FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in
your building.
5. Extinguish any open flame.
6. Leave the building.
7. Immediately call your local gas
supplier after leaving the building.
Follow the gas supplier’s
instructions.
8. If you cannot reach your gas
supplier, call the Fire Department.

Blackheat BH

WARNING

Fire Hazard
Keep all flammable objects, liquids and
vapors the minimum required clearances to combustibles away from
heater.
Some objects will catch fire or explode
when placed close to heater.

™

The Economical Unitary
Infrared Heater
Installation, Operation &
Service Manual
BH-40
BH-60
BH-80
BH-100
BH-115

BH-125
BH-140
BH-150
BH-175
BH-200

Failure to follow these instructions can
result in death, injury or property
damage.

Installer

WARNING
Improper installation, adjustment, alteration, service
or maintenance can result in death, injury or
property damage. Read the Installation, Operation
and Service Manual thoroughly before installing or
servicing this equipment.
Installation must be done by a contractor qualified
in the installation and service of gas-fired heating
equipment or your gas supplier.

Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your serviceman with necessary information.

Roberts-Gordon LLC
1250 William Street
P.O. Box 44
Buffalo, New York 14240-0044
Telephone: +1.716.852.4400
Fax: +1.716.852.0854
Toll Free: 800.828.7450

© 2012 Roberts-Gordon LLC

www.rg-inc.com
www.radiantheaters.com

P/N 170102NA Rev. M 02/12

TABLE OF CONTENTS
SECTION 1: Heater Safety...................................................... 1
1.1 Manpower Requirements ............................................. 1
1.2 Safety Labels and Their Placement ............................. 1
1.3 California Proposition 65 .............................................. 1
SECTION 2: Installer Responsibility ..................................... 4
2.1 Wall Tag ....................................................................... 4
2.2 Corrosive Chemicals.................................................... 4
2.3 National Standards and Applicable Codes .................. 4
SECTION 3: Clearances to Combustibles............................. 5
3.1 Required Clearances to Combustibles......................... 5
SECTION 4: National Standards and Applicable Codes ... 10
4.1 Gas Codes................................................................. 10
4.2 Aircraft Hangars ......................................................... 10
4.3 Public Garages .......................................................... 10
4.4 Electrical .................................................................... 10
4.5 Venting....................................................................... 10
4.6 High Altitude .............................................................. 10
SECTION 5: Major Components .......................................... 11
5.1 Standard Parts List .................................................... 12
SECTION 6: Heater Installation............................................ 14
6.1 Burner Tube Installation ............................................ 18
6.2 Tube Clamp Package Installation .............................. 19
6.3 Coupling and Tube Assembly.................................... 19
6.4 Turbulator Installation ................................................ 21
6.5 Reflector Installation .................................................. 22
6.6 Burner Installation...................................................... 24
SECTION 7: Optional Heater Accessories .......................... 25
7.1 U-Tube Configuration.................................................. 25
7.2 Elbow Package Configuration..................................... 28
7.3 Reflector Side Extension ............................................ 31
7.4 Lower Clearance Shield Installation ........................... 32
7.5 Two-Foot Decorative Grille Installation ....................... 32
7.6 Protective Grille Installation ........................................ 34
SECTION 8: Venting.............................................................. 35
8.1 Venting....................................................................... 35
8.2 Unvented Operation................................................... 36
8.3 Horizontal Venting...................................................... 36
8.4 Vertical Venting .......................................................... 36
8.5 Unvented Operation Tube Termination ...................... 36
8.6 Length Requirements ................................................ 36
8.7 Horizontal Ventilation 4'' (10 cm) Pipe........................ 36
8.8 Vertical Ventilation 4'' (10 cm) Pipe............................ 37
8.9 Common Side Wall Venting ....................................... 37
8.10 Common Vertical Venting ........................................ 38

8.11 Outside Combustion Air Supply ............................... 39
SECTION 9: Gas Piping........................................................ 41
SECTION 10: Wiring.............................................................. 43
10.1 Line Voltage Thermostat Wiring............................... 43
10.2 Low Voltage Thermostat Wiring ............................... 44
10.3 Internal Wiring.......................................................... 45
10.4 Ladder Diagram ....................................................... 46
10.5 Electrical Connection to the Burner ......................... 46
SECTION 11: Operation and Maintenance.......................... 47
11.1 Sequence of Operation ............................................ 47
11.2 To Shut Off Heater.................................................... 47
11.3 To Start Heater ......................................................... 47
11.4 Pre-Season Maintenance and Annual Inspection..... 47
11.5 Maintenance Checklist ............................................. 48
SECTION 12: Troubleshooting............................................. 50
12.1 Troubleshooting Flow Chart ..................................... 51
12.2 Manifold Gas Pressure Setting ................................ 53
SECTION 13: Replacement Parts ........................................ 54
SECTION 14: General Specifications .................................. 57
14.1 Material Specifications............................................. 57
14.2 Heater Specifications............................................... 57
14.3 Suspension Specifications....................................... 57
14.4 Controls Specifications ............................................ 57
SECTION 15: The ROBERTS GORDON BLACKHEAT BH
Warranty ......................................................... 59
®

© 2012 Roberts-Gordon LLC
All rights reserved. No part of this work covered by the copyrights herein may be reproduced
or copied in any form or by any means - graphic, electronic, or mechanical, including
photocopying, recording, taping or information storage and retrieval systems - without the
written permission of Roberts-Gordon LLC.

Printed in U.S.A.

TM

TABLE OF FIGURES
Figure 1: Top and Bottom Panel Label Placement .................... 2
Figure 2: Side and Back Panel Label Placement ...................... 3
Figure 3: Standard Reflector ..................................................... 6
Figure 4: One Side Reflector..................................................... 6
Figure 5: Two Side Reflectors ................................................... 6
Figure 6: 45° Tilt Reflector ........................................................ 7
Figure 7: U-Tube, Standard Reflector........................................ 7
Figure 8: U-Tube, 45° ................................................................ 7
Figure 9: U-Tube, Opposite 45° Reflector ................................. 8
Figure 10: 2-Foot Deco Grille and Protective Grille ................... 8
Figure 11: Lower Clearance Shield ........................................... 8
Figure 12: Venting ..................................................................... 9
Figure 13: Major Component Descriptions.............................. 11
Figure 14: Critical Hanger Placement ..................................... 15
Figure 15: Linear Heater Assembly Overview ........................ 16
Figure 16: Linear Heater Layout Overview ............................. 17
Figure 17: Linear Heater Layout Overview (Continued) .......... 18
Figure 18: U-Tube Heater Assembly Overview ...................... 26
Figure 19: U-Tube Heater Layout Overview ........................... 27
Figure 20: U-Tube Layout Overview (Continued) .................... 28
Figure 21: Reflector Joint Detail .............................................. 30
Figure 22: Tube Termination ................................................... 36
Figure 23: Gas Connection with Flexible Gas Hose................ 42

LIST OF TABLES
Table 1: Contents of BH-Series Burner Carton....................... 12
Table 2: Contents of Core and Extension Packages .............. 12
Table 3: BH-Series Component Package Guide .................... 13

SECTION 1: HEATER SAFETY

SECTION 1: HEATER SAFETY
Your Safety is Important to Us!
This symbol is used throughout the
manual to notify you of possible fire,
electrical or burn hazards. Please pay
special attention when reading and
following the warnings in these
sections.

Installation, service and annual inspection of heater
must be done by a contractor qualified in the
installation and service of gas-fired heating
equipment.
Read this manual carefully before installation,
operation or service of this equipment.
This heater is designed for heating nonresidential
indoor spaces. Do not install in residential spaces.
These instructions, the layout drawing, local codes
and ordinances, and applicable standards that apply
to gas piping, electrical wiring, venting, etc. must be
thoroughly understood before proceeding with the
installation.
Protective gear is to be worn during installation,
operation and service. Thin sheet metal parts, such
as the reflector portion of the heater and the various
venting components, have sharp edges. To prevent
injury, the use of work gloves is recommended. The
use of gloves will also prevent the transfer of body
oils from the hands to the surface of the reflector.
Before installation, check that local distribution
conditions, nature of gas and pressure, and
adjustment of the appliance are compatible.
This heater must be applied and operated under the
general concepts of reasonable use and installed
using best building practices.
This appliance is not intended for use by persons
(including children) with reduced physical, sensory or
mental capabilities, or lack of experience and
knowledge, unless they have been given supervision
or instruction concerning use of the appliance by a
person responsible for their safety. Children should
be supervised to ensure that they do no play with the
appliance.
For additional copies of the Installation, Operation
and Service Manual, please contact Roberts-Gordon
LLC.

1.2 Safety Labels and Their Placement
Product safety signs or labels should be replaced by
the product user when they are no longer legible.
Please contact Roberts-Gordon or your ROBERTS
GORDON® independent distributor to obtain
replacement signs or labels. See Page 2, Figure
1through Page 3, Figure 2.
1.3 California Proposition 65
In accordance with California Proposition 65
requirements, a warning label must be placed in a
highly visible location on the outside of the
equipment (i.e., near equipment’s serial plate). See
label placement drawing on Page 3, Figure 2 for label
location. Avoid placing label on areas with extreme
heat, cold, corrosive chemicals or other elements. To
order additional labels, please contact RobertsGordon LLC or your ROBERTS GORDON®
independent distributor.

1.1 Manpower Requirements
To prevent personal injury and damage to the heater,
two persons will be required for installation.

1 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

FIGURE 1: Top and Bottom Panel Label Placement

Gas Connection Label

Top Panel
Vent Length Label

Logo Label
Description
Logo Label
Vent Length Label
Gas Connection Label

Part Number
91031101
91039500
91018123

Bottom Panel

2 of 59

SECTION 1: HEATER SAFETY

FIGURE 2: Side and Back Panel Label Placement

Description
Part Number
Rating Plate Label
91010401
Lighting Instruction Plate Label
91029602
Wiring Label
91030301
Clearances to Combustibles Label
91013412
Proposition 65 Label
91070015
Thermostat Connection Label (not shown)
91037902

3 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

SECTION 2: INSTALLER RESPONSIBILITY
The installer is responsible for the following:
• To install the heater, as well as the gas and
electrical supplies, in accordance with applicable
specifications and codes. Roberts-Gordon LLC
recommends the installer contact a local Building
Inspector or Fire Marshal for guidance.
• To use the information given in a layout drawing
and in the manual together with the cited codes
and regulations to perform the installation.
• To install the heater in accordance with the
clearances to combustibles.
• To furnish all needed materials not furnished as
standard equipment.
• To plan location of supports.
• To provide access on all sides for burner servicing
and removal.
• To provide the owner with a copy of this
Installation, Operation and Service Manual.
• To never use heater as a support for a ladder or
other access equipment and never hang or
suspend anything from heater.
• To ensure there is adequate air circulation around
the heater and to supply air for combustion,
ventilation and distribution in accordance with
local codes.
• To safely and adequately install heater using
materials with a minimal working load of 75 lbs
(33 kg).
• To ensure the heater is placed in an approved
application.
2.1 Wall Tag
A laminated wall tag is available for the heater as
a permanent reminder of the safety instructions and
the importance of the required clearances to
combustibles. Please contact Roberts-Gordon or
your ROBERTS GORDON® independent distributor
to obtain the wall tag. Affix the tag by peeling
off the backing of the adhesive strips on the rear
surface and position the tag on a wall near the
heater (e.g. thermostat or ROBERTS GORDON®
Controller).
A copy of the wall tag (P/N 91037912) is illustrated on
the back cover. For an immediate solution, you may
affix this copy on the wall near the heater.
Know your model number and installed configuration.
Model number and installed configuration are found on
the burner and in the Installation, Operation and
Service Manual. See Page 6, Figure 3 through Page
9, Figure 12. Write the proper clearance dimensions in
4 of 59

permanent ink according to your model number and
configuration in the open spaces on the tag.
2.2 Corrosive Chemicals

CAUTION

Product Damage Hazard
Do not use heater in area containing
corrosive chemicals.
Refer to appropriate Material Safety Data
Sheets (MSDS).
Failure to follow these instructions can result
in product damage.
Roberts-Gordon LLC cannot be responsible for
ensuring that all appropriate safety measures are
undertaken prior to installation; this is entirely the
responsibility of the installer. It is essential that the
contractor, the sub-contractor, or the owner identifies
the presence of combustible materials, corrosive
chemicals or halogenated hydrocarbons* anywhere
in the premises.
* Halogenated Hydrocarbons are a family of
chemical compounds characterized by the
presence of halogen elements (fluorine, chlorine,
bromine, etc.). These compounds are frequently
used in refrigerants, cleaning agents, solvents, etc.
If these compounds enter the air supply of the
burner, the life span of the heater components will
be greatly reduced. An outside air supply must be
provided to the burners whenever the presence of
these compounds is suspected. Warranty will be
invalid if the heater is exposed to halogenated
hydrocarbons.
2.3 National Standards and Applicable Codes
All appliances must be installed in accordance with
the latest revision of the applicable standards and
national codes. This refers also to the electric, gas
and venting installation. Note: Additional standards
for installations in public garages, aircraft hangars,
etc. may be applicable.

SECTION 3: CLEARANCES TO COMBUSTIBLES

SECTION 3: CLEARANCES TO COMBUSTIBLES
3.1 Required Clearances to Combustibles
Clearances are the required distances that
combustible objects must be away from the heater to
prevent serious fire hazards. Combustibles are
materials that may catch on fire and include common
items such as wood, paper, rubber, fabric, etc.
Maintain clearances to combustibles at all times
for safety.
Clearances for all heater models are located on the
burner of the heater and on Page 6, Figure 3 through
Page 9, Figure 12 in this manual. Check the
clearances on each burner for the model heater
being installed to make sure the product is suitable
for your application and the clearances are
maintained. Read and follow the safety guidelines
below:
• Keep gasoline or other combustible materials
including flammable objects, liquids, dust or
vapors away from this heater or any other
appliance.
• The stated clearances to combustibles represents
a surface temperature of 90° F (50° C) above
room temperature. Building materials with a low
heat tolerance (such as plastics, vinyl siding,
canvas, tri-ply, etc) may be subject to degradation
at lower temperatures. It is the installer’s
responsibility to assure that adjacent materials
are protected from degradation.
• Maintain clearances from heat sensitive
equipment and workstations.
• Maintain clearances from vehicles parked below
the heater.
• Maintain clearances from swinging and overhead
doors, overhead cranes, vehicle lifts, partitions,
storage racks, hoists, building construction, etc.
• In locations used for the storage of combustible
materials, signs must be posted to specify the
maximum permissible stacking height to maintain
required clearances from the heater to the
combustibles. Signs must be posted adjacent to
the heater thermostat. In the absence of a
thermostat, signs must be posted in a
conspicuous location.
• Consult local Fire Marshal, Fire Insurance Carrier
or other authorities for approval of proposed
installation when there is a possibility of exposure
to combustible airborne materials or vapors.
• Hang heater in accordance to the minimum
suspension requirements on Page 15, Figure 14.

WARNING

Fire Hazard
Keep all flammable objects, liquids and
vapors the minimum required clearances to
combustibles away from heater.
Some objects will catch fire or explode when
placed close to heater.
Failure to follow these instructions can result
in death, injury or property damage.
• If the radiant tubes must pass through the building
structure, be sure that adequate sleeving and fire
stop is installed to prevent scorching and/or fire
hazard.

5 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.

FIGURE 3: Standard Reflector
Model

A

(inches)
B
C

BH-40

6

27

52

27

16

69

133

69

BH-60

6

35

62

35

16

89

158

89

BH-80

6

38

65

38

16

97

166

97

BH-100

6

40

70

40

16

102

178

102

BH-115/125

6

46

76

46

16

117

194

117

BH-140/150

6

50

79

50

16

127

201

127

BH-175/200

8

52

82

52

21

133

209

133

Model

A

(inches)
B
C

D

A

BH-40

6

9

52

44

16

23

133

112

BH-60

6

9

62

47

16

23

158

120

BH-80

6

9

69

54

16

23

176

138

BH-100

6

9

76

59

16

23

194

150

BH-115/125

6

9

82

65

16

23

209

166

BH-140/150

6

9

85

69

16

23

216

176

BH-175/200

8

9

88

73

21

23

224

186

Model

A

(inches)
B
C

D

A

BH-40

6

15

52

15

16

39

133

39

BH-60

6

23

65

23

16

59

166

59

BH-80

6

25

71

25

16

64

181

64

BH-100

6

27

77

27

16

69

196

69

BH-115/125

6

32

83

32

16

82

211

82

BH-140/150

6

35

87

35

16

89

221

89

BH-175/200

8

40

91

40

21

102

232

102

D

A

(centimeters)
B
C

D

FIGURE 4: One Side Reflector

A

B

D

C

(centimeters)
B
C

D

FIGURE 5: Two Side Reflectors

A

B

6 of 59

D

C

(centimeters)
B
C

D

SECTION 3: CLEARANCES TO COMBUSTIBLES

NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.

FIGURE 6: 45° Tilt Reflector
Model

A

(inches)
B
C

BH-40

8

8

50

46

21

21

127

117

BH-60

8

8

59

54

21

21

150

138

BH-80

8

8

65

60

21

21

166

153

BH-100

10

8

73

64

26

21

186

163

BH-115/125

10

8

77

69

26

21

196

176

BH-140/150

12

8

83

74

31

21

211

188

BH-175/200

12

8

85

79

31

21

216

201

D

A

(centimeters)
B
C

D

FIGURE 7: U-Tube, Standard Reflector

BH-40

(inches)
A
B
C
D
- UNAPPROVED -

(centimeters)
A
B
C
D
- UNAPPROVED -

BH-60

6

35

62

30

16

89

158

77

BH-80

6

38

68

37

16

97

173

94

BH-100

6

40

75

39

16

102

191

100

BH-115/125

6

46

78

43

16

117

199

110

BH-140/150

6

50

83

47

16

127

211

120

BH-175/200

8

54

87

51

21

138

221

130

Model
A
C

B

D

FIGURE 8: U-Tube, 45°
A

C

(centimeters)
A
B
C
D
- UNAPPROVED -

BH-60

8

8

59

42

21

21

150

107

BH-80

8

8

65

46

21

21

166

117

BH-100

8

8

73

52

21

21

186

133

BH-115/125

8

8

77

61

21

21

196

155

BH-140/150

8

8

83

66

21

21

211

168

BH-175/200

8

8

85

70

21

21

216

178

Model
D

B

BH-40

(inches)
A
B
C
D
- UNAPPROVED -

7 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.

FIGURE 9: U-Tube, Opposite 45° Reflector

BH-40

(inches)
A
B
C
D
- UNAPPROVED -

(centimeters)
A
B
C
D
- UNAPPROVED -

BH-60

8

54

59

22

21

138

150

56

BH-80

8

60

65

22

21

153

166

56

BH-100

10

64

73

22

26

163

186

56

BH-115/125

10

70

77

22

26

178

196

56

BH-140/150

12

74

83

22

31

188

211

56

BH-175/200

12

76

85

22

31

194

216

56

Model
A
B

D

C

FIGURE 10: 2-Foot Deco Grille and Protective Grille

A

C
B

D

Model

A

(inches)
B
C

BH-40

6

27

52

27

16

69

133

69

BH-60

6

35

62

35

16

89

158

89

BH-80

6

38

65

38

16

97

166

97

BH-100

6

40

70

40

16

102

178

102

BH-115/125

6

46

76

46

16

117

194

117

BH-140/150

6

50

79

50

16

127

201

127

BH-175/200

8

52

82

52

21

133

209

133

Model

A

(inches)
B
C

D

A

BH-40

6

34

27

34

16

87

69

87

BH-60

6

39

33

39

16

100

84

100

BH-80

6

40

38

40

16

102

97

102

BH-100

6

50

44

50

16

127

112

127

BH-115/125

6

54

48

54

16

138

122

138

BH-140/150

6

55

50

55

16

140

127

140

D

A

(centimeters)
B
C

D

FIGURE 11: Lower Clearance Shield*

A

B

D

C

BH-175/200

*When installed in the first 10' (3 m).

8 of 59

- UNAPPROVED -

(centimeters)
B
C

- UNAPPROVED -

D

SECTION 3: CLEARANCES TO COMBUSTIBLES

NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.

FIGURE 12: Venting

A

Unvented
Radiant Tubes
Vented

E

Vent
Pipes

F

Model

A

(inches)
E

F

(centimeters)
A
E
F

BH-40

14

18

18

36

46

46

BH-60

14

18

18

36

46

46

BH-80

20

24

18

51

61

46

BH-100

20

24

18

51

61

46

BH-115/125

20

24

18

51

61

46

BH-140/150

20

30

18

51

77

46

BH-175/200

20

30

18

51

77

46

9 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

SECTION 4: NATIONAL STANDARDS AND
APPLICABLE CODES
4.1 Gas Codes
The type of gas appearing on the nameplate
must be the type of gas used. Installation must
comply with national and local codes and
requirements of the local gas company.
United States: Refer to National Fuel Gas Code
NFPA 54/ANSI Z223.1 - latest revision.
Canada: Refer to Natural Gas and Propane
Installation Code CSA B149.1 - latest revision.
4.2 Aircraft Hangars
Installation in aircraft hangars must be in
accordance with the following codes:
United States: Refer to Standard for Aircraft
Hangars, NFPA 409 - latest revision.
Canada: Refer to Natural Gas and Propane
Installation Code CSA B149.1 - latest revision.
In aircraft storage and servicing areas, heaters
shall be installed at least 10' (3 m) above the
upper surface of wings or of engine enclosures
of the highest aircraft which may be housed in
the hangar. The measurement shall be made
from the wing or engine enclosure (whichever is
higher from the floor) to the bottom of the heater.
• In shops, offices and other sections of aircraft
hangars communicating with aircraft storage or
servicing areas, heaters shall be installed not
less than 8' (2.4 m) above the floor.
• Suspended or elevated heaters shall be so
located in all spaces of aircraft hangars that they
shall not be subject to injury by aircraft, cranes,
movable scaffolding or other objects. Provisions
shall be made to assure accessibility to
suspended heaters for recurrent maintenance
purposes.

4.3 Public Garages
Installation in garages must be in accordance
with the following codes:
United States: Refer to Standard for Parking
Structures NFPA 88A - latest revision or the
Code for Motor Fuel Dispensing Facilities and
Repair Garages, NFPA 30A - latest revision.
Canada: Refer to Natural Gas and Propane
Installation Code CSA B149.1 - latest revision.
• Heaters must not be installed less than 8'
(2.4 m) above the floor. Minimum clearances to
combustibles must be maintained from vehicles
parked below the heater.
• When installed over hoists, minimum
clearances to combustibles must be maintained
from the upper most point of objects on the hoist.
4.4 Electrical
The heater must be electrically grounded in
accordance with the following codes:
United States: Refer to National Electrical Code®,
NFPA 70 - latest revision. Wiring must conform to
the most current National Electrical Code®, local
ordinances and any special diagrams furnished.
Canada: Refer to Canadian Electrical Code,
CSA C22.1 Part 1 - latest revision.
4.5 Venting
The venting must be installed in accordance with
the requirements within this manual and the
following codes:
United States: Refer to National Fuel Gas Code
NFPA 54/ANSI Z223.1 - latest revision.
Canada: Refer to Natural Gas and Propane
Installation Code CSA B149.1 - latest revision.
4.6 High Altitude
These heaters are approved for installations up
to 2000' (610 m)(US), 4500' (1370 m)(Canada)
without modification. Consult factory if US
installation is above 2000' (610 m) or Canadian
installation is above 4500' (1370 m).

10 of 59

SECTION 5: MAJOR COMPONENTS

SECTION 5: MAJOR COMPONENTS
FIGURE 13: Major Component Descriptions
Burner with Tube Gasket
Must be installed with the
flame observation window
facing down.

Reflector (Aluminum or
Stainless Steel)
Alternate overlap as shown on
overview and on Page 17,
Figure 16. Minimum overlap is
6'' (16 cm).

Burner Tube
Supplied in 10' (3 m) lengths.
Burner tube is always the first
tube after the burner.

Tube
Hot rolled or heat treated
aluminized tube supplied in
10' (3 m) lengths.

Tube and Reflector Hanger
with Clamp Package
Position this hanger no more
than 4” (10 cm) away from the
burner.

Coupling Assembly with Lock

Reflector End Cap
Punch out center section to
accommodate tube.

Tube and Reflector Hanger
Suspend system from these
hangers.
Vent Adapter

Reflector Support Strap &
Wire Form

Flex Gas Line with
Shut Off Cock

Turbulator
Turbulator must be installed in the
last standard section of tube.
Turbulator is not required on the
BH-125/150/175/200. For
installation, see Page 21, Step 6.4

11 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

5.1 Standard Parts List
Table 1: Contents of BH-Series Burner Carton
Part No.

Description

BH-40 BH-60 BH-80 BH-100 BH-115 BH-125 BH-140 BH-150 BH-175 BH-200

ET71XXXXX Burner (Rate and Fuel Varies)

1

1

1

1

1

1

1

1

1

1

90709700 Blower Assembly with Cord

1

1

1

1

1

1

1

1

1

1

02568200 Gasket (Burner to Burner Tube)

1

1

1

1

1

1

1

1

1

1

90709801 Gasket (Blower to Burner)

1

1

1

1

1

1

1

1

1

1

170102NA Installation, Operation and Service Manual

1

1

1

1

1

1

1

1

1

1

91201708 Pipe Nipple (Black) 1/2" NPT x 4"

1

1

1

1

1

1

1

1

1

1

94273914 Hex Head Bolts 5/16" - 18 Rolok

4

4

4

4

4

4

4

4

4

4

96411600 Split Lock Washer

4

4

4

4

4

4

4

4

4

4

*91412200 Flexible Stainless Steel Gas Hose, 1/2" NPT (US Models Only)

1

1

1

1

1

1

-

-

-

-

*91412204 Flexible Stainless Steel Gas Hose, 3/4" NPT (US Models Only)

-

-

-

-

-

-

1

1

1

1

91907302 S-Hooks

2

2

2

2

2

2

2

2

2

2

91911700 Outside Air Collar

1

1

1

1

1

1

1

1

1

1

94118106 #8 x 3/8 Hex Washer Head (for Outside Air Collar)

3

3

3

3

3

3

3

3

3

3

92311800 Keps Nut

4

4

4

4

4

4

4

4

4

4

03051503 Turbulator Adapter

1

1

1

1

1

-

1

-

-

-

03051504 Turbulator 2.5' (76 cm), Aluminized Steel

2

4

4

1

3

-

1

-

-

-

03051505 Turbulator 2.5' (76 cm), Stainless Steel

1

-

-

-

-

-

-

-

-

-

*Canadian models: Rubber (Type 1) Gas Hoses available as an accessory. See Page 41.
Table 2: Contents of Core and Extension Packages
Core Packages
Hot Rolled
Part No.

Description

Extension Packages

Aluminized

Hot Rolled

Aluminized

20' 30' 40' 10' 20' 30' 40' 10' 20' 30' 40' 10' 20' 30' 40'
(6m)

(9m)

(12m)

(3m)

(6m)

(9m)

(12m)

(3m)

(6m)

(9m)

(12m)

(3m)

(6m)

(9m)

(12m)

91409300 Tube, Hot Rolled Steel, 10' (3 m)

1

2

3

-

-

-

-

1

2

3

4

-

-

-

-

91409408 Tube, HT Aluminized, 10' (3 m)

-

-

-

-

1

2

3

-

-

-

-

1

2

3

4

03051101 Burner Tube, ALUMI-THERM Steel, 10' (3 m)

-

1

1

-

-

1

1

-

-

-

-

-

-

-

-

03051601 Burner Tube, HT ALUMI-THERM Steel, 10' (3 m)

1

-

-

1

1

-

-

-

-

-

-

-

-

-

-

01312700 Coupling Assembly

1

2

3

-

1

2

3

1

2

3

4

1

2

3

4

02750303 Standard Reflector, 8' (3.5 m)

3

4

6

2

3

4

6

2

3

4

6

2

3

4

6

02750800 End Cap

2

2

2

2

2

2

2

-

-

-

-

-

-

-

-

03090100 Tube and Reflector Hanger

3

4

5

2

3

4

5

1

2

3

4

1

2

3

4

91907302 S-Hook

3

4

5

2

3

4

5

1

2

3

4

1

2

3

4

03050010 Reflector Support Package (Strap, Wire Form, Screws)

2

3

5

1

2

3

5

2

3

4

6

2

3

4

6

®

91107720 U-Clip Package

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

90502700 Vent Adapter

1

1

1

1

1

1

1

-

-

-

-

-

-

-

-

01318901 Tube Clamp Package

1

1

1

1

1

1

1

-

-

-

-

-

-

-

-

CP20HRS

CP30HRS

CP40HRS

CP10ALUM

CP20ALUM

CP30ALUM

CP40ALUM

EXP10HRS

EXP20HRS

EXP30HRS

EXP40HRS

EXP10ALUM

EXP20ALUM

EXP30ALUM

EXP40ALUM

®

Part Number

12 of 59

SECTION 5: MAJOR COMPONENTS

Table 3: BH-Series Component Package Guide

Model

Tubing Length

Core Packages

Minimum

Standard

Aluminized

BH-40

10' (3 m)

-

CP10ALUM

BH-60

20' (6 m)

CP20HRS

CP20ALUM

BH-80

20' (6 m)

CP20HRS

CP20ALUM

BH-100

30' (9 m)

CP30HRS

CP30ALUM

BH-115

30' (9 m)

CP30HRS

CP30ALUM

BH-125

40' (12 m)

CP40HRS

CP40ALUM

BH-140

40' (12 m)

CP40HRS

CP40ALUM

BH-150

50' (15 m)

CP30HRS + EXP20HRS

CP30ALUM + EXP20ALUM

BH-175

50' (15 m)

CP30HRS + EXP20HRS

CP30ALUM + EXP20ALUM

BH-200

60' (18 m)

CP30HRS + EXP30HRS

CP30ALUM + EXP30ALUM

Additional tubing length may be added to heater. Tubing must be heat-treated, aluminized or porcelain
coated. Any additional tubing lengths are considered as vent length for length determination. Maximum
venting length for minimum heater length is 45' (13.7 m) total.

