System Sensor Supervised Control Module M500S Users Manual
M500S to the manual b5c308ef-07d5-4a24-a6a0-70bc8ae9068e
2015-02-02
: System-Sensor System-Sensor-Supervised-Control-Module-M500S-Users-Manual-490698 system-sensor-supervised-control-module-m500s-users-manual-490698 system-sensor pdf
Open the PDF directly: View PDF .
Page Count: 4
Download | |
Open PDF In Browser | View PDF |
I56-3850-002 INSTALLATION AND MAINTENANCE INSTRUCTIONS M500S Supervised Control Module 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 www.systemsensor.com Specifications Normal Operating Voltage: 15 to 32 VDC Maximum Current Draw: 6.5mA (LED On) Operating Current: 350 µA max., 1 communication every 5 seconds 47k EOL resistor; 485 µA max. (Communicating, NAC Shorted) Maximum NAC Line Loss: 4 VDC External Supply Voltage (between Terminals T10 and T11) Maximum (NAC): Regulated 24VDC Maximum (Speakers): 70.07 V RMS, 50 W Max. NAC Current Ratings: For class B wiring system, the current rating is 3A; For class A wiring system, the current rating is 2A Temperature Range: 32˚F to 120˚F (0˚C to 49˚C) Humidity: 10% to 93% Non-condensing Dimensions: 41/2˝ H × 4˝ W × 11/4˝ D (Mounts to a 4˝ square by 21/8˝ deep box.) Accessories: SMB500 Electrical Box; CB500 Barrier Before Installing This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules. Figure 2A. Module mounting with barrier: Figure 2B: NOTICE: This manual should be left with the owner/user of this equipment. General Description M500S Supervised Control Modules are intended for use in intelligent, twowire systems, where the individual address of each module is selected using the built-in rotary decade switches. This module is used to switch an external power supply, which can be a DC power supply or an audio amplifier (up to 80 VRMS), to notification appliances. It also supervises the wiring to the connected loads and reports their status to the panel as NORMAL, OPEN, or SHORT CIRCUIT. The M500S has two pairs of output termination points available for fault-tolerant wiring and a panel-controlled LED indicator. This module can be used to replace an M500C module that has been configured for supervised wiring operation. ISOLATED QUADRANT Compatibility Requirements To ensure proper operation, these modules shall be connected to listed compatible system control panels only. Figure 1. Controls and indicators: C1050-00 Wiring NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. When using control modules in nonpower limited applications, the System Sensor CB500 Module Barrier must be used to meet UL requirements for the separation of power-limited and nonpower-limited terminals and wiring. The barrier must be inserted into a 4˝×4˝×21/8˝ junction box, and the control module must be placed into the barrier and attached to the junction box (Figure 2A). The power-limited wiring must be placed into the isolated quadrant of the module barrier (Figure 2B). 1. Install module wiring in accordance with the job drawings and appropriate wiring diagrams. 2. Set the address on the module per job drawings. 3. Secure module to electrical box (supplied by installer), as shown in Figure 2A. C0909-01 Mounting The M500S mounts directly to 4-inch square electrical boxes (see Figure 2A). The box must have a minimum depth of 21/8 inches. Surface mounted electrical boxes (SMB500) are available from System Sensor. SS-460-001 1 I56-3850-002 Figure 3. Typical notification appliance circuit configuration, NFPA Style Y: CONNECT MODULES TO LISTED COMPATIBLE CONTROL PANELS ONLY 24 VDC CIRCUIT DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS. (−) )+( CONTROL MODULE 24 VDC POWER SUPPLY ISOLATED, REGULATED, POWER LIMITED PER NFPA 70. LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP. (−) MODULE POLARITIES ARE SHOWN IN ALARM (−) (−) (−) )+( SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX. TWISTED PAIR IS RECOMMENDED )+( 47K EOL RESISTOR ELR-47K FROM PANEL OR PREVIOUS DEVICE ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED )+( (−) (+) )+( TO NEXT CONTROL MODULE OR END-OF-LINE RELAY. ONE RELAY REQUIRED FOR EACH CIRCUIT. SOME CONTROL PANELS HAVE RELAY BUILT IN AND DO NOT REQUIRE EXTERNAL WIRING. REFER TO PANEL MANUAL. UL LISTED EOL RELAY SHOWN ENERGIZED 24 VDC COIL EOLR-1 TO NEXT DEVICE *NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE. C0913-05 Figure 4. Typical fault tolerant notification appliance circuit configuration, NFPA Style Z: 24 VDC POWER SUPPLY ISOLATED, REGULATED, POWER LIMITED PER NFPA 70. LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP. 24 VDC CIRCUIT DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS. )–( CONTROL MODULE )+( MODULE POLARITIES ARE SHOWN IN ALARM )–( )+( EOL RESISTOR IS INTERNAL AT TERMINALS 8&9 )–( )–( )+( FROM PANEL OR PREVIOUS DEVICE SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX. TWISTED PAIR IS