TRANE Air Conditioner/heat Pump(outside Unit) Manual L0904669
User Manual: TRANE TRANE Air conditioner/heat pump(outside unit) Manual TRANE Air conditioner/heat pump(outside unit) Owner's Manual, TRANE Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF .
Page Count: 8
Download | |
Open PDF In Browser | View PDF |
18-AC55D1-3 :!l!i i Condensing n 4Trx6 ALL phases of this installation IMPORTANT -- This Document pack upon completion of work. must comply is customer with NATIONAL, property and is to remain These instructions do not cover all variations in systems nor provide for every possible contingency to be met in connection with installation. All phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser's purposes, the matter should be referred to your installing dealer or local distributor. A. GENERAL The following instructions See special wiring and cover 4TrX6 Condensing Units. sequence of operation on page STATE AND LOCAL 5. NOTICE: These outdoor units may be used with indoor units equipped with Thermostatic Expansion Valve only. with this unit. UNIT CONTAINS CODES Please return to service information R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE TO USE PROPER SERVICE TOOLS MAY RESULT IN EQUIPMENT DAMAGE OR PERSONAL INJURY. SERVICE USE ONLY R-410A REFRIGERANT APPROVED POE COMPRESSOR AND OIL. 5 FT. ABOVE UNIT-UNRESTRICTED These units use R-410A refrigerant which operates at 50% to 70% higher pressures than R-22. Use only R-410A approved service equipment. Refrigerant cylinders are painted a "Rose" color to indicate the type of refrigerant and may contain a "dip" tube to allow for charging of liquid refrigerant into the system. All R-410A systems use a POE oil that readily absorbs moisture from the atmosphere. To limit this "hygroscopic" action, the system should remain sealed whenever possible. Never break a vacuum with air and alwayA change the driers when opening the system for component replacement. Check for transportation damage after unit is uncrated. Report promptly, to the carrier, any damage found to the unit. To determine the electrical power requirements of the unit, refer to the nameplate of the unit. The electrical power available must agree with that listed on the nameplate. B. LOCATION & PREPARATION 1. When removing unit from the pallet, the basepan. Remove tabs by cutting shown in Figure 2 (see page 2). OF THE UNIT notice the tabs on with a sharp tool as 2. The unit should be set on a level support pad at least as large as the unit base pan, such as a concrete slab. If this is not the application used please refer to application bulletin "XL16i-APG**-EN" (* latest revision number). 3. The support pad must NOT be in direct contact with any structure. Unit must be positioned a minimum of 12" from any wall or surrounding shrubbery to insure adequate airflow. Clearance must be provided in front of control box (access panels) & any other side requiring service access to meet National Electrical Code. Also, the unit location must be far enough away from any |nsta||er's @ Guide 1. Determine BASEPAN TAB REMOVAL 2. Consider the most practical NOTE: Large diameter tubing has been shaped. TABS AS 4. The top discharge five (5) feet above area must the unit. be unrestricted from unit(s) close 5. When the outdoor unit is mounted on a roof, be sure the roof will support the unit's weight. Properly selected isolation is recommended to prevent sound or vibration transmission to the building structure. 6. The maximum length of refrigerant lines from outdoor indoor unit should NOT exceed eighty (80) feet. to 7. If outdoor unit is mounted above the air handler, maximum lift should not exceed twenty-five (25) feet (suction line). If air handler is mounted above condensing unit, maximum lift should not exceed twenty-five (25) feet (liquid line). NOTE: Refer to "'Refrigerant Piping Software" Pub. No. 32-3312-0", and "'Refrigerant Piping Manual" Pub. No. 32-3009=0* (the position of the * denotes latest revision number). 