Siemens Sed2 Vfd Electronic Bypass Option 125 3208 Users Manual
125-3208 to the manual b9a68406-89a6-4729-9695-388644f4b67a
2015-02-05
: Siemens Siemens-Sed2-Vfd-Electronic-Bypass-Option-125-3208-Users-Manual-409938 siemens-sed2-vfd-electronic-bypass-option-125-3208-users-manual-409938 siemens pdf
Open the PDF directly: View PDF .
Page Count: 64
Download | |
Open PDF In Browser | View PDF |
SED2 VFD Electronic Bypass Options Operating Instructions Item Number 125-3208, Rev. FA SED2 VFD Electronic Bypass Option Operating Instructions NOTICE The information contained within this document is subject to change without notice and should not be construed as a commitment by Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. assumes no responsibility for any errors that may appear in this document. All software described in this document is furnished under a license and may be used or copied only in accordance with the terms of such license. WARNING The Siemens Building Technologies SED2 Variable Frequency Drives are shipped without EMC line filters. (The EMC filter is most commonly used in Europe.) Where local codes or customer/installation requirements dictate, separately orderable Class A line filters are available. More stringent Class B line filters are also available for most models. Installation of these filters satisfies the requirements for the EU's EMC directive. SERVICE STATEMENT Control devices are combined to make a system. Each control device is mechanical in nature and all mechanical components must be regularly serviced to optimize their operation. All Siemens Building Technologies, Inc. branch offices and authorized distributors offer Technical Support Programs that will ensure your continuous, trouble-free system performance. For further information, contact your nearest Siemens Building Technologies, Inc. representative. CREDITS Product or company names mentioned herein may be the trademarks of their respective owners. Copyright © 2007 by Siemens Building Technologies, Inc. TO THE READER Your feedback is important to us. If you have comments about this manual, please submit them to SBT_technical.editor@siemens.com Country of Origin: US Table of Contents Table of Contents How to Use this Manual................................................................................................ 1 Manual Organization.................................................................................................. 1 Manual Notations ....................................................................................................... 1 Where To Send Comments ....................................................................................... 2 Reference Documents ............................................................................................... 2 Safety Instructions........................................................................................................ 3 Electronic Bypass Option Overview ........................................................................... 4 General Description ................................................................................................... 4 Controller Board......................................................................................................... 5 Contactors.................................................................................................................. 6 Keypad Functions ...................................................................................................... 6 Installation Instructions ............................................................................................... 9 Environmental Conditions.......................................................................................... 9 Mechanical Installation .............................................................................................. 9 Inspection ................................................................................................................ 9 Dimensions and Weights ........................................................................................ 9 Mounting.................................................................................................................. 10 Electrical Installation .................................................................................................. 12 Startup Procedures....................................................................................................... 19 Safety Precautions..................................................................................................... 19 Installation Inspection ................................................................................................ 19 Power-On................................................................................................................... 19 Quick Commissioning ................................................................................................ 21 Additional Parameter Settings ................................................................................... 31 Flying Start .............................................................................................................. Automatic Restart.................................................................................................... Vdc Controller.......................................................................................................... Pulse Frequency ..................................................................................................... Motor Data Identification ......................................................................................... Reset to Factory Defaults........................................................................................ 31 33 36 37 38 40 Required SED2 Parameter Settings ............................................................................ 41 Siemens Building Technologies, Inc. i SED2 VFD Electronic Bypass Option Operating Instructions Application Feature Setup ........................................................................................... 42 Overview .................................................................................................................... 42 Auto Bypass without Interlock.................................................................................... 42 Description .............................................................................................................. Settings ................................................................................................................... Example SED2 Settings.......................................................................................... Interlock ..................................................................................................................... 42 43 43 44 Description .............................................................................................................. Settings ................................................................................................................... Wiring Example for Interlock ................................................................................... Essential Services...................................................................................................... 44 44 46 46 Description .............................................................................................................. Settings ................................................................................................................... Wiring Example for Essential Services ................................................................... Interlock and Auto Bypass on VFD Fault................................................................... 46 47 47 48 Description .............................................................................................................. 48 Settings ................................................................................................................... 48 Wiring Example for Interlock and Auto Bypass on VFD Fault ................................ 48 Technical Specifications .............................................................................................. 49 Troubleshooting............................................................................................................ 51 Power-on Initialization Failure (Unit Fault Condition) ............................................... 51 Override Jumper ........................................................................................................ 52 Fuses ......................................................................................................................... 52 ii Siemens Building Technologies, Inc. How to Use this Manual How to Use this Manual Manual Organization This manual contains the following sections: • How to Use this Manual, describes the organization of this manual and the symbols used throughout this manual. • Safety Instructions, provides general guidelines for your safety and to prevent equipment damage. • Electronic Bypass Option Overview, describes the Electronic Bypass Option Controller board, inputs, outputs, contactors, and keypad. • Installation Instructions, provides mounting information and details on electrical connections. • Startup Procedures, provides step-by-step procedures to start up the Electronic Bypass Option. • Required SED2 Parameter Settings, lists SED2 parameter settings necessary for operation of the Electronic Bypass Option. • Application Feature Setup, describes application features and provides the necessary parameter settings. • Technical Specifications, lists Electronic Bypass Option and SED2 VFD specifications. • Troubleshooting, provides guidelines for troubleshooting the Electronic Bypass Option. Manual Notations Notation Symbol Meaning WARNING: Indicates that personal injury/loss of life may occur if you do not perform a procedure as specified. CAUTION: Indicates that equipment damage, or loss of data may occur if you do not perform a procedure as specified. NOTES: (no symbol) Siemens Building Technologies, Inc. Provides other important information or helpful hints. 