TRANE Package Units(both Units Combined) Manual L0905326

User Manual: TRANE TRANE Package Units(both units combined) Manual TRANE Package Units(both units combined) Owner's Manual, TRANE Package Units(both units combined) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 8

DownloadTRANE  Package Units(both Units Combined) Manual L0905326
Open PDF In BrowserView PDF
YC-UM-2B
32-5033-03

TI
FO
UAL
For service and owner's

Library

Service Literature

Product Section

Unitary

Product
Model

Packaged Gas/Electric
YC*

Literature Type

User's Manual

Sequence
Date

use

November

File No.

SV-UN-RT-YC-UM-2B

2B
2001
11/01

Model:

YC*024 F/G 1
YC*030 F/G 1
YC*036F/G 1,3,4

IM PORTANT--This
work.

WARNING:

YC*042 F/G 1,3
YC*048F/G 1,3,4
YC*060F/G 1,3,4

Combination Cooling/
Gas Heating Package
Unit

Document is customer propertyand is to remain with this unit. Please return to service information pack upon completion of

Iftheinformation

in this manual

is not followed
exactly, a fire or explosion
may result causing
property damage, personal injury or loss of life.
Do not store or use gasoline
or other
flammable
vapors and liquids in the vicinity of this or any other appliance
m

WHAT TO DO IF YOU SMELL

GAS

• Do not try to light any appliance.
• Do not touch any electrical switch;
do not use any phone in your building.
,, Immediately
call your gas supplier
from a neighbor's phone. Follow the
gas supplier's
instructions.
,, If you cannot reach your gas supplier, call the fire department.

Installation and service must be performed by a qualified installer, service
agency or the gas supplier.

WARNING:

Do NOT USE THIS UNIT IF
ANY PART HAS BEEN UNDER WATER. IMMEDIATELY
CALL A QUALIFIED
SERVICE
TECHNICIAN
TO
INSPECT THE FURNACE AND TO REPLACE ANY
PART OF THE CONTROL SYSTEM AND ANY GAS
CONTROL WHICH HAS BEEN UNDER WATER.

© 2001 American Standard Inc. All rights reserved

WARNING:

SHOULD
OVERHEATING

OCCUR, OR THE GAS SUPPLY FAIL TO SHUT OFF,
SHUT OFF THE GAS VALVE TO THE UNIT BEFORE
SHUTTING OFF THE ELECTRICAL SUPPLY.

The following

warning

complies

with State of California

WARNING:

law, Proposition

65.

Hazardous Gasses!

Exposure to fuel substances or by-products of incomplete
fuel combustion is believed by the state of California to
cause cancer, birth defects, or other reproductive harm.

The following

warning

complies

with State of California

,WARNING:

law, Proposition

65.

This product contains

fiberglass wool insulation! Fiberglass dust and ceramic
fibers are believed by the State of California to cause
cancer through inhalation. Glasswool fibers may also
cause respiratory, skin, or eye irritation.

GENERAL iNFORMATiON
OVERVIEW
Your combination gas heating / electric cooling unit is designed to comfort condition all year long with safe, efficient,
trouble-free operation. It is important that you understand
how to operate and maintain your unit to keep it operating
safely and efficiently. This manual will acquaint you with these
important procedures. Familiarize yourself with this manual
and store it in a convenient location for future reference.
Any additions, changes, or conversions required in order for
the unit to satisfactorily meet the application needs, should be
made by a qualified product distributor or local service dealer,
using factory specified and approved parts. See figure 1 for
component layout.
Remember these instructions at all times:
•

Never perform any maintenance procedures
electrical power to the unit is turned off.

until the

•

Never perform any maintenance procedures until the gas
valve in gas supply line is turned off.

•

Never remove any panel from the unit while it is operating.

•

Never remove panels or parts from the unit that are not
discussed in this manual.

•

Never cover the unit since it is designed to operate year
round.

Your unit is of complex design. To ensure that it performs
safely and give long-lasting service, some of the maintenance
work must be performed by a qualified serviceman.
When a serviceman is referred to in this manual, it is describing a service technician that has had special training or a
number of years experience in servicing this type of
equipment. It is your responsibility to select a qualified
service company that can provide a serviceman of this caliber.

THERMOSTAT
Room thermostats are delicate temperature-sensing controls.
Their main function is to energize and de-energize the heating
or cooling circuit to maintain the temperature setting you
select.
Many thermostats contain a room thermometer to indicate the
approximate room temperature, and a temperature scale at
the adjustment indicator to select the desired indoor air
temperature. In addition, most thermostats have a selector
mode switch with Heat, Off and Cool positions, and a fan
switch with On and Auto positions.
When the selector switch is positioned at Off your unit will not
operate in either heat or cool modes. If the selector switch is
set at heat, the unit will automatically cycle on and off to
maintain the desired temperature settings. The unit will also
operate automatically when the selector switch is positioned
at Cool.

HEAT

EXCHANGER

COIL

DRAIr

OUTDOOR
COIL

BLOWER

UNIT

CONTROL

BOX

FLUE

BOX

FURNACE
COM BUSTION
FAN BLOWER

GAS

VALVE

PRESSURE
SWITCH

GENERAL INFORMATION
The fan selector switch can be used to operate the indoor fan
continuously by positioning it at On. When set at Auto, the fan
will only operate when required during the heating or cooling
cycles.
To ensure that the thermostat operates properly, it must be
level and positioned to avoid the influence of such external
heat sources as lamps, televisions or other heat-producing
appliances.

AiR FILTERS
Filters are to be used with the YC*024-060F heating/cooling
units. The basic unit does not have filters in it. However, a filter
accessory is offered that will allow filters to be installed in the
unit. Otherwise a filter rack must be installed by the installer in
the duct work. Affix filter label supplied with the unit adjacent to
the filter area.

TABLE 1 -= FILTER DATA
NOMINAL
CFM

UNIT

FILTER*
Sq.Ft.=SlZE

FILTER
RESISTANCE

YC~024F/G

800

2.67

0.05

YC~030F/G

1000

3.33

0.05

YC~036F/G

1200

4

0.05

YC~042F/G

1400

4.67

0.05

YC~048F/G

1600

5.33

0.05

YC~060F/G

2000

6.67

0.05

Fliers must be installed in the return air system.
* Based on 300 FPM face velocity.
** If permanent filters are used, be sure to size following the manufacturer's
recommendations with a clean filter resistance of 0.05 inches of water
column.

HEATING SYSTEM
HEATING

CYCLE

OPERATION

Your unit's heating system has a solid-state electronic ignition
control that lights the furnace burners each time the thermostat
calls for heat. At the end of each heating cycle, the furnace
burners are extinguished. This type of system is called Direct
Spark Ignition (DSI).
A normal heating cycle begins when the air temperature in your
home drops below the thermostat setting. The thermostat than
energizes the heating electrical circuit that starts and controls
the furnace burners. Shortly after the burner ignite, the indoor
fan starts and circulates warm air through your home.
When the air temperature rises to the thermostat setting, the
thermostat de-energizes the heating electrical circuit, which in
turn, extinguishes the furnace burners. The indoor fan continues to circulate warm air until most of the heat is removed from
the unit's combustion chamber.

SAFETY

1. Set the thermostat's heating adjustment lever at its lowest
setting; then move the selector switch to the Off position.
2. Turn off all electric power to the unit.
3. This unit is equipped with an ignition device which automatically lights the burners.
CAUTION:
burner.

If flames from the burner are not properly drawn into the heat
exchanger, a Flame Rollout Protection Control will open causing the furnace to shut off. The cause must be investigated by
a qualified serviceman.

SYSTEM

START-UP

Since your unit has an automatic ignition system, it is easy to
start the heating cycle at the beginning of the heating season.
In order for this unit to operate properly and safely, the furnace
needs air for both combustion and ventilation. Accordingly,
observe the area in which the furnace is installed. Check to
make sure that all the air openings are unobstructed.

Never attempt

to manually

light the

4. Remove the access panel that contains the following label:

REMOVE
THiS
PANEL
GAiN j
ACCESS TO
THE
GAS TO
VALVE
5. Turn gas control "OFF" either by turning the knob

CONTROLS

Your unit is equipped with an automatic reset safety limit
control to prevent overheating. When this control opens, it
shuts down the heating electrical circuit until the unit cools
down sufficiently. Inadequate airflow (i.e. caused by dirty air
filters or defective fan motor), may cause the unit to cycle on
and off as the limit control trips and automatically resets. If you
suspect that the unit is cycling on its limit control, immediately
contact a serviceman for instructions.

HEATING

Likewise, insure that the spacing around the furnace it self is
not blocked or obstructed.

clockwise O to the "OFF" position or by moving the
toggle switch to "OFF". See Figure 2.
NOTE: Some valves require the knob to be pushed in slightly
before turning.
DO NOT FORCE!
.

Wait (5) five minutes to clear any gas. If you then smell
gas, STOP! Follow "For Your Safety',' "What To Do If You
Smell Gas" instructions on the front page. If you do not
smell gas, go to next step.

7. Turn gas "ON" eitherbyturnningthe
knob counterclockwise _*')to "ON position or by moving the toggle switch to
"ON".
8. Replace panel remove in Step 4.
9. Turn on all electrical power to the unit.
10. Set thermostat to desired temperature and move the selector switch to the "ON" position. The unit will now operate
automatically.

HEATING SYSTEM
11. If the unit will not operate, followthe instructions "TO TURN
OFF GAS TO UNIT" (under HEATING SYSTEM SHUTDOWN) and call your service technician or gas supplier.
Important Note: The unit is to be adjusted to obtain an air rise
that is specified on the nameplate.

HEATING

SYSTEM

SHUTDOWN

To shut down the heating system for brief periods of time,
simply adjust the thermostat selector switch to the "OFF"
position.

! REMOVE THIS PANEL TO GAiN I
ACCESS TO THE GAS VALVE
4. Turn gas control "OFF" either byturning the knob clockwise
Fto the "OFF" position or by moving the toggle switch to
F". See Figure 2.
NOTE: Some valves require the knob to be pushed in slightly
before turning.
DO NOT FORCE!

If you need to turn the gas off to the unit, follow the steps below:

5. Replace panel removed in Step 3 above.

TO TURN OFF GAS TO UNIT

CAUTION: If this is done during the cold weather months,
provisions must be taken to prevent freeze-up of all water
pipes and water receptacles. Whenever your home or building is to be vacant, arrange to have someone inspect your
structure for proper temperature. This is very important in
below freezing weather, if for any reason your furnace should
failto operate, damage such as frozen water pipes could result.

1. Set the thermostat to lowest setting.
2. Turn off all electric power to the unit. If service is to be
performed.
3. Remove the access panel that contains the following label:

COOLING
COOLING SYSTEM
OPERATION

START-UP

AND

Once electrical power is supplied to the unit, cooling operation
is controlled by the thermostat. With the thermostat selector
switch set at COOL, move the cooling adjustment lever to its
lowest setting to energizethe unit cooling system. Nowthat the
unit is operating, cool air will begin to circulate through your
building. Finally, reposition the cooling adjustment lever to the
desired room temperature; your unit will continue to operate in
the cooling mode automatically.

SYSTEM
COOLING

SYSTEM

SHUTDOWN

If you wish to shut down the cooling system, the best method
is to move the thermostat selector switch to the OFF position.
To shut down the unit completely, turn off the main electrical
power supply to the unit.
Anytime you think the cooling system is not operating properly,
shut down unit operation at the thermostat and contact a
serviceman for instructions.

ROUTINE MAINTENANCE
You can do some of the periodic maintenance functions for the
unit yourself; this includes replacing (disposable) or cleaning
(permanent) the air filters, cleaning the cabinet, cleaning the
condenser coil, and conducting a general unit inspection on a
regular basis.

WARNING:

BEFORE
REMOVING
UNIT
I

ACCESS PANELS TO SERVICE UNIT, OPEN UNIT I
DISCONNECT
SWITCH TO PREVENT INJURY OR I
DEATH DUE TO ELECTRICAL SHOCK OR CONTACT I
WITH MOVING PARTS.
I

AIR FILTERS
it is very important to keep the central duct system air filters
clean. Be sure to inspect them at least once each month when
the system is in constant operation. (In new homes, check the
filters at least ever week for the first 4 weeks.)
If you have disposable-type filters replace them with new filter
of the same type and size. DO NOT ATTEMPT TO CLEAN
DISPOSABLE FILTERS.

