TRANE Air Conditioner/heat Pump(outside Unit) Manual L0810502

User Manual: TRANE TRANE Air conditioner/heat pump(outside unit) Manual TRANE Air conditioner/heat pump(outside unit) Owner's Manual, TRANE Air conditioner/heat pump(outside unit) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 8

DownloadTRANE  Air Conditioner/heat Pump(outside Unit) Manual L0810502
Open PDF In BrowserView PDF
18-BC42 D 1-2

To

Library
Product Section
Product

It's Hard

Model

To Stop A Trane_. M

Literature Type

I STALLER'
GUI E

Sequence
Date
File No.
Supersedes

Model:

Heat Pumps

TWZ036-060A
IMPORTANT
-- This Document
pack upon completion
of work.

is customer

property

and is to remain

These instructions
do not cover all variations
in systems
nor provide
for every possible
contingency
to be met in
connection
with installation.
Al! phases
of this installation must comply
with NATIONAL,
STATE AND LOCAL
CODES.
Should further
information
be desired or should
particular
problems arise which are not covered sufficiently for
the purchaser's
purposes, the matter should be referred to your
installing
dealer or local distributor.
A.

with this unit.

Please

return

to service

information

d)

GENERAL

NOTICE:
The TWZ036-06OA
proved
with indoor
units
expansion
valve refrigerant
Check for transportation
promptly, to the carrier,

outdoor
equipped
controls.

units
with

are only apthermostatic

damage after unit is uncrated.
Report
any damage found to the unit.

To determine
the electrical
power requirements
of the unit,
refer to the nameplate
of the unit. The electrical power available
must agree with that listed on the nameplate.
The Weathertron
® Heat Pump has been designed and manufactured to withstand
and operate
in severe winter conditions.
However, there are precautionary
steps which should be taken
at the time of installation
which will help assure the efficient
operation of the unit. It is recommended
that these precautions be taken
for units being
installed
in areas
where
snow accumulation
and prolonged
below
freezing
temperatures
occur.
1. Units should be elevated 3 to 12 inches above the pad or
rooftop, depending on local weather. This additional
height will
allow better drainage
of snow and ice (melted during defrost
cycle) prior to its refreezing.
This should prevent a build-up of
ice around the unit which occurs when unit is not elevated.
Insure
that drain
holes in unit base pan are not obstructed
preventing
draining
of defrost
water.
2. If possible, avoid locations that are likely to accumulate
snow
drifts.
If not possible, a snow drift barrier should be installed
around the unit to prevent a build-up of snow on the sides of the
unit and should be of sufficient distance from the unit to prevent
restriction
of airflow to and from the unit. Also allow for proper
maintenance
space. The barrier should be constructed
of materials which will blend in with the building design.

3. Avoid locating
the unit where
condensation
and freezing
of
defrost
vapor may annoy
the customer.
For instance,
installing
the unit under
a bedroom,
kitchen,
or picture
window
may be
annoying
to the customer
since condensate
and fog will occur
during
the defrost
cycle.

4. Avoid locating the unit under the eaves or other overhead
structures
as sizeable icicles may form and the unit may be
damaged by these falling icicles.

Since the manufacturer
has a policy of continuous
product improvement,
it reserves the right to change
specifications
and design without notice.

© American

Standard

Inc.

1997

Dwg.

No. 18-BC42D1-2

I STALLER'S
B. REFRIGERANT

FLOW

GUI

E

CONTROLS

1. Determine

Use only approved indoor units. The indoor coil flow control must
be equipped with a thermal expansion valve. Indoor units without factory installed TXV must be modified to include the approved
BAYTXV-kit.
C. LOCATION

& PREPARATION

OF THE

1. The unit should be set on a level support
as the unit base pan.

UNIT

types

of bends

NOTE:
Large diameter
it has been shaped.

way to run the lines.

to be made and space limitations.

tubing

will be very difficult

to rebend

once

3. Determine
the best starting point for routing the refrigerant
tubing -- INSIDE OR OUTSIDE THE STRUCTURE.

pad at least as large

2. The support
pad must NOT be in direct contact with any
structure.
The unit must be positioned a minimum of 12" from
any wall or surrounding
shrubbery
to insure adequate airflow. A
30" clearance must be provided in front of control box (access
panels) & any other side requiring
service access to meet National Electrical
Code. The unit must be far enough away from
any structure
to prevent excess roof run-off water from pouring
directly on the unit.
3. The top discharge area must
(5) feet above the unit.