1 SED2 VFD Electronic Bypass Option Operating Instructions Where To Send Comments Your feedback is important to us. If you have comments about this manual, please submit them to technical.editor@sbt.siemens.com. Reference Documents The following SED2 documentation is available from your local Siemens Building Technologies, Inc. representative: 2 • SED2 VFD Startup Operation, and Maintenance Manual (125-3201), provides operating instructions and procedures for the SED2. • SED2 VFD Parameter Reference Guide (125-3214), provides descriptions of SED2 parameters. • SED2 VFD Submittal Sheet (154-042), provides a synopsis of the SED2 product line, accessories, and technical data. • SED2 VFD Electronic Bypass Options Submittal Sheet (154-051), provides a comprehensive overview of the SED2 Electronic Bypass option. Siemens Building Technologies, Inc. Safety Instructions Safety Instructions The following guidelines are provided for your safety, to prevent damage, and to extend the service life of the SED2 product and any connected equipment. Read this information carefully. Specific Warnings, Cautions, and Notes are provided in the relevant sections of this manual. WARNING: • The SED2 uses hazardous voltages and controls potentially dangerous rotating mechanical parts. Non-compliance with warnings or failure to follow the instructions contained in this manual can result in loss of life, severe personal injury, or serious damage to property/equipment. • Only authorized personnel should work on this equipment, and only after becoming familiar with all local regulations and ordinances; safety notices; and installation, operation, and maintenance procedures in this manual. Successful and safe operation of this equipment depends upon its proper handling, installation, operation, and maintenance. • Before carrying out any installation and commissioning procedures, you must read all safety instructions and warnings, including all warning labels attached to the equipment. Make sure that the warning labels are kept in a legible condition and ensure missing or damaged labels are replaced. • Observe the regulations of Safety Code VBG 4.0 (in particular, “Permissible Deviations when Working with Live Parts”) whenever measuring or testing is performed on live equipment. Also, use suitable electronic tools. • Only use this equipment for the purpose specified by the manufacturer. Unauthorized modifications and the use of spare parts and accessories that are not sold or recommended by the manufacturer of the equipment can cause fires, electric shocks, and injuries. • Prevent the general public from accessing or approaching this equipment. NOTE: Keep these Operating Instructions near the equipment and available to all users. Siemens Building Technologies, Inc. 3 SED2 VFD Electronic Bypass Option Operating Instructions Electronic Bypass Option Overview General Description BYPASS CONTACTOR 4 • Keypad • Step-down power transformer • Contactors: − Bypass − Output − Input (optional) • Overload (current) relay • Reactor (optional) • Disconnect switch (or optional circuit breaker) • Fuses (optional) • Cable harnesses CONTROLLER BOARD MOTOR OUTPUT CONTACTOR SED2 VFD KEYPAD (DOOR MOUNTED) INPUT CONTACTOR STEP-DOWN POWER TRANSFORMER REACTOR (OPTIONAL) OUTPUT CONTACTOR BYPASS CONTACTOR VFD0094R1 Controller board INPUT CONTACTOR Figure 1. Functional Block Diagram of Typical Electronic Bypass Option. The SED2 Electronic Bypass (E-Bypass) Option consists of a SED2 VFD, and a bypass enclosure with electronic controls (Figure 2). The electronic controls include: • OVERLOAD RELAY VFD VFD0093R1 During normal operation in a typical application, the input and output contactors close and the SED2 operates the motor (Figure 1). The bypass contactor provides the ability to operate the motor on utility power and eliminate the SED2 from the motor control circuit. The SED2 Electronic Bypass Option also allows you to select features that enhance the control of the contactors and the outputs that report operation. OVERLOAD (CURRENT) RELAY DISCONNECT SWITCH (OR OPTIONAL CIRCUIT BREAKER SHOWN) Figure 2. Typical SED2 E-Bypass Components. Siemens Building Technologies, Inc. Electronic Bypass Option Overview Controller Board The Controller board is the foundation of the SED2 Electronic Bypass Option. It controls communications to and from the SED2, keypad, isolated digital inputs, relay/digital outputs, and contactors (Figure 3). SED2 INTERFACE Supports two SED2 non-isolated, digital relay outputs and three SED2 digital inputs. The maximum current draw for a relay output is 2 mA and the voltage between the digital output source and return lines is 24V. The Controller board provides unregulated, non-isolated 24V to power the SED2 digital inputs. J4 CONTROLLER BOARD BASIC SANITY TEST INDICATOR Provides indication of initialization and normal operation. FACTORY USE ONLY Connector J8 is for factory use only. DIGITAL INPUTS Supports six isolated digital inputs for customer use. The inputs require a contact closure capable of providing a low impedance path at currents less than 20 mA. J3 MCU ON OFF J8 SW1 KEYPAD INTERFACE Supports inputs and outputs from the Electronic Bypass Option keypad. The keypad provides user interface indicators and push buttons. J2 J1 TRANSFORMER DIGITAL RELAY OUTPUTS Supports six digital relay outputs for customer use. Each relay has a maximum rating of 2A at 120 Vac. OVERRIDE JUMPER 5 ON 5 J7 J5 CONTACTOR POWER CONTROLS 2 Automatic Bypass selector switch; requires SED2 programming. Essential Services selector switch. SW1 ON Not used, factory test selector switch #2; leave this switch OFF. Not used, factory test selector switch #1; leave this switch OFF. Interlock selector switch; requires SED2 programming. 1 3 4 OPTIONS 3 4 2 1 VFD0095R1 J6 OFF DIP SWITCHES The Controller board DIP switches enable/disable the Electronic Bypass Option features. F1 When the switch is ON the option is enabled; when the switch is OFF the option is disabled. Figure 3. Controller Board Inputs and Outputs. Siemens Building Technologies, Inc. 5 SED2 VFD Electronic Bypass Option Operating Instructions Contactors The Controller board provides two or three relay contact circuits controlled by the Electronic Bypass Option: bypass, input, and output contactors. Each circuit includes a NO relay. Controller board connector J7 enables circuit connections. The relay circuits route power to the SED2 and the motor via the contactors. Controlling the contactors through the relay circuits is the main function of the Controller board. Bypass Contactor – The bypass relay on the Controller board controls the bypass contactor. The output and bypass relays are interconnected to 120 Vac Hot. This enables a safety circuit that prevents the bypass and output contactors from simultaneously being energized. Output Contactor – The output relay on the Controller board controls the output contactor. Input Contactor – The input relay on the Controller board controls the optional input contactor. Keypad Functions Input Contactor VFD Enable Bypass VFD Hand Start Input On/Off Bypass Contactor Overload Relay Bypass Input Contactor VFD Remote Start Enable Output Contactor Motor VFD Fault STOP RESET Safety Fault Essential Services INTERLOCK START LOGIC Remote Start Output Contactor Overload Fault Enable Commanded Proofed 2-CONTACTOR KEYPAD VFD0097R1 VFD0096R1 Auto Bypass Enabled Bypass Contactor Overload Relay Motor STOP RESET Hand Start Auto Bypass Enabled VFD Fault Safety Fault Essential Services INTERLOCK START LOGIC Overload Fault Enable Commanded Proofed 3-CONTACTOR KEYPAD Figure 4. E-Bypass Keypad Indicators and Pushbuttons. The keypad provides user interface indicators and pushbuttons. The following table describes specific pushbutton and indicator functions: 6 Siemens Building Technologies, Inc. Electronic Bypass Option Overview VFD0102R1 VFD0101R1 VFD0100R1 VFD0099R1 VFD0098R1 Pushbutton/Indicator Input On/Off The Input On/Off pushbutton is supplied with the optional drive input contactor. In VFD mode, this switch does nothing. In bypass mode, this switch closes/opens the input contactor, switching the SED2 power on/off. Enable Enables SED2 operation by closing the input and output contactors. Hand Start Manually enables bypass mode operation by ensuring that the output contactor is open and then closing the bypass contactor. Remote Start Activates the bypass mode and operates the bypass contactor according to the status of the Remote Start input on the Controller board. STOP RESET Opens the output and bypass contactors, disconnecting the motor. VFD0103R1 VFD Fault Safety Fault VFD0104R1 Safety Fault Overload Fault VFD Fault VFD0105R1 When a VFD Fault is indicated, the VFD Fault indicator lights and the VFD Fault Relay output on the Controller Board is triggered. Overload Fault VFD Fault Safety Fault The Safety Fault indicator lights when either of the Remote Safety inputs on the Controller board opens. The motor is prohibited from operating in either the VFD or bypass modes while either of these contacts is open. EXCEPTION: Essential Services ignores a Safety Fault. NOTE: If not using the Remote Safety feature, hard wire the two Remote Safety inputs. If the Electronic Bypass Option current overload relay trips, the Overload Fault indicator lights and the motor will not run in bypass mode. Overload Fault Auto Bypass Enabled VFD0106R1 Description Essential Services When the Auto Bypass DIP switch is enabled, the Auto Bypass Enabled indicator is on steady. Bypass operation is automatically initiated by the SED2. When Auto Bypass is active, the Auto Bypass Enabled indicator flashes. When the Essential Services DIP switch is enabled, the Essential Services indicator is on steady. VFD0107R1 Auto Bypass Enabled Essential Services When the Essential Services input is open, normal operation is indicated as the output contactor remains closed to keep the motor running and the Essential Services indicator is on steady. When the Essential Services input is closed, the bypass contactor closes and the Essential Services indicator flashes. Nothing can interrupt the Essential Services mode except for the Essential Services input opening. Siemens Building Technologies, Inc. 7 SED2 VFD Electronic Bypass Option Operating Instructions Pushbutton/Indicator Description VFD0108R1 When the Interlock DIP switch is enabled, the Interlock Start Logic Enable indicator is on steady. Any call to start the motor in either VFD or bypass modes will not start the motor; instead it will close the Programmable Output relay on the Controller board. INTERLOCK START LOGIC Enable Commanded Proofed The Programmable Output can be used to actuate another device. When this occurs, the Interlock Start Logic Commanded indicator also lights, and the Interlock Start Logic Proofed indicator flashes. A contact closure from this other device is wired to the Interlock Start on the Controller board which then starts the motor and turns the Interlock Start Logic Proofed indicator on steady. This feature is also called damper end switch relay logic. 8 Siemens Building Technologies, Inc. Installation Instructions Installation Instructions Environmental Conditions Install the Electronic Bypass Option in a heated, indoor controlled environment that is free of moisture and conductive contaminants such as condensation and dust. The air entering the unit for ventilation/cooling must be clean and free from corrosive gases. The ambient temperature must be between 14°F and 104°F (-10°C to 40°C) and the relative humidity must be 0% to 95% noncondensing. Do not mount unit in direct sunlight. Mechanical Installation Inspection 1. As you unpack the Electronic Bypass Option, check for shipping damage. In the event of damage, contact the transport company. 2. Locate the Electronic Bypass Option nameplate and confirm that the unit is configured to the installation requirements. 3. Verify the delivery is complete. If not, contact the supplier. Dimensions and Weights Figure 5 shows overall and mounting dimensions for the Electronic Bypass Option. Figures 6 through 8 show conduit locations. Approximate weights are as follows. NOTE: Bypass Frame Size Weight lb (kg) A B C D E F 45 (20) 55 (25) 75 (34) 150 (68) 180 (82) 470 (213) Exact weight will be affected by actual horsepower/voltage and selected power options. Siemens Building Technologies, Inc. 9 SED2 VFD Electronic Bypass Option Operating Instructions Mounting 1. To ensure safe installation, verify that the surface of the mounting location is level. 2. Mount the Electronic Bypass Option vertically with the SED2 operator panel, Electronic Bypass Option keypad, and disconnect accessible. Depth With Handle 10.4 (26) = Protective Shield Depth With Handle 9.6 (24) Depth With Handle 9.6 (24) 13.2 (34) 11.5 (29) 20.8 (53) 1 (2.5) 2 (5) 2.9 (7.4) 4 (10) 1.5 (3.8) 53.5 (136) 48 (122) 34 (86) 10.5 TYP (27) 12.4 (31) 10.6 (27) 1.5 (3.8) Frame Size A and B Depth With Handle 12.2 (31) 20.8 (53) 11.5 TYP (29) 11 TYP (28) 19.9 (51) 2 (5) Frame Size C 2.9 (7.4) 3 (7.6) 3.4 (8.6) Frame Size D Depth 17.4 (44) 45.5 (116) 57.5 (146) 58.5 (149) VFD0127R2 10 TYP (25) NOTE: 19.9 (51) Frame Size E 5.5 (14) Frame Size F It is recommended to leave 6 inches (15 cm) around the top and sides of the unit. Figure 5. E-Bypass Dimensions in Inches (Centimeters). 10 Siemens Building Technologies, Inc. Installation Instructions 1/2 (1.3) AND 3/4 (1.9) CONDUIT KNOCKOUTS 1/2 (1.3) AND 3/4 (1.9) CONDUIT KNOCKOUTS 3/4 (1.9) AND 1 (2.5) CONDUIT KNOCKOUTS 1-1/4 (3.2) AND 1-1/2 (3.8) CONDUIT KNOCKOUTS (3) 8 (20.3) 6 (15.2) 4 (10.2) 2-3/4 (6.9) VFD0202R1 3-5/8 (9.2) VFD0201R1 2-1/8 (5.3) 9-1/2 (24.1) 7-3/8 (18.7) 13-5/8 11-7/8 (34.6) (30.1) 16 (40.7) Figure 7. Frame Sizes D and E Conduit Locations. Viewed from Bottom; Dimensions in Inches (Centimeters). Figure 6. Frame Sizes A through C Conduit Locations. Viewed from Bottom; Dimensions in Inches (Centimeters). 15-3/8 (39.1) 8-1/2 (21.7) 20-3/8 (51.7) VFD0203R1 4-1/4 (10.8) 3/4 (1.9) AND 1 (2.5) CONDUIT KNOCKOUTS (3) 3 (7.6) CONDUIT KNOCKOUTS (2) Figure 8. Frame Size F Conduit Locations. Viewed from Top; Dimensions in Inches (Centimeters). Siemens Building Technologies, Inc. 11 SED2 VFD Electronic Bypass Option Operating Instructions Electrical Installation See Figure 9 for all Electronic Bypass Option wiring. 1. Route shielded twisted pair (recommended wire type) cable, 24 gauge minimum control wiring in conduit through knockout and into housing (Figures 10 through 12). Connect control wiring per job-specific drawings. NOTES: • Terminate shield at control device. • Control wiring is 12 to 26 AWG and tightening torque is 5 lb-in. 2. If applicable, route communications wiring (P1) in conduit through knockout and into housing (Figures 10 through 12). Continue to route communications wiring to SED2 and terminate per SED2 VFD Startup, Operation, and Maintenance Manual (125-3201). 3. Route motor wiring in conduit through knockout and into housing (Figures 10 through 12). Connect motor wiring to motor overload and ground lug. See Tables 1 through 4 for wire sizes and tightening torques. 4. Route input power wiring in conduit through knockout and into housing (Figures 10 through 12). Connect input power wiring to disconnect switch and ground lug or to circuit breaker and ground lug. See Tables 1 through 4 for wire sizes and tightening torques. 12 Siemens Building Technologies, Inc. Installation Instructions OPTIONAL SUPPLEMENTARY POWER FUSES - MAIN SHORT CIRCUIT PROTECTION BY OTHERS (SEE NOTE 1) DISC1 FU1 L1 1L1 (T1) (L1) POWER SUPPLY L2 3 PHASE (T2) 60 Hz L3 (T3) GND M1 2L1 1L2 (L2) 2L2 1L3 (L3) 2L3 OPTIONAL OPTIONAL DRIVE INPUT INPUT LINE CONTACTOR REACTOR M3 3L1 R (2) (1) A1 A2 3L2 S (4) (3) B1 B2 GND GND LUG 3L3 (6) (5) T C1 OPTIONAL OUTPUT LOAD REACTOR VFD L1 U L2 V L3 W C2 U1 (5) (6) (3) (4) (1) (2) U A1 A2 V1 M2 OL1 (1) (2) 1T1 (T1) (3) (4) 1T2 (T2) (5) (6) 1T3 (T3) V B1 B2 C1 C2 W1 W M AC MOTOR (CUSTOMER SUPPLIED) GND VFD0160R1 1L1 GND LUG 1L2 TO STEP-DOWN CONTROL TRANSFORMER NOTES: 1. Branch circuit protection to be provided by installer, per UL508A, if not provided with drive. 2. For bypass operation, modify these drive parameters: P0702[0] and P0702[1] = 3, P0748 = Digital Out 1 Reverse ( ). 3. Control and communication wiring should be 300V UL minimum. 4. Communication wiring should be run with maximum separation possible from all other wiring. 5. Essential service mode operates the motor full speed (bypass) with no protection for the motor or system. 6. Ensure that automatic bypass will not damage the system before activating. 7. See Table 8 for proper fuse and wire sizes. 8. See Siemens Publication No. 125-3201 for SED2 input/output control signal wiring details. Figure 9. E-Bypass Power Circuit. Siemens Building Technologies, Inc. 13 SED2 VFD Electronic Bypass Option Operating Instructions SED2 VFD SED2 VFD CONTROLLER BOARD INPUT CONTACTOR (OPTIONAL) INPUT CONTACTOR (OPTIONAL) J2 CONTROL WIRING (DIGITAL INPUTS/ OUTPUTS) VIA 2 KNOCKOUTS COMMUNICATIONS WIRING (P1) VIA 1 KNOCKOUT CONTROLLER BOARD COMMUNICATIONS WIRING (P1) VIA 1 KNOCKOUT J2 CONTROL WIRING (DIGITAL INPUTS/ OUTPUTS) VIA 2 KNOCKOUTS J1 REACTOR (OPTIONAL) REACTOR (OPTIONAL) J1 TRANSFORMER TRANSFORMER POWER FUSES (OPTIONAL) OUTPUT CONTACTOR GROUND LUGS BYPASS CONTACTOR GROUND LUGS BYPASS CONTACTOR DISCONNECT SWITCH (OR OPTIONAL CIRCUIT BREAKER) T1 T2 T3 DISCONNECT SWITCH (OR OPTIONAL CIRCUIT BREAKER) L1 L2 L3 MOTOR OVERLOAD T1T2T3 MOTOR OVERLOAD MOTOR WIRING VIA KNOCKOUT INPUT POWER WIRING VIA KNOCKOUT VFD0112R1 VFD0111R2 POWER FUSES (OPTIONAL) OUTPUT CONTACTOR Figure 10. Routing of Power and Control Wiring for Frame Sizes A and B. MOTOR WIRING VIA KNOCKOUT DISCONNECT SWITCH (OR OPTIONAL CIRCUIT BREAKER) L1 L2 L3 MOTOR WIRING VIA KNOCKOUT INPUT POWER WIRING VIA KNOCKOUT Figure 11. Routing of Power and Control Wiring for Frame Sizes C, D, and E. GROUND LUGS (2) INPUT POWER WIRING VIA KNOCKOUT T3T2T1 SED2 VFD L3 L2 L1 MOTOR OVERLOAD BYPASS CONTACTOR OUTPUT CONTACTOR J2 J1 CONTROLLER BOARD VFD0113R1 TRANSFORMER INPUT CONTACTOR (OPTIONAL) POWER FUSES (OPTIONAL) COMMUNICATIONS WIRING (P1) VIA 1 KNOCKOUT REACTOR (OPTIONAL) Figure 12. Routing of Power and Control Wiring for Frame Size F. 14 Siemens Building Technologies, Inc. Installation Instructions Table 1. Wire Sizes and Tightening Torques for E-Bypass with 208V Drive. Circuit Breaker Part Number Bypass Frame HP Size kW Amps Wire Size * Disconnect Switch Torque, Wire lb-in Size * (Nm) Overload Torque, lb-in (Nm) Wire Size * Ground Lug Max Torque, Torque, Range, Backup Wire lb-in lb-in Amps Fuse, Size * (Nm) (Nm) Amps VBE10.5---- A 0.5 0.37 2.3 14-10 Cu 32 (3.6) 18-10 13 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 1.8 - 2.5 10 14-2 35 (4) VBE10.7---- A 0.7 0.55 3.0 14-10 Cu 32 (3.6) 18-10 13 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 2.2 - 3.2 12 14-2 35 (4) VBE11.0---- A 1.0 0.75 3.9 14-10 Cu 32 (3.6) 18-10 13 - 17 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 2.8 - 4 16 14-2 35 (4) VBE11.5---- B 1.5 1.1 5.5 14-10 Cu 32 (3.6) 18-10 13 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 4.5 - 6.3 25 14-2 35 (4) VBE12.0---- B 2.0 1.5 7.4 14-10 Cu 32 (3.6) 18-10 13 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 5.5 - 8.0 30 14-2 35 (4) VBE13.0---- B 3.0 2.2 10.4 14-10 Cu 32 (3.6) 18-10 13 - 17 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 7 - 10 40 14-2 35 (4) VBE15.0---- C 5.0 4.0 16.7 14-10 Cu 32 (3.6) 14-8 17 - 22 (1.9 - 2.5) 14-10 18 - 22 (2 - 25) 14 - 20 80 14-2 35 (4) VBE17.5---- C 7.5 5.5 22.0 14-10 Cu 20 - 60 (2.2 - 6.8) 14-8 17 - 22 (1.9 - 2.5) 14-10 18 - 22 (2 - 25) 20 - 25 100 14-2 35 (4) VBE110.---- C 10 7.5 28 10-1/0 20 - 60 (2.2 - 6.8) Cu 14-8 17 - 22 (1.9 - 2.5) 18-3 27 - 40 (3.1 - 4.5) 22 - 32 125 14-2 35 (4) VBE115.---- D 15 11.0 42 10-1/0 20 - 60 (2.2 - 6.8) Cu 14-6 22 - 27 (2.5 - 3.1) 18-3 27 - 40 (3.1 - 4.5) 40 - 50 200 14-2 35 (4) VBE120.---- D 20 15.0 54 10-1/0 20 - 60 (2.2 - 6.8) Cu 12-1 22 - 27 (2.5 - 3.1) 10-1/0 36 - 53 (4.1 - 6) 45 - 63 250 14-2 35 (4) VBE125.---- D 25 18.5 68 3-3/0-3 Cu 80 (9) 12-1 22 - 27 (2.5 - 3.1) 10-1/0 36 - 53 (4.1 - 6) 57 - 75 300 14-2 35 (4) VBE130.---- E 30 22.0 80 3-3/0-3 Cu 80 (9) 12-1 22 - 27 (2.5 - 3.1) 10-1/0 36 - 53 (4.1 - 6) 70 - 90 350 14-2 35 (4) VBE140.---- F 40 30.0 104 6 - 350 kcmil 120 - 275 (14 - 31.1) Cu 12-1 22 - 27 (2.5 - 3.1) 6-3/0 124 - 210 50 - 200 (14 - 23.7) 800 14-2/0 50 (5.6) VBE150.---- F 50 37.0 130 6 - 350 120 - 275 kcmil 120 - 275 6 - 350 (13.5 - 31.1) (14 - 31.1) kcmil Cu 6-3/0 124 - 210 50 - 200 (14 - 23.7) 800 14-2/0 50 (5.6) VBE160.---- F 60 45.0 154 6 - 350 120 - 275 kcmil 120 - 275 6 - 350 (13.5 - 31.1) (14 - 31.1) kcmil Cu 6-3/0 124 - 210 50 - 200 (14 - 23.7) 800 14-2/0 50 (5.6) * Wire size is AWG unless noted otherwise. Use Copper (Cu) wire that is rated 167°F (75°C) minimum 600 Vac. Siemens Building Technologies, Inc. 15 SED2 VFD Electronic Bypass Option Operating Instructions Table 2. Wire Sizes and Tightening Torques for E-Bypass with 230V to 240V Drive. Circuit Breaker Part Number Bypass Frame HP Size kW Amps Wire Size * Disconnect Switch Torque, Wire lb-in Size * (Nm) Overload Torque, lb-in (Nm) Wire Size * Ground Lug Max Torque, Torque, Range, Backup Wire lb-in lb-in Amps Fuse, Size * (Nm) (Nm) Amps VBE20.5---- A 0.5 0.37 2.2 14-10 Cu 32 (3.6) 18-10 13 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 1.8 - 2.5 10 14-2 35 (4) VBE20.7---- A 0.7 0.55 3.0 14-10 Cu 32 (3.6) 18-10 13 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 2.2 - 3.2 12 14-2 35 (4) VBE21.0---- A 1.0 0.75 3.9 14-10 Cu 32 (3.6) 18-10 13 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 2.8 - 4 16 14-2 35 (4) VBE21.5---- B 1.5 1.1 5.5 14-10 Cu 32 (3.6) 18-10 13 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 4.5 - 6.3 25 14-2 35 (4) VBE22.0---- B 2.0 1.5 6.8 14-10 Cu 32 (3.6) 18-10 13 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 5.5 - 8.0 30 14-2 35 (4) VBE23.0---- B 3.0 2.2 9.6 14-10 Cu 32 (3.6) 18-10 13 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 7 - 10 40 14-2 35 (4) VBE25.0---- C 5.0 4.0 15.2 14-10 Cu 32 (3.6) 14-8 17 - 22 (1.9 - 2.5) 14-10 18 - 22 (2 - 25) 14 - 20 80 14-2 35 (4) VBE27.5---- C 7.5 5.5 22 14-10 Cu 20 - 60 (2.2 - 6.8) 14-8 17 - 22 (1.9 - 2.5) 14-10 18 - 22 (2 - 25) 20 - 25 100 14-2 35 (4) VBE210---- C 10 7.5 28 10-1/0 20 - 60 (2.2 - 6.8) Cu 14-8 17 - 22 (1.9 - 2.5) 18-3 27 - 40 (3.1 - 4.5) 22 - 32 125 14-2 35 (4) VBE215---- D 15 11.0 42 10-1/0 20 - 60 (2.2 - 6.8) Cu 14-6 22 - 27 (2.5 - 3.1) 18-3 27 - 40 (3.1 - 4.5) 40 - 50 200 14-2 35 (4) VBE220---- D 20 15.0 54 10-1/0 20 - 60 (2.2 - 6.8) Cu 12-1 22 - 27 (2.5 - 3.1) 10-1/0 36 - 53 (4.1 - 6) 45 - 63 250 14-2 35 (4) VBE225---- D 25 18.5 68 3-3/0-3 Cu 80 (9) 12-1 22 - 27 (2.5 - 3.1) 10-1/0 36 - 53 (4.1 - 6) 57 - 75 300 14-2 35 (4) VBE230---- E 30 22.0 80 3-3/0-3 Cu 80 (9) 12-1 22 - 27 (2.5 - 3.1) 10-1/0 36 - 53 (4.1 - 6) 70 - 90 350 14-2 35 (4) VBE240---- F 40 30.0 104 6 - 350 kcmil 120 - 275 (14 - 31.1) Cu 12-1 22 - 27 (2.5 - 3.1) 6-3/0 124 - 210 50 - 200 (14 - 23.7) 800 14-2/0 50 (5.6) VBE250---- F 50 37.0 130 6 - 350 kcmil 120 - 275 6 - 350 120 - 275 (14 - 31.1) kcmil (13.5 - 31.1) Cu 6-3/0 124 - 210 50 - 200 (14 - 23.7) 800 14-2/0 50 (5.6) VBE260---- F 60 45.0 154 6 - 350 kcmil 120 - 275 6 - 350 120 - 275 (14 - 31.1) kcmil (13.5 - 31.1) Cu 6-3/0 124 - 210 50 - 200 (14 - 23.7) 800 14-2/0 50 (5.6) * Wire size is AWG unless noted otherwise. Use Copper (Cu) wire that is rated 167°F (75°C) minimum 600 Vac. 16 Siemens Building Technologies, Inc. Installation Instructions Table 3. Wire Sizes and Tightening Torques for E-Bypass with 380V to 480V Drive. Circuit Breaker Part Number Bypass Frame HP Size kW Amps Wire Size * Disconnect Switch Torque, Wire lb-in Size * (Nm) Overload Torque, lb-in (Nm) Wire Size * Torque, lb-in (Nm) Range, Amps VBE30.5---- A 0.5 0.37 1.1 14-10 Cu 32 (3.6) 18-10 13 - 17 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) .7 - 