- 1 -
Exit Stopper®
STI-6400 Series
Features
· Alarm helps prevent unauthorized exits/entries through doors.
· Easy to install.
· Select volume, alarm duration and delay settings.
· May be mounted on top, right, left or next to almost any door.
· User can select on-site whether to use an alarm or annunciator.
· Less expensive than heavy horizontal bar type units and practical for all
emergency doors.
· Contact STI for custom applications.
We protect the things that protect you.®
- 2 -
Table of Contents
· Warnings and Cautions ........................................................................................... Page 2
· Warranty Information ............................................................................................... Page 2
· Specifications ......................................................................................................... Page 3
1. Dimensions ......................................................................................................... Page 3
2. Polycarbonate ..................................................................................................... Page 3
3. Electronics .......................................................................................................... Page 3
4. Remote Horn ...................................................................................................... Page 3
· Circuit Board Set-Up ............................................................................................... Page 4
· Terminal Strip Layout ............................................................................................... Page 4
· Switch Settings ....................................................................................................... Page 4
· Alarm Feature Description ....................................................................................... Page 5
· Installation Instructions All Units / STI-6400 ............................................................. Page 5
· Mounting Options ................................................................................................... Page 6
· STI-6402 Double Door additional install notes ....................................................... Page 6
· STI-6403 Remote Horn additional install notes ...................................................... Page 6
· STI-6404 Double Door with Remote Horn additional install notes .......................... Page 6
· STI-6405 Exit Stopper with Momentary Reset ....................................................... Page 6
Warnings
All units are recommended for indoor use, not for outdoor use. Unit must be tested periodically
to verify the life of battery. STI recommends you change the 9 Volt battery twice a year. Installer
may need to purchase a simple audio-meter, typically available at your local electronics store,
to measure the sound in areas where the alarm is expected to be heard during normal noise
environment. Results from this test may prove it beneficial to purchase additional exit stopper
units. When purchasing a remote unit (STI-6403 or STI-6404) you will need to periodically test
the connections to make sure audibles function at a sound level to alert staff. Maximum of
three remote alarms may be used in parallel.
All specifications and information shown are current as of publication and subject to change
without notice.
Warranty Information
· Three year guarantee against breakage of polycarbonate in normal use (one year on electro
mechanical and electronic components).
· Electronic warranty form at www.sti-usa.com/wc14
- 3 -
Specifications
Polycarbonate Enclosure
Dimensions 5.375” W x 5.375” H x 2 “ D (137mm x 137mm x 51mm)
Flammability UL94 V-2
Wall Thickness 0.12 in (3.05mm)
Electronics: STI-6403 and STI-6404 - Remote Horn Unit
Power Source 9 VDC operating power* only
Horn Volume at 1 ft. 95 dB low / 105 dB high
Stand by Current 0 A
Alarm Current 50mA at 95 dB/ 200 mA at 105 dB
* Power source for the STI-6403 and STI-6404 Remote Horn uses a separate power
source from the STI-6400 alarm. The Remote Horn contains an internal 9 volt battery.
Horn operates when the Form C contact at main unit is activated on alarm.
Electronics: STI-6400 - All Units
9 VDC Alkaline or 9V-24VDC wired
Class II UL Listed transformer
Horn Volume at 1 ft. 95 dB low / 105 dB high
Relay Output Form C Dry Contacts 0-30 VDC or VAC, 1 Amp
Stand by Current 10uA
Alarm Current 130mA at 95 dB / 200mA at 105 dB
Operating Temperature
Range
Power Source
32° to 113°F (0° to 45°C)
- 4 -
Circuit Board Set-up
Figure 1
TERMINAL BLOCK
(SEE BELOW)
FOR COMPLETE ALARM OPTIONS
AND SWITCH SETTINGS SEE CHART
ON REVERSE SIDE.
PC BOARD
JP5
JP2
JP4
JP3
JP7
SWITCH
ALARM
DURATION
ALARM VOLUME SWITCH
DOOR PROP SWITCH
ARMING SWITCH
)
(FACTORY DEFAULT SETTINGS
(FACTORY DEFAULT SETTINGS)
(ON)
(ON)
(OFF)
(OFF)
(OFF)
TERMINAL BLOCK
FOR COMPLETE ALARM OPTIONS
AND SWITCH SETTINGS SEE CHART
ON REVERSE SIDE.
PC BOARD
JP5
JP2
JP4
JP3
JP7
SWITCH
ALARM
DURATION
ALARM VOLUME SWITCH
TRIP DELAY SWITCH
ARMING SWITCH
)
(FACTORY DEFAULT SETTINGS
(FACTORY DEFAULT SETTINGS)
(ON)
(ON)
(OFF)
(OFF)
(OFF)
Switch Settings
Volume - High (105 dB) at 1 ft. ON*
Volume - Low (95 dB) at 1 ft. OFF
Duration - 30 Second Alarm OFF* OFF*
Duration - 180 Second Alarm OFF ON
Duration - Continuous Alarm ON OFF
Duration - Annunciator Mode ON ON
Trip - Immediate OFF*
Door Prop Mode ON
Arming - Immediate ON*
Arming - 30 Second Delay OFF
FEATURE JP2 JP3 JP4 JP5 JP7
Slide black lever to desired ON/OFF position as labeled on circuit board.
*Factory Settings
POLYCARBONATE COVER
POLYCARBONATE BASE
120 dB HORN
ALARM DURATION
ALARM TRIP DELAY
EXIT DELAY
VOLUME
VIEW OF THE CIRCUIT BOARD
SCREW
6 x 1 1/4 in.
(2) PROVIDED
ANCHOR
(2) PROVIDED
BOTTOM SURFACE AS SHOWN
WIRES THROUGH NOTCH ON
AND ROUTE REED SWITCH
REMOVE FRONT COVER
VIEW SHOWING MAGNET INSTALLATION
MAGNET
NC COM NO GD V+ RS1 RS2 KEYSW
TERMINAL BLOCK WIRING CONNECTIONS
FORM C
DRY
CONTACTS
REMOTE
POWER
INPUT
9-24 VDC
REED
SWITCH
TERMINALS
KEY SWITCH
TERMINALS
INTERNAL REED SWITCH
(RS1)
ALARM DURATION
ALARM TRIP DELAY
EXIT DELAY
VOLUME
VIEW OF THE CIRCUIT BOARD
MAXIMUM GAP 3/4 in. (19mm)
3/8 in. (9.5mm) ON METAL DOOR
AND FRAME
SPACERS (USE AS NECESSARY)
NOTE: 2 SPACERS UNDER BOTH
MAGNET AND REED SWITCH
MUST BE USED ON STEEL DOORS
4
3
2
1
NC COM NO GD V+ RS1 RS2 KEYSW
SLOTS
FLANGES
TERMINAL STRIP
9 VOLT BATTERY
19011 TAMPERPROOF SCREW
(1) PROVIDED
19016 TAMPER WRENCH
(1) PROVIDED
BASE
19014 MOUNTING SCREW
(4) PROVIDED
REED SWITCH
MOUNTING LOCATIONS
(LABELED 1-4)
COVER
NC COM NO GD V+ RS1 RS2 KEYSW
4
3
2
1
NC COM NO GD V+ RS1 RS2 KEYSW
SLOTS
FLANGES
TERMINAL STRIP
9 VOLT BATTERY
19011 TAMPERPROOF SCREW
(1) PROVIDED
19016 TAMPER WRENCH
(1) PROVIDED
BASE
19014 MOUNTING SCREW
(4) PROVIDED
REED SWITCH
MOUNTING LOCATIONS
(LABELED 1-4)
COVER
4
3
2
1
ALARM SOUNDS WHEN DOOR IS OPENED
EMERGENCY USE ONLY
ON OFF
NCCOM NO GD V+ RS1 RS2 KEYSW
SLOTS
FLANGES
TERMINAL STRIP
9 VOLT BATTERY
TAMPERPROOF SCREW
(1) PROVIDED
TAMPER WRENCH
(1) PROVIDED
BASE
MOUNTING SCREW
(4) PROVIDED
REED SWITCH
MOUNTING LOCATIONS
(LABELED 1-4)
COVER
TO KEY
SWITCH
KIT-E06402 REED SWITCH
(RS2)
OPTIONAL:
TO REMOTE
HORN
STI-6403
TERMINAL BLOCK
VIEW SHOWING INSTALLATION OF
ADDTIONAL REED SWITCH KIT-E06402
3/4 in. (19mm)
MAXIMUM GAP
3/8 in. (9.5mm) ON
METAL DOOR AND FRAME
MAGNET ASSEMBLY
(SEE ABOVE FOR INSTALLATION)
DOOR
SWING
6400 SWING
MAGNET
DOOR STOP
MAGNET MUST BE
INSTALLED OPPOSITE
RAISED RIB ON OUTER COVER
SCREW
6 x 1 1/4 in.
