18004 2 Little Giant Vcc 20 Submittal User Manual

18345 1 Little Giant Vcc-20 Submittal 18345_1_Little Giant VCC-20 Submittal

User Manual: Pump 18004 2 Little Giant Vcc-20 Submittal

Open the PDF directly: View PDF PDF.
Page Count: 2

Wastewater Water Systems HVAC Industrial Engineered Products
Low profile for limited spaces
Vertical centrifugal pump design
Automatic start, stop and high level water
detection (safety overflow switch)
3/8" O.D. barbed discharge adapter with built-in
check valve (installed on the pump)
1/4” O.D. barbed discharge adapter (included in
the box)
Two inlet openings
(one 1.0” and one 1-1/8” diameter)
Safety overflow float activated switch
Two 5” safety overflow switch lead wires
Thermally protected, fan cooled motor
Built-in wall mount tabs
Intermittent liquid temperature up to 120 ºF
20' shut-off head
6 ft, 3-conductor cable with grounded 3-prong
plug (115 V and 230 V models)
Designed for automatic collection and removal of
condensate from air conditioning, refrigeration
and dehumidification equipment when gravity
drainage is not possible or practical. Also suitable
for high efficiency oil and gas-fired condensing
furnace equipment
Features
Motor — 1/30 hp
Discharge — 3/8" O.D. barbed
Housing/tank cover — ABS
Motor Cover — ABS
Volute — ABS
Tank — ABS
Impeller — Glass filled polypropylene
Check valve — Acetal
Applications
Construction
VCC-20 Series
HVAC
Engineering Data
Specications
Replacement Parts
Item Part Number
Tank 154004
Impeller 154009
Volute 154015
Cover, motor 154006
Check valve 154715
Switch pump 950337
Seal ring 928006
Safety switch 154714
Float/stem 154017
Adapter, 1/4" 154037
Head - Meters
Flow - Liters/Hour
Head - Feet
Flow - Gallons/Hour
0
2.5
5
7.5
0 50 100 150 200 250 300 350
0
5
10
15
20
25
0 25 50 75 100
230 v
P.O. Box 12010
Oklahoma City, OK 73157-2010
Phone: 1.800.701.7894
Fax: 1.800.678.7867
www.LittleGiantPump.com Form 995123 – 08/12
Item
No.
Model
No.
Discharge
Size HP Volts Hertz Amps Watts
Performance (GPH@Head) Shutoff Cord
Length (ft)
Weight
(lbs)1' 5' 10' 20' Ft PSI
554200
VCC-20ULS
3/8" OD Barbed 1/30 115 60 1.5 93 80 70 45 0 20 8.6 6 5.40
554210 3/8" OD Barbed 1/30 230 50/60 0.6 75 80 70 45 0 17 7.4 6 5.40
NOTE: GPH is through check valve.
Performance Data
""
""
"
"
"
"
"
"
"
"

Navigation menu