PACKAGE HEAT PUMP UNITS
RJNA- HIGH EFFICIENCY SERIES
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
*Unit shown with
optional louver
panels installed.
“CERTIFIED UNDER THE
A.R.I. CERTIFICATION
PROGRAM—A.R.I.
STANDARD 240”
ISO 9001:2000
2
TABLE OF CONTENTS
Introduction ..................................................................................................3-4
Model Identification Options............................................................................5-6
General Data
RJNA- Series ..........................................................................................7-13
General Data Notes ........................................................................................14
Performance Data
RJNA- Series ........................................................................................15-18
Airflow Performance
RJNA- Series ........................................................................................19-21
Electrical Data
RJNA- Series ........................................................................................22-23
Units with Heater Kits
RJNA- Series ........................................................................................24-30
Dimensional Data ......................................................................................31-33
Accessories ..............................................................................................34-41
Mechanical Specifications ..............................................................................42
Typical Wiring ............................................................................................43-49
Limited Warranty ............................................................................................50
3
INTRODUCTION
These quality features are included in the Rheem
Outdoor Package Heat Pumps
Evaporator Coil/Filter Access
Optional Electric Heater Kit
Compressor Access
Control Box Access
Blower Access
4
INTRODUCTIONINTRODUCTION
ENGINEERING FEATURES
RJNA- Series Package Heat Pumps
1. All models feature Copeland®Scroll®compressors offering maximum reliability, efficiency, and quiet
operation.
2. One-piece top over the indoor section with drip lip, drawn painted base pan, and 1" [25.4 mm] raised flanges
for supply/return air connections provides superior water management.
3. Convertible horizontal and vertical airflow design allows maximum field flexibility and minimizes inventory
requirements.
4. Standard full perimeter forkable baserail with lifting holes for easier maneuvering and installations.
5. Factory installed one-inch [25.4 mm] throw away filter with provisions for two-inch [50.8 mm] filter.
6. Direct or belt drive options to accommodate a wide range of design conditions as high as 1.5 inches
[37 kPa] of external static pressure.
7. Easily removable filter, blower, electric heat, and compressor/control access panels permits prompt service.
8. Number and color coded wiring helps facilitate service and maintenance.
9. Common cabinet and components allows for installation flexibility and fewer parts to inventory.
10. Standard high pressure control on all models.
11. Externally mounted refrigerant gauge ports for easy service diagnostics.
12. Side and base electric power entry helps minimize roof penetrations.
13. Quick assembly common roof curbs helps save field labor and maximize size flexibility.
14. Factory or field installed electric heat kits available up to 24 KW.
15. Easy to install plug-in, slip-in economizers; 100% fully modulating, single enthalpy.
16. Quality powder paint finish offers long lasting protection against extreme weather conditions and is able to
withstand 1000 HR salt spray test.
[ ] Designates Metric Conversions
5
MODEL IDENTIFICATION—RJNA- SERIES
RJNA—A036JK000
Electric Heat
000 = No Resistance Heat
010 = 10 kW Resistance Heat
015 = 15 kW Resistance Heat
020 = 20 kW Resistance Heat
Drive Package
K = Direct Drive
L = Belt Drive
M = Belt Drive—High Static
Electrical Designation
J = 208-230 V, 1 PH, 60 Hz
C = 208-230 V, 3 PH, 60 Hz
D = 460 V, 3 PH, 60 Hz
Nominal Cooling Capacity
(BTUH) [kW]
036 = 36,000 [10.55]
042 = 42,000 [12.31]
048 = 48,000 [14.07]
060 = 60,000 [17.58]
Future Technical Variations
Design Series
A= 1st Design
Efficiency Designation
N= 13 SEER
Product Classification
J = Package Heat Pump—
Light Commercial
Tra d ebrand
R = Rheem
[ ] Designates Metric Conversions
6
OPTIONS—RJNA- SERIES
Option Code
Low Ambient Reduced Height
Baserails
AA
Side Flow
AD
AF x
AK x
Hail Guard
x
xBD x
xCK x x
xBX x
AL x
No Options
Freeze Stat
Time Delay
xBS x
FACTORY INSTALLED OPTION CODES FOR RJNA (3-5 Ton) [10.6-17.6 kW]
(A036, A042, A048, A060)
Example: RJNA-A060CK000XXX (where XX is factory installed option)
Example: No Options
RJNA-A060CK000
Example: No Options with Factory Installed Economizer
RJNA-A060CK000AAB
Example: Options with Hail Guard, Low Ambient, Time Delay and Freeze Stat with No Factory Installed Economizer
RJNA-A060CK000BDA
Example: Options same as above with Factory Installed Economizer
RJNA-A060CK000BDB
No Economizer Single Enthalpy Economizer
With Barometric Relief
A x
B x
ECONOMIZER SELECTION FOR RJNA-
“x” indicates factory installed option.
[ ] Designates Metric Conversions
7
GENERAL DATA—RJNA- SERIES
Model RJNA- Series A036CK A036CL A036CM A036DK
Cooling Performance1
Gross Cooling Capacity Btu [kW] 37,600 [11] 37,600 [11] 37,600 [11] 37,600 [11]
EER/SEER211.6/13 11.6/13 11.6/13 11.6/13
Nominal CFM/ARI Rated CFM [L/s] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566]
ARI Net Cooling Capacity Btu [kW] 36,000 [10.5] 36,000 [10.5] 36,000 [10.5] 36,000 [10.5]
Net Sensible Capacity Btu [kW] 26,823 [7.9] 26,823 [7.9] 26,823 [7.9] 26,823 [7.9]
Net System Power kW 3.1 3.1 3.1 3.1
Heating Performance (Heat Pumps)
Heating Temp. Btuh [kW] Rating 35,600 [10.4] 35,600 [10.4] 35,600 [10.4] 35,600 [10.4]
System Power KW/COP 3.2/3.3 3.2/3.3 3.2/3.3 3.2/3.3
Low Temp. Btuh [kW] Rating 21,200 [6.2] 21,200 [6.2] 21,200 [6.2] 21,200 [6.2]
Net Weight lbs. [kg] 517 [235] 517 [235] 517 [235] 517 [235]
System Power KW/COP 3/2.08 3/2.08 3/2.08 3/2.08
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
HSPF (Btu/Watts-hr) 7.7 7.7 7.7 7.7
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB)383 83 83 83
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 16.56 [1.54] 16.56 [1.54] 16.56 [1.54] 16.56 [1.54]
Rows / FPI [FPcm] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9]
Net Latent Capacity Btu [kW] 9177 [2.7] 9177 [2.7] 9177 [2.7] 9177 [2.7]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 5.16 [0.48] 5.16 [0.48] 5.16 [0.48] 5.16 [0.48]
Rows / FPI [FPcm] 3 / 13 [5] 3 / 13 [5] 3 / 13 [5] 3 / 13 [5]
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM [L/s] 4000 [1888] 4000 [1888] 4000 [1888] 4000 [1888]
No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP
Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/10x10 [254x254] 1/10x10 [254x254] 1/10x10 [254x254] 1/10x10 [254x254]
Drive Type/No. Speeds Direct/3 Belt/Variable Belt/Variable Direct/3
No. Motors 1 1 1 1
Motor HP 1/2 1/2 3/4 1/2
Motor RPM 1075 1725 1725 1075
Motor Frame Size 48 56 56 48
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Yes Yes Yes
(No.) Size Recommended in. [mm] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406]
Refrigerant Charge Oz. [g] 182 [5160] 182 [5160] 182 [5160] 182 [5160]
Weights
Ship Weight lbs. [kg] 532 [241] 532 [241] 532 [241] 532 [241]
CONTINUED
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
See Page 14 for Notes.
[ ] Designates Metric Conversions
8
GENERAL DATA—RJNA- SERIES
Model RJNA- Series A036DL A036DM A036JK A042CK
Cooling Performance1
Gross Cooling Capacity Btu [kW] 37,600 [11] 37,600 [11] 37,600 [11] 42,500 [12.5]
EER/SEER211.6/13 11.6/13 11.6/13 11.8/13
Nominal CFM/ARI Rated CFM [L/s] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566] 1400/1400 [661/661]
ARI Net Cooling Capacity Btu [kW] 36,000 [10.5] 36,000 [10.5] 36,000 [10.5] 40,500 [11.9]
Net Sensible Capacity Btu [kW] 26,823 [7.9] 26,823 [7.9] 26,823 [7.9] 30,124 [8.8]
Net System Power kW 3.1 3.1 3.1 3.4
Heating Performance (Heat Pumps)
Heating Temp. Btuh [kW] Rating 35,600 [10.4] 35,600 [10.4] 35,600 [10.4] 40,000 [11.7]
System Power KW/COP 3.2/3.3 3.2/3.3 3.2/3.3 3.6/3.28
Low Temp. Btuh [kW] Rating 21,200 [6.2] 21,200 [6.2] 21,200 [6.2] 23,200 [6.8]
Net Weight lbs. [kg] 517 [235] 517 [235] 517 [235] 521 [236]
System Power KW/COP 3/2.08 3/2.08 3/2.08 3.3/2.06
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
HSPF (Btu/Watts-hr) 7.7 7.7 7.7 7.7
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB)383 83 83 83
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 16.56 [1.54] 16.56 [1.54] 16.56 [1.54] 16.56 [1.54]
Rows / FPI [FPcm] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9]
Net Latent Capacity Btu [kW] 9177 [2.7] 9177 [2.7] 9177 [2.7] 10,376 [3]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 5.16 [0.48] 5.16 [0.48] 5.16 [0.48] 5.16 [0.48]
Rows / FPI [FPcm] 3 / 13 [5] 3 / 13 [5] 3 / 13 [5] 3 / 13 [5]
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM [L/s] 4000 [1888] 4000 [1888] 4000 [1888] 4000 [1888]
No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP
Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/10x10 [254x254] 1/10x10 [254x254] 1/10x10 [254x254] 1/10x10 [254x254]
Drive Type/No. Speeds Belt/Variable Belt/Variable Direct/3 Direct/3
No. Motors 1 1 1 1
Motor HP 1/2 3/4 1/2 1/2
Motor RPM 1725 1725 1075 1075
Motor Frame Size 56 56 48 48
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Yes Yes Yes
(No.) Size Recommended in. [mm] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406]
Refrigerant Charge Oz. [g] 182 [5160] 182 [5160] 182 [5160] 177 [5018]
Weights
Ship Weight lbs. [kg] 532 [241] 532 [241] 532 [241] 536 [243]
CONTINUED
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
See Page 14 for Notes.
[ ] Designates Metric Conversions
9
GENERAL DATA—RJNA- SERIES
Model RJNA- Series A042CL A042CM A042DK A042DL
Cooling Performance1
Gross Cooling Capacity Btu [kW] 42,500 [12.5] 42,500 [12.5] 42,500 [12.5] 42,500 [12.5]
EER/SEER211.8/13 11.8/13 11.8/13 11.8/13
Nominal CFM/ARI Rated CFM [L/s] 1400/1400 [661/661] 1400/1400 [661/661] 1400/1400 [661/661] 1400/1400 [661/661]
ARI Net Cooling Capacity Btu [kW] 40,500 [11.9] 40,500 [11.9] 40,500 [11.9] 40,500 [11.9]
Net Sensible Capacity Btu [kW] 30,124 [8.8] 30,124 [8.8] 30,124 [8.8] 30,124 [8.8]
Net System Power kW 3.4 3.4 3.4 3.4
Heating Performance (Heat Pumps)
Heating Temp. Btuh [kW] Rating 40,000 [11.7] 40,000 [11.7] 40,000 [11.7] 40,000 [11.7]
System Power KW/COP 3.6/3.28 3.6/3.28 3.6/3.28 3.6/3.28
Low Temp. Btuh [kW] Rating 23,200 [6.8] 23,200 [6.8] 23,200 [6.8] 23,200 [6.8]
Net Weight lbs. [kg] 521 [236] 521 [236] 521 [236] 521 [236]
System Power KW/COP 3.3/2.06 3.3/2.06 3.3/2.06 3.3/2.06
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
HSPF (Btu/Watts-hr) 7.7 7.7 7.7 7.7
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB)383 83 83 83
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 16.56 [1.54] 16.56 [1.54] 16.56 [1.54] 16.56 [1.54]
Rows / FPI [FPcm] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9]
Net Latent Capacity Btu [kW] 10,376 [3] 10,376 [3] 10,376 [3] 10,376 [3]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 5.16 [0.48] 5.16 [0.48] 5.16 [0.48] 5.16 [0.48]
Rows / FPI [FPcm] 3 / 13 [5] 3 / 13 [5] 3 / 13 [5] 3 / 13 [5]
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM [L/s] 4000 [1888] 4000 [1888] 4000 [1888] 4000 [1888]
No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP
Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/10x10 [254x254] 1/10x10 [254x254] 1/10x10 [254x254] 1/10x10 [254x254]
Drive Type/No. Speeds Belt/Variable Belt/Variable Direct/3 Belt/Variable
No. Motors 1 1 1 1
Motor HP 1/2 3/4 1/2 1/2
Motor RPM 1725 1725 1075 1725
Motor Frame Size 56 56 48 56
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Yes Yes Yes
(No.) Size Recommended in. [mm] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406]
Refrigerant Charge Oz. [g] 177 [5018] 177 [5018] 177 [5018] 177 [5018]
Weights
Ship Weight lbs. [kg] 536 [243] 536 [243] 536 [243] 536 [243]
CONTINUED
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
See Page 14 for Notes.
[ ] Designates Metric Conversions
10
GENERAL DATA—RJNA- SERIES
Model RJNA- Series A042DM A042JK A048CK A048CL
Cooling Performance1
Gross Cooling Capacity Btu [kW] 42,500 [12.5] 42,500 [12.5] 49,500 [14.5] 49,500 [14.5]
EER/SEER211.8/13 11.8/13 11.65/13 11.65/13
Nominal CFM/ARI Rated CFM [L/s] 1400/1400 [661/661] 1400/1400 [661/661] 1600/1600 [755/755] 1600/1600 [755/755]
ARI Net Cooling Capacity Btu [kW] 40,500 [11.9] 40,500 [11.9] 47,000 [13.8] 47,000 [13.8]
Net Sensible Capacity Btu [kW] 30,124 [8.8] 30,124 [8.8] 34,700 [10.2] 34,700 [10.2]
Net System Power kW 3.4 3.4 4 4
Heating Performance (Heat Pumps)
Heating Temp. Btuh [kW] Rating 40,000 [11.7] 40,000 [11.7] 46,500 [13.6] 46,500 [13.6]
System Power KW/COP 3.6/3.28 3.6/3.28 3.9/3.5 3.9/3.5
Low Temp. Btuh [kW] Rating 23,200 [6.8] 23,200 [6.8] 27,800 [8.1] 27,800 [8.1]
Net Weight lbs. [kg] 521 [236] 521 [236] 535 [243] 535 [243]
System Power KW/COP 3.3/2.06 3.3/2.06 3.7/2.22 3.7/2.22
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
HSPF (Btu/Watts-hr) 7.7 7.7 7.7 7.7
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB)383 83 83 83
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 16.56 [1.54] 16.56 [1.54] 16.56 [1.54] 16.56 [1.54]
Rows / FPI [FPcm] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9]
Net Latent Capacity Btu [kW] 10,376 [3] 10,376 [3] 12,300 [3.6] 12,300 [3.6]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 5.16 [0.48] 5.16 [0.48] 5.16 [0.48] 5.16 [0.48]
Rows / FPI [FPcm] 3 / 13 [5] 3 / 13 [5] 4 / 13 [5] 4 / 13 [5]
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM [L/s] 4000 [1888] 4000 [1888] 4000 [1888] 4000 [1888]
No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP
Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/10x10 [254x254] 1/10x10 [254x254] 1/10x10 [254x254] 1/10x10 [254x254]
Drive Type/No. Speeds Belt/Variable Direct/3 Direct/3 Belt/Variable
No. Motors 1 1 1 1
Motor HP 3/4 1/2 1/2 1/2
Motor RPM 1725 1075 1075 1725
Motor Frame Size 56 48 48 56
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Yes Yes Yes
(No.) Size Recommended in. [mm] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406]
Refrigerant Charge Oz. [g] 177 [5018] 177 [5018] 206 [5840] 206 [5840]
Weights
Ship Weight lbs. [kg] 536 [243] 536 [243] 550 [249] 550 [249]
CONTINUED
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
See Page 14 for Notes.
[ ] Designates Metric Conversions
11
GENERAL DATA—RJNA- SERIES
Model RJNA- Series A048CM A048DK A048DL A048DM
Cooling Performance1
Gross Cooling Capacity Btu [kW] 49,500 [14.5] 49,500 [14.5] 49,500 [14.5] 49,500 [14.5]
EER/SEER211.65/13 11.65/13 11.65/13 11.65/13
Nominal CFM/ARI Rated CFM [L/s] 1600/1600 [755/755] 1600/1600 [755/755] 1600/1600 [755/755] 1600/1600 [755/755]
ARI Net Cooling Capacity Btu [kW] 47,000 [13.8] 47,000 [13.8] 47,000 [13.8] 47,000 [13.8]
Net Sensible Capacity Btu [kW] 34,700 [10.2] 34,700 [10.2] 34,700 [10.2] 34,700 [10.2]
Net System Power kW 4 4 4 4
Heating Performance (Heat Pumps)
Heating Temp. Btuh [kW] Rating 46,500 [13.6] 46,500 [13.6] 46,500 [13.6] 46,500 [13.6]
System Power KW/COP 3.9/3.5 3.9/3.5 3.9/3.5 3.9/3.5
Low Temp. Btuh [kW] Rating 27,800 [8.1] 27,800 [8.1] 27,800 [8.1] 27,800 [8.1]
Net Weight lbs. [kg] 535 [243] 535 [243] 535 [243] 535 [243]
System Power KW/COP 3.7/2.22 3.7/2.22 3.7/2.22 3.7/2.22
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
HSPF (Btu/Watts-hr) 7.7 7.7 7.7 7.7
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB)383 83 83 83
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 16.56 [1.54] 16.56 [1.54] 16.56 [1.54] 16.56 [1.54]
Rows / FPI [FPcm] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9]
Net Latent Capacity Btu [kW] 12,300 [3.6] 12,300 [3.6] 12,300 [3.6] 12,300 [3.6]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 5.16 [0.48] 5.16 [0.48] 5.16 [0.48] 5.16 [0.48]
Rows / FPI [FPcm] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5]
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM [L/s] 4000 [1888] 4000 [1888] 4000 [1888] 4000 [1888]
No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP
Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/10x10 [254x254] 1/10x10 [254x254] 1/10x10 [254x254] 1/10x10 [254x254]
Drive Type/No. Speeds Belt/Variable Direct/3 Belt/Variable Belt/Variable
No. Motors 1 1 1 1
Motor HP 3/4 1/2 1/2 3/4
Motor RPM 1725 1075 1725 1725
Motor Frame Size 56 48 56 56
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Yes Yes Yes
(No.) Size Recommended in. [mm] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406]
Refrigerant Charge Oz. [g] 206 [5840] 206 [5840] 206 [5840] 206 [5840]
Weights
Ship Weight lbs. [kg] 550 [249] 550 [249] 550 [249] 550 [249]
CONTINUED
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
See Page 14 for Notes.
[ ] Designates Metric Conversions
12
GENERAL DATA—RJNA- SERIES
Model RJNA- Series A048JK A060CK A060CL A060CM
Cooling Performance1
Gross Cooling Capacity Btu [kW] 49,500 [14.5] 63,500 [18.6] 64,000 [18.8] 64,000 [18.8]
EER/SEER211.65/13 11.55/13 11.55/13 11.55/13
Nominal CFM/ARI Rated CFM [L/s] 1600/1600 [755/755] 2000/2000 [944/944] 2000/2000 [944/944] 2000/2000 [944/944]
ARI Net Cooling Capacity Btu [kW] 47,000 [13.8] 61,500 [18] 61,500 [18] 61,500 [18]
Net Sensible Capacity Btu [kW] 34,700 [10.2] 43,800 [12.8] 43,800 [12.8] 43,800 [12.8]
Net System Power kW 4 5.3 5.3 5.3
Heating Performance (Heat Pumps)
Heating Temp. Btuh [kW] Rating 46,500 [13.6] 60,500 [17.7] 60,500 [17.7] 60,500 [17.7]
System Power KW/COP 3.9/3.5 5/3.5 5/3.5 5/3.5
Low Temp. Btuh [kW] Rating 27,800 [8.1] 36,000 [10.5] 36,000 [10.5] 36,000 [10.5]
Net Weight lbs. [kg] 535 [243] 565 [256] 565 [256] 565 [256]
System Power KW/COP 3.7/2.22 4.4/2.3 4.4/2.3 4.4/2.3
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
HSPF (Btu/Watts-hr) 7.7 7.7 7.7 7.7
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB)383 83 83 83
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 16.56 [1.54] 16.56 [1.54] 16.56 [1.54] 16.56 [1.54]
Rows / FPI [FPcm] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9]
Net Latent Capacity Btu [kW] 12,300 [3.6] 17,700 [5.2] 17,700 [5.2] 17,700 [5.2]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 5.16 [0.48] 5.16 [0.48] 5.16 [0.48] 5.16 [0.48]
Rows / FPI [FPcm] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5]
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM [L/s] 4000 [1888] 4000 [1888] 4000 [1888] 4000 [1888]
No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP
Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/10x10 [254x254] 1/11x9 [279.4x228.6] 1/10x10 [254x254] 1/10x10 [254x254]
Drive Type/No. Speeds Direct/3 Direct/2 Belt/Variable Belt/Variable
No. Motors 1 1 1 1
Motor HP 1/2 13/4 1
Motor RPM 1075 1100 1725 1725
Motor Frame Size 48 48 56 56
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Yes Yes Yes
(No.) Size Recommended in. [mm] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406]
Refrigerant Charge Oz. [g] 206 [5840] 184 [5216] 184 [5216] 184 [5216]
Weights
Ship Weight lbs. [kg] 550 [249] 580 [263] 580 [263] 580 [263]
CONTINUED
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
See Page 14 for Notes.
[ ] Designates Metric Conversions
13
GENERAL DATA—RJNA- SERIES
Model RJNA- Series A060DL A060DM A060JK
Cooling Performance1
Gross Cooling Capacity Btu [kW] 64,000 [18.8] 64,000 [18.8] 63,500 [18.6]
EER/SEER211.55/13 11.55/13 11.55/13
Nominal CFM/ARI Rated CFM [L/s] 2000/2000 [944/944] 2000/2000 [944/944] 2000/2000 [944/944]
ARI Net Cooling Capacity Btu [kW] 61,500 [18] 61,500 [18] 61,500 [18]
Net Sensible Capacity Btu [kW] 43,800 [12.8] 43,800 [12.8] 43,800 [12.8]
Net System Power kW 5.3 5.3 5.3
Heating Performance (Heat Pumps)
Heating Temp. Btuh [kW] Rating 60,500 [17.7] 60,500 [17.7] 60,500 [17.7]
System Power KW/COP 5/3.5 5/3.5 5/3.5
Low Temp. Btuh [kW] Rating 36,000 [10.5] 36,000 [10.5] 36,000 [10.5]
Net Weight lbs. [kg] 565 [256] 565 [256] 565 [256]
System Power KW/COP 4.4/2.3 4.4/2.3 4.4/2.3
Refrigerant Control TX Valves TX Valves TX Valves
HSPF (Btu/Watts-hr) 7.7 7.7 7.7
Compressor
No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB)383 83 83
Outdoor Coil—Fin Type Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled
Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 16.56 [1.54] 16.56 [1.54] 16.56 [1.54]
Rows / FPI [FPcm] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9]
Net Latent Capacity Btu [kW] 17,700 [5.2] 17,700 [5.2] 17,700 [5.2]
Indoor Coil—Fin Type Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled
Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 5.16 [0.48] 5.16 [0.48] 5.16 [0.48]
Rows / FPI [FPcm] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5]
Refrigerant Control TX Valves TX Valves TX Valves
Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller
No. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1
CFM [L/s] 4000 [1888] 4000 [1888] 4000 [1888]
No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP
Motor RPM 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/10x10 [254x254] 1/10x10 [254x254] 1/11x9 [279.4x228.6]
Drive Type/No. Speeds Belt/Variable Belt/Variable Direct/2
No. Motors 1 1 1
Motor HP 3/4 1 1
Motor RPM 1725 1725 1100
Motor Frame Size 56 56 48
Filter—Type Disposable Disposable Disposable
Furnished Yes Yes Yes
(No.) Size Recommended in. [mm] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406]
Refrigerant Charge Oz. [g] 184 [5216] 184 [5216] 184 [5216]
Weights
Ship Weight lbs. [kg] 580 [263] 580 [263] 580 [263]
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
See Page 14 for Notes.
[ ] Designates Metric Conversions
14
GENERAL DATA—RJNA- SERIES
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not
include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for
operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment
certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.
[ ] Designates Metric Conversions
COOLING PERFORMANCE DATA—RJNA-A036
HEATING PERFORMANCE DATA—RJNA-A036
DR —Depression ratio
dbE —Entering air dry bulb
wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power—KW input
NOTES:
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
IDB—Indoor air dry bulb [ ] Designates Metric Conversions
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 1440 [680] 1200 [566] 960 [453] 1440 [680] 1200 [566] 960 [453] 1440 [680] 1200 [566] 960 [453]
DR .16 .13 .08 .16 .13 .08 .16 .13 .08
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
46.4 [13.60]
27.9 [8.18]
2.2
44.8 [13.13]
25.5 [7.47]
2.2
43.1 [12.63]
23.1 [6.77]
2.2
43.4 [12.72]
33.5 [9.82]
2.2
41.9 [12.28]
30.6 [8.97]
2.2
40.4 [11.84]
27.7 [8.12]
2.1
41.1 [12.05]
34.8 [10.20]
2.2
39.7 [11.63]
31.8 [9.32]
2.2
38.2 [11.20]
28.8 [8.44]
2.1
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
45.5 [13.33]
27.3 [8.00]
2.3
43.9 [12.87]
25.0 [7.33]
2.3
42.3 [12.40]
22.6 [6.62]
2.3
42.6 [12.48]
32.9 [9.64]
2.3
41.1 [12.05]
30.0 [8.79]
2.3
39.6 [11.61]
27.2 [7.97]
2.3
40.2 [11.78]
34.2 [10.02]
2.3
38.8 [11.37]
31.3 [9.17]
2.3
37.4 [10.96]
28.3 [8.29]
2.3
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
44.5 [13.04]
26.7 [7.83]
2.5
42.9 [12.57]
24.4 [7.15]
2.4
41.3 [12.10]
22.1 [6.48]
2.4
41.5 [12.16]
32.3 [9.47]
2.4
40.0 [11.72]
29.5 [8.65]
2.4
38.6 [11.31]
26.8 [7.85]
2.4
39.2 [11.49]
33.6 [9.85]
2.4
37.8 [11.08]
30.7 [9.00]
2.4
36.4 [10.67]
27.9 [8.18]
2.4
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
43.3 [12.69]
26.1 [7.65]
2.6
41.7 [12.22]
23.9 [7.00]
2.5
40.2 [11.78]
21.7 [6.36]
2.5
40.3 [11.81]
31.7 [9.29]
2.6
38.9 [11.40]
29.0 [8.50]
2.5
37.5 [10.99]
26.3 [7.71]
2.5
38.0 [11.14]
33.0 [9.67]
2.6
36.6 [10.73]
30.2 [8.85]
2.5
35.3 [10.35]
27.4 [8.03]
2.5
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
42.0 [12.31]
25.6 [7.50]
2.7
40.5 [11.87]
23.4 [6.86]
2.6
39.0 [11.43]
21.2 [6.21]
2.6
39.0 [11.43]
31.1 [9.11]
2.7
37.6 [11.02]
28.5 [8.35]
2.6
36.3 [10.64]
25.8 [7.56]
2.6
36.7 [10.76]
32.4 [9.50]
2.7
35.4 [10.37]
29.7 [8.70]
2.6
34.1 [9.99]
26.9 [7.88]
2.6
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
40.7 [11.93]
25.0 [7.33]
2.8
39.3 [11.52]
22.8 [6.68]
2.8
37.8 [11.08]
20.7 [6.07]
2.7
37.7 [11.05]
30.5 [8.94]
2.8
36.4 [10.67]
27.9 [8.18]
2.7
35.1 [10.29]
25.3 [7.41]
2.7
35.4 [10.37]
31.9 [9.35]
2.8
34.2 [10.02]
29.1 [8.53]
2.7
32.9 [9.64]
26.4 [7.74]
2.7
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
39.5 [11.58]
24.4 [7.15]
2.9
38.1 [11.17]
22.3 [6.54]
2.9
36.7 [10.76]
20.2 [5.92]
2.8
36.5 [10.70]
30.0 [8.79]
2.9
35.2 [10.32]
27.4 [8.03]
2.9
33.9 [9.94]
24.8 [7.27]
2.8
34.2 [10.02]
31.3 [9.17]
2.9
33.0 [9.67]
28.6 [8.38]
2.9
31.8 [9.32]
25.9 [7.59]
2.8
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
38.4 [11.25]
23.8 [6.98]
3.0
37.0 [10.84]
21.8 [6.39]
3.0
35.7 [10.46]
19.7 [5.77]
2.9
35.4 [10.37]
29.3 [8.59]
3.0
34.2 [10.02]
26.8 [7.85]
3.0
32.9 [9.64]
24.3 [7.12]
2.9
33.1 [9.70]
30.7 [9.00]
3.0
31.9 [9.35]
28.0 [8.21]
3.0
30.8 [9.03]
25.4 [7.44]
2.9
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
37.5 [10.99]
23.2 [6.80]
3.1
36.1 [10.58]
21.2 [6.21]
3.1
34.8 [10.20]
19.2 [5.63]
3.0
34.5 [10.11]
28.7 [8.41]
3.1
33.3 [9.76]
26.3 [7.71]
3.1
32.1 [9.41]
23.8 [6.98]
3.0
32.2 [9.44]
30.0 [8.79]
3.1
31.0 [9.09]
27.5 [8.06]
3.1
29.9 [8.76]
24.9 [7.30]
3.0
45
[46.1]
Total BTUH [kW]
Power
35.4 [10.37]
2.4
34.9 [10.23]
2.5
34.4 [10.08]
2.6
33.6 [9.85]
2.7
33.1 [9.70]
2.7
32.6 [9.55]
2.8
31.9 [9.35]
2.9
IDB
31.4 [9.20]
3.0
31.0 [9.09]
3.1
60°F [15.5°C]
50
[10]
70°F [21.1°C]
Total BTUH [kW]
Power
37.6 [11.02]
2.5
80°F [26.7°C]
37.1 [10.87]
2.5
36.6 [10.73]
2.6
CFM [L/s]
35.8 [10.49]
2.7
35.3 [10.35]
2.8
1440 [680] 1200 [566] 960 [453] 1440 [680] 1200 [566] 960 [453] 1440 [680] 1200 [566] 960 [453]
34.8 [10.20]
2.8
34.1 [9.99]
2.9
33.6 [9.85]
3.0
33.1 [9.70]
3.1
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
0
[-17.8]
Total BTUH [kW]
Power
8.9 [2.61]
2.1
8.7 [2.55]
2.1
8.6 [2.52]
2.2
7.0 [2.05]
2.3
6.9 [2.02]
2.4
6.8 [1.99]
2.4
5.3 [1.55]
2.6
5.2 [1.52]
2.6
5.1 [1.49]
2.7
5
[26.7]
Total BTUH [kW]
Power
12.2 [3.58]
2.1
12.0 [3.52]
2.2
11.9 [3.49]
2.2
10.4 [3.05]
2.4
10.2 [2.99]
2.4
10.1 [2.96]
2.5
8.6 [2.52]
2.6
8.5 [2.49]
2.7
8.4 [2.46]
2.7
10
[-12.2]
Total BTUH [kW]
Power
15.5 [4.54]
2.2
15.3 [4.48]
2.2
15.1 [4.43]
2.3
13.6 [3.99]
2.4
13.5 [3.96]
2.5
13.3 [3.90]
2.5
11.9 [3.49]
2.6
11.8 [3.46]
2.7
11.6 [3.40]
2.8
15
[32.2]
Total BTUH [kW]
Power
18.7 [5.48]
2.2
18.5 [5.42]
2.3
18.2 [5.33]
2.3
16.9 [4.95]
2.4
16.6 [4.86]
2.5
16.4 [4.81]
2.6
15.1 [4.43]
2.7
14.9 [4.37]
2.8
14.7 [4.31]
2.8
20
[-6.6]
Total BTUH [kW]
Power
21.8 [6.39]
2.2
21.5 [6.30]
2.3
21.2 [6.21]
2.4
20.0 [5.86]
2.5
19.7 [5.77]
2.5
19.4 [5.69]
2.6
18.3 [5.36]
2.7
18.0 [5.28]
2.8
17.7 [5.19]
2.9
25
[37.8]
Total BTUH [kW]
Power
24.8 [7.27]
2.3
24.5 [7.18]
2.3
24.1 [7.06]
2.4
23.0 [6.74]
2.5
22.7 [6.65]
2.6
22.3 [6.54]
2.6
21.3 [6.24]
2.8
21.0 [6.15]
2.8
20.7 [6.07]
2.9
30
[-1.1]
Total BTUH [kW]
Power
27.7 [8.12]
2.3
27.3 [8.00]
2.4
26.9 [7.88]
2.4
25.9 [7.59]
2.5
25.5 [7.47]
2.6
25.1 [7.36]
2.7
24.1 [7.06]
2.8
23.8 [6.98]
2.9
23.5 [6.89]
2.9
35
[43.3]
Total BTUH [kW]
Power
30.5 [8.94]
2.4
30.0 [8.79]
2.4
29.6 [8.67]
2.5
28.6 [8.38]
2.6
28.2 [8.26]
2.6
27.8 [8.15]
2.7
26.9 [7.88]
2.8
26.5 [7.77]
2.9
26.1 [7.65]
3.0
40
[4.4]
Total BTUH [kW]
Power
33.0 [9.67]
2.4
32.6 [9.55]
2.5
32.1 [9.41]
2.5
31.2 [9.14]
2.6
30.7 [9.00]
2.7
30.3 [8.88]
2.7
29.5 [8.65]
2.9
29.0 [8.50]
2.9
28.6 [8.38]
3.0
15
SYSTEMS PERFORMANCE—RJNA- SERIES
COOLING PERFORMANCE DATA—RJNA-A042
HEATING PERFORMANCE DATA—RJNA-A042
DR —Depression ratio
dbE —Entering air dry bulb
wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power—KW input
NOTES:
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
IDB—Indoor air dry bulb [ ] Designates Metric Conversions
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 1680 [793] 1400 [661] 1120 [529] 1680 [793] 1400 [661] 1120 [529] 1680 [793] 1400 [661] 1120 [529]
DR .18 .15 .11 .18 .15 .11 .18 .15 .11
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
50.3 [14.74]
30.8 [9.03]
2.3
48.5 [14.21]
28.2 [8.26]
2.3
46.8 [13.72]
25.6 [7.50]
2.2
47.6 [13.95]
37.2 [10.90]
2.3
46.0 [13.48]
34.0 [9.96]
2.3
44.3 [12.98]
30.8 [9.03]
2.2
45.0 [13.19]
38.6 [11.31]
2.3
43.4 [12.72]
35.3 [10.35]
2.3
41.9 [12.28]
32.0 [9.38]
2.2
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
50.3 [14.74]
30.8 [9.03]
2.4
48.5 [14.21]
28.1 [8.24]
2.4
46.8 [13.72]
25.5 [7.47]
2.4
47.7 [13.98]
37.1 [10.87]
2.4
46.0 [13.48]
33.9 [9.94]
2.4
44.3 [12.98]
30.8 [9.03]
2.4
45.1 [13.22]
38.5 [11.28]
2.4
43.5 [12.75]
35.2 [10.32]
2.4
41.9 [12.28]
31.9 [9.35]
2.4
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
49.6 [14.54]
30.3 [8.88]
2.6
47.8 [14.01]
27.7 [8.12]
2.5
46.1 [13.51]
25.1 [7.36]
2.5
46.9 [13.75]
36.6 [10.73]
2.6
45.3 [13.28]
33.5 [9.82]
2.5
43.6 [12.78]
30.4 [8.91]
2.5
44.3 [12.98]
38.1 [11.17]
2.6
42.8 [12.54]
34.8 [10.20]
2.5
41.2 [12.07]
31.6 [9.26]
2.5
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
48.3 [14.16]
29.6 [8.67]
2.7
46.6 [13.66]
27.1 [7.94]
2.7
44.9 [13.16]
24.5 [7.18]
2.6
45.6 [13.36]
35.9 [10.52]
2.7
44.0 [12.90]
32.9 [9.64]
2.7
42.4 [12.43]
29.8 [8.73]
2.6
43.0 [12.60]
37.4 [10.96]
2.7
41.5 [12.16]
34.2 [10.02]
2.7
40.0 [11.72]
31.0 [9.09]
2.6
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
46.7 [13.69]
28.8 [8.44]
2.9
45.0 [13.19]
26.3 [7.71]
2.8
43.4 [12.72]
23.9 [7.00]
2.8
44.0 [12.90]
35.1 [10.29]
2.9
42.5 [12.46]
32.1 [9.41]
2.8
40.9 [11.99]
29.1 [8.53]
2.8
41.4 [12.13]
36.5 [10.70]
2.9
40.0 [11.72]
33.4 [9.79]
2.8
38.5 [11.28]
30.3 [8.88]
2.8
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
45.0 [13.19]
27.9 [8.18]
3.0
43.4 [12.72]
25.5 [7.47]
3.0
41.8 [12.25]
23.1 [6.77]
2.9
42.4 [12.43]
34.3 [10.05]
3.0
40.9 [11.99]
31.3 [9.17]
3.0
39.4 [11.55]
28.4 [8.32]
2.9
39.8 [11.66]
35.7 [10.46]
3.0
38.4 [11.25]
32.6 [9.55]
3.0
37.0 [10.84]
29.6 [8.67]
2.9
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
43.5 [12.75]
27.2 [7.97]
3.1
42.0 [12.31]
24.9 [7.30]
3.1
40.4 [11.84]
22.5 [6.59]
3.0
40.8 [11.96]
33.5 [9.82]
3.1
39.4 [11.55]
30.7 [9.00]
3.1
38.0 [11.14]
27.8 [8.15]
3.0
38.2 [11.20]
34.9 [10.23]
3.1
36.9 [10.81]
32.0 [9.38]
3.1
35.6 [10.43]
29.0 [8.50]
3.0
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
42.4 [12.43]
26.7 [7.83]
3.3
40.9 [11.99]
24.4 [7.15]
3.2
39.4 [11.55]
22.1 [6.48]
3.2
39.7 [11.63]
33.0 [9.67]
3.3
38.3 [11.22]
30.2 [8.85]
3.2
36.9 [10.81]
27.4 [8.03]
3.2
37.1 [10.87]
34.4 [10.08]
3.3
35.8 [10.49]
31.5 [9.23]
3.2
34.5 [10.11]
28.6 [8.38]
3.2
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
41.9 [12.28]
26.5 [7.77]
3.4
40.4 [11.84]
24.3 [7.12]
3.4
39.0 [11.43]
22.0 [6.45]
3.3
39.3 [11.52]
32.9 [9.64]
3.4
37.9 [11.11]
30.1 [8.82]
3.4
36.5 [10.70]
27.3 [8.00]
3.3
36.7 [10.76]
34.3 [10.05]
3.4
35.4 [10.37]
31.4 [9.20]
3.4
34.1 [9.99]
28.4 [8.32]
3.3
45
[46.1]
Total BTUH [kW]
Power
36.9 [10.81]
2.6
36.4 [10.67]
2.7
35.9 [10.52]
2.7
36.1 [10.58]
2.9
35.6 [10.43]
3.0
35.1 [10.29]
3.1
34.6 [10.14]
3.2
IDB
34.1 [9.99]
3.3
33.6 [9.85]
3.4
60°F [15.5°C]
50
[10]
70°F [21.1°C]
Total BTUH [kW]
Power
43.7 [12.81]
2.7
80°F [26.7°C]
43.1 [12.63]
2.7
42.5 [12.46]
2.8
CFM [L/s]
42.9 [12.57]
3.0
42.3 [12.40]
3.1
1680 [793] 1400 [661] 1120 [529] 1680 [793] 1400 [661] 1120 [529] 1680 [793] 1400 [661] 1120 [529]
41.7 [12.22]
3.1
41.3 [12.10]
3.3
40.8 [11.96]
3.3
40.2 [11.78]
3.4
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
0
[-17.8]
Total BTUH [kW]
Power
9.5 [2.78]
2.0
9.4 [2.75]
2.1
9.3 [2.73]
2.1
8.7 [2.55]
2.3
8.6 [2.52]
2.4
8.5 [2.49]
2.5
7.1 [2.08]
2.6
7.0 [2.05]
2.7
6.9 [2.02]
2.7
5
[26.7]
Total BTUH [kW]
Power
13.9 [4.07]
2.1
13.7 [4.02]
2.1
13.5 [3.96]
2.2
13.1 [3.84]
2.4
12.9 [3.78]
2.5
12.7 [3.72]
2.5
11.5 [3.37]
2.7
11.4 [3.34]
2.7
11.2 [3.28]
2.8
10
[-12.2]
Total BTUH [kW]
Power
17.1 [5.01]
2.2
16.9 [4.95]
2.2
16.7 [4.89]
2.3
16.3 [4.78]
2.5
16.1 [4.72]
2.5
15.9 [4.66]
2.6
14.8 [4.34]
2.7
14.6 [4.28]
2.8
14.3 [4.19]
2.9
15
[32.2]
Total BTUH [kW]
Power
19.5 [5.71]
2.2
19.3 [5.66]
2.3
19.0 [5.57]
2.3
18.7 [5.48]
2.5
18.4 [5.39]
2.6
18.2 [5.33]
2.7
17.2 [5.04]
2.8
16.9 [4.95]
2.9
16.7 [4.89]
2.9
20
[-6.6]
Total BTUH [kW]
Power
21.5 [6.30]
2.3
21.2 [6.21]
2.3
20.9 [6.13]
2.4
20.6 [6.04]
2.6
20.4 [5.98]
2.7
20.1 [5.89]
2.7
19.1 [5.60]
2.9
18.8 [5.51]
2.9
18.6 [5.45]
3.0
25
[37.8]
Total BTUH [kW]
Power
23.3 [6.83]
2.3
23.0 [6.74]
2.4
22.7 [6.65]
2.5
22.5 [6.59]
2.7
22.2 [6.51]
2.7
21.8 [6.39]
2.8
20.9 [6.13]
2.9
20.6 [6.04]
3.0
20.3 [5.95]
3.1
30
[-1.1]
Total BTUH [kW]
Power
25.4 [7.44]
2.4
25.1 [7.36]
2.5
24.7 [7.24]
2.5
24.6 [7.21]
2.7
24.2 [7.09]
2.8
23.9 [7.00]
2.9
23.0 [6.74]
3.0
22.7 [6.65]
3.1
22.4 [6.56]
3.2
35
[43.3]
Total BTUH [kW]
Power
28.1 [8.24]
2.5
27.8 [8.15]
2.5
27.4 [8.03]
2.6
27.3 [8.00]
2.8
26.9 [7.88]
2.9
26.5 [7.77]
2.9
25.8 [7.56]
3.1
25.4 [7.44]
3.1
25.0 [7.33]
3.2
40
[4.4]
Total BTUH [kW]
Power
31.9 [9.35]
2.5
31.4 [9.20]
2.6
31.0 [9.09]
2.7
31.0 [9.09]
2.9
30.6 [8.97]
2.9
30.2 [8.85]
3.0
29.5 [8.65]
3.1
29.1 [8.53]
3.2
28.7 [8.41]
3.3
16
SYSTEMS PERFORMANCE—RJNA- SERIES
COOLING PERFORMANCE DATA—RJNA-A048
DR —Depression ratio
dbE —Entering air dry bulb
wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power—KW input
NOTES:
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
HEATING PERFORMANCE DATA—RJNA-A048
IDB—Indoor air dry bulb [ ] Designates Metric Conversions
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 1920 [906] 1600 [755] 1280 [604] 1920 [906] 1600 [755] 1280 [604] 1920 [906] 1600 [755] 1280 [604]
DR .18 .15 .11 .18 .15 .11 .18 .15 .11
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
59.9 [17.55]
35.6 [10.43]
2.7
57.8 [16.94]
32.6 [9.55]
2.6
55.7 [16.32]
29.5 [8.65]
2.6
56.2 [16.47]
43.0 [12.60]
2.7
54.3 [15.91]
39.3 [11.52]
2.7
52.3 [15.33]
35.6 [10.43]
2.6
53.5 [15.68]
46.0 [13.48]
2.7
51.7 [15.15]
42.0 [12.31]
2.6
49.8 [14.59]
38.1 [11.17]
2.6
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
58.7 [17.20]
35.1 [10.29]
2.9
56.6 [16.59]
32.1 [9.41]
2.8
54.5 [15.97]
29.1 [8.53]
2.8
55.0 [16.12]
42.5 [12.46]
2.9
53.1 [15.56]
38.8 [11.37]
2.8
51.2 [15.01]
35.2 [10.32]
2.8
52.3 [15.33]
45.5 [13.33]
2.9
50.5 [14.80]
41.6 [12.19]
2.8
48.7 [14.27]
37.7 [11.05]
2.8
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
57.4 [16.82]
34.6 [10.14]
3.0
55.4 [16.24]
31.6 [9.26]
3.0
53.4 [15.65]
28.7 [8.41]
3.0
53.8 [15.77]
41.9 [12.28]
3.1
51.9 [15.21]
38.3 [11.22]
3.0
50.0 [14.65]
34.7 [10.17]
3.0
51.1 [14.98]
44.9 [13.16]
3.0
49.3 [14.45]
41.1 [12.05]
3.0
47.5 [13.92]
37.2 [10.90]
2.9
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
56.1 [16.44]
33.9 [9.94]
3.2
54.1 [15.86]
31.0 [9.09]
3.2
52.1 [15.27]
28.1 [8.24]
3.1
52.5 [15.39]
41.2 [12.07]
3.2
50.6 [14.83]
37.7 [11.05]
3.2
48.8 [14.30]
34.2 [10.02]
3.1
49.8 [14.59]
44.2 [12.95]
3.2
48.0 [14.07]
40.4 [11.84]
3.2
46.3 [13.57]
36.7 [10.76]
3.1
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
54.7 [16.03]
33.1 [9.70]
3.4
52.8 [15.47]
30.3 [8.88]
3.4
50.9 [14.92]
27.5 [8.06]
3.3
51.1 [14.98]
40.4 [11.84]
3.4
49.3 [14.45]
37.0 [10.84]
3.4
47.5 [13.92]
33.5 [9.82]
3.3
48.4 [14.18]
43.5 [12.75]
3.4
46.7 [13.69]
39.7 [11.63]
3.3
45.0 [13.19]
36.0 [10.55]
3.3
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
53.3 [15.62]
32.3 [9.47]
3.6
51.4 [15.06]
29.6 [8.67]
3.5
49.5 [14.51]
26.8 [7.85]
3.5
49.6 [14.54]
39.6 [11.61]
3.6
47.9 [14.04]
36.3 [10.64]
3.5
46.2 [13.54]
32.9 [9.64]
3.5
46.9 [13.75]
42.7 [12.51]
3.6
45.3 [13.28]
39.0 [11.43]
