Schneider Electric Connexium Ethernet Gateway Tsxetg100 Users Manual Installation Guide ENG

TSXETG100 to the manual 79d09192-7223-49ac-9edd-d4519cc2e6c9

2015-02-06

: Schneider-Electric Schneider-Electric-Connexium-Ethernet-Gateway-Tsxetg100-Users-Manual-526983 schneider-electric-connexium-ethernet-gateway-tsxetg100-users-manual-526983 schneider-electric pdf

Open the PDF directly: View PDF PDF.
Page Count: 2

DownloadSchneider-Electric Schneider-Electric-Connexium-Ethernet-Gateway-Tsxetg100-Users-Manual- ConneXium TSXETG100 Installation Guide ENG  Schneider-electric-connexium-ethernet-gateway-tsxetg100-users-manual
Open PDF In BrowserView PDF
ConneXium Ethernet Gateway
TSXETG100

SAFETY PRECAUTIONS

Quick Start Checklist
❏
❏
❏

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Only qualified workers should install this equipment. Such work should be performed only after
reading this entire set of instructions.
• NEVER work alone.
• Before performing visual inspections, tests, or maintenance on this equipment, disconnect all
sources of electric power. Assume that all circuits are live until they have been completely deenergized, tested, and tagged. Pay particular attention to the design of the power system. Consider
all sources of power, including the possibility of backfeeding.
• Be sure to follow instructions for Class I, Division 2 environment. Refer to the “Class I, Division 2
Compliant Installation Requirements and Warnings” section.
• Apply appropriate personal protective equipment (PPE) and follow safe electrical practices. For
example, in the USA, see NFPA 70E.
• Turn off all power supplying the equipment in which the ETG is to be installed before installing and
wiring the ETG.
• Always use a properly rated voltage sensing device to confirm that power is off.
• Beware of potential hazards, wear personal protective equipment, and carefully inspect the work
area for tools and objects that may have been left inside the equipment.
• The successful operation of this equipment depends upon proper handling, installation, and
operation. Neglecting fundamental installation requirements may lead to personal injury as well as
damage to electrical equipment or other property.

Installation Guide
63230-319-221A1

10/2009

❏
❏
❏

DESCRIPTION
1. 24 Vdc control power connection
2. 10/100BaseTx (802.3af) connection
3. LEDs:
Ethernet:
• LK: Active link
• TX: Transmitting data
• RX: Receiving data
• 100: Link speed. 100 Mb = ON, 10 Mb = OFF

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, and D or non-hazardous locations
only.

Serial:
• RS485: RS485 mode = ON, RS232 mode = OFF
• TX: Transmitting data
• RX: Receiving data

WARNING

Power/Status

EXPLOSION HAZARD
•
•

Substitution of any components can impair suitabiity for Class I, Division 2.
Do not disconnect while the circuit is live or unless the area is known to be free of ignitable
concentrations.

Failure to follow this instruction can cause death or serious injury.

INTRODUCTION

Field conductors need to be suitable for use in a 70°C temperature ambient and “USE COPPER
CONDUCTOR ONLY”.

CLASS I, DIVISION 2 COMPLIANT INSTALLATION
REQUIREMENTS AND WARNINGS

Failure to follow these instructions will result in death or serious injury.

4.
5.
6.
7.
8.

DIN rail release
Reset button (press to reboot the ETG; no data is lost)
RS485 connection
Dip switches
RS232 connection

All terminal strip screws must be tightened to a torque of 5-7 in/lb (0.56 - 0.79 Nm)

Box Contents
•
•
•
•
•

It is recommended that the sealed relay device be inspected periodically to check for degradation of the
materials and to replace the complete product, not the sealed deivce if any degradation is found.

Mount the unit.
Determine the control power method and connect the power.
Configure the Ethernet communications settings with a web browser (using an Ethernet crossover
cable) or with HyperTerminal (using a null modem cable, which is included in the TCSEAK0100
configuration kit [sold separately]).
Configure the serial ports.
Configure the device list.
Wire the serial ports.

WARNING

ETG unit and connectors
Registration card
Installation guide
Technical Library CD-ROM
Technical support contact sheet

POTENTIAL EQUIPMENT DAMAGE

Additional Resources

TOP

Exposure to some solvents can degrade the sealing properties of materials used in this Gateway.

1

Failure to follow this instruction can cause equipment damage.

2

FRONT
LK

3

BOTTOM

RS485

TX

TX

RX

RX

100

/

5

Documentation and Firmware: Go to www.schneider-electric.com.
Sealed Relay Device information includes:
•
•
•
•

INSTALLATION
Dimensions
65.8
2.59

Ethernet Configuration

Power-over-Ethernet (PoE [IEEE 802.3af])

Before configuring the ETG, obtain a unique static IP address, subnet mask, and default gateway address
from your network administrator. Use a Web browser or HyperTerminal to configure the ETG with the
information obtained from your network administrator.

A

72
2.83

35
1.38

57.9
2.28 80.8
3.18 90.7
3.57

B

Ethernet Switch with
endspan PoE ports

45.2
1.78

Ethernet Switch

Midspan PoE Injector
(part number TCSEAV0100)
10/100BaseTx

49.5
1.95
Millimeters
Inches

Removal

Option
Frame Format

Ethernet Setup Using a Web Browser
1. Disconnect your computer from your network.
NOTE: After disconnecting from your network, your computer should automatically use the default IP
address 169.254.###.### (### = 0 to 255) and the default subnet mask 255.255.0.0. If the IP address
is not automatically configured, contact your network administrator to set up a static IP address.
2. Connect an Ethernet crossover cable from the ETG to the computer.

Media Type

Power Supply
+24 Vdc ± 10%

ETG Control
Power
Connector

DIN Rail
(TS-35)

2

Fuse
disconnect

24 Vdc
Power
Source

(7) +

+

(6) –

–

2

Slide release

Ethernet
crossover
cable
To computer
Ethernet port

Setting

Used to define the physical Ethernet
connection.

•
•
•
•
•

10T/100Tx Auto
10BaseT-HD
10BaseT-FD
100BaseTX-HD
100BaseTX-FD

Default: 10T/100Tx Auto

NOTE: If you enter an IP address that is
already in use, you will be prompted to
select a different IP address.

0.0.0.0 to 255.255.255.255
Default: 169.254.0.10
0.0.0.0 to 255.255.255.255

Subnet Mask

Used to enter the Ethernet IP subnet mask
address of your network.

Default Gateway

Used to enter the gateway (router) IP
0.0.0.0 to 255.255.255.255
address used for wide area network (WAN)
Default: 0.0.0.0
communications.

Default: 255.255.0.0

Ethernet Setup Using HyperTerminal
1. Attach a null modem cable (see below).

24Vdc Control Power

1

Description

Used to select the format for data sent over Ethernet II, 802.3 SNAP
an Ethernet connection.
Default: Ethernet II

Used to enter the static IP address of the
ETG.

10/100BaseTx
(802.3af) port

2.5
0.10

NOTE: Use a PoE injector that fully complies with the IEEE 802.3af standard for active midspan devices,
such as the TCSEAV0100 from Schneider Electric.

8

ETG Ethernet and TCP/IP Settings

68.3
2.69

Mount

Click

Table 1:

IP Address

DIN Rail Mounting and Removal

7

Sealed Device: Relay
Manufacture of Plastic Material: Ticona
Designation of Plastic Material: H140, E130I, T840 or T130
Generic Name of Plastic Material: Liquid Crystal Polymer (LCP)

Powering the ETG
The ETG supports PoE (IEEE 802.3af), allowing the ETG to be powered over an Ethernet connection. Use
either configuration A or B below:

6

4

NOTE: See “Powering the ETG” for powering options.
3. Start Internet Explorer (version 6.0 or higher).
4. In the Address text box, type 169.254.0.10, then press Enter.
5. Type Administrator for your user name, type Gateway for your password, then click OK. User names
and passwords are case sensitive.
6. Click Setup.
7. If the “Ethernet & TCP/IP” page isn’t open, click Ethernet & TCP/IP in the menu on the left side of the
page.
8. Select the frame format and media type (see Table 1 for a description of each option).
9. Enter your IP address, subnet mask, and default gateway address assigned to your ETG by your
network administrator (see Table 1 for a description of each option), then click Apply.
10. Reconnect your computer to your network. If you assigned a static IP address to your computer in step
1, you must restore your computer’s original settings before reconnecting to your network.

RJ45 to
DB9
adapter

RS232 serial
port
(See Table 3
on page 2
for pinouts)
Ethernet
crossover
cable

NOTE: The RJ45 to DB9 adapter and the Ethernet crossover cable are included in the TCSEAK0100
configuration kit (sold separately).

1
NOTE: For Class I, Division 2 installations, tighten the terminal strip screws to a torque of 5-7 in/lb
(0.56 - 0.79 Nm).

2. Click Start > Run, then type hypertrm.
3. In the Name text box, type a name for the new connection (for example, ETG config), then click OK.
4. In the Connect using drop-down list box, select the computer COM port you will be using, then
click OK.

1

5. Set the COM properties as follows: Bits per second = 19200, Data bits = 8, Parity = None, Stop bits = 1,
and Flow control = None.
6. Click OK.
7. Start the ETG Setup Utility:
a. Cycle power or press the reset button on the ETG.
b. While the green Power/Status LED blinks rapidly, press Enter on the computer keyboard to access
the setup utility. See Table 2 for a description of the setup options.
NOTE: The Power/Status LED stops blinking after 5 seconds.
Table 2:

ETG Setup Utility Options

Option

Description

Setting

Serial Configuration

RS485 Wiring

1.
2.
3.
4.

NOTE: For surge protection, we recommend connecting the shield wire directly to an external earth ground
at a single point. For instructions on wiring common Schneider Electric devices, see the wiring instructions
on the ETG100 Technical Library CD.

Start Internet Explorer.
In the Address text box, type the IP address assigned to your ETG, then press Enter.
Type Administrator for your user name, type Gateway for your password, then click OK.
Click Serial Port or Device List as appropriate and proceed to the sections below.

Up to 32 devices.

1
2

Used to select the format for data sent over an
Ethernet connection.

Ethernet II, 802.3 SNAP

Mode

Master, Slave

Master

Default: Ethernet II

Physical Interface

RS485 4-wire, RS485 2-wire, RS232

RS485 2-wire

Used to enter the static IP address of the ETG.

Transmission Mode

Modbus RTU, Modbus ASCII

Modbus RTU

NOTE: If you enter an IP address that is already 0.0.0.0 to 255.255.255.255
in use, you will be prompted to select a different Default: 169.254.0.10
IP address.

Baud Rate

2400, 4800, 9600, 19200, 38400, 56000➀, 57600➀

19200

Parity

Even, Odd, None

Even

0.0.0.0 to 255.255.255.255
Default: 0.0.0.0

Saves the settings and exits the setup utility.

—

ETG

White
Red
Shield

3. If Mode is set to Slave, enter a unique IP address for each remotely connected device. See the User’s
Guide 63230-319-211 for more information about the slave mode.
4. Click Apply to save changes.

Pin No.
Pin 1

Description
Data Set Ready

Rx+
RxTx+
Tx-

Rx+
RxTx+
Tx-

Rx+
RxTx+
Tx-

4,000 ft (1,219 m)

19200

5,000 ft (1,524 m)

2,500 ft (762 m)

38400

5,000 ft (1,524 m)

1,500 ft (457 m)

NOTE: This table is only to be used as a guide.

+

1

6

ON
OFF
2

3

4

5

4-wire

Terminators

Dip switch settings
shown are the
recommended settings
for 4-wire and 2-wire
daisy chains. The 2wire dip switch settings
are the default.

2-wire

UP/ON DOWN/OFF

RS232 Serial Port

2-wire Devices
Up to 32 devices
Terminator
(120 Ω resistor)

Belden 9841

NOTE: The ETG pinout for the RJ45 (RS232) is compliant with the EIA/TIA-561 standard. To ensure
proper connections with other Schneider Electric products, examine the wiring for each device. See the
wiring instructions on the ETG100 Technical Library CD for more information, or contact your local
Schneider Electric support representative.
The RS232 port is used to configure the ETG network parameters, and also can be used for serial
communication using Modbus. The ETG RS232 port is wired as a data terminal equipment (DTE) device
and uses a standard RJ45 connector.

1. Click Device List.
2. Select the number of viewable devices (1 to 128). The default number of devices is eight.
3. In Master mode, enter the Local ID for each attached device on the daisy chain. In Slave mode, enter
the Local ID, Remote ID, and select the Connection for each device that needs to be remotely
connected.
4. Click Apply.

SPECIFICATIONS

Tx Rx Rx- Rx+ –

NOTE: The color code shown is for Belden 8723. The color code for Belden 9842 is Blue/White (Tx+),
White/Blue (Tx-), Orange/White (Rx+), and White/Orange (Rx-).

To set up the Device List for the ETG:

NOTE: An RJ45 to DB9 adapter is included in the TCSEAK0100 configuration kit (sold separately) for use
with an Ethernet crossover cable.

ETG

Slave 1

Slave 2

(3) Rx+ (D1)
(4) Rx- (D0)
(5)

L+
L-

L+
L-

Slave 3

L+
L-

Terminator

MAINTENANCE AND TROUBLESHOOTING

Problem

Possible Cause

Solution
Verify all IP parameters are correct.

Control Power Input
Power-over-Ethernet

Class 3

Operating Input Range

24 Vdc (±10%) sourced by Class 2 rated power
supply

Received Line Signal Detector (Data Carrier Detect)

Pin 3

Data Terminal Ready

Pin 4

Signal Ground

Burden, maximum

4W

Pin 5

Received Data

Isolation

1.5 kV

Transmit Data

Environmental

Pin 7

Clear To Send

Ambient Operating Temperature

0°C to + 60°C

Pin 8

Request To Send

Storage Temperature

–40°C to +85°C

Humidity Rating

5–95% Relative Humidity (non-condensing) at
+55°C

Pollution Degree

Class 2

Maintenance
The ETG does not require maintenance, nor does it contain any user-serviceable parts. If the ETG
requires service, contact your local sales representative for help. Refer to the technical support contacts
provided in the shipping carton for a list of support phone numbers by country. Do not open the ETG
enclosure; this will void the product warranty agreement.

Cannot browse the Incorrect network
ETG.
configuration.

Diagnostics

Forgot
administrator
password.

The Diagnostics page served by the ETG, displays diagnostic data that may be helpful in troubleshooting
network problems. This page also contains information about your specific ETG, including the serial
number, manufacturing date, and media access control (MAC) address. Clicking the Reset button on this
page clears all cumulative counters.

Verify ETG receives requests (ping ETG by going to DOS
prompt and typing “ping” and the ETG IP address, e.g.,
ping 169.254.0.10).
Verify all browser internet options connections settings
are correct.
Call your local sales representative for assistance.

NOTE: This page will show accumulated readings since the ETG was last activated. If power to the ETG is
lost, all values reset to zero.

Troubleshooting

Physical
Weight

6 oz. / 170 g

Dimensions

Height (3.18 in. / 80.8 mm),
Width (2.83 in. / 72 mm),
Depth (2.59 in. / 65.8 mm)

Enclosure

10,000 ft (3,048 m)

Slave 3

Slave 2

In Master mode, Modbus devices do not have to be defined in the Device List, but it helps you manage
your system.

Pin 2

Pin 6

Slave 1

(1) Tx+ (TXD1)
(2) Tx- (TXD0)
(3) Rx+ (RXD1)
(4) Rx- (RXD0)
(5)

Green

White
Shield

RS232 Pin Assignments (EIA/TIA-561 for RJ45)

5,000 ft (1,524 m)

9600

Dip Switch Settings

Blue

Table 3:

10,000 ft (3,048 m)

RS485 Biasing and Termination

Black

For daisy-chain devices on the COM port:

Default: 10T/100Tx Auto
7

➀ RS232/Modbus ASCII only.

•

5,000 ft (1,524 m)

4800

Default Setting

Device List

10T/100Tx Auto
10BaseT-HD
10BaseT-FD
100BaseTx-HD
100BaseTx-FD

Max distance for 17–32 devices

10,000 ft (3,048 m)

Jumper (2-wire)

Default: 255.255.0.0

•
•
•
•
•

Used to define the physical Ethernet
connection.

6

0.0.0.0 to 255.255.255.255

Options

Max. distance for 1–16 devices

2400

Bias

Used to enter the default gateway (router) IP
address used for wide area network (WAN)
communications.

5

Parameter

Baud Rate

Termination

Used to enter the subnet mask of your network.

Default: English

Two (2)
Terminators
(120 Ω resistor)

Belden 8723 or 9842

1. Click Serial Port.
2. Select the mode, physical interface, transmission mode, baud rate, and parity for the serial COM port.
NOTE: Attached serial devices must have the same baud rate, parity, and wiring mode settings. If you are
using RS485, set the mode according to whether your daisy chain is 2-wire or 4-wire.

English, French, Spanish, German

4

4-wire Devices

Serial Port

Used to select the language for the current
HyperTerminal session.

3

Daisy Chain Maximum Distances

IP30

Regulatory/Standards Compliance for Electromagnetic Interference
Emissions (radiated and conducted)

EN 55022 / EN 55011 / FCC Class A

Immunity for Industrial Environments:
Electrostatic Discharge
Radiated RF
Electrical Fast Transients
Surge
Conducted RF
Power Frequency Magnetic Field

EN 61000-6-2
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-8

Regulatory / Standards Compliance for Safety
International (CB Scheme)

IEC 60950

USA

UL 508 / UL 60950/ISA 12.12.01

Canada

cUL (complies with CSA C22.2, #60950)

Europe

EN 60950

Australia / New Zealand

AS/NZS 60950

Other Regulatory / Standards Compliance
Europe

CE

Transparent Ready

B15

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• This equipment must be installed and serviced only by qualified personnel.
• Qualified persons performing diagnostics or troubleshooting that require electrical conductors to be
energized must comply with and follow safe electrical work practices. For example, in the USA, see
NFPA 70E.
Failure to follow these instructions can result in death or serious injury.

Problem

Possible Cause

Source power is not
Power/Status LED applied or is not stable.
is not lit.
LED is burned out.
Ethernet link LED
is not lit.

Proper link is not
established.

Power/Status LED
repeats a four
blink-pause
pattern

The IP address that the
ETG was assigned is
being used by another
networked device.

Solution
Apply power or check power source.
Check to see if other LEDs operate properly.
Make sure the proper cable is used and connected.
Make sure the proper media type is selected in the ETG
Communications setup configuration.
Assign a new IP address to the ETG or to the conflicting
device.
NOTE: When a duplicate IP address is detected, the ETG
resets its specified IP address to the default IP address.
When the ETG detects the conflict no longer exists, it will
use the specified IP address.

www.schneider-electric.com

This product must be installed, connected, and used in compliance with prevailing
standards and/or installation regulations. As standards, specifications, and designs change
from time to time, please ask for confirmation of the information given in this publication.
© 2009 Schneider Electric. All Rights Reserved.

2



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : No
XMP Toolkit                     : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04
Create Date                     : 2004:08:09 09:48:41Z
Creator Tool                    : FrameMaker 8.0
Modify Date                     : 2009:08:11 08:15:56Z
Producer                        : Acrobat Distiller 9.0.0 (Windows)
Copyright                       : 2009
Format                          : application/pdf
Title                           : ConneXium TSXETG100 Installation Guide ENG
Creator                         : Schneider Electric
Document ID                     : uuid:3b5b090a-8bf1-467b-9b36-24d0475793e3
Instance ID                     : uuid:e5287049-021d-415a-b8ac-0a3784b13262
Page Mode                       : UseNone
Page Count                      : 2
Author                          : Schneider Electric
EXIF Metadata provided by EXIF.tools

Navigation menu