64376 3 Generac 6245 Product Specs

: Pump 64376 3 Generac 6245 Product Specs 64376_3_Generac 6245 Product specs pdf

Open the PDF directly: View PDF PDF.
Page Count: 5

1 of 5
¡ INNOVATIVE DESIGN & PROTOTYPE TESTING are key components
of GENERAC’S success in “IMPROVING POWER BY DESIGN.” But it
doesn’t stop there. Total commitment to component testing, reliability
testing, environmental testing, destruction and life testing, plus testing
to applicable CSA, NEMA, EGSA, and other standards, allows you to
choose GENERAC POWER SYSTEMS with the confidence that these
systems will provide superior performance.
¡
TRUE POWER™ ELECTRICAL TECHNOLOGY: Superior harmonics
and sine wave form produce less than 5% Total Harmonic Distortion for
utility quality power. This allows confident operation of sensitive electronic
equipment and micro-chip based appliances, such as variable speed HVAC
systems.
¡ TEST CRITERIA:
PROTOTYPE TESTED NEMA MG1-22 EVALUATION
SYSTEM TORSIONAL TESTED MOTOR STARTING ABILITY
¡ SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION.
This state-of-the-art power maximizing regulation system is standard on
all Generac models. It provides optimized FAST RESPONSE to changing
load conditions and MAXIMUM MOTOR STARTING CAPABILITY by
electronically torque-matching the surge loads to the engine. Digital
voltage regulation at ±1%.
¡ SINGLE SOURCE SERVICE RESPONSE from Generac’s extensive dealer
network provides parts and service know-how for the entire unit, from the
engine to the smallest electronic component.
¡ GENERAC TRANSFER SWITCHES. Long life and reliability are
synonymous with GENERAC POWER SYSTEMS. One reason for this
confidence is that the GENERAC product line includes its own transfer
systems and controls for total system compatibility.
Includes:
True Power™ Electrical Technology
Two Line LCD Multi-Lingual Digital
Evolution™ Controller (English/Spanish/
French /Portuguese)
Two Transfer Switch Options Available:
50 or 100 Amp Pre-Wired Switch or
200 Amp Smart Switch.
See Page 4 for Details.
Electronic Governor
External Main Circuit Breaker,
System Status & Maintenance
Interval LED Indicators
Sound Attenuated Enclosure
Flexible Fuel Line Connector
Composite Mounting Pad
Natural Gas or LP Gas Operation
5 Year Limited Warranty
UL 2200 Listed
Standby Power Rating
Models 006237-0, 006245-0 (Steel - Bisque) - 8 kW 60Hz
Models 006437-0, 006438-0, 006439-0 (Steel - Bisque) - 11 kW 60Hz
Models 006240-0, 006241-0, 006247-0 (Steel - Bisque) - 14 kW 60Hz
FEATURES
GUARDIAN® SERIES
Residential Standby Generators
Air-Cooled Gas Engine
8/11/14kW
®
8/11/14kW
*Note: CUL certification only applies to unbundled units and units packaged with pre-wired switches.
Units packaged with the Smart Switch are UL certified in the USA only.
2 of 5
8/11/14kW features and benefits
Engine
•Generac (OHVI) design Maximizes engine “breathing” for increased fuel efficiency. Plateau honed cylinder walls and plasma moly rings
helps the engine run cooler, reducing oil consumption resulting in longer engine life.
•“Spiny-lok” cast iron cylinder walls Rigid construction and added durability provide long engine life.
•Electronic ignition/spark advance These features combine to assure smooth, quick starting every time.
•Full pressure lubrication system Pressurized lubrication to all vital bearings means better performance, less maintenance and longer engine life.
Now featuring up to a 2 year/200 hour oil change interval.
•Low oil pressure shutdown system Superior shutdown protection prevents catastrophic engine damage due to low oil.
•High temperature shutdown Prevents damage due to overheating.
Generator
•Revolving field
Allows for smaller, light weight unit that operates 25% more efficiently than a revolving armature generator.
Skewed stator Produces a smooth output waveform for compatibility with electronic equipment.
•Displaced phase excitation
Maximizes motor starting capability.
•Automatic voltage regulation Regulates the output voltage to ±1% prevents damaging voltage spikes.
•UL 2200 listed For your safety.
Transfer Switch
•Fully automatic Transfers your vital electrical loads to the energized source of power.
•Pre-wired, color-coded conduits
(Pre-wired switches only)
Ensures the easiest, trouble-free installation.
•DPM Technology
(Smart Switch only)
Digital Power Management Technology allows for the smart control of two air conditioners without any additional
items.
•Remote mounting Mounts near your existing distribution panel for simple, low-cost
Evolution™ Controls
•Auto/Manual/Off illuminated buttons Selects the operating mode and provides easy, at-a-glance status indication in any condition.