8. Locate and install indoor coil or air handler in accordance with instruction included with that unit. C. iNSTALLiNG REFRIGERANT If using existing refrigerant are brazed, not soldered. Condensing LINES lines make certain that all joints units have provisions for braze connections. Pressure taps are provided on the service valves unit for compressor suction and liquid pressures. of outdoor The indoor end of the recommended refrigerant line sets may be straight or with a 90 degree bend, depending upon situation requirements. This should be thoroughly checked out before ordering refrigerant line sets. to rebend once it Determine the best starting point for routing the refrigerant tubing -- INSIDE OR OUTSIDE THE STRUCTURE. 4. Provide a pull-thru hole of sufficient liquid and gas lines. 5. Be sure the tubing is of sufficient size to allow both length. -- do not kink or dent. 7. Route the tubing making all required bends and properly secure the tubing before making connections. 8. for at least will be very difficult 3. 6. Uncoil the tubing structure to prevent excess roof run-offwater pouring directly on the unit. Do not locate to bedroom(s). way to run the lines. types of bends to be made and space limitations. To prevent a noise within the building structure due to vibration transmission from the refrigerant lines, the following precautions should be taken: a. When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type hangers. b. Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings. c. Where the refrigerant lines run through they should be insulated and isolated. d. Isolate the lines from all ductwork. D. SERVICE a wall or sill, VALVE OPERATION BRASS LiQUiD LiNE SERVICE VALVE The Brass Liquid Line Service Valve is factory shipped in the seated position to hold factory charge. The pressure tap service port (when depressed) opens only to the field brazing side of the valve when the valve is in the seated position. The liquid line valve is not a back seating valve (see WARNING below). Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn valve stem counterclock= wise only until the stem contacts the rolled edge. (See Figure 3) No torque is required. BRASS GAS LiNE SERVICE VALVE The Brass Gas Line Service Valve is shipped in the closed position to hold the factory refrigerant charge. The pressure tap service port (when depressed) opens only to the field brazing side when the valve is in the closed position. The Gas Line Service Valve is full open with a 1/4 turn. See Figure 4. BRAZING REFRIGERANT LINES 1. Remove lower access cover to access service valves. The gas line must always be insulated. 2. Before brazing, remove plugs from external eopper stub tubes. Clean internal and external surfaces of stub tubes prior to brazing. in scroll compressor applications, dome temperatures may be hot. Do not touch top of compressor, may cause minor to severe burning. 3. Cut and fit tubing, 90 ° bends. The units are factory charged with the system charge required -when using fifteen (15) feet of connecting line. Unit nameplate charge is the same. 5. Do NOT allow uninsulated contact with bare gas line. Final refrigerant charge adjustment is necessary. the Charging Charts in the outdoor unit Service Facts. © American Standard inc. 2005 Use 4. Insulate minimizing the use of sharp the entire gas line and its fittings. 6. Precautions should to the pressure tap liquid line to come in direct be taken to avoid valve core during heat damage brazing. It is 18-AC55D1-3 |nstaI|er's ® 5. Close offvalve to vacuum pump and observe the micron gauge. If gange pressure rises above 500 microns in one (1) minuS, then evacuation is incomple_ or sys_m has a leak. LiQUiD LiNE SERVICE VALVE ROLLED Guide EDGE TO 6. If vacuum gauge does not rise above 500 microns in one (1) minute, the evacuation should be complete. CAP's,'-- @ / UNIT SIDE OF CAPTIVATE _ STEM 7. With vacuum pump and micron gauge blanked of[; open valve on R-410A cylinder and charge refrigerant lines and indoor coil with vapor to tank pressure of R-410A supply. HEX HEADED SERVICE_VALVE NOTE: DO NOT VENT REFRIGERANT SYSTEM SERVICE PORT 8. Close valve on R-410A supply cylinder. Close valves on manifold gauge set and remove refrigerant charging hoses from liquid and gas pressure tap ports. / LIQUID LINE CONNECTION NOTE: A 3/16" Allen wrench is required to open liquid line service valve. A I/4" Open End or Adjustable wrench is required to open gas line valve. A 3/4" Open End wrench is required to take off the valve stem cap. recommended that the pressure tap port valve core be removed and a wet rag wrapped around the valve body. NOTICE: Use care to make sure that no moisture port, while wet rag is being used. enters pressure tap NOTICE: Precautions should be taken to avoid heat damage to basepan during brazing. It is recommended to keep the flame directly off of the basepan. 7. Use a Dry Nitrogen Purge and Brazing Alloy without flux when brazing the field line to the copper factory connection. Flow dry nitrogen into either valve pressure tap port, thru the tubing and out the other port while brazing. 8. Braze using accepted good brazing techniques. LEAK CHECK IMPORTANT: Replace pressure tap port valve core before attaching hoses for evacuation. Alter the brazing operation of refrigerant lines to both the outdoor and indoor unit is completed, the field brazed connections must be checked for leaks. Pressurize through the service valve ports, the indoor unit and field refrigerant lines with dry nitrogen to 300 psi. Use soap bubbles or other leak-checking methods to see that all field joints are leakfree! If not, release pressure; then repair! SYSTEM EVACUATION NOTE: Since the outdoor unit has a refrigerant liquid line valves must remain closed. INTO THE ATMOSPHERE. 9. The liquid line shut-offvalve can now be opened. Remove shut-off valve cap. Fully insert hex wrench into the stem and back out counterclockwise until valve stem just touches rolled edge (approximately five [5] turns) observing WARNING statement on page 3. See Figure 3. 10. Replace liquid service pressure tap port cap and valve stem cap. These caps MUST BE REPLACED to prevent leaks. Replace valve stem cap and pressure tap cap finger tight, then tighten an additional 1/6 turn. 11. The gas valve can now be opened. Open the gas valve by removing the shut-offvalve cap and turning the valve stem 1/4 turn counterclockwise, using 1/4" Open End or Adjustable wrench. See Figure 4. 12. The gas valve is now open for refrigerant flow. Replace valve stein cap to prevent leaks. Again, these caps MUST BE REPLACED to prevent leaks. Replace valve stem cap and pressure tap cap finger tight, then tighten an additional 1/6 turn. See Figure 4. If refrigerant lines are longer than 15 fhet and/or a difihrent size than recommended, it will be necessary © GAS LiNE SERVICE VALVE CAP _ _--_ UNIT SIDE OF VALVE # PRESSURE 2. Attach appropriate hoses from manifold and liquid line pressure taps. center hose of manifold 18-AC55D1-3 gauges gauge reads TAP PORT gauge to gas NOTE: Unnecessary switching of hoses can be avoided and complete evacuation of all lines leading to sealed system can be accomplished with manifold center hose and connecting branch hose to a cylinder of R-410A and vacuum pump. 4. Evacuate until the micron 350 microns. 114 TURN ONLY COUNTERCLOCKWISE charge, the gas and 1. Upon completion of leak check, evacuate the refrigerant lines and indoor coil before opening the gas and liquid line valves. 3. Attach to to vacuum no higher / / GAS LINE CONNECTION CAP _ S pump. than CORE 3 |nsta||er's Guide adjust system refrigerant charge upon installation. See unit Service Facts. E. ELECTRICAL completion F. COMPRESSOR of CONNECTIONS When installing or servicing this equipment, ALWAYS exercise basic safety precautions to avoid the possibility of electric shock. 1. Power -wiring and grounding with local codes. of equipment 2. Power supply must agree with equipment 3. Install a separate disconnect must G. OPERATIONAL PROCEDURES comply unit. 4. Ground the outdoor unit per local code requirements. 5. Provide flexible electrical conduit whenever vibration transmission may create a noise problem within the structure. H. ELECTRIC HEATERS Electric heaters, if used, are to be installed in the air handling device according to the instructions accompanying the air handler and the heaters. 