NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 1
42" Wood Burning Fireplaces
P/N 700,026M REV. C 11/2003
BR-42 BC-42
BRI-42 BCI-42
BR-42-2 BC-42-2
MODELS
WH Report No. J99025865B-231
STANDARD SERIES
This installation manual will enable you to obtain a safe, efficient and
dependable installation of your fireplace system. Please read and under-
stand these instructions before beginning your installation.
Do not alter or modify the fireplace or its components under any
circumstances. Any modification or alteration of the fireplace system,
including but not limited to the fireplace, chimney components and
accessories, may void the warranty, listings and approvals of this system
and could result in an unsafe and potentially dangerous installation.
IMPORTANT! TO ASSURE PROPER ALIGNMENT OF GLASS DOORS:
INSTALL THIS FIREPLACE IN A SQUARE AND PLUMB CONDITION,
USING SHIMS AS NECESSARY AT SIDES AND/OR BOTTOM.
PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE.
INSTALLATION
INSTRUCTIONS
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
2
TABLE OF CONTENTS
Safety Rules .................................... page 2
Tools and Building Supplies ............ page 2
Precautions ..................................... page 3
Introduction ..................................... page 3
Clearances/Height Requirements..... page 3
Chimney System ............................. page 3
Assembly Outline............................. page 4
Location of Fireplace ....................... page 4
Assembly Steps ............................... page 5
Preinstallation Notes........................ page 5
Clearances ....................................... page 5
Installing the Fireplace ..................... page 5
Fireplace Specifications .................. page 6
Framing Specifications.................... page 7
Installing the Chimney System ........ page 8
30° Offset through Floor/Ceiling ...... page 9
Ten Foot Rule Summary .................. page 11
Multiple Terminations ...................... page 11
Chimney Component Calculations ... page 11
Special Offset Instructions............... page 12
Offset Calculations........................... page 12
Vertical Elevation Chart ................... page 12
Offset Elevation Chart ..................... page 13
Installing Offsets.............................. page 14
Optional Equipment Considerations. page 14
Forced Air Kits ................................. page 14
Combustion Air Kits ........................ page 15
Gas Line Connection........................ page 15
Vent Free Appliances ....................... page 15
Glass Doors ..................................... page 16
Cold Climate Insulation.................... page 16
Fireplace Finishes ............................ page 16
Mantels and Trim............................. page 16
Hearth Extensions/Wall Shields ....... page 16
Finish Requirements ........................ page 18
Installation Components .................. page 18
IMPORTANT: PLEASE READ AND
UNDERSTAND THESE RULES TO
FOLLOW FOR SAFETY.
1. Before starting your fireplace installation,
read these installation instructions carefully to
be sure you understand them completely and in
entirety. Failure to follow them could cause a
fireplace malfunction resulting in serious injury
and/or property damage.
The manufacturer is not responsible for any
smoking or related problems that may result
from the lack of adequate combustion air. It is
the responsibility of the builder/contractor to
ensure that adequate combustion air has been
provided for the fireplace.
13. DO NOT use a fireplace insert or any other
products not specified herein by the manufac-
turer for use with this fireplace. All gas log sets
must be operated with the damper clamped
open, including unlisted “vent free” log sets.
Listed “vent-free” log sets may be operated
with the damper closed.
14. "Smoke free” operation is not warranteed
nor are we responsible for inadequate system
draft caused by mechanical systems, general
construction conditions, inadequate chimney
heights, adverse wind conditions and/or un-
usual environmental factors or conditions be-
yond our control.
15. Never, under any circumstances, install a
fireplace, chimney component or any acces-
sories, that has visible or suspected physical
damage as a result of handling or transporta-
tion. These items should be inspected by your
distributor or qualified factory representative
to ensure safe condition. When in doubt, con-
sult your distributor.
16. For additional safety considerations and
complete operating instructions, refer to the
Care and Operation Manual provided with the
fireplace.
TOOLS AND BUILDING SUPPLIES
NORMALLY REQUIRED
Tools should Include:
Phillips screwdriver
Hammer
Saw and/or sabersaw
Level
Measuring tape
Plumb line
Electric drill and bits
Pliers
Square
Building supplies:
Framing materials
Wall finishing materials
Caulking materials (noncombustible)
Fireplace surround and hearth
extension materials (noncombustible)
2. Always check your local building codes. The
installation must comply with all local, regional,
state and national codes and regulations.
3. These fireplaces must be installed with
Security Chimneys FTF8 (8" inside diameter)
Chimney System only. These systems are in-
tended for use in any application where a
traditional masonry type fireplace would ap-
ply. The chimney system must always vent to
the outside of the building.
4. To ensure a safe fireplace system and to
prevent the build-up of soot and creosote,
inspect and clean the fireplace and chimney
prior to use and periodically during the heating
season.
5. Use solid fuel only. DO NOT use artificial
wax based logs, chemical chimney cleaners or
flame colorants in your fireplace.
6. DO NOT use charcoal or coal under any
circumstances.
7. NEVER use gasoline, gasoline-type lantern
fuel, kerosene, charcoal lighter fluid, or similar
liquids to start or “freshen up” a fire in this
fireplace. Keep any flammable liquids a safe
distance from the fireplace.
8. NEVER leave children unattended when
there is a fire burning in the fireplace.
9. Always keep flue damper open when heat is
present in the fireplace.
10. Before servicing, allow the fireplace to
cool. Always shut off any electricity or gas to
the fireplace while working on it. This will
prevent any possible electrical shock or burns.
11. This fireplace is not intended to heat an
entire home or be used as a primary heat
source. It is designed to ensure homeowner
comfort by providing supplemental heat to the
room.
12. Always ensure an that adequate supply of
replacement combustion air from the outside
of the house is accessible to the fire to support
normal combustion. Fireplaces consume large
volumes of air during the normal combustion
process. In the event the home is tightly sealed
with modern energy efficient features, the op-
tional combustion air kit may not provide all
the air required to support combustion.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 3
Figure 1
TYPICAL INSTALLATION
*Construction Materials:
• framing materials • paneling
• particle board • flooring
• millboard • dry wall
• plywood • etc.
PRECAUTIONS
Note: These fireplace systems are not difficult
to install. However, in the interest of safety, it
is recommended that the installer be a quali-
fied or certified “tradesman” familiar with com-
monly accepted fireplace installation and safety
techniques as well as prevailing local codes.
The most important areas of concern dealing
with the installation of factory-built fireplaces
are clearances to combustible materials, proper
assembly of component parts, height of the
chimney system, the proper use of accesso-
ries supplied by the manufacturer and the
techniques employed in using finishing mate-
rials applied to the wall surrounding the fire-
place, hearth extensions and wall shields. Each
of these topics will be covered in thorough
detail throughout this manual. Please give
each your special attention as you progress
with your installation.
INTRODUCTION
General Information
These fireplaces are conventional radiant heat
fireplaces with standard bar grates, optional
outside combustion air kits and optional deco-
rative glass doors.
Note: Illustrations shown reflect “typical” in-
stallations with nominal dimensions and are
for design and framing reference only. Actual
installations may vary due to individual design
preferences. However, always maintain mini-
mum clearances to combustible materials and
do not violate any specific installation require-
ments.
These fireplaces have been tested and listed by
Warnock Hersey (Report No. J99025865B-231)
to U.L. standard 127. These units are intended
for installation in residential homes and other
buildings of conventional construction includ-
ing commercial, not in mobile homes.
These fireplaces have been tested for installa-
tion in Canada to ULC-S610. For installations
in Canada, the chimney clearance to com-
bustibles must be 2 inches and the Cold
Climat Kit must be installed.
These fireplace systems are designed for in-
stallation in accordance with the National Fire
Protection Standard for chimneys, fireplaces
and solid fuel burning appliances; NFPA 211
and in accordance with codes such as the
BOCA Basic/National Codes, the Standard Me-
chanical Code and the Uniform Building Codes.
When complete these fireplace systems con-
sists of five basic “sub-systems”:
1. The Fireplace
2. The Chimney and Termination
3. The Optional Glass Doors
4. The Optional Combustion Air Kits
5. Optional Cold Climate Kit (Mandatory in
Canada).
CLEARANCES AND HEIGHT
REQUIREMENTS
The fireplace may be placed on or near normal
construction materials*. The combustion air
kit, firestop spacer and roof flashing (not chase
flashings) may be placed directly on or against
normal construction materials.* The chimney
and fireplace outer wrapper require a mini-
mum 1"** air space to combustibles. A com-
bustible mantle may be installed 12" above the
opening of the fireplace as per NFPA 211,
Section 7-2.3.3 (1992). In Canada, the mini-
mum is 18" above the fireplace opening.
The minimum installed height of the completed
fireplace system is 15' 0". The maximum height
is 60' 0".
The fireplace and chimney system must be
enclosed when installed in or passing through
a living area where combustibles or people may
come in contact with it. This is important to
prevent possible personal injury or fire hazard.
For questions, please call your distributor or
the manufacturer. Special restrictions apply to
the front and facing of the fireplace and nearby
walls (See pages 16, 17 and 18 ).
CHIMNEY SYSTEM
These fireplaces are designed and code listed
for use with Security Chimneys FTF8 chimney
System only. Always use Security Chimneys
FTF8 chimney components with these fire-
places. Do not modify or alter these compo-
nents as this may cause a potential serious
hazard and void the Warranty.