3.5
43.6 [12.78]
35.4 [10.37]
3.5
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
51.7 [15.15]
31.5 [9.23]
3.8
49.9 [14.62]
28.8 [8.44]
3.7
48.1 [14.10]
26.1 [7.65]
3.6
48.1 [14.10]
38.8 [11.37]
3.8
46.4 [13.60]
35.5 [10.40]
3.7
44.7 [13.10]
32.2 [9.44]
3.7
45.4 [13.31]
41.9 [12.28]
3.7
43.8 [12.84]
38.3 [11.22]
3.7
42.2 [12.37]
34.7 [10.17]
3.6
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
50.2 [14.71]
30.7 [9.00]
3.9
48.4 [14.18]
28.1 [8.24]
3.9
46.6 [13.66]
25.5 [7.47]
3.8
46.5 [13.63]
38.0 [11.14]
4.0
44.9 [13.16]
34.8 [10.20]
3.9
43.3 [12.69]
31.5 [9.23]
3.8
43.8 [12.84]
41.0 [12.02]
3.9
42.3 [12.40]
37.5 [10.99]
3.9
40.8 [11.96]
34.0 [9.96]
3.8
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
48.5 [14.21]
29.9 [8.76]
4.1
46.8 [13.72]
27.4 [8.03]
4.0
45.1 [13.22]
24.8 [7.27]
4.0
44.9 [13.16]
37.2 [10.90]
4.1
43.3 [12.69]
34.1 [9.99]
4.1
41.7 [12.22]
30.9 [9.06]
4.0
42.2 [12.37]
40.3 [11.81]
4.1
40.7 [11.93]
36.8 [10.79]
4.0
39.2 [11.49]
33.4 [9.79]
4.0
45
[46.1]
Total BTUH [kW]
Power
44.2 [12.95]
2.8
43.6 [12.78]
2.9
43.0 [12.60]
2.9
43.7 [12.81]
3.1
43.1 [12.63]
3.2
42.5 [12.46]
3.3
42.7 [12.51]
3.5
IDB
42.1 [12.34]
3.6
41.5 [12.16]
3.7
60°F [15.5°C]
50
[10]
70°F [21.1°C]
Total BTUH [kW]
Power
47.2 [13.83]
2.8
80°F [26.7°C]
46.5 [13.63]
2.9
45.8 [13.42]
3.0
CFM [L/s]
46.6 [13.66]
3.2
46.0 [13.48]
3.3
1440 [680] 1200 [566] 960 [453] 1440 [680] 1200 [566] 960 [453] 1440 [680] 1200 [566] 960 [453]
45.3 [13.28]
3.3
45.6 [13.36]
3.5
45.0 [13.19]
3.6
44.3 [12.98]
3.7
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
0
[-17.8]
Total BTUH [kW]
Power
13.5 [3.96]
2.4
13.3 [3.90]
2.4
13.1 [3.84]
2.5
13.0 [3.81]
2.7
12.8 [3.75]
2.8
12.6 [3.69]
2.8
12.0 [3.52]
3.1
11.8 [3.46]
3.1
11.6 [3.40]
3.2
5
[26.7]
Total BTUH [kW]
Power
17.3 [5.07]
2.4
17.1 [5.01]
2.5
16.8 [4.92]
2.6
16.8 [4.92]
2.8
16.5 [4.84]
2.8
16.3 [4.78]
2.9
15.8 [4.63]
3.1
15.5 [4.54]
3.2
15.3 [4.48]
3.3
10
[-12.2]
Total BTUH [kW]
Power
21.0 [6.15]
2.5
20.7 [6.07]
2.5
20.4 [5.98]
2.6
20.5 [6.01]
2.8
20.2 [5.92]
2.9
19.9 [5.83]
2.9
19.5 [5.71]
3.2
19.2 [5.63]
3.2
18.9 [5.54]
3.3
15
[32.2]
Total BTUH [kW]
Power
24.6 [7.21]
2.5
24.3 [7.12]
2.6
23.9 [7.00]
2.6
24.1 [7.06]
2.8
23.7 [6.95]
2.9
23.4 [6.86]
3.0
23.1 [6.77]
3.2
22.7 [6.65]
3.3
22.4 [6.56]
3.4
20
[-6.6]
Total BTUH [kW]
Power
28.1 [8.24]
2.6
27.7 [8.12]
2.6
27.3 [8.00]
2.7
27.6 [8.09]
2.9
27.2 [7.97]
3.0
26.8 [7.85]
3.0
26.6 [7.80]
3.3
26.2 [7.68]
3.3
25.8 [7.56]
3.4
25
[37.8]
Total BTUH [kW]
Power
31.5 [9.23]
2.6
31.1 [9.11]
2.7
30.6 [8.97]
2.7
31.0 [9.09]
2.9
30.6 [8.97]
3.0
30.1 [8.82]
3.1
30.0 [8.79]
3.3
29.6 [8.67]
3.4
29.1 [8.53]
3.5
30
[-1.1]
Total BTUH [kW]
Power
34.8 [10.20]
2.7
34.3 [10.05]
2.7
33.9 [9.94]
2.8
34.3 [10.05]
3.0
33.8 [9.91]
3.1
33.3 [9.76]
3.1
33.3 [9.76]
3.3
32.8 [9.61]
3.4
32.4 [9.50]
3.5
35
[43.3]
Total BTUH [kW]
Power
38.1 [11.17]
2.7
37.5 [10.99]
2.8
37.0 [10.84]
2.8
37.5 [10.99]
3.0
37.0 [10.84]
3.1
36.5 [10.70]
3.2
36.5 [10.70]
3.4
36.0 [10.55]
3.5
35.5 [10.40]
3.6
40
[4.4]
Total BTUH [kW]
Power
41.2 [12.07]
2.8
40.6 [11.90]
2.8
40.0 [11.72]
2.9
40.7 [11.93]
3.1
40.1 [11.75]
3.2
39.5 [11.58]
3.2
39.7 [11.63]
3.4
39.1 [11.46]
3.5
38.5 [11.28]
3.6
17
SYSTEMS PERFORMANCE—RJNA- SERIES
COOLING PERFORMANCE DATA—RJNA-A060
HEATING PERFORMANCE DATA—RJNA-A060
DR —Depression ratio
dbE —Entering air dry bulb
wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power—KW input
NOTES:
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
IDB—Indoor air dry bulb [ ] Designates Metric Conversions
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 2500 [1180] 2000 [944] 1500 [708] 2500 [1180] 2000 [944] 1500 [708] 2500 [1180] 2000 [944] 1500 [708]
DR .22 .19 .15 .22 .19 .15 .22 .19 .15
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
74.9 [21.95]
44.2 [12.95]
4.0
71.6 [20.98]
39.6 [11.61]
3.9
68.4 [20.05]
35.0 [10.26]
3.8
71.3 [20.90]
53.4 [15.65]
3.9
68.2 [19.99]
47.8 [14.01]
3.9
65.1 [19.08]
42.3 [12.40]
3.8
67.6 [19.81]
57.5 [16.85]
3.9
64.6 [18.93]
51.5 [15.09]
3.8
61.7 [18.08]
45.5 [13.33]
3.8
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
74.4 [21.80]
44.3 [12.98]
4.2
71.2 [20.87]
39.7 [11.63]
4.1
67.9 [19.90]
35.0 [10.26]
4.1
70.8 [20.75]
53.5 [15.68]
4.2
67.7 [19.84]
47.9 [14.04]
4.1
64.6 [18.93]
42.3 [12.40]
4.0
67.1 [19.67]
57.6 [16.88]
4.1
64.2 [18.82]
51.5 [15.09]
4.1
61.2 [17.94]
45.5 [13.33]
4.0
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
73.3 [21.48]
43.8 [12.84]
4.5
70.2 [20.57]
39.2 [11.49]
4.4
67.0 [19.64]
34.7 [10.17]
4.3
69.7 [20.43]
53.0 [15.53]
4.4
66.7 [19.55]
47.5 [13.92]
4.3
63.6 [18.64]
41.9 [12.28]
4.2
66.0 [19.34]
57.1 [16.73]
4.4
63.1 [18.49]
51.1 [14.98]
4.3
60.3 [17.67]
45.2 [13.25]
4.2
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
71.8 [21.04]
43.0 [12.60]
4.7
68.7 [20.13]
38.5 [11.28]
4.6
65.6 [19.23]
34.0 [9.96]
4.5
68.2 [19.99]
52.2 [15.30]
4.6
65.2 [19.11]
46.7 [13.69]
4.5
62.3 [18.26]
41.3 [12.10]
4.4
64.5 [18.90]
56.3 [16.50]
4.6
61.7 [18.08]
50.4 [14.77]
4.5
58.9 [17.26]
44.5 [13.04]
4.4
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
70.0 [20.51]
41.9 [12.28]
4.9
67.0 [19.64]
37.5 [10.99]
4.8
63.9 [18.73]
33.2 [9.73]
4.7
66.4 [19.46]
51.1 [14.98]
4.8
63.5 [18.61]
45.8 [13.42]
4.7
60.6 [17.76]
40.4 [11.84]
4.6
62.7 [18.38]
55.2 [16.18]
4.8
60.0 [17.58]
49.4 [14.48]
4.7
57.2 [16.76]
43.7 [12.81]
4.6
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
68.0 [19.93]
40.7 [11.93]
5.1
65.1 [19.08]
36.5 [10.70]
5.0
62.1 [18.20]
32.2 [9.44]
4.9
64.4 [18.87]
49.9 [14.62]
5.1
61.6 [18.05]
44.7 [13.10]
5.0
58.8 [17.23]
39.5 [11.58]
4.9
60.7 [17.79]
54.0 [15.83]
5.0
58.1 [17.03]
48.4 [14.18]
4.9
55.4 [16.24]
42.7 [12.51]
4.8
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
66.0 [19.34]
39.6 [11.61]
5.4
63.1 [18.49]
35.4 [10.37]
5.3
60.3 [17.67]
31.3 [9.17]
5.1
62.4 [18.29]
48.8 [14.30]
5.3
59.7 [17.50]
43.7 [12.81]
5.2
56.9 [16.68]
38.6 [11.31]
5.1
58.7 [17.20]
52.8 [15.47]
5.3
56.1 [16.44]
47.3 [13.86]
5.2
53.6 [15.71]
41.8 [12.25]
5.1
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
64.1 [18.79]
38.5 [11.28]
5.6
61.3 [17.97]
34.5 [10.11]
5.5
58.5 [17.14]
30.5 [8.94]
5.4
60.5 [17.73]
47.7 [13.98]
5.5
57.8 [16.94]
42.7 [12.51]
5.4
55.2 [16.18]
37.8 [11.08]
5.3
56.8 [16.65]
51.8 [15.18]
5.5
54.3 [15.91]
46.4 [13.60]
5.4
51.8 [15.18]
41.0 [12.02]
5.3
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
62.4 [18.29]
37.8 [11.08]
5.8
59.7 [17.50]
33.8 [9.91]
5.7
57.0 [16.71]
29.9 [8.76]
5.6
58.8 [17.23]
47.0 [13.77]
5.7
56.2 [16.47]
42.1 [12.34]
5.6
53.7 [15.74]
37.2 [10.90]
5.5
55.1 [16.15]
51.1 [14.98]
5.7
52.7 [15.44]
45.7 [13.39]
5.6
50.3 [14.74]
40.4 [11.84]
5.5
45
[46.1]
Total BTUH [kW]
Power
59.9 [17.55]
3.8
58.9 [17.26]
3.9
57.8 [16.94]
4.1
58.3 [17.09]
4.2
57.3 [16.79]
4.4
56.3 [16.50]
4.5
58.2 [17.06]
4.7
IDB
57.2 [16.76]
4.9
56.2 [16.47]
5.0
60°F [15.5°C]
50
[10]
70°F [21.1°C]
Total BTUH [kW]
Power
63.1 [18.49]
3.9
80°F [26.7°C]
62.0 [18.17]
4.0
60.9 [17.85]
4.1
CFM [L/s]
61.5 [18.02]
4.3
60.4 [17.70]
4.5
2500 [1180] 2000 [944] 1500 [708] 2500 [1180] 2000 [944] 1500 [708] 2500 [1180] 2000 [944] 1500 [708]
59.3 [17.38]
4.6
61.4 [17.99]
4.8
60.4 [17.70]
5.0
59.3 [17.38]
5.1
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
0
[-17.8]
Total BTUH [kW]
Power
16.6 [4.86]
3.0
16.3 [4.78]
3.1
16.0 [4.69]
3.2
15.0 [4.40]
3.4
14.7 [4.31]
3.5
14.4 [4.22]
3.7
14.9 [4.37]
3.9
14.6 [4.28]
4.1
14.4 [4.22]
4.2
5
[26.7]
Total BTUH [kW]
Power
22.7 [6.65]
3.1
22.3 [6.54]
3.2
21.9 [6.42]
3.3
21.1 [6.18]
3.5
20.7 [6.07]
3.6
20.3 [5.95]
3.7
21.0 [6.15]
4.0
20.6 [6.04]
4.2
20.3 [5.95]
4.3
10
[-12.2]
Total BTUH [kW]
Power
28.5 [8.35]
3.2
28.0 [8.21]
3.3
27.5 [8.06]
3.4
26.9 [7.88]
3.6
26.4 [7.74]
3.7
25.9 [7.59]
3.8
26.8 [7.85]
4.1
26.3 [7.71]
4.2
25.9 [7.59]
4.4
15
[32.2]
Total BTUH [kW]
Power
34.0 [9.96]
3.3
33.4 [9.79]
3.4
32.8 [9.61]
3.5
32.3 [9.47]
3.7
31.8 [9.32]
3.8
31.2 [9.14]
3.9
32.3 [9.47]
4.2
31.7 [9.29]
4.3
31.1 [9.11]
4.5
20
[-6.6]
Total BTUH [kW]
Power
39.1 [11.46]
3.4
38.4 [11.25]
3.5
37.7 [11.05]
3.6
37.5 [10.99]
3.8
36.8 [10.79]
3.9
36.2 [10.61]
4.0
37.4 [10.96]
4.3
36.8 [10.79]
4.4
36.1 [10.58]
4.6
25
[37.8]
Total BTUH [kW]
Power
43.9 [12.87]
3.5
43.2 [12.66]
3.6
42.4 [12.43]
3.7
42.3 [12.40]
3.9
41.5 [12.16]
4.0
40.8 [11.96]
4.1
42.2 [12.37]
4.4
41.5 [12.16]
4.5
40.7 [11.93]
4.7
30
[-1.1]
Total BTUH [kW]
Power
48.4 [14.18]
3.5
47.6 [13.95]
3.7
46.7 [13.69]
3.8
46.8 [13.72]
4.0
46.0 [13.48]
4.1
45.1 [13.22]
4.2
46.7 [13.69]
4.5
45.9 [13.45]
4.6
45.1 [13.22]
4.8
35
[43.3]
Total BTUH [kW]
Power
52.6 [15.42]
3.6
51.7 [15.15]
3.7
50.7 [14.86]
3.9
50.9 [14.92]
4.0
50.1 [14.68]
4.2
49.2 [14.42]
4.3
50.9 [14.92]
4.6
50.0 [14.65]
4.7
49.1 [14.39]
4.8
40
[4.4]
Total BTUH [kW]
Power
56.4 [16.53]
3.7
55.4 [16.24]
3.8
54.5 [15.97]
4.0
54.8 [16.06]
4.1
53.8 [15.77]
4.3
52.9 [15.50]
4.4
54.7 [16.03]
4.6
53.8 [15.77]
4.8
52.8 [15.47]
4.9
18
SYSTEMS PERFORMANCE—RJNA- SERIES
External Static Pressure—Inches W.C. [kPa]
CFM [L/s] Air Delivery/RPM/Watts—208 Volts Side Discharge—Wet Coil
4.0
[14.07] Low
Blower Size/
Motor
HP [w] &
# of Speeds
Nominal
Cooling
Capacity
Tons [kW]
3.5
[12.30]
Factory
Motor
Speed
1400/1800
Manufacturer
Recommended
Air-Flow Range
(Min/Max) CFM
Motor
Speed
10x10
1/2 HP [373]
3 Speed Motor
High
CFM
Low
1766 [833] 1719 [811] 1671 [789] 1617 [763]
1225/1575
10x10
1/2 HP [373]
3 Speed Motor
1550 [732] 1465 [691]
10x10
1/2 HP [373]
3 Speed Motor
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
Watts 735 719 697 671 639 603
Watts 493 481 468 452 431 402
Med
CFM 1397 [659] 1344 [634] 1319 [622] 1297 [612] 1249 [589] 1147 [541]
3.0
[10.55] Low 1050/1350 Low
CFM 1275 [602] 1235 [583] 1210 [571] 1181 [557] 1132 [534] 1045 [493]
Watts 561 537 522 508 488 454
0.8 [.20] 0.9 [.22] 1.0 [.25]
5.0
[17.6]
High
CFM
Low
2185 [1031] 2148 [1014] 2112 [997] 2076 [980]
1750/2250
11x9
1 HP [746]
2 Speed
Motor 2040 [963] 2005 [946] 1970 [930]
780
1935 [913]
Watts 675 685 700 720 735 750 770 805
1900 [897]
Low
CFM 1974 [932] 1935 [913] 1897 [895] 1860 [878] 1823 [860] 1788 [844] 1753 [827]
605
1719 [811]
Watts 490 505 510 545 555 575 600 625
1686 [796]
DIRECT-DRIVE BLOWER 208 AIRFLOW PERFORMANCE
External Static Pressure—Inches W.C. [kPa]
CFM [L/s] Air Delivery/RPM/Watts—230/460 Volts Side Discharge—Wet Coil
4.0
[14.07] High
Blower Size/
Motor
HP [w] &
# of Speeds
Nominal
Cooling
Capacity
Tons [kW]
3.5
[12.30]
Factory
Motor
Speed
1400/1800
Manufacturer
Recommended
Air-Flow Range
(Min/Max) CFM
Motor
Speed
10x10
1/2 HP [373]
3 Speed
Motor
Med
CFM
Med.
1964 [927] 1902 [898] 1839 [868] 1771 [836]
1225/1575
10x10
1/2 HP [373]
3 Speed
Motor
1693 [799] 1602 [756]
10x10
1/2 HP [373]
3 Speed
Motor
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
Watts 847 811 780 751 721 688
*5.0*
[17.6]
High
CFM
Low
2185 [1031] 2148 [1014] 2112 [997] 2076 [980]
1750/2250
11x9
1 HP [746]
2 Speed
Motor 2040 [963] 2005 [946] 1970 [930]
780
1935 [913]
Watts 675 685 700 720 735 750 770 805
1900 [897]
Low
CFM 1974 [932] 1935 [913] 1897 [895] 1860 [878] 1823 [860] 1788 [844] 1753 [827]
605
1719 [811]
Watts 490 505 510
Watts 578 565 549 528 502 472
545 555
Med
CFM 1601 [756] 1561 [737] 1517 [716] 1466 [692] 1401 [661] 1317 [622]
3.0
[10.55] Low 1050/1350 Low
CFM 1455 [687] 1423 [672] 1388 [655] 1345 [635] 1289 [608]
575
1214 [573]
Watts 659 636 613 589 562 529
600 625
1686 [796]
0.8 [.20] 0.9 [.22] 1.0 [.25]
DIRECT-DRIVE BLOWER 230/460 AIRFLOW PERFORMANCE
19
AIRFLOW PERFORMANCE—RJNA- SERIES
*There is not a 5-ton 460 Volt Direct Drive.
[ ] Designates Metric Conversions
20
AIRFLOW PERFORMANCE—RJNA- SERIES
825
Models RJNA-A036 [10.55 kW] & A042 [12.31 kW]—Heat Pump (13 SEER)
External Static Pressure—Inches of Water [kPa]
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] 0.8 [.20] 0.9 [.22] 1.0 [.25] 1.1 [.27] 1.2 [.30] 1.3 [.32] 1.4 [.35] 1.5 [.37]
RPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM W
900 [425] 665 290 730 300 780 315 830 330 875 360 920 375 960 390 990 410 1040 445 1080 470 1140 510 1190 540 1235 590
1000 [472] 625 275 680 295 750 310 805 325 850 345 895 375 935 390 970 410 1015 435 1065 465 1100 500 1160 530 1210 560 1255 610
1100 [519] 640 300 710 315 780 325 830 340 875 365 915 390 955 405 990 430 1040 450 1080 485 1115 540 1180 540 1230 600 1270 630
1200 [566] 670 315 735 330 800 345 850 365 890 385 935 410 975 430 1010 450 1060 475 1100 520 1145 560 1200 600 1250 630 1285 660
1300 [614] 625 315 700 330 770 350 830 370 875 400 915 415 955 440 990 450 1040 495 1085 530 1125 565 1165 590 1220 645 1260 675 1305 710
1400 [661] 655 340 730 365 795 385 850 400 890 430 935 445 975 470 1010 500 1070 540 1110 575 1150 615 1195 645 1230 685 1280 725 1325 760
1500 [708] 685 380 755 390 415 870 435 915 450 955 480 990 505 1040 545 1090 590 1135 630 1180 660 1220 720 1255 740 1295 785 1350 820
1600 [755] 730 420 790 435 850 455 890 490 935 505 970 525 1005 550 1075 605 1110 640 1160 680 1200 730 1245 780 1280 800 1325 840 1365 885
1700 [802] 755 465 825 475 875 505 915 535 955 550 985 570 1040 630 1100 685 1135 710 1185 750 1225 800 1265 830 1295 875 1350 910 — —
1800 [850] 790 500 850 530 890 550 935 570 975 600 1020 650 1080 690 1125 740 1165 770 1210 830 1245 870 1290 910 1310 930 — —
Voltage 208/230-460—3 Phase
Air
Flow
CFM [L/s]
Drive Package L M N (Field-Supplied)
Motor H.P. [w] 1/2 [373] (3/4 [559] - 575V) 3/4 [559] 3/4 [559]
Blower Sheave 6.9 Pitch Diameter 6.4 Pitch Diameter 6.4 Pitch Diameter
Motor Sheave Adjustable 2.4-3.4 Pitch Diameter Adjustable 3.4-4.4 Pitch Diameter Adjustable 4.0-5.0 Pitch Diameter
Turns Open 0 1 23 4 5 6 0 1 2 3 45 6
RPM 935 875 830 780 730 680 625 1295 1230 1185 1135 1085 1000 955 RPM Range 1090-1365
Factory sheave settings are shown in bold print.
BELT-DRIVE AIRFLOW PERFORMANCE
NOTE: Bold lines separate L, M and N drives respectively.
1160
1275
895
Models RJNA-A048 [14.06 kW]—Heat Pump (13 SEER)
RPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM W
1200 [566] 745 340 810 375 390 900 400 945 420 1000 440 1040 460 1075 490 1115 540 1170 580 1215 620 1260 650 1300 685
1300 [614] 695 330 770 365 835 395 880 415 920 435 975 455 1010 470 1060 490 1100 530 1140 570 1190 600 1235 640 1270 685 1315 740
1400 [661] 725 350 795 395 855 420 895 435 945 455 995 470 1030 500 1070 520 1115 560 600 1205 640 1250 685 1290 745 1335 810
1500 [708] 690 360 750 390 820 425 875 450 920 465 970 480 1010 500 1055 560 1100 580 1140 630 1180 660 1230 700 1270 760 1315 815 1350 865
1600 [755] 720 390 780 430 850 460 895 480 945 500 990 530 1035 565 1075 590 1115 635 1160 680 1205 725 1250 770 1290 830 1335 890 1365 935
1700 [802] 750 430 810 465 870 485 920 500 970 530 1015 570 1055 600 1090 645 1140 695 1180 735 1225 790 1270 845 1315 910 1350 960 — —
1800 [850] 780 475 840 515 540 945 555 990 600 1035 625 1080 660 1115 710 1155 740 1205 800 1250 860 1295 930 1340 995 1365 1030 — —
1900 [897] 820 520 870 560 925 580 970 600 1015 640 1060 690 1115 750 1145 790 1185 835 1225 880 900 1315 1010 1355 1060 — — — —
2000 [944] 850 585 900 610 950 630 1000 665 1045 715 1090 760 1130 810 1170 865 1205 900 1255 965 1300 1050 1340 1100 1365 1140 — — — —
865
External Static Pressure—Inches of Water [kPa]
Air
Flow
CFM [L/s]
Voltage 208/230-460—3 Phase
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] 0.8 [.20] 0.9 [.22] 1.0 [.25] 1.1 [.27] 1.2 [.30] 1.3 [.32] 1.4 [.35] 1.5 [.37]
Factory sheave settings are shown in bold print.
Note: See component air resistance table in this manual.
[ ] Designates Metric Conversions
NOTE: Bold lines separate L, M and N drives respectively.
Drive Package L M N (Field-Supplied)
Motor H.P. [w] 1/2 [373] (3/4 [559] - 575V) 3/4 [559] 3/4 [559]
Blower Sheave 6.9 Pitch Diameter 6.4 Pitch Diameter 6.4 Pitch Diameter
Motor Sheave Adjustable 2.8-3.8 Pitch Diameter Adjustable 3.4-4.4 Pitch Diameter Adjustable 4.0-5.0 Pitch Diameter
Turns Open 012 3 4 5 6 0 1 23 4 5 6
RPM 990 945 895 850 800 750 695 1270 1225 1170 1115 1065 1015 965 RPM Range 1090-1365
BELT-DRIVE AIRFLOW PERFORMANCE
BELT-DRIVE AIRFLOW PERFORMANCE
COMPONENT AIR RESISTANCE
NOTES:
1. Performance shown with dry coil, standard 1" [25.4 mm] filters & side discharge. Add component resistance to determine total E.S.P.
2. Standard CFM @ .075 lbs./cu. ft.
3. Motor efficiency = 80%
4. BHP = Watts x Motor Eff.
746
[ ] Designates Metric Conversions
Factory sheave settings are shown in bold print.
External Static Pressure—Inches of Water [kPa]
Model RJNA-A060 [17.58 kW]—Heat Pump (13 SEER)
Voltage 208/230-460—3 Phase
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] 0.8 [.20] 0.9 [.22] 1.0 [.25] 1.1 [.27] 1.2 [.30] 1.3 [.32] 1.4 [.35] 1.5 [.37]
RPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM WRPM W
1400 [661] — — — — 780 370 815 385 875 425 930 460 970 490 1030 540 1065 570 1105 595 1150 615 1195 645 1235 660 1300 705 1340 745
1500 [708] — — — — 795 405 840 415 895 440 945 500 995 540 1045 595 1080 615 1135 650 1165 675 1215 700 1255 735 1320 775 1355 805
1600 [755] — — 780 390 805 425 870 470 915 510 965 560 1015 600 1060 640 1105 680 1145 705 1180 730 1225 750 1275 790 1340 840 1365 880
1700 [802] — — 795 450 840 490 895 530 940 570 990 605 1035 640 1075 680 1120 725 1160 755 1200 790 1245 815 1300 855 1355 905 1375 940
1800 [850] 780 455 815 470 870 540 915 540 965 675 1010 660 1055 710 1100 760 1140 785 1175 810 1225 850 1260 880 1320 930 1365 985 1390 1020
1900 [897] 800 485 850 530 895 590 945 640 995 675 1035 720 1070 775 1120 810 1160 850 1200 890 1245 915 1290 960 1335 1000 1375 1050 1405 1100
2000 [944] 830 550 880 605 930 655 970 700 1015 730 1055 790 1105 830 1145 875 1180 910 1225 950 1260 980 1320 1035 1350 1075 1385 1120 — —
2100 [991] 860 615 915 655 955 705 1005 760 1040 820 1090 870 1130 910 1170 950 1210 995 1250 1020 1290 1060 1335 1100 1370 1150 1400 1200 — —
2200 [1038] 895 680 945 735 995 780 1030 830 1060 880 1120 940 1155 980 1195 1020 1240 1055 1275 1100 1320 1140 1360 1180 1385 1225 — — — —
2300 [1085] 940 755 975 795 1015 830 1065 910 1100 965 1150 1025 1180 1050 1225 1095 1265 1125 1310 1175 1350 1230 1375 1260 1405 1320 — — —
2400 [1133] 970 825 1015 880 1040 925 1100 1005 1145 1055 1175 1085 1225 1140 1260 1175 1300 1210 1340 1255 1370 1315 1400 1375 — — — — —
Air
Flow
CFM [L/s]
Drive Package L M
Motor H.P. [w] 3/4 [559] 1 [746]
Blower Sheave 6.4 Pitch Diameter 6.4 Pitch Diameter
Motor Sheave Adjustable 2.8-3.8 Pitch Diameter Adjustable 3.4-4.4 Pitch Diameter
Turns Open 0 1 23 4 5 6 0 1 2 34 5 6
RPM 1095 1040 995 940 890 835 780 1405 1360 1305 1250 1195 1145 1095
Component
Standard Indoor Airflow—CFM [L/s]
1000 [472] 1200 [566] 1400 [661] 1600 [755] 1800 [850] 2000 [944] 2200 [1038] 2400 [1133]
Resistance—Inches Water [kPa]
Wet Coil .035 .040 .060 .070 .085 .100 .110 .120
Downflow .055 .060 .066 .072 .080 .086 .093 .100
Economizer
R.A. Damper .05 .06 .07 .08 .09 .10 .11 .12
NOTE: L-Drive left of bold line, M-Drive right of bold line.
21
AIRFLOW PERFORMANCE—RJNA- SERIES
ELECTRICAL DATA – RJNA SERIES
Minimum Circuit
Ampacity 19/19
Unit Information
Unit Operating
Voltage Range 187-253
Minimum Overcurrent
Protection Device Size 25/25
Maximum Overcurrent
Protection Device Size 25/25
Compressor Motor
No. 1
Volts 208/230
Phase 3
HP 2.5
RPM 3450
Amps (RLA) 9.6/9.6
Amps (LRA) 77/77
Condenser Motor
No. 1
Volts 208/230
Phase 1
HP 1/3
Amps (FLA) 2.2
Amps (LRA) 4.7
Evaporator Fan
No. 1
Volts 208/230
Phase 1
HP 1/2
Amps (FLA) 2.7
Amps (LRA) 6.5 10.6
2.2
1/2
3
208/230
1
4.7
2.2
1/3
1
208/230
1
77/77
9.6/9.6
3450
2.5
3
208/230
1
25/25
20/20
18/18
187-253
16.8
3.2
3/4
3
208/230
1
4.7
2.2
1/3
1
208/230
1
77/77
9.6/9.6
3450
2.5
3
208/230
1
25/25
25/25
19/19
187-253
3.6
1.5
1/2
1
460
1
2.4
1
1/3
1
460
1
35
4.8
3450
2.5
3
460
1
15
15
9
414-506
5.3
1.1
1/2
3
460
1
2.4
1
1/3
1
460
1
35
4.8
3450
2.5
3
460
1
15
15
9
414-506
8.4
1.6
3/4
3
460
1
2.4
1
1/3
1
460
1
35
4.8
3450
2.5
3
460
1
15
15
9
414-506
6.5
2.7
1/2
1
208/230
1
4.7
2.2
1/3
1
208/230
1
83/83
15/15
3450
2.5
1
208/230
1
35/35
30/30
25/25
187-253
6.5
2.7
1/2
1
208/230
1
4.7
2.2
1/3
1
208/230
1
77/77
10.3/10.3
3450
3
3
208/230
1
25/25
25/25
20/20
187-253
10.6
2.2
1/2
3
208/230
1
4.7
2.2
1/3
1
208/230
1
77/77
10.3/10.3
3450
3
3
208/230
1
25/25
25/25
19/19
187-253
16.8
3.2
3/4
3
208/230
1
4.7
2.2
1/3
1
208/230
1
77/77
10.3/10.3
3450
3
3
208/230
1
25/25
25/25
20/20
187-253
3.6
1.5
1/2
1
460
1
2.4
1
1/3
1
460
1
39
5.1
3450
3
3
460
1
15
15
10
414-506
5.3
1.1
1/2
3
460
1
2.4
1
1/3
1
460
1
39
5.1
3450
3
3
460
1
15
15
10
414-506
8.4
1.6
3/4
3
460
1
2.4
1
1/3
1
460
1
39
5.1
3450
3
3
460
1
15
15
10
414-506
6.5
2.7
1/2
1
208/230
1
4.7
2.2
1/3
1
208/230
1
95/95
16.5/16.5
3450
3
1
208/230
1
40/40
35/35
27/27
187-253
-A036CK -A036CL -A036CM -A036DK -A036DL -A036DM -A036JK -A042CK -A042CL -A042CM -A042DK -A042DL -A042DM -A042JK
1. Horsepower Per Compressor.
2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.
22
ELECTRICAL DATA—RJNA- SERIES
ELECTRICAL DATA – RJNA SERIES
Minimum Circuit
Ampacity
Minimum Overcurrent
Protection Device Size
22/22
25/25
Maximum Overcurrent
Protection Device Size 30/30
Compressor Motor
No. 1
Volts 208/230
Phase 3
HP 3.5
RPM 3450
Amps (RLA) 12.4/12.4
Amps (LRA)
Unit Information
Unit Operating
Voltage Range
88/88
187-253
Condenser Motor
No. 1
Volts 208/230
Phase 1
HP 1/3
Amps (FLA) 2.2
Amps (LRA) 4.7
Evaporator Fan
No. 1
Volts 208/230
Phase 1
HP 1/2
Amps (FLA) 2.7
Amps (LRA) 6.5 24
3.8
1
3
10.6
2.2
1/2
3
208/230
1
4.7
2.2
1/3
1
208/230
1
88/88
12.4/12.4
3450
3.5
3
208/230
1
30/30
25/25
21/21
187-253
208/230
16.8
3.2
3/4
3
208/230
1
4.7
2.2
1/3
1
208/230
1
88/88
12.4/12.4
3450
3.5
3
208/230
1
30/30
25/25
22/22
187-253
1
3.6
1.5
1/2
1
460
1
2.4
1
1/3
1
460
1
44
6.4
3450
3.5
3
460
1
15
15
11
414-506
4.7
5.3
1.1
1/2
3
460
1
2.4
1
1/3
1
460
1
44
6.4
3450
3.5
3
460
1
15
15
11
414-506
2.2
8.4
1.6
3/4
3
460
1
2.4
1
1/3
1
460
1
44
6.4
3450
3.5
3
460
1
15
15
11
414-506
1/3
6.5
2.7
1/2
1
208/230
1
4.7
2.2
1/3
1
208/230
1
109/109
18.3/18.3
3450
3.5
1
208/230
1
45/45
35/35
30/30
187-253
1
0
7.6
1
1
208/230
1
4.7
2.2
1/3
1
208/230
1
123/123
17.3/17.3
3450
5
3
208/230
1
45/45
40/40
32/32
187-253
208/230
16.8
3.2
3/4
3
208/230
1
4.7
2.2
1/3
1
208/230
1
123/123
17.3/17.3
3450
5
3
208/230
1
45/45
35/35
28/28
187-253
1
123/123
17.3/17.3
3450
5
3
208/230
1
45/45
35/35
28/28
187-253
8.4
1.6
3/4
3
460
1
2.4
1
1/3
1
460
1
62
8.2
3450
5
3
460
1
20
20
14
414-506
12
1.9
1
3
460
1
2.4
1
1/3
1
460
1
62
8.2
3450
5
3
460
1
20
20
14
414-506
0
7.6
1
1
208/230
1
4.7
2.2
1/3
1
208/230
1
148/148
28.8/28.8
3450
5
1
208/230
1
60/60
60/60
46/46
187-253
-A048CK -A048CL -A048CM -A048DK -A048DL -A048DM -A048JK -A060CK -A060CL -A060CM -A060DL -A060DM -A060JK
1. Horsepower Per Compressor.
2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.
23
ELECTRICAL DATA—RJNA- SERIES
24
UNITS WITH HEATER KITS—RJNA- SERIES
*A10C+
*A10C+ 7.2/9.6 24.56/32.75 20.0/23.1 44/48 45/45 50/50
*A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 69/76 70/70 80/80
*A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 48/52 50/50 60/60
*A15C+ 10.8/14.4 36.84/49.13 30.1/34.7 56/62 60/60 70/70
*A21C+ 14.4/19.2 49.13/65.51 40.1/46.2 69/76 70/70 80/80
7.2/9.6
A036CK
No Heat 19/19 25/25 25/25
24.56/32.75 20.0/23.1 45/48
*A06C+ 4.2/5.6 14.33/19.10 11.7/13.5 33/36 35/35 40/40
45/45 50/50
*A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 70/77 70/70 80/80
*A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 49/53 50/50 60/60
*A15C+ 10.8/14.4 36.84/49.13 30.1/34.7 57/63 60/60 70/70
*A21C+ 14.4/19.2 49.13/65.51 40.1/46.2 70/77 70/70 80/80
A042CK
No Heat 20/20 25/25 25/25
*A06C+ 4.2/5.6 14.33/19.10 11.7/13.5 34/36 35/40 40/40
*A11C+ 7.2/9.6 24.56/32.75 20.0/23.1 45/48 45/45 50/50
*A10C+
*A10C+
*A11C+ 7.2/9.6 24.56/32.75 20.0/23.1 44/48 45/45 50/50
7.2/9.6 24.56/32.75 20.0/23.1 47/51 50/50 60/60
*A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 72/80 80/80 80/80
*A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 51/56 60/60 60/60
*A15C+ 10.8/14.4 36.84/49.13 30.1/34.7 60/66 60/60 70/70
*A21C+ 14.4/19.2 49.13/65.51 40.1/46.2 72/80 80/80 80/80
7.2/9.6
A048CK
No Heat 22/22 25/30 25/30
24.56/32.75 20.0/23.1 57/61
*A06C+ 4.2/5.6 14.33/19.10 11.7/13.5 37/39 40/45 40/45
60/60 70/70
*A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 82/90 90/90 90/90
*A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 61/66 70/70 70/70
*A15C+ 10.8/14.4 36.84/49.13 30.1/34.7 70/75 70/70 80/80
*A21C+ 14.4/19.2 49.13/65.51 40.1/46.2 82/90 90/90 90/90
A060CK
No Heat 32/32 40/45 40/45
*A06C+ 4.2/5.6 14.33/19.10 11.7/13.5 47/49 50/60 50/60
*A11C+ 7.2/9.6 24.56/32.75 20.0/23.1 57/61 60/60 70/70
*A11C+ 7.2/9.6 24.56/32.75 20.0/23.1 47/51 50/50 60/60
25/29 25/30
50/58 50/60
30/34 30/35
38/44 40/45
50/58 50/60
19/19 25/25 25/25
25/29 25/30
15/17 15/20
50/58 50/60
30/34 30/35
38/44 40/45
50/58 50/60
20/20 25/25 25/25
15/17 15/20
25/29 25/30
25/29 25/30
25/29 25/30
50/58 50/60
30/34 30/35
38/44 40/45
50/58 50/60
22/22 25/30 25/30
25/29 25/30
15/17 15/20
50/58 50/60
30/34 30/35
38/44 40/45
50/58 50/60
32/32 40/45 40/45
15/17 15/20
25/29 25/30
25/29 25/30
208-240 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
Model
No.
RJNA-
RXJJ-
Heater Kit
Nominal kW
Rated
Heater kW
@ 208-240 V
Heater
KBTU/Hr
@ 208-240 V
Heater
Amp.
@ 208-240 V
Unit Min. Ckt.
Ampacity
@ 208-240 V
Over Current
Protective Device Size
Min./Max.
@ 208 V
Min./Max.
@ 240 V
Heater Kit
Min. Ckt.
Ampacity
Heater Kit
Max. Fuse
Size
Heat Pump Min.
Ckt.
Ampacity
208-240 V
Heat Pump Over Current
Protective Device Size
Min./Max.
@ 208 V
Min./Max.
@ 240 V
Single Power Supply For Both Unit and Heater Kit Separate Power Supply For Both Unit and Heater Kit
+ Field Installed Only
* = For Canadian Use Only. Uses “P” Fuses for Inductive Circuit.
25
UNITS WITH HEATER KITS—RJNA- SERIES
*A10C+
*A10C+ 7.2/9.6 24.56/32.75 20.0/23.1 43/47 45/45 50/50
*A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 68/75 70/70 80/80
*A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 47/51 50/50 60/60
*A15C+ 10.8/14.4 36.84/49.13 30.1/34.7 55/61 60/60 70/70
*A21C+ 14.4/19.2 49.13/65.51 40.1/46.2 68/75 70/70 80/80
7.2/9.6
A036CL
No Heat 18/18 20/25 20/25
24.56/32.75 20.0/23.1 44/47
*A06C+ 4.2/5.6 14.33/19.10 11.7/13.5 32/35 35/35 35/40
45/45 50/50
*A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 69/76 70/70 80/80
*A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 48/52 50/50 60/60
*A15C+ 10.8/14.4 36.84/49.13 30.1/34.7 56/62 60/60 70/70
*A21C+ 14.4/19.2 49.13/65.51 40.1/46.2 69/76 70/70 80/80
A042CL
No Heat 19/19 25/25 25/25
*A06C+ 4.2/5.6 14.33/19.10 11.7/13.5 33/35 35/40 35/40
*A11C+ 7.2/9.6 24.56/32.75 20.0/23.1 44/47 45/45 50/50
*A10C+
*A10C+
*A11C+ 7.2/9.6 24.56/32.75 20.0/23.1 43/47 45/45 50/50
7.2/9.6 24.56/32.75 20.0/23.1 46/50 50/50 50/50
*A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 71/79 80/80 80/80
*A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 50/55 50/50 60/60
*A15C+ 10.8/14.4 36.84/49.13 30.1/34.7 59/65 60/60 70/70
*A21C+ 14.4/19.2 49.13/65.51 40.1/46.2 71/79 80/80 80/80
7.2/9.6
A048CL
No Heat 21/21 25/30 25/30
24.56/32.75 20.0/23.1 53/57
*A06C+ 4.2/5.6 14.33/19.10 11.7/13.5 36/38 40/40 40/45
60/60 60/60
*A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 78/86 80/80 90/90
*A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 58/62 60/60 70/70
*A15C+ 10.8/14.4 36.84/49.13 30.1/34.7 66/72 70/70 80/80
*A21C+ 14.4/19.2 49.13/65.51 40.1/46.2 78/86 80/80 90/90
A060CL
No Heat 28/28 35/45 35/45
*A06C+ 4.2/5.6 14.33/19.10 11.7/13.5 43/45 45/50 45/50
*A11C+ 7.2/9.6 24.56/32.75 20.0/23.1 53/57 60/60 60/60
*A11C+ 7.2/9.6 24.56/32.75 20.0/23.1 46/50 50/50 50/50
*A24C+ 18.0/24.0 61.41/81.88 50.1/57.8 78/86 100/100 110/110
25/29 25/30
50/58 50/60
30/34 30/35
38/44 40/45
50/58 50/60
18/18 20/25 20/25
25/29 25/30
15/17 15/20
50/58 50/60
30/34 30/35
38/44 40/45
50/58 50/60
19/19 25/25 25/25
15/17 15/20
25/29 25/30
25/29 25/30
25/29 25/30
50/58 50/60
30/34 30/35
38/44 40/45
50/58 50/60
21/21 25/30 25/30
25/29 25/30
15/17 15/20
50/58 50/60
30/34 30/35
38/44 40/45
50/58 50/60
28/28 35/45 35/45
15/17 15/20
25/29 25/30
25/29 25/30
50/58 50/60
Model
No.
RJNA-
RXJJ-
Heater Kit
Nominal kW
Rated
Heater kW
@ 208-240 V
Heater
KBTU/Hr
@ 208-240 V
Heater
Amp.
@ 208-240 V
Unit Min. Ckt.
Ampacity
@ 208-240 V
Over Current
Protective Device Size
Min./Max.
@ 208 V
Min./Max.
@ 240 V
Heater Kit
Min. Ckt.
Ampacity
Heater Kit
Max. Fuse
Size
Heat Pump Min.
Ckt. Ampacity
208-240 V
Heat Pump Over Current
Protective Device Size
Min./Max.
@ 208 V
Min./Max.
@ 240 V
208-240 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
Single Power Supply For Both Unit and Heater Kit Separate Power Supply For Both Unit and Heater Kit
+ Field Installed Only
* = For Canadian Use Only. Uses “P” Fuses for Inductive Circuit.
26
UNITS WITH HEATER KITS—RJNA- SERIES
*A10C+
*A10C+ 7.2/9.6 24.56/32.75 20.0/23.1 44/48 45/45 50/50
*A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 69/76 70/70 80/80
*A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 48/52 50/50 60/60
*A15C+ 10.8/14.4 36.84/49.13 30.1/34.7 56/62 60/60 70/70
*A21C+ 14.4/19.2 49.13/65.51 40.1/46.2 69/76 70/70 80/80
7.2/9.6
A036CM
No Heat 19/19 25/25 25/25
24.56/32.75 20.0/23.1 45/48
*A06C+ 4.2/5.6 14.33/19.10 11.7/13.5 33/36 35/35 40/40
45/45 50/50
*A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 70/77 70/70 80/80
*A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 49/53 50/50 60/60
*A15C+ 10.8/14.4 36.84/49.13 30.1/34.7 57/63 60/60 70/70
*A21C+ 14.4/19.2 49.13/65.51 40.1/46.2 70/77 70/70 80/80
A042CM
No Heat 20/20 25/25 25/25
*A06C+ 4.2/5.6 14.33/19.10 11.7/13.5 34/36 35/40 40/40
*A11C+ 7.2/9.6 24.56/32.75 20.0/23.1 45/48 45/45 50/50
*A10C+
*A10C+
*A11C+ 7.2/9.6 24.56/32.75 20.0/23.1 44/48 45/45 50/50
7.2/9.6 24.56/32.75 20.0/23.1 47/51 50/50 60/60
*A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 72/80 80/80 80/80
*A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 51/56 60/60 60/60
*A15C+ 10.8/14.4 36.84/49.13 30.1/34.7 60/66 60/60 70/70
*A21C+ 14.4/19.2 49.13/65.51 40.1/46.2 72/80 80/80 80/80
7.2/9.6
A048CM
No Heat 22/22 25/30 25/30
24.56/32.75 20.0/23.1 53/57
*A06C+ 4.2/5.6 14.33/19.10 11.7/13.5 37/39 40/45 40/45
60/60 60/60
*A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 78/86 80/80 90/90
*A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 58/62 60/60 70/70
*A15C+ 10.8/14.4 36.84/49.13 30.1/34.7 66/72 70/70 80/80
*A21C+ 14.4/19.2 49.13/65.51 40.1/46.2 78/86 80/80 90/90
A060CM
No Heat 28/28 35/45 35/45
*A06C+ 4.2/5.6 14.33/19.10 11.7/13.5 43/45 45/50 45/50
*A11C+ 7.2/9.6 24.56/32.75 20.0/23.1 53/57 60/60 60/60
*A11C+ 7.2/9.6 24.56/32.75 20.0/23.1 47/51 50/50 60/60
A24C+ 18.0/24.0 61.41/81.88 50.1/57.8 78/86 100/100 110/110
25/29 25/30
50/58 50/60
30/34 30/35
38/44 40/45
50/58 50/60
19/19 25/25 25/25
25/29 25/30
15/17 15/20
50/58 50/60
30/34 30/35
38/44 40/45
50/58 50/60
20/20 25/25 25/25
15/17 15/20
25/29 25/30
25/29 25/30
25/29 25/30
50/58 50/60
30/34 30/35
38/44 40/45
50/58 50/60
22/22 25/30 25/30
25/29 25/30
15/17 15/20
50/58 50/60
30/34 30/35
38/44 40/45
50/58 50/60
28/28 35/45 35/45
15/17 15/20
25/29 25/30
25/29 25/30
50/58 50/60
Model
No.
RJNA-
RXJJ-
Heater Kit
Nominal kW
Rated
Heater kW
@ 208-240 V
Heater
KBTU/Hr
@ 208-240 V
Heater
Amp.
@ 208-240 V
Unit Min. Ckt.
Ampacity
@ 208-240 V
Over Current
Protective Device Size
Min./Max.
@ 208 V
Min./Max.
@ 240 V
Heater Kit
Min. Ckt.
Ampacity
Heater Kit
Max. Fuse
Size
Heat Pump Min.
Ckt.
Ampacity
@ 208-240 V
Heat Pump Over Current
Protective Device Size
Min./Max.
@ 208 V
Min./Max.
@ 240 V
208-240 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
Single Power Supply For Both Unit and Heater Kit Separate Power Supply For Both Unit and Heater Kit
+ Field Installed Only
* = For Canadian Use Only. Uses “P” Fuses for Inductive Circuit.
27
UNITS WITH HEATER KITS—RJNA- SERIES
*A10D+
*A10D+ 9.6 32.75 11.6 24 25 25
*A20D+ 19.2 65.51 23.1 38 40 40
*A12D+ 11.2 38.21 13.5 26 30 30
*A15D+ 14.4 49.13 17.3 31 35 35
*A21D+ 19.2 65.51 23.1 38 40 40
9.6
A036DK
No Heat 9 15 15
32.75 11.6 24
*A06D+ 5.6 19.10 6.7 18 20 20
25 25
*A20D+ 19.2 65.51 23.1 39 40 40
*A12D+ 11.2 38.21 13.5 27 30 30
*A15D+ 14.4 49.13 17.3 31 35 35
*A21D+ 19.2 65.51 23.1 39 40 40
A042DK
No Heat 10 15 15
*A06D+ 5.6 19.10 6.7 18 20 20
*A11C+ 9.6 32.75 11.6 24 25 25
*A10D+
*A11C+ 9.6 32.75 11.6 24 25 25
9.6 32.75 11.6 26 30 30
*A20D+ 19.2 65.51 23.1 40 40 40
*A12D+ 11.2 38.21 13.5 28 30 30
*A15D+ 14.4 49.13 17.3 33 35 35
*A21D+ 19.2 65.51 23.1 40 40 40
A048DK
No Heat 11 15 15
*A06D+ 5.6 19.10 6.7 20 20 20
*A11C+ 9.6 32.75 11.6 26 30 30
15 15
30 30 — —
17 20
22 25
29 30 — —
—— 91515
15 15
915
30 30 — —
17 20
22 25
29 30 — —
10 15 15
915
15 15
15 15
15 15
30 30 — —
17 20
22 25 — —
29 30 — —
11 15 15
915
15 15
Model
No.
RJNA-
RXJJ-
Heater Kit
Nominal kW
Rated
Heater kW
@ 480 V
Heater
KBTU/Hr
@ 480 V
Heater
Amp.
@ 480 V
Unit Min. Ckt.
Ampacity
@ 480 V
Over Current
Protective Device Size
Min./Max.
@ 480 V
Min./Max.
@ 480 V
Heater Kit
Min. Ckt.
Ampacity
Heater Kit
Max. Fuse
Size
Heat Pump Min.
Ckt.
Ampacity
@ 480 V
Heat Pump Over Current
Protective Device Size
Min./Max.
@ 480 V
Min./Max.
@ 480 V
480 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
Single Power Supply For Both Unit and Heater Kit Separate Power Supply For Both Unit and Heater Kit
+ Field Installed Only
* = For Canadian Use Only. Uses “P” Fuses for Inductive Circuit.
28
UNITS WITH HEATER KITS—RJNA- SERIES
*A10D+
*A10D+ 9.6 32.75 11.6 24 25 25
*A20D+ 19.2 65.51 23.1 38 40 40
*A12D+ 11.2 38.21 13.5 26 30 30
*A15D+ 14.4 49.13 17.3 31 35 35
*A21D+ 19.2 65.51 23.1 38 40 40
9.6
A036DL
No Heat 9 15 15
32.75 11.6 24
*A06D+ 5.6 19.10 6.7 18 20 20
25 25
*A20D+ 19.2 65.51 23.1 39 40 40
*A12D+ 11.2 38.21 13.5 27 30 30
*A15D+ 14.4 49.13 17.3 31 35 35
*A21D+ 19.2 65.51 23.1 39 40 40
A042DL
No Heat 10 15 15
*A06D+ 5.6 19.10 6.7 18 20 20
*A11C+ 9.6 32.75 11.6 24 25 25
*A10D+
*A10D+
*A11C+ 9.6 32.75 11.6 24 25 25
9.6 32.75 11.6 26 30 30
*A20D+ 19.2 65.51 23.1 40 40 40
*A12D+ 11.2 38.21 13.5 28 30 30
*A15D+ 14.4 49.13 17.3 33 35 35
*A21D+ 19.2 65.51 23.1 40 40 40
9.6
A048DL
No Heat 11 15 15
32.75 11.6 28
*A06D+ 5.6 19.10 6.7 20 20 20
30 30
*A20D+ 19.2 65.51 23.1 43 45 45
*A12D+ 11.2 38.21 13.5 31 35 35
*A15D+ 14.4 49.13 17.3 35 35 35
*A21D+ 19.2 65.51 23.1 43 45 45
A060DL
No Heat 14 20 20
*A06D+ 5.6 19.10 6.7 22 25 25
*A11C+ 9.6 32.75 11.6 28 30 30
*A11C+ 9.6 32.75 11.6 26 30 30
*A24D+ 24.0 81.88 28.9 50 50 50
15 15
30 30 — —
17 20
22 25
29 30 — —
—— 91515
15 15
915
30 30 — —
17 20
22 25
29 30 — —
10 15 15
915
15 15
15 15
15 15
30 30 — —
17 20
22 25 — —
29 30 — —
11 15 15
15 15
915
30 30 — —
17 20
22 25
29 30 — —
14 20 20
915
15 15
15 15
37 40 — —
Model
No.
RJNA-
RXJJ-
Heater Kit
Nominal kW
Rated
Heater kW
@ 480 V
Heater
KBTU/Hr
@ 480 V
Heater
Amp.
@ 480 V
Unit Min. Ckt.
Ampacity
@ 480 V
Over Current
Protective Device Size
Min./Max.
@ 480 V
Min./Max.
@ 480 V
Heater Kit
Min. Ckt.
Ampacity
Heater Kit
Max. Fuse
Size
Heat Pump Min.
Ckt.
Ampacity
@ 480 V
Heat Pump Over Current
Protective Device Size
Min./Max.
@ 480 V
Min./Max.
@ 480 V
480 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
Single Power Supply For Both Unit and Heater Kit Separate Power Supply For Both Unit and Heater Kit
+ Field Installed Only
* = For Canadian Use Only. Uses “P” Fuses for Inductive Circuit.
29
UNITS WITH HEATER KITS—RJNA- SERIES
*A10D+
*A10D+ 9.6 32.75 11.6 24 25 25
*A20D+ 19.2 65.51 23.1 38 40 40
*A12D+ 11.2 38.21 13.5 26 30 30
*A15D+ 14.4 49.13 17.3 31 35 35
*A21D+ 19.2 65.51 23.1 38 40 40
9.6
A036DM
No Heat 9 15 15
32.75 11.6 24
*A06D+ 5.6 19.10 6.7 18 20 20
25 25
*A20D+ 19.2 65.51 23.1 39 40 40
*A12D+ 11.2 38.21 13.5 27 30 30
*A15D+ 14.4 49.13 17.3 31 35 35
*A21D+ 19.2 65.51 23.1 39 40 40
A042DM
No Heat 10 15 15
*A06D+ 5.6 19.10 6.7 18 20 20
*A11D+ 9.6 32.75 11.6 24 25 25
*A10D+
*A10D+
*A11D+ 9.6 32.75 11.6 24 25 25
9.6 32.75 11.6 26 30 30
*A20D+ 19.2 65.51 23.1 40 40 40
*A12D+ 11.2 38.21 13.5 28 30 30
*A15D+ 14.4 49.13 17.3 33 35 35
*A21D+ 19.2 65.51 23.1 40 40 40
9.6
A048DM
No Heat 11 15 15
32.75 11.6 28
*A06D+ 5.6 19.10 6.7 20 20 20
30 30
*A20D+ 19.2 65.51 23.1 43 45 45
*A12D+ 11.2 38.21 13.5 31 35 35
*A15D+ 14.4 49.13 17.3 35 35 35
*A21D+ 19.2 65.51 23.1 43 45 45
A060DM
No Heat 14 20 20
*A06D+ 5.6 19.10 6.7 22 25 25
*A11D+ 9.6 32.75 11.6 28 30 30
*A11D+ 9.6 32.75 11.6 26 30 30
*A24D+ 24.0 81.88 28.9 50 50 50
15 15
30 30 — —
17 20
22 25
29 30 — —
—— 91515
15 15
915
30 30 — —
17 20
22 25
29 30 — —
10 15 15
915
15 15
15 15
15 15
30 30 — —
17 20
22 25 — —
29 30 — —
11 15 15
15 15
915
30 30 — —
17 20
22 25
29 30 — —
14 20 20
915
15 15
15 15
37 40 — —
Model
No.
RJNA-
RXJJ-
Heater Kit
Nominal kW
Rated
Heater kW
@ 480 V
Heater
KBTU/Hr
@ 480 V
Heater
Amp.
@ 480 V
Unit Min. Ckt.
Ampacity
@ 480 V
Over Current
Protective Device Size
Min./Max.
@ 480 V
Min./Max.
@ 480 V
Heater Kit
Min. Ckt.
Ampacity
Heater Kit
Max. Fuse
Size
Heat Pump Min.
Ckt.
Ampacity
@ 480 V
Over Current
Protective Device Size
Min./Max.
@ 480 V
Min./Max.
@ 480 V
480 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
Single Power Supply For Both Unit and Heater Kit Separate Power Supply For Both Unit and Heater Kit
+ Field Installed Only
* = For Canadian Use Only. Uses “P” Fuses for Inductive Circuit.
A036JK
No Heat 25/25 30/35 30/35
*A10J+ 7.2/9.6 24.56/32.75 34.7/40.0 69/75 70/70 80/80
*A06J+ 4.2/5.6 14.33/19.10 20.2/23.3 51/55 60/60 60/60
*A11J+ 7.2/9.6 24.56/32.75 34.7/40.0 69/75 70/70 80/80
*A20J+ 14.4/19.2 49.13/65.51 69.3/80.0 112/125 125/125 125/125
*A12J+ 8.4/11.2 28.66/38.21 40.4/46.7 76/84 80/80 90/90
*A15J+ 10.8/14.4 36.84/49.13 52.0/60.0 90/100 90/90 100/100
*A21J+ 14.4/19.2 49.13/65.51 69.3/80.0 112/125 125/125 125/125
*A10J+ 7.2/9.6 24.56/32.75 34.7/40.0 71/77 80/80 80/80
*A20J+ 14.4/19.2 49.13/65.51 69.3/80.0 114/127 125/125 150/150
*A12J+ 8.4/11.2 28.66/38.21 40.4/46.7 78/86 80/80 90/90
A15J 10.8/14.4 36.84/49.13 52.0/60.0 92/102 100/100 110/110
*A21J+ 14.4/19.2 49.13/65.51 69.3/80.0 114/127 125/125 150/150
A042JK
No Heat 27/27 35/40 35/40
*A06J+ 4.2/5.6 14.33/19.10 20.2/23.3 53/56 60/60 60/60
*A11J+ 7.2/9.6 24.56/32.75 34.7/40.0 71/77 80/80 80/80
*A10J+
*A10J+ 7.2/9.6 24.56/32.75 34.7/40.0 73/80 80/80 80/80
A20J 14.4/19.2 49.13/65.51 69.3/80.0 116/130 125/125 150/150
*A12J+ 8.4/11.2 28.66/38.21 40.4/46.7 80/88 80/80 90/90
A15J 10.8/14.4 36.84/49.13 52.0/60.0 95/105 100/100 110/110
*A21J+ 14.4/19.2 49.13/65.51 69.3/80.0 116/130 125/125 150/150
7.2/9.6
A048JK
No Heat 30/30 35/45 35/45
24.56/32.75 34.7/40.0 90/96
*A06J+ 4.2/5.6 14.33/19.10 20.2/23.3 55/59 60/60 60/70
100/110 100/110
A20J 14.4/19.2 49.13/65.51 69.3/80.0 133/146 150/150 150/150
*A12J+ 8.4/11.2 28.66/38.21 40.4/46.7 97/105 100/110 110/110
A15J 10.8/14.4 36.84/49.13 52.0/60.0 111/121 125/125 125/125
*A21J+ 14.4/19.2 49.13/65.51 69.3/80.0 133/146 150/150 150/150
A060JK
No Heat 46/46 60/60 60/60
*A06J+ 4.2/5.6 14.33/19.10 20.2/23.3 72/75 80/90 80/90
*A11J+ 7.2/9.6 24.56/32.75 34.7/40.0 90/96 100/110 100/110
*A11J+ 7.2/9.6 24.56/32.75 34.7/40.0 73/80 80/80 80/80
44/50 45/50
87/100 90/100
51/59 60/60
65/75 70/80
87/100 90/100
25/25 30/35 30/35
44/50 45/50
26/30 30/30
——
87/100 90/100
51/59 60/60
65/75 70/80
87/100 90/100
27/27 35/40 35/40
26/30 30/30
44/50 45/50
44/50 45/50
44/50 45/50
87/100 90/100
51/59 60/60
65/75 70/80
87/100 90/100
30/30 35/45 35/45
44/50 45/50
26/30 30/30
——
87/100 90/100
51/59 60/60
65/75 70/80
87/100 90/100
46/46 60/60 60/60
26/30 30/30
44/50 45/50
44/50 45/50
Model
No.
RJNA-
RXJJ-
Heater Kit
Nominal kW
Rated
Heater kW
@ 208-240 V
Heater
KBTU/Hr
@ 208-240 V
Heater
Amp.
@ 208-240 V
Unit Min. Ckt.
Ampacity
@ 208-240 V
Over Current
Protective Device Size
Min./Max.
@ 208 V
Min./Max.
@ 240 V
Heater Kit
Min. Ckt.
Ampacity
Heater Kit
Max. Fuse
Size
Heat Pump Min.
Ckt.Ampacity
208-240 V
Heat Pump Over Current
Protective Device Size
Min./Max.
@ 208 V
Min./Max.
@ 240 V
208-240 VOLT, SINGLE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
Single Power Supply For Both Unit and Heater Kit Separate Power Supply For Both Unit and Heater Kit
+ Field Installed Only
* = For Canadian Use Only. Uses “P” Fuses for Inductive Circuit.
30
UNITS WITH HEATER KITS—RJNA- SERIES
UNIT DIMENSIONS
PACKAGE
HEAT PUMPS
[ ] Designates Metric Conversions
31
UNIT DIMENSIONS—RJNA- SERIES
UNIT DIMENSIONS
PACKAGE
HEAT PUMPS
[ ] Designates Metric Conversions
BOTTOM VIEW
32
UNIT DIMENSIONS—RJNA- SERIES
SELECTION PROCEDURE
1. Determine cooling and heating requirements at design
conditions.
Example:
Total cooling capacity ............43,600 BTUH [12.78 kW]
Sensible cooling capacity ......34,000 BTUH [9.96 kW]
Condenser entering air ..........95°F [35°C]
Evaporator entering air ..........63°F [17°C] wb/76°F [24°C] db
Indoor air flow ........................1600 CFM [755 L/s]
External static pressure ..........1.1 in wg
Required efficiency ................13 SEER
2. Select unit to meet cooling requirements.
Since total cooling is within the range of 4 ton [14.07 kW] unit and
requires 13 SEER efficiency level, enter cooling performance
table, at 95°F [35°C] outdoor temperature, 63°F [17°C] wb enter-
ing indoor air, and 1600 CFM [755 L/s]:
Total capacity ..........................46,700 BTUH [13.68 kW]
Power input ............................3.3 kW
And also, at 76°F [24°C] db indoor entering air, and using the for-
mula at the bottom of the page:
Sensible capacity....................33,710 BTUH [9.87 kW]
3. Determine blower speed and power to meet the system
requirements.
At the given external static pressure of 1.1 in wg, the belt model
must be selected. Enter the belt drive blower performance table
at 1600 CFM [755 L/s] and 1.1 in wg ESP:
RPM ..................1205
Watts ..................725
Drive ..................M
4. Calculate indoor blower BTUH heat effect.
BTUH = Watts x 3.413 = 2474
5. Calculate net cooling capacities.
Net total cooling = 46,700 – 2474 = 44,226 BTUH [12.96 kW]
Net sensible cooling = 33,716 – 2474 = 31.242 BTUH [9.16 kW]
Accessory Shipping—lbs [kg]
Economizer 142 [64]
Power Exhaust 30 Est. [13]
Fresh Air Damper (Manual) 11 [5] 9 [4]
25 Est. [11]
130 [59]
Operating—lbs [kg]
Fresh Air Damper (Motorized) 13 [6]
Roof Curb 8" 84 [38]
Roof Curb 14" 92 [42] 88 [40]
80 [36]
11 [5]
Roof Curb 24" 108 [49] 104 [47]
Horizontal Economizer 90 [41] 80 [36]
WEIGHTS
A B C D
23% 27% 23% 27%
Capacity Tons [kW]
3-5 [10.6-17.6]
Corner Weights by Percentage
381/4[972] 253/4 [654]
3-5 [10.6-17.6]
Capacity Tons [kW] A in. [mm] B in. [mm]
CENTER OF GRAVITY (C.G.)
[ ] Designates Metric Conversions
*Allow 57” for economizer on duct side.
33
UNIT DIMENSIONS—RJNA- SERIES
Accessory
Description
Model Application
3 to 5 Ton
[10.6 to 17.6 kW]
Accessory
Model No.
3 to 5 Ton
[10.6 to 17.6 kW]
Roofcurb Adapters RJNA-
RXRX-BBCDB21
RXRX-BBCDB22
RXRX-BBCDB23
Economizer with Single Enthalpy RJNA- RXRD-KECM3
Time Delay RJNA- RXMD-B01
Low Ambient Control to 0°F [-18°C] RJNA- RXPZ-C01
Fresh Air Damper Manual RJNA- RXRF-FBA1
Fresh Air Damper Motorized RJNA- RXRF-FBB1
Rectangular to Round 18"
Duct Adapters for Concentric Diffuser RJNA- RXMC-CB03
Concentric Diffuser 18" Step RJNA- RXRN-FA60
Concentric Diffuser 18" Flush RJNA- RXRN-FA70
Electric Heater Kits RJNA-
RXJJ-A06 (J, C, D)
RXJJ-A10 (J, C, D)
RXJJ-A11 (J, C, D)
RXJJ-A12 (J, C, D)
RXJJ-A15 (J, C, D)
RXJJ-A20 (J, C, D)
RXJJ-A21 (J, C, D)
RXJJ-A24 (J, C, D)
Roofcurb 24" RJNA- RXKG-BAD24
Rectangular to Round 16" Side RJNA- RXMC-BB01
Louver Kit (3 Sides) All RJNA Models RXRX-AAD01B
Factory Installed
3 to 5 Ton
[10.6 to 17.6 kW]
No
Yes
Yes
Yes
No
No
No
No
No
See Heater Kit
Electric Table
No
No
Yes
Dual Enthalpy Kit RJNA- RXRX-AV02 No
CO2Sensor RJNA- RXRX-AR02 No
Power Exhaust RJNA- RXRX-BFF04C No
Roofcurb 14" RJNA- RXKG-BAD14 No
ACCESSORY EQUIPMENT
*Voltage
J = 208-230 VAC-1PH-60HZ D = 460 VAC-3PH-60HZ
C = 208-230 VAC-3PH-60HZ
NOTES: Economizer is designed for downflow
or horizontal applications.
34
ACCESSORIES—RJNA- SERIES
Roofcurb Adapters
Old Models OLD CURB MODEL ROOFCURB ADAPTER NEW MODEL
MEDIUM CABINET (3 TON [11 kW])
21 SERIES RXPA-CA21 (1)
RXRA-DB21 (2) RXRX-BBCDB21
RJNA
(-)SNC, (-)SND, (-)SNE
(-)RGE, (-)RGF, (-)RGG
(-)PNC, (-)PND
EXTRA LARGE CABINET
(3.5-5 TON [12-18 kW])
23 SERIES RXPA-CA23 (1)
RXRA-DB23 (2) RXRX-BBCDB23
(-)SNC, (-)SND, (-)SNE
(-)RGE, (-)RGF,
(-)RGG (4-5 TON [14-18 kW])
(-)PNC, (-)PND, (-)RGH
(3.5, 4 TON [12-14 kW])
LARGE CABINET
(3-3.5 TON [11-12 kW]) 22 SERIES RXPA-CA22 (1)
RXRA-DB22 (2) RXRX-BBCDB22
(-)RGE, (-)RGF, (-)RGG,
(-)RGH (3 TON [11 kW])
(1) SLOPE TYPE (2) FULL PERIMETER TYPE
RXJ J —A 15 C
Electrical Designation
J = 208-230 V, 1 PH, 60 Hz
C = 208-230 V, 3 PH, 60 Hz
D = 460 V, 3 PH, 60 Hz
Nominal Heater kW
06 = 6 kW 15 = 15 kW
10 = 10 kW 20 = 20 kW
11 = 11 kW * 21 = 21 kW *
12 = 12 kW 24 = 24 kW
* Canadian Models Only
Design Series
A = Initial Design
Accessory Designation
J = Electric Heater
Accessory Classification
J = Package Heat Pump
X = Accessory
R = Trade Name
Field Installed Resistance
Heater Kits
Electric Heater Kits are designed for field
installation using either single-point power
wiring or dual circuit wiring. Low voltage
plugs are provided to allow for quick
connection to the unit. Removing a block-
off panel on the unit allows the heater
elements to be inserted into the supply air
down stream from the indoor coil and
supply air blower.
[ ] Designates Metric Conversions
Model Number Identifier:
35
ACCESSORIES—RJNA- SERIES
ROOFCURBS (Full Perimeter)
Rheem’s new roofcurb design can be utilized on
3 through 5 ton [10.6-17.6 kW] models.
Two available heights (14" [356 mm] and
24" [610 mm]) for ALL models.
Quick assembly corners for simple and fast assembly.
Opening provided in bottom pan to match the
“Thru the Curb” electrical connection opening
provided on the unit base pan.
2" [51 mm] x 4" [102 mm] Nailer provided.
Insulating panels provided.
Sealing gasket (28" [711 mm]) provided
with Roofcurb.
Packaged for easy field assembly.
[ ] Designates Metric Conversions
TYPICAL INSTALLATION
Roofcurb Model Height of Curb
RXKG-BAD14 14" [356 mm]
RXKG-BAD24 24" [610 mm]
ROOFCURB FOR 3-5 TON
[10.6-17.6 kW] MODELS
36
ACCESSORIES
[ ] Designates Metric Conversions
Features Honeywell Controls
Available factory installed or field accessory
Gear Driven Direct Drive Actuator
Fully Modulating (0-100%)
Low Leakage Dampers
Horizontal or Downflow Applications
Slip-In Design for Easy Installations
Plug-In Polarized 12-pin Electrical Connections
Pre-configured—No Field Adjustments Necessary
Standard Barometric Relief Damper Provided
Single Enthalpy with Dual Enthalpy Upgrade Kit
CO2Input Sensor Available (Field Installed)
Economizer slips in complete for Downflow or
Horizontal Duct application
Field Assembled Hood Ships with Economizer
Optional Remote Minimum Position (Honeywell
#S963B1128) is Available from ProStock
Field Installed Power Exhaust Available
ECONOMIZERS
RXRD-KECM3—3-5 Ton [10.6-17.6 kW] Models Single Enthalpy with Barometric Relief
RXRX-AV02—Dual Enthalpy Kit
3-5 Ton [10.6-17.6 kW] Models
RXRX-AR02—3-5 Ton [10.6-17.6 kW] Models Optional CO2Sensor
3-5 TON [10.6-17.6 kW] MODELS
37
ACCESSORIES
Illustration
ST-A0903-01
INTEGRAL POWER EXHAUST FOR ECONOMIZER
(FIELD INSTALLED ONLY)
RXRX-BFF04C—3-5 Ton [10.6-17.6 kW] Models 208-230 V, 1 PH, 60 Hz
For RXRD-KECM3 Economizer
Downflow or horizontal applications
Requires separate power supply with disconnect
Adjustable switch on economizer, factory preset to
energize power exhaust at 95% outside air position
Polarized plug connects power exhaust relay
to economizer
[ ] Designates Metric Conversions
FRESH AIR DAMPER
3 to 5 Ton [10.6 to 17.6 kW] Models
RXRF-FBA1 (Manual)
RXRF-FBB1 (Motorized)
Model No. Volts
RXRX-BFF04C 208-230
No. of Fans
1 1
Phase
240
Watts (ea.)
2600
High Speed
1700 1.06
FLA (ea.)
1.9
LRA (ea.)
CFM RPM
CFM is at 0" w.c. external static pressure.
POWER EXHAUST KIT FOR RXRD-ECCM(-), RXRD-EECM(-) ECONOMIZERS
FRESH AIR DAMPER
I319.DGN
38
ACCESSORIES
DUCT ADAPTERS (3 TO 5 TON [10.6 TO 17.6 kW] MODELS)
Rectangular to Round
Transitions (Downflow)
RXMC-CB03 – 18" [457 mm] Round
Available in 18 inch round
to fit all units. Drops
into and secures to
RXKG- Series Roofcurbs.
For use with
Concentric Diffusers.
[ ] Designates Metric Conversions
39
ACCESSORIES
SIDE DISCHARGE CONCENTRIC DIFFUSER
RXRN-FA60 (3 to 5 Ton [10.6 to 17.6 kW] Models)
For Use With Duct Adapter (RXMC)
Model No. A B C D E F G H I J K Duct
Size
RXRN-FA60 475/8"
[1210 mm]
235/8"
[600 mm]
113/8"
[289 mm]
211/2"
[546 mm]
451/2"
[1156 mm]
221/2"
[572 mm]
111/2"
[292 mm]
103/4"
[273 mm]
451/2"
[1156 mm]
211/2"
[546 mm]
71/8"
[181 mm] 18RD
Model No. CFM [L/s] Static
Pressure
Throw
Feet
Neck
Vel.
Jet
Vel.
Noise
Level
RXRN-FA60
1000 [472] .14 10-17 351 351 20
1200 [566] .17 11-18 421 421 20
1400 [661] .20 12-19 491 491 20
1600 [755] .24 12-20 561 561 20
1800 [850] .30 13-21 632 632 20
2000 [944] .36 14-23 702 702 20
2200 [1038] .40 16-25 772 772 20
DIMENSIONAL DATA
ENGINEERING DATA
[ ] Designates Metric Conversions
40
ACCESSORIES
FLUSH MOUNT CONCENTRIC DIFFUSER
RXRN-FA70 (3 to 5 Ton [10.6 to 17.6 kW] Models)
For Use With Duct Adapter (RXMC)
DIMENSIONAL DATA
ENGINEERING DATA
Model No. A B C D E F G H Duct
Size
RXRN-FA70 475/8"
[1210 mm]
235/8"
[600 mm]
131/2"
[343 mm]
21"
[533 mm]
45"
[1143 mm]
221/2"
[572 mm]
111/4"
[286 mm]
101/2"
[267 mm] 18RD
Model No. CFM [L/s] Static
Pressure
Throw
Feet
Neck
Vel.
Jet
Vel.
Noise
Level
RXRN-FA70
1000 [472] .14 15-20 391 694 20
1200 [566] .17 16-22 469 833 25
1400 [661] .20 17-24 547 972 30
1600 [755] .24 18-25 625 1111 30
1800 [850] .30 20-28 703 1250 35
2000 [944] .36 21-29 781 1389 40
2200 [1038] .40 22-30 859 1528 40
[ ] Designates Metric Conversions
41
ACCESSORIES
THERMOSTATSPACKAGE HEAT PUMPS
RECOMMENDED HEAT PUMP THERMOSTATS
Units Without Economizer
Honeywell
T7300A1005
T8611R1166
T874R
T841A1209
T874G1881 Q674F1360
Included
Q674F1360
Included
Q7300C1006
1
1
1
1
1
2
2
2
2
2
Manufacturer Model Sub-Base Cooling
Stages
Heating
Stages
T8141A Included 1 2
General Electric 3AAT86B8A2 Included 1 2
3AAT83D9C1 Included 1 2
White-Rodgers 1F59-057 Included 1 2
1F92-71 Included 2 3
Maple Chase 962-0 Included 1 2
962-1 Included 1 2
Units With Economizer
Honeywell T874W1031 Included 2 3
SAMPLE
SPECIFICATIONS
Unit shall be completely factory assembled
and performance tested to provide the
required cooling and heating functions suit-
able for outdoor installations. Unit shall be
UL/cUL listed and rated in accordance to
ARI Standard 210.
Cabinet
Unit casing, base pan and framework shall
be manufactured of galvanized sheet metal
primed and finished with powder paint
capable of withstanding a 1000-hour salt
spray test per ASTM B 117. Unit interior cab-
inet surfaces shall be insulated with a mini-
mum 1/2-inch thick foil faced insulation.
Access panels shall be easily removable
providing access to the blower, filter, heating
compartment, and compressor/control box.
Unit base rails shall be provided with fork
insertion slots and rigging holes. Conden-
sate drain pan shall be of sloped design to
conform to ASHRAE 62. Unit shall be sup-
plied ready for vertical airflow and be easily
convertible to horizontal airflow at or before
installation.
Compressor(s)
Unit shall be provided with fully hermetic
scroll compressor(s) with internally protected
safety controls.
Coils
The evaporator and condenser coils shall
be fabricated of copper tubes with mechani-
cally bonded aluminum plate fins. They
shall be pressure tested prior to assembly
into the unit, and electronically leak tested
after assembly.
Condenser Fan
A single direct drive propeller fan shall dis-
charge air vertically upward. The fan motor
shall be permanently lubricated and have
built-in overload protection.
Evaporator Blower
A single, double inlet, centrifugal wheel
shall rotate in permanently lubricated ball
bearings. The wheel shall be made from
steel with corrosion resistant finish and shall
be statically and dynamically balanced.
ACCESSORIES
ROOF CURB
Curb shall be full perimeter type, complying
with the standards of the National Roofing
Contractors Association. Design shall pro-
vide for drop-in of supply and return ducts
prior to setting unit, and include an insulat-
ing panel for the rest of the curb area.
Economizer
Economizer shall be completely assembled
for field installation. Unit shall include all
controls and dampers including the baro-
metric relief damper.
Manual Fresh Air Damper
Damper shall consist of damper and rain-
hood which is manually preset to admit up
to 35% of outside air for field installation.
Motorized Fresh Air Damper
Damper shall consist of motor, damper, and
rainhood which can admit up to 35% of out-
side air for field installation.
Electric Heat Kits
Electric heat kits shall be available in a wide
range of capacity with branch circuit fusing
allowing single point wiring. Kits shall be
UL/cUL approved. Each kit shall be offered
as a field or factory installed option.
Pressure Controls
High and low pressure controls shall be
included for field or factory installation.
Low Ambient Control
Low ambient control shall be provided to
cycle the condenser fan in response to
condensing pressure and allow operation
to 0 degrees F. The option shall be field or
factory installed.
Time Delay Control
Time delay control shall be provided to
prevent the compressor from restarting 5
minutes after shutdown. The control shall
be field or factory installed.
Louver Panel Kits
Field or factory installed louver kits shall
be provided for condenser coil protection
against hail or flying debris.
[ ] Designates Metric Conversions
42
MECHANICAL SPECIFICATIONS—RJNA- SERIES
43
WIRING SCHEMATICS—RJNA- SERIES
44
WIRING SCHEMATICS—RJNA- SERIES
45
WIRING SCHEMATICS—RJNA- SERIES
46
WIRING SCHEMATICS—RJNA- SERIES
47
WIRING SCHEMATICS—RJNA- SERIES
48
WIRING SCHEMATICS—RJNA- SERIES
49
WIRING SCHEMATICS—RJNA- SERIES
GENERAL TERMS OF LIMITED WARRANTY
Before proceeding with installation, refer
to installation instructions packaged
with each model, as well as complying
with all Federal, State, Provincial, and
Local codes, regulations, and practices.
RHEEM
AIR CONDITIONING
DIVISION
5600 Old Greenwood Road, Fort Smith, Arkansas 72908
“In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.”
PRINTED IN U.S.A. 8-05 DC FORM NO. P11-763 REV. 1
Supersedes Form No. P11-763
BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE FROM
YOUR RETAILER.
Rheem will furnish a replacement for any part of this product
which fails in normal use and service within the applicable
periods stated, in accordance with the terms of the limited
warranty.
For Complete Details of the Limited Warranty, Including Applicable Terms
and Conditions, See Your Local Installer or Contact the Manufacturer
for a Copy.
Compressor ...................................................Five (5) Years
Electric Heating Elements ...............................Five (5) Years
Any Other Part
1-Phase Models .............................................Five (5) Years
3-Phase Models...............................................One (1) Year