548044 3 Zoeller Simplex Control Panel Sizing Chart

548034 3 Zoeller Simplex Control Panel Recommendation Applications 548034_3_Zoeller Simplex Control Panel Recommendation Applications

548036 3 Zoeller Simplex Control Panel Sizing Chart 548036_3_Zoeller Simplex Control Panel Sizing Chart

548041 3 Zoeller Simplex Control Panel Sizing Chart 548041_3_Zoeller Simplex Control Panel Sizing Chart

548031 3 Zoeller Simplex Control Panel Recommendation Applications 548031_3_Zoeller Simplex Control Panel Recommendation Applications 548031_3_Zoeller Simplex Control Panel Recommendation Applications pdf pumpproducts

548031 3 Zoeller Simplex Control Panel Sizing Chart 548031_3_Zoeller Simplex Control Panel Sizing Chart 548031_3_Zoeller Simplex Control Panel Sizing Chart pdf pumpproducts

: Pump 548044 3 Zoeller Simplex Control Panel Sizing Chart 548044_3_Zoeller Simplex Control Panel Sizing Chart pdf

Open the PDF directly: View PDF PDF.
Page Count: 2

© Copyright 2016 Zoeller® Co. All rights reserved.
SECTION: 2.50.200
FM1228
1216
Supersedes
0815
SIMPLEX CONTROL PANEL RECOMMENDED APPLICATIONS
* Order with piggyback oat switch or (B) model pump.
Product information presented
here reects conditions at time
of publication. Consult factory
regarding discrepancies or
inconsistencies.
MAIL TO: P.O. BOX 16347 • Louisville, KY 40256-0347
SHIP TO: 3649 Cane Run Road • Louisville, KY 40211-1961
(502) 778-2731 • 1 (800) 928-PUMP • FAX (502) 774-3624
visit our web site:
www.zoeller.com
®
Your Peace of Mind is Our Top Priority
®
SINGLE PHASE SIMPLEX CONTROL PANELS
MODEL # VOLTS PHASE AMPS HP Plug-In Panel* Circuit Breaker
Disconnect
N53 115 19.7 0.3 10-1019 10-1037
E53 230 1 4.8 0.3 10-1023 10-1036
N55 115 19.7 0.3 10-1019 10-1037
E55 230 1 4.8 0.3 10-1023 10-1036
N57 115 19.7 0.3 10-1019 10-1037
E57 230 1 4.8 0.3 10-1023 10-1036
N59 115 19.7 0.3 10-1019 10-1037
E59 230 1 4.8 0.3 10-1023 10-1036
N98 115 19.4 0.5 10-1019 10-1037
E98 230 1 4.7 0.5 10-1023 10-1036
N137 115 110.7 0.5 10-1019 10-1037
E137 230 1 5.8 0.5 10-1023 10-1036
I137 208 16.2 0.5 — 10-1036
N139 115 110.7 0.5 10-1019 10-1037
E139 230 1 5.8 0.5 10-1023 10-1036
I139 208 15.5 0.5 — 10-1036
N140 115 112.0 1.0 10-1019 10-1037
E140 230 1 6.0 1.0 10-1023 10-1036
N161 115 115.5 0.5 10-1038
E161 230 1 7.5 0.5 10-1023 10-1037
I161 208 18.8 0.5 10-1037
N163 115 115.0 0.5 10-1019 10-1038
E163 230 1 7.5 0.5 10-1023 10-1037
I163 208 18.5 0.5 10-1037
E165 230 1 10.2 1.0 10-1023 10-1037
