801 Avenida Acaso, Camarillo, Ca. 93012 • (805) 494-0622 •
www.sdcsecurity.com • E-mail: service@sdcsecurity.com

INSTALLATION INSTRUCTIONS
350 NARROW LINE EMLOCK
Retrofits Discontinued Locknetics 350+
Provides Superior Architectural Appearance

12-1/2”

2-1/4”
10”
1-1/2”

3/4”
2"

Interlocking
Mounting Plate
Quick Mount
Interlocking
Mounting Assembly

Frame

Mounting Screws
Armature

Outswing

Electrical Instructions:

Electrical Specifications:

Use properly fused U. L. Listed Power Supply

Dual Voltage

Do not install a diode in parallel with any magnetic lock. A diode
will cause a delay when releasing the door and residual magnetism
to occur.

Power Consumption

12 or 24VDC
560mA@12VDC
309mA@24VDC

DS Door Status Sensor SPDT, 250mA@24VDC
LS Lock Status Sensor SPDT, 1A@24VDC
Resistive

Access controls and/or release contacts must be located in series
with the positive (+) power lead of the EmLock.

Supplied Mounting Hardware

Any low voltage condition will cause erratic operation of the
optional board sensor.
Although SDC recommends the use of a Regulated DC power supply.
A significant voltage drop will occur when using a full wave bridge rectifier.
Installation Location – Indoor Dry

SIGNALING
C

US

PATENT NO. 5,376.910

LISTED
P:\INSTALLATION INST\Electromagnetic Locks\INST-350.vsd

REV -.1

03-16

Page 1

Any suggestions or comments to this instruction or
product are welcome. Please contact us through
our website or email engineer@sdcsecurity.com

1. Fold template as indicated on dotted line. For single doors locate template against the door and header on the
lock jamb side of the frame.
2. Mark and drill holes as indicated by the template.

STEPS 1 & 2

3. Mount armature to door.

STEP 3
STEEL WASHER 2X

5/16-18 SOC HD
SCREW
WITH 3/16 (5MM)
ALLEN HEX

ARMATURE

REINFORCEMENT
TUBE

1-3/4“ HOLLOW
METAL DOOR

5/8“ DRILL

1/2” DRILL
SEXNUT

RUBBER WASHER

HOLLOW METAL DOOR
From Sexnut side of door, drill exactly 1/2” hole thru one metal
thickness only. From Armature side of door, drill 5/8” hole to insert
reinforcement tube. Press in sexnut and reinforcement tube all the
way and mount armature to door using hardware provided.

4. Install magnet onto the header with the magnetic stripes towards the door side of the stop.
Assure that the magnet and armature line up properly, then tighten down ALL mounting screws.

STEP 4

P:\INSTALLATION INST\Electromagnetic Locks\INST-350.vsd

REV -.1

03-16

Page 2

5. Holding the magnet housing at each end, engage the entire length of the interlock detail, by pushing towards the
door. Tap with a soft hammer to ensure proper alignment and engagement.
CAUTION: The lock body must be held in place until secured with mounting screws. Secure socket head
screws provided inside the housing at each end. Start screws into threads carefully to avoid stripping the
threads. Check alignment and tighten screws. Pull wires through frame, mounting plate and magnet housing

STEP 5

6. Select jumper position for 12VDC or 24VDC. Connect power to magnetic lock.
SWITCH or
ACCESS
CONTROL
1
+
2
-

+

Power
Supply

3 4
NO C

A/C
MAINS

5
NC

Lock
Status
Switch
(Relay)

POWER
SUPPLY

-

+
12VDC
or
24VDC

LED Status Indicator:
RED – Energized and Unsecure

-

GREEN – Energized and Secure

24VDC

DOOR POSITION
SENSOR *
N/C – RED
COM – BLK
N/O - GRN

*Door Position Sensor (Reed switch)
NC
COM
RED (open with door closed)
BLACK
GREEN (closed with door closed)
NO

Voltage Jumper
12VDC

7. Test operation. When all is operating properly, tighten
all screws.

To maintain surface plating from corrosion:
Do not touch the lock face with your hands.
Clean lock face with Scotch-Brite pad by 3M (do not use
sandpaper).
Apply a thin film of rust inhibitor (LPS-3) on lock face.
Repeat application on armature plate.
P:\INSTALLATION INST\Electromagnetic Locks\INST-350.vsd

REV -.1

03-16

Page 3



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Create Date                     : 2016:03:22 08:22:42-07:00
Modify Date                     : 2016:03:22 08:22:42-07:00
Author                          : sdc-36
Subject                         : 
Page Count                      : 3
Page Layout                     : SinglePage
Page Mode                       : UseNone
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:6b773a69-f29d-11e5-0000-43ffd60428d4
Producer                        : PDFCreator 2.2.1.0
Keywords                        : 
Creator Tool                    : PDFCreator 2.2.1.0
Document ID                     : uuid:6b773a69-f29d-11e5-0000-43ffd60428d4
Format                          : application/pdf
Title                           : INST-350
Creator                         : sdc-36
Description                     : 
EXIF Metadata provided by EXIF.tools

Navigation menu