System Sensor 2Wt B Users Manual

4WT-B to the manual e65f66be-6f29-4bf5-be67-06701f2857a1

2015-02-02

: System-Sensor System-Sensor-2Wt-B-Users-Manual-490729 system-sensor-2wt-b-users-manual-490729 system-sensor pdf

Open the PDF directly: View PDF PDF.
Page Count: 4

DownloadSystem-Sensor System-Sensor-2Wt-B-Users-Manual-  System-sensor-2wt-b-users-manual
Open PDF In BrowserView PDF
INSTALLATION AND MAINTENANCE INSTRUCTIONS

Series
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com

Photoelectric Smoke Detector
Models: 2W-B, 2WT-B
4W-B, 4WT-B
Before Installing
Please read thoroughly System Sensor manual A05-1003,
Applications Guide for System Smoke Detectors, which provides
detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available
from System Sensor at no charge.

Two LEDs on the detector provide a local visual indication of the
detector’s status:
Table 1: Detector LED Modes
Power-up
Normal (standby)
Out of sensitivity
Freeze Trouble
Alarm

NOTICE: This manual shall be left with the owner/user of this
equipment.
IMPORTANT: This detector must be tested and maintained regularly following NFPA 72 requirements. At a minimum, cleaning
should be performed annually.

Green LED
Blink 10 sec
Blink 5 sec
—
—
—

Red LED
Blink 10 sec
—
Blink 5 sec
Blink 10 sec
Solid

After an initial power-up delay, the red and green LEDs will blink
synchronously once every ten seconds. It will take approximately 80
seconds for the detector to finish the power-up cycle (see Table 2).

General Description
Models 2W-B and 2WT-B are 2-wire photoelectric smoke detectors; models 4W-B and 4WT-B are 4-wire photoelectric smoke
detectors. All models incorporate a state-of-the-art optical sensing
chamber and an advanced microprocessor. The microprocessor
allows the detector to automatically adjust its sensitivity back
to the factory setting when it becomes more sensitive due to
contaminants settling in its chamber. In order for this feature
to work properly, the chamber must never be opened while
power is applied to the smoke detector. This includes cleaning,
maintenance or screen replacement. Should it become necessary,
the screen/sensing chamber is field replaceable. Models 2WT-B
and 4WT-B also feature a restorable, built-in, fixed temperature
(135°F) thermal detector and are also capable of sensing a freeze
condition if the temperature is below 41°F.

Table 2: Power-up Sequence for LED Status Indication*
Condition
Initial LED Status Indication
Initial LED Status Indication
(if excessive electrical noise is present)

Duration
80 seconds
4 minutes

*Refer to Electrical Specifications for start-up time in conjunction with panel alarm
verification.

NOTE: If, during power-up, the detector determines there is
excessive electrical noise in the system such as those caused by
improper grounding of the system or the conduit, both LEDs will
blink for up to 4 minutes before displaying detector status (see
Table 2).
After power-up has completed and the detector is functioning
normally within its listed sensitivity range, the green LED blinks
once every five seconds. If the detector is in need of maintenance
because its sensitivity has shifted outside the listed limits, the red
LED blinks once every five seconds. When the detector is in the
alarm mode, the red LED latches on. The LED indication must not
be used in lieu of the tests specified under Testing. In a freeze
trouble condition, the red LED will blink once every 10 seconds
(refer to Table 1).

All i3 Series detectors are designed to provide open area protection. Two-wire models must be used with compatible UL Listed
panels only.
When used with an i3 Series compatible control panel or the i3
Series 2W-MOD module (refer to installation manual D500-46-00),
the 2W-B and 2WT-B are capable of generating a “maintenance
needed” signal. The 2W-MOD can indicate a need for cleaning,
replacement, or a freeze condition (2WT-B only) at the control
panel or module.

To measure the detector’s sensitivity, the i3 Series Model SENSRDR Infrared Sensitivity Reader tool (see Figure 4) should be
used.

Installation of the 2W-B, 2WT-B, 4W-B, and 4WT-B detectors is
simplified by the use of a mounting base that may be pre-wired
to the system, allowing the detector to be easily installed or
removed. The mounting base installation is further simplified by
the incorporation of features compatible with drywall fasteners.

Models 2W-B and 2WT-B also include an output that allows an
optional Model RA400Z Remote Annunciator to be connected.
Mounting
Each i3 Series detector is supplied with a mounting base that can
be mounted:
1. To a single gang box, or
2. To a 31⁄2-inch or 4-inch octagonal box, or
3. To a 4-inch square box with a plaster ring, or
4. Direct mount or to ceiling using drywall fasteners (Figure 2).

D100-96-00

1

I56-1800-08R

Figure 1: Mounting of Detector
Wiring Installation Guidelines
All wiring must be installed in compliance with the National
Electrical Code, applicable state and local codes, and any special
requirements of the local Authority Having Jurisdiction.
Proper wire gauges should be used. The conductors used to connect smoke detectors to the alarm control panel and accessory
devices should be color-coded to reduce the likelihood of wiring
errors. Improper connections can prevent a system from responding properly in the event of a fire.

S0121-00

The i3 Series heads and bases are keyed so that a 2-wire head will
only mount to a 2-wire base, and a 4-wire head will only mount
to a 4-wire base. The heads and bases are clearly identified as
either 2-wire or 4-wire. When mounting the i3 Series, ensure that
the head is mounted to the correct base.

The screw terminals in the mounting base will accept 14–22
gauge wire. For best system performance, all wiring should be
installed in separate grounded conduit; do not mix fire alarm
system wiring in the same conduit as any other electrical wiring.
Twisted pair may be used to provide additional protection against
extraneous electrical interference.

Tamper-Resistant Feature
The i3 Series detectors include a tamper-resistant feature that
prevents removal from the mounting base without the use of a
tool. To engage the tamper-resistant feature, cut the small plastic
tab located on the mounting base (Figure 2), and then install the
detector. To remove the detector from the base once it has been
made tamper resistant, use a small screwdriver to depress the
square tamper release tab, located on the skirt of the mounting
base, and turn the detector counterclockwise.

Wire connections are made by stripping approximately 1⁄4-inch
of insulation from the end of the feed wire, inserting it into the
proper base terminal, and tightening the screw to secure the wire
in place.
Two-Wire Compatibility
System Sensor two-wire smoke detectors are marked with a
compatibility identifier located on the label on the back of the
product. For two-wire models 2W-B and 2WT-B, connect detectors
only to compatible alarm control panels as identified by System
Sensor’s compatibility chart. This chart contains the current list of
detectors and UL Listed compatible control units. A copy of this
list is available from System Sensor upon request.

Figure 2: Tamper-Resistant Feature
DIRECT MOUNT
HOLES

Wiring Diagrams
Figure 3a: Wiring Diagram, 2W-B and 2WT-B
2-WIRE +
ZONE –

SNAP OFF TAB
FOR TAMPER LOCK

EOL
RESISTOR

RA400Z

TAMPER
RELEASE TAB

RA400Z

S0226-00
(5) RA –

(4) RA +

(3) – IN/OUT

2W-B or
2WT-B

(2) + OUT

(1) + IN

(5) RA –

(4) RA +

(3) – IN/OUT

(2) + OUT

(1) + IN

2-WIRE
CONTROL
PANEL

Do NOT Install Detectors in the Following Areas:
• In or near areas where particles of combustion are normally
present such as kitchens; in garages (vehicle exhaust); near
furnaces, hot water heaters, or gas space heaters.
• In very cold or very hot areas.
• In wet or excessively humid areas, or next to bathrooms with
showers.
• In dusty, dirty, or insect-infested areas.
• Near fresh air inlets or returns or excessively drafty areas. Air
conditioners, heaters, fans, and fresh air intakes and returns
can drive smoke away from the detector.

2W-B or
2WT-B
S0133-00

Figure 3b: Wiring Diagram, 4W-B and 4WT-B
AUX OR +
SMOKE
POWER –

EOL
RELAY
(A77-716B)

–
IDC +
EOL
RESISTOR

(5) COM

(3) – IN/OUT

(4) NO

(1) + IN

(2) + OUT

(3) – IN/OUT

(4) NO

4W-B or
4WT-B

CAUTION

(5) COM

(1) + IN

4-WIRE
CONTROL
PANEL

(2) + OUT

Consult NFPA 72, the local Authority Having Jurisdiction (AHJ),
and/or applicable codes for specific information regarding the
spacing and placement of smoke detectors.

4W-B or
4WT-B
S0134-00

Smoke detectors are not to be used with detector guards unless
the combination has been evaluated and found suitable for that
purpose.
D100-96-00

2

I56-1800-08R

3. If the detector is within the listed sensitivity limits, the
detector’s red LED should light within five seconds.

2-Wire i3 Detector Wired in Style D Configuration:
CAUTION

Figure 5: Recessed Test Switch Opening and SENS-RDR
Position

Any 2-wire i3 smoke detector (2W-B, 2WT-B, 2WTA-B, or 2WTR-B)
wired in the Style D initiating device circuit (IDC) configuration
requires the use of a 2W-MOD2 module. This is because fire
alarm control panels vary by manufacturer on the implementation of Style D circuits. Therefore, the only way to insure proper
operation of 2-wire i3 smoke detectors (2W-B, 2WT-B, 2WTA-B, or
2WTR-B) on Style D IDC’s is to use a 2W-MOD2 module. Refer
to the 2W-MOD2 installation manual, document D500-46-00,
for Style D wiring diagrams. The 2W-MOD2 installation
manual may be downloaded from the System Sensor web site
at www.systemsensor.com.

POSITION SENS-RDR
AT AN ANGLE ON THE
OVAL AREA OR AT THE
CHAMBER OPENING
BY THE WORD “PAINT”

LED

RECESSED TEST SWITCH

S0135-00

B. Smoke Entry Test
Hold a smoldering punk stick or cotton wick at the side of the
detector and gently blow the smoke through the detector until
it alarms.
C. Direct Heat Method (models 2WT-B and 4WT-B only)
Using a 1000-1500 watt hair dryer, direct the heat toward either
of the thermistors. Hold the heat source about 12 inches from
the detector to avoid damage to the plastic.

Installation
WARNING

Remove power from alarm control unit or initiating device circuits
before installing detectors.
NOTE: To install units so that corresponding LEDs are lined up,
refer to the “Green LED” indicator on the base.
1. Wire the mounting base screw terminals per Figure 3a or
Figure 3b, as applicable.
2. Place detector on the base and rotate clockwise. The detector
will drop into the base and lock into place with a “click”.
3. After all detectors have been installed, apply power to the
alarm control unit.
4. Test each detector as described in Testing.
5. Reset all the detectors at the alarm control unit.
6. Notify the proper authorities that the system is in operation.

NOTE: For the above tests, the detector will reset only after the
power source has been momentarily interrupted.
If a detector fails any of the above test methods, its wiring should be
checked and it should be cleaned as outlined in the Maintenance
section. If the detector still fails, it should be replaced.
Notify the proper authorities when the system is back in service.
Loop Verification (models 2W-B and 2WT-B only)
Loop verification is provided by the EZ Walk loop test feature.
This feature is for use with i3 Series compatible control panels or
the i3 Series 2W-MOD module only. The EZ Walk loop test verifies
the initiating loop wiring and provides visual status indication at
each detector.
1. Ensure proper wiring and power is applied. Wait approximately six minutes before performing EZ Walk test.
2. Place control panel or module in EZ Walk Test mode (refer
to panel manufacturer’s manual or 2W-MOD manual D50046-00).
3. Observe the LEDs on each detector:

CAUTION

Dust covers are an effective way to limit the entry of dust into
the smoke detector sensing chamber. However, they may not
completely prevent airborne dust particles from entering the detector. Therefore, System Sensor recommends the removal of detectors
before beginning construction or other dust producing activity. When
returning the system to service, be sure to remove the dust covers
from any detectors that were left in place during construction.
Testing
Detectors must be tested after installation and following
maintenance.

Table 3: EZ Walk Test Detector Modes
Green LED

NOTE: Before testing, notify the proper authorities that maintenance is being performed and the system will be temporarily out
of service. Disable the zone or system undergoing maintenance to
prevent any unwanted alarms.

Red LED

Proper Operation

Double blink 5 sec

—

Out of Sensitivity

—

Double Blink 5 sec

Freeze Condition

—

Double Blink 10 sec

NOTE: The EZ Walk loop test must not be used instead of alarm
testing.

Ensure proper wiring and power is applied. After power up, allow
80 seconds for the detector to stabilize before testing.

Maintenance
NOTE: Before performing maintenance on the detector, notify
the proper authorities that maintenance is being performed and
the system will be temporarily out of service. Disable the zone or
system undergoing maintenance to prevent any unwanted alarms.
Power must be removed from the detector before performing
maintenance of any kind.

Test i3 Series detectors as follows:
A. Test Switch
1. An opening for the recessed test switch is located on the
detector housing (See Figure 5).
2. Insert a small screwdriver or allen wrench (0.18w max.) into
the test switch opening; push and hold.
D100-96-00

PUSH RECESSED
SWITCH WITH A
0.18w MAX.
DIAMETER TOOL

3

I56-1800-08R

1. Remove the detector cover by turning counterclockwise. (See
Figure 6.)
2. Vacuum the cover or use canned air to remove any dust or
debris.
3. Remove the top half of the screen/sensing chamber by lifting
straight up (Figure 6).
4. Vacuum or use canned air to remove any dust or particles that
are present on both chamber halves.
5. Replace the top half of the screen/sensing chamber by aligning the arrow on the screen/sensing chamber with the arrow
on the housing. Press down firmly until the screen/sensing
chamber is fully seated.
6. Replace the detector cover by placing it over the screen/sensing
chamber and turning it clockwise until it snaps into place.
7. Reinstall the detector and test. (See the Testing section.)
8. Notify the proper authorities when the system is back in service.

Figure 6: Removing/Replacing Screen/Sensing Chamber

Electrical Specifications 2-wire 4-wire
System Voltage – Nominal: 12/24 12/24 Volts Non-polarized
Min.:
8.5
8.5 Volts
Max.:
35
35 Volts
Max. Ripple Voltage:
30
30 % peak to peak
of applied voltage
Max. Standby Current:
50
50 µA average
Peak Standby Current:
100
— µA
Max. Alarm Current:
130
20 mA 12 Volt Systems
(For 2W-B and 2WT-B,
panel must limit current) 130
23 mA 24 Volt Systems
Alarm Contact Ratings:
—
0.5 Amp @ 30 V AC/DC
Alarm Reset Time:
0.3
0.3 sec
Max. Start-up Capacitance: 0.1
— µF
Latching Alarm:
Reset by momentary power interruption
Maximum Initial
Start-up Time:
45
15 sec
Alarm Verification*
Start-up Time:
15
15 sec

Physical Specifications
Heat Sensor
(Model 2WT-B and 4WT-B):
Freeze Trouble
(Model 2WT-B and 4WT-B):
Operating Temperature Range:
2W-B and 4W-B:
2WT-B and 4WT-B:
Operating Humidity Range:
Storage Temperature Range:
Diameter (including base):
Height (including base):
Weight:

REMOVABLE
DETECTOR
COVER

SCREEN/SENSING
CHAMBER
(TOP HALF)

DETECTOR
HOUSING

S0136-00

135°F (57.2°C)
41°F (5°C)
32 to 120°F (0 to 49°C)
32 to 100°F (0 to 37.8°C)
0 to 95% RH non-condensing
–4 to 158°F (–20 to 70°C)
5.3 inches
2.0 inches
6.3 oz.

*Assumes the panel’s alarm verification reset time is 10 seconds or less. Should the alarm verification reset exceed 10 seconds, use the maximum initial start-up time.

Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
System Sensor warrants its enclosed smoke detector to be free from defects in
materials and workmanship under normal use and service for a period of three
years from date of manufacture. System Sensor makes no other express warranty for this smoke detector. No agent, representative, dealer, or employee of
the Company has the authority to increase or alter the obligations or limitations
of this Warranty. The Company’s obligation of this Warranty shall be limited to
the repair or replacement of any part of the smoke detector which is found to
be defective in materials or workmanship under normal use and service during
the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return
Authorization number, send defective units postage prepaid to: System Sensor,

Repair Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174.
Please include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to repair or replace units which are found to
be defective because of damage, unreasonable use, modifications, or alterations
occurring after the date of manufacture. In no case shall the Company be liable for
any consequential or incidental damages for breach of this or any other Warranty,
expressed or implied whatsoever, even if the loss or damage is caused by the
Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion
may not apply to you. This Warranty gives you specific legal rights, and you may
also have other rights which vary from state to state.

FCC Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if
not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference
will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.

D100-96-00

4

I56-1800-08R
©2005 System Sensor



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Page Count                      : 4
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:a2de0162-1b8b-43d8-9c3b-4ddd320ffa43
Producer                        : Acrobat Distiller 6.0.1 (Windows)
Trapped                         : False
Create Date                     : 2007:01:18 16:13:28-07:00
Modify Date                     : 2007:01:18 16:13:28-07:00
Metadata Date                   : 2006:11:22 09:23:04-07:00
Creator Tool                    : Adobe InDesign CS2 (4.0)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 10278 bytes, use -b option to extract)
Version ID                      : 1
Instance ID                     : uuid:8ca89d9e-d862-11d9-9123-000393bb68ba
Rendition Class                 : proof:pdf
Document ID                     : adobe:docid:indd:defdfa7a-4db9-11d8-8442-edc96cca7d5f
Format                          : application/pdf
Title                           : untitled
Creator                         : Adobe InDesign CS2 (4.0)
EXIF Metadata provided by EXIF.tools

Navigation menu