SDC INST 101 DE_KDE DE KDE Installation Instructions

User Manual: SDC 101-DE KDE Installation Instructions Installation Instructions

Open the PDF directly: View PDF PDF.
Page Count: 12

DownloadSDC INST-101-DE_KDE 101-DE KDE Installation Instructions INST-101-DE
Open PDF In BrowserView PDF
801 Avenida Acaso, Camarillo, Ca. 93012 • (805) 494-0622 •
www.sdcsecurity.com • E-mail: service@sdcsecurity.com

INSTALLATION INSTRUCTIONS
101-DE/101-KDE

Verbal Exit Instructions or
Alarm Tone Only and
Digital Countdown Display
Application:
®

When unauthorized egress is initiated SDC Exit Check delays egress
through the door for 15 seconds (or 30 seconds). Meanwhile, the person
exiting must wait while personnel or security responds. The door unlocks
after 15 seconds have elapsed permitting egress. When powered by a fire
control supervised power supply, the lock will release immediately in an
emergency. The integral digital keypad eliminates the need to carry and
locate keys for reset and bypass functions.

Exit Check® applications include:
Restricting the egress of wandering patients for their own safety.
HUGS® Infant Protection System compatibility
Restricting the egress of commercial center patrons for security application needs.
Controlling pedestrian traffic in transportation facilities, including airport jetways and tarmacs
Reducing Shoplifting and Employee Theft

Features:
Egress Delay

Control Inputs

15 or 30 second exit delay
1 or 2 second nuisance delay

1 to 30 second request-to-exit and bypass
input with anti-tailgate and jumper
selectable door prop alarm.
Reset

Built-In 3 Function keypad
Alarm and lock reset
1 to 30 second bypass
Sustained bypass
Additional keyswitch optional

Built-In Annunciation

15

Door armed and locked.

00

Alarm countdown has ended,
door is unlocked and alarm sounding
until reset.

--

Door unlocked and alarm is shunted
(REX or Bypass)

-- ---

Door has been opened after REX,
Bypass or Alarm.

Monitoring Outputs
Armed mode
Egress initiation status
Released status

Optional EMLock Outputs

Armed mode
Door position sensor – indicates door
Nuisance mode
open and door closed, commonly used to
Irreversible egress mode
verify egress after release.
Release mode
Magnetic bond sensor – indicates locked
Digital countdown mode
with full holding force, low holding force,
Field selectable voice notification or tone
unlocked and tampering.
Field selectable male voice with security
message or female voice with safety
Choice of Mounting
message
Recessed mounted
(3 gang metal plaster ring included)
Triggering Options
Surface mounted with optional 3 gang
Egress alarm triggered by door
box (DEC-J)
movement when used with SDC
Optional shroud (SHD-J) to be used with
1500DE series EMLocks.
DEC-J surface box.
Trigger input from external device
field selectable (N/O or N/C)
P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd

Display Modes

Rev E

07-15

Page 1

Code Compliance
IFC International fire Code
IBC International Building Code
NFPA 101 Life Safety Code
NFPA 1 Uniform Fire Code
California Building Code
Field selectable automatic or manual
power up after emergency release or
power loss. Use of manual power up
complies with California Building Code
(OSHPD) requirements.
Any suggestions or comments to this instruction or
product are welcome. Please contact us through
our website or email engineer@sdcsecurity.com

101-DE/101-KDE Operational Description
The door is closed and secured by latching hardware. The model 101-DE/101-KDE Exit Check controller sends power
to the magnetic lock or Delayed Egress Panic Device to lock the door in the secured position. The integral digital
display shows the unlock delay time.
Activation / Alarmed Release :
Activation of the Exit Check’s trigger input initiates the 15 or 30 second unlock cycle . A pre-activation warning tone is
sounded during the short nuisance delay period and the integral display starts counting down. To prevent false alarms,
removing the trigger input activation during the nuisance delay period will silence the pre-activation warning tone, reset
the countdown display and keep the door locked.
Once the nuisance delay period has been exceeded, the Exit Check continues to count down during an irreversible
door release cycle. The integral digital countdown display and voice commands continue to inform the person intending
to exit of the seconds remaining until unlock. An alarm output is activated to alert personnel of an unauthorized exit.
After the 15 or 30 second delay cycle has expired, the Exit Check will remove power to the locking device, releasing the
door and allowing free egress.
Reset / Relock:
The Exit Check can be manually reset by authorized personnel by closing the door and entering a code on the integral
digital keypad, momentarily turning the optional reset key switch to the reset position or by momentarily activating a N/O
switch connected to the remote reset terminals.
Request to Exit / Authorized Bypass:
A Request to Exit cycle is initiated by entering an authorized REX code on the integral digital keypad, momentarily
turning the optional key switch to the bypass position or momentarily activating a N/O switch connected to the REX
terminals. The power will be removed from the locking device allowing free egress. After the request to exit cycle has
expired, the Exit Check will automatically reapply power to the locking device to re-secure the door.
Unlocking the door for extended periods of time (Authorized Bypass mode) is accomplished by entering an Authorized
Bypass code on the integral keypad, momentarily turning the optional key switch to the Bypass position or placing a
maintained closure across REX terminals. Releasing the closure across the REX terminals will restart the Request to
Exit cycle. Entering the Reset code on the integral digital keypad, or momentarily turning optional key switch to the
Reset position will immediately reapply power to the locking device to re-secure the door.

(NFPA-101)
The 101-DE/101KDE operation
complies with the following building
and fire codes: NFPA 101; NFPA 1UFC; UBC; IBC; IFC; SBC;
California Building Code. Listings:
UL Listed: Special Locking
Arrangements and Auxiliary Locks;
California State Fire Marshal
(CSFM) Listed.

Option
Code

Delay Release
Time

Nusiance
Time

Reset after
Alarm

Lock Status on
Power-Up

NA

15 sec or 30 sec
Selectable

1 sec or 2 sec
Selectable

Manual

Locked or Unlocked
Selectable

ND

15 sec
Fixed

0 sec or 1 sec
Selectable

Manual

Locked or Unlocked
Selectable

NH

30 sec
Fixed

0 sec or 1 sec
Selectable

Manual

Locked or Unlocked
Selectable

NC

15 sec
Fixed

0 sec or 1 sec
Selectable

Manual

Unlocked
Fixed

(CBC Compliant)

Per BOCA compliance, the Exit Check is manually reset by authorized personnel after an alarm by closing the door and
actuating the integral reset key switch or by momentarily closing a contact connected to the remote reset terminals. In
addition, reset will be automatically initiated once the door has been opened, then closed and remains closed for 30
consecutive seconds.
Option Delay Release
Nusiance
Reset after
Lock Status on
(BOCA/Chicago)
Code
Time
Alarm
Time
Power-Up
The 101-DE/101-KDE operation
Locked
or Unlocked
15 sec
0 sec or 1 sec
Auto/Manual
BD
complies with BOCA National
Selectable
Fixed
Selectable
Building Code and the Chicago
Locked or Unlocked
30 sec
0 sec or 1 sec
Auto/MAnual
Building Code: UL Listed, Special
BH
Selectable
Fixed
Selectable
Locking Arrangements and Auxiliary
Locked or Unlocked
Locks.
15 sec
0 sec
Auto/Manual
BC
Fixed

P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd

Rev E

07-15

Page 2

Fixed

Selectable

Typical System Wiring –
Single Door w/ Latching Hardware
WARNING:
APPLICATION OF VOLTAGE TO THE DRY CONTACT INPUTS OF THIS UNIT
WILL CAUSE PERMANENT DAMAGE AND VOID THE WARRANTY
3 conductors
2 conductors
To Smoke Detection
System – Dry, Closed
Contact

AC Mains

Power
Supply

To Fire Panel – Dry, Closed Contact
2 conductors
6 conductors

4 conductors
PUSH UNTIL ALARM
SOUNDS. DOOR CAN BE
OPENED IN 15 SECONDS.

101-DE
101-KDE

Models: 1511DE, 1571DE & 1581DE
1–1/4"

Note: Armature assembly with tray
required for proper operation of the
trigger switch.

Door

DOOR
ARMATURE
5/16 – 18
ARMATURE
MOUNTING
SCREW

SEX NUT

Armature tray
assembly

Mount magnet and armature
tray assembly per template

P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd

Rev E

1/2”
ARMATURE HOLDER

EMLock

07-15

Page 3

KEY CYLINDER INSTALLATION
(KDE Model Only)

WITH KEY CYLINDER IN PROPER
POSITION INSIDE SWITCH BLOCK,
TIGHTEN THE SET SCREW TO
LOCK CYLINDER IN PLACE.

1-1/4” KEY CYLINDER
REQUIRES COLLAR

1-1/8” KEY CYLINDER
7185SC1-26D-KD

RECESSED MOUNTING
DRY WALL
1) Cut hole in dry wall to
dimensions shown.
5-3/4”

2) Mount wall bracket
over hole.
3) Carefully insert unit and
secure with screws
supplied.

3-3/4"

PU
S
DO H UN
OR TIL
CA ALA
NB R
SE EOP M SO
CO
U
ND ENED NDS
S.
IN1 .
5

SURFACE MOUNT 3 GANG BOX OVER
EXISTING RECESSED 2 GANG BOX
1) Attach optional 3 Gang Surface
Mount Box to existing recessed 2 gang
box using screws supplied.
2) Carefully insert unit and
secure with screws
supplied.

P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd

Rev E

07-15

Page 4

PU
S
DO HUN
OR TIL
CA ALA
NB R
SE EOP M SO
CO
U
ND ENED NDS
S.
IN1 .
5

1) Attach optional 3 Gang Surface
Mount Box to wall using
screws supplied.

SURFACE MOUNT
3 GANG BOX
TO WALL

1a) Knockouts are located on
two surfaces of the box to
allow wire conduit insertion.
P
SO USH
U
OP UNDS NTIL
EN . D ALA
ED OO
IN1 RC RM
5S AN
EC
ON BE
DS
.

2) Carefully insert unit and
secure with screws
supplied.

OUTSIDE WALL or
POST MOUNTING
with WEATHER SHROUD
1) Use optional 3 Gang Box inside
optional Shroud as a template to
drill pilot holes through
shroud and into post (or wall).
2) Mount 3 Gang Box and Shroud
to Post with screws supplied.
3) Carefully insert unit and
secure with screws
supplied.
To
Power
Supply

P
SO USH
OP UNDS UNTIL
EN . D ALA
ED OO
IN1 RC RM
5S AN
EC
ON BE
DS
.

P
SO USH
OP UNDS UNTIL
EN . D ALA
ED OO
IN1 RC RM
5SE AN
CO BE
ND
S.

P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd

Rev E

07-15

Page 5

CAUTION:
101-DE CONTROLLERS ARE
DESIGNED FOR INDOOR USE.
UNIT IS NOT WATER PROOF

RECOMMENDED MOUNTING
PROCEDURE

USE 1-1/4” SCREWS SUPPLIED WITH
WALL MOUNT FRAME TO HANG UNIT
TEMPORARILY FOR WIRING PURPOSES

A

A

SLIDE PACKING FOAM BETWEEN WALL
AND UNIT TO PREVENT DAMAGE TO FACEPLATE

NO
PWR

WIRE UNIT AS SHOWN
(SHOWN WITH NO OPTIONS).

LOCK

C

NC NO

RED RLY

C

C NO

NC

GRN RLY

TRIG

C

NO

REX

C NO

C NO

RESET

IBO

J6
KEYPAD
RESET

J1

P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd

Rev E

07-15

Page 6

SP1

J4

VIEW A-A

MODEL 101-DE

MODEL 101-KDE

Trigger
Switch

101-DE / 101-KDE
SDC MODELS

TRIG REX RESET IBO

- + NO C NCNO C NC C NO C NO C NO C NO

1511DE
1571DE
1581DE

1575DE
1576DE

-

- +

GRN RLY

+ 3 4 5 6 7 8

PWR LOCK RED RLY

Note for 1581DE only:
Peel double sided tape on
trigger switch clip and stick
flush against end-block and
sidewall as shown.

To
Power
Supply

8
5 6
4
3
+

+

l

-

To
Power
Supply

Trigger
Switch

Trigger
Switch

JUMPER J1*

[OFF]

[ON]

ON

1
2

PAIR OF
DOORS
DIP SWITCH
SETTINGS
DELAY
TIME
NUISANCE
DELAY

*JUMPER J1 (DOOR PROP)

15

30

1

2

*
*

INSTALLED: The 101DE/KDE will enter the alarm mode if the
door is held open past the request to exit period.
REMOVED: The 101DE/KDE will remain unlocked if the door is
held open past the request to exit period. No alarm will sound.
The 101DE/KDE will relock and rearm upon closure of the door.

3
4

REX/BYPASS
PERIOD

5

TRIGGER
TYPE

6

PWR UP
STATE

7

ALARM
TYPE

8

*

-

C NO C NO C NO C NO

3

- + - + NO C

4

5 6

7

TRIG REX RESET IBO

PWR LOCK RED R

7

8

101-DE
101-KDE

MESSAGE

15

N/O

20

30

1

N/C

UNLOCKED

LOCKED

CONTROLLER SPECIFICATIONS

*

INPUT VOLTAGE

TONE
ONLY

VOICE/TONE

FEMALE
MSG

MALE
MSG

MAX CURRENT DRAW
(CONTROLLER ONLY)

12 VDC OR 24 VDC
180mA @ 12/24 VDC

WARNING!

MAX CURRENT
(LOCK OUTPUT)

1 Amp @ 12/24 VDC

CONTACT THE AUTHORITY HAVING JURISDICTION FOR APPROVAL
PRIOR TO SELECTING DELAY TIME OR PWR-UP SETTINGS

MONITOR RELAYS
CONTACT RATING

1 Amp @ 12/24 VDC
(RESISTIVE)

Functionality of the switches vary with the program option code. See Page 2
for a detailed description.

TEMPERATURE

P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd

Rev E

07-15

Page 7

o

o

0 C – 70 C

System Operation
POWER-UP UNLOCKED

POWER-UP LOCKED

The door is unlocked. To enter the
Armed Mode, turn the keyswitch to
Reset or enter the Reset Code
“11 ” on the keypad

--

15

The door is
locked and
secure

or 30

*

DELAYED EGRESS MODE
15

14

...

01

The door is still locked and secure. The display is counting
down with audible alarm/voice instructions. Once the display
reaches “00”, the door will unlock.

ALARMED UNLOCKED [Alternating Display]
00

The door is unlocked and the alarm
is sounding. To return to Armed
Mode, close the door and turn the keyswitch
to Reset or enter the Reset Code “11 “
on the keypad

The door is unlocked and
has been opened

00
-- ---

*

RESET [Armed]
15

or 30

*

Keypad Code 11

The door is locked and secure

AUTHORIZED EGRESS [REX]
--

Door Closed

-- ---

Door has
been opened

Door Closed

-- ---

Door has
been opened

*

(Green LED Solid)

*

(Green LED Flashing)

Keypad Code 22

The door is unlocked until the REX timer has expired or
until the door has been opened and then closed.

BYPASS [Maintained Unlock]
--

(Green LED solid)

Keypad Code 33

The door is unlocked indefinitely. To return to Armed Mode, enter the
Reset Code “11 “on the keypad.