6. The use of color coded low voltage wire is recommended to simplify connections between the outdoor unit, the thermostat and the indoor unit. Table 1 -- NEC Class I! Control AND CHECKOUT Final phases of this installation are the unit Operational and Checkout Procedures which are found in this instruction (see page 8). To obtain proper performance, all units must be operated and charge adjustments made in accordance with procedures found in the Service Facts. nameplate. switch at the outdoor START UP After all electrical wiring is complete, SET THE THERMOSTAT SYSTEM SWITCH IN THE OFF POSITION SO COMPRESSOR WILL NOT RUN, and apply power by closing the system main disconnect switch. This will activate the compressor sump heat (where used). Do not change the Thermostat System Switch until power has been applied for one (1) hour. Following this procedure -will prevent potential compressor overload trip at the initial start-up. I. START CONTROL Wiring Some models have quick start components which are factory installed. For models that do not have factory installed start components, provisions are made for a field installed start kit accessory. When adding an accessory, follow the instructions provided with the kit. 24 VOLTS WIRE SIZE MAX. WIRE LENGTH 18 AWG 150 FT 16 AWG 225 FT. 14 AWG 300 FT. J. OUTDOOR THERMOSTAT An outdoor thermostat TAYSTAT250A may be field installed. For data, see wiring diagram attached to unit and instruction sheet packaged with outdoor thermostat. 7. Table i defines maximum total length of low voltage wiring from outdoor unit, to indoor unit, and to thermostat. K. XL SEACOAST SHIELD All units are shipped with a black Seacoast Shield. Removal of the shield will potentially shorten the life of the joints in the outdoor coil. 8. Mount the indoor thermostat in accordance with instruction included with the thermostat. Wire per appropriate hook-up diagram (included in these instructions). L. TROUBLESHOOTING TROUBLESHOOTING CHART -- WHAT TO CHECK SYSTEM FAULTS REFRIGERANT CIRCUIT LiquidPressure TooHigh i i i LiquidPressure TooLow i i i SP Suction Pressure TooHigh i i i S Suctioo Pressure TooLow i i i LiquidRefdg. FIoodback TXVSystem i i i LiquidRefdg. FIoodback Capillary TubeSystem i i i I.D,CoilFrssthg i i i Compressor RuneInadequate orNoCooling i i i PPSPS SS SS P P SS S P s sPs SS P SS SP PS p SP PS SPS ELECTRICAL Cornpreeeor & O.D.FanDoNotStart Compressor WillNotStartButO.D.FanRuns O.D.FanWon'tStart Compressor HumsButWon'tStart Compressor CyclesonIOL I.D.BlowerWon'tStart P- PrimaryCauses S-SecondaryCauses 4 18-AC5 5D 1-3 |nsta||er's FIELD HOOK=UP DIAGRAMS VARIABLE SPEED AIR HANDLER T'STAT 2 STAGE IR CONDITIONER FOR 4TTX6 MODELS ONLY VARIABLE SPEED 2 STAGE FURNACE T 'STAT Guide AI 2 STAGE CONDITIONER See __ See "Note A NoteA E23 PRINTED FROM DI54017P02 Notes: 1, Be sure power supply agrees with equipment nameplate, 2, Power wiring and grounding of equipment must comply with local codes, 3, Low voltage wiring to be No, 18 AWG minimum conductor, PRINTED FROMDI54018P02 4, If outdoor thermostat (ODT) is not used, connect W2 to W3, 5, Be sure the jumper between "R" and "BK" is cut or removed (See Note B below), 6, With "O" and "Y/Y2" energized, indoor fan is at 80% airflow, 7, With "O", "Y/Y2" and "BK" energized, (_ G ÷ indoor fan is at 100% airflow, AiR HANDLER 0 R B FACTORY WIRING LEGEND-- (_ Y YIo FIELD WIRING I FURNACE The Factory installed jumper between "R" and "BK" on the Furnace circuit board must be cut. See Note B. W3 W2 Wl T BK ..... ÷ "_'_Jumper See Note B REQUIRED WIRING Refer to Field Hook-up Diagrams above. 4TTX6 units require 80% airflow with "YI" (first stage), 100% airflow with "Y2" (second stage). Note A - The installer must jumper at the LVq-B "R" to "O". Note B - Cut/remove the factory installed "BK" jumper (See Figures 1 & 2) Connect "Y1" from thermostat to "Y/Y2" at VS Air Handler/VS Furnace to "Y1" at Outdoor Unit. Connect "Y2" from thermostat to "BK" at VS Air Handler/VS Furnace to "Y2" at Outdoor Unit. 18-AC55D1-3 5 |nsta||er's Guide 4TTX6 OUTLINE DRAWING NOTE: ALL DIMENSIONS ARE iN IVllVl(iNCHES). SERVICE PANEL FLECTRICAL AND REFRIGERA T COMPONENTCI AAANC:S PER PRE:VAI NG COD_S r t UNIT SHOULD BE PLACED SO ROOF RUNwOFF WATER DOES NOT POUR DIREC/{Y ON UNIF, AN()SROUID BE AT LEAST 505 (12") FROM WALL AND ALL SURROUNDING SItRUBBERY ON TWOSIDES OTHER]WO SIDES UNRES1RICT(D I -- E ECTR CAL PANEL BRAZE CONNECTION WITH I/4" SAE FIARE PRESSURE TAP fITtINGS , _ I!4 h_ .... ", I 0 FOR ALTERNATE EIECTR}CAL ROU11NG G L J MODELS BASE A 4TTX6024B 3 1118 (44) 4TTX6036B 4 4TTX6048B 4TTX6060B B -._" p; GAS 1IN{ }/4 tURN BALL S_RVI_ VALVE, "D" ID FEMALE BRAZED CONNECT!ON WITH I/4" SAE FLARE PRESSURE TAP FITTING C D E F G H J K 829 (32-5/8) 756 (29-3/4) 5/8 5/16 143 (5-5/8) 92 (3-5/8) 210 (8-1/4) 79 (3-1/8) 692 (27-1/4) 1064 (41-7/8) 946 (37-1/4) 870 (34-1/4) 3/4 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 730 (28-3/4) 4 1267 (49-7/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 730 (28-3/4) 4 1267 (49-7/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 730 (28-3/4) From Dwg. D152635 6 Rev. 11 18-AC5 5D 1-3 Installer's MOUNTING Guide HOLE LOCATION NOTE: ALL DIMENSIONS ARE IN MM (INCHES). 794 i _ ,',11 56) _ Iil 6 '4) ....................................... 48,2 ( S 99) ................................... "--J 599 2358 BASE 3 NOTE: For model base size, see table on page 6. 18-AC55D1-3 -- BASE 4 :i i c, From Dwg. D152637 Rev. 1 7 |nsta||er's Guide CHECKOUTPROCEDURE After installation 1. Refrigerant 2. Suction has been completed, Line, Leak checked Lines and Fittings it is recommended that the entire system .................................. properly insulated ........... [ ] [ ] 3. Have all Refrigerant Lines been secured and isolated properly? ........................................................ [ 4. Have passages through masonry been sealed? If mortar is used, prevent mortar from coining into direct contact with copper tubing ........................ [ ] 5. Verify tightness [ ] of all electrical connects ................... 6. Observe outdoor fan during on cycle for clearance and smooth operation .................................................. [ 7. Indoor coil drain line drains freely. Pour water into drain pan .............................................................. [ CHECKOUT PROCEDURE be checked against [ ] 9. Return [ ] 10. Thermostat thermometer is accurate. Check against a reliable thermometer. Adjust per instructions with thermostat ...................................... [ ] 11. Is correct speed tap being used? (Indoor blower motor) .................................................. [ ] 12. Operate complete system in each mode to insure safe operation ................................................... [ ] air filter installed 1 TO CHECK @ Cool Off @ Heat 2 IndoorFan Operation 3 CoolingOperation 4 CheckingPerformance & Charge CLOSED (ON) COMPONENTOPERATION Fan Switch Auto On X Sump Heat ............................................ WiTH MAiN P( )WER DISCONNECTS INDOORTHERMOSTAT SWITCHSETTING Step No. the following list: 8. Supply registers and return grilles open and unobstructed ................................................................ indoor Blower Runs Outdoor Fan Runs Compressor Runs @ Comp. Sump Heater X x Ix I X x Ix Ixlxl Furnace Heat Comes On X X X X I X I X X USEOHAFITSATTACHEDTO O.D. UNIT Ix ! ! 5 Heating@ 6 Informowner on howto operatesystem andwhat to expectof it. At the sametime deliverOwner'sUseand Care Booklet. X Ix Ix Ii @ Alsosetthermostatdial to callfor coolingor heatingasnecessary. @ Checkonlynecessaryif heatingunit is used for indoorsectionandwiringhas beendisturbedduringinstallationof coolingequipment. @ When applicable. lr 4N£ P.I. Trane A business of American Standard Companies wi4pw.trane.com Trane has a policy of continuous product and product data improvement design and specifications without notice. and it reserves the right to change 1/O5
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 8 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Wed May 13 04:13:04 2009 Author : Title : Subject :EXIF Metadata provided by EXIF.tools