2. Consider

the most practical

be unrestricted

for at least

4. Provide a pull-thru
hole of sufficient size to allow both liquid
and gas lines plus fittings to clear. The location of this hole (if
practical) should be just about the wall plate which is resting on
the foundation.
5. Be sure the tubing
6. Uncoil

the tubing

is of sufficient

length.

-- do not kink or dent.

7. Route the tubing making
all required
bends
secure the tubing before making connections.

and

properly

five
8. To prevent
a noise within the building
structure
due to
vibration transmission
from the refrigerant
lines, the following
precautions
should be taken:

4. When the outdoor unit is mounted on a roof, be sure the roof
will support
the unit's weight.
Properly
selected vibration
isolators are recommended
to prevent transmission
to the building structure.

a. When the refrigerant
lines have to be fastened to floor
joists or other framing in a structure,
use isolation type hangers.

5. The maximum
length of refrigerant
lines from outdoor
indoor unit should NOT exceed eighty (80) feet.

b. Isolation hangers
should also be used -when refrigerant
lines are run in stud spaces or enclosed ceilings.

6. Maximum difihrence
five (25) feet.

in elevation

to

should not exceed twenty-

7. Locate and install indoor coil or blower coil in accordance with
instruction included with that unit.

c. Where the refrigerant
lines run through
should be insulated
and isolated.
d. Isolate
E. SERVICE

8. A pull-thru hole for the refrigerant
sufficient size to allow the passage
lines.

lines should be provided of
of both liquid and suction

9. Determine
if adequate power supply
according to nameplate
specifications.
10. Install
codes.

the unit in accordance

D. INSTALLING

is available

with national,

REFRIGERANT

and correct

state,

and local

LINES

Pressure
taps are provided on the service
service valve of outdoor unit for compressor

valve plate and on
suction and liquid

pressures.

The indoor end of recommended
refrigerant
line sets may be
straight
or with a 90 degree bend, depending
upon situation
requirements.
This should be thoroughly
checked out before
ordering refrigerant
line sets.
The gas line must always

be insulated.

The units are factory charged with the system charge required
when using twenty-five
(25) feet of connecting line. Unit nameplate charge is the same. Final refrigerant
charge adjustment
is necessary,
use the Charge
Charts
in the outdoor
unit
Service Facts.

PAGE 2

a wall or sill, they

the lines from all ductwork.
VALVE

BRASS LIQUID
ERATION

AND

OPERATION
GAS LINE

SERVICE

VALVE

OP-

The Service Valves are factory shipped in the seated position to
hold factory charge.
The pressure
tap service port (when depressed) opens only to the field brazing side of the valve when the
valve is in the seated position. The liquid line valve isnot a back
seating valve (see WARNING
below).

WARNING:

Extreme
caution
should
be
exercised
so the internal
steel stem retaining
ring is not
damaged
by backing
out the valve stem when opening
the
valve.
If the valve stem is forced
out past the retaining
ring, system pressure
could force the valve stem out of the
valve body. If the retaining
ring is missing,
do not attempt
to open the valve.
See Figure
2.
BRASS

GAS LINE

BALL

SERVICE

VALVE

The Brass Gas Line Ball Service Valve is shipped in the closed
position to hold the factory refrigerant charge. The pressure tap
service port (when depressed) opens only to the field brazing side
when the valve is in the closed position.
The Gas Line Service Valve is full open with a 1/4 turn counterclockwise.
See Figure 3.

