ELECTRICAL ALTERNATOR CONTROL PANEL - FOR DUPLEX INSTALLATIONS

An Electrical Alternator is used on a Duplex pump application where automatic alternation of the pumps is desired for added protection in residential or commercial
applications. With one pump operating to handle normal flow, a second pump becomes operational in the event the water level continues to rise. The built-in
alarm system, a standard feature, can be connected to sound when the second pump becomes operational (3-float switch system) or independently (4-float switch
system). All electrical systems must be installed by a qualified electrician and according to the National Electrical Code. (See Section 430-71 though 430-113, plus
any others that apply.)

NEMA 1 ENCLOSURE

Control Panel Features:
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•

Hand-Off-Auto Toggle Switch for each pump.
Green pump run pilot light for each pump.
Alarm test and silence switches.
Red pilot light (Nema 1 Only) and audible alarm with 83 to 85 decibel rating for
a high water condition.
Red Alarm Beacon included with Nema 4X enclosure.
Auxiliary Dry Contact.
High Water Alarm.
On Single Phase - Circuit breaker for each pump.
On Three Phase - Motor protective switch with overload protection.
Magnetic starter for each pump.
Alternating mechanism.
Numbered terminal strip for connecting pumps and variable level float switches.
Nema 1 - general purpose or
Nema 4X - Watertight enclosures available.
Integral auxiliary terminal board connections (dry contact) for remote alarm
devices.
3 or 4 variable level float switch control operation.
10-0092
Three 20’ float switches included with single phase panels.
UL Listed.
2 Year Warranty
The use of off-the-shelf components provide for relatively easy field maintenance
and repair.
Float switches not included with three phase panels (See FM0526).

NEMA 4X ENCLOSURE

CONTROL PANEL USED WITH SINGLE PHASE PUMPS
NEMA 1 ENCLOSURE WITH 20’ FLOAT SWITCH
Order
No.

Dimensions
HxWxD

Volts

Amp Range

10-1039
10-1040
10-0092*

12” x 10” x 6”
12” x 10” x 6”
12” x 10” x 6”

115
115
115/200/230

7-15
15-20
0-20

NEMA 4X ENCLOSURE WITH 20’ FLOAT SWITCH
Order
No.
10-1041
10-1042
10-1043
10-1044
10-1045
10-1046
10-0093*

Dimensions
HxWxD
12” x 10” x 6”
12” x 10” x 6”
12” x 10” x 6”
12” x 10” x 6”
12” x 10” x 6”
12” x 10” x 6”
12” x 10” x 6”

Volts
115
115
115/200/230
115/200/230
115/200/230
115/200/230
115/200/230

Amp Range
7-15
15-20
0-7
7-15
15-20
20-30
0-20

* Branch circuit protection provided by installing electrician.

10-0093
Products may not be exactly as illustrated

NOTE: 600 and X600 Series single phase pumps require special panels that include start components. See Selection Guide FM0712 for correct panel selection.
NOTE: All variable level float switches in this section are mechanically activated and do not contain mercury.
© Copyright 2006 Zoeller Co. All rights reserved.

CONTROL PANEL USED WITH THREE PHASE PUMPS
DUPLEX ELECTRICAL ALTERNATING SYSTEM

NEMA 4X ENCLOSURE (Float Switches not included)
Order
No.
10-1102
10-1104
10-1106
10-1108
10-1110
10-1111
10-1112
10-1114
10-1115
10-1183
10-1154
10-1156
10-1158

Dimensions
HxWxD
14” x 12” x 6”
14” x 12” x 6”
14” x 12” x 6”
14” x 12” x 6”
14” x 12” x 6”
14” x 12” x 6”
14” x 12” x 9”
14” x 12” x 6”
14” x 12” x 6”
14” x 12” x 6”
14” x 12” x 6”
14” x 12” x 6”
14” x 12” x 6”

Volts*
200/230/460
200/230/460
200/230/460
200/230/460
200/230/460
200/230/460
200/230/460
200/230/460
200/230/460
200/208
575
575
575

Amp Range
1.0 - 1.6
1.6 - 2.5
2.5 - 4.0
4.0 - 6.3
6.0 - 10.0
9.0 - 14.0
13.0 - 18.0
17.0 - 23.0
20.0 - 25.0
23.0 - 32.0
1.6 - 2.5
2.5 - 4.0
4.0 - 6.3

*Three phase panel has multi-tap transformer with secondary fusing.

ALARM LIGHT

DISCONNECT

PUMP POWER SUPPLY

CONTROL & ALARM
POWER SUPPLY
(SINGLE PHASE ONLY)

NOTE: ALARM - CONTROL
CIRCUIT SHOULD BE
SEPARATE FROM
PUMP POWER
(SINGLE PHASE ONLY)

ELECTRICAL ALTERNATOR
CONTROL PANEL

NOTE: THREE PHASE PANELS HAVE A
TRANSFOMER WITH SECONDARY FUSING.

INDICATOR LAMPS (INSIDE ENCLOSURE)
TOGGLE SWITCHES (INSIDE ENCLOSURE)

ZOELLER UNICHCEK
CHECK VALVE (2" OR 3")
4 FLOAT SYSTEM
ALARM BELL "ON"
BOTH PUMPS ALREADY
ACTIVATED SET ABOVE OVERRIDE
AND BELOW INLET

2" OR 3" DISCHARGE PIPE
FLOOR FLANGE

4" HUB INLET

ZOELLER FIBERGLASS
OR POLYETHYLENE
BASIN

"ALARM-OVERRIDE LEVEL SET
ABOVE "ON" FLOAT AND
BELOW INLET BOTH PUMPS
"ON" ALARM BELL "ON"
3 FLOAT SYSTEM

ZOELLER FLOAT SWITCH

ZOELLER SEWAGE PUMP

5"

"ON" LEVEL PUMPS ALTERNATE
OPERATION EACH CYCLE MAXIMIZE
BASED ON DEPTH AND VOLUME
OF BASIN
MINIMUM "OFF" LEVEL

Sequence of Operation for Duplex Panel
1. Operation can begin after the following:
- Correct voltage is supplied to Panel
- Panel is properly grounded
- Pumps are connected correctly to Panel
- Panel Circuit Breakers are closed
- Floats are installed properly
- Overload Protection is adjusted to Pump nameplate amps
- Pump HOA Switches are set to “Auto”
- Control On/Off Switch is set to “On”
2. When the “Stop” and “Lead” floats are closed Pump 1 will energize
and the Pump 1 Pump Run Light will illuminate. Pump 1 will remain
operational until the “Stop” float opens.
3. The next time the “Stop” and “Lead” floats are closed the Alternating
Circuit will energize Pump 2 and the Pump 2 Pump Run Light will
illuminate. Pump 2 will remain operational until the “Stop” float opens.
This cycle will repeat each time the fluid level rises and falls.
4. If the fluid level continues to rise after the first pump has been energized the “Lag” float will close. When the “Lag” float has closed the
second Pump will Energize. Both Pumps will remain operational until
the “Stop” float opens.

SK289

5. In a three float system when the “Lag” float is closed the following will
also occur:
- The External High Water Light will illuminate
- The Audible High Water Horn will sound
- The Auxiliary Dry Contacts will close
6. In a four float system, the alarm float should be the third float causing
an alarm to sound when the lead pump fails to operate or the rate of
in flow into the basin exceeds the capacity of one pump. When the
alarm float is closed the following will occur.
- The External High Water Light will illuminate
- The Audible High Water Alarm will sound
- The Auxiliary Dry Contacts will close
As the liquid level continues to rise the fourth float will close, energizing
the lag pump. The lag pump and the lead pump will remain energized
until the "Stop" float opens.
NOTE: In Duplex systems where it is considered normal for two pumps
to operate in tandem during peak flow conditions, the third and fourth
float may be reversed.
7. The Audible High Water Horn can be silenced by pressing the Alarm
Silence Button. When the “Alarm” float opens the External High Water
Light, Audible High Water Horn and Dry Auxiliary Contacts will be
reset.

All electrical systems must be installed by a qualified licensed electrician and according to the National Electrical
Code. (See section 430-71 through 430-113 plus any others that apply)
Refer to FM0712 for correct selection of Electrical Alternator.
© Copyright 2006 Zoeller Co. All rights reserved.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Author                          : mikem
Create Date                     : 2006:03:21 15:21:09-05:00
Modify Date                     : 2014:04:10 11:05:03-04:00
Subject                         : FM0486
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Producer                        : Acrobat Distiller 7.0.5 (Windows)
Creator Tool                    : Windows NT 4.0
Metadata Date                   : 2014:04:10 11:05:03-04:00
Format                          : application/pdf
Title                           : FM0486-Electrical Alternator Control Panel Catalog Sheet
Description                     : FM0486
Creator                         : mikem
Document ID                     : uuid:aa029ff4-7140-4511-b400-80b8f6eca9bc
Instance ID                     : uuid:8b35eb0f-4618-4cb3-af87-dd6448a9f893
Page Count                      : 2
EXIF Metadata provided by EXIF.tools

Navigation menu