1.0 VBE30.7---- A 0.7 0.55 1.6 14-10 Cu 32 (3.6) 18-10 13 - 17 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 1.1 - 1.6 VBE31.0---- A 1.0 0.75 2.1 14-10 Cu 32 (3.6) 18-10 13 - 17 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 1.4 - 2.0 VBE31.5---- A 1.5 1.1 3.0 14-10 Cu 32 (3.6) 18-10 13 - 17 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 2.2 - 3.2 VBE32.0---- A 2.0 1.5 3.4 14-10 Cu 32 (3.6) 18-10 13 - 17 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 2.8 - 4 VBE33.0---- B 3.0 2.2 4.8 14-10 Cu 32 (3.6) 18-10 13 - 17 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 3.5 - 5 VBE35.0---- B 5.0 4.0 7.6 14-10 Cu 32 (3.6) 18-10 13 - 17 (1.5 - 1.7) 18-14 7 - 10.3 (.8 - 1.2) 7 - 10 VBE37.5---- C 7.5 5.5 11 14-10 Cu 32 (3.6) 18-10 13 - 17 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 9 - 12 VBE310---- C 10 7.5 14 14-10 Cu 32 (3.6) 18-10 13 to17 (1.5 - 1.7) 14-10 18 - 22 (2 - 2.5) 11 - 16 VBE315---- C 15 11.0 21 14-10 Cu 20 - 60 (2.2 - 6.8) 14-8 17 - 22 (1.9 - 2.5) 14-10 18 - 22 (2 - 2.5) 17 - 22 VBE320---- C 20 15.0 27 10-1/0 20 - 60 Cu (2.2 - 6.8) 14-8 17 - 22 (1.9 - 2.5) 18-3 27 - 40 (3.1 - 4.5) 22 - 32 VBE325---- D 25 18.5 34 10-1/0 20 - 60 Cu (2.2 - 6.8) 14-6 22 - 27 (2.5 - 3.1) 18-3 27 - 40 (3.1 - 4.5) 28 - 40 VBE330---- D 30 22.0 40 10-1/0 20 - 60 Cu (2.2 - 6.8) 14-6 22 - 27 (2.5 - 3.1) 18-3 27 - 40 (3.1 - 4.5) 28 - 40 14-6 22 - 27 (2.5 - 3.1) 18-3 27 - 40 (3.1 - 4.5) 40 - 50 Ground Lug Max Torque, Backup Wire lb-in Fuse, Size* (Nm) Amps 4 14-2 35 (4) 6 14-2 35 (4) 8 14-2 35 (4) 12 14-2 35 (4) 16 14-2 35 (4) 20 14-2 35 (4) 40 14-2 35 (4) 45 14-2 35 (4) 60 14-2 35 (4) 80 14-2 35 (4) 125 14-2 35 (4) 150 14-2 35 (4) 150 14-2 35 (4) 200 14-2 35 (4) 300 14-2 35 (4) 350 14-2 35 (4) 400 14-2/0 50 (5.6) VBE340---- D 40 30.0 52 10-1/0 20 - 60 Cu (2.2 - 6.8) VBE350---- E 50 37.0 65 10-1/0 20 - 60 Cu (2.2 - 6.8) 12-1 22 - 27 (2.5 - 3.1) 10-1/0 36 - 53 (4.1 - 6) 57 - 75 VBE360---- E 60 45.0 77 3-3/0 Cu 80 (9) 12-1 22 - 27 (2.5 - 3.1) 10-1/0 36 - 53 (4.1 - 6) 70 - 90 VBE375---- F 75 55.0 96 3-3/0 Cu 80 (9) 12-1 22 - 27 (2.5 - 3.1) 10-1/0 36 - 53 (4.1 - 6) 80 - 100 VBE3100---- F 100 75.0 124 6 - 350 kcmil 120 - 275 6 - 350 120 - 275 (14 - 31.1) kcmil (13.5 - 31.1) Cu 6-3/0 124 - 210 50 - 200 (14 - 23.7) 800 14-2/0 50 (5.6) VBE3125---- F 125 90.0 156 6 - 350 kcmil 120 - 275 6 - 350 120 - 275 (14 - 31.1) kcmil (13.5 - 31.1) Cu 6-3/0 124 - 210 50 - 200 (14 - 23.7) 800 14-2/0 50 (5.6) VBE3125-HA F — 90.0 178 6 - 350 kcmil 120 - 275 6 - 350 120 - 275 (14 - 31.1) kcmil (13.5 - 31.1) Cu 6-3/0 124 - 210 50 - 200 (14 - 23.7) 800 14-2/0 50 (5.6) * Wire size is AWG unless noted otherwise. Use Copper (Cu) wire that is rated 167°F (75°C) minimum 600 Vac. Siemens Building Technologies, Inc. 17 SED2 VFD Electronic Bypass Option Operating Instructions Table 4. Wire Sizes and Tightening Torques for E-Bypass with 500V to 600V Drive. Circuit Breaker Part Number Bypass Frame Size HP VBE40.5---- C 0.5 0.37 .9 14-10 Cu 32 (3.6) VBE40.7---- C 0.7 0.55 1.3 14-10 Cu VBE41.0---- C 1.0 0.75 1.4 kW Amps Disconnect Switch Torque, Wire lb-in Size * (Nm) Overload Ground Lug Max Torque, Torque, Range, Backup Wire lb-in lb-in Amps Fuse, Size* (Nm) (Nm) Amps Torque, lb-in (Nm) Wire Size * 18-10 13 - 17 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) .7 - 1.0 4 14-2 35 (4) 32 (3.6) 18-10 13 - 17 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) .9 - 1.25 5 14-2 35 (4) 14-10 Cu 32 (3.6) 18-10 13 - 17 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 1.1 - 1.6 6 14-2 35 (4) 32 (3.6) 18-10 13 - 17 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 1.8 - 2.5 10 14-2 35 (4) Wire Size * VBE41.5---- C 1.5 1.1 2.1 14-10 Cu VBE42.0---- C 2.0 1.5 2.7 14-10 Cu 32 (3.6) 18-10 13 - 17 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 2.2 - 3.2 12 14-2 35 (4) VBE43.0---- C 3.0 2.2 3.9 14-10 Cu 32 (3.6) 18-10 13 - 17 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 2.8 - 4 16 14-2 35 (4) VBE45.0---- C 5.0 4.0 6.1 14-10 Cu 32 (3.6) 18-10 13 - 17 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 4.5 - 6.3 25 14-2 35 (4) VBE47.5---- C 7.5 5.5 9 14-10 Cu 32 (3.6) 18-10 13 - 17 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 7 - 10 40 14-2 35 (4) VBE410.---- C 10 7.5 11 14-10 Cu 32 (3.6) 18-10 13 - 17 (1.5 - 1.7) 18-14 7 - 10.3 (8 - 1.2) 9-2 45 14-2 35 (4) VBE415.---- C 15 11.0 17 14-10 Cu 32 (3.6) 14-8 17 - 22 (1.9 - 2.5) 14-10 18 - 22 (2 - 2.5) 14 - 20 80 14-2 35 (4) VBE420.---- C 20 15.0 22 10-1/0 20 - 60 (2.2 - 6.8) Cu 14-8 17 - 22 (1.9 - 2.5) 14-10 18 - 22 (2 - 2.5) 17 - 22 80 14-2 35 (4) VBE425.---- C 25 18.5 27 10-1/0 20 - 60 (2.2 - 6.8) Cu 14-6 22 - 27 (2.5 - 3.1) 18-3 27 - 40 (3.1 - 4.5) 22 - 32 125 14-2 35 (4) VBE430.---- D 30 22.0 32 10-1/0 20 - 60 (2.2 - 6.8) Cu 14-6 22 - 27 (2.5 - 3.1) 18-3 27 - 40 (3.1 - 4.5) 28 - 40 150 14-2 35 (4) VBE440.---- D 40 30.0 41 10-1/0 20 - 60 (2.2 - 6.8) Cu 14-6 22 - 27 (2.5 - 3.1) 18-3 27 - 40 (3.1 - 4.5) 36 - 45 175 14-2 35 (4) VBE450.---- E 50 37.0 52 10-1/0 20 - 60 (2.2 - 6.8) Cu 14-6 22 - 27 (2.5 - 3.1) 18-3 27 - 40 (3.1 - 4.5) 40 - 50 200 14-2 35 (4) VBE460.---- E 60 45.0 62 10-1/0 20 - 60 (2.2 - 6.8) Cu 12-1 22 - 27 (2.5 - 3.1) 10-1/0 36 - 53 (4.1 - 6) 45 - 63 250 14-2 35 (4) VBE475.---- F 75 55.0 77 3-3/0 Cu 80 (9) 12-1 22 - 27 (2.5 - 3.1) 10-1/0 36 - 53 (4.1 - 6) 70 - 90 350 14-2/0 50 (5.6) VBE4100---- F 100 75.0 99 3-3/0 Cu 80 (9) 12-1 22 - 27 (2.5 - 3.1) 10-1/0 36 - 53 (4.1 - 6) 80 - 100 400 14-2/0 50 (5.6) VBE4125---- F 125 90.0 125 120 - 275 (14 - 31.1) 10-1/0 124 - 210 50 - 200 (14 - 23.7) 800 14-2/0 50 (5.6) 6 - 350 kcmil 120 - 275 6 - 350 (14 - 31.1) kcmil Cu * Wire size is AWG unless noted otherwise. Use Copper (Cu) wire that is rated 167°F (75°C) minimum 600 Vac. 18 Siemens Building Technologies, Inc. Startup Procedures Startup Procedures Safety Precautions WARNING: When you connect input power to the Electronic Bypass Option, the motor terminals are energized even if the motor is not running. Do not make any connections with input power connected to the Electronic Bypass Option. Disconnect and lock out power to the drive before servicing it. Failure to disconnect input power may cause serious injury or death. CAUTION: After you disconnect input power, the DC bus capacitors must be allowed to discharge to a safe voltage. This will take about 5 minutes. Installation Inspection Inspect the mechanical and electrical installation for compliance with local electrical codes and regulations. After installation, verify that: • Electronic Bypass Option and motor are properly grounded. • Input power and motor wire sizes are correct and connections are secure. • Control wiring is correct, connections are secure, and wire shield is properly grounded. • Control wiring is not routed with power wiring. • Electronic Bypass Option has proper ventilation. • Internal Bypass connections are secure. Power-On 1. Turn on Electronic Bypass Option power. Power-on initialization performs a basic sanity test (approximately 7 seconds) to initialize the Controller board. Also, the Stop/Reset indicator will flash. A unit fault condition occurs if the Electronic Bypass Option did not pass the basic sanity test. See the Troubleshooting section in this manual for more details. Siemens Building Technologies, Inc. 19 SED2 VFD Electronic Bypass Option Operating Instructions After the basic sanity test, if the DIP switches have not changed and there is no operator intervention, the most recent bypass function is restored. If the DIP switches have changed, the Electronic Bypass Option activates the Stop/Reset function. 2. Press the Enable key on the Electronic Bypass Option keypad to place the unit in VFD mode. 3. Perform SED2 commissioning per the SED2 VFD Startup, Operation, and Maintenance Manual (125-3201). If using the Quick Commissioning mode, end this mode with P3900 = 3 to run a motor calculation without resetting the SED2 to factory defaults. 4. After basic SED2 operation is established and verified, turn SED2 power off via the Electronic Bypass Option input power device and verify that no dangerous voltages are present in the enclosure. 5. Select Electronic Bypass Option application features using the DIP switches. DIP Switch Settings for E-Bypass Features. Switch Position NOTE: Description 1 Essential Services selector switch. 2 Automatic Bypass selector switch; requires SED2 programming. 3 Interlock selector switch; requires SED2 programming. 4 Factory test #1 selector switch. Not used; leave this switch OFF. 5 Factory test #2 selector switch. Not used; leave this switch OFF. When the switch is ON, the feature is enabled; when the switch is OFF, the feature is disabled. For details on the Electronic Bypass Option features, see the Application Feature Setup section in this manual. 6. Re-apply power to the Electronic Bypass Option. On units with three contactors, energize the SED2 by pressing the Input pushbutton on the Electronic Bypass Option keypad. 7. Program the SED2 per the Application Feature Setup section in this manual. 8. Test all SED2 and bypass features. 20 Siemens Building Technologies, Inc. Startup Procedures 9. If motor rotation is incorrect in either VFD, bypass, or both modes, have the appropriate site personnel take corrective action as follows: − Wrong Rotation in Bypass, Right in VFD Mode – Swap two input leads on the main input device of the Electronic Bypass Option. − Wrong Rotation in VFD, Right in Bypass Mode – Swap two input leads on the main input device of the Electronic Bypass Option and swap two motor leads at the motor overload in the Electronic Bypass Option. − Wrong Rotation in both VFD and Bypass Modes – Swap two motor leads at the motor overload in the Electronic Bypass Option. Quick Commissioning Parameter P0010 is the Commissioning Parameter Filter. It allows you to select a group of parameters that can be used for quick commissioning, including motor data, and motor ramp-up and ramp-down settings. It is important to use parameter P0010 to commission the SED2, parameter P0003 to select the access level for using parameters, and parameter P0004 to filter the parameters according to their functionality. When Commissioning Parameter Filter P0010 = 1, it initiates the quick commissioning procedure. It is recommended that you use the quick commissioning procedure. However, experienced users may commission the equipment without the P0004 filter functions. At the end of the quick commissioning procedure, set parameter P3900 = 3. This setting performs the necessary motor calculations and sets all remaining parameters (those not included in P0010 = 1) to the factory default values. If 3900 is set to a value greater than 0, P0010 is automatically reset to 0. (If P0010 = 1, the SED2 cannot start.) The process of performing motor calculations and setting all parameters to factory default values is only possible via quick commissioning. Siemens Building Technologies, Inc. 21 SED2 VFD Electronic Bypass Option Operating Instructions Parameter P0003 Description User Access Level Allows you to access more parameters. 1 = Standard 2 = Extended Action 1. to access parameter Press r0000 and to enter the SED2 parameter mode. 2. Press to advance to parameter P0003. 3. to access the Press parameter values level. 4. Press to advance to 3 (expert level). 5. Press to confirm and save the P0003 = 3 setting. Setting/ Default Setting = 3 Default = 1 3 = Expert NOTE: Before starting quick commissioning, set P0003 = 3 to ensure all necessary parameters are available during quick commissioning. P0010 Quick Commissioning 1. 0 = Ready to Run to access parameter Press r0000 and to enter the SED2 parameter mode. Setting = 1 Default = 0 1 = Quick Commissioning 30 = Factory Setting 2. Repeatedly press to advance to parameter P0010. 3. to access the Press parameter values level. 4. Press 5. Press to confirm and save the P0010 = 1 setting. to advance to 1. NOTES: 1. P0010 must always be set back to 0 before operating the motor. 2. If P3900 is greater than 0 on completion of commissioning, P0010 is automatically set back to 0. 22 Siemens Building Technologies, Inc. Startup Procedures Parameter P0100 Description Operation for Europe/N. America 0 = 50 Hz, kW (Europe) factory default 1 = 60 Hz, hp (North America) 2 = 60 Hz, kW (North America) Action 1. Press to advance to parameter P0100. 2 Press to access the parameter values level. 3. Press 4. Press to confirm and save the P0100 = 1 setting. The setting of Motor Frequency and Unit of Measurement DIP switch 2 overrides P0100 settings 0 and 1. to advance to 1. Setting/ Default Setting = 1 Default = 0 or 1 (Default is determined by the setting of the motor frequency and unit of measurement DIP switches.) NOTES: 1. Stop the SED2 (that is, disable all pulses) before changing this parameter. 2. Changing P0100 resets all rated motor parameters as well as other parameters that depend on the rated motor parameters (such as P0340, Calculation of motor Parameters). P0304* Rated Motor Voltage 1. to advance to Press parameter P0304. Setting = Motor nameplate 2. to access the Press parameter values level. Default = Varies by model 3. to advance to Press nominal voltage. 4. Press to confirm and save the setting. 10V to 2000V. Rated motor voltage (V) from motor nameplate. * Motor related parameters. Siemens Building Technologies, Inc. 23 SED2 VFD Electronic Bypass Option Operating Instructions Parameter P0305* Description Action 1. Press to advance to parameter P0305. Setting = Motor nameplate 2. Press to access the parameter values level. Default = Varies by model 3. to advance to Press nominal current. 4. to confirm and save Press the setting. 1. Press to advance to parameter P0307. Rated motor power (kW or hp) from motor nameplate. 2. Press to access the parameter values level. If P0100 =1 (60 Hz, hp, North America), then motor power is in hp. 3. Press to advance to nominal power. 4. to confirm and save Press the setting. Rated Motor cosPhi (P308), or Rated Motor Efficiency (P0309) 1. to advance to Press parameter P0308 or P0309. Setting = Motor nameplate 0.000 to 1.00 (P0308) or 0.0 to 99.9 (P0309) 2 to access the Press parameter values level. P0308 Default = 0.00 3. Press to advance to nominal cosPhi or motor efficiency. P0309 Default = Varies by model (hp/voltage dependent) 4. Press to confirm and save the setting. Rated Motor Current 0A to 10,000A. Rated motor current (A) from motor nameplate. P0307* Rated Motor Power 0 kW or hp to 200 kW or hp. P0308*, or P0309 Setting/ Default Rated motor cosPhi or motor efficiency from motor nameplate. If P0100 = 2 and P0307 = kW, P0308 displays. If P0100 = 1 and P0307 = hp, P0309 displays. Setting = Motor nameplate Default = Varies by model (hp/voltage dependent) P0309 = 100% corresponds to super conducting. NOTE: This parameter is available when P0003 = 3 and P0010 = 1. * Motor related parameters. 24 Siemens Building Technologies, Inc. Startup Procedures Parameter P0310* Description Rated Motor Frequency Action Setting = Motor nameplate 60 Hz 1. Press to advance to parameter P0310. Rated motor frequency (Hz) from motor nameplate. 2. Press to access the parameter values level. Pole pair number is recalculated automatically if the parameter is changed. 3. Press to advance to nominal frequency (60 Hz). 4. to confirm and save Press the setting. 1. Press to advance to parameter P0311. Setting = Motor nameplate 2. Press to access the parameter values level. Default = Varies by model A setting of 0 causes an internal calculation of this value. 3 to advance to Press nominal motor speed. Vector control and V/f control with speed controller require this value. 4. Press to confirm and save the setting. 12 Hz to 650 Hz P0311* Setting/ Default Rated Motor Speed 0 to 40,000 1/min Rated motor speed (rpm) from motor nameplate. Default = 50 Hz/60 Hz Default is dependent on the setting of the motor frequency and unit of measurement DIP switches. Slip compensation in V/f control requires this value for correct operation. Pole pair number is recalculated automatically if the parameter is changed. * Motor related parameters. Siemens Building Technologies, Inc. 25 SED2 VFD Electronic Bypass Option Operating Instructions Parameter P0640 Description Motor Overload Factor Action 1. 10% to 400% Press to advance to parameter P0640. Setting/ Default Setting = As applicable Default = 110 Limited to the maximum SED2 output current rating, or to 400% of the rated current (P0305), whichever is lower. P0700(0)** 2. Press to access the parameter values level. 3. NOTE: This parameter is available when P0003 = 3 and P0010 = 1. Press to advance to desired value. 4. Press to confirm and save the setting. Selection of Command Source (Start Command) 1. to advance to Press parameter P0700. Selects the command source as follows: 2. Press to access the parameter indexes. 3. Press to advance to index [0], IN000, AUTO. 4. to confirm index Press selection. 5. Press 6. to confirm and save Press the setting. 0 = Factory default setting 1 = BOP (keypad) Setting = 2 Default = 2 2 = Terminal digital input 4 = USS on BOP link (AOP) 5 = USS on COM link 6 = CB (Communications board or module) on COM link (P1/N2) to advance to 2. NOTE: Changing this parameter resets (to default) all settings on the selected item. For example, changing from 1 to 2 resets all digital inputs to default settings. ** Parameters have two index settings: IN000 = Auto and IN001 = Hand. 26 Siemens Building Technologies, Inc. Startup Procedures Parameter P0700[1]** Description Selection of Command Source (Start Command) Selects the command source as follows: Action 1. 2. Press to confirm index selection. 3. Press 4. Press to confirm and save the setting. 5. Press again to return to the parameter selection level. 0 = Factory default setting 1 = BOP (keypad) 2 = Terminal digital input 4 = USS on BOP link (AOP) 5 = USS on COM link to advance to index Press [1], IN001, HAND. 6 = CB (Communications board or module) on COM link (P1/N2) Setting/ Default Setting = 1 Default = 1 to advance to 1. NOTE: Changing this parameter resets (to default) all settings on the selected item. For example, changing from 1 to 2 resets all digital inputs to default settings. P1000[0]** Selection of Frequency Setpoint 1. to advance to Press parameter P1000. Setting = 2 Default = 2 (Speed Command Source) Selects the frequency setpoint source as follows: 1 = Motor potentiometer setpoint/BOP (keypad) 2 = Analog input 2. to access the Press parameter indexes. 3. Press to advance to index [0], IN000, AUTO. 4 Press to confirm index selection. 5. Press 6. Press to confirm and save the setting. 3 = Fixed frequency setpoint 4 = USS on BOP Link/AOP 5 = USS on COM link 6 = CB (Communications board or module) on COM link (P1/N2) to advance to 2. ** Parameters have two index settings: IN000 = Auto and IN001 = Hand. Siemens Building Technologies, Inc. 27 SED2 VFD Electronic Bypass Option Operating Instructions Parameter P1000[1]** Description Selection of Frequency Setpoint Action 1. to advance to index Press [1], IN001, HAND. Setting/ Default Setting = 1 Default = 1 (Speed Command Source) 2. Press to confirm index selection. 1 = Motor potentiometer setpoint/AOP 3. Press 2 = Analog input 4. Press to confirm and save the setting. 5. Press again to return to the parameter selection level. 1. to advance to Press parameter P1080. Selects the frequency setpoint source as follows: to advance to 1. 3 = Fixed frequency 4 = USS on BOP Link/AOP 5 = USS on COM link 6 = CB (Communications board or module) on COM link (P1/N2) P1080 Minimum Motor Frequency 0 Hz to 650 Hz Minimum motor frequency at which the motor will run irrespective of the frequency setpoint. This value applies to both clockwise and counterclockwise rotation. 2. to access the Press parameter values level. 3. Press to advance to desired value. 4. to confirm and save Press the setting. Site Setting (20% to 30% Max) Default = 10 ** Parameters have two index settings: IN000 = Auto and IN001 = Hand. 28 Siemens Building Technologies, Inc. Startup Procedures Parameter P1082 Description Maximum Motor Frequency Action 1. 0 Hz to 650 Hz Maximum motor frequency at which the motor will run regardless of the frequency setpoint. This value applies to both clockwise and counterclockwise rotation. Press to advance to parameter P1082. 2. Press to access the parameter values level. 3. Press value. 4. Press to confirm and save the setting. to advance it desired Setting/ Default Site Setting Default = 50 or 60 (Default is determined by the setting of the motor frequency and unit of measurement DIP switches.) NOTE: This value is limited internally to 200 Hz or five times the rated motor frequency (P0305). When P1300 is greater than or equal to 20 (control mode = vector control), the value displays via r0209 (maximum frequency). P1120 Ramp-up Time 1. 0s to 650s Press to advance to parameter P1120. 2. to access the Press parameter values level. 3. Press value. 4. to confirm and save Press the setting. to advance it desired Site Setting Default = 10 Typical fan = 120s Typical pump = 30s NOTES: 1. Setting the ramp-up time too short can cause the SED2 to trip (F0001 over current, F0002 over voltage, or F0003 under voltage). 2. If using an external frequency setpoint with set ramp rates (such as from a PLC), achieve optimum SED2 performance by setting ramp time (P1120 and P1121) slightly shorter than those of the PLC. Siemens Building Technologies, Inc. 29 SED2 VFD Electronic Bypass Option Operating Instructions Parameter P1121 Description Ramp-down time Action 1. 0s to 650s Press to advance to parameter P1121. 2. Press to access the parameter values level. 3. Press value. 4. Press to confirm and save the setting. to advance it desired Setting/ Default Site Setting Default = 30 Typical fan = 120s Typical pump = 30s NOTES: 1. Setting the ramp-up time too short can cause the SED2 to trip (F0001 over current, F0002 over voltage, or F0003 under voltage. 2. If using an external frequency setpoint with set ramp rates (such as from a PLC), achieve optimum SED2 performance by setting ramp times (P1120 and P1121) slightly shorter than those of the PLC. P3900 End Quick Commissioning 1. 0 = End without motor calculation or factory reset. 1 = End with motor calculation and factory reset (recommended on SED2 without bypass option). 2 = End with motor calculation and with I/O reset. 3 = End with motor calculation but without I/O reset (recommended with SED2 with bypass option). Press to advance to parameter P3900. 2. Press to access the parameter values level. 3. Press to advance to 1. 4. Press setting. to confirm the Setting = 1 Default = 0 NOTES: 1. P0010 must always be set back to 0 before operating the motor. 2. If P3900 is greater than 0 on completion of commissioning, P0010 is automatically set back to 0. 3. If P0700 either indeed was changed during this process, programming of P0704 = 3 is required. 30 Siemens Building Technologies, Inc. Startup Procedures Additional Parameter Settings NOTE: If Display Selection for r0000, parameter P0005 = 21 (actual frequency), then the BOP display alternately shows setpoint values and the actual value (0 Hz). Flying Start Parameter P1200 Description Flying Start Starts SED2 into a spinning motor by rapidly changing the output frequency of the SED2 until the actual motor speed is found. Then, the motor runs up to setpoint using the normal ramp time. 0 = Flying start disabled. 1 = Flying start is always active, start in direction of setpoint. 2 = Flying start is active, if power on, fault, OFF2, start in direction of setpoint. 3 = Flying start is active if fault, OFF2, start in direction of setpoint. 4 = Flying start is always active, only in direction of setpoint. 5 = Flying start is active if power on, fault, OFF2, only in direction of setpoint. 6 = Flying start is active if fault, OFF2, only in direction of setpoint. Action 1. Press to enter the SED2 parameter mode and to display r0000. Setting/ Default Minimum = 0 Default = 0 Maximum = 6 2. Press to advance to parameter P1200. 3. to access the Press parameter values level. 4. Press to advance to desired setting. 5. Press to confirm and save the setting. Suggested = 2 NOTES: 1. Flying start is useful for motors with high inertia loads. 2. Settings 1 through 3 search in both directions. Settings 4 through 6 search only in the direction of the setpoint. 3. Flying start must be used in cases where the motor may still be turning (such as after a brief input power break) or can be driven by the load. Otherwise, overcurrent trips occur. 4. If the SED2 faults on F0002 (overvoltage) on a start command, flying start may have to be optimized by reducing the values in P1203 and P1202. Siemens Building Technologies, Inc. 31 SED2 VFD Electronic Bypass Option Operating Instructions Parameter P1202 Description Motor Current: Flying Start Defines search current used for flying start. Value is in % based on the rated motor current (P0305). Action 1. Press to enter the SED2 parameter mode and to display r0000. 2. Press to advance to parameter P1202. 3. Press to access the parameter values level. 4. Press to advance to desired value. 5. Press to confirm and save the setting. Setting/ Default Minimum = 10 Default = 100 Maximum = 200 NOTE: Reducing the search current may improve performance for flying start if the inertia of the system is not very high. P1203 Search Rate: Flying Start Sets factor by which the output frequency changes during flying start to synchronize with the turning motor. This value, entered in % relative to the default time factor, defines the initial gradient and influences the time taken to search for the motor frequency. The search time is the time taken to search through all frequencies between f_max + 2 × f_slip to 0 Hz. 1. to enter the SED2 Press parameter mode and to display r0000. 2. to advance to Press parameter P1203. 3. to access the Press parameter values level. 4. to advance to Press desired value. 5. Press to confirm and save the setting. Minimum = 10 Default = 100 Maximum = 200 NOTES: 1. P1203 = 100% is defined as giving a rate of 2% of f_slip, nom/ms. 2. P1203 = 200% would result in a rate of frequency change of 1% of f_slip, nom/ms. 3. A higher value produces a flatter gradient, and thus a longer search time. A lower value has the opposite effect. 32 Siemens Building Technologies, Inc. Startup Procedures Automatic Restart CAUTION: Settings 2 through 7 can cause the motor to restart unexpectedly. Parameter P1210 Description Automatic Restart Action 1. Press to enter the SED2 parameter mode and to display r0000. 2. to advance to Press parameter P1210. 3. to access the Press parameter values level. 4. Press to advance to desired setting. 5. to confirm and save Press the setting. Enables SED2 restart after a supply power break or after a fault. P1210 = 0, Disabled: Automatic restart is disabled. P1210 = 1, Trip reset after power on (P1211 disabled: The inverter will acknowledge (reset) faults; that is, it will reset a fault when it is re-applied. This means the inverter must be fully powered down, a brownout is not sufficient. The inverter will not run until the ON command has been toggled. P1210 = 2, Restart after supply power blackout (P1211 disabled): The inverter will acknowledge the fault F0003 at power on after blackout and will restart the drive. It is necessary that the ON command is wired via digital input (DIN). Setting/ Default Minimum = 0 Default = 1 Maximum: 5=Control Board Version 1.20 or earlier 6=Control Board Version 1.30 7=Control Board Version 1.40 Suggested: 3=Control Board Version 1.20 or earlier 6=Control Board Version 1.30 7=Control Board Version 1.40 P1210 = 3, Restart after brownout or fault (P1211 enabled): For these settings it is fundamental that the drive only restarts if it has been in a RUN state at the time of the faults (F0003, etc.). The inverter will acknowledge the fault and will restart the drive after a blackout or brownwout. It is necessary that the ON command is wired via digital input (DIN). Siemens Building Technologies, Inc. 33 SED2 VFD Electronic Bypass Option Operating Instructions Automatic Restart Continued Parameter P1210 (Continued) Description Action Setting/ Default P1210 = 4, Restart after supply power brownout (P1211 disabled): For these settings it is fundamental that the drive only restarts if it has been in a RUN state at the time of the fault (F0003). The inverter will acknowledge the fault and will restart the drive after a blackout or brownwout. It is necessary that the ON command is wired via digital input (DIN). P1210 = 5, Restart after blackout or fault (P1211 disabled): The inverter will acknowledge the faults (F0003 etc.) at power on after blackout and will restart the drive. It is necessary that the ON command is wired via digital input (DIN). P1210 = 6, Restart after supply power brown/blackout or fault (P1211 disabled): The inverter will acknowledge the faults (F0003 etc.) at power on after blackout or brownout and will restart the drive. It is necessary that the ON command is wired via digital input (DIN). Setting 6 causes the motor to restart immediately. P1210 = 7, Restart after supply power brown/blackout or fault (P1211 enabled): This setting is for use where an external bypass system or process is interlocked with a relay that is set to P0731/P0732=52.3 (fault). The inverter functions the same as P1210=6 (trip on brownout, blackout or fault) but uses P1211 and only sets the fault bit P0731/P0732=52.3 when the specified number of restarts defined in P1211 has expired. If no trip occurs after 2 hours, the fault counter is reset. NOTES: 1. Auto restart requires a constant ON command (such as via a digital input). 2. P1200 flying start must be used in cases where the motor may still be turning, such as after a brief input power break, or can be driven by the load. 3. A supply power brownout is when the power is interrupted and reapplied before the operator panel display has gone dark. It is a very short supply power break where the DC link has not fully collapsed. 4. A supply power blackout is when the operator panel display has gone dark before the power is reapplied. It is a long supply power break where the DC link has fully collapsed. 34 Siemens Building Technologies, Inc. Startup Procedures Parameter P1211 Description Number of Restart Attempts Specifies the number of times SED2 will attempt to restart after supply power brownout or fault, if P1210 automatic restart is activated. P1212 Time to First Restart Selects the time (seconds) before the SED2 is restarted for the first time if P1210 automatic restart is activated. Siemens Building Technologies, Inc. Action 1. Press to enter the SED2 parameter mode and to display r0000. 2. to advance to Press parameter P1211. 3. to access the Press parameter values level. 4. Press to advance to desired value. 5. Press to confirm and save the setting. 1. Press to enter the SED2 parameter mode and to display r0000. 2. to advance to Press parameter P1212. 3. to access the Press parameter values level. 4. to advance to Press desired value. 5. to confirm and save Press the setting. Setting/ Default Minimum = 0 Default = 3 Maximum = 10 Suggested = 10 Minimum = 0 Default = 3 Maximum = 10 Suggested = 10 35 SED2 VFD Electronic Bypass Option Operating Instructions Parameter P1213 Description Restart Time Increment Selects the amount (seconds) that the restart time is incremented for each restart of the SED2 if P1210 automatic restart is activated. Action Setting/ Default 1. Press to enter the SED2 parameter mode and to display r0000. Minimum = 0 Default = 30 Maximum = 1000 2. to advance to Press parameter P1213. Suggested = 10 3. to access the Press parameter values level. 4. Press to advance to desired value. 5. Press to confirm and save the setting. Vdc Controller Parameter P1240 Description Configuration of Vdc Controller Action 1. to enter the SED2 Press parameter mode and to display r0000. 2. to advance to Press parameter P1240. 3. Press to access the parameter values level. 4. to advance to Press desired value. 5. Press to confirm and save the setting. Enables/disabled Vdc controller. The Vdc controller dynamically controls the DC link voltage to prevent overvoltage trips on high inertia systems. Vdc-max automatically increases ramp-down times to keep the DC link voltage (r0026) within limits. 0 = Vdc controller disabled 1 = Vdc-max controller enabled 2 = Reserved 3 = Reserved 36 Setting/ Default Minimum = 0 Default = 1 Maximum = 3 Siemens Building Technologies, Inc. Startup Procedures Pulse Frequency Parameter P1800 Description Pulse Frequency Sets pulse frequency (kHz) of power switches in SED2. The frequency can be changed in increments of 2 kHz. Pulse frequencies > 4 kHz selected on 380V to 480V units reduce the maximum continuous motor current. Action 1. 2. to enter the SED2 Press parameter mode and to display r0000. Press to advance to parameter P1800. Setting/ Default Minimum = 4 Default = Varies by model (hp/voltage dependent) Maximum = 16 3. to access the Press parameter values level. 4. Press to advance to desired value. 5. Press to confirm and save the setting. NOTES: 1. Minimum pulse frequency depends on P1082 (maximum frequency) and P0310 (rated motor frequency). 2. At 4 kHz, full output current is obtained up to 50 degrees C (CT mode); over 50 degrees C, full output may be obtained at 8 kHz. 3. If silent operation is not absolutely necessary, lower pulse frequencies may be selected to reduce SED2 losses and radio-frequency emissions. 4. Under certain circumstances, the SED2 may reduce the switching frequency to provide protection against over-temperature. Siemens Building Technologies, Inc. 37 SED2 VFD Electronic Bypass Option Operating Instructions Motor Data Identification Parameter P1910 Description Motor Data Identification Action 1. Performs stator resistance measuring. 0 = Disabled. 2. Press to advance to parameter P1910. 3. Press to access the parameter values level. 4. Press 1 = Identification of Rs with parameter change. 2 = Identification of Rs without parameter change. 3 = Identification of the saturation characteristic with parameter change. to enter the SED2 Press parameter mode and to display r0000. Setting/ Default Minimum = 0 Maximum = 20 to advance to setting P1910=1. Press to confirm and save the setting. 20 = Set voltage vector. When P1910=1, Alarm A0541 (motor data identification active) is output and internally P0340 is set to 3. Initiate the measuring operation with a continuous (steady-state) ON command. The motor aligns itself and current flows through it. Diagnostics are possible using r0069 (CO: phase current). On completion of the motor data identification routine, P1910 resets (P1910=0, motor data identification routine inhibited) and Alarm A0541 is cleared (deleted). 5. 38 To set the SED2 into a defined state, issue an OFF1 command. Siemens Building Technologies, Inc. Startup Procedures Motor Data Identification Continued 6. Press to advance to setting to confirm P1910=3. Press and save the setting. When P1910=3, Alarm 0541 (motor data identification active) is output and internally P0340 is set to 2. Initiate the measuring operation with a continuous (steady-state) ON command. On completion of the motor data identification routine, P1910 resets (P1910=0, motor data identification routine inhibited) and Alarm A0541 is cleared (deleted). 7. To set the SED2 into a defined state, issue an OFF1 command. NOTES: 1. Motor must be cool to perform motor data identification. 2. Before selecting motor data identification, perform quick commissioning. 3. This measurement may take several minutes depending on motor size. 4. When P1910=1, the calculated value for stator resistance (P0350) is overwritten. 5. When P1910=2, the values already calculated (P0350) are not overwritten. 6. When choosing the setting for measurement, observe the following: − P1910=1 means that the value is actually adopted as P0350 parameter setting and applied to the control as well as being shown in the read-only parameters. − P1910=2 means that the value is only displayed. That is, it is shown for checking purposes in the read-only parameter r1912 (identified stator resistance). The value is not applied to the control. Siemens Building Technologies, Inc. 39 SED2 VFD Electronic Bypass Option Operating Instructions Reset to Factory Defaults Parameter P0010 P0970 Description Reset to Factory Default Action 1. Resets SED2 parameters to the factory defaults. to enter the SED2 Press parameter mode and to display r0000. 2. Press to advance to parameter P0010. 3. to access the Press parameter values level. 4. Press 5. Press to confirm and save the setting. 6. Press P0970. 7. to access the Press parameter values level. 8. Press 9. Press to confirm and save the setting. Setting/ Default P0010: Setting = 30 Default = 0 P0970: Setting = 1 Default = 0 to advance to 30. to go to parameter to advance to 1. NOTES: 1. First set P0010 = 30. 2. Stop SED2 (that is, disable all pulses) before you reset parameters to factory default values. 3. The following parameters retain their values after a factory reset: • P0918 (address of CB, communications board or module) • P2010 (USS baud rate) • P2011 (USS address) 4. The reset process takes about 10 seconds. 40 Siemens Building Technologies, Inc. Required SED2 Parameter Settings Required SED2 Parameter Settings The following SED2 parameters are programmed by the factory before shipping. If these parameters are changed or if the SED2 is ever reset to factory default, you must reset these parameters as follows: Parameter Setting P0748 P0702 in000 3 P0702 in001 3 P0731 52.3 NOTES: 1. The Interlock Start on the Controller board is simply a follower that can be used to tell the drive to do anything by closing the SED2 Interlock Start and programming P0704. 2. The Programmable Output on the Controller board is simply a follower of the SED2 Relay. 3. The SED2 Fault must always be programmed as a fault. Do not change the SED2 relay fault for other uses via P0731. 4. Changing P0700 resets all digital inputs and P0702 will require programming. Siemens Building Technologies, Inc. 41 SED2 VFD Electronic Bypass Option Operating Instructions Application Feature Setup Remote Start Input Overview Remote Safety #1 DIGITAL INPUTS The Controller board supports six isolated digital inputs and six digital relay outputs for customer use (Figure 13). The digital inputs include: Remote Start Input, Remote Safety #1 and #2, Interlock Start, Essential Services, and Overload Trigger. The digital outputs include: VFD Fault • Programmable Output • Drive Select • Bypass Select • Bypass Running • Overload Fault Interlock Start Essential Services Overload Trigger DIGITAL OUTPUTS VFD0114R2 • Remote Safety #2 Programmable Output, NO COM NC VFD Fault, NO COM NC Drive Select, COM NO Bypass Select, COM NO Bypass Running, COM NO Overload Fault, COM NO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 J2 J1 Figure 13. Controller Board Digital Inputs and Outputs. Auto Bypass without Interlock Description The Auto Bypass feature enables the SED2 to initiate automatic bypass mode operation. Closing of the SED2 Relay sends the motor to hand bypass mode. See the SED2 VFD Startup, Operation, and Maintenance Manual (125-3201) for programming of this relay and for its desired action. When the SED2 initiates bypass mode operation, the following occurs: 42 • The SED2 stops delivering power • The output contactor opens. • The bypass contactor closes and the Programmable Output on the Controller board closes. Siemens Building Technologies, Inc. Application Feature Setup NOTES: 1. All safety conditions must be met for bypass mode operation. 2. The input contactor remains energized. The Electronic Bypass Option will return to VFD mode operation as soon as the SED2 Relay in control opens. When the Electronic Bypass Option returns to VFD mode operation, the following occurs: • The SED2 Relay opens, the Programmable Output on the Controller board opens, and the bypass contactor opens. • The output contactor closes. NOTE: All safety conditions must be met for VFD mode operation. 4 2 3 3 4 During operation, the Auto Bypass Enabled indicator is on steady. 1 SW1 1 VFD0117R1 ON 2 NOTE: 5 5 ON The Auto Bypass feature requires that Controller board DIP Switch 2 is set ON. OFF Settings Example SED2 Settings Set parameters P0732 and P0748 for Auto Bypass on Drive Fault. Programming of the SED2 Relay is required for proper Auto Bypass activation. Set P0732 and P0748 as follows: Parameter Setting P0732 in000 52.3 P0732 in001 52.3 P0748 Siemens Building Technologies, Inc. 43 SED2 VFD Electronic Bypass Option Operating Instructions Interlock Description The Interlock feature (also called damper end switch logic) enables the SED2 outputs to inhibit motor start until a safety condition (proofing sequence) is confirmed. Any call to start the motor from the SED2 or bypass does not directly start the motor, but instead initiates the following Interlock procedure: • The Interlock Start Logic Enable indicator is ON. Proofing is required to start in VFD or bypass mode. • The Interlock Start Logic Command indicator turns ON and the Proofing indicator flashes. • When in VFD mode, the SED2 Relay closes and the Controller board Programmable Output closes to initiate the proofing sequence. The Programmable Output relay is used to supply power to an external device such as a damper actuator. • When not in VFD mode, the Controller board ignores the SED2 Relay. • When in bypass mode, any call to start the motor in bypass (in either hand bypass or auto bypass) initiates the proofing sequence. The Programmable Output closes and is used to supply power to an external device such as a damper actuator. • When control of the external device (such as a damper actuator) is satisfied, it must supply a contact closure to the Controller board Interlock Start. The Interlock Start Logic Command indicator turns OFF and the Proofing indicator turns ON. The motor then starts in the selected mode. • Any call for the motor not to be running requires a new proofing sequence to be initiated. NOTE: This feature can only be used with a hardwired start/stop command. ON 4 5 5 44 1 SW1 1 VFD0118R1 1. The Interlock Start Logic Enabled indicator is on steady. ON 2 NOTES: 2 3 3 4 The Interlock feature requires that Controller board DIP Switch 3 is set ON. OFF Settings Siemens Building Technologies, Inc. Application Feature Setup 2. Example assumes hardwired start is in auto. If other, modify P0732 as appropriate. For proper Interlock operation, set the following SED2 parameters: • P0700 in000 = 2 Digital input that is the start command in the auto mode (from the damper end switch) • P0700 in001 = 2 Digital input that is the start command in the hand mode (from the damper end switch) • P0701 in000 = 99 and P0701 in001 = 99 Initiate BiCo • P0702 in000 = 3 and P0702 in001 = 3 • P0732 in000 = 722.0 Tells the drive through BiCo that instead of starting the drive in auto mode when the Remote Start input closes, it should close the SED2 Relay. NOTE: If P1 is the start command in auto, change the following parameters: P0003 = 4 (before changing this setting, note the current setting) P3950 = 46 P0732 in000 = 2090.0 P0003 = Change back to previous setting (1, 2, or 3) • P0732 in001 = 19.0 Tells the drive through BiCo that instead of starting the drive in hand mode when the green Start button is selected, it should close the SED2 Relay. • P0704 in000 = 1 and P0704 in001 = 1 NOTE: For a complete description of BiCo, see the SED2 VFD Startup, Operation, and Maintenance Manual (125-3201). Siemens Building Technologies, Inc. 45 SED2 VFD Electronic Bypass Option Operating Instructions DIGITAL INPUTS Wiring Example for Interlock Remote Start Input Remote Safety #1 Remote Safety #2 Customer Proof Interlock Start DIGITAL OUTPUTS VFD0115R2 Power to Customer Device Programmable Output, NO COM NC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 J2 J1 Essential Services Description The Essential Services feature allows full-power bypass mode control of the motor during an emergency scenario. Activation of Essential Services overrides any other selected operation. Essential Services ensures that the bypass contactor will not open when a safety input or overload opens. Power goes directly to the motor. NOTES: 1. If using both the Interlock and Essential Services features, Essential Services waits 10 seconds for the Interlock to confirm the safety condition (such as opening a damper). After the 10-second delay, Essential Services controls the motor regardless of the Interlock safety condition status. 2. Use extreme care when using the Essential Services mode. All safety circuits are no longer active (including motor overload and safety inputs to the Controller board). 46 Siemens Building Technologies, Inc. Application Feature Setup 4 3 4 2 3 The Essential Services indicator is on steady. 1 SW1 1 VFD0119R1 ON 2 NOTE: 5 5 ON The Essential Services feature requires that Controller board DIP Switch 1 is set ON. OFF Settings Essential Services does not require SED2 parameter settings. The Essential Services feature simply puts the Electronic Bypass Option into override bypass mode no matter what operation is selected. Wiring Example for Essential Services VFD0116R1 DIGITAL INPUTS Siemens Building Technologies, Inc. Customer Essential Services Initiation Essential Services 1 2 3 4 5 6 7 8 9 10 11 12 J2 47 SED2 VFD Electronic Bypass Option Operating Instructions Interlock and Auto Bypass on VFD Fault Description Interlock and Auto Bypass features are both active. Auto bypass now becomes auto bypass on a VFD fault only (bypass is initiated by the SED2 Fault and this digital output must always be programmed to VFD fault). • All set-up is the same as with Interlock (see the Interlock section in Application Feature Setup). • Hand bypass is now initiated by SED2 Fault. • The Programmable Output is still used to initiate the proofing sequence. 4 1 SW1 VFD0120R1 1 2 2 3 3 4 During operation, the Auto Bypass Enabled indicator is on steady. Also, the Interlock Start Logic Enabled indicator is on steady. ON NOTE: 5 5 ON Interlock and Auto Bypass requires that Controller board DIP Switches 2 and 3 are set ON. OFF Settings See the Auto Bypass without Interlock on VFD Relay Output and Interlock sections for parameter settings. DIGITAL INPUTS Wiring Example for Interlock and Auto Bypass on VFD Fault Remote Start Input Remote Safety #1 Remote Safety #2 Customer Proof Interlock Start DIGITAL OUTPUTS VFD0115R2 Power to Customer Device 48 Programmable Output, NO COM NC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 J2 J1 Siemens Building Technologies, Inc. Technical Specifications Technical Specifications Table 5. Electronic Bypass Specifications. Specifications Description 208V, 3 ac±10% 240V, 3 ac ±10% Input Voltage (3 phase) 480V, 3 ac ±10% 575V, 3 ac ±10% Digital Inputs Six Digital Inputs as follows: • Remote start input • Remote safety 1 • Remote safety 2 • Interlock start • Essential services • Overload trigger Inputs require a contact closure capable of providing a low impedance path at currents less than 20 mA. Relay/Digital Outputs Six Relay/Digital Outputs as follows: • VFD fault • Programmable output • Drive select • Bypass select • Running on bypass • Overload fault Each relay has a maximum rating of 2A at 120V ac. Operating: 14°F to 104°F (-10°C to 40°C) Temperature Storage: –40°F to 158°F (–40°C to 70°C) Humidity 0 to 95% rh, noncondensing Table 6. SED2 Specifications. Drive Specifications Input voltage, 3 phase power, and amps Description 200V to 240V, 3 ac ± 10%. 1/2 hp to 60 hp, (2.3 Amps to 154 Amps) 380V to 480V, 3 ac ± 10% 1/2 hp to 125 hp, (1.2 Amps to 178 Amps) 500V to 600V, 3 ac ± 10% 1 hp to 125 hp, (2.3 Amps to 125 Amps) Input frequency 47 Hz to 63 Hz Output frequency 0 Hz to 150 Hz Power factor ≥0.9 VFD degree of efficiency 96% to 97% Switch-on current Less than nominal input current Siemens Building Technologies, Inc. 49 SED2 VFD Electronic Bypass Operating Instructons Table 6. SED2 Specifications (Continued). Drive Specifications Description Auxiliary supply 24V Glavanically separated, unregulated auxiliary supply (18V to 32V) 100 mA Overload capacity 110% for 60 seconds Control method Linear, parabolic and programmable V/f; and flux current control low-power mode PWM frequency 4k Hz to 16k Hz (adjustable in 2k Hz increments) Fixed frequencies 15 programmable Skip frequency bands 4 programmable Setpoint resolution 0.01 Hz digital, 0.01 Hz serial, 10 bit analog Digital inputs (sink/source) 6: fully programmable and scalable isolated digital inputs, switchable Analog inputs 2: 0 to 10 Vdc, 0/4 to 20 mA, can also be configured as digital inputs or Ni 1000 input Relay outputs 2: configurable 30 Vdc/5A (resistive), 250 Vac 2A (inductive) Analog outputs 2: programmable (0/4 to 20 mA) Serial interface RS-485 Transmission rate: Up to 38.4k Baud Protocols: Siemens, P1 and Johnson, N2; Protection level IP20: NEMA Type 1 with protective shield and gland plate installed IP54: NEMA Type 12 (400V and 500V series only) Temperature ranges Operating: 14°F to 104°F (–10°C to 40°C) Storage: –40°F to 158°F (–40°C to 70°C) Humidity 95% rh, non-condensing Operational altitudes Up to 3280 ft (1000m) above sea level without de-rating Protection features Under-voltage, Over-voltage, Overload, Ground fault, Short circuit, Stall prevention, Locked motor, Motor overtemperature l2t PTC, Over-temperature, Parameter PIN protection Standards UL, cUL NOTE: SED2 Compliance with EN61000-3-12: From September 1st, 2005 all electrical apparatus covered by the EMC directive will have to comply with EN61000-3-12 “Limits for harmonic currents produced by equipment connected to public low voltage systems with input currents > 16A and =< 75 A per phase”. Siemens variable speed drives of the product range SED2 (Micromaster 436) fulfil the requirements of the EN 61000-3-12 (without the need for external line reactors) regarding the THD values of Table 3 under the pre condition of Rsce > 190. The required PWHD values will not be achieved. Due to this fact it is recommended to apply for connection approval at the local electricity board. The local electricity board will evaluate among many other data the content of the 5th harmonic current and the Line Power Factor "Lambda”, which is the ratio of active power and apparent power. Siemens frequency inverters are optimized in design and operation characteristics regarding energy efficiency and less interference with line supplies. 50 Siemens Building Technologies, Inc. Troubleshooting Troubleshooting WARNING: Always disconnect all power sources before opening the SED2 Electronic Bypass Option. Power-on Initialization Failure (Unit Fault Condition) During power-on initialization, a unit fault condition occurs if the Electronic Bypass Option did not pass the basic sanity test. Rather than flash normally, the basic sanity test indicator pauses, flashes a fault code, and then repeats. Table 7 shows the fault codes. For example, if the basic sanity test indicator flashes three times rapidly, pauses, and then repeats, this means that there is a keypad failure. Table 7. Basic Sanity Test Fault Codes. Basic Sanity Test Fault Code/Flashes Description 1 Non-Volatile Memory Failure 2 Flash Memory Failure (CRC, cyclic redundancy check) 3 Keypad Failure 4 RAM Memory Failure (not used) 5 EEPROM Read error 6 EEPROM Write Failure 7 Runtime Flash Failure (CRC, cyclic redundancy check) 8 Main Program Failed (or hangs) It may be possible to recover from the unit fault condition by simply attempting a power down/up of the Electronic Bypass Option. If the unit fault condition still exists, replace the Controller board. CAUTION: When powering down/up the Electronic Bypass Option, power down the unit, wait 5 minutes, and then power up the unit. Siemens Building Technologies, Inc. 51 SED2 VFD Electronic Bypass Option Operating Instructons Override Jumper An Override Jumper (J8) is supplied on the Controller board. Moving this jumper to the override position removes the Controller board and its keypad from the control and closes the drive output contactor (and the input contactor if supplied). BPEC BPEC J2 J1 J1 J8 J8 VFD0121R1 J2 OVERRIDE JUMPER J8 SHOWN IN NORMAL POSITION OVERRIDE JUMPER J8 SHOWN IN OVERRIDE POSITION Figure 14. Override Jumper J8 Location and Positions. Fuses The Controller board contains a fuse (F1) under its cover (Figure 15). Determine if the fuse F1 needs replacement as follows: 1. If the basic sanity test indicator (Figure 15) is flashing, fuse F1 is OK and no action is required. 2. Verify that 120 Vac power is available on the secondary side of the Electronic Bypass Option power transformer (Figure 15). If power is not proper, check the Electronic Bypass Option components such as: • Power transformer • Power transformer fuses (F2, F3, and F4). Table 8 provides fuse replacement information. 3. If power is proper, check fuse F1 as follows: • Power down the Electronic Bypass Option. • Remove the Controller board cover. • Remove fuse F1. • Use an ohm meter to check the fuse. • Replace fuse F1 if necessary. NOTE: 52 Replace fuse F1 with an 8 AG, 1/2 amp, 250V, fast-acting instrument fuse such as a Bussmann AGX1/2 or Littlefuse 361.500. Siemens Building Technologies, Inc. Troubleshooting Table 8. Fuse Replacement Information. Bypass Option Part Number Primary Fuse (F3 and F4) Secondary Fuse (F2) VBE10.5… to VBE17.5… Bussmann/Littlefuse LP-CC-1 Bussmann/Littlefuse LP-CC-6/10 VBE110… to VBE110… Bussmann/Littlefuse LP-CC-2 Bussmann/Littlefuse LP-CC-1 1/4 VBE115… to VBE160… Bussmann/Littlefuse LP-CC-3 Bussmann/Littlefuse LP-CC-2 VBE20.5… to VBE27.5… Bussmann/Littlefuse LP-CC-1 Bussmann/Littlefuse LP-CC-6/10 VBE210… to VBE210… Bussmann/Littlefuse LP-CC-2 Bussmann/Littlefuse LP-CC-1 1/4 VBE215… to VBE260… Bussmann/Littlefuse LP-CC-3 Bussmann/Littlefuse LP-CC-2 VBE30… to VBE315… Bussmann/Littlefuse LP-CC-1/2 Bussmann/Littlefuse LP-CC-6/10 VBE320… to VBE320… Bussmann/Littlefuse LP-CC-1 Bussmann/Littlefuse LP-CC-1 1/4 VBE325… to VBE3125… Bussmann/Littlefuse LP-CC-1 1/2 Bussmann/Littlefuse LP-CC-2 VBE40… to VBE420… Bussmann/Littlefuse FNQ-R-4/10 Bussmann/Littlefuse LP-CC-6/10 VBE425… to VBE425… Bussmann/Littlefuse LP-CC-8/10 Bussmann/Littlefuse LP-CC-1 1/4 VBE430… to VBE4125… Bussmann/Littlefuse LP-CC-1 1/4 Bussmann/Littlefuse LP-CC-2 Siemens Building Technologies, Inc. 53 SED2 VFD Electronic Bypass Option Operating Instructons VFD Bypass Hand Start Input Contactor Bypass Contactor Remote Start Overload Relay Motor STOP RESET Auto Bypass Enabled VFD Fault Safety Fault Essential Services INTERLOCK START LOGIC Overload Fault Enable Commanded Proofed VFD DO#1, NO COM VFD DO#2, NO COM VFD DI#1 Isolated 0V VFD DI#2 10 9 8 7 VFD DI#3 6 NOTE: 3-Contactor Keypad Shown. KEYPAD INTERFACE Basic Sanity Test LED SED2 VFD 1 J4 3 4 5 ON SW1 DIP Switch J2 Remote Start Input 1 2 3 4 5 6 7 8 9 10 11 12 J1 13 14 15 16 17 18 19 20 21 22 23 24 25 26 Remote Safety #1 Remote Safety #2 Interlock Start Essential Services Overload Trigger Programmable Output, NO COM NC VFD Fault, NO COM NC Drive Select, COM NO Bypass Select, COM NO Bypass Running, COM NO Overload Fault, COM NO Override Jumper J6 CONTACTOR CONTROLS CUSTOMER SUPPLIED 3-PHASE POWER VFD0122R2 SED2 Fault MCU J8 Factory Use Only DIGITAL OUTPUTS OK to Run SED2 Relay 2 J3 Ribbon Cable for Keypad Pushbuttons and Indicators DIGITAL INPUTS Remote Start/Stop Interlock Start Confirm VFD INTERFACE Output Contactor CONTROLLER BOARD HIGH VOLTAGE FUSE FUSE F3 F4 TRANSFORMER HIGH VOLTAGE/ 120V STEP-DOWN POWER TRANSFORMER F1 J7 J5 8 9 10 11 12 13 14 7 6 5 4 3 2 1 3 2 1 Input Contactor ISO_IN6A Output Contactor NO ISO_IN6B Bypass Contactor NO Not Used Output Contactor NC 120V Neutral Bypass Contactor COM 120V Neutral 120V Hot 120V Neutral 120V Hot 120V Neutral VFD Enable 5 8 28 6 25 24 22 21 OFF Input On/Off VFD DI#3 VFD DI#2 Isolated 0V VFD DI#1 COM VFD DO#2, NO COM VFD DO#1, NO FUSE Earth Ground 120V Neutral 120V Hot F2 INPUT CONTACTOR OUTPUT CONTACTOR BYPASS CONTACTOR INPUT DEVICE OF VFD WITH ELECTRONIC BYPASS MOTOR Figure 15. Controller Board Inputs and Outputs. 54 Siemens Building Technologies, Inc. Troubleshooting Siemens Building Technologies, Inc. 55 SED2 VFD Electronic Bypass Option Operating Instructons Siemens Building Technologies, Inc. 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 Tel: +1 847-215-1000 Fax +1 847-215-1093 Siemens Building Technologies, Ltd. 2185 Derry Road West Mississauga, ON L5N 7A6 Canada Tel: +1 905-819-5800 www.sbt.siemens.com
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes XMP Toolkit : 3.1-701 Producer : Acrobat Distiller 7.0 (Windows) Creator Tool : PScript5.dll Version 5.2.2 Modify Date : 2007:04:18 16:46:11-05:00 Create Date : 2007:04:18 16:46:11-05:00 Format : application/pdf Title : Microsoft Word - 125-3208.doc Creator : AdamsL Document ID : uuid:80566386-6bd1-4949-8d01-6fba76f38094 Instance ID : uuid:f6979217-7186-4c47-950f-2fba8e09e7b4 Page Count : 64 Author : AdamsLEXIF Metadata provided by EXIF.tools