(2) PROVIDED
SPACERS - USE
AS NECESSARY
NOTE: (2) SPACERS MUST BE
USED ON STEEL DOORS
ANCHOR
(2) PROVIDED
MAGNET
6400 UNIT
DOOR
SWING
JAMB
DOOR STOP
DOOR
TYPICAL FLUSH MOUNT DOOR JAMB
INSTALLATION
TYPICAL RECESSED MOUNT DOOR JAMB
INSTALLATION
JUMPER WIRE
All models are shipped with jumper
wire installed for use with one reed
switch (RS2). If using second reed
switch, remove jumper wire and insert
second reed switch.
- 5 -
Alarm Feature Description
· Volume Switch JP2 - Sets alarm volume to high 105 dB or low 95 dB.
· Duration Switch JP3 and JP4 - Amount of time alarm sounds after trip. Arming resets at
end of duration if door is closed. Alarm will not reset if in continuous mode; alarm will sound
until reset with the key or until battery is drained.
Annunciator mode will sound a series of short beeps until door is closed or 15 seconds.
· Door Prop Mode Switch JP5 - Once unit is armed with the key (OFF to ON) the alarm
will sound if the door remains open for 15 seconds. If the door opens and closes within 15
seconds, the alarm will not sound.
· Arming Delay Switch JP7 - Delays arming of alarm for 30 seconds. To start arming delay
timing, cycle the key switch (OFF to ON). Door must remain closed for 30 seconds for alarm
to arm.
Installation Instructions
1. Set switches on circuit board to
desired alarm settings (Fig. 1).
2. If using external power source, use
Class II UL Listed transformer. 9V
battery will be in no-load standby.
3. Mount main unit on or next to the door
using hardware provided. Reed switch
may be moved to one of four positions
shown in Fig. 2 or you may route the
reed switch through the knockout in
the bottom of the cover as shown in
Fig. 3.
4. Mount magnet using hardware
provided. Magnet must be within ¾” of
the reed switch when door is closed.
Please refer to figures 7, 8 and 9 for
other mounting options.
Note: When mounting on metal doors
or door frame, use plastic spacers
provided. Magnet must be within 3/8”
of the reed switch when door is closed.
5. If installing STI-6402, STI-6403, STI-
6404 or STI-6405 continue to page 6.
6. Replace cover by sliding flanges on
inside of cover into slots on base, snap
closed and replace the tamper screw.
Figure 3
POLYCARBONATE COVER
POLYCARBONATE BASE
120 dB HORN
ALARM DURATION
ALARM TRIP DELAY
EXIT DELAY
VOLUME
VIEW OF THE CIRCUIT BOARD
SCREW
6 x 1 1/4 in.
(2) PROVIDED
ANCHOR
(2) PROVIDED
BOTTOM SURFACE AS SHOWN
WIRES THROUGH NOTCH ON
AND ROUTE REED SWITCH
REMOVE FRONT COVER
VIEW SHOWING MAGNET INSTALLATION
MAGNET
NC COM NO GD V+ RS1 RS2 KEYSW
TERMINAL BLOCK WIRING CONNECTIONS
FORM C
DRY
CONTACTS
REMOTE
POWER
INPUT
9-24 VDC
REED
SWITCH
TERMINALS
KEY SWITCH
TERMINALS
INTERNAL REED SWITCH
(RS1)
ALARM DURATION
ALARM TRIP DELAY
EXIT DELAY
VOLUME
VIEW OF THE CIRCUIT BOARD
MAXIMUM GAP 3/4 in. (19mm)
3/8 in. (9.5mm) ON METAL DOOR
AND FRAME
SPACERS (USE AS NECESSARY)
NOTE: 2 SPACERS UNDER BOTH
MAGNET AND REED SWITCH
MUST BE USED ON STEEL DOORS
4
3
2
1
NC COM NO GD V+ RS1 RS2 KEYSW
SLOTS
FLANGES
TERMINAL STRIP
9 VOLT BATTERY
19011 TAMPERPROOF SCREW
(1) PROVIDED
19016 TAMPER WRENCH
(1) PROVIDED
BASE
19014 MOUNTING SCREW
(4) PROVIDED
REED SWITCH
MOUNTING LOCATIONS
(LABELED 1-4)
COVER
NC COM NO GD V+ RS1 RS2 KEYSW
4
3
2
1
NC COM NO GD V+ RS1 RS2 KEYSW
SLOTS
FLANGES
TERMINAL STRIP
9 VOLT BATTERY
19011 TAMPERPROOF SCREW
(1) PROVIDED
19016 TAMPER WRENCH
(1) PROVIDED
BASE
19014 MOUNTING SCREW
(4) PROVIDED
REED SWITCH
MOUNTING LOCATIONS
(LABELED 1-4)
COVER
4
3
2
1
ALARM SOUNDS WHEN DOOR IS OPENED
EMERGENCY USE ONLY
ON OFF
NCCOM NO GD V+ RS1 RS2 KEYSW
SLOTS
FLANGES
TERMINAL STRIP
9 VOLT BATTERY
TAMPERPROOF SCREW
(1) PROVIDED
TAMPER WRENCH
(1) PROVIDED
BASE
MOUNTING SCREW
(4) PROVIDED
REED SWITCH
MOUNTING LOCATIONS
(LABELED 1-4)
COVER
TO KEY
SWITCH
KIT-E06402 REED SWITCH
(RS2)
OPTIONAL:
TO REMOTE
HORN
STI-6403
TERMINAL BLOCK
VIEW SHOWING INSTALLATION OF
ADDTIONAL REED SWITCH KIT-E06402
3/4 in. (19mm)
MAXIMUM GAP
3/8 in. (9.5mm) ON
METAL DOOR AND FRAME
MAGNET ASSEMBLY
(SEE ABOVE FOR INSTALLATION)
DOOR
SWING
6400 SWING
MAGNET
DOOR STOP
MAGNET MUST BE
INSTALLED OPPOSITE
RAISED RIB ON OUTER COVER
SCREW
6 x 1 1/4 in.
(2) PROVIDED
SPACERS - USE
AS NECESSARY
NOTE: (2) SPACERS MUST BE
USED ON STEEL DOORS
ANCHOR
(2) PROVIDED
MAGNET
6400 UNIT
DOOR
SWING
JAMB
DOOR STOP
DOOR
TYPICAL FLUSH MOUNT DOOR JAMB
INSTALLATION
TYPICAL RECESSED MOUNT DOOR JAMB
INSTALLATION
JUMPER WIRE
POLYCARBONATE COVER
POLYCARBONATE BASE
120 dB HORN
ALARM DURATION
ALARM TRIP DELAY
EXIT DELAY
VOLUME
VIEW OF THE CIRCUIT BOARD
SCREW
6 x 1 1/4 in.
(2) PROVIDED
ANCHOR
(2) PROVIDED
BOTTOM SURFACE AS SHOWN
WIRES THROUGH NOTCH ON
AND ROUTE REED SWITCH
REMOVE FRONT COVER
VIEW SHOWING MAGNET INSTALLATION
MAGNET
NC COM NO GD V+ RS1 RS2 KEYSW
TERMINAL BLOCK WIRING CONNECTIONS
FORM C
DRY
CONTACTS
REMOTE
POWER
INPUT
9-24 VDC
REED
SWITCH
TERMINALS
KEY SWITCH
TERMINALS
INTERNAL REED SWITCH
(RS1)
ALARM DURATION
ALARM TRIP DELAY
EXIT DELAY
VOLUME
VIEW OF THE CIRCUIT BOARD
MAXIMUM GAP 3/4 in. (19mm)
3/8 in. (9.5mm) ON METAL DOOR
AND FRAME
SPACERS (USE AS NECESSARY)
NOTE: 2 SPACERS UNDER BOTH
MAGNET AND REED SWITCH
MUST BE USED ON STEEL DOORS
4
3
2
1
NC COM NO GD V+ RS1 RS2 KEYSW
SLOTS
FLANGES
TERMINAL STRIP
9 VOLT BATTERY
19011 TAMPERPROOF SCREW
(1) PROVIDED
19016 TAMPER WRENCH
(1) PROVIDED
BASE
19014 MOUNTING SCREW
(4) PROVIDED
REED SWITCH
MOUNTING LOCATIONS
(LABELED 1-4)
COVER
NC COM NO GD V+ RS1 RS2 KEYSW
4
3
2
1
NC COM NO GD V+ RS1 RS2 KEYSW
SLOTS
FLANGES
TERMINAL STRIP
9 VOLT BATTERY
19011 TAMPERPROOF SCREW
(1) PROVIDED
19016 TAMPER WRENCH
(1) PROVIDED
BASE
19014 MOUNTING SCREW
(4) PROVIDED
REED SWITCH
MOUNTING LOCATIONS
(LABELED 1-4)
COVER
4
3
2
1
ALARM SOUNDS WHEN DOOR IS OPENED
EMERGENCY USE ONLY
ON OFF
NCCOM NO GD V+ RS1 RS2 KEYSW
SLOTS
FLANGES
TERMINAL STRIP
9 VOLT BATTERY
TAMPERPROOF SCREW
(1) PROVIDED
TAMPER WRENCH
(1) PROVIDED
BASE
MOUNTING SCREW
(4) PROVIDED
REED SWITCH
MOUNTING LOCATIONS
(LABELED 1-4)
COVER
TO KEY
SWITCH
KIT-E06402 REED SWITCH
(RS2)
OPTIONAL:
TO REMOTE
HORN
STI-6403
TERMINAL BLOCK
VIEW SHOWING INSTALLATION OF
ADDTIONAL REED SWITCH KIT-E06402
3/4 in. (19mm)
MAXIMUM GAP
3/8 in. (9.5mm) ON
METAL DOOR AND FRAME
MAGNET ASSEMBLY
(SEE ABOVE FOR INSTALLATION)
DOOR
SWING
6400 SWING
MAGNET
DOOR STOP
MAGNET MUST BE
INSTALLED OPPOSITE
RAISED RIB ON OUTER COVER
SCREW
6 x 1 1/4 in.
(2) PROVIDED
SPACERS - USE
AS NECESSARY
NOTE: (2) SPACERS MUST BE
USED ON STEEL DOORS
ANCHOR
(2) PROVIDED
MAGNET
6400 UNIT
DOOR
SWING
JAMB
DOOR STOP
DOOR
TYPICAL FLUSH MOUNT DOOR JAMB
INSTALLATION
TYPICAL RECESSED MOUNT DOOR JAMB
INSTALLATION
JUMPER WIRE
Figure 2
Test Alarm
Note: STI recommends testing the alarm in factory settings (see Switch Settings) prior to mounting.
1. Make sure key switch is in the OFF position.
2. Remove tamper screw on the side of the unit using the tamper wrench provided. Remove
housing cover. Save the tamper wrench for future service and battery replacement (Fig. 2).
3. Connect battery.
4. Place magnet next to reed switch. Note: For STI-6402 model, insert jumper wire in RS2
terminals or install second reed switch and place magnet next to reed switches 1 & 2.
5. Turn the key switch to the ON position.
6. Move magnet away from reed switch. Unit should alarm immediately.
7. Turn unit off with the key to silence alarm.
- 6 -
STI-6402 Double Door Install Notes
1. If not using extra reed switch,
leave jumper wire across
terminals RS2 on terminal block.
2. Determine length needed for reed
switch wires. STI provides 1 reed
switch with 6 ft. wires. Cut to desired
length.
3. Connect first reed switch in RS1 and
second in RS2 (Fig. 5). (Refer to Fig. 1
for additional details.)
*Note: Alarm will sound when either door is
opened.
STI-6403 Remote Horn Install Notes
STI-6403 REMOTE HORN UNIT INSTALLATION
ROUTE WIRES
THROUGH NOTCH KEY SWITCH
1. Remove cover.
2. Connect two conductor wire (14-24
AWG) from main unit terminal block
pins COM and NO to remote horn unit
terminal block. (wire not provided).
Units can be set up to 300 ft. apart. Not
polarity sensitive (refer to Fig. 1 and Fig.
5 for details).
3. Connect internal battery.
4. Mount similar to main unit with #8 x 1 in.
screws and anchors if necessary.
5. Replace cover and screws.
6. Turn key switch to ON position.
*Note: The ON/OFF key position is opposite from
6400 main unit. Remote horn sounds when
main unit alarm is activated.
STI-6404 Double Door with Remote Horn Install Notes
The STI-6404 is a combination unit for double doors with a remote horn. Reference the installation
instructions for the main unit, the STI-6402 and the STI-6403 for complete installation.
STI-6405 Exit Stopper with Momentary Reset
The STI-6405 uses a momentary switch. After initial
installation, unit is always on and you do not have to
remember to turn it on when you leave a protected area.
This model also eliminates having to remember to re-arm it
because it is never off.