Permanent-type filters can be cleaned by washing them with a
mild detergent and water. Make sure that the filters are thoroughly dry before reinstalling them in the unit. (or duct system).
NOTE: Itmay be necessaryto replace permanent filter annually
if washing fails to clean the filter, or if the filter shows signs of
deterioration. Be sure to use the same type and size as was
originally installed.

UNIT CABINET
Even though the unit cabinet is designed to withstand exposure
to outdoor weather, you can extend the life of the cabinet panel
by cleaning and waxing then twice each year. Application of a
light coat of automobile wax is recommended.

CONDENSER

COIL

Unfiltered air circulates through the units condenser coil and
can cause the coil's surface to become clogged with dust, dirt,
etc. To clean the coil, vertically (i.e., with the fins) stroke the coil
surface with a soft-bristled brush.

Besureto keepallvegetation
awayfromthecondenser
coil
area.
GENERAL

UNIT INSPECTION

Occasionally check over the unit; look and listen for unusual or
abnormal operating characteristics. Do not remove any access
panels. If you suspect your unit is not operating properly,
contact a serviceman for instructions.

MAINTENANCE
COOLING

PERFORMED

SEASON

the ignition control and spark electrode are operating.

To keep your unit operating safely and efficiently, The Company recommends that a qualified serviceman check over the
entire system at least once a year, and any other time that you
feel one is needed. Your serviceman may examine these areas
of the unit:
1. filters (for possible cleaning)
2. motors (condenser and evaporator motors are permanently lubricated)

b. Turn off the gas supply with the unit operating to verify
that the gas valve closes, and that a re-ignition cycle is
initiated by the ignition control.
.

coils (for possible cleaning)

5. safety controls

.

7. condensate

.

(for mechanical cleaning)

6. electrical components and wiring (for possible replacement and connection tightness)

.

drain (for possible cleaning)

8. inspect the unit duct connections to see that they are
physically sound and sealed to the unit casing.

.

9. inspect the unit mounting support to see that it is sound.
10. inspect the unit to see that there is no obvious unit
deterioration.

,WARNING:

TO PREVENT INJURY OR DEATH

DUE TO ELECTRICAL SHOCK OR CONTACT WITH MOVING
PARTS, LOCK UNIT DISCONNECT SWITCH IN OPEN
POSITION BEFORE SERVICING UNIT.

WARNING:

TO PREVENT AN EXPLOSION I

OR POSSIBLE INJURY, DEATH AND EQUIPMENT DAMAGE,I
DO NOT STORE COMBUSTIBLE MATERIALS, GASOLINE I
OR OTHER FLAMMABLE VAPORS OR LIQUIDS NEAR THE
UNIT.

HEATING

SEASON

Complete the unit inspections and service routines described
below at the beginning of each heating season.
These steps should ONLY be performed by qualified service
technicians.
1. Inspect the control panel wiring and heating controls to make
sure connections are tight and wiring insulation is intact.
a. Turn the unit on and off at the thermostat to be sure

Check the operation of the gas ignition system.

3. Check the burner manifold pressure. An 1/8-inch pipe plug
is provided in the gas valve for this purpose.

3. gaskets (for possible replacement)
4. refrigerant

BY SERVICEMAN

.

Inspect the control panel wiring to verify that all electrical
connections are tight, and that wire insulation is intact.
Visually inspect all of the unit's flue product passageways for
excessive deposit buildup and corrosion. If buildup or corrosion is apparent, perform the necessary repairs.
Arrange for a qualified serviceman to inspect the unit ever
other heating season to maintain safe and efficient operation.
Visually check the main burner flames. They should be
bright blue flames extending up to the heat exchanger
sections. (See Figure 2.)
Never store anything flammable or combustible around or
near the unit.

@

LiMiTED WARRANTY
COMBINATION

GAS ELECTRIC

AiR CONDiTiONER

YCC, YCD, YCH, YCP, YHC and YSC
Models Less Than 20 Tons for Residential Use*
(Parts Only)
This limited warranty is extended by American Standard Inc., to the original purchaser and to any succeeding
owner of the real property to which the Combination Gas Electric Air Conditioner is originally affixed, and
applies to products purchased and retained for use within the U.S.A. and Canada.
f any part of your Combination Gas Electric Air Conditioner fails because of a manufacturing defect within five
rears from the date of the original purchase, Warrantor will furnish without charge the required replacement
)art. Any local transportation, related service labor, diagnosis calls, air filters, refrigerant and related items are
qot included.
If the sealed motor-compressor fails because of a manufacturing defect within five years from the date of
original purchase, Warrantor will fumish without charge the required replacement compressor. Any local
transportation, related service labor, diagnosis calls, refrigerant and related items are not included.
In addition, if the steel heat exchanger fails because of a manufacturing defect within the sixth through tenth
year from the date of original purchase, Warrantor will fumish without charge a replacement heat exchanger.
Any local transportation, related service labor and diagnosis calls are not included.
This limited warranty does not cover failure of your combination gas electric air conditioner if it is damaged
while in your possession, failure attributable or caused by unreasonable use of the combination gas electric
air conditioner andlor failure to properly maintain the combination gas electric air conditioner as set forth in the
Use and Care manual.
This limited warranty applies to product installedon or after 10/1/'2001 where product is manufactured after
1/1/'2000. This limited warranty is not retroactive to any installations prior to 10/1/'2001 or on product produced
3rior to 2000.
'['HE LiMiTED WARRANTY
AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER
WARRANTIES
AND LiABiLiTiES, WHETHER iN CONTRACT OR iN NEGLIGENCE,
EXPRESS
OR iMPLiED, IN LAW OR iN FACT, iNCLUDING IMPLIED WARRANTIES
OF
MERCHANTABiLiTY
AND FITNESS FOR PARTICULAR
USE, AND iN NO EVENT SHALL
WARRANTOR
BE LIABLE FOR ANY iNCiDENTAL OR CONSEQUENTIAL
DAMAGES.
Some states do not allow limitations on how long an implied limited warranty lasts or do not allow the
exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not
apply to you. This limited warranty gives you specific legal rights, and you may also have other rights which
vary from state to state.
Parts will be provided by our factory organization through an authorized service organization in your area
listed in the yellow pages. If you wish further help or information concerning this limited warranty, contact:
American Standard Inc.
Troup Highway
Tyler, TX 75711-9010
Attention: Manager, After Sales Support
GW-618-4001
* This limited warranty is for residential usage of this equipment and not applicable when this equipment is
used for a commercial application. A commercial use is any application where the end purchaser uses the
3roduct for other than personal, family or household purposes.

LiMiTED WARRANTY
COMBiNATiON

GAS ELECTRIC AiR CONDiTiONER
YCZ, YCY AND YCX
Models Less Than 20 Tons for Residential Use*
(Parts Only)

This limited warranty is extended byAmerican Standard Inc., to the original purchaser and to any succeeding owner of the real

property to which the Combination Gas Electric Air Conditioner is originally affixed, and applies to products
purchased and retained for use within the U.S.A. and Canada.
If any part of your Combination Gas Electric Air Conditioner fails because of a manufacturing defect within five
years from the date of the original purchase, Warrantor will furnish without charge the required replacement
part. Any local transportation, related service labor, diagnosis calls, air filters, refrigerant and related items are
not included.
In addition, ifthe sealed motor-compressor(s) fail(s) or the outdoor coilt should become defective, either or
both events occurring because of a manufacturing defect within the sixth through tenth year from the date of
original purchase, Warrantor will furnish without charge the required replacement compressor and/or outdoor
coil. Any local transportation, related service labor, diagnosis calls, refrigerant and related items are not
included.
tNOTE: If your Combination Gas Electric Air Conditioner is installed within one mile of salt water, including but
not limited to seacoasts and inland waterways, your outdoor coil warranty as stated above is limited to five
years from the date of original purchase.
In addition, ifthe steel heat exchanger fails because of a manufacturing defect within the sixth through
twentieth year
from the date of original purchase, Warrantor will furnish without charge a replacement heat exchanger. Any
local transportation, related service labor and diagnosis calls are not included.
This limited warranty does not cover failure of your combination gas electric air conditioner if it is damaged
while in your possession, failure attributable or caused by unreasonable use of the combination gas electric
air conditioner and/or failure to properly maintain the combination gas electric air conditioner as set forth in the
Use and Care manual.
This limited warranty applies to product installed on or after 10/1/2001 where product is manufactured after
1/1/2000. This limited warranty is not retroactive to any installations prior to 10/1/2001 or on product produced
prior to 2000.
THE LIMITED WARRANTY
AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL
OTHER WARRANTIES
AND LiABiLiTIES, WHETHER IN CONTRACT OR iN NEGLIGENCE,
EXPRESS OR iMPLiED, iN LAW OR iN FACT, INCLUDING IMPLIED WARRANTIES
OF
MERCHANTABiLiTY
AND FITNESS FOR PARTICULAR
USE, AND iN NO EVENT SHALL
WARRANTOR
BE LIABLE FOR ANY iNCiDENTAL OR CONSEQUENTIAL
DAMAGES.
Some states do not allow limitations on how long an implied limited warranty lasts or do not allow the
exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not
apply to you. This limited warranty gives you specific legal rights, and you may also have other rights which
vary from state to state.
Parts will be provided by our factory organization through an authorized service organization in your area
listed in the yellow pages. Ifyou wish further help or information concerning this limited warranty, contact:
American Standard Inc.
Trou p Highway
Tyler, TX 75711-9010
Attention: Manager, After Sales Support
GW-617-4001
* This limited warranty is for residential usage of this equipment and not applicable when this equipment is
used for a commercial application. A commercial use is any application where the end purchaser uses the
product for other than personal, family or household purposes.

LiMiTED WARRANTY
COMBiNATiON
GAS ELECTRIC AiR CONDiTiONER
YCZ, YCY, YCX, YCC, YCD, YCH, YCP, YHC and YSC
Models Less Than 20 Tons for Commercial Use*
(Parts Only)
This warranty is extended by American Standard Inc., to the original purchaser and to any succeeding owner
of the real property to which the Combination Gas Electric Air Conditioner is originally affixed, and applies to
products purchased and retained for use within the U.S.A. and Canada. There is no warranty against
corrosion, erosion or deterioration.
If any part of your Combination Gas Electric Air Conditioner fails because of a manufacturing defect within one
year from the date of the original purchase, Warrantor will furnish without charge the required replacement
part.
In addition, ifthe sealed motor-compressor fails because of a manufacturing defect within the second through
fifth year from the date of original purchase, Warrantor will fumish without charge the required replacement
compressor.
In addition, ifthe steel heat exchanger fails because of a manufacturing defect within the second through fifth
year from the date of original purchase, Warrantor will furnish without charge a replacement heat exchanger.
Warrantor's obligations and liabilities under this warranty are limited to furnishing F.O.B. Warrantor factory or
warehouse at Warrantor designated shipping point, freight allowed to Buyer's city, replacement parts for
Warrantor's products covered under this warranty. Warrantor shall not be obligated to pay for the cost of lost
refrigerant. No liability shall attach to Warrantor until products have been paid for and then liability shall be
limited solely to the purchase price of the equipment under warranty shown to be defective.
THE WARRANTY AND LiABILiTY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER
WARRANTIES
AND LiABiLiTiES, WHETHER iN CONTRACT OR iN NEGLIGENCE,
EXPRESS
OR iMPLiED, iN LAW OR IN FACT, iNCLUDiNG iMPLiED WARRANTIES
OF
MERCHANTABiLiTY
AND FITNESS FOR PARTICULAR
USE, AND iN NO EVENT SHALL
WARRANTOR
BE LIABLE FOR ANY iNCiDENTAL OR CONSEQUENTIAL
DAMAGES.
Some states do not allow limitations on how long an implied warranty lasts or do not allow the exclusion or
limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
American Standard Inc.
Trou p Highway
Tyler, TX 75711-9010
Attention: Manager, After Sales Support
GW-606-4800
* This warranty is for commercial usage of said equipment and not applicable when the equipment is used for
a residential application. Commercial use is any application where the end purchaser uses the product for
other than ersonal, famil or household ur oses.

American

Standard

6200 Troup Highway
Tyler, TX 75711-9010

Inc.

0( °s

Since American -Standard has a policy of continuous
product and product data improvement, it reserves the right
to change design and specification without notice.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 8
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 4, 0, 0, 13
Create Date                     : Sat Jun 06 04:15:28 2009
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu