Resolution RE214 Wireless Smoke Detector User Manual
Resolution Products, Inc. Wireless Smoke Detector
User Manual

I
N
S
T
A
L
L
G
U
I
D
E
I
Smoke Alarm is a fire-protection device 
that alarms when it detects smoke or 
temperatures above 135°F (57°C).
Features
•  UL217 and ULC531 listings
•  Smoke and heat detection
•  5 year warranty
Quick Start Guide 
1.  Remove the mounting plate.
2.  Pull the battery tab.
3.  Restore the mounting plate and 
twist it fully onto the smoke alarm.
Note: Enrollment is possible only 
if the mounting plate is twisted 
onto the smoke alarm.
4.  Enroll Loop 1 of the smoke alarm 
by placing the panel into wireless 
enrollment mode and then hold 
down the smoke’s test button until 
the smoke alarm beeps. Release the 
test button until the sounder stops 
beeping, and then press and hold 
the test button again to enroll.
5.  Remove the mounting plate and 
refer to Sections 2 and 6 for 
positioning and installation.
6.  After mounting plate is installed 
restore the smoke alarm onto the 
mounting plate and fully test the 
smoke alarm per Section 7. 
To replace the battery, detach the 
smoke alarm from its mounting plate 
and replace the batteries. 
Attention  
This manual should be read prior to use and retained for further information.
Verify proper enrollment and operation using your security panel’s installation manual.
Test Smoke Alarm
Pull Battery Tab
Position Smoke Alarm
12 inches
minimum
12 inches
minimum
RE214 Honeywell® Compatible Smoke and Heat Alarm

The Alarm will emit a short beep and flash the 
Yellow LED when it becomes partially depleted. 
Check the date when the Alarm should be 
replaced which is given on the sidewall of the 
Alarm. When electronic self testing indicates 
that the battery is becoming low the Alarm will 
beep and the yellow LED will flash at the same 
time (about every 48 seconds) to warn the 
user. This indicates that the battery or batteries 
must be replaced.
1.2.2. Contaminated chamber
If the Alarm sounds without any apparent 
smoke being present, press the test button to 
silence the Alarm for 10 minutes (as described 
in 1.1.5 above). If the Alarm sounds again 
it may be contaminated. Pressing the test 
button again, within 4 minutes of the Alarm 
re-sounding, will get the Alarm to compensate 
for chamber contamination. This will normally 
resolve the problem.
If the Alarm re-sounds for a third time, the 
Alarm is excessively contaminated and must 
be replaced. If it is not convenient to replace 
it immediately, pressing the test button within 
4 minutes of it going into alarm (for the third 
time) will silence the Alarm for 8 hours – 
however it will give two short beeps (second 
apart) every 10 minutes to remind the user it 
has been disabled. If the contamination clears 
the Alarm will return to normal operation.
(Note: this does not reduce the users fire 
protection, as a Smoke Alarm in continuous 
alarm due to a fault, is useless and must be 
silenced – by taking the Alarm down or as 
described here. This procedure has the added 
Indicator Summary
Normal Operation Action Red LED Yellow LED Sounder
Power Up Insert Battery 1 Flash 1 Flash Off
Standby Off Off Off
Sensing Fire Rapid Flashing Off Full Sound
Fault Mode Action Red LED Yellow LED Sounder
Low Battery Off 1 Flash every 48 sec 1 Beep
Faulty Smoke Sensor Off 2 Flashes every 48 sec 2 Beeps
Faulty Heat Sensor  Off 2 Flashes every 48 sec 2 Beeps
End of Life Off 3 Flashes every 48 sec 3 Beeps
Silence Sounding 
Alarm
Press & Release Button 1 Flash every 8 sec Off Off for 10 mins
Silence “End of Life” 
indication (up to 
30 days)
Press & Release Button Off Off for 72 hours Off for 72 hours
Test Mode Action Red LED Yellow LED Sounder
Test Smoke Alarm Press Button Rapid Flashing Off Full Sound
Alarm Memory Action Red Led Yellow LED Sounder
24 Hour Memory 2 Flashes every 48 
sec for 24 hours
Off Off
Long Term Memory Press & Hold Button Rapid Flashing Off Rapid Chirping
1.1. Normal Operation
1.1.1. Power Up
Twist off the Alarm from the mounting plate 
(see Quick Start Guide). Remove the battery 
tab to power the Alarm, the red LED will flash 
once followed by one flash of the yellow LED 
to indicate that the Alarm has been powered 
successfully and is now in standby mode.
1.1.2. Standby
In standby mode there are no active visible or 
audible indications which can be intrusive to 
the householder. To confirm that the Alarm is 
operational perform a weekly button test.
1.1.3. Weekly button test
Press and hold the test button and verify that 
the red LED flashes rapidly and the Alarm 
ramps up to full sound.
1.1.4. Sensing Fire
As soon as the Alarm senses smoke it will 
go into Alarm. The red LED on the Alarm 
sensing smoke flashes rapidly to indicate this 
is the Alarm sensing smoke / fire. Follow the 
instruction in section 3 and evacuate the 
building.
1.1.5. Silence False / Nuisance alarm
Occasionally Smoke Alarms can be activated 
by phenomena other than fire, e.g. dust, 
insects, cooking fumes. Once you are sure it is 
a nuisance alarm press the large test button to 
silence the Alarm for 10 minutes – the red LED 
will then flash every 8 seconds for 10 minutes.
1.2. Fault Conditions
1.2.1. Low battery
2

benefits that the user is reminded every 10 
minutes by two short beeps that the Alarm 
needs to be replaced and that if the problem 
clears the Alarm will return to detecting fire).
1.2.3. Faulty smoke chamber
In the unlikely event of the smoke sensing 
chamber becoming defective, the Alarm will 
give 2 short beeps with 2 yellow LED flashes 
every 48 seconds. The Alarm must then be 
replaced.
If it is not convenient to replace it immediately, 
pressing the test button will silence the beeps 
and stop the yellow LED flashing for 12 hours. 
This can be repeated as required.
2.  Location and Positioning
Introduction
Congratulations on purchasing a Smoke  
Alarm. You can easily install these Alarms 
throughout the property on escape routes, on 
each storey, in corridors and in closed rooms to 
give warning of fire.
Heat Alarms can be installed in kitchens 
and other areas where Smoke Alarms are 
unsuitable.
NATIONAL FIRE PROTECTION ASSOCIATION 
REQUIRED PROTECTION
Smoke Detection. Where required by 
applicable laws, codes, or standards for the 
specified occupancy, approved single- and 
multiple-station Smoke Alarms shall be 
installed as follows: 
(1)  In all sleeping rooms and guest rooms
(2)  Outside of each separate dwelling unit 
sleeping area within 6.4 m (21 ft) of any door 
to a sleeping room, the distance measured 
along a path of travel
(3)  On every level of a dwelling unit, including 
basements
(4) On every level of a residential board 
and care occupancy (small facility), including 
basements and excluding crawl spaces and 
unfinished attics
(5) In the living area(s) of a guest suite
(6) In the living area(s) of a residential board 
and care occupancy (small facility)
Are More Smoke Alarms Desirable? The 
required number of smoke detectors might 
not provide reliable early warning protection 
for those areas separated by a door from 
the areas protected by the required smoke 
detectors. For this reason, it is recommended 
that the householder consider the use of 
additional smoke detectors for those areas 
for increased protection. The additional areas 
include the basement, bedrooms, dining room, 
furnace room, utility room, and hallways not 
protected by the required smoke detectors. 
The installation of smoke detectors in kitchens, 
attics (finished or unfinished), or garages is 
not normally recommended, as these locations 
occasionally experience conditions that can 
result in improper operation.
The equipment should be wired and installed 
in accordance with National Fire Protection 
Association’s Standard 72, Chapter 11 and 
National Electric Code, NFPA 70, Chapter 
3. (National Fire Protection Association, 
Batterymarch Park, Quincy, MA 02269).
For Canadian installations wiring methods 
shall be in accordance with CSA C22.1, 
Canadian Electrical Code, Part I, Safety 
Standard for Electrical Installations.  Testing 
and maintenance procedures shall be in 
accordance with CAN/ULC-S552, Standard for 
the Maintenance and Testing of Smoke-Alarms.
IMPORTANT!
Specific requirements for Smoke Alarm 
installation vary from state to state and from 
region to region. Check with your local Fire 
Department for current requirements in your 
area.
SMOKE ALARMS 
Sufficient smoke must enter your Smoke Alarm 
before it will respond. Your Smoke Alarm 
needs to be within 6.4 metres (21ft) of the fire 
to respond quickly. Smoke Alarms also need 
to be in positions where they can be heard 
throughout the property, so they can wake 
you and your family in time for everyone to 
escape. A single Smoke Alarm will give some 
protection if it is properly installed, but most 
homes will require two or more (preferably 
interconnected) to ensure that a reliable early 
warning is given. For recommended protection 
you should put individual Smoke Alarms in all 
rooms where fire is most likely to break out 
(apart from the kitchen and bathroom).
Your first Smoke Alarm should be located 
between the sleeping area and the most likely 
sources of fire (living room for example), but it 
should not be more than 6.4 metres (21ft)from 
the door to any room where a fire may start 
and block your escape from the house.
Multi-Storey Dwellings
If your home has more than one floor, at least 
one Alarm should be fitted on each level (see 
Figure 1). Preferably the Alarms should be 
interconnected (if feature is present on unit) 
so as to give sufficient warning throughout 
the property.
Figure 1 illustrates where Smoke and Heat 
Alarms should be located in a typical two 
storey house. Note the spacings in “Protection 
Levels” which ensure the early detection of fire 
and that the warning will be heard.
3

room is the most likely place for a fire to start 
at night, followed by the kitchen (where a 
Heat Alarm is recommended) and then the 
dining room. Consideration should be given to 
installing Smoke Alarms in any bedrooms where 
fires might occur, for instance, where there is 
an electrical appliance such as an electric 
blanket or heater, or where the occupant is 
a smoker. In addition, consideration should 
be also given to installing Smoke Alarms in 
any rooms where the occupant is unable to 
respond very well to a fire starting in that 
room, such as an elderly or sick person or a 
very young child.
Checking Alarms Can Be Heard
With the Alarms sounding in their intended 
locations check that the alarm can be heard 
in each bedroom with the door closed, above 
the sound of any TV/audio systems. The TV/
audio systems should be set to a reasonably 
loud conversation level. If you cannot hear 
the alarm over the sound of the TV/audio 
system, the chances are it would not wake you. 
Interconnecting the Alarms will help to ensure 
that the alarm will be heard throughout the 
property.
Positioning
Ceiling Mounting
Hot smoke rises and spreads out, so a central 
ceiling position is the recommended location. 
The air is “dead” and does not move in corners, 
therefore Smoke Alarms must be mounted 
away from corners. Keep at least 305mm 
(12”) from walls and corners (see Figure 3). 
Additionally, mount the unit at least 305mm 
(12”) from any light fitting or decorative 
object which might prevent smoke entering 
the Smoke Alarm.
Figure 3
PLACE IN CENTRAL
LOCATION AND 
NOT WITHIN
305mm (12”)
OF ANY CORNER
SMOKE ALARMS
<610mm (24”) FROM APEX
DEAD AIR 
SPACE
Wall Mounting
If ceiling mounting is impractical, Smoke Alarms 
may be mounted on a wall, provided that:
a) the top of the detection element is between 
150mm (6”) and 305mm (12”) below the ceiling 
(see; Figure 3a).
b) the bottom of the detection element is 
above the level of any door openings;
Wall mounting should only be considered where 
close spaced beams or similar obstructions may 
Locate Heat Alarms in rooms adjoining escape 
routes - kitchens, garages, boiler houses etc. 
where Smoke Alarms are unsuitable.
Figure 1
For minimum protection
- Smoke Alarm on each storey
- in each sleeping area
- every 6.4 metres (21ft) of hallways and 
rooms
- within 3 metres (10ft) of all bedroom doors
- all units interconnected (where feature is 
present)
For recommended protection
(in addition to the above):
- Smoke Alarms in every room (except 
kitchens and bathrooms)
- Heat Alarms located in kitchens, garages 
etc. within 5.3m (17ft) of potential fire 
sources
Single Storey Dwelling
If the premises is one storey you should put 
your first Smoke Alarm in a corridor or hallway 
between the sleeping and living areas. Place it 
as near to the living area as possible, but make 
sure that it can be heard loudly enough in the 
bedroom to wake someone. See Figure 2 for 
placement example.
In houses with more than one sleeping area, 
Smoke Alarms should be placed between each 
sleeping area and the living area and it is 
recommended that Heat Alarms should be 
placed in the kitchen and garage.
Figure 2
Bedroom
Bedroom
Bedroom
Bathroom
Bath
Dining Room
Laundry
Room
Living Room
Kitchen
Recommended Protection
Fire authorities recommend you put individual 
Smoke Alarms in or near all rooms where fire 
is most likely to break out (apart from the 
locations to avoid e.g bathrooms). The living 
4

• Near a decorative object, door, light fitting, 
window moulding etc., that may prevent 
smoke from entering the Alarm.
• Surfaces that are normally warmer or colder 
than the rest of the room (e.g. attic hatches). 
Temperature differences might stop smoke 
from reaching the Alarm.
• Next to or directly above heaters or air 
conditioning vents, windows, wall vents etc. 
that can change the direction of airflow.
• In very high or awkward areas (e.g. over 
stairwells) where it may be difficult to reach 
the Alarm (for testing, hushing or battery 
replacement).
• Locate the Alarm at least 1m (39”) from 
dimmer controlled lights and wiring as some 
dimmers can cause interference.
• Locate Alarm at least 1.5m (59”) and route 
wiring at least 1m away from fluorescent 
light fittings as electrical “noise” and/or 
flickering may affect the unit.
3. Fire Safety Advice
When using household protective devices, basic 
safety precautions should always be followed, 
including those listed below
• Please read all instructions.
• Rehearse emergency escape plans so 
everyone at home knows what to do in case 
the alarm sounds.
• Use the Alarm Test Button to familiarise your 
family with the Alarm sound and to practice fire 
drills regularly with all family members. Draw 
up a floor plan that will show each member 
at least 2 escape routes from each room in the 
house. Children tend to hide when they don’t 
know what to do. Teach children how to escape, 
open windows, and use roll up fire ladders and 
stools without adult help. Make sure they know 
what to do if the alarm goes off.
• Constant exposures to high or low 
temperatures or high humidity may reduce 
battery life.
• Nuisance alarms can be quickly silenced by 
fanning vigorously with a newspaper or similar 
to remove the smoke or press the test / hush 
button.
• Do not attempt to recharge or burn the 
battery, as it may explode.
• If it is necessary to remove the battery 
for separate disposal, handle carefully to 
avoid possible eye damage or skin irritation if 
battery has leaked or corroded.
• To maintain sensitivity to smoke, do not 
paint or cover the Alarm in any manner; do 
not permit any accumulation of cobwebs, dust 
or grease.
• If Alarm has been damaged in any way or 
does not function properly, do not attempt 
preclude ceiling mounting. It is considered to 
be the responsibility of the installer/client to 
determine if the presence of asbestos in the 
ceiling material would make ceiling mounting 
‘impractical’.
Figure 3a
On a Sloping Ceiling
With a sloping or peaked ceiling install a 
Smoke Alarm within 610mm (24”) of the peak 
(measured vertically). If this height is less than 
610mm (24”) the ceiling is regarded as being 
flat (see Figure 4).
Figure 4
SMOKE ALARMS
<610mm (24”)
APEX
xx
Locations to avoid
DON’T place Smoke Alarms in any of the 
following areas:
• Bathrooms, kitchens, shower rooms, garages 
or other rooms where the Smoke Alarm may 
be triggered by steam, condensation, normal 
smoke or fumes. Keep at least 6 metres (20ft) 
away from sources of normal smoke/fumes.
• Locate away from very dusty or dirty areas 
as dust build-up in the chamber can impair 
performance. It can also block the insect screen 
mesh and prevent smoke from entering the 
smoke detector chamber.
• Do not locate in insect infested areas. 
Small insects getting into the smoke detector 
chamber can cause intermittent alarms.
• Places where the normal temperature can 
exceed 100°F (38.7°C) or be below 40°F 
(4.4°C) (e.g. attics, furnace rooms, directly 
above ovens or kettles etc.) as the steam 
could cause nuisance alarms.
5

3. Get out as fast as you can. Do not stop 
for packing. Have a prearranged meeting 
place outside for all family members. Check 
everybody is there.
4. Call the Fire Brigade from a neighbour’s 
house or mobile phone. Remember to give your 
name and address.
5. NEVER re-enter a burning house.
4. Alarm Limitations
Limitations of Smoke Alarms
While Smoke Alarms are extremely effective, 
independent authorities have stated that they 
may be ineffective in some circumstances. 
There are a number of reasons for this:
• Smoke Alarms will not work if the batteries 
are depleted or if they are not connected.  
Replace the batteries if necessary. Also check 
the replace by date on the side of the Alarm.
• Smoke Alarms will not detect fire if sufficient 
smoke does not reach the Alarm. Smoke may 
be prevented from reaching the Alarm if the 
fire is too far away, for example, if the fire is 
on another floor, behind a closed door, in a 
a repair - see section 5 ‘Getting Your Alarm 
Serviced’.
• This appliance is intended ONLY for premises 
having a residential type environment.
• This is not a portable product. It must be 
mounted following the instructions in this 
instruction leaflet.
• Smoke Alarms are not a substitute for insurance. 
The supplier or manufacturer is not your insurer.
Fire Safety Hints
Store petrol and other flammable materials in 
proper containers.
Discard oily or flammable rags.
Always use a metal fireplace screen and have 
chimneys cleaned regularly.
Replace worn or damaged sockets, switches, 
home wiring and cracked or frayed electrical 
cords and plugs.
Do not overload electrical circuits.
Keep matches away from children.
Never smoke in bed. In rooms where you 
do smoke, always check under cushions for 
smouldering cigarettes and ashes.
Be sure all electrical appliances and tools have 
a recognised approval label.
Smoke alarms are not to be used with detector 
guards unless the combination has been 
evaluated and found suitable for that purpose.
This device cannot protect all persons at all 
times. It may not protect against the three 
most common causes of fatal fires:
1. Smoking in bed.
2. Leaving children at home alone.
3. Cleaning with flammable liquids, such as 
petrol.
Further information can be obtained from the 
Fire Department.
Planning Your Escape Route For When The 
Alarms Sound
1. Check room doors for heat or smoke.  Do not 
open a hot door. Use an alternate escape route. 
Close doors behind you as you leave.
2. If smoke is heavy, crawl out, staying close to 
floor. Take short breaths, if possible, through a 
wet cloth or hold your breath. More people die 
from smoke inhalation than from flames.
6

chimney, in a wall cavity, or if the prevailing 
air draughts carry the smoke or heat away.  
Installing Smoke Alarms on both sides of closed 
doors and installing more than one Alarm as 
recommended in this leaflet very significantly 
improve the probability of early detection.
• The Smoke Alarms may not be heard.
• A Smoke Alarm may not wake a person who 
has taken drugs or alcohol.
• The Alarms may not detect every type of 
fire to give sufficient early warning. They 
are particularly ineffective with: fires caused 
by smoking in bed, escaping gas, violent 
explosions, poor storage of flammable rags 
and/or liquids, (for example petrol, paint, 
spirits etc), overloaded electrical circuits, arson, 
children playing with matches.
• Current studies have shown smoke alarms 
may not awaken all sleeping individuals, and 
that it is the responsibility of individuals in the 
household that are capable of assisting others 
to provide assistance to those who may not 
be awakened by the alarm sound, or to those 
who may be incapable of safely evacuating the 
area unassisted
Limitations of Heat Alarms
There are various situations where a Heat 
Alarm may not be effective:
• Fires where the victim is intimate with a 
flaming initiated fire; for example, when a 
person’s clothes catch fire while cooking.
• Fires where the heat is prevented from 
reaching the Heat Alarm due to a closed door 
or other obstruction.
• Incendiary fires where the fire grows so 
rapidly that an occupant’s egress is blocked 
even with properly located Heat Alarms
5. Getting Your Alarm Serviced
If your Alarm fails to work after you have 
read the sections on “Installation”, “Testing, 
Maintenance and Power Supply Monitoring”, 
then contact Customer Assistance at the nearest 
address given at the end of this leaflet. If it needs 
to be returned for repair or replacement put it 
in a padded box with the battery disconnected. 
Send it to “Customer Assistance” at the nearest 
address given on the Alarm or in this leaflet. State 
the nature of the fault, where the Alarm was 
purchased and the date of purchase.
6. Installation
Installation Procedure
1. Select a location complying with the advice 
in Section 2.
2. Lift off the mounting plate from the Smoke 
Alarm.
3. Place the mounting plate on the ceiling 
exactly where you want to mount the Alarm. 
With a pencil, mark the location of the two 
screw holes.
4. Taking care to avoid any electrical wiring in the 
ceiling, drill holes using a 5.0mm drill bit through 
the centre of the marked locations. Push the 
plastic screw anchors provided into the drilled 
holes. Screw the mounting plate to the ceiling.
5. Insert the battery or batteries as per the 
Quick Start Guide, ensuring the orientation 
is correct. If the battery is already installed in 
your Alarm just pull the battery tab to power 
the Alarm.