*

KDE Model Only:
KEY SWITCH BYPASS [Maintained Unlock]
--

Door Closed

-- ---

Door has
been opened

(Green LED Solid)

The door is unlocked indefinitely. To return to Armed Mode, close the door and
turn the keyswitch to RESET or enter the Reset Code “11 “ on the keypad.

*

Keypad Programming
KEYPAD STATUS LEDS

FACTORY PROGRAMMED CODES
User Pin
No. Code
01 1234

GREEN Steady : Power on, No errors,
No outputs are active
Fast : No errors,
Flash At least one output is active

02

RED Steady : General error, invalid code
entered

03
04

YELLOW

Flash : For ADA requirements, it will light
each time a key is pressed
Slow : Keypad is in Programming Mode
Flash

P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd

Rev E

07-15

*
11
*
22
*
33
*

Output
Code
NA

Function
Master Code (default)

2

Reset

3

Authorized Exit (Rex)

4

Bypass

If the factory programmed codes are acceptable for your
installation, no additional programming is required.
Page 8

Changing the Master Code
User 1 is always used as the Master Code and is required to access keypad programming. The Factory
Default Master Code is “1234 ”. It is strongly recommended that a new Master Code is assigned after
installation. WRITE DOWN THE NEW CODE. If the master code is lost, you must use the keypad reset jumper
on the main circuit board to enter programming mode by using the Default Master Code.
To Change the Master Code (User 1)
1) Enter Programming Mode: Press 99# Master Code .
2) Assign new Master Code : Press 1# 01# New Pin Code# Output Relay #

*

For example: 99# 1234 1# 01# 3871# 0#
3) Press
to exit programming mode.

*

**

*

*.

changes the Master code from 1234 to 3871.

Entering Programming Mode
Press 99# Master Code
For example: 99# 1234

*

*.

Enters programming mode using the Default Master Code.
Output Relay Codes

Adding a User / Changing User Pin Codes (Option 1)
To add a user:
Press 1# User Number (2 digits)# New Pin Code# Output Relay #
For example: 1# 05# 55# 3#

*

2= Reset
3= Authorized Exit
4= Bypass

*.

adds user 5's pin code as one that will activate authorized exit.

Deleting a User (Option 2)
To delete a user:
Press 2# User Number (2 digits)#
For example: 2# 05#

*

*.

deletes user 5.

Erase All Users (Option 8)
To ERASE ALL USERS!!
Press 8# .
All users are erased and the Default Master Code is reset to 1234.

*

Exit Programming Mode
Press

** .

Returning the Keypad to Factory Default Settings
Short the Keypad Reset [J4] jumper terminal located on the main controller board.
Press 99# 1234 8# .

* *

J1

Press 3#1#2# . Sets the Output #1 (Reset) for 2 seconds.
Press 3#2#2# . Sets the Output #2 (Auth Exit) for 2 seconds.
Press 3#3#0# . Sets the Output #3 (Bypass) for latching.

*
*
*

Press 1#02#11#2# . Adds user # 2 with a code of 11. [Reset]
Press 1#03#22#3# . Adds user # 3 with a code of 22. [Auth Exit]
Press 1#04#33#4# . Adds user # 4 with a code of 33. [Bypass]

*
*
*

Press

** to exit programming mode.

Remove the shorting jumper from the KP RST terminal.
P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd

Rev E

07-15

Page 9

KEYPAD
RESET

J4

J6
TRIG

C

NO

REX

C NO

RESET

C

NO

IBO

C NO

Door Without Latch Assembly
Activation By Sure Exit Push Bar
R

MODELS

TO FIRE COMMAND
CENTER

Power Supply

101-DE

115 VAC

101-KDE
1575DEU
1576DEU

1581DEV
1571DEV
1511DEV

PUSH UNTILALARM
SOUNDS.
DOOR
CAN BE
PUSH UNTIL
ALARM
OPENED IN
15 SECONDS.
SOUNDS.
DOOR
CAN BE
OPENED IN 15 SECONDS.

DELAYED EGRESS CONTROLLER
101-DE Wall mount controller with keypad control and reset, 180mA @ 12/24 VDC.
101-KDE Wall mount controller with both keypad and key switch control and reset (less cylinder).

Power Transfer
Hinge or Loop

MSB550/PSB560
REX Bar

MAGNETIC LOCK WITH INTEGRATED ACTIVATION SENSOR
Specify 2 for pair of doors.
1511DEV Single, 1650 lbs. holding force, 670/350 mA @ 12/24 VDC, 628 std
1571DEV Single, 1200 lbs. holding force Energey Saver, 250/125 mA @ 12/24 VDC, 628 std
1581DEV Single, 650 lbs. holding force, 440/220 mA @ 12/24 VDC, 628 std
Outdoor Locks.
1575DEU Single outdoor magnetic lock with bond sensor, 630
1576DEU Single face drilled outdoor magnetic lock with bond sensor, 630

Door With Latch Assembly
Activation By Door Movement
Power
Supply

TO FIRE COMMAND
CENTER
115 VAC

Lock Finish
Not available with outdoor lock
V 628 Clear Anodized Aluminum (Std)
Y Black Anodized

X Dark Bronze Power Coat (313/613 equal)
PUSH UNTIL ALARM
SOUNDS. DOOR CAN BE
OPENED IN 15SECONDS.

Optional Outputs
Magnetic Bond sensor, indicates locked with full holding force, low holding force,
unlocked, tampering and obstructions (1581DEV SPST only).
D Door position sensor, indicates door open and door closed. Commonly used to
verify egress after alarm and exit delay activation. Not available with 1581DE,
1576DE or 1575DE.
VI Spanish, or English and Spanish, or English and French verbal announcement.
VIC Custom verbal announcement (minimum 10 piece purchase).
B

Standard Exit
Device
No switch
No Power Transfer

ACCESSORIES
SPECIFICATIONS

MSB550
PSB560
101-SP
101-4AM
TCC
101-1AK

DEC-J
SHD-J

Mechanical REX Exit bar for activation of locks on doors without latch assemblies.
Sure Exit® REX sensor bar for activation of locks on doors without latch assemblies
External 15W speaker connects directly to 101-DE for enhanced decibels on site or
remote voice message annunciation.
Four door station with LED’s and alarm tone for remote annunciation (indoor use).
Desk top console for remote control and annunciation of 4 – 12 doors.
Outdoor reset/bypass key switch with LED and Audible annunciator. 2-gang outdoor
box required. (Interior 101-DE and 1575DE or 1576DE outdoor magnetic lock required).
(Cylinder not included).
3-gang Interior surface mount box for 101-DE
1, 2 or 3 gang box mounted.
Shroud for surface mount box DEC-J outdoor use
DEC-J required.
DEC-J
101-DE, DEC-J, SHD-J
Only 101DE/KDE have been UL Listed as
Special Locking Arrangements to UL
standard 294 and NFPA 101.

P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd

Rev E

07-15

Page 10

Inputs:
Voltage input:
Reset input:
Rex input:
Trigger:
IBO input:

Auto sensing 12/24 VDC
N/O, Dry
N/O, Dry
N/C or N/O, Dry
N/O, Dry

Monitoring Outputs:
Alarm Output:
1 Amp @ 30VDC SPDT, dry
Locked Output:
1 Amp @ 30VDC SPDT, dry
Mechanical Specifications:
Controller:
6.5" x 4.5" x 1.5"
(165 x 114 x 38mm)
1581DE:
8.75" x 2.125" x 1.25"
(222 x 54 x 32mm)
1571DE/1511DE: 11" x 2.75" x 1.562"
(279 x 69.9 x 39.7mm)
1575DE/1576DE: 8.7" x 2.5" x 1.6"
(221 x 63.5 x 41mm)

Connecting to a Infant/Patient Monitoring System
1. Locate jumper [J6] (above the IBO input). Verify that it is NOT installed across both pins.
2. Close AND hold the REX input. The 101-DE will be in Bypass Mode and will be unlocked.
3. Whenever the IBO input is closed AND held, the 101-DE will immediately relock and rearm.
Egress is possible by activating the Exit Check’s trigger input and initiating the irreversible 15 or 30 second
unlock cycle.
4. Releasing the IBO input will return the 101-DE to the Bypass Mode.
5. Releasing the REX input will rearm the system.
6. Upon power-up, you must manually reset the lock to activate the IBO input.
Door With Latch Assembly –
Activation By Door Movement
TO PATIENT MONITORING
SYSTEM

Power
Supply

TO FIRE COMMAND
CENTER
115 VAC

J1
PUSHUNTILALARM
SOUNDS. DOOR CAN BE
OPENED IN 15SECONDS.
KEYPAD
RESET

Standard Exit
Device
No switch
No Power Transfer

J6
TRIG

C

Close to
Override
Bypass

101-DE / 101-KDE
PWR LOCK RED RLY
- +

GRN RLY

J4

NO

REX

C NO

RESET

C

NO

IBO

Jumper must be removed.

C NO

Close &
Hold to
Unlock

PATIENT
MONITORING
SYSTEM

TRIG REX RESET IBO

- + NO C NCNO C NC C NO C NO C NO C NO

- + 3 4 5 6 7 8

To
Regulated
Power
Supply

1511DE
1571DE
1581DE

Trigger
Switch

Connection to a Infant/Patient Monitoring
System has not been investigated by UL.

P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd

Rev E

07-15

Page 11

1575DE
1576DE

Connecting Optional Accessories
Door Without Latch Assembly
Activation By Sure Exit Push Bar
R

Power
Supply

TO FIRE COMMAND
CENTER
115 VAC

PUSHUNTILALARM
SOUNDS.
DOOR
CANBE
PUSHUNTIL
ALARM
OPENED IN
15SECONDS.
SOUNDS.
DOOR
CAN BE
OPENED IN 15 SECONDS.

MSB550/PSB560
REX Bar

Power Transfer
Hinge or Loop

Remote Speaker
w/ plug-in
connector

101-SP

EXTERNAL
DPS**

J1

SP1

KEYPAD
RESET

Contact required for
** Door
Anti-Tailgate and Door Prop

J4

operation, when a remote
trigger device is used.
J6
PWR

LOCK

RED RLY

NO

TRIG

GRN RLY

C NC NO

C

NC

C NO

REX

C

NO

RESET

IBO

C NO

C NO

Jumper [J6] must be installed
across both pins.
Door Contact is shown with
the door closed.
REMOTE
RESET

To
Regulated
Power
Supply
Lock
Power

REMOTE
BYPASS

REMOTE
TRIGGER

MSB550,
PSB560

REMOTE
ANNUCIATION
GRN LED (+)
RED LED (+)

101-1A or
101-1AK

LED COM (-)

P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd

Rev E

07-15

Page 12

101-1AK



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
Create Date                     : 2015:07:22 08:15:53-07:00
Modify Date                     : 2015:07:22 08:15:53-07:00
Author                          : sdc-36
Subject                         : 
Page Count                      : 12
Page Layout                     : SinglePage
Page Mode                       : UseNone
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:0ae09065-32e0-11e5-0000-2ffa7464e975
Producer                        : PDFCreator 2.1.2.0
Keywords                        : 
Creator Tool                    : PDFCreator 2.1.2.0
Document ID                     : uuid:0ae09065-32e0-11e5-0000-2ffa7464e975
Format                          : application/pdf
Title                           : INST-101-DE_KDE
Creator                         : sdc-36
Description                     : 
EXIF Metadata provided by EXIF.tools

Navigation menu