Dwg. No. 18-BC42D1-2

I STALLER'S

@

NOTICE:
pressure

LiQUiD LiNE SERVICE VALVE

GUI

E

Use care to make sure that no moisture
tap port, while wet rag is being used.

enters

6. Remove braze shield from clear plastic bag. Soak pad in water
and place over suetion and liquid lines to protect unit finish. See
Figure 4. Discard pad when finished with brazing.
UNIT SIDE OF
SERVICE

LIQUIDLINE

7. Use a Dry Nitrogen Purge and Brazing Alloy without flux
when brazing the field line to the copper factory connection. Flow
dry nitrogen into either valve pressure tap port, thru the tubing
and out the other port while brazing.

HEX HEADED

8. Braze

using accepted

good brazing

techniques.

CONNECTION

LEAK

CHECK

IMPORTANT:
fore attaching
RETAINING

BRAZING

REFRIGERANT

RING

LINES

1. Before brazing, remove plugs from external copper stub tubes.
Clean internal
and external
surfaces of stub tubes prior to
brazing.
2. Cut and fit tubing
3. Insulate
4. Do NOT
contact with

the entire

minimizing

the use of sharp

90 ° bends.

liquid

line

to come

in direct

5. Precautions
should be taken
to avoid heat damage
to
the pressure
tap valve core during brazing.
It is recommended that the pressure
tap port valve core be removed
and a wet rag wrapped
around
the valve body.

LiNE SERVICE
CAP

UNIT

valve

core

be-

After brazing operation of refrigerant
lines to both the outdoor
and indoor unit is completed,
the field brazed connections
must
be checked for leaks. Pressurize
through the service valve ports,
the indoor unit and field refrigerant
lines with dry nitrogen to
200 psi. Use soap bubbles or other leak-checking
methods to see
that all field joints are leak-free! If not, release
pressure;
then
repair!
SYSTEM

EVACUATION

NOTE:
Since the outdoor
unit has a refrigerant
and liquid
line valves
must remain
closed.

charge,

the gas

VALVE

1. Upon completion of leak check, evacuate the refrigerant
lines
and indoor coil before opening the gas and liquid line valves.
2. Attach appropriate
hoses
liquid line pressure
taps.

from manifold

gauge

to gas and

NOTE:
Unnecessary
switching
of hoses can be avoided and
complete evacuation
of all lines leading to sealed system can be
accomplished
with manifold center hose and connecting branch
hose to a cylinder of HCFC-22 and vacuum pump.
3. Attach
4. Evacuate
microns.

_

center
until

hose of manifold
the micron

gauges

gauge

reads

to vacuum

pump.

no higher

than

350

5. Close offvalve to vacuum pump and observe the micron gauge.
If gauge pressure rises above 500 microns in one (1) minute, then
evacuation
is incomplete
or system has a leak.

SIDE

OF VALVE

#
PRESSURE

port

gas line and its fittings.

allow uninsulated
bare gas line.

GAS

Replace
pressure
tap
hoses for evacuation.

TAP

PORT

j
/
GAS

LINE

CONNECTION

d,

CAP

_

6. If vacuum gauge does not rise above 500 microns
minute, the evacuation
should be complete.

in one (1)

7. With a vacuum pump and micron gauge blanked off, open
valve on HCFC-22 cylinder and charge refrigerant lines and
indoor coil with vapor to tank pressure of HCFC-22 supply.

&

NOTE:
DO NOT
ATMOSPHERE.

VENT

REFRIGERANT

INTO

THE

CORE

Dwg. No. 18-BC42D1-2

PAGE 3

I STALLER'S

GUI

E
If refrigerant
lines are longer than 25 feet and/or a dift_rent size
than recommended,
it will be necessary to adjust system refrigerant charge upon completion
of installation.

HEAT SHIELD

F. ELECTRICAL

CONNECTIONS

WARNING: When
installing
this equipment,
tions to avoid

or servicing
ALWAYS exercise
basic safety
precauthe possibility
of electric
shock.

1. Power -wiring and grounding
local codes.
2,

Power

supply

3. Install

must

a separate

4. Ground

agree with equipment
disconnect

the outdoor

of equipment

switch

must comply with

nameplate.

at the outdoor

unit.

unit per local code requirements.

5. Provide flexible electrical conduit whenever vibration
mission may create a noise problem within the structure.

trans-

6. The use of color coded low voltage -wire is recommended
to
simplify connections between the outdoor unit, the thermostat,
and the indoor unit.

Table 1 -- NEC Class II Control

Wiring

24 VOLTS
WIRE SIZE

MAX. WIRE LENGTH

*22 AWG

30 FT.

20 AWG

100 FT.

18 AWG

150 FT

16 AWG

225 FT.

14 AWG

300 FT.

8. Close valve on HCFC-22 supply cylinder.
Close valves on
manifold gauge set and remove refrigerant
charging hoses from
liquid and gas pressure tap ports.
NOTE:
A 3/16"
Allen
wrench
is required
to ()pen liquid
line
service valve. A 1/4" Open End or Adjustable
wrench is required
to ()pen gas line valve. An Adjustable
or 3/4" Open End wrench
is required
to take ()['['the valve stern cap.

9. The liquid line shut-offvalve
can now be opened. Remove shutoffvalve cap. Fully insert hex wrench into the stein and backout
counterclockwise
until valve stein just touches retainer
ring
(approximately
five (5) turns) observing WARNING
statement.
See Figure 2.

*If 22 AWG is used, make
7. Table 1 defines maximum
from outdoor unit, to indoor

11. The gas valve can now be opened.
Open the gas valve by
removing
the shut-off valve cap and turning
the valve stem
1/4 turn counterclockwise,
using 1/4" Open End or Adjustable
wrench.
See Figure 3.
12. The gas valve is now open for refrigerant
stem cap to prevent leaks. See Figure 3.

PAGE 4

quality

wire.

total length of low voltage
unit, and to thermostat.

wiring

8. Mount the indoor thermostat
in accordance
with instruction
included with the thermostat.
Wire per appropriate
hook-up
diagram (included in these instructions).
G. ELECTRICAL

10. Replace liquid service pressure tap port cap and valve stem
cap. These caps MUST BE REPLACED
to prevent
leaks.
Replace valve stein and pressure
tap cap finger tight, then
tighten an additional
1/6 turn.

sure it is high

HEATERS

Electric heaters, if used, are to be installed in the air handling
device according to the instructions
accompanying
the air handler and the heaters.
H. START
These units
installed.

KIT
have

quick

start

components

which

are factory

flow. Replace valve

Dwg. No. 18-BC42D1-2

I STALLER'S
I.

OUTDOOR

THERMOSTAT

GUI

E

K. OPERATIONALANDCHECKOUTPROCEDURES

An outdoor thermostat
TAYSTAT250A
may be field installed.
For data see wiring diagram attached
to unit and instruction
sheet packaged with outdoor thermostat.

Final phases of this installation
are the unit Operational
and
Checkout Procedures
which are found on page 8 of this instruction.

J. DEFROSTCONTROL

L.

The demand defrost control measures
heat pump outdoor ambient temperature
with a sensor located outside the outdoor coil. A
second sensor located on the outdoor coil is used to measure the
coil temperature.
The diflhrence between the ambient and the
colder coil temperature
is the dift_rence or delta-T measurement.
This delta-T measurement
is representative
of the operating
state and relative capacity of the heat pump system. By measuring the change in delta-T, we can determine
the need for defrost.
The coil sensor also serves to sense outdoor coil temperature
for
termination
of the defrost cycle.

After all electrical wiring is complete, SET THE THERMOSTAT
SYSTEM SWITCH IN THE OFF POSITION SO COMPRESSOR
WILL NOT RUN, and apply power by closing the system main
disconnect switch. This will activate the compressor
sump heat.
Do not change the Thermostat
System Switch until power has
been applied long enough to evaporate any liquid of HCFC-22 in
the compressors
(30 minutes for each pound of HCFC-22 in the
system as shown on the nameplate).
Following this procedure
will prevent compressor
damage at the initial start-up.

FAULT

DETECTION

A fault condition is indicated by the flashing
control inside the heat pump control box.

light on the defrost

In normal operation, the defrost control light will flash once each
second. If the light is flashing more than once per second or notat-all, refer to the service manual for that unit.

COMPRESSOR

SUMP

HEAT

Record the "POWER
below:

APPLIED

Time

A.M./P.M.

DATA" on the designated

lines

Date

By

Electrician
(SEE WIRING DIAGRAMS )

PIN

IDENTIFICATION

1. NORM.
= Normal
(This wire, as shipped, is unattached
to
any pin. In this position, the default condition is normal operation. However, after checking for proper operation,
the wire
should be returned
to the normal pin.)
2. TST. = Test
(Red test wire in this position
defrost board timings.)

speeds

up all

3. FOR. DFT. = Forced Defrost (Touch the red test wire to this
pin for ten (10) seconds to initiate a forced defrost.
Return wire
to the normal pin after defrost initiates.)

4. FOR. FLT. = Forced Fault (Touch the red test wire to this pin
for ten (10) seconds to demonstrate
a fault condition.)
DEFROSTCONTROLCHECKOUT
Normal
a.
b.
c.
d.

operation

LED on
24V AC
24V AC
Defrost
Defrost"
operating

If a defrost
information

requires:

board flashing 1 time/second.
between R & B
between Y & B with unit operating
initiation
when test wire is moved to "Forced
pin, then return to "Normal Pin", with unit
in heating mode.

control problem
in control box.

Dwg. No. 18-BC42D1-2

is suspected,

re%r to the

service

PAGE 5

I STALLER'S

GUI

A TYPICAL

E

FIELD WIRING DIAGRAM FOR TWZ036-060A
VARIABLE SPEED AiR HANDLERS

WITH

NOTES:
1. POWER WIRING AND GROUNDING
COMPLY WITH LOCAL CODES.
2. BE SURE POWER
NAMEPLATE.
3. LOW VOLTAGE
CONDUCTOR.
4. USE COPPER

SUPPLY

WIRING

OF EQUIPMENT

3 HEAT/2

AGREES

WITH

ONLY.

IS NOT USED, CONNECT
TO W2.
IS NOT USED, CONNECT
TO W1.

7. IF ELECTRIC
CONNECT A
IF ELECTRIC
CONNECT A
8. CONNECT

A JUMPER

WIRE

A JUMPER

WIRE

HEAl PUMP
O, D, SECTION
ITWO

HEATER DOES NOT HAVE 3RD CONTACTOR
JUMPER WIRE FROM W3 TO W2.
HEATER DOES NOT HAVE 2ND CONTACTOR
JUMPER WIRE FROM W2 TO W1.

OUTDOOR

TO POWER SUPPLY PER
LOCAl CODED &AS DEF NED

CO@

MINIMUM

5. POLARIZED
PLUG SECTION PM-A IS ATTACHED TO HEATER
CONTROL BOX. SECTION 1-PF IS FACTORY WIRED INTO
AIR HANDLER.
6. IF ODT-B
FROM W3
IF ODT-A
FROM W2

//EATPUMP
TAYSTATS02

EQUIPMENT

TO BE NO. 18 A.W.G.

CONDUCTORS

E!ECTRON!C
THERMOSTAT

MUST

F TO THERMOSTAT

COMPRESSORS/

(CH),
J

(BH).

......
:tL_

F AS SHOWN.

9. IF AN INSUFFICIENT
NUMBER OF CONDUCTORS
IS PRESENT,
OMIT F CONNECTION
TO THE THERMOSTAT
AND CONNECT
OUTDOOR F TO R IN THE OUTDOOR UNIT.

I

{
.............................
i

NOT
10 X2_i/_,

10. X2 MUST BE CONNECTED
TO VARIABLE SPEED AIR HANDLER
TERMINAL W3 AS SHOWN FOR PROPER INDOOR AIR FLOW
DURING THE DEFROST CYCLE.

\/\//

OPERATION,

0OTA (

.......

IN ER COMPONENI WIRING

............................24 V. _ FACTORY
......................
LINE V._" WRING

TO POWR SbPPI Y
PER

OCAL CODES

24V.
_ FIELD
lINE V:,#W!RF;6

From Dwg. 21B151201

A TYPICAL

FIELD WIRING
VARIABLE

DIAGRAM FOR TWZ036-060A
SPEED FURNACES

Rev. 0

WiTH

NOTES:
1. POWER WIRING
LOCAL CODES.

AND GROUNDING

2. BE SURE POWER
3. LOW VOLTAGE
4. USE COPPER

SUPPLY

WIRING

OF EQUIPMENT

AGREES

WITH

MUST COMPLY

EQUIPMENT

TO BE NO. 18 A.W.G. MINIMUM

CONDUCTORS

WITH

NAMEPLATE.

ELECTRONICHEATPUMP
THERMOSTATTAYSTAT502
3 HEAT/2COOL

CONDUCTOR.

TO POWER SUPPLY PER
LOCAL CODES & AS DEFINED
IN FIELD WIRING FABLE

ONLY.

5. MAKE THIS JUMPER CONNECTION ONLY IF THE FURNACE
ENABLE SIGNAL FOR HEATING OPERATION.
6. BONNET THERMOSTAT
REQUIRED IF BONNET
OF 150 ° OR GREATER IS ANTICIPATED.

HEATPUMP

NEEDS FAN

TEMPERATURE

T_

]

_m

__M;_I tl
VARIABLE

SPEED

GAS FURNACE
I WITH ICM FAN MOTORI

£.
[NTER-COMPONENT WIRING

-_'

2dV, ]
FACTORY
LINE V._"WIRING

I

I

L]

SEE FURNACE DIAGRAM
FOR PROPER OIP SWITCH
SETTINGS AND HUMIDISTAT
OPERATION,

L'_

-[0POWER SUPPLY
PER LOCAL CODES

LTAYPLUS103A

24V.
] FIELD
LINE V,_ WIRING

From Dwg. 21B151210

PAGE 6

Rev. 0

Dwg. No. 18-BC42D1-2

I STALLER'S
TWZ036=060A

OUTLINE

GUI

E

DRAWING
NOTE: ALL DIMENSIONS
ARE IN MM (INCHES).

SERVICE

PANEL

_

ELECTRICAL
AND REFRIGERANT
COMPONENTS
CLEARANCES
PER
PREVAILING
CODES.

UNIT
SHOULD
BE PLACED
SO ROOF
RUN-OFF
WAFER
DOES
NO]
POUR
DIRECTLY
ON UNIT,
AND
SHOJLD
BE
AT
LEAST
305
(12")
FROM
WALL
AND ALL
SURROUNDING
SHRUBBERY
ON TWO SIDES,
OTHER
TWO SIDES
UNRESTRICTED.

!r

,,

!! !
U !
28,6

11-1/8)

222
(7/8)
ELECTR]CAL
22.2

17/8)

LOW

VOL

PRESSURE
I/4"

DA

FLARE

K,(},

D A, ItOLE
POWER
D[A,

/

m m

!!

U
il

I
I

I!
Ii

II
II

II
I

El

I

IE

II

I

U !

!I

m F

U

m

m

A

i! ! !i m !

SUPPLY
_ OLE

!

H !

lADE

_1 I

TAPS

!

m m !
II II I

El
II

I
I

II
II

II
II

I
I

H

II

i!

m m m !

II

II

I

H m m m !

FITFINGS

LINE

lr

!!

!! m m

U',!!im!',

W[FH

229

LIQUID

![

19)

i

1!5

(4

4

II

I/2)

SERVICE

VALVE,'E'O.D.
FEMALE
BRAZED
CONNECq
ION
WITH
I/4"
SAE
FLARE
PRESSURE
TAP
_-ITT[NG.

GAS LINE
BALL
SERVICE
VALVE,
BALL
I/4
TURN
"D'O.D.
FEMALE
BRAZED
CONNECTION
WITH
I/4"
SAE
FLARE
PRESSURE
TAP
FITTING.