Figure 5
ROTATE UNIT ANTI-CLOCKWISE
UNIT WILL NOT TWIST OFF - IT MAY BE
TAMPERPROOFED - SEE FIGURE 8
6. Carefully line up the Alarm on to the 
mounting plate, gentle press home and twist 
clockwise. 
Install all the other Alarms similarly.
7. Press the Test button on each Alarm to ensure 
that the Alarm works (see Figure 6).  
Figure 6
Smoke Alarm
Tamperproofing the Alarm
The Alarm can be made tamperproof to prevent 
unauthorised removal of the Alarm.
Break off the small pillar on the base as shown 
in  Figure 7a.  To remove the Alarm from 
the ceiling it is now necessary to use a small 
screwdriver, to release the catch (push catch 
towards the ceiling) and then twist off the 
7

Alarm (see Figure 7b).
Figure 7a - How to Tamperproof
BREAK OFF
SMALL PILLAR
Figure 7b - How to Remove
PUSH UP CATCH & TWIST
ALARM ANTI-CLOCKWISE TO REMOVE
If necessary it is possible to further secure 
the Alarm by using a No.2 or No.4 (2 to 3mm)  
(1/8”) diameter - not supplied) self tapping 
screw 6 to 8mm (1/4”) long (see Figure 7d), to 
firmly lock the Alarm and its mounting plate 
together (see Figure 7c).
Figure 7c
TAMPERPROOF SCREW
Figure 7d
6 to 8 mm
2 to 3 mm
SELF TAPPING
SCREW
Attach the Alarm to the mounting plate.
Line up the screw  (not supplied) on the “U” 
shaped recessed area shown in Figure 7c and 
screw firmly home.
To remove the Alarm from the ceiling, 
remove the screw first, and then twist off 
anti-clockwise.
7. Testing, Maintenance and 
Power Supply Monitoring
Your Alarm is a life saving device and should be 
checked periodically. 
7.1 Manually Testing your Alarms
It is recommended that you test your Alarms 
after installation and then at least weekly to 
ensure the units are working. It will also help 
you and your family to become familiar with 
the sound of the Alarms.
- Press and hold the Test Button until the 
Alarm sounds and the red light flashes (see 
Figure 7).  The Alarm will stop sounding shortly 
after the button is released. 
- Repeat this procedure for all other Alarms in 
the system.
WARNING:  Do not test with flame.
This can set fire to the Alarm and damage the 
house. We do not recommend testing with 
smoke as the results can be misleading unless 
special apparatus is used.
When you press the Test button it simulates 
the effect of smoke in a Smoke Alarm which it 
could experience in a real fire.
7.2 Test/Silence Button to Control Nuisance 
Alarms
The Smoke Alarms have a combined Test/
Silence button to help you control nuisance/
false alarms.
If, when the Alarm sounds, there is no sign of 
smoke or noise to indicate that there is a fire, 
it should be assumed that it is due to an actual 
fire and the dwelling should be evacuated 
immediately.
Check the house carefully in case there is a 
small fire smouldering somewhere.
Check whether there is some source of smoke 
or fumes, for example cooking fumes being 
drawn past the Alarm by an extractor.
If there are frequent nuisance/false alarms 
it may be necessary to re-locate the Smoke 
Alarm away from the source of the fumes.
If you installed Alarms with RF modules and 
did not House Code / enroll them in your 
system, you may be receiving alarm signals 
from a neighbouring system. This can be easy 
rectified by “House Coding” your Alarms - see 
relevant RF Module Instruction booklet.
1. To cancel a false alarm from a Smoke Alarm 
(which has its red light flashing rapidly), press 
the Test/Silence button (the Smoke Alarm will 
automatically switch to a reduced sensitivity 
8

Replace battery with Panasonic CR123A, use 
of another battery may present a risk of fire 
or explosion.
7.4 Cleaning your Alarm
Clean your Alarm regularly. Use a soft bristle 
brush or the brush attachment of your vacuum 
cleaner to remove dust and cobwebs from the 
side slots where the smoke enters. To clean 
the cover, wipe with a damp cloth and dry 
thoroughly.
WARNING: Do not paint your Alarm.
Other than the maintenance and cleaning 
described in this leaflet, no other customer 
servicing of this product is required.  Repairs, 
when needed, must be performed by the 
manufacturer.
7.5 Chamber Cleaning
Cleaning or replacing of the chamber cover 
should only be carried out by suitably trained 
personal. 
1. Remove the Alarm from the mounting plate.
2. Remove the battery or batteries. 
3. With a flat screwdriver unclip the three 
cover clip points (see figure 8a).
4. Remove the cover (see figure 8b).
5. Unplug the thermistor by holding the 
thermistor PCB and pulling the pins out of 
the sockets (see figure 8c). 
6. To remove the chamber top turn the 
chamber anti-clockwise approx. 15 degrees 
(see figure 8d).
7. Blow out or use a soft bristled brush to 
remove dust and dirt form the chamber 
base. 
8. Fit a new chamber top and clip in place by 
turning clock-wise 15 degrees.
9. Insert the thermistor PCB into the sockets 
and ensure the thermistor is perpendicular 
to the chamber (see figure 8e).
10. Place the cover back on the Alarm taking 
care to ensure the thermistor is protruding 
out the cover (see figure 8f).
11. Replace the battery / batteries and reattach 
to the mounting plate.
12. Press the test button to ensure the Alarm is 
working correctly.
Figure 8a
condition).
The Smoke Alarms will be silenced for a period 
of approximately 10 minutes. The red light on 
the cover of the Smoke Alarm will flash every 
8 seconds to indicate that the unit has been 
silenced.
2. The Smoke Alarm will reset to normal 
sensitivity at the end of the silenced period 
(10 minutes). If additional silenced time is 
required, simply push the Test/Silence button 
again.
3. If kitchen usage/layout is such that there 
are an unacceptable level of nuisance alarms, 
re-locate the Smoke Alarm further away where 
it will be less affected by cooking fumes etc. 
We recommend the use of a Heat Alarm in the 
Kitchen area to avoid such nuisance alarms.
7.3 Power Supply Monitoring
7.3.1 What to do when an Alarm is beeping:
A Smoke Alarm is beeping about every 48 
seconds with the yellow light flashing at the 
same time:
- Replace the Battery or Batteries.
7.3.2 Battery Replacement
When the battery power is low and replacement 
is necessary, the Smoke Alarm will “beep” and 
the yellow light will flash at the same time 
about once every 48 seconds for at least 
7 days. The battery must then be replaced. 
Also, replace the battery if the Alarm does 
not sound when the Test Button is pressed. 
When you replace the battery you must press 
the Test button to check that the Alarm is 
functioning correctly. Only replace the battery 
with: Panasonic CR123A Batteries.
Dispose of used battery promptly.  Keep away 
from children.  Do not disassemble and do not 
dispose of in fire
Replacement batteries can be purchased at 
your local hardware store.
Warning!
CONSTANT EXPOSURES TO HIGH OR LOW 
TEMPERATURES OR HIGH HUMIDITY MAY 
REDUCE BATTERY LIFE.
Use only batteries specified in marking. Use 
of a different battery may have a detrimental 
effect on Alarm operation.
These cells are intended for use at ordinary 
temperatures where anticipated high 
temperature excursions are not expected to 
exceed 100°C (212°F).
Prolonged periods of alarm will also reduce 
battery life.
Caution:  The battery used in this device 
may present a fire or chemical burn hazard 
if mistreated.  Do not recharge, disassemble, 
heat above 100°C (212°F) or dispose of in fire.  
9

Figure 8b
Figure 8c
Figure 8d
Figure 8e
Figure 8f
8.6 Smoke Alarm Automatic Self-Test
The smoke chamber in the Smoke Alarms 
automatically tests itself every 16 seconds. 
If the chamber is degraded it will beep twice 
every 48 seconds with 2 yellow LED flashes at 
the same time. If this happens clean the unit. 
If the beeping persists and the beep does not 
coincide with a yellow light flash, return the 
unit for service (see Section 5 - Getting Your 
Alarm Serviced).
8.7 Dust and Insect Contamination
All Smoke Alarms and particularly the optical 
(photoelectric) type are prone to dust and 
insect ingress which can cause false alarms.
The latest design, materials and manufacturing 
techniques have been used in the construction 
of Resolution Products’ Alarms to minimise 
the effects of contamination. However it 
is impossible to completely eliminate the 
effect of dust and insect contamination, and 
therefore, to prolong the life of the Alarm you 
must ensure that it is kept clean so that excess 
dust does not build up. Any insects or cobwebs 
in the vicinity of the Smoke Alarm should be 
promptly removed.
