TRANE Air Conditioner/heat Pump(outside Unit) Manual L0903230

User Manual: TRANE TRANE Air conditioner/heat pump(outside unit) Manual TRANE Air conditioner/heat pump(outside unit) Owner's Manual, TRANE Air conditioner/heat pump(outside unit) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 8

DownloadTRANE  Air Conditioner/heat Pump(outside Unit) Manual L0903230
Open PDF In BrowserView PDF
2TTR2-1N-1B
18=AC51 D2-3

ALL phases

of this

installation

IMPORTANT
-- This Document
pack upon completion of work.

must

Condensing

n

2TTR2018-060,

& 2TrR0060

comply

is customer

with

2TrR1018-060

NATIONAL,

property

STATE

and is to remain

These instructions
do not cover all variations
in
systems
nor provide
for every possible
contingency
to
be met in connection
with installation.
All phases
of
this installation
must comply
with NATIONAL,
STATE
AND LOCAL CODES.
Should further information
be
desired or should particular
problems arise which are not
covered sufficiently for the purchaser's
purposes, the matter
should be referred to your installing dealer or local distributor.

©

AND LOCAL

with this unit.

CODES
Please

return

to service information

5 FT. ABOVE UNIT-UNRESTRICTED

A. GENERAL
The following instructions
Condensing Units.

cover 2TTR2, 2TTR1 & 2TTR0;

NOTE:
These outdoor units may be used with indoor units
equipped with Thermostatic Expansion Valve or
Accutron rM FlOW Control Check Valve (EC.C. V) assembly
for refrigerant flow control only.
Check for transportation
damage after unit is uncrated.
Report promptly, to the carrier, any damage found to the
unit.
To determine
the electrical power requirements
of the unit,
refer to the nameplate
of the unit. The electrical power
available must agree with that listed on the nameplate.

B. LOCATION & PREPARATION
1. When removing unit from the pallet,
the basepan. Remove tabs by cutting
shown in Figure 2 (see page 2).

OFTHE

UNIT

notice the tabs on
with a sharp tool as

2. The unit should be set on a level support pad at least as
large as the unit base pan, such as a concrete slab. If this
is not the application used please refer to application
bulletin "Trane APB2001-02".
3. The support pad must NOT be in direct contact with any
structure.
Unit must be positioned a minimum of 12"
from any wall or surrounding
shrubbery
to insure
adequate airflow. Clearance must be provided in front of
control box (access panels) & any other side requiring
service access to meet National Electrical Code. Also,
the unit location must be far enough away from any
structure to prevent excess roof run-off water from
pouring directly on the unit. Do not locate unit(s) close to
bedroom(s).

4,

The top discharge area must be unrestricted
five (5) feet above the unit.

for at least

5. When the outdoor unit is mounted on a roof, be sure the
roof will support the unit's weight. Properly selected
isolation is recommended
to prevent sound or vibration
transmission
to the building structure.
6,

The maximum length of refrigerant
lines from outdoor
indoor unit should NOT exceed sixty (60) feet.

to

7. If outdoor unit is mounted above the air handler,
maximum lift should not exceed sixty (60) feet (suction
line). If air handler is mounted above condensing unit,
maximum lift should not exceed sixty (60) feet (liquid
line).
NOTE:
Refer to "Refrigerant

Piping Software"

Pub. No. 32-3312-02.

8. Locate and install indoor coil or air handler in accordance with instruction
included with that unit.

|nstaIIer's

@

Guide
4,

Provide a pull-thru hole of sufficient
liquid and gas lines.

5,

Be sure the tubing

BASEPAN TAB REMOVAL

6. Uncoil the tubing

is of sufficient

size to allow both

length.

--- do not kink or dent.

7. Route the tubing making all required bends and properly
secure the tubing before making connections.
8,

To prevent a noise within the building structure
due to
vibration transmission
from the refrigerant
lines, the
following precautions
should be taken:
a. When the refrigerant
lines have to be fastened to floor
joists or other framing in a structure,
use isolation
type hangers.

C. ACCUTRON

TM

FLOW CONTROL

VALVE

If the indoor unit System Refrigerant
Flow control is an
Accutron TM orifice and check valve assembly, an orifice size
change may be necessary.
The outdoor model determines
the required orifice size.
Check the listed orifice size on nameplate
of the selected
outdoor model. If the indoor unit is factory shipped with a
difihrent orifice size, the orifice must be changed to obtain
system rated performance.
IMPORTANT:
The outdoor unit is shipped with the proper size orifice and a
stick-on orifice size label in an envelope attached to the outdoor
unit. Outdoor unit nameplate will have correct orifice size
specified as BAYFCCV---A for rated performance.

D. INSTALLING

REFRIGERANT

if using existing refrigerant
are brazed, not soldered.
Condensing

LINES

lines make certain that all joints

units have provisions

for braze connections.

Pressure taps are provided on the service valves
unit for compressor suction and liquid pressures.

of outdoor

The indoor end of the recommended
refrigerant
line sets may
be straight or with a 90 degree bend, depending upon situation requirements.
This should be thoroughly checked out
before ordering refrigerant
line sets.

b. Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings.
c. Where the refrigerant
lines run through
they should be insulated and isolated.

a wall or sill,

d. Isolate the lines from all ductwork.

E. SERVICE

VALVE OPERATION

BRASS LIQUID AND GAS LINE SERVICE VALVES
The Brass Liquid and Gas Line Service Valves are factory
shipped in the seated position to hold factory charge. The
pressure tap service port (when depressed) opens only to the
field brazing side of the valve when the valve is in the seated
position.
The liquid line valve is not a back seating valve
(see WARNING below).

Extreme caution should be exercised when opening the
Liquid Line Service Valve. Turn valve stem counterclockwise only until the stem contacts the rolled edge. (See
Figure 4) No torque is required.
BRASS GAS LiNE BALL SERVICE VALVE
The Brass Gas Line Ball Service Valve is shipped in the
closed position to hold the factory refrigerant
charge. The
pressure tap service port (when depressed) opens only to the
field brazing side when the valve is in the closed position. The
Gas Line Ball Service Valve is full open with a 1/4 turn. See
Figure 5.
BRAZING REFRIGERANT LINES
1. Remove lower access cover to access service valves.

The gas line must always be insulated.

2. Before brazing, remove plugs from external copper stub
tubes. Clean internal and external surfaces of stub
tubes prior to brazing.

in scroll compressor applications, dome temperatures may
be hot. Do not touch top of compressor, may cause minor
to severe burning.

®

The units are factory charged with the system charge
required when using fifteen (15) feet of connecting line.
nameplate
charge is the same.
Final refrigerant
charge
adjustment
is necessary.
the Charging Charts in the outdoor unit Service Facts.
1. Determine
2. Consider

the most practical

BRAZE TYPE INDOOR END
SEALING

CAP

Unit

\FLO
CON,
OOL

Use

way to run the lines.

CHECK VALVE

BOD_V

__LC.V.)

ORIFICE

types of bends to be made and space limitations.

NOTE:
Large diameter tubing will be very difficult
has been shaped.

to rebend once it

3. Determine the best starting point for routing the refrigerant tubing- -INSIDE OR OUTSIDE THE STRUCTURE.
© 2003 American Standard Inc. All Rights Reserved

AS SH_

LIQUID LINE
FIELD SUPPLIED

18-AC51 D2-3

|nstaI|er's

©

LIQUID LINE SERVICE VALVE

Guide

GAS LINE SERVICE VALVE

ROLLED EDGE TO

ROLLED

EDGE

TO

CAP-_=--

CAP._

_)

/

)/CAPTIVATE

CAPTIVATE STEM
UNIT
SERVICE

SIDE

_HEX

OF

VALVE

STEM

HEADED
VALVE SYSTEM

/

SERVICE'_

SERVICE "_
PORT

_

/
--

3. Cut and fittubing,
90°bends.

minimizingthe

4. Insulate

gas line and its fittings.

the entire

5. Do NOT allow uninsulated
contact with bare gas line.

PORT

/
LIQUID LINE
CONNECTION

GAS

use ofsharp

2. Attach appropriate
hoses from manifold
and liquid line pressure taps.

liquid line to come in direct

6. Precautions
should be taken to avoid heat damage
to the pressure
tap valve core during
brazing.
It is
recommended
that the pressure
tap port valve
core be removed
and a wet rag wrapped
around
the valve body.
NOTE:
Use care to make sure that no moisture
port, while wet rag is being used.

tap

NOTE:
Precautions should be taken to avoid heat damage to
basepan during brazing. It is recommended to keep the
flame directly off of the basepan.
7. Use a Dry Nitrogen Purge and Brazing Alloy without flux
when brazing the field line to the copper factory connection. Flow dry nitrogen into either valve pressure tap
port, thru the tubing and out the other port while brazing.
8. Braze using accepted

good brazing

techniques.

LEAK CHECK
IMPORTANT:
Replace pressure tap port valve core before attaching hoses for
evacuation.
Alter the brazing operation of refrigerant
lines to both the
outdoor and indoor unit is completed, the field brazed
connections must be checked for leaks. Pressurize
through
the service valve ports, the indoor unit and field refrigerant
lines with dry nitrogen to 350-400 psi. Use soap bubbles or
other leak-checking
methods to see that all field joints are
leak-free! If not, release
pressure;
then repair!

gauge to gas

NOTE:
Unnecessary switching of hoses can be avoided and
complete evacuation of all lines leading to sealed system
can be accomplished
with manifold center hose and
connecting branch hose to a cylinder of HCFC-22 and
vacuum pump.
3. Attach center

hose of manifold

4. Evacuate until the micron
350 microns.
enters pressure

LINE

CONNECTION

gauges

to vacuum

gauge reads no higher

pump.
than

5,

Close offvalve to vacuum pump and observe the micron
gauge. If gauge pressure rises above 500 microns in one (1)
minuS, then evacuation is incomple_ or sys_m has a leak.

6,

If vacuum gauge does not rise above 500 microns
(1) minute, the evacuation
should be complete.

in one

7. With vacuum pump and micron gauge blanked oil; open
valve on HCFC-22 cylinder and charge refrigerm_t lines
_md indoor coil with vapor to tank pressure of HCFC-22
supply.
NOTE:
DO NOT VENT REFRIGERANT

@

GAS LINE BALL
CAP

UNIT

INTO THE ATMOSPHERE.

SERVICE

VALVE

_

SIDE

OF VALVE

#
PRESSURE

TAP

PORT

/

/
GAS

LINE

CONNECTION

SYSTEM EVACUATION
NOTE:
Since the outdoor unit has a refrigerant
liquid line valves must remain closed.

charge, the gas and

1. Upon completion of leak check, evacuate the refrigerant
lines and indoor coil before opening the gas and liquid
line valves.

18-AC51 D2-3

3

|nsta||er's

Guide

8. Close valve on HCFC-22
supply cylinder. Close valves
on manifold gauge set and remove refrigerant
charging
hoses from liquid and gas pressure tap ports.
NOTE:
A 3/16" Allen wrench is required to open liquid line service
valve. A 1/4" Open End or Adjustable wrench is required
to open gas line valve. A 3/4" Open End wrench is required
to take off the valve stem cap.
9. The liquid line shut-offvalve
can now be opened. Remove
shut-off'valve
cap. Fully insert hex wrench into the stem
and backout counte, rclockwise until valve stem just touches
rolled edge (approximately
five [5] turns) observing
WARNING
statement
on page 2. See Figure 4.
10. Replace liquid service pressure tap port cap and valve
stem cap. These caps MUST BE REPLACED
to
prevent leaks. Replace valve stem cap and pressure tap
cap finger tight, then tighten an additional
1/6 turn.
11. The gas valve can now be opened. Open the gas valve by
removing the shut-off valve cap and turning the valve
stein 1/4 turn counterclockwise,
using 1/4" Open End or
Adjustable wrench. See Figure 5.
12. The gas valve is now open for refrigerant
flow. Replace
valve stem cap to prevent leaks. Again, these caps
MUST BE REPLACED
to prevent leaks. Replace valve
stem cap and pressure tap cap finger tight, then tighten
an additional 1/6 turn. See Figure 5.
If refrigerant
lines are longer than 15 feet and/or a
difthrent size than recommended,
it will be necessary to
adjust system refrigerant
charge upon completion of
installation.
See unit Service Facts.

F. ELECTRICAL

When installing or servicing this equipment, ALWAYS
exercise basic safety precautions to avoid the possibility of
electric shock.
of equipment

2. Power supply must agree with equipment
3. Install
4. Ground

a separate
the outdoor

disconnect

G. COMPRESSOR

must

comply

nameplate.

switch at the outdoor

unit.

unit per local code requirements.

5. Provide flexible electrical conduit whenever vibration
transmission
may create a noise problem within the
structure.

H. OPERATIONAL
PROCEDURES

I. ELECTRIC

HEATERS

Electric heaters, if used, are to be installed in the air handling device according to the instructions
accompanying
the
air handler and the heaters.

J. START CONTROL
Some models have quick start components which are factory
installed. For models that do not have factory installed start
components,
provisions are made for a field installed start kit
accessory. When adding an accessory, follow the instructions
provided with the kit.

THERMOSTAT

An outdoor thermostat
TAYSTAT250B may be field installed.
For data, see wiring diagram attached to unit and instruction
sheet packaged with outdoor thermostat.

L. SEACOAST

SHIELD

Units installed -within one mile of salt water, including
seacoasts and inland waterways,
require the addition of
BAYSEAC001 (Seacoast Kit) at the time of installation.
IMPORTANT'.
See Limited Warranty information in Use and Care Manual

M. TROUBLESHOOTING
TROUBLESHOOTING

CHART -- WHAT TO CHECK

SYSTEMFAULTS

REFRIGERANT

Wiring

AND CHECKOUT

Final phases of this installation
are the unit Operational
and
Checkout Procedures which are found in this instruction
(see
page 8). To obtain proper performance,
all units must be
operated and charge adjustments
made in accordance with
procedures found in the Service Facts.

6. The use of color coded low voltage wire is recommended
to simplify connections between the outdoor unit, the
thermostat
and the indoor unit.
Table 1 -- NEC Class tt Control

START UP

After all electrical wiring is complete, SET THE THERMOSTAT SYSTEM SWITCH IN THE OFF POSITION SO
COMPRESSOR
WILL NOT RUN, and apply power by
closing the system main disconnect switch. This will activate
the compressor sump heat (where used). Do not change the
Thermostat
System Switch until power has been applied for
one (1) hour. Following this procedure -will prevent potential
compressor overload trip at the initial start-up.

K. OUTDOOR

CONNECTIONS

1. Power wiring and grounding
with local codes.

8. Mount the indoor thermostat
in accordance with instruction included with the thermostat.
Wire per appropriate
hook-up diagram (included in these instructions).

CIRCUIT

LiquidPressureT00High

24 VOLTS

P

P

S

P

S

S

S

Suction Pressure Too High

WIRE SIZE

MAX. WIRE LENGTH

18 AWG

150 FT

16 AWG

225 FT.

14 AWG

300 FT.

Suction Pressure Too Low
Liquid Refrig FIoodback TXV System
Liquid Refrig Floodback Capillary Tube System

LiquidPressure
TooLow
ID CoilFrosting

Compressor Runs Inadequate or No Cooling
ELECTRICAL
Compressor&ODFanDoNotStart

ODC°mpress°rFan
Won'tWilIstadH°t
Start But OD

7. Table i defines maximum total length of low voltage
wiring from outdoor m_it, to indoor unit, and to thermostat.

P

S

P

P

P

Compressor Hums But Won't Start
Compressor Cycles oil IOL
ID

Blower Won't Start

P- Pril_ry

4

P

Fan Runs

Causes

S Secondary Causes

18-AC51 D2-3

|nstal|er's
TYPICAL

FIELD HOOK=UP DIAGRAMS
VARIABLE SPEED
AIR HANDLER

T'STAT

T 'STA1

AI

A R tIANDL

Guide

AIR COI/Dli}ONER

CONDITIONER

/--,,,

IT...... R

'IL..y

/,--,,,

...... y

.... 6

ODI A

ODT

_" .... Wl

I_

!L,o
....

w2
/" ,i?x

PRINTEDFROMB152g01P02

PRINTEDFROMB152908P02
CONNECTIONS TO BE MADE FOR
OPERA]ION
OF BLOWER WlIH
HUMIDISTAT
IN COOLING

I-STAGE
OR
2STAGE
FURNACE

T'STAT

AIR CQND!TIONER

I'D

n

2 S ;.,G

,

Lil'/_C

Ai;i

(01'}

i101', R

j r_ R
'! I

NOTE

,V?

PRINTED FROMB152903 P02

:

J

j NOTE* i

_
ii_

i
[

PRINTED FROM B152907 P03
_rW2 present

"kW2presentonlyon2 stage
thermostat
andfurnace

thermostat

only on 2 stage
and furnace

Notes:

LEGEND

1. Be sure power supply agrees with equipment nameplate.
2. Power wiring and grounding of equipment must comply with local codes.
3. Low voltage wiring to be No. 18 AWG minimum conductor.
4. ODT-B must be set lower than ODT-A.

.....

FACTORY WIRING

5. If outdoor thermostats

_

FIELD WIRING

18-AC51 D2-3

(ODT)

are not used, connect Wl

to W2 and W3.

5

|nsta||er's

Guide
2TTR2, 2TTR1 & 2TTR0 OUTLINE

DRAWING

Note: All dimensions are in MM (inches).
B

/

SERe CE P:_4

LECiR

,%q

.......... _

A_D RE R 6F J5_i

_['

14(

C{):} _

f

G

v

_

'D"

i :)
NE S:R/iCE
F ,_E

PR SSUP,E T,sP
lOP DiSCIIAR(_E AREA 51<)Ui D BE
UNRESTRICiED
kOR AT {EAST
i524 (5 FEET)
ABOVE UNli
URil
SHOUiD BE PLACED SO ROOF
RU_ OFF W_[ER DOES NOI PO_R DiRE¢[L¥
ON U_iT,
AND S}iOiiiD
B_ AT [¸EAST 305 {12"}
kROM WAil¸¸ AND
A[[
SURROUNDING SHRUBBERY ON iWO SIDES¸
OTilER /WO SIDES UNRESIRIC/ED

L O ID

F

-//

i_1_

Li[,

M _ ,
BR,ZE8
T

SER,

I,C
C

"" I D :EAE
IR/, 0 COl,_C10;'

H

f

T
d

,*

::} ....

P

Z_

SS;J[

;_

[:lING

_"_

FIG. 3

K
EtECTR

CAI

SER_' CE

_

P/*S E J

.........

iI

?S (I)

i

f
22

286

,: /8'

{

O_,
lif)tE
LO¢? VO i_8E

'_

[)lb

22 2 /8}
}A
HOlE
':OX DO"O',l
:0

OU:}
¢0
'Eli
I,,RE

NE

, : D O'

...........

'_]

14

"j

''°"

N C0";1o:01
EL CtRICZ_L
OW !
f _ ................

SERV CE
A
NL

_-

B!AZE

PPESS RE TZ>P

,E,
_i:

-" i= ":_:::
H

T N{:S

_

i

i

6

MODELS

BASE

RG.

A

c

D

E

F

G

H

J

K

2TI-R0060A

3

1

832 (32-3/4)

829 (32-5/8)

756 (29-3/4)

1-1/8

3/8

143 (5-5/8)

92 (3-5/8)

210 (8-1/4)

79 (3-1/8)

508(20)

B

2TI-R1018A

1

3

648 (25-1/2)

502(19-3/4)

476 (18-3/4)

5/8

1/4

149 (5-7/8)

19 (3/4)

89 (3-1/2)

16 (5/8)

460 (18-1/8)

2TI-R1024A

1

3

648 (25-1/2)

502(19-3/4)

476 (18-3/4)

3/4

5/16

149 (5-7/8)

19 (3/4)

89 (3-1/2)

16 (5/8)

460 (18-1/8)

2TI-R1030A

2

2

651 (25-5/8)

724 (28-1/2)

651 (25-5/8)

3/4

5/16

127 (5)

57 (2-1/4)

180 (7-1/8)

44 (1-3/4)

457 (18)

2TI-R1036A

2

2

651 (25-5/8)

724 (28-1/2)

651 (25-5/8)

7/8

3/8

127 (5)

57 (2-1/4)

18o (7-1/8)

44 (1-3/4)

457 (18)

2TI-R1042A

2

2

730 (28-3/4)

724 (28-1/2)

651 (25-5/8)

7/8

3/8

137 (5-3/8)

65 (2-5/8)

21o (8-1/4)

57 (2-1/4)

457 (18)

2TI-RlO48A

2

2

730 (28-3/4)

724 (28-1/2)

651 (25-5/8)

1-1/8

3/8

137 (5-3/8)

65 (2-5/8)

210 (8-1/4)

57 (2-1/4)

457 (18)

2]q-RIO60A

3

933 (36 3/4)

829 (32-5/8)

756 (29-3/4)

1-1/8

3/8

143 (5-5/8)

92 (3-5/8)

210 (8-1/4)

79 (3-1/8)

508(20)

23q-R2018A

2

2

651 (25-5/8)

724 (28-1/2)

651 (25-5/8)

5/8

1/4

127 (5)

57 (2-1/4)

180 (7-1/8)

44 (1-3/4)

457 (18)

2TI-R2024A

2

2

730 (28-3/4)

724 (28-1/2)

651 (25-5/8)

3/4

5/16

137 (5-3/8)

65 (2-5/8)

210 (8-1/4)

57 (2-1/4)

457 (18)

2TI-R2030A

2

2

730 (28-3/4)

724 (28-1/2)

651 (25-5/8)

3/4

5/16

137 (5-3/8)

65 (2-5/8)

210 (8-1/4)

57 (2-1/4)

457 (18)

23q-R2036A

2

2

832 (32-3/4)

724 (28-1/2)

651 (25-5/8)

7/8

3/8

137 (5-3/8)

65 (2-5/8)

210 (8-1/4)

57 (2-1/4)

457 (18)

2FrR2042B

3

1

832 (32-3/4)

829 (32-5/8)

756 (29-3/4)

7/8

3/8

143 (5-5/8)

92 (3-5/8)

210 (8-1/4)

79 (3-1/8)

508 (20)

23q-R2048A

3

1

933 (36-3/4)

829 (32-5/8)

756 (29-3/4)

1-1/8

3/8

143 (5-5/8)

92 (3-5/8)

210 (8-1/4)

79 (3-1/8)

2FrR2060B

4

1

1045 (41-1/8)

946 (37-1/4)

870 (34-1/4)

1-1/8

3/8

152 (6)

98 (3-7/8)

219 (8-5/8)

86 (3-3/8)

508(20)
508(20)

1

From Dwg. 21D152898

6

Rev. 7

18-AC51 D2-3

|nsta||er's
MOUNTING

Guide

HOLE LOCATION

Note: All dimensions

are in MM (Inches).
p

342

(i3

3')

/////

_

_'!_

382
.........
,,,
M_d/

i
294

( I I 58 ;

BASE 1
[24

?05

(490)

(80i')

_398

(i5
5iY

(?034)

6Y)

ii

(6i4)

............................................
4 PL;_CES

BASE 2

688

53f

(_i'

09)

(i5i9)

22i

(869)[

NOTE: For model base size,
see table on page 6.
From Dwg. 21D152637

18-AC51 D2-3

Rev. 1

7

|nsta||er's

Guide
CHECKOUT

After installation
1. Refrigerant
2. Suction

has been completed,
Line, Leak checked

Lines and Fittings

it is recommended

that the entire system

..................................

properly

insulated

...........

3. Have all Refrigerant
Lines been secured and
isolated properly? ........................................................

[

]

[

]

[

4. Have passages through masonry been sealed?
If mortar is used, prevent mortar from coining
into direct contact with copper tubing ........................

[

5. Verify tightness

[

of all electrical

connects

...................

6. Observe outdoor fan during on cycle for clearance
and smooth operation ..................................................

[

7. Indoor coil drain line drains freely. Pour water
into drain pan ..............................................................

[

CHECKOUT

PROCEDURE

PROCEDURE

]
]

be checked against

8. Supply registers and return grilles open and
unobstructed
................................................................

[

]

9. Return

[

]

10. Thermostat
thermometer
is accurate. Check
against a reliable thermometer.
Adjust per
instructions
with thermostat
......................................

air filter installed

[

]

11. Is correct speed tap being used?
(Indoor blower motor) ..................................................

[

]

12. Operate complete system in each mode to
insure safe operation ...................................................

[

]

1

TO CHECK

@
Cool

Off

@
Heat

2

IndoorFan Operation

3

CoolingOperation

4

CheckingPerformance
& Charge

CLOSED

(ON)

COMPONENTOPERATION

Fan Switch
Auto
On

X

Sump Heat

............................................

WiTH MAiN P( )WER DISCONNECTS

INDOORTHERMOSTAT
SWITCHSETTING
Step
No.

the following list:

indoor
Blower
Runs

Outdoor
Fan
Runs

Compressor
Runs

@ Comp.
Sump
Heater

X

x

I

X

x

Ix

Furnace
Heat
Comes On

Ix

X

X

X

X

I
X
I
X
X
USECHARTSATTACHEDTO O.D. UNIT

Ixlxl

Ix

!

!

5

Heating@

6

Informowner on howto operatesystem andwhat to expectof it. At the sametime deliverOwner'sUseand Care Booklet.

X

Ix

Ix

Ii

@ Alsosetthermostatdial to callfor coolingor heatingasnecessary.
@ Checkonlynecessaryif heatingunit is used for indoorsectionandwiringhas beendisturbedduringinstallationof coolingequipment.
@ When applicable.

C

Trane
A business

Literature Order Number

2TTR2-1N-1B

File Number

SV-UN-S/S-2TTR2-1N-1B

P.I.

Supersedes

SV-U N-S/S-2TTR2-1N-

Stocking Location

PI Louisville & Webb/Mason-Houston

1A

of

American Standard Companies
gq4zw.trane.com

Trane has a policy of continuous product and product data improvement
design and specifications without notice.

and it reserves the right to change



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 8
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 4, 0, 0, 13
Create Date                     : Mon Mar 23 04:18:30 2009
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu