TRANE Furnace/Heater, Gas Manual L0902549
User Manual: TRANE TRANE Furnace/Heater, Gas Manual TRANE Furnace/Heater, Gas Owner's Manual, TRANE Furnace/Heater, Gas installation guides
Open the PDF directly: View PDF .
Page Count: 38
Download | |
Open PDF In Browser | View PDF |
IIIIII IIIIIII IIIIIII IIIIII II 1 8- CD1 9 D8- 1 5 Upflow / Horizontal & Downflow / Horizontal, Gas-Fired, Direct Vent, 2-Stage Condensing Furnaces with Variable Speed Inducer *UX2B060A9362A *UX2D120A9602A *DX2C100A9482A *UX2B080A9422A *DX2B060A9362A *DX2D120A9602A *UX2C100A9482A *DX2B080A9422A *__First letter may be "A" or "T" ALL phases of this installation must comply with NATIONAL, IMPORTANT -- This Document is customer Please return to service information STATE AND LOCAL CODES property and is to remain with this unit. pack upon completion of work. *UX2 *DX2 DOWNFLOW A!R FLOW A/R FLOW UPFLOW AIR FLOW / UPFLOW/HORIZONTAL LEFT \ DOWNFLOW/HORIZONTAL / i RIGHT FLOW _ \ ° A341624P03 Installer's Guide SAFETY SECTION The following safety practices and precautions must be followed during the installation, servicing, and operation this furnace. of 1. Use only with the type of gas approved for this furnace. Refer to the furnace rating plate. 2. Install this furnace only in a location and position as specified in "Location and Clearances" (page 3), of these instructions. 3. Provide adequate combustion and ventilation air to the furnace space as specified in "Air for Combustion and Ventilation" (pages 7-8), of these instructions. 4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the "Venting" section (pages 13-23), of these instructions. 5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in "Gas Piping" (page 31), of these instructions. 6. Always install the furnace to operate within the furnace's intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified on the unit rating plate. Airflow with temperature rise for cfm versus static is shown in the Service Facts accompanying this furnace. 7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. 8. A gas-fired furnace for installation in a residential garage must be installed as specified in "Location and Clearances" section (page 3), of these instructions. 9. The furnace may be used for temporary heating of buildings or structures under construction only when the following conditions have been met: a. The furnace venting system must be complete and installed per manufacturer's instructions. b. The furnace is controlled only by a room thermostat (no field jumpers). c. The furnace return air duct must be complete and sealed to the furnace and clean air filters are in place. d. The furnace input rate and temperature rise must be verified to be within nameplate marking. e. 100% of the furnace combustion air requirement must come from outside the structure. f. The furnace return air temperature range is between 55 and 80 degrees Fahrenheit. g. Clean the furnace, duct work, and components upon substantial completion of the construction process, and verify furnace operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer's instructions. 10. This product must be gas piped by a Licensed Plumber or Gas Fitter in the Commonwealth of Massachusetts. To prevent shortening its service life, the furnace should not be used as a "Construction Heater" during the finishing phases of construction until the requirements listed in item 9, a-g of the safety section of this publication have been met. Condensate in the presence of chlorides and fluorides from paint, varnish, stains, adhesives, cleaning compounds, and cement create a corrosive condition which may cause rapid deterioration of the heat exchanger. © 2008 Trane All Rights Reserved CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation: 1. Seal any unused openings in the venting system. 2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition. 3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other deficiencies which could cause an unsafe condition. 4. Close fireplace dampers. 5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan. 6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously. 7. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CAN/CGA B149 Installation Codes. 8. After it has been determined that each appliance connected to the venting system properly vents where tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use. Safety signal words are used to designate a degree or level of seriousness associated with a particular hazard. The signal words for safety markings are DANGER, WARNING, and CAUTION. a. DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. This signal word is limited to the most extreme situations. b. WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. c. CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury, death or property damage. Improper servicing could result in dangerous operation, serious injury, death, or property damage. 1 8-CD1 9D8-1 5 Installer's GENERAL Contents The manufacturer assumes no responsibility for equipment installed in violation of any code or regulation. It is recommended that Manual J of the Air Conditioning Contractors Association (ACCA) or A.R.I. 230 be followed in estimating heating requirements. When estimating heating requirements for installation at Altitudes above 2000 ft., remember the gas input must be reduced (See GAS INPUT ADJUSTMENT). Material in this shipment has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in shipment. Unpack carefully after moving equipment to approximate location. If damage to contents is found, report the damage immediately to the delivering agency. Codes and local utility requirements governing the installation of gas fired equipment, wiring, plumbing, and flue connections must be adhered to. In the absence of local codes, the installation must conform with latest edition of the National Fuel Gas Code ANSI Z223.1 • National Installation Code, CAN/CGA B149.1. The latest code may be obtained from the American Gas Association Laboratories, 400 N. Capitol St. NW, Washington D.C. 20001. 1-800-699-9277 or www.aga.org These furnaces have been classified as CATEGORY IV furnaces in accordance with latest edition of ANSI Z21.47 standards ° CAN/CGA 2.3. Category IV furnaces operate with positive vent static pressure and with a flue loss less than 17 percent. These conditions require special venting systems, which must be gas tight and water tight. These Category IV Direct Vent furnaces are approved for installation in Manufactured/Mobile housing when used with BAYMFGH001A. LOCATION AND CLEARANCES The location of the furnace is normally selected by the architect, the builder, or the installer. However, before the furnace is moved into place, be sure to consider the following requirements: 1. Is the location selected as near the chimney or vent and as centralized for heat distribution as practical? 2. Do all clearances between the furnace and enclosure equal or exceed the minimums stated in Clearance Table on the Outline Drawings. 3. Is there sufficient space for servicing the furnace and other equipment? A minimum of 24 inches front accessibility to the furnace must be provided. Any access door or panel must permit removal of the largest component. 4. Are there at least 3 inches of clearance between the furnace combustion air openings in the front panel and any closed panel or door provided? 5. Are the ventilation and combustion air openings large enough and will they remain unobstructed? If outside air is used, are the openings set above the highest snow accumulation level? (See the Air for Combustion and Ventilation section.) 6. Allow sufficient height in supply plenum above the furnace to provide for cooling coil installation, if the cooling coil is not installed at the time of this furnace installation. 7. A furnace shall be installed protected from water. so electrical components 8. If the furnace is installed in a residential garage, it must be installed so that the burners, and the ignition 18-CD19D8-15 Guide are Installation Instructions General Location and Clearances Outline Drawings Upflow Installation Downflow Installations Air For Combustion and Ventilation Duct Connections Return Air Filters General Venting Venting Materials Vent Tables Horizontal Venting Through Wall Venting Through the Roof Venting Routed Through a Masonry Chimney Downward Venting Condensate Drain Instructions Field Wiring Diagrams Electrical Connections Gas Piping Combustion and Input Check High Altitude Derate Start-up and Adjustment Preliminary Inspections Lighting Instructions Sequence of Operation Control and Safety Switch Adjustments Abnormal Conditions IFC Error Flash Codes Fault Code Recovery source are located not less than 18 inches above the floor and the furnace must be located or protected to avoid physical damage from vehicles. IMPORTANT: The furnace must be installed level The only allowable variation would be slightly to the left and/or forward in upflow installations or slightly toward the front in horizontal installations. This is necessary for proper condensate drainage. Do not install the furnace in a corrosive or contaminated atmosphere. Failure to follow this warning could result in early equipment failure. Do not install the furnace directly on carpeting, tile or other combustible material other than wood flooring. For vertical downflow application, subbase (BAYBASE205) must be used between the furnace and combustible flooring. When the downflow furnace is installed vertically with a cased coil, a subbase is not required. 3 ii 4_ | *UX2 UPFLOW / HORIZONTAL OUTLINE 3 DRAWING ,l-m.. -,-- 5/8" l (ALL 4- I/ilJ ltl IN INCHES) Ill _---r_2"FLUE I I CONNECT II II 01_0 AIR /._ ARE DIM "B" OUTLET t°_ DIM "C" DIMENSIONS SEE NOTES I & 2 "E" 5/8" J "'--4-1/16" OUTSIDEAIR 7/8" HOLE_ ELECTRICALLY.... SUPPLY ,_._ 1/78" x 7/8"_ IS 7/8" KNOCKOUT ELECTRICAL SUPPLY (ALTERNATE) ONLY) , ',1-3-15/16" _ .... SIDE _1 SLOT KNOCKOUT CONDENSATE DRAIN (HORIZONTAL) "--2-1/16" IZONTAL -¢1-1/2" APPLICATION I/2"_ -_1-1/2" KNOCKOUT GAS SUPPLY (ALTERNATE) GAS SUPPLY I-I/8" KNOCKOUTCONDENSATE DRAIN [ "-2-1/8" I/8" KNOCKOUT DRAIN (ALTERNATE) __T I-5/16"--=- 40" ;0-5/8" o 18- I -7/8 22- 2 ii /4" 23-3/4" --,_ I --__20-1/4" 5 " 28- I / 2" -_,. DIM "A" ---,'- -,- I/2" MINIMUMCLEARANCETO COMBUSTIBLE Model (See Note 1 & 2) -i _1 DIM "A" DIM "B" DIM "C" DIM "D" DIM "E" DIM "F" *UX2B060A9362A *UX2B080A9422A 17-1/2" 2-1/4" 16-1/4" 16" 7-1/2" 2" *UX2C100A9482A 21" 2-1/2" 19-3/4" 19-1/2" 9" 3" *UX2D120A9602A 24-1/2" 2-15/16" 23-1/4" 23" 10" 3" DIM "D" AIR INLET I "• I * Prefix 3/4,,_3/4" --_ I_ 24- I/32" _-J L 3-7/32" May Be "A" or "T" Notes: 1. *UX2D120A9602A Requires 3" Diameter Vent Pipe. Oo *UX2C100A9482A Requires 2-1/2" or 3" Diameter Vent Pipe. 2. Diameter of Vent Pipe may be limited to 2-1/2" or 3" on some 6 models at different ED proper application. ED oo i ol From Dwg. 21C341884 Rev. 1 altitudes. Refer to the Vent Length Table for SIDES REAR FRONT TOP FLUE MATERIALS O 0 3 I 0 IN. IN. IN, IN. IN. HORIZONTAL(FLUE BSCHARGE ON THE LEFTI ALCOVE SIDES RIGHT O IN LEFT O IN REAR 6 IN FRONT 18 IN TOP I IN, FLUE 0 IN, CLOSET SIDES RIGHT LEFT REAR FRONT TOP FLUE I I 3 3 I 0 IN IN IN IN IN IN, Ill n_ iI *DX2 DOWNFLOW oo i © 0 ....... _2" F u , qo 0 oo CON'\ECT SEE IOTE / HORIZONTAL OUTLINE DRAWING (ALL DIMENSIONS ARE IN INCHES) J i t_n ....... 19 5'8 ....... / / ,; llOlR z.N '. ',, IS _i i ,, t,,_l . I C,\I ON // / / / 2-i ,'8 ......... "- _,S,'8' (ONNIC / L C R CAL ON AI Ei!'NA I ,_'S'/6' i( IRICA CONN ?liON ,*,L ERNAIE) NOC Oi k c,,,INE_T k. ' 0 " i 0 ?5" /z" i ! DIM "A" ,.-.