TRANE Package Units(both Units Combined) Manual L0903511

User Manual: TRANE TRANE Package Units(both units combined) Manual TRANE Package Units(both units combined) Owner's Manual, TRANE Package Units(both units combined) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 12

DownloadTRANE  Package Units(both Units Combined) Manual L0903511
Open PDF In BrowserView PDF
STALLATI
E
TI
TE
CE
Model:

Manufactured Housing
Package Cooling
W/ Optional Electric Heat
2-112 - 4 Ton

TCM030F1
TCM036F1
TCM042F1
TCM048F1

IMPORTANT--

This Document

18-AB33D2-3

is customer

property and is to remain with this unit. Please retum to service information

All phases of this installation must comply with the NATIONAL, STATE & LOCAL CODES.
tion must conform with National Electric Code ==ANSVNFPA 70 or "LATEST REVISION."

Since the manufacturer has a policy of continuous product and product data improvement,
it reserves the right to change design and specification without notice.
© 2001 American Standard Inc. All rights reserved

pack upon completion

of work.

In the absence of local codes, the installa-

Dwg. No. X730377 P02

GENERAL iNFORMATiON
IMPORTANT: Read this entire manual before beginning
lation procedures.

instal=

SAFETY NOTICE. THIS INFORMATION IS INTENDED FOR
USE BY INDIVIDUALS POSSESSING ADEQUATE BACKGROUNDS OF ELECTRICAL AND MECHANICAL EXPERIENCE. ANY ATTEMPT TO REPAIR A CENTRAL AIR CONDITIONING PRODUCT MAY RESULT IN PERSONAL INJURY
AND/OR PROPERTY DAMAGE. THE MANUFACTURER OR
SELLER CANNOT BE RESPONSIBLE FOR THE INTERPRETATION OF THIS INFORMATION, NOR CAN IT ASSUME
LIABILITY IN CONNECTION WITH ITS USE.

IMPORTANT:
RECONNECT ALL GROUNDING DEVICES.
ALL PARTS OF THIS PRODUCT CAPABLE OF CONDUCTING
ELECTRICAL CURRENT ARE GROUNDED. IF GROUNDING
WIRES, SCREWS, STRAPS, CLIPS, NUTS OR WASHERS
USED TO COMPLETE A PATH TO GROUND ARE REMOVED
FOR SERVICE, THEY MUST BE RETURNED TOTHEIR ORIGINAL POSITION AND PROPERLY FASTENED.
IMPORTANT: ALL POWER LEGS MAY NOT BE BROKEN BY
CONTACTORS. SEE WIRING DIAGRAM ON UNIT CONTROL
BOX COVER.

Read this manual carefully before attempting to install, operate, or
perform maintenance on this unit. Installation and maintenance
should be performed by qualified service technicians only.
NOTE:
"Warnings" and "Cautions" appear at appropriate
places in this manual
Your personal safety and the proper
operation of this air conditioning product require thatyou follow
them carefully. The manufacturer assumes no liability for
installations or servicing performed by unquafified personnel.

INSPECTION
1. Check for damage after the unit is unloaded. Report promptly,
to the carrier, any damage found to the unit. Do not drop the unit.
IMPORTANT: The use of "spreader bars" is required when
hoisting the unit (to prevent damage to sides and top).

i

1

2. Check the unit's nameplate to determine if the unit is correct for
the intended application. The power supply must be adequate
for both the unit and all accessories.
3. Check to be sure the refrigerant charge has been retained during
shipment.

BEFORE STARTING THE COMPRESSOR, THE CRANKCASE
HEATER SHOULD BE ENERGIZED FOR EIGHT HOURS.

LOCATIONS AND RECOMMENDATIONS
These units are designed for outdoor installation. For proper installation, the following recommendations must be considered.

5.

Select a location that will permit unobstructed airflow into the
condenser coil and away from the fan discharge and permit unobstructed service access into the compressor compartment. Suggested airflow clearances and service clearances are given in
Figure 2.

6.

NOTE: Unit shipped for horizontal installation.
The discharge air from the condenser fans must be unrestricted for
a minimum of 3 feet above the unit.
NOTE: ff any internal accessories are to be added to the unit it
should be done at the shop if at all practical.
1. Unit should be positioned so Roof-Run-Off water does not pour
directly on unit.
2. Exhaust vents or other sources of contaminated air should not
be near unit air inlet if outside air is to be introduced as a makeup air or the economizer ventilation feature is to be used.
3. Check the handling facilities to insure the safety of personnel and
the unit(s).
4. CAUTION MUST BE TAKEN AT ALL TIMES TO AVOID PERSONAL INJURIES AND/OR DAMAGE TO EQUIPMENT.

Page 2

7.

The unit must be mounted level for proper drainage of defrost
water through the holes in the base pan.
Flexible duct connectors must be of a flame retardant material. All
duct work outside of the structure must be insulated and weatherproofed in accordance with local codes.
Holes through exterior walls must be sealed in accordance with
local codes.

8. Access and service clearances for the unit must be given careful
consideration when locating the duct entrance openings. Figures 1 and 2 provide unit dimensions.
9. All fabricated outdoor ducts should be as short as possible.
10. Be sure the hole in the structure for the ducts is large enough to
accommodate the fabricated ducts andthe insulation surrounding
them.

CLEARANCES
1. The recommended clearances for single-unit installations are
illustrated in Figures 1 and 2. These minimum requirements are not
only an important consideration when determining unit placement,
but they are also essential to ensure adequate serviceability,
maximum capacity, and peak operating efficiency.
2. Any reduction of the unit clearances indicated in this illustration
may result in condenser coil starvation, or the recirculation of warm
condenser air.

Dwg. No. X730377 P02

iNSTALLATiON
Check unit nameplate for supply voltage required. Determine if
adequate electrical power is available. Refer to specification sheet.

1.

2.

GROUND

LEVEL -- HORIZONTAL

Attach the supply and return air ducts to the unit.

UNITS

For ground level installations, the unit should be positioned on a pad
the size ofthe unit or larger. The unit must be level on the pad. The
pad must not come in contact with the structure. Be sure the outdoor
portion of the supply and return air ducts are as short as possible.

3. Insulate any ductwork outside of the structure with at least 2
inches of insulation and weatherproof. There must be a weatherproof seal where the duct enters the structure.
4.

Proceed with the installation

Place the unit on the pad and the five (5) rubber isolators
provided.

as follows:

Complete the installation according
following sections of this manual.

to the instructions

in the

DUCTWORK
ATTACHING
TO UNIT

HORIZONTAL

DUCTWORK

All conditioned air ductwork should be insulated to minimize heating
and cooling duct losses. Use a minimum of two (2) inches of
insulation with a vapor barrier. The outside ductwork must be
weatherproofed between the unit and the building.

When attaching ductwork to a horizontal unit, provide a flexible
watertight connection to prevent noise transmission from the unit to
the ducts. The flexible connection must be indoors and made out
of heavy canvas.
NOTE: Do

not

draw the

canvas

taut between the solid

ducts. IJ

FILTER INSTALLATION
TABLE

AIR FILTERS
Filters are to be used with the TCM030=048F heating/cooling units.
The basic unit does not have filters in it. However, a filter frame
accessory is offered that will allow filters to be installed within the
unit.
Otherwise a filter rack must be installed by the installer in the duct
work.
Affix the filter label supplied with the unit adjacent to the filter area.

CONDENSATE
A 3/4-inch female NPT condensate drain connection is provided on
the evaporator access panel end of the unit. See Figure 4. Provide
a trap and fill it with water before starting the unit to avoid air from
being drawn through.
Follow local codes and standard piping
practices when running the drain line. Pitch the line downward away
from the unit. Avoid long horizontal runs. See Figure 3.
NOTE: Do not use reducing fittings in the drain lines. The condensate drain must be:

1

NOMINAL

FILTER*

FILTER

TCM030F

CFM
1000

(Sq Ft) SIZE
3.33

RESISTANCE
0.05

TCM036F

1200

4.00

0.05

TCM042F

1400

4.67

0.05

TCM048F

1600

5.33

0.05

UNIT

* Filters must be installed in the return air system. The above square
footages are based on 300 F.P.M. face velocity. If permanent filters are
used, size per mfg. recommendation with clear resistance of 0.05" WC.

DRAIN PiPiNG

®

3/4" PVC OR COPPER
TUBING AND

1-1/2" MIN.

• Made of 3/4" pipe size.
• Pitched 1/4" per foot to provide free drainage to convenient drain
system.
• Trapped.
• Must not be connected to closed drain system.

Dwg. No. X730377 P02

Page 3

DiMENSiONAL
(_

TCC030-048F

SPACER
WCMO42F

CORNER

POST_

WCM042

ONLY_

DATA

OUTLINE

PANEL_
ONLY_

W5

RETURN
-SUPPLY
PANEL

COIL
& BLOWER PANEL

&

_

CONDENSOR
WCMO42F

- FRONT

/-CENTER
GRAVITY

OF

COl
ONLY

FOR

5/4"

DRAIN
FEMALE
NPT

o
LTER
ACCESS

PANEL

RETURN
OPENING

CORNER WEIGHT (LBS)

MODEL

UNIT
WEIGHT

Wl

W2

W3

W4

TCMO30F

75

64

82

97

318

TCMO36F

92

72

77

99

340

TCMO42F

91

71

79

102

343

TCMO48F

93

72

81

104

350

Page 4

A

B

55-1/4

36

c

D

E

12
29-3/16

12

36

29-3/16

14

G

H

12-5/16
17-1/8

14
62-3/4

F

12-5/16

10-1/16

17

11-3/16
22-3/4

12-5/16

10-1/16

17

J

K

20-3/16

25-5/16

18-5/8

24-3/16

19

24

19

24

Dwg. No. X730377 P02

DiMENSiONAL
TCC030-048F

DATA

OUTLINE

- REAR

C

HOLE
(UNIT

FOR
1/2"
CONTROL

CONDUIT
WIRES)

--

CONDENSER
CONTROL
ACCESS

BOX
PANEL

HEATER
ACCESS

PANEL
AREA
ONLY
TCCO42F,
WCC060F

729945
RECOMMENDED

SERVICE

COIL
IN
THIS
ON WCC050
& -056F,
WCCO42F,
WCCO48F
&

CLEARANCE

BACK

6.0"

LEFT SIDE

30.0"

RIGHT SIDE

24.0"

FRONT SIDE

30.0"

MODEL

A

B

TCMO30F
TCMO36F
TCMO42F

55-1/4

36

TCMO48F

62-3/4

36

Dwg. No. X730377 P02

COIL

C

D

E

29-3/16

12-15/16

4-7/8

29-3/16

14-1/2

4-7/8

F

KNOCKOUTS

FOR 3/4" AND1-1/4"

CONDUIT

Page 5

ELECTRICAL
ELECTRICAL

CONNECTIONS

Electrical wiring and grounding must be installed in accordance with
local codes or, in the absence of local codes, with the National
Electrical Code ANSI/NFPA 70, Latest Revision.

ELECTRICAL

POWER

It is important that proper electrical power be available for the unit.
Voltage variation should remain within the limits stamped on the unit
nameplate.

DISCONNECT

Do not short thermostat
transformer.

Provide an approved weatherproof disconnect either on the side of
the unit or within close proximity and within sight of the unit.

PROTECTION

wires since this will damage the control

Recommended wire sizes and lengths for installing the unit thermostat are provided in Table 2. The total resistance of these low
voltage wires must not exceed one (1) ohm. Any resistance in
excess of 1 ohm may cause the control to malfunction because of
the excessive voltage drop

TABLE 2
THERMOSTAT

SWITCH

OVER CURRENT

WiRiNG

WIRE

SIZE
18

WIRE SIZE AND MAXIMUM LENGTH
MAXIMUM

LENTGH
75

16

125

14

200

(Ft)

The branch circuit feeding the unit must be protected as shown on
the unit rating plate.

POWER

THERMOSTAT

WIRING

The power supply lines must be run in weathertight conduit to the
disconnect and into the bottom of the unit control box. Provide strain
relief for all conduit with suitable connectors.
Provide flexible conduit supports whenever vibration transmission
may cause a noise problem within the building structure.
Be sure all connections

are made tight.

See Figure 4.

NOTES: For branch circuit wiring (main power supply to unit
disconnect), wire size for the length of run should be determined
using the circuit ampacity found on the unit nameplate and the
N.E.C.
For more than 3 conductors in a raceway or cable, see the
N.E.C. for derating the ampacity of each conductor.
GROUNDING: THE UNIT MUST BE ELECTRICALLY GROUNDED
IN ACCORDANCE WITH LOCAL CODES OR THE NATIONAL
ELECTRIC CODE.
NOTE: Ground the unit
diagram for location.

internally

CONTROL

(CLASS

WIRING

as provided.

HEAT ANTICIPATOR

The thermostat heat anticipators should be set to equal the amperage draw of the Wl thermostat circuit.

IMPORTANT:
Upon completion of wiring check all electrical
connections,
including factory wiring within the unit. Make
sure all connections are tight. Replace and secure all electrical box
covers and access doors before leaving the unit or turning on the
power to the unit.
After all electrical wiring is complete, set the thermostat
system
switch in the OFF position so that the compressor
will not run
and then apply power by closing the system main disconnect
switch. This will activate the compressor sump heat. Do not change
the Thermostat System Switch until power has been applied long
enough to evaporate any liquid R-22 in the compressor.
It is
recommended that the sump heater be energized for eight (8) hours
prior to starting.

See wiring

ll)

Low voltage control wiring should not be run in conduit with power
wiring unless Class 1 wire of proper voltage rating is used. Route
the thermostat cable or equivalent single leads of No. 18 AWG
colored wire from the thermostat subbase terminals through the
rubber gromment on the unit. See Figure 2 for the control entry
location. Make connections as shown on the unit wiring diagram
and in Figure 4.

Page 6

Dwg. No. X730377 P02

@

TCM-F FIELD WiRiNG
PACKAO

D COOl

NR/F

FCTR

i,S

HEAT

DIAGRAM

LN i T

I
I
I

I
I

I

I

HEAFER
CONTROl
iSOX

•
4

I
I

/_

B{st}

IL
I

I

,(, K:

I

/_

i

t_ N° _

Y

2

,_

:?i

.....
:

<)_',E R

,_

y

.,

TYP CAI
n-,f
5 Pi
>o/,i R

5Pil
,ov,'

N0'

I, 8

R

zj

TI [RM(){

]

4

4 C(il/)
[L .......... 55A(D)
i A(E A E'_

',

J U'v'

,E

NO E

z,,,iR)

B

C0 ,s,_0N

(

r;'¢;_.......

/,I

s

R2

24 vOLtS

_AG[

:LiClllC

[[A]

R

I_1

i_
NOTES:

F

O

i

SINGLE
FC=?/ R
ENTRY
/_CCESSORY
CONNECT

IONS

1, FUSED DISCONNECT
81ZE_ POWER
MUST COMPLY
WITH CODES

WIRING

2, BE SURE POWER
NAMEPLATE,

WITH

3, LOW VOL3AGE
N i Vc'(N

I _11

N

4, SEE HEATER

A IER ARE A

SUPPLY

WIRING

6, JUMPER
HEATING

TO BE 18 AWG

NAMEPLATE

5, SEE UNIT AND HEATER
MUST

AGREES

MINIMUM

FOR CURRENT
DIAGRAM

BE CONNECTED

AND

GROUNDING

EQUIPMENT

CONDUCTOR,

RATING

FOR ELECTRICAL
BETWEEN

OF EQUIPMENT

AND HEATER

OF HEATER

USED

CONNECTION

DETAILS

1 AND 2 FOR F:AN TO OPERATE

IN

7, SOME THERMOSTATS
PROVIDE THE 'G' SIGNAL IN THE COOLING
MODE ONLY
TO PROVIDE THE 'G' SIGNAL IN THE HEATING
MODE AN ACCESSORY
RELAY
IS REQUIRED,
SEE FIG 3 FOR PROPER
CONNECTIONS
I
I

8, FOR COOLING
ONLY OMIT THE ELECTRIC
WIRES, AND THE 'W' SIGNAL THERMOSTAT

i ......
v
,,o

,o/,[

S

NISLE
N RY

,,or

ASSOCIATED

POWER

9, FIG 4 DEMONSTRATES
CONNECTION
OF THE TWO STAGE ELECTRIC
THERMOSTAT
ACCESSORY
ONLY, FOR FURTHER
UNIT CONNECTION
REFER TO THE OTHER FIGURES,

HEAT
DETAILS

10 THE 41A(BR) WIRE IS FIRST STAGE ELECTRIC
HEAT
IF THE ELECTRIC
HEATER ACCESSORY
HAS TWO HEATING
STAGES THE 41C(BR) WiRE
SECOND STAGE ELECTRIC
HEAT,

IS

,_cE ARFA

c?ou\;

R

_0,1!/ _

C

JNIT

HEATER,
WIRE,

hLJ I ()
I }} %'10S

}

CI /_NG OVEIR
,A C()N }}C ON

F: C.

4

%9'0
E,A,I

S//'_O
E EC[R
IC
CC,NNE C =ON_

: [R:

[0_'

,',2i
NTER

ACE /,_lz,

CO_,IPO[ ENT

WRING

j
24

v

N{

I-w,
J

I

I _ ¸'

-:

F

I

% i?ilR

C I

NO

_x,,,

[
N

Y

v2 -_ L,_i

,',1 _ q(

%

r E k,

TA

0

, AI

C757977P01

RE','

2

From Dwg. 21C757977P01

Owg. No, X730377 P02

Rev. 2

Page 7

START - UP
PRE-START

QUICK CHECKLIST

OPERATING

• Is the unit properly located and level with the proper clearance?
• Is the duct work correctly sized, run, taped,
weatherproofed with proper unit arrangement.
Installation section.

insulated, and
See Ductwork

• Is the condensate line properly sized, run, trapped, and pitched?
• Is the filter of the correct size and number?
place?

Is it clean and in

• Is the wiring properly sized and run according to the unit wiring
diagram?
• Are all the wiring connections,

including those in the unit, tight?

• Has the unit been properly grounded and fused with the recommended fuse size? See Wiring Data.
• Is the thermostat level, correctly wired, well located, and set for
the proper heat anticipation?
• Have the air conditioning systems been checked at the service
ports for charge and leak tested if necessary?
• Do the condenser fan and indoor blower turn free without rubbing,
and are they tight on the shafts?

PRESSURES

After the unit has operated in the cooling mode for a short period of
time, install pressure gauges on the gauge ports of the discharge
and suction line valves. Check the suction and discharge pressures
and compare them to the normal operating pressures provided in
the unit's SERVICE FACTS.
NOTE: Do not use the pressures from the unit's SERVICE FACTS
to determine the unit refrigerant charge. The correct charge is
shown on the unit nameplate. To charge the system accurately,
weigh in the charge according to the unit nameplate.

VOLTAGE
With the compressor operating, check the line voltage at the unit.
The voltage should be within the range shown on the unit nameplate. If Iowvoltage is encountered, checkthe size and length of the
supply line from the main disconnect to the unit. The line may be
undersized for the length of the run.

COOLING

SHUT DOWN

Place the system selector in the OFF position or reset thermostat at
a setting above room temperature.
Do not de-energize the main power disconnect except when unit is
to be serviced. Power is required to keep the heat pump compressor warm and boil off refrigerant in the compressor.

STARTING

THE UNIT IN THE HEATING

MODE

• Has the indoor blower speed been determined and the proper
speed been set? See the Unit Wiring Diagram.

NOTE: See the section on "'Sequence of Operation"
description of the heating operating sequence.

• Has all work been done in accordance with applicable local and
national codes?

Check to make sure all grilles and registers are open and all unit
access doors are closed before start-up.

• Are all covers and access panels in place to prevent air loss and
safety hazards?

HEATING

STARTING

THE UNIT IN THE COOLING

MODE

CAUTION: Before starting the system on the cooling cycle, turn the
thermostat switch to OFF and close the unit disconnect switch. This
procedure energizes the compressor crankcase heater, vaporizing
any liquid refrigerant in the crankcase. This is a precaution against
foaming at start-up which could damage the compressor bearings.
Allow the heater to operate a minimum of eight (8) hours.
NOTE: See the section on "Sequence of Operation" for a description of the cooling operating sequence.

for a

SHUT-DOWN

Place the system selector switch at OFF or place the heating
selector lever at a setting below room temperature.

WARNING:

DO NOT

OPERATE

THE

UNIT

WITHOUT THE EVAPORATOR
FAN ACCESS PANEL IN
PLACE.
REINSTALL
THE
ACCESS
PANEL
AFTER
PERFORMING ANY MAINTENANCE PROCEDURES ON THE
FAN. OPERATING
THE UNIT WITHOUT THE ACCESS
PANEL PROPERLY INSTALLED MAY RESULT IN SEVERE
PERSONAL INJURY OR DEATH.

To start the unit in the cooling mode, set the thermostat system
switch to COOL and move the thermostat COOL indicator to a
setting below room temperature.
The condenser (outdoor) fan
motor compressor and evaporator (indoor) fan motor will operate
automatically.

Page 8

Dwg. No. X730377 P02

SEQUENCE OF OPERATION
GENERAL

The compressor circuit starts with power from the control transformer through the thermostat switch "YI" to the compressor
contactor (CC) coil. This closes the (CC) contacts and starts the
compressor (CPR) and the outdoor fan motor (ODM). When the call
for cooling is complete, the compressor contactor (CC), outdoor fan
motor (ODM), and indoor fan relay (F) is de-energized.

Operation of the system cooling (and optional heating) cycles is
controlled by the position of the system switch on the room thermostat. Once the system switch is placed in either the HEAT OR
COOL position, unit operation is automatic. The optional automatic
changeover thermostat, when in the AUTO position, automatically
changes to heat or cool with sufficient room temperature change.

HEATING

m ELECTRIC

HEATERS

With the unit disconnect closed, voltage is supplied to the unit
control transformer and the crankcase heater (if provided). On
single phase units, the crankcase heater is optionally field installed.

On a call for heat, power from the thermostat is received at "Wl",
which energizes the "AH" contactor coil. The "AH" contactor closes
powering the heater, provided all element limits are closed.

COOLINGmMECHANICALCOMPRESSORCYCLE

If two stages of heat are provided and additional heat is required, the
thermostat's second stage "W2" circuit is energized powering the
"BH" contactor coil.

On a call for mechanical cooling, the indoor fan "G" and the
compressor circuit "YI" are energized. The indoor fan circuit "G"
starts with power from the control transformer and then energizes
the fan relay coil (F). This closes the fan relay (F) contacts and the
indoor fan motor (IDM) starts.

NOTE: The indoor thermostat must be configured to provide a "G"
signal to energize the indoor fan relay (F) during the heating mode.
The heater control circuit will not be energized unless the indoor fan
relay (F) is energized.

TROUBLESHOOTING

REFRIGERANT

CHART

CIRCUIT
P

Liquid Pressure Too high
Liquid Pressure Too Low

S

Suction Pressure Too High

S

Suction Pressure Too Low
Liquid Refrigerant

fioodback

Liquid Refrig. fioodback

P

S

P
P

P

S
S

S

S

P

S

S
S

(TXV System)
P

(Cap. Tube System)

I. D. Coil Frosting
Compressor

S

S

S

or No Cooling

S

P

S

P

P

S

P

S

S
S

P

Runs Inadequate

S

S

P
P

S

P

S

ELECTRICAL
Compressor

& O.D. fan Do Not Start

p

Compressor

Will Not Start But O.D. Fan Runs

P
P

S
S

P

P

P

P

P

P
S

O.D. Fan Won't Start

P

P

Compressor

Hums But Will Not Start

P

P

P

P

S

S

Compressor

Cycles on IOL

P

P

P

P

S

P

I.D. Blower Won't Start
P-PRIMARY
Dwg.

CAUSES

No. X730377

P02

p
S-SECONDARY

CAUSES

S

S

S

P

S

S

S

S

S

P
X664590

Page9

MAINTENANCE
ROUTINE

MAINTENANCE

BY OWNER

You can do some of the periodic maintenance functions for your
TCM=F unit yourself; this includes replacing the disposable or
cleaning the permanent air filters, cleaning the unit cabinet, clearing
the condenser coil, and conducting a general unit inspection on a
regular basis.
Be sure to inspect them at least once each month when the
system is in constant operation. (In new homes, checkthe filters
every week for the first four (4) weeks.)
If you have disposable-type filters, replace them with new filters of
the same type and size. Do not attempt to clean disposable
filters.
Permanent-type filters can be cleaned by washing them with a mild
detergent and water. Make sure that the filters are thoroughly dry
before reinstalling them in the unit (or duct system).
NOTE: It may be necessary to replace permanent filters annually
if washing fails to clean the filter or if the filter shows signs of
deterioration.
Be sure to use the same type and size as was
originally installed.

CONDENSER

Unfiltered air circulates through the unit's condenser coil and can
cause the coil's surface to become clogged with dust, dirt, etc. To
clean the coil, vertically (i.e., with the fins) stroke the coil surface
with a soft-bristled brush.
away from the condenser coil area.

MAINTENANCE
PERFORMED
BY
SERVICEMAN
-- COOLING SEASON
To keep your unit operating safely and efficiently, the manufacturer
recommends that a qualified serviceman check the entire system at
least once each year and any other time that you feel one is needed.
Your serviceman should examine these areas of your TCY-F unit:
• filters (for cleaning or replacement)
• motors and drive system components
• gaskets (for possible replacement)
• safety controls (for mechanical cleaning)
• electrical components
connection tightness)

Complete the unit inspections and service routines described below
at the beginning of each heating season.
• Visually inspect the unit to ensure that the airflow required for
condenser coil is not obstructed from the unit.
• Inspect the control panel wiring to verify that all electrical connections are tight and that the wire insulation is intact.

The following

warning

complies

with State of California

AWARNING:

and wiring (for possible replacement and

The following

warning

complies

65.

This product contains

with State of California

law, Proposition

This product

65.

contains

fiberglass
wool insulation! Fiberglass dust and ceramic
fibers are believed by the State of California to cause
cancer through inhalation. Glasswool
fibers may also
cause respiratory,
skin, or eye irritation.

PRECAUTIONARY

MEASURES

• Avoid breathing fiberglass dust.
• Use a NIOSH approved dust/mist respirator.
• Avoid contact with the skin or eyes. Wear longsleeved, loose-fitting clothing, gloves, and eye
protection.
• Wash clothes separately from other clothing: rinse
washer thoroughly.
• Operations such as sawing, blowing, tear-out, and
spraying may generate fiber concentrations requiring
additional respiratory protection. Use the appropriate
NIOSH approved respirator in these situations.

• condensate drain (for cleaning)

FIRST AID MEASURES

• unit duct connections (to see that they are physically sound and
sealed to the unit casing)

Eye Contact

-

Skin

-

• unit mounting support (for structural integrity)
• the unit (for obvious unit deterioration)

law, Proposition

fiberglass wool insulation! Fiberglass dust and ceramic
fibers are believed by the State of California to cause
cancer through inhalation. Glasswool fibers may also
cause respiratory, skin, or eye irritation.

AWARNING:

COIL

Be sure to keep all vegetation

MAINTENANCE
PERFORMED
BY
SERVICEMAN
-- HEATING SEASON

Contact

Flush eyes with water to remove dust.
If symptoms persist, seek medical
attention.
Wash affected areas gently with soap
and warm water after handling.
A150988P01

Page 10

Dwg. No. X730377 P02

LiMiTED WARRANTY
CENTRAL AiR CONDiTiONER
TCC, TCD, TCH, TCK, TCM,
TCP, THC and TSC
Models Less Than 20 Tons for Residential

Use*

(Parts Only)
This limited warranty is extended by American Standard Inc., to the original purchaser and to any
succeeding owner of the real property to which the Air Conditioner is originally affixed, and applies to
products purchased and retained for use within the U.S.A. and Canada.
If any part of your Air Conditioner fails because of a manufacturing defect within five years from the date of
the original purchase, Warrantor will furnish without charge the required replacement part. Any local
transportation, related service labor, diagnosis calls, refrigerant and related items are not included.
If the sealed motor-compressor fails because of a manufacturing defect within five years from the date of
original purchase, Warrantor will furnish without charge the required replacement compressor. Any local
transportation, related service labor, diagnosis calls, refrigerant and related items are not included.
This limited warranty does not cover failure of your Central Air Conditioner if it is damaged while in your
possession, failure attributable or caused by unreasonable use of the Central Air Conditioner and/or failure to
properly maintain the Central Air Conditioner as set forth in the Use and Care manual.
This limited warranty applies to product installedon or after 10/1/'2001 where product is manufactured after
1/1/'2000. This limited warranty is not retroactive to any installations prior to 10/1/'2001 or on product
produced prior to 2000.
THE LIMITED

WARRANTY

AND LIABILITY

SET FORTH HEREIN

ARE IN LIEU OF ALL

OTHER WARRANTIES
AND LiABiLiTiES, WHETHER iN CONTRACT OR iN NEGLIGENCE,
EXPRESS OR iMPLIED, IN LAW OR iN FACT, iNCLUDiNG BUT NOT SPECiFiCALLY
LiMiTED
TO iMPLiED WARRANTIES
OF MERCHANTABiLiTY
AND FITNESS FOR PARTICULAR
USE,
AND iN NO EVENT SHALL WARRANTOR
BE LIABLE FOR ANY iNCiDENTAL OR
CONSEQUENTIAL
DAMAGES.
Some states do not allow limitations on how long an implied limited warranty lasts or do not allow the
exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not
apply to you. This limited warranty gives you specific legal rights, and you may also have other rights which
vary from state to state.
Parts will be provided by our factory organization through an authorized service organization in your area
listed in the yellow pages. If you wish further help or information concerning this limited warranty, contact:
American Standard Inc.
Troup Highway
Tyler, TX 75711-9010
Attention: Manager, After Sales Support
GW-609-4001
* This limited warranty is for residential usage of this equipment and not applicable when this equipment is
used for a commercial application. A commercial use is any application where the end purchaser uses the
product for other than personal, family or household purposes.

Dwg. No. X730377 P02

Page 11

LiMiTED WARRANTY
CENTRAL AiR CONDiTiONER
TCY, TCX, TCC, TCD, TCH, TCK,
TCM, TCP, THC and TSC
Models Less Than 20 Tons for Commercial

Use*

(Parts Only)
This warranty isextended by American Standard Inc., to the original purchaser and to any succeeding
owner ofthe real propertyto which the Air Conditioner is originally affixed, and appliesto products
purchased and retained for use within the U.S.A. and Canada. There isno warranty against corrosion,
erosion ordeterioration.
If any par[ ofyourAir Conditioner fails because of a manufacturing defect within one year from the date of
the original purchase, Warrantor will furnish without charge the required replacement par[.
In addition, if the sealed motor-compressor fails because of a manufacturing defect within the second
through fifth yearfrom the date of original purchase, Warrantor will furnish without charge the required
replacement compressor. Warrantor's obligations and liabilities under thiswarranty are limited to fumishing
F.O.B.Warrantor factory orwarehouse replacement par[s forWarrantor's products covered under this
warranty. Warrantor shall not be obligated to payforthe cost of lost refrigerant. No liability shall attach to
Warrantor until products have been paid for and then liability shall be limited solelyto the purchase price of
the equipment under warranty shown to be defective.
THE WARRANTY
AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER
WARRANTIES
AND LIABILITIES, WHETHER IN CONTRACT OR IN NEGLIGENCE,
EXPRESS OR iMPLiED, iN LAW OR iN FACT, iNCLUDiNG
BUT NOT SPECiFiCALLY
LIMITED TO IMPLIED WARRANTIES
OF MERCHANTABILITY
AND FITNESS FOR
PARTICULAR USE, AND iN NO EVENT SHALL WARRANTOR
BE LIABLE FOR ANY
iNCiDENTAL OR CONSEQUENTIAL
DAMAGES.
Some states do not allow limitations on how long an implied warranty lasts or do not allowthe exclusion or
limitation of incidental or consequential damages, sothe above limitation or exclusion may not applyto you.
Thiswarranty gives you specific legal rights, and you may also have other rights which vary from state to
state.
American Standard Inc.
Troup Highway
Tyler, TX 75711-9010
Attention: Manager, After Sales Suppor[
GW-602-4800
This warranty isforcommercial usage of said equipment and not applicable when the equipment is used
for a residential application. Commercial use is any application where the end purchaser uses the product
for otherthan personal, family or household purposes.

Since American-Standard
has a policy of continuous
product improvement, it reserves the right to change the
specifications and design without notice.

American-Standard
6200 Troup Highway
Tyler,TX 75703

Page 12

Inc.

01: )0s

Technical Literature

- Printed in U.S.A.

Dwg. No. X730377 P02



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 12
Page Layout                     : SinglePage
Page Mode                       : UseNone