When the alarm is triggered, to silence the alarm, insert the
key and turn completely to the “RESET” position and hold
for 2 seconds, then release. The switch will spring back to
its original position and push the key out. To turn the unit
off, supply power must be removed.
RESET
Figure 4
Figure 5
POLYCARBONATE COVER
POLYCARBONATE BASE
120 dB HORN
ALARM DURATION
ALARM TRIP DELAY
EXIT DELAY
VOLUME
VIEW OF THE CIRCUIT BOARD
SCREW
6 x 1 1/4 in.
(2) PROVIDED
ANCHOR
(2) PROVIDED
BOTTOM SURFACE AS SHOWN
WIRES THROUGH NOTCH ON
AND ROUTE REED SWITCH
REMOVE FRONT COVER
VIEW SHOWING MAGNET INSTALLATION
MAGNET
NC COM NO GD V+ RS1 RS2 KEYSW
TERMINAL BLOCK WIRING CONNECTIONS
FORM C
DRY
CONTACTS
REMOTE
POWER
INPUT
9-24 VDC
REED
SWITCH
TERMINALS
KEY SWITCH
TERMINALS
INTERNAL REED SWITCH
(RS1)
ALARM DURATION
ALARM TRIP DELAY
EXIT DELAY
VOLUME
VIEW OF THE CIRCUIT BOARD
MAXIMUM GAP 3/4 in. (19mm)
3/8 in. (9.5mm) ON METAL DOOR
AND FRAME
SPACERS (USE AS NECESSARY)
NOTE: 2 SPACERS UNDER BOTH
MAGNET AND REED SWITCH
MUST BE USED ON STEEL DOORS
4
3
2
1
NC COM NO GD V+ RS1 RS2 KEYSW
SLOTS
FLANGES
TERMINAL STRIP
9 VOLT BATTERY
19011 TAMPERPROOF SCREW
(1) PROVIDED
19016 TAMPER WRENCH
(1) PROVIDED
BASE
19014 MOUNTING SCREW
(4) PROVIDED
REED SWITCH
MOUNTING LOCATIONS
(LABELED 1-4)
COVER
NC COM NO GD V+ RS1 RS2 KEYSW
4
3
2
1
NC COM NO GD V+ RS1 RS2 KEYSW
SLOTS
FLANGES
TERMINAL STRIP
9 VOLT BATTERY
19011 TAMPERPROOF SCREW
(1) PROVIDED
19016 TAMPER WRENCH
(1) PROVIDED
BASE
19014 MOUNTING SCREW
(4) PROVIDED
REED SWITCH
MOUNTING LOCATIONS
(LABELED 1-4)
COVER
4
3
2
1
ALARM SOUNDS WHEN DOOR IS OPENED
EMERGENCY USE ONLY
ON OFF
NCCOM NO GD V+ RS1 RS2 KEYSW
SLOTS
FLANGES
TERMINAL STRIP
9 VOLT BATTERY
TAMPERPROOF SCREW
(1) PROVIDED
TAMPER WRENCH
(1) PROVIDED
BASE
MOUNTING SCREW
(4) PROVIDED
REED SWITCH
MOUNTING LOCATIONS
(LABELED 1-4)
COVER
TO KEY
SWITCH
KIT-E06402 REED SWITCH
(RS2)
OPTIONAL:
TO REMOTE
HORN
STI-6403
TERMINAL BLOCK
VIEW SHOWING INSTALLATION OF
ADDTIONAL REED SWITCH KIT-E06402
3/4 in. (19mm)
MAXIMUM GAP
3/8 in. (9.5mm) ON
METAL DOOR AND FRAME
MAGNET ASSEMBLY
(SEE ABOVE FOR INSTALLATION)
DOOR
SWING
6400 SWING
MAGNET
DOOR STOP
MAGNET MUST BE
INSTALLED OPPOSITE
RAISED RIB ON OUTER COVER
SCREW
6 x 1 1/4 in.
(2) PROVIDED
SPACERS - USE
AS NECESSARY
NOTE: (2) SPACERS MUST BE
USED ON STEEL DOORS
ANCHOR
(2) PROVIDED
MAGNET
6400 UNIT
DOOR
SWING
JAMB
DOOR STOP
DOOR
TYPICAL FLUSH MOUNT DOOR JAMB
INSTALLATION
TYPICAL RECESSED MOUNT DOOR JAMB
INSTALLATION
JUMPER WIRE
Figure 6
- 7 -
Mounting Options
TYPICAL DOUBLE DOOR INSTALLATION
STI 6402
*Note: When mounting reed switch on door and the main unit on wall, wire service loop must be used.
TYPICAL DOUBLE DOOR INSTALLATION
STI-6402
Figure 7
Figure 8
Figure 9
POLYCARBONATE COVER
POLYCARBONATE BASE
120 dB HORN
ALARM DURATION
ALARM TRIP DELAY
EXIT DELAY
VOLUME
VIEW OF THE CIRCUIT BOARD
SCREW
6 x 1 1/4 in.
(2) PROVIDED
ANCHOR
(2) PROVIDED
BOTTOM SURFACE AS SHOWN
WIRES THROUGH NOTCH ON
AND ROUTE REED SWITCH
REMOVE FRONT COVER
VIEW SHOWING MAGNET INSTALLATION
MAGNET
NC COM NO GD V+ RS1 RS2 KEYSW
TERMINAL BLOCK WIRING CONNECTIONS
FORM C
DRY
CONTACTS
REMOTE
POWER
INPUT
9-24 VDC
REED
SWITCH
TERMINALS
KEY SWITCH
TERMINALS
INTERNAL REED SWITCH
(RS1)
ALARM DURATION
ALARM TRIP DELAY
EXIT DELAY
VOLUME
VIEW OF THE CIRCUIT BOARD
MAXIMUM GAP 3/4 in. (19mm)
3/8 in. (9.5mm) ON METAL DOOR
AND FRAME
SPACERS (USE AS NECESSARY)
NOTE: 2 SPACERS UNDER BOTH
MAGNET AND REED SWITCH
MUST BE USED ON STEEL DOORS
4
3
2
1
NC COM NO GD V+ RS1 RS2 KEYSW
SLOTS
FLANGES
TERMINAL STRIP
9 VOLT BATTERY
19011 TAMPERPROOF SCREW
(1) PROVIDED
19016 TAMPER WRENCH
(1) PROVIDED
BASE
19014 MOUNTING SCREW
(4) PROVIDED
REED SWITCH
MOUNTING LOCATIONS
(LABELED 1-4)
COVER
NC COM NO GD V+ RS1 RS2 KEYSW
4
3
2
1
NC COM NO GD V+ RS1 RS2 KEYSW
SLOTS
FLANGES
TERMINAL STRIP
9 VOLT BATTERY
19011 TAMPERPROOF SCREW
(1) PROVIDED
19016 TAMPER WRENCH
(1) PROVIDED
BASE
19014 MOUNTING SCREW
(4) PROVIDED
REED SWITCH
MOUNTING LOCATIONS
(LABELED 1-4)
COVER
4
3
2
1
ALARM SOUNDS WHEN DOOR IS OPENED
EMERGENCY USE ONLY
ON OFF
NCCOM NO GD V+ RS1 RS2 KEYSW
SLOTS
FLANGES
TERMINAL STRIP
9 VOLT BATTERY
TAMPERPROOF SCREW
(1) PROVIDED
TAMPER WRENCH
(1) PROVIDED
BASE
MOUNTING SCREW
(4) PROVIDED
REED SWITCH
MOUNTING LOCATIONS
(LABELED 1-4)
COVER
TO KEY
SWITCH
KIT-E06402 REED SWITCH
(RS2)
OPTIONAL:
TO REMOTE
HORN
STI-6403
TERMINAL BLOCK
VIEW SHOWING INSTALLATION OF
ADDTIONAL REED SWITCH KIT-E06402
3/4 in. (19mm)
MAXIMUM GAP
3/8 in. (9.5mm) ON
METAL DOOR AND FRAME
MAGNET ASSEMBLY
(SEE ABOVE FOR INSTALLATION)
DOOR
SWING
6400 SWING
MAGNET
DOOR STOP
MAGNET MUST BE
INSTALLED OPPOSITE
RAISED RIB ON OUTER COVER
SCREW
6 x 1 1/4 in.
(2) PROVIDED
SPACERS - USE
AS NECESSARY
NOTE: (2) SPACERS MUST BE
USED ON STEEL DOORS
ANCHOR
(2) PROVIDED
MAGNET
6400 UNIT
DOOR
SWING
JAMB
DOOR STOP
DOOR
TYPICAL FLUSH MOUNT DOOR JAMB
INSTALLATION
TYPICAL RECESSED MOUNT DOOR JAMB
INSTALLATION
JUMPER WIRE
POLYCARBONATE COVER
POLYCARBONATE BASE
120 dB HORN
ALARM DURATION
ALARM TRIP DELAY
EXIT DELAY
VOLUME
VIEW OF THE CIRCUIT BOARD
SCREW
6 x 1 1/4 in.
(2) PROVIDED
ANCHOR
(2) PROVIDED
BOTTOM SURFACE AS SHOWN
WIRES THROUGH NOTCH ON
AND ROUTE REED SWITCH
REMOVE FRONT COVER
VIEW SHOWING MAGNET INSTALLATION
MAGNET
NC COM NO GD V+ RS1 RS2 KEYSW
TERMINAL BLOCK WIRING CONNECTIONS
FORM C
DRY
CONTACTS
REMOTE
POWER
INPUT
9-24 VDC
REED
SWITCH
TERMINALS
KEY SWITCH
TERMINALS
INTERNAL REED SWITCH
(RS1)
ALARM DURATION
ALARM TRIP DELAY
EXIT DELAY
VOLUME
VIEW OF THE CIRCUIT BOARD
MAXIMUM GAP 3/4 in. (19mm)
3/8 in. (9.5mm) ON METAL DOOR
AND FRAME
SPACERS (USE AS NECESSARY)
NOTE: 2 SPACERS UNDER BOTH
MAGNET AND REED SWITCH
MUST BE USED ON STEEL DOORS
4
3
2
1
NC COM NO GD V+ RS1 RS2 KEYSW
SLOTS
FLANGES
TERMINAL STRIP
9 VOLT BATTERY
19011 TAMPERPROOF SCREW
(1) PROVIDED
19016 TAMPER WRENCH
(1) PROVIDED
BASE
19014 MOUNTING SCREW
(4) PROVIDED
REED SWITCH
MOUNTING LOCATIONS
(LABELED 1-4)
COVER
NC COM NO GD V+ RS1 RS2 KEYSW
4
3
2
1
NC COM NO GD V+ RS1 RS2 KEYSW
SLOTS
FLANGES
TERMINAL STRIP
9 VOLT BATTERY
19011 TAMPERPROOF SCREW
(1) PROVIDED
19016 TAMPER WRENCH
(1) PROVIDED
BASE
19014 MOUNTING SCREW
(4) PROVIDED
REED SWITCH
MOUNTING LOCATIONS
(LABELED 1-4)
COVER
4
3
2
1
ALARM SOUNDS WHEN DOOR IS OPENED
EMERGENCY USE ONLY
ON OFF
NCCOM NO GD V+ RS1 RS2 KEYSW
SLOTS
FLANGES
TERMINAL STRIP
9 VOLT BATTERY
TAMPERPROOF SCREW
(1) PROVIDED
TAMPER WRENCH
(1) PROVIDED
BASE
MOUNTING SCREW
(4) PROVIDED
REED SWITCH
MOUNTING LOCATIONS
(LABELED 1-4)
COVER
TO KEY
SWITCH
KIT-E06402 REED SWITCH
(RS2)
OPTIONAL:
TO REMOTE
HORN
STI-6403
TERMINAL BLOCK
VIEW SHOWING INSTALLATION OF
ADDTIONAL REED SWITCH KIT-E06402
3/4 in. (19mm)
MAXIMUM GAP
3/8 in. (9.5mm) ON
METAL DOOR AND FRAME
MAGNET ASSEMBLY
(SEE ABOVE FOR INSTALLATION)
DOOR
SWING
6400 SWING
MAGNET
DOOR STOP
MAGNET MUST BE
INSTALLED OPPOSITE
RAISED RIB ON OUTER COVER
SCREW
6 x 1 1/4 in.
(2) PROVIDED
SPACERS - USE
AS NECESSARY
NOTE: (2) SPACERS MUST BE
USED ON STEEL DOORS
ANCHOR
(2) PROVIDED
MAGNET
6400 UNIT
DOOR
SWING
JAMB
DOOR STOP
DOOR
TYPICAL FLUSH MOUNT DOOR JAMB
INSTALLATION
TYPICAL RECESSED MOUNT DOOR JAMB
INSTALLATION
JUMPER WIRE
- 8 -
Inst. 6400 SEPT2014
Printed in USA Subject to change without notice.
2306 Airport Rd • Waterford, MI 48327, USA
Phone: 248-673-9898 • Fax: 248-673-1246
info@sti-usa.com • www.sti-usa.com