Scientech Electronics LS30N Alarm Base Unit User Manual

Scientech Electronics Co., Ltd. Alarm Base Unit

User Manual

      LLiiffeeSSOOSS   THE ADVANCED SECURITY & AUTOMATION SYSTEM FOR YOUR HOME & BUSINESS        Model LS-30 OPERATION MANUAL V5.23
   Table of Contents                                                                               Page    INTRODUCTION & INSTALLATION ---------------------------------------------------------   1               BASE UNIT --------------------------------------------------------------------------------------   3               STATUS INDICATORS ------------------------------------------------------------------------  4               ELECTRICAL INSTALLATION -------------------------------------------------------------  5               MECHANICAL INSTALLATION ---------------------------------------------------------    6   USER OPERATION --------------------------------------------------------------------------------    7               START OPERATION --------------------------------------------------------------------------   9               (2) System Check ------------------------------------------------------------------------------   10                     (2-1) Telephone Number Check ----------------------------------------------------------  11                     (2-2) Voice Check --------------------------------------------------------------------------   12                     (2-3) Device Check ------------------------------------------------------------------------  12               (3) Master Mode --------------------------------------------------------------------------------  13 OPERATION MODES OF LS-30 -----------------------------------------------------------  15 REACTION OF LS-30 TO DIFFERENT ALARMS -------------------------------------  16 ANSWERING THE CALL FROM LS-30 -------------------------------------------------  17 DIAL-IN CONTROL -------------------------------------------------------------------------  18   INSTALLER & CMS SETTINGS ----------------------------------------------------------------- 19               (4) Installer Mode ------------------------------------------------------------------------------  20                       (4-1) Set Timer ---------------------------------------------------------------------------    20                       (4-2) Set Telephone ----------------------------------------------------------------------     22                                 (4-2-1) Set Telephone Number --------------------------------------------------  24                       (4-3) Set Sound ---------------------------------------------------------------------------  26                       (4-4) Set Device --------------------------------------------------------------------------  28                                 (4-4-1) Change Device Setting -------------------------------------------------     29                       (4-5) Set Siren ----------------------------------------------------------------------------   31                       (4-6) Set Misc. ---------------------------------------------------------------------------     32               (5) CMS Mode ---------------------------------------------------------------------------------   33   SPECIFICATIONS---------------------------------------------------------------------------------   34   APPENDIX -------------------------------------------------------------------------------------------  35 A-1, In-coming Message Display. A-2, Connection Diagram for USB or RS-232 Computer Interface A-3, Connection Diagram for Ethernet Adaptor and Internet Remote Access A-4, Connection Diagram for X-10 Power Line Interface A-5, Terminal Board Connection A-6, Using the Same Telephone Line to Connect LS-30, Fax Machine and Telephone Answering Machine A-7, Partial Arm for Group Numbers “91” to “99”
                                INTRODUCTION & INSTALLATION                                  1
  Thank you for purchasing the LS-30 IP Based Wireless Security & Automation Control System. By adopting  modern  microprocessor  control and communication  technologies,  the  LS-30  is  designed  to provide all the most advanced features that you need to protect  your home and  business. Moreover, you can  operate  the  system  and  read  its  status  by  using  the  proprietary  GUI  (Graphic  User  Interface) HyperSecureLink through the Internet, from all over the world. The LS-30 is not only a security system but also an automation controller that allows you to set as many as 15 programmable switches to execute daily commands throughout a whole week. With optional environmental sensors and auto-control switches, the LS-30  also operates as an environmental  monitor/control center to record  all the environmental data and save your energy consumption automatically. Although the LS-30 is a very powerful device, thanks to the interactive HMI (Human Machine Interface) programming technology, its operation is simple. Just follow the instructions shown on the LCD display by answering the questions with YES/NO buttons or pressing the correct keys, and the settings are done. You  can  also  set  up  the  system  on  your  laptop  or  PC  using  the  optional  USB/RS-232  adapter  and HyperSecureLink software.   The  set  up  is  simple,  switch  on  back  up  battery,  connect  the  Base  Unit  to  power,  enroll  sensors  and accessories, connect the telephone line, set the telephone numbers and record the voice messages, and then the LS-30 is at your service.   As your security requirements grow and you become more familiar with the system, you can expand and accessorize the LS-30 to meet your specific needs. Simply call your local dealer; trained professionals can answer any questions you have regarding additional accessories. Main Features:    Smart Home System with Security, Environment monitoring/ control and energy saving.  Computer and Internet interface to set, download and upload system parameters and events.  Interactive programming with 16 x 2 LCD display.  Detailed 512-event log with time tag.  288 sensors/ zones can be accommodated with15 programmable switches.  Receiving RF signal strength indication and jamming detection.  Robust multi-million RF coding and special transmission timing design, avoiding interferences.  Responds to panic, burglary, fire, medical alarm and environmental hazards.  Burglar zones with supervised sensors, door and window open/ close detection.  Special Monitoring mode to record all the activities in the protected area without triggering the alarm.  9 independent partial arm zones, one LS-30 can operate as 10 independent burglar alarm systems.  Automatic operation and switch control by schedule and scene settings. (Only can be set by computer.)  Built-in voice dialer stores up to 10 phone numbers, 1 pager and 2 CMS data links.  Hands-free speakerphone, two-way voice communication.  Dial-in control of listen-in, 2-way communication, arm, disarm, event report and switch control.  Latchkey function to inform parents when kids leave or return home.  AC power loss and restore will inform the user by voice.  Inactivity monitoring to take care of the elderly or physically challenged at home.  Remote access through Internet by Ethernet Adaptor or through PSTN by Data Communication Module.  Alarm report through Internet with fast response and saving communication charges.         (Ethernet Adaptor & Data Communication Module are optional devices.) 2
  BASE UNIT  Front Panel                                                                                                                      Side Panel       Rear Panel         1. ALARM OUT SELECTOR: Set the Alarm Relay Output terminals as DC output or dry contacts when the relay activates. 2. Terminal Board (Refer to the APPENDIX A-5): One pair of Alarm Relay output, +12VDC (12~15V   /300mA max.) output and ground terminal, three wire sensor inputs, two Aux. outputs. 3. COM1 (Refer to the APPENDIX A-2, A-3): Communication port for USB/RS-232 Adaptor, Ethernet Adaptor and Data Communication Module. 4. COM2 (Refer to the APPENDIX A-4, A-6): Communication port for Relay Module (XRM-01)/X-10 Power Line Interface Controller.  Key Board & Status Display                                                                                                                                                             Emergency Buttons  Speaker LCD Display Key Board LED status Microphone To trigger the Emergency help, press both buttons simultaneously. Speaker Volume Control Power adaptor I/P 2. Terminal Board   Telephone Line I/P Phone Set Connector Wire Duct 1.ALARM OUT SELECTOR 3.COM1 4.COM2 5.AUX. Audio  3 Key A & AWAY ARM Key B & HOME ARM Key C, STATUS CLEAR & PAUSE Key D, DISARM & ENTER Key 1 & Hands-free Telephone Key 2 & Switch Control Key 3 & Alarm Relay Control Key 4 & Door Open (Reserved) YES NO FUNC / ESC  Key 5 & message in reading (Refer to A-1)