5/8}

.....60

MODELS
TWZ036A-A

TWZ048A-A

TWZ060A-A

{2

3/8)

A

B

C

1095

1010

902

(43-1/8)

(39-3/4)

(35-1/2)

1095

1010

902

(43-1/8)

(39-3/4)

(35-1/2)

1095

1010

902

(43-1/8)

(39-3/4)

(35-1/2)

D

E

7/8

3/8

1-1/8

3/8

1-1/8

3/8

From Dwg. 21 D147482 Rev. 6

Dwg. No. 18-BC42D1-2

PAGE 7

I STALLER'S

GUI

E

CHECKOUT
After installation has been completed,
following list:
1. Refrigerant

PROCEDURE

it is recommended

be checked

against

the
[

]

[

]

[

]

4. Have passages through masonry been sealed? If mortar is used, prevent mortar from
coming into direct contact with copper tubing ....................................................................................

[

]

5. Indoor coil drain line drains freely.

Pour water into drain pan ............................................................

[

]

6. Supply

open and unobstructed

[

]

7. Return air filter installed ......................................................................................................................

[

]

8. Thermostat thermometer
is accurate. Check against a reliable thermometer.
Adjust
per instructions with thermostat ..........................................................................................................

[

]

9. Is correct

[

]

2. Suction

Line, Leak checked

that the entire system

..........................................................................................................

Lines and Fittings properly

3. Have all Refrigerant

registers

speed

insulated ......................................................................................

Lines been secured

and return grilles

tap being used?

and isolated properly?

(Indoor

blower

motor)

........................................................

...............................................................

...................................................................

SYSTEM OPERATIONAL

CHECK

IMPORTANT: To prevent compressor damage which may result from the presence
crankcase, these procedures should be followed at initial Start-Up and at anytime
12 hours or more.

of LIQUID refrigerant in the
the power has been off for

1. Before proceeding with this "Operational Check," go to "Compressor Sump Heat Section" of this instruction to
determine the time compressor heat has been "ON," and make entry of the designated lines, in Step 2.
2. Start-Up Time

A.M./P.M.

Time Lapse

Power Applied Time

Hours

A.M./P.M.
Minutes.

3. If Steps 1 and 2 cannot be used, then place thermostat's system switch in the "OFF" position and apply power
by closing system disconnect switch. This energizes compressor
heat and evaporates the liquid in the
crankcase. TO EVAPORATE LIQUID ALLOW AT LEAST ONE-HALF HOUR PER POUND (HCFC-22), AS
SHOWN ON UNIT NAMEPLATE.
OPERATING PRESSURES: After the unit has operated in the cooling mode for a short period of time, install
pressure gauges on the gauge ports of the discharge and suction line valves. Check the suction and discharge
pressures and compare them to the normal operating pressures provided in the unit's Service Facts.

NOTE: Use the pressures from Service Facts to determine the unit refrigerant charge.
To charge the system accurately, use charging curve, or pressures depending
on flow control.

4. Except as required for safety while servicing: DO NOT OPEN SYSTEM

DISCONNECT

SWITCH.

SUPPLEMENTARY HEATERS CHECKOUT PROCEDURES, IF USED
DOES HEATER
1. Be sure the fused disconnect

3. Check fuses for proper size per nameplate

NOTE:

OPERATION

Technical Literature

PAGE 8

and grounding
specifications

................................

[

]

according to codes .....................................

[

]

[

]

[

]

.....................................................................

in place and secured ..................................................................................

OF HEATERS

SYSTEM.

CIRCUIT?

switch is "OFF," and safety label (if any) is attached

2. Check on field wiring for sound connections

4. Check control box panel-

REQUIRE A SEPARATE

MUST BE CHECKED

DURING THE OPERATION

CHECK OF THE TOTAL
The

-Printed

in U.S.A.

Trane

Company

6200 Troup Highway
Tyler, TX 75707

Dwg. No. 18-BC42D1-2



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 8
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 4, 0, 0, 13
Create Date                     : Thu Nov 06 04:16:03 2008
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu