POWERS™ Controls
Technical Instructions
Document No. 155-029P25
AP 331-3
December 3, 2004
No. 6 Pneumatic Damper Actuator
331-2793 Actuator
331-2857 Actuator
with Clevis and Pin
331-3012 Extended Shaft and Frame
Mounting
Description The POWERS Controls No. 6 Pneumatic Damper Actuator is a heavy-duty, rolling
diaphragm, spring return actuator designed to drive large dampers, centrifugal
refrigeration inlet vanes, and other applications requiring a large, effective diaphragm
area and long stroke.
Features All metal body construction
Replaceable ozone-resistant, silicone rubber, rolling diaphragm
Pivot mounting for extended shaft or frame mounting
Positioning relay (optional)
Adjustable forward travel stops (optional)
Three spring ranges for sequencing with other control devices
Product Numbers See Table 1.
Application The No. 6 Pneumatic Damper Actuator controls outdoor, return air, exhaust, face and
bypass, and fan discharge dampers. It is recommended for heavy-duty applications
using multi-section dampers where either unison or sequence operation is required.
Certain actuators in Table 1 are UL Recognized Components for
fire/smoke applications under category EMKU2. This category covers
pneumatic damper actuators used on fire dampers and leakage rated
dampers.
Siemens Building Technologies, Inc.
Technical Instructions POWERS™ Controls No. 6 Pneumatic Damper Actuator
Document No. 155-029P25
December 3, 2004
Table 1. Product Numbers for No. 6 Pneumatic Damper Actuators.
Product Numbers
Nominal Spring Range
Description
Mounting Style 3-8 psi
(21-55 kPa)
3-13 psi
(21-90 kPa)
8-13 psi
(55-90 kPa)
Actuator, integral pivot Pivot 331-2793 331-2794 331-30601
Actuator, integral pivot and forward travel stops (Figure
1)
Pivot — 331-2796 331-2988
Actuator with clevis for frame mounting (Figure 2) or
remote extended shaft mounting (Figure 3)
Pivot2 331-2857 331-2858
331-28561
Actuator with clevis and positioning relay (Figure 16) Pivot2 — — 332-2856
Actuator, integral pivot with pivot post 3 Extended Shaft 331-3012 331-3013 331-30111
Actuator, integral pivot with pivot post and positioning
relay3 (Figure 16)
Extended Shaft with
Positioning Relay
— — 332-3011
1 UL Recognized Components for Fire/Smoke Applications.
2 Also order frame mounting kit accessories.
3 Mounted on plate for extended shaft with clevis and crank for 3/8-inch (10-mm), 7/16-inch (11-mm), or 1/2-inch
(13-mm) diameter shaft. Parts for frame mounting (blade drive) included with kit.
NOTE: When the actuator is ordered with universal mounting, the mounting plate, pivot post and hardware, clevis,
damper crank, rocker arm, and all screws/nuts are included. Order other frame mounting accessories as
required, if not supplied by damper manufacturer.
Specifications Effective diaphragm area 17.9 inches2 (115 cm2)
Stroke 4 inch (102 mm)
Housing Aluminum
Stem Type 416 stainless steel
Diaphragm Ozone-resistant silicone rubber
Spring Steel
Bearing Bronze oilite
Maximum air pressure 30 psig (210 kPa)
Nominal spring ranges 3 to 8 psi (21 to 55 kPa)
3 to 13 psi (21 to 90 kPa)
8 to 13 psi (55 to 90 kPa)
Ambient temperature range
Operation -20°F to 200°F (-29°C to 93°C)
Air connection 1/8-inch NPT
Type of mounting Pivot, universal (extended shaft or
frame mount)
Thrust and torque rating See Table 2
Dimensions See Figure 13 through Figure 16
Shipping Weight 9 lb (4.08 kg)
Agency Approvals Complies with UL555 and UL555S
Page 2 Siemens Building Technologies, Inc.
POWERS™ Controls No. 6 Pneumatic Damper Actuator Technical Instructions
Document No. 155-029P25
December 3, 2004
Accessories Damper shaft extension kits:
1/2-inch (13-mm) diameter, 2-1/4 inch (57-mm) rod 331-631
(See TB-128 POWERS™ Controls Damper Shaft Extension
Technical Bulletin 155-205P25)
1/2-inch (13-mm) diameter, 9-inch (229-mm) long hollow rod 333-184
1/2-inch (13-mm) diameter, 9-inch (229-mm) long rod 333-042
1–inch (25–mm) diameter 11-5/8 inch (295-mm) long (Ruskin) 333–194
Damper shaft extension kit adapter - 3/8 inch (10 mm) diameter 331-632
(for use with Damper Shaft Extension Kit 333-042)
Actuator shaft extensions:
10-1/8 inch (257-mm) long 331-434A
Adapter kit for 1/2-inch NPT pipe 333-030
Cranks - damper shaft:
3/8-inch (10-mm) - 1/2-inch (13-mm) diameter,
Selectable radius 331-941
5/8-inch (16-mm) diameter 333-182
3/4-inch (19-mm) diameter 333-183
1-inch (25-mm) diameter 333-181
Cast iron crank with set screws 333-078
Linkage kit, 4-inch (102-mm) link and crank 331-958
Universal mounting plate
3/4-inch shaft 331-623
1-inch shaft (use with 333-194) 331-623A
Flange bearing (1/2 inch, 13 mm) 331-862
(for 331-623 Universal Mounting Plate)
Right angle mounting plate 333-208
Remote mounting kit (extended shaft), Figure 3 331-618
Positioning relay 147-2000
Positioning relay mounting kit 147-276
Frame mounting kits
One-section damper (Figure 5) 751*
Two-section damper (Figure 6) 752*
* Order frame mounting kits and damper blade clip kit from
Arrow United Industries.
Frame mounting lug 331-569
Mounting lug screws (three required for frame mounting lug) 034-123K
Offset Mounting Bracket (Figure 14) 333-176
Travel Stop Kit (for model 3 and 4 actuators only) 333-197
Damper Blade Rocker Arm 333-034
Screws (two) 030 510J
Nuts (two) 041-230J
Service Kits Silicone diaphragms (package of five) 333-572
Siemens Building Technologies, Inc. Page 3
Technical Instructions POWERS™ Controls No. 6 Pneumatic Damper Actuator
Document No. 155-029P25
December 3, 2004
Actuator Sizing The quantity of actuators required depends on several torque factors. To determine the
quantity of actuators required for the installation:
1. Obtain damper torque ratings (ft-lb/ft2) from the damper manufacturer.
2. Determine the area of the damper.
3. Calculate the total torque required to move the damper:
Total Torque = Torque Rating x Damper Area
4. Calculate the total quantity of actuators required:
Number of Total Damper Torque Required
Actuators =SF1 × Actuator Torque (see Table 2)
1 Safety Factor: When calculating the number of actuators required, a safety factor
should be included for unaccountable variables such as slight misalignments, aging of
the damper, etc. A suggested safety factor is 0.80 (or 80% of the rated torque).
See AB-300 Damper Actuator Sizing and Selection Application Bulletin in the HVAC
Systems/Controls Reference Data (125-1853) for additional sizing information. See
TB-181 Powers™ Controls Maximum Thrust Ratings of Pneumatic Damper Actuators
Technical Bulletin (155-219P25) for additional torque requirements.
Table 2. Thrust and Torque Rating.
Maximum Thrust lb. (N) Torque Rating* lb-in (Nm)
Full Stroke Forward 2-Position Operation
or Positioner
Nominal
Spring
Range 15psi
(103 kPa)
18 psi
(124 kPa)
25 psi
(172 kPa)
Spring
Return
(No Stroke)
0 psi (0 kPa)
Gradual
Operation
15 psi
(103 kPa)
18 psi
(124 kPa)
25 psi
(172 kPa)
3-8 psi
(21-55 kPa)
125 (556) 179 (796) 304
(1352)
54 (240) 50 (5.6) 75 (8.5) 75 (8.5) 75 (8.5)
3-13 psi
(21-90 kPa)
36 (160) 89 (396) 214 (952) 54 (240) 50 (5.6) 75 (8.5) 75 (8.5) 75 (8.5)
8-13 psi
(55-90 kPa)
36 (160) 89 (396) 214 (952) 144 (640) 50 (5.6) 202 (22.8) 202 (22.8) 202 (22.8)
* With maximum hysteresis of 2.5 psi (17.2 kPa) @ 90° rotation.
Page 4 Siemens Building Technologies, Inc.
POWERS™ Controls No. 6 Pneumatic Damper Actuator Technical Instructions
Document No. 155-029P25
December 3, 2004
Operation
Standard Actuator
(Figure 1)
The air tubing from a controlling instrument is connected to the actuator’s upper housing.
With no control pressure to the actuator, the compression spring forces the spring seat
and actuator shaft toward the upper housing, but is limited by the E-ring. As the control
pressure increases, the spring compression is overcome and the actuator shaft
gradually moves outward. Conversely, as control pressure decreases, the spring returns
the shaft to the position at which the air pressure on the diaphragm balances the spring
tension. For each value of control pressure there is a corresponding position of the shaft.
Table 3. Standard Actuator Components.
Item Part No. Description Qty. Material
1 047-061J Retaining E-ring 1 Steel
2 333-217 1 × 1-1/4 in. Hex Nut 1 Brass
3 — Spring Retainer 1
4 Stem Guide Assembly 1
5 — Lower Housing 1 Aluminum
6 333-572
(pkg. of 5)
Diaphragm 1 Silicone
rubber
7 599-00413 5/16 in.-18 × 1
Large Hex Cap Screw
6 Steel
8 — Upper Housing 1 Aluminum
9 Helical Compression Spring 1
331-091 3 to 13 psi (21 to 90 kPa)
331-208 3 to 8 psi (21 to 55 kPa)
331-094 8 to 13 psi (55 to 90 kPa)
10 Piston Plate and Stem
Assembly
1 Aluminum/
SS
11 — Retaining C-ring 1 Steel
Figure 1. Standard Actuator.
12 333-197 Stop Kit (Optional) Steel
Extended Shaft
Mounting—Pivot
Actuator
1. Order one of the following and see Table 4 for parts lists:
Actuator: 331-3011, 331,-3012, 331-3013, or 332-3011
2. Slip the 3/4-inch (19-mm) diameter hole in the mounting plate over the damper
shaft.
3. Slip the crank over the damper shaft. With the actuator assembly to the left of the
damper shaft, an increase in actuator pressure rotates the damper blade CW
when the crank is above the damper shaft, or CCW when the crank is below the
damper shaft. See Figure 2.
With the actuator assembly to the right of the damper shaft, an increase in
actuator pressure rotates the damper blade CCW when the crank is above the
damper shaft or CW when the crank is below the damper shaft.
4. Position the mounting plate and attach it to the duct with four screws.
5. When the actuator cannot be directly mounted, drive the extended damper shaft
using the Remote Mounting Kit 331-618 and Actuator 331-2856. See Figure 3.
Siemens Building Technologies, Inc. Page 5
Technical Instructions POWERS™ Controls No. 6 Pneumatic Damper Actuator
Document No. 155-029P25
December 3, 2004
Table 4. Extended Shaft/Frame Mounting Assemblies Components.
Item Part No. Description Qty. Material
1 041-162J Nut 1 Steel
2 046-020K Lockwasher 1 Steel
3 047-061K Retaining E-ring 2 Steel
4 331-565 Pivot Post 1 Steel
5 041-142 Nut 1 Steel
6 333-207 Clevis 1 Zinc Plated Steel
7 331-293 Clevis Pin 1 Zinc Plated Steel
8 331-807 Hitch Pin 1 Zinc Plated Steel
9 331-941 Crank Assembly 1
10 331-623 Actuator Mounting Plate 1 Steel
— 034-283 Mounting Screws 4 Steel
Figure 2. Extended Shaft/Frame Mounting Actuator Assembly.
Figure 3. Remote Mounting Kit 331-618 with 331-2856 Actuator Mounted.
Frame Mounting -
Type A
Order one each of the following. See Table 4 for parts lists:
Actuator and Clevis: 331-2856, 331-2857, or 331-2858
Frame Mounting Kit: 751 for one-section damper, or 752 for two-section damper
All frame mounting kits must be ordered from Arrow United Industries.
Page 6 Siemens Building Technologies, Inc.
POWERS™ Controls No. 6 Pneumatic Damper Actuator Technical Instructions
Document No. 155-029P25
December 3, 2004
One-Section Damper
Kit 751
See Figure 4 and
Figure 5
1. Attach the damper mounting bracket to the lower right-hand corner (or upper
left-hand corner if necessary) of the damper section with the six screws provided.
For Arrow United Industries 1770 dampers, add the shim provided between the
bracket and bottom of the frame. Have the damper manufacturer drill the holes in the
damper frame (Figure 5).
2. Have the damper manufacturer drill the holes in the damper blade for the blade clips
(Figure 4). Use the same clip location for both normally open and normally closed
dampers. Attach the damper blade clip to the damper blade (Figure 4). Put the
damper in its normal position, open or closed. Connect the push rod to the trunnion
in the blade clip and tighten the setscrew. Connect the other end of the push rod to
the crank on the drive shaft and tighten the trunnion setscrew on the push rod.
Position the crank so the push rod is parallel to the bracket, then tighten the crank
setscrews.
3. lnstall the actuator in the actuator support bracket using the pivot shaft and hitch
pins. The pivot shaft should be in the holes about 17-1/2 inch (445 mm) from the
drive shaft. The actuator support bracket can also mount in the vertical position for
installations where space is limited.
Figure 4. Damper Blade Clip.
4. Position the crank driven by the actuator as follows:
a. Normally open damper: the crank is above the drive shaft.
b. Normally closed damper: the crank is below the drive shaft.
5. Connect the actuator clevis to the crank. Put the damper in its normal position, open
or closed. Stroke the actuator 1/4-inch (6 mm) with a hand pump, then tighten the
crank setscrews. This will ensure tight damper closure.
Figure 5. One-section Damper.
Siemens Building Technologies, Inc. Page 7
Technical Instructions POWERS™ Controls No. 6 Pneumatic Damper Actuator
Document No. 155-029P25
December 3, 2004
Frame Mounting -
Type A,
Continued
Two-Section Damper
Kit 752
See Figure 6 and
Figure 7
1. Follow the steps in One-Section Damper.
2. Attach the Damper Blade Clip to the damper blade in the second damper section.
Repeat Step 2 in One-Section Damper. The push rod will connect to the extra crank
on the drive shaft.
Figure 6. Two-section Damper.
Figure 7. Actuator and Clevis Assembly 331-2857 (Typical)
Attached to Frame Mounting Kit 752.
Dimensions in Inches (Millimeters).
Page 8 Siemens Building Technologies, Inc.
POWERS™ Controls No. 6 Pneumatic Damper Actuator Technical Instructions
Document No. 155-029P25
December 3, 2004
Frame Mounting -
Type B
See Figure 8 through
Figure 10
1. Order one each of the following:
Actuator assembly: 331-3011, 331-3012, 331-3013, or 332-3011
Mounting Lug: 331-569
2. Weld the mounting lug parallel and 5/16-inch (8 mm) from the inside edge of the
damper frame and perpendicular to it. See Figure 8. Weld the lug along both sides.
The lug should be as close as possible to the corner of the damper frame to
minimize deflection. The damper manufacturer should weld the lug.
Figure 8. Frame Mounting—Type B.
Dimensions in Inches (Millimeters).
3. If the damper frame is aluminum, light gauge sheet metal, or an unusual shape, bolt
a 3/16-inch (5-mm) thick, flat piece of steel to the frame. Then weld the mounting lug
to it.
4. Attach Rocker 333-034 to blade in proper position for normally open or normally
closed damper using 2 nuts, 041-230K, and 2 screws, 030-510J. See Figure 9 and
Figure 10.
5. Attach the mounting plate to the mounting lug as follows:
a. Normally Open damper: attach the plate to the lug. Place the pivot post in Hole
4. See Figure 9.
b. Normally Closed damper: attach the plate to the lug. Place the pivot post in Hole
3. See Figure 10.
6. Fasten the clevis to the rocker. Discard the crank and other parts not used.
7. The actuator mounting plate has a tendency to pivot at the point where the lug is
welded to the damper frame when the actuator strokes. It is recommended that
some means be devised in the field to prevent this from happening. A threaded rod
attached to the mounting plate and duct wall will normally work.
Siemens Building Technologies, Inc. Page 9
Technical Instructions POWERS™ Controls No. 6 Pneumatic Damper Actuator
Document No. 155-029P25
December 3, 2004
Frame Mounting - Type B, Continued
Figure 9. Frame Mounting,
Normally Open Damper.
Figure 10. Frame Mounting,
Normally Closed Damper.
Actuator Mounting
Figure 11. Actuator Mounting Plate 331-623
Pivot Shaft Locations.
Dimensions in Inches (Millimeters).
Table 5. Mounting Plate Hole Identification.
Hole Used For
1 No. 6 Actuator extended shaft
mounting.
2 Not used.
3 No. 4 Actuator extended shaft.
No. 6 Actuator frame mounting NC
4 No. 6 Actuator frame mounting NO
5 No. 4 Actuator frame mounting NC
6 No. 4 Actuator frame mounting NO
Figure 12. Actuator Mounting Plate 331-623A
Pivot Shaft Locations.
Table 6. Pivot Post Hole Identification.
Hole Used For
1 No. 6 Actuator extended shaft mounting
2 Not used
No. 4 Actuator extended shaft 3
No. 6 Actuator frame mounting NC
4 No. 6 Actuator frame mounting NO
5 No. 4 Actuator frame mounting NC
6 No. 4 Actuator frame mounting NO
Page 10 Siemens Building Technologies, Inc.
POWERS™ Controls No. 6 Pneumatic Damper Actuator Technical Instructions
Document No. 155-029P25
December 3, 2004
Dimensions
Figure 13. Extended Shaft Remote Mounting with Travel Stops.
Dimensions in Inches (Millimeters).
Offset Mounting
Bracket
This bracket is
designed to offset
Universal Mounting
Plate 331-623 or
331-623A from the
ductwork.
NOTE: Depending on
the application, two
brackets may be
required to support
the actuator and
universal mounting
plate.
Figure 14. Offset Mounting Bracket 333-176.
Dimensions in Inches (Millimeters).
Siemens Building Technologies, Inc. Page 11
Technical Instructions POWERS™ Controls No. 6 Pneumatic Damper Actuator
Document No. 155-029P25
December 3, 2004
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as
design improvements are introduced. POWERS is a trademark of Siemens Building Technologies, Inc. Other product or company names
mentioned herein may be the trademarks of their respective owners. © 2004 Siemens Building Technologies, Inc.
Siemens Building Technologies, Inc.
1000 Deerfield Parkway
Your feedback is important to us. If you have
comments about this document, please send
Dimensions,
Continued
Figure 15. Actuator Mounting Plate 331-623.
Dimensions in Inches (Millimeters).
Figure 16. No. 6 Actuator with the
RL 147 Positioning Relay Mounting.
Dimensions in Inches (Millimeters).
Buffalo Grove, IL 60089-4513
U.S.A.
them to technical.editor@siemens.com Page 12
Document No. 155-029P25
Country or Origin: US
Page 1 of 12 - Siemens Siemens-331-2856-332-2856-Ap-331-3-Users-Manual- Powers Control - No. 6 Pneumatic Damper Actuator  Siemens-331-2856-332-2856-ap-331-3-users-manual
Page 2 of 12 - Siemens Siemens-331-2856-332-2856-Ap-331-3-Users-Manual- Powers Control - No. 6 Pneumatic Damper Actuator  Siemens-331-2856-332-2856-ap-331-3-users-manual
Page 3 of 12 - Siemens Siemens-331-2856-332-2856-Ap-331-3-Users-Manual- Powers Control - No. 6 Pneumatic Damper Actuator  Siemens-331-2856-332-2856-ap-331-3-users-manual
Page 4 of 12 - Siemens Siemens-331-2856-332-2856-Ap-331-3-Users-Manual- Powers Control - No. 6 Pneumatic Damper Actuator  Siemens-331-2856-332-2856-ap-331-3-users-manual
Page 5 of 12 - Siemens Siemens-331-2856-332-2856-Ap-331-3-Users-Manual- Powers Control - No. 6 Pneumatic Damper Actuator  Siemens-331-2856-332-2856-ap-331-3-users-manual
Page 6 of 12 - Siemens Siemens-331-2856-332-2856-Ap-331-3-Users-Manual- Powers Control - No. 6 Pneumatic Damper Actuator  Siemens-331-2856-332-2856-ap-331-3-users-manual
Page 7 of 12 - Siemens Siemens-331-2856-332-2856-Ap-331-3-Users-Manual- Powers Control - No. 6 Pneumatic Damper Actuator  Siemens-331-2856-332-2856-ap-331-3-users-manual
Page 8 of 12 - Siemens Siemens-331-2856-332-2856-Ap-331-3-Users-Manual- Powers Control - No. 6 Pneumatic Damper Actuator  Siemens-331-2856-332-2856-ap-331-3-users-manual
Page 9 of 12 - Siemens Siemens-331-2856-332-2856-Ap-331-3-Users-Manual- Powers Control - No. 6 Pneumatic Damper Actuator  Siemens-331-2856-332-2856-ap-331-3-users-manual
Page 10 of 12 - Siemens Siemens-331-2856-332-2856-Ap-331-3-Users-Manual- Powers Control - No. 6 Pneumatic Damper Actuator  Siemens-331-2856-332-2856-ap-331-3-users-manual
Page 11 of 12 - Siemens Siemens-331-2856-332-2856-Ap-331-3-Users-Manual- Powers Control - No. 6 Pneumatic Damper Actuator  Siemens-331-2856-332-2856-ap-331-3-users-manual
Page 12 of 12 - Siemens Siemens-331-2856-332-2856-Ap-331-3-Users-Manual- Powers Control - No. 6 Pneumatic Damper Actuator  Siemens-331-2856-332-2856-ap-331-3-users-manual

Navigation menu