INSTALLATION & OPERATING
INSTRUCTIONS

Models 504–2004

Types H, WH, P & WHP

L
W

WARNING: Improper installation, adjustment, alteration, service or maintenance can
cause property damage, personal injury, exposure to hazardous materials* or loss of
life. Review the information in this manual carefully. *This unit contains materials that
have been identified as carcinogenic, or possibly carcinogenic, to humans.

FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and
liquids or other combustible materials in the vicinity of this or any other appliance. To
do so may result in an explosion or fire.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas
supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.

Installation and service must be performed by a qualified installer, service agency or
the gas supplier.

This manual should be maintained in legible condition and kept adjacent to the heater or in a safe place for future
reference.

CATALOG NO. 3400.54E

Effective: 03-25-10

Replaces: 03-19-09

P/N 241317 Rev. 6

Rev. 5 reflects the following:
Changes to: Air Filter instructions on page 11, minor text changes on pages 13 and 14, Figs. 10 and 11 on page 15,. Fig 12
and Table G on page 16, Fig 13 on page 17, minor text changes on page 20, Fig. 21 on page 22, Figs. 22-28 on pages 2530, Table N on page 29, Fig. 35 on page 32, Mode 8 description on page 33, minor text changes on pages 42, 43 and 46,
Troubleshooting chart on page 48.
Additions: Fig. 2 on page 6, Low-lead requirement on page 5, Fig. 8 on page 11, note on page 12, Caution on page 20, Fig.
22 on page 22, Fig. 36 on page 33, air filter instructions on pages 50 and 51.

2

CONTENTS
WARNINGS
BEFORE INSTALLATION
Product Receipt
Model Identification
Ratings and Certifications
Installations at Elevation
Component Locations
General Information
GENERAL SAFETY
Time/Temperature Relationships in
Scalds
INSTALLATION
Installation Codes
Equipment Base
Clearances
Combustion and Ventilation Air
Conventional Combustion Air Supply
Water Piping
Hydronic Heating
Gas Supply
Electrical Power Connections
Field Wiring Connection
Venting
Venting Installation Tips
Venting Configurations
Engineered Vent Systems

Outdoor Installation
Controls
Heater Sequence of Operation
WIRING DIAGRAMS
START-UP
Pre Start-up
Start-Up
OPERATION
Lighting Instructions
To Turn Off Gas To Appliance
UDB Fault History
TROUBLESHOOTING
MAINTENANCE
Suggested Minimum
Maintenance Schedule
Preventative Maintenance Schedule
Filter Maintenance
Filter Replacement
APPENDIX
Inside Air Contamination
IMPORTANT INSTRUCTIONS FOR
THE COMMONWEALTH OF
MASSACHUSETTS
WARRANTY
START-UP CHECKLIST

4
5
5
5
5
5
6
6
7

7
8
8
8
8
9
11
12
14
19
20
22
22
24
24
27

3

29
30
37
40
42
42
43
46
46
47
47
48
49

49
49
50
51
51
51
52
53
55

WARNINGS
Pay Attention to These Terms
DANGER:
WARNING:
CAUTION:
NOTE:

Indicates the presence of immediate hazards which will cause severe
personal injury, death or substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause
severe personal injury, death or substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause
minor personal injury or product or property damage if ignored.
Indicates special instructions on installation, operation, or maintenance which
are important but not related to personal injury hazards.

DANGER: Make sure the gas on which the heater
will operate is the same type as that specified on the
heater rating plate.

CAUTION: Operation of this heater in low
temperature systems requires special piping.
Harmful internal condensation will occur if the inlet
water temperature does not exceed 120°F. Warranty
claims will be denied when condensation occurs.

WARNING: Should overheating occur or the gas
supply valve fail to shut, do not turn off or disconnect
the electrical supply to the heater. Instead, shut off
the gas supply at a location external to the heater.

CAUTION: If this heater is to be installed above
radiation level, it must be provided with a low water
cut-off device at the time of heater installation.

WARNING: Do not use this heater if any part has
been under water. Immediately call a qualified
service technician to inspect the heater and to
replace any part of the control system and any gas
control which has been under water.

CAUTION: This heater requires forced water
circulation when the burner is operating. See
minimum and maximum flow rates. Severe damage
will occur if the heater is operated without proper
water flow circulation.

WARNING: To minimize the possibility of improper
operation, serious personal injury, fire, or damage to
the heater:
•

•

CAUTION: If this heater is to be installed in a
negative or positive pressure equipment room, there
are special installation requirements. Consult factory
for details.

Always keep the area around the heater free of
combustible materials, gasoline, and other
flammable liquids and vapors.

NOTE: Minimum 18 AWG, 105°C, stranded wire
must be used for all low voltage (less than 30 volts)
external connections to the unit. Solid conductors
should not be used because they can cause
excessive tension on contact points. Install conduit
as appropriate. All high voltage wires must be the
same size (105°C, stranded wire) as the ones on the
unit or larger.

Heater should never be covered or have any
blockage to the flow of fresh air to the heater.

WARNING: Risk of electrical shock. More than one
disconnect switch may be required to de-energize
the equipment before servicing.
WARNING - CALIFORNIA PROPOSITION
65: This product contains chemicals known to the
State of California to cause cancer, birth defects or
other reproductive harm.

4

BEFORE INSTALLATION

the upper rear jacket panel of the heater. The model
number will have the form H7-2004 or similar depending on the heater size and configuration. The letter(s)
in the first group of characters identifies the application
(H = Hydronic Heating, P = Pool Heating, WH =
Domestic Hot Water (DHW), WHP = Water Heater for
Pool Heating). The number which follows identifies the
firing mode (7 = electronic modulation, 1 = On/Off).
The second group of characters identifies the size of
the heater (three or four numbers representing the
approximate MBTUH input), and, where applicable, a
letter, indicating the manufacturing series.

Raypak strongly recommends that this manual be reviewed thoroughly before installing your MVB heater.
Please review the General Safety information before
installing the heater. Factory warranty does not apply
to heaters that have been improperly installed or operated. (Refer to the warranty at the back of this
manual.) Installation and service must be performed
by a qualified installer, service agency or gas supplier.
If, after reviewing this manual, you still have questions
which this manual does not answer, please contact
your local Raypak representative or visit our website at
www.raypak.com.

Ratings and Certifications
Standards:

Thank you for purchasing a Raypak product. We hope
you will be satisfied with the high quality and durability
of our equipment.

•

•

Product Receipt

•

On receipt of your heater it is suggested that you visually check for external damage to the shipping crate. If
the crate is damaged, make a note to that effect on the
Bill of Lading when signing for the shipment. Next,
remove the heater from the shipping packaging.
Report any damage to the carrier immediately.

•

•
•

ANSI Z21.56 · CSA 4.7 - latest edition, Gas-Fired
Pool Heaters
ANSI Z21.13 · CSA 4.9 - latest edition, Gas-Fired
Hot Water Boilers
CAN 3.1 - latest edition, Industrial and
Commercial Gas-Fired Package Boilers
ANSI Z21.10.3 · CSA 4.3 - latest edition, Gas Water Heaters
SCAQMD Rule 1146.2
Low-lead content (<.25%) CSA-verified

All Raypak heaters are National Board Approved, and
design-certified and tested by the Canadian Standards
Association (CSA) for the U.S. and Canada. Each
heater is constructed in accordance with Section IV of
the American Society of Mechanical Engineers
(ASME) Heater Pressure Vessel Code and bears the
ASME stamp. This heater also complies with the latest
edition of the ASHRAE 90.1 Standard.

On occasion, items are shipped loose. Be sure that
you receive the correct number of packages as indicated on the Bill of Lading.

Claims for shortages and damages must be filed with
the carrier by consignee. Permission to return goods
must be received from the factory prior to shipping.
Goods returned to the factory without an authorized
Returned Goods Receipt number will not be accepted.
All returned goods are subject to a restocking charge.

WARNING: Altering any Raypak pressure vessel
by installing replacement heat exchangers, tube
bundle headers, or any ASME parts not
manufactured and/or approved by Raypak will
instantly void the ASME and CSA ratings of the
vessel and any Raypak warranty on the vessel.
Altering the ASME or CSA ratings of the vessel also
violates national, state, and local approval codes.

When ordering parts, you must specify the model and
serial number of the heater. When ordering under warranty conditions, you must also specify the date of
installation.

Purchased parts are subject to replacement only
under the manufacturer’s warranty. Debits for defective replacement parts will not be accepted. Parts will
be replaced in kind only per Raypak’s standard warranties.

Installations at Elevation

Rated inputs are suitable for up to 4,500 ft elevation
without de-rating. Consult your local representative or
the factory for installations at altitudes over 4,500 ft
above sea level. No hardware changes are required to
the heaters for installations up to 10,000 ft (adjustments may be required).

Model Identification

The model identification number and heater serial
number are found on the heater rating plate located on
5

Component Locations

HIGH VOLTAGE
ELECTRICAL CONNECTIONS

Fig. 3: Component Locations – Rear

Panels omitted for clarity
Fig. 1: Component Locations – Side

Top panel, blower and gas train omitted for clarity
Fig. 4: Component Locations – Top

General Information
Model
No.
504
754

1104

1504
2004

Panels omitted for clarity
Fig. 2: Component Locations – Front

MBTUH
Input*

Max.*

Min.*

750

525

500

1100

1500
1999

*H7 units only.

6

Water
Conn.
(NPT)

Gas
Conn.
(NPT)
N

P

Flue

Intake

1

1

10

6

1

12

350

2

770

2-1/2

1-1/4

1400

2-1/2

2

1050

2

2-1/2

Vent
Size
(in.)

1

1-1/4

Table A: Basic Data

1
1
1

8

10
14

6
6
8
8

GENERAL SAFETY

To meet commercial hot water use needs, the high
limit safety control on this water heater will shut off the
main gas valve before the outlet temperature reaches
210°F. However, water temperatures over 125°F can
cause instant severe burns or death from scalds.
When supplying general purpose hot water, the recommended initial setting for the temperature control is
125°F.

This section applies to Hot Water Supply Boilers and
Hot Water Heaters ONLY. For sanitary rinse applications where outlet temperatures of 180°F to 195°F are
required, a boiler is recommended since the 210°F
limit on water heaters will NOT allow the heater to
maintain these desired sanitary rinse temperatures.

Water temperature over 125°F can
cause instant severe burns or death
from scalds.

Safety and energy conservation are factors to be considered when setting the water temperature on the
thermostat. The most energy-efficient operation will
result when the temperature setting is the lowest that
satisfies the needs of the application.

Children, disabled, and elderly are
at highest risk of being scalded.
See instruction manual before setting temperature at water heater.
Feel water before bathing or showering.

Water temperature over 125°F can cause instant
severe burns or death from scalds. Children, disabled
and elderly are at highest risk of being scalded.
•
•

Temperature limiting valves are
available, see manual.

Feel water before bathing or showering.
Temperature limiting valves are available.

Time/Temperature
Relationships in Scalds

NOTE: When this water heater is supplying general
purpose hot water for use by individuals, a
thermostatically controlled mixing valve for reducing
point of use water temperature is recommended to
reduce the risk of scald injury. Contact a licensed
plumber or the local plumbing authority for further
information.

The following chart details the relationship of water
temperature and time with regard to scald injury and
may be used as a guide in determining the safest
water temperature for your applications.

Maximum water temperatures occur just after the
heater’s burner has shut off. To determine the water
temperature being delivered, turn on a hot water
faucet and place a thermometer in the hot water
stream and read the thermometer.

Water
Temp.

Time to Produce Serious
Burn

120°F

More than 5 minutes

125°F

1-1/2 to 2 minutes

130°F

About 30 seconds

135°F

About 10 seconds

140°F

Less than 5 seconds

145°F

Less than 3 seconds

150°F

About 1-1/2 seconds

155°F

About 1 second

Table courtesy of The Shriners Burn Institute

7

Table B: Time to Produce Serious Burn

Equipment Base

The temperature of the water in the heater can be regulated by using the Raypak Modulating Temperature
Control. To comply with safety regulations, the control
is set at 120°F when shipped from the factory (Mode 3
default setting for Tank Target).

The heater should be mounted on a level, structurally
sound surface. The heater is approved for installation
on a combustible surface but must NEVER be
installed on carpeting. Gas-fueled equipment installed
in enclosed parking garages must be located at least
18 in. above the floor.

To adjust the water temperature, follow the instruction
for the operation of the control starting on page 30 of
this manual. The control is shown below for identification purposes only. (See Fig. 5.)

CAUTION: This heater should be located in an
area where water leakage will not result in damage
to the area adjacent to the appliances or to the
structure. When such locations cannot be avoided, it
is recommended that a suitable catch pan,
adequately drained, be installed under the
appliance. The pan must not restrict air flow.
In addition, the heater shall be installed such that the
gas ignition system components are protected from
water (dripping, spraying, rain, etc.) during appliance
operation or service (circulator replacement, control
replacement, etc.).
If the heater needs to be secured to the ground, use
the brackets that were used to bolt the heater to the
shipping pallet.

Fig. 5: Modulating Temperature Control

Clearances

CAUTION: Hotter water increases the risk of
scalding! There is a hot water scald potential if the
thermostat is set too high.

Indoor Installations

INSTALLATION
Installation Codes

Installations must follow these codes:

•

•

•

•

•

Local, state, provincial, and national codes, laws,
regulations and ordinances
National Fuel Gas Code, ANSI Z223.1/NFPA 54 –
latest edition (NFGC)
National Electrical Code, ANSI/NFPA 70 - latest
edition (NEC)
Standard for Controls and Safety Devices for
Automatically Fired Boilers, ANSI/ASME CSD-1,
(CSD-1) when required
For Canada only: CAN/CSA B149 Natural Gas
and Propane Installation Code and CSA C22.1
C.E.C. Part 1 (C22.1)

Heater
Side

Minimum Clearance
from Combustible
Surfaces

Minimum
Service
Clearance

Floor*

0”

0”

Rear

12”

24”

Right Side

1”

1”

Left Side

1”

1”

Top

0”

10”

Front

Open

24”

Vent

1”

1”

*DO NOT install on carpeting.

Table C: Clearances – Indoor Installations

8

When installed according to the listed minimum clearances from combustible construction, these heaters
can still be serviced without removing permanent
structural construction around the heater. However, for
ease of servicing, a clearance of at least 24 in. in front,
at least 24 in. on the rear and 10 in. above the top of
the heater is required. This will allow the heater to be

codes and the requirments of the gas supplier. Three
sides must be open in the area under the overhang.
Roof water drainage must be diverted away from
heaters installed under overhangs.

The combustion air intake terminal MUST be used for
outdoor installations. The elbow is shipped loose to be
installed on the rear of the heater at the job site.
Heater
Side

Min. Clearance
from Combustible
Surfaces

Minimum
Service
Clearance

Front

Open

24”

Left Side

1”

Rear

12”

Right Side
Top

Vent
Termination

1”

Unobstructed
12”

24”
1”
1”

10”
12”

Table D: Clearances – Outdoor Installations

Combustion and Ventilation Air
NOTE: Use of this heater in construction areas
where fine particulate matter, such as concrete or
dry-wall dust, is present may result in damage to the
heater that is not covered by the warranty. If
operated in a construction environment, a clean
source of combustion air must be provided directly to
the heater.

Indoor Units

Venting not shown for clarity. Heater must be vented per instructions in this manual

This heater must be supplied with sufficient quantities
of non-contaminated air to support proper combustion
and equipment ventilation. Combustion air can be supplied via conventional means where combustion air is
drawn from the area immediately surrounding the
heater, or via direct vent, where combustion air is
drawn directly from outside. All installations must comply with the requirements of the NFGC (U.S.) and
B149 (Canada), and all local codes.

Fig. 6: Minimum Clearances from Combustible
Surfaces – Indoor and Outdoor Installations

serviced in its installed location without movement or
removal of the heater.

Service clearances less than the minimum may
require removal of the heater to service either the heat
exchanger or the burner components. In either case,
the heater must be installed in a manner that will
enable the heater to be serviced without removing any
structure around the heater.

CAUTION: Combustion air must not be
contaminated by corrosive chemical fumes which
can damage the heater and void the warranty. (See
the Appendix.)

Outdoor Installations

These heaters are design-certified for outdoor installation. Heaters must not be installed under an overhang
unless they are in accordance with local installation

NOTE: It is recommended that the intake vent be
insulated to minimize sweating.
9

Fig. 7: Minimum Clearances from Vent/Air Inlet Terminations – Indoor and Outdoor Installations
1

1
2

t
TT
*

2

U.S. Installations

Canadian Installations

A

Clearance above grade, veranda, porch,
deck, or balcony

1 ft (30 cm)

1 ft (30 cm)

B

Clearance to window or door that may be
opened

4 ft (1.2m) below or to side
of opening; 1 foot (30 cm)
above opening

3 ft (91 cm)

C

Clearance to permanently closed window

*

*

D

Vertical clearance to ventilated soffit located
above the terminal within a horizontal distance of 2 ft (61cm) from the centerline of the
terminal

5 ft (1.5m)

*

E

Clearance to unventilated soffit

*

*

F

Clearance to outside corner

*

*

G

Clearance to inside corner

6 ft (1.83m)

*

H

Clearance to each side of center line extended above meter/regulator assembly

*

3 ft (91 cm) within a height
15 ft above the meter/regulator assembly

I

Clearance to service regulator vent outlet

*

6 ft (1.83m)

J

Clearance to non-mechanical air supply inlet
to building or the combustion air inlet to any
other appliance

4 ft (1.2m) below or to side
of opening; 1 ft (30 cm)
above opening

3 ft (91 cm)

K

Clearance to mechanical air supply inlet

3 ft (91 cm) above if within
10 ft (3m) horizontally

6 ft (1.83m)

L

Clearance above paved sidewalk or paved
driveway located on public property

7 ft (2.13m)

7 ft (2.13m) t

M

Clearance under veranda, porch, deck or
balcony

*

12 in. (30 cm) TT

In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code
In accordance with the current CAN/CGA-B149 Installation Codes
Vent terminal shall not terminate directly above sidewalk or paved driveway located between 2 single family dwellings that serves
both dwellings
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor and top of terminal and
underside of veranda, porch, deck or balcony is greater than 1 ft (30cm)
Clearances in accordance with local installation codes and the requirements of the gas supplier

Table E: Vent/Air Inlet Termination Clearances

10

Air Filter

or sealed single-wall galvanized ducting. The duct will
attach directly to the air collar located on the rear of the
heater, using three or four sheet metal screws (not
supplied) equally positioned around the circumference
of the duct. The screen assembly should be removed
before attaching any air duct to the heater. The screws
and duct connection point must be sealed with RTV
(not supplied). TruSeal is generally used when damaging contaminants are present in the mechanical
room.

An air filter is supplied standard with the heater. This
filter is shipped loose for field installation. Refer to the
Air Filter Kit Installation Instructions (Part No. 241338)
for details.

All ducting must be self-supported.

CAUTION: Use TruSeal combustion air if
damaging airborne contaminants are or may be
present in the heater area. See the Appendix of this
manual regarding air contamination.

Conventional Combustion Air
Supply

Fig. 8: Air Filter Box

Direct Vent

U.S. Installations

If outside air is drawn through the intake pipe directly
to the unit for combustion:

All Air from Inside the Building

The confined space shall be provided with TWO permanent openings communicating directly with an
additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for a
room large in comparison (NFGC). The total input of all
gas utilization equipment installed in the combined
space shall be considered in making this determination. Each opening shall have a minimum free area of
1 in.2 per 1,000 BTUH (2,225 mm2 per kW) of the total
input rating of all gas utilization equipment in the confined space, but not less than 100 in.2 (645 cm2). One
opening shall commence within 12 in. (305 mm) of the
top, and one opening shall commence within 12 in.
(305 mm) of the bottom of the enclosure. The minimum dimension of air openings shall be not less than
3 in. (76 mm) in any direction.

1. Install combustion air direct vent in accordance
with Fig. 27 (horizontal) or Fig. 28 (vertical) of this
manual (pages 28 and 29, respectively).

2. Provide adequate ventilation of the space occupied by the heater(s) by an opening(s) for
ventilation air at the highest practical point communicating with the outdoors. The total
cross-sectional area shall be at least 1 in.2 of free
area per 20,000 BTUH (111 mm2 per kW) of total
input rating of all equipment in the room when the
opening is communicating directly with the outdoors or through vertical duct(s). The total
cross-sectional area shall be at least 1 in.2 of free
area per 10,000 BTUH (222 mm2 per kW) of total
input rating of all equipment in the room when the
opening is communicating with the outdoors
through horizontal duct(s).

All Air from Outdoors

The confined space shall communicate with the outdoors in accordance with one of the methods below.
The minimum dimension of air openings shall not be
less than 3 in. (76 mm) in any direction. Where ducts
are used, they shall be of the same cross-sectional
area as the net free area of the openings to which they
connect.

3. In cold climates, and to mitigate potential freezeup, Raypak highly recommends the installation of
a motorized sealed damper to prevent the circulation of cold air through the heater during the
non-operating hours.

TruSeal™ Combustion Air

In addition to the 3 previous steps, combustion air may
be ducted directly to the heater by using PVC, CPVC

11

1. Two permanent openings, one commencing
within 12 in. (305 mm) of the top, and one commencing within 12 in. (305 mm) of the bottom of

the enclosure, shall be provided. The openings
shall communicate directly, or by ducts, with the
outdoors or spaces (crawl or attic) that freely communicate with the outdoors.

2. For heaters using a barometric damper in the vent
system there shall be a permanent air supply
opening(s) having a cross section area of not less
than 1 in.2 per 7,000 BTUH (320 mm2 per kW) up
to and including 1 million BTUH, plus 1 in.2 per
14,000 BTUH (160 mm2 per kW) in excess of 1
million BTUH. This opening(s) shall be either
located at or ducted to a point not more than 18 in.
(450 mm) nor less than 6 in. (152 mm) above the
floor level. The duct can also “goose neck” through
the roof. The duct is preferred to be straight down
and terminated 18 in. (450 mm) from the floor, but
not near piping. This air supply opening requirement shall be in addition to the air opening for
ventilation air required in 1. (above).

a. Where directly communicating with the outdoors or where communicating to the
outdoors through vertical ducts, each opening shall have a minimum free area of 1 in.2
per 4,000 BTUH (550 mm2 per kW) of total
input rating of all equipment in the enclosure.

b. Where communicating with the outdoors
through horizontal ducts, each opening shall
have a minimum free area of 1 in.2 per 2,000
BTUH (1,100 mm2 per kW) of total input rating of all equipment in the enclosure.

WARNING: Care must be taken to ensure that the
equipment room is not under negative pressure
conditions.

2. One permanent opening, commencing within 12
in. (305 mm) of the top of the enclosure, shall be
permitted where the equipment has clearances of
at least 1 in. (25 mm) from the sides and back and
6 in. (152 mm) from the front of the appliance. The
opening shall directly communicate with the outdoors or shall communicate through a vertical or
horizontal duct to the outdoors or spaces that
freely communicate with the outdoors, and shall
have a minimum free area of:

3. For heaters not using a barometric damper in the
vent system, and when air supply is provided by
natural air flow from outdoors for a power burner
and there is no draft regulator, drafthood or similar
flue gas dilution device installed in the same
space, in addition to the opening for ventilation air
required in 1., there shall be a permanent air supply opening(s) having a total cross-sectional area
of not less than 1 in.2 for each 30,000 BTUH (74
mm2 per kW) of total rated input of the burner(s),
and the location of the opening(s) shall not interfere with the intended purpose of the opening(s)
for ventilation air referred to in 1. This opening(s)
can be ducted to a point not more than 18 in. (450
mm) nor less than 6 in. (152 mm) above the floor
level. The duct can also “goose neck” through the
roof. The duct is preferred to be straight down 18
in. (450 mm) from the floor, but not near piping.

a. 1 in.2 per 3,000 BTUH (740 mm2 per kW) of
the total input rating of all equipment located in
the enclosure, and

b. Not less than the sum of the areas of all vent
connectors in the confined space.

WARNING: Do not use the “one permanent
opening” method if the equipment room is under
negative pressure conditions.

4. Refer to the B149 Installation Code for additional
information.

Canadian Installations

CAUTION: All combustion air must be drawn from
outside of the building; the mechanical equipment
room must communicate directly with the outdoors.

Water Piping
General

1. Ventilation of the space occupied by the heater
shall be provided by an opening(s) for ventilation
air at the highest practical point communicating
with the outdoors. The total cross-sectional area of
such an opening(s) shall be at least 10% of the
area required in 2. and 3. (below), but in no case
shall the cross-sectional area be less than 10 in.2
(65 cm2).

The heater should be located so that any water leaks
will not cause damage to the adjacent area or structures.

12

NOTE: In lieu of installing the System Temp Sensor
in the system return loop, an alternate system using
a buffer tank (see Fig. 31) can be used for better system temperature control.

feed valve. Test at standard operating pressure for
at least 24 hours.

CAUTION: This heater requires forced water
circulation when the burner is operating. See Table F
and Table G for minimum and maximum flow rates
and water pump selection. The pump must be
interlocked with the heater to prevent heater
operation without water circulation.

2. Make sure constant gauge pressure has been
maintained throughout test.
3. Check for leaks. Repair if found.

NOTE: Minimum pipe size for in/out connections is
2 in. NPT for 504 and 754 models and 2-1⁄2 in NPT for
1104–2004 models. Verify proper flow rates and ∆T
as instructed in this manual.

Cold Water Operation

CAUTION: Damage due to internal condensation
may occur if the heater inlet water temperature does
not exceed 120°F (49°C) within 7 minutes of startup.

Relief Valve Piping

WARNING: Pressure relief valve discharge piping
must be piped near the floor and close to a drain to
eliminate the potential of severe burns. Do not pipe
to any area where freezing could occur. Refer to
local codes.

This heater is equipped with a proprietary condensate
evaporation system which will evaporate any condensate that may begin to accumulate inside the primary
heat exchanger with water temperatures as low as
120°F (49°C).

Heaters operated with an inlet temperature of less
than 120°F (49°C) MUST have a manual bypass (see
Fig. 16) or an approved low-temperature operation
system (Figs. 9 and 10) to prevent problems with condensation.
This
piping
is
similar
to
a
primary/secondary boiler installation, with a bypass
acting as the secondary boiler piping. Raypak strongly recommends that thermometer(s) be placed into the
heater piping next to the in/out header to facilitate temperature adjustment. Inlet water temperatures below
120°F (49°C) can excessively cool the products of
combustion, resulting in collection of condensate in the
heat exchanger area beyond the capacity of the condensate evaporation system.

Temperature & Pressure Gauge

The temperature and pressure gauge is shipped loose
for field installation and must be installed within 12
inches of the boiler outlet (if possible) in an easily
readable location. Installation must comply with ASME
Section IV as well as all applicable national, state and
local codes.

Hydrostatic Test

Unlike many types of heaters, this heater does not require hydrostatic testing prior to being placed in
operation. The heat exchanger has already been factory-tested and is rated for 160 psi operating pressure.
However, Raypak does recommend hydrostatic testing of the piping connections to the heater and the rest
of the system prior to operation. This is particularly
true for hydronic systems using expensive glycolbased anti-freeze. Raypak recommends conducting
the hydrostatic test before connecting gas piping or
electrical supply.

Failure to reach or exceed 120°F (49°C) within 7 minutes may damage or cause failure of the heat
exchanger, combustion chamber, or other parts within
the combustion chamber. It can cause operational
problems, bad combustion, sooting, flue gas leakage
and reduced service life of the appliance and the vent
system. A bypass allows part of the heater discharge
water to be mixed with the cooler water returning to the
heater inlet to increase the heater inlet temperature
above 120°F (49°C). This precautionary measure
should prevent the products of combustion from condensing beyond the ability of the condensate
management system employed in this heater in most
installations. Warranty claims will be denied for
damage or failures caused by condensation.

Leaks must be repaired at once to prevent damage to
the heater. NEVER use petroleum-based stop-leak
compounds.
To perform hydrostatic test:

1. Connect fill water supply. With bleed valve open,
fill heater with water. When water flows from bleed
valve, shut off water. Close bleed valve. Carefully
fill the rest of the system, making sure to eliminate
any entrapped air by using high-point vents. Close

13

Cold water operation issues are applicable to both
cold water start and cold water run applications. Cold
water operation for 7 minutes or less on initial daily
start-up is acceptable. Where cold water starts will last

longer than 7 minutes or where cold water operation is
continuous, provisions must be made to mix higher
temperature outlet water with the colder inlet water
and thereby raise the inlet temperature to at least
120°F (49°C) within the 7-minute time limit.

and manually adjusted to achieve an inlet temperature
of 120°F (49°C) or higher as adjusted at the minimum
temperature in this narrow temperature range (i.e.
Range 75°F to 85°F – adjust bypass with temperature
at 75°F (24°C)) so that when temperature is 85°F
(29°C), minimum inlet temperature would be 130°F
(54°C). An injector pump arrangement may also be utilized to keep the heater loop at or above 120°F (49°C).
An injector pump approach has the added value of
being able to adjust to changes in the system water
coming back to the heater take-off.

Cold Water Starts

Cold water starts, where the inlet water temperature
remains below 120°F (49°C) for more than 7 minutes,
must have cold water start protection. Known protection methods consist of mixing heated outlet water
with the inlet water using a bypass to raise the inlet to
120°F (49°C) or higher. Once the system is heated up
and has return water temperatures of 120°F (49°C) or
higher, the mixing of outlet water with inlet water is no
longer needed and the bypass can be shut off. If the
bypass is not shut off as the system heats up, the outlet temperature may continue to climb and trip the high
limit, thereby shutting down the heater. Thus an automatic valve system, such as a three-way proportional
valve or a modulating two-way valve to control the
bypass, should be utilized.

*

*Maximum 4 times the pipe diameter or 12”, whichever is less.

Fig. 10: Cold Water Run

Hydronic Heating
Pump Selection

In order to ensure proper performance of your heater
system, you must install a correctly-sized pump. Raypak requires designing for a ∆T within the range of
10°F to 40°F (5°C to 20°C). See Table F for acceptable flow rates for each model (∆T is the temperature
difference between the inlet and outlet water when the
heater is firing at full rate).

*

*Maximum 4 times the pipe diameter or 12”, whichever is less.

Feedwater Regulator

Fig. 9: Cold Water Start

Raypak recommends that a feedwater regulator be installed and set at 12 psi minimum pressure at the
highest point of the system. Install a check valve or
back flow device upstream of the regulator, with a
manual shut-off valve as required by local codes.

Cold Water Run

Cold water run differs from cold water start in that the
system water entering the heater remains below
120°F (49°C) continuously. Typically, this is the case in
swimming pool heating. If the system water is kept in
a narrow temperature range of no more than 10°F
(5°C), a permanent manual bypass can be employed

14

Input Output

Model
No.

MBTUH

504

500

420

1104

1100

924

754

750

1504

1500

2004

1999

630
1260
1679

20° ∆T

gpm

∆P

gpm

6.0

42

42

2.7

92

13.3

63

30° ∆T

gpm

∆P

gpm

2.9

32

1.7

32

13.3

63

8.0

1.4

62

6.7

112

26.9

46

Note: Basis for minimum flow is ∆T. Basis for maximum flow is gpm.

Piping

Min. Flow

∆P

28

84

40° ∆T

84

4.1
16.0

∆P

∆T

gpm

1.7

40

25

1.1

46

4.1

63
84

Max. Flow

8.0

16.0

34
40
40
40

∆P

∆T

100

13.8

13

113

22.2

22

100
113
113

11.3

18.6
27.2

8

16
30

Table F: Heater Rates of Flow and Pressure Drops

All high points should be vented. A heater installed
above radiation level must be provided with a low water cut-off device (sales order option F-10). This
heater, when used in connection with a refrigeration
system, must be installed so that the chilled medium is
piped in parallel with the heater with appropriate
valves to pre-vent the chilled medium from entering
the heater.

THERMOSTAT OR
SYSTEM SENSOR

The piping system of a hot water heater connected to
heating coils located in air handling units where they
may be exposed to circulating refrigerated air, must be
equipped with flow control valves or other automatic
means to prevent gravity circulation of the heater
water during the cooling cycle. It is highly recommended that the piping be insulated.

*Maximum 4 times the pipe diameter or 12”, whichever is less.

Air-Separation/Expansion Tank

Fig. 12: Single Heater - Low-Temperature (Heat Pump)
Application with Primary/Secondary Piping

All heaters should be equipped with a properly sized
expansion tank and air separator fitting as shown in
Fig. 11.

THERMOSTAT OR
SYSTEM SENSOR

*Maximum 4 times the pipe diameter or 12”, whichever is less.

Fig. 11: Air-Separation/Expansion Tank

15

Fig. 13: Dual Heaters (Reverse/Return)
with Primary/Secondary Piping

Three-Way Valves

NOTE: If local codes require a vacuum relief valve,
acquire one locally and install per valve
manufacturer’s instructions.

Three-way valves intended to regulate system water
temperatures by reducing flow in the boiler should not
be used. Raypak heaters are high-recovery, low-mass
heaters which are not subject to thermal shock. See
Fig. 16 and instructions on page 17 for adjusting the
manual bypass.

Potable Water and Space Heating

CAUTION: When this heater is used for both
potable water and space heating, observe the
following to ensure proper operation.

Domestic Hot Water

1. All piping materials and components connected to
the water heater for the space heating application
shall be suitable for use with potable water.

When designing the water piping system for domestic
hot water applications, water hardness should be considered. Table G indicates the suggested flow rates for
soft, medium and hard water. Water hardness is expressed in grains per gallon.

2. Toxic chemicals, such as used for boiler treatment,
shall not be introduced into the potable water used
for space heating.

SYSTEM
SUPPLY

3. If the heater will be used to supply potable water,
it shall not be connected to any heating system or
components previously used with a non-potable
water heating appliance.

4. When the system requires water for space heating
at temperatures higher than 140°F (60°C), a
means such as a mixing valve shall be installed to
temper the water in order to reduce scald hazard
potential.
Pool Heating

SYSTEM
RETURN

When a boiler or water heater is used in a pool heating application, ensure that all the following installation
requirements are met.

Fig. 14: Single Domestic Hot Water Heater and Storage
Tank
Model
No.
504
754

MBTUH

Input

Output

∆T

gpm

750

630

25

50

500

1104

1045

2004

1900

1504

Soft (0-4 grains per gallon)

1425

420
888

1211

1615

17
30
30
30

∆P

MTS

SHL

∆T

gpm

4.0

2

6.3

20

65

50

3.6

60

6.4

2-1/2

26.1

2-1/2

82

110

Medium (5-15 grains per gallon)

12.7

2

2-1/2

5.9
7.6

14.9
29.8

13
20
22
29

∆P

MTS

SHL

6.4

2

2-1/2

65

5.5

92

13.2

2-1/2

113

27.4

2-1/2

113

22.3

2

Hard* (16-25 grains per gallon)
∆T

gpm

10.2

13

100

26.3

22

113

9.3

15.9
31.3

9

16
29

∆P

MTS

SHL

13.8

2

22.2

95

10.4

113

18.7

2-1/2

27.4

2-1/2

113

22.3

2

2-1/2

∆T = Temperature rise, °F
∆P = Pressure drop through heat exchanger, ft
SHL = System head loss, ft (based on heater and tank placed no more than 5 ft apart and equivalent length of 50 eq ft of tubing)
gpm = Gallons per minute, flow rate
MTS = Minimum tubing size
*Must utilize optional cupro-nickel tubes. If over 25 grains per gallon, a water softener/treatment system must be utilized.
Caution: For scale free operation with "Hard Water" (16-25 grains per gallon of total hardness), the operating control must NOT be set
higher than 130°F. For higher than 130°F operation, a water softener/treatment system must be utilized.

Table G: Domestic Water Heater Flow Rate Requirements

16

18.1
22.6
26.3
31.3

The MVB must be equipped with a field-supplied external pump and bypass arrangement. This
arrangement blends outlet water with the inlet water to
increase the inlet water temperature to a minimum of
105°F (40°C) for Pool Heater (P and WHP) versions
and 120°F (49°C) for Hydronic Heating (H7) or
Domestic Hot Water (WH1) versions, thereby reducing
the likelihood of condensation forming on the heat
exchanger. The pump also serves to circulate water
through the heater from the main system piping.

1. Turn on pump.

2. Turn on heater and wait until heater goes to full
fire.

3. With the heater operating at 100% firing rate, set
Valve A (the bypass) to 1⁄2 open position, and Valve
B to fully open position. See Fig. 16.

4. Adjust Valve A until the inlet water temperature is
105°F (40°C) or 120°F (49°C) depending upon
heater type.

CAUTION: Power to the heater should be
interlocked with the main system pump to make sure
the heater does not fire without the main system
pump in operation. Improper flow control can
damage the heater. Uncontrolled flow (too high) or
restricted flow (too low) can seriously damage the
heater. Follow these instructions to make sure your
heater is properly installed.

NOTE: Opening the valve will increase the
temperature and closing the valve will decrease the
temperature.

5. If this process does not raise the inlet water temperature to 105°F (40°C) for Pool Heater (P and
WHP) versions and 120°F (49°C) for Hydronic
Heating (H7) or Domestic Hot Water (WH1) versions and Valve A is fully open, then slowly throttle
Valve B closed to increase the inlet water temperature to the required temperature.

To complete the installation of the pool heater, the pool
thermostat must be installed in the main return water
line, upstream of the heater. This will ensure that the
heater will be energized at the right time.

POOL
THERMOSTAT
FROM
FILTER

*
TO POOL

CHEMICAL
FEED

*Maximum 4 times the pipe diameter or 12”, whichever is less.

Fig. 15: Single Pool Heater Application

Adjustment of the manual bypass valve is critical to
proper operation of the heater. The manual bypass
valve should be adjusted to achieve a minimum inlet
water temperature of 105°F (40°C) for Pool Heater (P
and WHP) versions and 120°F (49°C) for Hydronic
Heating (H7) or Domestic Hot Water (WH1) versions
and a system supply water temperature below 140°F
(60°C). When starting with a cold pool, make initial
adjustments. Make final adjustments when pool water
approaches desired temperature.

The use of a bypass is required for proper operation in
a pool heating application. Use the following instructions to set the manual bypass:

Fig. 16: “H” Bypass Setting

17

Pool/Spa Water Chemistry

NOTE: For automatic temperature adjustment, a
Cold Water Run (CWR) system can be used instead
of a manual bypass. See Fig. 10.

CAUTION: Corrosive water voids all warranties.

CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can
damage the heater and void the warranty.

NOTE: Chemical imbalance can cause severe
damage to your heater and associated equipment.
Chemical imbalance can cause severe damage to the
pool heater and associated equipment. Maintain the
water chemistry according to the chart below. If the
mineral content and dissolved solids in the water
become too high, scale forms inside the heat exchanger tubes, reducing heater efficiency and damaging the
heater. If the pH drops below 7.2, this will cause corrosion of the heat exchanger and severely damage the
heater. Heat exchanger damage resulting from chemical imbalance is not covered by the warranty.

Winterizing Your Heater

Heaters installed outdoors as pool heaters in freezing
climate areas should be shut down for the winter. To
shut down the heater, turn off manual main gas valve
and main gas shut-off. Close isolation valves. Drain
the heater using the hose bibs located on the bottom
of the heat exchanger.
NOTE: There are 2 separate drains on the MVB
that must BOTH be drained to protect the heat
exchanger. These are both accessible by removing
the lower front door from the heater. Drain any
piping of all water that may experience belowfreezing temperatures.

For your health and the protection of your pool equipment, it is essential that your water be chemically
balanced. The following levels must be used as a
guide for balanced water.
Occasional chemical shock dosing of the pool or spa
should not damage the heater providing the water is
balanced.

Automatic chemical dosing devices and salt chlorinators are usually more efficient in heater water, unless
controlled, they can lead to excessive chlorine level
which can damage your heater.

Recommended Level(s)

Fiberglass Pools

Fiberglass Spas

Other Pool and Spa
Types

7.3-7.4

7.6-7.8

Water Temperature

68-88°F (20-31°C)

89-104°F (31-40°C)

Total Alkalinity (ppm)

120-150

120-150

Salt (ppm)

6000 Maximum

6000 Maximum

6000 Maximum

Total Dissolved Solids
(ppm)

3000 Maximum

3000 Maximum

3000 Maximum

pH

Calcium Hardness (ppm)
Free Chlorine (ppm)*

7.3-7.4

200-300

150-200

2-3

2-3

*Free Chlorine MUST NOT EXCEED 5 ppm!

Table H: Water Chemistry

18

68-104°F (20-40°C)
80-120

200-400
2-3

Further advice should be obtained from your pool or
spa builder, accredited pool shop, or chemical supplier for the correct levels for your water.

The heater must be isolated from the gas supply piping system by closing the upstream manual shut-off
valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than
1/2 psi (3.45 kPa). Relieve test pressure in the gas
supply line prior to reconnecting the heater and its
manual shut-off valve to the gas supply line. FAILURE
TO FOLLOW THIS PROCEDURE MAY DAMAGE
THE GAS VALVE. Over-pressurized gas valves are
not covered by warranty. The heater and its gas connections shall be leak-tested before placing the
appliance in operation. Use soapy water for leak test.
DO NOT use an open flame.

Automatic Chlorinators and
Chemical Feeders

All chemicals must be introduced and completely diluted into the pool or spa water before being circulated
through the heater. Do not place sanitizing chemicals
in the skimmer. High chemical concentrations will
result when the pump is not running (e.g. overnight).
Chlorinators must feed downstream of the heater and
have an anti-siphoning device to prevent chemical
back-up into the heater when the pump is shut off.
NOTE: High chemical concentrates from feeders
and chlorinators that are out of adjustment will cause
rapid corrosion to the heat exchanger. Such damage
is not covered under the warranty.
NOTE: Failure of a heat exchanger due to lime
scale build-up on the heating surface, low pH or
other chemical imbalance is non-warrantable.

Gas Supply

Fig. 17: Gas Supply Connection

DANGER: Make sure the gas on which the heater
will operate is the same type as specified on the
heater’s rating plate.

CAUTION: Do not use Teflon tape on gas line pipe
thread. A pipe compound rated for use with natural
and propane gases is recommended. Apply
sparingly only on male pipe ends, leaving the two
end threads bare.

Gas piping must have a sediment trap ahead of the
heater gas controls, and a manual shut-off valve located outside the heater jacket. It is recommended
that a union be installed in the gas supply piping adjacent to the heater for servicing. The gas supply
pressure to the heater must not exceed 10.5 in. WC for
natural gas or 13.0 in. WC for propane gas. A poundsto-inches regulator must be installed to reduce the gas
supply pressure if it is higher than noted above. This
regulator should be placed a minimum distance of 10
times the pipe diameter upstream of the heater gas
controls. Refer to Table I for maximum equivalent pipe
lengths.

CAUTION: Support gas supply piping with
hangers, not by the heater or its accessories. Make
sure the gas piping is protected from physical
damage and freezing, where required.

Gas Supply Pressure

A minimum of 4.0 in. WC and a maximum of 10.5 in.
WC upstream gas pressure is required under load and
no-load conditions for natural gas. A minimum of 4.0
in. WC and a maximum of 13.0 in. WC is required for
propane gas. The gas pressure regulator(s) supplied
on the heater is for low-pressure service. If upstream
pressure exceeds these values, an intermediate gas
pressure regulator, of the lockup type, must be
installed.

Gas Supply Connection

CAUTION: The heater must be disconnected from
the gas supply during any pressure testing of the gas
supply system at test pressures in excess of 1/2 psi
(3.45 kPa).
19

Model
No.
504

1 in. NPT

N

15

754

1104

5

P

35
15

1504

1-1/4 in. NPT

1-1/2 in. NPT

65

150

150

360

15

35

35

75

N

P

35

75

10

2004

20

N

70
20

2 in. NPT

P

N

175

250

45

60

P

2-1/2 in. NPT
N

100

250

225

35

85

85

150

150

P

275
200

Natural Gas – 1,000 BTU/ft3, 0.60 specific gravity at 0.5 in. WC pressure drop
Propane Gas – 2,500 BTU/ft3, 1.53 specific gravity at 0.6 in. WC pressure drop

Table I: Maximum Equivalent Pipe Length

When connecting additional gas utilization equipment
to the gas piping system, the existing piping must be
checked to determine if it has adequate capacity for
the combined load.

•

•
•

The gas valve pressure regulator on the heater is
nominally preset as noted in Table J.

•

During normal operation, carbon dioxide should be 8.5
to 9.0% at full fire for natural gas and between 9.5 and
10.0% for propane gas. Carbon monoxide should be
‹100ppm.
Model
No.
504
754

1104

1504
2004

The MVB 504-1504 heaters are wired for 120 VAC, 12
amps while the MVB 2004 heaters are wired for 120
VAC, 18 amps. Consult the wiring diagram shipped
with the heater. Before starting the heater, check to
ensure proper voltage to the heater and pump.

Manifold Gas Pressure
(High Fire Values)

Natural Gas

Propane Gas

-0.4

-0.1

-0.1
-1.0
-2.4
-1.0

NOTE: Manifold pressures should be ±0.2 in. WC.

National Electrical Code and any other national,
state, provincial or local codes or regulations having jurisdiction.
Safety wiring must be NEC Class 1.
Heater must be electrically grounded as required
by the NEC.
In Canada, CSA C22. 1 C.E.C. Part 1.

Boiler mounted pumps (up to 3⁄4 hp) get their power
supply directly from the boiler power supply (connections in rear wiring box). Install a circuit breaker sized
sufficiently for both the heater and the pump. Pumps
larger than 3⁄4 hp must use a separate power supply
and run the power through the optional pump contactor which is located in the rear wiring box. Use
appropriately-sized wire as defined by NEC, CSA
and/or local codes. All primary wiring should be 125%
of minimum rating.

-0.1
-0.2
-0.6

-0.5

If any of the original wire as supplied with the heater
must be replaced, it must be replaced with 105°C wire
or its equivalent.

Table J: Manifold Gas Pressure Settings

CAUTION: For proper operation, no more than a
30% drop in gas supply pressure from no-load to fullload conditions is acceptable. Under no
circumstances should the pressure be outside the
listed operational range.

All high voltage wiring connections to the MVB heater
are made inside the rear wiring box as shown in Fig.
18. Pump power should be taken from terminals 2
(Com), 3 (GND) and 6 (Hot) – 3⁄4 hp and smaller ONLY.
Power to the MVB heater should be connected to terminals 1, 2, and 3 as noted in Fig. 18. All low voltage
wiring, including sensors, interlocks, enable/disable,
and various options are wired into terminals 1–20 on
the front wiring panel as noted in Fig. 18.

Electrical Power Connections
Installations must follow these codes:

20

WARNING: Using a multi-meter, check the
following voltages at the circuit breaker panel prior to
connecting any equipment. Make sure proper
polarity is followed and house ground is proven.
(See Fig. 19.)
Check the power source:

AC = 108 VAC Minimum, 132 VAC MAX
AB = 108 VAC Minimum, 132 VAC MAX
BC = <1 VAC Maximum

FRONT WIRING PANEL LOW VOLTAGE ELECTRICAL CONNECTIONS

Fig. 18: Wiring Electrical Connections

Field-Connected Controllers

Fig. 20: Multi-meter

It is strongly recommended that all individually-powered control modules and the heater should be
supplied from the same power source.

Making the Electrical Connections
Refer to Fig. 18-21.

NOTE: Field-supplied isolation relays should be
installed when field-connected controllers are
mounted more than 50 equivalent feet (18 AWG)
from heater. See wiring diagrams.

1. Verify that circuit breaker is properly sized by
referring to heater rating plate. A dedicated circuit
breaker should be provided.
2. NOTE: Current draw noted on rating plate does
not include pump current.

NOTE: Minimum 18 AWG, 105°C, stranded wire
must be used for all low voltage (less than 30 volts)
external connections to the unit. Solid conductors
should not be used because they can cause
excessive tension on contact points. Install conduit
as appropriate. All high voltage wires must be the
same size (105°C, stranded wire) as the ones on the
unit or larger.

3. Turn off all power to the heater. Verify that power
has been turned off by testing with a multi-meter
prior to working with any electrical connections or
components.

4. Observe proper wire colors while making electrical connections. Many electronic controls are
polarity sensitive. Components damaged by improper electrical installation are not covered by
warranty.

Check the Power Source
BLACK

5. Provide overload protection and a disconnect
means for equipment serviceability as required by
local and state code.

CIRCUIT
BREAKER

WHITE

6. Install heater controls, thermostats, or building
management systems in accordance with the
applicable manufacturers’ instructions.

GREEN
GROUND

A B

7. Conduit should not be used as the earth ground.

C

Fig. 19: Wiring Connections

21

Venting

NOTE: A grounding electrode conductor shall be
used to connect the equipment grounding
conductors, the equipment enclosures, and the
grounded service conductor to the grounding
electrode.

CAUTION: Proper installation of flue venting is
critical for the safe and efficient operation of the
heater.

General

Field Wiring Connection

Appliance Categories

CAUTION: Label all wires prior to disconnection
when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper
operation after servicing.

Heaters are divided into four categories based on the
pressure produced in the exhaust and the likelihood of
condensate production in the vent.

Category I – A heater which operates with a non-positive vent static pressure and with a vent gas
temperature that avoids excessive condensate production in the vent.

DANGER: SHOCK HAZARD

Make sure electrical power to the heater is disconnected to avoid potential serious injury or damage to
components.

Category II – A heater which operates with a non-positive vent static pressure and with a vent gas
temperature that may cause excessive condensate
production in the vent.

Category III – A heater which operates with a positive
vent pressure and with a vent gas temperature that
avoids excessive condensate production in the vent.

Category IV – A heater which operates with a positive
vent pressure and with a vent gas temperature that
may cause excessive condensate production in the
vent.

HIGH VOLTAGE
WIRING

See Table K for appliance category requirements.

NOTE: For additional information on appliance
categorization, see appropriate ANSI Z21 Standard
and the NFGC (U.S.), or B149 (Canada), or
applicable provisions of local building codes.

Fig. 21: High Voltage Wiring Location

CAUTION: Condensate drains for the vent piping
are required for installations of the MVB. Follow vent
manufacturer instructions for installation and location
of condensate drains in the vent. Condensate drain
must be primed with water to prevent gas flue leak
and must be routed to an appropriate container for
neutralization before disposal, as required by local
codes.

LOCATOR DIMPLES
FOR OPTIONAL
COMPONENTS

Fig. 22: Locator Dimples for Optional Components

WARNING: Contact the manufacturer of the vent
material if there is any question about the appliance
categorization and suitability of a vent material for
application on a Category III or IV vent system.
Using improper venting materials can result in
personal injury, death or property damage.
22

Combustion
Air Supply
From Inside Building
(Non-Direct Venting)

From Outside Building
(Direct Venting)

Exhaust
Configuration

Heater Venting
Category

Horizontal Throughthe-Wall Venting

III

Vertical
Venting

I

Vertical
Venting

I

Horizontal Throughthe-Wall Venting

III

Certified
Materials

B-Vent
Equivalent

Combustion Air
Inlet Material

Stainless Steel
AL29-4C
B-Vent
Equivalent

Stainless Steel
AL29-4C

Galvanized Steel
PVC
ABS
CPVC

Table K: Venting Category Requirements

6. Un-insulated single-wall metal vent pipe shall not
be used outdoors in cold climates for venting gasfired equipment.

Support of Vent Stack

The weight of the vent stack or chimney must not rest
on the heater vent connection. Support must be provided in compliance with applicable codes. The vent
should also be installed to maintain proper clearances
from combustible materials. Use insulated vent pipe
spacers where the vent passes through combustible
roofs and walls.

7. Through-the-wall vents for Category II and IV
appliances and non-categorized condensing appliances shall not terminate over public walkways or
over an area where condensate or vapor could
create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves, or
other equipment. Where local experience indicates that condensate is a problem with Category
I and III appliances, this provision shall also apply.

Vent Terminal Location

NOTE: During winter months check the vent cap
and make sure no blockage occurs from build-up of
snow or ice.

8. Locate and guard vent termination to prevent accidental contact by people or pets.
9. DO NOT terminate vent in window well, stairwell,
alcove, courtyard or other recessed area.

1. Condensate can freeze on the vent cap. Frozen
condensate on the vent cap can result in a blocked
flue condition.

10. DO NOT terminate above any door, window, or
gravity air intake. Condensate can freeze, causing
ice formations.

2. Give special attention to the location of the vent
termination to avoid possibility of property damage or personal injury.

11. Locate or guard vent to prevent condensate from
damaging exterior finishes. Use a rust-resistant
sheet metal backing plate against brick or masonry surfaces.

3. Gases may form a white vapor plume in winter.
The plume could obstruct a window view if the termination is installed near windows.

12. DO NOT extend exposed vent pipe outside of
building beyond the minimum distance required
for the vent termination. Condensate could freeze
and block the vent pipe.

4. Prevailing winds, in combination with below-freezing temperatures, can cause freezing of
condensate and water/ice build-up on buildings,
plants or roofs.

U.S. Installations

5. The bottom of the vent terminal and the air intake
shall be located at least 12 in. above grade, including normal snow line.

Refer to the latest edition of the National Fuel Gas
Code.
23

Vent termination requirements are as follows:

1. Vent must terminate at least 4 ft below, 4 ft horizontally from or 1 ft above any door, window or
gravity air inlet to the building.

5. Within 6 ft (1.8 m) of any gas service regulator
vent outlet.
6. Less than 1 ft (305 mm) above grade level.

2. The vent must not be less than 7 ft above grade
when located adjacent to public walkways.

7. Within the 3 ft (915 mm) of a window or door which
can be opened in any building, any non-mechanical air supply inlet to any building or the
combustion air inlet of any other appliance.

3. Terminate vent at least 3 ft above any forced air
inlet located within 10 ft.

8. Underneath a verandah, porch or deck, unless the
verandah, porch or deck is fully open on a minimum of two sides beneath the floor, and the
distance between the top of the vent termination
and the underside of the verandah, porch or deck
is greater than 1 ft (305 mm).

4. Vent must terminate at least 4 ft horizontally, and
in no case above or below unless 4 ft horizontal
distance is maintained, from electric meters, gas
meters, regulators, and relief equipment.

5. Terminate vent at least 6 ft away from adjacent
walls.

Venting Installation Tips

6. DO NOT terminate vent closer than 5 ft below roof
overhang.
7. The vent terminal requires a 12 in. vent terminal
clearance from the wall.

Support piping:
•
•
•

8. Terminate vent at least 1 ft above grade, including
normal snow line.

9. Multiple direct vent installations require a 4 ft
clearance between the ends of vent caps located
on the same horizontal plane.

WARNING: Examine the venting system at least
once a year. Check all joints and vent pipe
connections for tightness, corrosion or deterioration.

WARNING: The Commonwealth of Massachusetts
requires that sidewall vented heaters, installed in
every dwelling, building or structure used in whole or
in part for residential purposes, be installed using
special provisions as outlined on page 53 of this
manual.

Venting Configurations

For heaters connected to gas vents or chimneys, vent
installations shall be in accordance with the NFGC
(U.S.), or B149 (Canada), or applicable provisions of
local building codes.

Canadian Installations

Natural Draft Vertical Venting
(Category I)

Refer to latest edition of the B149 Installation code.
A vent shall not terminate:

Installation

1. Directly above a paved sidewalk or driveway
which is located between two single-family dwellings and serves both dwellings.

Natural draft venting uses the natural buoyancy of the
heated flue products to create a thermal driving head
that expels the exhaust gases from the flue. The negative draft must be within the range of -.01 to -.08 in.
WC as measured 12 in. above the appliance flue outlet to ensure proper operation. Vent material must be
listed by a nationally recognized test agency.

2. Less than 7 ft (2.13 m) above a paved sidewalk or
paved driveway located on public property.

3. Within 6 ft (1.8 m) of a mechanical air supply inlet
to any building.

4. Above a meter/regulator assembly within 3 ft (915
mm) horizontally of the vertical centre-line of the
regulator.

horizontal runs—at least every 5 ft
vertical runs—use braces
under or near elbows

The maximum and minimum venting length for Category I appliances shall be determined per the NFGC
(U.S.) or B149 (Canada).

24

Model
No.

Certified
Vent
Material

504
754

1104

1504
2004

Vent Size
(in.)
8

Category I
(Type B
Equivalent)

10
10
12

Vertical Vent
Height1 (ft)

Min.

Max.

5

25

Combustion Air
Intake Pipe
Material
Galvanized
Steel,
PVC,
ABS,
CPVC

Air Inlet
Max. Length* (ft)

6” Ø

8” Ø

45

100**

14

1 Vent lengths are based on a lateral length of 2 ft. Refer to the latest edition of the NFGC for further

details. When vertical height exceeds 25 ft, consult factory prior to installation.
* Subtract 10 ft per elbow. Max. 4 elbows.
** Adapters supplied by others.

Table L: Category I Vertical Venting

The diameter of vent flue pipe should be sized according to the NFGC (U.S.) and B149 (Canada).

The connection from the appliance vent to the stack
must be as direct as possible. The horizontal breaching of a vent must have an upward slope of not less
than 1/4 inch per linear foot from the heater to the vent
terminal. The horizontal portions of the vent shall also
be supported for the design and weight of the material
employed to maintain clearances and to prevent physical damage or separation of joints.
Termination

The vent terminal should be vertical and should terminate outside the building at least 2 ft above the highest
point of the roof that is within 10 ft. The vent cap
should have a minimum clearance of 4 ft horizontally
from and in no case above or below (unless a 4 ft horizontal distance is maintained) electric meters, gas
meters, regulators and relief equipment. The distance
of the vent terminal from adjacent public walkways,
adjacent buildings, open windows and building openings must be consistent with the NFGC (U.S.) or B149
(Canada). Gas vents supported only by flashing and
extended above the roof more than 5 ft should be securely guyed or braced to withstand snow and wind
loads.
CAUTION: A listed vent cap terminal adequately
sized, must be used to evacuate the flue products
from the building.
25

Fig. 23: Vertical Venting

45

10” Ø

85**

common venting system placed in operation, while the
other appliances remaining connected to the common
venting system are not in operation.

Common Venting

Manifolds that connect more than one heater to a common chimney must be sized to handle the combined
load. Consult available guides for proper sizing of the
manifold and the chimney. At no time should the area
of the common vent be less than the area of the
largest heater exhaust outlet.

1. Seal any unused opening in the common venting
system.

2. Visually inspect the venting system for proper size
and horizontal pitch and verify there is no blockage, restriction, leakage, corrosion or other unsafe
condition.

WARNING: Vent connectors serving appliances
vented by natural draft shall not be connected into
any portion of mechanical draft systems operating
under a positive pressure.

3. Insofar as is practical, close all building doors and
windows and all doors between the space in which
the appliances remaining connected to the common venting system are located and other spaces
of the building. Turn on clothes dryers and any appliance not connected to the common vent
system. Turn on any exhaust fans, such as range
hoods and bathroom exhausts, at maximum
speed. Do not operate summer exhaust fan. Close
fireplace dampers.

CAUTION: Vent connectors for natural draft
venting systems must be Type B or better.

Common venting systems may be too large once an
existing unit is removed. At the time of removal of an
existing appliance, the following steps must be followed with each appliance remaining connected to the

Fig. 24: Typical Common Venting

26

4. Place in operation the appliances being inspected.
Follow the manufacturer’s instructions for lighting
each appliance. Adjust thermostat so appliance
will operate continuously.

Model
No.

Vent Size
(in.)

Volume of
Flue Products
(CFM)

754

10

260

1504

12

504

5. Check the pressure at a pressure tap located 12
in. above the bottom joint of the first vertical vent
pipe. Pressure should be anywhere between -0.01
and -0.08 in. WC.

1104

6. After it has been determined that each appliance
remaining connected to the common venting system properly vents when tested as outlined above,
return doors, windows, exhaust fans, fireplace
dampers and other gas burning appliances to their
previous conditions of use.

2004

8

10
14

NOTE: Data for 100% firing rate.

170
380
510
680

Table M: Typical Volume of Flue Products

Horizontal Through-the-Wall Direct
Venting (Category III)

7. Any improper operation of the common venting
system should be corrected so that the installation
conforms with the NFGC (U.S.) or B149 (Canada).
When re-sizing any portion of the common venting
system, the common venting system should be resized to approach the minimum size as
determined using the appropriate tables in Appendix G in the NFGC (U.S.) or B149 (Canada).

Engineered Vent Systems

Table M provides boiler discharge vent volumes of flue
products at full fire for the calculation of appropriate
vent sizing for common venting.
WARNING: Vent connectors serving any other
appliances shall not be connected into any portion of
mechanical draft systems operating under a positive
pressure. If an MVB heater is installed to replace an
existing heater, the vent system MUST be verified to
be of the correct size and Category. If it is NOT, it
MUST be replaced.

Fig. 25: Horizontal Through-the-Wall Venting

NOTE: For extractor sizing, typical CO2 levels are
8.5% for natural gas and 9.5% for LP gas and flue
temperature of 350° F.

OPTIONAL HORIZONTAL THROUGH-THE-WALL VENTING
(CATEGORY IV)

27

Fig. 26: Alt. Horizontal Through-the-Wall Venting

•
•
•
•

NOTE: While a drain connection is required in the
vent of all Cat. III horizontal MVB installations, the
drain can be accomplished in several different ways.
The figures in this manual show the drain in a vent
tee, however, this can also be accomplished using
an inline collector for condensing stacks or an inline
vertical or horizontal collector available from several
of the listed vent manufacturers.

75’ of
65’ of
55’ of
45’ of

straight
straight
straight
straight

flue pipe
flue pipe and one elbow
flue pipe and two elbows
pipe and three elbows

The vent cap is not considered in the overall length of
the venting system.
The vent must be installed to prevent flue gas leakage.
Care must be taken during assembly to ensure that all
joints are sealed properly and are airtight. The vent
must be installed to prevent the potential accumulation
of condensate in the vent pipes. It is required that:
1. The vent must be installed with a condensate
drain located in proximity to the heater as directed
by the vent manufacturer.
2. The vent must be installed with a slight upward
slope of not less than 1/4 inch per foot of horizontal run to the vent terminal.

3. The vent must be insulated through the length of
the horizontal run.
Termination

The flue direct vent cap MUST be mounted on the exterior of the building. The direct vent cap cannot be
installed in a well or below grade. The direct vent cap
must be installed at least 1 ft above ground level and
above normal snow levels. The Raypak-approved
stainless steel flue direct vent cap must be used (sales
order option D-15). The vent terminal must be located
NO CLOSER than 12” off the wall.

Fig. 27: Horizontal Through-the-Wall Direct Venting

CAUTION: This venting system requires the
installation of a condensate drain in the vent piping
per the vent manufacturer’s instructions. Failure to
install a condensate drain in the venting system will
void all warranties on this heater.

WARNING: No substitutions of flue pipe or vent
cap material are allowed. Such substitutions would
jeopardize the safety and health of inhabitants.

Installation

Direct Vent—Vertical

These installations utilize the heater-mounted blower
to vent the combustion products to the outdoors.
Combustion air is taken from inside the room and the
vent is installed horizontally through the wall to the outdoors. Adequate combustion and ventilation air must
be supplied to the equipment room in accordance with
the NFGC (U.S.) or B149 (Canada).

The total length of the horizontal through-the-wall flue
system should not exceed 75 equivalent ft in length. If
horizontal run exceeds 75 equivalent ft, an appropriately sized variable-speed extractor must be used.
Each elbow used is equal to 10 ft of straight pipe. This
will allow installation in one of the four following
arrangements:

Installation

These installations utilize the heater-mounted blower
to draw combustion air from outdoors and force the
heated flue products through the vent pipe under positive pressure. The vent material must be in
accordance with the above instructions for vent materials. Vent material must be listed by a nationally
recognized test agency.

28

The connection from the appliance flue to the stack
must be as direct as possible and should be the same
size or larger than the vent outlet.

Certified
Vent
Material

Model
No.
504

Vent
Size
(in.)

Maximum
Horizontal
Vent Length
(ft)**

8

754

Category III

1104

1504

10
10
12

2004

** Subtract 10 ft per elbow. Max. 4 elbows.
t Adapters supplied by others.

Combustion Air
Intake Pipe
Material

Air Inlet
Max. Length** (ft)
6” Ø

8” Ø

45

100t

Galvanized Steel,
PVC,
ABS,
CPVC

75

14

45

10” Ø

85t

Table N: Category III Horizontal Vent & Horizontal Direct Vent

a minimum clearance of 4 ft horizontally from and in no
case above or below (unless a 4 ft horizontal distance
is maintained) electric meters, gas meters, regulators
and relief equipment. The distance of the vent terminal
from adjacent public walkways, adjacent buildings,
open windows and building openings must be consistent with the NFGC (U.S.) or B149 (Canada).
Flues supported only by flashing and extended above
the roof more than 5 ft should be securely guyed or
braced to withstand snow and wind loads.

The air inlet opening MUST be installed 1 ft above the
roof line or above normal snow levels that might obstruct combustion air flow. This dimension is critical to
the correct operation of the heater and venting system
and reduces the chance of blockage from snow. The
vent cap must have a minimum 3 ft vertical clearance
from the air inlet opening.

Fig. 28: Direct Vent - Vertical

WARNING: No substitutions of flue pipe or vent
cap material are allowed. Such substitutions would
jeopardize the safety and health of inhabitants.

CAUTION: This venting system requires the
installation of a condensate drain in the vent piping
per the vent manufacturer’s instructions. Failure to
install a condensate drain in the venting system will
void all warranties on this heater.

Outdoor Installation

See Table L for Category I venting guidelines.

Outdoor models must be vented with listed vent material per the following instructions and installed with the
optional factory-supplied outdoor vent kit. A special
vent cap and air intake hood are provided in accordance with CSA requirements. These must be
installed as illustrated in Fig. 29.

It is recommended that the intake vent be insulated in
colder climates.

Termination

The flue terminal should be vertical and should terminate outside the building at least 2 ft above the highest
point of the roof within 10 ft. The vent cap should have

29

Care must be taken when locating the heater outdoors, because the flue gases discharged from the

vent cap can condense as they leave the cap.
Improper location can result in damage to adjacent
structures or building finish. For maximum efficiency
and safety, the following precautions must be
observed:
1.
2.

3.

4.
5.
6.

NOTE: The vent cap and air intake hood must be
furnished by the heater manufacturer in accordance
with its listing (sales order option D-11).

NOTE: Condensate can freeze on the vent cap.
Frozen condensate on the vent cap can result in a
blocked flue condition.

Outdoor models must be installed outdoors and
must use the outdoor vent cap and air intake hood
available from the manufacturer (sales order
option D-11).
Periodically check venting system. The heater’s
venting areas must never be obstructed in any
way and minimum clearances must be observed
to prevent restriction of combustion and ventilation
air. Keep area clear and free of combustible and
flammable materials.

Freeze Protection

The Raypak electronic temperature control includes a
freeze protection feature. In the event the temperature
drops below 40°F at any of the boiler temperature sensors, the pump is turned on and will remain on until the
temperature at all boiler sensors rises to 45°F.

Controls

Do not locate adjacent to any window, door, walkway, or gravity air intake. The vent must be
located a minimum of 4 ft horizontally from such
areas.

WARNING: Installation, adjustment and service of
heater controls, including timing of various operating
functions, must be performed by a qualified installer,
service agency or the gas supplier. Failure to do so
may result in control damage, heater malfunction,
property damage, personal injury, or death.

Install above grade level and above normal snow
levels.

Vent terminal must be at least 3 ft above any
forced air inlet located within 10 ft.

WARNING: Turn off the power to the heater before
installation, adjustment or service of any heater
controls. Failure to do so may result in board
damage, heater malfunction, property damage,
personal injury, or death.

Adjacent brick or masonry surfaces must be protected with a rust-resistant sheet metal plate.

CAUTION: This appliance has provisions to be
connected to more than one supply source. To
reduce the risk of electric shock, disconnect all such
connections before servicing.
CAUTION: Risk of electric shock: More than one
disconnect switch may be required to de-energize
the equipment before servicing.

The Raypak electronic temperature control is provided to maintain the desired system water
temperature. The control has various modes of operation which are described on the following pages.
To minimize short cycling, locate the system (target)
sensor as follows:
Setpoint: The intended system supply temperature.

Fig. 29: Outdoor Venting

30

Deadband: Deadband is a band of temperature sensing where no action occurs. All temperature controllers
have a deadband and the purpose is to prevent shortcycling of the heater. The on-board temperature
controller has a deadband of 2ºF around the differential.
Differential: A heat source must be operated with a
temperature differential in order to prevent shortcycling. The temperature differential is divided around
the “target” temperature or set-point. The Call For Heat
(CFH) contact will close in the controller when the
water temperature is below the target temperature by
1/2 of the differential setting, and will open when the
water temperature is above the target temperature by
1/2 of the differential setting. See Fig. 30.

Fig. 31: Buffer Tank Piping

Mode 2 – Setpoint operation using primary/secondary
piping. The control operates the heater to satisfy a
remote system sensor. The heater is turned off based
on boiler target and boiler differential (factory default
H7, P and WHP boilers). See Fig. 32.

Fig. 30: Differential Graph

For systems with less than 4:1 turndown, the control
should be placed in the system return, upstream of the
inlet piping to the heater, as shown in Figs. 32, 34 and
35. This placement will avoid short cycling the heat
source. Raypak recommends using a smaller differential setting when controlling the water temperature on
the return side. As a starting point, set the return differential to 10ºF and this will allow the system return
temperature to vary 5ºF above and 5ºF below the setpoint.

For systems with more than 4:1 turndown, the recommended location of the system (target) sensor is in the
system supply loop, downstream of the outlet piping
from the heater. When controlling systems with more
than 4:1 turndown; set the supply side differential to
20ºF and the temperature will vary ±10ºF around the
setpoint.
In lieu of installing the target sensor in the system
return, a properly-sized buffer tank can be installed as
shown in Fig. 31. Consult factory for buffer tank sizing.

*

*Maximum 4 times the pipe diameter or 12”, whichever is less.

Fig. 32: Mode 2 Primary/Secondary Piping

Mode 3 – Dedicated DHW operation using UniTemp
80 piping. A call for heat is determined by the DHW
sensor and the DHW boiler target. The heater outlet
water is also controlled to the boiler target temperature
(factory default WH1 water heaters). See Fig. 33.

Operating Modes

Mode 1 (Not supported) – Setpoint operation using
primary piping. The heater outlet water temperature is
controlled to the boiler target setpoint.

31

trol operates the boiler burner to maintain the boiler
target at the boiler outlet sensor.

Mode 7 – Designed for an external input signal with
primary/secondary piping. The external input signal
can be provided from a BMS, an EMS or an external
control. The external input signal changes the boiler
target according to a linear scale (see Tables O & P).
The control operates the boiler burner to maintain the
boiler target at the system sensor. See Fig. 35.

ELECTRONIC

Fig. 33: Mode 3 Dedicated DHW

Mode 4 (Not supported) – Outdoor reset using primary piping. The heater is operated as in Mode 1.
However, the target temperature is based on outdoor
reset.

Mode 5 – Outdoor reset using primary/secondary piping. The heater is operated as in Mode 2. However, the
target temperature is based on outdoor reset. See Fig.
34.

*

*Maximum 4 times the pipe diameter or 12”, whichever is less.

Fig. 35: Mode 7 Primary/Secondary Piping with
External Target Temp

0-10 VDC

0-20 mA*

Boiler Target

1

2

50°F

0
2
3
4

*Maximum 4 times the pipe diameter or 12”, whichever is less.

Fig. 34: Mode 5 Primary/Secondary Piping with
Outdoor Reset

Mode 6 (Not supported) – Designed for an external
input signal with primary piping. The external input signal can be provided from a BMS, an EMS or a
sequencing control. The external input signal changes
the boiler target according to a linear scale. The con-

8

106.7°F

12

144.1°F

6

7

14

9

10

*Requires a 500Ω resistor.

32

68.9°F

10

8

--- (OFF)

4

5
6

*

0

16
18
20

87.8°F

125.6°F
163.3°F
182.2°F
201.1°F
220°F

Table O: 0-10 VDC or 0-20 mA External Input Signal

2-10 VDC

4-20 mA*

Boiler Target

1

2

--- (OFF)

0
2
3
4

0
4
6
8

--- (OFF)
50°F

71.3°F
92.5°F

5

10

113.8°F

7

14

156.3°F

18

198.8°F

6
8
9

10

*Requires a 500Ω resistor.

12
16
20

RAYPAK
MODULATING
TEMP CONTROL

OUTDOOR AIR
SENSOR

135°F

177.5°F
220°F

Table P: 2-10 VDC or 4-20 mA External Input Signal

*

*Maximum 4 times the pipe diameter or 12”, whichever is less.

Mode 8 – This mode is for remote firing control of the
heater via an external sequencer such as the Raypak
TempTracker MOD+. The Boil Max setting is the
heater shutdown temperature (max temperature). The
heater is enabled via dry contact at the Enable/Disable
connection at the low voltage terminal strip, and the firing rate is controlled by a 0-10 VDC signal from the
external sequencer. A control signal of ≥0.5 VDC
equates to minimum fire, and a signal of 10 VDC
equates to 100% firing rate.

Fig. 36: Mode 8 Primary/Secondary Piping with
External Direct Drive

BOIL ON - Accumulated runtime of heater (up to 999
hours, then resets to 0).
BOIL OUT - Actual heater outlet water temperature.
BOIL START - Starting boiler water temperature.

BOIL SUP - Actual system supply water temperature.

NOTE: For Modes 7 and 8, connect to pins 13 and
14 on the low-voltage panel. See page 21. Use
these modes for systems using an external signal.

BOIL TARGET - Target temperature that the heater is
trying to maintain.

Definitions

‘BURNER’ DELAY - Holds control output at ignition
setting from the start of the ignition sequence to the
specified burner delay time (0 to 3:00 min.).

NOTE: The defined terms are not active in all
modes of control operation.

DEM 1 - Indicates 24 VDC signal has been supplied to
the H+D terminal.

% OUT - Current percent modulation rate of heater.

BOIL DSGN - Design boiler water temperature used in
heat loss calculations.

DEM 2 - Indicates 24 VDC Flame Proof signal is present.

BOIL MASS - This setting allows adjustment in the
field for high or low thermal masses; High thermal
mass (setting=3) provides slower reaction, lower thermal mass (setting=1) provides faster reaction.

DIFF - The operating differential of the heater; The
heater outlet water temperature is allowed to rise
above the BOIL TARGET temperature by 1⁄2 of this differential before the heater shuts off. For example, if
the heater target temperature is set to 160°F (71°C)
and the differential is set to 10°F (5°C), on temperature
rise, the heater will shut off at 165°F (74°C). Once the
heater shuts off, it will not come on again until the temperature falls to 155°F (68°C).

BOIL MAX - Highest outlet water temperature that the
control is allowed to use as a target temperature.

BOIL MIN - Lowest outlet water temperature that the
control is allowed to use as a target temperature.

33

Item

Modes

Boil Target

3

2

Boiler (H7)

Default Setting

2, 5, 7, 8

Boil Max

3

Boil Min

2, 3, 5, 7

Boil Mass

All

‘Burner’ Delay

140°F

OFF, 70 to 220°F

180°F

OFF, 70 to 220°F

160°F

5, 7

Range

OFF, 70 to 190°F

200°F

OFF, 120 to 225°F

135°F

OFF, 80 to 180°F

180°F

All

0:00 min

Diff

2, 3, 5, 7

Auto

DHW Diff

3

OFF, 120 to 190°F
0:00 to 3:00 min

1 (Low)

1 (Low), 2 (Med), 3 (High)

3

120°F

OFF, 70 to 190°F

‘Pump’ Dly

All

3:00 min

OFF, 0:20 to 9:55 min, ON

Outdr Design

5

-10°F

-60 to 32°F

DHW Target

Outdr Start

5°F

5

Boil Start

Boil Dsgn

70°F

5

135°F

5

70°F

5

WWSD
Units

All

Mode

N/A

Offset

7

External Input Signal

7

Auto, 2 to 42°F
2 to 10°F

35 to 85°F

35 to 150°F

180°F

120 to 220°F

°F

°F or °C

2

2 to 10 VDC
0°F

35 to 100°F
2, 3, 5, 7, 8

2 to 10 VDC or 0 to 10 VDC
-10°F to 10°F

Table Q: Temperature Control Default Setpoints—Boiler

Pool Heater (P, WHP)

Item

Modes

Default Setting

Boil Max

2

86°F

Boil Target
Boil Min

2
2

78°F

OFF, 45 to 106°F

70°F

OFF, 45 to 106°F

‘Burner’ Delay

All

0:00 min

Diff

2

1°F

Boil Mass

All

Range

OFF, 70 to 106°F
0:00 to 3:00 min

1 (Low)

1 (Low), 2 (Med), 3 (High)
1 to 3°F

‘Pump’ Dly

All

3:00 min

OFF, 0:20 to 9:55 min, ON

Mode

N/A

2

2

Units

All

°F

°F or °C

Table R: Temperature Control Default Setpoints—Pool Heater

34

Item
Boil Target

Water Heater (WH1)

Modes

Default Setting

3, 7

160°F

2

140°F

OFF, 70 to 190°F

180°F

OFF, 120 to 190°F
0:00 to 3:00 min

Boil Max

2, 3, 6, 7

‘Burner’ Delay

All

0:00 min

Diff

2, 3, 7

Auto

DHW Diff

3

Boil Min

Boil Mass

2, 3, 7

135°F

OFF, 70 to 190°F
OFF, 80 to 180°F

1 (Low)

1 (Low), 2 (Med), 3 (High)

3

120°F

OFF, 70 to 190°F

‘Pump’ Dly

All

3:00 min

OFF, 0:20 to 9:55 min, ON

Mode

N/A

3

2, 3, 7

Offset

7

DHW Target

Units

External Input Signal

All

Range

5°F

All

°F

7

2 to 10 VDC
0°F

Auto, 2 to 42°F
2 to 10°F
°F or °C

2 to 10 VDC or 0 to 10 VDC
-10°F to 10°F

Table S: Modulating Temperature Control Default Setpoints—Water Heater

installing a 500 Ω resistor on the external input signal
device’s terminals.

EXTERNAL INPUT SIGNAL – Selects external input
signal range (0-10VDC or 2-10VDC):

FP - Flame proof warning.

0-10VDC or 0-20 mA external input signal – When
the 0-10VDC signal is selected, an input voltage of 1
VDC corresponds to a boiler target temperature of
50°F (10°C). An input voltage of 10 VDC corresponds
to a boiler target temperature of 220°F (104°C). As the
voltage varies between 1 VDC and 10 VDC, the boiler
target temperature varies linearly between 50°F
(10°C) and 220°F (104°C) (refer to Table O). If a voltage below 0.5 VDC is received, the boiler target
temperature is displayed as “– – –” indicating that
there is no longer an internal call for heat. A 0-20 mA
signal can be converted to a 0-10 VDC signal by
installing a 500 Ω resistor on the external input signal
device’s terminals.

2-10VDC or 4-20 mA external input signal – When
the 2-10VDC signal is selected, an input voltage of 2
VDC corresponds to a boiler target temperature of
50°F (10°C). An input voltage of 10 VDC corresponds
to a boiler target temperature of 220°F (104°C). As the
voltage varies between 2 VDC and 10 VDC, the boiler
target temperature varies linearly between 50°F
(10°C) and 220°F (104°C) (refer to Table P). If a voltage below 1.5 VDC is received, the boiler target
temperature is displayed as “– – –” indicating that
there is no longer an internal call for heat. A 4-20 mA
signal can be converted to a 2-10 VDC signal by

MODE - Operating mode of the heater.

OFFSET - The Offset setting allows the boiler target
temperature to be fine tuned to the external input signal. The control reads the external input signal and
converts this to a boiler target temperature. The Offset
setting is then added to the boiler target temperature.
OUTDR - Outdoor air temperature.

OUTDR DESIGN - Design outdoor air temperature
used in the heat loss calculation.
OUTDR START - Starting outdoor air temperature.

PUMP DLY - Sets the operating time of the pump once
the CFH is satisfied.
TANK - Current DHW tank temperature (Mode 3).
TANK DIFF - Storage tank differential (Mode 3).

TANK TARGET - Target temperature in the DHW
storage tank (Mode 3).
35

Rank

Item Field

Number Field

Type

Fault Description

1

FP

Err

Warning

Flame proof warning

BOIL OUT

OPn

Error

Boiler outlet sensor open

BOIL IN

OPn

Error

Boiler inlet sensor open

SUP

OPn

Error

System sensor open

OUTDR

OPn

DHW

OPn

0

E01

2

BOIL OUT

4

BOIL IN

3
5
6
7

SUP

8

OUTDR

10

DHW

9

11

Err

Error

SHr

Error

SHr

Error

SHr

Error

SHr

Error

SHr

UNITS - Selects the temperature units to be displayed
(°F or °C).

Operation

The Raypak electronic temperature control uses a
Liquid Crystal Display (LCD) as a method of supplying information. The LCD is used to setup and monitor
system operation by means of three push buttons
(Item, L and M) shown at the bottom of Fig. 37.

Buttons
Selects
Menus,
Items and
adjusts
settings

All items displayed by the control are organized into
two menus, the view menu and the adjust menu. The
active menu is displayed in the upper right hand side
of the display in the menu field. The default menu is
the view menu.

System sensor short

Outdoor sensor short

Error

DHW sensor open

DHW sensor short

Menu Field
Displays the current menu
Number Field
Displays the
current value of
the selected
item
DHW
Modulation

External Input
Offset Signal

Modulating
Control

Item

Status Field
Displays the
current status
of the control’s
inputs, outputs
and operation

Fig. 37: Modulating Temperature Control Display

menu name, “ADJUST” will be displayed in the menu
field.

When the temperature control is powered up, the control turns on all segments in the display for 2 seconds,
then the software version is displayed for 2 seconds.
At the end of that 4 second period, the control enters
the normal operating mode and “VIEW” is displayed.
Pressing the scroll button “scrolls” through the displayed values in the “VIEW” menu.

To make an adjustment to a setting in the control,
begin by selecting the “ADJUST” menu. To change
from the view menu to the adjust menu, simultaneously press and hold all three buttons for 1 second. The

{

Boiler inlet sensor short

Outdoor sensor open

Item Field
Displays an
abbreviated
name of the
selected item

WWSD - Selects the outdoor temperature that shuts
the heater off, no matter what the demand. NOTE: The
WWSD segment will be displayed on the LCD.

Boiler outlet sensor short

Error
Error

Table T: Error Codes

EEPROM error

The menu will automatically revert back to the view
menu after 20 seconds of keyboard inactivity. Then
scroll to the desired item using the scroll button. Finally, use the L or M button to make the adjustment.
In the absence of other information, the values provided in Tables Q, R and S should be used as default
settings.

36

Heater Sequence of Operation

The optional single-try ignition module will lock out
after failing to light one time. To reset it, press and
release the small, recessed black push button located
inside of the cut-out on the lower right-hand corner of
the ignition module case. Turning off the power to
the heater WILL NOT reset the ignition module.

If all limits are satisfied and there is a call for heat:

1. The heater pump is powered and begins circulating water through the heat exchanger.
2. The blower is powered and goes through a 15 second prepurge beginning when air flow is proven by
closure of the blower suction air pressure switch.
3. The igniter is powered, and once proven, heats up
for 20 seconds.

4. The gas valve is then energized for a 4 second
trial for ignition period. Trial for ignition is fixed at
50% input. The heater is allowed to modulate once
flame is proven and the firing rate will adjust to
match the load based on the configuration and settings of the temperature control or external input.

5. Once the heat demand is satisfied the gas valve
will close and the blower will run a 30 second post
purge. The heater pump will continue to circulate
water for 0 to 10 minutes depending on the pump
delay setting on the Raypak modulating temperature control.

Condition

On

System OK; No faults present

Off

Possible control fault; Check power

1 Flash

Low air

2 Flashes

Flame in combustion chamber;
No call for heat

3 Flashes

Ignition lockout

4 Flashes

Low HSI current

5 Flashes

Low 24 VAC

6 Flashes

Internal fault; Replace control
Table U: Ignition Module
Diagnostic LED Flash Codes

High Limit—Manual Reset

Ignition Module

This heater is equipped with a fixed setting manual reset high limit temperature device as standard or it may
have an optional adjustable setting manual reset high
temperature device.

When additional heat is needed, the combustion air
blower starts to purge air from the combustion chamber for 15 seconds. On proof-of-air flow, the
air-proving switch closes and the igniter is energized.
To ensure safe operation, the gas valve cannot open
until the igniter is verified. The main burner is automatically lit when the device is powered and pre-purged.
The heater performs its own safety check and opens
the main valve only after the igniter is proven to be
capable of ignition. The standard ignition module will
attempt to light three times before locking out. To reset
it, turn off power to the heater, wait 30 seconds and reapply power.

Fig. 38: Ignition Module

Code

The fixed setting manual reset high limit is located on
the In/Out header of the heat exchanger on the right
side of the heater (accessible through the front door
for reset as necessary).

The optional adjustable manual reset high limit is located inside the heater junction box. Push the reset
button and adjust the setting to approx. 40°F (20°C)
above desired outlet temperature.

37

Fig. 39: High Limit (Manual Reset)

High Limit—Auto Reset (Optional)

Modulating Temperature Control

This heater may be equipped with an optional adjustable auto reset high limit temperature device.

This heater is equipped with a Raypak modulating
temperature control. Refer to information starting on
page 30 for information on the setting and use of this
control.

The optional adjustable auto reset high limit is located
inside the heater junction box. Adjust the setting to
approx. 20°F (10°C) above desired outlet temperature.

Fig. 42: Modulating Temperature Control

Low Water Cut-Off (Optional)

The optional low water cut-off automatically shuts
down the burner whenever water level drops below the
level of the sensing probe. A 5-second time delay prevents premature lockout due to temporary conditions
such as power fluctuations or air pockets.

Fig. 40: Adjustable High Limit (Auto Reset)

Flow Switch

This standard, dual-purpose control, mounted and
wired in series with the main gas valve, shuts off
heater in case of pump failure or low water flow.

Fig. 43: Low Water Cut-Off

High & Low Gas Pressure Switches
(Optional)
Fig. 41: Flow Switch

38

The optional low gas pressure switch connection
mounts upstream of the gas valve (on the inlet flange
to the gas valve) and is accessible through the removable access panels on the rear of the heater to reset
the gas pressure switch, as necessary. It is used to
ensure that sufficient gas pressure is present for prop-

Blocked Vent Switch

er valve/regulator performance. The low gas pressure
switch automatically shuts down the heater if gas supply drops below the factory setting of 3.0 in. WC for
natural gas or propane gas.

This heater is equipped with a blocked vent pressure
switch to prevent the operation of the heater when too
much of the vent is blocked. This switch is located on
the right side of the heater near the right rear corner.

The optional high gas pressure switch connection
mounts down-stream of the gas valve. Special ports
are located on the backside of the gas valve and
accessible from the front of the heater (to reset the gas
pressure switch) or through the removable access
panels on the rear of the heater (to reset the gas pressure switch), as necessary. If the gas pressure
regulator in the valve fails, the high gas pressure
switch automatically shuts down the burner.
Operation of either the High or Low Gas Pressure
Switch will turn on an LED inside the switch housing.
Push the top of the plastic switch housing as shown in
Fig. 44 to reset a tripped pressure switch. The white
LED will go out when the switch is reset.

Fig. 46: Blocked Vent Switch

UDB Diagnostic Board

This heater is equipped with a diagnostic board which
will indicate faults as they occur. Refer to the Troubleshooting section for instructions on accessing,
reviewing and clearing these faults.

Fig. 44: High/Low Gas Pressure Switch

Air Pressure Switch

This heater is equipped with an air pressure switch to
prove the operation of the blower before allowing the
ignition control to begin a Call for Heat. It is located on
the right side of the lower flange of the blower mounting assembly, directly behind the junction box.

Fig. 47: UDB Diagnostic Board

Fig. 45: Air Pressure Switch

NOTE: The wiring diagrams in this manual show all
standard options. Refer to the large wiring diagram
provided with your heater for options installed on
your specific unit(s).
39

WIRING DIAGRAM -

Models H & WH

40

WIRING DIAGRAM - Models P & WHP

41

START-UP

BEFORE OPERATING, smell all around the appliance
area for gas. Be sure to smell near the floor because
some gas is heavier than air and will settle on the floor.

NOTE: The following steps must be performed by a
factory-trained technician.

WHAT TO DO IF YOU SMELL GAS:

Pre Start-up

•
•

Filling System (Heating Boilers)

•

Fill system with water. Purge all air from the system.
Lower system pressure. Open valves for normal system operation, and fill system through feed pressure.
Manually open air vent on the compression tank until
water appears, then close vent.

•

•

Air Purge (Domestic Hot Water
Heaters)

•

Purge all air from system before heater operation. This
can be normally accomplished by opening a downstream valve.

Raypak offers an optional air vent valve for the MVB
heaters which can be installed directly into the inlet
side of the header to ensure that air is purged from the
system. This option also includes an adapter to allow
the air vent to be piped (in the field) to a suitable drain
as re-quired by the jurisdiction having authority.

•

Do not try to light any appliance.
Do not touch any electrical switch; do not use any
telephone in your building.
Immediately call your gas supplier from a neighbor’s telephone. Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call the fire
department.
Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not turn
by hand, do not try to repair it, call a qualified service technician. Forced or attempted repair may
result in a fire or explosion.
Do not use this appliance if any part has been
under water, immediately call a qualified service
technician to inspect the appliance and to replace
any part of the control system and any gas control
which has been under water.
Check around unit for debris and remove combustible products, i.e. gasoline, etc.

Pre Start-up Check

1. Verify the heater is filled with water.
2. Check system piping for leaks. If found, repair
immediately.
3. Vent air from system. Air in system can interfere
with water circulation.
4. Purge air from gas line to heater.

CAUTION: An air vent valve should be installed at
the highest point in the system for proper operation.
If water piping is located higher than the header, the
air vent valve should be relocated to the highest
point in the installed system.

Initial Start-up

Venting System Inspection

Required tools

1. Check all vent pipe connections and flue pipe material.

•
•
•
•
•
•

2. Make sure vent terminations are installed per code
and are clear of all debris or blockage.

For Your Safety

WARNING: If you do not follow these instructions
exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.

(1) 12-0-12 (24” scale) U-tube manometer
(2) 6-0-6 (12” scale) U-tube manometer
Screwdrivers (assorted sizes and shapes)
(1) Crescent wrench (8” or 10”)
(1) Multi-meter
(1) Amp probe

(Metric Allen wrenches will be required for servicing
the gas valve, but not during start-up)
NOTE: Digital manometers are not recommended.

This appliance has a hot surface igniter. It is equipped
with an ignition device which automatically lights the
burners. Do not try to light the burners by hand.

Preparation

WARNING: Do not turn on gas at this time.

42

Check Power Supply

3. If the gas pressure is greater than 14.0 in. WC,
turn off the main gas shut-off valve, upstream of
the heater.

With multi-meter at incoming power, check voltage
between:

Start-Up

Hot - Common (≈120 VAC)

NOTE: The values in Tables V, W and X represent
the conditions when the heater is at full firing rate at
sea level.

Hot - Ground (≈120 VAC)

Common - Ground (< 1 VAC)

NOTE: Pressure and combustion data are provided
with the heater.

WARNING: If Common - Ground is > 1 VAC,
STOP: Contact electrician to correct ground failure.
Failure to do this may burn out 120V-24V
transformer, or may cause other safety control
damage or failure.

1. Turn power on.

2. Turn on the heater, wait approximately 15 seconds
after the blower starts, and the igniter should start
to glow (observable through the observation port
located at the front, bottom of the heater). Look
into the sight glass located at the bottom of the
front panel to check igniter operation. Gas valve
should open in 45-60 seconds.

Attach Manometers to Measure Pressures

1. Turn off main gas valve.

2. Attach (1) 12” scale manometer to an upstream
bleedle valve on the gas supply pipe to the heater
(Measure point “A” in Fig. 48).

3. The heater ignites at 50% of full rate (as indicated
on the LCD display of the temperature control
located in the upper right of the front panel).

3. Attach (1) 24” scale manometer to the manifold
pressure tap located on the elbow downstream of
the valve (Measure point “D” in Fig. 48).

4. If the burner fails to light on the first trial, it will try
for ignition up to three times before going into lockout with the standard ignition module. If the heater
is equipped with the optional single-try ignition
module, it will go into lockout.

4. Attach (1) 12” scale manometer near the fan-proving switch. Pull black cap from air pressure switch
tee and connect the manometer. NOTE: Retain
caps for reinstallation later.

5. Wait until the controller indicates 100% on the firing rate display screen (approximately 30
seconds).

Blower Check

1. Check blower suction using the manometer
attached to the fan pressure switch tee, with the
heater firing at 100% input. The reading should be
as noted in Table V for both natural and propane
gas.

TO BURNER
GAS

A

B
C

D

Fig. 48: Gas Pressure Measurement Locations

2. FOR REFERENCE ONLY: Measure the blower
amp draw with the heater firing at 100% input and
compare the measured value to the values in
Table U. The amp draw is measured with a clampon type amp probe clamped to the 14 AWG black
power wire going into the blower.

Check Gas Supply Pressure

1. Slowly turn on main gas shut-off valve.

2. Read the gas supply pressure from the manometer; minimum supply pressure for natural gas is 4.0
in. WC, recommended supply is 7.0 in. WC, minimum supply pressure for propane gas is 4.0 in.
WC, recommended supply is 11.0 in. WC (dynamic readings, full fire input).

43

3. When firing at 100%, the desired heater combustion CO2 is between 8.5 and 9.0% for natural gas
and 9.5 and 10.0% for propane with CO less than
100 ppm. If this combustion cannot be achieved

with the blower suction within the tolerances specified in Table T, contact the factory. The reference
amp draw reading may help to indicate if there is
a problem with the system or if blower adjustment
is required.

CAUTION: Special manifold and air settings may
be required.

Finishing

NOTE: Most commercially available amp probes
are not accurate enough and/or are not shielded well
enough to read accurately in the heater
environment. Blower amp draw readings are for
reference only.

1. Record all data on the “Start-up Checklist” located
at the back of this manual.

2. Disconnect the manometers and reconnect the
cap on the fan pressure switch tee and reinsert the
sealing screws into the bleedle valves.

Manifold Check

3. Start-up is complete and the heater should be
operating properly.

1. Check manifold gas pressure at the gas valve outlet pressure tap (connection “D” in Fig. 48). This
pressure should read per the values in Table X for
natural and propane gas.

Safety Inspection

1. Check all thermostats and high limit settings.

2. During the following safety checks leave manometers hooked up, check and record.

2. If the pressure reading differs by more than ± 0.2
in. WC, STOP – Call the factory for directions
on what to do next!
504
754
1104
1504
2004

Air Pressure
Setting (in. WC)
-2.3
-2.9
-4.0
-4.0
-4.1

Model No.

Amp Draw

Model No.

3. If other gas-fired appliances in the room are on the
same gas main, check all pressures on the MVB
with all other equipment running.

Setting
Tolerance
± 0.2 in. WC
± 0.2 in. WC
± 0.2 in. WC
± 0.2 in. WC
± 0.2 in. WC

4. Check thermostats for ON-OFF operation.
5. Check high limits for ON-OFF operation.

6. While in operation, check flow switch operation.

7. Check the low gas pressure switch (if provided).
(For proper adjustment, use the attached
manometers, if available, to set pressure. The
scales on the switch are approximate only.) Low
gas pressure switch (if provided) must be set at
3.0 in. WC for natural gas and propane gas.

Table V: MVB Air Pressure Settings

504
754
1104
1504
2004

1.9
2.9
5.5
8.1
13.0

Setting
Tolerance
+0.0/-0.2
+0.0/-0.2
+0.0/-0.2
+0.0/-0.2
+0.0/-0.5

8. Make sure that the high gas pressure switch (optional) is set to 3.0 in. WC for both natural gas and
propane gas.

Table W: MVB Amp Draw (Reference Only)

Model No.
504
754

1104

1504
2004

Follow-Up

Manifold Gas Pressure Setting
High Fire Values (in. WC)
Natural Gas
Propane Gas
-0.1

-0.1

-1.0

-0.2

-0.4
-2.4
-1.0

Safety checks must be recorded as performed.
Turn heater on. After main burner ignition:
1. Check manometer for proper readings.

-0.1

2. Cycle heater several times and re-check readings.

-0.6

3. Remove all manometers and replace caps and
screws.

-0.5

Table X: MVB Manifold Pressure Settings

44

4. Check for gas leaks one more time.

Leak Test Procedure: Dual-Seat Gas
Valve

7. After no leakage has been verified at all valve
seats and test valves, open downstream leak test
valve and restore electrical power to the heater.

Proper leak testing requires three pressure test points
in the gas train.

Remove the access panel on the rear of the heater to
access the gas valve for this test. Test point A is a bleedle valve located upstream of the combination gas
valve on the supply manifold.
Test point B is a bleedle valve located between the two
automatic gas valve seats.

Test point C is a bleedle valve located downstream of
both automatic gas valve seats and upstream of the
manual valve. Refer to Fig. 49.
These tests are to be conducted with the electrical
power to the heater turned OFF.
1. Manually close the downstream leak test valve.

2. Open the bleedle valve at test point A and connect
a manometer to it. Verify that there is gas pressure
and that it is within the proper range (NOTE: must
not exceed 14.0 in. WC).

TO BURNER
GAS

A

B
C

3. Open test point B and connect a rubber tube to it.
Connect the other end of the tube to a manometer
and look for a build-up of pressure. Increasing
pressure indicates a leaking gas valve which must
be replaced.

D

Fig. 49: Leak Test Procedure

Post Start-Up Check

Check off steps as completed:

4. Next, close the upstream manual gas valve (field
supplied) and remove the manometers from the
bleedle valves in test point A and test point B.
Connect a rubber tube from the test point A bleedle valve to the test point B bleedle valve and
open the upstream manual gas valve. Make sure
that test point A & B bleedle valves have been
opened so as to allow gas to flow. This will bring
gas pressure to the second valve seat.

1.

2.
3.

5. Open the bleedle valve at test point C and connect
a second rubber tube to it. Connect the other end
of the tube to a manometer and look for a build-up
of pressure. Increasing pressure indicates a leaking gas valve which must be replaced.

4.
5.

6. Remove rubber tube and manometers. Close
each test point bleedle valve as the tubes are
removed.

6.

7.
45

Verify that the heater and heat distribution units or
storage tank are filled with water.

Confirm that the automatic air vent (if used) was
opened two full turns during the venting procedure.
Verify that air has been purged from the system.

Verify that air has been purged from the gas piping, and that the piping has been checked for
leaks.
Confirm that the proper start-up procedures were
followed.
Inspect burner to verify flame.

Test safety controls: If heater is equipped with a
low water cut-off or additional safety controls, test

8.

9.

OPERATION

for operation as outlined by manufacturer. Burner
should be operating and should go off when controls are tested. When safety devices are restored,
burners should re-ignite after pre-purge time
delay.

Lighting Instructions

1. Before operation, make sure you have read all of
the safety information in this manual.

Test limit control: While burner is operating, move
indicator on high limit control below actual water
temperature. Burner should go off while blower
and circulator continue to operate. Raise setting
on limit control above water temperature and
burner should re-ignite after pre-purge time delay.
NOTE: Ignition control may have to be reset
after this portion of the test.

2. Remove upper front panel.

3. Set the thermostat to the lowest setting.

4. Turn off all electrical power to the appliance.

5. This appliance is equipped with an ignition device
which automatically lights the burner. Do not try to
light the burner by hand.

Test ignition system safety device:

a.

Open manual gas valve. Turn power on.

c.

When the heater is in operation, pull hose off
the air switch. The burner should go off almost
immediately.

b.

d.

6. Turn on main manual gas valve field installed near
gas inlet connection on back of heater.

Set thermostat to call for heat.

7. Wait 5 minutes to clear out any gas. Then smell for
gas, especially near the floor. If you then smell
gas, STOP! Follow the steps in the safety information on the front cover of this manual. If you do not
smell gas, go to next step.

Reattach hoses. Burner should re-ignite after
pre-purge time delay. NOTE: Ignition control
may have to be reset after this portion of
the test.

8. Turn on all electrical power to the appliance.

9. Set thermostat to desired setting. The appliance
will operate. The igniter will glow after the prepurge time delay (15 seconds). After igniter
reaches temperature (30 seconds) the main valve
should open. System will try for ignition up to three
times (one time on optional single-try ignition module). If flame is not sensed, lockout will
commence.

10. To restart system, follow lighting instructions in the
Operation section.

11. Check to see that the high limit control is set
above the design temperature requirements of the
system. For multiple zones: Check to make sure
the flow is adjusted as required in each zone.

12. Check that the heater is cycled with the thermostat. Raise the setting on the thermostat to the
highest setting and verify that the heater goes
through the normal start-up cycle. Reduce to the
lowest setting and verify that the heater goes off.

10. If the appliance will not operate, follow the instructions “To Turn Off Gas To Appliance,” and call your
service technician or gas supplier.
11. Replace upper front panel.

13. Observe several operating cycles for proper operation.

12. If heater fails to start, verify the following:

a. There are no loose connections or that the
service switch is off.

14. Set the heater thermostat to desired temperature.

15. Review all instructions shipped with this heater
with owner or maintenance person, return to envelope and give to owner or place the instructions
inside front panel on heater.

b. High temperature limit switch is set above water temperature or manual reset high limit is
not tripped.
c.

46

Thermostat is set above water temperature.

UDB Fault History

d. Gas is on at the meter and the heater.
e. Incoming dynamic gas pressure to the gas
valve is NOT less than 4.0 in. WC for natural
gas or propane gas.

To view the fault codes in the UDB history file:

1. Press the UP or DOWN buttons on the membrane
switch for 2 seconds to access the fault history.

To Turn Off Gas To Appliance

2. Press either button to scroll through the recorded
faults in history.

1. Shut off manual gas valve field installed near gas
inlet connection on back of heater.

3. The most recent fault recorded will be the first fault
displayed (the last 16 faults are stored in the history, on a rolling basis). There is no time or date
stamp associated with these faults.

2. Remove upper front panel.

3. Set the thermostat to lowest setting.

4. Turn off all electrical power to the appliance if service is to be performed.

4. When the history of faults has been exhausted,
pushing the UP or DOWN buttons again will roll
the fault history over and it will start again.

5. Replace access panel.

5. To exit the fault history, wait for 10 seconds and
the board will automatically exit the history mode.

To clear the fault history, press and hold both the UP
and DOWN buttons for 5 seconds while the power is
on.
NOTE: Once the history has been cleared, it cannot
be recovered.
Diagnostic information is provided any time a fault is
recorded. This information is intended to assist in
locating the problem with the heater, but is not exhaustive.
If multiple fault conditions occur at the same time, only
the fault that caused the heater to shut down will be
recorded in the history.

47

TROUBLESHOOTING
Step 1

Does the power switch provide
power to the control panel?

Check the switch and/or
line voltage

NO

Is there a Call For
Heat?

YES

NO

Unit is in standby mode.

YES

Step 2

NO

Is Disable connection intact?

Reattach.

YES

Step 3

Does the combustion air
blower come on?

Is there 120VAC at the blower or
blower relay?

NO

Check and correct power
connections at main terminal
block, circuit breaker panel or
blower relay.

NO

YES
Is 4-20mA present at the quick
disconnects on the black and blue
wires of the temperature controller?
YES

YES

Is 24VAC at the NC side of
the air pressure switch?

Correct Safety

Is there continuity in the wire
between F2 and Pin J5-6?

NO

Is blower pressure setting
(vacuum) correct?

NO

NO

Replace air pressure switch.

Is 24VAC at PS on ignition module?
Is connecting plug secure?

Correct wiring.

NO

YES

Step 6

Does igniter prove?

NO

YES

Is Amp draw during heatup for HSI greater than
3.1 Amps?

YES

NO

Is air switch bouncing?

Replace HSI

NO
YES

Step 7

Is the flame sensor signal to the
ignition module greater than 1 uA DC?

Is gas pressure correct?

NO

Step 8

Step 9

Is static and dynamic inlet gas
pressure correct?

Is the unit running?
YES
The unit is okay

NO

YES

YES

NO

YES

Call our Technical Service Department

1-805-278-5300

48

NO

Repair or
Replace wire.

Correct the shutter
setting or blower
amp draw.

NO

YES

YES

Step 5

Replace temperature
controller.

NO

YES

Does F2 on ignition module
have AC power?

Step 4

Is diagnostic board
indicating open
safeties?

NO

Correct the gas pressure.

MAINTENANCE

by local codes.

3. Check that area is free from combustible materials, gasoline, and other flammable vapors and
liquids.

Suggested Minimum
Maintenance Schedule

4. Check air filter and replace as necessary.

Regular service by a qualified service agency and
maintenance must be performed to ensure maximum
operating efficiency.

5. Follow pre-start-up check in the Start-up section.

6. Visually inspect burner flame. It should be light
blue at full input. Remove and visually inspect hot
surface igniter and sensor for damage, cracking or
debris build-up.

Maintenance as outlined below may be performed by
the owner.

Daily

7. Check operation of safety devices. Refer to manufacturers’ instructions.

1. Check that the area where the heater is installed
is free from combustible materials, gasoline, and
other flammable vapors and liquids.

8. Follow oil-lubricating instructions on pump (if required). Over-oiling will damage pump.
Water-lubricated circulators do not need oiling.

2. Check for and remove any obstruction to the flow
of combustion or ventilation air to heater.

9. To avoid potential of severe burn, DO NOT REST
HANDS ON OR GRASP PIPES. Use a light touch;
return piping will heat up quickly.

Monthly

1. Check for piping leaks around pumps, mixing
valves, relief valves, and other fittings. If found,
repair at once. DO NOT use petroleum-based
stop-leak compounds.

10. Check blower and blower motor.

11. Check for piping leaks around pumps, relief valves
and other fittings. Repair, if found. DO NOT use
petroleum-based stop-leak.

2. Visually inspect burner flame.

3. Visually inspect venting system for proper function, deterioration or leakage.

Periodically

1. Check relief valve. Refer to manufacturer’s
instructions on valve.

4. Visually inspect for proper operation of the condensate drain in the venting. If leaks are observed
repair at once.

2. Test low water cut-off (if equipped). Refer to manufacturer’s instructions.

5. Check air vents for leakage.

Preventive Maintenance
Schedule

Yearly (Beginning Of Each Heating
Season)

The following procedures are recommended and are
good practice for all MVB installations.

Schedule annual service call by qualified service
agency.

Daily

1. Visually check top of vent for soot. Call service
person to clean. Some sediment at bottom of vent
is normal.

2. Visually inspect venting system for proper function, deterioration or leakage. Ensure that
condensate drain is inspected and ensure that
condensate is being directed to appropriate condensate management system or drain, as required

1. Check gauges, monitors and indicators.

2. Check instrument and equipment settings. (See
“Post Start-Up Check” on page 45.)

49

3. Check burner flame. (Should see light blue flame
at full input rate).

Weekly

6. Perform leakage test on gas valves (See Fig. 49.)
and procedure on page 45.

For low-pressure heaters, test low-water cut-off
device. (With heater in pre-purge, depress the low
water cut-off test button. Appliance should shut-off
and ignition fault light should come on. Depress reset
button on front of heater control panel to reset).

7. Test air switch in accordance with manufacturer’s
instructions. (Turn panel switch to the “On” position until blower is proven, then turn the switch to
“Off.”
8. Inspect and clean burner using shop air.

Monthly

1. Check flue, vent, stack, or outlet dampers.

As Required

3. Test high and low gas pressure interlocks (if
equipped). (See “Safety Inspection” on page 44.)

2. Check drip leg and gas strainers.

1. Recalibrate all indicating and recording gauges.

4. Check igniter. (Resistance reading should be 4270 ohms at ambient temperature).

1. Recondition or replace low water cut-off device (if
equipped).

2. Test blower air pressure. (See “Blower Check” on
page 43.)

3. Check flame failure detection system. (See “Post
Start-Up Check,” page 45.)

Semi-Annually

2. Check flame failure detection system components.

5. Check flame signal strength. (Flame signal should
be greater than 1 microampere as measured at
the 2 pins on the upper left corner of the ignition
control).

3. Check firing rate control by checking the manifold
pressure. (See “Manifold Check” on page 44.)

4. Check piping and wiring of all interlocks and shutoff valves.

6. Check firing rate control by checking the manifold
pressure. (See “Manifold Check” on page 44).

5. Check air filter and replace as necessary.

Annually

7. Test safety/safety relief valves in accordance with
ASME Heater and Pressure Vessel Code Section
IV.

2. Test high limit and operating temperature. (See
“Post Start-Up Check,” page 45.)

Filter Maintenance

4. Conduct a combustion test at full fire. Carbon dioxide should be 8.5 to 9.0% at full fire for natural gas,
and between 9.5 to 10.0% for propane gas.
Carbon monoxide should be < 100 ppm.

•

1. Test flame failure detection system and pilot turndown.

NOTE: Use Raypak replacement filters, kit number
012552F (12”X12”) for models 504-1104 and kit
number 012553F (16”X16”) for models 1504-2004.

3. Check flame sensor.

•

5. Check valve coil for 60 cycle hum or buzz. Check
for leaks at all valve fittings using a soapy water
solution (while heater is operating). Test other
operating parts of all safety shut-off and control
valves and increase or decrease settings
(depending on the type of control) until the safety
circuit opens. Reset to original setting after each
device is tested.

50

Inspect quarterly

Replace when tracking pressure exceeds -0.5 in.
WC at 100% fan speed, except for models 1104
and 2004, which need to be replaced when tracking pressure exceeds -0.7 in. WC at 100% fan
speed.

Filter Replacement

stainless steel, which is commonly used in high efficiency systems. The heater can be supplied with
corrosion-resistant, non-metallic intake air vent material. You may, however, choose to use outside
combustion air for one or more of these reasons:

1. Remove the filter box cover by loosening and
removing the two wing nuts holding it in place.

1. Installation is in an area containing contaminants
listed below which will induce acidic condensation.
2. You want to reduce infiltration into your building
through openings around windows and doors.

3. You are using AL29-4C stainless steel vent pipe,
which is more corrosion-resistant than standard
metallic vent pipe. In extremely contaminated areas, this may also experience deterioration.
Products causing contaminated combustion air:
•
•
•
•
•
•
•
•
•
•
•
•

Fig. 50: Remove the Air Filter Box Cover

2. Remove the filter by lifting it straight up and out of
the slot in the filter box.

•
•

spray cans containing chloro/fluorocarbons
permanent wave solutions
chlorinated waxes/cleaners
chlorine-based swimming pool chemicals
calcium chloride used for thawing
sodium chloride used for water softening
refrigerant leaks
paint or varnish removers
hydrochloric acid/muriatic acid
cements and glues
antistatic fabric softeners used in clothes dryers
chloride-type bleaches, detergents, and cleaning
solvents found in household laundry rooms
adhesives used to fasten building products
similar products

•
•
•
•
•
•
•
•
•
•
•

dry cleaning/laundry areas
metal fabrication plants
beauty shops
refrigeration repair shops
photo processing plants
auto body shops
plastic manufacturing plants
furniture refinishing areas and establishments
new building construction
remodeling areas
open pit skimmers

•
•

remove products permanently, OR
install TruSeal direct vent.

Areas where contaminated combustion air commonly
exists:

Fig. 51: Remove the Air Filter

3. Reverse steps 1 and 2 to install the new filter. Use
Raypak replacement filters, kit number 012552F
(12”X12”) for models 504-1104 and kit number
012553F (16”X16”) for models 1504-2004.

APPENDIX

Inside Air Contamination

Check for areas and products listed above before installing heater. If found:

All heaters experience some condensation during
start-up. The condensate from flue gas is acidic.
Combustion air can be contaminated by certain vapors
in the air which raise the acidity of the condensate.
Higher acidity levels attack many materials including
51

Important Instructions for the Commonwealth of Massachusetts

The Commonwealth of Massachusetts requires compliance
with regulation 248 CMR 4.00 and 5.00 for installation of
through – the – wall vented gas appliances as follows:

(b) EXEMPTIONS: The following equipment is exempt from
248 CMR 5.08(2)(a)1 through 4:

1. The equipment listed in Chapter 10 entitled "Equipment
Not Required To Be Vented" in the most current edition of
NFPA 54 as adopted by the Board; and

(a) For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7) feet
above finished grade in the area of the venting, including but
not limited to decks and porches, the following requirements
shall be satisfied:

2. Product Approved side wall horizontally vented gas fueled
equipment installed in a room or structure separate from the
dwelling, building or structure used in whole or in part for residential purposes.

(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the
manufacturer of Product Approved side wall horizontally
vented gas equipment provides a venting system design or
venting system components with the equipment, the instructions provided by the manufacturer for installation of the
equipment and the venting system shall include:

1. INSTALLATION OF CARBON MONOXIDE DETECTORS.
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gasfitter shall
observe that a hard wired carbon monoxide detector with an
alarm and battery back-up is installed on the floor level
where the gas equipment is to be installed. In addition, the
installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an
alarm is installed on each additional level of the dwelling,
building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the
property owner to secure the services of qualified licensed
professionals for the installation of hard wired carbon
monoxide detectors

1. Detailed instructions for the installation of the venting system design or the venting system components; and

2. A complete parts list for the venting system design or venting system.

(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the
manufacturer of a Product Approved side wall horizontally
vented gas fueled equipment does not provide the parts for
venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the
manufacturer:

a. In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an attic, the
hard wired carbon monoxide detector with alarm and battery
back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the owner
shall have a period of thirty (30) days to comply with the
above requirements; provided, however, that during said
thirty (30) day period, a battery operated carbon monoxide
detector with an alarm shall be installed.

1. The referenced "special venting system" instructions shall
be included with the appliance or equipment installation
instructions; and
2. The "special venting systems" shall be Product Approved
by the Board, and the instructions for that system shall
include a parts list and detailed installation instructions.

2. APPROVED CARBON MONOXIDE DETECTORS. Each
carbon monoxide detector as required in accordance with
the above provisions shall comply with NFPA 720 and be
ANSI/UL 2034 listed and IAS certified.

(e) A copy of all installation instructions for all Product
Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting
instructions, and/or all venting design instructions shall
remain with the appliance or equipment at the completion of
the installation.

3. SIGNAGE. A metal or plastic identification plate shall be
permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with
the exhaust vent terminal for the horizontally vented gas
fueled heating appliance or equipment. The sign shall read,
in print size no less than one-half (1/2) inch in size, "GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".

GAS PRESSURE SUPERVISION

The Commonwealth of Massachusetts requires listed high
and low gas pressure switches (manual reset) for any model
with a maximum firing input greater than 1,000,000 Btu/Hr in
accordance with 248 CMR 7.04(11)(d).

4. INSPECTION. The state or local gas inspector of the side
wall horizontally vented gas fueled equipment shall not
approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage
installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.

A gas pressure regulator (field supplied) is required in the
gas train ahead of the heater, for heaters having input rates
greater than 1,000,000 Btu/Hr, in accordance with 248 CMR
7.04 Figure 3B requirements.

52

LIMITED PARTS WARRANTY
MVB – TYPES H AND WH
MODELS 504-2004
SCOPE
Raypak, Inc. (“Raypak”) warrants to the original owner that all parts of this heater which are actually manufactured by Raypak will be free
from failure under normal use and service for the specified warranty periods and subject to the conditions set forth in this Warranty. Labor
charges and other costs for parts removal or reinstallation, shipping and transportation are not covered by this Warranty but are the
owner’s responsibility.

HEAT EXCHANGER WARRANTY
Domestic Hot Water
Five (5) years from date of heater installation. Includes copper heat exchanger with bronze waterways.
Ten (10) years from date of heater installation. Includes only cupro-nickel heat exchanger with bronze waterways.
Space Heating (Closed Loop System)
Ten (10) years from date of heater installation. Includes both cupro-nickel and copper heat exchanger with bronze water-ways.
Thermal Shock Warranty
Twenty (20) years from date of heater installation against “Thermal Shock” (excluded, however, if caused by heater operation at large
changes exceeding 150°F between the water temperature at intake and heater temperature, or operating at heater temperatures exceeding 230°F).

ANY OTHER PART MANUFACTURED BY RAYPAK
One (1) year warranty from date of heater installation, or eighteen (18) months from date of factory shipment based on Raypak’s records,
whichever comes first.
SATISFACTORY PROOF OF INSTALLATION DATE, SUCH AS INSTALLER INVOICE, IS REQUIRED. THIS WARRANTY WILL BE
VOID IF THE HEATER RATING PLATE IS ALTERED OR REMOVED.

ADDITIONAL WARRANTY EXCLUSIONS
This warranty does not cover failures or malfunctions resulting from:
1. Failure to properly install, operate or maintain the heater in accordance with our printed instructions provided;
2. Abuse, alteration, accident, fire, flood and the like;
3. Sediment or lime build-up, freezing, or other conditions causing inadequate water circulation;
4. High velocity flow exceeding heater design rates;
5. Failure of connected systems devices, such as pump or controller;
6. Use of non-factory authorized accessories or other components in conjunction with the heater system;
7. Failing to eliminate air from, or replenish water in, the connected water system;
8. Chemical contamination of combustion air or use of chemical additives to water.

PARTS REPLACEMENT
Under this Warranty, Raypak will furnish a replacement for any failed part. The failed part must first be returned to Raypak if requested,
with transportation charges prepaid, and all applicable warranty conditions found satisfied. The replacement part will be warranted for
only the unexpired portion of the original warranty. Raypak makes no warranty whatsoever on parts not manufactured by it, but Raypak
will apply any such warranty as may be provided to it by the parts manufacturer.

TO MAKE WARRANTY CLAIM
Promptly notify the original installer, supplying the model and serial numbers of the unit, date of installation and description of the problem. The installer must then notify his Raypak distributor for instructions regarding the claim. If either is not available, contact Service
Manager, Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 or call (805) 278-5300. In all cases proper authorization must first be
received from Raypak before replacement of any part.

EXCLUSIVE WARRANTY - LIMITATION OF LIABILITY
This is the only warranty given by Raypak. No one is authorized to make any other warranties on Raypak’s behalf. THIS WARRANTY IN
LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. RAYPAK’S SOLE LIABILITY AND THE SOLE REMEDY AGAINST
RAYPAK WITH RESPECT TO DEFECTIVE PARTS SHALL BE AS PROVIDED IN THIS WARRANTY. IT IS AGREED THAT RAYPAK
SHALL HAVE NO LIABILITY, WHETHER UNDER THIS WARRANTY, OR IN CONTRACT, TORT, NEGLIGENCE OR OTHERWISE,
FOR ANY SPECIAL, CONSEQUENTIAL, OR INCIDENTAL DAMAGE, INCLUDING DAMAGE FROM WATER LEAKAGE. Some states
do not allow limitations on how long an implied warranty lasts, or for the exclusion of incidental or consequential damages. So the above
limitation or exclusion may not apply to you.
This Limited Warranty gives you specific legal rights. You may also have other rights which may vary from state to state. We suggest that
you complete the information below and retain this certificate in the event warranty service is needed. Reasonable proof of the effective
date of the warranty (date of installation) must be presented, otherwise, the effective date will be based on the rate of manufacture plus
thirty (30) days.
Original Owner

Model Number

Mailing Address

Serial Number
Date of Installation

City

State

Daytime Telephone Number
RAYPAK, INC

Zip Code

Installation Site
Contractor/Installer

2151 Eastman Avenue Oxnard, CA 93030-9786

(805) 278-5300

53

Fax (800) 872-9725

www.raypak.com

LIMITED PARTS WARRANTY
MVB – TYPES P & WHP
MODELS 504–2004
SCOPE
Raypak, Inc. (“Raypak”) warrants to the original owner that all parts of this heater which are actually manufactured by Raypak will be free
from failure under normal use and service for the specified warranty periods and subject to the conditions set forth in this Warranty. Labor
charges and other costs for parts removal or reinstallation, shipping and transportation are not covered by this Warranty but are the
owner’s responsibility.

HEAT EXCHANGER WARRANTY
Five (5) years from date of heater installation. Includes cupo-nickel heat exchanger with bronze and cast iron waterways.
Thermal Shock Warranty
Twenty (20) years from date of heater installation against “Thermal Shock” (excluded, however, if caused by heater operation at large
changes exceeding 150°F between the water temperature at intake and heater temperature, or operating at heater temperatures exceeding 230°F).

ANY OTHER PART MANUFACTURED BY RAYPAK
One (1) Year warranty from date of heater installation, or eighteen (18) months from date of factory shipment based on Raypak’s records,
whichever comes first.
SATISFACTORY PROOF OF INSTALLATION DATE, SUCH AS INSTALLER INVOICE, IS REQUIRED. THIS WARRANTY WILL BE
VOID IF THE HEATER RATING PLATE IS ALTERED OR REMOVED.

ADDITIONAL WARRANTY EXCLUSIONS
This warranty does not cover failures or malfunctions resulting from:
1. Failure to properly install, operate or maintain the heater in accordance with our printed instructions provided;
2. Abuse, alteration, accident, fire, flood and the like;
3. Sediment or lime build-up, freezing, or other conditions causing inadequate water circulation;
4. High velocity flow exceeding heater design rates;
5. Failure of connected systems devices, such as pump or controller;
6. Use of non-factory authorized accessories or other components in conjunction with the heater system;
7. Chemical contamination of combustion air or use of chemical additives to water.
8. Misuse or neglect, including but not limited to freeze-ups, operating the heater with cabinet door off, having flow restrictions or obstructions between the heater outlet and pool/spa or not maintaining proper chemical balance (pH level must be between 7.2 and 7.8 and
total alkalinity between 100 and 150 PPM. Total Dissolved Solids (TDS) must be no greater than 2500 PPM).

PARTS REPLACEMENT
Under this Warranty, Raypak will furnish a replacement for any failed part. The failed part must first be returned to Raypak if requested,
with transportation charges prepaid, and all applicable warranty conditions found satisfied. The replacement part will be warranted for
only the unexpired portion of the original warranty. Raypak makes no warranty whatsoever on parts not manufactured by it, but Raypak
will apply any such warranty as may be provided to it by the parts manufacturer.

TO MAKE WARRANTY CLAIM
Promptly notify the original installer, supplying the model and serial numbers of the unit, date of installation and description of the problem. The installer must then notify his Raypak distributor for instructions regarding the claim. If either is not available, contact Service
Manager, Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 or call (805) 278-5300. In all cases proper authorization must first be
received from Raypak before replacement of any part.

EXCLUSIVE WARRANTY - LIMITATION OF LIABILITY
This is the only warranty given by Raypak. No one is authorized to make any other warranties on Raypak’s behalf. THIS WARRANTY IN
LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. RAYPAK’S SOLE LIABILITY AND THE SOLE REMEDY AGAINST
RAYPAK WITH RESPECT TO DEFECTIVE PARTS SHALL BE AS PROVIDED IN THIS WARRANTY. IT IS AGREED THAT RAYPAK
SHALL HAVE NO LIABILITY, WHETHER UNDER THIS WARRANTY, OR IN CONTRACT, TORT, NEGLIGENCE OR OTHERWISE,
FOR ANY SPECIAL, CONSEQUENTIAL, OR INCIDENTAL DAMAGE, INCLUDING DAMAGE FROM WATER LEAKAGE. Some states
do not allow limitations on how long an implied warranty lasts, or for the exclusion of incidental or consequential damages. So the above
limitation or exclusion may not apply to you.
This Limited Warranty gives you specific legal rights. You may also have other rights which may vary from state to state. We suggest that
you complete the information below and retain this certificate in the event warranty service is needed. Reasonable proof of the effective
date of the warranty (date of installation) must be presented, otherwise, the effective date will be based on the rate of manufacture plus
thirty (30) days.

Original Owner

Model Number

Mailing Address

Serial Number
Date of Installation

City

State

Daytime Telephone Number

RAYPAK, INC

Zip Code

Installation Site
Contractor/Installer

2151 Eastman Avenue Oxnard, CA 93030-9786

(805) 278-5300

54

Fax (800) 872-9725

www.raypak.com

START-UP CHECKLIST FOR FAN-ASSISTED
RAYPAK PRODUCTS
This start-up checklist is to be completely filled out by the service technician starting up the Raypak Boiler or Heater
for the first time. All information may be used for warranty purposes and to ensure that the installation is correct.
Additionally this form will be used to record all equipment operation functions and required settings.
GAS SUPPLY DATA
Regulator Model & Size
Gas Line Size (in room)
Length of Gas Line
Low Gas Pressure Setting
High Gas Pressure Setting
Gas Shut-Off Valve Type
( Ball, Lube cock)
Sediment Trap
Port

CLEARANCES
_________ / ______CFH
________________In. NPT
________________Eq Ft
________________In. WC
________________In. WC
________________

_______________In.
_______________In.
_______________In.
_______________In.
_______________In.

ELECTRICAL
________________Y/N
_______Std______Full

VISUAL INSPECTION OF COMPONENTS
Verify inspection was done and condition of components are in
good working order with a “yes”
Wiring Harness
_________________ Y/N
Burner/s (flame)
_________________ Y/N
Refractory (visual)
_________________ Y/N
Remote flame sense
_________________ Y/N
Covers in place for outdoor
_________________ Y/N

VENTING
Vent Size: _____________
Category: _________
Vent Material:
Vent Termination Type:
Combustion Air Openings:
Ventilation air

Front Clearance
Right Side Clearance
Left Side Clearance
Rear Clearance
Overhead Clearance

Stack Height:_______
sketch vent on reverse side ***
__________________
__________________
Low __________ in2
High __________ in2

Voltage Supply (VAC)
Voltage -24 VAC
Voltage Com to Ground
Hot Surface Igniter
Auto High Limit Setting
Manual Reset High Limit Setting
Operating Control Setting

No Load______ Load_____
_______________VAC
_______________VAC
_______________Ohms
_______________deg F
_______________deg F
_______________deg F

Sketch plumbing on reverse side

WATER SUPPLY
Flow Rate in GPM or Delta T
Measure flow rate at full fire
Pump Economaster setting
Low Water Cutoff
Number of Tanks and Size
Plumbing Size
Pump Size: _________(boiler)
Impeller trim____________
Louvers __________________

_______________If Avail
_______________Minutes
_______________Test
Qty____ _______Gallons
_______________
Pump HP: ______
Pump Model___________
Screens________________

EMISSIONS SETTINGS AND TEST INFORMATION
(AT FULL FIRE)

Nominal Factory Recommended Settings

Blower Pressure Setting
Supply Gas Pressure
Verify stable pressure static &
Pilot Gas Pressure
Manifold Gas Pressure

See manual or card tag
See manual or card tag

_________________In. WC
_________________In. WC
dynamic condition
_________________In. WC
_________________In. WC

See manual or card tag
See manual or card tag

The following measurements must be obtained with a Combustion Analyzer.
NOX
_________________PPM
Less than 20 PPM (If required by Certifying Agency)
Free Oxygen
_________________%
See manual
CO
_________________PPM
Less than 150 PPM
CO2
_________________%
See manual
Model Number: ______________________________
*** Note: draw venting with details, such as extractors,
barometric dampers, blast dampers or draft inducers

Serial Number: _______________________________
Site Altitude Above Sea Level __________________Ft.

Job Name _______________________________________________________________________________________
Address _________________________________________________________________________________________
Physical Location of Boiler: Indoors______; Outdoors______; Ground Level______; Roof______; Below Grade______
Mechanical Contractor / Installer _______________________________________________________________________
Date and Time of Start-up _____________Print Name and Signature of Start-up Technician_________________________

Information must be faxed to: (805) 278-5471 in order to ensure warranty consideration

55

Attn: Service Manager

www.raypak.com
Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468
Litho in U.S.A.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Page Count                      : 56
X Press Private                 : %%DocumentProcessColors: Cyan Magenta Yellow Black.%%EndComments
Creator                         : QuarkXPress(R) 7.5
Create Date                     : 2010:05:07 13:36:31
Modify Date                     : 2010:05:07 13:36:31
Producer                        : QuarkXPress(R) 7.5
Title                           : 6000.59 - New RP2100.qxd
EXIF Metadata provided by EXIF.tools

Navigation menu