RCI 6 Series/7 Series Installation Instructions IS6A R0614

User Manual: RCI 6 Series/7 Series Installation Instructions Installation Instructions

Open the PDF directly: View PDF PDF.
Page Count: 6

1. Determine the vertical centerline of the door lock face and
the horizontal centerline of the latch.
IMPORTANT: When determining the horizontal centerline
observe the following:
FOR MORTISE LOCKS: Align the angled ramps of the lip
bracket with the deadlock trigger of the mortise latch.
FOR CYLINDRICAL LOCKS: Align the center of the latch with
the center of the strike opening.**
2. Transfer both the horizontal and vertical centerlines to the
doorframe.**
3. Prepare the doorframe for cutting as shown in the
appropriate drawing.
4. If required, install the ‘no weld’ mounting brackets per page 4.
5. Attach the strike faceplate to the lip bracket with the self-
tapping screws provided. (It may be desirable to leave
these screws slightly loose to facilitate insertion into the
doorframe.
6. Connect the incoming wiring from the power supply (see
wiring instructions).
7. Install the door strike in the doorframe using the screws
provided.
E
K
B
A
F
M
G
C
G
D
R
X
C
L
C
L
M
S6504 Aluminum Frames, 1-3/16” Insert Depth
Modular AS65 with B604 faceplate
MEASUREMENT
FRACTIONAL
INCHES
DECIMAL
INCHES
METRIC
mm
A 1-1/4 1.250 31.75
B 4-7/8 4.875 123.83
C 3-3/8 3.375 85.73
D 1-3/16 1.188 30.16
E 3/8 .375 9.53
F 1/8* .125* 3.18*
G 1-11/16 1.688 42.86
Vertical Vertical Vertical
X C/L C/L C/L
Door Door Door
R 5/32 0.156 3.97
K 4-1/8 4.125 104.78
M 12-24
Vertical Centerline
of Door**
INSTALLATION
Electric Strikes
6 Series
Instructions
E
K
B
A
F
M
G
C
G
D
R
X
C
L
C
L
M
L6504 Aluminum Frames, 1-1/16” Insert Depth
Modular AL65 with B604 faceplate
MEASUREMENT
FRACTIONAL
INCHES
DECIMAL
INCHES
METRIC
mm
A 1-1/4 1.250 31.75
B 4-7/8 4.875 123.83
C 3-3/8 3.375 85.73
D 1-3/32 1.094 27.78
E 3/8 .375 9.53
F 1/8* .125* 3.18*
G 1-11/16 1.688 42.86
Vertical Vertical Vertical
X C/L C/L C/L
Door Door Door
R 5/32 0.156 3.97
K 4-1/8 4.125 104.78
M 12-24
Vertical Centerline
of Door**
NOTE: Specifications subject to change without notice.
* Dimension F is measured from face of mounting tab to face of frame.
** Dimension X on the drawing is determined by the vertical centerline of the door. If the latch incorporates a deadlocking pin additional steps will be neces-
sary to ensure proper operation of the deadlocking pin. Measure the thickness of the deadlocking pin and add this thickness to Dimension X to relocate the
vertical centerline an appropriate distance on the frame.
© 2014 RutheRfoRd ContRols Int’l | A doRMA GRoup CoMpAny
www.rutherfordcontrols.com • Phone: 1.800.265.6630 • fax: 1.800.482.9795 • e-mail: sales@rutherfordcontrols.com
is6a pCn14014
r06/14tG
The L65 Low Profile version accepts 1/2” or 5/8” latch projection (perfect for narrow stile aluminum frames). The S65 Standard
version is ideal when you require 3/4” latch projection.
FC
G
G
A
M
BK
E
X
R
D
C
L
M
C
L
S6507 Aluminum & Wood Frames, 1-3/16” Insert Depth
Modular AS65 with B607 faceplate
A 1-1/4 1.250 31.75
B 6-7/8 6.875 174.63
C 3-3/8 3.375 85.73
D 1-3/16 1.188 30.16
E 3/8 0.375 9.53
F 1/8* .125* 3.18*
G 1-11/16 1.688 42.86
Vertical Vertical Vertical
X C/L C/L C/L
Door Door Door
R 5/32 .156 3.97
K 6-1/8 6.125 155.58
M 12-24
MEASUREMENT
FRACTIONAL
INCHES
DECIMAL
INCHES
METRIC
mm
Vertical Centerline
of Door**
6 Series Installation Instructions (Continued)
X
E
K
B
R
M
D
G
G
C
A
M
MEASUREMENT
FRACTIONAL
INCHES
DECIMAL
INCHES
METRIC
mm
A 1-1/8 1.125 28.58
B 5-7/8 5.875 149.23
C 3-3/8 3.375 85.73
D 1-3/16 1.188 30.16
E 1/4 0.250 6.35
F 1/8* .125* 3.18*
G 1-11/16 1.688 42.86
Vertical Vertical Vertical
X Door Door Door
R 5/32 .156 3.97
K 5-3/8 5.375 136.53
M 12-24
Vertical Centerline
of Door**
L6505 Aluminum & Wood Frames, 1-1/16” Insert Depth
Modular AL65 with B605 faceplate
X
E
K
B
R
M
D
G
G
C
A
M
MEASUREMENT
FRACTIONAL
INCHES
DECIMAL
INCHES
METRIC
mm
A 1-1/8 1.125 28.58
B 5-7/8 5.875 149.23
C 3-3/8 3.375 85.73
D 1-3/32 1.094 27.78
E 1/4 0.250 6.35
F 1/8* .125* 3.18*
G 1-11/16 1.688 42.86
Vertical Vertical Vertical
X C/L C/L C/L
Door Door Door
R 5/32 .156 3.97
K 5-3/8 5.375 136.53
M 12-24
Vertical Centerline
of Door**
FC
G
G
A
M
BK
E
X
R
D
C
L
M
C
L
L6507 Aluminum & Wood Frames, 1-1/16” Insert Depth
Modular AL65 with B607 faceplate
A 1-1/4 1.250 31.75
B 6-7/8 6.875 174.63
C 3-3/8 3.375 85.73
D 1-3/32 1.094 27.78
E 3/8 0.375 9.53
F 1/8* .125* 3.18*
G 1-11/16 1.688 42.86
Vertical Vertical Vertical
X C/L C/L C/L
Door Door Door
R 5/32 .156 3.97
K 6-1/8 6.125 155.58
M 12-24
MEASUREMENT
FRACTIONAL
INCHES
DECIMAL
INCHES
METRIC
mm
Vertical Centerline
of Door**
NOTE: Specifications subject to change without notice.
* Dimension F is measured from face of mounting tab to face of frame.
** Dimension X on the drawing is determined by the vertical centerline of the door. If the latch incorporates a deadlocking pin additional steps will be
necessary to ensure proper operation of the deadlocking pin. Measure the thickness of the deadlocking pin and add this thickness to Dimension X to
relocate the vertical centerline an appropriate distance on the frame.
For wood frame door installations, substitute #12 wood screws for dimension M.
© 2014 RutheRfoRd ContRols Int’l | A doRMA GRoup CoMpAny
www.rutherfordcontrols.com • Phone: 1.800.265.6630 • fax: 1.800.482.9795 • e-mail: sales@rutherfordcontrols.com
2
S6505 Aluminum & Wood Frames, 1-3/16” Insert Depth
Modular AS65 with B605 faceplate
6 Series Installation Instructions (Continued)
C
G
G
F
M
A
D
E
K
B
XM
C
L
C
L
S6514 Hollow Metal Frames, 1-3/16” Insert Depth
Modular AS65 with B614 faceplate
MEASUREMENT
FRACTIONAL
INCHES
DECIMAL
INCHES
METRIC
mm
A 1-1/4 1.250 31.75
B 4-7/8 4.875 123.83
C 3-3/8 3.375 85.73
D 1-3/16 1.188 30.16
E 3/8 .375 9.53
F 1/8* .125* 3.18*
G 1-11/16 1.688 42.86
Vertical Vertical Vertical
X C/L C/L C/L
Door Door Door
K 4-1/8 4.125 104.78
M 12-24
Vertical Centerline
of Door**
C
G
G
F
M
A
D
E
K
B
XM
C
L
C
L
L6514 Hollow Metal Frames, 1-1/16” Insert Depth
Modular AL65 with B614 faceplate
MEASUREMENT
FRACTIONAL
INCHES
DECIMAL
INCHES
METRIC
mm
A 1-1/4 1.250 31.75
B 4-7/8 4.875 123.83
C 3-3/8 3.375 85.73
D 1-3/32 1.094 27.78
E 3/8 .375 9.53
F 1/8* .125* 3.18*
G 1-11/16 1.688 42.86
Vertical Vertical Vertical
X C/L C/L C/L
Door Door Door
K 4-1/8 4.125 104.78
M 12-24
Vertical Centerline
of Door**
X
E
K
B
R
M
D
G
G
C
A
M
S6508 Aluminum & Wood Frames, 1-3/16” Insert Depth
Modular AS65 with B608 faceplate
MEASUREMENT
FRACTIONAL
INCHES
DECIMAL
INCHES
METRIC
mm
A 1-7/16 1.438 36.51
B 7-15/16 7.938 201.61
C 3-3/8 3.375 85.73
D 1-3/16 1.188 30.16
E 1/4 0.250 6.35
F 1/8* .125* 3.18*
G 1-11/16 1.688 42.86
Vertical Vertical Vertical
X C/L C/L C/L
Door Door Door
R 5/32 .156 3.97
K 7-7/16 7.438 188.91
M 12-24
Vertical Centerline
of Door**
X
E
K
B
R
M
D
G
G
C
A
M
L6508 Aluminum & Wood Frames, 1-1/16” Insert Depth
Modular AL65 with B608 faceplate
MEASUREMENT
FRACTIONAL
INCHES
DECIMAL
INCHES
METRIC
mm
A 1-7/16 1.438 36.51
B 7-15/16 7.938 201.61
C 3-3/8 3.375 85.73
D 1-3/32 1.094 27.78
E 1/4 0.250 6.35
F 1/8* .125* 3.18*
G 1-11/16 1.688 42.86
Vertical Vertical Vertical
X C/L C/L C/L
Door Door Door
R 5/32 .156 3.97
K 7-7/16 7.438 188.91
M 12-24
Vertical Centerline
of Door**
NOTE: Specifications subject to change without notice.
* Dimension F is measured from face of mounting tab to face of frame.
** Dimension X on the drawing is determined by the vertical centerline of the door. If the latch incorporates a deadlocking pin additional steps will be neces-
sary to ensure proper operation of the deadlocking pin. Measure the thickness of the deadlocking pin and add this thickness to Dimension X to relocate the
vertical centerline an appropriate distance on the frame.
For wood frame door installations, substitute #12 wood screws for dimension M.
© 2014 RutheRfoRd ContRols Int’l | A doRMA GRoup CoMpAny
www.rutherfordcontrols.com • Phone: 1.800.265.6630 • fax: 1.800.482.9795 • e-mail: sales@rutherfordcontrols.com
3
6 Series Installation Instructions (Continued)
© 2014 RutheRfoRd ContRols Int’l | A doRMA GRoup CoMpAny
www.rutherfordcontrols.com • Phone: 1.800.265.6630 • fax: 1.800.482.9795 • e-mail: sales@rutherfordcontrols.com
4
Frame
Self-Adhesive
Mounting Shim (8
incl.)
Mounting Tab
(2 incl.)
12-24 Machine
Screws (2 per tab)
Mounting Tab Kit Instructions
Mounting tab kit is for use with aluminum and steel frames that
do not have factory installed mounting tabs for electric strike
installation.
1. Prepare the frame as shown in the approximate drawing.
Fasten the mounting tab to the faceplate of the strike,
selecting the appropriate shims for the installation.
2. Using the assembled strike and tabs as a template, place
against the frame and mark the mounting hole locations.
Remove and drill a 3/16” hole in frame for each mounting tab
and countersink the frame.
3. Remove the tabs from the faceplate and install in the frame
using the 12-24 x 3/8” machine screws supplied. Tabs are
zinc plated and drilled and tapped for this purpose.
4. Make final electrical connections per wiring instructions
and mount strike to the tabs with the 12-24 x 3/8” machine
screws.
Trim Plate Instructions
1. Position the Trim Plate on the frame cut-out to verify fit and
coverage.
2. Adjust cut-out if required.
3. Bend the four tabs to hold the Trim Plate onto the frame.
4. For a tighter fit, pre-bend the two long flange tabs before
sliding onto the frame where space allows.
5. Secure the strike to the frame as per strike installation
instructions.
C
Red Black
Optional LMKM
Latch
Monitor
Keeper
Monitor
NC
NO
NO
C
NC
24VDC
Terminal
+–
12VDC
12-24VAC
Terminal
+–
Red
Black
Fail Unlocked
Rotate the adjustment screw so the dimple is fully rotated
to opposite the faceplate side of the strike (fully counter
clockwise). Your strike is now fail unlocked and requires power
to lock. See Fig. 1.
Fail Locked
Rotate the adjustment screw so the dimple is fully rotated to the
faceplate side of the strike (fully clockwise). Your strike is now
fail locked and requires power to unlock the door. See Fig 2.
Lip Bracket Adjustment
If your door or latch is out of adjustment, the insert can be
adjusted forward or back as required for proper alignment to
the latch. See Fig. 3
1. Remove the strike from the frame.
2. Remove the faceplate from the strike.
3. 2 screws secure the lip bracket to the main insert.
4. Loosen these screws approximately 1-1/2 to 2 full turns to
allow the insert to move forward or backward as required.
5. Once the adjustment is made tighten all screws and
reinstall the strike in the frame.
6 Series Installation Instructions (Continued)
Li
p
Bracket Scre
w
Faceplate
Removed Ad
j
ustment
Dir
ec
tio
n
Li
p
Bracket
S
trike Inser
t
Keeper
Fig. 1 Fail Unlocked = screw fully counter clockwise
Fig. 2 Fail Locked = screw fully clockwise
Fig. 3 Lip bracket adjustment
Wiring Instructions
NOTE: Overheated or Burnt Coils caused by incorrect input
voltage / wire harness combinations will not be covered under
warranty.
Use 12VDC wire harness for 12VDC or 12-24VAC input power.
Use 24VDC wire harness for 24VDC input power only.
Attach the red wire to (+) positive of the power supply. Attach the
black wire to the (–) negative of the power supply (see Fig. 4).
If using AC power, polarity is not observed.
NOTE: If a suppression diode is required for access control,
observe proper polarity.
Latch Monitor Wires
Black = Common (C)
Blue = Normally Close (NC)
Orange = Normally Open (NO)
Keeper Monitor Wires
Black = Common (C)
Yellow = Normally Closed (NC)
Green = Normally Open (NO)
When using LMKM option:
If the lockset on the door has a 1/2” or 5/8” latch projection,
The L65 model is appropriate.
If the lockset on the door has a 3/4” latch projection,
you must use the S65 model.
NOTE: Contacts are indicated with the keeper in a closed and
locked condition, with no latch present.
Fig. 4 Wiring the 6 Series electric strike
© 2014 RutheRfoRd ContRols Int’l | A doRMA GRoup CoMpAny
www.rutherfordcontrols.com • Phone: 1.800.265.6630 • fax: 1.800.482.9795 • e-mail: sales@rutherfordcontrols.com
5
6 Series Troubleshooting
Latch or keeper are not
functioning properly
Confirm that the keeper is closing properly and that the lever in
the strike cavity is operating freely.
SolutionPossible CausesProblem
Strike will not lock or
unlock properly
No power to the insert Using a multimeter, confirm that you have the correct output
voltage at the power supply.
Using a multimeter, confirm that you have the correct input
voltage at the strike.
Confirm that all connections are tight and secure.
Incorrect voltage used Confirm that the insert and power supply are the proper voltage.
Strike is binding Confirm that the strike keeper functions when the door is open. If
the strike operates correctly, adjust door or strike to eliminate any
backpressure.
Confirm that the strike cavity depth is compatible with the lock
set.
Strike releases but
won’t buzz
Improper power supply Replace the power supply with a correct voltage AC power supply,
and the 12V connector. If this cannot be done, a DC piezo buzzer
can be installed.
Strike makes a buzzing
sound
Improper power supply Replace the power supply with a correct voltage DC power supply.
Insert has a burnt smell Improper voltage Confirm that you have the correct output voltage at the power supply.
Improper application A strike connected to an AC power supply will buzz unless a
rectifier is installed.
Improper installation Confirm that the correct connector was used when installing the
strike 12V for 12VDC & 12-24VAC, 24V for 24VDC only.
Confirm that all connections are tight and secure.
Mortise lock not dead
latching
Improper Installation Check alignment of dead latch and lip bracket ramp.
Door has sagged Adjust door alignment.
Cylindrical deadlatching not
working
Improper Installation /
Door has warped
Adjust the strike horizontal adjustment. (See Installation
Instructions).
Door won’t latch Door has warped or sagged
creating excessive back
pressure
Re-align door in frame or replace.
Monitor switch is not
functioning
Short in wiring Confirm that all connections are tight and secure.
Using a multimeter confirm continuity of the N/O & N/C sides of
the switch.
1.
2.
3.
4.
5.
6.
7.
8.
© 2014 RutheRfoRd ContRols Int’l | A doRMA GRoup CoMpAny
www.rutherfordcontrols.com • Phone: 1.800.265.6630 • fax: 1.800.482.9795 • e-mail: sales@rutherfordcontrols.com
6