I165 208 112.6 1.0 10-1037
E185 230 1 9.8 1.0 10-1023 10-1037
I185 208 111.5 1.0 10-1037
I186 208 117.2 1.5 10-1038
E186 230 1 13.7 1.0 10-1023 10-1037
E188 230 1 14.0 1.5 10-1023 10-1037
I188 208 116.8 1.5 10-1038
E189 230 1 17.1 2.0 10-1038
I189 208 120.5 2.0 — 10-1201
N264 115 19.4 0.4 10-1019 10-1037
E264 230 1 4.7 0.4 10-1023 10-1036
N266 115 110.4 0.5 10-1019 10-1037
E266 230 1 5.5 0.5 10-1023 10-1036
I266 208 16.2 0.5 — 10-1036
N267 115 110.4 0.5 10-1019 10-1037
E267 230 1 5.5 0.5 10-1023 10-1036
I267 208 16.2 0.5 — 10-1036
N268 115 110.4 0.5 10-1019 10-1037
E268 230 1 5.5 0.5 10-1023 10-1036
I268 208 16.2 0.5 — 10-1036
N270 115 115.0 1.0 10-1019 10-1038
E270 230 1 7.5 1.0 10-1023 10-1037
N282 115 110.3 0.5 10-1019 10-1037
E282 230 1 5.0 0.5 10-1023 10-1036
I282 208 16.1 0.5 — 10-1036
E284 230 1 8.9 1.0 10-1023 10-1037
I284 208 19.3 1.0 10-1037
N292 115 115.0 0.5 10-1019 10-1038
E292 230 1 7.5 0.5 10-1023 10-1037
I292 208 18.8 0.5 10-1037
E293 230 1 10.2 1.0 10-1023 10-1037
I293 208 112.0 1.0 10-1037
E294 230 1 13.7 1.5 10-1023 10-1037
I294 208 117.8 1.5 10-1038
E295 230 1 17.1 2.0 10-1038
I295 208 120.5 2.0
E404 230 1 12.9 2.0 10-1023 10-1037
I404 208 114.4 2.0 10-1037
E405 230 1 19.0 3.0 10-1038
I405 208 120.2 3.0 — 10-1201
© Copyright 2016 Zoeller® Co. All rights reserved.
NOTE: For pump prex identication see News & Views 0052
(1) Single Piggyback Variable Level Float Switch included with Control and Alarm Panel/15 Amp Max.
(2) Double Piggyback Variable Level Float Switch included with Control and Alarm Panel/15 Amp Max.
(3) Magnetic Contactor Control with 3 Variable Level Float Switches included with Control and Alarm 20 Amp Max.
(4) Can be used with SPB; DPB or pumps requiring special panels that include Start Components.
(5) 600 Series single phase pumps require special panels that include Start Components.
All Simplex Enclosures are NEMA 4X
(Outdoor/Indoor)
SINGLE PHASE SIMPLEX
CONTROL PANEL(5)
MODEL # VOLTS PHASE AMPS HP
E611 230 1 6.9 1.0 10-0920
E621 230 1 8.9 1.5 10-0921
E631 230 1 14.5 2.0 10-0922
E641 230 1 17.0 3.0 10-0923
E651 230 1 28.0 5.0 10-0924
THREE PHASE CONTROL
PANEL
MODEL # VOLTS PHASE AMPS HP
F137 230 3 2.6 0.5 10-1078
G137 460 3 1.4 0.5 10-1074
J137 200 3 2.6 0.5 10-1078
F139 230 3 2.6 0.5 10-1078
G139 460 3 1.2 0.5 10-1074
J139 200 3 2.6 0.5 10-1078
F161 230 3 5.2 0.5 10-1080
J161 200 3 6.4 0.5 10-1082
G161 460 3 2.9 0.5 10-1078
BA161 575 32.4 0.5 10-1132
F163 230 3 4.8 0.5 10-1080
J163 200 3 6.0 0.5 10-1082