**Note: 2" clearance to combustibles around
chimney components required in Canada.
WARNING: MODELS THAT HAVE THE
"-2" SUFFIX HAVE NOT BEEN TESTED
WITH AN UNVENTED GAS LOG SET. TO
REDUCE RISK OF FIRE OR INJURY, DO
NOT INSTALL AN UNVENTED GAS LOG
SET INTO THIS FIREPLACE.
Outside
Combustion
Air Kit
(Optional)
Chimney and
Termination
Radiant Model Shown
The "C" models are designed as heat circulating
fireplaces and may be fitted with accessory
fans.
The BRI and BCI models are fully insulated for
installation in colder climates.
WARNING: FAILURE TO USE MANUFAC-
TURE PROVIDED PARTS, VARIATIONS
IN TECHNIQUES AND CONSTRUCTION
MATERIALS OR PRACTICES OTHER THAN
THOSE DESCRIBED IN THIS MANUAL
MAY CREATE A FIRE HAZARD AND VOID
THE LIMITED WARRANTY.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
4
WARNING: IF INSULATION IS USED, THE
FIREPLACE MUST NOT BE PLACED DI-
RECTLY AGAINST IT. INSULATION OR
VAPOR BARRIERS, IF USED, MUST FIRST
BE COVERED WITH GYPSUM BOARD,
PLYWOOD, PARTICLE BOARD OR OTHER
MATERIAL TO ASSURE INSULATION AND
VAPOR BARRIERS REMAIN IN PLACE.
Figure 2
Chimney Height
The total height of your completed fireplace
system from the surface the fireplace rests on
to the chimney top must not exceed 60' and
must also meet minimum height requirements.
Refer to the minimum system height chart.
LOCATION OF FIREPLACE
Carefully select the proper location for heat
circulation, aesthetics, chimney obstructions
and clearance to side wall(s). With proper pre-
planning, a slight adjustment of a few inches
can save considerable time and expense later
during construction and assembly.
Figure 4
Carefully consider the position of the fireplace
opening with respect to the location of adja-
cent or nearby stairwells, bath or kitchen ex-
haust fans and/or return air registers for forced
air furnaces/air conditioners that could cause
a smoking fireplace condition if the house is
tightly insulated.
When locating the fireplace, consideration must
be given to combustibles and final finishing.
See
Figure 5
and confine the final location of
combustible finish materials to the "Safe Zone".
DO NOT permanently place furniture or other
items such as decorative pillows within 60" of
the fireplace front face.
Insulate Joists
Same As Ceiling
Draft Stops
Firestop
CTDT
Termination
Note: Non-
Combustible
Chase
Flashing
Must Be
Used To
Cover
Chase
Opening
Optional
Insulation
In Outside
Walls Of
Chase
Solid
Continuous
Surface
Outside
Base
Insulation
(Thermal Barrier)
8'
Level
Chase Enclosure
A chase is a vertical box-like structure con-
structed to surround the fireplace and chimney.
Refer to
Figure 2
for a typical chase configura-
tion. As with all chimney installations, avoid
overhead obstructions such as trees, power
lines, etc. A chase should be constructed and
insulated just like any outside wall. In a cold
climate, we recommend the base of the chase
should also be insulated between the solid
continuous floor beneath the fireplace and the
chase bottom. Chase insulation in a cold cli-
mate installation is not required for safety.
ASSEMBLY OUTLINE
Before You Start
Check your inventory list to be sure you have all
the necessary parts supplied in good usable
condition. Check also for any concealed damage.
Check the operation of the damper. The damper
is controlled through the use of a control lever
located within the firebox opening at the top
center in front of the firebox lintel (
Figure 3
).
The control lever snaps into place at either
extreme of its range of motion. When locked
in position all the way to the right, the damper
is open. When locked in position all the way to
the left, the damper is closed.
Figure 3
Note: Do not insulate the chase cavity with
blown or fill type insulation materials.
Note: Local codes may not require firestopping
at the ceiling levels for outside chase installa-
tions. However, it is recommended for safety
and the reduction of heat loss.
WARNING: DO NOT PACK OR FILL RE-
QUIRED AIR SPACES WITH INSULATION
OR OTHER MATERIAL. NO MATERIAL IS
ALLOWED IN THESE AREAS.
Damper
Closed Damper
Open
Lintel
Combustion
Air Actuator
Figure 5
Hearth
Hearth
Optional
Outside Chase
Wall
Covering
Black Portion Of Frame
Not To Be Covered With
Combustible Materials
Safe
Zone
45°
12”
12”
Door
Opening
1”
Security's FTF8 Pipe
Vertical Installation 15' 0"
One Offsets 15' 0"
Two Offsets 25' 0"
Minimum System Height
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 5
Note: Install the hearth extension only as illus-
trated.
The safety strips should extend from front of
the fireplace at least 1 ¹⁄₂" and should extend to
be at least flush with the sides. In the event a
wooden support is used to elevate the fireplace
above the floor, a “Z” type safety strip should be
fabricated and used to protect the front surface
of the wood support as well as the floor beneath
the hearth extension (
Figures 8 and 9
). The
safety strips should be tacked down to prevent
possible movement.
Note: The “Z” type safety strip is not supplied.
1. Estimate the total weight of the fireplace
system including chimney and surround ma-
terials such as brick, stone, etc., to be in-
stalled. Shipping weights for the fireplace
may be found on page 18.
2. Measure the square footage of the floor
space to be occupied by the system, surrounds
and hearth extensions.
3. Note the floor construction, i.e. 2 x 6’s, 2 x 8’s
or 2 x 10’s, single or double joists, type and
thickness of floor boards.
4. Use this information and consult your local
building code to determine if you need addi-
tional support.
CAUTION: DO NOT BLOCK THE HEAT-CIRCU-
LATING AIR INLET AND OUTLET PORTS ON
CIRCULATING MODELS. DOING SO MAY RE-
SULT IN A POTENTIAL FIRE HAZARD.
If you plan to raise the fireplace and hearth
extension, build the platform assembly then
position fireplace and hearth extension on top.
Secure the platform to the floor to prevent
possible shifting.
CLEARANCES
Minimum clearance to combustibles for the
appliance is as follows: sides and back - 1" (25
mm), floor - 0" (0 mm), adjacent wall - 12" (305
mm), ceiling - 37 ¹⁄₂" (953 mm).
INSTALLING THE FIREPLACE
Step 1. Slide the fireplace into prepared fram-
ing or position fireplace in its final position and
frame later.
The fireplace may not be recessed into a com-
bustible floor. Maintain the floor to hearth clear-
ance established by the fireplace lower front
face.
Step 2. Insert the provided metal safety strips,
beneath the fireplace as illustrated (
Figures 6, 7
and 8
). The safety strips should overlap ¹⁄₂" for
continual coverage of the floor.
Note: Safety strips are not required when fire-
place rests on a noncombustible surface.
ASSEMBLY STEPS
Note: The following steps represent the normal
sequence of installation. Each installation is
unique, however, and might require a different
sequence.
1. Position firebox prior to framing or into
prepared framing.
2. Install the chimney system.
3. Connect house wiring to the fireplace for
later attachment of optional blower.
4. Install optional outside combustion air kit.
5. Plumb gas line if a decorative gas appliance
will be used. (Gas connections should only be
performed by an experienced, licensed/certi-
fied tradesman.)
6. Complete the installation, finish wall mate-
rial, surround and hearth extension to your
individual taste.
7. Assemble and attach optional glass door
assembly.
Study the three dimensional illustration (
Fig-
ure 1
) to get a general idea of each element of
your fireplace system.
PRE-INSTALLATION NOTES
The fireplace may be installed directly on a
combustible floor or raised on a platform of an
appropriate height. Do not place fireplace on
carpeting, vinyl or other soft floor coverings. It
may, however, be placed on flat wood, ply-
wood, particle board or other hard surfaces.
Be sure fireplace rests on a solid continuous
floor or platform with appropriate framing for
support and so that no cold air can enter the
room from under the fireplace.
The fireplace may be positioned and then the
framing built around it, or the framing may be
constructed and the fireplace positioned into
the opening.
Usually, no special floor support is needed for
the fireplace, however, to be certain:
Figure 7
Figure 6
1" (25 mm) Space
Metal Safety Strip Floor
Hearth
Extension
Maintain
1" (25 mm)
Air Space
At Back
And Sides
Top Spacer
Note: Hearth extensions must not interfere with
circulating grillwork
Metal Safety Strip Floor
Hearth
Extension
Platform
1" (25 mm) Space
Maintain
1" (25 mm)
Air Space
At Back
And Sides
Note: Hearth extensions must not interfere with
circulating grillwork
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
6
FIREPLACE SPECIFICATIONS
Figure 10
Figure 8
Figure 9
Step 3. Refer to fireplace drawings and specifi-
cations on pages 6 and 7 for framing dimensions
and details. Frame appliance enclosure as illus-
trated in
Figures 11 through 14
on page 8.
IMPORTANT: UNDER NO CIRCUMSTANCES
CAN THE FIREPLACE TOP SPACERS (
FIGURE
10
) BE REMOVED OR MODIFIED, NOR MAY
YOU NOTCH THE HEADER TO FIT AROUND OR
BE INSTALLED LOWER THAN THE SPACERS.
THE HEADER MAY BE IN DIRECT CONTACT
WITH THE TOP SPACERS BUT MAY NOT BE
SUPPORTED BY THEM.
Note: The framed depth, 20
⁵⁄₈
" (524 mm) from
a framed wall, must always be measured from
a finished surface. If a wall covering such as
drywall is to be attached to the rear wall, then
the 20
⁵⁄₈
" (524 mm) must be measured from
the drywall surface. It is important that this
dimension be exact.
If the appliance is to be elevated above floor
level, a solid continuous platform must be
constructed.
The header may rest on the top metal spacers,
but must not be notched to fit around them.
Consult all local codes.
45"
(1143 mm)
31 ⁹⁄₁₆"
(802 mm)
21 ¹⁄₄"
(540 mm)
8 ³⁄₁₆"
(208 mm)
Top View
Right Side
Gas Line
Access Junction
Box
Combustion
Air Inlet
9 ⁷⁄₈"
(251 mm)
43"
(1092 mm)
21 ¹⁄₄"
(540 mm)
43"
(1092 mm)
21 ¹⁄₄"
(540 mm)
Left Side
45"
(1143 mm)
Front
43"
(1092 mm)
7 ³⁄₁₆"
(183 mm)
41"
(1041 mm)
2"
(51 mm)
12 ¹⁄₂"
(318 mm)
22 ⁵⁄₁₆"
(566 mm)
13 ⁷⁄₁₆"
(341 mm)
8 ³⁄₈"
(213 mm)
Fireplace Top Spacer
Fireplace
Top Spacer
Gas Line
Access 19"
(483 mm)
10"
(254 mm)
12 ¹⁄₂"
(318 mm)
47"
(1194 mm)
1"
(25 mm)
38"
(965 mm)
Blocking
Metal Safety Strips
Metal Safety Strips
1 ¹⁄₂"
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 7
FRAMING SPECIFICATIONS
Figure 11
Figure 12
Figure 13
Figure 15
Figure 16
Figure 14
Framing Dimensions
A46 ¹⁄₄" 1175 mm
B43 ¹⁄₂" 1105 mm
C33" 838 mm
D17 ¹⁄₂" 445 mm
E76 ¹⁄₄" 1937 mm
F38 ¹⁄₈" 968 mm
G21 ⁵⁄₈" 549 mm
H20 ⁵⁄₈" 524 mm
J53 ⁷⁄₈" 1368 mm
Framing Dimensions for Roof
FTF8 at 1" FTF8 at 2"
Pitch C D* C D*
0/12 14 ¹⁄₂" 14 ¹⁄₂" 16 ¹⁄₂" 16 ¹⁄₂"
(368 mm) (368 mm) (419 mm) (419 mm)
6/12 14 ¹⁄₂" 17" 16 ¹⁄₂" 19"
(368 mm) (442 mm) (419 mm) (483 mm)
12/12 14 ¹⁄₂" 21 ¹⁄₂" 16 ¹⁄₂" 23 ¹⁄₂"
(368 mm) (546 mm) (419 mm) (579 mm)
A
G
Inside Chase
H
Back Wall of Chase/Enclosure
Including Finising Materials if any
Rough
Framing Face
(Unfinished Shown)
FOAK Combustion
Air Kit
A
Outside Chase
G
C
H
Back Wall of Chase/Enclosure
Including Finising Materials
if any
Rough
Framing Face
(Unfinished Shown)
FOAK
Combustion
Air Kit - Optional
Note: All framing dimensions calcu-
lated for 1/2" dry wall at the fireplace
face. If sheathing the chase or finish-
ing with other thickness materials,
calculations will need to be made.
* Perpendicular to roof ridge
Corner Installation
J
D
A
E
F
Back Wall of
Chase/Enclosure
Including Finising
Materials
if any
Rough
Framing Face
(Unfinished Shown)
FOAK Combustion
Air Kit - Optional
A
B
Ceiling Framing
C
D
Roof Framing
Header
Fireplace Framing
B
A
(See Note)
Note: When Framing With 6” Studs Header Must
Be 17” (432mm) Higher. Use Security Chimney’s
OR15 Offset/Return Elbow To Recess The Chimney
Back 2 1/2” (64mm). Flat Frame Down To A False
Header At (B). Maintain Required Clearance To
Chimney At All Times.
Framing Dimensions for Ceiling
Flue Type A B
FTF8 Vertical 14 ¹⁄₂" 14 ¹⁄₂"
(368 mm) (368 mm)
FTF8 Vertical 16 ¹⁄₂" 16 ¹⁄₂"
at 2" (419 mm) (419 mm)
FTF8 Offset 30°14 ¹⁄₂" 25"
(368 mm) (635 mm)
FTF8 Offset 30°16 ¹⁄₂" 27"
at 2" (419 mm) (686 mm)
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
8
Step 4. Fireplace should be secured to side
framing members using the full length nailing
tabs at the top and bottom of the fireplace front
face. Use 8d nails (
Figure 17
).
Figure 17
Note: The nailing tabs and the area directly
behind the nailing tabs are exempt from the
clearances described on page 5. Maintain at
least 1/2" clearance from the firebox wrapper to
the framing at the closest point of contact,
directly adjacent to the flange.
For Canadian Installations
A cold Climate Kit FTF8-CCK3-LD must be
installed. CCK3 kits are available from
FireCraft through your local dealer. Installer
must supply suitable length of 6" Diameter,
class "0" metallic air duct.
Proceed with Steps 5 through 8
Step 5. Install the Cold Climate Kit to the
fireplace following the instructions provided
with the kit, (
Figure 18
).
8d Nail
Figure 20
Step 3. Position appropriate firestop spacer at
ceiling and nail temporarily with two (2) 8d
nails. Use flat firestop spacer, Model F8FS-2, if
chimney penetrates ceiling vertically. If chim-
ney penetrates ceiling at 30° angle (offset chim-
ney), use 30° firestop spacer, Model F8FS30.
Use one nail on opposite sides to hold firestop
spacer in position. Nail permanently, using at
least two (2) more 8d nails, after chimney
sections have been assembled through the
firestop spacer and after any necessary adjust-
ments have been made. Firestop spacer must
be secured by at least four (4) 8d nails when
completely installed.
CAUTION: ALLOW MINIMUM 1"* CHIMNEY
AIR SPACE TO COMBUSTIBLE FRAMING MEM-
BERS THROUGHOUT VERTICAL OR OFFSET
CHIMNEY INSTALLATION.
A minimum 1"* air space must be reserved for
all combustible materials extending for any
continuous length surrounding the chimney.
*Note: 2" clearance to combustibles required
in Canada.
Reference
Figures 15 and 16
and charts Fram-
ing Dimensions for Ceiling and Roof, which
specify minimum ceiling and roof dimensions.
In new construction, to determine chimney cen-
ter line, use plumb line from roof or ceiling above
fireplace to center of flue collar on fireplace.
For remodeling, plumb to center of flue collar
from ceiling above, drive nail through ceiling
from below to mark position, then mark and cut
to passage from above ceiling (around nail)
(
Figure 20
). Then plumb from ceiling or roof
level directly above hole which has just been
completed.
Figure 18
Step 6. Connect the 6" (102 mm) Class 0 air
duct provided by installer, to the duct collar on
the fireplace and secure with two (2) screws
from the kit’s hardware package.
Step 7. Route the Class 0 air duct out the back
or side wall, up through the ceiling or floor
joists to an outside wall. The air inlet hood
should be located above snow level or above
any anticipated snow level, (
Figure 19
).
Figure 19
Note: If the fireplace is installed against an inside
wall, the class 0 air duct may be extended into a
ventilated attic space at least 18" (475mm) above
the attic floor. Secure the air inlet hood to a
vertical post with the inlet positioned downward.
Ensure that nothing blocks the hood opening.
This hood must never terminate higher than
three (3) feet below the termination.
Step 8. Cut or frame a hole through the outside
wall for the installation of the air inlet hood. A 6-
1/2" diameter hole is required. Feed the loose
end of the flexible duct through the hole and
attach to the collar on the air inlet hood using two
(2) screws from the kit's hardware package.
Insert the hood into the opening. Secure the inlet
hood in place with nails driven through the holes
in the flange. Seal with noncombustible water-
proof silicon type caulking.
INSTALLING THE CHIMNEY SYSTEM
Step 1. Before continuing, check the operation
of the damper, as described on page 4, (
refer to
Figure 3
).
Step 2. Using standard construction framing
techniques, construct opening for chimney route
up through the ceiling(s) and roof or through an
outside chase.
Framing must maintain adequate minimum air
space clearance at all times.
Install As Shown With
Opening In Downward
Position Do Not Block
Entrance
5 Foot Min. Height
From Outside
Ground Level
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 9
Note: If there is a room above ceiling level,
firestop spacer must be installed on the bottom
side of the ceiling. If an attic is above ceiling
level, firestop spacer must be installed on top
side of ceiling joist (Figures 21 and 22 ).
Figure 21
Figure 22
CHIMNEY 30° OFFSET THROUGH FLOOR
OR CEILING
It may be necessary to assemble the chimney at
30° when passing through the floor or ceiling
area. Use the F8FS30 firestop spacer as shown
in
Figures 23 and 24
. Support the chimney at
floor or ceiling penetration with a FTF8 stabi-
lizer if distance of chimney below ceiling is 10'
or more. Maintain 1"* minimum air space to
combustibles from chimney sections.
*Note: 2" clearance to combustibles required
in Canada.
Firestop Spacer
Room Above
Firestop Spacer
Attic Above
F8FS30
Firestop Spacer
FTF8-S4 Stabilizer
1"* Min.
Air Space
30° Firestop
And Attic Above
10'
Max.
Attic Space
1"* Min.
Air Space
Figure 23
F8FS30
Firestop Spacer
FTF8-S4 Stabilizer
30° Firestop
And Room Above
10'
Max.
Room Above
1"* Min.
Air Space
1"* Min.
Air Space
Figure 24
For Canada Only
When installing the chimney system through
an open attic space, the attic shield assembly-
firestop spacer must be used (
Figure 25
). This
installation is required only for use in Canada.
Note: For Canadian installations, all chimney
installed outside the building must be constructed
with galvalume (outer sections only) effective
January 1, 1992. The appropriate model desig-
nations are located in the back of this manual.
Step 4.
Note:
Chimney sections are con-
structed with a unique locking tab design,
which ensures an immediate, tight assembly
between sections. Plan your chimney require-
ments carefully before assembly as chimney
is difficult to disassemble after installation. If
disassembled, the tabs might become dam-
aged. Be certain tabs are properly formed to
ensure locking tabs engage properly.
The Security Chimneys FTF8 chimney system
is a two piece chimney, which snap together
from the fireplace up. Start with the inner flue
section with the lanced end up, snap lock it in to
the matching collar on top of the fireplace. At all
subsequent joints, the upper flue section fits
into the preceding flue section. Each piece
snaps together by means of locking tabs (9
locking tabs per joint). Check each piece by
pulling up slightly from the top to ensure proper
engagement before installing the next section.
Figure 25
Open Attic Space
If the flue has been installed correctly, it will not
separate when you test it. Also, the inner flue
joint where each section is joined should be
tight and flat without gaps (
Figure 26
).
Figure 26
Outer pipe section installs in just the opposite
way; the lanced end goes down and each new
section goes OVER the outside of the previous
section installed (
Figure 27
).
Figure 27
Note: Assemble one component of chimney at a
time (inner section first, then outer section last)
before proceeding with the next complete section.
Continue to assemble the chimney up through
framed opening. Assemble just enough to pen-
etrate the roof flashing openings (
Figure 28
).
Always maintain 1"* minimum air space to
combustible materials and always check each
chimney joint (inner and outer) to ensure proper
engagement. Check vertical alignment of chim-
ney so that it projects from the roof in true
vertical position.
Figure 28
Locking
Tabs
(Lances)
1"* Min. Air Space
To Combustibles
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
10
Next, slide roof flashing over extended chimney
section that previously has been installed above
the roof opening in Step 4. FTF8 flashings
require flashing spacers. Slide flashing all the
way down until the flashing base rests flat on
the roof (
Figure 30
). Again, check the vertical
position of the chimney and the 1"* minimum
air space to combustibles.
Figure 30
Note: Do not caulk or seal the ventilating
openings.
Step 7. Secure flashing by nailing along the
perimeter into roof using 8d nails. If shingled
roof, slide upper end and sides of roof flashing
under shingles (trim if necessary), seal the top
and both sides of the flashing to the roof with
roof caulking. Cover nail heads with roof caulk-
ing (
Figure 31
).
Figure 31
Step 8. The standard Security Chimneys FTF8
roof flashing assemblies include a storm col-
lar. Slide the storm collar over outer chimney,
rest on flashing spacers and align with top
surface of flashing. Insert tab in slot, pull tight
and bend tab back over slot. Seal storm collar
to outer chimney with roof caulking or mastic
around entire circumference of pipe. Also add
extra roof caulking to the tab/slot area to seal
completely against water penetration (
Figure
32
). Check all joints very carefully to ensure
no water intrusion can take place.
Locking Band
Mastic
Figure 32
Step 9. Security Chimneys locking bands,
Model FLB, may be required if the chimney
extends too high above the roof flashing. As a
general rule, if the chimney extends more than
6' above the roof flashing, the use of locking
bands is advisable to strengthen the chimney
assembly. Align the locking band at the chim-
ney joint. Locking bands wrap around pipe
joints equally covering the joints of both pipe
sections. Use the nut provided and TIGHTEN
snugly. Do not overtighten as this might dam-
age the chimney section (
refer to Figure 32
).
Note: If chimney extends more than 8' above
roof surface, guy wires are also recommended.
Use three (3) guy wires, attach to locking band
assembly, extend and secure to roof in a trian-
gular pattern (Figure 33 ). Guy wires are not
supplied by the manufacturer.
Roof Ridge
120°
Figure 33
Step 10. Using a FTF8-CTD Round Termination:
1. Hold the FTF8-CTD over top of last chimney
section (
see Figure 34
).
2. Center inner slip section in inner flue pipe-
slip down.
3. Center outer locking section over outer flue
pipe. Push down until locking tabs are firmly
engaged.
Security's chimney sections do not need to be
screwed together. Additional reinforcement is
not necessary except in certain offset condi-
tions (refer to page 14,
Figure 39
).
Step 5. The height of vertical chimney pipe
supported only by the fireplace must not ex-
ceed 30'. Chimney heights above 30' must be
supported by a Model FTF8-S4 stabilizer in-
stalled at 30' intervals.
Note: The Model FTF8-S4 adds 3" net effective
height to the total chimney system.
Install the Model FTF8-S4 stabilizer by fitting
inner section down into respective section of
proceeding flue pipe and locking outer stabi-
lizer section into place over the outer chimney
pipe. Position for proper clearance through
framed opening and nail straps securely (under
tension in “shear”) into place on framing. Use
8d nails. Attach successive lengths of chimney
pipe directly to stabilizer using same tech-
niques as described in Step 4 (
Figure 29
).
Figure 29
Note: Do not apply excessive pressure to any
subsequent chimney sections following the
stabilizer when installing. Ensure each subse-
quent chimney section is securely attached by
testing as noted in Step 4.
Step 6. Select the proper Security Chimneys
roof flashing based on pitch of roof. Use chart
below for selection:
Roof Pitch Model
Flat to 6/12 F8F6
6/12 to 12/12 F8F12
FTF8-S4 Stabilizer
*Note: 2" clearance to combustibles required
in Canada.
FTF8 Chimney
FTF8 Flashing
Flashing Spacers
Do Not Seal
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 11
Figure 34
4. Pull up slightly on CTD to ensure locking joint
has firmly engaged.
Using a FTF8-CTDT Chase Termination:
Refer to specific installation instructions in-
cluded with the FTF8-CTDT chase termination
for clearance and installation details.
Using a FTF8-CT1 Chase Termination:
Refer to specific installation instructions in-
cluded with FTF8-CT1 chase terminations for
clearance and installation details.
Using a FTF8-CT2 Chase Termination:
Refer to specific installation instructions in-
cluded with FTF8-CT2 chase terminations for
clearance and installation details.
Note: It is recommended that all exterior ex-
posed metal fireplace components; such as ter-
minations, flashings, storm collars and/or flue
be painted with a premium quality, high tem-
perature, rust preventative paint designed for
metal. This is especially important when instal-
lations are made in abnormally adverse or corro-
sive environments; such as near lakes, oceans or
in areas with consistently high humidity condi-
tions. Consult the paint manufacturers instruc-
tions for proper preparation and application.
*Note: 2" clearance to combustibles required
in Canada.
TEN FOOT RULE SUMMARY
The minimum chimney height above the roof
and/or to adjacent walls and buildings is speci-
fied by all major building codes.
If the horizontal distance from the peak of the
roof is less then 10', the top of the chimney
must be at least 2' above the peak of the roof.
If the horizontal distance from the chimney
edge to the peak of the roof is more than 10' a
chimney height reference point is established
on the roof surface 10' horizontally from the
chimney edge.
CTD
Termination Chimney
Figure 35
The top of the chimney must be at least 2' above
this reference point. In all cases, the chimney
cannot be less then 3' above the roof at the edge
of the chimney.
The 2' in 10' rule is necessary in the interest of
safety but does not ensure smoke-free opera-
tion. Trees, buildings, adjoining roof lines, ad-
verse wind conditions, etc., may require a taller
chimney should the fireplace not draft properly
(
see Figure 35
).
MULTIPLE TERMINATIONS
If more than one termination is located in the
same chase or within the same general proxim-
ity, we suggest they should be separated in
distance at least 24" horizontally from flue cen-
ter to flue center and stacked or staggered
vertically at least 18" apart, from the termina-
tion of one smoke exit to the termination of
another smoke exit (
Figure 36
).
FTF8 CHIMNEY COMPONENT
CALCULATIONS
The minimum installed height of the com-
pleted fireplace system is 15' 0". The maxi-
mum height is 60' 0".
To determine the number of chimney sections
and chimney components required, follow
these steps:
1. Determine total vertical height of the fire-
place installation. This dimension is the dis-
tance from the surface the fireplace sets on
to the point where smoke exits from the
termination.