In certain circumstances even with regular 
cleaning, contamination can build up in the 
smoke sensing chamber causing the Alarm 
to sound. If this happens the Smoke Alarm 
must be returned for servicing or replacement. 
Contamination is beyond our control, it is 
totally unpredictable and is considered normal 
wear and tear. For this reason, contamination 
is not covered by the guarantee and a charge 
is made for all such servicing work.
8.8 End of life
The entire Alarm must be replaced if:-
• The unit is installed for over 10 years (check the 
“replace by” date marked on the side of the unit).
Before the Alarm is safely discarded, remove 
from the mounting plate & disconnect the 
batteries.
Do not put the Alarm into a fire.
The Alarm should be disposed in a safe and 
environmentally  sound manner at your local 
recycle centre. Contact your local authority for 
further advise.
8. Troubleshooting
Alarms sound for no apparent reason
• Check for fumes, steam, etc. from the kitchen 
or bathroom. Paint and other fumes can cause 
nuisance alarms.
• Check for any sign of contamination such as 
cobwebs or dust. Clean the Alarm as described 
in Section 8 if necessary.
10

11
• Press the Test/Silence button on the Smoke 
Alarm causing the Alarm (this can be identified 
as the Alarm with the red light flashing 
rapidly) – this will silence the Smoke Alarm 
for 10 minutes (and also silence all other 
interconnected Alarms in the system).
The Alarm fails to sound when the Test 
button is pressed
• Check the age of the unit - see the “replace 
by” label on side of unit.
• If necessary replace the battery or batteries 
with Panasonic CR123A. 
9. System Compatibility and 
Wireless Verification
Smoke alarm model RE214 has only been 
evaluated at ETL with Honeywell Lynx Plus 
Model#: L3000
Test the system after finishing installation, 
enrollment, and configuration.  Refer the 
panel’s manual for instructions on testing the 
system.

Pro Tip
Pressing the test button on the smoke alarm will beep both the panel 
and smoke alarm.
Specications
Physical 
Housing Dimensions
Weight with Batteries
Mounting Fastener
4.7 x 1.8 inches (12.0 x 4.6 centimeters)
7.36 ounces (210 grams)
#6 screws and anchors (provided)
Environmental
Operating Temperature
Maximum Humidity
40°F to 100°F  (4.4°C to 37.8°C), Long Term
15% to 95% non-condensing relative humidity
Sensor Specications
Frequency
Replacement Batteries
Transmitted Indications
Loudness
Smoke Sensitivity
Heat Sensor
345 MHz
Two Panasonic CR123A   
Low Battery, Supervision
85 dBA at 10 feet (3m) minimum
1.95% to 4% OBS/Foot
135 ± 5°F (57 ± 2°C)
Certication
RE214 FCC, IC, UL217, ULC531
Specications subject to change without notice.
47-0023-02 • RevA • 2017-05-23
 Tech Support Line (877) 260-5578
www.ResolutionProducts.com
WARRANTY
Resolution Products, Inc. will replace non-portable 
products that are defective in their rst ve (5) years 
and all defective portable products in their rst two 
(2) years.
IC NOTICE
This device complies with Industry Canada license-
exempt RSS standard(s). Operation is subject to the 
following two conditions:
(1) This device may not cause interference, and
(2) This device must accept any interference, including 
interference that may cause undesired operation of 
the device.
Le présent appareil est conforme aux cnr d’Industrie 
Canada applicables aux appareils radio exempts de 
licence. L’exploitation est autorisée aux deux conditions 
suivantes:
(1) L’appareil ne doit pas produire de brouillage, et
(2) L’utilisateur de l’appareil doit accepter tout 
brouillage radioélectrique subi, même si le 
brouillage est susceptible d’en compromettre le 
fonctionnement.
IC: 8310A-RE214
FCC NOTICE
This device complies with Part 15 of the FCC rules. 
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference.
(2) This device must accept any interference that may 
be received, including interference that may cause 
undesired operation.
Changes or modications not expressly approved by 
the Resolution Products, Inc. could void the user’s 
authority to operate this equipment.
FCC ID: U5X-RE214
TRADEMARKS
“Honeywell” is a trademark owned by Honeywell 
International, Inc. 
Resolution Products, Inc. products will function with 
Honeywell systems.  However, no Resolution product 
is produced by, endorsed by, or is ofcially associated 
with Honeywell. 
Resolution recommends verifying proper enrollment 
and operation, per control panel installation 
instructions, at installation.