Siemens SB3 User Manual To The B18d5fd6 58b0 424a A5fd C8fc27ed073f

User Manual: Siemens SB3 to the manual

Open the PDF directly: View PDF PDF.
Page Count: 22

SENTRONSwitchboards
Types SB1, SB2, SB3 and RCIII
instruction
&
installation
GUIDE
SECTION PAGE
1.0 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1.1 Qualified Person . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1.2 Signal Words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1.3 Dangerous Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1.4 Field Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1.5 General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.0 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
3.0 Switchboard Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-5
3.1 Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
3.2 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
3.3 Shipping Damage Claims . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
3.4 Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
3.5 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-5
4.0 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-10
4.1 Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
4.2 Foundation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
4.3 Positioning of Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
4.4 Anchoring, Leveling and Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
4.5 Joining Shipping Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
4.6 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
4.7 Through Bus Splice Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7
4.8 Ground Bus Splice Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
4.9 Grounding and Bonding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
4.10 Busway Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
4.11 Switchboard Busway Flange Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
4.12 Conduit Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
4.13 Cable Pulling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
4.14 Cable Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
4.15 Cable Lashing Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
4.16 Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
5.0 Pre-Energizing, Inspection and Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-12
5.1 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
5.2 Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
5.3 Ground Fault Protection System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-12
6.0 Ground Fault Inspection and Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12-13
6.1 External Ground Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
6.2 Internal Ground Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12-13
7.0 Energizing and Operation, Switchboard Loading and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13-14
7.1 Placing Equipment Into Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
8.0 Switchboard Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
9.0 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14-15
9.1 Inspection and Maintenance Intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
9.2 Recommended Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
9.3 Maintenance Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
9.4 Cleaning Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
10.0 Adverse Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
10.1 Ambient Temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
10.2 Short Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
10.3 Arcing Damage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
10.4 Water Damage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
10.5 Corrosive Atmospheres . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
11.0 Informational Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-19
11.1 Torque Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
11.2 Wire Bending Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
11.3 Strap Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
11.4 Ground Fault Test Record - External . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
11.5 Ground Fault Test Record - Internal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
12.0 Service Bulletins . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT, NOR TO PROVIDE FOR EVERY POSSIBLE
CONTINGENCY TO BE MET IN CONJUNCTION WITH INSTALLATION, OPERATION OR MAINTENANCE. SHOULD FURTHER INFORMATION BE
DESIRED OR SHOULD PARTICULAR PROBLEMS ARISE WHICH ARE NOT COVERED SUFFICIENTLY FOR THE PURCHASER’S PURPOSES, THE MATTER
SHOULD BE REFERRED TO THE LOCAL SIEMENS SALES OFFICE. THE CONTENTS OF THIS INSTRUCTION MANUAL SHALL NOT BECOME PART
OF OR MODIFY ANY PRIOR OR EXISTING AGREEMENT, COMMITMENT OR RELATIONSHIP. THE SALES CONTRACT CONTAINS THE ENTIRE
OBLIGATION OF SIEMENS. THE WARRANTY CONTAINED IN THE CONTRACT BETWEEN THE PARTIES IS THE SOLE WARRANTY OF SIEMENS.
ANY STATEMENTS CONTINUED HEREIN DO NOT CREATE NEW WARRANTIES OR MODIFY THE EXISTING WARRANTY.
Contents
SECTION 1.0 - INTRODUCTION
The purpose of this manual is to assist the user in developing
safe and efficient procedures for the installation, maintenance
and operation of the equipment. For additional information,
refer to NEMA Standards Publication PB2.1 “General Instructions
for Proper Handling, Installation, Operation, and Maintenance
of Deadfront Distribution Switchboards rated 600 volts or less”
which is available from the NEMA web site (www.nema.org).
Contact the nearest Siemens representative if any additional
information is required.
Siemens warrants that on the date of shipment all goods
manufactured by Siemens are free of non-conformities in
workmanship and materials. If within one year from date
of initial operation, but not more than eighteen months from
date of shipment by Siemens, of any item of the goods, pur-
chaser discovers that such item was not as warranted above,
and promptly notifies company in writing thereof, company
shall remedy such defect by, at company’s option, adjustment,
repair or replacement of the item and any affected part of the
goods. Refer to “Standard Terms and Conditions of Sale” for
complete warranty terms.
1.1 Qualified Person
For the purpose of this manual a Qualified Person is one who
is familiar with the installation, construction or operation of the
equipment and the hazards involved. In addition, this person
has the following qualifications:
1.1.1. Training and authorization to energize, de-energize, clear,
ground and tag circuits and equipment in accordance with
established safety practices.
1.1.2. Training in the proper care and use of protective equip-
ment such as rubber gloves, hard hat, safety glasses,
face shields, flash clothing, etc., in accordance with
established safety procedures.
1.1.3. Training in rendering first aid.
1.1.4. Knowledgeable of NEC requirements and other
applicable codes, laws and standards
1.2 Signal Words
The signal words “Danger,” “Warning” and “Caution”
used in this manual indicate the degree of hazard that may
be encountered by the user. These words are defined as:
1.2.1. Danger - Indicates an imminently hazardous situation
which, if not avoided, will result in death or serious injury.
1.2.2.
Warning - Indicates a potentially hazardous situation which,
if not avoided, could result in death or serious injury.
1.2.3.
Caution - Indicates a potentially hazardous situation which,
if not avoided may result in minor or moderate injury.
1.3 Dangerous Procedures
In addition to other procedures described in this manual as dan-
gerous, user personnel must adhere to the following warnings:
1.3.1. Danger! High Voltage. Qualified personnel only. Lock
off all power to this equipment before working inside.
Always work on de-energized equipment. Always
de-energize equipment before performing any tests,
maintenance or repair.
1.3.2. Warning! Always perform maintenance on the inter-
rupting device after the closing mechanism(s) are
discharged.
1.3.3. Caution! Always let an interlock device or safety mech-
anism perform its function without forcing or defeating
the device.
1.3.4. Caution! Hydrocarbon spray propellants and hydro-
carbon compounds will cause degradation of certain
plastics. Contact your local Siemens representative
before using these products to clean or lubricate
components during installation or maintenance.
1.4 Field Service
“Siemens Industrial Services” can provide the following support
services for switchboards. Call 1-800-241-4453 to obtain addi-
tional information and schedule an appointment.
• Start-up Commissioning
• Component and System Testing
• Maintenance (Scheduled and Preventative)
• Repair and Refurbishing
• On Site Operational Training
1.5 General Description
Siemens switchboards are designed and manufactured to
perform efficiently under normal operating conditions. The
instructions included in this manual are provided to aid in
obtaining long and economical service from your switchboards.
For proper operation and maintenance, this information should
be distributed to the owner’s operators and engineers.
These instructions cover the standard construction details
of Siemens’ switchboards including auxiliary equipment and
necessary accessories. Any special equipment furnished in
accordance with purchase order requirements are covered
by supplementary instruction books.
The switchboards described in this manual are the dead-
front type as defined in NFPA70 (NEC), UL891 and NEMA
PB2. All parts, conductors, and insulation materials are
designed and constructed to suit the voltage class of
the equipment and are enclosed within grounded metal
enclosures.
The equipment furnished has been designed to operate in a
system having the circuit capacity specified by the purchaser.
If, for any reason, the equipment is later used in a different
system, or if the short-circuit capacity of the system is
increased, the momentary rating of the switchboards, the
interrupting capacity of the protective devices and the bus
capacity must be checked. Should the service be changed,
the equipment must be checked to assure that the short
circuit capacity, amperage and voltage class of the equip-
ment meets or exceeds the requirement of the new system.
Switchboards are free-standing units rated 6000 amperes or
less at 600 volts AC or less. A typical switchboard will contain
the service entrance section with main devices and distribution
sections with branch devices. The sections contain disconnect
devices, protective devices, auxiliary equipment, and any current
Introduction
2
transformers for metering, control, or ground fault protection.
Devices are applied in a broad range of sizes and mounting
arrangements. Outdoor switchboards consist of indoor equip-
ment enclosed in a weatherproof housing and a door over the
inner front panels.
Section 2.0 - SAFETY PRECAUTIONS
2.1. Only qualified persons familiar with the construction and
operation of switchboards should perform work described
in this set of instructions. Such work should be performed
only after reading this complete set of instructions.
2.2. Follow safety related work practices, as described in NFPA
70E, part II, at all times.
2.3. Hazardous voltages in electrical equipment can cause
severe personal injury or death. Energizing a switchboard
for the first time after initial installation or maintenance is
potentially dangerous. Inspection and maintenance should
be performed on switchboards and equipment to which
power has been cut off, disconnected, and electrically iso-
lated so that no accidental contact can be made with
energized parts.
2.4. Some types of electrical equipment will cause harmonics
in the electrical system which may result in overheating.
Consider this condition when determining switchboard
loading, as possible de-rating of equipment may be
necessary.
Section 3.0 - SWITCHBOARD PREPARATION
3.1 Receiving
Prior to shipment, each switchboard is inspected to ensure
structural and electrical construction is in compliance with
applicable specifications, codes, and standards. Depending
on the size and number of sections, the switchboard is
divided into shipping sections of one or more vertical sec-
tions and placed onto wooden skids. Each shipping section
is packaged, securely blocked and braced for shipment.
Whatever method of shipment, every precaution is taken
to minimize the possibility of damage and to ensure its safe
arrival. Relatively delicate instruments or devices may be included
and the assembly must be handled carefully when unloading.
When the equipment arrives at the destination, the packing
list or marking tag(s) should be checked against the equip-
ment actually received to make sure the shipment is correct
and complete. Claims for shortages or incorrect material must
be made in writing within 30 days after receipt of the shipment
and failure to give such a notice constitutes unqualified accept-
ance and a waiver of all such claims.
On shipments with more than one shipping group, marking tags
are attached to each crate or package for identification. In lieu of
the marking tags, the rating label on each section contains the
section marking. Refer to the general arrangement drawing for
the location of each unit within the group lineup.
3.2 Inspection
Inspect the equipment as soon as possible after receiving for
any damage that may have occurred in transit. Carefully remove
packing to inspect for any possible damage. Retain the packing
material for equipment storage or return shipment if neces-
sary. The switchboard should remain in an upright position
and secured to the shipping skid to prevent distortion of the
bottom frame when moving or handling.
3.3 Shipping Damage Claims
All claims for lost or damaged goods in transit are to be handled
by purchaser directly with the carrier. Notification to carrier within
the 15 day limit on concealed damage is essential if loss resulting
from unsettled claims is to be eliminated or minimized.
3.3.1. When shipment arrives, note whether equipment
is properly protected from the elements. Note trailer
number on which the equipment arrived. Note block-
ing of equipment. During unloading make sure count
agrees with delivery receipt.
3.3.2. Make immediate inspection upon arrival for visible
damage. This should be done prior to unloading when
possible. When total inspection cannot be made on
vehicles prior to unloading, close inspection during
unloading must be maintained and visible damage
noted. Take pictures if possible.
3.3.3. Any visible damage must be noted on the delivery
receipt and acknowledged with the driver’s signature.
The damage should be detailed as much as possible.
It is essential that a notation “Possible internal damage,
subject to inspection” be included on delivery receipt.
3.3.4. If driver will not sign the delivery receipt with damage
noted, the shipment should not be signed for by the
consignee or his agent.
3.3.5. Notify the Siemens Sales Office immediately of any
damage.
3.3.6. Arrange for a carrier inspection of damage immediately.
IMPORTANT: Do not remove equipment from the place
it was set when unloading. Be sure this location is properly
protected to ensure further damage will not occur. Equip-
ment must be inspected by carrier prior to handling after
receipt. This eliminates loss due to claims by carrier that
equipment was damaged or further damaged on site
after unloading.
3.3.7. Be sure equipment is properly protected from any further
damage by covering it properly after unloading. Equip-
ment should be stored in a clean dry place having a
uniform temperature to prevent condensation and
protected from further damage.
Safety Precautions and Switchboard Preparation
3
DANGER
Hazardous voltage.
Will cause death or serious
injury.
Keep out.
Qualified personnel only.
Disconnect and lock off all power
before working on this equipment.
3.3.8. If practical, make further inspection for possible concealed
damage while carrier inspector is on site. If inspection for
concealed damage is not practical at the time the carrier
is present, it must be done within 15 days of receipt of
equipment. If concealed damage is found, the carrier must
again be notified and inspection made prior to making any
corrective action to repair. Also notify Siemens Sales Office
immediately.
3.3.9. Obtain the original of the carrier inspection report and
forward it along with a copy of the noted delivery receipt
to the Siemens Sales Office. Approval must be obtained
by Siemens from the carrier before any repair work can
be performed. Before approval can be obtained, the docu-
ments requested must be in Siemens’ hands. The carrier
inspection report and/or driver’s signature on the delivery
receipt does not constitute approval to repair.
3.4 Handling
Each switchboard shipping section has provisions for attaching
lifting equipment. The lift points are designed for use with a
crane of adequate height and capacity. To estimate the maxi-
mum required crane capacity, multiply the number of sections
to be lifted by 2,000 pounds.
NOTE: 2,000 LBS IS AN AVERAGE WEIGHT. SOME SECTIONS
MAY HAVE A WEIGHT OF GREATER THAN 2,000 LBS. PLEASE
CALL THE SIEMENS SALES OFFICE TO VERIFY SECTION
WEIGHTS.
Switchboard sections may be moved by crane with lift cables
attached to the lifting bars on the top of the switchboard. If
crane facilities are unavailable, or if tight spaces prevent use
of a crane, rollers under the skids may be used.
Recommended lifting is by means of four cables connected
to an overhead crane or by fork lift.
3.4.1 Lifting By Means Of An Overhead Crane
Single Section Lifting The cables are connected to the lifting
brackets, mounted at the top front and top rear mounting loca-
tions (See Fig. #1A). A crane with sufficient height should be
used so the load angle (from horizontal) on the lifting cables
will be a minimum of 45 degrees, when viewed from side of
section. The lifting cables must have spreaders from side to
side to prevent twisting the lifting brackets.
Figure 1A
3.4.2 Multi-Section Lifting The method of lifting a multi-
section unit is similar to lifting single section. The cables need
to be connected to all lifting brackets. The lifting cables must
have correct spreader from side to side (See Fig #1B). A crane
with sufficient height and lift is required.
Figure 1B
3.4.3 Lifting By Means Of A Forklift
Forklift trucks should be used with care as improper lift points
could cause damage to equipment. Balance the load carefully
and use safety straps when handling with a forklift. Jacks may
be used to lift switchboard sections which are properly supported
by sturdy timbers. To prevent distortion of the enclosures, rollers
and cribbing of equal height must be used in sufficient number
to evenly distribute the load.
Figure 2 shows a method of using a forklift on an indoor
switchboard.
Figure 2
For alternate handling means, please refer to the NEMA
Standards Publication PB 2.1.
3.5. Storage
3.5.1 Indoor Switchboards
When switchboard is not to be installed immediately, it should
be unpacked, inspected and stored in a clean dry location having
adequate air circulation and uniform temperature to prevent
condensation. If switchboard is to be stored for any length of
time prior to installation, restore the packing for protection. If
the packing material is removed, cover the switchboard to
protect from dust, debris, and moisture.
Indoor switchboards are neither weatherproof nor drip-proof.
Therefore, it should be stored indoors. If it is to be kept either
outdoors or in a humid, unheated area, provide an adequate
covering to protect against weather and dirt, and place a heat
Switchboard Preparation
Minimum
Front View Side View
4
source of approximately 250 watts output within each vertical
section to prevent condensation. Space heaters are not standard
equipment on indoor switchboards. Remove any loose packaging
or flammable materials inside the switchboard before energizing
the heat source. Lubricate any moving parts such as hinges,
shutters, etc., if storage is for an extensive period of time.
3.5.2 Storage – Outdoor Switchboards
It is important that outdoor switchboards are stored exactly
as described for indoor switchboards. When it is necessary to
store outdoor switchboards in an area exposed to the weather
or under humid conditions, they should be kept clean and dry
as described above. Energize the self-contained space heaters
(if provided) and make certain that louvers and vents are
uncovered to allow air to circulate and cover shipping splits
to protect from the elements. Refer to wiring diagram drawing
for space heater circuit connections. Lubricate hinges, shutters,
and other moving parts.
Section 4.0 - INSTALLATION
The proper switchboard installation method depends on whether
the units are shipped as one complete group (maximum of 84.0”)
or in two or more shipping sections.The general arrangement
drawing supplied by the factory will indicate the shipping groups
and their respective location within the lineup. Units must be
assembled in accordance with the general arrangement drawing.
4.1. Location
Find the designated area on the building plan where the switch-
board will be installed. If this area is not specified, the location
chosen for installation should provide working clearances com-
plying with article 110.26 of the National Electrical Code (NEC).
Front accessible switchboards require that field connections
including mains, branches, ground, and neutral are accessible
and maintainable from the front. Equipment drawings identify
switchboards that require rear access.
4.2. Foundation Requirements
Extreme care should be taken in layout of foundation or floor.
Refer to general arrangement drawing for exact location of
anchor bolts, area for conduits, other limitations, and instruc-
tions. Foundations must be sufficiently strong to support
the weight of the equipment. Conduit couplings should be
stubbed flush with or below the finished floor level. (Refer to
NEC 408.10) After the equipment has been lowered to the
foundation and set in place, conduit extension sleeves may
be screwed into couplings.
Floors and sills must have a smooth level surface and be in the
same plane. The surface of the foundation must not protrude
above the grouted sills or bed plates at any point. Grouted sills
or bed plates must be set true and level and be in an aligned
position in the same plane to each other over the entire length.
Outdoor equipment is usually installed on a concrete pad with
a level and smooth surface. Outdoor equipment which has been
assembled on formed base plates must be supported at each
section. Adjacent units at each shipping split must be supported
on a single support, and this must be taken into consideration
when the foundation is designed and constructed.
4.3. Positioning of Sections
Positioning and connection of the switchboard sections at the
installation site is done in the following manner.
4.3.1. Space to the front and rear should be sufficient for
opening of doors, insertion and withdrawal of removable
breakers, inspection, and maintenance. Service entrance
equipment should be located as close as possible to
the incoming service of the building.
4.3.2. Clean the mounting surface to remove all dirt and debris.
Start with the left end shipping group and continue in
sequence. Maneuver the section into the desired posi-
tion using procedures described under “Handling.” Use
care in locating sections over conduit areas and beware
of any conduits which stub-up above floor level as these
may block sliding the section in either direction.
4.3.3. Prepare for the connections across shipping splits before
the equipment is moved into final position. Bus supports
and bus joints should be removed using side, rear and
front access options as required. Note the mounting
position and orientation and save hardware for use in
reinstallation.
4.3.4. Remove the shipping skid and stand the section in an
upright position. Remove all packing material and the
bottom floor plate if one is installed in the section. To
protect the bottom channel, any sliding force must be
carefully applied across the bottom 4 inches (100mm)
of the side to fully distribute the sliding force.
4.3.5. All shipping sections must be leveled and aligned to
each other in order to maintain proper alignment of the
horizontal main through bus and splice bus connections.
Bolt all section frames together and connect all through
bus and ground bus at shipping breaks using the splice
plate bus and hardware supplied. Tighten bolted connec-
tions in accordance with torque specifications indicated
on the instruction label supplied.
4.4. Anchoring, Leveling and Assembly
Indoor switchboard shipping groups are held in alignment by
bolts holding the vertical sections to each other. The entire
shipping group is to be anchored and leveled as a single
element without loosening any hardware until entire shipping
group is leveled and anchored. Supporting surfaces for the
switchboard at each anchoring bolt location must be level
and in the same plane. There must not be any projection above
this plane within the area covered by the switchboard cubicles.
Figure 3
Installation
5
Typical bolt-down hole provisions for cubical bottom, each section.
If the floor or ground sill channels do not meet this require-
ment, it may be necessary to shim in the following manner.
All anchor bolt locations in each cubicle must freely rest in firm
contact with the mounting support surfaces. There must not be
any projection or obstruction in other areas which may distort
the cubicle. Do not force cubicle in firm contact by drawing down
anchoring bolts as such drastic means will distort cubicles. Add 4”
(100mm) square shims adjacent to anchor bolts until firm con-
tact is achieved. Check each anchor bolt location (See Figure 3
and 4).
4.4.1. If side mounted lifting bars are supplied on shipping
sections, it is necessary to remove the lifting bars. If
top mounted lifting brackets are supplied on shipping
sections, removal is optional.
4.4.2. Tighten anchor bolts or weld to sills.
4.4.3. If line-up consists of multiple groups, move the next
group into position, with the rear of units in line and
tight against the adjacent group. Do not bolt groups
together at this time. Check that the cubicles are in
firm contact with the foundation at each corner and
anchor point and that bolt holes are in alignment.
Add square shims as necessary. Tighten the anchor
bolts. Now bolt groups together as described in
”Joining Shipping Sections.”
4.4.4. Repeat Step 3 above until all shipping groups have
been installed securely and in the correct order per
the front elevation drawing supplied from the factory.
Note: For seismic installation, refer to installation instructions
furnished with the equipment.
Figure 4
4.5. Joining Shipping Sections
The front panels and, if possible, the back plates should be
removed so that adjacent shipping section frames can be
bolted firmly together. Place 5/16-16 x 1.00 inch steel bolts
through the holes in each front and rear corner post as
shown in Figure 5. Torque the bolts to 12 ft lbs.
Figure 5
4.6. Electrical Connections
Electrical connections within switchboards are made using
either bus bar or cable. Bus bar is furnished for connections
between the main bus, circuit breakers fusible devices and
pads for cable terminations.
Switchboards are designed to fully comply with standard
electrical clearances. However, since cable and bus con-
nections are being made in the field, care must be taken
to ensure that all minimum clearances are maintained for
electrical connections.
4.7. Through Bus Splice Connections
When a switchboard group is split for shipping purposes, the
cross bus and ground bus connections must be made when
installing the equipment. To make these bolted connections,
refer to Figures 6 through 12 and these instructions:
4.7.1. Access to the main bus from the cable termination area
is achieved by removing the main bus compartment bar-
rier which separates the main bus from the cable area.
For some arrangements, it may be necessary to remove
items between the main bus barriers and the rear of the
unit in order to gain full access. After completion of the
bus assembly and installation, these items should be
reassembled in reverse sequence.
Between live parts 0-125V 126-250V 251-600V
of opposite polarity
Through Air 1/2” 3/4” 1”
Over Surface 3/4” 1 1/4” 2”
Between live parts 0-125V 126-250V 251-600V
and grounded metal
Through Air 1/2” 1/2” 1”
Over Surface 1/2” 1/2” 1”
6
Installation
Standard Indoor NEMA 1
West Coast Standard Outdoor NEMA 3R
East Coast Standard Outdoor NEMA 3R
Front
Front
Front
4.7.2. All surfaces must be free of dust, dirt or other foreign
material. Do not use any abrasive cleaner on plated con-
tact surfaces. Cleaning is normally not necessary and
should not be done unless parts are badly tarnished. If
cleaning is necessary, use a mild cleaner and thoroughly
remove all residue. Keep cleaning agent off insulation.
4.7.3. Before assembling any bus bar joint, check that the
bar is inserted through bus supports (when required).
Observe the relationship of the bus bar and maintain
this relationship when connecting bus bars. Spacers
may be required in some bus joint connections.
4.7.4. Assemble all joints with the parts dry. Do not use
grease or “no-oxide” product.
4.7.5. Use the hardware provided with the Splice Plate Kit.
Using smaller or different grade hardware may result
in over-heating of the connection.
4.7.6. Single Bolt Connections: Insert the bolt through the
hole on the tie plate and the through bus. Next, place
the large diameter Belleville washer on the 1/2-13 bolt.
Hand tighten the nut and then torque to 50 ft. lbs.
Duplicate for each set.
4.7.7. Four Bolt Connections: Position the (4) ³⁄₈ ,-16 carriage
bolts in the slotted holes in the splice plate and the
through bus. Hand tighten the ³⁄₈ ,-16 belleville washer
nut and then torque to 20 ft lbs. Duplicate for each set.
Older switchboards used Grade 2 hardware. See Hardware Grade Determination
Detail for determining which type of bolt is installed in the gear. Also, refer to the
torque table provided with the gear.
Figure 6 (Typical Bolt Alignment for Tie Plates)
Figure 7 (Splice Plate – Single Hole)
Figure 8 (Straight Tie Plate – Single Hole)
Figure 9 (Angle Tie Plate – Single Hole)
Figure 10 (Straight Tie Plate - Four Hole to Single Hole)
MAX.
HARDWARE GRADE TORQUE
³⁄₈ -16 5 20 FT/LBS
¹⁄² -13 5 50 FT/LBS
¹⁄² -13 2 22FT/LBS
SPLICE PLATES
THRU BUS
WHEN MORE THAN ONE SPLICE PLATE
IS PROVIDED PER PHASE INSTALL ON
EACH SIDE OF THE THRU BUS.
11-A-1021-01 REV. 2
7
Installation
Carriage
Bolt
Belleville
Washer
Nut
Belleville
Washer
Nut
Carriage
Bolt
Hardware Grade Determinations
Grade 2 Grade 5
Figure 11 (Offset Tie Plate – Four Hole to Single Hole)
Figure 12 (Straight Tie Plate - RCIII Only)
4.8 Ground Bus Splice Connections
Remove ground bus splice plate and rotate the bar into place.
Align and secure the ground bus splice connection between
shipping sections. Refer to Figure 13 for connection. Torque
connections to 6 ft lbs.
NOTE: Proper installation is essential for safe and proper
operation of ground fault protection system (when provided).
Figure 13
4.9. Grounding and Bonding
4.9.1 For grounded systems used as service equipment or as
a main switchboard on a separately derived system,
follow the steps below:
4.9.1.1. Run a grounding electrode conductor from the
grounding electrode at the installation site to the
switchboard grounding electrode conductor ter-
minal. Select the proper material and size the
grounding conductor to comply with sections
250.62, 250.66, and 250.166 of the National
Electric Code (NEC). Install the grounding electrode
conductor as specified in section 250.64(B) of the
National Electric Code (NEC). No ground conduc-
tors are allowed on load side of neutral disconnect
link or ground fault sensor.
4.9.1.2. If required, the main bonding jumper between the
neutral bus and the ground bus will be installed at
the factory. Ensure that the bonding jumper is in
place and properly labeled.
4.9.1.3.It is important that none of the grounding conduc-
tors are connected to load side of any neutral
disconnecting link or any sensor used for ground
fault protection.
4.9.1.4. When the system is a dual fed (double ended) and
has ground fault protection, refer to switchboard
front elevation drawing for proper grounding and
handling.
4.9.2. For ungrounded systems used as service equipment,
or as main switchboard on a separately derived system,
follow the steps below:
4.9.2.1.Run a grounding electrode as described in part
4.9.1.1. above.
4.9.3. If the system is grounded at any point ahead of the
switchboard, the grounded conductor must be run from
that point and connected to the ground bus as described
in paragraph 250.24(B) of the National Electric Code
(NEC). This conductor is required even if the switchboard
supplies only phase to phase loads.
4.9.4. For a switchboard not used as service equipment or as
a main switchboard on a separately derived system:
4.9.4.1.Use equipment grounding conductors sized
according to Table 250.122 of the National
Electric Code to ground the switchboard
frame and ground bus to the service ground,
or by bonding to the raceway enclosing the
main supply conductors in accordance with
sections 250.118 and 250.120 of the National
Electrical Code.
4.10 Busway Connection
Refer to the SENTRON™ Busway Storage, Installation and
Maintenance Instructions Piece No. 31-9918-01 supplied
with the Busway for installation of the busway runs.
4.11 Switchboard Busway Flange Connection
In some cases, the Sentron Busway standard stubs are shipped
to the job site already factory connected to the switchboard.
In applications where the flange stub is not installed from
the factory, refer to the following instructions below:
4.11.1. From inside the switchboards, remove the ³⁄₈ bolts
that fasten the switchboard bus to the busway flanges.
4.11.2. Remove the screws from the switchboard that are
around the opening busway cutout.
4.11.3. Insert the busway flange end into the switchboard bus
connectors in the switchboard and align the holes.
NOTE: Top plate is not designed to support weight of
busway. Busway must be supported by other means.
8
Installation
4.11.4. Insert the ³⁄₈ ” bolts at bus joint and torque to 20 ft lbs.
Tighten bus joint connections, all phases, neutral and
ground bars.
4.11.5. Insert the screws that attached the busway flange to
the switchboard top plate or outer cover.
4.11.6.Verify busway flange phasing with switchboard phasing
(i.e., ABCN, front to rear).
Figure 14
4.12 Conduit Area
All conduits and stubs must be located to avoid cable interference
with structural members and live bus. Deep switchboard frames
may need to have side-to-side frame support removed. Install
conduit properly, with appropriate hubs or sleeves and ring con-
nectors to protect cables and prevent water from entering and
accumulating in the switchboard. Bond all metallic conduit and
stubs to the switchboard with electrical connections sized accord-
ing to 250.122 of the National Electric Code. Before pulling cable,
verify that their size, temperature rating, and conductor insula-
tion comply with the switchboard markings. (Ref NEC 110.14(C)).
NOTES: 1) If bottom plates are furnished, holes for any
conduit entering the bottom of the switchboard must be
made by the customer. After making the holes, reinstall the
bottom plate. 2) Top plate is not designed to support weight
for conduit. Conduit must be supported by other means.
4.13 Cable Pulling
Siemens switchboards are constructed according to NEMA stan-
dards for cable arrangements. It is important that all cables enter
the switchboard in the conduit area shown on the front elevation
drawing and per the instructions shown below:
4.13.1. Use only cable sizes suitable for a proper fit with the
corresponding lugs.
4.13.2. Pull the proper number of line side and load side cables
as per the load served.
4.13.3. Position the cables inside the switchboard so that
they are not subject to physical damage.
4.13.4. Maintain the maximum possible bending radii and proper
clearance to bus bars and grounded parts. If any cables
are lying or bearing on structural members, support them
to relieve this condition or place suitable protective material
at the bearing point to protect the cable insulation.
4.13.5. Where cables enter or leave the switchboard, or pass
through any metal which has magnetic properties, be
certain to run all phase conductors and the neutral
through the same opening. See 300.20 (A) of the
National Electrical Code
4.13.6. Cables entering or exiting the switchboard should be in
the same section in which they are terminated, except
as noted in 408.3 of the National Electrical Code. See
Article 300 of the National Electrical Code for proper
wiring methods.
4.13.7. For Class 2 and Class 3 remote control, signaling and
power-limited circuits separation requirements, see
725.54 of the National Electrical Code.
4.13.8. Conductors of size 1/0 AWG and larger may be run in
parallel. When these conductors are run in parallel they
should be of the same size, length and material to assure
the equal division of current, as required by 310.4 of the
National Electrical Code.
4.14 Cable Termination
4.14.1. Strip a length of insulation from the end of the cable
sufficient to fit into the full length of the lug barrel,
being careful not to nick or ring the strands. Use a
proper insulation stripping tool.
4.14.2. Thoroughly clean aluminum cable contact surfaces
with a wire brush.
4.14.3. Apply an acceptable joint compound to the bare aluminum.
4.14.4. If compression type lugs are furnished on any switch or
circuit breaker, or as the main incoming power lugs, unbolt
and remove them. Insert the cable into the lug barrel and,
using the recommended crimping tool, make the specified
number of crimps. Wipe excess sealant from the connec-
tor and insulation. With the cables connected, remount
the lugs onto the bus bars, switches, or circuit breakers.
Torque the bolts per the chart on page 16.
4.14.5. Set screw type lugs may be furnished as main incoming
lugs and are standard on all devices supplied by Siemens.
Torque values for these lugs are marked on these units.
Torque values for other switchboard lugs are marked on
the switchboard.
4.15 Cable Lashing Requirements
For conductor lashing instructions on switchboards marked
65kA, 100kA or 200kA short circuit current ratings, refer
to the following instructions:
4.15.1. Switchboards with a single fusible main switch rated
4000A or less do not require lashing.
4.15.2. Switchboards with a single main molded case circuit
breaker rated 4000A or less do not require lashing.
When using insulated case SB Circuit Breaker, lashing
is required.
4.15.3. Switchboards with a single main fused circuit breaker
rated 4000A and less do not require lashing.
9
Installation
4.15.4. Switchboards of single section construction with fusible
disconnects, circuit breakers, or fusible circuit breakers do
not require lashing.
For switchboard sections requiring lashing, refer to the instruc-
tions below:
65kA
100kA
200kA
4.16 Control Wiring
Control wiring is carefully installed and checked at the factory.
Inter-group wiring at shipping splits can be readily connected by
referring to wire markings. These wires are of sufficient length
to be routed to their termination point after cubicles are bolted
together. Terminals for these leads are furnished by others to
suit the available crimping tools. When required, terminal block
hardware is furnished with the switchboard. All wiring diagrams
needed for installation are furnished in advance.
Wires can be easily traced on a wiring diagram furnished for the
switchboard. Each device is illustrated and each terminal on each
device is identified. The wire list adjacent to each device on the
diagram indicates the device and terminal number to which each
wire is connected at the next connection point.
All control wiring installed by the factory is neatly bundled and
secured to the cubicle side plate or wiring pan. Make all field
connections in a similar manner. Check that all parts and com-
ponents clear any additional wiring installed. All field wiring is
to be routed behind the cable retainer which is removable for
installation purposes. Use plastic or nylon ties to secure all field
installed wire to the cubicle structure.
SECTION 5.0 - PRE-ENERGIZING, INSPECTION AND TESTING
Before the equipment is energized, it must be thoroughly inspect-
ed and tested. Correct any deviations and re-inspect equipment
before energizing.
“Siemens Industrial Services” can provide the following support
services for switchboards. Call 1-800-241-4453 to obtain addi-
tional information and schedule an appointment.
• Start-up Commissioning
• Component and System Testing
• Maintenance (Scheduled and Preventative)
• Repair and Refurbishing
• On Site Operational Training
5.1 Inspection
Check the following points:
5.1.1. Visually inspect switchboard for any damage that may
have affected bus bar supports, device mountings or
reduced electrical clearances within the switchboard
(minimum clearance values are listed on Page 6).
5.1.2. Electrical disconnecting contacts, machine parts,
shutter, etc., checked for lubrication and operation.
5.1.3. Blocking, supports and other temporary ties removed
from breakers, instruments, relays, etc.
5.1.4. Check torque of all bus bar connections, including fac-
tory and field installed connections. (Torque values are
listed on Page 16.)
5.1.5. Proper fuses correctly installed.
5.1.6. Manually operate all devices (circuit breakers, switches,
etc.) Check for alignment and proper operation.
5.1.7. Operate all electrically operated devices (circuit break-
ers, switches, meters, relays, etc.). An auxiliary power
source may be required.
5.1.8. Temporary wiring jumpers (used on the secondaries of
current transformers tied to external devices, as shown
on wiring diagrams) removed.
5.1.9. Check current transformer shorting terminal block
screw position.
10
Pre-Energizing, Inspection and Testing
Lashing Instructions to 65,000A Maximum
To comply with UL short circuit withstand ratings the
adjacent Ø & N connections shall be lashed per the
instructions provided below.
Wrap line cables together with nominal 3/8”nylon rope
or rope having a minimum tensile strength of 2000 pounds.
From switchboard entrance to the point that the cables lace
together, wrap each run of cable with 1 turn every 3 inches.
Where cables lace into terminals,support must be added to
the cables per the diagram.This should be installed 6”from the
terminals and every 12” beyond that point.
Crimp Connectors - Referto instructions on connector forprop-
er crimping tool and quantity of crimps required.The lashing
shall be as described above.
11-1000-01 REV. 7
Lashing Instructions to 100,000A Maximum
To comply with UL short circuit withstand ratings the adjacent Ø
& N connections shall be lashed per the instructions pro-vided
below.
Wrap line cables together with nominal 3/8”nylon rope or
rope having a minimum tensile strength of 2000 pounds.From
switchboard entrance to the point that the cables lace together,
wrap each run of cable with 1 turn every 3 inches.Where cables
lace into terminals, support must be added to the cables perthe
diagram.This should be installed 6”from the terminals and every
9”beyond that point.
Crimp Connectors - Referto instructions on connector for
propercrimping tool and quantity of crimps required.The
lashing shall be as described above.
11-1001-01 REV. 6
Lashing Instructions to 200,000A Maximum
To comply with UL short circuit withstand ratings the adjacent
Ø & N connections shall be lashed per the instructions
provided below.
Crimp Connectors - Referto instructions on connector forproper
crimping tool and quantity of crimps required.Wrap line cables
together with nominal 1/2”nylon rope orrope having a minimum
tensile strength of 3000 pounds.Where cables lace into line
terminals support must be added to cable per the diagram
provided.This should be installed every 6”from line terminals
and every 6”above that point.
Note: Cable support must be re-installed over lug barrels after
cable termination.
11-1006-01 REV. 3
Cable Support Supplied by Siemens
5.1.10. All protective devices and relays are shipped from the
factory with all adjustable settings configured at the
lowest possible values. Adjustments based on required
system coordination study must be done by the end
user. Siemens Technical Services can be contracted to
perform
the system coordination study and system
commissioning.
5.1.11. Make sure ground connections properly made.
5.1.12. Make sure incoming primary and secondary connections
properly made and checked for shorts or undesired
grounds.
5.1.13. Make sure all equipment which has been removed
during assembly has been replaced.
5.1.14. Confirm that interlocks performing properly.
5.1.15. Disconnect devices checked per instruction books.
5.1.16. Make sure any filters in vent areas are clean and free of
foreign material.
5.1.17. Inspect and remove any tools or objects left inside
the equipment.
5.1.18. Make sure all covers are installed. Close doors and
ensure that all conductors are not pinched or nicked.
5.2 Testing
5.2.1. A megger test should be performed to ensure that all
connections made in the field are properly insulated.
Test from phase to phase, phase to ground, phase to
neutral, and neutral to ground with the neutral isolated
from ground and all overcurrent devices in the open
position. See NEMA PB2.1, Section 7.6. Resistance
readings of 1 Megohm or greater are preferred. If low
readings are observed and an investigation for possible
corrections does not correct test readings, then contact
your Siemens Sales Office for assistance.
5.2.2. A dielectric test should be made on the circuit for one
minute at twice the rated voltage plus 1,000 volts corre-
sponding to the rated volt of the equipment.
5.2.3 Voltage transformers, control power transformers, surge
arresters, and surge capacitors must be disconnected
during these test.
NOTE: The dielectric test voltage is given as a reference only for
those using dielectric tests to verify the integrity of connected
cable installations without disconnecting the cables from the
switchboard. It represents values believed to be appropriate
and approximately equivalent to the corresponding power fre-
quency withstand test values specified for each voltage rating
of switchboard. When performing dielectric tests, the voltage
should be raised to the test value in discrete steps and held for
a period of one minute.
In accordance with ANSI C37.20.02 Clause 5.5, Field Dielectric
Tests are also recommended when new units are added to
an existing installation, or after major field modifications. The
equipment should be put in good condition prior to the field
test. It is not expected that equipment shall be subjected to
these tests after it has been stored for long periods of time
or has accumulated a large amount of dust, moisture, or other
contaminants without being first restored to good condition.
5.3 Ground Fault Protection System
NEC Section 230.95 requires ground fault protection on all serv-
ice disconnects rated 1000 amperes and larger in switchboards
when fed by a solidly grounded wye system of more than 150
volts to ground. When provided, all ground fault protection
equipment for the switchboard is tested before shipment from
the factory. The ground fault protection system, when provided,
must be tested when first installed in accordance with NEC
Section 230.95 paragraph C .
There is an exception to this rule: Ground fault protection is not
required on fire pumps or continuous industrial loads where a
non-orderly shutdown would cause a hazard.
Health care facilities, such as hospitals require additional levels of
ground fault protection. These requirements are described in NEC
article 517.
Sections 215.10 and 240.13 of the NEC require ground fault pro-
tection on all 1000 ampere and larger devices, breakers, and
switches, applied in a system as described above, unless there is
ground fault protection upstream.
Many utilities use a grounded Wye secondary transformer and
bring a connection from the grounded mid-point to the
service section ground bar. When this is the case, ground fault
protection is required.
11
Pre-Energizing, Inspection and Testing
THIS CIRCUIT PROTECTED
BY GROUND FAULT PROTECTION
11-1004-01 Rev. 3
DANGER
Hazardous voltage.
Will cause death or serious
injury.
Keep out.
Qualified personnel only.
Disconnect and lock off all power
before working on this equipment.
For a 1000 ampere or larger 480 volt, 3-phase 3-wire service sec-
tion, an inquiry should be made to determine if the utility is using
a 3-wire delta secondary transformer. Should this be the case, no
ground fault protection is required.
Figure 15
WARNING: The following should be performed only by qualified
personnel as defined in NEC article 100. The ground fault sensor
(GFS), ground fault relay (GFR), must be installed as in Figure 15.
Note: Test report and test record forms found on Page 18
and 19 of this manual can be used to record ground fault
field testing.
6.0 GROUND FAULT INSPECTION AND TESTING
“Siemens Industrial Services” can provide the following support
services for switchboards. Call 1-800-241-4453 to obtain addi-
tional information and schedule an appointment.
• Start-up Commissioning
• Component and System Testing
• Maintenance (Scheduled and Preventative)
• Repair and Refurbishing
• On Site Operational Training
6.1 External Ground Fault
6.1.1. Disconnect Main Power Source.
6.1.2. Remove the neutral disconnect link. Make sure
the neutral is grounded only by the main bonding
jumper, which must be on the line side of the sensor.
6.1.3. Close all branch devices.
6.1.4. Using a “megger” type meter, measure the resistance
of the load phase and neutral to ground. This is to ensure
that no ground connections exist in the system. Resistance
readings of one (1) Megohm or greater are preferred.
6.1.5. Re-install the neutral disconnect link.
6.1.6. Open all devices.
6.1.7. Connect the main power source.
To test the entire system including the disconnect device.
Check for control power (LED should be illuminated).
Press the “push to test” switch on the relay.
The trip indicator should go to the “trip” position and the
disconnect device will open.
Release the “push to test” switch on the relay.
Reset the relay, and the disconnect device. System is
now back to normal.
To test the ground fault relay and sensor only (the sensor
will trip the relay in this test).
Check for control power, “LED” should be illuminated.
Press and hold the “shunt trip bypass” switch on the relay.
Press the “push to test” switch. The ground fault relay will trip.
Reset the relay, then release the “shunt trip bypass” switch.
System is now back to normal.
Note: Test Report form found on page 19 of this manual can
be used to record ground fault field testing.
6.2 Internal Ground Fault
The procedures below are for SJD6, SHJD6, SCJD6, SLD6, SHLD6,
SCLD6, SMD6, SHMD6, SCMD6, SND6, SHND6, SCND6, SPD6,
SHPD6, STD6, SHTD6, SBA, and SB4 breakers.
6.2.1 General
Siemens Sensitrip III and SB circuit breakers may be equipped
with integral ground fault protection. These devices are usually
identified by a “G” in the trip unit catalog number and the pres-
ence of the ground fault adjustments. The National Electrical
Code® requires that these devices be performance tested when
first installed (230.95(C). These instructions are intended to
guide the installer in meeting this requirement.
General Instructions
6.2.1.1. The interconnected system shall be evaluated when
initially installed by qualified personnel. It is also sug-
gested this be done periodically thereafter.
6.2.1.2. The proper location of the sensors around the bus of the
circuit to be protected shall be determined. This can be
done visually, with knowledge of which bus is involved.
6.2.1.3. The grounding points of the system shall be verified to
determine that ground paths do not exist that would
bypass the sensors.
6.2.1.4. The polarity of the sensor connections must agree with
the installation instructions to avoid improper operation.
12
Ground Fault Inspection and Testing
Disconnect
Device
Main Bonding
Jumper
Neutral Disconnect
Link No grounds permitted
downstream from
bonding jumper
neutral, if used
From Sensor
To Control Power Source
Load
Main Power Source
Ground
Fault
Relay (GFR)
Shunt
Trip
Device
To GFR To GFR
#2 #1
Fig. #1
Sensor (GFS)
Sensor (GFS)
Ground Fault Configuration
GFS #1, is the standard location
GFS #2, alternate location for GFS
Ground Fault Relay
6.2.1.5. A simulated test is to be done using a low voltage, high
current source. This test is not intended to verify the cali-
bration of the ground fault protection but to verify it is
properly functioning.
6.2.1.6. The results of this testing should be recorded on the
form provided at the end of this document or on other
appropri
ate forms and should be available to the inspec-
tion authority.
6.2.1.7. These breakers may be set for different modes of oper-
ation. Residual or Ground Return, as described in the
instructions supplied with the circuit breaker. For further
information on applications, refer to the NEMA standards
publication No. PB 2.2 Application Guide for Ground
Fault Protective Devices for Equipment.
6.2.1.8. Operation Test
Switch Setting - Residual Outgoing Circuit Method
6.2.1.8.1. 3 Phase / 3 Wire
Using Figure 16, individually test breaker
poles A, B and C for proper Ground Fault
operation.
Each of the circuit breaker’s front panel controls should be set
to the highest setting. Using a low-voltage current source, apply
a test current equal to 125 percent of the ground fault pickup
setting to one pole of the circuit breaker. The circuit breaker
must trip.
Figure 16
Warning: NEVER pass test current through an unterminated
Neutral Sensor. Permanent sensor damage may occur if operated
in this manner.
6.2.1.8.2. 3 Phase/4 Wire
Using Figure 16, individually test breaker poles A, B and C
in conjunction with the proper Neutral Sensor for proper
Ground Fault operation.
Each of the circuit breaker’s front panel controls should be
set to the highest setting. Using a low-voltage current source,
apply 125 percent of the ground fault setting to one pole of the
circuit breaker. The circuit breaker must not trip. Reduce the test
current to zero.
Using a suitable means, short the X1/wire and X2/wire connec-
tions together on the Neutral Sensor. Re-apply the 125 percent
test current to the breaker pole under test. The breaker must trip.
Reduce the test current to ZERO and remove the shorting means
from the Neutral Sensor.
6.1.2.9. GF Switch Setting - Ground Return
Ground Return Method
6.1.2.9.1. 3 Phase/3 Wire or 3 Phase/4 Wire
Each of the circuit breaker’s front panel controls should
be set to the highest setting. Using a low-voltage cur-
rent source, apply a current equal to 125 percent of
the ground fault pickup setting per Figure 17. The
circuit breaker must trip.
Figure 17
Note: Test report form found on page 18 can be used to record
ground fault field testing.
FAILURE TO PROPERLY MAINTAIN EQUIPMENT CAN RESULT IN
DEATH, SERIOUS INJURY OR PRODUCT FAILURE. THE INSTRUC-
TIONS CONTAINED HEREIN SHOULD BE CAREFULLY REVIEWED,
UNDERSTOOD AND FOLLOWED. THE FOLLOWING MAINTENANCE
PROCEDURES MUST BE PERFORMED REGULARLY.
SECTION 7.0 - ENERGIZING AND OPERATION
WARNING. HAZARDOUS VOLTAGES IN ELECTRICAL EQUIP-
MENT CAN CAUSE SEVERE PERSONAL INJURY OR DEATH.
ENERGIZING A SWITCHBOARD FOR THE FIRST TIME AFTER
INITIAL INSTALLATION OR MAINTENANCE IS POTENTIALLY
DANGEROUS.
7.1 Placing Equipment Into Service
Only qualified personnel should place equipment into service.
Proceed as follows:
7.1.1. Check all interrupting devices. Set all devices to open
position. Check and open all control circuits.
7.1.2. Energize primary incoming power source to equipment.
Note: The primary incoming power source should not
exceed the normal rating of equipment.
13
Energizing and Operation
Refer to breaker instructions
for correct neutral sensor
wiring terminations.
DANGER
Hazardous voltage.
Will cause death or serious
injury.
Keep out.
Qualified personnel only.
Disconnect and lock off all power
before working on this equipment.
Switchboard Loading and Maintenance
7.1.3. Close control circuit to check all instruments, relays,
meters, etc., during this time. Note: There should be
no load on switchboard when it is energized.
7.1.4. Energize in sequence starting at the source and work
towards the load. Close main device, then feeder
devices, then branch devices to source load. As the
smallest branch load is added, observe instruments.
Allow several minutes before connecting additional load.
7.1.5. Gradually connect more loads to equipment. Observe
instruments and allow several minutes before adding
additional load. Follow this procedure until the full load
is connected.
7.1.6. After all mains and branch devices have been closed,
down stream loads such as lighting load, contactors,
heaters, and motors may be turned on.
7.1.7. Check primary and secondary circuits for overheating.
Also check all instruments during the first week of
operation.
SECTION 8.0 - SWITCHBOARD LOADING
8.0.1. Main Lug Switchboards (without main).
The total continuous load current through the supply bus
should not exceed the current rating of the switchboard.
8.0.2. Single Main Switchboards
The total continuous load current on main device should
not exceed 80 percent of main device unless rated for
100 percent of its ampere rating. The same will apply to
each main of a multi-main switchboard. Feeders and
branch circuits follow same 80 percent rule for load
applied to feeder and branch circuit.
8.0.3. Some types of electrical equipment will cause harmon-
ics in electrical systems. This may result in overheating.
When determining loading of switchboard, this condition
should be considered. Possible de-rating of equipment
may be necessary.
SECTION 9.0 - MAINTENANCE
FAILURE TO PROPERLY MAINTAIN EQUIPMENT CAN RESULT IN
DEATH, SERIOUS INJURY OR PRODUCT FAILURE. THE INSTRUC-
TIONS CONTAINED HEREIN SHOULD BE CAREFULLY REVIEWED,
UNDERSTOOD AND FOLLOWED. THE FOLLOWING MAINTENANCE
PROCEDURES MUST BE PERFORMED REGULARLY.
9.1 Inspection and Maintenance Intervals
Periodic inspections and maintenance are essential to obtain
safe and reliable operation. When equipment is operated under
“Usual Service Conditions,” maintenance and lubrication is
recommended at least annually. Generally, “usual service condi-
tions” are defined as an environment in which the equipment is
not exposed to excessive dust, acid fumes, damaging chemicals,
salt air, rapid or frequent changes in temperature, vibration, high
humidity, and extremes of temperature. Where equipment is
exposed to these conditions, more frequent maintenance is
recommended.
For the safety of maintenance personnel, as well as others who
might be exposed to hazards associated with maintenance
activities, the safety related work practices of NFPA 70E, parts II
and III and other recognized safety practices such as those con-
tained in the National Electric Code and OSHA should always be
followed when working on electrical equipment. Maintenance
personnel should be trained in the safety practices, procedures
and requirements that pertain to their respective job assignments.
This manual should be reviewed and retained in a location readily
accessible for reference during maintenance of this equipment.
The user must establish a periodic maintenance program to
ensure trouble-free and safe operation. The frequency of inspec-
tion, periodic cleaning and preventative maintenance schedule
will depend upon the operating conditions. NFPA Publication
70B, “Electrical Equipment Maintenance” may be used as a
guide to establish such a program.
A preventative maintenance program is not intended to
cover reconditioning or major repair, but should be designed
to reveal, if possible, the need for such actions in time to pre-
vent malfunctions during operation.
9.2 Recommended Maintenance
Periodic maintenance includes cleaning, lubrication and the
exercising of component parts. The interval between mainte-
nance checks can vary depending on the amount of usage
and environmental conditions of each installation.
The maximum recommended inspection interval should not
exceed one year and should include all the tests shown in
the section below, “Maintenance Tasks.”
Always inspect the switchboard after a fault (see section 10.0
on Adverse Conditions”). Instruction manuals for the various
disconnecting and overcurrent devices mounted in the switch-
board are indicated in the “Supplemental Instruction Manuals”
section and are available through your local Siemens sales office.
A permanent record of all maintenance work should be kept.
The record should include a list of periodic checks and tests
made, the date they were made, the condition of the equip-
ment, and any repairs or adjustments that were performed.
9.3 Maintenance Tasks
9.3.1. Before any maintenance is performed on a switch-
board that has been energized for at least 3 hours,
it is recommended, just prior to inspection, a simple
hand test be performed. This test should consist
DANGER
Hazardous voltage.
Will cause death or serious
injury.
Keep out.
Qualified personnel only.
Disconnect and lock off all power
before working on this equipment.
14
of placing your hand on the front and side of the
equipment enclosure, the deadfront surfaces of
circuit breakers, switches, interior trims, doors for
at least 3 seconds. If you cannot maintain contact
with the surfaces due to the extreme temperatures,
this may be an indication of trouble and immediate
investigation is required.
Warning: Switchboards contain voltages that may
cause severe injury or death. Power to the switch
board should be turned off, disconnected and elec-
trically isolated so that accidental contact cannot
be made with energized parts during inspection
and maintenance, unless otherwise specified.
9.3.2. Before starting work on the equipment, the following
should be completed on any equipment that will affect
the area of the work:
A.
Disable remote control and automatic transfer schemes.
B. De-energize all direct and back feed power and control
sources, test and ground
C.
Disconnect all voltage and control power transformers.
D. Open all disconnects.
9.3.3. Include the following items in your procedure:
A. Check general condition of switchboard installation.
B. Inspect interior for accumulation of dust, dirt or any
foreign matter. Vacuum the interior to remove any dirt
or dust deposits. Do not use an air hose as pressurized
air may blow dust into critical electrical contact areas.
C. Check the interior carefully for moisture, condensation
buildup, or signs of any previous wetness. Inspect all
conduit entrances and cracks and seal off any leaks to
eliminate moisture. Clean air filters by washing in a mild
household detergent.
D. Examine indicating lamps and replace as required.
E. Check terminal blocks contacts for loose connections.
F. Check instrument and control switches and inspect
their contacts.
G.
Check for proper condition of instrument transformers.
Replace burned out fuses, if any. Check primary and
secondary connections.
H. Remove dust from all de-energized insulators.
I. Inspect bus bars and connections for proper condition.
If bus bars are overheating, check for poor or loose con
nections or for overload.
J. Examine fuse clip contact pressure and contact means.
If signs of over-heating or looseness, contact sales for
replacement.
K. Look for and replace deteriorated insulated material
where sealing compound has melted.
L. Examine all safety interlocks to insure they are func-
tional and in proper working order.
M. Carefully inspect all devices for any worn, cracked, or
missing parts. Manually open and close devices sev-
eral times to insure they are in proper working order.
Perform maintenance of interrupting devices as out
lined in the device instruction manual. Do not open
sealed breaker or trip unit as calibration may be dis-
turbed. Return to factory for any replacement. For
reference, see NEMA AB4-2000.
N. Check space heaters and thermostat (if equipped) for
proper operation.
O. Maintain other auxiliary equipment per their respec-
tive instruction book requirements.
P. Lubricate mechanisms, contacts, and other moving
components. Do not lubricate parts of molded case
circuit breakers.
Q. Inspect painted surfaces and touch up as needed.
R. Check for signs of rodent or insect nesting inside the
switchboard.
S. Replace, reassemble, re-insulate, return all items to
proper operating conditions and remove grounds
prior to energization.
T. Ensure satisfactory operation of relays and instru-
ments as per instruction books furnished separately.
Do not leave device covers off longer than necessary.
When a cover has been broken, cover the device
temporarily and replace broken glass as soon as
possible.
U. Test ground fault protection system (if furnished).
V. Conduct an electrical insulation resistance test to
ensure that the switchboard is free of short circuit
and ground.
9.3.4.THIS CHECKLIST DOES NOT REPRESENT AN EXHAUSTIVE
SURVEY OF MAINTENANCE STEPS NECESSARY TO ENSURE
SAFE OPERATION OF THE EQUIPMENT. PARTICULAR APPLI-
CATIONS MAY REQUIRE FURTHER PROCEDURES. SHOULD
FURTHER PROCEDURES BE DESIRED OR SHOULD PARTICULAR
PROBLEMS ARISE WHICH ARE NOT COVERED SUFFICIENTLY
FOR THE PURCHASER'S PURPOSES, THE MATTER SHOULD
BE REFEREED TO THE LOCAL SALES OFFICE.
DANGEROUS VOLTAGES ARE PRESENT IN THE EQUIPMENT
WHICH CAN CAUSE DEATH, SERIOUS INJURY OR PROPERTY
DAMAGE. ALWAYS DE-ENERGIZE AND GROUND THE EQUIP-
MENT BEFORE MAINTENANCE. MAINTENANCE SHOULD BE
PREFORMED ONLY BY QUALIFIED PERSONNEL.
THE USE OF UNAUTHORIZED PARTS IN THE REPAIR OF THE
EQUIPMENT, TAMPERING BY UNQUALIFIED PERSONNEL,
WILL RESULT IN DANGEROUS CONDITIONS WHICH CAN
CAUSE DEATH, SERIOUS INJURY OR EQUIPMENT DAMAGE.
FOLLOW ALL SAFETY INSTRUCTIONS CONTAINED HEREIN.
9.4 Cleaning Insulation
Most of the plastics and synthetics used in insulation systems
are attacked by solvents containing aromatics or halogenated
hydrocarbons which may cause crazing and deformation of
the material reducing the dielectric strength. ISOPROPYL
ALCOHOL IS THE ONLY RECOMMENDED SOLVENT CLEANER.
15
Maintenance
SECTION 10.0 - ADVERSE CONDITIONS
10.1 Ambient Temperatures
Switchboards are designed for installation where the average
ambient temperature will not exceed 40ºC (104ºF). For higher
temperatures, derating may be required. Contact the nearest
Siemens representative to discuss your special application.
10.2 Short Circuits
Overcurrent protective devices will normally prevent electrical
damage except at the actual point where the short circuit or fault
condition occurred. However, the high mechanical stress devel-
oped by short circuit currents may cause damage to conductors,
insulation, or other equipment installed within the switchboard.
After any fault, a thorough inspection of the entire system must
be made to ensure there is no damage to conductors, insulation
or equipment (Refer to inspection and maintenance procedures.)
In addition, overcurrent protective device(s) which performed
the short-circuit interruption must be inspected for possible
arcing damage to contacts, arc chutes, and/or insulation. Do
not open any sealed devices or breaker trip units. Equipment
should be hi-pot tested prior to being placed back in service.
If device is damaged, replacement of that device is required.
10.3 Arcing Damage
During a fault, some organic insulation materials carbonize when
subjected to the intense heat of an electrical arc, and lose their
insulation qualities. Any carbon deposits or tracking must be com-
pletely removed with a dry, lint-free cloth, or the material must
be replaced before re-energization. Contact your local Siemens
sales representative before clean up and corrective action.
10.4 Water Damage
Completely de-energize the switchboard if there is any sign of
moisture or water damage. If damage is believed to be extensive,
or if the equipment has been subjected to moisture for extended
periods, contact your local Siemens sales representative.Addi-
tional information is also available from NEMA publication,
“Guidelines for Handling Water Damaged Electrical Equipment.”
10.5 Corrosive Atmospheres
Switchboards are designed to give optimum performance when
installed in normal indoor or outdoor locations. Where corrosive
atmospheres are encountered, special precautions must be taken
to minimize their effect. Exposed metallic surfaces, non-insulated
bus bars, disconnect switches, primary and secondary discon-
necting contact, wire ends, instrument terminals, etc. must all
be protected. At each maintenance inspection, all of the old
grease should be wiped off of the contacts and new lubricant
applied to all sliding surfaces.
Apply the material in a layer .03-.06” thick. Use only Siemens
Electrical Contact Lubricant, Part No. 15-171-370-002, available
in 8 oz. tubes. Other exposed components can be protected with
a coat of glyptol or other corrosion-resistant coating. When old
grease becomes dirty, wipe the part clean and apply new grease
immediately.
SECTION 11.0 - INFORMATIONAL CHARTS
11.1 Torque Values
16
Adverse Conditions and Informational Charts
NOTE
THIS EQUIPMENT HAS BEEN TESTED AND INSPECTED BEFORE SHIPMENT. SHIP-
PING CONDITIONS MAY HAVE LOOSENED SOME CONNECTIONS .
BEFORE ENERGIZING, IT IS RECOMMENDED THAT THE TIGHTNESS OF ALL CON-
NECTIONS BE CHECKED.
BELLEVILLE WASHER NUTS THREAD FORMING SCREWS
Bolt Torque Screw Torque in lbs-in.
Size Lbs.-in. Lbs.-ft. Size 0.125 Thick 0.187 Thick 0.25 Thick
1/4-20 72 6 AL CU AL CU AL CU
5/16-18 144 12 8-32 20 25 30 35 30 35
3/8-16 240 20 10-24 20 25 30 50 30 50
1/2-13600 50 1/4-20 30 50 30 72 50 72
BREAKER CONNECTING MACHINE SCREW
Screws Torque in inch lbs
#10 20
1/4” 72
FIELD WIRED CONNECTORS - TIGHTENING TORQUE
Torque all wire connectors, where not marked on the device or component, to
the values indicated in the table below:
Hex Socket Set Screw Slotted Head Screws
Socket Size Torque AWG Torque Lbs.-in.
(Across Flats) Lbs.-in. Wire Small Hole Large Hole
Size #6 - Max. 1/0 Max.
7/32” 150
1/4” 200 #14-10 20 35
5/16” 275 #8 25 40
3/8” 375 #6 35 45
1/2” 500 #4 45
9/16” 600 #3-1/0 50
BRANCH LOAD CONDUCTORS-PANEL MOUNTED DEVICES
This switchboard designed for installation of conductors per NEC 312.6. Refer
to branch circuit devices for cable size and torque.
EXCEPTIONS FOR 38” WIDE ENCLOSURES
(1) 400 ampere twin mounted JD6, JXD6, JXD2, HJD6, SJD6, CJD6, SHJD6 and
SCJD6 type are limited to a maximum of (1) 500 MCM OR (2) 250 MCM CU-AL
per pole.
As a minimum, wire bending space as required (NEC Tables 312.6(A) and
312.6(B) for this product is based on wire or cable sizes per table 310-16 of the
NEC. Circuits 110 amps and less are sized from the 60º C aluminum column.
Above 110 amps circuits are sized from the 75º C aluminum column. 400 amp
circuits are based on (2) 250 or (1) 500 kcmil cables per phase. 600 amp cir-
cuits and greater are sized based on multiple 500 kcmil cables per phase.
CONNECTORS USED TO TERMINATE FIELD MADE CONNECTIONS ARE SUITABLE
FOR USE WITH CU OR AL 60 DEG C OR 75 DEG C RATED CONDUCTORS. UNLESS
NOTED OTHERWISE ON THE DEVICES.
CAUTION: IF A PANELBOARD IS INSTALLED IN THE SWBD AND MORE THAN 10%
OF THE BREAKER POLES OR FUSIBLE UNITS ARE SUPPLYING LIGHTING AND/OR
APPLIANCE CIRCUITS THEN THIS UNIT IS NOT TO EXCEED 42 CIRCUITS (NEC ARTI-
CLE 408.14, 408.15) ALSO, IF THIS UNIT IS USED AS SERVICE EQUIPMENT, IT IS
LIMITED TO SIZE DISCONNECTS (NEC ARTICLE 230.71).
BOLTED PRESSURE EXCEPTION: WHEN CABLES ARE MOUNTED DIRECTLY TO
BOLTED PRESSURE SWITCH TERMINALS, REFER TO CABLE SELECTION INSTRUC-
TIONS ON SWITCH.
Torque requirements shown in table are for Grade 5 hardware. Older switch-
boards were supplied with grade 2 hardware. Grade 2 hardware shall be torqued
at 22 FT/LBS or 264 IN/LBS. Refer to Page 7 for a drawing to determine which
grade of hardware is installed.
Informational Charts
11.2 Wire Bending Requirements
Wire Bending space at terminals shall be measured in a
straight line from the end of the lug or wire connector (in
the direction that the wire leaves the terminal) to the wall,
barrier, or obstruction.
For removable (compression type) and lay-in-wire terminals
intended for only one wire, bending space shall be permitted
to be reduced by the number of inches shown in parenthesis.
11.3 Strap Kits
11.3.1 Connecting Strap Kits - Circuit Breaker
For use with Series 6 Circuit Breaker, SB1, SB2 and SB3
Switchboards — includes copper straps, cover plates and
necessary hardware for switchboards. For replacement strap
kits for RCIII switchboards, contact your local sales office.
Note: D = Denotes double branch or twin mounting
S = Denotes single mount
11.3.2 Filler Plates
For use with Series 6 Circuit Breaker Panelboards, SB1, SB2, and
SB3 Switchboards.
Note: When a front filler plate is not completely filled with break-
ers, the openings in the unused space must be closed with 1-pole
filler plates from table.
11.3.3 Connecting Strap Kits Vacu-Break and HCP
For use with SB1, SB2 and SB3 Switchboards. Includes copper
straps and necessary hardware for switchboards.
11.3.4 Blank Plates — Circuit Breaker and Vacu-Break
For use with Series 6, SB1, SB2, and SB3 Switchboards.
Strap Kit
Catalog Height
Breaker Type Number (inches) Mounting
BL, BLH, HBL, BQD SBLBD 3.75 D
ED2, ED4, ED6, HED4, HED6 6E62 3.75 D
CED6 6CLE2 3.75 D
QJ2, QJH2, QH2-H 6QJ2 5D
FXD6, FD6, HFD6 6F62 5D
CFD6 6CLF1 5S
JXD2, JXD6, JD6, HJD6 6JJ61 8.75 S
Single Branch
JXD2, JXD6, JD6, HJD6 6JJ62 8.75 D
Double Branch
CJD6 6CLJ1 8.75 S
SJL, SJD6, SHD6 6SJL1 8.75 S
SCJD6 6SCJ1 8.75 S
LXD6, LD6, HLD6 6LL61 8.75 S
CLD6 6CLL1 8.75 S
SLL, SLD6, SHLD6 6SLL1 8.75 S
SCLD6 6SCL1 8.75 S
LMD6, HLMD6 SLM1D 8.75 S
MD6, HMD6, CMD6 SMND 10 S
SMD6, SHMD6, SCMD6 SSMND 10 S
ND6, HND6, CND6 SMND 10 S
SND6, SHND6, SCND6 SSMND 10 S
Wire Bending NEC 312.6
WIRES A B
#1/0 3-1/2” 5-1/2”
1-300 5” 10”(3)
1-500 6” 14”(3)
1-750 8” 17”(3)
2-300 8” 10”(2)
2-500 8” 14”(3)
2-750 12” 19”(3)
3-400 10” 14”(3)
3-500 10” 15”(3)
3-750 14” 22”(3)
4-500 12” 16”(3)
4-750 16” 24”(3)
5-500 14” 16”(3)
5-750 18” 24”(3)
17
Height Catalog Number
(inches) Series 6
1¹⁄₄ 6FPB01
2¹⁄₂ 6FPB02
3³⁄₄ 6FPB03
56FPB05
10 6FPB10
Ampere Unit Height Catalog
Rating (inches) Number
30-30 5, 7¹⁄₂
30-60 5, 7¹⁄₂
60-60 5, 7¹⁄₂ VB657
60-100 7¹⁄₂
100-100 7¹⁄₂
100 7¹⁄₂
200 7¹⁄₂, 10 VB671
200-200 10 VB610
400-600 15 VB6150
800-1200 (HCP) 16¹⁄₂ F6162D
Breaker Filler Plate
Frame Catalog Number
BQ, BQH, HBQ, E2, E4, E6, HE4, HE6,
E2-A, E-4A, E6-A, HE4-A OR HE6-A QF3
AND ED2, ED4, ED6, HED4, HED6
Informational Charts
11.4 Ground Fault Test Record - Internal
PERFORMANCE TEST REPORT
GROUND FAULT PROTECTION
Job: ______________________________________________________________________________________________________________
Location:______________________________________________________ Date of Test: _______________________________________
Circuit:_____________________________________________________________________________________________________________
Switchboard: _________________________________________________________________________Single/Double End _____________
Disconnect Device: _________________________________________________________________________________________________
GF Protective Device: _______________________________________________________________________________________________
GF Sensor: ________________________________________________________________________________________________________
Test Equipment: (Describe on back or attach a page.)
Test Setup and Method: (Describe on back or attach a page.)
A. INSPECTION
1. Wiring and conductors
2. Connections and wire clamping
3. Bonding, splice bussing and grounding
4. Sensor mounting and wiring
5. Control circuit overcurrent protection
6. Other: _______________________________________________________________________________________________________
B. INSULATION RESISTANCE
1. Neutral-to-ground
2. Neutral-to-enclosure
3. Enclosure and grd. bus-to-ground
4. Grounded service conductor-to-ground
5. Other: _______________________________________________________________________________________________________
C. OPERATION TEST
1. GF protective device setting: _______________A, _____________________sec. Time Curve: _____________________________
2. Control Power ________________________________________________________________________________________________
3. Test Current: (a) __________________________________A, x ______________________ turns = _______________________AT
or (b) Test set signal ________________________________________________________________________________________
or (c) Primary Current _______________________________A
4. Trip operation
5. Time Delay: one second or less
6. Test button, lamp, indicator operation
7. Other: ________________________________________________________________________________________________________
D. LABEL AFFIXED
E. EQUIPMENT RESTORED TO OPERATIONAL CONDITION
GFP settings (as left) _____________________________________________________________________________________________
Tested by: _________________________________________________________
(1) This test record to be retained by those in charge of the building electrical installation.
(2) Make the report available to the authority having jurisdiction.
Dwg. No. 15-7732 Rev. 1
18
19
Test Record
Date By Amp Setting Time Setting Notes
Informational Charts
PERFORMANCE TEST REPORT
GROUND FAULT PROTECTION
Job: ______________________________________________________________________________________________________________
Location:______________________________________________________ Date of Test: _______________________________________
Circuit:_____________________________________________________________________________________________________________
Switchboard: _________________________________________________________________________Single/Double End _____________
Disconnect Device: _________________________________________________________________________________________________
GF Protective Device: _______________________________________________________________________________________________
GF Sensor: ________________________________________________________________________________________________________
Test Equipment: (Describe on back or attach a page.)
Test Setup and Method: (Describe on back or attach a page.)
Disconnect
Device
Main Bonding
Jumper
Neutral Disconnect
Link No grounds permitted
downstream from
bonding jumper
neutral, if used
From Sensor
To Control Power Source
Load
Main Power Source
Ground
Fault
Relay (GFR)
Shunt
Trip
Device
To GFR To GFR
#2 #1
Fig. #1
Sensor (GFS)
Sensor (GFS)
Ground Fault Testing
Warning: The following should be performed only by qualified personnel as defined in N.E.C. Article 100. The ground fault sensor (GFS), ground fault
relay (GFR), must be installed as in Fig. 1.
GFS #1, is the standard location
GFS #2, alternate location for GFS
1. Disconnect Main Power Source.
2. Remove the neutral disconnect link. Make sure the neutral is
grounded only by the main bonding jumper, which must be on
the line side of the sensor.
3. Close all branch devices.
4. Using a “megger” type meter, measure the resistance of the load
phase and neutral to ground. This is to ensure that no ground
connections exist in the system. Resistance readings of (1)
Megohm or greater are preferred.
5. Re-install the neutral disconnect link.
6. Open all branch devices.
7. Connect the main power source.
8. To Test The Entire System.
a. Check for control power. (LED should be illuminated).
b. Press the “push to test” switch on the relay.
c. The trip indicator should go to the “tripped” position and the
disconnect device should operate.
d. Release the “push to test” switch and return the trip indicator to
the “reset” position.
e. Reset or “close” the disconnect device for normal operation of
the switchboard.
9. This test meets the requirements of the National Electrical Code
Section 230.95 (C).
11.5 Ground Fault Test Record- External
Service Bulletins
SECTION 12.0 - SERVICE BULLETINS
ED Frame Installation and Instruction Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .IPIM-0271E
FD Frame Installation and Instruction Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .IPIM-0272D
JD & LD Frame Installation and Instruction Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .IPIM-0273C
MD & ND Frame Installation and Instruction Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .IPIM-0274D
PD & RD Frame Installation and Instruction Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .IPIM-0275B
Sensitrip® JD & LD Frame Installation and Instruction Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .IPIM-0277B
Sensitrip MD & ND Frame Installation and Instruction Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .IPIM-0278B
Sensitrip PD Frame Installation and Instruction Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .IPIM-0279A
SB Encased System Breakers 800A - 5000A Installation and Instruction Manual . . . . . . . . . . . . . . . . . . . . . . . . .IPIM-2210C
SB Electrical Trip Unit Installation and Instruction Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .IPIM-2203C
RL Breaker Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SGVT-2002A
ACCESS Installation System Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SGIN-6028A
REFERENCE INFORMATION
NFPA7O (NEC)
NFPA 70 E
NEMA PB2
NEMA PB2.1
NEMA PB2.2
NEMA AB4
UL891
20
Siemens Energy & Automation, Inc.
3333 Old Milton Parkway
Alpharetta, GA 30005
1-800-964-4114
seainfo@sea.siemens.com
www.sea.siemens.com/power
Order # SWIM-00100-0603 Rev 0603 B&A
(Siemens Internal Part Number 11-A-1077-01 Rev. 1)
© 2003 Siemens Energy & Automation, Inc. All Rights Reserved
Siemens is a registered trademark of Siemens AG. SENTRON and Sensitrip are registered trademarks of Siemens Energy & Automation, Inc.
Product names mentioned may be trademarks or registered trademarks of their respective companies. Specifications are subject to change
without notice.

Navigation menu