2. Determine the number of chimney compo-
nents required, except chimney sections. This
would include firestop spacers, stabilizers, roof
flashing, etc.
3. The effective heights of the components are:
The Fireplace = 42 ¹⁄₄"
FTF8-12 = 10 ¹⁄₄"
FTF8-18 = 16 ¹⁄₄"
FTF8-36 = 34 ¹⁄₄"
FTF8-48 = 46 ¹⁄₄"
FTF8-CTD Termination = 4"
FTF8-CT1 Termination = 12" to 18"
FTF8-CT2 Termination = 15" to 23"
FTF8-CTDT Termination = 12" to 18"
FTF8-S4 Stabilizer * = 3"*
* Required for every 30' of vertical chimney
and/or 10' of offset chimney.
CTD
18"
18"
24" 24"
CTDT
CTDT
Less Than 10'
3'
Min
2' Min.
10' 3'
Min
Figure 36
This suggestion is provided in the interest of
better operation. If the terminations are located
too close to each other, smoke may migrate
from one flue into the other.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
12
FTF8 VERTICAL ELEVATION CHART
Height Of Number Of FTF8
Chimney Only Chimney Lengths
Inches Feet/Inches 12" 18" 36" 48"
Height Of Number Of FTF8
Chimney Only Chimney Lengths
Inches Feet/Inches 12" 18" 36" 48"
386 ¹⁄₂ 32 2 ¹⁄₂ 0108
390 ³⁄₄ 32 6 ³⁄₄ 2008
396 ³⁄₄ 33 0 ³⁄₄ 1108
404 ¹⁄₂ 33 8 ¹⁄₂ 0018
414 ³⁄₄ 34 6 ³⁄₄ 1018
416 ¹⁄₂ 34 8 ¹⁄₂ 0009
420 ³⁄₄ 35 0 ³⁄₄ 0118
426 ³⁄₄ 35 6 ³⁄₄ 1009
432 ³⁄₄ 36 0 ³⁄₄ 0109
437 36 5 2 0 0 9
443 36 11 1 1 0 9
450 ³⁄₄ 37 6 ³⁄₄ 0019
461 38 5 1 0 1 9
462 ³⁄₄ 38 6 ³⁄₄ 00010
466 ³⁄₄ 38 10 ³⁄₄ 0119
472 ³⁄₄ 39 4³⁄₄ 10010
478 ³⁄₄ 39 10 ³⁄₄ 01010
483 40 3 2 0 0 10
489 40 9 1 1 0 10
496 ³⁄₄ 41 4 ³⁄₄ 00110
507 42 3 1 0 1 10
508 ³⁄₄ 42 4 ³⁄₄ 00011
513 42 9 0 1 1 10
519 43 3 1 0 0 11
525 43 9 0 1 0 11
529 ¹⁄₄ 44 1 ¹⁄₄ 20011
535 ¹⁄₄ 44 7 ¹⁄₄ 11011
543 45 3 0 0 1 11
553 ¹⁄₄ 46 1 ¹⁄₄ 10111
555 46 3 0 0 0 12
559 ¹⁄₄ 46 7 ¹⁄₄ 01111
565 ¹⁄₄ 47 1 ¹⁄₄ 10012
571 ¹⁄₄ 47 5 ¹⁄₄ 01012
575 ¹⁄₂ 47 11 ¹⁄₂ 20012
581 ¹⁄₂ 48 5 ¹⁄₂ 11012
589 ¹⁄₄ 49 1 ¹⁄₄ 00112
599 ¹⁄₂ 49 11 ¹⁄₂ 10112
601 ¹⁄₄ 50 1 ¹⁄₄ 00013
605 ¹⁄₂ 50 5 ¹⁄₂ 01112
611 ¹⁄₂ 51 11 ¹⁄₂ 10013
617 ¹⁄₂ 51 5 ¹⁄₂ 01013
621 ¹⁄₂ 51 9 ¹⁄₂ 20013
627 ¹⁄₂ 52 3 ¹⁄₂ 11013
635 ¹⁄₂ 52 11 ¹⁄₂ 00113
645 ¹⁄₂ 53 9 ¹⁄₂ 10113
647 ¹⁄₂ 53 11 ¹⁄₂ 00014
651 ¹⁄₂ 54 3 ¹⁄₂ 01113
657 ¹⁄₂ 54 9 ¹⁄₂ 10014
663 ¹⁄₂ 55 3 ¹⁄₂ 01014
667 ³⁄₄ 55 7 ³⁄₄ 20014
673 ³⁄₄ 56 1 ³⁄₄ 11014
681 ¹⁄₂ 56 9 ¹⁄₂ 00114
691 ³⁄₄ 57 7 ³⁄₄ 10114
693 ¹⁄₂ 57 9 ¹⁄₂ 00015
697 ³⁄₄ 58 1 ³⁄₄ 01114
703 ³⁄₄ 58 7 ³⁄₄ 10015
709 ³⁄₄ 59 1 ³⁄₄ 01015
714 59 6 2 0 0 15
720 60 0 1 1 0 15
727 ³⁄₄ 60 7 ³⁄₄ 00115
738 61 6 1 0 1 15
739 ³⁄₄ 61 7 ³⁄₄ 00016
744 62 0 0 1 1 15
11 0 11 1 0 0 0
17 1 5 0 1 0 0
21 ¹⁄₄ 19¹⁄₄ 2000
27 ¹⁄₄ 23¹⁄₄ 1100
35 2 11 0 0 1 0
47 3 11 0 0 0 1
51 ¹⁄₄ 43¹⁄₄ 0110
57 ¹⁄₄ 49¹⁄₄ 1001
63 ¹⁄₄ 53¹⁄₄ 0101
67 ¹⁄₄ 57¹⁄₄ 2001
73 ¹⁄₄ 61¹⁄₄ 1101
81 ¹⁄₄ 69¹⁄₄ 0011
93 ¹⁄₄ 79¹⁄₄ 0002
97 ¹⁄₄ 81¹⁄₄ 0111
102 ¹⁄₂ 86¹⁄₂ 1002
109 ¹⁄₄ 91¹⁄₄ 0102
113 ¹⁄₂ 95¹⁄₂ 2002
119 ¹⁄₂ 911¹⁄₂ 1102
127 ¹⁄₄ 10 7 ¹⁄₄ 0012
137 ¹⁄₂ 11 5 ¹⁄₂ 1012
139 ¹⁄₄ 11 7 ¹⁄₄ 0003
143 ¹⁄₂ 11 11 ¹⁄₂ 0112
149 ¹⁄₂ 12 5 ¹⁄₂ 1003
155 ¹⁄₂ 12 11 ¹⁄₂ 0103
159 ³⁄₄ 13 3 ³⁄₄ 2003
165 ³⁄₄ 13 9 ³⁄₄ 1103
173 ¹⁄₂ 14 5 ¹⁄₂ 0013
183 ³⁄₄ 15 3 ³⁄₄ 1013
185 ¹⁄₂ 15 5 ¹⁄₂ 0004
189 ³⁄₄ 15 9 ³⁄₄ 0113
195 ³⁄₄ 16 3 ³⁄₄ 1004
201 ³⁄₄ 16 9 ³⁄₄ 0104
206 17 2 2 0 0 4
212 17 8 1 1 0 4
219 ³⁄₄ 18 3 ³⁄₄ 0014
230 19 2 1 0 1 4
231 ³⁄₄ 19 3 ³⁄₄ 0005
236 19 8 0 1 1 4
242 20 2 1 0 0 5
248 20 8 0 1 0 5
252 21 0 2 0 0 5
258 21 6 1 1 0 5
266 22 2 0 0 1 5
276 23 0 1 0 1 5
278 23 2 0 0 0 6
282 23 6 0 1 1 5
288 24 0 1 0 0 6
294 ³⁄₄ 24 6 ³⁄₄ 0106
298 ¹⁄₄ 24 10 ¹⁄₄ 2006
304 ¹⁄₄ 25 4 ¹⁄₄ 1106
312 26 0 0 0 1 6
322 ¹⁄₄ 26 10 ¹⁄₄ 1016
324 27 0 0 0 0 7
328 ¹⁄₄ 27 4 ¹⁄₄ 0116
334 ¹⁄₄ 27 10 ¹⁄₄ 1007
340 ¹⁄₄ 28 4 ¹⁄₄ 0107
344 ¹⁄₂ 28 8 ¹⁄₂ 2007
350 ¹⁄₂ 29 2 ¹⁄₂ 1107
358 ¹⁄₄ 29 10 ¹⁄₄ 0017
368 ¹⁄₂ 30 8 ¹⁄₂ 1017
370 ¹⁄₄ 30 10 ¹⁄₄ 0008
374 ¹⁄₂ 31 2 ¹⁄₂ 0117
380 ¹⁄₂ 31 8 ¹⁄₂ 1008
Step 2. Use “Height of Chimney Only” column
in The Vertical Elevation Chart to determine
combinations of chimney used above return
elbow to achieve desired heights. Reference
Components Effective Height Chart in vertical
elevation chart section.
4. Determine amount of chimney height re-
quired by subtracting total combined height of
all pre-selected components (fireplace and
chimney components from total desired height.)
Reference Vertical Elevation Chart and deter-
mine the number of chimney sections (quantity
and length) required.
SPECIAL OFFSET INSTRUCTIONS
To clear any overhead obstructions, you may
offset your chimney system using Security's
30° offset and return elbows. Use two elbows -
an offset elbow to initiate the offset and a return
elbow to terminate it. A 30° offset elbow, an-
gling in any direction, may be the first compo-
nent used off the top of the fireplace flue collar.
The offset and return elbows may be attached
together, or a section or sections of chimney
may be used between, but do not exceed 20' in
total length between elbows. If sections of pipe
exceed 10' between elbows, a chimney stabi-
lizer must be used at the midpoint (
Figure 37
).
The stabilizer support straps must be attached
under tension (in shear) to structural framing
members above. When two sets of elbows are
used, the maximum combined length of chim-
ney used between elbows cannot exceed 20'
(
Figure 38
). Example: If C1 = 10' then C2 cannot
exceed 10'.
If an offset exceeds 6' in length, each chimney
joint beyond the first 6' of offset to the return
elbow, must be secured by a No. 8 x ¹⁄₂" sheet
metal screw located at the underside of the joint
(
Figure 39
).
A ¹⁄₈" diameter hole must be drilled in the
chimney joint using a ¹⁄₈" diameter drill. Hole
should be drilled in center of joint overlap
(
Figure 40
). Be sure to drill only through the
outer chimney casting. Do not puncture the
inner flue.
Maximum offset of chimney system is 30°. Two
offsets must not be assembled to form a 60° offset.
However, two sets of offset and return elbows may
be used on a single flue system, provided the total
height of the system exceeds 25'.
Return elbow support straps must be securely
attached under tension (in shear) to structural
framing members above. Do not substitute a
FTF8-30 offset elbow in place of a FTF8-E30
return elbow.
OFFSET CALCULATIONS
Step 1. Use Offset Chart to determine amount
of horizontal offset (A) and height (B) for vari-
ous chimney section assemblies.
Step 3. Use Elevation Chart as job estimator
only. Add necessary firestop spacers and sta-
bilizers as required. Firestop spacers must be
used as shown in
Figures 23 and 24
and
stabilizers as shown in
Figure 29
.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 13
A B FTF8-ES30 Number of FTF8 Chimney Sections
Offset Height Offset/Return FTF8-S4
(Inches) (Inches) Elbow Stabilizer 12" 18" 38" 48"
415³⁄₄ 100000
924¹⁄₂ 101000
12 29 ³⁄₄ 100100
14 ¹⁄₄ 33 ¹⁄₂ 102000
17 ¹⁄₄ 38 ¹⁄₂ 101100
20 ¹⁄₄ 43 ³⁄₄ 100200
21 45 ¹⁄₄ 1 0 0010
22 ¹⁄₄ 47 ¹⁄₂ 1 0 2 1 0 0
25 ¹⁄₄ 52 ¹⁄₂ 1 0 1 2 0 0
26 ¹⁄₄ 54 ¹⁄₄ 101010
27 55 ³⁄₄ 100001
28 ¹⁄₄ 57 ³⁄₄ 1 0 0 3 0 0
29 ¹⁄₄ 59 ¹⁄₄ 100110
31 ¹⁄₄ 63 1 0 2010
32 ¹⁄₄ 64 ¹⁄₂ 101001
34 ¹⁄₄ 68 ¹⁄₄ 1 0 1110
35 ¹⁄₄ 69 ³⁄₄ 100101
37 ¹⁄₄ 73 ¹⁄₄ 100210
38 ¹⁄₄ 75 1 0 0 0 2 0
39 ¹⁄₄ 77 1 0 2110
41 ¹⁄₂ 80 ¹⁄₂ 101400
43 ¹⁄₄ 83 ³⁄₄ 1 0 1 0 2 0
44 ¹⁄₄ 85 ¹⁄₄ 100011
45 ¹⁄₄ 87 ¹⁄₂ 1 0 0 3 1 0
46 ¹⁄₄ 89 1 0 0 1 2 0
48 ¹⁄₄ 91 ¹⁄₂ 1 0 2 0 2 0
49 ¹⁄₄ 94 ¹⁄₄ 101011
50 ¹⁄₄ 95 ³⁄₄ 100002
51 ¹⁄₄ 97 ³⁄₄ 1 0 1 1 2 0
54 ¹⁄₄ 103 1 0 0 2 2 0
55 ¹⁄₄ 104 ¹⁄₂ 101002
56 ¹⁄₂ 106 ¹⁄₂ 1 0 2 1 2 0
58 ¹⁄₄ 109 ³⁄₄ 100102
61 ³⁄₄ 116 1 1 1 0 3 0
64 ³⁄₄ 121 ¹⁄₄ 110130
67 124 ³⁄₄ 112030
68 ³⁄₄ 128 1 1 0 0 1 2
70 130 1 1 1 1 3 0
73 135 ¹⁄₄ 1 1 0230
74 ³⁄₄ 138 ¹⁄₄ 110003
79 145 ¹⁄₂ 1 1 1 0 4 0
80 147 ¹⁄₄ 1 1 1 0 0 3
82 150 ³⁄₄ 1 1 0 1 4 0
82 ¹⁄₄ 152 1 1 0 1 0 3
Figure 38
Figure 37
OFFSET ELEVATION CHART
Stabilizer
A
1
20'
Max.
B
1
10' Max.
Offset
Elbow
Return
Elbow
A
1
C
1
B
1
B
2
C
2
A
2
A
1
C
1
B
1
B
2
C
2
A
2
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
14
Figure 43
HOUSE
WIRING
COVER PLATE
Replace Cover Plate
After Electrical
Hook-Up
POWER TO THE FIREPLACE
The Optional Blower Kit
Operates on 115 volt 60 Hz
150 watts AC
GROUND
WIRE
House Wiring Must Be Secured
With The Appropriate Electrical
Connector To The Fireplace
Convenience Outlet Wiring
Measure height to the ceiling from the top of
fireplace-dimension “B.” Use the appropriate
Offset Elevation Chart to find dimension “A.”
Mark point where you will drive your nail to
show the center point for your offset ceiling cut.
Step 2. Proceed by using the Straight Up Instal-
lation Instructions for cutting and framing ceil-
ing and roof openings.
Note: See Framing and Dimension Chart for the
sizes of the ceiling and roof openings. The size
of the roof opening varies with the degree of
pitch of the roof.
Offset Elbow Assembly
Offset elbows install the same as chimney
sections. First, snap the inner section INTO the
preceding inner section of flue. Check connec-
tion by pulling up slightly to ensure a tight fit.
Next, the outer sections snap lock OVER the
preceding outer section of chimney. Again,
check outer section by pulling up slightly to
ensure proper connection is made.
Return Elbow Assembly
Return elbows install the same way as round
terminations and stabilizers:
Step 1. Hold return elbow over top of last
chimney section.
Step 2. Center inner slip section into inner flue
pipe-slip down.
Step 3. Center outer-locking section over outer
chimney pipe. Push down until locking joint has
firmly engaged.
Step 4. Pull up slightly on return elbow to
ensure locking joint has firmly engaged.
Step 5. Secure support straps to framing
members by nailing under tension in sheer
(
Figure 42
).
Figure 39
Figure 40
Figure 41
Chimney
Section
Joints
No. 8 x 1/2" SMS
Screws Required At
Every Joint Past 6'
No Screws Required In
Joints For First 6' of Offset
4'
6'
Underside Of Chimney
Chimney Section (S)
FTF8-E30 Return Elbow*
FTF8-30 Offset Elbow* B
A
*Part of Offset/Return Package Model FTF8-ES30
Return
Elbow
Note: The return elbow assembly performs the
same function as a stabilizer. Consider this
when determining the need for a stabilizer.
Note: Do not apply excessive pressure to any
subsequent chimney section following return
elbow assembly when installing. Ensure that
each subsequent chimney section is securely
attached by testing as noted above.
OPTIONAL EQUIPMENT
CONSIDERATIONS
Blower Kits (Circulating Models Only)
Blower Kits model FBK-100/200 are available
for use with circulating models. The Blower
Kit can be installed prior to or after installation
of the fireplace.
When installing the FBK-100 Blower Kit, a
Blower Switch Kit (Model FUBSK) is required.
This switch kit allows for a unit mounted
blower switch to be used. The FUBSK is not
included and must be purchased separately.
The FBK-200 Blower Kit comes standard with
a wall mounted variable speed control switch.
Note: The fireplace must have provisions for
a wall mounted On/Off switch in order to install
the FBK-200.
THE FIREPLACE MUST BE WIRED TO THE
HOUSE ELECTRICAL SYSTEM AT THE TIME
OF INSTALLATION IN ORDER FOR THE OP-
TIONAL FANS TO OPERATE, (SEE
FIGURES
43 AND 44
).
Note: The utilization of fans will increase the
air flow around the firebox. However, only a
minimal increase in heat output should be
anticipated.
INSTALLING OFFSETS
First, review the Offset Elevation Chart and
Figure 41
for reference.
Step 1. Determine the offset distance where
chimney is to pass through the first ceiling-
dimension “A.” To find this point on your
ceiling, first determine the center point for a
vertical chimney following the instructions for
vertical installation.
