Suprema BEW2-OAP BioEntry W2 User Manual

Suprema Inc. BioEntry W2

User Manual

EnglishVersion 1.00BioEntry W2INSTALLATION GUIDEwww.supremainc.comEN 101.00.BEW2 V1.00A
Contents     Safety Instructions .......................................................................................... 3 Introduction ...................................................................................................... 5 Components ................................................................................................................................................... 5 Name and function of each part ............................................................................................................... 6 Cables and connectors......................................................................................................................................................... 7 How to enroll a fingerprint ........................................................................................................................ 8 Selecting a finger for fingerprint input ........................................................................................................................ 8 Fingerprint enroll method ................................................................................................................................................ 8 Installation ........................................................................................................ 9 Fixing the bracket and the product .......................................................................................................... 9 Power supply connection ........................................................................................................................... 10 Network connection .................................................................................................................................... 10 TCP/IP ..................................................................................................................................................................................10 TTL input connection ................................................................................................................................. 11 Relay connection ......................................................................................................................................... 12 Fail Safe Lock ....................................................................................................................................................................12 Fail Secure Lock ................................................................................................................................................................12 Automatic door connection ............................................................................................................................................13 Connecting as a standalone ...................................................................................................................... 14 Connecting to Secure I/O 2 ...................................................................................................................... 15 Wiegand connection ................................................................................................................................... 16 Resetting Network Settings ......................................................................................................................... 16 Product specifications .................................................................................. 17 Dimensions ................................................................................................................................................... 18 FCC  Compliance Information ....................................................................... 19 Appendix ........................................................................................................ 20 Escape clause ............................................................................................................................................... 20 Copyright notice .......................................................................................................................................... 20
 Safety Instructions 3 Safety Instructions Observe the following instructions to use the product safely and prevent any risk of injury or property damage.  Warning Noncompliance of instructions could lead to serious injury or death. Installation   Do not install the product in a place with direct sunlight, moisture, dust, or soot. • A fire or electric shock may occur. Do not install the product in a place with heat from an electric heater. • A fire or electric shock may occur due to overheating. Install the product in a dry place. • Otherwise, a product damage or electric shock may occur due to moisture. Install the product in a place with no electromagnetic interference. • Otherwise, a product damage or electric shock may occur. The user should not install or repair the product independently. • A fire, electric shock, or personal injury may occur.   • If the product has been damaged due to independent installation or repair of the product by the user, free A/S service will not be provided. Operation   Do not allow liquids such as water, beverages, or chemicals get into the product.   • A fire, electric shock, or product damage may occur.   Caution Noncompliance of instructions could lead to minor injury or product damage. Installation   Do not install the power supply cable in a place where people pass by. • Product damage or physical injury may occur.   Do not install the product near a highly magnetic object such as a magnet, TV, (especially CRT) monitor, or speaker. • A product failure may occur. If installing the product outside where the product is completely exposed, it is recommended to install the product together with the enclosure. Use a separate power supply for Secure I/O 2, electric lock and BioEntry W2 respectively. • If connecting and using the power supply to these devices together, the devices may malfunction. When installing a number of devices, allow a space between the devices for installation. • Otherwise, one device may affect the RF performance of other devices, resulting in malfunction.
 Safety Instructions 4 Operation   Do not drop the product or apply an impact to the product. • A product failure may occur. Be careful not to contaminate or damage the fingerprint contact unit with a dirty hand or foreign substances.   • Deterioration in fingerprint authentication performance and a product failure may occur.   When cleaning the product, wipe the product with a soft and dry cloth and no water, benzene or alcohol.   • Otherwise, a product failure may occur.     RTC battery Replacing the battery with an incorrect type of battery may cause explosion. Discard the battery according to the appropriate regional or international waste regulations.
 Introduction 5 Introduction Components    Components may vary according to the installation environment.      Note BioEntry W2 Bracket PVC anchor (2 EA) Fixing screw (2 EA) Diode (1 EA) 120 Ω resistor (1 EA) Drilling template Quick guide Ferrite core (1 EA) Heat shrink tubes
 Introduction 6 Name and function of each part    Name Feature LED lamp Indicates the operational status of the product with the color of the LED lamp. RF card authentication unit Reads RF cards for entering and exiting. Fingerprint authentication unit   Reads fingerprints placed on it for entering and exiting. Cable • TTL input cable   • Wiegand input or output cable • Power cable • RS485 cable • Ethernet connector • Relay output cable LED lamp for Network Shows the status of the network connection. Network reset button Resets the network configuration. For details, refer to the Resetting Network Setting.    Fingerprint   authentication unit   LED lamp RF card  authentication unit  LED status indicator for Network Network reset button Cable
 Introduction 7 Cables and connectors        Pin Name Color 1 RLY NO   Gray (White stripe) 2 RLY COM   Green (White stripe)   3 RLY NC   Orange (White stripe) 4  VB2 Blue Brown 5  VB1 Red Green 6 WG D0 Green 7 WG D1 White 8 WG GND Black 9 TTL IN 1 Brown 10 TTL IN 0 Purple   11 PWR +VDC   Red   12 Not Connected   Pink   13 PWR GND   Black (White stripe) 14 485 TRXN Yellow (Black stripe) 15 485 TRXP   Blue (White stripe) 16 485 GND White (Black stripe) 17 ENET TXP   White 18 ENET TXN Orange   19 ENET RXP Black 20 ENET RXN Yellow
 Introduction 8 How to enroll a fingerprint In order to improve the fingerprint authentication rate, register the fingerprint correctly. BioEntry W2 can recognize a fingerprint even if the angle and position of a user's fingerprint input change. If you register the fingerprint with attention to the following matters, the authentication rate can be improved. Selecting a finger for fingerprint input • In preparation for the case that the fingerprint of a specific finger cannot be used, for example if the user is lifting a load with one hand or a finger gets hurt, up to 10 fingerprints for each user can be registered.   • In the case of a user whose fingerprint cannot be recognized well, the authentication rate can be improved by enrolling the same finger twice repeatedly.   • If a finger has a cut or the fingerprint is blurry, select another finger for the fingerprint. • It is recommended to use the index finger or the middle finger when scanning the fingerprint. The authentication rate can be reduced if it is difficult to place another finger at the center of fingerprint sensor accurately.  Fingerprint enroll method 1 Place the finger with the fingerprint to be registered on the fingerprint authentication unit and press the finger gently for better authentication.    2 After a beep sounds, scan the fingerprint of the registered finger again (scan the fingerprint of a finger to be registered twice).  Cautions for enrolling a fingerprint When a fingerprint is recognized, it is compared with the initially registered fingerprint, so the initial fingerprint enroll is the most important. Pay attention to the following matters when enrolling the fingerprint. • Place the finger deep enough to contact with the sensor completely. • Place the center of the fingerprint in the center of the sensor.   • If a finger has a cut or the fingerprint is blurry, select another finger for the fingerprint.   • Scan the fingerprint correctly without moving according to the instruction on the screen.   • If you make the finger upright so that the contact area with the sensor has decreased or the angle of finger has warped, fingerprint authentication may not be performed.    When the fingerprint recognition fails BioEntry W2 can recognize a fingerprint regardless of a change of season or finger condition. However, the authentication rate may vary according to the external environment or fingerprint input method.   If the fingerprint authentication cannot be done smoothly, it is recommended to take the following measures.   • If the finger is smeared with water or sweat, dry off the finger and then scan the finger. • If the finger is too dry, blow your breath on the fingertips and then scan the finger. • If the finger has a cut, register the fingerprint of another finger. • The initially registered fingerprint often may have not been scanned correctly, so register the fingerprint again according to ‘Cautions for enrolling a fingerprint’.      Note
 Installation 9 Installation Fixing the bracket and the product 1 Determine the correct position to install the bracket using the provided drilling template. Fix the bracket firmly using fixing screws through the bracket to the position where BioEntry W2 will be installed.   • If installing BioEntry W2 on a concrete wall, drill holes, insert PVC anchors, and fix them with fixing screws. • To avoid RF interference, a minimum separation distance must be maintained.  2 Install BioEntry W2 onto the fixed bracket.     Wall Wall 30 cm 30 cm Note
 Installation 10 3 Connect BioEntry W2 to the bracket by rotating the product fixing screw.  Power supply connection   • Use a power supply adaptor of DC 12 V (± 10%) with a minimum of 1,500 mA which has obtained the approval of IEC/EN 60950-1. If you wish to connect and use another device to the power supply adaptor, you should use an adaptor with a current capacity which is the same or larger than the total power consumption required for the terminal and another device.     • Use a separate power supply for Secure I/O 2, the electric lock, and the BioEntry W2 respectively. If connecting and using the power supply to these devices together, the devices may malfunction. Network connection TCP/IP LAN connection (connecting to a hub) You can connect the product to a hub using a general type CAT-5 cable.     BioEntry W2 Hub PC Note BioEntry W2 11  -  PWR +VDC Red   13  -  PWR GND Black (White stripe) UPS (Optional) DC power 11 13
 Installation 11 LAN connection (connecting to a PC directly) BioEntry W2 has an automatic MDI/MDIX function so that it can be connected to a PC directly using a normal straight type CAT-5 cable, not a cross cable.   TTL input connection        BioEntry W2 9  -  TTL IN 1 Brown 10  -  TTL IN 0 Purple   16  -  485 GND White (Black stripe) 16 9    10   Door sensor Door button 16 BioEntry W2 PC
 Installation 12 Relay connection Fail Safe Lock In order to use the Fail Safe Lock, connect N/C relay as shown in the figure below. There is normally a current flowing through the relay for the Fail Safe Lock. When the relay is activated, blocking the current flow, the door will open. If the power supply to the product is cut off due to a power failure or an external factor, the door will open.   • Install a diode at both sides of the door lock wire as shown in the figure to protect the relay from the reverse current, which occurs when the door lock operates. • Take caution of the installation direction of the diode. Install the diode close to the door lock. • Use a separate power supply for BioEntry W2 and the door lock. Fail Secure Lock In order to use the Fail Secure Lock, connect N/O relay as shown in the figure below There is normally no current flowing through the relay for the Fail Secure Lock. When the current flow is activated by the relay, the door will open. If the power supply to the product is cut off due to a power failure or an external factor, the door will lock.   • Install a diode at both sides of the door lock wire as shown in the figure to protect the relay from the reverse current, which occurs when the door lock operates. • Take caution of the installation direction of the diode. Install the diode close to the door lock. • Use a separate power supply for BioEntry W2 and the door lock.    Note BioEntry W2 Deadbolt /  Door strike DC power 2  1  1    -  RLY NO Gray (White stripe) 2    -  RLY COM  Green (White stripe) Note BioEntry W2 2    -  RLY COM  Green (White stripe) 3    -  RLY NC Orange (White stripe) Deadbolt /  Door strike DC power 2  3
 Installation 13 Automatic door connection      BioEntry  W2 Automatic door Controller Sensor Door Lock Door button 1  -  RLY NO Gray (White stripe) 2    -  RLY COM  Green (White stripe) 2  1
 Installation 14 Connecting as a standalone BioEntry W2 can be connected to the door lock, door button, and door sensor directly without connecting a separate I/O device.      • BioEntry W2 can be used as a multi-door controller with the slave devices with the RS485 cable. The slave devices are used as dummy readers and authentication is performed in the master device. • If Xpass is connected to the master device, only card authentication can be used. • The maximum number of slave devices available to connect varies according to the authentication method, number of users, and number of devices. Also note that the number of slave devices affects the fingerprint authentication speed. • A master device can control 31 slave devices. The bandwidth of RS485 allows for up to 7 fingerprint authentication devices to be connected. • For more information, contact the Suprema technical support team (support@suprema.co.kr).   Note BioEntry W2 PC Relay Door  sensor Door button  1  2 3 11  13 DC power DC power Deadbolt /  Door strike Hub Fail Safe Lock  Fail Secure Lock  or Power  16   9  16  10 TTL connection 9  -  TTL IN 1 Brown   10  -  TTL IN 0 Purple 16  -  485 GND White (Black stripe) Relay  connection 1  -  RLY NO Gray (White stripe) 2  -  RLY COM Green (White stripe) 3  -  RLY NC Orange (White stripe) Power supply connection 11  -  PWR +VDC Red 13  -  PWR GND Black (White stripe)
 Installation 15 Connecting to Secure I/O 2 Secure I/O 2 is an I/O device, can be connected to BioEntry W2 with the RS-485 cable. Security can be maintained even if the connection between BioEntry W2 and Secure I/O 2 has been lost or the power supply to BioEntry W2 has been shut off due to external factors.  • Use an AWG24 twisted pair with a maximum length of 1.2 km for the RS-485 cable. • If connecting with a RS-485  daisy chain, connect the termination resistor (120 Ω) to both ends of the daisy chain connection. If connected to the middle line, the signal level becomes smaller and the communication performance will deteriorate. Make sure to connect it to both ends of the daisy chain connection.       • BioEntry W2 can be used as a multi-door controller with the slave devices with the RS485 cable. The slave devices are used as dummy readers and authentication is performed in the master device. • If Xpass is connected to the master device, only card authentication can be used. • The maximum number of slave devices available to connect varies according to the authentication method, number of users, and number of devices. Also note that the number of slave devices affects the fingerprint authentication speed. • A master device can control 31 slave devices. The bandwidth of RS485 allows for up to 7 fingerprint authentication devices to be connected. • For more information, contact the Suprema technical support team (support@suprema.co.kr).    Note BioEntry W2 PC Secure I/O 2 Hub Door button Door sensor Power RS-485 connection 14  -  485 TRXN Yellow (Black stripe) 15  -  485 TRXP Blue (White stripe) 16  -  485 GND White (Black stripe) 14 13 15 Door lock DC power DC power DC power 11 16 Power supply connection 11  -  PWR +VDC Red 13  -  PWR GND Black (White stripe) RS-485
Installation 16 Wiegand connection Resetting Network Settings 1 Turn the power on. 2 Press the network reset button on the rear of device until the device restart automatically. 3 Connect the device with default values. •TCP/IP address: DHCP address assignment (If DHCP address assignment is failed, 169.254.0.1 will be set.) •Server mode: Disabled •RS-485: PC connection, 115200 bps 4 Change the TCP/IP address or RS-485 information. 5 Turn the power off later on and then check the network setting is properly. BioEntry W2 RFID reader 6    -  WG D0 Green 7  -  WG D1 White 8  -  WG GND  Black 8 7 6 8 7 6 Use as a Wiegand input device Use as a Wiegand output device Control device BioEntry W2
 Product specifications 17 Product specifications Category  Feature  Specification Credential Biometric Fingerprint RF  Option 125 KHz EM/HID Proxy,   13.56 MHz MIFARE/DESFire/DESFire EV1/Felica/NFC/iClass RF read range  * MIFARE/DESFire/EM/HID Proxy/iClass/ISO15693 : 50 mm, Felica: 30 mm General CPU 1.2 GHz Quad Core Memory 2GB Flash + 256 MB RAM LED Multi-color Sound Multi-tone  Buzzer Operating temperature -20°C  -  50°C   Storage temperature -40°C  -  70°C Operating humidity 0%  -  80%,  non-condensing Storage humidity 0%  -  90%,  non-condensing Dimension (W x H x D) 50 mm x 172 mm x 43.5 mm (Bottom) / 38.2 mm (Top) Weight Device:  251g Bracket:  43g (Including washer and bolt) IP rating IP67 IK rating IK08 Certificates CE, FCC, KC, RoHS, REACH, WEEE Fingerprint Image dimension 272 x 320 pixels Image bit depth 8bit, 256 grayscale   Resolution 500  dpi Template SUPREMA / ISO 19794-2 / ANSI 378 Extractor / Matcher MINEX certified and compliant   LFD Supported Capacity Max. User (1:1) 500,000 Max. User (1:N) 100,000 Max. Template (1:1) 1,000,000 Max. Template (1:N) 200,000 Max. Text Log 1,000,000 Interface Ethernet Supported (10/100 Mbps, auto MDI/MDI-X) RS-485 1ch  Master / Slave  (Selectable) Wiegand 1ch  Input /  Output  (Selectable) TTL  input 2ch Input Relay 1 Relay   PoE Supported Tamper Supported Electrical Power Voltage: DC 12 V   Current: Max. 600 mA Switch input VIH Min.  3  V Max. 5  V Switch input VIL Max. 1  V Switch Pull-up resistance 4.7  kΩ (The input ports are pulled up with 4.7  kΩ.) Wiegand output VOH More than 4.8 V Wiegand output VOL Less than 0.2  V Wiegand output Pull-up   resistance Internally pulled up with 1 kΩ Relay Voltage: Max. 30VDC Current: 1A  * RF read range will vary depending on the installation environment.
Product specifications 18 Dimensions (Unit: mm) 50 172 38.2 43.5 172 39.4 156.8
FCC Compliance Information 19 FCC Compliance Information THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: •Reorient or relocate the receiving antenna. •Increase the separation between the equipment and receiver. •Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. •Consult the dealer or an experienced radio/TV technician for help. Modifications not expressly approved by the manufacturer could void the user's authority to operate the equipment under FCC rules. This appliance and its antenna must not be co-located or operation in conjunction with any other antenna or transmitter. A minimum separation distance of 20 cm must be maintained between the antenna and the person for this appliance to satisfy the RF exposure requirements.
Appendix 20 Appendix Escape clause •The information in this manual is provided with regard to the Suprema's products. •The right to use is acknowledged only for products included in the terms and conditions of the sales agreement guaranteed bySuprema. The right of license to other intellectual property rights not discussed in this manual is not acknowledged. •Suprema does not guarantee or hold responsibility for the suitability and commerciality of the product for a specific purpose, or theinfringement of patent, copyright, or other intellectual property rights with regard to sales or usage of Suprema's products. •Do not use the product of Suprema under the situations related to medical, rescue of human lives, or maintenance of life, as a personmay get injured or lose his/her life due to product malfunction. If an accident occurs while a consumer is using the product under the situations described as examples above, employees, subsidiaries, branches, affiliated companies and distributors of Suprema do notaccept responsibility nor will they reimburse for all related direct and indirect expenses or expenditure including attorney fees even ifthe consumer has discovered any shortcomings in the product design or manufacturing process and claims this as a significant fault. •Suprema may modify the product size and specifications at any time without proper notice in order to improve the safety, function and design of the product. Designers must keep in mind that functions or descriptions indicated as "to be implemented" or "undefined"may change at any time. Suprema will implement or define such functions or descriptions in the near future and Suprema accepts no responsibility for compatibility issues and any other problems arising from such compatibility issues. •If you wish to obtain the newest specifications before ordering the product, contact Suprema through a Sales Representative or localdistributor of Suprema. Copyright notice The copyright of this document is vested in Suprema. The rights of other product names, trademarks and registered trademarks are vested in each individual or organization that owns such rights.