RCI Wire Gauge Reference Chart Zl10wgc R0313

User Manual: RCI Wire Gauge Reference Chart Product Sheet

Open the PDF directly: View PDF PDF.
Page Count: 1

DownloadRCI  Wire Gauge Reference Chart Zl10wgc R0313
Open PDF In BrowserView PDF
Power Supplies

Wire Gauge Chart
10 Series

®

Determining
Wire Gauge
Example:
Power supply voltage equals
12 volts. Load equals 3 electromagnetic locks. Each lock
requires 0.280 amps of current.
Total current draw equals
(3 x 0.280 = 0.840 amps). Round
off current to 1 Amp. (Always
round off in an upward direction.)
Distance from farthest electromagnetic lock equals 100 feet. Use the
12V chart and locate the 1.00 Amp
column along the top of the chart.
Select the distance in left column
closest to the distance of the
farthest lock. The wire gauge
required can be found by cross
referencing the rows vertically and
horizontally.
(#14 AWG).

Total One Way
Length of
Wire Run (ft.)

LOAD CURRENT @ 24V

100

1/4A
24

1/2A
20

3/4A
18

1A
18

150
200
250
300
400
500
750

22
20
18
18
18
16
14

18
18
16
16
14
14
12

16
16
14
14
12
12
10

16
14
14
12
12
10
10

1-1/4A 1-1/2A
16
16
14
14
12
12
10
10
-

14
12
12
12
10
-

2A
14

3A
12

12
12
12
10
-

10
10
10
-

1000

14

10

10

-

-

-

-

-

1500

12

10

-

-

-

-

-

-

2A
12

3A
10

10
-

-

Total One Way
Length of
Wire Run (ft.)

LOAD CURRENT @ 12V

100

1/4A
20

1/2A
18

3/4A
16

1A
14

150
200
250
300
400
500
750

18
16
16
16
14
14
12

16
14
14
12
12
10
10

14
12
12
12
10
10
-

12
12
10
10
-

1-1/4A 1-1/2A
14
12
12
10
10
10
-

12
10
10
-

1000

10

-

-

-

-

-

-

-

1500

10

-

-

-

-

-

-

-

Wire Gauge Chart courtesy of Electronic locking Devices by John L. Schum

Types of Wire:

Hookup wire is available in both solid and stranded wire
types. Stranded wire is the accepted standard for system
hookup as it is more flexible and less likely to break.
It’s made of several small-diameter wires twisted
together to form one larger-diameter conductor. To prevent
the strands from separating, stranded wire is usually tinned
(solder applied to ends of wire). This makes connections
easier and prevents the wire from fraying.

ZL10WGC

Wire Gauge:

Wire is given a gauge number to classify it by its size or
thickness. American wire gauge (AWG) is the most
common measurement for electrical wire size – the lower
the wire gauge number, the larger the wire diameter and
the greater the current carrying capability.

Wire Insulation:

The wire insulation should be UL or CSA approved for the
maximum voltage to which the wire will be subjected. Normally, the wire rating is three to six times greater than the
maximum voltage to be applied to the wire.

©2013 Rutherford controls • www.rutherfordcontrols.com
USA: 2517 SQUADRON COURT, SUITE 104, VIRGINIA BEACH, VA 23453 • Canada: 210 shearson crescent, cambridge, on n1t 1j6
PHONE • 1.800.265.6630 • 519.621.7651 • FAX: 1.800.482.9795 • 519.621.7939 • e-mail: sales@rutherfordcontrols.com

R03/13CA



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.3-c011 66.145661, 2012/02/06-14:56:27
Create Date                     : 2013:03:21 16:59:25-04:00
Metadata Date                   : 2013:03:21 16:59:37-04:00
Modify Date                     : 2013:03:21 16:59:37-04:00
Creator Tool                    : Adobe InDesign CS6 (Macintosh)
Instance ID                     : uuid:2a7c9414-55dc-bb43-8823-452018d1fa83
Original Document ID            : xmp.did:0180117407206811BB1DEEA46A428FED
Document ID                     : xmp.id:0580117407206811822AA860673B9357
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:0480117407206811822AA860673B9357
Derived From Document ID        : xmp.did:CEC38C6E2720681192B09E437B524045
Derived From Original Document ID: xmp.did:0180117407206811BB1DEEA46A428FED
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CS6 (Macintosh)
History Changed                 : /
History When                    : 2013:03:21 16:59:25-04:00
Format                          : application/pdf
Producer                        : Adobe PDF Library 10.0.1
Trapped                         : False
Page Count                      : 1
Creator                         : Adobe InDesign CS6 (Macintosh)
EXIF Metadata provided by EXIF.tools

Navigation menu