Figure 42
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 15
Figure 44
THIS FIREPLACE IS NOT INTENDED TO BE
USED AS A SUBSTITUTE FOR A FURNACE TO
HEAT AN ENTIRE HOME. USE FOR SUPPLE-
MENTARY HEATING ONLY.
The FBK-100/200 Blower Kits are design certi-
fied by Warnock Hersey for use with these
appliances.
Always check local building codes. Installation
of the FBK Blower Kits must comply with local
regulations as well as the National Electric
Code.
Combustion Air Kits
These appliances are equipped with an outside
(make-up) air door and integral actuator arm. If
the appliance is to be installed with an outside
air vent system, use only FireCraft Models
FAOK or FAOK-LD Combustion Air Kits. These
kits come complete with detailed installation
instructions and all components necessary in
completing a combustion air vent system.
After completing the installation of the optional
combustion air vent system the actuator arm
must be put in service and tested to ensure
proper operation before completing any enclo-
sure around the firebox. Failure to do so may
result in extensive and costly rework.
WARNING: DO NOT REMOVE THE AC-
TUATOR ARM LOCKING SCREW UNLESS
THE COMPLETE OUTSIDE AIR VENT SYS-
TEM HAS BEEN INSTALLED IN ACCOR-
DANCE WITH THE DETAILED INSTRUC-
TIONS PROVIDED WITH THE KIT.
Figure 45
Locate the actuator arm along the right side of
the appliance firebox opening and refer to
Figure 45
. After completing the installation of
the Outside Combustion Air Kit remove and
discard the actuator arm locking screw.
To operate, push the end of the actuator to the
left as shown in
Figure 45
, until it "pops" free of
its "locked" position. Pull the actuator forward
to open the combustion air door, and push it
back to close. To "lock" the combustion air
door closed, ensure the actuator is pushed all
the way back then push the end of the actua-
tors to the right until the step in the actuator
moves behind the appliance front face within
the slotted opening.
Operate the actuator through several cycles
including the "lock position. Ensuring proper
operation and freedom of movement. Return
the actuator arm to the locked position.
Gas Line Connection
Install a ¹⁄₂" gas supply line through fireplace
wall for connection to a decorative gas appli-
ance inside the firebox. Outside, the gas supply
line connects to a gas shut-off valve recessed
flush into the wall or floor. The valve should be
controlled by a removable valve key for safety.
Always plumb gas line installation per local
codes. Check all connections with soap suds;
leaks will bubble. Never test any gas line con-
nection with a match or open flame.
This provision is intended for connection to a
decorative gas appliance incorporating an au-
tomatic shut-off device and complying with the
Standard for Decorative Gas Appliances for
installation in vented fireplaces, ANSI Z21.60
(1991) or American Gas Association draft re-
quirements for Gas-Fired Log Lighters for Wood
Burning Fireplaces, Draft No. 4 dated August,
1993. Install in accordance with the National
Fuel Gas Code, ANSI Z223.1. This complies
with the revised U.L. 127 standard.
Remove Locking Screw
and “Pop” Actuator to the
Left Before Initial Use
Combustion Air
Actuator
Pull Forward to Open,
Push Back to Close
Vent Free Appliances
This unit has been tested and approved to
ANSI/IAS/AGA Z21.11.2 for use with unvented
gas appliances and complies with the stan-
dard for Factory-Built fireplaces, UL 127, when
installed with unvented gas log sets. Special
instructions with regards to mantle installa-
tions must be taken into consideration when
installing such appliances.
The unit has been tested for use with any
unvented log sets having a maximum rating of
32,000 BTU. The minimum mantle configura-
tion for these log sets are outlined in
Figures
46 and 47
.
Log sets with 40,000 BTU may be installed
provided that no combustible mantle projec-
tions are placed lower than 18 inches from the
fireplace opening.
These fireplaces have been marked with a
maximum rating of 32,000 BTU to assure that
homeowners do not exceed the allowable lim-
its for all allowed installations of mantles. That
limit may be increased to 40,000 BTU, pro-
vided that the mantle installed complies with
the 18-inch limitation and a copy of these
instructions are available.
NEVER INSTALL AN UNVENTED GAS LOG
SET WITH A BTU GREATER THAN 32,000 IF
COMBUSTIBLE MANTLE PROJECTIONS ARE
LOWER THAN 18 INCHES ABOVE THE FIRE-
PLACE OPENING.
BLOWER THREE
PRONGED PLUG TO
GROUNDED OUTLET
WARNING: MODELS THAT HAVE THE
"-2" SUFFIX HAVE NOT BEEN TESTED
WITH AN UNVENTED GAS LOG SET. TO
REDUCE RISK OF FIRE OR INJURY, DO
NOT INSTALL AN UNVENTED GAS LOG
SET INTO THIS FIREPLACE.
CAUTION: WHEN USING THE DECORATIVE
GAS APPLIANCE, THE FIREPLACE DAMPER
MUST BE SET IN THE FULLY OPEN POSITION.
CAUTION: PLUMBING CONNECTIONS SHOULD
ONLY BE PERFORMED BY A QUALIFIED, LI-
CENSED PLUMBER. MAIN GAS SUPPLY MUST
BE OFF WHEN PLUMBING GAS LINE TO FIRE-
PLACE OR PERFORMING SERVICE.
If you’re installing a gas line, connect it before
the fireplace is framed and enclosed in the
finished wall. The gas knockout is determined
by the indentation located at the bottom and
slightly off center in the side refractories.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
16
It is especially important to insulate between
the studs of an outside chase cavity and under
the floor if the floor is above ground level. Do
not place insulation directly against the fire-
place or chimney system.
FIREPLACE FINISHES
Mantels and Trim
It is sometimes best to frame your fireplace
after it is positioned and the chimney is in-
stalled. Frame enclosure for chimney and fire-
place with 2 x 4’s (or heavier) lumber.
Note: The header may rest on the two (2) metal
top spacers on top of the unit but the header
must not be notched to fit around the spacers.
These fireplaces may sit directly on a combus-
tible surface. A 2" air space is required be-
tween combustible framing and the chimney.
A 1" air space is required between combustible
framing and fireplace outer wrapper. In Canada,
the minimum height for a combustible mantel
is 18" (457 mm) above the fireplace opening.
Figure 46
shows typical Canadian installa-
tions. For installations other than Canada,
combustible mantels and trim may be in-
stalled 12" above the fireplace opening as per
NFPA 211, Section 7-2.3.3. and
Figure 47
. If
a mantel is of a noncombustible material, it is
exempt from these requirements as long as it
does not interfere with the installation or op-
eration of glass doors.
*Note: 2" clearance to combustibles required
in Canada.
Hearth Extensions and Wall Shields
A hearth extension must be installed with
all fireplaces. It is to protect the combustible
floor in front of the fireplace from both radiant
heat and sparks. The hearth extension must
extend 8" beyond both sides of the fireplace
opening and 16" beyond the front (
Figure 48
).
Use a hearth extension constructed of a du-
rable noncombustible material having an equal
or greater insulating value of k = .43BTU IN/FT2
HR °F or a thermal resistance that equals or
exceeds r = 2.33 HR °F FT2/BTU IN. With these
values, determine the minimum thickness/
material required using the formula and the
Table on page 17.
Note: Any noncombustible material whose k
value is less than .43 or whose r value is more
than 2.33 is acceptable.
If the fireplace is installed on a combustible
floor, use the metal safety strips (provided) on
the floor extending half under the fireplace and
half under the hearth extension (refer to
Fig-
ures 6 and 7
).
A wall shield is required where a continuous
perpendicular side wall is within 12" of the
fireplace opening, (
Figure 49
). Use a 36" x 36"
wall shield constructed of millboard or a du-
rable, noncombustible material having an equal
or greater insulating value than K = .54BTU IN/
FT2 HR °F. At no time may a perpendicular side
wall be positioned closer than 9 inches.
Figure 47
THE KNOCKOUT IS ALWAYS REMOVED FROM
INSIDE THE FIREPLACE. DO NOT REMOVE
THE KNOCKOUT UNLESS YOU ARE INSTALL-
ING A GAS LINE. If removal is attempted from
the outer wrapper, side refractory damage may
occur. With a medium-sized hammer, lightly
tap the surface of the indentation. The refrac-
tory material is very thin in this area and is easily
removed. Once a small hole has been made,
continue tapping until you have reached suffi-
cient diameter for the gas line to fit through. The
entire knockout does not have to be removed.
Remove insulation in the gas line channel.
IMPORTANT: REPACK INSULATION MATERIAL
IN SQUARE HOLE AROUND GAS LINE, INTE-
RIOR AND EXTERIOR OF FIREPLACE, TO SEAL.
Glass Doors
If glass doors are to be installed on these
fireplaces, refer to specific installation instruc-
tions packed with the glass doors. Use only the
doors that are listed for use with these fire-
places. Use of other non-listed glass door on
these fireplaces may constitute a potential fire
hazard and is not recommended.
CAUTION: CERTAIN GLASS DOORS OVERLAP
THE BLACK METAL FACING OF THE FIRE-
PLACE. IF THE FIREPLACE HAS BEEN FACED
WITH NONCOMBUSTIBLE MATERIALS, THERE
MIGHT NOT BE SUFFICIENT CLEARANCE TO
INSTALL THE GLASS DOORS OF YOUR
CHOICE. ENSURE ADEQUATE CLEARANCE IS
MAINTAINED AT ALL TIMES SO AS NOT TO
INTERFERE WITH THE INSTALLATION AND
OPERATION OF GLASS DOORS.