•Sealed, raised buttons Smooth, weather-resistant user interface for programming and operations.
•Utility voltage sensing Constantly monitors utility voltage, setpoints 60% dropout, 80% pick-up, of standard voltage.
•Generator voltage sensing Constantly monitors generator voltage to ensure the cleanest power delivered to the home.
•Utility interrupt delay Prevents nuisance start-ups of the engine, adjustable 2-1500 seconds from the factory default setting of 10
seconds by a qualified dealer.
•Engine warm-up Ensures engine is ready to assume the load, setpoint approximately 5 seconds.
•Engine cool-down Allows engine to cool prior to shutdown, setpoint approximately 1 minute.
•Programmable seven day exerciser Operates engine to prevent oil seal drying and damage between power outages by running the generator for 12
minutes every week.
•Smart battery charger Delivers charge to the battery only when needed at varying rates depending on outdoor air temperature.
•Main line circuit breaker Protects generator from overload.
•Electronic governor Maintains constant 60 Hz frequency.
Unit
•Weather protective enclosure Ensures protection against mother nature. Hinged key locking roof panel for security. Lift-out front for easy access
to all routine maintenance items. Electrostatically applied textured epoxy paint for added durability.
•Enclosed critical grade muffler Quiet, critical grade muffler is mounted inside the unit to prevent injuries.
•Small, compact, attractive Makes for an easy, eye appealing installation.
•SAE Sound attenuated enclosure ensures quiet operation.
Installation System
•1ft. (305mm) flexible fuel line connector Easy installation.
•Composite mounting pad
8/11/14kW
®
3 of 5
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514,
ISO3046 and DIN6271). * Maximum wattage and current are subject to and limited by such factors as fuel Btu/megajoule content, ambient temperature, altitude, engine power and condition, etc. Maximum
power decreases about 3.5 percent for each 1,000 feet (304.8 meters) above sea level; and also will decrease about 1 percent for each 6° C (10° F) above 16° C (60°F). Sound output ratings from certain
points on the generator subject to change based on installation parameters.
Generator
Model 006237-0, 006245-0 (8 kW)
006437-0, 006438-0,
006439-0 (11 kW)
006240-0, 006241-0,
006247-0, (14 kW)
Rated Maximum Continuous Power Capacity (LP) 8,000 Watts* 11,000 Watts* 14,000 Watts*
Rated Maximum Continuous Power Capacity (NG) 7,000 Watts* 10,000 Watts* 14,000 Watts*
Rated Voltage 240 240 240
Rated Maximum Continuous Load Current – 240 Volts (LP/NG) 33.3/29.2 45.8/41.7 58.3/58.3
Total Harmonic Distortion Less than 5% Less than 5% Less than 5%
Main Line Circuit Breaker 35 Amp 50 Amp 60 Amp
Phase 1 1 1
Number of Rotor Poles 2 2 2
Rated AC Frequency 60Hz 60Hz 60Hz
Power Factor 1.0 1.0 1.0
Battery Requirement (not included) Group 26R, 12 Volts and 525 CCA Minimum
Unit Weight (Pounds/Kilos) 360/163.3 407/184.6 435/197.3
Dimensions (L x W x H) in./mm 48 x 25 x 29/1218 x 638 x 732
Sound output in dB(A) at 23 ft. (7m) with generator operating at normal load 62 63 66
Engine
Type of Engine GENERAC OHVI GENERAC OHVI V-TWIN GENERAC OHVI V-TWIN
Number of Cylinders 122
Displacement 410cc 530cc 992cc
Cylinder Block Aluminum w/Cast Iron Sleeve Aluminum w/Cast Iron Sleeve Aluminum w/Cast Iron Sleeve
Valve Arrangement Overhead Valve Overhead Valve Overhead Valve
Ignition System Solid-state w/Magneto Solid-state w/Magneto Solid-state w/Magneto
Governor System Electronic Electronic Electronic
Compression Ratio 9.5:1 9.5:1 9.5:1
Starter 12 Vdc 12 Vdc 12 Vdc
Oil Capacity Including Filter Approx. 1.5 Qts./1.4L Approx. 1.7 Qts./1.6L Approx. 1.9 Qts./1.8L
Operating RPM 3,600 3,600 3,600
Fuel Consumption
Natural Gas ft³/hr (m³/hr)
1/2 Load
Full Load
Liquid Propane ft3/hr (gal/hr) [Liters/hr]
1/2 Load
Full Load
72 (2.21)
121 (3.43)
31.6 (0.87) [3.29]
51.6 (1.42) [5.37]
124 (3.51)
195 (5.52)
42.8 (1.18) [4.45]
70 (1.92) [7.28]
177 (5.01)
279 (7.9)
67.2 (1.85) [6.99]
111.6 (3.07) [11.61]
Note: Fuel pipe must be sized for full load. Required fuel pressure to generator fuel inlet at all load ranges - 3.5-7" water column (7-13mm mercury) for natural gas, 10-12" water column (19-22mm
mercury) for LP gas. For Btu content, multiply ft3/hr x 2500 (LP) or ft3/hr x 1000 (NG). For Megajoule content, multiply m³/hr x 93.15 (LP) or m³/hr x 37.26 (NG).
Controls
2-Line Plain Text Multi-Lingual LCD Display Simple user interface for ease of operation.
Mode Buttons: Auto Automatic Start on Utility failure. 7 day exerciser.
Manual Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Off Stops unit. Power is removed. Control and charger still operate.
Ready to Run/Maintenance Messages Standard
Engine Run Hours Indication Standard
Programmable start delay between 2-1500 seconds Standard (programmable by dealer only)
Utility Voltage Loss/Return to Utility Adjustable From 140-171V/190-216V
Future Set Capable Exerciser/Exercise Set Error Warning Standard
Run/Alarm/Maintenance Logs 50 Events Each
Engine Start Sequence Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration).
Starter Lock-out Starter cannot re-engage until 5 sec. after engine has stopped.
Smart Battery Charger Standard
Charger Fault/Missing AC Warning Standard
Low Battery/Battery Problem Protection and Battery Condition Indication Standard
Automatic Voltage Regulation with Over and Under Voltage Protection Standard
Under-Frequency/Overload/Stepper Overcurrent Protection Standard
Safety Fused/Fuse Problem Protection Standard
Automatic Low Oil Pressure/High Oil Temperature Shutdown Standard
Overcrank/Overspeed (@ 72Hz)/RPM Sense Loss Shutdown Standard
High Engine Temperature Shutdown Standard
Internal Fault/Incorrect Wiring Protection Standard
Common External Fault Capability Standard
Field Upgradable Firmware Standard
8/11/14kW specifications
8/11/14kW
®
4 of 5
8/11/14kW
8/11/14kW switch options
®
Model 006237-0 (8 kW) Model 006437-0 (11 kW) Model 006240-0 (14 kW)
No. of Poles 2 2 2
Current Rating (Amps) 50 50 100
Voltage Rating (VAC) 250 250 250
Utility Voltage Monitor (Fixed)*
-Pick-up
-Dropout
80%
60%
80%
60%
80%
60%
Return to Utility* approx. 15 sec. approx. 15 sec. approx. 15 sec.
Exerciser weekly for 12 minutes* Standard Standard Standard
UL Listed Standard Standard Standard
Total of Pre-wired Circuits
No. 15A 120V
No. 20A 120V
No. 20A 240V
No. 30A 240V
No. 40A 240V
No. 50A 240V
10
3
3
1
1
-
-
12
5
3
-
1
1
-
14
4
6
1
-
1
-
Circuit Breaker Protected
Available RMS Symmetrical
Fault Current @ 250 Volts 10,000 10,000 10,000
Pre-Wired Switch Features
Electrically operated, mechanically-held contacts
for fast, positive connections.
Rated for all classes of load, 100% equipment
rated, both inductive and resistive.
• 2 pole, 250 VAC contactors.
• 30 millisecond transfer time.
• Dual coil (100A) and single coil (50A) designs.
Main contacts are silver plated or silver alloy to
resist welding and sticking.
NEMA 1 (indoor rated) enclosure is standard on
the pre-wired switch.
Pre-wired 30 foot (9.1 meter) whip to connect to
the provided 5 foot pre-wired whip and external
connection box.
Pre-wired 2 foot (0.61 meter) whip, color coded to
connect into the existing electrical panel.
Mechanical Dimensions
Amps Height Width Depth
H1 H2 H3 W1 W2 W3
50 18.5 in. 22.5 in. 22 in. 10.5 in. 15.4 in. 14.4 in. 3.8 in
470mm 571.8mm 558.8mm 266.7 392mm 366mm 97.5mm
100 23.5 in. 26.4 in. N/A 8.3 in. 12.6 in. N/A 6.3 in.
597mm 671.7mm N/A 211mm 320.7mm N/A 159.6mm
Wire Ranges
Amps Conductor Lug Neutral Lug Ground Lug
50 1/0 - #14 2/0 - #14 2/0 - #14
100 2/0 - #14 2/0 - #14 2/0 - #14
Dimensions
Dimensions
Smart Switch Features
available on 11 & 14kW models only
• Includes Digital Power Management Technology standard (DPM).
• Intelligently manages two air conditioner loads with no additional hardware.
Up to four more large (120/240VAC) loads can be managed when used in
conjunction with Power Management Modules (PMM).