RECOMMENDED )–( ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED )+( UL LISTED EOL RELAY SHOWN ENERGIZED 24 VDC COIL EOLR-1 CONNECT MODULES TO LISTED COMPATIBLE CONTROL PANELS ONLY )+( TO NEXT CONTROL MODULE OR END-OF-LINE RELAY. ONE RELAY REQUIRED FOR EACH CIRCUIT. SOME CONTROL PANELS HAVE RELAY BUILT IN AND DO NOT REQUIRE EXTERNAL WIRING. REFER TO PANEL MANUAL. (–) (+) TO NEXT DEVICE *NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE. C0914-05 SS-460-001 2 I56-3850-002 Figure 5. Typical wiring for speaker supervision and switching, NFPA Style Y: AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM. SEE PANEL INSTALLATION MANUAL FOR DETAILED INFORMATION. WIRES MUST BE SUPERVISED PER NFPA AUDIO CIRCUIT DO NOT LOOP WIRE AROUND TERMINALS 10 & 11. BREAK WIRE TO ENSURE SUPERVISION OF CONNECTIONS. AUDIO AMPLIFIER, 70.7 Vrms MAX. AMPLIFIER MUST PROVIDE WIRING SUPERVISION PER NFPA. )–( )–( )–( )+( )+( )–( CONTROL MODULE )+( )–( )+( 47K EOL RESISTOR ELR-47K CONNECT MODULES TO LISTED COMPATIBLE CONTROL PANELS ONLY SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX. TWISTED PAIR IS RECOMMENDED )+( (–) (+) MODULE POLARITIES ARE SHOWN IN ALARM SUPERVISION TO NEXT CONTROL MODULE LAST MODULE MUST RETURN WIRES FOR SUPERVISION FROM PANEL OR PREVIOUS DEVICE TO NEXT DEVICE SPEAKERS MUST BE LISTED FOR FIRE PROTECTION. REFER TO THE RELAY CONTACT RATING TABLE FOR MAXIMUM LOAD. *NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE. C0915-03 Figure 6. Typical fault tolerant wiring for speaker supervision and switching, NFPA Style Z: AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM. SEE PANEL INSTALLATION MANUAL FOR DETAILED INFORMATION. AUDIO CIRCUIT DO NOT LOOP WIRE AROUND TERMINALS 10 & 11. BREAK WIRE TO ENSURE SUPERVISION OF CONNECTIONS. AUDIO AMPLIFIER, 70.7 Vrms MAX. AMPLIFIER MUST PROVIDE WIRING SUPERVISION PER NFPA. CONNECT MODULES TO LISTED COMPATIBLE CONTROL PANELS ONLY WIRES MUST BE SUPERVISED PER NFPA )–( )+( CONTROL MODULE )–( )+( )–( )+( 47K EOL RESISTOR IS INTERNAL AT TERMINALS 8 & 9 SUPERVISION )–( )–( )+( )+( BYPASS CAPACITORS: 100µ A2143-20 NONPOLARIZED <10µA LEAKAGE FROM PANEL OR PREVIOUS DEVICE SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX. TWISTED PAIR IS RECOMMENDED ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED (–) (+) TO NEXT CONTROL MODULE LAST MODULE MUST RETURN WIRES FOR SUPERVISION MODULE POLARITIES ARE SHOWN IN ALARM TO NEXT DEVICE SPEAKERS MUST BE LISTED FOR FIRE PROTECTION. REFER TO THE RELAY CONTACT RATING TABLE FOR MAXIMUM LOAD. *NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE. C0916-03 SS-460-001 3 I56-3850-002 WARNING All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module. Three-Year Limited Warranty System Sensor warrants its enclosed module to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this module. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the module which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Repair Department, RA SS-460-001 #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state. 4 I56-3850-002 ©2009 System Sensor
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.3 Linearized : No XMP Toolkit : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:08:23 Create Date : 2009:02:09 09:55:05-06:00 Modify Date : 2009:02:09 09:55:19-06:00 Metadata Date : 2009:02:09 09:55:19-06:00 Creator Tool : Adobe InDesign CS3 (5.0.3) Thumbnail Format : JPEG Thumbnail Width : 256 Thumbnail Height : 256 Thumbnail Image : (Binary data 8504 bytes, use -b option to extract) Version ID : 1 Instance ID : uuid:366355fa-02d6-5742-881e-9d5066ef3c20 Document ID : adobe:docid:indd:a3ada2d4-dfc5-11dd-a19a-d832931d4524 Rendition Class : proof:pdf Derived From Instance ID : 942850ac-d7df-11dc-bf79-bb8017c0347a Derived From Document ID : adobe:docid:indd:4362ce94-15db-11d8-b2e4-8fa6e2e97ba9 Derived From Version ID : 1 Manifest Link Form : ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream Manifest Placed X Resolution : 72.00, 72.00, 72.00, 72.00, 72.00, 72.00 Manifest Placed Y Resolution : 72.00, 72.00, 72.00, 72.00, 72.00, 72.00 Manifest Placed Resolution Unit : Inches, Inches, Inches, Inches, Inches, Inches Manifest Reference Instance ID : uuid:C8E6CE0A1699DC119ED08C06D361F2DB, uuid:CFE6CE0A1699DC119ED08C06D361F2DB, uuid:57DB6954B699DC119ED08C06D361F2DB, uuid:ACDBE915ACA4DC119ED08C06D361F2DB, uuid:59DB6954B699DC119ED08C06D361F2DB, uuid:5BDB6954B699DC119ED08C06D361F2DB Manifest Reference Document ID : uuid:3B313C156BFE11DBAFF1B13156E52882, uuid:CBE6CE0A1699DC119ED08C06D361F2DB, uuid:E8EE4409A87911DB8098FF03DB81C7FE, uuid:E8EE440BA87911DB8098FF03DB81C7FE, uuid:E8EE440DA87911DB8098FF03DB81C7FE, uuid:E8EE440FA87911DB8098FF03DB81C7FE Format : application/pdf Producer : Adobe PDF Library 8.0 Trapped : False Page Count : 4 Creator : Adobe InDesign CS3 (5.0.3)EXIF Metadata provided by EXIF.tools