COLD CLIMATE INSULATION
If you live in a cold climate, it is especially
important to seal all cracks around the fireplace
opening with noncombustible material and
wherever cold air could enter the room. Sur-
rounding materials must be caulked where it
meets the black metal facing of the fireplace to
avoid cold air intrusion. Use noncombustible
caulking material only on fireplace facing to
seal. Also, the outside air inlet duct should be
wrapped with noncombustible insulation to
minimize the formation of condensation. Do
not place insulation materials on top of fire-
place or against chimney sections.
Note: A 1"* air space must be preserved for all
combustible materials extending for any con-
tinuous length adjacent to the chimney. Figure 46
12"*
Min.
8 3/8"*
Fireplace
Opening
Spacer
Combustible
Mantel
and Trim
12"
Max.
1 1/2"
Finished
Wall
Typical Installation
*Both Of These Dimensions Must Be At Least 18”
When An Unvented Gas Log Set Rated At 32,000
BTU Or Higher Is Used. (Maximum 40,000 BTU)
Header
Fireplace
Opening
Spacer
Finished
Wall
Canadian Installation
Header
8" Max.
(203mm)
18" Min.
(457mm)
Combustible
Mantel
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 17
Figure 48
Figure 49
Methods of Determining Hearth Extension
and Wall Shield Equivalents
To determine the thickness required for any
material when either the k or r values are
known:
TM= Thickness of material in inches
kM= K value of desired material
rM= R value of desired material
TL= Minimum listed thickness
Example: Micore CV230 is to be used for the
hearth extension fireplace. How thick must this
material be?
Using the k formula:
Desired k value of desired Min. thickness
Required = material (per inch) x of Listed
Thickness k value of listed Material
material (per inch)
TM (inches) = kMx TL
.43
TM (inches) = 0.43* x 1"
0.43
Answer using k = 1 x 1" = 1
1" thickness Micore will be required.
Using the r formula:
Desired r value of listed Min. thickness
Required = material (per inch)x of Listed
Thickness r value of desired Material
material (per inch)
TM (inches) = 2.33 x TL
rM
TM (inches) = 2.33 x 1"
2.33*
Answer using r = 1 x 1" = 1 =
1" thickness Micore will be required.
At times it is important to know what combina-
tion of materials are acceptable for use as
hearth extensions. The “R values” are used to
determine acceptable combinations of materi-
als because “R values” are additive where r and
k values are not.
Hearth Extension Dimensions
A16"
B35"
C8"
D51"
A
B
D
CC
“R value” = 1 = r x thickness of material used
k
Alternative Hearth Extension
and Wall Shield Materials
Listed Values Min. Thick
Material k r TL
Millboard .43 2.33 1"
Alternative Values Min. Thick
Materials k r TM
Wonderboard 1.92 0.56 4 ¹⁄₄"
Common brick 5.00 0.20 11 ⁵⁄₈"
Cement mortar 5.00 0.20 11 ⁵⁄₈"
Ceramic tile 12.5 0.08 29 ¹⁄₈"
Marble 11.0 0.09 25 ⁷⁄₈"
Micore CV230 0.43 2.33 1"
(U.S. Gypsum)
Ceraform 126 0.27 3.70 ⁵⁄₈"
(Johns-Manville)
Example: Given that the required “R value” for
a suitable hearth extension used must be equal
to or greater than:
“R” = r x TL = 2.33 x 1" = 2.33.
If it is desired to elevate a marble hearth exten-
sion to a level of 5" or more above the floor
surface. What combination of noncombustible
materials can be used to accomplish this?
If common brick is used so that the 3 ¹⁄₂"
dimension is the height, “R” for the common
brick becomes:
“R”M = r x TM = 0.20 x 3 ¹⁄₂" = .70
Using ¹⁄₂" of mortar to set the brick, “R” for the
mortar is calculated as follows:
“R”M = r x TM = 0.20 x ¹⁄₂" = .10
*value taken from chart
If fireplace is installed diagonally across a 90°
corner; no wall shields are required.
Wall Shield Required
Where Less Than 12"
A
B
C
C
36"
36"
D
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
18
Secure the hearth extension to the floor to
prevent possible shifting.
FINISH TO YOUR TASTE
There are a wide variety of “finished looks” for
these fireplaces, from formal wall decor with
elaborate mantels to rustic wood paneling or
warm brick facings.
Only noncombustible materials like stone, tile,
brick, etc., may overlap the black front facing.
Do not extend these materials beyond the black
facing and into the firebox area. Be sure not to
interfere with the installation and operation of
glass doors or block the upper or lower grilles.
Seal all joints between the black facing and wall
surrounds to prevent air intrusion. Use non-
combustible caulking material only to seal the
black metal facing to the surround material on
the finished wall.
Combustible materials may project beyond the
sides of the fireplace opening as long as they
are kept within the shaded areas illustrated in
Figure 52
.
Figure 51
Figure 52
12"
12" Min. Distance To
Unprotected Side Wall
9"
45°
Combustible
Materials
Allowed In
Shaded Area
“Safe Zone”
9" 1"
Min. Distance To
Protected Side Wall
Fireplace
A ³⁄₄" marble slab set in ¹⁄₂" mortar covers the
brick, “R” for the marble and mortar becomes:
“R”M = r x TM = 0.09 x ³⁄₄" = .068
“R”M = r x TM = 0.20 x ¹⁄₂" = .10
The sum of all “R values” is:
.70 + .10 +. 068 + .10 = .968
This would not be an acceptable combination
of material for the hearth extension since the
total calculated “R value” of the materials used
is under the required “R value” of 2.33. An
additional layer of insulating materials must
be used.
WARNING: THE CRACK BETWEEN THE
FIREPLACE AND THE HEARTH EXTEN-
SION MUST BE SEALED WITH A NON-
COMBUSTIBLE MATERIAL.
WARNING: WHEN INSTALLING HEARTH
EXTENSION IN FRONT OF A NON-CIRCU-
LATING FIREPLACE MODEL, THE FIRE-
PLACE MUST BE RAISED IF HEIGHT OF
HEARTH EXTENSION EXCEEDS 7" ABOVE
THE BOTTOM OF FIREPLACE (
FIGURE 50
).
7"
Max. Thickness Of Hearth Extension When
Non-Circulating Models Are On The Floor
WARNING: WHEN INSTALLING THE
HEARTH EXTENSION BE CAREFUL NOT
TO BLOCK THE HEAT-CIRCULATING AIR
INLET GRILL ON CIRCULATING MODELS.
WARNING: WHEN INSTALLING HEARTH
EXTENSION IN FRONT OF A CIRCULAT-
ING FIREPLACE MODEL, THE FIREPLACE
MUST BE RAISED IF HEIGHT OF HEARTH
EXTENSION EXCEEDS 2" ABOVE BOTTOM
OF FIREPLACE (
FIGURE 51
).
Figure 50
5 1/2"
2"
Max. Thickness Of Hearth Extension When
Circulating Models Are On The Floor
Shipping Weight 188 lbs.
INSTALLATION COMPONENTS
The following items are available for use in the
installation of this appliance.
Unit Mounted
Blower Switch Kit 91L48 FUBSK
Chimney Section 63L10 FTF8-12
63L13 FTF8-18
63L14 FTF8-36
63L15 FTF8-48
Canadian 62L92 FTF8-18C
Chimney Section 62L93 FTF8-36C
Take Off Boot 91L04 FATO
Storm Collar 63L59 FSC
Locking Band 63L60 FLB
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 19
INSTALLATION COMPONENTS
Outside Combustion Air Kits
(with duct) 81L87 FOAK
(without duct) 81L88 FOAK-LD
Combination
Offset/Return Elbow 63L28 FTF8-OR15
Firestop Spacer (Flat) 63L29 F8FS
Firestop Spacer (Flat) 63L31 F8FS-2
63L38 F8F6
Flashing 63L39 F8F12
Round Termination 63L42 FTF8-CTD
Chase Termination
(Square) 63L48 FTF8-CT1
Chase Termination
(Round) 63L45 FTF8-CTDT
Chase Termination
(Square) 63L51 FTF8-CT2
Forced Air Blower Kits
-Single Speed 80L84 FBK-100
-Variable Speed 80L85 FBK-200
(FBK-200 Models Only)
Chase Termination 96L20 FTF8-CTT
Chase Termination 96L22 FTF8-ATT
Stabilizer 63L25 FTF8-S4
Firestop Spacer (30°) 63L30 F8FS30
Firestop Spacer (30°) 63L32 F8FS30-2
Offset/ Return
Package (30°) 63L22 FTF8-ES30
Attic Shield Assembly 63L67 FTF8-FSASCold Climate Kit 63L65 FTF8-CCK3-LD
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
20
Printed in U.S.A. © 2001 by LENNOX
P/N 700,026M REV. C 11/2003
The manufacturer reserves the right to make changes at any time, without notice, in design,
materials, specifications, prices and also to discontinue colors, styles and products.
Consult your local distributor for fireplace code information.