  STATUS INDICATORS  There are three LED indicators in green, yellow and red colors on the front panel. They represent the system operation mode and alarm/ warning status as listed in the following table.           Note: If there is any pending alarm message in the event log memory, the ALARM indicator (red LED) will be lighted and a warning “Dong” sound will be issued in every 5 minutes to alert the user when  the  system  is  in Disarm Mode  (Refer to  (4-3)  Set  Sound-Alarm Warning).  The indicator (red  LED) and  the  warning  sound  will be  turned  off  after the  user  runs the  Event  Check  function (Refer to (2) System Check-Event Check) or press (Hotkey)              to  clear  the  status  indicator in Disarm Mode.            Sensors & Zones        (All sensors are divided into five main categories) 1. 32 Controller /Panic Devices (C): Remote Controller, Keypad, Card Reader. 2. 128 Burglary Sensors/Sirens (B): Door Magnet, PIR (Passive Infrared), Glass Break Detector, Vibration Sensor, Pressure Change Detector, Wireless Siren. 3. 64 Fire Sensors (F): Smoke/Heat/Flame Detector, CO Detector, Gas Detector, Fire Call Point. 4. 32 Medical Help Transmitters (M): Medical Button, Inactivity Detector. 5. 32 Special Sensors (S): Temperature/Humidity Sensor, Flood,/Light Detector, Analog/Power Meter.    All the sensors are  numbered with two  double-digit zone  numbers from (01-01) to  (99-99), the first two-digit number is the Group number and the second two-digit number is the Unit number, set by the Installer in the initial installation. Ex.1, C 01-02: Controller number 01-02 (Group number 01, Unit number 02). Ex.2, B 02-04: Burglar Sensor number 02-04 (Group number 02, Unit number 04).  Group  number:  The  user  can  group  several  sensors  by  using  the  same  Group  Number.  For example, the sensors in the first floor can be assigned as group number “01” and the sensors in the second floor can be assigned as group number “02”.   Note: Special group numbers ”00” for Base Unit (Z), “80” to “89” for Xkeypad (C) , “90” for status indicator (Special Sensor). “91” to “99” for the Partial Arm Zones (Z) (Please refer to APPENDIX A-8). State                              LED  Red  Yellow Green DISARM  OFF  OFF  Flash HOME  OFF  Flash  OFF AWAY  Flash  OFF  OFF DISARM with Warning Message  OFF  ON  Flash DISARM with Alarm Message      ON      OFF  Flash DISARM with Warning & Alarm Message     ON      ON  Flash HOME with Warning Message      OFF  ON      OFF HOME with Alarm Message      ON  Flash      OFF HOME or AWAY with Warning   & Alarm Message     ON  ON      OFF AWAY with Warning Message  Flash  ON      OFF AWAY with Alarm Message  ON      OFF      OFF 4 ALARM  WARM AWAY  HOME  DISARM
   ELECTRICAL INSTALLATION  1. Switch on the internal rechargeable battery.          The LS-30 Base Unit can accommodate 2 rechargeable battery packs. Battery pack 1 is 9.6V/800mA(built-in) and Battery pack 2 (optional) is 9.6V/600mA, providing 15-26 hours back up time. 2. Plug in the power adaptor. 3. Key in the Installer password. (The default Installer password is “1234”.)       (Refer to the Passwords Block in page 8.) 4. Enter the Installer Mode. (Refer to (4) Installer Mode). 5. Program the basic settings a) Telephone numbers (Refer to (4-2) Set Telephone – (4-2-1) Set Telephone Number)   b) Record voice message (Refer to (4-3) Set Sound-Record Voice) c) Enroll all the wireless devices by registering their ID codes in the Base Unit.                   (Refer to (4-4) Set Device-Enroll Device) 6. Set other functions if necessary. 7. Connect the telephone line  APPENDIX A-6), Data Communication Module or Ethernet adaptor (if remote access is needed, refer to the APPENDIX A-3).  Note: For Data Communication Module and Ethernet adaptor, please refer to their user guides. 8. Install the Wireless Siren and register the Base Unit’s ID code into the Wireless Siren.*   * This is only needed for the system equipped with optional Wireless Siren.     (Refer to (4-5) Set Siren-Siren/Relay Test and the instructions of the Wireless Siren) 9. Enter into Master Mode and adjust the clock. (Refer to (3) Master Mode – Set Clock) 10. Test other functions, if any have been set. For details, please read the description on the following pages carefully.  All the above settings also can be done through the proprietary GUI program “HyperSecureLink”. Please refer to the “HyperSecureLink” User Guide.    Turn over the Base Unit, open the battery compartment   and push the battery switch to the ON (UP) position. Note: If external power fails, the internal backup batteries can supply operational power to the Base Unit for 15 to 26 hours, depending on the battery type in the Base Unit. Battery Switch Battery 1 Battery 2 (optional) 5
  MECHANICAL INSTALLATION Placement of the Base Unit It is important for the Base Unit to have a good reception quality for the RF signals transmitted from all the sensors and controllers.  Place the Base Unit around the central area at your home or business if possible.  Keep the Base Unit away from large appliances and other metal objects.  Locate the Base Unit near a power outlet and a telephone socket (if telephone line is needed.).  Install the Door Sensors, PIR and all the other sensors according to your site planning. Check the radio signal quality from the RSSI (Receiving Signal Strength Indication) reading on the LCD by pressing the test button on the sensors. Relocate the sensors/Base Unit to get the best reading (dB number) if necessary. If the dB number is less than 40dB (Standard Version) then you should adjust the location of the sensors/Base Unit or add a RF Repeater to the system to extend the RF operation range. (Do not attach the transmitter on a metal surface; this will shrink the RF signal transmission range.) Plug in the AC adaptor and telephone line.     Attach the Base Unit to the wall using the Mounting Bracket                     1. Attach the Mounting Bracket on the wall. 3. Attach the Base Unit to the Mounting Bracket and push up.   4.Tighten the screws Mounting Bracket  Tamper Switch Cam 2. Insert the screw for the keyhole 6
                   USER OPERATION                     7
   The HMI  (Human  Machine  Interface)  of the  LS-30 adopts the interactive programming technique,  so that  all  settings  and  operations  can  be  done  very  easily  just  by  answering  YES  or  NO  and following the instructions on the display to enter figures.                                   Using the HMI  If the LCD shows a question mark (?), just answer by pressing the YES  or NO  button.             Ex: The LCD shows Master Mode? , Press the YES  button to enter into Master Mode.      If the LCD shows the word Enter then key in proper figures followed by the Enter (D) key.                   Ex: The LCD shows      Seconds(0-255)                                                           Enter: The system asks the user to enter the figures between 0 and 255 and then press the Enter (D) key. (If the user keys in 6 , 4, D, it means the timer is set at 64 seconds).  For all the Check functions, use the  ↑  and  ↓  keys to scroll up and down the screen.                                                                                   Reading the programming flow chart           State A          State A-1                                                                   Down arrow                                                                                                              Select the next state   State Loop A      State A-2        Sub-state of State A-2                                                                                                                      Right arrow                               State A-3                                                                 Enter into the sub-state    Note: Pressing    FUNC/ESC  at any time will let you leave the current state loop.             Password As many as 14 passwords can be set in the system, each with a max. of 8 digits.    Master Password (User1, default”0000”): The user with this password is authorized to manage the other user passwords and user settings. 7 General User Passwords (User 2- 8): Open to 7 general users; with any of these passwords a user can change operation modes, and check all the system status. 2 Latchkey User  Passwords  (User  9-10):  User 9 and User 10 are  also called Latchkey Users. The  LS-30  will  dial  the  Latchkey  Number  (Refer  to  (4-2-1)  Set  Telephone  Number- Latchkey Number) when these users arm or disarm the system. *Duress  Code (User 11,default “8862”): Using this code to operate the system,  the  LS-30 will   send a duress signal to the CMS. Installer Password (default”1234”): The user with this password is authorized to enter into the Installer Mode. 2 CMS Passwords (CMS1 default “1111”, CMS2 default “2222”): Open to 2 CMS stations for CMS parameter setting and system check.     8
  START OPERATION       When you apply the power to the LS-30 for the first time, the LCD display shows “System Reset”   & time information. This informs the user about the time of system power on. User can key in “0000DC” to clear the display and entering the Initial State.   After entering the password, the user can select System Check function, Hot Key Control function or enter Master, Installer and CMS modes.                                                                                             Initial State                               Master or User Password          Installer or CMS Password                                                                       (*Only valid in Disarm Mode)                   Hot Key Process                  System Check? Or Press Hot Key            System Check?                                   Hot Key Enter        Yes                No                                Yes    No              System Check           Master Mode        Installer Mode        CMS Mode                    (2)                  (3)              (4)               (5)  Hot Key: By pressing the keys below, you can enter into the specific operation mode directly.                                                 For AWAY, HOME & DISARM Modes - refer to the OPERATION MODES OF LS-30.   The ARM Mode in this manual means AWAY or HOME Mode. 9 Enter AWAY Mode. (Quick Away: Press the key for 2 seconds to enter AWAY Mode from “Disarm”.                                                           Ignore the password request.) Enter HOME Mode. (Quick Home: Press the key for 2 seconds to enter Home Mode from “Disarm”.                                                           Ignore the password request.) Clear LED/LCD alarm/warning status, reset siren and stop dialing immediately. Enter DISARM Mode & reset siren. Enter  hands-free  Telephone  Mode.  The  Base  Unit  can  be  used  as  a  hands-free telephone for 10 minutes when you enter this mode.   Press ESC  to disconnect and return to normal operation. Switch control (XRM-01 Relay Module and X-10 switch control module are optional.) Close or open the alarm relay terminals on the rear panel. Open Door (reserved).  Reading Come-In-Message (Refer to Appendix A-1)
   (2) System Check               Event Check                    Check By Sequence                                                                                            Check By Date                                            Telephone Number Check            (2-1)                                                  Voice Check          (2-2)                                                Device Check           (2-3)   Event Check: The Base Unit can store 512 event records in its memory. These events can be checked by time sequence or by entering the date information. Use the  ↑  and  ↓  keys to scroll up and down the events. .                                                 Reading Event Log from the LCD Display  Ex.1: LCD shows            C02-03    Disarm 04/26 22:08    01 The Controller (C) numbered 02-03 set the system in Disarm state at 04/26 22:08;   this is the latest event (Event # 01).  Ex.2: LCD shows              B01-02    Burglar 01/13 19:32    253 The Burglar sensor (B) numbered 01-02 issued a burglar alarm at 01/13 19:32,   this event is numbered as 253.  Ex.3: LCD shows              Z00-11    Disarm 12/22 08:00    03 The Master (user number 1) enters the Base Unit (Z) into Disarm state at 12/22 08:00 from Keyboard, this event is numbered as 03.     Note: All the events generated by the Base Unit are marked with Zgg-uu. gg = 00 (Event of Base Unit itself),    gg = 91-99 (Event of partial zones.) uu = 0x (Event of Base Unit itself),       x=0 (Base Unit), x=1 (Aux1 I/P), x=2 (AUX2 I/P), x=3 (Sensor In),     x=5 (Emergency Button), x=6 (Inactivity) uu = 1y (Command from keyboard, y = User number.) uu = 2y (Command from Remote, like Dial-in control, USB/RS-232 or Internet.) y=1 (master), y=2-8 (user 2-8), y=9,0 (latchkey users), y=b (Duress), y=c (Installer), y=d (CMS1), y=e (CMS2), y=f (User can’t be specified)   10
  (2-1) Telephone Number Check                Common 1 Number  Common 2 Number  Common 3 Number  Common 4 Number  Panic Number  Burglar Number  Fire Number  Medical Number  Special Number  Latchkey Number    Pager Number  Pager Data   Show the telephone numbers stored in the memory and their answering types. (refer to (4-2-1) Set Telephone Number to check the usage of different telephone numbers).                                            Reading the Telephone Number Display If the telephone number is over 16 digits, it will be divided into two parts to be shown on the   screen, use the  ↓  key to check the lower part of the number.           Common1                                        Common1                                        Common2         123456789012345-      Press  ↓    -6789V                      Press  ↓        2222222222T     The above example shows that the Common 1 number is: 1234567890123456789, and     Answering is set by Voice.     The V or T following the last digit of the telephone number indicates whether the answering   status is Voice or Tone. (refer to (4-2-1) Set Telephone Number.)            11
  (2-2)    Voice Check               All Voice        Common Segment        Panic Segment        Burglar Segment        Fire Segment        Medical Segment        Special Segment    Latchkey Disarm Segment  Latchkey Away Segment  Playback the pre-recorded voice messages. (refer to (4-3) Set Sound to check the usage of different segments of the voice messages).   (2-3) Device Check            Controller                Burglar Sensor                        Fire Sensor                    Check By Sequence              Medical Button              Check By Zone Number    Special Sensor  Check the current status of all the devices, using the  ↑  and  ↓  keys to scroll up and down the number.  Reading the Device Status Display  Ex.1          Remote Ctl.    02      The number 2 Controller is a Remote Controller, Zone number is     C01-02  Normal      01-02, and status is normal. Ex.2                                            The number 7 Burglar sensor is a Magnetic sensor, Zone number is   10-12,      10-12, with some kind of trouble. (go to (2) System Check-Event Check to check what kind of trouble happened to this sensor.)   Mag.Sensor    07 B10-12  Trouble 12
  (3)        Master Mode                          Set Bell                  Door Bell On                                                                Device Test              Door Bell Off                               Set Monitor Mode      Monitor Mode (Only can be entered in Disarm Mode)  Set Partial ARM          Disarm Mode  COM1 Control        COM1 On/Off      Need Password?  Set Entry Delay      (Refer to (4-1) Set Timer- Set Entry Delay.)        Set Exit Delay        (Refer to (4-1) Set Timer- Set Exit Delay.)  Set Clock                  Time          Date            Day  Set Switch          X-10                    Set House Code                                                                                    Type2-Type5        Set Switch Auto Control                                                                                     (Reserved)                              *Deny Arm if not Ready  Set Password                          Master                                                          User 2 ~ User 8  User 9, 10 (Latchkey User)  User 11(Duress Code)  Bell ON/OFF (default= ON): Enable/Disable the doorbell chime. Bell ON: In Disarm Mode, the Base Unit will issue a doorbell sound (Ding! Dong!) when receiving a     triggering signal from a Burglar sensor with its Bell ON/OFF status set in the ON state. Bell OFF: No doorbell chime will sound. Note: The Bell function only works for the Burglar Sensor if its Bell ON/OFF status is set in the ON state. (refer to (4-4-1) Change Device Setting-Burglar Sensor-Enable State-Bell ON/OFF.)  Device Test: The system opens a 5-minute test window for the user to test the operation of all the sensors (not including the Remote Controller and Keypad). In this period, when the Base Unit receives any signal from the sensors, it will only sound beeps and not trigger any alarm. When the 5 minutes are over, the system returns to its original operation mode automatically. The system will escape from the test mode immediately when it receives an Arm/Disarm signal. 13
   Monitor Mode: In this mode all the trigger signals from the Burglar Sensors (not including the sensors assigned in Group number 91-99 Partial Arm Zones) will be recorded in the Event Log as trigger signals only; no alarm will be issued. The purpose of this mode is for the recording of all activities in the protected area while in Disarm Mode. The system will return to Disarm Mode only by changing state in this setting or from COM1 port command. Set Partial ARM:           Groups 91 to 99 are nine independent protected zones and these zones can be Armed /Disarmed individually. (Please refer to APPENDIX A-8) Set COM1 Control: (default Enable, No Need Password) Control Enable: The COM1 interface is open for the user to access the system.           Need Password: Password (Only Master and CMS passwords can access the LS-30.) must be attached to the control commands from the COM1 port.                 (If “Need Password” is set on the Base Unit then the password must be set when running the HyperSecureLink software also. Refer to “HyperSecureLink” User Guide.)           No Need Password: No password needed for the control commands from the COM1 port. Control Disable: The COM1 port interface is closed. Note: If this setting is disabled. The Base Unit can’t communicate with the RS-232/USB Adaptor, Data Communication Module and Ethernet Adaptor. Set Switch (Default X-10 type): X-10 Type: House Code <A-P>: (default <A>) This code should be the same as the House Code set on the X-10 switches, user can select from A to P.       Set Switch Auto Control: Set the switch working schedule for automation control applications.             (please refer to the X-10 device operation instruction.)        Entry Delay: Refer to Installer Mode (4-1) Entry Delay. Exit Delay: Refer to Installer Mode (4-1) Exit Delay. * Deny Arm if not Ready (Default =No): System will not enter into “Away” or “Home” mode if not all the door or window magnets are closed.             (This function only valid for the control command from Remote Controller, Keypad, Key board on the panel and rear panel control input. Arming control from COM1 command, phone dial-in and scheduled Auto Operation will not affected by this setting.) Set Password: Latchkey User: User 9 and User 10 are also called Latchkey Users. The LS-30 will dial the Latchkey Number (Refer to (4-2-1) Set Telephone Number- Latchkey Number) when these users arm or disarm the system. *Duress Code (Default 8862): This code is used to notify the CMS (Central Monitoring Station) that an emergency event has occurred that requires immediate assistance. When using this code to set the operation mode, the system will send a duress event to the CMS immediately.     14
  OPERATION MODES OF LS-30  The  LS-30  can  be  set  into  three  operation  modes  to  fulfill  your  requirements  in  different  times  and situations. AWAY Mode: When you leave your home or business, set the system into Away Mode.      (Hot Key) Enter into AWAY Mode                                                      Away Mode Arming Sequence                                              Disarm                            Exit Delay                      AWAY mode active  → System status:                                      ↑        (0-255 seconds)   Set AWAY mode                   Note:  When  you  place  the  LS-30 in  AWAY  Mode, the Base Unit will clear any previous alarm and warning status on the LCD & LED and check the state of the Door Magnet sensors. If any of the sensors is still open (for example, you forgot to close the back door before you leave), the Base Unit will issue a warning message (insert 20 seconds Exit Delay automatically if no Exit Delay  has been set) and show the  zone number of the  sensor on the LCD display for you to check.  HOME Mode: In this operation mode, those burglar sensors with their Enable State - Home Mode = Active will still be on alert  and offer  the protection  you need  while at home. (Refer to (4 4-1) Installer Mode - Set Device - Change Device Setting - Burglar Sensor - Enable State - Home Mode = Active.) (Hot Key)      Enter HOME Mode  Note:  When  you  place  the  LS-30  in  Home  Mode,  the  Base  Unit  will  check  the  status  of  the  Door Magnet  sensors.  If  any  of  the  sensors  is  still  open  (for  example,  you  forgot  to  close  the  back door), the Base Unit will issue a warning message and show the zone number of the sensor on the LCD display for you to check.             The  Base  Unit  will  clear any  previous  alarm  and warning  status  on  the  LCD  &LED  when  the Home Mode is entered from the Disarm Mode. DISARM/ MONITOR Mode: The LS-30 will not issue any alarm for Burglar sensors, but 24-Hour Zone sensors (refer to (4-4-1) Change Device Setting - Burglar Sensor - 24-Hour Zone), Fire sensors, Panic, Medical Buttons and Special sensors still work all the time. (Hot Key)        Enter DISARM MODE             Note: About Monitor Mode Please refer to (3) Master Mode- Monitor Mode. 15
  REACTION OF LS-30 TO DIFFERENT ALARMS  The response of the LS-30 to various alarms and abnormalities is shown below. Burglar alarms can only be issued when the system is in AWAY or HOME mode, while Fire, Panic, Medical and Special alarms can be triggered anytime, regardless of the system operation mode. When any of these alarms occur, the LS-30 will dial the correct phone numbers to call for help.                                  Burglar Alarm Response                                  AWAY Mode                  Entry Delay                        Burglar Alarm  →     System status:                                ↑      (0-255 seconds)          ↑     Burglar sensor triggered              Siren goes off, dialing---  If  necessary,  you  can  interrupt  dialing  and  stop  the  siren  by  disarming  the  system,  and  clear  the  alarm LED/LCD by pressing (Hot Key)    Press (Hot Key)      : stop siren, stop dialing, clear LED/LCD status.                                            Sources  &  Responses Alarm Trigger Sources  Dialing Tel. Numbers Besides CMS Voice message on telephone Voice on   Base Unit Siren Status  Burglar  PIR  Door Magnet  Glass Break Detector  Vibration Sensor Pager+ Burglar+ Common 1-4+   Burglar+ Common  Silent  Programmable, Fire   Smoke Detector  Gas Detector  CO Detector Pager+ Fire+ Common 1-4+   Fire+ Common Fire Message Programmable  Programmable, Panic   Panic button of   Remote Controller  Wireless Keypad  Emergency buttons on  Base Unit   Pager+ Panic+ Common 1-4+   Panic+ Common  Silent  Programmable,   * Siren off Medical   Wireless Medical Button  Inactivity Pager+ Medical+Common 1-4+   Medical+ Common  Medical Message Programmable   Programmable,  Special     Temperature Sensor  Humidity Sensor  Flood Detector  Light Detector  Analog Sensor  Power Meter Pager+ Special+ Common 1-4+   Special+ Common  Special Message Programmable  Programmable (Disarm State) None                None                 Silent  Programmable Sensor Tampered   All sensors (Arm State) Same As Burglar Alarm Sensor Trouble or Low Battery All sensors  None  None  Silent  OFF 16
   ANSWERING CALLS FROM THE LS-30  When you receive a call from the LS-30, you can follow the procedures below to communicate with the system.   When you pick up the phone, your voice on the line will trigger the appropriate message from the LS-30 (For the telephone number assigned as voice acknowledgement).  You will hear the prerecorded message twice, telling you what event happened to the system.  After the announcement, the LS-30 enters into monitoring and 2-way communication mode for 60 seconds. You can hear any sound picked up by the microphone on the Base Unit or talk to the people inside the house. During these 60 seconds, you can also control your LS-30 through the telephone keypad.  If you don’t press any key during this period, the first 30 seconds will be listen-only and then -after two beeps- the system will enter into 2-way hands-free speaker phone automatically. Ten (10) seconds before the termination of the telephone connection, one beep will be delivered to remind the user. Press    0    : LS-30 disconnects immediately; stop any further dialing; stop siren.   Press    1    : LS-30 disconnects immediately and dials the next number, stop siren.   Press    3    : Enter into speak-only mode. (The microphone on the LS-30 is disabled.) Press    5    : Enter into 2-way hands-free speaker phone. Press    8    : Enter into listen-only monitoring.   Press any other key: LS-30 will extend the connection for another 60 seconds.  The sound of the siren or noise from the environment may interrupt the decoding of the input key tone, so keep pressing the key until the command becomes effective.   If this telephone number needs a DTMF tone acknowledgment, remember to press a key (any key) on the telephone keypad in the answering process to prevent LS-30 from redialing this number later.                                                        Answering Sequence      LS-30                              Voice                                 Dialing                      Announcement                      60 sec. Monitoring &                                       Twice                            2-way Communication   Ring!---Ring!                                                                  0 : LS-30 disconnects, stops further dialing & stops the siren. 1 : LS-30 disconnects and dial next number. 3 : Enter into speak-only mode. 5 : Enter into 2-way hands free speaker phone. 8 : Enter into listen-only monitoring.  : If any other DTMF key is pressed, the connection is extended for another 60 seconds. 17 Answered by voice (“hello”) or by pressing a DTMF key Only accept Commands   5 and 8
  DIAL-IN CONTROL User  can  control  and  check  with  your  LS-30  from  a  phone  anywhere  in  the  world  by  enabling  the auto-answer function (refer to (4-2) Set Telephone – Set Auto Answer) and set the ring count number.  Notes: 1. If you connect a fax machine or auto-answering machine on the same telephone line, you might need to refer to their manuals and Appendix A-7 to avoid any disoperation. 2. The ring count number is only effective for the dial-in from PSTN (land line) and it should be over three rings; otherwise, the noise on the phone line may trigger the dial-in control process. 3. The pulse-dialing phone set can’t dial in to control the system. The operation of dial-in control is as follows:   1. Dial the telephone number to which LS-30 is connected. 2. After the preset ring count number (for land line), you will hear beeps. 3.    Key in the user password (preceded by * and followed by # ) from the telephone keypad within 30 seconds. If the system recognizes the password you will hear beeps, otherwise you should enter again. 4. After the password has been recognized, the LS-30 will enter into monitoring mode for 30 seconds and then -after two beeps- the system will enter into 2-way hands-free speaker phone automatically. Ten (10) seconds before the termination of the telephone connection, one beep will be delivered to remind the user. 5. During the 60 seconds, you can also enter commands from the telephone keypad to control the LS-30. *    0 : Disarm the LS-30 after you exit Dial-in Control (echoed by voice). *    1 : Arm the LS-30 in Home Mode after you exit Dial-in Control (echoed by voice). *    2 : Arm the LS-30 in Away Mode after you exit Dial-in Control (echoed by voice). *    3 : Enter into speak-only mode (echoed by “OK”). *    4 : Check alarm event and operation mode (echoed by voice). *    5 : Enter 2-way hands-free speaker phone (echoed by “OK”). *    6    x    x    1 : Turn on the switch number x    x (xx = 01-15) (echoed by “OK”). *    6    x    x    0 : Turn off the switch number x    x (xx = 01-15) (echoed by “OK”). *    7    1 : Turn on the Relay (echoed by “OK”). *    7    0 : Turn off the Relay (echoed by “OK”). *    8 : Enter into listen-only monitoring (echoed by “OK”). *    9 : Disconnect the line immediately. Any other keys will extend the monitoring period for another 60 seconds (echoed by beeps).        The Process of Dial-in Control          Dial Phone Number                    Enter Password                  60 sec. Monitoring &                             Ring count as preset      within 30 seconds              2-way Communication                                         -----------                          *xx--xx#              Ready for key tone command      18 Ring  Ring
                                                         INSTALLER & CMS SETTINGS                      19
   The Installer Mode is for the installer to set up the system.    Enter Installer Password   (4) Installer Mode               Set Timer                    (4-1)        Set Telephone                  (4-2)        Set Sound                      (4-3)        Set Device                      (4-4)        Set Siren                        (4-5)        Set Misc.                        (4-6)                                                                  (4-1)    Set Timer                      Set Entry Delay                        Set Exit Delay                                Set Inner Siren Time                                                  Set Relay Action Time                                                   Set Sensor Supervise Time                  Unit In Second  Set Remote Siren Time                    Unit In Minute                                  20
  Entry Delay for Burglar Sensors: (0-255 seconds, default=0 sec.)         This setting is the time between any burglar sensor triggers and the alarm reaction procedure starts. When  you  return  home  and  open  the  door,  the  Base  Unit  will  issue  warning  beeps  (if  the  Entry Delay Beep = On) to remind you that the system is still in the Arm state and you should disarm the system within this time. (Refer to the (4-3) Set Sound - Entry Delay Beep.)                                                  AWAY Mode                  Entry Delay                        Burglar Alarm  → System status:                                      ↑      (0-255 seconds)          ↑     Burglar sensor triggered              Siren goes off, dialing--- This Delay only works on the Burglar Sensor with its Delay ON/OFF setting in ON state.   (Refer to (4-4-1) Change Device Setting - Burglar Sensor - Enable State - Delay ON/OFF.)             For the system controlled by Wireless Keypad, this timer should be set more than 20 seconds. Exit Delay for Controllers: (0-255 seconds, default=0 sec.) This  setting  is  the  time  between  selecting  the  AWAY  mode  and  when  the  AWAY  arm becomes  effective. During this  time,  the  Base  Unit  will  issue  warning  beeps to  remind  the people still in the house to leave as soon as possible. Since the Door Open signal may last for 10 seconds, so add 10 seconds to the time you need to leave the house as the Exit Delay. (Ex. you need 20 seconds to leave the house, set Exit Delay=30s)                                              Disarm                            Exit Delay                    AWAY ARM effective  → System status:                                      ↑      (0-255 seconds)   Set AWAY mode                 This Delay only works on the Controller with its Delay ON/OFF setting in ON state.   (Refer to (4-4-1) Change Device Setting-Controller-Enable State-Delay ON/OFF)                 For the system controlled by Wireless Keypad, this timer should be set more than 20 seconds. Inner Siren Time: 0-255 seconds (default, 60 sec.)   The time of the Inner Siren sounds when an alarm trips and Inner Siren is enabled. (Refer to (4-5) Set Siren-Set Inner Siren.) Relay Action Time: 0 second to 120 minutes (default, 60 sec.)   The activation time of the Alarm Relay output (on the rear panel) when the alarm trips. Sensor Supervise Time: 0-24 Hours (default, 12 Hours) The LS-30 is a supervised RF wireless system, meaning supervised sensors send “heartbeat” RF signals to the Base Unit at a certain time interval. If the Base Unit does not receive the RF check signal  from  a  supervised  sensor  within  the  Sensor  Supervise  Time,  the  LS-30  considers  this sensor to be missing and issues a warning message. This time can be set from 0 to 24 hours (0 hour means that the system will not check the “heartbeat” signal. Please note, the time shorter than 4 hours would increase sensor “RF Loss” possibility. Remote Siren Time: 0 seconds to 30 minutes (default, 60 sec.)   The  time  of  the  wireless Remote  Siren  sounds  when  the alarm trips.  (The  Remote  Siren is  an Option.) 21
  (4-2) Set Telephone        Set Telephone Number                        (4-2-1)  Set Dial Mode                      Tone                              Pulse 33/66                              Pulse 40/60    Set Auto Answer        Auto Answer On          Set Ring Count                          Auto Answer Off  Set Telephone Line Cut Detection                Permanent Off                               Away Mode On                               Permanent On  Set Cease Dialing Mode              30 Minutes Due                                                                          CMS Report OK  Set Tel. Ringer                        Tel. Ringer On/ Off                                          Set Dial Tone Check            Dial Tone Check Enable/ Disable                   Dial Mode: Tone /Pulse 33/66 /Pulse 40/60 (default, Tone)   Check your telephone system and select the proper Tone or Pulse mode for the auto-dialer. Auto Answer Ring Count: Auto Answer ON with Ring Count 1-30 /Auto Answer OFF   (default, Auto Answer OFF)   Auto-Answer  ON:  The  Base  Unit  will  answer  the  incoming  call  automatically  after  the  ring  count number set in this command has been reached. (You have to switch on this function, if you want to  use  dial-in  control.  Three  or  more  ring  counts  are  recommended  to  avoid  triggering  by noise.) Auto Answer OFF: The Base Unit will not answer the incoming call.        22
  Telephone Line Cut Detection: Permanent OFF /Away Mode ON /Permanent ON   (default, Permanent OFF) The LS-30 checks the telephone line voltage and if the line voltage is abnormal, the siren will go off (the Inner Siren should be switched on) to alert the user. (refer to (4-5) Set Siren - Inner Siren.) Permanent OFF: Never check the telephone line state. Away Mode ON: Check the telephone line state only in AWAY mode. Permanent ON: Always check the telephone line state. Note: To implement this function the telephone line must not connect any auto answering devices like FAX machine or TAM (Telephone Answer Machine). Cease Dialing Mode: 30 Minutes /CMS Report OK (default, 30 Minutes) 30  Minutes:  The  auto-dialer  stops  dialing  after  30  minutes  or  after  all  the  telephone  numbers have been dialed 5 times without a successful connection. CMS Report OK: The auto-dialer stops dialing after the report to CMS is successful.        The Latchkey number still will be dialed when the Latchkey Controller Arms/Disarms the system or the detection of Power Loss/Restore event, even this status is set as “CMS Report OK”.  Tel. Ring: ON/OFF (default, OFF) Tel. Ring ON: Sound the ringer for incoming calls. Tel. Ring OFF: Ringer deactivated for incoming calls.   Dial Tone Check: Enable/Disable (default, Enable) Dial Tone Check Enable: The auto-dialer checks for a dial tone before dialing. Dial Tone Check Disable: The auto-dialer will not check for a dial tone and dials immediately.                     23
  (4-2-1) Set Telephone Number            Common 1 Number    Common 2 Number        Common 3 Number                Common 4 Number  Panic Number                              Answer By Voice  Burglar Number                              Answer By Tone  Fire Number  Medical Number  Special Number  Latchkey/(power) Number    Pager Number  Pager Data  As many as 10 telephone numbers and one pager number can be set in the auto-dialer, each up to 23 digits. 4 common numbers and pager number: These will be dialed in all types of alarm. They can be the numbers of your office, friends, neighbors or family members. 5 specific numbers each for different alarms: These will be dialed only when the LS-30 is triggered by the specified alarm. For example, the fire number will be dialed only in a fire alarm.   Latchkey number /Power status report number: This number will be dialed, disregard the Cease Dialing Mode Setting (refer to (4-2) Set Telephone- Set Cease Dialing Mode), if following things happen: 1). When  a  Latchkey Remote  Controller  (Refer  to  (4-4-1)  Change  Device  Setting-  Enable  State- Latchkey)  or  a  user  with  the  Latchkey  password  (User  9  or  User  10  password) leave  the  house (change  from  Disarm/  Home  Mode  to  Away  Mode)  or  enter  into  the  house  (change  from  Away Mode to Disarm/ Home Mode). This function is useful to parents who want to make sure their children have returned home safely. Usually, the Latchkey number will be the parents’ mobile phone number.    24  Note: This function is not applicable for Partial Zone 91-99.
      2). When the Base Unit detects AC power break or restore, this number will be dialed after a random   delay of 60-120 seconds, The pre-recorded messages (power loss/power restore) will be played when the call is successfully connected.  Pause Insertion             Note: Use the Pause key    to insert pauses between telephone number digits for dialing   to/from a PABX extension number. Each pause is equivalent to a 3-second break.   Answering status: Voice /Tone (default, Voice).   After  dialing,  the  LS-30  needs  an  acknowledgement  from  the  called  party,  either  by  voice like  “Hello”  or  by  a  DTMF  key  tone  to  ensure the  call  is  connected  successfully.  With  no acknowledgement, the call will be deemed to be failed and will be redialed in the next loop.  Dialing Sequence for Alarm Report  CMS1  Number →→→→CMS2  Number →→→→Pager →→→→Specific  alarm  number →→→→1st  to  4th Common numbers If there is any number that cannot be connected successfully, the auto-dialer will skip to the next one and try again in the next loop until all the numbers have been tried 5 times or the cease dialing condition has been reached. (refer to (4-2) Set Telephone - Set Cease Dialing Mode.)  Note: 1, CMS1 and CMS2 are Central Monitoring Station numbers (refer to the (5) CMS Mode). 2,  If  Ethernet  Report  has  been  set  (refer  to  (5)  CMS  Mode-Set  CMS1-Ethernet Report)  the  alarm  report  will  be  sent  to  Internet  CMS  Server  first  before  any  alarm report through PSTN.                25
   (4-3) Set Sound          Record Voice          Common Segment 13 Second Record                                          Panic Segment 4 Second Record                                          Burglar Segment 4 Second Record  Fire Segment 4 Second Record  Medical Segment 4 Second Record  Special Segment 4 Second Record              Latchkey Disarm 4 Second Record              Latchkey Away 4 Second Record  Voice Check                                                  (Same as 2-2)                                          Set Entry Delay Sound        Beep      Away Mode      Off                                                                                              Alarm Warning          Alarm Warning On/ Off  Record Voice: After an alarm call connects successfully, the LS-30 will play the prerecorded voice message that corresponds to the alarm type. The messages should be recorded in their specified segments. Common Segment (13 seconds): The voice to be played during all alarm types. This segment should contain your name, address and telephone number. Ex: “This is ---, I live at---, phone number is---.” Panic Segment (4 seconds): The voice to be played during a Panic alarm. Ex: “Break-in! Break-in! Calling for emergency help.”   Burglar Segment (4 seconds): The voice to be played during a Burglar alarm. Ex: “Burglar! Burglar! Calling for emergency help.”   Fire Segment (4 seconds): The voice to be played during a Fire alarm. Ex: “Fire! Fire! Calling for emergency help.”   Medical Segment (4 seconds): The voice to be played during a Medical alarm. Ex: “Heart patient! Calling for emergency help.”   Special Segment (4 seconds): The voice to be played during a Special alarm. Ex: “High temperature in the building! Calling for an alert.”       Latchkey Disarm (4 seconds): The voice to be played when a latchkey user disarms the system.                         Ex: “I’m home.”   Latchkey Away (4 seconds): The voice to be played when a latchkey user sets the system in AWAY mode.                         Ex: “I’m out.” 26
   Entry Delay Sound: Beep/ Away Mode /OFF (default, OFF )        Beep : The Base Unit will generate beeps during the Entry Delay interval and the beeping speed will get faster until the end of the delay time. (Refer to (4-1) Set Timer-Entry Delay) Away Mode Voice : The Base Unit will generate the voice of “Away Mode” during the Entry Delay interval until the end of the delay time. (Refer to (4-1) Set Timer-Entry Delay)        OFF: No beeps during the Entry Delay interval.     *Alarm Warning: ON/OFF (default, OFF)        Alarm Warning ON: The Base Unit generates “Dong” sound in every 5 minutes if there is any pending alarm status (RED LED constantly on) on the panel.        Alarm Warning OFF: No “Dong” sound even with pending alarm in Disarm Mode.                                27
  (4-4) Set Device                Enroll Device                  Controller Enroll                                                                  Burglar Sensor Enroll                                                                        Fire Sensor Enroll                      Zone Number                                                                  Medical Button Enroll                                                                Special Sensor Enroll  Change Device Setting            (4-4-1)  Delete Device            Controller Delete                                                                  Burglar Sensor Delete                                                            Fire Sensor Delete                      Zone Number                                                      Medical Button Delete                                                              Special Sensor Delete                                       Special Sensor Limit Set              Enter Zone Number        High/Low Limit                                                                                                                                                                                  Wire Sensor Assignment        Select Input      Select Type      (4-4-1) Enable State   Enroll Device: The LS-30 uses smart code technology. The Base Unit identifies its sensors by their unique IDs, so the Base Unit has to learn all the sensors’ ID code in the initial system setup. (Each sensor has a unique ID that is preset at the factory.)                                                                 60 seconds for Device Enroll After initiating the Enroll Device procedure, there is a 60-second time window for the device to transmit a RF signal to complete the code learning.  Delete Device: Remove the device from the system. Special Sensor Limit Set: Set High/Low trigger limits for Special sensors like temperature sensor and   humidity sensor. Please refer to the special sensor’s user guide. Wire Sensor Assignment: Set the parameters for the wire sensor inputs from the rear panel.   Up to three wire sensors can be assigned.               (The wire sensor input can be selected as a close or open trigger. The Zone numbers of the wire sensors are fixed to “00-01=Aux1”, “00-02=Aux2”,   “00-03=Sensor In”.)  28
  (4-4-1) Change Device Setting                  Controller Change                                                                                Burglar Sensor Change                  Enter Zone Number  Fire Sensor Change                    Enable State    Medical Button Change                Zone Number  Special Sensor Change              Switch Control Enable state of devices: Device On Duty/Bypass (default, On Duty): (For all devices) Device On Duty: This sensor is working in the system currently. Device Bypass: Bypass this sensor; the system will ignore the alarm signal received from this sensor.   Delay ON/OFF (default, Delay=OFF): (For Controller & Burglar sensor) Delay ON: (Refer to (4-1) Set Timer - Exit Delay/Entry Delay.) For the Remote Controller, the Exit Delay time will be imposed on the Away command from this controller. For the Burglar sensor, the Entry Delay time will be imposed on the Burglar alarm signal from this sensor. Delay  OFF:  The  trigger  signal  or  command  from  this  sensor  or  controller  will  be  processed immediately, regardless of the Exit/Entry Delay setting in (4-1). 24-Hour Zone YES/NO (default, 24-Hour Zone= NO): (For Burglar sensor) 24-Hour Zone/YES: This Burglar sensor’s trigger signal will be processed all the time regardless of the system’s operation mode, either in Arm or Disarm. 24-Hour Zone/NO: This sensor’s trigger signal will only be processed in Arm Mode.   Home Mode Active/Inactive (PIR default= Inactive, Magnet default= Active): (For Burglar sensor) Home Mode Active: This Burglar sensor will trigger an alarm in Home Mode operation. Home Mode Inactive: This Burglar sensor will not trigger an alarm in Home Mode operation, it will only trigger an alarm in Away Mode operation. Pre-warning ON/OFF (default, Pre-warning OFF): (For Burglar Sensor)    Pre-warning ON: When this device is triggered in Arm condition, it only turns on the corresponding switches those set by this device for 30 seconds to warn the person who approaching the protected area. (If 24-Hour Zone set, the switches will turn on anytime when this device is triggered.). It won’t trigger burglar alarm. Voice Warn ON/OFF (default, Voice Warn ON): (For Fire, Medical and Special alarm sensors) Voice Warn ON: If this sensor triggers an alarm, there will be a 30-second voice warning from the Base Unit before the alarm reaction procedure starts. Voice Warn OFF: There is no voice warning. The Base Unit responds immediately when there is an alarm triggered by this device.   Siren/Relay ON/OFF (default, Siren/Relay ON, only OFF for Controller): (For all devices) Siren/Relay  ON:  The  Relay  will  act  and  sirens  (both  Inner  Siren  and  Remote  Siren)  will  go  off when there is an alarm triggered by this sensor after the Delay time or Voice Warning passes.             Siren/Relay OFF: The Relay will not act and sirens will keep silent when there is an alarm triggered 29
  by this device. Bell ON/OFF (default, Bell OFF): (For Burglar sensor) Bell  ON:  In  Disarm  Mode,  the  Base  Unit  will  issue  a  doorbell  chime  when  receiving  a  trigger     signal  from  this  sensor  if  the  Bell  status  is  set  to  ON  in  Master  Mode  (refer  to  (3)  Master Mode - Bell Check - Door Bell.) Bell OFF: Doorbell chime will not sound when receiving a trigger signal from this sensor. Suggestion: This state should be switched on for the Door Magnet sensors on the front and back doors.   Latchkey ON/OFF (default, Latchkey= OFF): (For Remote Controller, Not for the Controllers assigned in Group number 91-99 Partial Arm Zones) Latchkey ON: This Remote Controller is assigned as a Latchkey Remote Controller. (refer to (4-2-1) Set Telephone Number - Latchkey Number.) Latchkey OFF: No latchkey number will be dialed for this controller.   Inactivity ON/OFF (default, Inactivity=OFF): (For Burglar Sensor)       Inactivity ON: This Burglar Sensor is assigned as an Inactivity Sensor (no longer be a Burglar Sensor or Pre-warning Sensor) to monitor the activity of an elderly or physically challenged person in the protected area. If no activity has been detected during the preset Inactivity Time (refer to (4-6) Set Misc.-Set Inactivity) an Inactivity Alarm (medical) will be issued.             Inactivity OFF: This is a normal Burglar Sensor. Supervision ON/OFF: (Automatically set by the sensor itself) (Refer to (4-1) Set Timer - Sensor Supervise Time.)      Supervision ON: System will check the “heartbeat” signal from this sensor.    Supervision OFF: System will not check the “heartbeat” signal from this sensor. Type Alarm/Control (default, Type=Alarm): (For Special Sensors)         To assign the Special Sensor as an Alarm Device or a Control Device.  (refer to the manual of the Special Sensor.) Operation Low/High (default, Operation=Low): (For Special Sensor)         To activate the switches or the Relays when the reading reaches the low limit or high limit for the sensor that is set in Control Type. (refer to the manual of the Special Sensor.) Switch control: Select the switches that will be activated when this sensor is triggered.       Note: Switch #16 is not allowed for this purpose as this switch has been assigned as the indicator of the Arm/ Disarm Status. (refer to (4-6) Set Misc.- Set SW # 16.) X-10 Switch As many as 15 switches (switch #16 is for Operation Mode indication, refer to (4.6)) can be controlled by each system. For settings of the X-10 switches, refer to the instructions of the X-10 device manual.   Note: For a Remote Controller, if you press the DISARM button in DISARM Mode, the switches that have been assigned as active switches will be turned ON or OFF alternatively. Entry Delay ON/OFF (default, Entry Delay=OFF): (For Wire Sensor input only)       The Entry Delay time (refer to 4-1) should be imposed on the trigger of this input or not. Trigger Close/Open (default, Trigger=Close): (For Wire Sensor input only)             Alarm will be triggered by close (grounding) or open (>3V) the sensor input contact (or voltage). *Away Close/Open (default, Away=Close): (For Wire Sensor input assigned as a Controller only)             System will enter Away or Disarm Mode by close (grounding) or open (>3V) the sensor input contact (or voltage). 30
  (4-5) Set Siren            Set Inner Siren                        Inner Siren On/OFF          Set Mode Change Chirp            Mode Chirp On/OFF      Set Tamper Siren In Disarm            Siren On/OFF  Siren/Relay Test              Start Test  Inner Siren: ON/OFF (default, ON) Inner Siren On: Enable the Inner Siren. Inner Siren Off: Switch off the Inner Siren. (The Siren keeps silent in alarm and warning states.)                  The conditions for the Inner Siren to go off when alarm trips:     1. The Inner Siren is enabled.     2. The Siren/Relay ON/OFF attribute of the sensor is in the ON state. (refer to (4-4-1) Change Device Setting-Siren/Relay ON/OFF.)     3. The Inner Siren Time has been set. (refer to (4-1) Set Timer-Inner Siren Time)      Mode Change Chirp: ON/OFF (default, OFF) Mode Change Chirp On: The Sirens sound short chirps (Disregard the Inner Siren status) when the operation mode changes by Remote Controller or Wireless Keypad. (Disarm: 1 chirp, Away: 2 chirps, Door Open warning: 5 chirps).       Mode Change Chirp Off: The Sirens will keep silent when the operation mode changes.  Tamper Siren In Disarm: ON/OFF (default, OFF)                                 Tamper Switch There is a Tamper Switch in the Base Unit (please refer to Attach the Base Unit to the wall using the Mounting  Bracket).  This  switch  will  be  closed  by  the  Tamper  Switch  Cam  when  the  Base  Unit  is attached to the Mounting Bracket. If someone detaches the Base Unit from the Mounting Bracket, the Tamper Switch will be triggered.   Also refer to the specific sensors’ descriptions for more about their tamper function. Tamper Siren In Disarm On: The Siren will go off for 10 seconds, (the Inner Siren has been enabled) if someone detaches the Base Unit from the Mounting Bracket or triggers the Tamper Switch (on Base Unit or sensors) in Disarm Mode.        Tamper Siren In Disarm Off: The siren will not go off when receiving the tamper signal from sensors or from the Base Unit in Disarm Mode. Siren/Relay  Test:  This  test  will  activate  the  Inner  Siren,  close  the  Relay  contacts  and  send  an Activate signal to the Remote Siren (if a remote siren is installed) immediately regardless of the Inner Siren state.      31
   (4-6)            Set Misc.                Set RF Jamming Warning          Check ROM Version          Reset To Factory Default              Enter to Reconfirm    Emergency Button Assignment  Set Inactivity                Inactivity ON            Inactivity Time  Set Password                Inactivity OFF  Set Modem      Ring Count= 1~30      Set SW #16          Arm/Disarm =ON   RF Jamming Warning: (default, OFF) Enable or disable the RF jamming warning. Reset To Factory Default: All the settings in the Base Unit will be returned to factory default except recorded voice and telephone numbers. Emergency Button Assignment: Panic /Medical (default, Panic) Select the function of the Emergency Button as a Panic Button or a Medical Button (The zone number of this button is 00-05.). Set Inactivity: ON /OFF (default, OFF) Inactivity On with time (0-72 hours):   1, Treats the Inactivity signal from the Wireless Medical Button as a Medical Alarm.     (The Medical Button will send Inactivity signal if no activity has been detected in 12 hours.) 2, If no activity has been detected during this time from any Inactivity Sensor (Refer to (4-4-1) Change Device Setting-Burglar Sensor-Enable State-Inactivity) the system will issue the Inactivity Medical Alarm (with zone number of 00-06). Inactivity Off: Ignore the Inactivity signal from the Wireless Medical Button and don’t check the Inactivity Timer. Set Password: (default, “1234”) Edit the Installer Password. Set Modem–Ring Count (1-30): (default, Ring Count=3)       This setting is only valid for the system equipped with an optional Data Communication Module. After this ring count number the Module will connect (off hook) to the telephone line automatically.    Note: After this ring count has been set, user should connect the Module to the system then enter Master Mode and press Hotkey “C” (clear status) to pass this parameter to the Module. Set SW #16: (default, ARM ON): Set the #16 switch as an Arm/Disarm status indicator.             Arm On: The #16 switch will be turned on in Away and Home Mode.       Disarm On: The #16 switch will be turned on in Disarm and Monitor Mode.   32
  (5) CMS Mode        Set CMS1                     Set Mode Change Report              Report On/ Off               Set CMS2                                                                     Auto Link Check              Auto Link Check On      Check Interval                                                                    Loopbcak Test                  Auto Link Check Off                                                            Set 2 Way Audio          2 Way Audio ON/OFF                                              Set DTMF Data Time        DTMF Data=50ms /100ms                                        Set Telephone Number          Telephone Number                                                                                    Account Number                                        Set Password                      CMSx Number                                             (CMS1 only)                                         Set CMS Report                Report All/ One                                                              Ethernet Report (CMS1 only)  Mode Change Report: ON /OFF (default=OFF, For PSTN)           Mode Change Report On: The LS-30 will report to the CMS if the operation mode (Away/Home/Disarm) has been changed. Auto Link Check: ON/OFF (default=OFF, For PSTN)   Auto Link Check On: The LS-30 will send a check signal to the CMS periodically.   Loopback Test: (For PSTN) The LS-30 will send a link check signal to the CMS immediately. 2 Way Audio: ON/OFF (default=OFF, For PSTN)   2 Way Audio ON: The Base Unit will enter into 2-way voice communication mode after sending the alarm report to the CMS. (This function only works with a digital receiver using Contact ID and has 2-way voice capability.) DTMF Data Time: 50ms/100ms for PSTN report (default=50ms, For PSTN) Select the DTMF data pulse time as 50ms or 100ms for the Contact ID protocol.   (Please consult with your CMS provider if you want to change this parameter.) Telephone number & account number: *The PSTN (land line) CMS telephone number (16 digits Max.). *The user account (8 digits Max.). The CMS1 account number is also used for IP Alarm Report Password: The CMS password to access the LS-30 Base Unit. CMS Report: (default, Report ALL) Report All: Report to CMS1, CMS2 and Internet service centers.   Report One: Stop further CMS report if any one of the above reports is successful. Ethernet Report: YES/NO (default NO), only for the system equipped with Ethernet/wifi/GPRS Adaptor. Alarm message will be reported to the CMS server through the Internet. 33
   SPECIFICATIONS    Base Unit Input Power: 15VDC/800mA regulated. Standby Current: 50mA. RF : (Follows local regulations, other frequencies as requested) Frequency: 915Mhz receiver, 433Mhz transmitter Data Modulation: OOK. Power: less than 10mW. Range: about 100m to 300m @open field, 25℃  (Depends on sensors). Receiver Type: super heterodyne. RF Security Code: 16,777,216 combinations with check sum for each type of sensors.   More than 4 billion combinations in total. Communication Link: Standard PSTN (land line), Optional Ethernet Telephone Dialing: Pulse/Tone selectable. Preset Telephone Number: 10 phone numbers, one pager, 2 CMS data links   Voice Recording: 120 seconds in total. Emergency announcement in 6 segments, 13 seconds for common segment, 4 seconds each for Panic, Burglar, Fire, Medical, Special and Latchkey/ Power segments. Event Log: max. 512 records. Display: 3 LEDs, 2x16 LCD panel with blue color backlight. Sensor Zones: total 288 zones. (Burglar zones x 128, Fire zones x 64, Controller zones x 32,   Medical zones x 32, Special sensor zones x 32) Memory Back-up Time: Min. 3 months after power break. Battery Back Up Operation Time: about 15-26 hours standby. (depends on back up battery type, only for the operation of the Base Unit) Password: 14 passwords each with max. 8 digits. 3 Wire Sensor Inputs: Each can be assigned as Panic, Burglar, Fire, Medical, Tamper or Controller. Alarm Out: 230V AC /5A rate relay contacts or DC output selectable. Delay Activation Time: 0- 255 seconds programmable.   Digital Interfaces COM1(RJ9): UART (0-5V, 9600/ 8 bits/no parity/1stop bit) For RS-232 Adaptor, USB Adaptor or Ethernet Adaptor..   Digital Interface COM2(RJ45): (for switch control interface) Switch control: Control of 16 units X-10 switches or (XRM-01) Relay Modules. I2C Adaptor (optional) Remote Display Memory: 30 characters/set, total 10 sets. Internal Siren: 110dB at 30cm distance. CMS protocol: Contact ID with                             Clock Accuracy: within 5 seconds daily. Telephone Line Cut Detection Voltage: 20V+/- 4V. (this function may not be used in some countries.) Operation Temp.: -10℃~50℃.   Storage Temp.: -20℃~60℃. Humidity: 10-95%RH. Size: 248x180x52 mm. Weight: about 950 g.  Note: External GSM is an option for European market, LS-30 don’t use wi-fi, only wire Ethernet interface.   (The manufacturer reserves the right to change the specifications without prior notice)  34
  APPENDIX A-1. In-coming Message Display. A user or a CMS can send messages to the LS-30 if the Base Unit has been connected to the Internet through the Ethernet Adaptor (optional) by using the HyperSecureLink program. The LCD  display will  show “Messages Come In” and issue a  warning sound periodically  to remind the  user  if  any  new  message  has  been  received  by  the  LS-30  Base  Unit.  The  user  can  check  the message by pressing (Hot Key) 5 after the password has been entered in Disarm Mode. Up to ten 30-character messages with time tag can be stored in the memory of the Base Unit. Stop the warning sound by pressing (Hot Key) C after entering the password.     (Note: ! and & are not allowed in the message)  A-2. Connection Diagram for USB or RS-232 Computer Interface                                                         COM1 cable                                USB or RS-232 Adaptor            HyperSecureLink Software          (Note: For the USB Adaptor driver, please refer to the USB-3 Installation Guide in the CD ROM.)  A-3. Connection Diagram for the Ethernet Adaptor or the Data Communication Module                                                     COM1 Cable                                         A-4. Connection Diagram for the X-10 Power Line Interface                                                           X-10 Appliance Module              X-10 power Line Interface Controller            X-10 or COM2 Cable         . Internet Or PSTN ToCOM1 Power Line To LS-30 COM2 HyperSecureLink or CMS polling software To PC USB or COM Port To LS-30 COM1 35  Data communication Module connects to Telephone network Ethernet Adaptor connect to Internet Router Ethernet/wifi/GPRS Adaptor or Data Communication Module
  A-5. Terminal Board Connection                            _                               +                                                                            +12V DC: This terminal provides +12V~15V/300mA output for the customers to connect their own devices.                   (Note:  The  output  voltage  depends  on  the  power  adaptor  and  will  be  shut  down  if  the  external power fails.) ALARM OUT: These two terminals are the Alarm Relay Outputs. These two terminals can be selected as dry  contacts  or  9V~15V/GND  output,  depending  on  the  setting  of  the  ALARM  OUT SELECTOR. SENSOR  INPUT:  There  are  three  terminals:  AUX  1  (Wire  Sensor  1),  AUX  2  (Wire  Sensor  2)  and SENSOR IN (Wire Sensor 3), can accept NO/NC type alarm sensor input. Refer to (4-4) Set Device-Wire Sensor Assignment for the settings of these three sensor inputs. AUX OUT 2: This output represents the status of system operation mode. In the ARM mode (AWAY & HOME) this output will  send out +5V voltage (protected  by a  serial  2k  ohms  resistor) to this terminal. The user can connect a LED display for ARM state indication purposes.        A-6. Using the same telephone line to connect the LS-30, Fax machine and Telephone Answering                       Machine (TAM)                                                                                           Telephone Line                                                                           To Phone                                                                      (See Note 2)                              Fax                                    TAM                              Phone set  The LS-30 Base Unit, a Fax Machine and a TAM can be connected to the same telephone line and all these devices will still be able to accept their own dial-in control signal.  1. The auto answering ring counts (Refer to (4-2) Set Telephone-Set Auto Answer for LS-30) should be set as:   LS-30 ring count> Fax ring count >TAM ring count. Wire   Sensor 1 Wire Sensor 2 Arm LED Indicator Wire Sensor 3 Wire Siren 36
     Ex. If the ring count of the LS-30 is 8, the ring count of the Fax should be 6 and ring count of TAM should be 4. 2. Set the operation mode of the Fax machine in TAM mode. (Please refer to the manual of the Fax machine.) 3. When you dial in, the TAM will connect first.  If you want to record a message on the TAM, just do it.    If you want to send a Fax, just press the send button on the Fax machine.  If you want to control the LS-30 system, after the announcement from the TAM is over (or the Fax tone from the Fax machine is over) then key in the password, and the LS-30 will take control of the telephone line.  Note:  1,  The  Line  Cut  Detection  function  should  be  disabled  (Refer  to  (4-2)  Set  Telephone-Set Telephone  Line  Cut  Detection-Permanent Off),  otherwise  the  LS-30  will  trigger  the line cut detection alarm when the TAM or Fax has taken control of the telephone line.       2, If this function can’t work normally, please connect a ground wire from the  GND pin of the  terminal  board  to  the  earth  of  the  power  socket  to  reduce  the  noise  from  the  power system.            A-7. Partial Arm for Group Numbers “91” to “99” The Group Numbers from “91” to “99” are partial arming zones. They can be controlled by a Remote Controller, Wireless Keypad, Panel keyboard or through the HyperSecureLink software individually but   independent of the main groups (Group Number “01”~”89”). The Remote Controller or Wireless Keypad with Group Number ”9x” only controls the corresponding burglar sensors with the same Group Number ” 9x”. For example, Remote Controller with Group Number “ 91” only controls (Away, Home, Disarm) the burglar sensors with the Group Number “91”. When the LS-30 receives an AWAY/HOME/DISARM signal from the Remote Controller of Group Number “9x”, the Base Unit announces the Away/Home/Disarm operation with Group Number, but the LCD and LEDs (Green, Red and Yellow) will only follow the status of the main groups (Group number ” 01”~”89”), unaffected by the status of Group Number “91”~”99”.                                   Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:             37  —Reorient or relocate the receiving antenna.—Increase the separation between the equipment and receiver.—Connect the equipment into an outlet on a circuit different from that to which the receiver isconnected.—Consult the dealer or an experienced radio/TV technician for help.
Manual-BackCover.jpg (2544x3685x16M jpeg)
    Device List Item Device Name Zone No. (xx-xx) Location (User Name) Initial Date of Battery 1         2         3         4         5         6         7         8         9         10         11         12         13         14         15         16         17         18         19         20         21         22         23         24         25         26         27         28         29         30