G163 460 3 2.9 0.5 10-1078
BA163 575 32.4 0.5 10-1132
F165 230 3 7.4 1.0 10-1082
J165 200 3 7.5 1.0 10-1082
G165 460 3 3.7 1.0 10-1078
BA165 575 33.0 1.0 10-1134
F185 230 3 7.4 1.0 10-1082
J185 200 3 7.5 1.0 10-1082
G185 460 3 3.7 1.0 10-1078
BA185 575 33.3 1.0 10-1134
F186 230 3 9.2 1.5 10-1082
J186 200 3 10.3 1.5 10-1083
G186 460 3 4.6 1.5 10-1080
BA186 575 33.6 1.5 10-1134
F188 230 3 8.9 1.5 10-1082
J188 200 3 10.3 1.5 10-1083
G188 460 3 4.6 1.5 10-1080
BA188 575 33.5 1.5 10-1134
F189 230 3 11.2 2.0 10-1083
J189 200 3 13.2 2.0 10-1084
G189 460 3 6.0 2.0 10-1080
BA189 575 35.8 2.0 10-1136
F266 230 3 2.6 0.5 10-1078
G266 460 3 1.5 0.5 10-1074
J266 200 3 2.6 0.5 10-1078
F267 230 3 2.6 0.5 10-1078
G267 460 3 1.5 0.5 10-1074
J267 200 3 2.6 0.5 10-1078
F268 230 3 2.6 0.5 10-1078
G268 460 3 1.5 0.5 10-1074
J268 200 3 2.6 0.5 10-1078
F282 230 3 3.0 0.5 10-1078
J282 200 3 3.6 0.5 10-1078
G282 460 3 1.7 0.5 10-1076
BA282 575 31.4 0.5 10-1130
F284 230 3 5.0 1.0 10-1080
J284 200 3 5.5 1.0 10-1080
G284 460 3 2.6 1.0 10-1078
BA284 575 32.2 1.0 10-1132
THREE PHASE CONTROL
PANEL
MODEL # VOLTS PHASE AMPS HP
F292 230 3 5.2 0.5 10-1080
J292 200 3 6.4 0.5 10-1082
G292 460 3 2.9 0.5 10-1078
BA292 575 32.4 0.5 10-1132
F293 230 3 7.6 1.0 10-1082
J293 200 3 8.2 1.0 10-1082
G293 460 3 4.0 1.0 10-1080
BA293 575 33.3 1.0 10-1134
F294 230 3 9.5 1.5 10-1082
J294 200 3 10.8 1.5 10-1083
G294 460 3 4.8 1.5 10-1080
BA294 575 33.8 1.5 10-1134
F295 230 3 12.2 2.0 10-1084
J295 200 3 14.3 2.0 10-1084
G295 460 3 6.1 2.0 10-1082
BA295 575 34.9 2.0 10-1136
F404 230 3 10.5 2.0 10-1083
J404 200 3 13.8 2.0 10-1084
G404 460 3 5.2 2.0 10-1080
BA404 575 34.1 2.0 10-1136
F405 230 3 12.2 3.0 10-1083
J405 200 3 14.8 3.0 10-1084
G405 460 3 6.1 3.0 10-1082
BA405 575 34.8 3.0 10-1136
F611 230 3 4.2 1.0 10-1080
G611 460 3 2.1 1.0 10-1076
J611 200 3 4.8 1.0 10-1080
BA611 575 31.7 1.0 10-1132
F621 230 3 5.1 1.5 10-1080
G621 460 3 2.6 1.5 10-1078
J621 200 3 5.9 1.5 10-1080
BA621 575 32.0 1.5 10-1132
F631 230 3 6.8 2.0 10-1082
G631 460 3 3.4 2.0 10-1078
J631 200 3 7.8 2.0 10-1082
BA631 575 32.7 2.0 10-1134
F641 230 3 9.6 3.0 10-1083
G641 460 3 4.8 3.0 10-1080
J641 200 3 11.0 3.0 10-1083
BA641 575 33.9 3.0 10-1134
F651 230 3 15.2 5.0 10-1084
G651 460 3 7.6 5.0 10-1082
J651 200 3 17.5 5.0 10-1086
BA651 575 36.1 5.0 10-1136
F661 230 3 22.0 7.5 10-1087
G661 460 3 11.0 7.5 10-1083
J661 200 3 25.3 7.5 10-1174
BA661 575 39.0 7.5 10-1138
SIMPLEX CONTROL PANEL RECOMMENDED APPLICATIONS