 (Macintosh)
Instance ID                     : uuid:e7350e7b-6f2d-bc4f-8ec4-536cc8fdfc97
Original Document ID            : xmp.did:FFA80FA20D206811822AB393D8713994
Document ID                     : xmp.id:0180117407206811822AB408C03D588C
Rendition Class                 : proof:pdf
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CS6 (Macintosh)
History Changed                 : /
History When                    : 2014:07:25 05:49:36-04:00
Derived From Instance ID        : xmp.iid:FBBF954846206811822AB393D8713994
Derived From Document ID        : xmp.did:FFA80FA20D206811822AB393D8713994
Derived From Original Document ID: xmp.did:FFA80FA20D206811822AB393D8713994
Derived From Rendition Class    : default
Format                          : application/pdf
Producer                        : Adobe PDF Library 10.0.1
Trapped                         : False
Page Count                      : 4
Creator                         : Adobe InDesign CS6 (Macintosh)
EXIF Metadata provided by EXIF.tools

Navigation menu