A major answer to the changing heating-fuel situation

HOT WATER MODELS IN 9 SIZES
8 kw (27,301 Btuh) to 40 kw (136,506 Btuh)

Before purchasing this appliance,
read important energy cost and
efficiency information available
from your contractor.

TM

Monitron Compact, easy to install for new or “standby” installations

Monitron combines the availability and dependability of electricity with the
comfort and performance of conventional hydronic heating using baseboard,
radiant or cast-iron radiators.
TYPICAL WIRING DIAGRAM
Monitron as a replacement unit: Works with virtually any existing
hot water hydronic radiation system. Although rated in kilowatts, it is
also clearly identified by BTU output.
Monitron as a standby unit: Particularly suitable for commercial
and industrial facilities, or office buildings which can’t risk down-time
with their existing heating equipment. If oil or gas is temporarily unavailable, the owner easily switches the heating system to the electric boiler.

Monitron as a primary heating unit offers:
• The convenience of electricity and the comfort of hydronics.
• The elimination of a chimney.
• Competitive pricing with electric baseboard systems.
• Simple zoning by zone valves.
TO ZONE VALVE
TRANSFORMER
WHEN USED

Monitron by Slant/Fin is the electronic-age boiler designed to save
energy for new or existing heating systems.

Monitron installed as primary boiler.

America’s Best - Built Electric Boiler
• One piece cast-iron heat exchanger.
• Built in air eliminator.
• Internal baffles improve heat transfer.

Energy-saver
electric sequential control package *
With manual mild-weather energy-saver switches *
NORMAL OPERATIONS

OPTIONAL MILD-WEATHER OPERATION

When the thermostat calls for heat, the circulator turns on and the
first electric heater bank is energized. At preset 30-second intervals,
the other heater banks automatically energize. The circulator continues operating until the room thermostat is satisfied. A flow switch
supplied by Slant/Fin or others is required. It prevents the elements
from being energized unless the circulator is operating. This avoids
element burnout.

Mild-weather energy savings are made possible through the use of
circuit breakers on the breaker panel. This permits the owner to
manually switch off one or more of the elements. Then, when just a
moderate amount of heat is needed, all the elements are not energized, cycling is reduced, and overheating is diminished. This energy-saving feature is standard on Monitron models EH-12-S through
EH-40-S.

* All models except EH-8 and EH-10

Standard equipment
•
•
•
•
•
•

Dual limit aquastat
Altitude pressure and temperature gauge
Safety relief valve (unmounted)
Circulator relay and heater contactors
Circuit breaker (one or two heaters per breaker)
Low voltage thermostat with adjustable heat anticipator
(packed separately)
• Drain cock, 3⁄4 " (packed separately)
• Built-in air separator

• Cast-iron ASME approved heat exchanger
• Terminal blocks for circulator, thermostat, flow switch and
for zone valve transformer
• Sequencer
• Complete jacketing
• U.L. listed, ASME authorized
• Flow switch. Not included with, but necessary on all models
• Circuit breaker for circulator and control circuit.

FEATURES
30 PSI PRESSURE
RELIEF VALVE

CONTACTORS
FOR HEATER
ELEMENTS

SEQUENCER

ALTITUDE
PRESSURE
AND TEMPERATURE
GAUGE

HEATER
ELEMENTS

CAST IRON
ASME HEAT
EXCHANGER

DUAL LIMIT AQUASTAT

CIRCULATOR
RELAY

CIRCUIT BREAKERS
TERMINAL
BLOCKS

DIMENSIONS

NOTES:
1. May be totally enclosed.
2. All clearance dimensions are
minimum.
3. All dimensions are in inches.

RATINGS AND SPECIFICATIONS
SINGLE
PHASE
Neutral Lug
SINGLE
D.O.E
Size (AWG)
PHASE Capacity
Boiler
* KW at *(Btu/hr) at Solid
Stranded
Model No. 240 VAC 240 VAC Cu ¶ AL Cu ¶ AL

SINGLE PHASE –– THREE WIRE
THREE PHASE –– FOUR WIRE 208 VAC WYE §
Grounding
Grounding
D.O.E
Lug Size
Lug Size
†
**
Heater
Main
Lug
† Heater
Main Lug
Capacity
(AWG)
(AWG)
KW at (Btuh) at Size (AWG)
Amps at
Amps at
Size (AWG)
208
VAC
240
VAC
CU ¶ AL
208 VAC
¶ AL
Cu
¶ AL
CU ¶ AL
Cu
208 VAC

EH8S

8

27000

14-12

12

6-2/0

14-4

6-4

33

EH10S

10

34000

14-12

12

6-2/0

14-4

6-4

42

–––

–––

EH12S

12

41000

14-12

12

6-2/0

14-4

6-4

50

9.012

31000

EH16S

16

55000

14-12

12

6-2/0

14-4

6-4

67

12.016

41000

EH20S

20

68000

14-12

12

6-2/0

14-4

6-4

83

15.020

51000

EH24S

24

82000

14-12

12

6/2/0

14-4

6-4

100

18.024

EH28S

28

96000

14-12

12

2-250 MCM

14-4

6-4

117

21.028

EH32S

32

109000

14-12

12

2-250 MCM

14-4

6-4

133

EH40S

40

137000

14-12

12

2-250 MCM

6-2/0

–––

167

* Multiply by 0.751 for values at 208 volts AC.
** Multiply by 0.867 for values at 208 volts AC.
† For total current add, to the value shown in the table, the current draw for
circulator and/or zone valve transformer (12 Amp. max.),
‡ Leg with the highest value of line current of an unbalanced 3 phase load.

–––

–––

–––

–––

–––

–––

–––

–––

–––

–––

6-2/0

14-4

6-4

25.1

6-2/0

14-4

6-4

‡38.1

6-2/0

14-4

6-4

‡48

62000

6-2/0

14-4

6-4

‡60

72000

6-2/0

14-4

6-4

‡60

24.032

82000

6-2/0

14-4

6-4

‡73

30.040

103000

6-2/0

14-4

6-4

‡95.4

¶ Aluminum conductors may be used, lug size, conduit size, ampacity and all
applicable codes permitting. However, aluminum conductors may not be
used for model EH-40 single phase.
§ 3 phase 240V special model also available.
Consult factory for information.

Specify Model as follows: Model Number. Single or three Phase.
“135S” for single phase, 120V/240V, 120V/208V WYE. 3 wire (see
note (1) below) with control circuit breaker.
“345S” for three phase, 120V/208V WYE. 4 wire (see note (1)
below) with control circuit breaker.
Note No. 1: Voltage of any line to ground cannot exceed
125 VAC.

Example: EH-20-135S=20KW boiler for 120V/240V.
120V/208V Single Phase 3 wire.

ELECTRICAL
•
•

Single branch circuit for 3 wire 120/208 V WYE, 120/240 Volt a.c.
single phase, 60 Hz or for 4 wire 120/208V WYE three
phase, 60Hz a.c. See note (1) above.
Circulator relay 12 AMP Max, 120V a.c.

•
•

Heating elements: Low-density replaceable. Copper sheathed
and silver brazed base.
Relays: Heavy-duty contactors, 48 AMP U.L. rating

TYPICAL PIPING DIAGRAM
FOR USE WITH TWO-WAY ZONE VALVES

NOTES:
1. Optional blocking gate valve and hose end valve
used (with drain valve) for fast fill and purge of
system.
IMPORTANT Close bypass line valve
(if used) during purging.
2. Circulator should not be installed at lowest point
of piping.
3. There should be no elbows, tees, or change of
pipe size for at least 5 diameters of pipe size
(see table below) upstream and downstream of
flow switch.

Boiler Model

Flow Switch
McDonnell
& Miller No.

Pipe
Size

EH-40
FS8W
1 1⁄4 IN.
EH-8 Thru EH-32 FS4-3T3-1 1 IN.

Minimum Length of
Straight Pipe Upstream
and Down-Stream
of Flow Switch

8 1⁄2 IN.
6 1⁄2 IN.

© Slant/Fin Corp. 2003. Printed in U.S.A. 1203. Publication EH-10

SLANT/FIN CORPORATION., Greenvale, N.Y. 11548 • www.slantfin.com
Phone: (516) 484-2600 • Fax: (516) 484-5921
In Canada: Slant/Fin LTD/LTEE, Mississauga, Ontario • www.slantfin.ca



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : 3.1-701
About                           : uuid:30f5dac8-46da-11d8-94f1-0030656cfbcc
Producer                        : QuarkXPress(tm) 6.0
X Press Private                 : %%DocumentProcessColors: Cyan Magenta Yellow Black.%%EndComments
Create Date                     : 2004:01:14 16:18:47Z
Creator Tool                    : QuarkXPress(tm) 6.0
Modify Date                     : 2006:01:18 16:48:44-05:00
Metadata Date                   : 2006:01:18 16:48:44-05:00
Document ID                     : uuid:ed790453-46d9-11d8-94f1-0030656cfbcc
Instance ID                     : uuid:325d433e-886c-11da-942a-0030656cfbcc
Format                          : application/pdf
Page Count                      : 4
Creator                         : QuarkXPress(tm) 6.0
EXIF Metadata provided by EXIF.tools

Navigation menu