Electrically operated, mechanically-held contacts for fast, clean connections.
Rated for all classes of load, 100% equipment rated, both inductive and resistive.
• Service equipment rated, dual coil design.
• Rated for both aluminum and copper conductors.
• NEMA/UL 3R aluminum outdoor enclosure.
• Main contacts are silver plated or silver alloy to resist welding and sticking.
Model 006438-0 (11kW) / 006241-0 (14kW)
No. of Poles 2
Current Rating (Amps) 200
Voltage Rating (VAC) 250
Utility Voltage Monitor (Fixed)*
-Pick-up
-Dropout
80%
60%
Return to Utility* approx. 13 sec.
Exercise weekly for 12 minutes* Standard
UL Listed Standard
Enclosure Type NEMA/UL 3R
Withstand Rating (Amps) 22,000
Lug Range 250MCM - #6
H2
DEPTH
H1
W2
W1
200 Amps 120/240, 1ø
Open Transition Service Rated
Height Width Depth
H1 H2 W1 W2
Inches 27.24 30.0 11.4 13.5 7.09
mm 692.0 762.4 289.0 343.0 180.0
*Function of Evolution Controller
Note: The 50 amp switch is flush mountable. H1 and W1 refer to mounting hole spacing.
H2 and W2 are cover dimensions. H3 and W3 are the enclosure dimensions without cover.
*Function of Evolution Controller
H1
W1
W2
H2
H1
W1
W2
H2
50 Amp Switch
100 Amp Switch
5 of 5
®
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2013 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0197980SBY-E Printed in U.S.A. 04/05/13
731.9 mm
[28.8 in.]
637.6 mm
[25.1 in.]
LEFT SIDE VIEW
642 mm
[25.3 in.] 76.2 mm [3.0 in.]
PEA GRAVEL
MINIMUM
TRANSFER
SWITCH
8KW - 17KW
(IF SUPPLIED)
TRANSFER
SWITCH
20KW
(IF SUPPLIED)
1218 mm
[47.9 in.]
FRONT VIEW
1226 mm
[48.3 in.]
H2
H1
W1
W2
H2
H1
W1
W2
Dimensions shown are approximate. Contact your Generac dealer for certified drawings. DO NOT USE THESE DIMENSIONS FOR INSTALLATION PURPOSES.
®
Model # Product Description
5819 26R Wet Cell Battery Every standby generator requires a battery to start the system. Generac offers the
recommended 26R wet cell battery for use with all air-cooled standby product.
6212 Cold Weather Kit
If the temperature regularly falls below 32°F (0°C), install a cold weather kit to maintain
optimal battery and oil temperatures. Kit consists of a battery warmer and oil filter heater with
built-in thermostats.
5621 Auxiliary Transfer Switch
Contact Kit
The auxiliary transfer switch contact kit allows the transfer switch to lock out a single large
electrical load you may not need. Not compatible with 50 amp pre-wired switches.
5839 Fascia Base Wrap Kit
The fascia base wrap snaps together around the bottom of the new air cooled generators.
This offers a sleek, contoured appearance as well as offering protection from rodents and
insects by covering the lifting holes located in the base.
5703 Paint Kit
If the generator enclosure is scratched or damaged, it is important to touch-up the paint to
protect from future corrosion. The paint kit includes the necessary paint to properly maintain
or touch-up a generator enclosure.
6482 - 8kW
6483 - 11kW
6484 - 14kW
Scheduled Maintenance Kit Generac's scheduled maintenance kits provide all the hardware necessary to perform
complete routine maintenance on a Generac automatic standby generator.
5928 Wireless Remote
Completely wireless and battery powered, Generac's wireless remote monitor provides
you with instant status information without ever leaving the house. Not compatible with
CorePower or EcoGen systems.
5951 Advanced Wireless Remote
Remotely control generator functions with the advanced model's LCD display. In addition to
remote testing of the generator, set the excercise cycle and maintenance interval reminders.
Not compatible with CorePower or EcoGen systems.
6199 PMM Starter Kit
The PMM Starter Kit consists of a 24VAC, field installed transformer that enables the use
of the 24VAC Power Management Modules (PMMs) and one PMM. The standard controller
(without starter kit) can control two HVAC loads with no additional hardware.
6186 Power Management Module
(50 Amps)
Power Management Modules are used in conjunction with the Smart Switch to increase its
power management capabilities. It gives the Smart Switch additional power management
flexibility not found in any other transfer switch. Not compatible with pre-wired switches.
6463 Mobile Link™ Device
Generac's Mobile Link device allows you to check the status of your generator from anywhere
that you have access to an Internet connection from a PC or with any smart device. You will
even be notified when a change in the generator’s status occurs via e-mail or text message.
8/11/14kW available accessories
dimensions
®
8/11/14kW

Navigation menu