EXTROL® HYDRONIC EXPANSION TANKS FOR NON-POTABLE WATER INSTALLATION & OPERATION INSTRUCTIONS Models EX-15 through EX-90 Models SX-30V through SX-160V NOTE: Inspect for shipping damage. Notify freight carrier or store where purchased immediately if damage is present. To avoid risk of personal injury and property damage, if the product appears to be malfunctioning or shows signs of corrosion, call a qualified professional immediately. Current copies of the product manual can be viewed at www.amtrol.com. Use proper safety equipment when installing. THIS IS THE SAFETY ALERT SYMBOL. IT IS USED TO ALERT YOU TO POTENTIAL PERSONAL INJURY AND OTHER HAZARDS. OBEY ALL SAFETY MESSAGES THAT FOLLOW THIS SYMBOL TO REDUCE THE RISK OF PERSONAL INJURY AS WELL AS PROPERTY DAMAGE. USE ONLY IN CLOSED HYDRONIC SYSTEMS. Do not install on domestic water systems, or in open heating systems. Corrosion and tank failure may result. Use a ® Therm-X-Trol or Therm-X-Span® for domestic water systems. Use a Radiant EXTROL® for radiant heating systems where air elimination equipment or barrier tubing is not used. READ CAREFULLY THE PRODUCT INSTALLATION, OPERATING AND MAINTENANCE MANUAL. FAILURE TO FOLLOW THE INSTRUCTIONS AND WARNINGS IN THE MANUAL MAY RESULT IN SERIOUS OR FATAL INJURY AND/OR PROPERTY DAMAGE, AND WILL VOID THE PRODUCT WARRANTY. THIS PRODUCT MUST BE INSTALLED BY A QUALIFIED PROFESSIONAL. FOLLOW ALL APPLICABLE LOCAL AND STATE CODES AND REGULATIONS, IN THE ABSENCE OF SUCH CODES, FOLLOW THE CURRENT EDITIONS OF THE NATIONAL PLUMBING CODE AND NATIONAL ELECTRIC CODE, AS APPLICABLE. This Product, like most Products under pressure, may over time corrode, weaken and burst or explode, causing serious or fatal injury, leaking or flooding and/or property damage. To minimize risk, a licensed professional must install and periodically inspect and service the Product. A drip pan connected to an adequate drain must be installed if leaking or flooding could cause property damage. Do not locate in an area where leaking could cause property damage to the area adjacent to the appliance or to lower floors of the structure. CALIFORNIA PROPOSITION 65 WARNING! This product contains a chemical known by the State of California to cause cancer and to cause birth defects or other reproductive harm. (California Installer/Contractor - California law requires that this notice be given to consumer/end user of this product.) For more information: www.amtrol.com/prop65.html RUPTURE OR EXPLOSION HAZARD. Do not expose product to freezing temperatures or temperatures in excess of 240°F. Do not adjust the pre-charge or re-charge this Product except during installation or regular inspection. Replace the Product and do not adjust the pre-charge if corroded, damaged or with diminished integrity. Adjustments to pre-charge must be done at ambient temperature only. Failure to properly size the Product or follow these instructions may result in excessive strain on the system and may lead to Product failure, serious or fatal personal injury, leakage, and/or property damage. A relief valve must be installed to prevent pressure in excess of local code requirement or maximum working pressure designated in the Product Manual, whichever is less. At least once every 3 years or if discharge is present, a licensed contractor should inspect the pressure relief valve and replace if corrosion is evident or the valve does not function. FAILURE TO INSPECT THIS VALVE AS DIRECTED COULD RESULT IN UNSAFE PRESSURE BUILD-UP WHICH CAN RESULT IN PRODUCT FAILURE, SERIOUS INJURY OR DEATH AND/OR SEVERE PROPERTY DAMAGE AND VOID THE PRODUCT WARRANTY. Chlorine & Aggressive Water: The water quality can significantly influence the life of this Product. You should test for corrosive elements, acidity, total solids and other relevant contaminants, including chlorine and treat your water appropriately to insure satisfactory performance and prevent premature failure. PLEASE READ THE FOLLOWING INSTRUCTIONS CAREFULLY IMPORTANT GENERAL SAFETY INFORMATION ADDITIONAL SPECIFIC SAFETY ALERTS APPEAR IN THE FOLLOWING INSTRUCTIONS. Pre-Installation 1 Visually inspect for any damage. Ensure expansion tank is sized properly for application (Figure 1). 2. Remove plastic cap from air valve. 3. With tank empty of water, adjust air precharge to match system fill pressure. 4. Replace and tighten plastic cap on air valve. FAILURE TO PROPERLY SEAL VALVE CAP WILL RESULT IN LOSS OF PRECHARGE CAUSING PRODUCT TO FAIL. 2. Install the EXTROL on the supply side of the boiler, on the suction-side of the heating circulator(s) (Figure 2). 3. Pressurize the system and check for leaks. Repair as necessary. 4. Restart the boiler system and check for relief valve discharge. If the relief valve drips, the tank may be improperly charged or undersized. 5. The EXTROL is now operational and will absorb expanded water during boiler operation. Maintenance Models SX-30V through SX-60V are floor standing and may not be hung from the piping. A professional plumber should check the complete system, including the expansion tank, yearly and more frequently as the system ages. Checking the precharge allows a small quantity of air to escape and can result in an insufficient air charge. Always check the precharge while the tank is isolated and empty of water, and be sure to maintain the proper precharge whenever the tank is inspected. Do not install the EXTROL on a dead-end pipe or wherever air can collect. This can cause corrosion and possible leakage. EX Models: Five (5) Year Limited Warranty Mount tank vertically only. Ensure the piping can support the entire weight of the tank when full of water. Installation Warranty SX Models: One (1) Year Limited Warranty 1. Drain the boiler system or isolate the area where the EXTROL will be installed. Visit www.amtrol.com for complete warranty details. Figure 1. Figure 2. Boiler Type of Radiation Net Output Finned Tube Convectors Radiators Baseboard in 1000’S Baseboard or or Unit Cast Iron Cast Iron of BTU/Hr. Radiant Panel Heaters 25 EX-15 EX-15 EX-15 EX-15 50 EX-15 EX-15 EX-30 EX-30 75 EX-30 EX-30 EX-30 EX-60 100 EX-30 EX-30 EX-60 EX-60 125 EX-30 EX-60 EX-60 EX-90 150 EX-30 EX-60 EX-90 EX-90 175 EX-60 EX-60 SX-30V SX-30V 200 EX-60 EX-60 SX-30V SX-30V 250 EX-60 EX-90 SX-30V SX-40V 300 EX-90 SX-30V SX-30V SX-40V 350 SX-30V SX-30V SX-40V SX-60V 400 SX-30V SX-40V SX-40V SX-60V Sizing based on: 12 psig Fill; 30 psig Relief Valve; 200°F Average Temperature. In-Line Models: EX-15 through EX-90 Air Vent Air Purger System Supply Flow-Check Valve PressureReducing Valve Shut-Off Valve Circulator Backflow Preventer Shut-Off Valve Water Supply System Return System Purge Relief Valve Extrol Expansion Tank Boiler Type of Radiation and Piping System Boiler Finned Tube Net Output in Baseboard or Radiant 1000’s of BTU Panels with Series Loop System 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1,000 1,100 1,200 1,300 1,400 1,500 SX- 30V SX- 30V SX- 30V SX-30V SX-30V SX-40V SX-40V SX-40V SX-40V SX-60V SX-60V SX-60V SX-60V SX-60V SX-60V SX-90V SX-90V SX-90V SX-90V SX-90V SX-110V SX-110V Convectors or Unit Heaters with One Pipe System SX-30V SX-30V SX-30V SX-30V SX-40V SX-40V SX-40V SX-60V SX-60V SX-60V SX-60V SX-60V SX-90V SX-90V SX-90V SX-90V SX-90V SX-90V SX-90V SX-110V SX-130V SX-130V Radiators or One Pipe System SX-30V SX-30V SX-40V SX-40V SX-60V SX-90V SX-60V SX-60V SX-90V SX-90V SX-90V SX-90V SX-90V SX-90V SX-110V SX-110V SX-110V SX-110V SX-110V SX-130V SX-160V SX-160V Cast Iron Radiators with Series Loop System SX-30V SX-40V SX-40V SX-60V SX-60V SX-90V SX-90V SX-90V SX-90V SX-90V SX-90V SX-110V SX-110V SX-110V SX-110V SX-110V SX-110V SX-130V SX-130V SX-160V SX-160V (2)SX-110V Stand Models: SX-30V through SX-160V Air Vent Air Separator System Supply Flow-Check Valve PressureReducing Valve Backflow Preventer Shut-Off Valve Shut-Off Valve System Purge Water Supply System Return Circulator Relief Valve Extrol Expansion Tank Boiler Sizing based on: Average Boiler Water Volume; Average Water Volume; Fill Pressure 12 psig; Relief Pressure 30 psig © 2014 AMTROL Inc. 1400 Division Road, West Warwick, RI USA 02893 T: 800.426.8765 F: 800.293.1519 www.amtrol.com Mark of the Originator Part #: 9015-183 (06/14)
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes Create Date : 2014:07:02 15:38:15-04:00 Creator : Adobe InDesign CS5 (7.0) Modify Date : 2015:05:11 11:00:10-04:00 Tagged PDF : Yes XMP Toolkit : Adobe XMP Core 5.4-c005 78.147326, 2012/08/23-13:03:03 Metadata Date : 2015:05:11 11:00:10-04:00 Creator Tool : Adobe InDesign CS5 (7.0) Page Image Page Number : 1, 2 Page Image Format : JPEG, JPEG Page Image Width : 256, 256 Page Image Height : 256, 256 Page Image : (Binary data 10972 bytes, use -b option to extract), (Binary data 13204 bytes, use -b option to extract) Instance ID : uuid:7bc7e267-c5c2-4ab3-bac9-85bf4e0601b9 Document ID : xmp.did:CC4A06AD0D2068118083F8181B0B97E8 Original Document ID : xmp.did:5312D5C30F20681180839DCD3F44A4EF Rendition Class : proof:pdf History Action : created, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved History Instance ID : xmp.iid:5312D5C30F20681180839DCD3F44A4EF, xmp.iid:D6AF5DA91020681180839DCD3F44A4EF, xmp.iid:D7AF5DA91020681180839DCD3F44A4EF, xmp.iid:0F5159271320681180839DCD3F44A4EF, xmp.iid:FEBB90C91420681180839DCD3F44A4EF, xmp.iid:187B2D321520681180839DCD3F44A4EF, xmp.iid:CB95A4AE1520681180839DCD3F44A4EF, xmp.iid:855D690A1820681180839DCD3F44A4EF, xmp.iid:448B7A091920681180839DCD3F44A4EF, xmp.iid:840A32602820681180839DCD3F44A4EF, xmp.iid:37789CE4C520681180839DCD3F44A4EF, xmp.iid:D742E055C920681180839DCD3F44A4EF, xmp.iid:888065F4CE20681180839DCD3F44A4EF, xmp.iid:F7BF3388092068118083B1070EFE8E45, xmp.iid:BB0382AA0D2068118083F8181B0B97E8, xmp.iid:BC0382AA0D2068118083F8181B0B97E8, xmp.iid:CC4A06AD0D2068118083F8181B0B97E8, xmp.iid:CCC09357102068118083F8181B0B97E8, xmp.iid:AD7141A0712068118C14FFF55A489FC5, xmp.iid:F4EBB075722068118C14FFF55A489FC5, xmp.iid:DA8A362E962068118C14FFF55A489FC5, xmp.iid:F471703F962068118C14FFF55A489FC5, xmp.iid:7D2F1E74072068118083EC7F5CA03946, xmp.iid:C7AA8C72082068118083EC7F5CA03946, xmp.iid:799AFB713420681195FEDE729445C80E, xmp.iid:5C1B26DE5A20681195FEDE729445C80E, xmp.iid:1BA1137407206811871FE131CE053400, xmp.iid:BA10377B0D206811871FE131CE053400, xmp.iid:6065EB1B1F206811871FE131CE053400, xmp.iid:4949D10B182268118C14BEF610A9D84C, xmp.iid:FAB8CD3F1D2268118C14BEF610A9D84C History When : 2013:05:13 11:18:33-04:00, 2013:05:13 11:24:14-04:00, 2013:05:13 11:24:14-04:00, 2013:05:13 11:42:05-04:00, 2013:05:13 11:53:46-04:00, 2013:05:13 11:56:42-04:00, 2013:05:13 12:00:11-04:00, 2013:05:13 12:17:04-04:00, 2013:05:13 12:24:12-04:00, 2013:05:13 14:14-04:00, 2013:05:14 09:01:33-04:00, 2013:05:14 09:26:11-04:00, 2013:05:14 10:06:25-04:00, 2013:05:15 09:19:22-04:00, 2013:05:16 09:55:36-04:00, 2013:05:16 09:55:40-04:00, 2013:05:16 09:55:40-04:00, 2013:05:16 10:14:45-04:00, 2014:02:26 15:53:44-05:00, 2014:02:26 15:59:42-05:00, 2014:02:27 11:01:17-05:00, 2014:02:27 11:01:46-05:00, 2014:05:22 11:47:31-04:00, 2014:05:22 11:54:38-04:00, 2014:05:23 08:40:27-04:00, 2014:05:23 15:22:06-04:00, 2014:06:26 13:10:46-04:00, 2014:06:26 13:53:55-04:00, 2014:06:26 16:00:06-04:00, 2014:07:01 14:24:03-04:00, 2014:07:01 15:01:17-04:00 History Software Agent : Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0 History Changed : /;/metadata, /metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata Derived From Instance ID : xmp.iid:BC0382AA0D2068118083F8181B0B97E8 Derived From Document ID : xmp.did:5312D5C30F20681180839DCD3F44A4EF Derived From Original Document ID: xmp.did:5312D5C30F20681180839DCD3F44A4EF Derived From Rendition Class : default Doc Change Count : 761 Format : application/pdf Producer : Adobe PDF Library 9.9 Trapped : False Page Count : 2EXIF Metadata provided by EXIF.tools