Sanyo Khs3672R Users Manual
2015-01-26
: Sanyo Sanyo-Khs3672R-Users-Manual-336154 sanyo-khs3672r-users-manual-336154 sanyo pdf
Open the PDF directly: View PDF .
Page Count: 2
System: 36KS72R Indoor/Outdoor: KHS3672R/C3672R
Wall Mounted Air Conditioner
Power V/PH/Hz 230/208/1/60
Circuit Ampacity
Fuse Size, Max.
Compressor
No. used
R.L. Amps - L.R.
Outdoor Unit
Fan type
Dia. (in.) - No. Speeds
Type Drive - No. Speeds
No. Poles
No. Motors
CFM
F.L. Amps
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area
Tube Size
Indoor Unit
Fan type
Dia. & Length (in.) - No. Speeds
No. Speeds
No. Poles
No. Motors
CFM
Indoor Sound Rating
F.L. Amps
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area
Tube Size
Drain Connection Size
Refrigerant
Lbs. - R410a (outdoor unit)
Control
Connection
Line Length, Max (ft.)
Lift Difference, Max (ft.)
Line Size
Line Size
Dimensions
Indoor Unit
Outdoor Unit
Weight
Net
Shipping
Shipping Volume
Performance Data @ ARI Standard Conditions (230/208V)
Cooling
Total Capacity
Sensible Capacity
Latent Capacity
SEER
Dehumidification
Amps
Power Inputs
Outdoor Sound Rating
(A) 15-35 Indoor-Outdoor
(A) 15-35 Indoor-Outdoor
General Data (at 230V)
1
(A) 16.4-17.5
Propeller
18-7/64-1
DC Motor
(RPM) 8 - 830
(W) 1 - 90
15.9
(Pints/H) 10.0
(BTU/H) 31,400 (9,500-31,400)
(BTU/H) 22,030
(BTU/H) 9,370
(Uncrated) 14-9/16 x 59-1/16 x 9-7/16
(W) 3,750/3,750
Aluminum Fin & Copper Pipe
Slit Plate - Inner Rifeled
(in.) 3/8”
6.17
Split System Submittal Data
Electric Expansion Valve
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
Approval:
Date:
Construction:
Unit #:
Drawing #:
2 - 14.1
(sq.ft.) 7.26
(lbs.) 72.8 143
(A) 17.9/19.8
(in. O.D. Discharge) 3/8”
(in. O.D. Suction) 5/8”
DC Rotary Inverter
(High) 1942
(A) 17.3
R410A
(in.) H x W x D
(Crated) 18-7/16 x 62-9/16 x 12-9/16
Indoor Outdoor
(cu.ft.) 8.4 13.0
Indoor Outdoor
(lbs.) 90.4 161
(dB-A) 52
Cross Flow
4-13/18 L46 - 1
3 & Auto
(RPM, High) 4 - 1273
(W) 1 - 50
Aluminum Plate Fin & Copper Tube
Slit Plate - Inner Riffeled
(in.) 3/8”
3 - 12.7
(sq.ft.) 3.23
(HI/Med/Lo) 830/710/590
(A) 0.5
(in.) 1-1/4”
(Hi) (dB-A) 48
Flare
165
50 (outdoor lower), 100 (outdoor higher)
(Uncrated) 30-23/32 x 37 x 13-3/8
(Crated) 34-31/32 x 39-31/32 x 16-3/32
Print Form
Dimensions
Sanyo Commercial Solutions
A Division of SANYO North America
1300 Michael Drive
Wood Dale, IL 60191 USA
www.sanyohvac.com
Features
Controls
Remote Controller
Temperature Control
Timer
Night Setback
Air Louver
Power Failure Automatic Restart
Self-Diagnosis
Air Filter
Options
Refrigerant Line Set
Fresh Air Intake
Airduct Extension
Indoor Frame Extension
Condensate Drain Pump
Non-Removeable Remo-con Bracket
Operating Range
Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling Maximum 95F DB/71F WB 115F DB
Minimum 67F DB/57F WB 0F DB
Built-In
Washable, Anti-Mold
Built-In
Available
N/A
N/A
N/A
Available
Available
Microprocessor
LCD Wireless Type, Temp. Sensor Built In
(Horizontal) Manual
24 Hr. Program
IC Thermostat
Built-In
(Vertical) Automatic
Dimensional Data for 36K72R
Indoor unit : KH3672R
Dimensional Data for 36K72R
Indoor unit : KH3672R