- 23/i6" "--- ¢ ...... s ,,,Jr ,E If --w ,,,,J u v DA T, MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS Model (See Note 1) DIM "D" ! A 3/4 o_ a,, 6,_ .... j DIM "B" DIM "C" DIM "D" *DX2BO60A9362A *DX2BO80A9422A 17-1/2" 2-1/4" 16-1/4" 16" *DX2C100A9482A 21" 2-1/2" 19-3/4" 19-1/2" *DX2D120A9602A 24-1/2" 2-15/16" 23-1/4" 23" i 7 _,,4" Prefix May Be "A" or "T" From Dwg. 21C341885 Rev. 1 DIM "A" Notes: 1. Diameter of Vent Pipe may be limited to 2-1/2" or 3" on some models at different altitudes. Refer to the Vent Length Table for proper application. DOWNFLOW SIDES REAR I ROi' I O[ i I bE 0 0 3 ', N N 0 HORIZONTAL (FLUE DISCHARGE ON THE LEFT) ALCOVE SIDES RI iT 0 \ REAR iRON[ -OR FlU 6 18 0 _N N N \ | Itl Iit m m I1 II CLOSET SIDES [EFT REAR FRONT lOP F I U_ ;N _N _N iN iN ml I1 Installer's Guide UPFLOW INSTALLATION Standoffs and screws (See Figure 1) are included with the cased coils for attachment to the furnace. There are clearance alignment holes near the bottom of the coil wrapper. Drill screws are used to engage the furnace top flanges. The standoff is inserted into the cabinet alignment hole. The drill screws are inserted through the standoffs then screwed into the furnace flange. The coil is always placed downstream of the furnace airflow. STANDOFFS (4) DRILL SCREWS (4) J FOR VERTICAL TABLE 1 CABINET RETURN FLOOR OPENING PLENUM OPENING WIDTH DUCT WIDTH "A.... B.... C.... D" 14-1/2" 13-1/4" 13-5/8" 20-1/8" 12-5/8" 19-3/8" 17-1/2" 16-1/4" 16-5/8" 20-1/8" 15-5/8" 19-3/8" 21" 19-3/4" 20-1/8" 20-1/8" 19-1/8" 19-3/8" 23-1/4" 23-5/8" 20-1/8" 22-5/8" 19-3/8" 24-1/2" HORIZONTAL INSTALLATION The coil and furnace must be fully supported when used in the horizontal position. It is always recommended that an auxiliary drain pan be installed under a horizontally installed evaporator coil or 90% gas furnace. Connect the auxiliary drain line to a separate drain line (no trap is needed in this line). Three brackets (with screws) are included with downflow furnaces for installation to stabilize and secure the furnace and TXC cased coil in the horizontal position. See Figure 4. © - SCREWS (BOTH BIDES) DOWNFLOW STANDOFFS (BOTH DOWNFLOW (_ INSTALLATIONS CABINET SIDE SUB-BASE FLANGE (BENT UP) FLANGE (BENT UP) DUCT Do not install the furnace directly on carpeting, tile or other combustible material other than wood flooring. For vertical downflow application, subbase (BAYBASE205) must be used between the furnace and combustible flooring. When the downflow furnace is installed vertically with a cased coil, a subbase is not required. Required floor opening: (DOWNFLOW) See Figure 3 and Table I ONLY IMPORTANT: The 2/4TXC cased coil must be placed downstream of the furnace. In horizontal installations, the apex of the coil may point either toward or away from the furnace. See the 2/4TXC coil Installer's Guide for more details. SIDES) CABINET SIDE SUB-BASE CASED COIL CONNECTION BRACKET FOR DOWNFLOW FURNACE IN HORIZONTAL The cased coil is secured to the furnace and both the furnace and the cased coil must be properly supported. The brackets mount using the rear screws on the coil case and use the screws provided to secure the bracket to the furnace. The remaining bracket is placed as close to center as possible (horizontally) between the coil case front and the furnace bottom channel (for downflow/horizontal furnace). Use four of the screws provided to secure the bracket. The upflow furnace, converted to horizontal, aligns and attaches the TXC coil as in Figure 1. However, the coil requires additional support. The furnace may be installed in an attic or crawl space in the horizontal position by placing the furnace on the left side (as viewed from the front in the vertical position). The horizontal furnace installation in an attic should be on a service platform large enough to allow for proper clearances on all sides and service access to the front of the furnace (See Figure 5 & Clearance Tables, pages 4-5). Line contact is only permissible between lines formed by intersections of the top and two sides of the furnace casing and building joists, studs, or framing. The furnace may be placed horizontally in a crawl space on a pad or other noncombustible material which will raise the unit for sufficient protection from moisture. @ UPFLOW/ I HORIZONTAL I SHOWN WITH DIRECT VENT 18-CD19D8-15 Installer's Furnace locations may be in a "confined "unconfined space". ® [-50 CU. FT. OR MORE ..... \ / The furnace must be supported at both ends and the middle when installed horizontally. The furnace must also be elevated approximately 4-6 inches to allow clearance for the condensate drain to exit the cabinet in the horizontal position. The horizontal furnace may also be suspended from the joists using 3/8" all-thread rods with pieces of angle iron underneath the furnace to form a hanging rack at both ends and the midpoint. The rods need to be of sufficient length to allow for proper clearances from combustible materials. The angle iron needs to be at least 32" in length to allow for access to service panels. If these furnaces are installed in a nondirect vent capacity then the adequate flow of combustion and ventilating air must not be obstructed from reaching the furnace. Air openings provided for combustion air must be kept free of obstructions which restrict the flow of air. Airflow restrictions affect the efficiency and safe operation of the furnace. Keep this in mind should you choose to remodel or change the area which contains your furnace. Furnaces must have a free flow of air for proper performance. Provisions for combustion and ventilation air shall be made in accordance with latest edition of Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1 -- CAN/CGA B 149.1 or applicable provisions of the local building codes. Special conditions created by mechanical exhausting of air and fireplaces must be considered to avoid unsatisfactory furnace operation. OUTSIDE AIR IS RECOMMENDED The use of indoor air for most applications is acceptable, unless there is the presence of corrosive chemicals or contamination. Certain types of installation will require the use of outside air for combustion. The following types of installations will require use of OUTDOOR AIR for combustion, due to chemical exposures: * Commercial buildings * Buildings with indoor pools * Furnaces installed in "confined" laundry rooms * Furnaces installed in "confined" hobby or craft rooms * Furnaces installed near chemical storage areas. 18-CD19D8-15 or an Confined spaces are installations with less than 50 cu. ft. of space per 1000 BTU/hr input from all equipment installed. Air for combustion and ventilation requirements can be supplied from inside the building as in Figure 9 or from the outdoors, as in Figure 10. Q air MINIMUM AREA IN SQUARE FEET FOR UNCONFINED SPACE INSTALLATIONS FURNACE MAXIMUM BTUH INPUT RATING WITH 8 FT. CEILING MINIMUM AREA IN SQUARE FEET OF UNCONFINED SPACE 60,000 80,000 100,000 120,000 375 500 625 875 AND VENTILATION Exposure to the following substances in the combustion supply will also require OUTDOOR AIR for combustion: * Permanent wave solutions * Chlorinated waxes and cleaners * Chlorine based swimming pool chemicals * Water softening chemicals * Deicing salts or chemicals * Carbon Tetrachloride * Halogen type refrigerants * Cleaning solvents (such as perchloroethylene) * Printing inks, paint removers, varnish, etc. * Hydrochloric acid * Cements and glues * Antistatic fabric softeners for clothes dryers * Masonry acid washing materials space" Unconfined space is defined in Figure 6. These spaces may have adequate air by infiltration to provide air for combustion and ventilation. Buildings with tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), may need additional air to be provided as described for confined space. UNCONFINED AIR FOR COMBUSTION Guide ® m CONFINED SPACE m FURNAOF -I LESS THAN 50 CU. FT. PER 1000 BTU/HR. INPUT ALL EQUIP. INSTALLED 1. All air from inside the building as in Figure 9: The confined space shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Refer to Table 2 for minimum open areas requirements. 2. All air from outdoors as in Figure 10: The confined space shall be provided with two permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Refer to Table 2, for minimum open areas requirements. TABLE 2 MINIMUM FREE AREA IN SQUARE INCHES EACH OPENING FURNACE ONLY) Furnace Maximum BTUH/INPUT Rating 60,000 80,000 100,000 120,000 Air From Inside lOO lOO lOO 12o Air From Outside Vertical Duct Horizontal Duct 15 20 25 30 30 40 50 60 7 Installer's Guide DUCT CONNECTIONS Air duct systems should be installed in accordance with standards for air conditioning systems, National Fire Protection Association Pamphlet No. 90. They should be sized in accordance with ACCA Manual D or whichever is applicable. ® CONFINED AIR FROM SPACE INSIDE BUILDING Central furnaces, when used in connection with cooling units, shall be installed in parallel or on the upstream side of the cooling coil to avoid condensation in the heat exchanger. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be adequate to prevent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in full heat or cool position. CONFINED SPACE PERMANENT OPENINGS _J iiiiiiiiiiii On any job, flexible connections of nonflammable material may be used for return air and discharge connections to prevent transmission of vibration. Though these units have been specifically designed for quiet, vibration free operation, air ducts can act as sounding boards and could, if poorly instMled, amplify the slightest vibration to the annoyance level. ® CONFINED SPACE AIR FROM OUTDOORS When the furnace is located in a utility room adjacent to the living area, the system should be carefully designed with returns to minimize noise transmission through the return air grille. Although these furnaces are designed with large blowers operating at moderate speeds, any blower moving a high volume of air will produce audible noise which could be objectionable when the unit is located very close to a living area. It is often advisable to route the return air ducts under the floor or through the attic. Such design permits the installation of air return remote from the living area (i.e. central hall). L CONFINEDSPACE CONFINED SPACE When the furnace is installed so that air circulated by the furnace to areas containing the furnace, the return air by a duct(s) sealed to the furnace and the space containing the furnace. k AIR FROM VENTILATED ATTIC/CRAWL SPACE _ ATTIC LOUVERS DOORS - AIR SPACE ALTERNATE INLET A_R _ RETURN AIR DUCT SYSTEMS Where there is no complete return duct system, the return connection must be run full size from the furnace to a location outside the utility room, basement, attic, or crawl space. Do Not install cabinet. ,UTLET CONFINED INLET AIR DUCT the supply ducts carry outside the space shall also be handled terminating outside return air through the back of the furnace Do Not install return air through cabinet on horizontal applications. the side of the furnace NOTE: Minimum return air temperature is 55 ° F. All return air duct systems should provide return air filters. 1. Set the furnace in place. CONFINED SPACE AIR FROM VENTILATED of 2. For upflow side return installations, remove the insulation around the opening in the blower compartment. ATTIC :LOUVERS TO OUTDOORS CONFINEDSPACE INLET AIR DUCT 8 for installation 3. The side panels of the notches that are used for return air, refer to drawing on page 4 for various furnaces. upflow furnace include locating as guides for cutting an opening Figure 11 and the outline duct connection dimensions for NOTE: On upflow 5 ton airflow models, if the airflow requirement exceeds 1800 CFM, these models will require return air openings and filters on both sides; OR 1 side and the bottom; OR just the bottom. 18-CD19D8-15 Installer's 4. Ifa 3/4" flange is to be used for attaching the air inlet duct, add to cut where indicated by dotted lines in Figure 11. Cut corners diagonally and bend outward to form flange. 5. If flanges are not required, and a filter frame is installed, cut between locating notches (Figure 11). 6. The bottom panel of the upflow furnace must be removed for bottom return air. Remove the filter and lay the furnace on its back. Remove the two 1/4" hex screws securing the bottom front channel to the cabinet. Lower the front edge of the bottom front channel and pull forward to remove the channel. The bottom return air panel will now easily slide out of the cabinet. Reinstall the bottom front channel and filter for upflow bottom return installations. 7. The filter retainer is factory supplied for upflow bottom return. Use the filter retainer on side or bottom if filter is to be used within the furnace cabinet on upflow only installations. 8. The horizontal installation of the upflow furnace requires an external filter section. Do NOT use the bottom return filter within the furnace. Filter kits are available for horizontal applications. Guide NOTE: On upflow 5 ton airflow models, if the airflow requirement exceeds 1800 CFM, these models will require return air openings and filters on both sides; OR 1 side and the bottom; OR just the bottom. The upflow furnace blower door has a hinge at the bottom which allows the door to tilt forward for filter replacement without the door being removed (See Figure 12). The furnace filter in the bottom or side configuration can be removed by simply turning the two latches on the blower door and tilting the door forward. The filter rails are spring loaded for automatic adjustment allow standard size, locally obtainable replacement filters. The filter rack itself slides to adjust to the required width needed for bottom or side return (See Figure 13). to BOTTOM FILTER RACK INSTALLATION With the filter removed, the filter rack is compressed and then inserted into the bottom of the furnace. The retaining screw/pin on each side inserts into engagement holes at the bottom of the furnace cabinet side. 9. Connect duct work to furnace. See Outline Drawing for supply and return duct size and location. Flexible duct connectors are recommended to connect both supply and return air ducts to the furnace. If only the front of the furnace is accessible, it is recommended that both supply and return air plenums are removable. RETURN AIR FILTERS (NOT SUPPLIED) TYPICAL UPFLOW RETURN AIR FILTER INSTALLATIONS Filters are not factory supplied for these furnaces. furnaces require high velocity type air filters. The be located within the furnace blower compartment UPFLOW furnaces in either a BOTTOM or SIDE right side) return air inlet. Some filters may need trimmed for side or bottom filter use. These filters may for (left side or to be TABLE 3 MODELS NUMBERS CABINET WIDTH *UX2B060A9362A *UX2B080A9422A *UX2C100A9482A FILTER QTY & SIZE 17-1/2" *UX2D120A9602A 1- 17"X25"X 1" 21" 1 - 20" X 25" X 1" 24-1/2" 1 - 24" X 25" X 1" * First letter may be "A" or "T" ** NOTE - On 5 ton airflow models, if the airflow requirement exceeds 1800 CFM, these models will require return air openings and filters on both sides; OR 1 side and the bottom; OR just the bottom. ® UPFLOW LOCATING FURNACE -,. VIDED FOR SIDE NOTCHESCUTOUT PRORETURN I/- j CUT OUT FOR SIDE FILTER q J *- "_ ,_ *SEE OUTLINE DRAWING _ 18-CD19D8-15 FILTER RACK RAILS I I 4.. ® '_ SPRINGS ONLY I *_ Blower Door Hinge and Bottom Filter Rack Installation I RONT of Furnace AUTOMATIC ADJUSTMENT RETAINING PIN (Both Sides) Optional Filter Rack Accessory Kit - BAYRACK960A 9 Installer's Guide ",.: ..... .. _ _ BlowerDeck iiii iiiiiiiiiiii II _ Engagement II • II _ " II II Filter Rack BOTTOM ENGAGEMENT Retaining Furnace " Screw/Pin Filter Rack Cabinet SideHole Engagement For Filter Rack Bottom Panel ENGAGEMENT !'" ..... '_" I1 11 HOLE DETAIL (Typical both sides and blower deck) BLOWER OPTIONAL FILTER RACK INSTALLATION FOR SIDE RETURN AIR ON UPFLOW FURNACES (Left or Right) If side air return is desired, it is necessary to move the filter rack from the bottom of the furnace and reinstall it on the side. The following instructions should be used: a. Open or remove the blower door. b. Remove the filter. c. Compress the filter rack to disengage the retaining pins/screws from the furnace sides and slide the filter rack out. d. Leave the bottom _lnstallation _)_Bottom Return With For Filter Rack Installation With Side Return Cabi net .,.,,)_ Side panel in place. f. Reinstall the furnace chamfer end first. filter on the side inserting ® Retaining Screw/Pin SIDE CUTOUT the Filter RETAINING PIN Rack Assembly \ -_ Rack F (Bo_[__, Filter Rack Retaining Screw/Pin III I I.] [[I EngagementHole For Filter Rack InstallationWith Bottom Return Furnace Blower Deck Furnace e. After the side cutout is made following the directions in the "Return Air Duct Connections" section on pages 8 and 9, compress the filter rack and reinstall in the side of the furnace. Confirm that the upper retaining pin/screw locks into the engagement hole in the blower deck and the lower pin/screw rests against the side of the bottom panel. See Figures 15-19. Furnace Cabinet Side EngagementHole J/ JJ // I[ V/zJ L_z/Rack FILTER RACK BOTTOM PANEL RAILS INSTALLED Typical Upflow Left Side Return Filter Installation Optional Filter Rack Accessory Kit - BAYRACK960A 10 18-CD19D8-15 Installer's Guide BLOWER DOOR/HINGE REMOVAL If clearance or other problems create a problem in using the tilting door, the blower door hinge may be removed without creating any problems with the seal of the furnace. To remove the blower door, tilt the door forward 2 to 3 inches and pull up. To remove the tilt feature, simply remove the lower hinge as shown in Figure 22. The bottom of the blower door will catch in the bottom of the furnace front channel for door replacement. Typical Upflow Right Side Return Filter Rack Installation O Door Hinge Removed ALTERNATE UPFLOW FILTER CLIP / BRACKET INSTALLATION (KIT09224) 1. Determine the location to be used. The furnace cabinet has dimples for location of the alternate furnace clips (Side return only). Pre-drill clearance holes with a 3/16" drill. Bottom return holes are pre-drilled. CHAMFER END OF FILTER INTO RACK 2. Install the clips in front and rear of the desired location using the screws provided. The filter clip with the leaf spring mounts in the rear of the cabinet. GOES FILTER FIRST RETURN AIR FILTERS FOR UPFLOW FURNACE IN HORIZONTAL CONFIGURATION When the Upflow Furnace is installed in the horizontal configuration, the return air filters must be installed exterior to the cabinet. Remote filter grilles may be used for homeowner convenience or the filters may be installed in the duct work upstream of the furnace. See Figure 21. f_ ALTERNATE FILTER CLIPS LOCATION FILTER CLIP - KIT09224 TYPICAL RETURN AIR FILTER INSTALLATION IN UPFLOW MODEL IN HORIZONTAL POSITION 18-CD19D8-15 11 Installer's Guide INSTALLING THE FILTER The filter may need to be cut to fit the unit depending location of the return air filter. TABLE 4 on the MODELS NUMBERS A score line and the words "CUT HERE" are located on the end of the filter. If your application requires cutting the filter, do so as indicted by the score mark. RETURN 17-1/2" 2 - 14" X 20" X 1" *DX100R948 21" 2 - 16" X 20" X 1" *DX120R960 24-1/2" 2 - 16" X 20" X 1" *DX080R942 AIR BOTTOM SIDE 17-1/2" DO NOT CUT DO NOT CUT 21" DO NOT CUT CUT ON LINE 24-1/2" DO NOT CUT CUT ON LINE TYPICAL DOWNFLOW FURNACE RETURN AIR FILTER INSTALLATIONS Two filters are factory supplied for each downflow furnace. These furnaces require high velocity type air filters. Downflow furnace filters must be located outside the furnace cabinet. Typical installations are shown in Figure 24. Tables 5 and 6 provide information for installation of the filter retaining brackets shipped with downflow furnaces. @ FILTER QTY & SIZE *DX060R936 UNIT SIZE iiiiiiiiiiii CABINET WIDTH *First letter may be "A" or "T" TABLE 5 LOCATING FILTER RETAINER BRACKETS DUCTWORK IN CABINET WIDTH RETURN DUCT WIDTH DIMENSION "A .... DIMENSION B" FILTER BRACKET LOCATION* 17-1/2" 21" 24-1/2" 16-1/4" 19-3/4" 23-1/4" 15" 19-1/2" 22" 14" 14" 14" 14-3/8" 13-1/8" 13-5/8" * LOCATION DIMENSION SCREW HOLES FOR IS THE FROM END BRACKET. OF DUCT AGAINST THE FURNACE TO THE p. Optional BAYFLTR206 Door Kit BOptiyFLnTRI06 Airflow DOWNFLOW / ow% ow; TABLE 6 MINIMUM CLEARANCE FROM COMBUSTIBLE MATERIALS FOR UPFLOW/HORIZONTAL AND DOWNFLOW/HORIZONTAL FURNACES UNIT LOCATION FURNACE SURFACE HORIZONTAL CLOSET HORIZONTAL ALCOVE / ATTIC SIDES 0" 1" 0" BACK 0" 3" 6" TOP 1" 1" 1" FRONT 3" 3" 18" VENT 0" 0" 0" NOTE: CLEARANCE 12 VERTICAL CLOSET REQUIRED AT TOP OF PLENUM IS 1" 18-CD19D8-15 Installer's I The following warning complies with State of California law, Proposition 65. Hazardous Gases! Carbon monoxide, fire or smoke can cause injury, death, and!or property damage. serious bodily A variety of potential sources of carbon monoxide can be found in a building or dwelling such as gas-fired clothes dryers, gas cooking stoves, water heaters, furnaces and fireplaces. The U.S. Consumer Product Safety Commission recommends that users of gas-burning appliances install carbon monoxide detectors as well as fire and smoke detectors per the manufacturer's installation instructions to help alert dwelling occupants of the presence of fire, smoke or unsafe levels of carbon monoxide. These devices should be listed by Underwriters Laboratories, Inc. Standards fbr Single and Multiple Station Carbon Monoxide Alarms, UL 2034 or CSA International Standard, Residential Carbon Monoxide Alarming Devices, CSA 6.19 NOTE: The manufacturer of your furnace does not test any detectors and makes no representations regarding any brand or type of detector. GENERAL THIS FURNACE VENTING MUST BE VENTED TO THE OUTDOORS. THESE FURNACES ARE INDUCED DRAFT VENTED AND MUST NOT BE CONNECTED TO ANY VENT SERVING ANOTHER APPLIANCE. PLEASE NOTE THAT THESE FURNACES USE POSITIVE-PRESSURE VENT SYSTEMS. Proper venting is essential to obtain maximum efficiency from a condensing furnace. Proper installation of the vent system is necessary to assure drainage of the condensate and prevent deterioration of the vent system. American Gas Association has certified the design of condensing furnaces for a minimum of 0" clearance from combustible materials with a single wall plastic vent pipe. The recommended system is assembled from 2", 2-1/2", or 3" plastic pipe and fittings (See Table 7, page 15). Where the system is routed to the outdoors through an existing masonry chimney containing flue products from another gas appliance, or where required by local codes, then 3" venting of Type 29-4C stainless steel must be used in place of PVC material. These furnaces have been classified as CATEGORY IV furnaces in accordance with ANSI Z21.47 "latest edition" standards. Category IV furnaces operate with positive vent pressure and with a vent gas temperature less than 140 ° F. above the dewpoint. These conditions require special venting systems, which must be gas tight and water tight. NOTE: When an existing furnace is removed from a venting system serving other gas appliances, the venting system is likely to be too large to properly vent the remaining attached appliances. 18-CD19D8-15 The following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation. 1. Seal any unused Exposure to fuel substances or by-products of incomplete fuel combustion is believed by the state of California to cause cancer, birth defects, or other reproductive harm. Guide openings in the common venting system. 2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition. 3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan, close fireplace dampers. 4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so appliance will operate continuously. 5. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return door, windows, exhaust fans, fireplace dampers and any other gasburning appliance to their previous conditions of use. If improper venting is observed during any of the above tests, the remaining common venting system must be corrected. Correction could require rerouting or resizing the remaining vent system. IMPORTANT: These furnaces may be installed as Direct Vent (sealed combustion) or as Nondirect vent (single pipe). The furnaces are shipped DIRECT VENT with sealed combustion. For DIRECT VENT APPLICATION: The furnaces must be vented to the exterior of the house and combustion air MUST come through the inlet air pipe FROM OUTSIDE AIR. The pipes DO NOT have to exit the exterior of the house together or on the same side of the house. For NONDIRECT VENT APPLICATION: The furnace shall be vented to the exterior of the house, but combustion air may enter from the surrounding area as long as combustion air requirements are met. (See AIR FOR COMBUSTION AND VENTILATION) FURNACE VENT/INLET PIPE INSTALLATION There are many different variations of the vent/inlet air pipe combination. The vent/inlet air combination used for installation of these furnaces depends on the needs of the location. However, these guidelines must be followed: 1. The furnace must vent outside the structure. 2. Furnace combustion air requirements must be met for nondirect, single pipe applications (See example on next page). 3. For direct vent application of these furnaces, the vent pipe and air inlet pipe do not have to exit in the same air space or even on the same surface of the structure. However, the longest individual pipe will decide the value fbr the longest allowable equivalent vent/inlet air length as shown in the vent length table. 13 Installer's Guide NOTE: BAYVENT200* accessories can be used for inlet and outlet terminals when the pipes do not exit the structure together. The following are EXAMPLES ONLY: EX. 4-The inlet air does not have to come from outside the structure. Example 4 shows the inlet air (See Note), may come from the attic if the requirements for combustion air are met as shown in the section AIR FOR COMBUSTION AND VENTILATION. EX. 1 -- Attic Example 1 shows that the vent may go vertical while the inlet air may be on any side of the structure. The vent pipe would decide the maximum equivalent length for the pipe depending on the furnace and pipe size. Vent Vent _(Soe Note) FurnaceL Air Inlet =_ Furnace EX. 2 -Example 2 shows the vent pipe exhausting through the roof and the inlet air coming from the interior of the house (See Note). The inlet air coming from the interior of the house must meet combustion requirements for area, etc., as shown in the section AIR FOR COMBUSTION AND VENTILATION in this Installer's Guide. NOTE: ff only the flue gas pipe is to the outside of the structure, a straight section of pipe (long enough to exit the furnace cabinet) must be attached to the inlet air side with an elbow (which is 5 to 10 equiv, ft.) installed on the end to prevent dust and debris from falling directly into the furnace. VENT FITTING MATERIAL - PLASTIC Gas and liquid tight single wall vent fittings, designed for resistance to corrosive flue condensate, MUST be used throughout. Listed in Table 7 are 2", 2-1/2", and 3" size fittings that meet these requirements. The materials listed are various grades of PVC and ABS plastic. Air_ Inlet_ _ PIPE JOINTS: All joints must be fastened and sealed to prevent escape of combustion products into the building. Vent NOTE: It is recommended that the first joints from the furnace be connected and sealed with high temperature RTV. This will enable the pipes to be removed later without cutting. (See Note) EX. 3 -- Be sure to properly Example 3 shows the vent exiting one side of the house while the inlet air is on the opposite side of the structure. Here the vent pipe length must be within the allowable length for the size of furnace and size of the vent pipe. This example demonstrates that the pipes do not have to exit on the same side of the structure. BONDING OF PVC Commercially available solvent cement for PVC must be used to join PVC pipe fittings. Follow instructions on container carefully. Pipe and Fitting PVC Primer Procedure support -ASTM these joints. D1785, D2466, and Solvent Cement for Cementing Joints D2661, & D2665 - ASTM D2564 - RefASTM D2855 1. Cut pipe square, remove ragged edges and burrs. Chamfer end of pipe, then clean fitting socket and pipe joint area of all dirt, grease, moisture or chips. Vent Air Inlet =_ 14 Furnace 2. After checking pipe and socket for proper fit, wipe socket and pipe with cleaner-primer. Apply a liberal coat of primer to inside surface of socket and outside of pipe. DO NOT ALLOW PRIMER TO DRY BEFORE APPLYING CEMENT. 3. Apply a thin coat of cement evenly in the socket. Quickly apply a heavy coat of cement to the pipe end and insert pipe into fitting with a slight twisting movement until it bottoms out. 18-CD19D8-15 Installer's 4. Hold the pipe in the fitting for 30 seconds to prevent tapered socket from pushing the pipe out of the fitting. Guide NOTE: Follow venting instructions carefully when using PVC cemenL 5. Wipe all excess cement from the joint with a rag. Allow 15 minutes before handling. Cure time varies according to fit, temperature and humidity. IMPORTANT: All joints must be water tight. Flue condensate is somewhat acidic, and leaks can cause equipment damage. TABLE 7 PVC VENT FITTING MATERIAL These fittings are available from your Gas Furnace Distributors. q 2-3/16" 1-518" [ i_ _----- 4-1/2" WALL MOUNT FLANGE 5-5/8" WALL MOUNT BAY69X 148 FLANGE BAY69X 147 PLASTIC PIPE DESIGNATIONS PVC ASTM STANDARD F891 D2665 D1785 D2241 PIPE TYPE CELLULAR DWV ALLOWABLE TEMPERATURE CORE "158 PIPE SCH 40, 80, 120 SDR SERIES MARKING ASTM F891 *'158 ASTM D2665 *'158 ASTM D1785 *'158 ASTM D2241 CPVC ASTM STANDARD D2846 F441 F442 PIPE TYPE CPVC SCH SDR ALLOWABLE TEMPERATURE 41 *'212 MARKING ASTM D2846 40, 80 *'212 ASTM F441 SERIES *'212 ASTM F442 ABS ASTM STANDARD PIPE TYPE ALLOWABLE TEMPERATURE D2661 SCH 40 DWV **'180 F628 SCH 40 DWV CELLULAR CORE MARKING ASTM **'180 D2661 ASTM F628 * - Allowable temperatures based on classifications covered in ASTM D4396 [Deflection Temps Under Load (264 PSI)] ** - Allowable temperatures based on classifications covered in ASTM D1784 [Deflection Temps Under Load (264 PSI)] *** - Allowable temperatures based on classifications covered in ASTM D3965 [Deflection Temps Under Load (264 PSI)] Connection should just air joint be be separated pipes must length. of the pipe and collar of the combustion air inlet be a friction fit. It is recommended that the inlet sealed with RTV type sealant to allow the joint to for possible future service. The inlet and vent be properly supported throughout the entire (_ VENT AND INLET AIR CONNECTIONS Seal VENT PIPE with RTV sealant Connection of the vent pipe to the vent collar should also be accomplished using RTV type sealant. This type sealant provides a connection which remains flexible and can be separated in the future if service needs require the removal of the vent pipe for service or clearance. NOTE: Vent termination kit BA YAIR3OAVENTA or BA YVENT2OOB may be used in addition to the horizontal and vertical termination options shown in the following figures. 18-CD19D8-15 Front of Furnace Seal INLET AIR PIPE with RTV sealant 15 Installer's Guide VENT ALTITUDE 0-7,000 TABLE MAXIMUM TOTAL EQUIVALENT FOR VENT AND INLET AIR Feet LENGTH IN FEET (SEE NOTES) 2 INCH PIPE 2.5 INCH PIPE 3 or 4 INCH PIPE UX2/DX2B060A9362A 200 200 200 UX2/DX2B080A9422A 50 120 200 UX2/DX2C100A9482A Not Allowed 60 200 UX2/DX2D120A9602A Not Allowed Not Allowed 200 2 INCH PIPE 2.5 INCH PIPE 3 or 4 INCH PIPE UX2/DX2B060A9362A 100 100 100 UX2/DX2B080A9422A 25 60 100 UX2/DX2C100A9482A Not Allowed 30 100 UX2/DX2D120A9602A Not Allowed Not Allowed 100 7,000-9,500 iiiiiiiiiiii LENGTH 9,500-12,000 Feet 2 INCH PIPE 2.5 INCH PIPE 3 or 4 INCH PIPE UX2/DX2B060A9362A Feet 50 50 50 UX2/DX2B080A9422A Not Allowed 30 50 UX2/DX2C100A9482A Not Allowed Not Allowed 50 UX2/DX2D120A9602A Not Allowed Not Allowed 50 NOTES: * - First letter may be "A" or "T" 1. Minimum vent length for all models: 3' horizontal or 3' vertical. 2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace). If different inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See note 6 below for exception). The inlet pipe can be of a larger diameter, but never smaller than the vent pipe. 3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH (Vent or Inlet air pipes). 4. One SHORT radius 90 ° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is equivalent to 6' of 3" pipe. One 90 ° elbow is equivalent to 71/2' of 21/2'' pipe or 5' of 2" pipe. Two 45 ° elbows equal one 90°elbow. 5. The termination tee or bend must be included in the total number of elbows. If the BAYAIR30AVENTA termination kit is used, the equivalent length of pipe is 5 feet. BAYVENT200B 6. Pipe adapters are field supplied (except 120). equivalent length is 0 feet. HORIZONTAL INSTALLATION (Upflow/Horizontal or Downflow/Horizontal) 2" _' COUPLING NOTE: In horizontal venting when the factory supplied "off-set" (2)(3 reducing coupling) is used for 3" vent pipe installation, make sure the marking "Top" is located on the top side of the pipe. The straight side must be on bottom for proper condensate drainage. This coupling is factory supplied only with the followinomodels: UC120 & DC120. UX120 & UY120 UXIO0 _ UYIO0, UX808C960, and all DX & DY models. FACTORY SUPPLIED ONLY WITH THE FOLLOWING MODELS: UC120 & DC120 UX120 & UY120 UX100 & UY100 UX080C960 ALL DX & DY MODLES LABEL SAYS \\\\\ "TOP" VENT OUTLET 16 18-CD19D8-15 Installer's Guide G ELBOW AND TEE MUST BE AS CLOSE TOGETHER AS POSSIBLE iiiiliiiiii;iiii¸ POSSIBLE CONFIGURATIONS FOR TWO PIPE VENTING SYSTEMS @ NOTE: VENT A ND INL ET MUS T BE SUPPOR TED A T A MAXIMUM OF 3' INTER VALS SEE VENTING TABLE STRAPS OR OTHER SUITABLE SUPPORTS AT MAXIMUM OF 3'-0" INTERVALS COMBUSTION AIR USE ONLY APPROVED TERMINATION STRAP (FIELDSUPPLIED) RAIN CAI --) COMBUSTION AIR INLET n UPWARD / VENT X PITCH -- 1/4" PER FOOT FIRST SUPPORT SHOULD BE AS CLOSE TO FURNACE CONNECTION AS POSSIBLE. L OUTSIDE WALL I 1"_+1/2" ELBOW COMBUSTION 40" UPFLOW DOWNFLOW OR MODELS NOTE:ANY THROUGH MUST FITTINGS PASSING AN UNHEATED SPACE BEINSULATED. AIR (FIELD SUPPLIED) BA YAIR3OAVENTA 45° ELBOW OUTSIDE WALL STUB CUT AT 45 ° ANGLE 18-CD19D8-15 17 Installer's Guide ® COUPLING _'_ STU r ( PLASTIC • PVC WALL MOUNT FLANGE I II / APPROVED TERMINATION 12"MINIMUM TO OVERHANG // VENT CAP NORMALLY MAINTAIN 12" (18" FOR CANADA) MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE WHICHEVER IS GREATER BAYVENT200B 1" CLEARANCE (AIR SPACE ) EXPECTED SNOW ACCUMULATION VENTINGTHROUGH COMBUSTIBLEWALLS Pitch-- 1/4 Inch Per FL CLEARANCE ( 0" ACCEPTABLE FOR PVC VENT PIPE ) ( 1" ACCEPTABLE FOR TYPE 29-4C STAINLESS STEEL VENT PIPE ) ® PVC WALL MOUNT FLANGE COUPLING ( PLASTIC VENTING ) 14 / 61N. MIN. I_-- j lj(TOJOINT)_ M_ BAYAIR30AVENTA (Sidewall) When the vent pipe is exposed to temperatures below freezing, i.e., when it passes through unheated spaces, etc., the pipe must be insulated with 112 inch (22.7 mm) thick Armaflex-type insulation or equal. If the space is heated sufficiently to prevent freezing, then the insulation would not be required. If domestic water pipes are not protected from freezing then it is assumed the space meets the condition of a heated space. HORIZONTAL VENTING THROUGH WALL These furnaces may be installed as direct vent (as shipped) or as nondirect vent. Installation must conform to national, state, and local codes. The vent & inlet terminals minimum above normally must be located at least 12" expected snow accumulation level. Avoid areas where staining or condensate drippage may be a problem. Location of the vent/wind terminal should be chosen to meet the requirements of Figure 39 for either direct or nondirect vent applications. PITCH -- Venting through the wall must maintain 1/4" per foot pitched upward to insure that condensate drains back to the furnace. / IOPTIONAL) APPROVED / TERMINATION 12" MIN. ABOVE NORMALLY EXPECTED SNOW ACCUMULATION VENTING THROUGH NON-COMBUSTIBLE Pitch- 1/4 Inch Per Ft. WALLS materials. This can be avoided by using the roof or chimney venting option. When wall venting is used on any surface that can be affected by this moisture, it is recommended that a corrosion resistant shield (24 inches square) be used behind the vent terminal. This shield can be wood, plastic, sheet metal, etc. Also, silicone caulk all cracks, seams and joints within 3 feet of the vent terminal. COMBUSTIBLE MATERIAL WALL A minimum clearance of 1" to combustible materials must be maintained when using single wall stainless steel venting. See Figure 31. Shield material to be a minimum of 24 gauge stainless or aluminized sheet metal. Minimum dimensions are 12"x12". Shield must be fastened to both inside and outside of wall. Use screws or anchor type fasteners suited to the outside or inside wall surfaces. NONCOMBUSTIBLE MATERIAL WALL The hole through the wall must be large enough to maintain pitch of vent and properly seal. Use cement mortar seal on inside and outside of wall. See Figure 32. FLUE GAS DEGRADATION -- The moisture content of the flue gas may have a detrimental effect on some building 18 18-CD19D8-15 Installer's @ Guide SUPPORT HORIZONTAL PIPE EVERY 3' 0" WITH THE FIRST SUPPORTAS CLOSE TO THE FURNACE AS POSSIBLE. INDUCED DRAFT BLOWER, HOUSING, AND WEIGHT OF THE FLUE PIPE. FURNACE MUST NOT SUPPORT THE __ | _-I {_ {_ I_ I_ PITCH - t $4" PER FOOT 40" UPFLOVV OR.DO".rv_FLOW FURNACE HORIZONTAL AND VERTICAL ® VERTICAL REMOVE RIBS FROM VENT 9" MIN. VENT"_ _ 12' :t I"_ / DISTANCE FROM TOP OF VENT TO BO1TOM OF AIR INLET MUST I I _ MAINTAINED 12-INCH CLEAr4ANCE ABOVE HIGHEST MUST BE AN_C!PATED SNOW LEVEL MAXIMUM NOT TO EXCEED 24 INCHES ABOVE ROOF, MAINTAIN 12 IN. (18 IN. FOR CANADA) I ABOVE HIGHEST ANTICIPATED SNOW LEVEL. MAXIMUM OF 24 IN. ABOVE ROOF. COMBUSTION AIR INLET MAINTAIN VENT REMOVE RIBS FROM CAP ,_ COMBUSTION _ AIR ROOF (FIELD 12 IN. (18 IN. FOR CANADA) MINIMUM CLEARANCE _ SEAL BETWEEN FLANGE, PIPE, COUPLING AND METAL PANEL WITH HI TEMP RTV SILICONE SEALANT ANTICIPATED SNOW LEVEL. MAXIMUM OF ABOVE HIGHEST 24 IN. ABOVE ROOF PIPE COUPLING BOOT SUPPLIED) suP SUPPORT FLANGE (FIELD SUPPLIED) ELBOW (FIELD SUPPLIED) CEILING GALVANIZED FIRESTOP SHOULD BE FABRICATED WITH 3-7/8" DIA. HOLE FOR SUPPORT FLANGE COMBUSTION AIR BAYAIR30AVENTA 18-CD19D8-15 (VERTICAL) (12" x 12" PANEL OR 12" DIA MIN.) CLEARANCE ( 1 " ACCEPTABLE (0" FOR ACCEPTABLE TYPE 29-4C FOR PVC VENT STAINLESS STEEL PIPE) VENT PIPE ) VENTING THROUGH CEILING 19 Installer's Guide VENTING THROUGH THE ROOF When penetrating roof with a 2" PVC vent pipe, a 2" electrical conduit flashing may be used for a weather tight seal. Lubricate flexible seal on flashing before PVC pipe is pushed through the seal. (Field Supplied) ® SEAL BETWEEN FLANGE, PIPE, COUPLING AND METAL PANEL WITH HI TEMP RTV SILICONE SEALANT SUPPORT COUPLING _ FLANGE GALVANIZED NOTE: No vent cap as shown in Figure 34 is the preferred method for vertical vent termination in extremely cold climates. / FLOOR PANEL (FIRESTOP) In extreme climate conditions, insulate the exposed pipe above the roof line with Armaflex type insulation. VENT FITTING MATERIAL - STAINLESS STEEL Gas and liquid tight single wall metal vent fitting, designed for resistance to corrosive flue condensate such as Type 29-4C MUST be used throughout. These fittings locally. and fitting accessories FLUE PIPE CLEARANCE (0"ACCEPTABLE FOR PVC VENT PIPE) (1"ACCEPTABLE FOR TYPE29-4C STAINLESS STEELVENT are to be supplied PIPE) DIRECTION OF STAINLESS STEEL FITTING All stainless steelfittingmustbeinstalled withmaleend towards the furnace. ................................................................................ All horizontal stainless steel sections with the seam on top. All long horizontal sagging. All pipe joints of combustion sections must be positioned must be supported must be fastened and sealed products into the building. to prevent to prevent escape TYPE 29-4C STAINLESS STEEL VENTING USED THROUGH CHIMNEY THAT VENTS ANOTHER GAS APPLIANCE STAINLESS STEEL VENT CAP (OPTIONAL) SEE CAUTION ® 6 IN. MIN. PVC PLASTIC VENTING - ONLY THROUGH UNUSED CHIMNEY STAINLESS STEEL VENT CAP SUPPORT THE SINGLE WALL STAINLESS STEEL GAS VENTING AND CENTER IT IN THE CHIMNEY OPENING WITH ANGLES AS SHOWN OR ANOTHER EQUIVALENT MANNER. 6 IN. MIN. FLUE PIPE COUPLING TO SUPPORT PIPE FROM ANGLES OR OTHER SUITABLE SUPPORT METHOD SUPPORT THE SINGLE WALL FLUE PIPE AND CENTER IT IN THE CHIMNEY OPENING WITH ANGLES AS SHOWN OR ANOTHER EQUIVALENT MANNER. COUPLING AS REQUIRED NOTE: HORIZONTALVENTING TO VERTICAL VENTING FLUE PIPE NOTE: HORIZONTALVENTING TO VERTICALVENTING Do not run vent through chimney for wood burning or oil furnaces or incinerators. Do not run vent through chimney for wood burning or oil furnaces or incinerators or any other gas appliance. If remaining free area between single wall flue pipe and masonry chimney is to be used for another gas appliance venting area must be sufficient to vent that appliance and that appliance must be connected to chimney with separate entry openings. IMPORTANTThe single wall flue pipe joints must be sealed. IMPORTANTThe single wall flue pipe joints must be sealed. The 90 ° elbow connection to vertical pipe must be sealed to prevent condensate leakage to base of masonry chimney. The 90 ° elbow connection to vertical pipe must be sealed to prevent condensate leakage to base of masonry chimney. VENTING ROUTED THROUGH A MASONRY CHIMNEY 20 18-CD19D8-15 Installer's ® HORIZONTAL Guide VENT CLEARANCES INSIDE CORNER FV'] VENTTERMINAL (_) AIR SUPPLY INLET [] DETAIL AREAWHERE Non-Direct Vent Terminal Canadian Clearance balcony above A= grade, B= Clearance to window veranda, porch, deck, Clearance Vertical to permanently clearance closed to ventilated D= the terminal E= Clearance within to unventilated F= Clearance to outside G= Clearance to inside Clearance to each above may be opened located distance line of the to service of center Clearance to nonmechanical building or the combustion M= Clearance under 36 inches > 100,000 (91 cm) for appliances Btuh Btuh Btuh (3 kw), (3 kw) 4 feet (1.2m) below or to the side of opening; 1 foot (0.3m) above opening. (30 kw) above of 2 feet terminal line extended 3 feet (91 cm) with regulator vent outlet air supply a paved sidewalk on public property veranda, 15 feet (4.5 porch, 6 inches (15 cm) for appliances 12 inches (30 cm) for appliances and =/< 100,000 Btuh (30 kw), 36 inches (91 cm) for appliances inlet the =/< 10,000 Btuh (3 kw), > 10,000 Btuh (3 kw) > 100,000 Btuh 4 feet 7 feet (2.13 or balcony 12 inches (1.2 m) below or to side of opening; 1 foot (300 m) above opening (30 kw) 6 feet (1.83m) or paved deck, m) above assembly 3 feet (91 cm) air supply inlet to air inlet to any other to a mechanical a height meter/regulator appliance above located > 10,000 assembly J= Clearance driveway =/< 10,000 (30 cm) corner side Clearance L= (15 cm) for appliances 12 inches (30 cm) for appliances and =/< 100,000 Btuh (30 kw), 12 inches soffit I= Clearance (30 cm) corner meter/regulator K= US Installations window soffit a horizontal (61 cm) from the center H= Clearances Installations 12 inches or door that IS NOT PERMITTED or 6 inches C= TERMINAL 3 feet (91 cm) above if within 10 feet (3m) horizontally m) 1 7 feet (2.13 m) (30 cm) Notes: 1. 2. In accordance In accordance with with the the 1. :l:. A vent shall not terminate Pemitted only if veranda, directly above a sidewalk or paved driveway that is located between two single family porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. Clearance with in accordance 18-CD19D8-15 current current CSA B149.1 Natural ANSI Z223.1/NFPA local installation codes Gas and Propane Installation 54 National Fuel Gas Code. and the requirements of the Code. gas supplier dwelling and the manufacturer's and serves Installation both dwellings. Instructions. 21 iiiiiiiiiiiii Installer's Guide Direct Vent Terminal Canadian Clearance above deck, or balcony A= grade, veranda, Clearance opened C= 12 inches to window Clearance Vertical located D= Installations or door that may be to permanently closed US Installations porch, 6 inches B= Clearances (30 cm) (15 cm) for appliances 12 inches =/< 10,000 12 inches (30 cm) for appliances and =/< 100,000 Btuh (30 kw), 36 inches (91 cm) for appliances > 10,000 Btuh (3 kw), Btuh > 100,000 Btuh 6 inches (3 kw) (30 kw) (30 cm) (15 cm) for appliances =/< 10,000 Btuh (3 kw), 9 inches (23 cm) for appliances and =/< 50,000 Btuh (15 kw), 12 inches (30 cm) for appliances > 10,000 6 inches (15 cm) for appliances 9 inches (23 cm) for appliances and =/< 50,000 Btuh (15 kw), =/< 10,000 Btuh (3 kw), > 10,000 Btuh (3 kw) > 50,000 Btuh (3 kw) Btuh (15 kw) window clearance to ventilated soffit above the terminal within a horizontal distance of 2 feet (61 cm) from the center line of the terminal E= Clearance to unventilated F= Clearance to outside G= Clearance to inside H= Clearance extended I= Clearance to service Clearance to nonmechanical J= corner corner to each side of center line above meter/regulator assembly inlet to building iiiiiiiiiiii soffit inlet to any other regulator or the vent outlet air supply combustion appliance 36 inches Clearance L= Clearance above a paved sidewalk or paved driveway located on public property Clearance or balcony to a mechanical under 3 feet air supply veranda, porch, 15 feet (4.5 assembly the =/< 10,000 Btuh (3 kw), > 10,000 Btuh (3 kw) (91 cm) for appliances inlet m) above (91 cm) 6 inches (15 cm) for appliances 12 inches (30 cm) for appliances and =/< 100,000 Btuh (30 kw), air K= M= 3 feet (91 cm) with a height meter/regulator > 100,000 Btuh (30 kw) 12 inches 6 feet (1.83m) 7 feet deck, (30 cm) for appliances 3 feet (91 cm) above if within > 50,000 Btuh (15 kw) 10 feet (3m) horizontally (2.13 m) l- 12 inches (30 cm) :l: Notes: 1. 2. In accordance In accordance 1-. A vent :l:. * Pemitted Clearance @ with with the current the current shall not terminate only if veranda, in accordance DOWNWARD directly CSA B149.1 Natural ANSI Z223.1/NFPA above a sidewalk Gas and Propane Installation 54 National Fuel Gas Code. or paved driveway Code. that is located between two single family dwelling porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. with local installation codes and the requirements of the gas supplier and the manufacturer's and serves Installation both dwellings. Instructions. VENTING f Furnace may be in vertical or horizontal configurat_ r All horizontal pipes must be supported at maximum of 3 foot intervals I S EQUIVALENT FEET. 40 Inch SEE NOTES Slope 1/4" per ft. I DOWNWARD VENT LENGTH IS LIMITED TO A MAXIMUM OF 15 \ __ Upflow or Downflow Furnace II J Slope 1/4" per ft. NOTES: 6" Min. .._!._ A) Condensate trap for vent pipe must be a minimum of 6 inches in height. B) Condensate trap for vent and inlet pipe must be connected into a condensate drain pump; an open or vented drain; or it can be connected to the outlet hose of the furnace's condensate trap. Outdoor draining of the furnace and coil condensate is permissible if allowed by local codes. Caution should be taken to prevent drains from freezing or causing slippery conditions that could lead to personal injury. Excessive draining of condensate may cause saturated ground conditions that may result in damage to plants. c) The condensate trap should be primed at initial start up prior to heating season operation. 22 18-CD19D8-15 Installer's IMPORTANT: The Commonwealth of Massachusetts requires compliance with regulation 248 CMR 4.00 and 5.00 for installation of through - the - wall vented gas appliances as follows: For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied: 1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery backup is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. Guide 4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4. This appliance requires a special venting system. If BAYAIR30AVENTA or BAYVENT200B are used, a copy of the installation instructions for the kit shall remain with the appliance or equipment at the completion of installation. The venting system installation instructions can be obtained from the manufacturer by writing to the following address: American Standard, 6200 Troup Highway Tyler, TX 75707 Attention: Manager Inc. of Field Operations Excellence IMPORTANT: Products installed in Canada must use vent systems that are certified to the Standard for Type BH Gas Venting Systems (ULC $636) for Class II-A venting systems (up to 65°C). Components of the vent system must not be interchanged with other vent systems or unlisted pipe or fittings. Plastic components, specified primers, and glues must be from a single system manufacturer and not intermixed with other system manufacturer's vent system parts. In addition, the first three feet of the vent pipe must be visible for inspection. b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed. 2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI!UL 2034 listed and IAS certified. 3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS". 18-CD19D8-15 23 Installer's CONDENSATE Guide DRAIN INSTRUCTIONS IV!_ [q:la//[e] VERTICAL _I It is recommended that a drain pan be installed under the furnace to prevent property damage, personal injury or death from leaking condensate. APPLICATIONS Upflow furnace - The connection tubing for left and right side drainage is shipped in the blower compartment. Install the connection tubing from the trap to the side of the unit and trim all excess tubing to avoid ldnks. Downflow furnace - The furnace is shipped with the left side drainage setup. To change the right side drain, remove the drain lines from the trap, rotate the trap 180 ° so it exits to the right, reconnect the lines, and run a 1/2" CPVC pipe from the trap out through the right side knock-out. Use RTV silicone sealant to connect the CPVC pipe to the trap for ease of removing to clean the trap. Left side Right side UPFLOW (VERTICAL) UPFLOW (VERTICAL) Use extension hose here Use Inducer Drain hose without extension UPFLOW HORIZONTAL 17" UNITS (Left side only) 24 UPFLOW HORIZONTAL 21" & 24" UNITS (Left side only) 18-CD19D8-15 Installer's HORIZONTAL Guide APPLICATIONS Upflow and Downflow furnaces - All horizontal applications are left side only. It is always recommended that the auxiliary drain pan be installed under a horizontally installed evaporator and/or 90% gas furnace. Connect the auxiliary drain pan to a separate drain line (no trap is needed in this line). The trap must be repositioned to the exterior of the cabinet. Remove the trap from its present location and reposition the trap outside of the unit, through the long circular hole, next to the secondary recuperative cell. Remove the larger &'ain line (from the secondary cell) and trim to fit between the secondary cell and the new trap location. On upflow units, plug the hole in the blower deck where the tube went through. Cut off curved end of Inducer drain hose DOWNFLOW (HORIZONTAL) Remove the hose from the induced blower and reposition into the other &'ain tap of the inducer, which is located 90 ° clockwise around the inducer. Move the cap from that &'ain tap to the unused drain tap. On upflow units, plug the hole in the blower deck where the tube went through. This tube on downflow units will need to be cut to fit between the inducer and the trap. On upflow units, this tube may need to be extended, using the tubing shipped with the furnace. Connections must be made to an OPEN/VENTED DRAIN. Outdoor draining of the furnace and coil condensate is permissible if allowed by local codes. Caution should be taken to prevent drains from freezing or causing slippery conditions that could lead to personal injury. Excessive draining of condensate may cause saturated ground conditions that may result in damage to plants. DOWNFLOW NOTE: Use 1/2" or larger PVC or CPVC pipe and fittings as required for drain connections (fittings, pipe and solvent cement not provided). (VERTICAL) NOTE: A corrosion resistant condensate pump must be used ifa pump is required for a specific drain system. i IMPORTANT: The condensate drain should be installed with provisions to prevent winter freeze-up of the condensate drain line. Frozen condensate will block drains, resulting in furnace shutdown, ff the drain line cannot be installed in a conditioned space, then UL listed heat tape should be applied as required to prevent freezing (per manufacturer's instructions). The heat tape should be rated at 5 or 6 watts per foot at 120 volts. Self-regulating (preferred) or thermostatically controlled heat tape is required. Right side Use CPVC tubing from Trap outlet, over burner box to cabinet exit DOWN FLOW (VERTICAL) 18-CD19D8-15 Evaporator and furnace condensate drain piping may be manifolded together. A primary drain vent stack must be installed and terminated below the outlet of the secondary heat exchanger drain connection to prevent water from damaging furnace controls if the primary drain outlet plugs up. Where the furnace is installed above a finished ceiling, the primary drain vent stack must be installed such that overflow from the vent stack opening will flow into an axillary drain pan in order to prevent water damage to the finished ceiling below. 25 Installer's Guide FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE 1 STAGE HEATING USING A 1 STAGE HEATING THERMOSTAT NO COOLING 2 STAGE FURNACE T"STAT NOTES: SEE NOTE 7 L I 2 3 [] [] : [] [] If upflow over from stack drain the furnace must pan to finished flow [] is installed a finished ceiling, the primary drain into prevent ceiling SEE NOTE 8 6 7 [] 8 9 _]-_ overflow vent BE SURE POWER AGREES WITH EOglPMENT NAMPLATE(S) LOW VOLTAGE (24V AIRING) TO BE NO 18 AW G MIN GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES SET THERMOSTAT HE_T ,,yS ¢_TI_IPATOR AIRING OF DIAGR&M THESE LEADS PNOVIDE ' ROWERPER FOR UNIT CO_'iMECTION ELECTRONIC CLEANER AND HUMIDIFIER MAX LOAD I0 AMPS EACH THIS CONNECTION IS ONLY USED FOR THERMOSTATS REOUIRIMG CONNECTION TO THE 24 V POWER SUPPLY (COMMAN) SEE TWINNING CONNEDTION DIAGRAMS FOR PROPER CONNECTIONS WHEX USING THIS FEATURE WHEN A HEATING THERMOSTAT (WITHOUT FAN SWITCH) IS USED, NO WIRING ON "G" TERMINAL OF IFD IS USED AI _NI} A2 MilST BE JUM_ERED TOGETHER FOR _ROPER OPERATION SECOND STAGE HEATING AILL BEGIN I0 MINUTES AFTER FIRST STAGE AIR ,4 _FIELD ADDED JUMPER WlTOW2. •\SCREW GROU N D an auxiliary damage to [] below, 1 TER Primary drain vent stack must terminate below SEE NOTE 6 COMPO[ENT [] ,,MIRI ---- 24 V. "L FIELD L ]NE v. _* M_'I_ [NG -- 24 V. _ FA;T{ _Y L ]NE /.#>" 'A,'IR [MG G { secondary heat exchanger condensate drain outlet, To drain opening ",,, FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE 2 STAGE HEATING USING A 2 STAGE HEATING THERMOSTAT NO COOLING 2 STAGE T'STAT FURNACE SEE NOTE 7 Fq Pq Fq @ Fq E] D D FS CII,!f:C 24 ENT V'. ----LINE BE SURE POWER AGREES WITH EQUIPMENT NAMPLATE(S). LOW VOLTAGE (24V, WIRING) TO BE NO, 18 A.W,G. MIN., GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES. SET THERMOSTAT HEAT ANTICIPATOR PER UNIT WIRING DIAGRAM. THESE LEADS PROVIDE 115 V. POWER FOR CONNECTION OF ELECTRONIC CLEANER AND HUMIDIFIER MAX, LOAD 1.0 AMPS EACH. THIS CONNECTION IS ONLY USED FOR THERMOSTATS REQUIRING CONNECTION TO THE 24 V. POWER SUPPLY (COMMON) SEE TWINNING CONNECTION DIAGRAMS FOR PROPER CONNECTIONS WHEN USING THIS FEATURE, -L _ FIELD LINE 'M'. _, ',,'. G FACT Ow, Y '_'11_ I O _, From 26 AIR ',A"IF_]N(" ,/.j,/WIRI[ 2 -- I 2 3 4 5 SEE NOTE 6 D INTER NOTES' -D Dwg. 21B342024 Rev. 0 18-CD19D8-15 Installer's Guide FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE 2 STAGE HEATING, 1 STAGE COOLING USING A 2 STAGE HEATING, 1 STAGE COOLING THERMOSTAT (OUTDOOR SECTION WITHOUT TRANSFORMER) 2 STAGE FURNACE T'STAT SEE NOTE 7 OUTDOOR UNIT t-q D Fq (NO TRANSFORMER) NOTES: SEE I. 2. 3. 4. 5. 6. NOTE 8 D 7. D t--q D D 8. BE SURE POWERAGREES WITH EQUIPMENT NAMPLATE(S) LOW VOLTAGE (24V. WIRING) TO BE NO. 18 A.W.G. MIN.. GRO DIG OF EQ IPMENT MUST COMPLY WITH LOCAL CODES SET THERMOSTATHEAT ANTICIPATOR PER U IT WIRING DIAGRAM THESE LEADS PROVIDE 115 V. POWERFOR CON ECTION OF ELECTRONIC AIR CLEA ER AND HUMIDIFIER MAX. LOAD 1.0 AMPS EACH. THIS CONNECTION IS ONLY USED FOR THENMOSTATS REQUIRING CONNECTION TO THE 24 V. POWERSUPPLY. (COMMO) SEE TWINNING CO NECTION DIAGRAMS FOR PROPER CONNECTIONS WHE USING THIS FEATURE THE "Y" TERMINI AL FROM THE THERMOSTAT M ST BE WIRED TO THE "Y" TERMINAL OF THE FURNACECO TROL FOR PROPER BLOWER OPERATION DUAl G COOLING. D D SEE NOTE 6 TO 115Vl @ INTE:_ COM:_ONENT 24 V. 24 V. WIRING \ ----LINE PH., 60 HZ.,POWER SUPPLY PER LOCALCODES i i HUM SEE NOTE5 FIELD Y._ WIR ING WH _ --LINE FACTORY Y._ EAC SEE NOTE5 WIRIN( From Dwg. B342021 BK Rev. 0 L FIELD WIRING DIAGRAM FOR 2 STAGE FURNACE 2 STAGE HEATING, 1 STAGE COOLING USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT (OUTDOOR SECTION WITHOUT TRANSFORMER) 2 STAGE FURNACE T'STAT SEE NOTE 7 L OUTDOOR NOTES: I. 2. 3. 4. 5. -B UNIT (NO TRANSFORMER) ...... __ ---D 6. SEE 7. .N_O_T_E_S_ --D E_--- --D E_--- --[_. 8. 9. BE SURE POWERAGREES WITH EQUIPMENT NAMPLATE(S). LOW VOLTAGE (24V. WIRING) TO BE NO. 18 A.W.G. MIN.. GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES. SET THERMOSTAT HEAT ANTICIPATOR PER UNIT WIRING DIAGRAM. THESE LEADS PROVIDE 115 V. POWER FOR CONNECTION OF ELECTRONIC AIR CLEANER AND HUMIDIFIER MAX. LOAD I.O AMPS EACH. THIS CONNECTION IS ONLY USED FOR THERMOSTATS REQUIRING CONNECTION TO THE 24 V. POWERSUPPLY. (COMMON) SEE TWINNING CONNECTION DIAGRAMS FOR PROPER CONNECTIONS WHEN USING THIS FEATURE, THE "Y" TERMININAL FROM THE THERMOSTAT MUST BE WIRED TO THE "Y" TERMINAL OF THE FURNACE CONTROL FOR PROPER BLOWER OPERATION DURING COOLING. Wl AND W2 MUST BE JUMPERED TOGETHER FOR PROPER OPERATION. SECOND STAGE HEATING WILL BEGIN I0 MINUTES AFTER FIRST STAGE. 'T GROUND \ SCREW i FIELD ADDED _--_f,- JUMPER (NOTE 9) ,I I ! _b .................. F U R N AC E iK! JUNCTION SEE __ - ['-LH TO115V1 PH,, I .... - [_1 i 60 HZ., POWER B,< L_]_]_ "_'_' I _ I I'm J SUPPLYPER 1 LOCAL COOES | ,N INTER COMPONENT HUM SEE J -...... 24 V. ----LINE 18-CD19D8-15 FIELD NOTE__ ,,_11 I BOX 11 I , I V.TW]RING 24 --LINE \ ._______£_ rwH/I -- WIRING I WH/II V. "'_ V._y FACTORY WIRING EAC SEE NOTE 5 , B_< I ,, From Dwg. B342019 Rev. 0 27 Installer's Guide TWINNING CONNECTION FOR TWINNING 1 STAGE OUTDOOR UNIT NO. 1 (WITH TRANSFORMER) SEE NOTE 3 DIAGRAM UX/DX-R HEAT / 1 STAGE FURNACES COOLING THERMOSTAT NOTES 1 STAGE HEATING / COOLING THERMOSTAT FURNACE I NO. 1 FURNACE NO. _OTN FURNACESMUST 3_ ROWERE_FRON THE SANE _lGV LEG OF D_RCNIT PANEL¸ 2 SLOWEn OPERATION OF UNIT NO 2 IS SYNCRONIZED WITH UNIT NO I VIA SIGNALS FROM TWIN CONNECTION 2 _NSURE IN 24V FURNACE PHASE PRIOR CHECK VOITAGE EACH FURNACE /OV, I :Ul [ @@-(_ REVERSE ON ONE OF IF AN OUTDOOR iSOIATION (FIELD OI IF (F_ELO SUPPUEO> A_ERNaTE CONNECTION CURRENT NOTE 4 @ OUTDOOR UNIT NO. 1 (NO TRANSFORMER) ON BOTH DUT_ SEE _ CONNECTION CURRENT RELAYS _ RELAY ALT THERMOSTAT CONNECT MAY LEADS TRANSFORNER, /NSTA!L[D PILOT ISOLATION NOT OF THAN SECONDARY _'Ri') AS TO #) IF THE THERNOSTAT OR A_OV_ R_OUIRED FOR ELECTRONIC THERMOSTATS ..... i l l UNITS. 2ND STAGE WILL FIRE 10 MINUTES AFTER 1 ST RD RELAY NOT NEEDED AR_ RATED AT I OA CONNECTION S ARE CONNECTIONS, TRANSFORNERS RLFORZ5) EXCEEDS _DO _SOLATION CONTACTS AN USE AS US_ SRO_N SEE BL FURNACE UNIT HAS A RAY R{!AY MUST B_ SUCH RATING, I THE THE SUPPLIED {'NC'), TRANSFORMERS TO COMPLETING BET_EN "R" TERMINAIS 1{ VOLTAGE fS GREATER i i I[ TER I ,.J J CO_,IPONENT ......... I F-_-I BJ 24 V'. J h 24 V. L INE -- EONF 16URATION '_ FIELD /uiv'v'ISY'i]R'ING ISOLATION RELAy SEE NOTE 4 i I ,{]fffffffffffffff i I i I r % SEE NOTE 1 i, From % 5 ISOLATION RELAY Dwg. 21B341336 Rev. 2 {HELD SUPPLIED} SEE NOTE 4 :1 i i • • TWINNING CONNECTION DIAGRAM FOR TWINNING UX/DX-R FURNACES 2 STAGE HEAT/1 STAGE COOLING THERMOSTAT OUTDOOR UNIT NO. 1 (WITH TRANSFORMER) SEE NOTE 3 2 STAGE HEATING 1 STAGE COOLING THERMOSTAT I FURNACE NO. 2 BLOWER OPERATION OF UNIT NO 2 iS SYNCRONIZED WITH UMT NO 1 ViA SIGNA£5 FROM _IN CONNECTION R _OTN EURNAC[S THE SAME HSV INSUR_ 24V RUST I£D B[ POWERED O# CIRCUIT FURNAC_ #RON PANEl TRANSFORMERS AN_ IN PHASE PRIOR TO COMPLETING CONNECTIONS, CHECK VOLTAGE BETNEEN "R" TERMINALS OF EACH _URNACE /_ VOLTAGE IS GREATER THAN JOY, REVERSE ON ON# 0# THE S (FIELR Fq SUPPLIEO ('RE'), 4 THE _L AN RD SECONDARY #URNAC[ TRANSfORMeRS IF USE SUCH AS CURRENT RATING, USE PILOT RLYORYR EXCEEDS ) DUTY SEE ISOLATION RELAYS REIAY ALT TNERNOGTAT ISaAT_ON E] s?sj;?R RELAY (F_ELD SUPPUEO) SEE NOTE 4 r ...... , ' i CONTACTS ARE RATED AT IRA CONNECTION CURRENT {'RI') AS SNO_N (DO NOT CONNECT _ TO _) ISOIATION REIAY NOT NEEDED _F THE OUTDOOR UNIT NO. 1 (NO TRANSFORMER) LEADS iF OUTDOOR UNIT HAS A RAY TRANSFORM[R, AN ISOLATION RELAF MUST BE _NSTALLED THERMOSTAT OR ABOVE CONNECTION MAY DE REQUIRED THE RNOS TATS FOR ELECTRONIC RI; L ; F Bi INTER CO,,PC ENT ATERRATE Fq Fq : 2 4 ,/. I --L-- ; -- I Fq Fq LINE I ",/V]RINO CORF_G_RATION SEE NOTE 4 ......... R2; _1 _INlflG 24 LI[ h> F ]E k D ,/.J '/. E ',/'filING _ FACTO_{Y ._,/VIZ{IN(" I I I i % From Dwg 21B341337 Rev, 2 I i: • • 28 i "I i 18-CD19D8-15 Installer's TWINNING CONNECTION Guide DIAGRAM FOR TWINNING UX/DX-R FURNACES 2 STAGE HEAT / 2 STAGE COOLING THERMOSTAT OUTDOOR UNiT NO. 2 _OTE; 2STAGEHEATING 1STAGECOOLING (NO TRANSFORMER} SEE NOTE 3 THERMOSTAT FURNACE NO. 1 FURNACE NO.2 BLOWER OPEraTION Or wl_ UNIT.Olvl_sle._Ls °:ff_,22222 ° SOATO_ f OUTDOOR UNiT NO #[iAr '¢0T sY"°W 4 ¸ ; m; ; (NO TRANSFORMER) RI; _ i _,_ F TU[ Trfl2_OSTRT ISO_TI_ nE_¥ ISO_TION RElY (FIELD SUPPLIED) 1 i_i 'J OUTDOOR UNIT HITH TRANSFORMER SEE NOTE 3 I i tO a2l_; :: R2; i _; i i; : I , " z0, o' ISO_TION I RElY ACT_NAT_ CO.NECTION I I I % SEE NOTE 5 % ! % INTER CObIPONENT 24 /, IIL]NE From Dwg. 21 B341338 'FT[R]NG AL T!PNAT_ #HUt¢O (O_[ /. _PAT I_ I, FIE L D _'¢V[RINQ Rev. 2 --LINE 24 '/. " ;% "A'[ FA::T_ IN }RY G CARBON MONOXIDE POISONING HAZARD Failure to follow the installation instructions for the venting system being placed into operation could result in carbon monoxide poisoning or death. ELECTRICAL CONNECTIONS Make wiring connections to the unit as indicated on enclosed wiring diagram. As with all gas appliances using electrical power, this furnace shall be connected into a permanently live electric circuit. It is recommended that furnace be provided with a separate "circuit protection device" electric circuit. The furnace must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code, ANSI/NFPA 70 or CSA C22.1 Electrical Code, if an external electrical source is utilized. The integrated furnace control is polarity sensitive. The hot leg of the 120V power supply must be connected to the black power lead as indicated on the wiring diagram. Provision for hooldng up an electronic air cleaner and or humidifier is provided on the integrated control. Refer to the SERVICE FACTS literature diagram attached to furnace. 18-CD19D8-15 and unit wiring 29 Installer's Guide @ @ AUTOMATIC GAS VALVE WITH MANUAL SHUT-OFF MAIN MANUAL SHUT-OFF VALVE GROUND UNION JOINT DRIP LEG AUTOMATIC GAS VALVE WITH MANUAL SHUT-OFF MAIN MANUAL m SH UT-O FF VALVE GROUND UNION JOINT iii!iiiiii'i_iiiiliiliilii ._ DRIP _ LEG UPFLOW MAY BE LEFT OR RIGHT HAND GAS PIPING THE DOWNFLOW (VERTICAL) MAY BE INSTALLED LEFT OR RIGHT SIDE GAS PIPING MAIN MANUAL AUTOMATIC GAS VALVE WITH MANUAL SHUT-OFF VALVE SHUT-OFF MAIN MANUAL SHUT-OFF VALVE GROUND UNION JOINT DRIP LEG _ AIR FLOW GRO_ UNION JOINT / ! AUTOMATIC GAS VALVE WITH MANUAL SHUT-OFF HORIZONTAL FURNACE GAS PIPING MAY BE FROM EITHER SIDE (Typical UPFLOW Furnace in horizontal configuration shown) 30 18-CD19D8-15 Installer's GAS PIPING The upflow/horizontal furnace is shipped standard for left side installation of gas piping. A knockout is provided on the right side for an alternate gas piping arrangement. See Figure 45. The installation of piping shall be in accordance with piping codes and the regulations of the local gas company. Pipe joint compound must be resistant to the chemical reaction with liquefied petroleum gases. Refer to piping Table 8, for delivery sizes. Connect gas supply to the unit, using a ground joint union and a manual shut-off valve as shown in Figures 44 & 45. National codes require a condensation drip leg to be installed ahead of the controls as shown in Figures 45 & 46. Use a backup wrench on the gas valve when installing gas piping to prevent damage to the gas valve and manifold assembly. The furnace and its individual shut-offvalve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The furnace must be isolated from the gas supply piping by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa). NOTE: Maximum pressure to the gas valve for natural gas is 13.8" W.C. Minimum pressure is 5.0" W.C. Maximum pressure to the gas valve for propane is 13.8" W.C. Minimum pressure is 11.0" W.C. All gas fittings must be checked for leaks using a soapy solution before lighting the furnace. DO NOT CHECK WITH AN OPEN FLAME! © TABLE 8 Guide NATURAL GAS ONLY TABLE OF CUBIC FEET PER HOUR OF GAS FOR VARIOUS PIPE SIZES AND LENGTHS PIPE LENGTH OF PIPE SIZE 10 20 30 40 50 60 70 1/2 132 92 73 63 56 50 46 3/4 278 190 152 130 115 105 96 1 520 350 285 245 215 195 180 1-1/4 1050 730 590 520 440 400 370 This table is based on pressure drop of 0.3 inch W.C. and 0.6 SRGR. gas TABLE 9 ORIFICE INPUT RATING BTUH NUMBER OF BURNERS 60,000 80,000 100,000 3 4 5 120,000 6 SIZES MAIN BURNER ORIFICE DRILL SIZE NAT. GAS LP GAS 45 45 56 56 45 45 56 56 COMBUSTION AND INPUT CHECK (See also High Altitude Derate) 1. Make sure all gas appliances are off except the furnace. 2. Clock the gas meter with the furnace operating (determine the dial rating of the meter) for one revolution. 3. Match the "See" column in the gas flow (in cfh) Table 10 with the time clocked. 4. Read the "Flow" column clocked. opposite the number of seconds 5. Use the following factors if necessary: For 1 Cu. Ft. Dial Gas Flow CFH = Chart Flow Reading + 2 For 1/2 Cu Ft. Dial Gas Flow CFH = Chart Flow Reading + 4 For 5 Cu. Ft. Dial Gas Flow CFH = 10X Chart Flow Reading + 4 CORRECT METHOD OF CHECKING DIRECT VENT MANIFOLD PRESSURE WITH BURNER BOX REFERENCED I Separate the tube at the unit Tee and I _' reconnectwith a short piece of field supplied tube and another Teewith the "U" Manometer ,.-. T attached. /7 11 _ /¢_/ /1 unit tubing to original position after testing pressu re! --- _ _k_ \'\ _/ JJ ___. Field supplied barb fitting with manom eter tube is attached to the"OUTLET PRESSURE TAP" on the outlet II I] II /__ Be sure toreconneot I{ the manifold II "_t II II _ | _IL _ j side of the gas valve, A CAUTION: Beturn a,tubing, caps, an, or plugs tooriginal positions when pressure checks are completed. 18-CD19D8-15 31 Installer's Guide 6. Multiply the final figure by the heating value of the gas obtained from the utility company and compare to the nameplate rating. This must not exceed the nameplate rating. 7. Changes can be made by adjusting the manifold pressure (See Table 11), or changing orifices (orifice change may not always be required). To adjust the manifold pressure: a. Turn off all electrical power to the system. b. Attach a manifold pressure gauge to the outlet pressure tap marked "OUT PRESS TAP" on White-Rodgers gas valve model 36E or boss marked "OUT P" on White-Rodgers gas valve model 36G. (See Figure 48 for White-Rodgers gas valve model 36E and Figure 49 for White-Rodgers gas valve model 36G). For the gas valve model 36E, measurements require removal of the plug and installation of a barbed fitting. Attach flexible tubing and a manometer to the barbed fitting. For the gas valve model 36G, do not remove the pressure tap test screw. Loosen the pressure tap test screw one turn and install flexible tubing and a manometer directly onto the outlet pressure boss. c. The other side of the manifold pressure gauge must be referenced to the burner box as shown in Figure 46. d. Turn on system power and energize valve. e. For the White-Rodgers gas valve model 36E: GAS FLOW IN CUBIC FEET PER HOUR 2 CUBIC FOOT DIAL SEC. 8 9 10 11 FLOW 900 800 720 655 SEC. 29 30 31 32 FLOW 248 240 232 225 SEC. 50 51 52 53 FLOW 144 141 138 136 SEC. 82 84 86 88 FLOW 88 86 84 82 12 13 14 15 16 17 18 19 20 21 600 555 514 480 450 424 400 379 360 343 33 34 35 36 37 38 39 40 41 42 218 212 206 200 195 189 185 180 176 172 54 55 56 57 58 59 60 62 64 66 133 131 129 126 124 122 120 116 112 109 90 92 94 96 98 100 104 108 112 116 80 78 76 75 73 72 69 67 64 62 22 23 24 25 26 27 28 327 313 300 288 277 267 257 43 44 45 46 47 48 49 167 164 160 157 153 150 147 68 70 72 74 76 78 80 106 103 100 97 95 92 90 120 124 128 132 136 140 144 60 58 56 54 53 51 50 TABLE 11 32 PRESSURE SETTINGS (inches 3. Replace low adjustment securely. seal screw and tighten 4. Cycle the valve several setting. times to verify regulator 5. Adjust high fire by removing seal screw (See Figure 48). the high adjustment 6. To increase outlet pressure, turn the 3/32" socket set screw clockwise. To decrease outlet pressure, turn the set screw counterclockwise. The final manifold pressure setting shall be as specified in Table 11 with an input of no more than nameplate rating and no less than 93% of the nameplate rating, unless the unit is derated for high altitude. 7. Replace high adjustment securely. 8. Cycle the valve several setting. f. For the White-Rodgers seal screw and tighten times to verify regulator gas valve model 36G: HIGH ALTITUDE DERATE Input ratings (BTUH) of these furnaces are based on sea level operation and should not be changed at elevations up to 2,000 ft. If the installation is 2,000 ft. or above, the furnace input rate (BTUH) shall be reduced 4% for each 1,000 ft. above sea level. 1. Adjust low fire by removing the low adjustment seal screw (See Figure 48). TABLE 10 FINAL MANIFOLD 2. To increase outlet pressure, turn the 3/32" socket set screw clockwise. To decrease outlet pressure, turn the set screw counterclockwise. Adjust regulator until pressure shown on manometer matches the pressure specified in Table 11. w.c.) FUEL 2nd Stage Max. 1st Stage Max. NATURAL GAS 3.5" W.C. 1.7" W.C. LP GAS 10.5" W.C. 6.0" W.C. The furnace input rate shall be checked by clocldng the gas flow rate (CFH) and multiplying by the heating value obtained from the local utility supplier for the gas being delivered at the installed altitude. Input rate changes can be made by adjusting the manifold pressure (min 3.0 - max 3.7 in. W.C. - Natural Gas) or changing orifices (orifice change may not always be required). If the desired input rate cannot be achieved with a change in manifold pressure, then the orifices must be changed. LP installations will require an orifice change. IMPORTANT: Reinstall the propane orifices to the same depth as the orifices supplied with the equipment. Installation of this furnace at altitudes above 2,000 ft. (610m) shall be in accordance with the local codes, or in the absence of local codes, the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 or National Standard of' Canada, Natural Gas and Propane Installation Code, CSA 149.1. Installation of this furnace at altitudes above 2,000 ft. (610m) shall be made in accordance with the listed high Altitude Conversion Kit available with this furnace. PART NUMBERS TABLE 12 FOR REPLACEMENT ORIFICES DRILL SIZE PART NUMBER DRILL SIZE PART NUMBER 44 45 46 47 48 49 50 ORF00501 ORF00644 ORF00909 ORF00910 ORF01099 ORF00503 ORF00493 54 55 56 57 58 59 ORF00555 ORF00693 ORF00907 ORF00908 ORF01338 ORF01339 18-CD19D8-15 Installer's Guide See Table 13 forhelp in selectingorifices iforificechange is required. Fu_'nace input rate and temperature riseshould be checked again afterchanging orifices to confirm the proper rate forthe altitude. The vent length table on page 16 shows the required vent lengths for installationsat various altitudes. An optional high altitudeidt isavailable for installationsabove 5000 feet Installationsabove 12,000 feet are not allowed). TABLE 13 ROTATE THE FRONT COVER AS SHOWN Orifice ALTITUDE ABOVE SEA LEVEL Twist Drill Size If and Orifice Required At Other Elevations Installed At Sea Level 2000 3000 400G 5000 6000 700G 8000 9000 10000 42 43 44 45 46 47 42 44 45 46 47 48 43 44 45 47 47 48 43 44 45 47 47 49 43 45 46 47 48 49 44 45 47 48 48 49 44 46 47 48 49 50 45 47 48 49 49 50 46 47 48 49 50 51 47 48 50 50 51 52 54 55 56 57 58 54 55 56 58 59 55 55 56 59 60 55 55 57 59 60 55 56 57 60 61 55 56 57 60 62 55 56 58 61 62 56 56 59 62 63 56 56 59 63 63 56 57 60 63 64 From N_ional Fuel Gas Code-Table White-Rodgers @ ALL SIDE FLANGES MUST BE OUTSIDE OF THE BOX ROTATE THE FRONT COVER INWARD MAKING SURE THAT ALL SIDE FLANGES ARE OUTSIDE OF THE BOX. F-4 4. Cycle the valve several setting. 36E 2nd Stage (HI) Manifold Pressure Adjustment 1st Stage (LO) Manifold Pressure Adjustment Gas Valve On / Off Toggle Switch INSERT THE TOP FLANGE OF THE FRONT COVER UNDER THE LIP INSIDE THE BOX 5. Adjust high fire by removing the high adjustment regulator cover screw (See Figure 49). 6. To increase outlet pressure, turn the regulator adjust screw clockwise. To decrease outlet pressure, turn the regulator adjust screw counterclockwise. The final manifold pressure setting shall be as specified in Table 11 with an input of no more than nameplate rating and no less than 93% of the nameplate rating, unless the unit is derated for high altitude. 7. Replace high adjustment tighten securely. White-Rodgers36G 2nd Stage Adjustment (HI) Manifold Pressure times to verify regulator 8. Cycle the valve several setting. g. Turn off all electrical regulator cover screw and times to verify regulator power to the system. h. Remove the manometer and flexible tubing. Remove the barbed fitting and replace the plug or tighten the pressure test screw. i. Turn on electrical valve. power to the system and energize j.Using a leakdetection solution or soap suds,check for leaksatplugor pressurebossscrew. Gas Valve On / Off Toggle Switch 1st Stage (LO) Manifold Pressure Adjustment 1. Adjust low fire by removing the low adjustment regulator cover screw (See Figure 49). 2. To increase outlet pressure, turn the regulator adjust screw clockwise. To decrease outlet pressure, turn the regulator adjust screw counterclockwise. Adjust regulator until pressure shown on manometer matches the pressure specified in Table 11. 3. Replace and tighten securely. 18-CD19D8-15 the regulator NOTE: The manifold pressure must be referenced to the burner box. The burner box pressure tap equalizes the gas valve pressure regulator. Manifold pressure is checked by installing a tee (field supplied) in the tubing, between the tee coming from the burner box tube and the gas valve, in addition to the regular gas valve pressure tap on the outlet side of the gas valve. See Figure 47. cover screw 33 Installer's Guide EXPLOSION HAZARD! PROPANE GAS IS HEAVIER THAN AIR AND MAY COLLECT IN ANY LOW AREAS OR CONFINED SPACES. IN ADDITION, ODORANT FADE MAY MAKE THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE. IF THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCAVATED AREA OR A CONFINED SPACE, IT IS STRONGLY RECOMMENDED TO CONTACT A GAS SUPPLIER TO INSTALL A GAS DETECTING WARNING DEVICE IN CASE OF A GAS LEAK. NOTE: The manufacturer of your furnace does NOT test any detectors and makes no representations regarding any brand or type of detector. Replace and/or tighten all plugs removed or loosened when adjusting gas pressure. Leak check the fittings before placing the furnace into regular service. Failure to follow this warning could result in fire, explosion, or property damage. Table 12 lists the main burner orifices used with the furnace. If a change of orifices is required to correct the furnace input rating refer to Table 13. REINSTALLATION OF THE BURNER BOX COVER Figure 49 shows the correct way to reinstall the burner box cover if adjustment or replacement of the flame sensor, hot surface igniter, or main burner orifices have required removal of the cover. START-UP AND ADJUSTMENT PRELIMINARY INSPECTIONS Disconnect power to the unit before removing the blower door. Allow a minimum of 10 seconds for IFC power supply to drain to 0 volts. Failure to follow this warning could result in property damage, personal injury or death. With gas and electrical power "OFF" 1. Duct connections are properly sealed 2. Filters 3. Venting are in place is properly assembled 4. Blower door is in place Turn the main gas valve toggle switch (See Figures 48 & 49) within the unit to the "OFF" position. Turn the external gas valve to "ON". Purge the air from the gas lines. After purging, check all gas connections for leaks with a soapy solution -DO NOT CHECK W1TH AN OPEN FLAME. Allow 5 minutes for any gas that might have escaped to dissipate. LP Gas being heavier than air may require forced ventilation. Turn the toggle switch on the gas valve in the unit to the "ON" position. LIGHTING INSTRUCTIONS DO NOT attempt to manually light the burner. Failure to follow this warning could result in property damage, personal injury or death. 34 Lighting instructions appear on each unit. Each installation must be checked out at the time of initial start up to insure proper operation of all components. Check out should include putting the unit through one complete cycle as outlined below. Turn on the main electrical supply and set the thermostat above the indicated temperature. The ignitor will automatically heat, then the gas valve is energized to permit the flow of gas to the burners. After ignition and flame is established, the flame control module monitors the flame and supplies power to the gas valve until the thermostat is satisfied. To shut off For complete shutdown: Turn the gas cock knob on the main gas valve to the "OFF" position (See Figure 44). Disconnect the electrical supply to the unit. If this is done during the cold weather months, provisions must be taken to prevent freeze-up of all water pipes and water receptacles. Whenever your house is to be vacant, arrange to have someone inspect your house for proper temperature. This is very important during freezing weather. If for any reason your furnace should fail to operate damage could result, such as frozen water pipes. SEQUENCE OF OPERATION Thermostat call for heat (2-stage thermostat) Call for 1st stage only: Wl thermostat contacts close signaling the control module to run its self-check routine. After the control module has verified that the 1st stage pressure switch contacts are open and the limit switch(es) contacts are closed, the draft blower will be energized. As the induced draft blower comes up to speed, the pressure switch contacts will close and the ignitor warm up period will begin. The ignitor will heat for approx. 20 seconds, then the gas valve is energized in 1st stage to permit gas flow to the burners. The flame sensor confirms that ignition has been achieved within the 4 second ignition trial period. As the flame sensor confirms that ignition has been achieved, the delay to fan ON period begins timing and after approx. 45 seconds the indoor blower motor will be energized at low speed and will continue to run during the heating cycle. Call for 2nd stage after 1st stage: W2 thermostat contacts close signaling a call for 2nd stage heat. After a 30 second delay, the induced draft blower will be energized on high speed and the 2nd stage pressure switch contacts will close. The gas valve is energized in 2nd stage and the indoor blower motor in high speed. 2nd stage satisfied, 1st stage still called: W2 thermostat contacts open signaling that 2nd stage heating requirements are satisfied. The induced draft blower is reduced to low speed allowing the 2nd stage pressure switch contacts to open and the gas valve is reduced to 1st stage. The indoor blower motor is reduced to low speed. 1st stage satisfied: W1 thermostat contacts open signaling that 1st stage heating requirements are satisfied. The gas valve will close and the induced draft blower will be de-energized. The indoor blower motor will continue to run for the fan off period (Field selectable at 60, 100, 140 or 180 seconds), then will be de-energized by the control module. 18-CD19D8-15 Installer's Thermostat call for heat (1-stage Thermostat) W1/W2 (jumpered) thermostat contacts close signaling a call for heat. 1st stage sequence of operation remains the same as above. 2nd stage heat will energize after the stage delay timer (field selectable at .5, 5, 10 or 15 minutes) has expired. Thermostat satisfied: W1/W2 (jumpered) contacts open signaling the control module to close the gas valve. The induced draft blower is switched to low speed and de-energized after the post purge timer has expired. The indoor blower motor will continue to operate after the flames are extinguished and then is switched to low heat speed for the FAN-OFF period. Guide ROOM AIR THERMOSTAT HEAT ANTICIPATOR ADJUSTMENT Set the thermostat heat anticipator according to the current flow measured, or the settings found in the notes on the furnace wiring diagram (found in the SERVICE FACTS or inside the furnace casing). CONTROL AND SAFETY SWITCH ADJUSTMENTS INSTRUCTIONS TO THE OWNERS In the event that electrical, fuel, or mechanical failures occur, the owner should immediately turn the gas supply off at the manual gas valve, located in the burner compartment. Also turn off electrical power to the furnace and contact the service agency designated by your dealer. LIMIT SWITCH CHECK OUT The limit switch is a safety device designed to close the gas valve should the furnace become overheated. Since proper operation of this switch is important to the safety of the unit, it must be checked out on initial start up by the installer. BURNER BOX TEMPERATURE LIMIT DEVICE All models are equipped with a manual reset temperature limit located on the burner box. In case of excessive temperature, the limit will open and cause the circuit to open which shuts off all flow of gas. To check for proper operation of the limit switches, set the thermostat to a temperature higher than the indicated temperature to bring on the gas valve. Restrict the airflow by blocking the return air (disconnecting the indoor blower may trip the inducer limit). When the furnace reaches the maximum outlet temperature as shown on the rating plate, the burners must shut off. If they do not shut off after a reasonable time and overheating is evident, a faulty limit switch is probable and the limit switch must be replaced. After checking the operation of the limit control, be sure to remove the paper or cardboard from the return air inlet. Refer to Service Facts for additional instructions. NOTE TO INSTALLER Review the following warnings with the owner. Review contents of USER'S INFORMATION MANUAL with the owner. AIRFLOW ADJUSTMENT Check inlet and outlet air temperatures to make sure they are within iiiiiiiii;iiiiiiiiiiiiIi iiliiiiiiiiHii iiiithe ranges specified on the furnace rating nameplate. If the airflow needs to be increased or decreased, see the wiring diagram for information on changing the speed of the blower motor. iii i! Disconnect power to the unit before removing the blower door. Allow a minimum of 10 seconds for IFC power supply to drain to 0 volts. Failure to follow this warning could result in property damage, personal injury or death. This unit is equipped with a blower door switch which cuts power to the blower and gas valve causing shutdown when the door is removed. Operation with the door removed or ajar can permit the escape of dangerous fumes. All panels must be securely closed at all times for safe operation of the furnace. INDOOR BLOWER TIMING Heating: The integrated furnace control module controls the indoor blower. The blower start is fixed at 45 seconds after ignition. The FAN-OFF period is field selectable by dip switches SW-2, #1 and #2 at 60, 100, 140, or 180 seconds. The factory setting is 100 seconds. Wl-W2 stage delay (jumpered together) is field selectable by dip switch SW-1, #1 and #2 at .5, 5, 10 or 15 minutes. The factory setting is 10 minutes. (See wiring diagram). Cooling: The fan delay off period is factory set at 0 seconds. The option for 80 second delay off is field selectable by dip switch SW-2, #3 (See wiring diagram). 18-CD19D8-15 35 Installer's Guide ABNORMAL CONDITIONS 1. EXCESSIVE COMBUSTION PRESSURE (WIND IN EXCESS OF 40 MP.H.) VENT OR FLUE BLOCKAGE On a call for heat, the variable speed draft inducer must first ramp up to speed and close the pressure switch before the ignition sequence is allowed to begin. If the pressure switch does not close, the motor will ramp up to maximum speed and continue to operate there for about i minute. After one minute the integrated furnace control will turn the motor off for about 30 seconds then back on in an attempt to reestablish proper operation. This condition is indicative of a highly restricted or blocked inlet or outlet vent pipe or a failed pressure switch. If pressure against induced draft blower outlet becomes excessive, the pressure switch will open. If the pressure switch is open for more than 3.5 seconds, the variable speed draft inducer will speed up and attempt to close the pressure switch. If the pressure switch is not closed within 12 seconds or if the maximum speed of the motor is reached, the draft inducer sends a fault signal to the integrated furnace control. If the unit is operating in second stage, an inducer fault will cause the furnace control to transition the system to first stage and it will operate there for 10 minutes before attempting to run again in second stage. If the unit is operating in first stage, an inducer fault will cause the furnace control to shut the system down and wait 30 seconds before attempting to reestablish operation in first stage. 2. LOSS OF FLAME If loss of flame occurs during a heating cycle, or flame is not present at the sensor, the flame control module will close the gas valve. The flame control module will then recycle the ignition sequence, then if ignition is not achieved, it will shut offthe gas valve and lock out the system. 4. GAS SUPPLY FAILURE If loss of flame occurs during a heating cycle, the system integrated control module will recycle the ignition sequence, then if ignition is not achieved, the integrated control module will shut offthe gas vNve and lock out the system. 5. INDUCED DRAFT BLOWER FAILURE Please refer to the variable speed draft inducer troubleshooting manual for diagnostic assistance. 6. CONDENSATE DRAIN BLOCKAGE If the condensate drain is blocked, either by debris, improper draining, or by freezing condensate, the pressure switch will sense the accumulation ofcondensate in the furnace drain pan. The unit will not operate properly until the condensate drain has been cleared, and the condensate flows freely. 7. RESET AFTER LOCKOUT When the integrated control module has shut the system down and gone into lockout, the system must be manually reset before the unit will restart. The system can be reset by turning the system power off for more than 1 second, or by removing 24VAC from the control for more than 1 second, or by removing the thermostat call for heat for more than 1 second but less than 20 seconds. 8. RESET AFTER BURNER BOX LIMIT SHUTDOWN If the furnace shuts down, one thing that can be checked is the burner box temperature limit switch. It is located on the bottom of the burner box. The vent and combustion air inlet terminations should be checked for blockage. If blockage exists, clear the problem and then the reset button may be depressed. If there is no blockage of the terminations, the limit switch must be reset by a qualified servicer. 3. POWER FAILURE If there is a power failure during a heating cycle, the system will restart the ignition sequence automatically when power is restored, if the thermostat still calls for heat. 36 18-CD19D8-15 Installer's Guide FAULT CODE RECOVERY On power up, last 4 faults, if any, will be flashed on the red LED. The newest fault detected will flash first and the oldest last. There will be a 2 second delay between fault code flashes. Solid red LED error codes will not be displayed. The Green LED will be on solid during last At any other time the control is powered, the indicator light will operate as shown in Table LED will flash LitePort data (one flash) every fault recovery. Green LED 14 and the red 20 seconds. Fault Code Reset The last 4 fault codes can be erased from memory by powering up the control with "G" energized and then applying "R" to the "WI" terminal 3 times within 6 seconds. The control will acknowledge the reset by turning on the red LED for 2 seconds. Green Status LED TABLE 14 INTEGRATED GREEN FURNACE "STATUS" CONTROL LED FLASH CODES Flashing Slow --- Normal - No call for Heat Flashing Fast --- Normal - Call for Heat *UX / DX Integrated Furnace Control INTEGRATED FURNACE CONTROL RED LED "ERROR" 2 Flashes --- System Lockout (Retries 3 Flashes --- Draft Pressure Error- Possible problems: a) Venting problem b) Pressure switch problem c) Inducer problem 4 Flashes --- Open Temperature 5 Flashes --- Flame sensed when no flame should be present 6 Flashes--7 Flashes --- 115 volt AC power reversed, system voltage too low Gas valve circuit error 8 Flashes --- Low flame sense 9 Flashes --10 Flashes --- Open Inducer Limit switch Inducer communication error Solid --Solid Red w/Solid Green "STATUS" LED Internal GV error or Low TH voltage 18-CD19D8-15 Continuous or Recycles FLASH CODES exceeded) Limit Switch Reset caused ignitor (Triac) fault, poor grounding or by a blown fuse or internal error. 37 Trane 6200 Troup 03/08 Highway Tyler, TX 75707 For more information contact your local dealer (distributor) Since the manufacturer has a policy of continuous product and product data improvement, change design and specifications without notice. it reserves the right to
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 38 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Sun Mar 08 04:25:06 2009 Author : Title : Subject :EXIF Metadata provided by EXIF.tools