ProWORX 32
Programming Software for PLCs
User Guide

31003882 00

372 SPU 780 01EMAN

Version 1.0

2

372 SPU 780 01EMAN May 2002

Table of Contents

Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Chapter 1

Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Welcome to ProWORX 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing ProWORX 32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Logging in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Authorizing ProWORX 32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The ProWORX 32 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ProWORX 32 Client Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tracking Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ProWORX 32 Toolbar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contacting Schneider Electric . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Chapter 2

13
14
15
16
17
19
20
22
23
26

Working with Projects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Creating a New Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Selecting a Controller Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Converting Ladder Logic Databases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the ProWORX Server to Manage ProWORX 32 Projects . . . . . . . . . . . . .
Working with a ProWORX 32 Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using Emulation Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Instructions Supported in Emulation Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adding Emulation Instruction Solve Support . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Documentation Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the Documentation Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Importing and Exporting ProWORX 32 Documentation . . . . . . . . . . . . . . . . . . .
Protected Registers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using Search. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Address Used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The Knowledge Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

372 SPU 780 01EMAN May 2002

27
29
31
34
35
36
39
45
46
51
53
55
58
59
60
62

3

Chapter 3

Communications Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Connecting to a Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Communications Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Configuring Modbus Communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Modbus Communications by Modem. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Configuring Modbus Plus Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Configuring Ethernet Gateway Communications . . . . . . . . . . . . . . . . . . . . . . . . . 72
Configuring TCP/IP Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Network Explorer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

Chapter 4

Configuring a Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Controller Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Controller Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
‘General’ Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
‘Ports’ Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
‘Loadables’ Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Loadable Library Wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86

Chapter 5

Working with Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Initializing Logic in a Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Reading From a Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Writing to a Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Transferring Memory Contents to Controller EEPROM . . . . . . . . . . . . . . . . . . . . 94
Transferring the Flash RAM Executive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Transferring Memory Contents to Micro Flash RAM . . . . . . . . . . . . . . . . . . . . . . 96
Transferring Internal Flash or PCMCIA to Controller Flash . . . . . . . . . . . . . . . . . 97
Starting and Stopping Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
PLC Status Viewer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Analyze Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100

Chapter 6

Configuration Extensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Configuration Extensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Compact Phase II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Data Protect Extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Quantum Hot Standby . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
IO Scanner. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
IO Scanner Wizard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Peer Cop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Peer Cop Wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Profibus Extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Profibus Wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
S980 Extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
SY/MAX Extension. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
TCP/IP Extension. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125

4

372 SPU 780 01EMAN May 2002

Quantum VME Bus Extension. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126

Chapter 7

Using the Logic Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Logic Editor Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Logic Editor Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hotkey Template . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the Logic Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Working with Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Working with Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configurable Mnemonics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ISA Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnostic Trace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sweep (Online Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting Bookmarks in Logic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hardware Clock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Segment Scheduler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Equation Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mathematical Equations in Equation Networks . . . . . . . . . . . . . . . . . . . . . . . . .
Mathematical Operations in Equation Networks . . . . . . . . . . . . . . . . . . . . . . . .
Mathematical Functions in Equation Networks . . . . . . . . . . . . . . . . . . . . . . . . .

Chapter 8

Using the Traffic Cop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Traffic Cop Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Working with Drops and Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Working with Slots. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Online Module Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O Drawing Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Materials List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Chapter 9

127
129
130
132
135
138
140
142
144
146
148
149
151
152
153
154
156
158
161
163
164
165
167
169
171
172

Using the Data Watch Window . . . . . . . . . . . . . . . . . . . . . . . . 175
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Watch Window Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HMI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Trend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Trend - Mode Functionality Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Track Logic Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Track Traffic Cop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Instruction Editor / Terminal Block Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Instruction / Terminal Block Editor Display Scripts . . . . . . . . . . . . . . . . . . . . . .
Display Script Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Script Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Register Editor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

372 SPU 780 01EMAN May 2002

175
177
181
184
188
190
191
192
193
194
195
196
201
5

PID Tuner. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
DRUM Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
Importing and Exporting Data Watch Window Data. . . . . . . . . . . . . . . . . . . . . . 207

Chapter 10

Working with the ASCII Editor . . . . . . . . . . . . . . . . . . . . . . . . 209
ASCII Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209

Chapter 11

Working with Macros. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
Using Macros in Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216

Chapter 12

ProWORX 32 Utilities. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
BM85 Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
BootP Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Compare Utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
I/O Drawing Viewer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
The Ping Utility. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
MBP Stat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230

Chapter 13

ProWORX 32 Reporting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
Reporting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233

Chapter 14

ProWORX 32 Server. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
Using the ProWORX 32 Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240
Audit Trail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243

Chapter 15

Schneider Alliances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Using the Schneider Alliances Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
Using the Script Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
Using Script Editor Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252

Appendices

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255

Appendix A

I/O Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
800. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
A120. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
Compact TSX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
Micro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265
Momentum M1 and INTERBUS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
Quantum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
Sy/Max . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270

6

372 SPU 780 01EMAN May 2002

Appendix B
B.1

B.2

Appendix C

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Isolating Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Manual Procedure List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modbus Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stopcode Error Analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Status Words for S901 and S908 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ASCII Message Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable A Errors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable B Errors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communication Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controller State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controller Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EOL (End of Logic) Pointer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Global Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
S911 Hot Standby Status (S908) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Local Drop Communications Errors (S908). . . . . . . . . . . . . . . . . . . . . . . . . . . .
Machine Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Health . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Number of Segments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Status Word Pointer Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RIO Time-out. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Run/Load/Debug Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
S901/J200 Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
S908 Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stopcode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

271
272
272
273
274
276
277
280
280
281
282
283
284
286
287
288
289
290
291
292
293
295
296
297
298
299
300
301

Editing .DIF Files with Microsoft Excel. . . . . . . . . . . . . . . . . . 303
Editing .DIF files with Microsoft Excel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303

Glossary

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307

Index

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321

372 SPU 780 01EMAN May 2002

7

8

372 SPU 780 01EMAN May 2002

Safety Information

§

Important Information
NOTICE

Read these instructions carefully, and look at the equipment to become familiar with
the device before trying to install, operate, or maintain it. The following special
messages may appear throughout this documentation or on the equipment to warn
of potential hazards or to call attention to information that clarifies or simplifies a
procedure.
The addition of this symbol to a Danger or Warning safety label indicates
that an electrical hazard exists, which will result in personal injury if the
instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal
injury hazards. Obey all safety messages that follow this symbol to avoid
possible injury or death.

DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will
result in death, serious injury, or equipment damage.

WARNING
WARNING indicates a potentially hazardous situation, which, if not avoided, can result
in death, serious injury, or equipment damage.

CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result
in injury or equipment damage.

372 SPU 780 01EMAN May 2002

9

Safety Information

PLEASE NOTE

10

Electrical equipment should be serviced only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use
of this material. This document is not intended as an instruction manual for untrained
persons.
© 2002 Schneider Electric
All Rights Reserved

372 SPU 780 01EMAN May 2002

About the Book

At a Glance
Document Scope

This manual describes how to install, configure and use ProWORX 32 and all of its
components.
To find out about any changes to the manual after this version was published,
consult our web site at public.modicon.com.
Terms and Abbreviations
Numbers are written according to international practice as well as according to
approved SI (System International d’Unites) presentation; each thousand is
separated by a space, along with use of the decimal point, e.g., 12 345.67

Validity Note

This document applies to the installation and use of ProWORX 32 in Windows 98,
Windows Me, Windows XP, Windows NT 4.0, and Windows 2000 environments and
ProWORX Server in Windows XP, Windows NT 4.0, and Windows 2000
environments.

Related
Documents

372 SPU 780 01EMAN May 2002

Title of Documentation

Reference Number

Modicon Ladder Logic Block Library

840 USE 101 00

Modicon Modbus Plus PCI-85 Interface Adapter

890 USE 162 00

Modicon Quantum Hot Standby System Planning and Installation
Guide

840 USE 106 00

Modicon TSX Quantum Automation Series Hardware Reference
Guide

840 USE 100 00

TSX Momentum I/O Base User Guide

870 USE 002 00

Modicon A120 Series I/O Modules User Guide

890 USE 109 00

BM85 Bridge Multiplexer User’s Guide

890 USE 103 00

11

About the Book

Product Related
Warnings

Schneider Electric assumes no responsibility for any errors that may appear in this
document. If you have any suggestions for improvements or amendments or have
found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic
or mechanical, including photocopying, without the express written permission of
Schneider Electric. All rights reserved. Copyright 2002.

User Comments

We welcome your comments about this document. You can reach us by e-mail at
TECHCOMM@modicon.com

12

372 SPU 780 01EMAN May 2002

Getting Started

Welcome to ProWORX 32
About this
Manual

This manual is a guide for operating ProWORX 32. It does not contain information
about specific controllers, I/O cards, or ladder logic instructions. For further
hardware and ladder logic information, go to the ProWORX 32 on-line help system.

Getting Started
with
ProWORX 32

This chapter guides you through starting out with ProWORX 32.

What’s in this
Chapter?

This chapter contains the following topics:
Topic
System Requirements

372 SPU 780 01EMAN May 2002

Page
14

Installing ProWORX 32

15

Logging In

16

Authorizing ProWORX 32

17

The ProWORX 32 Environment

19

ProWORX 32 Client Security

20

Tracking Help

22

ProWORX 32 Toolbar

23

Contacting Schneider Electric

26

13

Getting Started

System Requirements
Hardware
Requirements

Software
Requirements

Hardware:
Hardware

Requirement

Processor

P200

Memory

128 MB

Hard Disk Space (Available)

200 MB

Installation Media Type

CD

Display

256 color VGA or higher

Software:
Software

Requirement

ProWORX 32 Client Operating Systems

Windows 98, Windows NT (Version 4.0, SP5 or higher),
Windows 2000, Window Me, and Windows XP.

ProWORX Server - Operating Windows NT (Version 4.0, SP5 or higher), Windows 2000,
Systems
and Windows XP.

14

Microsoft Internet Explorer

Version 5.0 or higher.

Microsoft MDAC

Version 2.5 or higher.

372 SPU 780 01EMAN May 2002

Getting Started

Installing ProWORX 32
Installing
ProWORX 32

ProWORX 32 requires the installation of MDac version 2.5 or greater and Internet
Explorer 5.0 or greater. Install the MDac software from the ProWORX 32 installation
CD, and ensure that you have a compatible version of Internet Explorer prior to
installing ProWORX 32. Then, to install ProWORX 32:
Step

Modifying or
Repairing the
ProWORX 32
Installation

Uninstalling
(Removing)
ProWORX 32

Action

1

Insert the ProWORX 32 CD into your CD-ROM drive. The ProWORX 32
installation screen should automatically load. If the ProWORX installation
program does not automatically load, you can open the installation in Windows
Explorer at CD Rom Drive → Setup.exe.

2

Select the Language you want to install ProWORX 32 in. (English, French,
German, Spanish.)

3

Follow the on-screen instructions to complete the installation of ProWORX 32.

If you have already installed ProWORX 32:
Step

Action

1

Insert the ProWORX 32 CD into your CD-ROM drive.

2

Select Modify to add new components, or remove already installed components.
Click Next and follow the on-screen instructions.

3

Select Repair to reinstall all components installed by the previous setup. Click
Next and follow the on-screen instructions.

If you have already installed ProWORX 32:

372 SPU 780 01EMAN May 2002

Step

Action

1

Insert the ProWORX 32 CD into your CD-ROM drive.

2

Select Remove to uninstall all installed components.

3

Click Next and follow the on-screen instructions.

15

Getting Started

Logging In
The ProWORX 32
Login Screen

When opening ProWORX 32 you are prompted with the ProWORX 32 Login screen.
If you are using projects that reside on a server or you want to communicate through
the server, enter the login information and click Login. If you are using only projects
that reside on the client, click Bypass.

Logging In to the
ProWORX 32
Server

To access the login screen from within ProWORX 32:

Logging Out of
the ProWORX 32
Server

Step

In the ProWORX 32 menu, select File → Login.

2

Enter the user name and password that your system administrator has given you
in the Name and Password fields.

3

Select your method of communicating with the server from TCP/IP and Modbus
Plus.

4

Enter the address of the server in the Server Address field.

5

Enter the timeout (seconds) in the Timeout field.

6

If you have selected TCP/IP, enter the port number in the Port Number field.

7

If you have selected Modbus Plus, enter the adapter number in the Adapter
Number field.

8

Click Login.

Closing ProWORX 32 client logs you out of the server or to log out while remaining
in ProWORX 32:
Step
1

16

Action

1

Action
From the ProWORX 32 menu, select File → Logout.

372 SPU 780 01EMAN May 2002

Getting Started

Authorizing ProWORX 32
Opening the
Authorization
Program

From the Windows Start menu:
Step
1

Using the
Authorization
Wizard

Action
Select Programs → ProWORX 32 → Authorization.

After opening the authorization wizard:
Step
1

2

3

4

372 SPU 780 01EMAN May 2002

Action
Select which task you would like to perform:
Authorize this PC: Sets up the PC you are currently using to run ProWORX
32.
l Transfer Authorization: Transfers authorization from one PC to another.
l Enter received code: If already registered, you are taken directly to the
Entering Authorization Code screen.
When you have made a selection, click Next.

l

Select which method you would prefer to authorize ProWORX 32 by, and click
Next:
l Authorize by Phone: A message box is displayed containing a customer
support phone number and the customer support hours of operation. Click
OK to return to the authorization application.
l Authorize by Fax: A fax page is printed containing the information you have
entered and a number to send the fax to.
l Authorize by Multi-User License Diskette: This option is used strictly for
uncopyprotected versions in which a diskette has been provided by
Schneider Electric. The contents of the diskette will be transferred onto your
machine.
l Authorize by Email: An email is sent to customer support containing the
information you have entered.
l Authorize by Web: You will be directed to a web page at the Schneider
Electric web site where the information that you have entered will be
displayed and an authorization number will be generated for you.
Select which product you want to authorize and click Next:
Online Only Client: Access to online only portions of ProWORX 32.
Lite Client: Access to Momentum, Compact, and Micro controllers only.
Full Development Client: Full access to all features of ProWORX 32.
Server: Full access to the ProWORX Server.

l
l
l
l

Enter all of your personal information in the User Information screen and click
Next. If you would like to view our privacy policy, click Privacy Policy.

17

Getting Started

Moving
Authorization

After selecting Transfer Authorization in Step One:
Step
1
2

Entering the
Authorization
Number

18

Action
Insert a diskette into your PC diskette drive.
Select which transaction you want to complete and click Next:
Transfer authorization from computer to diskette.
Transfer authorization from diskette to computer.

l
l

After receiving an authorization number:
Step

Action

1

A Code Entry Number and a Computer ID are created automatically

2

Enter the Authorization Number provided to you by customer support and click
Next.

3

To complete your ProWORX 32 authorization, click Finish.

372 SPU 780 01EMAN May 2002

Getting Started

The ProWORX 32 Environment
Overview

ProWORX 32 is organized in such a way that the information you need at any time
is readily accessible through the ProWORX 32 main interface.

Setting
ProWORX 32
Properties

From the My Computer right-click menu in the Navigation panel:
Step
1

Select Properties.

2

Select the Environment tab.

3

Set the following ProWORX 32 Environment parameters:

4

Auto Monitor/Logout: When selected with Logout, the Online Network Editor
closes after the specified amount of inactive time. When selected with Monitor,
the Online Network Editor closes after the specified amount of inactive time and
Monitor mode is activated.

5

Prompt For Read When Exiting Online: Displays a prompt to perform a read
after switching out of online mode.

6

Compare To Project On Attach: Displays a prompt to perform a compare when
switching to online mode.

7

Enable Audit Trails: Audit trails and the log book are viewable.

8

Automatically Update Used Tables Online: When going online, the used
tables are automatically updated.

9

Enable Scrolling Navigation Panel: When this option is selected, the
navigation panel shrinks showing only the panel’s border. To see the navigation
panel, hover your mouse over the border and the navigation panel expands.

10

372 SPU 780 01EMAN May 2002

Action

Instruction Toolbar: See ProWORX 32 Toolbar, p. 23.

19

Getting Started

ProWORX 32 Client Security
Overview

Security allows an administrator to disable features of ProWORX 32.

Setting Security
for a Client

From the My Computer right-click menu in the Navigation panel:

20

Step

Action

1

Select Security Settings to open the Client Security dialog.

2

To set and confirm the administrative password, enter the password into the
Password and Confirm Password boxes.

3

To set the rights that users have while running ProWORX 32 on this specific PC,
select rights from the Enabled Functionality group of rights. See User Rights
below for more information.

4

Click OK to confirm changes. Click Close to exit.

372 SPU 780 01EMAN May 2002

Getting Started

User Rights

User rights descriptions:

372 SPU 780 01EMAN May 2002

User Rights

Descriptions

Controller Configuration

The ability to change the controller configuration, or change
controller type.

Traffic Cop

The ability to edit in the traffic cop.

Communications

The ability to change the communications setup including the
controller’s address.

Logic

The ability to edit logic.

Forcing

The ability to force contacts and coils.

Insert

The ability to insert cells, rows, columns, and networks.

Delete

The ability to delete cells, rows, columns, and networks.

Sweep

The ability to enter sweep mode.

Data Editors

The ability to enter any of the data editors, If deselected, the
user is unable to change register data.

Extended Memory

The ability to edit extended memory registers.

Protected Registers

The ability to set ranges of 4xxxx addresses that are
uneditable. See Setting Protected Registers for more
information.

Configuration Extensions

The ability to edit the configuration extensions.

ASCII Messages

The ability to edit the ASCII messages.

Search

The ability to use the search feature.

Read

The ability to read from the controller.

Write

The ability to write to the controller.

Start/Stop

The ability to start or stop the controller.

Clear Audit Trails

The ability to remove all audit trail and logbook entries.

21

Getting Started

Tracking Help
Overview

Tracking help is a brief description or overview of the editor, instructions, or I/O card
that is currently selected in ProWORX 32.

Using Tracking
Help

From the ProWORX 32 menu:

22

Step

Action

1

Select View → Tracking Help to open the tracking help window.

2

To see more information about the current tracking help topic, press F1.

372 SPU 780 01EMAN May 2002

Getting Started

ProWORX 32 Toolbar
Overview

The ProWORX 32 toolbar holds all of the icon buttons that can be used to access
features, utilities, and tools needed to properly use ProWORX 32s development
capabilities.
Handle

Using the
Toolbar

ProWORX 32 Toolbar

From the ProWORX 32 toolbar right-click menu:
Step
1

Action
To add a toolbar, select a toolbar to add from the list. A toolbar that is displayed
is denoted by a check

Customizing the
Instruction
Toolbar

.

2

To remove a toolbar, select a toolbar to remove from the list.

3

To move a selected toolbar within the ProWORX 32 toolbar area, select the
toolbars handle, and drag and drop the toolbar to its desired location.

4

To customize the toolbars, click Customize. To view help concerning toolbar
customizing please refer the Windows help file, Windows Start Menu → Help.

In the project navigation panel:

372 SPU 780 01EMAN May 2002

Step

Action

1

From the project right-click menu, select Properties.

2

Select the Environment tab.

3

Scroll to the number of the button (1-14) you would like to change in the Button
Number field. eg. 1 = the leftmost button, 14 = the rightmost button.

4

Enter the name of the instruction to be placed on the toolbar in the Button Text
field.

23

Getting Started

Toolbar Listing

Default toolbars and items:
Toolbar
Standard Toolbar

Item
- Create a New Project
- Save the Active Project
- Print the Active Project
- Open Print Preview
- Open Report Setup
- Undo the most recent action (CTRL+Z)
- Repeats the most recent action
- Cut the current selection and copy to the system clipboard
(CTRL+X)
- Copy the current selection to the system clipboard (CTRL+C)
- Paste data from system clipboard to selected area (CTRL+V)
- Open the Search window (CTRL+F)
- Repeat the last Search operation (SHIFT+F4)
- Find and Replace (CTRL+H)
- Open Help (F1)

Control Toolbar. See
Working with a
ProWORX 32 Project,
p. 36

- Take project offline
- Take project to emulation
- Take project online
- Take project to combined mode

24

372 SPU 780 01EMAN May 2002

Getting Started

Toolbar
Online Control Toolbar

Item
- Start/Stop controller. See Starting and Stopping Controllers,
p. 98.
- Initialize logic. See Initializing Logic in a Controller, p. 90.

DWW Log Toolbar

l
l

- Read from controller. See Reading From a Controller, p. 91.
Read
Read extended memory

l
l
l
l

- Write to controller. See Writing to a Controller, p. 92.
Write logic
Relocate logic and data
Relocate logic only
Write extended memory
- First record
- Previous record
- Next Record
- Last record
- Pause/Resume
- Record

- Toggle between logging real-time data from a controller and
logging stored
Instruction Toolbar
- A user-defined set of instructions. Clicking an instruction adds it
to the logic editor at the cursor.

372 SPU 780 01EMAN May 2002

25

Getting Started

Contacting Schneider Electric
Contact
Information

Customer support is available to registered Schneider Electric users.
If you have a question about ProWORX 32 and can’t find the answer in the
ProWORX 32 Help system or the User’s Guide, contact our Customer Service staff
for assistance. You can reach Schneider’s Customer Support department by
Internet, phone, fax, or mail:
Schneider Electric
One High Street
North Andover, MA 01845
Internet: http://public.modicon.com/
E-mail: customercentral@schneiderautomation.com
Support Hotline: (888) 266-8705
Telephone: (978) 794-0800
Fax: (978) 975-9301

Support
Guidelines

To help us assist you quickly, we suggest you have the following information ready:

l The version and serial number of your copy of ProWORX 32. To find this
information, select About on the Help menu.

l What you were doing when the problem occurred, whether you can repeat it, and
any error messages you received.

l Your version of Windows. To find this information in Windows ME, 98, 95, 2000
or NT 4.x: click Start, then Settings. Select Control Panel. When the Control
Panel window opens, double-click System. When the System window opens,
select the General tab. Your version of Windows is listed under the heading
System.
l Information about your computer, including its processor type, memory, hard
drive size, video card type, and I/O boards.

26

372 SPU 780 01EMAN May 2002

Working with Projects

At a Glance
Overview

ProWORX 32 holds information about each of your controllers in a project. The
project stores:

l
l
l
l
l
l

372 SPU 780 01EMAN May 2002

The controller’s configuration
Ladder logic
Descriptors of the controller and ladder logic
Project properties
Data trends
Compare results

27

Working with Projects

What’s in this
Chapter?

28

This chapter contains the following topics:
Topic

Page

Creating a New Project

29

Selecting a Controller Type

31

Converting Ladder Logic Databases

34

Using the ProWORX Server to Manage ProWORX 32 Projects

35

Working with a ProWORX 32 Project

36

Using Emulation Mode

39

Instructions Supported in Emulation Mode

45

Adding Emulation Instruction Solve Support

46

Documentation Editor

51

Using the Documentation Editor

53

Importing and Exporting ProWORX 32 Documentation

55

Protected Registers

58

Using Search

59

Address Used

60

The Knowledge Base

62

372 SPU 780 01EMAN May 2002

Working with Projects

Creating a New Project
Creating a New
Project

From the ProWORX 32 tool bar:
Step
1

Overview

Action
Click File → New.

2

Enter a project name in the New Project Name box.

3

Click OK. The New Project Wizard appears.

The Project Configuration Wizard steps you through creating new default projects
and modify existing projects in ProWORX 32. The configuration wizard guides you
through a series of easy to understand steps to set up a project. Each step
configures an important area of the project.
Each screen in the wizard has a caption stating which step you are currently
completing. Also, each screen has a diagram and description detailing what the
current step involves.
The standard wizard buttons are:

372 SPU 780 01EMAN May 2002

Button

Function

Help

Displays context-sensitive help pertaining to the current step.

Cancel

Exits the wizard and no new project is created or no changes are saved.

Back

Returns the wizard to the previous step.

Next

Advances the wizard to the next step.

Finish

Completes the wizard and creates a new project or saves the changes.

29

Working with Projects

Step 1 - Select
Creation Method

30

Select a path to create a new project:
Path

Description

Online to Controller

This option sets up a project enough to go online to a controller.
The first step configures the parameters used to communicate
with the desired controller. This step encapsulates
communications setup; use of this step is identical to the Project
communications setup dialog. Click Next to display the Finish
step. Click Finish to go online to the desired controller.

Select Controller Type

This step allows you to set up the controller type. For more
information, see Selecting a Controller Type, p. 31.

Base on Existing Project

This option creates a project based on an existing project. First,
select an existing Project from the list of projects on the local
computer. ProWORX 32 creates a copy of the project and uses
it as the base for the new project. ProWORX 32 initializes the
logic and clears the traffic cop of the new project. ProWORX 32
then displays a communications setup step to configure
communications to the desired controller. On the finish step
click Finish to complete the new project creation.

Read from Controller

This option creates a project based on a read of the program
from an existing controller. ProWORX 32 displays a
communications setup step to configure communications to the
desired controller. On the Finish step click Finish. ProWORX
32 reads the contents of the controller into a new default project.

Use as a Macro

When selecting any offline options, you can click the Use as
Macro checkbox to create a macro-enabled database. For more
information, see Macros, p. 214.

372 SPU 780 01EMAN May 2002

Working with Projects

Selecting a Controller Type
Selecting a
Controller Type

This step includes two drop down lists to select a controller. To the right of the drop
down lists is a detailed description of the currently selected controller. Displayed
below the controller selection drop down list are pictures of the I/O type(s) supported
by the current controller.
To select a controller:

372 SPU 780 01EMAN May 2002

Step

Action

1

Select a controller family from the Pick a Controller Family drop-down box:
Compact, Micro, Momentum, 38x/48x, 484 Replacement, 68x/78x, 984ABX,
Atrium, Other, Quantum, or VME.

2

Select the desired controller from the Pick a Controller drop-down box. The list
of controllers depends on which controller family you selected in Step 1.

3

Click Next to continue.

31

Working with Projects

Controller
Details

The controller details available depends on the controller you have selected in the
previous step. Set the available controller details:
Controller Detail

Description

Executive Cartridge

Cartridges which determine the controller’s instruction set.
Select the one installed in your controller. The Executive
Cartridge is available for some 38x, 48x, 68x and Quantum
controllers.

Memory Pack

The amount of both Extended and User Logic memory in the
controller. Select the amount installed in your controller.
Available on a variety of x80 and 984 A/B controllers.

Extended Memory

Additional memory providing 6xxxx registers. Select the
amount installed in your controller. Available on a variety of
x80 and 984 A/B controllers.

Built-in XMRD/XMWT

Select Yes or No. The built-in extended memory functions
option is only available for the 984AS908.

User Logic

Memory available for ladder logic. Select the amount of
memory you want to use for ladder logic from the total amount
available in your controller. Available on a variety of x80 and
984 A/B controllers.

S908 Size

Select either 512 or 1024 (1k) input and output points per drop.
Available for most 68x and 78x controllers.

Micro I/O Mode

Micro controllers only. Select:
Single: The controller is independent, not in a parent/child
relationship.
l Parent: The controller is the parent in a parent/child
relationship.
l Child: The controller is the child in a parent/child
relationship.
Available for "Brick" controllers from the Micro 311/0 to the
Micro 612/4.

l

Click Next when you have set the controller details.

32

372 SPU 780 01EMAN May 2002

Working with Projects

Communications
Setup

Finish

To select a communications mode:
Step

Action

1

Select a communications tab: Modbus, Modbus Plus, Gateway, or TCP/IP.

2

Set the communications-specific properties as desired. For more information
see Communications Overview, p. 66.

3

If your project will communicate with a controller via the ProWORX server, click
the Use server to communicate check box.

4

Click Next to continue.

The finish step displays a summary of the selected controller type. Click Finish to
perform the operations set up in the previous steps. When the progress number
reaches 100% the wizard closes. The newly created project appears in the project
navigation tree.

372 SPU 780 01EMAN May 2002

33

Working with Projects

Converting Ladder Logic Databases
Overview

Old ladder logic databases created in 484, 884, ProWORX, ProWORX Plus,
ProWORX NxT, Modsoft, and Concept can be imported into the new format of
ProWORX 32. By importing a database using the ProWORX 32 convert function,
your logic, documentation, configuration, and other relevant areas of your project
are converted directly into ProWORX 32.

Converting a
Database

From the ProWORX 32 menu:

34

Step

Action

1

Select File → Import Database. The Select Database to Convert dialog
appears.

2

Select a database to convert from the following database types:
l 484 databases - *.CF4
l 884 databases - *.CF8
l Old ProWORX databases - *.CF9, *.DCF
l Modsoft databases - *.CFG
l Concept databases - *.ASC
l ProWORX Plus/NxT databases - *.DCF

3

When you have selected a database, click Open to start the conversion process.

4

To cancel the conversion, click Cancel in the Conversion Status dialog.

5

Click OK in the Conversion complete dialog to return to ProWORX 32.

372 SPU 780 01EMAN May 2002

Working with Projects

Using the ProWORX Server to Manage ProWORX 32 Projects
Overview

The ProWORX Server is an application used to store and manage ProWORX 32
projects. The following project transactions can occur between a ProWORX 32
client, and the ProWORX Server. For more information about the ProWORX Server,
see ProWORX 32 Server, p. 239.
In the project navigation panel of the ProWORX 32 client, from the project right-click
menu:

372 SPU 780 01EMAN May 2002

Transaction

Result

Select Get from Server.

The selected project is copied to your local PC. If you
plan to make changes to a project it is recommended
that you get the project from the server with a lock.

Select Get from Server with Lock.

The selected project is copied to your local PC. You
have sole access and editing capabilities for a project
when it is locked out to your PC.

Select Put to Server.

When you have finished making changes or you want
to add a project to the server, use the Put to Server
function. This function creates a copy of the project on
the server.

Select Unlock Project.

The project is unlocked so that other clients can
check it out of the server.

35

Working with Projects

Working with a ProWORX 32 Project
Projects in
Offline Mode

To work with a controller offline, you must create a project for it. This project stores
the controller’s traffic cop and configuration information, its ladder logic, and
descriptors of the controller and ladder logic. As you work in offline mode, editors
modify this data. Because the offline editors are not connected directly to the
controller, changes made in it do not take effect immediately. Instead, when you
have finished programming, you can write all your changes to the controller at once.

Taking a Project
Offline

From the project right-click menu in the Navigation panel:
Step
1

Action
Select Project State → Offline.

Projects in
Online Mode

To work with a controller online, select a project, and changes its mode to online.
ProWORX 32 then attaches to that controller with the communications settings
provided. The online editors read ladder logic, traffic cop information, register
contents, and the controller’s configuration directly from the controller and
ProWORX 32 writes back to it. Changes made in the online mode take effect in the
controller immediately, but don’t appear in its project until you read from the
controller.

Taking a Project
Online

From the project right-click menu in the Navigation panel:
Step
1

Action
Select Project State → Online.

Projects in
Emulation Mode

To work with a controller in emulation mode, you first make sure that the project is
in offline mode. Bringing a project into emulation mode allows you to emulate the
solving of logic without needing a controller. From emulation mode, you can view the
solving of logic, and the changing of register data. Use the online controls to start
and stop the emulator. For more information, see Using Emulation Mode, p. 39.

Taking a Project
to Emulation

From the project right-click menu in the Navigation panel:
Step
1

36

Action
Select Project State → Emulation.

372 SPU 780 01EMAN May 2002

Working with Projects

Projects in
Combined Mode

Combined mode is a combination of offline and online modes. When a project is in
combined mode, it attaches to the controller specified by the communication
settings. All work done in the editors are made directly to the controller. Work done
in the logic editor, traffic cop, and register editors are also saved back to the project
file, so there is no immediate need to read from the controller to update the project
file with all of the changes.

Taking a Project
to Combined
Mode

From the project right-click menu in the Navigation panel:
Step
1

Setting the
Project
Properties

Action
Select Project State → Combined.

From the project right-click menu in the Navigation panel:

372 SPU 780 01EMAN May 2002

Step

Action

1

Ensure that the project is selected in the navigation panel. The currently selected
project is denoted by its name being part of the ProWORX screen’s title bar.

2

Select Properties.

3

Select the Project tab.

4

Configure the project properties. See Project Properties Descriptions below.

5

Click OK to save changes.

37

Working with Projects

Project
Properties
Description

Property descriptions:
Property

Description

Detailed Project Name

Enter the detailed description of the current project.

Project

Enter a name (brief description) for the current project.

Client

Enter the name of the project’s client if applicable.

Author

Enter the name of the project author.

6 Digit Addressing

When On, sets all addressing to six digits, allowing
ProWORX 32 to enter and display constants greater than
9999. Auto is the default, which sets addressing to five digits
unless the controller has addresses configured that require
six.

Maximum Decimal Value

Restricts registers to a decimal value of either 9999 (default)
or 65535.

Enable Symbols

Enables or disables symbolic addressing.

Save to Flash on Exit of Online If the controller supports flash memory, selecting this
feature will save the controllers contents to memory on exit
of online.
Online Update Rate

38

Adjust how fast ProWORX 32 polls the controller for
information when online and running. The faster the update
rate, the more accurate the data displayed. But, as the
update rate is increased, the performance of the software
is reduced.

372 SPU 780 01EMAN May 2002

Working with Projects

Using Emulation Mode
Overview

The emulation function is used to test the integrity of the logic in a project without the
need of a PLC. Emulation mode allows you to check discrete states and register
contents, and test your logic in a "safe" environment.

Taking a Project
to Emulation

In the project navigation panel:
Step
1

Action
From the project right-click menu, select Project State → Emulation.

Setting up
Emulation

Before you test your logic, set the default states, or values into the emulator, so
when you use the Load command, you can debug your database file using the
states you have preset. Discretes may be set to OFF, ON, Enabled, Disabled OFF,
or Disabled ON. Register values may be set to Decimal, Hexadecimal, Binary,
ASCII, or Floating Point.

Setting
Emulation
Properties

From the project right-click menu in the Project Navigation Panel:

372 SPU 780 01EMAN May 2002

Step

Action

1

Select Properties. The properties window appears.

2

In the Properties window, select the Emulation tab.

39

Working with Projects

Setting the
Default Address
Data Values

40

You can toggle discretes or transfer values to arrays of registers during emulation
when setting states or register contents on a state or value.
Step

Action

1

In the Emulation Properties tab, enter an address or a range or addresses in the
format (axxxx-axxxx) in the Address Range field.

2

If you have entered an analog address range, enter a value in the Data Value
field. If you have entered a discrete address range, select a data value (Off, On,
Enables, Disabled Off, Disabled On) from the Data Value drop-down list.

3

If you have entered an analog address range, select a radix for the address
range from the Radix drop-down list.
Note: Floating point only works with two registers. All others can be set to work
on ranges of addresses.

4

Click OK to save the changes and return to ProWORX 32.

5

To load the default address values while in Emulation mode, select Emulation
→ Load Default Address Values from the logic editor right-click menu.

372 SPU 780 01EMAN May 2002

Working with Projects

Setting
Instructions with
Loopback

You can toggle discretes or transfer values to arrays of registers during emulation
when setting states or register contents based on a state or value. To edit the
loopback table, in the Emulation Properties tab:
Step

Enter the address where you want the loopback in the Ctrl Address field.
Control Address - The instruction address in the logic that is checked for a
condition while the logic is being emulated and Loopback is enabled.

2

Enter the state or value of the address in the Condition field.
Condition - The state or value of the Control discrete or analog. If the condition
of the Control’s address is true, the Loopback stores a new value or triggers a
new state in a Destination range of addresses.

3

Select the numeric system you want to enter your Condition in from the Radix
drop-down list.

4

Enter the number of scans you want the Condition to be monitored by before
being updated (0 to 65535) in the Scan Delay field.
Scan Delay - You may not want the Loopback function to immediately update
the Destination when a condition becomes true. By setting Scan Delay, you can
set the number of scans for which the Condition must remain true before the
Destination is updated.

5

Enter the address range by typing a the start and end addresses, separated by
a dash, in the Destination field. If there is only one Destination for that control
condition, enter only one address.
Destination - The Destination is the range of addresses to be driven when the
Loopback Control Condition is true.

6

For discrete destinations, select On or Off from the Data Value drop-down list.
Data Value - The Data Value is the new state or value to be placed in a
Destination address range when the Loopback Control Condition is true.

7

Select the numeric system you want to enter your Destination in from the Radix
drop-down list.

8

Click OK to save the changes and return to ProWORX 32.

9

To load the loopback table while in Emulation mode, select Emulation → Load
Loopback Table from the logic editor right-click menu.

10

372 SPU 780 01EMAN May 2002

Action

1

To enable or disable loopback while in Emulation mode, select Emulation →
Loopback Enabled from the logic editor right-click menu.

41

Working with Projects

Adjusting Scan
Time

Starting
Emulation

In the Emulation Properties tab:
Step

Action

1

Enter a scan time rate between 1 and 999 in the Scan Time field.
Note: This option does not speed up or slow down the emulator’s solving time.
It only affects how fast the timers increment.

2

Click OK to save the changes and return to ProWORX 32.

From the project navigation panel:
Step

Action

1

To start emulation, select Online Commands → Start/Stop.

2

Set the emulator’s solve mode in the Start/Stop dialog. See Setting the Solve
Mode for more information.

3

To start emulation in continuous solve mode, click Start.

Setting the Solve
Mode

Several solve modes are available to assist in emulating logic. You can set
Emulation to stop solving following any number of full sweeps, after a particular
network is solved, when a breakpoint is reached or to stop when certain logical
conditions are true or not true. You can change the solve mode by selecting Online
Commands → Start/Stop and selecting a solve mode radio button at anytime when
emulation is in a stopped state.

Setting the Solve
Mode to Sweep

In the start/stop dialog:

Solving by
Network

42

Step

Action

1

Select the Sweep radio button.

2

Enter the number of times you want the logic to be solved before stopping in the
Number of Scans to Sweep field.

3

To the Spacebar to run another sweep.

In the start/stop dialog:
Step

Action

1

Select the Network radio button.

2

Logic is solved network-by-network in order of networks, starting at segment
one, network one. Press the Spacebar to solve the next network.

372 SPU 780 01EMAN May 2002

Working with Projects

Solving by
Instruction

Solving to a
Breakpoint

Setting Emulator
Breakpoints

In the start/stop dialog:
Step

Action

1

Select the Instruction radio button.

2

Logic is solved instruction-by-instruction in order of instructions, starting at
segment one, network one, cell (1,1). Press the Spacebar to solve the next
instruction.

In the start/stop dialog:
Step

Action

1

Select the Break radio button. Select one of the following break types:

2

To set a break when a particular value is reached in a register, select Register
radio button. Enter the address in the Address field and a data value in the
Value field.

3

To set a break when a discrete value turns on or off, select the Discrete radio
button. Enter the address in the Address field and select Off to On or On to Off
in the Value field.

4

To set a break when the solve reaches a certain instruction type in logic, select
the Instruction radio button. Select the instruction to break at from the
Instruction drop-down list.

5

To set a break when a specific address is reached in logic, select the Address
radio button. Enter the address to break at in the Address field.

6

To break at the breakpoints set in the breakpoint table, select the Breakpoint
radio button. For more information on setting breakpoints, see Setting Emulator
Breakpoints.

7

Logic is solved in order until it comes to the first breakpoint at which point it stops.
To continue solving logic until the next breakpoint, press the Spacebar.

In the logic editor while in Emulation mode;

372 SPU 780 01EMAN May 2002

Step

Action

1

To set a breakpoiont at the cursor in the logic editor, select Emulation →
Breakpoint from the right-click menu.

2

To delete a breakpoint, select Emulation → Breakpoint Table from the rightclick menu. Select the row of the breakpoint that you want to delete and click
Delete. Click Close to exit the Breakpoint Table.

43

Working with Projects

Stopping
Emulation

44

From the project navigation panel:
Step

Action

1

To stop emulation, select Online Commands → Start/Stop.

2

Click Stop.

372 SPU 780 01EMAN May 2002

Working with Projects

Instructions Supported in Emulation Mode
Overview

Following is an alphabetical list of instructions support by ProWORX 32 1.0
emulation mode.

372 SPU 780 01EMAN May 2002

Instruction

Instruction

Instruction

Instruction

AD16

DV16

NBIT

SKP

ADD

EMTH (1-37)

NC

SRCH

AND

FIN

NCBT

SU16

BCD

FOUT

NO

SUB

BLKM

FTOI

NOBT

T.01

BLKT

IBKR

NTC

T->R

BROT

IBKW

OR

T->T

CMPR

ICMP

PTC

T0.1

CNR

ITOF

R->T

T1.0

COMP

JSR

RBIT

TBLK

CONV

LAB

RET

TEST

CR

MATH

RTTI

TTR

DCTR

MBIT

RTTO

UCTR

DIV

MSTR (reg read/write

SBIT

XOR

DMTH

MU16

SCIF

DRUM

MULT

SENS

45

Working with Projects

Adding Emulation Instruction Solve Support
Overview

ProWORX 32 has the capability of allowing advanced users to add instruction solve
support for the ProWORX emulator.

Creating an
Emulation
Solve File

Using a text editor:

46

Step

Action

1

Create a blank .ESF file in the ProWORX\32\EmulatorInst\ directory.

2

Name your .ESF file the same as the instruction that is to be solved. E.g.: The
ADD instruction’s emulation solve file would be named ADD.ESF.
Note: Do not use spaces in your emulation solve file name.

372 SPU 780 01EMAN May 2002

Working with Projects

Instruction Solve
File Function
Parameters

Parameter Descriptions
Variable

Description

Network

The network number where instruction is located.

Row

The row in logic where instruction is located.

Col

The column in logic where instruction is located.

TopTyp

The address type of the top node of the instruction (valid values: 0, 1, 3, 4, 8
for constants).

TopVal

The address offset of the top node of the instruction (valid values: 0 - 65535).

TopLen

The number of addresses the top node uses.

MidTyp

The address type of the middle node of the instruction (valid values: 0, 1, 3,
4, 8 for constants).

MidVal

The address offset of the middle node of the instruction (valid values: 0 65535).

MidLen

The number of addresses the middle node uses.

BotTyp

The address type of the bottom node of the instruction (valid values: 0, 1, 3,
4, 8 for constants).

BotVal

The address offset of the bottom node of the instruction (valid values: 0 65535).

BotLen

The number of addresses the bottom node uses.

UctrNum

Used only for UCTR instructions.

DctrNum

Used only for DCTR instructions.

Spare3

Spare parameter.

Note: All parameters must appear in the instruction subroutine declaration.

372 SPU 780 01EMAN May 2002

47

Working with Projects

Emulation Solve
File API Calls
API Call

Description

Power Flow Calls

Power flow calls are used to:
l Determine whether an instruction
should be solved (using
GetPowerFlow)
l To pass along powerflow to the next
cell (using SetPowerFlow)
l To activate an error condition (using
SetPowerFlow)
Power flow calls can be used to either
get or set a particular cell in logic.
Depending on the instruction being
solved, the row and col variables are
used to access a particular cell within
the 7 row x 11 column matrix.

GetPowerFlow(Network, Row, Col, PowerState)
SetPowerFlow(Network, Row, Col, 1)

Single Discrete State Calls
GetSingleDiscreteState(RefTyp, RefVal, State)
SetSingleDiscreteState(RefTyp, RefVal, 1)
Single Discrete History Calls
GetSingleDiscreteHistory(RefTyp, RefVal, History)
SetSingleDiscreteHistory(RefTyp, RefVal, State)
Single Discrete Disabled Calls
GetSingleDiscreteDisabled(RefTyp, RefVal, Disabled)
SetSingleDisabledState(RefTyp, RefVal, Disabled)

Single Register Data Calls
GetSingleRegisterData(RefTyp, RefVal, Data)
SetSingleRegisterData(RefTyp, RefVal, Data)
Group Discrete Calls
GetGroupDiscreteState(RefTyp, RefVal, NumGroups, State(), Disabled())
SetGroupDiscreteState(RefTyp, RefVal, NumGroups, State())
SetGroupDisabledState(RefTyp, RefVal, NumGroups, Disabled())

48

Single discrete state calls are used to
get or set the state of a 0xxxx or 1xxxx
address. The State will return with 0 for
Off or 1 for On. When calling the Set,
use either 0 for Off or 1 for On.
Single discrete history calls are used to
get or set the history of a 0xxxx or 1xxxx
address. The history will return with 0 for
Off or 1 for On. When calling the Set,
use either 0 for Off or 1 for On.
Single discrete disabled calls are used
to get or set the disabled status of a
0xxxx or 1xxxx address. The disabled
status will return with 0 for Enabled or 1
for Disabled. When calling the Set, use
either 0 for Enabled or 1 for Disabled.
Single register data calls are used to get
or set the data value of a 3xxxx or 4xxxx
address. Valid range for data is 0 to
65535.
Group discrete calls are similar to the
single calls except 16 discretes per
group are received or set at one time.
The arrays must contain data for as
many groups as are specified.

372 SPU 780 01EMAN May 2002

Working with Projects

API Call

Description

Group Register Calls

Group register calls are similar to the
single calls except that a group of
registers are received or set at one time.
The Data array must contain data for as
many groups as are specified.

GetGroupRegisterData(RefTyp, RefVal, NumGroups, Data())
SetGroupRegisterData(RefTyp, RefVal, NumGroups, Data())

372 SPU 780 01EMAN May 2002

49

Working with Projects

Emulation Solve
File Content
Example

ADD.ESF File Content Example:
Sub ADDINST (Network, Row, Col, TopTyp, TopVal, TopLen,
MidTyp, MidVal, MidLen, BotTyp, BotVal, BotLen, Spare1,
Spare2, Spare3)
dim State,TData,MData,Bdata
’is top input powered?
call LLEmulator.GetPowerFlow(Network,Row,Col-1,State)
If State<>0 then
’ get the value of top node
If (TopTyp=3) or (TopTyp=4) then
call LLEmulator.GetSingleRegisterData(TopTyp,TopVal,TData)
Else
TData=TopVal
End if
’get the value of middle node
If (MidTyp=3) or (MidTyp=4) then
call LLEmulator.GetSingleRegisterData(MidTyp,MidVal,MData)
Else
MData=MidVal
End if
BData=TData+Mdata
’overflow
If BData>9999 then
BData=BData-10000
call LLEmulator.SetPowerFlow(Network,Row,Col,1)
End if
’set value into bottom node
call LLEmulator.SetSingleRegisterData(BotTyp,BotVal,BData)
End if
End Sub

Note: Only emulation solve files for instructions currently not supported by the
Emulator are checked for by ProWORX 32. You cannot edit built-in instructions.

50

372 SPU 780 01EMAN May 2002

Working with Projects

Documentation Editor
Overview

The documentation editor, the defaulted bottom-left editor, allows you to see and
edit documentation for addresses and Traffic Cop items. It hot-tracks items that are
selected in the many of the editors, including the data watch window and traffic cop.
To open the documentation editor, select View → Documentation from the
ProWORX 32 menu
There are three sections of the documentation editor: Edit, Summary, and Traffic
Cop. To switch between sections, select the corresponding radio button at the top
of the documentation editor.

Opening the
Documentation
Editor Properties
Window

In the navigation tree:

372 SPU 780 01EMAN May 2002

Step

Action

1

Ensure the project folder is expanded and right-click the current project’s folder.

2

Select Properties from the right-click menu.

3

Select the Documentation tab in the properties window.

51

Working with Projects

Documentation
Editor Properties

52

These properties are found in the Properties window under the Documentation tab:
Property

To set:

Function

Total
Number of
Descriptor
Lines

In the Total Number of
Descriptor Lines box enter a
number between 3 and 9 or use
the arrow keys to increase or
decrease the number.

The descriptor field is a multi-line field that
can be set from 3 lines to 9 lines of
documentation. This preference forces the
editor to edit only the set number of lines of
the descriptor.

Number of
Visible
Descriptor
Lines

In the Number of Visible
Descriptor Lines box enter a
number between 1 and the Total
Number of Descriptor Lines
value or use the arrow keys to
increase or decrease the
number.

The descriptor field is a multi-line field that
can be set from 3 lines to 9 lines of
documentation. This preference forces the
editor to display only the number of lines of
the descriptor that are set.

Supported
Fields

In the Supported Fields frame, If a check box is unchecked, the
select the check boxes that you corresponding field will never be displayed.
want displayed.
If a check box is checked, the field will be
displayed as long as dependant properties
are set correctly.
E.g. If Symbols are disabled for the project,
the symbol field will not be displayed even
though the check box is checked.

372 SPU 780 01EMAN May 2002

Working with Projects

Using the Documentation Editor
Edit Mode
Overview

The edit mode is a completely customizable and editable visual representation of the
current project documentation. The edit mode hot-tracks items currently selected in
ProWORX 32 including instructions, I/O cards, and addresses in the Data Watch
Window.

Customizing the
Edit Mode Fields

In the documentation editor:

Using the Edit
Mode

To:

Function

Move a field

Click the field’s handle and drag it to the area of the
window that you would like the field moved to.

Resize a field

Click and drag the field’s handle.

Minimize or maximize a field

Click the field’s handle.

Enter an address into the Reference box to view the addresses documentation. To
navigate through documented addresses click the previous documented address
and next documented address
addresses click the previous address

Using the Singleline Mode

and next address

buttons.

The single-line documentation editor displays the currently selected address’
descriptors and is un-editable. To view the single-line documentation editor:
Step

Summary Mode
Overview

buttons. To navigate sequentially through

Action

1

Select the Display One Line Documentation Window check box in the
Properties dialog, Documentation tab. You can access the documentation
properties by select Properties from the Documentation Editor right-click menu

2

When viewing single-line documentation, to edit the current address, click Edit.

Summary mode shows the most common information for documented addresses.
Using the address type drop-down list box, select the type of address (Symbol, 0x,
1x, 3x, 4x, Xmem, or ‘All addresses’) you want to view. To edit the documentation of
any address, double-click on the appropriate row and the documentation editor will
switch to edit mode showing the selected address.

372 SPU 780 01EMAN May 2002

53

Working with Projects

Using the
Symbol Filter

When ‘Symbol’ has been selected in the address type drop-down list box, the Filter
box will be visible. The symbol filter is a simple query that filters the symbol summary
based on what criteria is entered into the filter. To view all symbols, leave the filter
empty and press ENTER.
The contents of the filter is the LIKE statement of an SQL SELECT statement.
Therefore, rules for entering text into the filter box are the same as composing an
SQL query. Some filter examples:

Traffic Cop Mode

54

Filter Text

Results

S*

All symbols that start with an ‘S’ are displayed.

*Switch

All symbols ending with ‘Switch’ are displayed.

[A-D]*

All symbols starting with ‘A’, ‘B’, ‘C’, or ‘D’ are displayed

*Switch*

All symbols with the letter sequence ‘Switch’ are displayed

Disk?

All symbols named ‘Disk(x)’ will be displayed. e.g. Disk1, Disk2, DiskA, etc.

Using the traffic cop editor, you can edit short comments for head, drop, rack and
slot addresses.

372 SPU 780 01EMAN May 2002

Working with Projects

Importing and Exporting ProWORX 32 Documentation
Overview

ProWORX 32 imports and exports database documentation in several formats. The
Documentation Import feature lets you bring documentation from existing files or
databases into ProWORX 32 without having to re-enter information. Documentation
Export lets you edit documentation in a separate word processing or spreadsheet
program.
Note: This function does not import controller logic.

Importing
Documentation

Exporting
Documentation

In the Project Navigation panel:
Step

Action

1

To append the documentation to the existing project documentation, select
Documentation Import → Append from the project right-click menu.

2

To merge or overlay the documentation with existing project documentation,
select Documentation Import → Overlay from the project right-click menu.

3

To delete all current documentation and import new documentation, select
Documentation Import → Create New from the project right-click menu.

4

Once you have selected the import type, select a file (.csv, .mdb, .doc, .xls) to
import from the Select Documentation File dialog and click Open.

In the Project Navigation panel:

372 SPU 780 01EMAN May 2002

Step

Action

1

From the project right-click menu, select Documentation Export. The Select
Destination File dialog appears.

2

Select a file type from the Save as type drop-down list box. (.csv, .mdb, .doc,
.xls)

3

Enter the export file name in the File name field.

4

Navigate to the folder where you want to save the exported file. Click Save.

55

Working with Projects

Import/Export
Formats

Import/Export format descriptions:
Format

Description

MS Word (.doc) Documentation is exported directly into an MS Word document. Each
address type is displayed on a separate table.
MS Excel (.xls)

Documentation is exported directly into an MS Excel Workbook. Each
address type is displayed on a separate MS Excel Worksheet. When
importing documentation, ProWORX 32 expects these sheets to be in the
same order with the same name.

MS Access
(.mdb)

Documentation is exported directly into an MS Access database. Each
address is in its own table.
Note: It is important that you do not move or rename fields within the
database if you are going to import your data.

.CSV File

The text file (.csv) is a comma-delimited file. This file can be edited using
any standard text editor (Notepad, Wordpad, etc.).
The comma-delimited line is different depending on the address type:
l 0xxxx/1xxxx - Address, Desc1, Desc2,...,Desc9, Short Comment
1,...,Short Comment 4, Symbol, ISA Symbol, Page Title, Long Comment
ID
l 3xxxx/4xxxx - Address, Desc1, Desc2,...,Desc9, Short Comment
1,...,Short Comment 4, Symbol
l 6xxxx/Networks/Segments - Address, Desc1, Desc2,...,Desc9, Short
Comment 1,...,Short Comment 4, Page Title, Long Comment ID
l Traffic Cop - Address (HxxDxxRxxSxxx), Desc1, Desc2,...,Desc9,
Short Comment 1,...,Short Comment 4

ProWORX
ASCII (.fil)

Files for exchanging data easily. By default, ProWORX 32 creates this type
of file for documentation.

ProWORX
Symbol (.fis)

Files for exchanging symbols.

Spreadsheet
Data
Interchange
Format (.dif)

ProWORX 32 creates standard .DIF files. Most spreadsheet programs can
import this format without difficulty. However, you must take special care
when transferring data to and from Microsoft Excel in .DIF files.

dBaseIV
ProWORX 32 creates standard .DBF files for use with Ashton-Tate’s data
Database (.dbf) management program dBaseIV. Most other data management and
spreadsheet programs (including Microsoft Excel) can read this format
without difficulty.

56

Traffic Cop
(.tef)

Importing a .TEF file overwrites the existing Traffic Cop data. Exporting
creates a .TEF file of the current Traffic Cop data. ProWORX 32 requires
both the .TEF and .DEF files to successfully import the documentation.

Concept (.txt)

When exporting, ProWORX 32 creates a .TXT file of the current descriptors
and symbols for 0x, 1x, 3x, 4x and symbols for constants to be used in
Concept.
372 SPU 780 01EMAN May 2002

Working with Projects

Note: In order to import and export using .doc (MS Word) and .xls (MS Excel) files,
you must have MS Word and/or MS Excel installed on your PC.

Note: Documentation files of type .fil, .fis, .dif, .dbf, .tef, and .txt are compatible
across these ProWORX applications: ProWORX NxT, ProWORXPLUS, and
ProWORX 32.

372 SPU 780 01EMAN May 2002

57

Working with Projects

Protected Registers
Overview

Ranges of output registers added to the Protected Registers table are protected.
Their data values are uneditable by users who do not have administative access to
ProWORX 32. To use registers in the protected registers table, ensure that the
Protected Registers check box is selected in the security settings. You can access
the security settings from the My Computer right-click menu in the Project
Navigation Panel.

Setting
Protected
Registers

Use the following steps to set protected registers:
Step
1

58

Action
From the project right-click menu in the project navigation panel, Select
Properties. The properties dialog appears.

2

In the Properties dialog, select the Protected Registers tab.

3

Enter 4xxxx addresses in the From and To fields.

4

Click Add to add the range of addresses to the Protected Registers table.

5

To delete a range of addresses from the Protected Registers table, select the
row to be deleted and then click Delete.

6

Click OK to save your changes and return to ProWORX 32.

372 SPU 780 01EMAN May 2002

Working with Projects

Using Search
Overview

The search dialog is used find, replace or go to addresses or symbols in ProWORX
32.

Using Find

From the ProWORX 32 menu:
Step

Using the Search
Panel

Action

1

Select Edit → Find (CTRL+F) to open the Search dialog.

2

Enter the value you want to search for in the Find What field.
Note: The value entered depends on the selection you make in the Search By
drop-down field. By default the value type is Address.

3

To search a specific area of the project or by a different value type, click
Advanced.

4

Select an area of ProWORX 32 from the Search drop-down box.

5

Select a value type to search by from the Search By drop-down box.

6

Click Find Next to complete a search. The search results are displayed in the
Search panel.

From the ProWORX 32 menu:

372 SPU 780 01EMAN May 2002

Step

Action

1

Select View → Search to open the search panel.

2

Select the tab of the area of ProWORX 32 that you want to go to.

3

Double-click the cell that contains the location of the address that you want to go
to.

4

To close the search panel, click the x in the top, right-hand corner.

59

Working with Projects

Address Used
Overview

The Address Used tables keep track of what addresses are used in logic, traffic cop,
peer cop and the I/O scanner. Each address has it’s own cell in the address used
grid.
The Used tables are updated every time an address is changed in one of the above
areas. The changes are reflected in the Used Table panel. The Used Tables are
useful for determining what addresses are used, how they are used and how many
times they are used. 0xxxx, 1xxxx, 3xxxx and 4xxxx address types are tracked. The
tables reflect the content of the currently selected project; switching projects
updates the used tables.
If the project is in online mode, there is a separate set of used tables for the online
device. This is due to the fact that the online device may have different contents than
the project database.

Using the
Address Used
Tables

Address Used
Display
Descriptions

60

From the ProWORX 32 menu:
Step

Action

1

Select View → Address Used to open the Address Used Tables.

2

To view an address type, select the corresponding tab. (0xxxx, 1xxxx, 3xxxx,
4xxxx.)

3

To select an address for logic, select the address from the used table and dragand-drop the address into the instruction that you want to use the address.

4

To show or hide the address used legend, click the Legend check box.

The Address Used table displays information as follows:
Display

Description

Top-left purple square

Address is used in logic.

Top-right blue square

Address is used in the traffic cop.

Bottom-left green square

Address is used in the Peer Cop.

Bottom-right yellow square

Address is used in the I/O Scanner.

An overlaid ‘C’

Coil is used in logic.

An overlaid ‘D’

Duplicate coil is used in logic.

372 SPU 780 01EMAN May 2002

Working with Projects

Finding a Free
Address

Rebuilding the
Address Used
Tables

In the Address Used window:
Step

Action

1

Select the tab of the address type that you want to find.

2

Click Find Free.

3

Enter an address where the search begins from in Start Address.

4

Enter the number of free addresses in a row that you need in Length.

5

Click Find to search for the free address(es). Click Close to exit the Find Free
section.

In the Address Used window:
Step
1

372 SPU 780 01EMAN May 2002

Action
To rebuild the address used tables, click Rebuild.
Note: If online, rebuilding requires a read from a PLC. The used tables are
unavailable while being rebuilt.

61

Working with Projects

The Knowledge Base
Overview

The Knowledge Base is a warehouse of accumulated process experience relating
to a specific project. It is used to identify solutions to problems that have occurred in
the past. It is also used to keep maintenance records of fixes.

Opening the
Knowledge Base

In the project navigation panel:
Step
1

Searching for
Keywords in the
Knowledge Base

Select Knowledge Base
.
Note: Each project has its own knowledge base, in other words, the knowledge
base is specific to the project.

After opening the knowledge base:
Step
1

62

Action

Action
Enter a word in the Keyword box.

2

Press Search. (All fields in the knowledge base are searched for the keyword.)

3

To find the next instance of the keyword, press the Search button again.
Note: You may also search for partial word matches.

372 SPU 780 01EMAN May 2002

Working with Projects

Adding a Record
to the Knowledge
Base

In the knowledge base utility:
Step
1

Deleting a
Record from the
Knowledge Base

Comment

Click Add.

The Knowledge Base Entry dialog will
pop up.

2

Enter a name into the Author box.

Max 55 characters.

3

Enter the problem description into the
Problem box.

Max 275 characters.

4

Enter the solution description into the
Solution box.

Max 440 characters.

5

Enter the name of an image that may
be associated with problem or solution
in the Image field.
The image name must be entered in
full including the file extension. e.g.
Image1.bmp is correct whereas
Image1 is not.

Valid image types are .bmp and .jpg.
The image must reside in
‘ProWORX\32\Projects\KBImages’.
Max image name length: 255
characters.

6

Click OK to save the record.

The Date and Time is added
automatically upon pressing OK.

In the knowledge base utility:
Step
1

Printing the
Knowledge Base

Action

Action

Comment

Click Delete.

The record that the cursor is highlighting
will be deleted.

In the knowledge base utility:
Step
1

372 SPU 780 01EMAN May 2002

Action
Click Print. The ProWORX 32 print setup appears. From here you can determine
specifically what you want to print.

63

Working with Projects

64

372 SPU 780 01EMAN May 2002

Communications Setup

Connecting to a Controller
Overview

ProWORX 32 can communicate with controllers in several ways. This chapter
explains how to configure ProWORX for several common types of network
connections. This chapter also describes how to select and attach to a controller,
both directly, and by scanning your entire network for devices.

What’s in this
Chapter?

This chapter contains the following topics:

372 SPU 780 01EMAN May 2002

Topic

Page

Communications Overview

66

Configuring Modbus Communications

67

Modbus Communications by Modem

68

Configuring Modbus Plus Communications

71

Configuring Ethernet Gateway Communications

72

Configuring TCP/IP Communications

73

Network Explorer

74

65

Communications Setup

Communications Overview
Overview

Before your computer can connect to a controller (or, for some systems, the gateway
which relays information to and from the controller), ProWORX 32 must be
configured for your communication system.
Note: To connect with each other, your computer and controller must be
configured for the same communication system with the same parameters.

Opening the
Communications
Setup Dialog

From the Project Navigator panel:
Step
1

Setting the
Default
Communications
Type

Editing
Communications
Parameters

Communicating
Using the Server

66

Action
Double-click the Communications icon in a project to open the communications
setup dialog.

In the Communications Setup dialog:
Step

Action

1

Select the tab of the communications you want to use.

2

Select the Set CommunicationsType as default communications check box.

In the Communications Setup dialog:
Step

Action

1

To edit a communications parameter, double-click the parameter, or, while the
parameter is selected, press Change Setting.

2

Make the desired changes in the Edit dialog and press OK to save changes.

In the Communications Setup dialog:
Step

Action

1

Ensure that you are logged on to the ProWORX Server.

2

To communicate with PLCs through the server’s communications portal, select
the Use Server to Communicate check box.

372 SPU 780 01EMAN May 2002

Communications Setup

Configuring Modbus Communications
Overview

Modicon’s master/slave protocol, standard on 984 and many other controllers.
Select this option if your computer is connected to a controller’s Modbus port, either
directly or through a modem.
Note: The controller must have the same Modbus settings as the computer. Set
Modbus parameters for your PLC with the Ports tab of the Controller Configuration
window or with its DIP switches.

Setting Modbus
Parameters

Select the Modbus tab and set the following communications parameters:
Parameter

Description

Modbus Address

The Modbus address of the PLC.

Port

Identifies which serial port on your PC is connected to the controller
or modem (if you are connecting to the controller through one).
Default is COM1.

Baud Rate

Sets the data transfer speed of your PC’s serial port in bits per
second. The PC and controller must be set to the same baud.
Default is 9600.

Parity

Adds a check bit to a packet to make the number of binary ones
always either odd (Odd parity) or even (Even parity). If parity is set
to None, the check bit is not added. The PC and controller must use
the same parity. Default is Even.

Stop Bits

Sets the number of bits at the end of a packet prepares the
receiving device for the next packet. The PC and controller must
use the same number of stop bits. Default is 1.

Data Mode

Identifies which data protocol (Remote Terminal Unit or ASCII) to
use. Both the PC and controller must use the same data protocol.
Default is RTU.

Timeout

Specifies the length of time the PC will wait for successful
communication with a controller before displaying an error
message. Default is 3 seconds.

Modem Type

If your computer is connected directly to the controller, set the
Modem Type to None. If your computer is directed to the controller
through a modem it must be configured. See Modbus
Communications by Modem.

When you have finished configuring the parameters, press OK.

372 SPU 780 01EMAN May 2002

67

Communications Setup

Modbus Communications by Modem
Overview

Controllers in remote locations can be equipped with RS-232 modems. Your
computer can then connect to the controller (by telephone, radio, or microwave
systems) using its own modem. Once the connection is established, the computer
and controller behave as if they were connected directly through a Modbus network.
You can easily configure ProWORX 32 to connect to controllers through dial-up and
dedicated-line modems. Before you begin, confirm that:

l The controller is properly connected to its RS-232 modem.
l Your computer is properly connected to its modem.
l The modems’ DIP switches, if they have them, are set like this:
DIP Switch Settings:
Modem DIP Switch Setting

Example: US Robotics Modem DIP
Switches (seen from back)

Data Terminal Ready Always On

Switch 1 (on left): Down

Verbal Word Results

Switch 2: Up

Result Code Display Enabled

Switch 3: Down

Command mode local echo

Switch 4: Up

Auto Answer

Switch 5: Up

Carrier Detect Normal

Switch 6: Up

Load Non-Volatile RAM Defaults

Switch 7: Up

Use AT Command Set (Smart Mode)

Switch 8 (on right): Down

After configuring ProWORX 32 to use a modem, it checks to see whether there is
an active connection each time you select a device on your network.

l If it cannot find one, ProWORX 32 asks you for a phone number to dial or, if your
modem uses a dedicated line, opens a connection automatically.

l If it finds a connection (or after opening one), you can choose to select a Modbus
device or close the connection and open a new one.
Use a modem connection to a controller just like a direct Modbus link. You can scan
for and attach to Modbus devices (and Modbus Plus devices, if the controller
supports Bridge Mode to allow you to connect to a Modbus Plus network) just as you
normally would.

68

372 SPU 780 01EMAN May 2002

Communications Setup

Setting the
Modbus Modem
Parameters

In the Communications Setup dialog:
Step

Action

1

Select the Modbus tab and set the communications parameters (see
Configuring Modbus Communications for parameter descriptions).

2

The controller must have the same Modbus settings as the computer. Set
Modbus parameters for your PLC with the Ports tab of the Controller
Configuration window.

3

Set the Port parameter to show the computer port connected to the modem;
otherwise, ProWORX 32 won’t be able to locate it.

4

The Modbus configuration must send exactly 10 bits per data package to your
modem. (See Modbus 10-bit Configurations below.)
Modems generally expect 10 bits in a data package; however, the Modbus
defaults (Even parity, RTU mode, and one stop bit) send 11 bits per package.
Change the Modbus settings to provide 10 bits per data package or ProWORX
32 will not be able to communicate with the modem. Alternatively, if your modem
supports large data packages, you can set its DIP switches to allow 11 bits per
data package (see your modem’s manual).

Modbus 10-bit
Configurations

5

Select the type of modem from the Modem Type parameter drop-down. (See
Modem Type Descriptions below.)

6

To edit the modem parameters, click Modem Setup. The Modem Configuration
dialog appears. (For parameter descriptions, see below.)

These Modbus configurations provide 10 bits per data package:
Parameters

ASCII Mode

RTU Mode

Start Bit

1 bit

1 bit

1 bit

Data

7 bits

7 bits

8 bits

Stop Bits: 1

1 bit

Stop Bits: 2

1 bit
2 bits

Parity: None

372 SPU 780 01EMAN May 2002

ASCII Mode

Parity: Odd or Even

1 bit

Total

10 bits

0 bits

0 bits

10 bits

10 bits

69

Communications Setup

Modem Type
Descriptions

Modbus Modem
Parameter
Descriptions

Modem Type specifies the kind of modem connected to your computer:
Modem Type

Description

None (Default)

For direct Modbus connections between the PC and controller without a
modem. This setting disables the other modem options.

Dial-Up

For standard modems which do not require a password. If you are
unsure, try this setting first. When you select a device, ProWORX 32
asks you for a number to dial.

Dial-Chat

For password-protected modems. After the connection is established, a
terminal window opens so you can enter text. When you select a device,
ProWORX 32 asks you for a number to dial.

Line/J478

For modems with a dedicated telephone line to the controller. You do
not have to type a number to dial. This setting disables the other modem
options.

LineRTS

For radio or microwave modems with a dedicated link to the controller.
You don’t have to type a number to dial. This setting disables the other
modem options.

Set the following Modem parameters:
Parameter

Description

Phone Number

The phone number of the modem that the PLC is attached to.

Initialization

Some modems require special initialization commands such as
ATZ before they can be used. Type a sequence of Hayes
modem commands in this field for ProWORX 32 to send to your
modem. Check your modem’s manual for the commands to turn
off error correction, compression, and software flow control and
turn on verbal word results.

Dial Command

Type ATDT for tone dialing (default) or ATD for pulse dialing.
This prefix is sent to the modem along with the phone number
you type in the Select Device dialog. To instruct the modem to
pause for half a second, type a comma (,).

Command Suffix

Characters appended to every command you send to the
modem, including the Initialization string and Hangup command.
The default is a carriage return and a line feed.

Hangup Command

To hang up your modem, ProWORX 32 sends the standard
Hayes modem command ATH. If your modem uses a different
command, enter it here. This command is prefixed with ,,,+++,,,.
Hanging up can take up to three seconds.

When you have finished configuring the parameters, press OK.

70

372 SPU 780 01EMAN May 2002

Communications Setup

Configuring Modbus Plus Communications
Overview

Modicon’s fast peer-to-peer protocol, standard on many 984 and other controllers.
Select this option if your computer is connected to a Modbus Plus network through
a network adapter card such as an SA85.

Setting Modbus
Plus Parameters

Select the Modbus Plus tab and set the following communications parameters:
Parameter

Description

Modbus Plus Address The Modbus Plus address of the PLC.
Adapter

Sets an identifying number for an SA85 Network Card. Up to two
SA85 cards, numbered 0 or 1, can be installed. A card’s identifying
number in ProWORX 32 must be the same as in the Device
command in the PC’s CONFIG.SYS file. Default is 0.

Timeout

Specifies the length of time the PC will wait for successful
communication with a controller before displaying an error message.
Default is 3 seconds.

When you have finished configuring the parameters, press OK.

372 SPU 780 01EMAN May 2002

71

Communications Setup

Configuring Ethernet Gateway Communications
Overview

A gateway connects two networks that would not normally be able to communicate
with each other. ProWORX 32 supports Modicon’s EMBP Gateway, which bridges
your computer’s TCP/IP Ethernet to the controller’s Modbus Plus network.
Note: Your computer’s Ethernet address is set in Windows by your network
administrator (as is its sub-network mask address, if necessary).

Setting Ethernet
Gateway
Parameters

Select the Gateway tab and set the following communications parameters:
Parameter

Description

Gateway Type

Select a Gateway type (SGATE, NR&D MEB, GATEWAY?)
to use TCP/IP to communicate with a computer which then
communicates with the PLC.

Modbus Plus Address

The Modbus Plus address of the PLC.

IP Address

The TCP/IP address of the computer linking your PC’s
Ethernet to your controller’s Modbus Plus network.

Timeout

Specifies the length of time the PC will wait for successful
communication with a controller before displaying an error
message. Default is 3 seconds.

When you have finished configuring the parameters, press OK.

72

372 SPU 780 01EMAN May 2002

Communications Setup

Configuring TCP/IP Communications
Overview

Some controllers can be equipped with TCP/IP cards. Select this option if both your
computer and controller use TCP/IP networking, regardless of whether they are on
the same network or are connected by a gateway.
Note: Your PC’s TCP/IP address is set in Windows by your network administrator
(as are the gateway and sub-network mask addresses, if necessary).

Setting TCP/IP
Parameters

Select the TCP/IP tab and set the following communications parameters:
Parameter

Description

IP Address

Enter a controller address in standard TCP/IP format: four numbers ranging
from 0 to 255 separated by periods (for example, 10.0.254.68 is valid).

Timeout

Enter a value that specifies the length of time the PC will wait for successful
communication with a controller before displaying an error message. Default
is 3 seconds.

Note: You must install the TCP/IP Configuration Extension into your controllers to
set TCP/IP addresses for their communication cards. For more information, see the
TCP/IP Extension, p. 125.
When you have finished configuring the parameters, press OK.

372 SPU 780 01EMAN May 2002

73

Communications Setup

Network Explorer
Overview

The Network Explorer finds controllers, bridges, bridge multiplexers, and other
devices attached to networks. ProWORX 32 displays the devices it finds by their
address number and also shows their type, mode, and status.
The results of a network scan are displayed in the panel tree on the left of the
display. If any PLCs are found, they are displayed on the right panel. The right panel
has two different views, the graphical, and the list view. The graphical view displays
a picture of the series of controller found, along with all of its data. The list view
displays the data in a spreadsheet format.

Using the
Network
Explorer

To access the network explorer:
Step
1

From the utilities menu in the project navigation, select Network Explorer. The
communications editor is launched. You can also access the Network Explorer
from the communications editor by clicking Network Explorer at the bottom right
of any of the communication type’s tab.

2

Select the default communications type in the Communications Overview, p. 66.
Click OK if you have opened the Explorer through the Utilities menu, or click
Network Explorer if you are running the Network Explorer from the
communications editor.

3

To return to the communications editor at any time, click Communications
Setup.

4

To switch between views, select either the Graphical View radio button or the
List View radio button.

5

74

Action

The following information is provided for each controller found:
Project Name - In certain controllers, you can save the project name inside of
a loadable. The project name will be retrieved if the controller is running and
the loadable is in logic.
l Controller Address
l Controller Type
l Current State of the Controller: Running, Optimized, Stopped (the Stopcode
is displayed). For more information, see Stopcode Error Analysis, p. 277.
l Current State of the Battery on the Controller: Good or Bad.
l Current State of the Memory Protect Switch of the Controller: On or Off.

l

372 SPU 780 01EMAN May 2002

Configuring a Controller

Controller Configuration
Overview

The Configuration editor is used to edit and view the current controller configuration
of the project. The configuration editor displays configuration options (properties)
within several tabs. Each tab contains one or more property lists used to display and/
or edit items relating to controller configuration. Properties that are displayed
depend on the controller that is being configured.

What’s in this
Chapter?

This chapter contains the following topics:

372 SPU 780 01EMAN May 2002

Topic

Page

Controller Configuration

76

‘General’ Tab

77

‘Ports’ Tab

80

‘Loadables’ Tab

83

Loadable Library Wizard

86

75

Configuring a Controller

Controller Configuration
Overview

Before you begin, use the Creating a New Project, p. 29 to select the right type of
controller. The options that appear in the configuration editor depend on the
controller type, so if the wrong one is selected, you can spend time configuring
options your controller does not support.

Configuring a
Controller

From the project navigation panel:
Step
1
2

76

Action
Click the Configuration icon
Click the tab for the options you want to configure:
General - Configures a controller’s memory, including the number of coils
and registers, I/O cards and drops, the amount of memory set aside for
Configuration Extensions, and the number and size of the ASCII messages
you want to use.
l Ports - Configures the controller’s serial and ASCII ports.
l Loadables - Extensions to a controller's capabilities. When they appear as
instructions (most of the time) they are represented as 3 node instructions.

l

3

Update parameters by clicking on the parameter row. Press ENTER to accept
the changes or ESC to decline the changes.

4

The changes made will be saved to the project or controller when the
configuration editor is closed. A prompt is displayed allowing you to confirm that
you want to save changes.

372 SPU 780 01EMAN May 2002

Configuring a Controller

‘General’ Tab
Overview

This tab in the Controller Configuration window allows you to configure a controller’s
memory. It contains many important options, including the number of coils, registers,
segments of logic, and I/O cards the controller will use, the amount of memory it sets
aside for configuration extensions, and the number and size of its ASCII messages.

General Tab
Parameters

The following parameters are editable:
Parameter

Description

Registers

For each of the 0xxxx, 1xxxx, 3xxxx, and 4xxxx register fields, type the
number of registers the controller will use. The controller polls all of these
registers each scan, so to keep your controller scanning quickly, set up only
as many registers as you need.

Segments

Type the number of logic segments the controller will use.

I/O Drops

Different controllers use different I/O drops:
l If you have a controller that uses Channels instead of I/O Drops, type the
number of channels the controller I/O will use. Channels always come in
pairs, so this must be an even number.
l If you have a Micro series controller in parent mode, type the number of
children (0 to 4) associated with it.
l If you have a Micro series controller in child mode, type the Child ID (1 to
4).

I/O Words

Quantum, Atrium, 785E_LMS, Momentum, Compact (E258, E265, E275,
E258) controllers only: type the maximum number of I/O words that will be
available for programming in the Traffic Cop. Check your controller
documentation for the appropriate values.

DCP Drop ID

680, 685, 685E, 780, 785, 785E or 785L controllers only: If another computer
uses this controller for distributed control, type the controller’s Distributed
Control Processor ID number (0 to 32).

I/O Time Slice Type the amount of time the controller will devote to peripheral port
communication, from 1 to 100 milliseconds. The default is 10 ms for 984A,
B, and X controllers and 20 ms for Quantum controllers.
Duplicate Coil
Start

Set the starting address to a non-zero value to enable the duplicate coil
range (i.e. allow coil addresses within this range to be assigned to more than
1 coil).
Set the range to 0 disable the duplicate coil address range. The starting
address of the duplicate coil range is part of the configuration and defines
the entire range of coils that will be treated as duplicate coils. The range is
from the starting address to the configured number of coils. Therefore to
enable the entire range of coils, set the starting address to 1.

372 SPU 780 01EMAN May 2002

77

Configuring a Controller

Parameter

Description

Remote
Channels

984A-S901, 984B-S901, and 584 controllers only: Select from 2 to 32
remote I/O channels. Channels always come in pairs, so this setting must be
an even number.

Total
Messages

Controllers that support ASCII messaging only: Type the total number of
ASCII messages the controller will use.

Message
Words

Controllers that support ASCII messaging only: Type the length (in machine
words) of your controller’s ASCII messages. One machine word is equal to
two ASCII characters.

ASCII Ports

Type the number of ASCII ports on the controller. This setting must be an
even number.

B984
Controller

Select the type of B984 controller you have: B884 or B886.

Input Latched

Select this option if you want the controller to freeze the input state on powerdown. Inputs remain frozen for one scan when the controller is powered
back up.

Settling Time

78

Group Settling Time allows you to set parameters for input digital filtering.
Each input value is polled through a filter based on a time window. You
can set the duration of the time window between 200 microseconds and
19.8 ms (in 200 microsecond increments).
l The module samples each input every 200 microseconds and uses the
time window associated with the input to determine the input state. If the
scanned input state is OFF, the input state is set OFF. If the scanned
input state is ON, the input state is set based on a history queue. If the
input was ON one time window ago, the input is set ON; if the input was
OFF, the input state is set OFF.
l The inputs are divided into four groups. The Settling Time of each can be
configured separately:
l Group 1: Inputs 1-4
l Group 2: Inputs 5-8
l Group 3: Inputs 9-12
l Group 4: Inputs 13-16

l

Battery Coil

Type the control address for the controller’s battery.

Timer
Register

Type the register offset used to store the controller’s timer value.

Time of Day
Clock

Type the register offset used to store the controller’s clock value. For more
information see Hardware Clock, p. 152.

Watch Dog
Timer

Type the time-out delay for the Watch Dog Timer, in tens of milliseconds.
The controller adds 250 ms to the value you enter. The default is 0000, which
represents 250 ms.

372 SPU 780 01EMAN May 2002

Configuring a Controller

Parameter

Description

Configuration
Extension
Used

Displays the amount of config extension space used. This field is not
editable.

Configuration
Extension
Size

Type the amount of memory (in machine words) to be set aside for
Configuration Extensions. Use the following information to calculate the
minimum Configuration Extension size:
l Configuration Overhead: 1 word
l Extension Overhead:
l TCP/IP: 100 words. For M1E Controllers: 20 Words.
l Data Protect: 8 words
l S980 Address: 8 words
l Quantum Hot Standby: 17 words
l VME Bus: 9 words
l Profibus: Approximately 4096 words; check your Profibus manual for
details
l Peer Cop: 5 words
Links: 3 words per link, plus:
-) Global Output: 4 words per link
-) Global Input: 2 words overhead plus, for each of up to 64 devices,
1 + twice the number of up to 8 sub-entries (max. 8). The maximum is
2 + (64*(1+2*8)) = 1090 words.
-) Specific Output: 2 words overhead plus 2 words for each of up to 64
devices. The maximum is 2+(2*64) = 130 words.
-) Specific Input: 2 words overhead plus 2 words for each of up to 64
devices. The maximum is 2+(2*64) = 130 words.
l SY/MAX: 52 words
l I/O Scanner: 4 M1E controllers; 10 words of overhead; 40 words of
overhead for anything other than M1E’s; 12 words/transaction.

372 SPU 780 01EMAN May 2002

Skips

Select this option to enable skips (segments can be skipped during solves).

Bridge Mode

Select True to enable Bridge Mode. Some controllers support Bridge Mode,
which allows you to connect to a Modbus Plus network through their Modbus
ports 1.
Note: To use Bridge Mode, your controller’s MEM/DIP switch must be in the
MEM position.

79

Configuring a Controller

‘Ports’ Tab
Overview

From this tab in the Controller Configuration window, you configure the controller’s
Modbus and ASCII ports. These settings do not affect the communications setup of
your PC in any way - only the controller’s.

Modbus Ports

The following parameters are editable:
Parameter

Description

Mode

Identifies which data protocol (Remote Terminal Unit or ASCII) to use.
Both the PC and controller must use the same data protocol. Default
is RTU.
If you select ASCII protocol for a port, you can only configure its Parity,
Stop/Data bits, and Baud settings.

Parity

Adds a check bit to a packet to make the number of binary ones always
either odd (Odd Parity) or even (Even Parity). If parity is set to None,
the check bit is not added. The PC and controller must use the same
parity. Default is Even.

Stop/Data

Sets the number of bits at the end of a packet which prepare the
receiving device for the next packet. The PC and controller must use
the same number of stop bits. Default is 1.

Baud

Sets the data transfer speed of the controller’s Modbus port in bits per
second. The PC and controller must be set to the same baud rate.
Default is 9600.

Head

Quantum controllers only: sets the slot number on the local drop
backplane where the CPU resides.

Dev Addr

Assigns the Modbus address for the port. Default is 1.

Delay

Sets the amount of time in tens of milliseconds the controller waits
after receiving a message before sending an acknowledgment.
Default is 1 (10); max. is 20 (200).

Modbus Port 2 Type Momentum M1 controllers only: Sets the port type of Modbus Port 2,
to either RS232 or RS485.

80

372 SPU 780 01EMAN May 2002

Configuring a Controller

Simple ASCII
Ports

Some Modicon controllers have RS-232 ports as part of Remote I/O drops.
Advanced programmers can use these ports (called simple ASCII or ASCII/DAP
ports), for serial communications between controllers and data terminal equipment.
In ladder logic, use the Block Move (BLKM) instruction to send and receive Simple
ASCII messages. Configure the number of ASCII ports for a controller by setting the
ASCII Ports parameter in the General tab.
The 984A, 984B, and Micro 311, 411, 512, 612 controllers have simple ASCII ports
having fewer properties than Modbus ports:

372 SPU 780 01EMAN May 2002

Parameters

Description

Parity

Adds a check bit to a packet to make the number of binary ones always
either odd (Odd Parity) or even (Even Parity). If parity is set to None,
the check bit is not added. The PC and controller must use the same
parity setting. Default is even.

Stop/Data

Sets the number of bits at the end of a packet which prepare the
receiving device for the next packet. The PC and controller must use
the same number of stop bits. Default is 1.

Baud

Sets the data transfer speed of the controller’s Modbus port in bits per
second. The PC and controller must be set to the same baud. Default
is 9600.

81

Configuring a Controller

ASCII Ports

This table allows the user to set each port to be compatible with the device to which
it is being connected.
There are five properties that can be set:
Property

Micro Ports

82

Description

Parity

Select EVEN, ODD, or NONE.

Baud Rate

The communication speed is set to one of the following
baud rates: 50, 75, 110, 134.5, 150, 300, 600, 1200,
1800, 2000, 2400, 3600, 4800, 7200, 9600, and 19200.

Number of Stop Bits

Select the number of stop bits for each data byte (1 or 2).
A system with NO PARITY generally uses 2 stop bits,
while a system with PARITY uses 1 stop bit.

Number of Data Bits

Select the number of data bits issued from the ASCII port
(a number from 5 to 8). The choice of 7 data bits is
standard for most ASCII devices.

Keyboard/Non-Keyboard

Select the attached device is defined as a keyboard or
non-keyboard device. The purpose of this function is to
allow you to modify the response of the ASCII port to
match the type of device to which it is connected. In the
keyboard mode, the port echoes back the input character
and requires delimiters to move to the next data field and
to terminate the message. Editing of input data is
possible from a terminal. In the non-keyboard mode, no
data is echoed back and, as a data field is completed, the
next available data field is entered or the message
automatically terminates. No editing capabilities are
supported.

If you are using a Micro 311, 411, 512, or 612 controller, assign it’s ports using the
Micro port drop-down menu. The assignments in the list are combinations of the
controller’s COM1, COM2, and I/O Expansion Link port. The assignments availabledepend on which Micro I/O Mode you set in the Controller Details section of the
General tab in the Controller Configuration editor.

372 SPU 780 01EMAN May 2002

Configuring a Controller

‘Loadables’ Tab
Overview

User loadables are instructions that do not come with a controller. Instead, they are
supplied by Modicon or third-party vendors and must be copied into a controller or
project to be used.
Loadables are extensions to a controller’s capabilities. When they appear as logic
function blocks (most of the time) they are represented as three node instructions.
The Loadables tab displays the loadables selected and available to be selected for
the current project.
The display shows a table of loadables and related information. A check mark is
shown beside loadables that are present in the project. Loadables with no check
mark are present in the loadable library, but are not currently available in the project.
To add or delete a loadable from a project, select or de-select the associated
checkbox.
Note: You can only add loadables that are already part of a loadable library. Using
a loadable is a two-step process: transferring it into a loadable library (see the
Loadable Library Wizard, p. 86), then selecting it from the library into the controller
or project by checking the loadables’ checkbox in the loadables tab and saving
changes.

Loadable
Parameter

Loadable’s parameter listing:

372 SPU 780 01EMAN May 2002

Parameter

Description

Name

User loadable name.

Opcode

A unique two-digit hexadecimal number used to identify an instruction in the
programmable controller logic.

Version

The version number of the installed loadable.

Type

Either MSL or USL.

83

Configuring a Controller

Updating
Loadables
Overview

Here are two possible scenarios that would require you to update a loadable:

l Periodically, new versions of loadables are made available. If you try to delete an
old loadable from the configuration, the configurator alerts you to the fact that it
is already used in logic and prevents the loadables’ deletion. As adding or
readding a loadable can be an extensive task, update loadable conveniently
allows you to replace a loadable without first deleting it from logic.
l You may have read a controller’s data into a project where the controller data
contained an .MSL loadable (i.e. an .EXE file from Schneider Electric or a third
party vendor). If the controller had been run prior to performing the read, the MSL
loadable in the project is unusable if written back to the controller. Use update
loadable to get the MSL loadable back to a state where it can be written to the
controller. Update loadable asks you for the original .EXE loadable. It places it
into the project and the project may then be rewritten successfully to the
controller.

Updating
Loadables

To update a loadable in a project:
Step
1

Copying a
Loadable to a
Controller

84

Action
Select Update from the right-click menu on the row of the loadable that you want
to update.

To copy a loadable to a controller or project:
Step

Action

1

Select the loadable’s checkbox. The Select Opcode dialog appears if no
Opcode has been set for the loadable.

2

Select an available Opcode from the list and click OK.

3

If you are offline, selected (checked) loadables are included in the project. Any
new loadables you check off will be added to the project when the configuration
changes are saved. To use the loadables in a controller, write to the controller.
See Writing to a Controller, p. 92 for more information.

4

If you are in online mode, changes are not made to the current project. If you add
loadables and close the configurator while online, the Configurator makes the
changes directly to the controller. (Note: The controller must be stopped.)

5

If you are in online combined mode any changes that you save are saved to the
current project and then written to the controller. (Note: The controller must be
stopped.)

372 SPU 780 01EMAN May 2002

Configuring a Controller

Deleting
Loadables

To delete a loadable from a controller or project:
Step
1

372 SPU 780 01EMAN May 2002

Action
To delete a loadable from a project or controller, deselect the loadable’s
checkbox.
Note: You cannot delete a loadable if it is used in logic.

85

Configuring a Controller

Loadable Library Wizard
Overview

Before you can place a user loadable into a controller or project, it must be read into
the loadable library. A loadable library holds a set of loadables for you so that you
only have to translate them to ProWORX 32 format once.
In the Loadable Library, you can read a loadable from disk, translate it to ProWORX
32 format, and move it into a library. You can read loadables from an existing project,
a Schneider Electric (.exe or .dat) or third party disk (.exe or .dat) or a ProWORX
.TLD library file.
Note: Reading a user loadable into a loadable library does not copy it into your
controller or project. Using a loadable is a two-step process: reading it into a
loadable library, then from the library into the controller or project (see ‘Loadables’
Tab, p. 83 for more information).

Note: You are unable to open the loadable library wizard while the controller
configuration editor is open.

Using the
Loadable Library

From the Navigation Panel, Utilities tab:
Step
1
2

3

86

Action
Select Loadable Library to open the Loadable Library Wizard.
Select one of the following options:
Edit Opcode - See Editing Opcodes below.
View Text - Displays the manufacturer’s notes for a loadable (if available).
Rebuild Library - On rare occasions, a library of loadables can become
damaged (for example, when a computer crashes and files are corrupted).
ProWORX 32 allows you to recreate a library from its .USL and .MSL files.
l Transfer Loadable into Loadable Library - Transfer loadables from a
project, an old ProWORX.tld file, Schneider Electric (.dat), or from within an
.exe into the loadables library. Also use this option to update the version of
existing loadables in the loadable library.

l
l
l

When you have completed using the loadable library wizard, click Finish.

372 SPU 780 01EMAN May 2002

Configuring a Controller

Editing Opcodes

An opcode is a unique number identifying a loadable in the controller or project.
Because each opcode must be different, they may need changing.
When a loadable is added to a project or controller, the configurator will compare the
new loadable’s opcode with the opcodes already used in the controller by built-in
instructions and previously loaded loadables. If it sees that the new loadable opcode
will conflict, the Select Opcode window appears.
However, if you happen to know an opcode that won’t conflict with the loadables
already in your controller you can use the Edit Opcode option in the wizard to make
the change. Then when you add the loadable in configuration, you won’t be
prompted to provide a new opcode.

372 SPU 780 01EMAN May 2002

87

Configuring a Controller

88

372 SPU 780 01EMAN May 2002

Working with Controllers

At a Glance
Overview

This chapter contains information on how to use ProWORX 32 to work with a
controller.

What’s in this
Chapter?

This chapter contains the following topics:
Topic

90

Reading From a Controller

91

Writing to a Controller

92

Transferring Memory Contents to Controller EEPROM

94

Transferring the Flash RAM Executive

95

Transferring Memory Contents to Micro Flash RAM

96

Transferring Internal Flash or PCMCIA to Controller Flash

97

Starting and Stopping Controllers

98

PLC Status Viewer

99

Analyze Device

372 SPU 780 01EMAN May 2002

Page

Initializing Logic in a Controller

100

89

Working with Controllers

Initializing Logic in a Controller
Overview

Initializing logic erases the networks, register contents and ASCII messages in a
programmable controller. The controller must be stopped before you can initialize
logic.
It is strongly recommended that you read the contents of the controller to a backup
database before initializing logic.
WARNING
Ensure data integrity is maintained.
You are about to erase the contents of your controller. If you want to
save any information stored in the controller, ensure that its contents
have been read to a database.
Failure to follow this precaution can result in severe injury or
equipment damage.

Initializing Logic

From the project right click menu:
Step
1

90

Action
Select Online Commands → Init Logic.

372 SPU 780 01EMAN May 2002

Working with Controllers

Reading From a Controller
Overview

The Read from Controller function transfers memory contents from a programmable
controller into a designated database. It is strongly recommended that you use this
function to backup the contents of a controller before working with it online.

Reading From a
Controller

From the project navigation panel:

372 SPU 780 01EMAN May 2002

Step

Action

1

Select the project you want to read to.

2

Ensure that you have selected the correct controller to read from and that the
project you are reading into is backed up if necessary. Also, check the
communications settings for the correct address.

3

From the project right click menu, select Online Commands → Read → Read
to read the logic, traffic cop, configuration, loadables, ASCII, state and disabled
tables.

4

Or, from the project right click menu, select Online Commands → Read →
Read Extended Memory to read only the extended memory registers.

5

You are prompted to confirm that you want to read the selected controller. Click
OK to perform the read.

6

When the read is complete, click OK to return to ProWORX 32.

91

Working with Controllers

Writing to a Controller
Overview

92

The Write to Controller function writes the contents of a database to a controller. The
controller must be stopped before you can write to it.

372 SPU 780 01EMAN May 2002

Working with Controllers

Writing to a
Controller

From the project navigation panel:
Step

Action

1

Select the project you want to write from.

2

Ensure that you have selected the correct controller to write to and that the
controller you are writing to is backed up if necessary. Also, check the
communications settings for the correct address.

3

From the project right click menu, select Online Commands → Write → Write
All to write the logic, traffic cop, configuration, loadables, ASCII, state, and
disabled tables. This command overwrites all existing PLC data.

4

Or, from the project right click menu, select Online Commands → Write →
Relocate Logic and Data to write the contents of the controller as long as
addresses and function blocks in logic are supported in the destination controller.
You can choose to update either the Logic, Coils Used, ASCII, and State/
Disabled tables, or just the Logic and Coils Used.

5

Or, from the project right click menu, select Online Commands → Write →
Write Extended Memory to write only the extended memory registers. Select all
extended memory files or a specific extended memory file and click OK.

6

ProWORX 32 checks to ensure that the controller and database match and the
results are stated in the Database/Controller Validation dialog. If the controller
and database match click Write or Relocate to carry out the desired function.
Potential reasons that the controller and database would not match include:
l The controller being written to may not have enough memory for the logic
being written.
l The controller address ranges many not be large enough
l The controller instruction set many not match the database
l The database may use duplicate coils, which most controllers do not support

7

When the write is complete, click OK to return to ProWORX 32.

CAUTION
Process Cancellation Warning
Cancelling a write while in operation may leave your PLC in an
indeterminate state.
Failure to follow this precaution can result in injury or equipment
damage.

372 SPU 780 01EMAN May 2002

93

Working with Controllers

Transferring Memory Contents to Controller EEPROM
Overview

This function works only with Compact controllers. This function cannot be
performed while the controller is running. You must stop the controller first.
Note: Do not attempt the transfer operation if the controller’s battery is LOW as the
processor contents may be lost.
Tip: Memory Protect is a switch on your controller that stops you from altering the
controller’s contents. The Memory Protect switch should be ON or the card
overwrites memory on power up.

Transferring
Controller
Memory to
EEPROM

94

From the project right-click menu in the navigation panel:
Step

Action

1

Select Online Commands → Write → Transferring to Flash/EEPROM/
PCMCIA.

2

A-series Compact controllers have four enhanced EEPROM options which may
be set prior to transferring:
l After power down, restore PLC to previous Run/Stop state.
l Start PLC after download from EEPROM.
l Save 4xxxx registers to EEPROM.
l Optimized Mode - When selected, the controller can’t be edited while online.

3

Click Transfer. You are prompted to stop the controller if it is running.

372 SPU 780 01EMAN May 2002

Working with Controllers

Transferring the Flash RAM Executive
Using
EXECLoader

To transfer the flash RAM executive, read a controller’s flash RAM executive into a
disk file, or write a device’s flash RAM executive from a disk file, use the third-party
EXECLoader application. The EXECLoader is a Windows based 32-bit program that
allows you to update the executive firmware in a variety of Schneider Electric PLC
modules.
Step
1

372 SPU 780 01EMAN May 2002

Action
To open EXECLoader, select EXECLoader from the Project Navigation panel,
Utilities tab.

95

Working with Controllers

Transferring Memory Contents to Micro Flash RAM
Overview

This function works only with Micro controllers. This function copies the memory
contents of a Micro controller to the controller’s flash RAM.
When the Micro controller receives power, it first checks to see if a valid
configuration is present in the data memory. If not, the contents of the flash RAM are
re-loaded into the controller memory.
Flash RAM may be used as an alternative to the optional battery backup, or as an
extra backup of the logic and configuration.

Transferring to
Micro Controller
Flash RAM

96

From the project right-click menu in the navigation panel:
Step

Action

1

Select Online Commands → Write → Transferring to Flash/EEPROM/
PCMCIA.

2

Click Transfer. You are asked whether or not you want ProWORX 32 to start the
controller after loading to Flash RAM.
Click Yes to have ProWORX 32 automatically start the controller after
transferring memory contents to Flash RAM.
Click No to keep the controller stopped after transferring memory contents to
Flash RAM.

3

If the controller is currently running, you are prompted to stop it. You must do so
to continue.

372 SPU 780 01EMAN May 2002

Working with Controllers

Transferring Internal Flash or PCMCIA to Controller Flash
Overview

This function copies the memory contents of a Compact TSX, Quantum 434, or
Quantum 534 controller to the controller’s flash RAM or PCMCIA memory card.
Note: Do not attempt the transfer operation if the controller’s battery is LOW as the
processor contents may be lost.
When the controller receives power, it first checks to see if a valid configuration is
present in the data memory. If not, the contents of the flash RAM or PCMCIA
memory card are re-loaded into the controller memory.
Flash RAM or PCMCIA memory card may be used as an alternative to the optional
battery backup or an extra backup of the logic and configuration.
This function cannot be performed while the controller is running. You must stop the
controller first.

Transferring the
Controller’s
Memory
Contents to
Controller Flash
or PCMCIA
Memory Card

From the project right-click menu in the navigation panel:

372 SPU 780 01EMAN May 2002

Step

Action

1

Select Online Commands → Write → Transferring to Flash/EEPROM/PCMCIA.

2

Select Internal Flash to transfer the current logic to flash memory or PCMCIA to
transfer the current logic to the PCMCIA memory card.

3

Compact controllers have enhanced options that may be set prior to transferring. Set
the parameters for internal flash and PCMCIA settings:
l Start PLC after download from EEPROM: Automatically starts the controller
with the logic that was stored in flash memory or the PCMCIA card during a power
failure.
l Save state RAM: Saves the last state to flash memory or the PCMCIA card in the
event of a power failure.

4

Type the number of registers to save in the 4xxxx registers to save field. The
specified number of registers are saved to flash memory or the PCMCIA card in the
event of a power failure.

5

Click Transfer to transfer the logic to flash memory or the PCMCIA card. You are
prompted to stop the controller if it is running.
Note: Click Clear Flash to clear the logic stored in the flash memory or the PCMCIA
card.

6

If the controller is currently running, click Stop.

97

Working with Controllers

Starting and Stopping Controllers
Starting and
Stopping a
Controller

From the ProWORX 32 Online Controls tool bar:
Step

Action

1
Click Start/Stop Controller.

The Start/Stop dialog appears.

2

For controllers that support it, you can select Optimization Mode. In the
optimized mode, the ability to edit or show power flow is disabled. You may have
to stop the controller to make logic changes. The 685E and 785E controllers
have a 2k buffer allowing editing during optimized mode. Once this buffer is full,
no further changes can be made until the controller stops.

3

Click Start to start the controller.

4

5

The start/stop dialog box displays the following controller information:
Project Name
Processor Type
Communications Type and Address
Current State

l
l
l
l

Click Stop to stop the controller.

WARNING
Controller may be Process-Critical.
Stopping a controller stops a controller from solving logic, or performing
I/O functions; the controller remains in the ready state. Stopping a
controller may have a major impact on your process. Always consider
fully the possible consequences of stopping a controller (i.e., is it
performing a critical operation?) before proceeding.
Failure to follow this precaution can result in severe injury or
equipment damage.

98

372 SPU 780 01EMAN May 2002

Working with Controllers

PLC Status Viewer
Overview

The status viewer monitors PLC status words. The PLC to be monitored is specified
by the project selected. Multiple projects can be monitored at once and results in the
word data grid are saved to the project. See Status Words for S901 and S908,
p. 280 for more information about status words.
Note: The words available are dependant on the PLC being monitored.

Checking the
Value of a Word

Logging
Word Data

Working with
Logged
Word Data

In the PLC status window:
Step

Action

1

Select the Update current node radio button

2

Select the word from the status word navigation panel that you want to see the
value of.
Note: Single bits are colored when set.

In the PLC status window:
Step

Action

1

Select the Record selected nodes radio button.

2

Select the word(s) from the status word navigation panel that you want to log by
clicking the check boxes beside the status word icons.

3

Click the Start Logging button.

4

To end the logging session, click the Stop Logging button.

After logging word data, right click on the logged data grid:

372 SPU 780 01EMAN May 2002

Step

Action

1

To clear the selected word data from the logged word data grid, click Delete.

2

To clear all word data from the logged word data grid, click Delete All.

3

To view the detailed word view and diagram of bits, click View Bits.

4

To print the logged word data, click Print.

99

Working with Controllers

Analyze Device
Overview

The Analyze feature is very useful in diagnosing problems with your PLC that
wouldn’t show up as part of typical online programming/commissioning. Analyze
device performs a checklist of predetermined tasks to find specific problems relating
to an I/O sub-systems health and general PLC status. The Analyze feature can
pinpoint problems for maintenance staff to correct as well as keep an up-to-date
knowledge base of maintenance records for future reference.

S901 Style
Analyze

The S901 Analyze performs Stopcode Error, Controller Status, Battery Failed,
Memory Protect, Single Sweep, Constant Sweep, S901/J200 Status, ASCII Error,
Channel Communications Health, Module Health checks. All potential problems are
placed into a report.

S908 Style
Analyze

The S908 Analyze performs Stopcode Error, Controller Status, Battery Failed,
Memory Protect, Single Sweep, Constant Sweep, Hot Standby, DCP Present, ASCII
Error Set, Remote I/O, S908 Error Set, Cable A Errors, Cable B Errors, Global
Comm Health, Cable A Comm Health, Cable B Comm Health, Local Drop Health,
Remote Drop Health, Remote Drop Cable A, Remote Drop Cable B, Drop
Communications, and Module Health checks. All potential problems are placed into
a report.

Understanding
the Analyze PLC
Output

Output graphics descriptions:
Graphic

Description
This area passed and no report entry has been made.
An entry has been made into the report signifying the state of the area.
A problem has been detected in the specific area. An entry in the report has
been made.

Viewing the
Analyze Device
Report

From the Analyze Device window:
Step
1

100

Action
Select the Report tab. (The Report window shows the date and time the problem
was found, and a brief description of the potential problem.)

372 SPU 780 01EMAN May 2002

Configuration Extensions

At a Glance
Overview

Configuration extensions are utilities that can be loaded into a controller. The
Configuration Extensions area contains several different hardware configuration
extensions. These extensions are controller-specific. Each different extension hasits
own editor and some of the more complex extensions have a wizard as well.

What’s in this
Chapter?

This chapter contains the following topics:

372 SPU 780 01EMAN May 2002

Topic

Page

Configuration Extensions

102

Compact Phase II

104

Data Protect Extension

105

Quantum Hot Standby

106

IO Scanner

108

IO Scanner Wizard

111

Peer Cop

113

Peer Cop Wizard

118

Profibus Extension

121

Profibus Wizard

122

S980 Extension

123

SY/MAX Extension

124

TCP/IP Extension

125

Quantum VME Bus Extension

126

101

Configuration Extensions

Configuration Extensions
Overview

Configuration extensions can be edited while the project is either online or offline.
Online changes can only be made to a stopped controller. The configuration
extension information is stored within the project and can be loaded at any time.
Available configuration extensions listed in the Active Extensions panl:
Configuration Extension Description
Data Protect

Prevents specific blocks of 0xxxx and 4xxxx references from
being modified by general Modbus data write commands.

Peer Cop

Allows you to configure data blocks to be transferred between
controllers on a Modbus Plus network.

S980 Addresses

Specifies the S980 station address.

Quantum Hot Standby

Allows additional configuration of the Quantum Hot Standby
setup.

Profibus

Configures a Quantum controller for Profibus communications.

TCP/IP

Configures controllers to connect to a TCP/IP network through a
communication card.

SY/MAX

Configures a Quantum controller for communication with SY/
MAX drops.

I/O Scanner

Allows you to configure data blocks to be transferred between
controllers on a TCP/IP network.

Compact Phase II

This extension is only available for Phase II Compact PLC’s

VME Bus

Configures a VME controller for communications with a VME
network.

Note: Before setting config extensions, you must set the Configuration Extension
Size parameter in the controller configuration editor. For more information see,
Configuring a Controller, General Tab Parameters, p. 77.

102

372 SPU 780 01EMAN May 2002

Configuration Extensions

Using the
Configuration
Extensions
Utility

In the project navigation tree:

372 SPU 780 01EMAN May 2002

Step

Action

1

Double-click the Configurations Extensions icon. The configuration
extensions window will appear showing only the extensions that are available for
the active project.

2

To add a configuration extension, select the check box beside the extension
icon.

3

To remove a configuration extension, de-select the check box beside the
extension icon.

4

To edit an extension, ensure that the extensions associated check box is
checked. Then, select the extension that you want to edit from the extensions
panel.
The status bar at the bottom of the Configuration Editor window shows the
number of words used, total number of words available and any error or status
messages as they may appear.

5

To save the changes that have been made, close the Configuration Extensions
window.

103

Configuration Extensions

Compact Phase II
Overview

Compact Phase II extensions allow the programming of functions specific to the
Compact Phase II controllers. This provides support for:

l PLC based password access
l Secure Data Area (SDA)
l Comm 1 CTS/RTS delay time settings.
Note: If the Compact Phase II extension does not appear in the Active Extensions
panel, it is not a valid extension for the current controller type.

Editing the
Compact Phase II
Extension

104

In the Active Extensions panel select the Compact Phase II extension, then:
Step

Action

1

Enter a Secure Data Area value between 0 and 128 in the SDA Size (K Words)
box. A zero value disables the feature.

2

Enter a value between 0 and 50 in the CTS Delay (x10 ms) box. A zero value
indicates the feature is disabled.
Note: This value is a factor of 10; if 5 is entered, 50 is assumed by the PLC.

3

Enter a value between 0 and 50 in the RTS Delay (x10 ms) box. A zero value
indicates the feature is disabled.
Note: This value is a factor of 10; if 5 is entered, 50 is assumed by the PLC.

4

Enter a password consisting of a maximum of 16 characters (A-Z, 0-9 and _) in
the PLC Password boxes. The PLC password can only be changed while
online. If the password is set to nothing, the PLC is not password protected.

372 SPU 780 01EMAN May 2002

Configuration Extensions

Data Protect Extension
Overview

Data Protect is used to protect specific 0xxxx and 4xxxx references from being
modified by Process Monitoring and Control software. Write access is allowed for all
0xxxx and 4xxxx references within the specified block.
References outside the ranges specified are protected from general Modbus data
write commands. By default, all 0xxxx and 4xxxx references are unprotected.
Note: If the Data Protection extension does not appear in the Active Extensions
panel, it is not a valid extension for the current controller type.

Editing the Data
Protect
Extension

In the Active Extensions panel select the Data Protect extension, then:

372 SPU 780 01EMAN May 2002

Step

Action

1

Enter an address in the 0xxxx Starting Address field. Default - 0:0001.

2

Enter the number of references that are to be left unprotected in the 0xxxx
Length field. ProWORX 32 shows the protected reference ranges in the 0xxxx
Protected Ranges boxes.
Suppose you type a Start value of 00017, and a Length of 1024. The first
protected range will be from 00001 (the first possible value) to 00016 (the last
value before the Start value you entered).
There will then be an unprotected range from 00017 to 01040 (00017 + 1024).
All references above 01041 are also protected.
If you enter a length that is too high (goes beyond the addresses configured for
the controller) ProWORX 32 automatically sets the value to include all addresses
above the Starting Address fields.

3

Enter an address in the 4xxxx Starting Address field. Default - 4:0001.

4

Enter the number of references that are to be left unprotected in the 4xxxx
Length field. ProWORX 32 shows the protected reference ranges in the 0xxxx
Protected Ranges boxes.

105

Configuration Extensions

Quantum Hot Standby
Overview

The Quantum Hot Standby extension allows additional configuration of the Quantum
Hot Standby setup. This lets you set the type of state RAM transfer between the
CHS110-00 modules. It also lets you set the Initial Command Register and the NonTransfer Area.This area is only available on version 2.x Quantum controllers that
contain the CHS loadable in the configuration.
Note: If the Quantum Hot Standby extension does not appear in the Active
Extensions panel, it is not a valid extension for the current controller type.

Editing the
Quantum Hot
Standby
Extension

106

In the Active Extensions panel select the Quantum Hot Standby extension, then:
Step

Action

1

In the General tab, enter the 4xxxx address of the command register used to
configure the hot standby system in the Command Register field. This register
must be transferred every scan and cannot be in the non-transfer area.
The initial command register contains the settings that are loaded into the
controller when it is started. If any changes need to be made while the controller
is running, the command register must be used, and not the initial command
register. Settings such as port address swapping, allowing an executive
upgrade, setting the standby’s mode on a logic mismatch, setting the controller’s
modes and overriding the key switch can be changed from the command
register.

2

Enter the starting address of the range of registers that are not to be transferred
from the primary controller to the standby in the Non-Transfer Area Start
Address field. This is commonly used to reduce scan time.
l The first two registers are used in reverse transfer operations. These
registers allow information to be passed from the standby to the primary
controller.
l The third register is the Status register, which stores the status of both
controllers. This register provides information on how the hot standby system
is operating, such as the power flow of the CHS instruction, position of the
controller’s A/B switch, and whether there is a logic mismatch between
controllers.
l All registers following the third register are ignored (not transferred) during
the scan.

3

Enter the length of the non-transfer register range in the Non-Transfer Area
Length field. This value can be from 1 through the total number of registers
configured in the controller.

372 SPU 780 01EMAN May 2002

Configuration Extensions

Step
4
5

6

372 SPU 780 01EMAN May 2002

Action
Click the Show Command/Status Registers to view the command and status
register contents in the Data Watch Window.
Select one of the following State RAM Transferred options:
Default (12K): All 0xxxx and 1xxxx registers (up to 8192 each) are
transferred.
l If 10000 or fewer 3xxxx and 4xxxx (combined) registers are configured,
then all are transferred.
l If more than 10000 3xxxx and 4xxxx (combined) registers are configured,
then (up to) 1000 3xxxx registers and all 4xxxx (up to a combined total of
10000) are transferred.
l Routine Only: All addresses defined in the routine transfer table are
transferred every scan. There must be a minimum of 16 4xxxx registers to
support the non-transfer area. The Routine Transfer Table is a range of
discretes and registers that must be configured as a multiple of 16.
l Routine and Extra: All addresses defined in the Routine Transfer Table and
in the extra tables are transferred. The range of each extra table must be a
multiple of 16. The extra tables can be transferred over multiple scans.
l All State RAM: All RAM configured in the controller is transferred every scan.

l

Select an address in the table and enter a reference length.
For Routine Transfer Table address lengths, this must be a value between 16
and the maximum configured size for that address.
l For Extra Transfer Table address lengths, this must be a value between 16
and the maximum configured size for that address exclusive of the range set
in the corresponding Routine table.
l Values must be a multiple of 16. The ranges defined are updated and
displayed to the right on the tables as the values change.

l

7

Enter the number of scans (1-255) needed for the primary controller to transfer
the extra transfer tables to the standby in the Scans to Transfer field,

8

Select the Initial Command Register tab.

9

Set the Swap Port (x) Addresses parameters to either Yes or No.

10

Set the Controller (x) Mode parameters to either Offline or Online.

11

Set the Standby Mode (on logic mismatch) to either Yes or No.

12

Set the Executive Upgrade Switch to either Enabled or Disabled.

13

Set the Keyswitch Override to either Enabled or Disabled.

107

Configuration Extensions

IO Scanner
Overview

The I/O Scanner extension provides data transfer between two or more controllers
on a TCP/IP network. The I/O Scanner lets you to simultaneously configure up to
128 communication transactions, depending on your controller. Because the TCP/
IP connection is established only once and remains connected during an entire
session, it makes this type of communication very efficient.
Note: If the IO Scanner extension does not appear in the Active Extensions panel,
it is not a valid extension for the current controller type.

IO Scanner
Wizard

ProWORX 32 includes a configuration wizard to step you through data transaction
setup between a local device and a number of remote devices on a TCP/IP network.

Editing the IO
Scanner
Extension

In the Active Extensions panel select the IO Scanner extension, then:

108

Step

Action

1

Select a card to edit from the Card Number drop-down list box. There may be
one, two or six cards available to edit depending on the PLC type. Each card has
an independent set of data values.

2

Enter an IP address in the IP Address field in the format (1-255).(1-255).(1255).(1-255) This address should match the TCP/IP extension for the selected
card.

3

Enter a 1xxxx or 3xxxx address that will receive health information in the Health
Block (1x/3x) field.

4

Enter the number (1-16) of the slot in the backplane the selected card inhabits in
the Head Number field. This value should match the value in the TCP/IP
extension for the selected card.

5

The transaction list displays up to 128 (64 for M1E PLC’s) transactions. A
transaction that isn’t configured is denoted by a red X, a partially configured
transaction is denoted by a yellow exclamation mark, and a configured
transaction is denoted by a green check mark.
To configure a transaction, right-click anywhere in the transaction list and select
Add Transaction. Transactions are configured in order so if you have three
transactions and select Add Transaction, the fourth transaction can be
configured.

6

To clear the configuration of the last transaction in the list, right-click anywhere
in the transaction list and select Delete Transaction or press the DELETE key.

7

Enter the IP address of the remote device that you are communicating with in the
IP Address field.

372 SPU 780 01EMAN May 2002

Configuration Extensions

Step

372 SPU 780 01EMAN May 2002

Action

8

Enter the value of the destination Unit ID in the Unit ID field. This is an identifier
for a pair of transactions (specifically Link Client/Server transactions). The
transaction pair must have matching Unit ID’s.
An example situation would include a single Server Write that sends data to the
matching Client Reads in a remote device. All Client Read transactions accept
the data sent from the single Server Write transaction as long as the Unit ID’s
match.

9

Enter a millisecond value representing the length of time to wait for a reply for
each transaction in the Health Timeout (0-50k) field.

10

Enter a millisecond value representing the length of time to wait before repeating
the transaction in the Repetition Rate (0-50k) field. A value of 0 indicates the
quickest possible rate.

11

Select one of the following functions from the Function drop-down list:
l Read - A unilateral read in which a local device reads data from a remote
device.
l Write - A unilateral write in which a local device writes data to a remote
device.
l Read/Write - A unilateral read/write in which a local device reads data from
and writes data to a remote device.
l Link Client Read - A paired function type in which a local device responds to
a write transaction from a remote device which must have a matching server
write.
l Link Client Write - A paired function type in which a local device writes to a
remote device which must have a matching server read.
l Link Client Read/Write - A paired function type in which a local device reads
and writes data to and from a remote device which must have a matching
server read and write.
l Link Server Read - A paired function type in which a local device initiates a
read from a remote device. The remote device must have a matching client
write.
l Link Server Write - A paired function type in which a local device writes to a
remote device. The remote device must have a matching client read.
l Link Server Read/Write - A paired function type in which a local device reads
and writes data to and from a remote device which must have a matching
client read/write.
Note: For unilateral function types, no intervention is required for the remote
devices. They respond to any Read or Write without the need to set up an I/O
Scanner transaction. Linked function types require two complementary
transactions, on in each device.

109

Configuration Extensions

Step

110

Action

12

Select a fallback value from the Fallback Value drop-down list box:
l Zero - Resets the data values for the selected transaction to zero in the event
of a power failure.
l Hold Last - Retains the last data values for the selected transaction and make
them available at restart in the event of a power failure.

13

Type the local data address receiving data from the remote controller in the Read
from Remote, To field.

14

Enter the remote address where the read data is coming from in the Read from
Remote, From field.

15

Enter the number of sequential registers to read in the Read from Remote,
Number To Read field. Up to 125 registers are allowed.

16

Enter the local data address that sends data to the remote controller in the Write
to Remote, From field.

17

Enter the remote address where the write data is going to in the Write to Remote,
To field.

18

Enter the number of sequential addresses to write in the Write to Remote,
Number To Write field. Up to 100 registers are allowed.

372 SPU 780 01EMAN May 2002

Configuration Extensions

IO Scanner Wizard
Overview

To launch the IO Scanner wizard, click the IO Scanner Wizard button situated
directly below the Active Extensions panel.
The wizard operates independently of the Offline/Online mode. All changes are
made to Offline projects with an option to modify Online devices as well. TCP/IP
communications are required only when modifying online devices.

Using the IO
Scanner Wizard

Read the introduction instructions on the first screen and click Next:

372 SPU 780 01EMAN May 2002

Step

Action

1

Set the transaction type by selecting either the Direct radio button or Link
Client/Server radio button. Click Next.
l Direct - Creates a single transaction in the local device. Data is transferred
regardless of the programming of the remote device. This option is simpler
than Link Client/Server but could pose more risk as the target device needs
no additional program to verify its operation.
l Link Client/Server - Creates a pair of matching transactions, one in each
device. The server makes a request from a client which then responds to that
request. This is a safer option than Direct transactions but is more complex
to set up and maintain.

2

Set the local device address by entering an IP address in the Local Device IP
Address box in the standard IP format (1-255).(1-255).(1-255).(1-255)
If you are using a Quantum PLC, select the slot that the NOE (or similar ethernet
adapter) card resides in from the Head Number drop-down list.
Click Next.

3

To properly use the IO Scanner extension, you must define target PLC’s to
communicate with. These target PLC’s are called Remote Devices. To add a
remote device, click Add. To remove a remote device, click Remove. At least
one remote device must be defined before proceeding.
l Select a project to add its associated remote device to the list by clicking the
Browse button and selecting a project to the Remote Device/Database box.
Enter the IP address of the PLC for the remote device’s project in the Select
an IP Address box.
If you are using a Quantum PLC, select the slot that the NOE (or similar
ethernet adapter) card resides in from the What slot in the remote rack is
this device mounted in? drop-down list.
Click Next to return to the remote device summary screen.
l Repeat the above step until all desired remote devices have been added.
When you have finished adding remote devices to the IO Scanner extension,
click Next.

111

Configuration Extensions

Step

112

Action

4

To transfer data from one device to another a transaction is required. Existing
transactions cannot be modified using the IO Scanner wizard and are greyed
out. Up to 128 transactions may be created, except if you are using the M1E
PLC’s, then only support 64 transactions can be supported. To add a new
transaction, click Add. To edit a transaction created by the IO Scanner wizard,
click Edit. To remove a transaction created by the IO Scanner wizard, click
Remove.
l After clicking Add to add a new transaction, you are prompted to select a
remote device. To do this, click on a remote device from the list, and press
Next.
l Now you can configure the new transaction. First, select a function from the
drop down list. Second, enter 4xxxx addresses into the From and To fields
and numeric values in the Number of Registers field in the Read from Remote
Device and Write to Remote Device areas.
l When you have finished editing the transaction, click Next
(To see descriptions of the functions and fields, see Editing the IO scanner
extension.)

5

The transaction summary screen displays a summary of all new transactions to
be written to the local device as well as the variously selected remote devices.
Ensure the transactions are correct and click Next
Caution: Clicking Next will proceed with the modifications and cannot be undone
once completed.
Note: Only offline databases are modified in this step.

6

Click the Update Online Devices button to update the physical devices defined
as remote devices by the wizard. This does not update the local device. That
must be done once the configuration extension editor is closed and all changes
are saved.
Caution: Online devices may be running! They must be stopped before their
contents can be modified. Before stopping any device, ensure that it is safe to do
so. Devices are restarted once the operation is complete. Also, when these
changes are complete, they cannot be undone.
Click Next.

7

Click the View Log File button to view a log of all changes made to the local and
remote devices. This file (ScannerWizard.log) may be saved and printed as
needed.
Click Finish to close the wizard and return to the Configuration Extension Editor.

372 SPU 780 01EMAN May 2002

Configuration Extensions

Peer Cop
Overview

The Peer Cop extension provides data transfer between two or more controllers on
a peer-to-peer network, as well as linking multiple networks using the S985
communication card. Peer Cop configures data blocks to be continuously
transferred (once per scan) between nodes on a Modbus Plus network. Data can be
broadcast to all nodes on a single link (Global I/O) or between specific Modbus Plus
nodes on a link (Specific I/O).
A maximum of 32 data registers or 512 (for example, 32*16) I/O points can be
transferred to or read from a controller at a time. Peer Cop is supported by the A145
and all E-Series and Quantum controllers. Up to three Links of the Peer Cop can be
configured and edited.
Note: If the Peer Cop extension does not appear in the Active Extensions panel, it
is not a valid extension for the current controller type.

Peer Cop Wizard

ProWORX 32 includes a configuration wizard to help you set your Peer Cop
extensions. To access the Peer Cop wizard, see Peer Cop Wizard, p. 118.

372 SPU 780 01EMAN May 2002

113

Configuration Extensions

Editing the Peer
Cop Extension

Global Input/
Output

In the Active Extensions panel select the Peer Cop extension, then:
Step

Action

1

The Peer Cop extension can be configured for up to three links. When you add
a link you will have access to the 64 possible devices on another peer-to-peer
network.
l Link 1 is the internal link; all devices on the local Modbus Plus network can
be accessed from Link 1.
l Links 2 and 3 are remote links through S985 cards.
To add a link, click Add Link. To clear the configuration of a link, click Clear
Link. To delete a link, click Delete Link.

2

To configure a link, set its Head Number, Time-out value, and Last Value
parameters.
For link 2 or 3, select a head number (1 through 16) from the Link x Head
Number drop-down list box. Head Number specifies the head number on a
Quantum rack. If you are using a Quantum Controller, you have the option of
editing the head number for the second or third link. The first link is internal,
therefore it cannot be edited.

3

Select a value from the Timeout (ms) drop-down list box. Time-out specifies the
health time-out interval. The default value is 500ms. This value specifies the
minimum time period a Peer Cop configured communication must fail before the
associated health bit is cleared. Valid time-out values range from 20ms to 2
seconds. If you type a value too big, the value truncates to a multiple of 20. For
example, 230 truncates to 220 (it is not rounded up to 240).

4

Select ‘Clear’ or ‘Hold’ from the Last Value drop-down list box. Last Value
specifies whether or not to hold the last value. When set to ‘Hold’, the input data
area associated with an unhealthy transfer is left in its previous state (i.e. the last
value with a health of OK).

Global I/O is one of two communication methods used by the Peer Cop extension
(the other is Specific I/O). Global I/O is a broadcast communication method, where
a message is broadcast (made available) to all controllers on the Modbus Plus
network. Global I/O data transfers do not require an acknowledgment from the
receiving controller, so there is no immediate overhead placed on the receiving
controller.
Note: You can view the register data of any global input/output or specific input/
output by clicking View Data. The data watch window will open displaying the
relevant data.

114

372 SPU 780 01EMAN May 2002

Configuration Extensions

Editing Global
Inputs

Global Input is used to receive global data from any device on a Modbus Plus
network. One entry (line) is available for each device (1 through 64). Each device’s
global data can also be received in pieces determined by Subfields.
Step

Editing Global
Input Subfields

Action

1

Select the Global Input icon in the Links panel.

2

Select a global input from the Global Input list by double-clicking on an input.
The global input properties grid appears.

3

Enter the starting point (1 through 32) of the broadcast data to read in the Index
field.

4

In the Start field, enter the destination for the received data (i.e., where the
received data is to be stored).

5

Enter the number of words (1 to 32) to read forwards from the Index value in the
Length field.
For example, suppose the source controller is broadcasting 10 words of data
using the Global Output function, but the receiving controller only uses words 3
to 7. You would type an Index value of 3 and a Length of 5.
Note: The length value plus the index value must be less than or equal to 33.

6

Select either BIN (default) or BCD from the Type drop-down field.

Each device’s global data can also be received in sections determined by Subfields.
You can define a subfield for each block of the broadcast data that you want the
controller, to receive while ignoring the remainder.
Step

372 SPU 780 01EMAN May 2002

Action

1

To view the subfields of a global input, click View Subfields.

2

Select a subfield from the Global Inputs Subfields list.

3

Subfields have the same parameters as inputs. When you are finished editing
the subfields parameters, click Return to go back to the list of global inputs.

115

Configuration Extensions

Editing the
Global Output

Global Output broadcasts the specified range of discretes or registers to the devices
on the Modbus Plus network. Each device used to access the data must also be
configured to accept Global Input from the broadcasting device (1-32).
Step

Specific Input/
Output

Action

1

Select the Global Output icon in the Links panel.

2

n the Start field, enter the destination for the received data (i.e., where the
received data is to be stored).

3

Enter the length (1-32) of the address range (i.e., the number of registers to
broadcast). in the Length field.

4

Select either BIN (default) or BCD from the Type drop-down field.

Specific I/O is one of two communication methods used by the Peer Cop extension
(the other is Global I/O). Specific I/O uses a one-to-one communication method and
requires an acknowledgment from the receiving device, which creates a certain
amount of overhead. When using Specific I/O, the destination controller must accept
the entire block of data from the source controller. This means that the Index value
used in Global I/O is not necessary.
Specific I/O allows you to configure multiple defined data blocks for transmission to
specific devices on the Modbus Plus network. The device receiving the data must
be configured for Specific Input from the broadcast device. The length (in words) of
the specific input (configured in the destination controller) must be identical in length
to the specific output (configured in the source controller). The input data, however,
can be stored in any type of reference desired. That is, five words of 4xxxx data can
be stored into five words of 0xxxx memory area.
Note: You can view the register data of any global input/output or specific input/
output by clicking View Data. The data watch window will open displaying the
relevant data.

116

372 SPU 780 01EMAN May 2002

Configuration Extensions

Editing Specific
Inputs

Editing Specific
Outputs

Select the Specific Input icon in the Links panel, then:
Step

Action

1

Select a specific input from the Specific Input list by double-clicking on an input.
The specific input properties grid appears.

2

In the Start field, enter the starting address of the block of data to be placed from
the source controller.

3

Enter the number of words (1 to 32) to be received from the source controller in
the Length field.

4

Select either BIN (default) or BCD from the Type drop-down field.

Select the Specific Output icon in the Links panel, then:

372 SPU 780 01EMAN May 2002

Step

Action

1

Select a specific output from the Specific Output list by double-clicking on an
output. The specific output properties grid appears.

2

In the Start field, enter the starting address for the block of data to be sent to the
destination controller.

3

Enter the number of words (1 to 32) to be sent to the destination controller in the
Length field.

4

Select either BIN (default) or BCD from the Type drop-down field.

117

Configuration Extensions

Peer Cop Wizard
Overview

To launch the peer cop wizard, click the Peer Cop Wizard button situated directly
below the Active Extensions panel.
ProWORX 32 includes a peer cop wizard to step you through transaction setup
between a local device and a number of remote devices on a Modbus Plus network.
The wizard operates independently of the Offline/Online mode. All changes are
made to Offline projects with an option to modify Online devices as well. Modbus
Plus communications are required only when modifying online devices.

Using the Peer
Cop Wizard

118

Read the introduction instructions on the first screen and click Next:
Step

Action

1

Enter an IP address (01-64).(00-64).(00-64).(00-64) in the Local Device MB+
Address box. Click Next.

2

Define target PLC’s for the PLC to communicate with by adding remote devices
to the Remote Device Summary list. Click Add to add a remote device and its
corresponding project. Click Remove to delete a remote device from the list.
l To configure the remote device being added to the extension, click Browse
to select a project, and enter an IP address in the Select MB+ Address for
this Device field.
l When you have configured the remote device, click Next.
Note: The Modbus Plus routing paths for the local device and all remote
devices must match. Only the last, non-zero, address value may be different.
All proceeding values must be the same because Peer Cop transactions
cannot pass across Modbus Plus bridges or multiplexers.

372 SPU 780 01EMAN May 2002

Configuration Extensions

Step

372 SPU 780 01EMAN May 2002

Action

3

To transfer data from one device to another a transaction is required. Existing
transactions cannot be modified using the peer cop wizard and are greyed out.
Up to 64 read and 64 write transactions may exist. To add a new transaction,
click Add. To edit a transaction created by the peer cop wizard, click Edit. To
remove a transaction created by the peer cop wizard, click Remove. When
finished adding or editing transactions, click Next.
l After clicking Add to add a new transaction, the Specific Transaction screen
appears, allowing you to configure the transaction. Select ‘Read’ or ‘Write’
from the Function drop down list. Read requests data from the remote device
and Write sends data to the remote device.
l Enter the 4xxxx address where the data comes from in the From field. The
address is from the remote device for a read function and from the local
device for a write function.
l Enter a 4xxxx address where the data is sent to in the To field. The address
is from the local device for a read function and from a remote device for a
write function.
l Enter the number of consecutive registers to transfer (1 through 32) in the
Word Length field.
l When you have finished configuring the transaction, click Next

4

The Global Transactions List lists all of the global device-to-device transactions.
Existing transactions cannot be modified using the peer cop wizard and are
greyed out.
To add a new global transaction, click Add. To edit a global transaction created
by the peer cop wizard, click Edit. To remove a global transaction created by the
peer cop wizard, click Remove. When finished adding or editing global
transactions, click Next.
Note: Up to 64 read transactions may exist although only one global output
transaction can exist. Of course, numerous global output transactions can be
defined for different remote devices. However, once the first global output
transaction is defined, the ‘From’ address cannot be changed.
l After clicking Add to add a new global transaction, the global transaction
screen appears, allowing you to configure the transaction. Select ‘Read’ or
‘Write’ from the Function drop down list. Read requests data from the remote
device and Write sends data to the remote device.
l Enter the 4xxxx address where the data comes from in the From field. The
address is from the remote device for a read function and from the local
device for a write function.
l Enter a 4xxxx address where the data is sent to in the To field. The address
is from the local device for a read function and from a remote device for a
write function.
l Enter the number of consecutive registers to transfer (1 through 32) in the
Word Length field.
l When you have finished configuring the global transaction, click Next

119

Configuration Extensions

Step

120

Action

5

The summary of transactions screen displays all of the new transactions created
by the wizard.
These transactions are written to the local device as well as the various remote
devices when Next is clicked.
To overwrite any transactions in the remote device that would interfere with the
new one, check the Overwrite Existing Remote Transactions check box.
Caution: Pressing ‘Next’ proceeds with all modifications, and cannot be undone.
Note: Only offline databases are modified in this step.

6

Click Update Online Devices to update the physical devices defined as remote
devices by the wizard. This does not update the local device. The local device
must be updated after the configuration extension editor is closed and all
changes are saved.
Caution: Online devices may be running! They must be stopped before their
contents can be modified. Before stopping any device, ensure that it is safe to do
so. Devices are restarted once the operation is complete. Also, when these
changes are complete, they cannot be undone.
Click Next.

7

Click View Log File to view all of the changes made to the local and remote
devices. This file (PeerWizard.log) may be saved or printed as needed.
Click Finish to exit the Peer Cop wizard.

372 SPU 780 01EMAN May 2002

Configuration Extensions

Profibus Extension
Overview

The Profibus configuration extension allows you to communicate with a Profibus
network. In order to successfully install and configure the Profibus configuration
extension, you will have to use a total of three separate utilities:

l The ProWORX 32 Profibus wizard
l Softing’s PROFI-KON software, included with the Profibus hardware
l Modicon’s SPU931 utility, also included with the Profibus hardware
Note: PROFI-KON and SPU931 are not ProWORX 32 products. While every effort
has been made to ensure the accuracy of these instructions, users of PROFIKON
and SPU931 do so at their own risk.

Note: If the Profibus extension does not appear in the Active Extensions panel, it
is not a valid extension for the current controller type.

Editing the
Profibus
Extension

The Profibus extension displayed in the configuration extensions utility is for display
purposes only. To edit and configure the Profibus extension, you must use the
Profibus wizard.

372 SPU 780 01EMAN May 2002

121

Configuration Extensions

Profibus Wizard
Overview

To launch the profibus wizard, click the Profibus Import Wizard button situated
directly below the Active Extensions panel.

Using the
Profibus Wizard

Follow the on-screen instructions as you make your way through the wizard:

122

Step

Action

1

Read the Introduction screen and click Next.

2

Select either the Create a new Profibus Station radio button or the Move
configuration extension from existing radio button. Click Next.

3

In order to configure a Profibus configuration extension, you have to have the
following directory layout: Drive → Plant Directory → Station Directory.
In the Select Plant Path screen, select a drive from the drive drop-down list box.
Next, select a plant directory from the directory list or click New Folder to enter
a new folder name into the list.
When you have selected a drive and a plant directory, click Next.

4

In the Select Station Path screen, select a station directory from the directory list
or click New Folder to enter a new folder name into the list. The selected folder
will hold the .cfg file and the .cfg file will have the same name as this folder.
When you have selected a drive and a plant directory, click Next.

5

If you have selected Create a New Profibus Station in the Options screen, then
pressing Next in the previous step will generate a .cfg file. If you have selected
Move configuration from existing, no .cfg file will be created and you will be taken
to the next step.

6

To configure the .cfg file you must use two external pieces of software:
l SyCon (System Configuration) - Use this software to configure the Profibus
Network.
l SPU-931 - Use this software to configure the Profibus-DB for the CRP811
Profibus card.
Once you have completed configuring the .cfg file, click Next.

7

Click Finish to move the Profibus configuration extension into your ProWORX
32 Project.

372 SPU 780 01EMAN May 2002

Configuration Extensions

S980 Extension
Overview

The S980 Configuration Extension stores the S980 station address. This address is
then used as part of the S980’s mismatch detection mechanism; when the controller
is powered up, the S980 checks to see if it has been moved to a different 984.
Note: If the S980 extension does not appear in the Active Extensions panel, it is
not a valid extension for the current controller type.

Editing the S980
Extension

In the Active Extensions panel select the S980 extension, then:
Step
1

372 SPU 780 01EMAN May 2002

Action
Enter up to a 12-digit hex number representing the S980 address in the Address
field.

123

Configuration Extensions

SY/MAX Extension
Overview

The SY/MAX configuration extension allows you to properly access and configure
up to six SY/MAX RIO cards. This extension is only available when using Quantum
controllers revision 2 or later.
Note: If the SY/MAX extension does not appear in the Active Extensions panel, it
is not a valid extension for the current controller type.

Editing the
SY/MAX
Extension

124

In the Active Extensions panel select the SY/MAX extension, then:
Step

Action

1

Select a card (1-6) from the Card drop-down list.

2

Enter a I/O drop number (-1 through 99) in the Module Drop Number field. Set
to -1 if the drop is not defined.

3

Enter the number of the slot (0 through 16) that the RIO card inhabits in the
Backplane Slot field. Set to 0 to remove a module.

4

Enter a retry number (1 through 255) in the Retry Count field.

5

Enter a timeout value (1ms through 65535ms) in the Timeout field.

372 SPU 780 01EMAN May 2002

Configuration Extensions

TCP/IP Extension
Overview

Before your controller can connect to a TCP/IP network, you must install and set up
the TCP/IP configuration extension. This extension lets the controller recognize its
TCP/IP communication card. For more information about configuring TCP/IP
communications, see Configuring TCP/IP Communications, p. 73.
Note: If the TCP/IP extension does not appear in the Active Extensions panel, it is
not a valid extension for the current controller type.

Editing the
TCP/IP
Extension

In the Active Extensions panel select the TCP/IP extension, then:

372 SPU 780 01EMAN May 2002

Step

Action

1

Select a card (1-6) from the Card drop-down list box.
Note: Different controllers support different numbers of communications cards:
l Quantum 113 Rev. 2 and 213 Rev. 2 controllers support two cards.
l Quantum 424 Rev. 2 supports up to six cards.
l M1E Momentum controllers only support one card and the Head Number is
fixed at one.

2

Select a head number (1 through 16) from the Head Number drop-down list box.

3

Enter an IP address (1-255).(1-255).(1-255).(1-255) in the IP Address, Subnet
Mask, and Gateway IP fields. 0.0.0.0 indicates an undefined address.

4

Select either Ethernet II or IEEE 802.3 from the Framing Type drop-down list
box.

5

Select either Extension or BOOTP Server from the IP Address Selection dropdown list box.
l Extension - Upon Power Up, the PLC will read its TCP/IP addressing
information from this extension.
l BOOTP - Upon Power Up, the PLC will require a BOOTP server to supply
TCP/IP addressing information.

125

Configuration Extensions

Quantum VME Bus Extension
Overview

The VME Bus extension lets a VME-424/X controller control data transfers between
devices on a master/slave Quantum network. In a master/slave protocol, one device
(the "master") has control over other devices ("slaves"). As the network runs, each
element can lose and gain master status, based on negotiations with other members
of the network.
Note: If the VME Bus extension does not appear in the Active Extensions panel, it
is not a valid extension for the current controller type.

Editing the VME
Bus Extension

126

In the Active Extensions panel select the VME Bus extension, then:
Step

Action

1

Enter the appropriate value in the Slave Interrupt Level field. Boards on a VME
Bus can send and respond to messages on seven interrupt levels, numbered
from 1 to 7. This field determines which interrupt level the board uses when it’s
acting as a slave.

2

Enter a value between 1 and 255 in the Status ID field. When the VME controller
receives an interrupt while acting as a slave, this is the value it sends.

3

Select an appropriate value for master arbitration type from the Master
Arbitration Type drop-down list. This field determines how the controller will
operate. Valid settings are Not System Controller, Primary Mode (PRI) or Round
Robin Mode (RRS).

4

Select an appropriate value for master release mode from the Master Release
Mode drop-down list. This field determines when a board acting as a master
relinquishes its master status. Valid settings are Release on Request (ROR),
Release When Done (RWD), Release On Clear (ROC), or Bus Capture and Hold
(BCAP). The proper setting depends on how your Quantum network is
configured.

5

Select the appropriate value for master VME Bus request level from the Master
Bus Request Level drop-down list. This field determines what priority the board
has when trying to acquire master status. It can range from BR0 (the lowest) to
BR3 (the highest).

6

For each interrupt level from Interrupt 1 to Interrupt 7, select whether it should
be Enabled or Disabled. These fields will only have an effect when the VME acts
as a master. If an interrupt level is:
l Enabled - The controller responds to any messages sent on that interrupt.
l Disabled - The controller ignores them.

372 SPU 780 01EMAN May 2002

Using the Logic Editor

At a Glance
Logic Editor
Overview

The Logic Editor is used to view and/or edit ladder logic in Offline, Online or
Emulation mode. In Offline mode, network logic is loaded into the Logic Editor from
the database when it is opened. In Online mode, network logic is read from the PLC
one network at a time. In Emulation mode the power flow is simulated using the
network logic loaded from the project.

372 SPU 780 01EMAN May 2002

127

Using the Logic Editor

What’s in this
Chapter?

128

This chapter contains the following topics:
Topic

Page

Logic Editor Overview

129

Logic Editor Properties

130

Hotkey Template

132

Using the Logic Editor

135

Working with Networks

138

Instructions

140

Working with Addresses

142

Configurable Mnemonics

144

ISA Symbols

146

Diagnostic Trace

148

Sweep (Online Only)

149

Setting Bookmarks in Logic

151

Hardware Clock

152

Segment Scheduler

153

Equation Networks

154

Mathematical Equations in Equation Networks

156

Mathematical Operations in Equation Networks

158

Mathematical Functions in Equation Networks

161

372 SPU 780 01EMAN May 2002

Using the Logic Editor

Logic Editor Overview
Overview

The Logic Editor is used to enter logic elements, display input/output data, and add
descriptors and force discretes.
The Logic Editor shows project ladder logic in either Offline, Online, Combined or
Emulation mode. In Offline mode, network logic is loaded into the Logic Editor from
the project when the editor is opened. In Online and Combined mode, network logic
is read from the PLC one network at a time. During idle states of Online mode,
networks around the currently displayed network may be cached for faster access
to the networks.
The logic editor is made up of four panels:
Panel

Description

Network
Navigator
panel

The Network Navigator Panel (tree) is used to navigate through networks and
segments. To display or hide the Network Navigator Panel, select View →
Navigation Tree from the logic editor right-click menu.

Logic Editor
panel

The Logic Panel contains the view of the logic contained in the currently
viewed network. The title of the Logic Panel contains the current network,
maximum network and the page title for the network. In Online and Emulation
mode, powerflow will be drawn per cell based on the properties of the Logic
Editor. The cursor tracks several features: instruction help placed in Tracking
Help window, tracking documentation for the current address in
Documentation editor and data for the current network.

Instructions
panel

The Instructions Panel contains a list of all available instructions for the
current project. New instructions are entered by dragging from the
Instructions Panel and dropping into the Logic Panel. The list of instructions
is alphabetically sorted. To display or hide the Instructions Panel, select View
→ Instruction List from the logic editor right-click menu.

Properties
Panel

The Properties Panel contains information about the current cell the cursor is
on. Depending on the type of cell, the Properties Panel will contain a 1, 2 or
3 high instruction. For a blank cell, the Properties Panel will contain only the
name property. To display or hide the Properties Panel, select View →
Properties from the logic editor right-click menu.

Note: The instructions, properties and networks panels can be opened or closed
using the right-click menu in the logic panel. Select View → Instruction List or
Properties or Navigation Tree..

372 SPU 780 01EMAN May 2002

129

Using the Logic Editor

Logic Editor Properties
Customizing the
Logic Editor
Display

Logic Editor
Display
Properties

The Logic properties dialog box tells ProWORX 32 how to display each cell in a
network. In the project navigation tree:
Step

Action

1

Right click the Logic icon.

2

Select Properties from the right-click menu.

3

Configure the logic editor properties as desired. See ‘Logic Editor Display
Properties’.

4

Click OK to save and apply changes.

In the logic editor properties window:
Property

Description

Color
The color of the descriptor, symbol, data, back reference, cursor background,
Configuration cursor foreground, logic background, logic foreground, and power flow is user
defined. Click the color box beside the text and select a color from the Color
dialog box.
To set the colors to their defaults, click the Default button. This will also set
the power flow line width to three.

130

Power Flow
Line Width

In Emulation or Online mode, the power line shows the flow of power. You
can adjust the width of this line from 1 to 6.

Display
Settings

Up to seven lines are available for each element: Five lines above the
instruction and two below it. For each line, select one of the following:
l Clear - This line is not displayed.
l Address - The address associated with the cell is displayed.
l Descriptor (1 - 9) - Descriptors specified in the documentation editor are
displayed.
l Symbol (1,2) - Symbols specified in the documentation editor are
displayed.
l Data - The addresses data is displayed.
l Back Ref - Back referencing information is displayed.
l Blank - This line is blank.

Column
Width

Select the column width for the seven lines of cell description. Increasing the
width allows less instructions to fit on the screen, but more descriptor, data
and symbol information to be displayed.

Always Fit 7
Rows x 11
Cols

Check the check box to always see the full grid of instructions in the window.
If the check box is unchecked, the cells will be displayed at full size and you
will have to scroll to see the entire network.

372 SPU 780 01EMAN May 2002

Using the Logic Editor

Property

Description

Show Coils in Check the check box to see the coils where they are solved by the controller.
Solve Column If the check box is unchecked, the coils will always be displayed in the 11th
column attached to the solve column by dots.
Multi Function When checked, function identifier constants are replaced with four-letter
Naming
descriptions of the function operation.

372 SPU 780 01EMAN May 2002

Confirm
Overwrites

You are prompted to confirm each time you overwrite an existing ladder logic
instruction with a new one. This security feature is useful when working
online.

Multi
Instruction
Insert

When checked, you can add as many instruction as you want without
specifying an associated address.

Confirm
Deletes

You are prompted to confirm each time you try to delete an instruction from
ladder logic. Use this function to protect your ladder logic, especially while
working online.

Use Insert/
Delete Key
Menus

When checked, you can access the Insert menu by pressing the INSERT key
and the Delete menu by pressing the DELETE key. When cleared, these keys
operate normally and the menus are only accessible from the Edit menu.

Show Cross
Reference
Tips

When checked, a tooltip will be visible showing the cross reference
information for the address that your cursor is hovered over. The tooltip is in
the format network.row.instruction.

ISA Symbols

When checked, enables the use of ISA symbols in the logic view.

131

Using the Logic Editor

Hotkey Template
Overview

The hotkey template is used to select the type of hotkey support that you wish to use.
The possible options are ProWORX 32, ProWORXPLUS, or Modsoft. The following
table lists the supported hotkeys for Modsoft and ProWORXPLUS.

Changing the
Hotkey Template

From the My Computer (in the Navigation panel), right-click menu:

132

Step

Action

1

Select Properties. The Properties dialog appears.

2

Select the Logic tab.

3

From the Hotkey Template drop-down, select the template you want to use.
(ProWORX 32 (default), ProWORXPlus, or Modsoft.

4

Click OK to save the changes and exit the Properties dialog.

372 SPU 780 01EMAN May 2002

Using the Logic Editor

Modsoft Hotkey
Listing

Modsoft Hotkey Listing:

372 SPU 780 01EMAN May 2002

Hotkey

Operation

ALT+F2

Invoke RDE

Data Watch Window

ALT+F3

Copy

Block Copy

ALT+F4

Delete

ALT+F5

Paste

Block Paste

ALT+F6

Offset

Replace

ALT+F7

Search

ALT+A

Append Network

ALT+B

Retrace

ALT+D

Delete Network

ALT+I

Insert Network Before

ALT+L

Latched Coil

ALT+M

Retentive Coil

ALT+N

Negative Transitional

ALT+P

Positive Transitional

ALT+T

Trace

ALT+V

Vertical Short

ALT+Z

DX-Zoom

CTRL+PgUp

Previous Segment

CTRL+PgDn

Next Segment

CTRL+Home

Goto 1st Network of Segment

CTRL+End

Goto Last Network of Segment

CTRL+F8

Configuration

ProWORX 32 Equivalent

Insert Previous Network

Insert Previous Network

Locate Coil

Register Editor

133

Using the Logic Editor

ProWORXPLUS
Hotkey Listing

134

ProWORXPLUS Hotkey Listing:
Hotkey

Operation

ALT+A

Address Used

ALT+C

Coil Rebuild (Offline), Coil Column (Online)

ALT+G

Global Addressiing

ALT+H

Help

ALT+J

Jump to Mark

ALT+L

Log Book

ALT+O

Locate Coil

ALT+R

Register Editor

ALT+S

Search

ALT+T

Trace (Online)

ALT+U

Undo

ALT+X

Mark Location and Exit

ALT+Z

Retrace

CTRL+D

Network Display Setup

CTRL+T

Terminal Block Search

CTRL+U

Unlink All Macros

ProWORX 32 Equivalent

Replace

Logic Properties

372 SPU 780 01EMAN May 2002

Using the Logic Editor

Using the Logic Editor
Editing Overview

The level to which you can edit in the logic editor is set in the client security settings.
For more information see ProWORX 32 Client Security, p. 20, User Rights.

Offline Edit Mode
Overview

Offline Edit Mode lets you make changes (e.g., entering instructions with undefined
addresses or duplicate coils) to network logic in the online logic editor without
updating the controller in real-time.

Switching to
Offline Edit Mode

From the logic editor right-click menu:
Step
1

Action
Select Edit → Offline Edit Mode.
While you are in Offline Edit Mode, the network appears in bright blue, with no
power flow or state flow shown. The status bar will display "Offline Edit Mode" in
bright blue. As long as you are in the Offline Edit Mode, changes made to the
network won’t be sent to the controller. Instead, they will be kept in a temporary
buffer until you exit the Offline Edit Mode or change networks.

Editing Logic in
Offline Edit Mode

In the logic editor:
Step
1

Action
Use the same editing conventions and procedures as the ProWORX 32 Offline
editor does.
Remember, however, that you cannot edit more than one network without either
cancelling the edit or writing the edit to the controller.

372 SPU 780 01EMAN May 2002

135

Using the Logic Editor

Exiting Offline
Edit Mode

From the logic editor right-click menu:
Step

Action

1

Select Edit → Offline Edit Mode.
-orSelect Edit → Save Network. (Only visible when in offline network mode.)
-orExit the logic editor.

2

You are then prompted about writing your changes to the controller:

l

l
l
Undoing and
Redoing Edits

Yes: ProWORX 32 checks the new network for undefined addresses and
duplicate coils. If none are found, ProWORX 32 deletes the original network
in the controller, and sends the new network (created in Offline Mode) to the
controller.
No: Returns to regular logic editor.
Cancel: Returns to Offline Edit Mode.

Use the undo/redo feature to reverse or reapply up to 10 actions.

Note: If you receive the messages "Undo information not recognized, clearing
undo/ redo information", a possible cause could be the register ranges that are set
for the PRWX loadable are being overwritten by theTraffic Cop, Peer Cop, MSTR,
or other instruction addresses that are already used. Search for address conflicts
with the Used Address feature, see Address Used, p. 60.

To Undo/Redo an
Edit

136

From the logic editor, right-click menu:
Step

Action

1

Select Edit → Undo or Edit → Redo. The Undo/Redo Stack dialog appears.

2

Click in the list where you want the starting point of the actions redone/undone.
The rows (actions) above the selected action are also selected.

3

Click OK to undo or redo the selected actions.

372 SPU 780 01EMAN May 2002

Using the Logic Editor

Undoing/
Redoing Online

While working online, the undo/redo feature only works when:

l The property Online Multiple Undo/Redo Enabled is selected. See Logic Editor
Properties, p. 130 for more information.

l The PRWX MSL loadable is added to your controller and is in the logic.
l You use a running controller that supports this feature.
Online undo/redo is supported by the following controllers:
984-685E

Adding the
PRWX MSL
Loadable

984-AT4

Compact A120 Series

984-785E

All Quantums

Compact TSX

984-785L

984-VM4

Atrium

After the Online Multiple Undo/Redo Enabled property is enabled:

372 SPU 780 01EMAN May 2002

Step

Action

1

Attach to a valid controller. The Add PRWX Loadable dialog box appears.

2

In the Command field, type an unused register to be used by ProWORX 32 to
control the loadable.

3

In the Table field, type an unused register of a starting range (4yyyy to
4yyyy+150) to used by ProWORX 32 to transfer data into the loadable.

4

In the Network field, type a value between one and the maximum number of
networks in the device. This number represents the network location to be
created and where the PRWX instruction will be placed. Up to 5000 networks
can be defined.

137

Using the Logic Editor

Working with Networks
Overview

A ladder logic network contains a 7x11 celled grid. Network logic is solved from leftto-right, top-to-bottom.

Inserting
Networks

In the logic editor:
Step

Action

1

To insert a network into a blank segment, select Insert Network from the
Network Navigator panel right-click menu.

2

To insert a network after the current network, select Insert → Next Network
from the Network Editor right-click menu.

3

To insert a network previous to the current network, select Insert → Previous
Network from the Network Editor right-click menu.

Moving
Networks

You can move or copy networks within or between segments and within or between
projects by using the standard Cut, Copy, and Paste functions. Theses functions
can be selected from the Network Navigator right-click menu, or from the ProWORX
32 toolbar.

Deleting
Networks

From the logic editor right-click menu:
Step
1

Working with
Network Rows
and Columns

138

Action
Select Delete → Network. The current network is deleted and the any remaining
networks are shifted up one network.

In the logic editor:
Step

Action

1

To insert a row or column, select Insert → Row (or) Column from the logic editor
right-click menu. You can only insert a row or column if it does not make the
network invalid. Inserting a column shifts existing columns to the right. Inserting
a row shifts existing rows down.

2

To delete a row or column, select Delete → Row (or) Column from the logic
editor right-click menu. You can only delete a row or column if it does not make
the network invalid. Deleting a column shifts existing columns to the left. Deleting
a row shifts existing rows up.

372 SPU 780 01EMAN May 2002

Using the Logic Editor

Initializing Logic

In the logic editor:
Step
1

372 SPU 780 01EMAN May 2002

Action
To initialize logic (delete all existing logic and networks from the current project),
select Initialize Logic from the loigc editor right-click menu.

139

Using the Logic Editor

Instructions
Overview

The Instruction Panel contains all available logic instructions. You can use the
instruction list to drag and drop instructions into logic.

Displaying the
Instruction List

From the logic editor right-click menu:
Step
1

Adding an
Instruction to a
Network

Action
Select View → Instruction List.

From the instruction panel:
Step

Action

1

You can drag-and-drop instructions from the instruction to any point in logic.

2

You can also add an instruction to the cell that the cursor is currently on, by
selecting an instruction from the Instructions Toolbar.

Moving
Instructions

You can move or copy instructions within or between networks and within or
between projects by using the standard Cut, Copy, and Paste functions. Theses
functions can be selected from the Logic Editor right-click menu, Edit, or from the
ProWORX 32 toolbar.

Finding
Instructions

To find all like instructions in ladder logic:

140

Step

Action

1

Set the logic editor cursor to the bottom node of the instruction that you want to
search for.

2

Select Search → Instruction Search from the logic editor right-click menu. E.g.
To find all ADD instructions in logic, set your cursor to the bottom node of an ADD
instruction anywhere in logic and select Instruction Search.

3

All instructions found are listed in the Search Results window in the format
InstructionName.Network.Row.Column.

4

To go to an instruction in the Logic Editor, double-click the desired instruction in
the Search Results window.

372 SPU 780 01EMAN May 2002

Using the Logic Editor

Deleting an
Instruction from
a Network

From the logic editor:
Step
1

Configuring an
Instruction

Instruction
Properties

Action
Select the instruction that you want to delete and press DELETE.

In the properties panel:
Step

Action

1

Select the property you want to configure.

2

Enter an appropriate value.

3

Press ENTER to update the instruction’s properties.

Property descriptions:

372 SPU 780 01EMAN May 2002

Property

Description

Top Type

Top node address type.

Top Offset

Top node address.

Mid Type

Middle node address type.

Mid Offset

Middle node address.

Bottom Type

Bottom node address type.

Bottom Offset

Bottom node address.

Name

Instruction name.

141

Using the Logic Editor

Working with Addresses
Editing
Addresses in
Ladder Logic

Finding
Addresses in
Ladder Logic

142

In the logic editor:
Step

Action

1

To edit a single address, double-click the cell that contains the address you want
to edit. Type the new address in the cell and press ENTER to save the changes.

2

You can also change the address by using the Properties panel and changing
the Type and Offset values for any given cell.

3

To edit a batch of addresses across networks, select Search → Replace.

4

Enter the address to replace in the Find What field and the address that is to
replace it in the Replace With field, and select Replace. The logic Replace
dialog appears.

5

Click Find Next to find an instance of the source address. If you want to replace
the address, click Replace. If not, click Find Next again, and so on. If you simply
want to replace all addresses, click Replace All.

In the logic editor:
Step

Action

1

To find a specific address, select Search → Find (CTRL+F).

2

Enter the address you want to search for in the Find What field.

3

Click Find Next to find the address in logic.

4

To find all like addresses in ladder logic, set the logic editor cursor to a cell that
contains the address that you want to search for.

5

Select Search → Address Search from the logic editor right-click menu. E.g. To
find all 10001 addresses in logic, set your cursor to a cell containing the address
10001 and select Address Search.

6

All Addresses found are listed in the Search Results window in the format
InstructionName.Network.Row.Column.

7

To go to an address in the Logic Editor, double-click the desired address in the
Search Results window.

372 SPU 780 01EMAN May 2002

Using the Logic Editor

Tracking Ladder
Logic Addresses
in the Data Watch
Window

Disabling and
Forcing
Discretes

From the logic editor right-click menu:
Step
1

To track the address at the cursor, select Data → Add Watch (CTRL+W) or
select Data → Track → Address.

2

To track all addresses in an instruction, select Data → Track → Instruction.

3

To track all addresses in a network, select Data → Track → Network.

4

To track all discrete addresses in a network, select Data → Track → Discrete.

You can force a discrete to the ON or OFF state. This removes control of the discrete
from logic: it remains in the fixed state until the force is removed. Enabling a discrete
removes the Disabled On or Disabled Off, placing control of the discrete back in
logic.
Step

Using Addresses
from the
Documentation
Editor

Action

Action

1

To force discretes in a network ON, select Data → Disable On (CTRL+S) from
the logic editor right-click menu.

2

To force discretes in a network OFF, select Data → Disable Off (CTRL+D) from
the logic editor right-click menu.

3

To return control of a discrete’s state back to logic, select Data → Enable
(CTRL+E) from the logic editor right-click menu.

In the Documentation Editor, summary view:

372 SPU 780 01EMAN May 2002

Step
1

Action
Select an address and drag-and-drop it into any instruction in logic or any
address property in the properties panel.

143

Using the Logic Editor

Configurable Mnemonics
Overview

In ProWORX 32, all instruction mnemonics are configurable, so you can use
mnemonics you are already familiar with.

Editing a
Mnemonic

From the project right-click menu in the Navigation panel:
Step
1

Mnemonics
Listing

144

Action
Select Properties.

2

Select the mnemonic to edit and click Edit or double-click the mnemonic to edit.

3

Type in the new mnemonic.

4

Click outside of the field or press ENTER.
Note: If you try to type an existing mnemonic, ProWORX 32 reverts to the old
mnemonic.

5

Click OK.

Mnemonic descriptions:
Mnemonic

Description

NO

-] [-

Normally Open

NC

-]\[-

Normally Closed

PTC

-]P[-

Off to On

NTC

-]N[-

On to Off

VTO

| OPEN

Vertical Open

VTS

| SHRT

Vertical Shunt

HSH

-SHRT

Horizontal Shunt

CNR

-()-

Normal Coil

CR

-(L)-

Latched Coil

SKP

SKP

Skip Function

UCT

UCTR

Up Counter

DCT

DCTR

Down Counter

T1

T1.0

Timer (seconds)

T0

T0.1

Timer (tenths)

T.

T.01

Timer (hundredths)

ADD

ADD

Addition

SUB

SUB

Subtraction

MUL

MULT

Multiplication
372 SPU 780 01EMAN May 2002

Using the Logic Editor

Mnemonic

372 SPU 780 01EMAN May 2002

Description

DIV

DIV

Division

RT

R->T

Register to Table

TR

T->R

Table to Register

TT

T->T

Table to Table

BLK

BLKM

Block Move

FIN

FIN

First-In

FOU

FOUT

First-Out

SRC

SRCH

Table Search

STA

STAT

System Status

AND

AND

Logical And

OR

OR

Inclusive Or

CMP

CMPR

Logical Compare

SEN

SENS

Logical Bit Sense

MBI

MBIT

Logical Bit Modify

COM

COMP

Logical Complement

XOR

XOR

Exclusive Or

BRO

BROT

Logical Bit Rotate

145

Using the Logic Editor

ISA Symbols
Overview

If the ISA Symbol Name field in the project is set up to support discrete addresses,
the network editor draws the ISA symbol instead of the ladder logic instruction.

Attaching an ISA
Symbol to a
Discrete Device

From the logic editor:

ISA Symbol
Reference

146

Step

Action

1

Select a discrete device.

2

Enter an ISA symbol name in the ISA Symbol field in the Documentation Editor.

ISA Symbols:
Symbol

Diagram

Symbol

CRNC

PBNC

CRNO

PBNO

FLSNC

PRSNC

FLSNO

PRSNO

FSNC

PSNC

FSNO

PSNO

Diagram

372 SPU 780 01EMAN May 2002

Using the Logic Editor

Symbol

372 SPU 780 01EMAN May 2002

Diagram

Symbol

LSNC

SOL

LSNO

TASN

LTG

TASNC

LTR

TGSN

HORN

TGSNO

Diagram

147

Using the Logic Editor

Diagnostic Trace
Overview

The Diagnostic Trace feature is a very powerful search mechanism. It is used to find
dependencies of a particular output (0xxxx). A search is performed to find the
destination point. Then each network is searched to find dependencies of the output
address. Each network is then searched to find dependencies of these
dependencies.

Why Use
Diagnostic
Trace?

Use Diagnostic Trace to isolate problems relating to a specific output. For instance,
if an output is off when it should be on, the Diagnostic Trace will search through logic
to determine which addresses affect its state.

Using Diagnostic
Trace

From the right-click menu in the logic panel:

Analyzing
Diagnostic Trace
Results

Step

Action

1

Make sure that the address you want to trace is selected and click Search →
Diagnostic Trace.

2

To move to an addresses cross reference, select the cross reference from the
address drop-down box. The logic editor moves to the selected network, row,
and column.

The Diagnostic Trace window shows the output address on the right side of the
window. The column to the left is all the dependencies of the output address. The
next column is all the dependencies of the dependencies.
Address color scheme:
Color

Description

Red

This address is likely to be the source of the problem.

Yellow

This address could be related to the problem.

Green

This address is not likely to be the source of the problem.

Note: To update the ladder logic cross references, select Update Cross
References from the logic editor right-click menu.

148

372 SPU 780 01EMAN May 2002

Using the Logic Editor

Sweep (Online Only)
Overview

The Sweep function is a powerful diagnostic tool that lets you solve logic for a set
number of scans or solve logic continuously with a constant time between scans.

Constant Sweep
Mode

The Constant Sweep mode sets the controller to scan and solve logic and update I/
O continuously, but with a constant time interval between scans.
If the actual scan time is less than the imposed scan time, the controller waits for the
imposed scan time to elapse before performing the next scan. If the actual scan time
is more than the imposed scan time, the controller finishes the scan, then continues
on with the next scan. This lets you slow the scan time to when debugging logic, so
that the controller doesn’t solve logic too quickly for you to catch errors.

Performing a
Constant Sweep

From the networks panel (tree), right click menu:
Step
1

Single Sweep

Action
Select Sweep.

2

In the Sweep Mode area, select the Constant Sweep radio button.

3

Enter the target time (in 10’s of milliseconds) for each scan in the Time box.

4

Enter a 4xxxx register to hold the target time value in the Register (4xxxx) box.
The actual time taken for each scan is placed in the next register, so a total of
two registers are used.

5

Click OK.

Single Sweep mode sets the controller to scan and solve logic, and update I/O for a
set number of scans only. When the sweep is finished, the controller stops solving
logic and updating I/O, waits until you manually trigger the sweep.
WARNING
Ensure hardware not part of critical process.
The Single Sweep function should not be used to debug controls on
machine tools, processes, or material handling systems when they are
active. Once the set number of scans is solved, all outputs are frozen in
their last state. Since no logic solving is occurring, all input information
is ignored. This can result in unsafe, hazardous, and destructive
operation of the machine or process connected to the controller.
Failure to follow this precaution can result in severe injury or
equipment damage.

372 SPU 780 01EMAN May 2002

149

Using the Logic Editor

Performing a
Single Sweep

From the networks panel (tree), right click menu:
Step
1

Select Sweep.

2

In the Sweep Mode area, select the Single Sweep radio button.

3

Enter the target time (in 10’s of milliseconds) for each scan in the Time box.
Note: If the actual scan takes less time than the target scan time, the controller
waits for the target scan time to elapse before performing the next scan. If the
actual scan takes more time than the target scan time, the controller finishes the
scan, then continues on with the next scan. This lets you force the scan time to
a higher rate when debugging logic that the controller may solve too quickly to
otherwise catch.

4

Enter the number of scans (1-15) to be performed during the sweep the Scans
box.

5

Click OK.

6

When you are ready to perform the sweep, select Sweep from the networks
panel (tree) right click menu.

7

8

150

Action

Select one of the following radio buttons:
Invoke: Select to start the sweep.
Trigger: Select to set a trigger for the sweep.
Turn Off: Select to shut off the sweep.

l
l
l

Click OK. The controller performs the scans (unless you selected Turn Off), then
stops solving logic with all outputs frozen in their last state.
You can then browse register contents and perform other diagnostics using this
"snapshot" of the solving process.

372 SPU 780 01EMAN May 2002

Using the Logic Editor

Setting Bookmarks in Logic
Overview

You can set bookmarks in your network logic so you can quickly return to a cell or
series of cells. The Mark and Goto Marks functions allow quick viewing of nonconsecutive areas of logic. By marking multiple cell locations on different networks,
you can use the mark table to quickly jump between the marked locations.

Setting a Mark in
Logic

In the logic editor:

Going to a
Marked Cell

Deleting a
Bookmark

Step

Action

1

Set the cursor to the cell that you want to mark.

2

Select Search → Mark from the right-click menu. The cell is added to the
Bookmark Table.

In the logic editor:
Step

Action

1

From the right-click menu, select Search → Goto Mark. The Goto Mark dialog
appears.

2

Select the mark you want to go to from the list and click Goto.

In the logic editor:

372 SPU 780 01EMAN May 2002

Step

Action

1

From the right-click menu, select Search → Goto Mark. The Goto Mark dialog
appears.

2

Select the mark you want to delete from the list and click Delete.

151

Using the Logic Editor

Hardware Clock
Overview

Many controllers have a built-in Time of Day clock. You can set these clocks if the
controllers starting register is configured in Configuration (see General Tab
Parameters, p. 77), you have the necessary rights, and the controller is running.

Configuring the
Hardware Clock

From the network tree right-click menu:
Step

Select Hardware Clock. The Hardware Clock dialog appears.

2

In the First Day of Week drop-down list box, select the day the controller will use
as the first day of the week.

3

4

Hardware Clock
Registers

Do one of the following:
To synchronize the controllers date and time with your computer, click Auto
Set.
l Type the date in mm-dd-yy format in the Controller Date box. Type the time
in hh-mm-ss format in the Controller Time box.

l

Click OK

The time of day clock requires eight 4xxxx registers in your controller:
Register
4xxxx

152

Action

1

Content
Controller Information. From the left:
Bit 1: Set Clock Values
Bit 2: Read Clock Values
Bit 3: Done
Bit 4: Errors

l
l
l
l

4xxxx + 1

Day of week (from 1 to 7)

4xxxx + 2

Month

4xxxx + 3

Day

4xxxx + 4

Year

4xxxx + 5

Hour (in 24-hour format)

4xxxx + 6

Minutes

4xxxx + 7

Seconds

372 SPU 780 01EMAN May 2002

Using the Logic Editor

Segment Scheduler
Overview

The Segment Scheduler governs when each segment of logic is solved and controls
which I/O drops are updated after each segment is solved.
The number of segments in the project is set in the Configuration editor. By default,
the segments are solved in numerical order (segment one first, segment two next,
and so on).

Using the
Segment
Scheduler

In the Networks panel right-click menu:
Step
1

Select Segment Scheduler.

2

Edit the fields in the Segment Scheduler dialog.

3

372 SPU 780 01EMAN May 2002

Action

Select the control input:
Continuous: Sets the segment in this row to be solved every scan.
Set Control: Sets the segment to be solved only when a discrete address is
in a specific state. If you select Set Control, you must also:
l Type the discrete address in the Address field, which controls whether the
segment in this row is to be solved.
l Select whether the segment in this row is to be solved when the control
discrete is On or Off.
l Watchdog Timer Reset: Inserts a Watchdog Timer.

l
l

4

Select the segment from the drop down list.

5

Select the input drop associated with the segment in this row during the solve
from the drop down box.

6

Select the output drop associated with the segment in this row during the solve
from the drop down box. For S901 projects/controllers the Drop In is replaced
with Chan In and Drop Out is replaced with Chan Out.

7

Click OK.

153

Using the Logic Editor

Equation Networks
Overview

An Equation Network provides an easy way to program complex math functions,
with values stored in register locations. Equations in an Equation Network are
presented in a regular, left-to-right format, technically known as "infix" notation. You
program Equation Networks and set its enable contact and output coil(s) in the
Equation Network Editor.
Equation Networks were introduced in Quantum Rev. 2 controllers; not all
controllers support Equation Networks. The easiest way to see if your controller
supports Equation Networks is by trying to create a new one—if your controller
doesn’t support it, the Equation Network option on the right-click Insert menu won’t
be available.

Creating an
Equation
Network

Using the
Equation
Network

In the Network Navigation panel:
Step

Select the network where you want to insert the equation network.

2

From the right click menu in the logic editor select Insert → Equation Network.
An equation network occupies a whole network, regardless of the contents of the
equation network.

In the Properties panel:
Step
1

154

Action

1

Action
Select an input type from the Input Type drop-down list.

2

Enter the input offset in the Input Offset property

3

Set the register address for the output coils. You can enter either the direct
address (in X:Y numeric format) or a symbolic address. You can also insert
addresses from the Symbols list panel, Used Register Address table and the
Descriptor Summary.See below for coil descriptions.

4

Enter an equation into the network by selecting the ellipsis box in the Equation
property or double-clicking anywhere in the Equation Editor Network. The
Equation Editor dialog appears.

372 SPU 780 01EMAN May 2002

Using the Logic Editor

Coil Descriptions

Coil descriptions:
Coil

Description

Solved OK

Solved OK is set when the equation is being solved without errors.

< Coil

Result<0 is set when the equation result is less than zero.

= Coil

Result=0 is set when the equation result is equal to zero.

> Coil

Result>0 is set when the equation result is greater than zero.

Error Coil

Error is set when errors have occurred while solving the equation.
While online, if the Error coil receives power, an error message will
appear under the coil describing the error.

Note: If you don’t want to use a particular output coil, leave the address for that coil
blank (or erase one already typed in). That coil will not be included in the Equation
Network.

Setting up an
Enable Contact

An Equation Network’s enable contact, when set, activates the Equation Network. If
an enable contact passes current, the Equation Network will be solved. You change
settings for the enable contact in the Enable Editor display.
To select a type for the enable contact, select the symbol of the enable contact that
corresponds with your chosen type. An enable contact can be a normally-open
contact, normally-closed contact, horizontal short, or a horizontal open.
To select a register address for the enable contact, in the Enable Contact address
field, type the direct address (in X:Y numeric format) or symbolic address for the
enable contact coil. This field is only available if the enable contact type is a
normally-open or normally closed contact.

372 SPU 780 01EMAN May 2002

155

Using the Logic Editor

Mathematical Equations in Equation Networks
Equation Format

ProWORX 32 expects equation elements to appear in a specific format. Operations
and functions each have their own format. Also, for each value, you must specify
what kind of value it is (register address, constant or symbol) and its data type
(signed integer, unsigned integer, etc.).

Equation Values
and Data Types

Each value can refer to a constant, register address or symbol. The Equation
Network Editor determines which data type the value is, based on the following
format.
Format

Meaning

Example

Default (no # sign or single quotes

Register address

40001

Prefixed by #

Constant

#123

Enclosed in single quotes

Symbol

‘HEIGHT’

The actual data type of a value is determined by its suffix, as shown in the following
table:
Suffix

Meaning

Example

None

16-bit Integer

#38

U

16-bit unsigned Integer

40001U

L

Long (32-bit) signed Integer

#-123L

UL

Long (32-bit) unsigned Integer

‘HEIGHT’UL

F

32-bit floating point (real)

#+1.45E-4F

Typically, you’d first indicate the register address where the calculated result is to be
stored, followed by an equal sign (the "assignment operator"), followed by the
calculation itself. For example:
40001 = 40002U + COS(40003UL) * #+1.35E-4F / ’HEIGHT’L

l 40002U is an address of a 16-bit unsigned integer.
l COS(40003UL) calculates the cosine of a long (32-bit) unsigned integer value
stored at address 40003.

l #+1.35E-4F is the floating point value of 0.000145, given in exponential notation.
l ’HEIGHT’L is a symbol of the name HEIGHT, representing the address of a long
(32-bit) signed integer.

l 40001 = indicates that the result of the calculation is to be stored in register
address 40001 as a 16-bit signed integer.

156

372 SPU 780 01EMAN May 2002

Using the Logic Editor

Everything to the right of the assignment operator also constitutes an expression.
An expression is any part of an equation that can be evaluated to a single value. This
can be a single constant or register address, or a complete mathematical operation.
For example, #35 is an expression, as are LOG(#10) and 40002U + COS(40003UL).
Complex expressions can contain other expressions within them, as in #3 * (40002U
+ COS(40003UL)). For the most part, any operator or function can be performed on
any expression, no matter how complex.
Note: It is good programming practice to enclose all expressions in parentheses,
even when they’re not actually needed. This makes the equation easier to read and
ensures that operations in an equation are solved in the correct order.

Exponential
Notation

Floating point numbers are normally specified in exponential notation, as in:
+1.34E-4
This represents 1.35 times 10 to the -4th power, or 1.35 times 0.0001. Thus, we
would shift the decimal place four places to the left to get 0.000135. The "-4" part is
called the exponent (note the preceding "E") and can be a positive or negative
number.
In the Equation Network Editor, you must also indicate:

l That these numbers are constants; and
l Their data types. For example, integers or floating point numbers.
The default data type is unsigned 16-bit integer. So, since the above value is a
fraction (and therefore must be a floating point number), it would have to appear as
#+1.35E-4F.
With no data type suffix, numbers in exponential notation are assumed to be
integers. For example, #+1.35E+2 represents the unsigned 16-bit integer value 135.
Exponential notation is particularly useful for very large integers.

372 SPU 780 01EMAN May 2002

157

Using the Logic Editor

Mathematical Operations in Equation Networks
Mathematical
Operations

The following table lists the mathematical operations you can include in your
equation:
Type

Operator

=
Assignment operator
The assignment operator = is used to
assign a storage place for the results
of the equation. All equations will use
the assignment operator. The format
is:

Result
Assignment

ADDRESS = EXPRESSION
Where ADDRESS is a valid register
address and EXPRESSION is a valid
value or expression assigned to the
address.

158

Unary Operators
"Unary" means "single", so unary
operators are used on only one value. ~
The unary operator is placed just
before the value or expression to
which it is applied. For example, (30002) returns -1 times the number
stored at address 30002.

Negation. The result is -1 times the
value.

Exponentiation operator
Takes values to a specified power.
40001**3 returns the (integer) value
stored at 40001, taken to the third
power.

**

Exponentiation

Arithmetic operators
These require two values, one before
and one after the operator. These
values can be any valid expression.
For example, #4 * 40003 results in
four multiplied by the value stored at
address 40003.

*

Multiplication

/

Division

+

Addition

-

Subtraction

Ones complement. This works on the
binary representation of a value: all 1s
are changed to 0s and vice versa.

372 SPU 780 01EMAN May 2002

Using the Logic Editor

Type

Operator

Result

Bitwise operators
Bitwise operators work on binary
(base 2) representations of values.

&

AND. The single bit result of an AND
operation is only true (1) if both bits are
set to 1.

l

l

372 SPU 780 01EMAN May 2002

|
In the case of AND, OR and XOR,
the computer applies the operator
to each digit in the two values: 010
XOR 011 (2 XOR 3 in decimal
^
numbers) results in 001 (1 in
decimal).
In the case of shifting operators,
the computer shifts all digits in the
<<
binary representation of the
number the given number of
places to the left or right. Digits on
one side of the number are lost,
and zeros fill in the blanks on the
other side. For example, for 8-bit >>
numbers, 77 << 2 means
01001101 shifted left two digits.
The binary result is 00110100, or
52 decimal.

OR. The single bit result of an OR
operation is true (1) if either bit is set to
1. The result is false (0) only if both bits
are set to 0.
XOR. Short for "Exclusive OR". The
single bit result of an XOR operation is
false (0) if both bits are the same, true
(1) otherwise.
Left Shift. The result of 40001<<#2 is
the binary representation of the
number stored at 40001 shifted left two
(#2) places. Zeros are added on the
right to fill in the gap.
Right Shift. The result of 40001>>#2 is
the binary representation of the
number stored at 40001 shifted right
two (#2) places. Zeros are added on
the left to fill in the gap.

Relational operators
These operators describe a
comparison between two values or
expressions. The result is always true
(1) or false (0). For example, #35 <=
#42 evaluates to 1 (true). Relational
operators are used in Conditional
expressions.

<

Less than.

<=

Less than or equal to.

=

Equal to.

<>

Not equal.

=>

Greater than or equal to.

>

Greater than.

Conditional operators
See below for details.

?:

Used in conditional expression.

Parentheses
Used to set precedence in solving
equations. To make sure certain
operations are solved before others,
enclose those operations in
parentheses.

()

159

Using the Logic Editor

Conditional
Expressions

In Equation Networks, conditional expressions take the following form:
EXPR1 RELOP (EXPR2) ? (EXPR3) : EXPR4
EXPR1 through EXPR4 can be any address, value or expression. If EXPR2 or
EXPR3 are not single values or addresses, they must be enclosed in brackets.
RELOP can be any relational operator, such as > (greater than) or <> (not equal to).
When solving a conditional expression, the computer first compares EXPR1 and
EXPR2, based on the relational operator. If the comparison is true, the value of the
conditional expression is the result of EXPR3. If the comparison is false, the value
of the conditional expression is EXPR4.
Note: It is especially good programming practice to enclose all expressions within
a conditional expression in parentheses, even when they’re not actually needed.
This makes the equation easier to read and ensures that operations are solved in
the correct order.

160

372 SPU 780 01EMAN May 2002

Using the Logic Editor

Mathematical Functions in Equation Networks
Mathematical
Functions

The following table lists the pre-defined math functions you can include in your
equation. Each of these functions takes one argument enclosed in brackets
following the function name. The argument can be any valid value or expression. For
example, COS(#35+40001) returns the cosine of 35 plus the number stored at
address 40001. In this table, X refers to a function’s argument (as in "COS(X)").

372 SPU 780 01EMAN May 2002

Function

Description

ABS(S)

Absolute value of X (i.e. negative numbers become positive).

ARCCOS(X)

Arc cosine of X radians.

ARCSIN(X)

Arc sine of X radians.

ARCTAN(X)

Arc tangent of X radians.

COS(X)

Cosine of X radians.

COSD(X)

Cosine of X degrees.

EXP(X)

Calculates e (approximately 2.7182818) to the Xth power.

FIX(X)

Converts floating point number X to an integer.

FLOAT(X)

Converts integer X to a floating point number.

LN(X)

Natural (base e) logarithm of X.

LOG(X)

Common (base 10) logarithm of X.

SIN(X)

Sine of X radians.

SIND(X)

Sine of X degrees.

SQRT(X)

Square root of X.

TAN(X)

Tangent of X radians.

TAND(X)

Tangent of X degrees.

161

Using the Logic Editor

162

372 SPU 780 01EMAN May 2002

Using the Traffic Cop

At a Glance
Traffic Cop
Overview

The Traffic Cop is used to visualize and configure I/O series, drops, cards, and slots.
Each I/O series (Quantum, Momentum, Symax, Compact A120, Compact TSX 800,
800, 200-500, DCP, S901, 900, Micro, Micro 984) has the same look and feel,
although some series have different I/O structures.

What’s in this
Chapter?

This chapter contains the following topics:

372 SPU 780 01EMAN May 2002

Topic

Page

Traffic Cop Overview

164

Working with Drops and Racks

165

Working with Slots

167

Online Module Status

169

I/O Drawing Generator

171

Materials List

172

163

Using the Traffic Cop

Traffic Cop Overview
Overview

The Traffic Cop is used to visualize and configure I/O series, drops, cards, and slots.
Each I/O series (Quantum, Momentum, Symax, Compact A120, Compact TSX 800,
800, 200-500, DCP, S901, 900, Micro, Micro 984) has the same look and feel,
although some series have different I/O structures.

Navigation Panel
(Tree)

The navigation panel shows a text-based representation of the traffic cop. The panel
is enabled regardless of which I/O series is selected. The tree provides a
hierarchical view of configured drops, racks and slots. Navigate through the tree to
select a drop or rack to view or to edit its configuration in the Drop or Slot Properties
Panel. Using the tree view you can insert, delete, and move any part of the tree
(drops, racks, or slots).

Visual
Representation

The Visual Representation of the I/O system consists of three views:

l Drop View - Visual representation of all racks and slots within the selected I/O
drop. Click on any slot to jump to the rack view that contains the selected slot.

l Rack View - Visual representation of all slots within the selected rack. Click on
any slot to access that slots properties in the Slot Properties Panel.

l Momentum View - Visual representation of the momentum traffic cop. This
shows only the current branch of I/O. If a new card can be programmed, the last
shown card is labelled "AVAILABLE".
Initializing the
Traffic Cop

In the traffic cop navigation panel:
Step

Action

1
Right-click the I/O series
2

you want to initialize.

Select Initialize from the pop-up menu.

WARNING
Ensure data integrity.
Initializing the traffic cop deletes all drops, racks, and slots, and clears
all properties.
Failure to follow this precaution can result in severe injury or
equipment damage.

164

372 SPU 780 01EMAN May 2002

Using the Traffic Cop

Working with Drops and Racks
Drop Properties
Panel

Lists user-editable and calculated properties pertaining to the selected drop.
Available drop properties are:
Property

To Edit:

Drop Series

Select a drop from the available Drop Series drop-down list box.

Hold-up Time

Enter a hold-up time value (3 - 65,535).

Rack (1-x)

Select a rack from the rack drop-down list box. (X represents the number
of racks available.)

ASCII Port

Enter an ASCII port value.

Input Bits

Read only - number of input bits used within the selected drop.

Output Bits

Read only - number of output bits used within the selected drop.

Status Word

Enter a 3xxxx address (holds the status information for the drop).

Read Only

Select TRUE or FALSE from the available drop mode drop-down list box.

Note: Not all properties are available for all drops - i.e. a Quantum drop will not
have an ASCII port property.

Working with
Drops

In the traffic cop navigation panel, select the drop
From the right-click menu:

372 SPU 780 01EMAN May 2002

you want to work with.

Function

Action

Comment

To insert a drop:

Select Insert.

Inserting a drop inserts a drop above the
selected drop and moves existing drops
down.

To edit a drop:

Select Edit.

You can edit the currently selected drop at
any time by editing properties in the Drop
Properties Panel.

To clear a drop:

Select Clear.

Clearing a drop clears all racks from the
selected drop.

To delete a drop:

Select Delete.

Deleting a drop deletes the currently
selected drop and moves the remaining
drops up.

165

Using the Traffic Cop

Working with
Racks

Using
Cut/Copy/Paste

In the traffic cop navigation panel, select the rack
From the right-click menu:
Function

Action

Comment

To insert a rack:

Select Insert.

Inserting a rack inserts a rack above the
selected rack and moves existing racks
down.

To edit a rack:

Select Edit.

You can edit the currently selected rack at
any time by editing the rack property in the
Drop Properties Panel.

To clear a rack:

Select Clear.

Clearing a rack clears all slots from the
selected rack.

To delete a rack:

Select Delete.

Deleting a rack deletes the currently
selected rack and moves remaining racks
up.

In the ProWORX 32 traffic cop:
Step
1

2

166

you want to work with.

Action
All items in the traffic cop (heads, drops, racks, and slots) can be cut, copied and
pasted. Also, items can be cut, copied, or pasted between different projects
traffic cops.
From the item right-click menu, select:
Cut - Removes the currently selected item (including documentation) from
the traffic cop into a buffer.
l Copy - Copies the currently selected item (including documentation) from the
traffic cop into a buffer.
l Paste - Inserts the buffered item (including documentation) into the currently
selected Slot/Rack/Drop/Head.
Note: A Slot copy can only be pasted into a slot, if the user attempts to paste
the slot onto a drop the paste will be ignored. This holds true for any item that
is pasted. The I/O series of the paste must match or it is ignored.
l Paste Special - The same as paste, but new available addresses are
automatically assigned to any slot that is pasted.

l

372 SPU 780 01EMAN May 2002

Using the Traffic Cop

Working with Slots
Slot Properties
Panel

Lists user-editable and calculated properties pertaining to the selected slot.
Available slot properties are:
Property

To Edit:

Card Name

Select a card from the available cards drop-down list box.

Description

Read only - description of the selected card.

Input Reference

Enter an address type. Only valid entries are accepted.

Input Data Mode

Select a data mode (BIN or BCD) from the data mode drop-down list
box.

Output Reference

Enter an address type. Only valid entries are accepted.

Output Data Mode

Select a data mode (BIN or BCD) from the data mode drop-down list
box.

Data Length

Enter the data length.

Power Rating

Read only - power rating of the selected card.

Bus Module Count

Read only - number of modules a Bus Module contains.

Bypass Local Bus

Select TRUE or FALSE from the bypass local bus drop-down list box.

Bypass remote

Select TRUE or FALSE from the bypass remote drop-down list box.

Card Config

Displays hex parameter data. To edit, double-click the Card Config
property and a Card Config dialog box will open.

Note: Not all properties are available for all slots - i.e. a discrete card will not have
the Data Mode property.

372 SPU 780 01EMAN May 2002

167

Using the Traffic Cop

Working with
Slots

168

In the traffic cop navigation panel, select the slot
From the right-click menu:

you want to work with.

Function

Action

Comment

To insert a slot:

Select Insert.

Inserting a slot inserts a slot above the
selected slot and moves existing slots down.
Leaving the Slot Properties Panel without
selecting a module while in a Momentum
traffic cop will result in the insert being
cancelled.

To edit a slot:

Select Edit.

You can edit the currently selected slot at
any time by editing properties in the Slot
Properties Panel.

To clear a slot:

Select Clear.

Clearing a slot clears the card from the
selected slot.

To delete a slot:

Select Delete.

Deleting a slot deletes the currently selected
slot and moves remaining slots up.

372 SPU 780 01EMAN May 2002

Using the Traffic Cop

Online Module Status
PLC Status/
Traffic Cop
Functionality
Matrix

Functionality Matrix:
PLC Status

Traffic Cop
Functionality

Module Status
Icon Reference

Online Running

Online Stopped

Offline

Read-Only

Yes

No

No

PLC Status
Update
Method

Automatically
every 3 seconds

Automatically
every 5 seconds

N/A

No

N/A

Online Health Yes
Online
Module
Recognition

No

Yes

N/A

Data
Committed
Method

N/A

Controller is
updated after
user verification

Project is
automatically
updated

Online Stopped - Module Recognition:
Icon

Description
Indicates that an associated slot is incorrect or missing.

,

,
Indicates a slot that is missing or not configured.
Indicates that an incorrect slot has been added to the traffic cop.

Online Running - Module Health:
Icon

Description
Indicates an unhealthy slot.

372 SPU 780 01EMAN May 2002

169

Using the Traffic Cop

Adding a Missing
Slot

From the traffic cop navigation panel:
Step

Action

1
Double-click the slot
that you want to add. (The correct slot will be selected
in the Module property combo-box in the Slot Properties Panel.)

Fixing an
Incorrect Slot

2

Press ENTER to accept the selected slot.

3

Configure the remaining properties of the selected slot.

From the traffic cop navigation panel:
Step

Action

1
Double-click the slot

170

that you want to fix.

2

Select the correct card from the Module property combo-box in the Slot
Properties Panel.

3

Press ENTER to accept the selected slot.

4

Configure the remaining properties of the selected slot.

372 SPU 780 01EMAN May 2002

Using the Traffic Cop

I/O Drawing Generator
Overview

The I/O Drawing Generator creates CAD (Computer-Assisted Design) drawings of
800, Micro, Quantum and A120 Traffic Cop series cards. The drawings are saved in
.DXF format, which is supported by most CAD programs.

Setting up the I/O
Drawing
Generator

From the project right-click menu in the navigation panel:

Using the I/O
Drawing
Generator

Step

Action

1

Select Properties.

2

Select the I/O Drawing tab.

3

Enter, or select by clicking Browse, the directory path to store the Symbol,
Master, Intermediate, and Final I/O drawings in. The I/O drawings created
reside in the selected path in a subdirectory which has the same name as the
project the drawings are created from.

4

Select Overwrite Existing Drawings to discard the existing drawings and save
the new ones in their place.

5

Select Ignore, Break, or Warn from the Missing Master Drawings options. This
property sets how ProWORX 32 reacts when a master drawing is missing while
the I/O drawings are being created.

In the project navigation panel:
Step
1

372 SPU 780 01EMAN May 2002

Action
I/O drawings are generated in a two-step process:
Intermediate: These drawings are used as a "working" step. Generating a
series of Intermediate drawings as you go can save time when it comes to
generating the Final drawings.
l Final: These drawings are generated based on the corresponding
Intermediate drawings.

l

2

To generate an intermediate drawing, select I/O Drawing → Intermediate
Drawings from the Traffic Cop right-click menu.

3

To generate a final drawing, select I/O Drawing → Final Drawings from the
Traffic Cop right-click menu.

4

To generate both an intermediate and final drawing, select I/O Drawing → Both
Drawings from the Traffic Cop right-click menu.

171

Using the Traffic Cop

Materials List
Overview

When you have finished configuring the I/O area of your system, you may want to
know what materials are required to create the hardware system as configured. The
material list function creates a list of all required materials (as configured) and their
associated part numbers.
When the materials list is first launched it will generate a list of materials required by
the selected project. The materials list will be created from the project if offline or
from the controller if online. On a second launch of the materials list the data will be
read from the project rather than generated. You can add prices and comments to
existing materials as well as add new materials to the list. The materials list can then
be printed or saved to HTML, MS Excel or MS Word.
Note: The Material List utility makes some assumptions about cabling that should
be checked and modified before printing.

Using the
Materials List

In the project navigation panel (tree):
Step

From the traffic cop icon right click menu, select Materials List.

2

Enter up to six lines of text in the Header text box. This text will be displayed at
the top of the printed materials list.

3

Add or edit materials in the grid. All fields are editable except Total which is
calculated.

4

To regenerate a material list from the controller or project, select Generate from
the materials grid right click menu.

5

To inset a row at the current cursor position, select Insert from the materials grid
right click menu.

6

To clear the currently selected row, select Clear from the materials grid right click
menu.

7

To delete the currently selected row and shuffle the remaining rows up, select
Delete from the materials grid right click menu.

8

To save the materials list to another format, select Save As from the materials
grid right click menu.

9
10

172

Action

1

To print out the materials list, select Print from the materials grid right click menu.
Close the materials list to save the changes.

372 SPU 780 01EMAN May 2002

Using the Traffic Cop

Cabling
Assumptions

Cabling Assumptions:

372 SPU 780 01EMAN May 2002

1

’97-5951-000 RG-11/U Coax Cable 1000 ft. reel’ This is the recommended cable for
use as Trunk cable. It can also be used for Drop cabling although it is recommended to
use the less expensive: ’97-5750-000 RG-6/U Coax Cable 1000 ft. reel’ for Drop
cabling. RG-6/U can also be used for Trunk cabling if the cable run is less than 5000 ft.
but is not recommended. If it is used then ’52-0488-000 RG-6/U BNC Connectors’ are
used in place of ’52-0401-000 RG-11/U F Connectors’ For cable runs over 8000 ft. up
to 15000 ft., CATV cable should be used but is not supplied by Modicon.

2

’AS-W801-012 I/O Signal Cable 12 ft.’ This also comes in 6 ft.’-006’and 1.5 ft.’
002’lengths.

3

’AS-W804-012 I/O Power Cable to rack with power 12ft.’ This also comes in 5 ft.’005’and 1.5 ft. ’-002’ lengths.

4

’AS-W802-012 I/O Power Cable to rack no power 12 ft.’ This is interchangeable with:
’AS-W808-002/-005/-008 Light-weight cable’ in 1.5,5 or 8 ft. lengths.

-

173

Using the Traffic Cop

174

372 SPU 780 01EMAN May 2002

Using the Data Watch Window

At a Glance
Data Watch
Window
Overview

The Data Watch Window is used to view and edit register data values for the
selected project. The project can be Online, Offline or in Emulation. Live, real time
data may be viewed or edited within the Data Watch Window. The data values may
be displayed in a number of ways depending on what Data Watch view is active.
Several views are available including a Generic Register Editor, a Data Watch/Edit
window, a Spreadsheet view, a Trend view, an Instruction view for specific
instructions, a Terminal Block view for specific I/O cards and a mini-HMI view. If the
preferences are selected, data for Traffic Cop and Network Logic elements are
tracked automatically. Data values may also be logged. These values are saved into
an external file for future use. Preferences and properties of the Data Watch Window
are saved in the project.

372 SPU 780 01EMAN May 2002

175

Using the Data Watch Window

What’s in this
Chapter?

176

This chapter contains the following topics:
Topic

Page

Data Watch Window Overview

177

Properties

181

HMI

184

Trend

188

Trend - Mode Functionality Table

190

Track Logic Editor

191

Track Traffic Cop

192

Instruction Editor / Terminal Block Editor

193

Instruction / Terminal Block Editor Display Scripts

194

Display Script Variables

195

Display Script Functions

196

Register Editor

201

PID Tuner

202

DRUM Summary

205

Importing and Exporting Data Watch Window Data

207

372 SPU 780 01EMAN May 2002

Using the Data Watch Window

Data Watch Window Overview
Overview

The watch window is the primary Data Watch Window. You can select any valid
address for the current device and view the data for that address. Up to 100
addresses of any type may be entered and tracked. The data may be edited at any
time. Register values may be changed and discrete values may be enabled or
forced on or off. Addresses are automatically saved on exit and reloaded on entry.
Any register data may be viewed or edited with any selected radix type. Available
radices are Decimal, Hex, Binary, ASCII, Signed integer, BCD, 32-bit Floating point
or 32-bit integer. The bottom status bar will display various information including
Status messages, Offline/Online/Emulation state, Running/Stopped state, Trigger
info and Clamping info.

Adding
Addresses to
Track in the Data
Watch Window

Clearing
Addresses

In the data watch window:
Step

Result

Double-click or press ENTER in the first available Address cell.

2

Insert a valid address into the Address cell.

3

Press ENTER to insert the address,
ESC to cancel the entry.

The Data and Radix fields are
automatically populated if the address
exists in the project. You can edit the
data or radix of an address by doubleclicking on the cell you want to change.

From the right-click menu:
Step
1

Loading
Addresses and
Data from a Log
File

Action

1

Action

Result

Select Clear.

All addresses are cleared from the
Window.

From the right-click menu:

372 SPU 780 01EMAN May 2002

Step

Action

Result

1

Select Load.

The DataWatch Address Load dialog
appears.

2

Select a log file and click OK.

All addresses from the file are added to
the Data Watch Window.

177

Using the Data Watch Window

Filling the Data
Watch Window
with Addresses

Setting the Radix
for Multiple
Addresses

Deleting
Addresses

178

From the right-click menu:
Step

Action

Result

1

Select Fill Addresses.

The Add Addresses dialog appears
within the Data Watch Window.

2

Enter an address in the Starting
Address box.

This is the first in a range of addresses
to be added to the Data Watch Window.

3

Enter a numeric value (1 through 100)
in the Number of Addresses box.

This is the length of the range of
addresses to be added to the Data
Watch window.

4

Click OK.

Addresses specified are added at the
current grid location. Existing addresses
may be overwritten.

In the data watch window:
Step

Action

Result

1

Select the radices you want to change.

2

From the right-click menu, select Set
Radix.

3

Select a radix from the Radix drop-down list box.

4

Click OK.

The Set Radices dialog appears within
the Data Watch Window.

All selected radices are updated to the
specified radix.

In the data watch window:
Step

Action

Result

1

Select the addresses you want to delete.

2

From the right-click menu, select
Delete Addresses.

Selected addresses are deleted.

3

Or, Select an address and press
DELETE.

Selected address is deleted.

372 SPU 780 01EMAN May 2002

Using the Data Watch Window

Jumping to a
Specific Address

Copying Data
Values from One
Range of
Addresses to
Another

Moving Data
Values from One
Range of
Address to
Another

From the right-click menu:
Step

Action

Result

1

Select Goto Address.

The Goto Address dialog appears within
the Data Watch Window.

2

Enter an address in the Select an Address to find box.

3

Click OK.

The specified address is selected in the
Data Watch Window.

From the right-click menu:
Step

Action

Result

1

Select Data Utilities → Copy Data.

The Data Utilities dialog appears within
the Data Watch Window.

2

Enter an address into the Start
Address box.

The value of this address is the first in
the range to be copied.

3

Enter an address into the End
Address box.

The value of this address is the last in
the range to be copied.

4

Enter an address into the Destination The value of this address is the first to be
Address box.
copied to in the sequential range of
addresses specified.

5

Click OK.

Values are copied.

From the right-click menu:

372 SPU 780 01EMAN May 2002

Step

Action

Result

1

Select Data Utilities → Move Data.

The Data Utilities dialog appears within
the Data Watch Window.

2

Enter an address into the Start
Address box.

The value of this address is the first in
the range to be copied.

3

Enter an address into the End
Address box.

The value of this address is the last in
the range to be copied.

4

Enter an address into the Destination The value of this address is the first to be
Address box.
moved to in the sequential range of
addresses specified.

5

Click OK.

Values are moved.

179

Using the Data Watch Window

Filling a Range of
Addresses with a
Data Value

Searching for a
Data Value

180

From the right-click menu:
Step

Action

Result

1

Select Data Utilities → Fill Data.

The Data Utilities dialog appears within
the Data Watch Window.

2

Enter an address into the Start
Address box.

The value of this address is the first in
the range to be filled.

3

Enter an address into the End
Address box.

The value of this address is the last in
the range to be filled.

4

Enter a numeric value into the Data
Value box.

This value is copied into all specified
addresses.

5

Click OK.

Address values are set to the specified
value.

From the right-click menu:
Step

Action

Result

1

Select Data Utilities → Search Data. The Search Data dialog appears within
the Data Watch Window.

2

Enter a numeric value into the Data
Value box.

This is the value to be searched for.

3

Click OK.

The address with the specified data
value are selected in the Data Watch
Window.

372 SPU 780 01EMAN May 2002

Using the Data Watch Window

Properties
Using the Data
Watch Window
Properties
Dialog

Multi Radix View

In the navigation window:
Step

Action

1

Right-click the Data Watch Window icon.

2

Select Properties from the drop-down list.

3

When you have made your property changes: To save the proerty changes and
close the properties window, click OK. To save the property changes and remain
in the properties window, click Apply.

When the Multi Radix View check box is selected, the Watch Window and the
Register Editor are in Multi Radix view. A column is assigned for each selected radix
(Hexadecimal, ASCII, Long, Binary, and/or Float) as well as one for Decimal. Each
column displays the data value for the given address in the selected format. Radices
cannot be edited.
When the Multi Radix View check box is not selected, the Watch Window and the
Register Editor will be in Single Radix view. Only one radix will be viewable per
address. Any radix can be changed.

Changing the
View
(Single Radix vs.
Multi Radix)

Trigger

In the Data Watch Window Properties dialog:
Step

Action

1

Click the Multi Radix View check box.

2

Select which radices (Hexadecimal (Hex), Binary (Bin), ASCII (Asc), Float, and
Long) you would like to view.

3

Click OK to save the changes and return to the Data Watch Window.

When the Trigger check box is selected, the value of a specific address is tracked.
When the data for this address reaches the specified value, the Data Watch Window
begins tracking and/or logging values. The data is not tracked or logged until the
condition is met.
When the Trigger check box is not selected, the Data Watch Window automatically
tracks and/or logs values.

372 SPU 780 01EMAN May 2002

181

Using the Data Watch Window

Setting a Trigger
Condition

Clamps

In the Data Watch Window Properties dialog:
Step

Action

1

Click the Trigger check box.

2

Enter the address that you would like to track in the Address box.

3

Select the > or < option button.

4

Enter a numeric value in the State box.

5

Click OK to save the changes and return to the Data Watch Window.

When the Clamps check box is selected, all data values tracked are forced inside
or outside of the range specified. This affects the display only and does not affect
the actual data values in the device. This also affects the data sent to the log file.
When the Clamps check box is not selected, all data values are displayed as their
actual data value.

Setting a Clamp

In the Data Watch Window Properties dialog:
Step
1

Action
Click the Clamp check box.

2

Enter a numeric value in the Lo Clamp box.

3

Enter a numeric value in the Hi Clamp box.

4

Select the Capture Inside or Capture Outside option button.

5

Click OK to save the changes and return to the Data Watch Window.

Log File Size
Limit

This value places a size limit on the Log file. Once the limit is reached, no further
logging will be done. The limit is in Megabytes.

Setting the Log
File Size Limit

In the Data Watch Window Properties dialog:

182

Step

Action

1

Enter a numeric value (in Megabytes) in the Max Log File Size box.

2

Click OK to save the changes and return to the Data Watch Window.

372 SPU 780 01EMAN May 2002

Using the Data Watch Window

Sample Rate

Specifies how often to poll the device for data. The faster the polling is, the more
accurate the data is, but the client computers responses will become more sluggish.
This rate also affects the rate that data points are logged. The minimum sample rate
is one read every sixty minutes, and the maximum sample rate is one read every 25
milliseconds.
Note: This is a target sample rate. The actual sample rate may be slower than you
specify due to a large amount of data being polled and the capabilities of your
machine.

Setting the
Sample Rate

In the Data Watch Window Properties dialog:

372 SPU 780 01EMAN May 2002

Step

Action

1

Move the Sample Rate slider to the right for a slower sample rate or to the left
for a faster sample rate.

2

Click OK to save the changes and return to the Data Watch Window.

183

Using the Data Watch Window

HMI
HMI Overview

This view displays a simple Human-Machine graphical grid-based workspace. It
allows data to be displayed, data values to be entered, discrete controls to be
enacted and basic animation to be visualized.
Each cell in the grid may have a series of pictures assigned to it. These pictures are
selected based on the data value of an address assigned to the cell. Therefore, as
the data changes, the pictures will change as well. Animated switches, gauges,
meters and similar graphics are available.

Setting the
Background
Color

Setting the
Number of Rows
and Columns

Creating Bitmap
Files to
Associate with
Address Values

184

In the Data Watch Window Properties dialog:
Step

Action

1

Click the Background Color - Select button.

2

Choose a color from the Color dialog.

3

Click OK to close the Color dialog.

4

Click OK to save the changes and return to the Data Watch Window.

In the Data Watch Window Properties dialog:
Step

Action

1

Enter a numeric value into the Number of Rows box. (Max: 10, Min: 1)

2

Enter a numeric value into the Columns box. (Max: 10, Min: 1)

3

Click OK to close the Color dialog.

4

Click OK to save the changes and return to the Data Watch Window.

Use Windows Explorer to:
Step

Action

1

Ensure all files you want to associate with a cell are in the same directory.

2

Ensure the files you want to associate with a cell are named sequentially
Correct: Timer_1.bmp, Timer_2.bmp, Timer_3.bmp,... Timer_10.bmp
Incorrect: Timer.bmp, TTwo.bmp, TimerThree.bmp,... Time10.bmp
Tip: The easiest way to name bitmaps for use in the HMI is to use the
’BitmapName_#.bmp’ format.

372 SPU 780 01EMAN May 2002

Using the Data Watch Window

Editing Cell Data

From the right-click menu:
Step

Associating a
Picture with an
Address Value

Action

1

Select Edit Data.

2

Enter a value in the Picture box. (This will update the value of the address
associated with the picture.)

3

Enter a value in the Monitor box. (This will update the value of the address being
monitored.)

4

Press OK to save changes.

From the right-click menu:

372 SPU 780 01EMAN May 2002

Step

Action

1

Select Edit Cell.

2

Select the Picture Enabled check box.

3

Enter an address into the Address box.

4

Select from the Stretch Picture drop-down list box how you would like the
pictures to be displayed. (Selecting None will trim the bottom and the right-side
of the picture to fit, selecting Fit Cell will make the entire picture fit the cell,
selecting Fit Width will trim the bottom of the picture, and selecting Fit Height
will trim the right-side of the picture.)

185

Using the Data Watch Window

Associating a
Picture with an
Address Value
(continued)

After entering an address to associate a picture with:
If...

Step

Action

you have entered a 1
discrete address
(0xxxx or 1xxxx)

Click Off Picture → Browse and select a bitmap (.bmp
file) to view when the value of the selected address is 0
(zero).

2

Click On Picture → Browse and select a bitmap (.bmp
file) to view when the value of the selected address is
not 0 (zero).

3

Press OK to save changes.

1

Click Picture → Browse and select the first bitmap
(.bmp) in a numbered sequence of bitmaps.

2

Enter a number in the Actual Range boxes. (These are
the low and high data values you expect or know the
address will hold.)

3

Enter a number in the # of Pictures box. (This number
will be used to associate different sequentially named
pictures with values from the selected address.)
E.g. If you enter as an actual range the values 0 and
999, then enter 10 into the # of pictures box,
Picture1.bmp (the picture you selected in step 1) will be
associated with values 1 through 99, Picture2.bmp will
be associated with values 100 through 199, and so on.

4

Press OK to save changes.

you have entered
an analog address
(3xxxx or 4xxxx):

Note: A maximum of 100 pictures may be associated with a cell.

Adding a Caption
to a Cell

186

From the right-click menu:
Step

Action

1

Select Edit Cell.

2

Select the Caption Enabled check box.

3

Enter the text you want displayed in the cell in the Caption box (Maximum 20
characters).

4

Click the Foreground button to select the text color.

5

Select the positioning (Top, Middle, or Bottom) of the caption from the
Alignment drop-down list box.

6

Press OK to save changes.

372 SPU 780 01EMAN May 2002

Using the Data Watch Window

Adding a Value
to Monitor

From the right-click menu:

372 SPU 780 01EMAN May 2002

Step

Action

1

Select Edit Cell.

2

Select the Data Monitor Enabled check box.

3

Enter an address into the Address box. (This address may be the same as or
different than the address associated with the picture.)

4

Click the Foreground button to select the text color.

5

Enter numeric values into the Actual Range boxes. (These are the low and high
values you expect or know the address will hold.)

6

Enter numeric values into the Scale Range boxes. (You can use the scale range
to display a ratio value or an offset value for data analysis purposes. You can
also set the Scale range to the same values as the Actual range to display raw
data.)

7

Select the positioning (Top, Middle, or Bottom) of the caption from the
Alignment drop-down list box.

8

Press OK to save changes.

187

Using the Data Watch Window

Trend
Trend Overview

This view does not allow editing of any on-screen information. It is for viewing data
only. When active, this view will display a graphical line chart of data values. The
time that the data was taken is displayed on the X axis. The data value is displayed
on the Y axis as well as on the right hand legend. This is useful for tracking changes
in data over time. There are several Zoom and pan functions available.

Setting the
Y-Axis Values

In the Data Watch Window properties dialog:

Setting the Alarm
Values

Step
1

Click the Auto Y Axis Scale check box to have the Y Axis automatically set and
adjust to include all data points.
- or Enter a numeric value into the Y Axis Min and Y Axis Max boxes to manually
set the Y Axis range.

2

Click OK to save the changes and return to the Data Watch Window

The alarm values are a range of ’safe’ values. Any value that is outside of this range
triggers an alarm state.In the Data Watch Window properties dialog:
Step

Setting the
Setpoint Value

Enter a numeric value into the Lo Alarm and/or Hi Alarm boxes.

2

Click OK to save the changes and return to the Data Watch Window.

The setpoint value is a baseline value that can be used as a reference. In the Data
Watch Window properties dialog:
Action

1

Enter a numeric value into the Setpoint box.

2

Click OK to save the changes and return to the Data Watch Window.

The resolution value is in Milliseconds and defines the width of the X Axis. This is
the time window of the visible data.In the Data Watch Window properties dialog:
Step

188

Action

1

Step

Setting the
Resolution Value

Action

Action

1

Enter a numeric value into the Resolution box.

2

Click OK to save the changes and return to the Data Watch Window.

372 SPU 780 01EMAN May 2002

Using the Data Watch Window

Using the Graph
Functionality

In the trend window:

372 SPU 780 01EMAN May 2002

Step

Action

1

Select the Mode you want to use (Scroll-X, Zoom-X, Scroll-Y, Zoom-Y, ScrollXY, Zoom-XY, Cursor, or Zoom-Box).

2

Left-click the data point you want to work from.

3

Hold-and-drag to manipulate the on-screen view of the data.

189

Using the Data Watch Window

Trend - Mode Functionality Table
Data Watch
Window - Trend

190

Mode Functionality Table:
Mode

Description of Functionality

Plot

Default view. This is the setting used when viewing a live trend or logged
data. If viewing live data, the trend automatically updates and scrolls.
Selecting Plot also resets the view to the default by cancelling any scroll
or zoom operations.

Scroll-X

Drag the trend chart left or right to view trend data by time. Not available
while viewing live data.

Zoom-X

Compresses or expands the X (Time) axis. This allows for viewing more
detail or more data points. Not available while viewing live data.

Scroll-Y

Drag the trend chart up or down to view trend data that may be beyond
the bounds of the current Y axis. Not available while viewing live data.

Zoom-Y

Compresses or expands the Y (Value) axis. This allows for viewing more
detail or more data points. Not available while viewing live data.

Scroll-XY

This allows for scrolling of the X and Y axis simultaneously. Not available
while viewing live data.

Zoom-XY

This allows for zooming of the X and Y axis simultaneously. Not available
while viewing live data.

Cursor

Shows a cursor, the value of the data point and the time it was taken for
a given trend line. Specific trend lines may be selected from the legend on
the right. The cursor my be moved via the mouse, keys or navigation
buttons. Not available while viewing live data.

Zoom-Box

Use a selection box to zoom into a specific part of the trend. Not available
while viewing live data.

View Selected
Only Checkbox

When Checked, the trend only displays the plot of the address selected in
the legend on the right. When cleared, all address plots are displayed.
Only available in cursor mode with logged data.

372 SPU 780 01EMAN May 2002

Using the Data Watch Window

Track Logic Editor
Track Logic
Editor

When the Track Logic check box is selected, the specified addresses in logic are
automatically added to the Data Watch window and their values tracked. When the
cursor position in logic is changed, the previously tracked addresses are removed
and a new set of addresses are tracked. There are four logic-related options that can
be tracked:

l Network - All addresses and their values from the most recently selected network
in the Logic Editor are displayed in the Watch Window.

l Instructions - All addresses and their values that are associated with the most
recently selected instruction are displayed in the Instruction Window.

l Discrete - All addresses with discrete values associated with the most recently
selected network in the logic editor are displayed in the Watch Window.

l Address - The most recently selected address and its value is displayed in the
Watch Window.
When the Track Logic and Track Traffic Cop check boxes are not selected,
addresses must be entered manually into the Watch Window in order to be tracked.
Tracking Logic
Editor
Addresses in the
Data Watch
Window

In the Data Watch Window Properties dialog:

372 SPU 780 01EMAN May 2002

Step

Action

1

Select the Track Logic check box.

2

Select the option button (Network, Instruction, Discretes, or Address) that you
want to track.

3

Click OK to save the changes and return to the Data Watch Window.

4

Ensure that the Logic Editor and Data Watch Window are open.

191

Using the Data Watch Window

Track Traffic Cop
Track Traffic Cop

When the Track Traffic Cop check box is selected, the specified addresses in the
Traffic Cop are automatically added to the Data Watch window and their values
tracked. As the cursor position is changed in the Traffic Cop, the tracked addresses
are also changed. The traffic cop-related option that can be tracked is:

l Slot - The associated addresses of the card in the most recently selected slot are
displayed in the Terminal Block Window.
When the Track Logic and Track Traffic Cop check boxes are not selected,
addresses must be entered manually into the Watch Window in order to be tracked.
Tracking Traffic
Cop Addresses
in the Data Watch
Window

192

In the Data Watch Window Properties dialog:
Step

Action

1

Select the Track Slot check box.

2

Click OK to save the changes and return to the Data Watch Window.

3

Ensure that the Traffic Cop and Data Watch Window are open.

372 SPU 780 01EMAN May 2002

Using the Data Watch Window

Instruction Editor / Terminal Block Editor
Instruction
Editor Overview

You can view the addresses and data of specific Logic instructions using the
Instruction Editor.
Additionally, the DRUM Summary and the PID Summary can activate the Instruction
Editor for the DRUM or PID function selected in the summaries. Only the addresses
referenced by the current instruction will be included.
The display is built using a user-defined VB script. These scripts are editable and
may be used to modify the on screen display in any way.

Viewing an
Instruction in the
Instruction
Editor

The Instruction Window works hand-in-hand with the Logic Editor. To view a certain
instruction simply select the desired instruction in the Logic Editor and the instruction
will be displayed in the Instruction Window

Terminal Block
Editor Overview

You can view the addresses and data of specific I/O cards using the Terminal Block
editor. Depending on property settings, you can view addresses and edit address
values found in the currently selected item (rack or slot) in the Traffic Cop.
The display is built using a user-defined VB script. These scripts are editable and
may be used to modify the on screen display in any way.

Viewing an I/O
Card in the
Terminal Block
Editor

The Terminal Block Window works hand-in-hand with the Traffic Cop. To view a
certain card simply select the desired card in the Traffic Cop and the card will be
displayed in the Terminal Block Window.

372 SPU 780 01EMAN May 2002

193

Using the Data Watch Window

Instruction / Terminal Block Editor Display Scripts
Display Scripts
Overview

The Instruction and Terminal Block views may be customized using specialized VB
Script files (.ucs). A large variety of .ucs files are provided for common instructions
and for some advanced I/O cards. All .ucs files use a standard set of functions that
link into the PRWX32 Data editor to provide the on screen elements needed. As
well, all regular VB Script functions (such as FOR loops and IF statements) are
available.
Note: The script must follow standard VBS coding methods and rules.

Creating a
Display Script
File

Naming a Display
Script File

194

From your Windows Start menu:
Step

Action

1

Open a blank script in a script editor (Notepad or Wordpad).

2

Enter the outline of the new script function as follows:
Sub FunctionName(TopAddr, MidAddr, BotAddr, TopLen, MidLen,
BotLen, Page, Unused1, Unused2) End Sub

3

Add functions to the script as needed.
Note: All functions must be prefixed by ’Call Editor.’ E.g., Call Editor.scAddGrid.

4

Save the script in the ProWORX\32\Scripts directory using the naming
conventions laid out in ‘Naming a display script file’.

Rules and guidelines:
Step

Action

1

Script files must be saved with a .ucs extension. E.g., VMER.ucs

2

Instruction scripts must be saved using their machine name. E.g., Correct:
MSTR.ucs, Incorrect: Master.ucs

3

Script file names cannot have spaces or punctuation in them. E.g. Correct:
DAO84010.ucs, Incorrect: DAO 840 10.ucs, DAO-840_10.ucs

372 SPU 780 01EMAN May 2002

Using the Data Watch Window

Display Script Variables
Variable
Description
Table

Variables used within the display script:
Variable

Type

Description

FunctionName

NA

The function name must be the same as the name of the
instruction or I/O card it supports. E.g. For the ADD
instruction, the function name would be "ADD", and the
script file name would be Add.ucs.

TopAddr

String

Instruction Editor: The address in the top node of the
instruction.
Terminal Block Editor: For cards with input addresses only,
the first input address. For cards with output addresses
only, the first output address. For cards with both input and
output addresses, the first input address.

MidAddr

String

Instruction Editor: The address in the second node of the
instruction if second node exists.
Terminal Block Editor: First output address for cards
containing both input and output addresses.

BotAddr

String

Instruction Editor: The address in the third node of the
instruction if third node exists.
Terminal Block Editor: Empty.

TopLen

Integer

Instruction Editor: The number of implied addresses
associated with the address in the top node.
Terminal Block Editor: Empty.

MidLen

Integer

Instruction Editor: The number of implied addresses
associated with the address in the middle node.
Terminal Block Editor: Empty.

BotLen

Integer

Instruction Editor: The number of implied addresses
associated with the address in the bottom node.
Terminal Block Editor: Empty.

Page

Integer

If a page control is specified in this script using
’scAddPages’, this will give the page number to display.

Unused1, Unused2 Empty

Reserved Values.

Note: All of these parameters will pass data into the script

372 SPU 780 01EMAN May 2002

195

Using the Data Watch Window

Display Script Functions
Functions Used
Within the
Display Script

Note: All functions must be prefixed by ’Call Editor.’ E.g., Call Editor.scAddGrid

Note: All strings must be surrounded by quotes. E.g., Call Editor.scSetRowInfo(1,
1, "This is a string description", "Decimal")

scAddGrid
(Address,
NumRows,
VisibleRows)

scSetRowInfo
(GridIndex,
GridRow,
TextString,
Radix)

196

This is the main function used to display data values. It is responsible for adding a
grid of addresses along with their data values and radices. All radices will default to
decimal. Grids are numbered starting at 1 in the order that they are added. This
number is used as an ID for other functions such as ’scSetRowInfo’.
Variable

Type

Variable Description

Address

Integer

The first address in a sequential list of addresses.

NumRows

Integer

The number of rows (and addresses) to display in
this grid.

VisibleRows

Integer

This will limit the grid to showing only the number of
rows specified. Additional rows will be accessible
via scrolling.

This function modifies the contents of a specific row in a specific grid. The
Description and a specific Radix may be added with this function.
Variable

Type

Variable Description

GridIndex

Integer

This is the Grid’s ID Number. See ’scAddGrid’.

GridRow

Integer

The row in this grid to modify. Valid rows start at 1
and go to the maximum number of rows this grid
contains.

TextString

String

The Description text to add.

Radix

String

What radix to display the data in. Valid entries are:
"Hexadecimal", "Binary", "ASCII", "Float", "Long",
"Signed", "BCD", and "Decimal".

372 SPU 780 01EMAN May 2002

Using the Data Watch Window

scGetText
(TextIndex)

scAddBitDisplay
(BitDisplayName
, GridNumber,
GridRow,
LineState,
Editable)

scAddBitInfo
(BitDisplayName
, BitNumber,
BitDescription)

This retrieves internal PRWX32 text strings. Usually you should use a literal text
string ("Hello") instead of this function.
Variable

Type

Variable Description

TextIndex

Integer

The number of the internal text string you wish to
retrieve.

This will add an ellipsis button to the specified Grid on the specified Row. This button
activates a Bit Display dialog that gives detailed bit-by-bit descriptions and editing
capabilities.
Variable

Type

Variable Description

BitDisplayName

String

This is a name to be used to identify this particular
display. A script may create numerous different Bit
Displays.

GridNumber

Integer

This is the Grid’s ID Number. See ’scAddGrid’.

GridRow

Integer

The row in this grid to modify. Valid rows start at 1
and go to the maximum number of rows this grid
contains.

LineState

String

A string of 16 numeric characters. The first
character is the MSB. Each character may be one
of:
l "0" - No Line
l "1" - Horizontal Stub
l "2" - Full Line
l "3" - End Stub

Editable

Boolean

Set to "True" to enable bit editing. Set to "False" to
make the display read only.

This adds a bit description to the contents of a specified Bit Display created with
’scAddBitDisplay’.

372 SPU 780 01EMAN May 2002

Variable

Type

Variable Description

BitDisplayName

String

This is a name to be used to identify this particular
display. See ’scAddBitDisplay’.

BitNumber

Integer

The number from 1 to 16 of the bit to add the
description to. 1 = LSB.

BitDescription

String

The description text to add.

197

Using the Data Watch Window

scAddBitEditValue
(BitDisplayName
, BitNumber,
FirstBit, LastBit,
Description,
Value)

scAddEquation
(EquationStr,
Var1, Var2, Var3,
Var4, Var5)

198

This creates a drop-down list box for a specified bit in the specified Bit Display. This
box may be used to set a block of bits to a specific pattern associated with a
descriptive state. Only one list entry is added per call. Entries are added in
sequential order.
Variable

Type

Variable Description

BitDisplayName

String

This is a name to be used to identify this particular
display. See ’scAddBitDisplay’.

BitNumber

Integer

The number from 1 to 16 of the bit to add the
description to. 1 = LSB.

FirstBit

Integer

The first bit number in a sequence to be modified
(MSB).

LastBit

Integer

The last bit number in a sequence to be modified
(LSB).

BitDescription

String

The description of the list entry.

Value

String

The binary pattern to set the bits to. (E.g.:
"110110")

This will create a functional equation in a box. Up to 5 variables may be included.
Variable

Type

Variable Description

EquationStr

String

A string containing the equation to display. Use "A",
"B" through "E"" to denote a variable. Variables will
be mapped to the data in a Grid row. (E.g.: "A + B
= C")

Var1 through Var5

String

A string in the format "a,b,r" where a=Grid ID
Number, b=Grid Row, r=Radix: "ILDF". The radix
value specifies the radix to display the equation
data in. Integer, Long, Double, or Float. Double is
not a normal radix. It builds a concatenation of 2 16
bit data values. These will be the data values that
appear in the equation. Use "" for variables that are
not used.

372 SPU 780 01EMAN May 2002

Using the Data Watch Window

scAddErrorField
(GridNumber As
Variant, GridRow
As Variant)

This will create an error box that displays an error message. This box will only be
visible if an error condition is met. Conditions are specified using the ’scAddErrorFieldText’ function. Error conditions are a particular value contained in a particular
register. A row in a grid defines this. Only one Error Field is allowed.
Variable

Type

Variable Description

GridNumber

Integer

This is the Grid’s ID Number. See ’scAddGrid’.

GridRow

Integer

The row in this grid to modify. Valid rows start at 1
and go to the maximum number of rows this grid
contains.

scAddErrorFieldText
(DataValue As
Variant,
ErrorText As
Variant)

This adds an error condition to an error field. Any number of conditions may be
added. A condition is true is a data value equals the specified value.

scAddPages
(NumPages)

This adds a Page selection control. Only one may be specified at a time. Pages are
numbered sequentially starting at one. This is useful if an instruction has a large
amount of information to display.

scAddPicklist
(ListName,
GridNumber,
GridRow)

Variable

Type

Variable Description

DataValue

Integer

A value that corresponds to an error.

ErrorText

String

The error message to display.

Variable

Type

Variable Description

NumPages

Integer

The total number of pages to display.

This will add a drop-down list box to a specified Grid at a specified Row. This list will
allow the easy selection of specific data values for the associated address. Each
pick list must be identified by giving it a name.

372 SPU 780 01EMAN May 2002

Variable

Type

Variable Description

ListName

String

This is a name to be used to identify this particular
pick list. A script may create numerous different
pick lists.

GridNumber

Integer

This is the Grid’s ID Number. See ’scAddGrid’.

GridRow

Integer

The row in this grid to modify. Valid rows start at 1
and go to the maximum number of rows this grid
contains.

199

Using the Data Watch Window

scAddToList
(ListID, ListText,
ListValue)

scAddStaticText
(TextSting)

200

This will add a data value to a pick list created with ’scAddPickList’.
Variable

Type

Variable Description

ListID

String

This is a name to be used to identify this particular
pick list. See ’scAddPickList’.

ListText

String

Text that will be appear in the List. Usually it
describes the purpose of a data value.

ListValue

Integer

A data value that will be set if this list entry is
selected.

This will add a static block of text. This is useful for titles, instructions, or additional
information not provided by any other means.
Variable

Type

Variable Description

TextString

TextString

The text to display.

372 SPU 780 01EMAN May 2002

Using the Data Watch Window

Register Editor
Register Editor
Overview

The Register Editor allows you to view and edit data for all available addresses. This
includes all discretes as well as all input, holding and extended registers.
Note: Addresses cannot be edited since they are specified by a project’s
configuration.

Changing the
Displayed
Address Type

In the Register Editor Window task bar:
Step
1

Displaying
Extended
Memory
Addresses

Action
Select an address type (0x, 1x, 3x, 4x, 6x) option button.
Note: Extended memory addresses are defined by memory file.

In the Register Editor Window task bar:

372 SPU 780 01EMAN May 2002

Step

Action

1

Select the 6x option button from the status bar.

2

Choose an extended memory file from the File drop-down list.

201

Using the Data Watch Window

PID Tuner
PID and PID2
Blocks Overview

PID and PID2 blocks are software programming blocks that allow a process tobe
controlled with no changes or additions to hardware. "PID" stands for "Proportional
Integral Derivative". While the PID2 is a more advanced version of the PID, both
operate in the same manner.
PID/PID2 Process
Process Input
Set Point (SP)

PID
Calculation

Output Value (OP)

Process Variable
(PV)

Process
Measurement
Process Output

The PID calculation compares a process variable (PV) with a desired control point
called the set point (SP). The calculation uses the difference between the set point
and the process variable to adjust the PID output value (OV), sometimes called the
control variable. This output value is used to manipulate an input to the process so
that, eventually, the measured process variable equals the desired set point.
PID Tuner
Overview

The PID summary displays a list of all the PID and PID2 instructions in the logic of
the current project. Each row in the grid gives the instruction name, its location in
logic, and the addresses of key data values related to that PID block.
The currently selected row has an associated PID Faceplate. This faceplate allows
simple tuning of the selected PID block. You may invoke manual mode or adjust the
setpoint value.
Note: There may be a delay while a search is performed for PID instructions in
logic.

202

372 SPU 780 01EMAN May 2002

Using the Data Watch Window

Adjusting the
Setpoint Value

In the PID Summary Window:
Step

Action

1

Click the Adjust button.

2

Click and drag the slider up to increase the setpoint and down to decrease the
setpoint.

Jumping to the
Currently
Selected PID
Block in the
Logic Editor

In the PID Summary Window:

Editing PID Data

In the PID Summary Window:

Step

Select the row of the PID or PID2 instruction that you want to jump to.

2

Click the Goto button. (The Logic Editor is activated and the cursor is positioned
on the selected PID block.)

Step

Trending PID
Data

Action

1

Action

1

Select the row of the PID or PID2 you want to edit

2

Click the Tune button. The Instruction Editor is activated containing the selected
PID or PID2 instruction. Here you may edit all data values related to the
instruction.

3

Click PID Summary tab to exit the Instruction window.

In the PID Summary Window:

372 SPU 780 01EMAN May 2002

Step

Action

1

Select the row of the PID or PID2 you want to trend.

2

Click the Trend button. The Trend Window is activated showing the trend data
of the selected PID or PID2.

3

Click PID Summary tab to exit the Instruction window.

203

Using the Data Watch Window

Setting the PID
Contact

204

In the PID Summary Window:
Step

Action

1

Click the Force Input Contact check box.
Note: This overrides the contact setting by disabling the contact. Ensure that this
does not result in any safety issues.

2

The default contact setting is Auto. To toggle the contact click the Auto/Manual
button. The label on the button specifies the current state of the contact. Auto =
ON, Manual = OFF. Adjusting this disables the contact immediately in front of the
top node of this PID instruction and forces it ON or OFF.

372 SPU 780 01EMAN May 2002

Using the Data Watch Window

DRUM Summary
DRUM
Instruction
Overview

The DRUM instruction operates on a table of 4x registers containing data
representing each step in a sequence. The number of registers associated with this
step data table depends on the number of steps required in the sequence. You can
pre-allocate registers to store data for each step in the sequence, thereby allowing
you to add future sequencer steps without having to modify application logic.
DRUM incorporates an output mask that allows you to selectively mask bits in the
register data before writing it to coils. This is particularly useful when all physical
sequencer outputs are not contiguous on the output module. Masked bits are not
altered by the DRUM instruction, and may be used by logic unrelated to the
sequencer.

Drum Summary
Overview

The DRUM summary displays a list of all the DRUM, ICMP and SCIF instructions in
the logic of the current project. They are sorted by their top address. This address’
data is known as its ’Step’ value. All instructions with the same Step value appear
together on the right. All the Step values that are available appear on the list to the
left.
Each row shows the instruction name, its location in logic, and key data values
related to that block. ’Steps Used’, ’Machine ID’. and ’Profile ID’ are all editable
values.
Note: There may be a delay while a search is performed for DRUM instructions in
logic.

Selecting a Step

In the DRUM Summary window:
Step
1

372 SPU 780 01EMAN May 2002

Action
Select an address from the left panel and all applicable instructions referencing
that address will be displayed.

205

Using the Data Watch Window

Editing DRUM
Summary Data

Editing
Instruction
Address Data
Value

206

In the DRUM Summary window:
Step

Action

1

Double-click the Steps Used, Machine ID, or Profile ID cell that you want to
edit.

2

Enter a value into the cell.

3

Press ENTER to save the changes, or ESC to cancel the changes.

In the DRUM Summary window:
Step

Action

1

Select the instruction you want to edit.

2

Click the Sequencer button.

3

In the Instruction Window, double-click the Data cell that you want to edit.

4

Enter a value into the cell.

5

Press ENTER to save the changes, or ESC to cancel the changes.

6

Click the DRUM Summary tab to exit the Instruction Window.

372 SPU 780 01EMAN May 2002

Using the Data Watch Window

Importing and Exporting Data Watch Window Data
Overview

Data watch window data can be imported or exported to or from a text file. This file
may be modified with any text editor or spreadsheet program such as Notepad or
Microsoft Excel.
Importing data watch window data is only available from the data watch window
and register editor when in offline mode. Exporting data watch window data is
available when in either online or offline mode.

Importing Data

From the data watch window right-click menu:
Step

Exporting Data

Action

1

Select Data Utilities → Import Data.

2

Select a file (.txt or .csv) to import.

3

Click Open.

4

Data from every address found in the Import file is imported regardless of which
addresses are on the screen prior to the import. Any address in the Import file
that is in the configured range of the Project being imported to will have its data
imported. A progress bars displays the progress of the import.

From the data watch window right-click menu:
Step
1

Select Data Utilities → Export Data.

2

Enter a new file name or select an existing file (.txt or .csv).

3

Click Open.

4

372 SPU 780 01EMAN May 2002

Action

The data is exported as follows:
Data Watch Window (Offline) - All addresses and data values currently
shown in the data watch window are exported. If there are no addresses,
nothing is exported.
l Data Watch Window (Online) - All addresses and data values currently
shown in the data watch window are exported. If there are no addresses,
nothing is exported. Note that the exported data is a snapshot of the data
values in the PLC.
l Register Editor (Offline) - All addresses and data values for the selected
address type are exported. For example, if the 4x type is selected, all
configured 4x addresses and data will be exported.

l

207

Using the Data Watch Window

Data Formats

Data watch window data import and export file formats:
File

208

Format

.TXT - Tab Separated Variable text file.

Address  Data

.CSV - Comma Separated Variable text file.

Address,Data

372 SPU 780 01EMAN May 2002

Working with the ASCII Editor

ASCII Editor
Using the ASCII
Editor

ASCII messages let your controller report information to you in plain language. Use
them, for example, if you want to see a written alert on your screen every time a
motor switches on or a printout every hour of how many items have passed by a
counter.
Use the ASCII Message Editor to enter and edit the messages you want your
controller or project to send.
Note: Use the ASCII Read Block (READ) and ASCII Write Block (WRIT) in your
ladder logic to send a message from a controller to your output device (such as a
screen, printer, or disk drive).

Configuring
ASCII Messages

Start by configuring your controller or project to use ASCII messages:

372 SPU 780 01EMAN May 2002

Step

Action

1

Confirm that your controller supports ASCII messages.

2

In the Controller Configuration Window → General Tab, configure the
controller’s ASCII parameters. (Total Messages, Message Words, and ASCII
Ports.) For more information see, Controller Configuration - General Tab.

3

Ensure your ASCII ports are configured correctly in the Ports tab of the Controller
Configuration Window. For more information, see Controller Configuration Ports Tab.

209

Working with the ASCII Editor

Message List

The message list panel contains all messages in the current project. Click a
message to edit or preview it in the Editor / Preview window.
Note: A yellow message denotes a message that has too many words.
From the right-click menu:

Editor/Preview
Window

To...

Function

Result

Cut/Copy/Paste
messages:

Select cut, copy, or paste

The message is added to the
windows clipboard and can be
pasted into any other message.

Insert a message:

Select Insert (INSERT)

Shuffles the messages up from
the selected message.

Clear a message:

Select Clear (DELETE)

Deletes all words from the
selected message.

Delete a message:

Select Delete (SHIFT+DELETE)

Deletes the selected message
and moves messages up.

Initialize all
messages:

Select Initialize

Clears all messages.

The editor window is a WYSIWYG message editor. Enter instructions into the editor
by using either the toolbox buttons or the keyboard hot keys. The preview window is
a view-only preview display of the currently selected ASCII message. To toggle
between the editor and preview windows, right-click the desired message and select
Preview or Editor.
Note: Instructions placed after a carriage return will be ignored.

Note: Do not confuse blank cells with spaces. Blank cells will be removed when
the message is saved.

210

372 SPU 780 01EMAN May 2002

Working with the ASCII Editor

ASCII Editor
Toolbox

To insert an item either click the corresponding button or press the hot-key. Items
are inserted at the cursor.

372 SPU 780 01EMAN May 2002

Tool

Description

Text Box

Up to 128 characters of text is displayed.

Button

Hot-Key
T

Binary

A placeholder for a binary field. Defined in
ladder logic using a WRIT instruction.

B

Octal

A placeholder for an octal field. Defined in
ladder logic using a WRIT instruction.

O

Integer

A placeholder for an integer field. Defined in
ladder logic using a WRIT instruction.

I

Hexadecimal

A placeholder for a hexadecimal field. Defined
in ladder logic using a WRIT instruction.

H

Leading 0
Integer

A placeholder for a leading 0 integer field.
Defined in ladder logic using a WRIT
instruction.

L

ASCII

A placeholder for an ASCII field. Defined in
ladder logic using a WRIT instruction.

A

Space

Consecutive blank spaces are displayed.

SPACE

Carriage
Return

Moves cursor to the next line.

ENTER

Repeat

A repeat is denoted by a repeat start ({) and a
repeat end (}). A repeat must have both a start
and an end.

{ - Start
} - End

Control

A control character is displayed.

CTRL

Flush

The message buffer contains a 256 byte data
field. These bytes contain data values ranging
from 00 to FF. The flush command clears all
characters form the message buffer.

BACKSPACE

Flush Num
Bytes

Removes from 1 through 255 bytes from the
beginning of the message buffer.

N/A

211

Working with the ASCII Editor

Tool

Tool Properties

212

Description

Button

Hot-Key

Flush Inclusive Clears specific groups of data from 1 to 255
times, or until a match is found. The terminator
value determines how many times the buffer is
flushed. The controller stops the buffer flushing
when it finds a match for the terminating
characters.

N/A

Flush
Exclusive

N/A

Clears the buffer until a match is found for the
terminating character pair. It does not flush the
match characters. This uses two registers. The
first register contains the type identifier and the
second contains the hex values of the
terminating pair. The hex values range from
0000 to FFFF. The controller searches for this
range in the buffer. If the second character of
the match pair is not a null (00), then the next
character in the buffer must be equal or the
search continues. If the last character test is
equal or null, the flush is performed up to but
not including the matched terminators.

Each tool has specific properties that are editable using the properties panel.
Changing a tools properties will automatically update the message editor and
preview windows.

372 SPU 780 01EMAN May 2002

Working with Macros

At a Glance
Overview

When writing logic networks, you may find yourself reusing pieces of code again and
again, changing addresses only for a few of the variables. In these cases,
subroutines might not be suitable-such as when large numbers of variables are
involved or when you want to reuse the same piece of code in different projects.
What you’re looking for is a macro.

What’s in this
Chapter?

This chapter contains the following topics:

372 SPU 780 01EMAN May 2002

Topic

Page

Macros

214

Using Macros in Logic

216

213

Working with Macros

Macros
Overview

Macros are generic pieces of logic networks you create with parameters instead of
actual addresses. Macros are programmed offline in the Logic Editor. When you
insert a macro in your main project, you map the parameters to real addresses. You
can insert the same macro in several places with different sets of mapped addresses
each time. The addresses change but the logic stays the same.
The main project retains its link to the inserted macros. This means ProWORX 32
notices if you make changes to a macro and informs you when you view it in the
Logic Editor.

Creating a Macro
Project

Editing a Macro

To create a macro project:
Step
1

Create a new ProWORX 32 offline project by selecting File → New Project from
the ProWORX menu. For more information about creating projects, see Creating
a New Project, p. 29.

2

Select the Use as a Macro checkbox and complete the remaining new project
wizard steps.

3

Once a macro project has been created it is denoted by the macro project icon,

In general, you edit a macro with the same tools as a regular project. However,
several ProWORX 32 functions are disabled when editing a macro project. Among
them are:

l
l
l
l
l
l
l
l

214

Action

Traffic Cop
Config Extensions
ASCII Functions
Extended Memory
PLC Status
I/O Drawing Generator
Analyze Device
Reading and Writing

372 SPU 780 01EMAN May 2002

Working with Macros

Using Macro
Parameters

While editing macro projects, you can assign macro parameters in place of register
addresses or symbols. These are the addresses that will change for each insertion
into the main project.
Macro parameters use this format: @txx

l The "t" represents the type of address: 0 for 0xxxx, 1 for 1xxxx, 3 for 3xxxx and 4
for 4xxxx.

l The "xx" represents the parameter number, which can be from 1 to 50.
For example, a macro parameter of @304 would represent the fourth programmable
address of the form 3xxxx. Note that @304 and @404 refer to different parameters
and are mapped to totally different addresses.
You can have a total of 200 parameters in your macro project - 50 for each address
type.

372 SPU 780 01EMAN May 2002

215

Working with Macros

Using Macros in Logic
Adding Macro
Projects to Logic

Insert macros into logic while working offline in the Logic Editor. To insert a macro
into a ProWORX 32 project:
Step

Removing Macro
Projects from
Logic

1

Select Insert → Macro from the logic editor right-click menu. The Available
Macros list appears.

2

Select a macro from the list and click OK. The Macro Parameters dialog
appears.

3

For each parameter, enter a Modicon address in the Address column.

4

When all the parameters have been mapped to Modicon addresses, click Insert.
ProWORX 32 checks each address to ensure it’s valid for the macro parameter’s
address type and range. If invalid addresses are found, you are returned to the
Macro Parameters dialog box. Otherwise, the macro’s logic is inserted into your
ProWORX 32 project and you are taken to the Macro Overview screen.

Deleting a macro from a project doesn’t erase the macro file from your hard drive it just removes an inserted macro’s logic from your main logic. To remove a macro
completely from your hard drive, first remove it from the project as described below,
then from the macro project right-click menu in the Navigation panel, select Delete.
To remove a macro from a ProWORX 32 project:
Step

216

Action

Action

1

Select the macro you want to delete and select Delete Macro from the network
navigation panel right-click menu. A confirmation dialog appears.

2

Click Yes and the macro is removed from the project.

372 SPU 780 01EMAN May 2002

Working with Macros

Logic Editor
Macro Display
Overview

The Macro Overview display appears in the Logic Editor when you move the cursor
onto an inserted macro. It also appears just after inserting a macro into a project.
This display gives the macro’s file name, description (the "Detailed Project Name"
as entered from the project properties), status, and a list of its parameters and the
Modicon addresses or symbols to which they are mapped.
The macro status can be one of two things:

l Macro has changed: The macro has been changed since it was inserted into the
main logic network. You may want to update the inserted macro to reflect the
changes made to the macro project it is linked to.
l Macro not found: The macro project file either no longer exists or has been
moved to a different directory.
Making Changes
in Macros

If you make changes to a macro project after it has been inserted into a main logic
network, you’ll have to update each copy of it within that logic network.
There may also be times when you want to make changes in logic to a single macro
insertion without changing the original macro project. In this case, you’ll have to
unlink that macro insertion. Unlinking a macro removes its connection to the original
macro project; the logic in that macro insertion becomes part of the regular main
project logic.
Once a macro insertion has been unlinked it cannot be re-linked. Changes made to
the macro project will no longer be detected by the Logic Editor.

Updating a
Macro in a
Project

In the logic editor:

372 SPU 780 01EMAN May 2002

Step

Action

1

Move the cursor onto a macro that needs to be updated. The Macro Overview
screen appears, with a status that reads "Macro Has Changed." (If the macro
status reads "Rec: xxx", where "xxx" is a series of numbers, then you don’t need
to update it.)

2

From the network navigation panel right-click menu, select Update Macro. The
macro’s logic is reinserted into the logic network.

217

Working with Macros

Unlinking a
Macro from a
Project

218

Note: Once you’ve unlinked a macro, you can’t re-link it.
Step

Action

1

While in the Logic Editor, move the cursor onto the macro you want to unlink. The
Macro Overview screen appears.

2

From the network navigation panel right-click menu, select Unlink Macro. A
confirmation dialog appears.

3

To unlink all macros, select Unlink All Macros from the network navigation rightclick menu.

4

Click Yes to confirm the unlink. The macro is unlinked and the Macro Overview
display disappears and you are returned to the Logic Editor.

372 SPU 780 01EMAN May 2002

ProWORX 32 Utilities

At a Glance
Overview

This chapter gives an in-depth look at the following ProWORX 32 Utilities:

What’s in this
Chapter?

This chapter contains the following topics:

372 SPU 780 01EMAN May 2002

Topic

Page

BM85 Setup

220

BootP Server

223

Compare Utility

226

I/O Drawing Viewer

228

The Ping Utility

229

MBP Stat

230

219

ProWORX 32 Utilities

BM85 Setup
Overview

A BM85 Bridge Multiplexer allows you to connect up to four Modbus devices or
networks of Modbus devices to a Modbus Plus network.
The BM85 Setup utility is used to configure a BM85 device. BM85 Setup can be run
as either a stand-alone application (BM85_Setup.exe in the ProWORX\32 directory)
or as a utility in the utility menu.

Working with the
BM85
Configuration
Dialog

Setting up the
BM85

220

In the BM85 Configuration Dialog;
To:

Action

Read current settings from the BM85,

Click Read from MUX.

Write configuration settings to the BM85,

Click Write to MUX.

Print configuration settings,

Click Print.

Save configuration settings to .mux file,

Click Save to File.

In the BM85 Configuration Dialog:
Step

Action

1

Select a Communications Port from the Communications Port drop-down box.

2

Enter a path and file name into the File Name box or click Browse to find a .mux
file.

3

To create a new .mux file, click Browse, navigate to the folder you want the file
to reside in and Enter a file name (*.mux) into the File Name box. When asked
if you want to create this file, click Yes. You can now edit the generic settings.

4

To retrieve and display the current settings of the BM85, click Read from MUX.

372 SPU 780 01EMAN May 2002

ProWORX 32 Utilities

Configuring the
Modbus Ports of
a BM85

Configure each of the BM85’s four ports by editing the parameters below:
Parameter
Port Type

372 SPU 780 01EMAN May 2002

Description
Selects the Modbus device that attaches to the port:
Master - Select for a master device, such as a PC
Slave - Select for a slave device, such as a PLC
Network - Select for a network of slave devices connected through a
modem
l X-Master - Select for a device in Silent Master mode

l
l
l

Address‘

Sets the address of a slave device from 1 to 247. Only available when
Port Type is Slave.

Baud Rate

Sets the speed of data transmission in bits per second. The default is
9600.

Stop Bits

Sets the number of bits at the end of a packet which prepare the
receiving device for the next packet. Either 1 or 2.

Parity

Adds a check bit to a packet to make the number of binary ones always
either odd (Odd Parity) or even (Even Parity). If Parity is set to None, the
check bit is not added. The PC and controller must use the same parity.
Default is None.

Data Mode

Selects a communications mode for the port: RTU or ASCII. Default is
RTU.

Priority

Determines the order in which the BM85 checks the ports, with 1 being
the highest priority and 4 the lowest. All ports must have different
priorities.

Link Time-out

Sets the maximum time in multiples of 100 milliseconds that the BM85
waits for slave devices to respond to commands before it sends an error
message.

Modem Booster

Determines whether the BM85 maintains a dedicated connection to a
slave device until it completes a command or transparently processes
other network traffic while it waits. This option is not available unless the
port type is set to Network. Note that this option should be set to No for
ports attached to 584 controllers operating in SAFE84 Mode.

221

ProWORX 32 Utilities

Working with
Routing Paths

Communicating
with the BM85

222

In the BM85 Configuration Dialog:
To:

Action:

Add a routing path

Select a table from the Table drop-down box, and an address
from the Address drop-down box. Enter a routing path in the
Installed Routing Path box. Click Add.

Remove a routing path

Select a routing path from the Address list box and press
DELETE or click Remove.

If you are having trouble communicating with the BM85:
Step

Action

1

Make sure the COM port selected is plugged into the BM85.

2

Make sure the port on the BM85 you are plugged into is in configure mode. Set
MODBUS Port Configuration switches on the BM85 to CONFIGURE, PORT 1,
9600 BAUD, NO PARITY, 1 STOP BIT (All off).

372 SPU 780 01EMAN May 2002

ProWORX 32 Utilities

BootP Server
Overview

ProWORX 32 supports the configuration of the IP Address of a Quantum NOE
Ethernet adapter, an ENT module or a Momentum controller via an Ethernet
network. The BootP server lets you record and configure a device’s IP Address and,
optionally, the Gateway IP Address and Sub network mask.

Using the BootP
Server

In the navigation panel, utilities tab:
Step

Action

1

Select Boot P to open the BootP Server utility.

2

To enable active pinging of devices in the list, select the Enable Active Device
Ping check box.

3

To check if there is a device at the specified IP address, click Ping. If successful,
the status field displays ‘Device found at specified IP Address’.

4

To exit the BootP Server utility, click Close.

BootP Listening

When a BOOTP client such as a PLC requires an IP address, it broadcasts a request
for an address across its Ethernet connection and through the TCP/IP network. It
continues broadcasting these requests periodically until a reply is received or a set
amount of time has passed. In the case where a PLC has a TCP/IP configuration
extension active, the information in the extension may be used to configure an IP
address if a BootP response is not received. The BOOTP Server listens for these
IP address requests and responds accordingly. The response includes an IP
address for the client. When the response is received, the client uses this new IP
as its own and may then be accessed normally through the TCP/IP network.

Using BootP
Listening

In the BootP Server utility:

372 SPU 780 01EMAN May 2002

Step

Action

1

Click Start Listening to make the BOOTP Server listen for incoming IP
requests. The BOOTP Server now responds to any BOOTP IP address requests
coming from Modicon devices.

2

Click Stop Listening and the BOOTP server ignores any incoming requests.

223

ProWORX 32 Utilities

Automatically
Checking IP
Addresses

In the BootP Server utility:
Step
1

Using the Device
List

224

Action
Click Enable Active Device Ping. This periodically pings each IP address in the
list. The status of the device located at the address is reported back in the Status
field.
Tip: Use Enable Active Device Ping when performing automatic BootP
operations. Once a BootP operation is complete, the success of the operation is
updated in the Status column in the list.

In the BootP Server utility:
Step

Action

1

To add a device to the BootP list, click New Device.

2

To remove a device from the BootP lists, select a device from the list and click
Delete Device.

3

To configure a device in the BootP list, select a device from the list and enter the
parameters into the available Device Info and Optional Parameters fields. For
parameter descriptions, see ‘Device Parameters’.

4

To have the ability to write the Gateway address and the Subnet mask to the
device, select the Write Optional Parameters check box, otherwise these
parameters are unavailable.

372 SPU 780 01EMAN May 2002

ProWORX 32 Utilities

Device
Parameters

BootP device parameter descriptions:

372 SPU 780 01EMAN May 2002

Parameter

Description

Device

Displays the description of the associated row selected in the BootP
Parameters table.

MAC Address

A 12 digit hexadecimal number uniquely identifying an Ethernet device. A
device’s MAC address cannot be changed. The MAC Address is on a label
(currently marked as the "IEEE GLOBAL ADDRESS") on each Schneider
Ethernet device.

IP Address

A logical 32-bit address used to identify a TCP/IP device. Each IP address
has two parts: the network ID and the host ID. The network IP identifies all
hosts (devices) that are on the same physical network. The host ID
identifies a specific host on a network. Each computer that runs TCP/IP
requires a unique IP address.
The IP Address may be available from or assigned by your network
administrator.

Status

The existing condition of the ping:
l Device Found: ProWORX 32 has found a Schneider device with this
MAC address and IP address
l Device not found: ProWORX 32 could not find a Schneider device with
this MAC address and this IP address.

Subnet Mask

Used to mask a portion of the IP address so that TCP/IP can distinguish
the network ID from the host ID. TCP/IP hosts communicate by using the
subnet mask to determine whether the destination host is located on a
local or remote network.
The Subnet Mask may be available from or assigned by your network
administrator.

Gateway

For communication with a host on another network, an IP host must be
configured with a route to the destination network. If a configured route is
not found, the host uses the gateway to transmit the traffic to the
destination host. The default gateway is where the IP sends packets that
are destined for remote networks. If a default gateway is not specified,
communications are limited to the local network.
The Gateway may be available from or assigned by your network
administrator.

225

ProWORX 32 Utilities

Compare Utility
Overview

ProWORX 32’s Compare function finds differences in logic and configuration
between a project and a controller or between two projects or between two
controllers. This powerful tool lets you be sure that your controllers are using the
right logic and are configured properly, and that a local project is the same as your
operation’s master project.
The compare function examines any or all of these elements:
Networks

Using Compare

Controller configuration

Coil state - Up to four ranges, each range 1 - 1600

DX instructions

Input state - Up to four ranges, each range 1 - 256

Traffic cop

3xxxx registers - Up to four ranges, each range 1 - 99

Segment Scheduler

4xxxx registers - Up to four ranges, each range 1 - 1800

ASCII port parameters

Coil disable - Up to four ranges, each range 1 - 1600

ASCII messages

Input disable - Up to four ranges, each range 1 - 256

In the utilities menu, select Compare:
Step

226

Coils used - Up to four ranges, each range 1 - 1600

Action

1

To view all of the elements, click Advanced.

2

To compare an element, select its checkbox. To compare all elements, click
Toggle.

3

To view the master databases existing compare report, select View Report.

4

To compare two projects, click Compare Browse and select a project from the
Master Project list. Click To Browse and select a project from the Compare
Project list. Deselect both Online checkboxes and click OK.

5

To compare a project and controller, follow step 4 but select the To, Online
check box.

6

To compare two controllers, follow step 4 but select the Compare, Online and
To, Online check boxes.

7

To run the compare, click OK.

372 SPU 780 01EMAN May 2002

ProWORX 32 Utilities

Using the
Compare Report

After selecting OK in the compare utility:
Step
1
2

Action
After clicking OK to run the compare from the compare setup menu, the compare
report is displayed in your default browser.
- Elements match.
- Element mismatch.
- Element compare not applicable.
- Element not compared.

372 SPU 780 01EMAN May 2002

3

For elements that are mismatched, click the text link to see mismatch element
details.

4

To print the compare report select File → Print from the compare index page.
To include the whole report select the Print all linked documents under the
Options tab in the Print dialog. Click Print.

227

ProWORX 32 Utilities

I/O Drawing Viewer
Overview

The drawings are in a .DXF format that is supported by most CAD programs. The I/
O Drawing Generator uses the master .DXF drawings to create I/O drawings based
on the I/O Configuration and Documentation information. Once the final .DXF
drawings are created, they can be imported using your CAD program.
This dialog box displays the I/O drawing for the current card. It also allows you to
print the displayed portion of the current .DXF drawing using the default Windows
printer settings. Several options are available to allow you to view your drawings.
Pan allows you to scroll the view of the drawings displayed in much the same way
as Autocad. Zoom allows you to zoom in on a selected section of the drawing. Zoom
Out takes you back to display the complete .DXF drawing.

Using the I/O
Drawing Viewer

228

From the Navigation panel, Utilities menu:
Step

Action

1

Select I/O Drawing Viewer to open the I/O drawing viewer.

2

To pan across the drawing, click Pan. Click the location you want to begin your
pan view. Drag the cursor to another location in the drawing and release the
mouse button. The view pans from the start location to your end location.

3

To zoom into the display, click Zoom. Click at the start location where you want
to begin your zoom. Drag your cursor to mark the area. A rectangle appears to
define the section of drawing you want to zoom in on. Release the mouse button.

4

To zoom out of the display, click Zoom Out.

5

To select a different .DXF drawing, from the I/O Drawing Display window, click
Open. The File Open dialog box appears. Select the .DXF to display, then click
OK.

6

To print a drawing, from the I/O Draw Display window, click Print. The drawing
is printed to your default printer.

7

To save the I/O drawing in another format, click Save As.

372 SPU 780 01EMAN May 2002

ProWORX 32 Utilities

The Ping Utility
Overview

Ping is a TCP/IP utility for testing a given IP address. The address is checked to see
if a device exists for it. If the address exists, the Ping is successful and a round trip
time (ms) is returned. If the ping fails, an error response will be given. This will help
diagnose problems with the TCP/IP communications as well as determining a
devices existence. Ping options are saved to the ProWORX .INI file.

Using the Ping
Utility

From the navigation tree utilities tab:

372 SPU 780 01EMAN May 2002

Step

Action

1

Select Ping.

2

Enter the IP address to ping in the IP Address to Ping box.

3

Click Ping to perform a ping. The status of the ping attempt is displayed in the
Return Status field and if successful, the ping time is displayed in the Round Trip
Time field.

4

Click Close to exit the ping utility.

229

ProWORX 32 Utilities

MBP Stat
Overview

To access device status and diagnostic tools, select one of the following items from
the device right-click menu:
Status and
Diagnostic Tools

Tool Tabs

Bus Status (CTRL+B)

Description
Used to obtain network status of nodes on the
network.

Active station
table

Active nodes on the network are highlighted.
Note: The node that the cursor is on is not
highlighted.

Token station
table

Nodes on the network that are receiving and passing
the token are highlighted. The Token Rotation Time
and Token Pass Counter are also displayed.
Note: The node that the cursor is on is not
highlighted.

Global data
station table

Nodes that are sending global data to the selected
node are flashing if the selected node is configured to
receive global data from the nodes.

Network Statistics (CTRL+N)

Obtain statistics for the node on which the cursor is
located.

Personality

Node information, such as type, address, version and
communication state, is displayed.

Error counter

Communication information and errors for the
selected node are displayed.

Receive buffers When the node selected is receiving specific input
from other nodes on the network, the number of
receive buffers in use is flashing.
Transactions

The number of data transactions for the 8 data paths
of the selected node:
l DM - Data master
l DS - Data slave
l PM - Programming master
l PS - Programming slave

Work-to-do

The type of programming and/or data activity for the 8
data paths of the selected node is displayed. A
flashing square indicates data activity.

Read Global Data (CTRL+G)

230

The global data being transmitted for the selected
node is displayed. The data can be viewed in HEX,
DEC signed or DEC unsigned format.
372 SPU 780 01EMAN May 2002

ProWORX 32 Utilities

Status and
Diagnostic Tools

Tool Tabs

Description

CPU status (CTRL+U)

CPU firmware, hardware revisions, and crash codes
are displayed. From here you can access the CPU
Status words.

Adapter statistics (CTRL+A)

CPU firmware, hardware revisions, and crash codes
are displayed. From here you can access the CPU
Status words.

Note: The Refresh slider allows you to set the rate at which the data is updated.
To stop communications with the selected device, click Stop. To begin
communications with the selected device, click Start.

372 SPU 780 01EMAN May 2002

231

ProWORX 32 Utilities

232

372 SPU 780 01EMAN May 2002

ProWORX 32 Reporting

Reporting
Overview

The ProWORX 32 reporting feature allows you to print many aspects of your project
to a file or printer. Reporting is a very powerful tool, which can be used to extract
information from your project into a printed document.

Using the
Printing Menu

From the ProWORX 32 menu:

372 SPU 780 01EMAN May 2002

Step

Action

1

Select File → Print to send the currently selected documentation to the printer.

2

Select File → Print Preview to view the current report as it will be printed.

3

Select File → Print Setup to edit the content and documentation that will make
up the report.

233

ProWORX 32 Reporting

Quick Picks

Quick picks are pre-defined sets of reporting options. Select an option in the quick
pick list box to get a pre-selected list of options for reporting. Choose an option in
the list box and the respective report options will be automatically selected.
The options are as follows:

Using the
Reporting Setup

234

Quick Pick

Description

Turn off all options

All report options are deselected.

Turn on all options

All report options are selected.

All networks

All settings within the Networks report option are selected.

Everything but networks

All settings within all report options are selected except the
Networks report option.

All documentation tables

All settings within the Descriptor Ranges option and
Documentation Tables options are selected.

All controller tables

All settings within the Configuration Tables, Traffic Cop,
Register Content Ranges, and Used Tables report options are
selected.

All used tables

All settings within the Used Tables report option are selected.

All mismatch tables

All settings within the Mismatch Tables report option are
selected.

After opening the reporting setup dialog (Step 3 in ‘Using the printing menu’):
Step

Action

1

Select the report options that you want to include in the report, from Networks,
Descriptor ranges, Documentation tables, Configuration tables, Traffic cop,
Register content ranges, Used tables, and Mismatch tables, by clicking the
corresponding check box.

2

Set the parameters within each report option that you have selected. (To see
further details pertaining to each report option, see below.)

3

To select all parameters, or deselect all parameters within a report option, click
Toggle All.

4

To save the current report options, click Save Settings.

5

To preview the report as it will be printed, click Print Preview.

6

When you are finished setting the report options, click Close.

372 SPU 780 01EMAN May 2002

ProWORX 32 Reporting

Networks

After selecting Networks from the report options list:
Step
1

Descriptor
Ranges

Documentation
Tables

Action
Select which networks that are to be printed by typing the numeric range of
networks in the Print Networks box. To select all networks enter "All". To select
no networks enter ‘None’.

2

Select whether you want One Network per Page or Two Networks per Page.

3

If you select One Network per Page, you can then select Cross References to
print all of the cross references that are associated with the particular network,
Network Long Comment to print long comments for the particular network.

After selecting Descriptor Ranges from the report options list:
Step

Action

1

Enter the range of descriptors to be printed for each address type. Valid entries
include: "1-100", "None", and "All".

2

Select Items Used in Logic to print addresses used in logic.

3

Select Items with Descriptions to print addresses that have descriptions.

4

Select All Items to print all coils. This includes all items used in logic and items
with descriptions.

After selecting Documentation Tables from the report options list:
Step
1

372 SPU 780 01EMAN May 2002

Action
Select any combination of the following documentation check boxes:
Log Book / Audit Trail
Symbol Table
Page Titles
Short Comments
Long Comments
Cross References

l
l
l
l
l
l

235

ProWORX 32 Reporting

Configuration
Tables

After selecting Configuration Tables from the report options list:
Step
1

Traffic Cop

1

236

Action
Select any combination of the following traffic cop check boxes:
Drop Summary
Rack Overview
Slot Summary
Descriptors
Symbols
Cross References
Short Comments

l
l
l
l
l
l
l

After selecting Register Content Ranges from the report options list:
Step
1

Address Used
Tables

Select any combination of the following configuration tables check boxes:
Configuration
Segment Scheduler
ASCII Messages
Config Extensions

l
l
l
l

After selecting Traffic Cop from the report options list:
Step

Register Content
Ranges

Action

Action
Enter a range of register contents to print in the address (3xxxx, 4xxxx, and
6xxxx (file 1 - 10)) boxes. Valid entries include: "1 - 100", "None", and "All".

After selecting Used Tables from the report options list:
Step

Action

1

Select whether you want a Brief or Full printout of the addresses used in logic.

2

Select the check boxes of the addresses you want to include in the report from:
0xxxx, 1xxxx, 3xxxx, and 4xxxx.

3

Click the Disable References check box to include the addresses that have
been disabled in logic.

372 SPU 780 01EMAN May 2002

ProWORX 32 Reporting

Mismatch Tables

After selecting Mismatch Tables from the report options list:
Step

372 SPU 780 01EMAN May 2002

Action

1

Select which addresses that have descriptors, but are not used in logic that you
want to include in the report by clicking the 0xxxx, 1xxxx, 3xxxx, and 4xxxx check
boxes under the Described But Not Used In Logic heading.

2

Select which addresses that are used in logic, but do not have descriptors that
you want to include in the report by clicking the 0xxxx, 1xxxx, 3xxxx, and 4xxxx
check boxes under the Used In Logic But Not Described heading.

237

ProWORX 32 Reporting

238

372 SPU 780 01EMAN May 2002

ProWORX 32 Server

At a Glance
Overview

The ProWORX 32 server (see Overview, p. 35) is the repository for projects, the
center for security, and a hub for communications.

What’s in this
Chapter?

This chapter contains the following topics:

372 SPU 780 01EMAN May 2002

Topic

Page

Using the ProWORX 32 Server

240

Audit Trail

243

239

ProWORX 32 Server

Using the ProWORX 32 Server
Logging on to
the ProWORX 32
Server

From the Windows start menu:
Step
1

Setting the
Server
Communications

Working with
Projects

Select Programs → ProWORX 32 → ProWORX Server

2

Enter the user name given to you by the system administrator in the Name field.

3

Enter your password in the Password field.

4

To logout of the ProWORX server, select File → Logout. To re-login, select File
→ Login.

5

Click Close to exit ProWORX 32 Server.

In the ProWORX Server menu:
Step

Action

1

Select File → Set Server Communications.

2

Select communications type from TCP/IP, MBP Adapter 0, and MBP Adapter
1 that the server uses to communicate with the clients.

3

If you have selected TCP/IP, enter the appropriate TCP/IP port number in the
TCP/IP Port Number field.

4

Click OK. To make the communications changes you must restart the ProWORX
32 Server.

Select the Projects tab:
Step
1

2

3

240

Action

Action
Select a project from the project tree. In the Project Info pane you will find:
Project Name
Project Status - Checked out by username or Not checked out

l
l

Click View Project Details to see further project information:
Project Name (Long) - A more descriptive project name
Project Description - A detailed description of the project
Client - The end-user of the project
Author - The author of the project
Controller Type
Controller Address - Communications type and address

l
l
l
l
l
l

Click View Audit Trail to view the transaction history of the project.

372 SPU 780 01EMAN May 2002

ProWORX 32 Server

Creating
ProWORX 32
Users

Creating
ProWORX 32
User Groups

Working with
ProWORX 32
Users and User
Groups

Select the Users tab:
Step

Action

1

Click Add User. The Add User dialog appears.

2

Enter the new users name in the User Name field.

3

Enter a distinct password in the Password field.

4

Click OK to confirm the new user.

5

To edit a user name or user password, click Edit User. To delete a user, click
Remove User.

Select the Users tab:
Step

Action

1

Click Add Group. The Group Rights dialog appears.

2

Enter the name of the new group in the Group Name field.

3

Select Administration Rights for the group.

4

Select Project Rights for the group.

5

Click OK to save the new group.

6

To edit a group name or group rights, click Edit Group Rights. To delete a
group, click Remove Group.

Select the Users tab:

372 SPU 780 01EMAN May 2002

Step

Action

1

To add a user to a user group, select a user from the Users list, select a group
from the User Groups list and click Add User to Group.

2

To remove a user from a user group, select a user from the User Groups list and
click Remove User From Group.

241

ProWORX 32 Server

User Rights

The Status Tab

242

User rights descriptions:
User Rights

Descriptions

Controller Configuration

The ability to change the controller configuration, or change
controller type.

Traffic Cop Editor

The ability to edit in the traffic cop.

Communications Setup

The ability to change the communications setup including the
controller’s address.

Logic Editor

The ability to edit logic.

Forcing

The ability to force contacts and coils.

Insert

The ability to insert cells, rows, columns, and networks.

Delete

The ability to delete cells, rows, columns, and networks.

Sweep

The ability to enter sweep mode.

Data Editors

The ability to enter any of the data editors, If deselected, the
user is unable to change register data.

Extended Memory

The ability to edit extended memory registers.

Configuration Extensions

The ability to edit the configuration extensions.

ASCII Messages

The ability to edit the ASCII messages.

Documentation Editor

The ability to change any of the documentation.

Read

The ability to read from the controller.

Write

The ability to write to the controller.

Start/Stop

The ability to start or stop the controller.

Clear Audit Trails

The ability to remove all audit trail and logbook entries.

Get Projects

The ability to get projects from the server.

Put Projects

The ability to put projects to the server.

The Status tab displays the following project information:
l User - The client currently logged in to the ProWORX Server
l Transfer Type - The type of transfer being performed (Data or File)
l Description:
l File - The file name and lock status
l Data - The data type
l Progress:
l File - A progress number or ‘Done’
l Data - The number of packets transferred

372 SPU 780 01EMAN May 2002

ProWORX 32 Server

Audit Trail
Overview

The audit trail keeps a record of project transactions between the ProWORX 32
client and ProWORX 32 server. Each transaction is stored as an entry in the audit
trail. Audit trail comments can be added to each record when putting a project to the
server.

Using the Audit
Trail

In the project navigation tree:
Step

Action

1

From the project right-click menu, select Audit Trail.

2

To view a specific transactions information, select a transaction from the list in
the navigation panel.
Transactions list:
l User - Who made the changes to the current transactions.
l Date and Time - When the transaction was completed.
l Changes Made - ProWORX 32 areas that were changed from the previous to
current transaction.
l User Comments - Any notes or comments that the user has entered when
putting the project to the server.
You can also navigate through the transactions by clicking the standard
navigation buttons at the top of the window.

3
To hide or view the navigation panel, click the view tree button

372 SPU 780 01EMAN May 2002

.

4

To clear all audit trail from transactions from the audit trail, click Clear Audit
Trail.

5

To print the current audit trail, click Print.

6

When you are finished, click Close to return to ProWORX 32.

243

ProWORX 32 Server

244

372 SPU 780 01EMAN May 2002

Schneider Alliances

At a Glance
Overview

Schneider Alliances is a third-party utility used by Schneider Alliances partners to
add or modify I/O cards.

What’s in this
Chapter?

This chapter contains the following topics:

372 SPU 780 01EMAN May 2002

Topic

Page

Using the Schneider Alliances Tool

246

Using the Script Editor

249

Using Script Editor Controls

252

245

Schneider Alliances

Using the Schneider Alliances Tool
Adding an I/O
Card

Editing an I/O
Card

Editing an I/O
Card Parameter

246

After opening Schneider Alliances:
Step

Action

1

Select an I/O system from the I/O System drop-down list box.

2

Click Add. (Certain default values are entered into the parameter list.)

3

Edit the parameters to match the card you are adding.

4

Click Update to save the new data, or click Cancel to remove the new data and
start over.

From the Schneider Alliances default screen:
Step

Action

1

Select an I/O system from the I/O System drop-down list box.

2

Select an existing card from the Card drop-down list box. (The current card data
is entered into the parameters list.)

3

Click Edit.

4

Edit the parameters you wish to update. (See Editing an I/O Card Parameter.)

5

Click Update to save the new data, or Cancel to undo the changes you have
made.

While adding or editing an I/O card:
Step

Action

1

Press ENTER or click the Value column of the desired parameter. (The selected
parameter will now be editable.)

2

Type a valid value or select a value from the drop-down list. (Some parameters
require you to click the ellipsis box for further configuration.)

3

Press ENTER to accept the new parameter, or ESC to cancel the change.

372 SPU 780 01EMAN May 2002

Schneider Alliances

Using the MCS
Simple 2 Editor

Using the Default
Parameter Data
Editor

After clicking the ellipsis box in the MCS Simple 2 parameter:
Step
1

Double-click the ’1’ or ’0’ to toggle a bit.

2

Click the Save button to save changes back to the main grid, or click Cancel to
return the main grid without updating any changes.

After clicking the ellipsis box in the Default Parameter Data parameter, the Data
Values dialog opens, showing the current number of rows in the Number of
Parameters Used parameter, and the current value in the Default Parameter Data
parameter. To edit the contents of a row, simply double-click the cell you want to
edit, and enter a Hex value. Use the following functions to further edit the parameter:
Function

I/O Card
Parameters

Action

Action

Comment

1

Click Add.

A blank cell is added to the end of the
grid.

2

Click Remove.

The currently selected row is deleted,
and the cells below are shuffled up.

3

Click Move Up.

The contents of the currently selected
cell are moved up one cell.

4

Click Move Down.

The contents of the currently selected
cell are moved down one cell.

Parameters list:

372 SPU 780 01EMAN May 2002

Parameter

Description

Card ID

Hex Value. The Unique Modicon ID for each card of an I/O series.

INTERBUS ID

Hex Value. The INTERBUS S ID of a card.

Drop Allowed

Momentum Only. Defines whether or not a Momentum CPU supports a
non-local, INTERBUS S drop.

Card Description

Description of the currently selected I/O card. This is used throughout
ProWORX 32 to pick, edit, and add I/O cards. Maximum ten characters.

Medium
Description

Text description displayed in the Traffic Cop when editing slot properties
of a card.

Long Description

A more detailed description of the card.

Power

The amount of power used by the card in the rack.

Power (+5)

Number of mA used by card at this power rating.

Power (+4.3)

Number of mA used by card at this power rating.

Power (-5)

Number of mA used by card at this power rating.

247

Schneider Alliances

Parameter

Description

Number of
Parameters Used

The number of Card config parameters that are used by default.

Default Number of The available number of parameter words by default.
Parameters
In Bytes

The number of input bytes used by the card.

Out Bytes

The number of output bytes used by the card.

In Bytes (IBus)

Momentum Only. Defines the number of input bytes for an INTERBUS
card.

Out Bytes (IBus)

Momentum Only. Defines the number of output bytes for an INTERBUS
card.

Module Type

Defines the type of card. Discrete, Analog, or Analog with no discretes
allowed.

Doc Only

Certain cards are not programmed into the controller memory, but are
still displayed in the traffic cop. These cards are documentation only
cards.

MCS Simple 1

Type of hardware module.

MCS Simple 2

Defines behavior of card.
See: Using the MCS Simple 2 editor.

Default Parameter The value of the card config words by default.
Data
Rack View Bitmap The bitmap displayed in the Traffic Cop rack View.
Drop View Bitmap The bitmap displayed in the Traffic Cop in Drop view.

248

Extra Bus Info

Momentum Only. One word that defines extra information for an
INTERBUS Drop.

Script Data

The WYSIWYG card config editor.

372 SPU 780 01EMAN May 2002

Schneider Alliances

Using the Script Editor
Overview

Schneider Alliances Script Editor is a WYSIWYG property based editor used to
create card configuration scripts. The VB Script file used by ProWORX 32 to display
card configuration is automatically created by the card configuration editor. These
scripts are used by ProWORX 32 to configure optional card parameters in the Traffic
Cop.

Adding a Control
to the Grid

From the script editor dialog:

372 SPU 780 01EMAN May 2002

Step

Action

1

Click a control in the ToolBox panel to add it to the grid.

2

Set the properties for the control.
Tip: To most effectively set your control, select the controls container in the
Container property first. This will move the control onto the desired frame.

3

Place the control by clicking the controls center selection handle, and holding
and dragging the control to the desired location.

4

Resize the control by clicking and dragging the controls perimeter selection
handles to the desired size.

249

Schneider Alliances

Common
Properties

Using the Event
Editor Dialog

Common control properties:
Property

Description

Left

The left-most part of the control in twips.
Note: For reference, there are 1440 twips per inch.

Top

The topmost part of the control in twips.

Width

The width of the control in twips.

Height

The height of the control in twips.

Caption

The text display related to the control.

Container

The container is the object that the control is anchored to.
Note: You can anchor a control to either the form (pbEditor) or to any frame.
When a control is anchored to a frame, the controls positional variables (Left
and Top) are relative to the anchor, not to the form.

StartBit

The first bit in a range of bits to edit.

EndBit

The last bit in a range of bits to edit.

Word

The word number you want to edit.
Note: To add a control that whose data value has no consequence to a word,
set the Word property to 0. The word list is 1-base.

Event

This is a portion of script that will execute when the value of the control is
changed.

The event of a control is executed when the data value of the control changes. The
event script allows you to enter VB script code to manipulate controls. The event
script editor will do minor error checking for syntax mistakes. The gird has a unique
Initialize function which is executed when the form is opened. Using events you can
hide controls using the .visible property, enable and disable controls using .enabled
and many other standard VB functions.
After clicking the ellipsis box in the Event property of a control:

250

Step

Action

1

Enter VB script code into the event window.

2

When finished, click OK to return to the script editor. Certain errors will be caught
by the event script editor and there will be an error message if any errors exist.
Certain errors will not be detected by the editor though and the I/O card’s script
will not be functional in the traffic cop.
To cancel your changes and return to the script editor, click Cancel.

372 SPU 780 01EMAN May 2002

Schneider Alliances

Editing
Parameter Data Card Config
Words Using
Controls

Editing Card
Config Word
Data Example

In the properties panel:
Step

Action

Comment

1

Select the control that will be used Valid controls are: Radio Buttons, Check
to edit a word.
Boxes, Data Edit Boxes, and Combo Boxes.

2

Select a word from the drop-down The word numbers correspond with the
list in the Word property.
Default Parameter Data words. 1 is the first
word, 2 is the second word, and so on.

3

Enter a bit number into the
StartBit property.

This is the first bit in a range of bits to be
edited. Valid bit numbers are 1 through 16.

4

Enter a bit number into the
StartBit property.

This is the last bit in a range of bits to be
edited. Valid bit numbers are 1 through 16.

Word ones current value is 10101010 - 10101010 (43690 decimal). A controls
properties are set as follows:

l
l
l
l

Word = 1
StartBit = 9
Word = 16
Data value of the control = 15

When the card config dialog is saved, word ones new value is 10101010 - 00001111
(43535 decimal). Notice, bits 9 through 15 (00001111) are equal to 15 which is what
the properties had specified.

372 SPU 780 01EMAN May 2002

251

Schneider Alliances

Using Script Editor Controls
Frame

Frames are used to enclose and group related controls. Scripts allow multiple layers
of frames to be added on top of each other. After a frame has been added to a grid
or previous frame, any of the available controls can be contained by (anchored to)
that frame.

Radio Button

Radio buttons are used on the grid or on a frame to display a limited set of options.
Only one radio button in a container can be selected at a time.
Control-specific properties:

Check Box

Property

Description

Data

The value that the bits are set to if the radio button is selected.

Check boxes are used on the grid or on a frame to display either/or options.
Control-specific properties:
Property

Description

DataChecked

The value that the bits are set to if the check box is checked.

DataUnchecked

The value that the bits are set to if the check box is unchecked.

Label

Most often used as a label for a combo box or a data edit box control, labels can be
used for on-screen instructions, as well as further detail or descriptions.

Combo Box

The combo-box is used when there are a set number of selections you want the user
to be able to choose from. Each item in the list has a corresponding data value.
Control-specific properties:

252

Property

Description

List

The list property provides an ellipsis box which when clicked opens up a
Combo Box Configuration dialog. The combo box configuration dialog
allows you to enter the contents and related values of the items in the list
box.

372 SPU 780 01EMAN May 2002

Schneider Alliances

Creating a List
for the Combo
Box

Data Edit Box

In the combo box configuration dialog:
Function

Action

1

To add an item to the list, Click Add.

2

Edit the Combo List Item and Item Data fields by double-clicking on the cell.

3

To move the item within the list, click Move Up and Move Down.

4

To remove an item, click Remove.

5

To save the items and data and return to the script editor, click OK. To cancel
changes and return to the script editor, click Cancel.

Data edit boxes are used on the grid or on a frame to allow the user to enter any
valid value. Valid values are determined by which radix is set for the data edit box.
For example, if ‘Binary’ is selected in the radix property, only ones and zeros are
valid data, and the value can only have a length of 16 characters.
Control-specific properties:
Property

Description

Radix

The mode of the edit box. Available options are Decimal, Binary, Hexadecimal,
ASCII, and Long.
Notes:
l All radices are have a 16-bit limit except Long, which has a 32-bit limit.
l A ‘Long’ data type will overwrite the word that is selected in the Word property
of the data edit box as well as the next word in the order that they are set in
the Default Parameter Data property of the I/O card.
l It is not recommended that you put a long data value in the last word. If the
last word is selected in the Word property, the ‘Long’ data value will be
truncated and put into the last word. This may alter the results you expected
significantly.

Command

The command button is a seldom used control but can be very useful for batch
processes. For example, you can have a button that will check or uncheck a group
of check boxes, or a button that would clear all fields in a group.

Time State
Properties

The time state property control is different from other controls in that it is a toggle
edit combo box. It is used to edit parameters of cards that are actually not passed
as data words. Namely, when editing the time-out state of a card, you would use a
timestate drop-down to set the parameter to "User Defined" or to "Last Value".

372 SPU 780 01EMAN May 2002

253

Schneider Alliances

254

372 SPU 780 01EMAN May 2002

Appendices

At a Glance
Overview

These appendices provide information on the I/O cards supported by ProWORX 32
and troubleshooting tools and resources.

What’s in this
Appendix?

The appendix contains the following chapters:
Chapter
A

372 SPU 780 01EMAN May 2002

Chapter Name

Page

I/O Cards

257

B

Troubleshooting

271

C

Editing .DIF Files with Microsoft Excel

303

255

Appendices

256

372 SPU 780 01EMAN May 2002

I/O Cards

At a Glance
Overview

This appendix lists the I/O cards supported by ProWORX 32 for the following I/O
series:

What’s in this
Chapter?

This chapter contains the following topics:

372 SPU 780 01EMAN May 2002

Topic

Page

800

258

A120

261

Compact TSX

263

Micro

265

Momentum M1 and INTERBUS

266

Quantum

267

Sy/Max

270

257

I/O Cards

800
800 Series Cards

258

I/O cards supported (in alphabetical order):
Card

Description

Card

Description

B802-008

115 VAC 8 Point Output
Module

B872-002

4-20 mA,1-5V 4 Channel
Analog Output

B803-008

115 VAC 8 Point Input Module B872-011

Selectable 4 Channel Voltage
Output

B804

16 Point Output Module

B872-100

4-20mA 4 Channel Current
Output Module

B804-016

115 VAC 16 Point Output
Module

B872-200

Selectable 4 Channel Voltage
Output

B804-116

115 VAC 16 Point Output
Module

B873-001

4-20mA,1-5V 4 Channel
Analog Input

B805-016

115 VAC 16 Point Input
Module

B873-002

4-20mA,1-5V 4 Channel
Analog Input

B806

32 Point Output Module

B873-011

-10 V to 10 V 4 Channel Analog
Input

B806-032

115 VAC 32 Point Output
Module

B873-012

-10 V to 10 V 4 Channel Analog
Input

B806-124

24 VAC 32 Point Output
Module

B873-200

V/A, Thermo, RTD, Strain
Gauge Input

B807

32 Point Input Module

B875-001

4-20mA, 1-5V 8 Channel
Analog Input

B807-032

115 VAC 32 Point Input
Module

B875-002

4-20mA, 1-5V 8 Channel
Analog Input

B807-132

115 VAC 32 Point Input
Module

B875-011

-10 V to 10 V 8 Channel Analog
Input

B808-016

230 VAC 16 Point Output
Module

B875-012

-10 V to 10 V 8 Channel Analog
Input

B809-016

230 VAC 16 Point Input
Module

B875-101

Fast selectable 8 Channel
Analog Input

B810-008

115 VAC 8 Isolated Output
Module

B875-102

Fast selectable 8 Channel
Analog Input

B814

8 Point Output Module

B875-111

Select. 8 channel Differential
Input

B814-001

NO Power Relay 8 Point
Output Module

B875-200

V/A, Thermo, RTD, Strain
Gauge Input

372 SPU 780 01EMAN May 2002

I/O Cards

372 SPU 780 01EMAN May 2002

Card

Description

Card

Description

B814-002

NC Power Relay 8 Point
Output Module

B877-111

Select. 16 channel Single
Ended Input

B814-108

NO/NC Power Relay 8 Point
Output Module

B881

Input/Output Module

B817

16 Point Isolated Input Module B881-001

24 VDC 16 Point Latched Input
(TrueHigh)

B817-116

115 VAC 16 Point Isolated
Input Module

B881-108

115 VAC 8 Point Protected
Output Module

B817-216

230 VAC 16 Point Isolated
Input Module

B881-508

125 VDC 8 Point True High
Output Module

B818-032

24 VDC 32 Point Output (True
High)

B882-032

24 VDC Diagnostic Output
Module

B819-032

230 VAC 32 Point Input
Module

B882-239

0-30 kHz 2 High Speed UpCounter Module

B820-008

10-60 VDC 8 Point Output
(True High)

B883

Input/Output Module

B821

8 Point Input Module

B883-001

0-50 kHz 2 High Speed UP/
Down Counter

B821-008

10-60 VDC 8 Point Input (True B883-101
High)

4 kHz CAM ABS Encoder
Input,8 Disc Out

B821-108

10-60 VDC 8 Point Input (True B883-111
High)

1 kHz CAM with Velocity
compensation

B824-016

24 VDC 16 Point Output (True
High)

B883-200

10 Thermocouple Input
Module

B825-016

24 VDC 16 Point Input (True
High)

B883-201

8 RTD Input Module

B826-032

24 VDC 32 Point Output (True
High)

B884-002

2 Loop, PID Control Module

B827-032

24 VDC 32 Point Input (True
High)

B885

Main Module

B828-016

5V TTL 16 Point Output

B885-002

ASCII/BASIC Module

B829-116

5V TTL 16 Input (Fast
Response)

B885-100

Motion Module

B832-016

24 VDC 16 Point Output (True
Low)

B885-110

Motion Module

B833-016

24 VDC 16 Point Input (True
Low)

B886-000

High Speed Logic Solver

259

I/O Cards

260

Card

Description

Card

Description

B836-016

12-250 VDC 16 Point Output
Module

B887-000

12 Register Bidirectional

B837-016

24 VAC/DC 16 Point Input
(True High)

B888-100

Datalogic CM1000 AutoID
interface

B838-032

24 VDC 32 Point Output (True
High)

D908-110

Distributed Control Single

B840-108

NO/NC Reed Relay 8 Point
Output Module

D908-120

Distributed Control Dual

B842-008

NO/NC Reed Relay 8 Point
Output Module

J890-001

RIO Single

B846

Analog MUX Module

J890-002

RIO Redundant

B846-001

Analog MUX (16 voltage to
one output)

J892-001

RIO ASCII Single

B846-002

Analog MUX (16 current to
one output)

J892-002

RIO ASCII Redundant

B849-016

48 VAC/DC 16 Point Input
Module

P800-003

Power Supply

B853-016

115 VAC/125 VDC 16 Input
(True High)

P802-001

Power Supply

B855-016

12 VDC 16 Point Input (Intr.
Safe)

P810-000

Power Supply

B862-001

4 Channel Register Output
(TTL Level)

P830-000

Power Supply

B863

4 Channel Register Input

P840-000

Power Supply

B863-001

4 Channel Register Input (TTL P884-001
Level)

Power Supply

B863-032

4 Channel Register Input (TTL P890-000
Level)

Power Supply

B864-001

8 Channel Register Output
(TTL Level)

Power Supply

B865-001

8 Channel Register Input (TTL S908-110
Level)

RIO Processor Single

B868-001

8 Channel Register Output
(TTL Level)

S908-120

RIO Processor Dual

B869-001

8 Channel Register Input (TTL S911-800
Level)

Hot Standby Module

B872

4 Channel Analog Output

P892-000

372 SPU 780 01EMAN May 2002

I/O Cards

A120
A120 Series
Cards

I/O cards supported (in alphabetical order):

372 SPU 780 01EMAN May 2002

Card

Description

Card

Description

ADU 204

4 Channel Register Input (+/0.5V)

DEP 208

230 VAC 8 Point Input Module

ADU 205

4 Channel Register Input (+/10V)

DEP 209

120 VAC 8 Point Input Module

ADU 206

4 Channel Register Input

DEP 210

115 VAC 8 Point Input Module

ADU 211

8 Channel Analog Input
Module

DEP 211

115 VAC 8 Point Input Module

ADU 212

8 Channel Analog Input
Module

DEP 214

12-60 VDC 16 Point Input
Module

ADU 214

4 Channel Multi Range A/D
Input

DEP 215

5 VDC TTL 16 Point Input
Module

ADU 216

8 Channel Thermocouple

DEP 216

24 VDC 16 Point Input Module

CM900

Auto Interface

DEP 217

24 VDC 16 Point Input Module

DAO 216

24 VDC 16 Point Output
Module

DEP 218

115 VAC 16 Point Input
Module

DAP 204

24 VDC 4 Point Relay (NO)
Module

DEP 220

Fast 24 VDC 16 Point Input
Module

DAP 208

24 VDC 8 Point Relay (NO)
Module

DEP 257

110 VDC 16 Point Input
Module

DAP 209

120 VAC 8 Point Output
Module

DEP 296

60 VDC 16 Point Isolated Input
Module

DAP 210

24-230 VAC 8 Point Output
Module

DEP 297

48 VDC 16 Point Isolated Input
Module

DAP 212

24 VDC 8 Point Input/4 Point
Output

M7251

Programmable Limit Switch

DAP 216

24 VDC 16 Point Output
Module

M7350

Resolver Decoder Function
Module

DAP 217

5-24 VDC 16 Point Output
Module

MOT 201

1 Slot 1 Axis Motion Control
Module Encoder

DAP 218

24-240 VAC 16 Point Output
Module

MOT 202

2 Slot 1 Axis Motion Control
Module Resolver & Encoder

DAP 220

24 VDC 8 Point Input/Output
Module

P120 000

Power Supply

261

I/O Cards

262

Card

Description

Card

Description

DAP 252

LowTemp 24 VDC 8 Point
Input/4 Point Output

P120 125

Power Supply

DAP 253

LowTemp 110VDC 8 Point
Input/4 Point Output

VIC 200

4 High Speed Pulse or 4 VRC
Inputs

DAP 292

60 VDC 8 Point Input/4 Point
Output

VIC 205

4 High Speed Pulse or 4 5V
TTL Inputs

DAU 202

2 Channel Register Output (+/ VIC 212
-10V)

4 High Speed Pulse or 12 VDC
Inputs

DAU 204

4 Channel Analog Output,
Opto-Isolation

VIC 224

4 High Speed Pulse or 24 VDC
Inputs

DAU 208

8 Channel Register Output (+/ ZAE 201
-10V)

High speed Counter/Positioner
(2 Relay)

DEO 216

24 VDC 16 Point Input Module ZAE 204

4 Channel High speed
Counter/Positioner

372 SPU 780 01EMAN May 2002

I/O Cards

Compact TSX
Compact TSX
Series Cards

I/O cards supported (in alphabetical order):

372 SPU 780 01EMAN May 2002

Card

Description

Card

Description

ADU 204

4 Channel Register Input (+/0.5V)

DAP 292

60 VDC 8 Point Input/4 Point
Output

ADU 205

4 Channel Register Input (+/10V)

DAU 202

2 Channel Register Output (+/10V)

ADU 206

4 Channel Register Input

DAU 204

4 Channel Analog Output,
Opto-Isolation

ADU 210

4 Channel Analog Input
Module

DAU 208

8 Channel Register Output (+/10V)

ADU 211

8 Channel Analog Input
Module

DEO 216

24 VDC 16 Point Input Module

ADU 212

8 Channel Analog Input
Module

DEP 208

230 VAC 8 Point Input Module

ADU 214

4 Channel Multi Range A/D
Input

DEP 209

120 VAC 8 Point Input Module

ADU 216

8 Channel Thermocouple

DEP 210

115 VAC 8 Point Input Module

ADU 257

8 Channel Thermocouple

DEP 211

115 VAC 8 Point Input Module

BKF 202

Interbus S Slave

DEP 214

12-60 VDC 16 Point Input
Module

BKF201-16

16 Word Interbus S Master

DEP 215

5 VDC TTL 16 Point Input
Module

BKF201-64

64 Word Interbus S Master

DEP 216

24 VDC 16 Point Input Module

DAO 216

24 VDC 16 Point Output
Module

DEP 217

24 VDC 16 Point Input Module

DAP 204

24 VDC 4 Point Relay (NO)
Module

DEP 218

115 VAC 16 Point Input
Module

DAP 208

24 VDC 8 Point Relay (NO)
Module

DEP 220

Fast 24 VDC 16 Point Input
Module

DAP 209

120 VAC 8 Point Output
Module

DEP 257

110 VDC 16 Point Input
Module

DAP 210

24-230 VAC 8 Point Output
Module

DEP 296

60 VDC 16 Point Isolated Input
Module

DAP 211

120 VAC 4 Point Output
Module

DEP 297

48 VDC 16 Point Isolated Input
Module

263

I/O Cards

264

Card

Description

Card

Description

DAP 212

24 VDC 8 Point Input/4 Point
Output

FRQ 204

Frequency and Speed
Measurement

DAP 216

24 VDC 16 Point Output
Module

KOS260-24

Universal Communications
Module

DAP 217

5-24 VDC 16 Point Output
Module

KOS260-64

Universal Communications
Module

DAP 218

24-240 VAC 16 Point Output
Module

MOT 201

1 Slot 1 Axis Motion Control
Module Encoder

DAP 220

24 VDC 8 Point Input/Output
Module

MOT 202

2 Slot 1 Axis Motion Control
Module Resolver & Encoder

DAP 250

24 VDC 8 Point Input/Output
Module

P120 000

Power Supply

DAP 252

LowTemp 24 VDC 8 Point
Input/4 Point Output

P120 125

Power Supply

DAP 253

LowTemp 110VDC 8 Point
Input/4 Point Output

ZAE 201

High speed Counter/Positioner
(2 Relay)

372 SPU 780 01EMAN May 2002

I/O Cards

Micro
Micro Series
Cards

I/O cards supported (in alphabetical order):

372 SPU 780 01EMAN May 2002

Card

Description

Card

Description

MIC128

16 IN, 12 Relay OUT 24V DC

MIC140

8 Bit Counter/Interrupt Input

MIC129

16 IN, 8 Relay OUT 24V DC

MIC141

4 IN, 2 OUT 12 Bit 0-10V

MIC130

16 IN, 4 Relay OUT 24V DC

MIC142

4 IN, 2 OUT 12 Bit 1-5V

MIC131

16 IN, 8 Triac 4 Relay OUT
115V

MIC143

4 IN, 2 OUT 12 Bit ñ10V

MIC132

16 IN, 8 Triac OUT 115V

MIC144

4 IN, 2 OUT 15 Bit 0-10V

MIC133

16 IN, 4 Relay OUT 115V

MIC145

4 IN, 2 OUT 14 Bit 1-5V

MIC134

16 IN, 8 Triac 4 Relay OUT
230V

MIC146

4 IN, 2 OUT 10V

MIC135

16 IN, 8 Triac OUT 230V

MIC147

16 Bit Timer/Count Value

MIC136

16 IN, 4 Relay OUT 230V

MIC148

1 Word IN, 1 Word OUT

MIC137

16 IN, 12 FET OUT 24V DC

MIC149

2 Words IN, 2 Words OUT

MIC138

16 IN, 8 FET OUT 24V DC

MIC150

4 Words IN, 4 Words OUT

MIC139

16 IN, 4 FET OUT 24V DC

MIC151

8 Words IN, 8 Words OUT

265

I/O Cards

Momentum M1 and INTERBUS
Momentum
Series Cards

266

I/O cards supported (in alphabetical order):
Card

Description

Card

Description

AAI030-00

8 Channel Differential Input

AEC920-00

High Speed Counter 50khz

AAI140-00

16 Channel single ended Input AMM090-00 24 VDC 4 In / 2 Out
Bidirectional

AAI520-40

4 Channel RTD/Thermocouple ANM050-10

Seriplex Interface

AAO120-00

4 Analog Output 0-20mA

ANR120-90

Bi-directional Analog (6 in/4
out) with 24 VDC (8 in/8 out)
discrete

AAO921-00

4 Analog Output 4-10mA

ARM370-30

24 VDC 10 In / 8 Out Relay

ADI340-00

24 VDC 16 Point I/P Module

ATV058-00

Single Phase Drive

ADI350-00

24 VDC 32 Point I/P Module

BAI036-00

8 Channel Analog I/P Module

ADI540-50

120 VAC 16 Point I/P Module

BAM096-00

4 I/P / 2 O/P Analog Module

ADI740-50

230 VAC 16 Point I/P Module

BAO126-00

4 Channel Analog O/P Module

ADM350-1X 24 VDC 16 In / 16 Out

BDI346-00

24 VDC 16 Point I/P Module

ADM370-10

24 VDC 16 In / 8 Out

BDI356-00

24 VDC 32 Point I/P Module

ADM390-10

24 VDC 16 In / 16 Out

BDI546-50

120 VAC 16 Point I/P Module

ADM390-30

24 VDC 10 In / 8 Out Relay

BDI746-50

230 VAC 16 Point I/P Module

ADM540-80

120 VAC 6 In / 3 Out Bi-Dir

BDM346-00

24 VDC 16 In / 16 Out

ADM690-50

115 VAC 10 In / 8 Out

BDM346-30

8 In / 8 Out Relay

ADO340-00

24 VDC 16 Point O/P Module

BDO346-00

24 VDC 16 Point O/P Module

ADO350-00

24 VDC 32 Point O/P Module

BDO356-00

24 VDC 32 Point O/P Module

ADO530-50

115 VAC 8 Point O/P Module

BDO946-50

ADO540-50

115 VAC 16 Point O/P Module BNO671-00

BUS Module

ADO730-50

24 VAC 8 Point O/P Module

Generic INTERBUS S
Modules

ADO740-50

230 VAC 16 Point O/P Module ISP001-0X

IBUS-XXXX

115 to 230 VAC 16 Point O/P

ISP Weighing Module

372 SPU 780 01EMAN May 2002

I/O Cards

Quantum
Quantum Series
Cards

I/O cards supported (in alphabetical order):

372 SPU 780 01EMAN May 2002

Card

Description

Card

Description

ACI030-00

Analog 8 Channel Unipolar
Input

DDI841-00

10-60 VDC 16 Input Module

ACI040-00

16 Channel Analog Current
Module

DDI853-00

10-60 VDC 32 Input Module

ACI050-00

32 Channel Analog Current In DDM390-00

16/8 Bidirectional 24 VDC

ACI051-00

32 Channel Analog Voltage/
Current

DDM690-00

125 VDC 4 Input/4 Output
HPO Module

ACI052-00

32 Channel Analog Voltage/
Current

DDO153-10

5 VDC 4x8 Output Module

ACO020-00

4-20 mA Analog Output
Module

DDO353-00

24 VDC 32 Output Module

ACO130-00

8 Channel Output Module

DDO353-01

24 VDC 32 Point Output
Module

AII330-00

I. S. 8 Channel Analog Input

DDO353-10

24 VDC True Low 32 Output
Module

AII330-10

I. S. 8 Channel Analog Input
Current

DDO364-00

24 VDC True High 96 Output
Module

AIO330-00

I. S. Analog Output

DDO843-00

10-60 VDC 16 Output

AMM090-00 Analog In/Out 4Ch/2Ch

DDO885-00

125 VDC 12 Point O/P Module

ARI030-10

8 Channel RTD

DEVNET-08 64 Register Devicenet
Scanner

ATI030-00

8 Channel Thermocouple

DEVNET-32 16 Register Devicenet
Scanner

AUI040-00

16 Channel Universal Input
Module

DII330-00

I. S. Digital Input

AVI030-00

8 Channel Bipolar, Analog
Input

DIO330-00

I. S. Digital Output

AVI050-00

32 Channel Analog Voltage In DRA840-00

16 Output Relay

AVO020-00

Analog Voltage Output Module DRC830-00

8 Output ISO Relay

CHS110-00

Hot Standby

DSI353-00

24 VDC 32 Point Input Module

CPS-111

115/230V AC Power Supply
3A

DVO853-00

10-30 VDC Verified Output
Module

CPS114

115/230V AC Power Supply
8A

EHC105-00

High Speed Counter 5
Channel

267

I/O Cards

268

Card

Description

Card

Description

CPS124

115/230V AC Power Supply
RED 8A

EHC202-00

High Speed Counter

CPS-211

24 V DC Power Supply 3A

EHC204-00

High Speed Counter 4
Channel

CPS-214

24 V DC Power Supply 8A

EHC208-00

High Speed Counter 8
Channel

CPS-224

24 V DC Power Supply RED
8A

EIA921-00

1 Channel AS-1 Module
Interface

CPS-414

48 V DC Power Supply SUM
8A

ERT854-10

32 Point Smart Digital Input

CPS-424

48 V DC Power Supply RED
8A

ESI062-10

2 Channel ASCII Interface

CPS-511

125V DC Power Supply 3A

GPS100-00

IRIG-B Time Sync Interface

CPS-524

125V DC Power Supply 8A

HLI340-00

Hi-Speed/Latch/Interrupt

CRA211-10

DIO Drop MB+

HRT100-00

HART Serial Communications
Card

CRA211-20

DIO Drop MB+

I2T010-00

I2T 10 Input / 10 Output

CRA212-10

DIO Drop MB+

I2T016-00

I2T 16 Input / 16 Output

CRA212-20

DIO Drop MB+

MCI186X

Resolver Interface Module

CRA931-00

RIO Drop S908

MCI18X1X2

Single Turn Interface

CRA932-00

RIO Drop S908

MCI18X3X4

MultiTurn Resolver Interface

CRP811-00

Profibus DP Interface Module

MMB102-00 Two axis motion with
incremental

CRP931-00

RIO Head S908

MMB104-00 Four axis motion with
incremental

CRP932-00

RIO Head S908

MMC120-0X 2-Axis Motion Control

DAI340-00

24 VAC ISO 16 Input Module

MMD102-00 Two axis absolute motion

DAI353-00

24/48 VAC 32 Input Module

MMD104-00 Four axis absolute motion

DAI440-00

48 VAC 2x8 Input Module

MSB101-00

Motion Inc Enc

DAI453-00

48 VAC 32 Input Module

MSC101-00

Motion Enc/Res

DAI540-00

115 VAC 16 Input Module
Isolated

NOA611-00

Interbus-S Master Module

DAI543-00

2x8 115 VAC Input Module

NOA611-10

Interbus-S Master with PCP

DAI553-00

115 VAC 32 Input Module

NOE211-00

Ethernet TCP/IP Twisted Pair

DAI740-00

230 VAC 16 Input Module

NOE251-00

Ethernet TCP/IP Fiber Optic

CPS-424

48 V DC Power Supply RED
8A

NOE311-00

Ethernet SY/MAX Twisted Pair

372 SPU 780 01EMAN May 2002

I/O Cards

372 SPU 780 01EMAN May 2002

Card

Description

Card

Description

DAM390-00

16/8 Bidirectional 24 VAC

NOE351-00

Ethernet SY/MAX Fiber Optic

DAM490-00

16/8 Bidirectional 48 VAC

NOE511-00

Ethernet MMS Twisted Pair

DAM590-00

16/8 Bidirectional 120 VAC

NOE551-00

Ethernet MMS Fiber Optic

DAO840-00

24-230 VAC 16 Output

NOE771-00

Ethernet TCP/IP 10/100
Megabit

DAO840-10

24-115 VAC 16 Output

NOE771-10

Ethernet TCP/IP 10/100
Megabit

DAO842-10

100-230 AC 16 Output Module NOL911-XX

DAO842-20

24-48 VAC 16 Output

NOM212-10 MB+ Drop Interface Card

DAO853-00

24-230 VAC 4x8 Output

NOM2XX00

LonWorks Interface

MB+ Drop Interface Card

DCF077-00

24 VDC Input Module

NOP911-00

Profibus FMS Interface Module

DDI153-10

5 VDC 4x8 Input Module

QSPXM

Seriplex Master

DDI353-00

24 VDC 32 Input Module

QUCM-SE

Programmable
communications module

DDI353-10

24 VDC True Low 32 Input
Module

SERX53-00

Sequence Of Events Recorder

DDI364-00

24 VDC 6x12 Fast Input
Module

XCP900-00

Battery Backup

DDI673-00

125 VDC 24 Point I/P Module

269

I/O Cards

Sy/Max
Sy/Max Series
Cards

270

I/O cards supported (in alphabetical order):
Card

Card

Description

CRM931-D1 Digital 2 Slot RIO Adapter

Description

RIM131

High Speed Counter Module

CRM931-D2 Digital 4 Slot RIO Adapter

RIM144

Multiplexed BCD Input Module

CRM931-D4 Digital 8 Slot RIO Adapter

RIM301

85-140 VAC 16 Input Module

DRM931-D8 Digital 16 Slot RIO Adapter

RIM331

32-Function 24V DC Input

CRM931RG

Register RIO Adapter Module

RIM361

16-Function 240V AC/DC Input

RDI116

16 Channel Input

RIM731

64-Function 24V AC/DC Input

RDI132

32 Channel Input

ROM121

4-Function Analog Output

RDI1XX

Input Module

ROM122

4-Function Isolated Output

RDO616

16 Channel Relay Output

ROM131

Stepper Motor Controller
Module

RDO732

32 Channel Relay Output

ROM141

Multiplexed BCD Output
Module

RDOXXX

Relay Output

ROM221

16-Function 120V AC Output

RIM101

16-Function 120V AC/DC
Input

ROM271

16-Function 120V AC
RelayOutput

RIM121

4-Function Analog Input

ROM421

35-140 VAC 16 Output Module

RIM123

8 Channel High Speed Analog ROM431
Input

RIM125

16-Function Analog Input

ROM441

32-Function 24V DC Output

RIM126

8 Channel Analog/Thermo
Input

ROM871

64-Function Relay Output

RIM127

12 Channel RTD Input Module SIM116

16-Function 240V AC Output

16 In Simulator

372 SPU 780 01EMAN May 2002

Troubleshooting

Troubleshooting
Troubleshooting
Overview

This chapter includes various tools and resources for troubleshooting networks,
ladder logic, I/O cards, etc. Contact support (see Contacting Schneider Electric,
p. 26) if you require further information about I/O cards.

What’s in this
Chapter?

This chapter contains the following sections:

372 SPU 780 01EMAN May 2002

Section

Topic

Page

B.1

General Troubleshooting

272

B.2

Status Words for S901 and S908

280

271

Troubleshooting

B.1

General Troubleshooting

Section Overview
Overview

The Troubleshooting tools help to reduce down time and improve your maintenance
personnel’s understanding of the controller installation.

What’s in this
Section?

This section contains the following topics:

272

Topic

Page

Isolating Faults

273

Manual Procedure List

274

Modbus Plus

276

Stopcode Error Analysis

277

372 SPU 780 01EMAN May 2002

Troubleshooting

Isolating Faults
Isolating Faults

Faults can fit into one of four categories:

372 SPU 780 01EMAN May 2002

Fault

Possible Causes/Fixes

Input/Output Faults

This is the most common type of fault. It occurs when an open,
short, or an electrical or mechanical malfunction happens.
Common locations for these faults are in the field devices and the
wiring between the I/O module that interfaces to the field device.

Controller Faults

These faults include a faulty controller or improper ladder logic.
The Controller Manual Check helps isolate a faulty Controller.

Communication Faults

Communication Faults: Modicon controllers communicate with the
I/O sub system through remote I/O processor communication
networks or within local drops on the Modbus subsystem. Faults
occur when two pieces of hardware unexpectedly stop
communicating or communications becomes unintelligible.

Invalid Command

When the warning ’Command Not Valid Unless Logged In’
appears, check the following:
l Ensure the cable is properly attached to the controller.
l Ensure that the controller you’re connected to isn’t logged onto
by another user.
l Ensure you’re using the correct cable.
l Ensure the cable is connected to the correct controller port.
If the problem persists, contact Schneider Electric’s Customer
Support.

273

Troubleshooting

Manual Procedure List
Procedure One

Controller failed to power up with good AC supply and fuse OK:
Step
1

Procedure Two

Check the input power select switch position is correct for supply voltage.

3

Check for loose crimps or screws at the power supply terminal strip.

4

Check fuses where relevant.

To replace a 38x/48x fuse:
Action

1

Remove memory and executing cartridges.

2

Remove 9 screws that hold the side (1/4 inch nut driver).

3

Remove line cord cover screws and the plastic line cord cover.

4

Remove 2 line cord standoffs (3/16 inch nut driver).

5

Remove screws near battery compartment.

6

The front part of the controller can now separate from the circuit board. The fuse
is located near the AC power connector.

7

Replace fuse with the same size and type.

To replace a 68x/78x fuse:
Step
1

274

Ensure that the power supply jumper is correct on the slot mount controllers.

2

Step

Procedure Two

Action

Action
Remove 2 thumbscrews and 2 machine screws with start washers as shown on
front view.

2

Remove small cover.

3

Remove 4 machine screws from rear cover and slide rear cover back 3 inches.
(Exec pack cover may have to be removed from the right side).

4

Carefully slide the left side section toward the back expose the two fuses.

5

Replace blown fuses with the same type and size.

372 SPU 780 01EMAN May 2002

Troubleshooting

Procedure Two

To replace a P930/P933 fuse:
Step

Procedure Three

1

Turn off the P930/P933 power supply.

2

Turn off the supply power to the power supply.

3

Remove the supply power line from the P930/P933 power terminal.

4

Loosen mounting screws on top and bottom of the front face of the P930/P933
and slide the P930/P933 out of the chassis.

5

Replace fuse with on of the same type and size.

Failure to attach to a running controller:
Step

Procedure Four

Action

Action

1

Ensure that the proper cables and software are being used.

2

Are the communication parameters on the computer the same as those on the
controller?

3

Check the cable attachment and pinout.

4

If Modbus Plus is being used then ensure the Modbus Plus driver is installed and
the Modbus Plus active LED on the SA85 or PC85 card and the controller are
flashing at six times a second. (The Modbus Plus Indicator normal operating
state.)

5

If this is the first time this cable has been used then test the cable.

If Modbus Plus is the chosen mode of communication, please ensure that the
Modbus Plus driver software is installed. You may use the Modbus Plus diagnostic
tools included with the driver suite. Check if the Modbus Plus active LED is flashing
both at the interface card (PCI85 or SA85) and at the PLC. Normal indication is six
times per second.

372 SPU 780 01EMAN May 2002

275

Troubleshooting

Modbus Plus
Modbus Plus
Communications
for Concept Exec
Loader

When using Modbus Plus communications and the interrupt is NOT "5C", you must
add the following line to the "modicon.ini" file located in the Windows folder:
Under the heading: [Ports]
MBP0 (or MBP1) = interrupt 5D

Modbus Plus
Indicator

On most Modbus Plus devices, a green LED flashes a repetitive pattern indicating
the communication status of the node. The patterns are:
l Six flashes per second: Normal operating state. The node is successfully
receiving and passing the token. All nodes in operation on the network should be
flashing this pattern.
l One flash per second: Node is offline after just being powered up or there is
another node on the network with the same address (duplicate addresses are not
allowed). The node remains in this state for five seconds, then attempts to go to
its normal operating state.
l Two flashes, then OFF for two seconds: Node is hearing the token being passed
among other nodes, but is never receiving the token. Check the network link for
an open or short circuit, or defective termination.
l Three flashes, then OFF for 1.7 seconds: Node is not hearing any other node. It
is periodically claiming the token, but finding no other node to which to pass it to.
Check the network link for an open or short circuit, or defective termination.
l Four flashes, then OFF for 1.4 seconds: Node has heard a valid message from
another node that is using the same address as this node. The node remains
offline in this state as long as it continues to hear the duplicate address. If the
duplicate address is not heard for five seconds, the node then changes to the
pattern of one flash every second.

276

372 SPU 780 01EMAN May 2002

Troubleshooting

Stopcode Error Analysis
Stopcode Error
Analysis

Bit/Error reference:

372 SPU 780 01EMAN May 2002

Bit

Error

0 (0001 Hex)

Illegal Configuration Someone or something has probably been
modifying controller memory and the configuration is
not valid for this controller. The error may also be
caused by a bad memory board or Executive pack or
by inserting the wrong memory or executive into a
controller.

Description

1 (0002 Hex)

984 A/B/X and 584 - Information saved in a coil and register has been
Backup Checksum corrupted. In order to recover the corrupted
information, the program must be reloaded. A bad
Error
memory board may also cause this error.

1 (0002 Hex)

984 -80 Series (984
A/B/X - some
PROMS) Discrete
Disabled Error

Usually caused by trying to start the controller in the
optimized mode with discrete points that are
disabled.

2 (0004 Hex)

Logic Checksum
Error

The calculated user logic checksum does not agree
with the stored checksum. It can be caused by an
illegal change of memory or by a bad memory board.
Try reloading the program. This error also occurs if
the ASCII area has been loaded incorrectly. If
reloading fails then try initializing the ASCII area. As
a last resort try replacing the memory board.

3 (0008 Hex)

Invalid Node Type

This error usually occurs when loading the
controller. It may be caused by loading or relocating
a program from a machine supporting a DX
instruction not supported or configured for in the
target machine, i.e. relocating a program with an
HSBY function block to a 984 not configured for an
HSBY. It may also be caused by loading a program
made on a 24 bit machine to a 16 bit machine i.e.,
specifying a constant greater than 999.

277

Troubleshooting

278

Bit

Error

Description

4 (0010 Hex)

Causes:
S908 RIO Head
Failure or Remote I/ l A failed S908 RIO board (replace the board)
O option failed
l Illegal board configuration in the 984 (e.g., the
wrong PROM pack)
l Configuring for more than one drop and not
attaching anything to the S908
l Cards contained in the Traffic Cop that are not
present in the field or cards in the field that
mismatch with the Traffic Cop.
l Powering up an intelligent I/O card (B984) at the
same time as the 984
l Attempting to start an HSBY system without the
S908 cards interconnected.
l Cycling power on the controller may be
necessary to clear this error.

5 (0020 Hex)

984 A/B/X and 584
CPU Diagnostic
Failure

The CPU board is bad and should be replaced.

5 (0020 Hex)

984 -80 Series Bad
Coil Used Table

The coils existing in the logic do not match those
found in the used table.

6 (0040 Hex)

Real Time Clock
Failure

The CPU board is bad and should be replaced.

7 (0080 Hex)

Watchdog Time
Expired

This bit is usually set in conjunction with another. It
often signals a Data transfer program that is too
large. The logic is not being solved fast enough.

(0090 Hex)

Real I/O Option
Failed

Check that the S908 card is properly installed and
that its ready light is on steady.

8 (0100 Hex)

No EOL Detected or This error usually occurs when a startup is
attempted after the incomplete loading of a program.
Bad Number of
Reload or try another program.
Segments
Note: You may receive this system error when you
first configure the system, before you have
programmed any logic. This is not a fatal error. The
system cannot find the end of logic because there is
no logic programmed from the primary to the
standby state.

9 (0200 Hex)

984 A/B/X and 584
State RAM Test
Failure

The continuously running diagnostics have failed.
Replace the RIO processor.

372 SPU 780 01EMAN May 2002

Troubleshooting

372 SPU 780 01EMAN May 2002

Bit

Error

Description

9 (0200 Hex)

984 -80 Series Bad
Power Down
Checksum

Cycle the power on the controller to clear the error or
Start Controller.

10 (0400 Hex)

SON Did Not Start
Segment

Improper programming from a programming device
or software package is usually the cause of start-ofnode failure.

11 (0800 Hex)

Bad Segment
Scheduler Table

The Segment Scheduler has been programmed
improperly.

12 (1000 Hex)

Illegal Peripheral
Intervention

This error is caused by an attempt to clear the
System Stop State word. A programming device has
altered memory in a non-authorized manner.

13 (2000 Hex)

Dim Awareness

The 984 has not been configured successfully. This
bit can be set in conjunction with other flags.

14 (4000 Hex)

984B and 584
Extended Memory
Parity Error

This error indication pertains to the 984B or
extended memory 584 only. Try reloading memory.
If that fails to solve the problem, replace the memory
board.

14 (4000 Hex)

984 -80 Series
Traffic Cop Failure

Usually caused by configuring for more than one
drop and not having an S908 remote I/O processor
in the controller rack. This error can also be caused
by too many points contained in the Traffic Cop (512
inputs and 512 outputs allowed per drop), or by
more cards in Traffic Cop than physically present
(Micro 984).

15 (8000 Hex)

Peripheral Port
STOP

This simply indicates the PLC has stopped.

279

Troubleshooting

B.2

Status Words for S901 and S908

At a Glance
Overview

With both the S901 and S908 controllers, the first 11 Status Words are always found
at absolute memory address 65-6F hex. Pointers determine the absolute memory
locations of the remaining words. A pointer for the start of the status information is
always located at address 6F hex.

What’s in this
Section?

This section contains the following topics:

280

Topic

Page

ASCII Message Status

281

Cable A Errors

282

Cable B Errors

283

Communication Status

284

Controller State

286

Controller Status

287

EOL (End of Logic) Pointer

288

Global Errors

289

S911 Hot Standby Status (S908)

290

Local Drop Communications Errors (S908)

291

Machine Configuration

292

Module Health

293

Number of Segments

295

Status Word Pointer Table

296

RIO Time-out

297

Run/Load/Debug Status

298

S901/J200 Status

299

S908 Errors

300

Stopcode

301

372 SPU 780 01EMAN May 2002

Troubleshooting

ASCII Message Status
Word 6D Hex
(109 Decimal)

This word reflects the status of the ASCII message database. Bits set in this word
indicate that errors occurred while creating or editing ASCII messages.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Number of ASCII messages and number of messages
pointers do not match
Invalid message pointer
Invalid message
Message checksum error

372 SPU 780 01EMAN May 2002

281

Troubleshooting

Cable A Errors
Cable A Errors

Cable A is the main cable connecting the remote I/O Processor to the Remote I/O
Interface.
Status Word

Description

173

The count of frame size errors and DMA overrun errors. The high order byte
represents a count of Cable A frame size errors. This indicates that the length
of the data message was incorrect. The low order byte represents a count of
DMA receiver overrun counts. This indicates that the hardware had more
data to send than was required.

174

The Cable A LAN receiver error counter and the Bad Drop reception on cable
A counter. This indicates a cable or noise problem to a drop. The "Drop
Communication Errors (173)" should be examined to determine which drop
is having problems.

175

The last received LAN error code for cable A. The LAN hardware detected
an error in receiving a message.

1 = Overrun error
1 = Alignment error
1 = CRC error
1 = Received message OK

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 = No end frame
1 = Short frame

282

372 SPU 780 01EMAN May 2002

Troubleshooting

Cable B Errors
Cable B Errors

Cable B is the secondary or redundant cable connecting the Remote I/O Processor
to the Remote I/O Interface (optional redundant cables).
Status Word

Description

176

The count of frame size errors and DMA overrun errors. The high order byte
represents a count of Cable B frame size errors. This indicates that the length
of the data message was incorrect. The low order byte represents a count of
DMA receiver overrun counts. This indicates that the hardware had more
data to send than was required.

177

The Cable B LAN receiver error counter and the Bad Drop reception on cable
B counter. This indicates a cable or noise problem to a drop. The "Drop
Communication Errors (173)" should be examined to determine which drop
is having problems.

178

The last received LAN error code for cable B. The LAN hardware detected
an error in receiving a message.

1 = Overrun error
1 = Alignment error
1 = CRC error
1 = Received message OK

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 = No end frame
1 = Short frame

372 SPU 780 01EMAN May 2002

283

Troubleshooting

Communication Status
Communication
Status 1/2 (S901)

The Remote I/O communication Status Word 1 shows errors and normal operating
indication of the indicated channel pair. Under normal operating conditions the lower
byte should be counting and the upper portion of the byte should match the lower
portion of the byte.
Any bits set in the upper byte indicates an error condition for the channel pair. Note
that a disconnected channel pair or a channel pair that does not exist will set the
function scheduled to 001 (Restart - communication reset).
1 = Message from controller is queued
Current message frame # to drop
Cable ID: 0 = Cable 0, 1 = Cable 1
# of next expected frame from drop
1 = Current message not
accepted at drop

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 = Current message not supported
1 = Response message count > transmitted byte count
1 = Response from remote interface not what expected
Function schedule
Function Schedule:
Binary Number Description

284

000

Normal I/O

001

Restart (comm reset)

010

Restart (application reset)

100

Inhibit

372 SPU 780 01EMAN May 2002

Troubleshooting

Communication
Status 2/2 (S901)

The Remote I/O communication Status Word 2 shows errors and the retry count on
lost communications. If communications is lost with the channel pair then the
corresponding error bit will be set and the retry counter will increment. If the retry
counter counts to maximum then other indicators will be affected.
Module health will show as ’0’. If communication is re-established, this error count
and error word is not cleared. The only way to clear this word is to cycle power on
the controller or issue a start and stop command.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Retry counter
1 = Command not supported by drop
1 = Invalid frame number
1 = Drop just powered up
1 = Address did not respond
1 = CRC error from address drop
1 = Character overrun error from addressed drop

372 SPU 780 01EMAN May 2002

285

Troubleshooting

Controller State
S908 Controller Word 65 Hex
(101 Decimal)

The Controller state word shows information pertaining to the state and size of the
controller. A state is any condition, which is either set for the life of the controller (16bit vs. 24-bit) or set by external events (memory protect). The upper bits have no
meaning for an 984/S908 or –80 -85 controllers. The AC power bit will always be on
or monitoring would not be possible. The down size flag indicates controllers with <
4K logic memory. Some Micro 984 controllers show a 0 for battery failed. The 16 bit
user logic bit indicates controllers that support 2048 references. (The 984B and the
780/785 are 24-bit controllers.)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 = Battery failed
1 = Memory protect OFF
1 = Run light OFF
1 = AC power ON
1 = 16-bit user logic (Max 2048
reference system
1 = Single sweep invoked
1 = Constant sweep invoked
S901 Controller Word 65 Hex
(101 Decimal)

286

The Controller state word shows information pertaining to the state and size of the
controller. A state is any condition that is either set for the life of the controller (16bit vs. 24-bit) or set by external events (memory protect). The AC power bit will
always be on or monitoring would not be possible. The down size flag indicates
controllers with < 4K logic memory. The 16-bit user logic bit indicates controllers that
support 2048 references. (The 984B and 584 Level 4 are 24-bit controllers.)
D0

Reserved

D1

Set offline mode

D2

Set data exchange active

D3

Operating mode

372 SPU 780 01EMAN May 2002

Troubleshooting

Controller Status
S908 and S901
Controllers Word 67
(103 Decimal)

The controller status words indicate certain statuses of the machine. A status is any
condition which changes during the running of the controller, usually from an internal
event.
Word 3 (4xxxx + 2) - General controller status:

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 = Existing DIM AWARENESS
Single sweeps (00)
1 = Constant sweep time exceeded
1 = Start command pending
1 = First scan

372 SPU 780 01EMAN May 2002

287

Troubleshooting

EOL (End of Logic) Pointer
Word 6B Hex
(107 Decimal)

This location contains the end of logic pointer. The EOL pointer provides the
hexadecimal address of the end of user logic.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
EOL pointer address

288

372 SPU 780 01EMAN May 2002

Troubleshooting

Global Errors
Global Errors
Status Word

Description

179

The Global Communication Status. This word stores communications status
for both cable A and cable B. Cable A is the main cable connecting the
remote I/O Processor to the Remote I/O Interface. Cable B is the optional
secondary or redundant cable. The specific information stored is shown in
the figure below.

180

Global Cumulative error counter for cable A. High byte - Framing error count
/ Low byte - No response count. Errors counted here cause the error counters
in Cable A Errors, p. 282 to increment.

181

Global Cumulative error counter for cable B. High byte - Framing error count
/ Low byte - No response count. Errors counted here cause the error counters
in Cable B Errors (169) to increment.

Figure 1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Dropout counter

Retry counter

0 = Cable B status error
0 = Cable A status error
0 = Communication health error

Note: It is possible for bits 2 and 3 to be ‘1’ and bit 1 to be ‘0’ "Cables (171)"

372 SPU 780 01EMAN May 2002

289

Troubleshooting

S911 Hot Standby Status (S908)
Word 66 Hex
(102 Decimal)

The hot standby status is valid if a redundancy system is present. It shows if the unit
is reporting present and healthy and the word also indicates if the unit is the primary
or secondary controller.
Word 4 (4xxxx + 3) - S911/R911 Hot Standby Status

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
S911/R911 present and healthy
0 = Controller set to A
1 = Controller set to B
0 = Controllers logic matches
1 = Controllers logic mismatches
Remote system state
Local system state
System State:
Binary Number

290

Description

01

Offline

10

Primary

11

Secondary

372 SPU 780 01EMAN May 2002

Troubleshooting

Local Drop Communications Errors (S908)
Status Words
182-184

Status Words 182 to 184 show the status of the local drop communication errors
(when a local drop is present). The first drop may or may not be a local drop
depending upon the controller type being used.
Status Word

Description

182

The overall health and retry counter for the local drop. If the MSB is not 1 then
there are Module Health (166) errors on the local drop.

183

The ourbus error count for the local drop. If the count is incrementing then
there are errors on the local drop. This may be caused by invalid information
in the traffic cop, an unhealthy module in the local drop, or a mismatch
between the traffic cop and the module that exists in a slot located in the local
drop.

184

The ourbus retry count for the local drop. Under normal operating conditions,
only the all modules healthy bit should be set.

Figure 1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 = All modules healthy
Retry counter

372 SPU 780 01EMAN May 2002

291

Troubleshooting

Machine Configuration
Word 61 Hex
(97Decimal)

This screen shows the options that are present for the attached controller. These
options include remote I/O (S908 processor), Modbus II, Hot Standby, Distributed
Control Processor (D908) and Coprocessors. It also indicates whether or not the
time of day option is available for this controller and the remote I/O adapter size.
Note: Some versions of the S908 remote I/O processor only support 6 remote drops.
A ’1’ indicates that an option is present.
Figure 1
0 = Small RIO (7 drops including 1 local)
1 = Large RIO (32 drops including 1 local)
0 = TOD present

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 = Copro 4 present
1 = Copro 3 present
1 = Copro 2 present
1 = Copro 1 present
1 = DCP present (-80), SA85 present (984 A/B)
1 = HSBY present
1 = Modbus II present
1 = Remote I/O present (RIO)

292

372 SPU 780 01EMAN May 2002

Troubleshooting

Module Health
S908 Controller

Module Health Status information consists of up to 160 words. A single bit is used
to represent the Health Status of a single module. A binary ’1’ means that the module
is healthy. Each drop in the I/O sub system has five words allocated to contain I/O
module status. Each of these five words contains the I/O module status of a single
rack within the drop. The most significant bit (MSB) represents the status of the
module in slot 1. Slot 2 module status is represented by the bit to the immediate right
of the MSB.
A healthy I/O module must meet the following conditions:
l The specified slot must be configured in the Traffic Cop.
l The slot must contain the module specified in the Traffic Cop.
l Valid communication must exist between the module and the interface.
l Valid communication must exist between the interface module and the controller.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Odd channel bits 1 through 8

Even channel bits 9 trough 16

Note: If a module is configured in the Traffic Cop and active, then the bit will be 1.

WARNING
Upgrade Recommended
On systems using J890/J892s with PROM rev 1000, slot 1 will be the
LSB. J890/J892s with PROM revs greater than 1000 will appear as
previously described. The earlier J890/J892s should be upgraded as
they will be incompatible with any user programming that assumes slot
1 status to be the MSB.
Failure to follow this precaution can result in severe injury or
equipment damage.

372 SPU 780 01EMAN May 2002

293

Troubleshooting

S901 Controller

The I/O Module Health Status information consists of words that represent the
module health for channel pairs. Each word represents 2 channels. The words are
also divided into input modules and output modules. A single bit is used to represent
the Health Status of a single module.
If the slot is inhibited in the Traffic Cop then the bit will be a ’0’. If the slot contains
an input module then the bit will be a ’1’. This will not be the case if the
Communication Status Word 2/2 (183) indicates an error.
If the slot contains an output module and if the active light is on then this bit will be
a ’1’. If the active light is off then this bit will be a ’0’. It is common to set the status
indicator for an output slot to toggle between ’0’ and ’1’ when active and healthy.
The Upper byte contains the status of the lower channel number of the channel pair
(for example, channel 1 for channel pair 1/2). The lower byte contains the status of
the higher channel number of the channel pair. Each byte represents the status of
slots 1 to 8 of the channel. The Most Significant Bit of the channel represents slot 1
and the Least Significant Bit shows the status of slot 8.
Status Word #012: Drop # 01/01 Rack # 1/5

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Slot #1 through Slot #11 E-Series

294

Plus these five w/Quantum

372 SPU 780 01EMAN May 2002

Troubleshooting

Number of Segments
Word 6A Hex
(106 Decimal)

This word is confirmed during power up to be the number of I/O exchange nodes
plus 1 (for end of logic). If this is not true then a stop code of 0100 would result.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Number of segments

372 SPU 780 01EMAN May 2002

295

Troubleshooting

Status Word Pointer Table
Description

296

The address in 6F points to a table of pointers 76 words long. It is important to
remember that this 76 word long table is a table of address pointers for the 75 word
long system status area.

372 SPU 780 01EMAN May 2002

Troubleshooting

RIO Time-out
Word 6C Hex
(108 Decimal)

This word contains the Remote I/O time-out constant and a bit that indicates if
redundant cables are present.
Note: Cable A and Cable B are used for remote I/O communications.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Redundant remote I/O cables
Remote I/O timeout constant

372 SPU 780 01EMAN May 2002

297

Troubleshooting

Run/Load/Debug Status
Word 6E Hex
(110 Decimal)

This word is a mode indicator for 984 controllers. The load mode is used for loading
a program to the controller. The run mode indicates that the controller was started
in the optimized mode (no editing allowed while running). The debug mode is the
normal mode of operation for a controller. In this mode network editing is allowed
while the controller is running.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
0
0
1

298

0 = Debug
1 = Run
0 = Load

372 SPU 780 01EMAN May 2002

Troubleshooting

S901/J200 Status
Word 68 Hex
(104 Decimal)

This word shows the status of the remote I/O processor. The upper 4 bits should be
zero under normal operating conditions. An error indicates a failure in the remote I/
O processor.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 = S901 (J200) memory failure
RIO error status
1 = S901 (J200) loopback failure
1 = S901 (J200) timeout
1 = S901 (J200) bad
RIO error status:
Binary Number Description

372 SPU 780 01EMAN May 2002

000

RIO did not respond

001

No response on loopback

010

Failed loopback data check

011

Timeout while awaiting response

100

RIO did not accept all of message

299

Troubleshooting

S908 Errors
S908 Errors

300

This word is the S908 start error code. This word will always be 0000 in a running
system. If an error does occur, the controller will not start and will generate a
Stopcode system error of 4000.
Number

Description

Number

Description

1

Bad Traffic Cop Length

23

Bad Number of Input Bytes

2

Bad Remote I/O Link Number

25

Bad First Reference Number

3

Bad Number of Drops

26

Bad Second Reference Number

4

Bad Traffic Cop Checksum

27

No Input or Output Bytes

10

Bad Drop Descriptor Length

28

Discrete Not on 16 Bit Boundary

11

Bad I/O Drop Number

30

Unpaired Odd Output Module

12

Bad Drop Holdup Time

31

Unpaired Odd Input Module

13

Bad ASCII Port Number

32

Unmatched Odd Module
Reference

14

Bad Number of Modules in Drop

33

1xxxx Reference After 3xxxx
Register

15

Drop Already Configured

34

Dummy Module Reference
Already Used

16

Port Already Configured

35

3xxxx Module Not a Dummy

17

More than 1024 Outputs

36

4xxxx Module Not a Dummy

18

More than 1024 Inputs

40

Dummy Then Real 1xxxx Module

20

Bad Module Slot Address

41

Real Then Dummy 1xxxx Module

21

Bad Module Rack Address

42

Dummy Then Real 3xxxx Module

22

Bad Number of Output Bytes

43

Real Then Dummy 3xxxx Module

372 SPU 780 01EMAN May 2002

Troubleshooting

Stopcode
S908 Controller Word 69 Hex
(105 Decimal)

This word contains a Stopcode that describes what kind of stop state (if any) that the
machine has. A ’1’ in the most significant bit indicates that the controller is not
running. Any other ’1’ bit indicates an error. It is possible to have multiple errors. For
a detailed explanation of Stopcodes, see Stopcode Error Analysis, p. 277.
Illegal configuration
State RAM checksum error
User logic checksum error
Invalid node
Invalid traffic cop
CPU logic solver failed or coil use table (for other controllers)
Real time clock error
Watchdog timer expired

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
No EOL / Bad # segments
State RAM test failed
Start of node did not start segment
Segment scheduler invalid
Illegal peripheral intervention
Controller in DIM AWARENESS
Extended memory parity error
Peripheral port stop

372 SPU 780 01EMAN May 2002

301

Troubleshooting

S901 Controller Word 69 Hex
(105 Decimal)

This word contains a Stopcode that describes what kind of stop state (if any) that the
machine has. A ’1’ in the most significant bit indicates that the controller is not
running. Any other ’1’ bit indicates an error. It is possible to have multiple errors. For
a detailed explanation of Stopcodes, see Stopcode Error Analysis, p. 277.
Illegal configuration
State RAM checksum error
User logic checksum error
Invalid node
IOP failure
CPU logic solver failed or coil use table (for other controllers)
Real time clock error
Watchdog timer expired

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
No EOL / Bad # segments
State RAM test failed
Start of node did not start segment
Segment scheduler invalid
Illegal peripheral intervention
Controller in DIM AWARENESS
Traffic cop error
Peripheral port stop

302

372 SPU 780 01EMAN May 2002

Editing .DIF Files with Microsoft
Excel

Editing .DIF files with Microsoft Excel
Overview

When Excel imports a .DIF file, it converts the controller addresses in the first
column of the database into numerical values which ProWORX 32 cannot read.
Excel also exchanges the rows and columns of the database in the .DIF file’s
header. Unless you correct these problems, an error appears when you try to import
a .DIF file back into ProWORX 32 after you have changed it in Microsoft Excel.
To use Excel to edit documentation, follow these seven steps:

Step One

Set the size of your descriptor fields for Microsoft Excel.
Step

Step Two

Action

1

Select the ProWORX 32 project whose documentation you want to edit.

2

From the project right-click menu in the navigation tree, select Properties.

3

In the properties dialog, select the Documentation tab.

4

Set Number of Descriptor Lines to 9.

5

Click OK to save changes and return to ProWORX 32.

Export your ProWORX 32 project as a .dif file.
Step

372 SPU 780 01EMAN May 2002

Action

1

From the project right-click menu in the navigation tree, select Export
Documentation.

2

Select a path and enter a file name in the Select Destination File dialog.

3

Click OK to export documentation.

303

Editing .DIF Files with Microsoft Excel

Step Three

Open and edit the documentation in Microsoft Excel.
Step
1

Action
Open the .DIF file in Microsoft Excel.
The number in Column A tells you what controller address the row describes. The
letter in Column B tells you what information the next cells in the row contain:
l D - Descriptors 1 through 9 in columns C through K.
l S - Short Comments 1 through 4 in columns C through F.
l L - Long Comment lookup number in column C.
l T - The Page Title in column C

2

304

Make your changes to the documentation.

372 SPU 780 01EMAN May 2002

Editing .DIF Files with Microsoft Excel

Step Four

Convert the controller addresses from numbers to text.
Step
1

Find an unused column in the spreadsheet. This temporary column holds
information during the conversion process.

2

In the first cell of the unused column, type: =TEXT(A1,"00000"). This formula
converts the numerical value in cell A1 into a text value which ProWORX 32 can
read. When you press ENTER, the text value appears in the cell where you
entered the formula.

3

Select the cell.

4

From the Excel menu, select Edit → Copy.

5

Select the temporary column by clicking its header. For example, if you entered
the TEXT formula into the first cell of Column M, now select all of Column M.

6

From the Excel menu, select Edit → Paste. This operation pastes the TEXT
formula copied from the first cell of the temporary column into all the other cells
in the column. Click Yes if a warning message appears telling you that the
selection is too large for Undo. The temporary column now contains the same
values as Column A, but formatted as text instead of numbers.

7

Select the entire temporary column again.

8

From the Excel menu, select Edit → Copy.

9

Step Five

Action

Select Column A.

10

From the Excel menu, select Edit → Paste Special, then click Values. The text
values from your temporary column replace the numerical values in column A.
Click Yes if a warning message appears telling you that the selection is too large
for Undo.

11

Select the entire temporary column.

12

From the Excel menu, select Edit → Clear then click All. The values in your
temporary column disappear. Click Yes if a warning message appears telling you
that the selection is too large for Undo.

Export the Microsoft Excel spreadsheet as a .dif file.
Step
1

372 SPU 780 01EMAN May 2002

Action
Save the edited database as a .DIF file.

305

Editing .DIF Files with Microsoft Excel

Step Six

Correct the rows and columns in the .dif header.
Step

Step Seven

1

Open the .DIF file with a text editor. (Notepad or Wordpad)

2

Switch the "VECTORS" and "TUPLES" values in the header of the .DIF file.

3

Save the edited database as an ASCII .DIF file.

Import the documentation back into ProWORX 32.
Step

306

Action

Action

1

From the project right-click menu in the navigation tree, select Import
Documentation (Append, Overlay or Create New).

2

Select the .dif file containing the changed documentation from the Select
Documentation File dialog.

3

Click Open. The documentation of the current project is updated.

372 SPU 780 01EMAN May 2002

Glossary

A
Address

1) On a communications network, the identifying number for a station such as a
PLC.
2) In a computer’s or PLC’s memory, a location where data, usually a specific input
or output value is stored.

Address Used
Table

A list of all I/O addresses in a controller, indicating which addresses are being used
in ladder logic instructions and which are not.

Analog

Inputs (such as temperature) or outputs (such as motor speed) which can have a
range of values. Compare to Discrete.

ASCII

American Standard Code for Information Interchange.
1) A way of encoding the standard text (the letters, numbers, etc. on your keyboard)
your computer generates.
2) A data transmission mode for Modbus communications which sends and receives
standard text. ASCII mode used 7 data bits while RTU mode uses 8.

ASCII Message

A text message transmitted or received by a programmable controller. These
messages are sent to or from a terminal through an ASCII port.

Assembly
Register

A register that accepts keyboard input for command and value entry in the Network
Editor.

372 SPU 780 01EMAN May 2002

307

Glossary

Attaching to

Also called selecting. Connecting your PC to a programmable controller so
ProWORX 32 can read its ladder logic, traffic cop information, and configuration,
and write changes back to it.

B
Baud Rate

For serial communications, the speed (in bits per second) at which data is
transmitted.

BCD

Binary Coded Decimal.

Binary

The base-two numbering system. It has two symbols: 1 (representing ‘On’) and 0
(‘Off’)

Bit

The smallest amount of information in binary: either a 1 or a 0.

Bits per Second
(BPS)

The number of bits passed from one device to another in one second. Used to
measure data transmission speed.

Block

A section of ladder logic which is defined while using the logic editor. This block can
be copied, deleted, saved, moved, and loaded.

BM85

See Bridge Multiplexer.

BP85

See Bridge Plus.

Bridge
Multiplexer

Allows you to connect up to four Modbus devices or networks of Modbus devices to
a Modbus Plus network. Nodes on the Modbus Plus network can access slave
devices connected to the BM85 Modbus ports.

Bridge Plus

Links together two Modbus Plus networks.

Byte

A group of eight bits. A byte stores a value from 0 to 255.

C
Cell

308

A single location in ladder logic.

372 SPU 780 01EMAN May 2002

Glossary

Channel

In an S901 I/O subsystem, a group of 128 inputs and 128 outputs assigned to a
segment. The ladder logic in the segment usually controls all I/O operations of the
corresponding channel.

Characters per
Inch (CPI)

The number of characters a printer prints in one inch. (Also called horizontal pitch.)

Checksum

A calculation that sums a range of data and compares it to a pre-calculated value.
This determines if the data is in error or has changed.

Coaxial Cable

A round cable containing two conductors, one inside the other (separated by a
insulator). The inner conductor transmits a signal while the outer conductor is a
shield.

Commentary

The descriptors, short comments, long comments, and page titles within a project.

Controller

An industrial control computer, also called a programmable logic controller or PLC.

CPS

Characters per Second.

Cross-Reference

A list of the networks in which a particular address can be found.

Current Element

The cell or ladder logic element being edited. The logic editor’s cursor is always on
the current element.

Current Network

The network being edited. The network displayed in the logic editor is always the
current network.

Cursor

A bar or block which indicates a position on the screen. Generally, the cursor is
located where something can be inserted or selected.

D
Data Bits

The bits in a data package which carry a message, distinct from start bits, stop bits,
and parity bits. Remote Terminal Unit mode (the Modbus default communication
mode) sends eight data bits per package. ASCII mode sends seven data bits per
package.

Data Contents

A printout showing the data values in a ladder logic program.

Data Register

A 4xxxx holding/output register.

372 SPU 780 01EMAN May 2002

309

Glossary

DCP Drop ID#

A distributed control processor drop address. It is equivalent to the drop number
used by the DCP.

DCP-908

A distributed control processor providing intelligent bidirectional communication
between a supervisory 984 controller and distributed 984 controllers.

Decimal

The base-ten number system. It consists of the symbols 0 through 9.

Default

A value automatically assigned by the computer in a software program. Usually, this
value can be changed.

Descriptor Field

One of up to nine text strings which are a short description of an address within a
ladder logic program.

Descriptor
Record

All descriptors, short comments, the long comment number, and the page title for
one address point.

Descriptor Table

The table of addresses displayed on the screen in the descriptor module.

Descriptor
Tables Listing

A group of printouts which consist of tables of descriptors, a table of short
comments, long comments, and mismatch tables.

Descriptors

A short description of an address within a ladder logic program. A number of
descriptor fields.

Device

Any programmable unit (such as a PLC, numeric controller, or robot) or I/O card.

Dim Awareness

The state of a PLC that contains no logic, configuration, or traffic cop information.

Directory

A group of files and/or subdirectories. A directory called the root directory is placed
on each disk when it is formatted. Subdirectories can be created within the root
directory and within other subdirectories. Files can be stored in a subdirectory or the
root directory. In Windows, directories are often called "folders".

Disable

To stop the programmable controller’s logic-solving mechanism from updating the
state of a coil or updating the state of a discrete input. Also see Force.

Discrete

Inputs (such as switches) or outputs (such as coils) that can only be on or off.
Discrete inputs are usually held in 1xxxx registers. Compare to Analog.

Display

A visual output device such as a monitor.

310

372 SPU 780 01EMAN May 2002

Glossary

Distributed I/O
(DIO)

One of four major architectures for input/output systems (also see Local I/O,
Remote I/O, and Peer-to-peer Communications). I/O that is installed away from
the PLC over a wide area and communicates with it through a Modbus Plus network.
One Quantum controller can support up to three distributed I/O networks, each with
up to 64 drops. The local rack houses a DIO processor for each network, which sets
the network’s head number.

Documentation

A description of a controller’s memory, logic, and configuration. The descriptors,
short comments, long comments, and page titles within a database.

Documentation
Editor

The editor in which descriptors, short comments, long comments, and page titles
can be entered and modified.

Double Precision

A 32-bit format which uses two registers to store numerical values.

Drop

A group of I/O cards physically connected together as an I/O network. A controller
reads information from the drop, solves logic, then writes results to the drop in one
segment of ladder logic. The Segment Scheduler controls the order in which drops
are serviced.

Duplicate Coil

An output coil address which has been assigned to more than one coil.

E
EEPROM

Electrically Eraseable Programmable Read-Only Memory.

Element

A ladder logic instruction such as a coil, timer, or short.

Enable

To allow a PLC, based on the logic programmed into it, to update the state of a coil
or input.

Equation
Network

A special section of logic that lets the programmer solve regular mathematical
equations within the network. Not supported by every controller.

Exponential
Notation

A format for numbers based on powers of 10. For example, +1.35E-4 indicates 1.35
multiplied by 10 to the power of -4 (i.e. with an exponent of -4), which works out to
0.000135.

Extended
Memory

Extra register memory available for some models of 984/584 controllers. It is
accessed through the XMRD and XMWT functions.

372 SPU 780 01EMAN May 2002

311

Glossary

Extension

The three letters after the period in a DOS file name, often used to indicate the file’s
purpose.

F
File

A collection of information stored on a disk. It can contain either a program or data.

File Name

The name of a file. ProWORX 32 uses DOS naming conventions: a file name can
have up to eight characters, followed by a period and a three character extension.

Force

To change the state of a coil or a discrete input, overriding any actions in ladder
logic. For example, if a coil is forced off, but the ladder logic is trying to turn it on, it
will remain off.

Function

A ProWORX 32 command or operation.

G
Global Address
Change

An operation in the Logic Editor which substitutes one address or a range of
addresses for another or several others.

H
Head

A collection of I/O drops tied to one CPU, DIO, or RIO processor. This term is
specific to Modicon’s Quantum hardware.

Hexadecimal

A base 16 representation of an integer. It uses the symbols 0 through 9 and letters
A through F.

I
I/O

312

Input/Output.

372 SPU 780 01EMAN May 2002

Glossary

I/O Configurator

A PLC internal operation that maps logic element addresses to physical I/O cards.
Also known as the Traffic Cop.

Instruction

One of the programmable controller’s instruction set.

L
Ladder Logic

A relay-based programming language typically used in programmable logic
controllers. So called because it looks vaguely like a ladder.

Ladder Logic
Documentation

Text information, notes, and other descriptions of the ladder logic.

Ladder Logic
Listing

A printout of a group of networks which make up a ladder logic program.

Latch

A coil, the state of which is backed up in memory.

Lines Per Page

The number of lines printed on a page when printing ladder logic listings.

Load

To retrieve data from a disk or other source.

Loader

A module that reads and writes ladder logic from a personal computer to a
programmable controller or an industrial programming terminal. It also starts and
stops a programmable controller from a personal computer.

Local I/O

One of four major architectures for input/output systems (also see Distributed I/O,
Remote I/O, and Peer-to-peer Communications). The PLC and I/O modules
communicate directly through wiring from the field. For Quantum controllers, local I/
O allows a CPU, power supply, and from one through 14 I/O modules in a single
backplane (up to 448 I/O points). Local I/O is limited to a single rack and is always
head number 0. RIO and DIO processors are added in the local rack to extend the
controller’s I/O system.

Logic Editor

The editor in which you edit ladder logic.

Long Comment

A block of text which comment on an address within a ladder logic program. These
are printed between the networks in the ladder listing.

LPI

Lines per inch.

372 SPU 780 01EMAN May 2002

313

Glossary

M
Machine Word

16 bits of data (two bytes). Also called a word.

Macro

Generic pieces of logic networks that can be inserted into main logic databases. See
also Macro Parameter.

Macro Parameter

A "placeholder" variable used in a macro. When inserted into a regular logic
database, each macro parameter is mapped to a real register address.

Master

A networked device which controls the devices it connects to. Compare to Slave.

Memory

The part of a computer or programmable controller which stores information for
manipulation.

Mismatch Tables

Two printouts which show the differences between two sets of data; for example,
between descriptor records that have been entered for PLC addresses and
addresses that have actually been used in a program.

Mnemonic
(ne-mon-ik)

1) A memory aid.
2) A computer instruction with an abbreviated name that indicates its function. For
example, BLKM is used for the Block Move instruction.

Mnemonic
Assignments

A table in the configuration menu that lists the configuration of function key levels,
prompts, and instruction mnemonics.

Modbus

Modicon’s RS-232C master-slave serial communications protocol.

Modbus Plus

Modicon’s high-speed, peer-to-peer, token-ring communications protocol.

Modem

Modulator/Demodulator. A communications device that allows a computer to
transmit information, usually over a standard telephone line.

Module

An input/output card.

Motion Control
I/O Drop

Usually, an I/O drop tied to an ICC410, 3220, or 3240 motion control system.

314

372 SPU 780 01EMAN May 2002

Glossary

N
Network

1) A unit of ladder logic in a matrix of elements that is 11 columns wide and seven
rows long. It is used to group a function’s ladder logic.
2) A chain of interconnected computers and/or programmable controllers which
share data.

Network
Comment

A descriptor record assigned to a network. Contains short comments, a long
comment, a page title and descriptors.

Network Listing

A printout of a group of networks of ladder logic which make up a program.

Network Logic

A programmable controller control program or the representation of a programmable
controller control program. It includes logic elements, networks, and register
contents.

Node

A device that is connected to a network and is capable of communicating with other
network devices, usually to send or receive I/O data.

Not Described
Mismatch Table

A printout of those programmable controller addresses in a ladder logic program
which do not have descriptor records.

O
Offline

When the computer is not connected to the programmable controller and works
instead from a database.

Online

When the computer is connected to a programmable controller, working with it
directly and in real time.

Operator

In mathematics (and in Equation Networks), a symbol or character that indicates a
specific operation to be performed on one or more elements, called operands. In "3
+ Y", the plus sign (+) is an operator that indicates addition between the two
operands, "3" and "Y".

Order of Solve

1) The order in which segments are solved, as ordered by the Segment Scheduler.

372 SPU 780 01EMAN May 2002

315

Glossary

2) The order in which elements are solved in a network.

P
Page Title

A line of text which describes a page or group of pages in a ladder logic listing.
Printed at the top of the page.

Path

The part of a file specification that indicates the drive and subdirectory the file is in.

PC

Personal Computer

Peer-to-Peer

One of four major architectures for input/output systems (also see Distributed I/O,
Local I/O, and Remote I/O). A protocol for networked devices in which any device
can initiate data transfer.

Power Flow

In logic, an instruction is highlighted if it solves true and passes power. All
instructions "upstream" of it (to its left in the Traffic Cop display) must also be
passing power.

Preset

The maximum value a timer or counter can have.

Processor

A Programmable Logic Controller.

Program

For PLC’s, a set of ladder logic instructions contained in a set of ProWORX 32 files
(a Project).

Programmable
Logic Controller
(PLC)

An industrial control computer, also known simply as a controller.

Project

A group of files sharing a common name (but different file extensions) where the
ladder logic program and descriptor data for a controller is stored.

ProWORX 32
Function

A ProWORX 32 command or operation.

316

372 SPU 780 01EMAN May 2002

Glossary

Q
Quick Print

A function that allows you to print a network to a printer, with or without
documentation.

R
Rack

A collection of up to 16 I/O modules mounted in one back plane.

Radix

The base system of a value. The radix of decimal numbers is 10, the radix of binary
numbers is 2 and the radix of hexadecimal numbers is 16. In ProWORX 32, the term
"radix" sometimes refers to a value’s data type: binary, integer, floating point and so
on.

Random Access
Memory (RAM)

Random Access Memory. Memory that holds programs while they are being
executed.

Read Only
Memory (ROM)

Memory that is not erased by a power failure and that is programmed at the factory
to hold vital information. This memory cannot be changed.

Remote I/O (RIO)

One of four major architectures for input/output systems (also see Distributed I/O,
Local I/O, and Peer-to-peer Communications). I/O that is installed away from the
PLC and communicates with it though a high-performance, S908 coaxial cable
network. For Quantum controllers, an interface device at each remote I/O drop
communicates with an RIO processor in the PLC. The interface device sets the
address of the drop. Each RIO processor supports up to 31 remote drops, each of
which allows 64 input words and 64 output words.

Remote Terminal
Unit (RTU)

A data transmission mode used for Modbus communications. RTU uses 8 data bits.

Reports Listing

A group of printouts which consist of hardware allocation, data usage, and data
contents for a ladder logic program.

Routing Path

The sequence of devices through which a message passes to reach its final
destination.

RS-232

A popular standard for a serial data link connection.

372 SPU 780 01EMAN May 2002

317

Glossary

Run Light

A light on the front panel of a controller that is on while the controller is running.

S
Save

To store information on a disk.

Search

To locate a specified network element (or elements) in the ladder logic.

Segment

A group of I/O networks solved as a unit by the programmable controller. The
Segment Scheduler controls the frequency of segment execution and order of I/O
operations. Each segment controls two I/O channels in a 584 or 984/S901
configuration, or one drop in a 984/S908 configuration.

Serial Port

A 9- or 25- pin port used for serial communications (for example, Modbus).

Short Comment

Up to four lines of text which comprise a comment about an address within a PLC
ladder logic program. Typically printed beside output instructions in the ladder
listing.

Short Comment
Field

One of up to four lines of text which comprise a comment about an address within a
PLC network logic program. Typically printed beside output instructions, or below
the network in the network listing.

Slave

A networked device controlled by another device. Slave devices to not initiate data
transactions. Compare to Master.

Slot

The position of an I/O module in a rack.

State Flow

In logic, an instruction is highlighted if it solves true instead of only when it passes
power (compare to Power Flow).

Stop Bits

Bits used to indicate the end of transmission of a data item or frame.

Subdirectory

A directory within a directory.

Sweep

For a PLC, one cycle of scanning inputs, solving logic, and writing outputs.

318

372 SPU 780 01EMAN May 2002

Glossary

T
TCP/IP

A communication protocol for computers connected through an Ethernet or Token
Ring network.

Text

A collection of ASCII characters.

Timeout

If communications fail, the program waits the specified number of seconds before
trying to communicate again.

Trace

An operation in the Network Editor that locates a specified output coil in the network
logic.

Traffic Cop

A programmable controller’s internal configuration that maps logic element
addresses to physical I/O cards.

U
Used Table

A list of all I/O addresses in a controller, indicating which addresses are being used
in instructions and which have not.

Utility

A computer program included in a software package, but run separately from the
package’s main program.

W
Word

16 bits of data (two bytes). Also called a machine word.

372 SPU 780 01EMAN May 2002

319

Glossary

320

372 SPU 780 01EMAN May 2002

Index

Symbols
.CSV, 56
.DBF, 56
.DIF, 56
Editing with MS Excel, 303
.DOC, 56
.FIL, 56
.FIS, 56
.MDB, 56
.TEF, 56
.TXT, 56
.XLS, 56

Authorization
Moving, 18
ProWORX 32, 17

B
Bitmap Files, in the HMI Window, 184
BM85 Bridge Multiplexer, 220
BootP Server, 223
Listening, 223
Bridge Multiplexer, 220
Configuring, 220
Modbus Ports, Configuring, 221
Troubleshooting, 222

A
Address Used Tables, 60
Address Used Tables, Printing, 236
Addresses
Finding Free, 61
Finding in Ladder Logic, 142
Forcing Discretes, 143
in the Logic Editor, 142
Tracking in the Data Watch Window, 177
Tracking, in Ladder Logic, 143
Analyze Device, 100
ASCII Messages
Configuring, 209
Editor, 209
Tools for Editing, 211
Audit Trail, 243

372 SPU 780 01EMAN May 2002

C
Clamps, in the Data Watch Window, 182
Client/Server, 35
Coils, in the Equation Network, 155
Communications
Ethernet Gateway, 72
Modbus, 67
Modbus by Modem, 68
Modbus Plus, 71
Setup, 66
TCP/IP, 73
Compact Phase II Configuration
Extension, 104
Compare
Projects and Controllers, 226
Reporting, 227
321

Index

Conditional Expressions, 160
Configuration Extensions
Compact Phase II, 104
Data Protect, 105
I/O Scanner, 108
I/O Scanner Wizard, 111
Overview, 102
Peer Cop, 113
Peer Cop Wizard, 118
Profibus, 121
Profibus Wizard, 122
Quantum Hot Standby, 106
Quantum VME Bus, 126
S980, 123
SY/MAX, 124
TCP/IP, 125
Configuring a BM85, 220
Configuring Controllers
ASCII Ports, 82
General Tab, 77
Loadables Tab, 83
Overview, 76
Ports Tab, 80
Simple ASCII Ports, 81
Contacting Schneider Electric, 26
Controllers
Comparing, 226
Configuring Configuring Controllers, 76
Initializing Logic, 90
Manual Procedure List, 274
Pinging, 229
Reading From, 91
Selecting, 31
Start/Stop, 98
Status, 99
Writing to, 92
Controls
Script Editor, 252
Converting Ladder Logic Databases, 34

D
Data Protect Configuration Extension, 105

322

Data Watch Window
Clamps, 182
DRUM Summary, 205
General Properties, 181
HMI, 184
Importing and Exporting, 207
Instruction Editor, 193
Log Files, 182
Logic Editor Addresses, Tracking, 191
PID Tuner, 202
Radicies, 181
Radicies, Setting, 178
Register Editor, 201
Sample Rate, 183
Terminal Block, 193
Traffic Cop Addresses, Tracking, 192
Trend, 188
Triggers, 181
Watch Window, 177
Desriptor Ranges, Printing, 235
Diagnostic Trace, 148
Documentation
Importing and Exporting, 55
Documentation Editor
Overview, 51
Using, 53
Documentation, Printing, 235
Drops, 165
DRUM Summary, 205

E
EEPROM, 94
Emulation, 39
Adding Instruction Solve Support, 46
Emulation Tab, 39
Enable Contact, Setting, 155
Environment Tab, 19
Equation Networks
Enable Contact, Setting, 155
Equation Formatting, 156
Mathematical Functions, 161
Mathematical Operations, 158
Overview, 154

372 SPU 780 01EMAN May 2002

Index

Equations
Exponential Notation, 157
Formatting, 156
Ethernet Gateway Communications, 72
EXECLoader, 95
Exporting
Data Watch Window Data, 207
Documentation, 55
Extended Memory Addresses
Displaying in the Register Editor, 201

F
Faults, Isolating, 273
Files
.ESF (Emulation Solve Files, 46
Bitmap, in the HMI Window, 184
Log Files, in the Data Watch
Window, 182
Find, 59
Finding Free Addresses, 61
Flash RAM, 96
Forcing Discrete Addresses, 143

H
Hardware Clock, 152
HMI
Background Color, Setting, 184
Bitmap Files, Creating, 184
Bitmap Files, Using, 185
Cell Captions, Using, 186
Cell Data, Editing, 185
Monitor Values, Adding, 187
Overview, 184
Rows and Columns, Setting, 184
Hotkey Template, 132

I
I/O
Drops, 165
Racks, 166
Slots, 167

372 SPU 780 01EMAN May 2002

I/O Cards
800 Series, 258
A120 Series, 261
Adding New, 246
Compact TSX Series, 263
Micro Series, 265
Momentum M1 and INTERBUS
Series, 266
Quantum, 267
Script Editor, 249
Script Editor, Using the, 249
Sy/MAX Series, 270
I/O Drawing
Generator, 171
Viewer, 228
I/O Scanner Configuration Extension
Editing, 108
Wizard, 111
Importing
Data Watch Window Data, 207
Documentation, 55
Initializing Controller Logic, 90
Installing ProWORX 32, 15
Instruction Editor
Display Scripts, 194
Overview, 193
Instructions
Finding in Ladder Logic, 140
in the Logic Editor, 140
Internal Flash, 97
ISA Symbols, 146

K
Knowledge Base, 62

L
Ladder Logic
Addresses, Finding, 142
Addresses, Tracking, 143
Initializing in a Controller, 90
Instructions, 140
Networks, 138
Loadable Library Wizard, 86

323

Index

Loadables
Copying, 84
Deleting, 85
Updating, 84
Log Files
Setting the File Size in the Data Watch
Window, 182
Logging In to ProWORX 32, 16
Logging Out of ProWORX 32, 16
Logic Editor
Bookmarks, 151
Diagnostic Trace, 148
Display, Customizing, 130
Equation Network, 154
Hardware Clock, 152
Instructions, 140
ISA Symbols, 146
Networks, 138
Overview, 129
Properties, 130
Segment Scheduler, 153
Sweep, 149
Tracking Addresses in the Data Watch
Window, 191

M
Macros, 214
Unlinking, 218
Using in Logic, 216
Marks, in Ladder Logic, 151
Materials List, 172
Mathematical Functions, 161
Mathematical Operations, 158
MBP Stat, 230
Micro
Flash RAM, 96
Mismatch Tables, Printing, 237
Mnemonics, 144
Modbus Communications, 67
Modbus Plus
Concept Exec Loader,
Communications, 276
LED Indicator, 276
Modbus Plus Communications, 71
ModConnect Schneider Alliances, 246
324

Modem Communications, 68
Modsoft
Hotkeys, 133
Moving Authorization, 18

N
NetScan Network Explorer, 74
Network Explorer, 74
Networks, 138
Printing, 235

O
Offline Edit Mode, 135
Online, Undo/Redo, 137
Opcodes, Editing, 87

P
PCMCIA, 97
Peer Cop Configuration Extension
Global Input, 114
Global Output, 114
Overview, 113
Specific Input, 116
Specific Output, 116
Subfields, 115
Wizard, 118
PID
Block Overview, 202
Tuner, 202
Ping, 229
PLC Status Viewer, 99
Ports
ASCII, 82
Micro, 82
Modbus, 80
Simple ASCII, 81
Profibus Configuration Extension
Overview, 121
Wizard, 122
Project
Emulation, 39
Project Properties Tab, 37

372 SPU 780 01EMAN May 2002

Index

Projects
Combined, 37
Converting, 34
Creating, 29
Emulation, 36
Managing, 35
Offline, 36
Online, 36
Selecting a Controller, 31
Wizard, 29
Protected Registers, 58
ProWORX 32
Authorization, 17
Contacting Support, 26
Environment, 19
Installing, 15
Logging In, 16
Reporting, 233
Security, 20
Server, 240
System Requirements, 14
Toolbar, 23
ProWORXPLUS
Hotkeys, 134

Q
Quantum Hot Standby Configuration
Extension, 106
Quantum VME Bus Configuration
Extension, 126
Quick Picks, 234

R
Racks, 166
Radix
Multi Radix View, Setting, 181
Setting Multiple Addresses, 178
Single Radix View, Setting, 181
Reading From a Controller, 91
Redo, in Logic, 136
Register Editor, 201
Register, Printing, 236
Registers
Protected, 58
372 SPU 780 01EMAN May 2002

Reporting, 233

S
S901
Analyzing, 100
S908
Analyzing, 100
Errors, 300
S980 Configuration Extension, 123
Sample Rate, in the Data Watch
Window, 183
Schneider Alliances
I/O Card Script Editor, 249
I/O Cards, 246
Overview, 246
Schneider Electric
Contacting, 26
Support Guidelines, 26
Script Editor
Controls, 252
Overview, 249
Using, 249
Scripts
Functions, Terminal Block/Instruction
Editor, 196
I/O Cards, 249
Instruction Editor, 194
Terminal Block, 194
Variables, Terminal Block/Instruction
Editor, 195
Search, 59
Search Panel, 59
Segment Scheduler, 153
Server
Creating Groups, 241
Creating Users, 241
Logging On, 240
Overview, 240
Setting Communications, 240
Status, 242
Slots, 167
Solve Mode, Emulation, 42
Starting a Controller, 98
Stopcode Error Analysis, 277
Stopping a Controller, 98
325

Index

Sweep
Constant Sweep, Performing, 149
Overview, 149
Single Sweep, Performing, 149
SY/MAX Configuration Extension, 124
Symbols
ISA, 146
System Requirements, 14

U
Undo, in Logic, 136
Uninstalling ProWORX 32, 15

W
Writing to a Controller, 92

T
Tables
Address Used, 60
TCP/IP
Communications, 73
TCP/IP Configuration Extension, 125
Terminal Block
Display Scripts, 194
Overview, 193
Toolbar, 23
Tracking Ladder Logic Addresses, 143
Traffic Cop
Drops, 165
Online Module Status, 169
Overview, 164
Printing, 236
Racks, 166
Slots, 167
Tracking Addresses in the Data Watch
Window, 192
Transferring Memory
EEPROM, 94
EXECLoader, 95
Flash RAM, 96
PCMCIA, 97
Trend
Alarm, Setting, 188
Graph Functionality, 189
Graph Functionality Table, 190
Overview, 188
Resolution, Setting, 188
Setpoint, Setting, 188
Y-Axis Values, Setting, 188
Triggers, in the Data Watch Window, 181
Troubleshooting, 271
Isolating Faults, 273
326

372 SPU 780 01EMAN May 2002



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : No
Create Date                     : 2002:05:03 08:46:43
Producer                        : Acrobat Distiller 4.0 for Windows