13 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

SECTION 6: HEATER INSTALLATION

WARNING

Severe Injury Hazard
Secure burner to burner tube with bolts and
lockwashers.
Hang heater with materials with a minimum
working load of 75 lbs (33 kg).
Failure to follow these instructions can result
in death, injury or property damage.

WARNING

Cut/Pinch Hazard
Wear protective gear during installation,
operation and service.
Edges are sharp.
Failure to follow these instructions can result
in injury.
To ensure your safety and comply with the terms of
the warranty, all units must be installed in
accordance with these instructions.
The gas or the electrical supply lines must not be
used to support the heater.
Do not locate the gas or electric supply lines directly
over the path of the flue products from the heater.
The heater must be installed in a location that it is
readily accessible for servicing.
The heaters must be installed in accordance with
clearances to combustibles as indicated on the rating
plate and in this instruction manual.
The minimum and maximum gas inlet pressures
must be maintained as indicated on the rating plate.
Typical installation configurations are shown on
Page 15, Figure 14.

14 of 59

Expansion and contraction of the tube dictates that
the minimum suspension lengths must be
maintained. See table on Page 15, Figure 14.

SECTION 6: HEATER INSTALLATION

FIGURE 14: Critical Hanger Placement

Typical Suspension Details
Beam Clamp
Anchor
Screw Hook
3/8"

24" min.*
(61 cm)

Chain Size
3/16"
Minimum

Rod 3/8"

Concrete Beam
Wood Beam
Locknut

Washers

“X”*
S-hooks

Turnbuckle
Not Included

* Allows for thermal expansion of system

S-hooks
Hanger

Side View
Hanger
Reflector

Must Be Within 4" (10 cm)

Description
S-Hook
Tube/Reflector Hanger

Part Number
91907302
03090100

Front View
Run Length
10' (3 m) - 50' (15.2 m)
51' (15.5 m) - 60' (18.3 m)
61' (18.6 m) - 80' (24.4 m)

45° Angle
Typical Expansion
±1" (3 cm)
±2" (5 cm)
±3" (8 cm)

Minimum “X” Length
12" (30.5 cm)
18" (45.7 cm)
24" (61 cm)

15 of 59

16 of 59
Reflector Support

Tube and Reflector Hanger
Coupling

Burner Tube

Tube Clamp
Package

Burner

Reflector End Cap

Reflector

Tube
Turbulator
(With Select Models)

Vent Adapter

U-Clips

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

FIGURE 15: Linear Heater Assembly Overview

SECTION 6: HEATER INSTALLATION

FIGURE 16: Linear Heater Layout Overview

b
c

LEGEND
g

Burner
Reflector

d

f
10' (3 m) Tube Length

Tube
Tube/Reflector
Hanger

b
c

g

Coupling Assembly

d

e

Vent Adapter
f

a = 14" (36 cm)
reflector width (not shown)

20' (6.1 m) Tube Length

b = 2" (5 cm)
end cap to burner

b

c = 2" (5 cm)
end cap to hanger
d = 7' 6" (2.3 m)
distance first hanger
e = 10' (3 m)
distance between hangers

g

c

d

e

e

f
30' (9.1 m) Tube Length

f = 12.5" (32 cm)
burner height
g = 11" (28 cm)
burner length

g

b
c

d

e

e

e

f

40' (12.2 m) Tube Length

g

b
c

d

e

e

e

e

f
50' (15.2 m) Tube Length

17 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

FIGURE 17: Linear Heater Layout Overview (Continued)
b
c

g

d

e

e

e

e

e

e

e

e

e

e

e

e

e

e

e

e

e

f
60' (18.3 m) Tube Length

g

b
c

d

f
70' (21. 3 m) Tube Length

g

b
c

d

e

f
80' (24.4 m) Tube Length

Step 6.1 Burner Tube Installation
NOTE:
Tubing requires a downward
slope of 1/2" (13 mm)
per 20' (6 m) away
from burner.

Offset mounting
hole must be
to the top.

S-Hook

Hanger
Burner Tube

Weld seam
must be to the
bottom of the tube.
7' 6" ± 1'
(229 cm ± 25 cm)

Description
Burner Tube
S-Hook
Tube/Reflector Hanger

18 of 59

Part Number
03051XXX
91907302
03090100

SECTION 6: HEATER INSTALLATION

Step 6.2 Tube Clamp Package Installation

Bolt

Tube Clamp
Flat
Washer

Nut

(Torque 120 in/lb
13.56 Nm)

Description
Tube Clamp Package
Tube Clamp
Bolt
Flat Washer
Nut

Part Number
01318901
01396801
97113940
95211600
92113900

Step 6.3 Coupling and Tube Assembly
Close coupling
A with
tab.

Start slide bar/coupling lock
B onto
coupling.

Tab
Slide Bar/Coupling Lock
Wide End
Coupling

Open

3" (8 cm) to
4" (10 cm)
Closed

C Insert tubes into coupling.

D Tighten coupling to join tubes.
Slide Bar/Coupling Lock
Coupling

Orient coupling so that
the impact block is in the
2:00 or 10:00 o’clock
positions.

Tube
Tube

Tube
Description
Coupling
Slide Bar/Coupling Lock
Tube

Part Number
01329600
01329700
91409XXX

19 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

Step 6.3.1 Coupling and Tube Assembly (Continued)
Tighten slide bar as shown below.

Drive slide bar until tight.
End of slide bar should be
within tolerance listed below.

± 2" (5 cm)
Correct slide bar
dimensions

Incorrect slide bar
position

• Repeat Step 6.3 A - D until all tubes are assembled. See Page 20, Step 6.3.2.

Step 6.3.2 Coupling and Tube Assembly (Continued)
Model
BH-40
BH-60
BH-80
BH-100
BH-115
BH-125
BH-140
BH-150
BH-175
BH-200

7' 6" ± 1'
(2.3 m ± .25 m)

10' ± 1'
(3 m ± .25 m)

Total Overall
Tube Length

20 of 59

Tube Length
Minimum
10' (3 m)
20' (6 m)
20' (6 m)
30' (9 m)
30' (9 m)
40' (12 m)
40' (12 m)
50' (15 m)
50' (15 m)
60' (18 m)

SECTION 6: HEATER INSTALLATION

Step 6.4 Turbulator Installation
Turbulator must be installed in the last
standard section of tube. Turbulator is
not required on the BH-125/150/175/200.
Twis t

Turbulator
Section
Turbulator
Adapter

Tab

Turbulator section 2.5'
(76.2 cm) (stainless) used in
BH-40 heaters must be in the
section of turbulator nearest
to the burner.
Description
Turbulator Adapter 2.5' (76.2 cm)
Turbulator Section 2' (61 cm)
Turbulator Section 2.5' (76.2 cm)(Stainless)
Tube

Turbulator Installation
Model
Tube Section
BH-40
1st 10' (3 m) Section
BH-60
2nd 10' (3 m) Section
BH-80
2nd 10' (3 m) Section
BH-100
3rd 10' (3 m) Section
BH-115
3rd 10' (3 m) Section
BH-125
N/A
BH-140
4th 10' (3 m) Section
BH-150
N/A
BH-175
N/A
BH-200
N/A

Pull String
Fold tab around outside
of tube nearest to the vent to
hold turbulator in place.
Part Number
03051503
03051504
03051505
91409XXX

21 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

Step 6.5 Reflector Installation

WARNING

Fire Hazard
Support reflector with reflector hanger
and support strap.
Reflector must not touch tube.
Failure to follow these instructions can result
in death, injury or property damage.

NOTE: All tube surfaces must be covered
by a reflector, except for a U-tube.

Hanger
Burner Tube

Reflector
Description
Tube/Reflector Hanger
Burner Tube
Reflector

22 of 59

Part Number
03090100
03051XXX
02750303

SECTION 6: HEATER INSTALLATION

Step 6.5.1 Reflector, U-Clip and Reflector Support Installation
The pictorial drawings of the heater construction in
reflector supports and U-clips depend on the
Section 6 are schematic only and provide a general individual installation. Use either pop rivets or sheet
guideline of where hangers, reflector supports and
metal screws instead of u-clips when installing end
U-clips are to be installed.
caps and joint pieces in areas where impact and high
To ensure proper expansion and contraction
wind may be a factor. The following rules must be
movement of the reflectors, a combination of U-clips observed.
and reflector supports are used. The positioning of
1. The first reflector after the burner must be affixed in
the middle of the reflector with a reflector support and
tight screws.

Tight
Sheet Metal
Screw

Wire Form

Reflector
End Cap

First Reflector

Reflector Support
Strap

U-clips

Overlap must be a
minimum of 6" (16 cm).

2B
Slip Overlap

6"
(16 cm)

2. The overlap at the first and second reflector is a slip overlap.
Thereafter, every third reflector joint is a slip overlap. A slip
overlap is achieved by either:
a.) both reflectors lay inside a hanger.
(No reflector support needed.)
b.) using a reflector support with
loose screws at the reflector
overlap.

Loose screws
loosened 1/16"
(.16 cm) to allow
slippage.
2A
Slip Overlap

3A
Non-Slip Overlap

3. The remaining reflector overlaps require a non-slip
overlap connection. To affix the reflectors together in
a non-slip overlap either:
a.) use reflector support and tight screws.
b.) if both reflectors lay inside a hanger, u-clips or
sheet metal screws may be used.
This section of three reflectors joined together must
be affixed to the tube with at least one reflector support
with tight screws.
Description
Reflector Support Package
Wire Form
Reflector Support Strap
Screw #8 x 3/4"
U-Clip Package
Reflector End Cap

Part Number
03050010
91908004
03050000
94320812
91107720
027508XX

Reflector
Reflector
Support

Reflector

Tight
Screws

3B
Non-Slip Overlap

U-clip
(2 Clips per
Non-slip Overlap
Inside a Hanger)

23 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

Step 6.6 Burner Installation

Extra chain min.
12" (30 cm)

S-hook

Burner Tube
Burner

Description
Bolt
Burner
Lock Washer
Gasket

24 of 59

Gasket

Part Number
94273914
ET71XXXXX
96411600
02568200

Lock
Washer

Bolt
(Torque 120 in/lb
13.56 Nm)

SECTION 7: OPTIONAL HEATER ACCESSORIES

SECTION 7: OPTIONAL HEATER ACCESSORIES

WARNING

Cut/Pinch Hazard
Wear protective gear during installation,
operation and service.
Edges are sharp.
Failure to follow these instructions can result
in injury.
7.1 U-Tube Configuration
Heaters (except BH-40) are approved for optional
U-tube configurations.
The U-tube may be installed in either a standard
horizontal position, a 45° position or in an opposite
45° position as shown on Page 7, Figure 7 through
Page 8, Figure 9. When using a U-tube configuration,
the following additional rules must be adhered to:
• A minimum of 10' (3 m) on BH-60/80 and a
minimum of 15' (4.5 m) on BH-100/115/125/140/
150/175/200 is required between the burner and
the U-tube.
• The correct turbulator (See Page 21, Step 6.4)
must be installed in the last standard section of
the tube.
• The burner must never be operated in a tilted
position.
• The heater must be properly supported at all
locations. See Page 27, Figure 19.

25 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

FIGURE 18: U-Tube Heater Assembly Overview
U-tube
Support Bracket
Reflector
Support

Burner

Vent Adapter

Turbulator
(With Select
Models)

Tube Clamp
Package

Reflector

Tube

Burner
Tube

U-tube, Standard
Couplings

1
U-tube,
45°

1

1

26 of 59

U-clips

2

Reflector
End Caps
U-bolt
1 4"Tight
(10 cm) u-bolt,

2

2

Loose U-bolt

4" (10 cm) u-bolt,
secured to burner tube
secured to bracket with
with 1/4" (.6 cm)
1/4" (.6 cm) lockwashers
lockwashers and
and 1/4" (.6 cm)-20 hex
1/4"(.6 cm) -20 hex nuts. nuts on top and bottom to
allow for tube expansion
and contraction.

U-tube,
Opposite 45°

2

U-bolt
Nut
Lock Washer
Lock Washer
Nut

U-tube
18" (46 cm)
Center to Center

SECTION 7: OPTIONAL HEATER ACCESSORIES

FIGURE 19: U-Tube Heater Layout Overview

LEGEND

g

b
c

e

Burner
Reflector

h

Tube 10' (3.0 m)

20' (6.1 m) Tube Length*

Tube 5' (1.5 m)**
Tube/Reflector
Hanger

g

Coupling
Assembly

b
c

d

f

U-tube
Vent Adapter
(Not Shown)

h
30' (9.1 m) Tube Length**

a = 14" (36 cm)
Reflector Width (Not Shown)
b = 2" (5 cm)
End Cap to Burner

g

c = 2" (5 cm)
End Cap to Hanger

b
c

d

e

d = 7' 6" (2.3 m)
Distance First Hanger
e = 10' (3.0 m)
Distance Between Hangers

h
40' (12.2 m) Tube Length

f = 5' (1.5 m)
Distance Between Last Full Tube
Hanger and Half Tube Hanger
g = 12.5" (32 cm) Burner Length
h = 11" (28 cm) Burner Height

g

b
c

d

e

f

* Requires the last reflector
before the u-tube to be cut in
half for use on both sides.
** Requires the last tube before
the u-tube to be cut in half for
use on both sides.

h
50' (15.2 m) Tube Length* **

27 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

FIGURE 20: U-Tube Layout Overview (Continued)
b
c
g

d

e

e

h
60' (18.3 m) Tube Length

b
c
g

d

e

e

f

h
70' (21.3 m) Tube Length**

b
c
g

d

e

e

e

h
80' (24.4 m) Tube Length

7.2 Elbow Package Configuration
Step 7.2.1 Elbow Installation
Tube

Coupling

Description
Elbow Package
90° Elbow
Coupling
Reflector End Cap
Reflector Joint Piece
U-Clip Package

28 of 59

Part Number
02718702
01335801
01312700
02750800
02750900
91107720

90° Elbow

Minimum Distance Required
Between Burner and Elbow
Minimum
Model
Distance
BH-40
10' (3 m)
BH-60
10' (3 m)
BH-80
10' (3 m)
BH-100
15' (4.5 m)
BH-115
15' (4.5 m)
BH-125
15' (4.5 m)
BH-140
15' (4.5 m)
BH-150
15' (4.5 m)
BH-175
15' (4.5 m)
BH-200
15' (4.5 m)

SECTION 7: OPTIONAL HEATER ACCESSORIES

Step 7.2.2 Elbow Installation

Tube

Coupling

Step 7.2.3 Reflector Joint Installation

Step 7.2.4 Reflector Joint Installation

29 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

Step 7.2.5 Reflector Joint Detail

FIGURE 21: Reflector Joint Detail

30 of 59

SECTION 7: OPTIONAL HEATER ACCESSORIES

7.3 Reflector Side Extension
Step 7.3.1 Bracket Installation
Tube

Reflector
Tube and Reflector Hanger

Reflector Support
Reflector Side
Extension Bracket
(2 per Reflector)
Use additional supports
in high air movement
applications.
Description
Reflector Side Extension Package
Reflector Side Extension
Retainer Clips
Sheet Metal Screws

Part Number
02712700
01368000
02751200
94118106

Order Separately
Reflector Side Extension Bracket

01329910

Step 7.3.2 Side Reflector Installation

#8 x 3/8 (3.9 x 9.5 mm) Sheet Metal Screw
Cut relief notches for
supports and hangers.

Retainer Clip
(2 per Side)
Reflector Side Extension

31 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

7.4 Lower Clearance Shield Installation
Step 7.4.1 Shield Support Strap Assembly

Reflector

17"
(43 cm)

12"
(30 cm)

Align Pilot Holes

Lower Clearance Shield
Locknuts

Washers

Screws

Description
Lower Clearance Shield Package
Shield Support Strap
Lower Clearance Shield 8' (2.4 m)
Locknut #8
Flat Washer #8
Screw #8 x 3/8''

Part Number
01397501
01397500
02793000
92311400
95310800
93511406

7.5 Two-Foot Decorative Grille Installation
Step 7.5.1 Grille Installation

Description
Aluminum Grille 2' x 4' (61 x 122 cm)

32 of 59

Part Number
91407000

SECTION 7: OPTIONAL HEATER ACCESSORIES

Step 7.5.2 Frame Shield Installation

Description
Deco Grille Shield

Part Number
01365900

Step 7.5.3 Reflector Side Extension Installation for Decorative Grilles

Distance "A"
Minimum
Maximum
2" (4 cm)
6" (15 cm)
6" (15 cm)
10" (26 cm)
10" (26 cm)
14" (37 cm)

Extension
Part No.
Width
01370408
8" (20 cm)
01370412
12" (30 cm)
01370416
16" (40 cm)

Description
Reflector Side Extension

Part Number
01370412

33 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

7.6 Protective Grille Installation
Step 7.6.1 Silicone Cap Installation

Silicone Cap
Grille
Finger

Description
Grille Section
Grille End Cap
Silicone Cap

Part Number
08050001
08050002
91915951-6P

Step 7.6.2 Grille End Cap Installation

B

A

Grille

Grille End Cap

C

D
Bend up 90°.

Pull outward.

Step 7.6.3 Grille Installation
Reflector

40"
(101 cm)

Grille

Final Grille
Section
Grille
End Cap

34 of 59

SECTION 8: VENTING

SECTION 8: VENTING

WARNING

Any portion of vent pipe passing through a
combustible wall must have an approved thimble
to conform with the above listed codes.
Vent pipe must be sloped downward away from the
heater 1/2'' (1 cm) for every 20' (6 m).

Carbon Monoxide Hazard
Heaters installed unvented must be interlocked
with sufficient building exhaust.
Heaters must be installed according to the
installation manual.
Failure to follow these instructions can result
in death or injury.

WARNING

The heater may be individually vented or common
vented. When venting horizontally, a maximum of two
heaters can be commonly vented. See Page 37,
Section 8.9. When venting vertically, a maximum of
four heaters can be commonly vented. See Page 38,
Section 8.10.
The heater may also be installed unvented in certain
circumstances according to building ventilation
codes. Refer to the above codes and Page 36,
Section 8.2 for further information. Unvented
operation also requires compliance with the
clearances to combustibles given on Page 9, Figure
12.
The bottom of the vent or air intake terminal shall not
be located less than 1' (0.3 m) above grade level.

Cut/Pinch Hazard
Wear protective gear during installation,
operation and service.
Edges are sharp.
Failure to follow these instructions can result
in injury.

The vent shall not terminate less than 7' (2.1 m)
above grade where located adjacent to public
walkways.
Vent terminal must be installed at a height sufficient
to prevent blockage by snow, and building materials
protected from degradation by flue gases.
Secure all joints with #8 x 3/8 sheet metal screws.
Seal all joints with high temperature silicone sealant.

8.1 Venting
This heater must be vented in accordance with the
rules contained in this manual and with the following
national codes and any state, provincial or local
codes which may apply:
United States: Refer to National Fuel Gas Code
NFPA 54/ANSI Z223.1 - latest revision.
Canada: Refer to Natural Gas and Propane
Installation Code CSA B149.1 - latest revision.

Vent terminal must be beyond any combustible
overhang.
8.1.1 United States Requirements
Vent must terminate at least 3' (0.9 m) above any
forced air inlet located within 10' (3.1 m).

Exhaust end of heater will accept a 4'' (10 cm) vent
pipe using the vent adapter (P/N 90502700). To
prevent leakage of condensation, install the vent
adapter with the seam on top and seal the joint using
a high temperature silicone sealant.

8.1.2 Canadian Requirements
The vent shall not terminate within 6' (1.8 m) of a
mechanical air supply inlet to any building.
The vent shall not terminate within 3' (0.9 m) of a
window or door that can be opened in any building,
any non-mechanical air supply inlet to any building,
or of the combustion air inlet of any other appliance.

Vent must terminate at least 4' (1.2 m) below, 4'
(1.2 m) horizontally from, or 1' (0.3 m) above any
door, operable window, or gravity air inlet into any
building.

35 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

8.2 Unvented Operation
Sufficient ventilation must be provided in the amount
of 4 cfm per 1000 Btu/h firing rate (United States); 3
cfm per 1000 Btu/h firing rate (Canada).
Use of optional outside combustion air is not
recommended with unvented heaters.
If exhaust fans are used to supply ventilation air, an
interlock switch must be used to prevent the heater
from coming on when the fans are off. This may be
done using a pressure switch.

A vent shall not extend less than 2' (0.6m) above the
highest point where it passes through a flat roof of a
building.
8.5 Unvented Operation Tube Termination
Turndown type vent terminal with a screen must be
installed at the exhaust end of the tube. Vent terminal
design shall not incorporate backdraft flap.
FIGURE 22: Tube Termination

8.3 Horizontal Venting
In noncombustible walls only, vent terminal
(P/N 02537801-1P) may be used.
For 4" (10 cm) vents in either combustible or
noncombustible walls, use Tjernlund VH1-4 (P/N
90502100) or equivalent, insulated vent terminal.
Follow the manufacturer's instructions for proper
installation.
For 6" (15 cm) common vents in either combustible
or noncombustible walls, use Tjernlund VH1-6 (P/N
90502101) or equivalent, insulated vent terminal.
Follow the manufacturer's instructions for proper
installation.
8.4 Vertical Venting
For 4'' (10 cm) common vent, an approved vent cap
(P/N 90502300) must be used.
For 6'' (15 cm) common vent, an approved vent cap
(P/N 90502302) must be used.
For common vertical venting of more than two
heaters, See Page 38, Section 8.10.

8.6 Length Requirements
The maximum vent length allowed is 45' (13.7 m).
The maximum outside air supply duct length allowed
is 45' (13.7 m).
The total vent length, plus outside air duct length,
plus any extensions to minimum heat exchanger
lengths, cannot exceed 65' (19.8 m).
Vent length should be limited to less than 20' (6 m). If
using vent lengths greater than 20' (6 m),
condensation will form in the vent pipe. Insulation
and additional sealing measures (high temperature
silicone at all seams) are required. Optional heat
exchanger beyond minimum lengths is considered as
vent length for length determination.
Subtract 15' (4.6 m) of maximum allowed vent or duct
length per vent elbow if more than two are used.

8.7 Horizontal Ventilation 4'' (10 cm) Pipe
SIDE VIEW
Non-Combustible Wall Only

Combustible or
Non-Combustible Wall

Vent Adapter

Vent Adapter

18" (46 cm)
Min.

4" (10 cm)
Single Wall Pipe
Vent Terminal
Description
Vent Terminal (Comb. Wall)
Vent Terminal

36 of 59

Part Number
90502100
02537801-XX

4" (10 cm) Single Wall Pipe

Vent Terminal

SECTION 8: VENTING

8.8 Vertical Ventilation 4'' (10 cm) Pipe

Description
Vent Cap 4" (10 cm)

Part Number
90502300

8.9 Common Side Wall Venting
TOP VIEW

Vent Terminal
Tjernlund VH1-6 or Equivalent
Outside Wall

Vent Adapter

6" (15 cm) Single Wall Pipe

Sweeping 'T'
Connection

Vent Adapter

4" (10 cm) Single Wall Pipe

Vent Terminal
Tjernlund VH1-6 or Equivalent
Outside Wall

6" (15 cm) Single Wall Pipe

Vent Adapter

Sweeping 'Y'
Connection
4" (10 cm) Single Wall Pipe
4" (10 cm) Single Wall Pipe
Description
Vent Terminal 6" (15 cm)

Part Number
90502101

Vent Adapter

Requirements:
• Maximum of two heaters can be commonly
vented through a side wall.
• Heaters must be of the same BTU output.
• Heaters must be controlled by a common
thermostat.

37 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

8.10 Common Vertical Venting

Requirements:
• Maximum of four heaters can be commonly
vented through the roof.
• Heaters must be of the same BTU output.
• Heaters must be controlled by a common
thermostat.
• Connections to a common stack must be
positioned to avoid direct opposition between
streams of combustion gases.

38 of 59

SECTION 8: VENTING

8.11 Outside Combustion Air Supply
IMPORTANT: If the building has a slight negative
pressure or corrosive contaminants, such as
halogenated hydrocarbons, are present in the air, an
outside combustion air supply to the heater is
required. Seal all combustion air pipe joints.

8.11.1 Length Requirements
Follow the constraints listed on Page 36, Section 8.6.

Use of optional outside combustion air is not
recommended with unvented heaters.
The air supply duct may have to be insulated to
prevent condensation on the outer surface. The
outside air terminal must not be more than 1' (31 cm)
above the vent terminal.
8.11.2 Vertical Outside Air Supply for Single Heater Installation

Description
Vent Cap 4" (10 cm)

Part Number
90502300

Vent Cap

Wall

8.11.3 Horizontal Outside Air Supply for Single Heater Installation

4" (10 cm)
Single Wall Pipe
Flex Hose
(Recommended)
Burner
Band Clamp
(Recommended)

Description
Vent Cap 4" (10 cm)

Part Number
90502300

39 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

8.11.4 Vertical Outside Air Supply for Double Heater Installation

Vent Cap
Roof
6" (15 cm) Single Wall Pipe
Flex Hose
(Recommended)
Burner
Band Clamp
(Recommended)

Description
Vent Cap 6" (15 cm)

Sweeping 'T'
Connection
Burner
Flex Hose
(Recommended)

4" (10 cm)
Single Wall Pipe

Part Number
90502302

Requirements:
• Heaters must be controlled by a common thermostat.
8.11.5 Horizontal Outside Air Supply for Double Heater Installation

Vent Cap

Outside Wall

6" (15 cm) Single Wall Pipe

Flex Hose
(Recommended)
Burner
Sweeping 'Y'
Connection
4" (10 cm) Single Wall Pipe
(Seal All Joints)
Burner
Band Clamp
(Recommended)

Description
Vent Cap 6" (15 cm)

Part Number
90502302

Requirements:
• Heaters must be controlled by a common thermostat.

40 of 59

SECTION 9: GAS PIPING

SECTION 9: GAS PIPING

WARNING

Fire Hazard
Tighten gas hose fittings to connect gas
supply according to Figure 23.
Gas hose can crack when twisted.
Gas hose moves during normal operation.
Use only 36" (91 cm) long connector of 1/2" or
3/4" nominal ID.
Connector supplied with heater for U.S.
models (not with Canadian models).
Failure to follow these instructions can result
in death, injury or property damage.

WARNING

Explosion Hazard
Leak test all components of gas piping
before operation.

Install the gas hose as shown on Page 42, Figure 23.
The gas hose accommodates expansion of the
heating system and allows for easy installation and
service of the burner. Before connecting the burners
to the supply system, verify that all high pressure
testing of the gas piping has been completed.
There is an expansion of the tube with each firing
cycle; this will cause the burner to move with respect
to the gas hose. This can cause a gas leak resulting
in an unsafe condition if the gas connection is not
made strictly in accordance with Figure 23 on Page
42.
Meter and service must be large enough to handle all
the burners being installed plus any other connected
load. The gas hose which feeds the system must be
large enough to supply the required gas with a
maximum pressure drop of 1/2" wc. When gas piping
is not included in the layout drawing, the local gas
supplier will usually help in planning the gas piping.
Gas lines must meet applicable codes:
United States: The Flexible Stainless Steel Gas
Hose (US models) supplied with the heater is certified per the Standard for Connectors for Gas Appliances, ANSI Z21.24/CSA 6.10 - latest revision.
Canada: The Rubber Type 1 Gas Hose (Canadian
models) optional with the heater is certified as being
in compliance with the Standard for Elastomeric
Composite Hose and Hose Couplings for Conducting
Propane and Natural Gas, CAN/CGA 8.1 - Latest
revision.
• Check the pipe and tubing ends for leaks
before placing heating equipment into
service. When checking for gas leaks, use a
soap and water solution; never use an open
flame.

Gas can leak if piping is not installed
properly.
Do not high pressure test gas piping with
heater connected.
Failure to follow these instructions can result
in death, injury or property damage.

41 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

FIGURE 23: Gas Connection with Flexible Gas Hose

CORRECT POSITIONS

CAUTION
Product Damage Hazard
Shut-Off Valve (included with gas hose) must
be parallel to burner gas inlet. The 3" (8 cm)
displacement shown is for the cold condition.
This displacement may reduce when the
system is fired.

Hold gas nipple securely with pipe wrench
when attaching gas hose.
Failure to follow these instructions can result
in product damage.
Vertical (as shown left)
45°

12"
(30 cm)

45°

3" (8 cm)
max. displacement
Rear View

Side View

Alternate
positions
okay
Flexible Gas Hose
36" (91 cm) length

90° Pipe Elbow
(Not Included)
Heater Movement

Pipe Nipple
Burner Assembly
(Shown Without Blower Assembly)

INCORRECT POSITIONS (WRONG INSTALLATION)
Heater Movement

Heater Movement

Heater Movement
Description
1/2" Flexible Stainless Steel Gas Hose (US Models)
3/4" Flexible Stainless Steel Gas Hose (US Models)
1/2" Rubber Type 1 Gas Hose (Canadian Models)
3/4" Rubber Type 1 Gas Hose (Canadian Models)

42 of 59

Heater Movement
Part Number
91412200
91412204
91412206
91412207

SECTION 10: WIRING

SECTION 10: WIRING
Heaters can be controlled using several methods.
Normally thermostats are used to control the heaters
but they can also be controlled by an energy
management system. Section 10.1 illustrates the
connection for heaters controlled by a line voltage
thermostat.
For heaters on a low voltage thermostat, See Page
44, Section 10.2. Heaters must be grounded in
accordance with applicable codes: United States:
Refer to National Electrical Code® NFPA 70 - latest
revision; Canada: Refer to Canadian Electrical Code
CSA C22.1 Part I - latest revision.

DANGER

Electrical Shock Hazard
Disconnect electric before service.
Heater must be properly grounded.

If any of the original internal wiring must be replaced,
it must be replaced with wiring materials having a
temperature rating of at least 105°C and 600 volts.

Failure to follow these instructions can result
in death or electrical shock.

10.1 Line Voltage Thermostat Wiring
Line Voltage Thermostat
120 V-60 Hz
Supply Circuit
L1

Additional
Burners

L2
N

Gnd.

H

N
Gnd.

H
Gnd.
Maximum 5 Burners
Per Thermostat

Burner 1

Burner 2

43 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

10.2 Low Voltage Thermostat Wiring
FRONT VIEW

SPST Transformer Relay

1

Black

4
COIL

BACK VIEW
R

Low Voltage Thermostat

C

3
2 6
W

5 COIL

G

Y

Black
120 V-60 Hz
Supply Circuit

White Red

L1
L2
Gnd.

Additional
Burners
N

H

N
Gnd.

H
Gnd.
Maximum 8 Burners
Per Relay

Burner 1
Description
SPST Transformer Relay
Low Voltage Thermostat

44 of 59

Part Number
90417600K
90425100

Burner 2

SECTION 10: WIRING

10.3 Internal Wiring

45 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

10.4 Ladder Diagram

10.5 Electrical Connection to the Burner

Connect wires together with
suitable approved wire connections.
L2
Gnd.

L1

Green White Black

Green to Gnd.
White to L2
Black to L1

Internal Wire Bundle
Burner Box

Electrical Cord or
Flexible Conduit
Conduit Hole
BX or Romex Connector

46 of 59

SECTION 11: OPERATION AND MAINTENANCE

SECTION 11: OPERATION AND MAINTENANCE

WARNING

DANGER

Electrical Shock Hazard
Disconnect electric
before service.

Explosion Hazard
Turn off gas supply to
heater before service.

Heater must be
connected to a properly
grounded electrical
source.

Burn Hazard
Allow heater to cool
before service.

Cut/Pinch Hazard
Wear protective gear
during installation,
operation and service.

Tubing may still be hot
Edges are sharp.
after operation.

Failure to follow these instructions can result in death, electric shock, injury or property damage.
This heater is equipped with a direct spark ignition
system.

8. When thermostat is satisfied, all power to the
unit is shut off.

11.1 Sequence of Operation
1. Turn the thermostat up. When the thermostat
calls for heat, the blower motor will energize.

11.2 To Shut Off Heater
Set thermostat to lowest setting.
Turn OFF electric power to heater.
Turn OFF manual gas valve in the heater supply line.

2. When the motor approaches nominal running
RPM, the pressure switch closes and activates
the ignition module.
3. After a 45 second prepurge, the ignition module
then opens the gas valve and energizes the
spark igniter.
4. When the flame is established, the sparking
sequence ceases.
5. If the flame is not established during the ignition
sequence, the ignition module closes the gas
valve and purge begins. Module will try 2
additional times for ignition (with purges in
between trials). If ignition is not established, the
module will lockout.
6. If the flame extinguishes during operation, the
ignition module will attempt the multiple trial
sequence described in step 5. If ignition is not
re-established, the module will lockout for one
hour or until reset.
7. After lockout, the control can be reset by turning
down thermostat for five seconds, and then
raising it again to desired temperature, or by
disconnecting power and then reconnecting.

11.3 To Start Heater
Turn gas valve and electric power OFF and wait five
minutes for unburned gases to vent from heater.
Turn ON main gas valve.
Turn ON electric power.
Set thermostat to desired temperature.
Burner should light automatically.
11.4 Pre-Season Maintenance and Annual
Inspection
To ensure your safety and years of trouble-free
operation of the heating system, service and annual
inspections must be done by a contractor qualified in
the installation and service of gas-fired heating
equipment.
Turn off gas and electric supplies before performing
service or maintenance. Allow heater to cool before
servicing.
Before every heating season, a contractor qualified in
the installation and service of gas-fired heating
equipment must perform a thorough safety
inspection of the heater.
For best performance, the gas, electrical, thermostat
connections, tubing, venting, suspensions and

47 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

overall heater condition should be throughly
inspected thoroughly.
NOTE: Gas flow and burner ignition are among the
first things that should be inspected.
Please see Page 48, Section 11.5 for suggested
items to inspect.
11.5 Maintenance Checklist
Installation Code and Annual Inspections:
All installation and service of ROBERTS GORDON®
equipment must be performed by a contractor
qualified in the installation and service of equipment
sold and supplied by Roberts-Gordon LLC and
conform to all requirements set forth in the
The Vicinity of the Heater

Vehicles and Other
Objects

ROBERTS GORDON® manuals and all applicable
governmental authorities pertaining to the
installation, service, operation and labeling of the
equipment.
To help facilitate optimum performance and safety,
Roberts-Gordon LLC recommends that a qualified
contractor conduct, at a minimum, annual
inspections of your ROBERTS GORDON® equipment
and perform service where necessary, using only
replacement parts sold and supplied by RobertsGordon LLC.

Do not store or use flammable objects, liquids or vapors near the heater.
Immediately remove these items if they are present.
See Page 5, Section 3.
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged underneath the reflector, in between the tubes or
in the decorative or protective grilles (included with select models).
Immediately remove objects in violation of the clearances to combustibles.

Reflector

See Page 5, Section 3.
Support reflector with reflector hanger and support strap.
Reflector must not touch tube.
Make sure there is no dirt, sagging, cracking or distortion.
Do not operate if there is sagging, cracking or distortion.
Make sure reflectors are correctly overlapped. See Page 23, Section 6.5.1.

Vent Pipe

Clean outside surface with a damp cloth.
Venting must be intact. Using a flashlight, look for obstructions, cracks on the
pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Remove any carbon deposits or scale using a wire brush.

Outside Air Inlet

Tubes

See Page 35, Section 8.
Inlet must be intact. Look for obstructions, cracks on the pipe, gaps in the
sealed areas or corrosion.
The area must be free of dirt and dust. Clean and reinstall as required.
Make sure there are no cracks.
Make sure tubes are connected and suspended securely.
See Page 14, Section 6.

Gas Line
Burner Observation
Window
48 of 59

Make sure there is no sagging, bending or distortion.
Clean or replace as required.
Check for gas leaks. See Page 41, Section 9.
Make sure it is clean and free of cracks or holes.
Clean and replace as required.

SECTION 11: OPERATION AND MAINTENANCE

Blower Scroll, Wheel and
Motor

Compressed air or a vacuum cleaner may be used to clean dust and dirt.

Burner Cup and Orifice

Clear of obstructions (even spider webs will cause problems).

Electrode

Carefully remove any dust and debris from the burner.
Replace if there are cracked ceramics, excessive carbon residue, or erosion
of the electrode.

Thermostat
Suspension Points

The electrode gap should be 1/8" (3.2 mm).
There should be no exposed wire or damage to the thermostat.
See Page 43, Section 10.
Make sure the heater is hanging securely. Look for signs of wear on the chain
or ceiling.

See Page 15, Figure 14.
Decorative and Protective The grille must be securely attached.
Grille (optional)
Check that the side reflector extensions are installed correctly and secured in
place if necessary. (Decorative grille only.)
See Page 32, Section 7.5 and Page 34, Section 7.6

Lower Clearance Shield
(optional)

Make sure shield is installed correctly and secured in place if necessary.
(Decorative grille only.) See Page 33, Section 7.5.2.
The lower shield must be securely attached. Inspect shield support straps
and lower clearance shield anchor points.
See Page 32, Section 7.4.
Make sure shield is installed correctly and secured in place if necessary.

Wall Tag

Safety Labels

See Page 32, Section 7.4.
If wall tag is present, make sure it is legible and accurate. Please contact
Roberts-Gordon LLC or your ROBERTS GORDON® independent distributor, if
you need a wall tag. See Page 4, Section 2.1
Product safety signs or labels should be replaced by the product user when
they are no longer legible. Please contact Roberts-Gordon LLC or your ROBERTS GORDON® independent distributor to obtain replacement signs or
labels. See Page 2, Figure 1 through Page 3, Figure 2.

49 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

SECTION 12: TROUBLESHOOTING

DANGER

Electrical Shock Hazard
Disconnect electric before service.
Heater must be properly grounded.
Failure to follow these instructions can result
in death or electrical shock.

WARNING

Fire Hazard
Keep all flammable
objects, liquids and
vapors the minimum
required clearances to
combustibles away
from heater.

Explosion Hazard
Turn off gas supply to
heater before service.

Burn Hazard
Allow heater to cool
before service.

Cut/Pinch Hazard
Wear protective gear
during installation,
operation and service.

Tubing may still be hot
Edges are sharp.
after operation.

Some objects will catch
fire or explode when
placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.

50 of 59

Is there spark at the igniter?

YES

Turn up thermostat.
Does the blower turn on?

NO

NO

Check wiring between the
power cord, blower motor
and transformer.
NO

YES

YES

NO

Reconnect transformer
wires. Place a jumper wire
across the pressure switch.
Is there a spark?
Replace transformer.

Replace ignition module.

NO

YES

Remove the blue and yellow
wires from the transformer.
Is there 24 V at the
transformer secondary?

YES

Are the air hoses to the
pressure switch secure and
leak free?

NO

YES

NO

Is the vent pipe or the inlet of
YES
the burner obstructed?

Replace blower.

YES

Unplug burner. Does the
blower turn freely?

YES

With the blue and yellow
wires still removed, is the
NO
voltage at the transformer
black and white leads 120 V?

Carefully reset spark gap
to 1/8"

Replace igniter and
ignition wire as needed.

Is the igniter gap
set at 1/8"?
NO

NO

YES

Unplug burner and check
igniter and ignition wire. Are
they damaged?

Check relay wiring
(if applicable) and wiring
to the burner.

Check thermostat wiring
and replace thermostat if
necessary.

Is there power 120 V at
the burner?
NO

NO

YES

Place a jumper across the
thermostat terminals.
Does the blower turn on?

Replace pressure switch

Repair, replace, or tighten
hoses as necessary.

Remove obstruction.

Blower bearings may have
failed. Replace blower.

NO

Is the blower obstructed?

YES

Remove obstruction.

SECTION 12: TROUBLESHOOTING

12.1 Troubleshooting Flow Chart

51 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

52 of 59

SECTION 12: TROUBLESHOOTING

12.2 Manifold Gas Pressure Setting

53 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

SECTION 13: REPLACEMENT PARTS

WARNING

DANGER

Electrical Shock Hazard

Explosion Hazard

Fire Hazard

Carbon Monoxide Hazard

Use only genuine ROBERTS GORDON® replacement parts per this installation, operation and
service manual.
Failure to follow these instructions can result in death, electric shock, injury or property damage.

54 of 59

SECTION 13: REPLACEMENT PARTS

55 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

Description
Mica Window Assembly
Electrode Gasket
Tube Gasket
Burner Cup Assembly
Gas Valve (Natural)
Gas Valve (LP)
Electrode
DSI Ignition Module
Transformer
Pressure Switch
(200)
(115, 140, 175)
(150)
(60, 80, 100, 125)
(40)
Motor/Blower Assembly
Blower Outlet Gasket

56 of 59

Part Number
02553203
02558501
02568200
03020100
90032500
90032502
90427400
90439500K
90436900K
90439801K
90439802K
90439803K
90439805K
90439808K
90709700-P
90709801

SECTION 14: GENERAL SPECIFICATIONS

SECTION 14: GENERAL SPECIFICATIONS
14.1 Material Specifications
14.3 Suspension Specifications
14.1.1 Reflectors
Hang heater with materials with a minimum working
load of 75 lbs (33 kg). See Page 15, Figure 14.
.024 Aluminum
(Optional .024 Stainless Steel Type 304)
14.4 Controls Specifications
14.2 Heater Specifications
Time switches, thermostats, etc. can be wired into
the electrical supply. External controls supplied as an
14.2.1 Ignition
optional extra.
Fully automatic, three-try, direct spark, electronic
ignition control, 100% safety shut-off.
General Specifications for BH-Series heaters are as follows:
End View

Side View

Reflector

12.5"
(32 cm)

Turbulator (select models)

12.5"
(32 cm)

Burner Tube

11"
(28 cm)

Minimum Length A

Recommended
Minimum Mounting Height*

Heat Input Rate

Length “A”

Model

(Btu/h) x (1000)

Minimum

Space

Spot

BH-40

40

10' (3 m)

8-10' (2.4 - 3 m)

8'(2.4 m)

BH-60

60

20' (6 m)

10-12' (3 - 3.6 m)

9' (2.7 m)

BH-80

80

20' (6 m)

12-15' (3.6 - 4.5 m)

11' (3.3 m)

BH-100

100

30' (9 m)

12-15' (3.6 - 4.5 m)

12' (3.7 m)

BH-115

115

30' (9 m)

15-20' (4.5 - 6 m)

15' (4.6 m)

BH-125

125

40' (12 m)

15-20' (4.5 - 6 m)

15' (4.6 m)

BH-140

140

40' (12 m)

20-25' (6 - 7.6 m)

20' (6.1 m)

BH-150

150

50' (15 m)

20-25' (6 - 7.6 m)

20' (6.1 m)

BH-175

175

50' (15 m)

25' (7.6 m)

23' (7 m)

BH-200

200

60' (18 m)

25' (7.6 m)

25' (7.6 m)

*See Page 5, Section 3 for clearances to combustibles.
GAS PRESSURE AT MANIFOLD:
Natural Gas:
3.5" wc
LP Gas:
10.5" wc
PIPE CONNECTION:
1/2" NPT (for BH-40, 60, 80, 100, 115 & 125)
3/4" NPT (for BH- 140, 150,175 & 200)
DIMENSIONS:
Vent Connection Size:
4" (10 cm)
Outside Air Connection Size: 4" (10 cm)
Refer to figure above for dimensional information.

GAS INLET PRESSURE:
Natural Gas:
for BH-40, 60, 80, 100,
115, 125, 140, 150
for BH-175, 200

4.6" wc Minimum
5.0" wc Minimum
14.0" wc Maximum
LP Gas:
11.0" wc Minimum
14.0" wc Maximum
ELECTRICAL RATING (ALL MODELS):
120 V - 60 Hz, 1 A
57 of 59

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

58 of 59

SECTION 15: THE ROBERTS GORDON® BLACKHEATTM BH WARRANTY

SECTION 15: THE ROBERTS GORDON®
BLACKHEATTM BH WARRANTY
ROBERTS-GORDON LLC WILL PAY FOR:
Within 36 months from date of purchase by buyer or 42
months from date of shipment by Roberts-Gordon LLC
(whichever occurs first), replacement parts will be provided
free of charge for any part of the product which fails due to
a manufacturing or material defect.
Roberts-Gordon LLC will require the part in question to be
returned to the factory. Roberts-Gordon LLC will, at its sole
discretion, repair or replace after determining the nature of
the defect and disposition of part in question.
ROBERTS GORDON® Replacement Parts are warranted
for a period of 12 months from date of shipment from
Roberts-Gordon LLC or the remaining ROBERTS
GORDON® BLACKHEATTM BH warranty.

ROBERTS-GORDON LLC WILL NOT PAY FOR:
Service trips, service calls and labor charges.
Shipment of replacement parts.
Claims where the total price of the goods have not
been paid.
Damage due to:
• Improper installation, operation or maintenance.
• Misuse, abuse, neglect, or modification of the
ROBERTS GORDON® BLACKHEATTM BH in any way.
• Use of the ROBERTS GORDON® BLACKHEATTM BH
for other than its intended purpose.
• Incorrect gas or electrical supply, accident, fire, floods,
acts of God, war, terrorism, or other casualty.
• Improper service, use of replacement parts or
accessories not specified by Roberts-Gordon.
• Failure to install or maintain the
ROBERTS GORDON® BLACKHEATTM BH as directed
in the Installation, Operation and Service Manual.
• Relocation of the ROBERTS GORDON®
BLACKHEATTM BH after initial installation
• Use of the ROBERTS GORDON® BLACKHEATTM BH in
a corrosive atmosphere containing contaminants.
• Use of the ROBERTS GORDON® BLACKHEATTM BH in
the vicinity of a combustible or explosive material.
• Any defect in the ROBERTS GORDON®
BLACKHEATTM BH arising from a drawing, design, or
specification supplied by or on behalf of the
consumer.
• Damage incurred during shipment. Claim must be filed
with carrier.

WARRANTY IS VOID IF:
The ROBERTS GORDON® BLACKHEATTM BH is not
installed by an contractor qualified in the installation and
service of gas fired heating equipment.
You cannot prove original purchase date and required
annual maintenance history.
The data plate and/or serial number are removed,
defaced, modified or altered in any way.
The ownership of the ROBERTS GORDON®
BLACKHEATTM BH is moved or transferred. This warranty
is non-transferable.

Roberts-Gordon LLC is not permitted to inspect the
damaged equipment and/or component parts.

READ YOUR INSTALLATION, OPERATION AND
SERVICE MANUAL.
If you have questions about your equipment, contact your
installing professional. Should you need Replacement
Parts or have additional questions, call or write:
Roberts-Gordon LLC
1250 William Street
P.O. Box 44
Buffalo, New York 14240-0044
Telephone: +1.716.852.4400
Fax: +1.716.852.0854
Toll Free: 800.828.7450
www.rg-inc.com
www.radiantheaters.com
Roberts-Gordon LLC's liability, and your exclusive
remedy, under this warranty or any implied warranty
(including the implied warranties of merchantability
and fitness for a particular purpose) is limited to
providing replacement parts during the term of this
warranty. Some jurisdictions do not allow limitations on
how long an implied warranty lasts, so this limitation may
not apply to you. There are no rights, warranties or
conditions, expressed or implied, statutory or otherwise,
other than those contained in this warranty.
Roberts-Gordon LLC shall in no event be responsible
for incidental or consequential damages or incur
liability for damages in excess of the amount paid by
you for the ROBERTS GORDON® BLACKHEATTM BH.
Some jurisdictions do not allow the exclusion or limitation
of incidental or consequential damages, so this limitation
or exclusion may not apply to you. This warranty gives you
specific legal rights, and you may also have other rights
which vary from jurisdiction to jurisdiction.
Roberts-Gordon LLC shall not be responsible for failure to
perform under the terms of this warranty if caused by
circumstances out of its control, including but not limited to
war, fire, flood, strike, government or court orders, acts of
God, terrorism, unavailability of supplies, parts or power.
No person is authorized to assume for Roberts-Gordon
LLC any other warranty, obligation or liability.

LIMITATIONS ON AUTHORITY OF
REPRESENTATIVES:
No representative of Roberts-Gordon LLC, other than an
Executive Officer, has authority to change or extend these
provisions. Changes or extensions shall be binding only if
confirmed in writing by Roberts-Gordon LLC's duly
authorized Executive Officer.

59 of 59



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : No
Page Mode                       : UseNone
XMP Toolkit                     : Adobe XMP Core 4.0-c321 44.398116, Tue Aug 04 2009 14:24:39
Creator Tool                    : FrameMaker 9.0
Modify Date                     : 2012:02:23 15:49:14-05:00
Create Date                     : 2012:02:23 15:44:15Z
Metadata Date                   : 2012:02:23 15:49:14-05:00
Format                          : application/pdf
Title                           : 170102NA Blackheat  BH Installation.book
Creator                         : john.marki
Producer                        : Acrobat Distiller 8.3.1 (Windows)
Document ID                     : uuid:19ce6a84-58bf-4c45-8d86-b57f7a486a98
Instance ID                     : uuid:0d0f47c0-8682-4e55-bfd7-9865f8329e99
Has XFA                         : No
Page Count                      : 70
Author                          : john.marki
EXIF Metadata provided by EXIF.tools

Navigation menu