71738 3 Berkeley B15P4MS10231 Cable Selection Guide

71740 3 Berkeley B20P4Ms07221 Cable Selection Guide 71740_3_Berkeley B20P4MS07221 Cable Selection Guide

71742 3 Berkeley B20P4Ms15221 Cable Selection Guide 71742_3_Berkeley B20P4MS15221 Cable Selection Guide

71744 3 Berkeley B20P4Ms10231 Cable Selection Guide 71744_3_Berkeley B20P4MS10231 Cable Selection Guide

71745 3 Berkeley B20P4Ms15231 Cable Selection Guide 71745_3_Berkeley B20P4MS15231 Cable Selection Guide

71746 3 Berkeley B30P4Ms10221 Cable Selection Guide 71746_3_Berkeley B30P4MS10221 Cable Selection Guide

: Pump 71738 3 Berkeley B15P4Ms10231 Cable Selection Guide 71738_3_Berkeley B15P4MS10231 Cable Selection Guide pdf

Open the PDF directly: View PDF PDF.
Page Count: 2

Customer Service: 1-888-782-7483 (USA) 1-888-363-PUMP (Canada) www.berkeleypumps.com Pentair Water Delavan, WI 53115 USA CB6342WS (10/24/11)
1
Cable Selection 4" submersible motors
Two different cable sizes can be used.
The example below is for reference and uses the CSIR chart below.
Depending on the installation, any number of combinations may be
used, as long as the total percentage length of the two cables used
does not exceed 100%. This is to ensure that adequate voltage will be
supplied to the motor.
In a replacement installation, the well already has 210 feet of buried
#12 cable between the service entrance and the well head. The
question is: What size cable is required in the well with a 1 HP, 230 Volt,
1 PH, 3W motor setting at 310 feet?
1. According to the table, #12 cable is large enough for the 1 HP motor
so the percent of the maximum allowable cable used by the 210-foot
run is 210 ÷ 359 = 58.5%, since 359 feet is the total allowable.
2. With 58.5% of the total allowable cable already used between the
service entrance and the well head, only 41.5% is left for the well.
Therefore, the 310 feet needed in the well can only utilize 41.5% of
the total feet allowed in the table.
3. From the table, 41.5% of the 573 feet for #10 cable equals only 238
feet, so a larger size is needed. For #8, 41.5% of 908 feet = 377 feet.
As a result, #8 can be used for the 310 feet in the well.
NOTE: Based on service factor amps, 30C ambient and 5% voltage drop.
(1) This table is based on copper wire. If aluminum wire is used it must be two sizes larger. Example: When the table calls for
#12 copper wire you would use #10 aluminum wire.
(2) Cables #14 to #0000 are AWG sizes.
EXAMPLE:
1 HP,
230 Volt, 3W,
1 PH Motor
using CSIR
chart
CAUTION
Use of wire size smaller than listed will void warranty.
All lengths in feet.
PENTEK® is a registered trademark of Pentair Water.
MOTOR LEAD LENGTHS – PENTEK® 2-WIRE MOTORS
60 Hz Motor Rating 60C and 75C Insulation – AWG Copper Wire Size
Volts HP 14 12 10 8643211/0 2/0 3/0 4/0
115 1/2 115 183 293 463 721 1150 1445 1825 2299 2902 3662 4623 5824
230
1/2 466 742 1183 1874 2915 4648 5843 7379 9295 11733
3/4 342 545 869 1376 2141 3413 4291 5419 6826 8617 10871
1 241 383 611 968 1506 2400 3018 3811 4801 6060 7646 9652
1-1/2 199 317 505 801 1246 1986 2496 3153 3972 5013 6325 7985
MOTOR LEAD LENGTHS – PENTEK 3-WIRE MOTORS
CSIR Control Boxes
60 Hz Motor Rating 60C and 75C Insulation – AWG Copper Wire Size
Volts HP 14 12 10 8643211/0 2/0 3/0 4/0
115 1/2 87 138 221 349 544 867 1090 1376 1734 2188 2761 3485 4391
230
1/2 348 553 883 1398 2175 3467 4359 5505 6935 8753
3/4 264 420 670 1061 1651 2632 3309 4178 5264 6644 8383
1 226 359 573 908 1413 2252 2831 3575 4504 5685 7173
CSCR Control Boxes
60 Hz Motor Rating 60C and 75C Insulation – AWG Copper Wire Size
Volts HP 14 12 10 8643211/0 2/0 3/0 4/0
230
1/2 447 711 1135 1797 2796 4458 5604 7078 8916 11254
3/4 348 553 883 1398 2175 3467 4359 5505 6935 8753 11044
1 304 484 772 1223 1903 3034 3814 4817 6068 7659 9663
1-1/2 197 314 501 793 1234 1968 2474 3124 3936 4968 6268
2180 286 456 722 1123 1790 2251 2843 3581 4520 5703
3133 211 337 534 830 1324 1664 2102 2648 3342 4217 5323
5206 326 507 809 1017 1284 1618 2042 2577 3253
Customer Service: 1-888-782-7483 (USA) 1-888-363-PUMP (Canada) www.berkeleypumps.com Pentair Water Delavan, WI 53115 USA CB6342WS (10/24/11)
2
NOTE: Based on service factor amps, 30C ambient and 5% voltage drop.
(1) This table is based on copper wire. If aluminum wire is used it must be two sizes larger. Example: When the table calls for
#12 copper wire you would use #10 aluminum wire.
(2) The portion of the total cable that is between the service entrance and a 3-phase motor starter should not exceed 25% of the
total maximum length to assure reliable starter operation.
(3) Cables #14 to #0000 are AWG sizes.
All lengths in feet.
MOTOR LEAD LENGTHS – PENTEK® 3-PHASE MOTORS
60 Hz Motor Rating 60C AND 75C Insulation – AWG Copper Wire Size
Volts HP 14 12 10 8643211/0 2/0 3/0 4/0
200
0.5 657 1045 1667 2641 4109
3/4 423 674 1074 1702 2648
1346 551 879 1392 2166 3454 4342
1.5 265 421 672 1064 1655 2638 3317
2217 344 549 870 1354 2158 2714 3427 4317 5449
3159 253 403 638 993 1583 1990 2513 3166 3996
594 150 239 379 590 940 1182 1493 1881 2374 2995 3781 4764
7.5 64 101 161 255 397 633 796 1005 1266 1598 2017 2546 3207
230
0.5 756 1202 1917 3037 4725 7532 9469
0.75 562 894 1426 2258 3513 5601 7041 8892
1466 742 1183 1874 2915 4648 5843 7379
1.5 359 571 912 1444 2246 3581 4502 5685 7162 9040
2288 459 732 1159 1803 2874 3613 4563 5748 7256 9155
3217 345 551 872 1357 2163 2719 3434 4326 5460 6889 8696 10956
5318 503 783 1248 1569 1982 2496 3151 3976 5019 6323
7.5 334 519 827 1040 1314 1655 2089 2635 3327 4192
460
0.5 2922 4648 7414
0.75 2191 3486 5560 8806
11753 2789 4448 7045
1.5 1370 2179 3475 5504
21153 1835 2926 4635 7212
3827 1315 2098 3323 5171
5516 820 1308 2072 3224 5140
7.5 325 516 824 1305 2030 3236 4068 5138 6472
10 255 405 647 1024 1593 2540 3193 4033 5080
575
1.5 2283 3631 5792
21660 2641 4212 6671
31336 2126 3390 5370
5721 1147 1829 2897 4507
7.5 548 871 1390 2202 3426
Cable Selection 4" submersible motors